1 Introduction The legal validity of this report can only be claimed on presentation of the complete report.
|
|
- Augustus Preston
- 5 years ago
- Views:
Transcription
1
2 Contents Page No 1 Introduction Details of classified element Type of function Description Test reports and test results in support of classification Summary of test report Field of direct application Test results Classification and direct field of application Reference of classification Classifications Field of direct application Limitations... 7 Test for: Pacific Rim Wood Ltd Page 2 of 7
3 1 Introduction This resistance to fire classification report defines the classification assigned to the doorset of Chiltern International Fire Ltd (CIFL) fire resistance test report Chilt/RF09105 in accordance with the procedures given in BSEN : A1: Details of classified element 2.1 Type of function The glazed single leaf doorset is defined as a door assembly. Its function is to resist fire in respect of the fire performance characteristics given in clause 5 of BSEN Description The doorset is described in the test report in support of this classification listed in clause 3. 3 Test reports and test results in support of classification 3.1 Summary of test report This classification report is supported by the following test report: Test laboratory Test sponsor Test report ref Test method Test date Chiltern International Fire Ltd Notified body No: 1314 Pacific Rim Wood Ltd Chilt/RF09105 BSEN : th June 2009 The doorset leaf measured 2145mm high x 927mm wide x 44mm thick overall and was hung in a timber frame. The leaf included a 525mm high x 475mm wide (sight size) glazed aperture. The perimeter frame to leaf edge gaps included intumescent seals, and 1mm thick Interdens intumescent was fitted underneath the hinge blades, latch forend and keep and encasing the body of the latch. Test for: Pacific Rim Wood Ltd Page 3 of 7
4 Key to drawing 1 Top rail Mixed tropical hardwood (stated density 610 kg/m 3 ) 70mm wide x 36mm thick incorporating a 9mm wide x 9mm deep tongue into the core. 2 Leaf core Parasorianthes falcateria or Albisia falcate (stated density 280 kg/m 3 ) 36mm thick overall in 3 layers of lamels, central layer horizontally orientated, outer layers vertically orientated grooved to accept the top rail 3 Facings MDF (nominal density kg/m 3 ) 4mm thick 4 Lipping Sapele, 6mm thick (nominal density 640 kg/m 3 ) fitted to all leaf edges 5 Frame head and jambs European Redwood, 32mm thick x 70mm deep (nominal density 510 kg/m 3 ) 6 Stop ) planted (pinned) European Redwood, 12mm thick x 32mm wide (Nominal density 510kg/m 3 ) 7 Intumescent strip Pyroplex Rigid Box Seal 8600, 20mm wide x 4mm thick, fitted centrally in the frame reveal 8 Glazing intumescent Intumescent Seals Ltd Therm A Glaze 30, 4mm thick x 15mm high, fitted between the glass and bead on both faces 9 Glazing bead Sapele, 20mm high x 20mm deep including a 6mm x 6mm bolection return, and 17º chamfer 10 Beading fixings Steel pins, 40mm long fitted 50mm from corners at 150mm centres at 30 to the face of the glass 11 Glass Pilkington Pyroshield wired safety glass, 7mm thick Test for: Pacific Rim Wood Ltd Page 4 of 7
5 3.2 Field of direct application The results of the fire test are directly applicable to similar constructions where one or more of the changes listed in the appendix are made and the construction continues to comply with the appropriate design code for its stiffness and stability. Other changes are not permitted. 3.3 Test results Integrity (E) Cotton pad Continuous flaming Gap gauges Insulation (I) Discrete area 1 (timber) Average set Standard set (Max) Discrete area 2 Maximum (glass) Door frame (Max) Radiation (W) (Minutes to 15kW/m²) 35 (thirty five) minutes 40 (forty) minutes 35 (thirty five) minutes* 3 (three) minutes * No failure of the test criteria had occurred at termination of the test at 40 minutes ** Failure by virtue of integrity failure at 35 minutes 4 Classification and direct field of application 4.1 Reference of classification This classification has been carried out in accordance with clause 7 of BSEN : A1: Performance Criteria Integrity The assessment of integrity shall be made on the basis of the following three aspects: a) cracks or opening in excess of given dimensions b) ignition of a cotton pad c) sustained flaming on the unexposed face Classification for integrity shall be according to whether or not the element is also classified both for integrity and insulation, the value of integrity is that determined by whichever of the three aspects fails first. Where an element is classified without an Test for: Pacific Rim Wood Ltd Page 5 of 7
6 insulation classification, the value of integrity is that determined by the time to failure of only the cracks/openings or sustained flaming aspects, whichever fails first. Thermal insulation In the specific case of doors and shutters, one out of two options of the thermal insulation criterion shall be used: 1 Thermal insulation I 1 The mean temperature rise on the unexposed face of the door leaf shall be limited to 140ºC above the initial mean temperature, with the maximum temperature rise at any point on the door leaf limited to 180ºC. No temperature measurements shall be taken into account on the door leaf within 25mm from the border line of the visible part of the door leaf. The temperature rise at any point on the frame shall be limited to 180ºC, measured at 100mm from the visible edge (on the unexposed face) of the door leaf, if the frame is wider than 100mm, otherwise it shall be measured at the frame/supporting construction boundary. 1 Thermal insulation I 2 The mean temperature rise on the unexposed face of the door leaf shall be limited to 140ºC above the initial mean temperature, with the maximum temperature rise at any point on the door leaf limited to 180ºC. No temperature measurements shall be taken into account on the door leaf within 100mm from the border line of the visible part of the door leaf. The temperature rise at any point on the frame shall be limited to 360ºC, measured at 100mm from the visible edge (on the unexposed face) of the door leaf, if the frame is wider than 100mm, otherwise it shall be measured at the frame/supporting construction boundary. Radiation Classification for radiation shall be given by the time for which the maximum value of radiation, measured as specified in the test standard, does not exceed 15kW/m 2. Test for: Pacific Rim Wood Ltd Page 6 of 7
7
Title: WF Report No: BMT/CR15113D. Prepared for: The Access Panel Company Ltd Foxhill Industrial Park Scunthorpe North Lincolnshire DN15 0QJ
Title: Resistance to fire classification report for a 'Premium Range Fire Rated EI 2 90 Access Panel' (client product reference) in accordance with BSEN 13501-2: 2007 +A1: 2009 WF Report No: BMT/CR15113D
More informationPage No 1 Introduction... 3
Contents Page No 1 Introduction... 3 2 Details of classified element... 3 2.1 Type of function... 3 2.2 Description... 3 3 Test reports and test results in support of classification... 3 3.1 Summary of
More informationAppendix A Performance Data Appendix B Tested Glazing System Appendix C Revisions Appendix D Data Sheets... 18
Contents Page No 1 Introduction... 3 2 General Description of Construction... 3 3 Leaf Sizes... 3 4 Configurations... 3 5 Leaf Size Adjustment... 4 6 Overpanels... 4 7 Glazing... 4 8 Door Frames... 5 9
More informationCERTIFICATE OF APPROVAL No CF 218 VICAIMA LIMITED
CERTIFICATE OF APPROVAL No CF 218 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of VICAIMA LIMITED Marlowe
More informationCERTIFICATE OF APPROVAL No CF 385 HOLLWAYS DOORS & FRAMES LIMITED
CERTIFICATE OF APPROVAL No CF 385 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of HOLLWAYS DOORS & FRAMES
More informationCERTIFICATE OF APPROVAL No CF 5389 FINANCIERA MADERERA SA
CERTIFICATE OF APPROVAL No CF 5389 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of N-550 KM 57, 15890
More informationCERTIFICATE OF APPROVAL No CF 538 G E DOOR MANUFACTURING LTD
CERTIFICATE OF APPROVAL No CF 538 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of G E DOOR MANUFACTURING
More informationCERTIFICATE OF APPROVAL No CF 581 CGI INTERNATIONAL LIMITED
CERTIFICATE OF APPROVAL No CF 581 This is to certify that, in accordance with CERTIFIRE s Rules for Certification The undermentioned products of International House, Millfield Lane, Haydock, WA11 9GA Tel:
More informationCERTIFICATE OF APPROVAL No CF 5497 AL HUDA INTERIORS FACTORY LLC
CERTIFICATE OF APPROVAL No CF 5497 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Abu Dhabi Musaffah
More informationCERTIFICATE OF APPROVAL No CF 572 JELD-WEN UK LIMITED
CERTIFICATE OF APPROVAL No CF 572 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of JELD-WEN UK LIMITED
More informationCERTIFICATE OF APPROVAL No CF454 VICAIMA LIMITED
CERTIFICATE OF APPROVAL No CF454 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of VICAIMA LIMITED Drakes
More informationCERTIFICATE OF APPROVAL No CF 535 HALSPAN LIMITED
CERTIFICATE OF APPROVAL No CF 535 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Muirhouses, Bo'ness,
More informationTitle: Global Assessment Blankfort 60 & Blankfort 60+ Doorsets for 60 Minutes Fire Resistance. Report No: Chilt/A12152 Revision E. WF Contract:
Title: Global Assessment Blankfort 60 & Blankfort 60+ Doorsets for 60 Minutes Fire Resistance Report No: Chilt/A12152 Revision E WF Contract: 391846 Valid 12 th November 2017 Valid Until: 12 th November
More informationCERTIFICATE OF APPROVAL No CF 395 EUROPEAN WOOD PRODUCTS LIMITED
CERTIFICATE OF APPROVAL No CF 395 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of EUROPEAN WOOD PRODUCTS
More informationThis classification report consists of five pages and may only be used or reproduced in its entirety.
Title: Classification of Fire Resistance Performance In Accordance With EN 0-2: 200 Notified Body No: 08 Product Name: Pyrobelite 2 Report No: WF 9 Issue No: Prepared for: Glaverbel S. A. BU Industrial
More informationPilkington Fire-Resistant Glass for Timber Door Systems.
Pilkington Pyroshield Pilkington Pyrodur Pilkington Pyrodur Plus Pilkington Pyrostop FIRE PROTECTION CI/Sf Ro8 May 24 (K3) Pilkington Fire-Resistant Glass for Timber Door Systems. from Enfield Doors Trust.
More informationDescription. Construction
BM Trada Certification Q-Mark Fire Door Scheme Certified Product Certificate 006/010 applies Description Blankfort 60 is a high density particleboard faced timber cored door blank specifically designed
More informationCERTIFICATE OF APPROVAL No CF 302 PREMDOR CROSBY LIMITED
CERTIFICATE OF APPROVAL No CF 302 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of PREMDOR CROSBY LIMITED
More informationCERTIFICATE OF APPROVAL No CF 185 LORIENT POLYPRODUCTS LIMITED
CERTIFICATE OF APPROVAL No CF 185 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Fairfax Road, Heathfield
More informationP.O. Box ZN Bleiswijk Brandpuntlaan Zuid NZ Bleiswijk The Netherlands
P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com Classification of the fire resistance according to EN 13501-2:2007+ A1:2009
More informationCERTIFICATE OF APPROVAL No CF 535 HALSPAN LIMITED
CERTIFICATE OF APPROVAL No CF 535 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of HALSPAN LIMITED Muirhouses,
More informationCERTIFICATE OF APPROVAL No CF 163 LEADERFLUSH SHAPLAND
CERTIFICATE OF APPROVAL No CF 163 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Head Office, Milnhay
More informationCERTIFICATE OF APPROVAL No CF 820 ZMR LTD TRADING AS MILLENNIUM DOOR SYSTEMS
CERTIFICATE OF APPROVAL No CF 820 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of ZMR LTD TRADING AS MILLENNIUM
More informationCERTIFICATE OF APPROVAL No CF 5155 PROMAT UK LIMITED
CERTIFICATE OF APPROVAL No CF This is to certify that, in accordance with TS General Requirements for Certification of Fire Protection Products The undermentioned products of B The Innovation Centre, Heywood
More informationCERTIFICATE OF APPROVAL No CF 380 PREMDOR CROSBY LIMITED
CERTIFICATE OF APPROVAL No CF 380 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of PREMDOR CROSBY LIMITED
More informationCERTIFICATE OF APPROVAL No CF 302 PREMDOR CROSBY LIMITED
CERTIFICATE OF APPROVAL No CF 302 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of PREMDOR CROSBY LIMITED
More informationCERTIFICATE OF APPROVAL No CF 291 SCHOTT UK LIMITED
CERTIFICATE OF APPROVAL No CF 291 1 This is to certify that, in accordance with TS General Requirements for Certification of Fire Protection Products The undermentioned products of Drummond Road, Stafford.
More informationCLASSIFICATION OF FIRE RESISTANCE IN ACCORDANCE WITH BS EN : A1:2009
Page 1 of 11 CLASSIFICATION OF FIRE RESISTANCE IN ACCORDANCE WITH BS EN 1501-2:2007 + A1:2009 Sponsor: Notified body number: Product name: Classification report number: Kingspan Limited ISOCAB France SAS-France
More information21 st November Title:
assessment report Title: The Fire Resistance Performance Of Previously Fire Tested Insulated Timber/ Composite Doorsets Incorporating Simonswerk TE525 Hinges WF Assessment Report No: 178450 Prepared for:
More informationPFPF and FTSG Agreed Assessment Rules for: FD30 Timber Based Doorsets
PFPF and FTSG Agreed Assessment Rules for: FD30 Timber Based Doorsets PFPF and FTSG Agreed Assessment Rules for: FD30 Timber Based Doorsets Document dated: Introduction The aim of the document is to give
More informationP.O. Box ZN Bleiswijk Brandpuntlaan Zuid NZ Bleiswijk The Netherlands
P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com Determination of the fire resistance according to EN 1364-1:1999 and FprEN 1364-1:2014
More informationTitle: The Fire Resistance Performance of Modified Timber Based Panelled Doorsets. WF Assessment Report No: Issue 8.
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The Fire Resistance Performance
More informationP.O. Box ZN Bleiswijk Brandpuntlaan Zuid NZ Bleiswijk The Netherlands
P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com Determination of the fire resistance according to EN 1364-1:1999 and FprEN 1364-1:2014
More informationTitle: The Fire Resistance Performance of Modified Timber Based Panelled Doorsets. WF Assessment Report No: Issue 6.
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The Fire Resistance Performance
More informationCERTIFICATE OF APPROVAL CERTIFICATE No CF 633 PUERTAS NORMA S.A.
CERTIFICATE OF APPROVAL CERTIFICATE No CF 633 This is to certify that, in accordance with CERTIFIRE s Rules for Certification The undermentioned products of PUERTAS NORMA S.A. Calle San Miguel, S/N 42140
More informationCERTIFICATE OF APPROVAL No CF 479 LEADERFLUSH SHAPLAND
CERTIFICATE OF APPROVAL No CF 479 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of LEADERFLUSH SHAPLAND
More informationCERTIFICATE OF APPROVAL No CF 5003 BUILDING LIFE (FIRE DOORS) LTD
CERTIFICATE OF APPROVAL No CF 5003 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of BUILDING LIFE (FIRE
More informationINDIGATECH CERTIFICATION SCHEDULE
INDIGATECH CERTIFICATION SCHEDULE for FORSTER INSULATED GLAZED DOORS & SCREENS UTILISING FUEGO LITE 60 COMPONENTS WITH A RANGE OF EI30 & EI60 GLASS TYPES This Schedule should be read in conjunction with
More informationCERTIFICATE OF APPROVAL No CF 5431 INTEGRATED DOORSET SOLUTIONS LIMITED (IDSL)
1 CERTIFICATE OF APPROVAL No CF 5431 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of INTEGRATED DOORSET
More informationCERTIFICATE OF APPROVAL No CF 198 PREMDOR CROSBY LIMITED
CERTIFICATE OF APPROVAL No CF 198 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of PREMDOR CROSBY LIMITED
More informationP.O. Box ZN Bleiswijk Brandpuntlaan Zuid NZ Bleiswijk The Netherlands
P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com Determination of the fire resistance according to EN 1364-1:1999 and FprEN 1364-1:2014
More informationCERTIFICATE OF APPROVAL No CF 5033 LORIENT POLYPRODUCTS LIMITED
CERTIFICATE OF APPROVAL No CF 5033 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Endeavour House, Fairfax
More informationCLASSIFICATION OF FIRE RESISTANCE FIRES-CR AUPE
CLASSIFICATION OF FIRE RESISTANCE FIRES-CR-179-17-AUPE A single leaf aluminium framed doorset, type ALIPLAST FR90 EI60 This is an electronic version of a classification report which was made as a copy
More informationFire Door Installation
FA LCON PANEL PRODUCTS LTD 14.1 It is vital that performance doorset are installed by competent tradesmen and It is strongly recommended that the installer is a member of a recognised quality assurance
More informationCERTIFICATE OF APPROVAL No CF 5395 HAEFELE GMBH & CO.KG
CERTIFICATE OF APPROVAL No CF 5395 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Adolf-Haefele-Str.1,
More informationCERTIFICATE OF APPROVAL No CF 5372 CORINTHIAN INDUSTRIES (ASIA) SDN BHD
CERTIFICATE OF APPROVAL No CF 5372 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of LOT. 37217, Jalan
More informationCERTIFICATE OF APPROVAL No CF 5508 CONSORT ARCHITECTURAL HARDWARE LTD
1 CERTIFICATE OF APPROVAL No CF 5508 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of 29-31 Lower Loveday
More informationTitle: The Fire Resistance Performance of Modified Timber Based Doorsets. WF Assessment Report No: Issue 2. Prepared for:
assessment report Title: The Fire Resistance Performance of Modified Timber Based Doorsets WF Assessment Report No: 163997 Issue 2 Prepared for: Sauerlander Spanplatten GmbH Postfach 5553 59805 Arnsberg
More informationHalspan Authorised Document Valid only when submitted with permission schedule. Title:
Title: Global Fire Resistance Assessment of Halspan 60 Prima Doorsets 60 Minutes Fire Resistance Valid 8 th August 2017 Valid Until: 8 th August 2022 Report No: WF Reference: WF387440 Prepared for: Halspan
More informationCERTIFICATE OF APPROVAL No CF 5174 BUILDING LIFE (FIRE DOORS) LTD
CERTIFICATE OF APPROVAL No CF 5174 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of BUILDING LIFE (FIRE
More informationCERTIFICATE OF APPROVAL No CF 292 NORMA DOORS TECHNOLOGIES, S.A.
CERTIFICATE OF APPROVAL No CF 292 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of NORMA DOORS TECHNOLOGIES,
More informationCERTIFICATE OF APPROVAL No CF5439 INTEGRATED DOORSET SOLUTIONS (IDSL)
CERTIFICATE OF APPROVAL No CF5439 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Ovi House, Ratcher
More informationTitle: Global Fire Resistance Assessment Vistamatic VS2 Vision Panel Fire Resisting Timber Doorset Assemblies 30 Minute Fire Resistance
Title: Global Fire Resistance Assessment Vistamatic VS2 Vision Panel Fire Resisting Timber Doorset Assemblies 30 Minute Fire Resistance Report No: Chilt/A12242 Revision A WF Contract: WF404612 Valid From:
More informationTitle: WF Report No: WF Contract No: Valid From: Valid Until: Prepared for: Egger (UK) Ltd.
Title: Global Fire Resistance Assessment of EGGER FD30 & FD30 Decor 44mm Door Blanks 30 Minutes Fire Resistance WF Report No: WF Contract No: WF406084 Valid 30 th October 2018 Valid Until: 30 th October
More informationCERTIFICATE OF APPROVAL No CF 5158 WHITE ALUMINIUM ENTERPRISES L.L.C.
CERTIFICATE OF APPROVAL No CF 5158 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Sector M-21, Mussafah
More informationFIRE RESISTANCE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION FIRES-JR NURE. Fire resistance shutter with retractable stairs, type LMF
FIRE RESISTANCE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION FIRES-JR-004-11-NURE Fire resistance shutter with retractable stairs, type LMF This is an electronic version of a classification report which
More informationCERTIFICATE OF APPROVAL No CF 154 J B KIND LIMITED & IRMADE- INDÚSTRIAS DE REVESTIMENTO DE MADEIRAS, S.A.
CERTIFICATE OF APPROVAL No CF 154 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of J B KIND LIMITED & IRMADE-
More informationCERTIFICATE OF APPROVAL No CF 5320 ZOO HARDWARE LTD
CERTIFICATE OF APPROVAL No CF 5320 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Unit B, Dukes Drive,
More informationCERTIFICATE OF APPROVAL No CF 5514 GRETSCH UNITAS LTD
CERTIFICATE OF APPROVAL No CF 5514 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Unit 5 Spitfire Close,
More informationIFC FIELD OF APPLICATION REPORT
NOTE: COMMERCIAL IN CONFIDENCE This document is provided for the purpose of demonstrating compliance with the appropriate performance levels required by a designated third party. It should not be divulged
More informationHalspan Authorised Document Valid only when submitted with permission schedule
Contents 1 Introduction... 3 2 General Description of Construction... 3 3 Leaf Sizes... 3 4 Configurations... 3 5 Leaf Size Adjustment... 4 6 Overpanels... 4 7 Glazing... 6 8 Door Frames... 10 9 Lipping
More informationAvailable online at ScienceDirect. Procedia Engineering 172 (2017 )
Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 172 (2017 ) 417 425 Modern Building Materials, Structures and Techniques, MBMST 2016 Doors with specific fire resistance class
More informationCLASSIFICATION OF FIRE RESISTANCE PERFORMANCE IN ACCORDANCE WITH EN : 2007
CLASSIFICATION OF FIRE RESISTANCE PERFORMANCE IN ACCORDANCE WITH EN 13501-2: 2007 Sponsor: Reynaers Aluminium NV/SA Oude Liersebaan 266 B-2570 Duffel BELGIUM Prepared by: Efectis Nederland B.V. Centre
More informationInstallation & Maintenance Guidelines. Contents
Installation & Maintenance Guidelines Timber door sets are delivered to site ready for fitting. However in order for installation to be completed satisfactory, it is important that certain handling, storage,
More informationCERTIFICATE OF APPROVAL No CF 5539 HAEFELE GMBH & CO KG
CERTIFICATE OF APPROVAL No CF 5539 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Postfach 12 37, D-72192
More informationCERTIFICATE OF APPROVAL No CF 735 UNITY HARDWARE LTD
CERTIFICATE OF APPROVAL No CF 735 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of 14 th Floor North Block,
More informationP.O. Box ZN Bleiswijk Brandpuntlaan Zuid NZ Bleiswijk The Netherlands
P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com DETERMINATION OF THE FIRE RESISTANCE ACCORDING TO EN 1364-1:2015 OF A NON-LOAD
More informationGlobal Fire Resistance Assessment of: Warm Springs Composite Products 60, 90 & 120 Minute Fire Resisting Doorsets. Report No: Chilt/A12138 Revision A
Global Fire Resistance Assessment of: Warm Springs Composite Products 60, 90 & 120 Minute Fire Resisting Doorsets Report No: WF Contract No; WF 406134 Issue date: 12 October 2018 Valid until: 12 October
More informationFire resistance according to EN :2008 of a Sectional door set, type Metacon OHD EI(1)-60
P.O. Box 554-2665 ZN Bleiswijk Brandpuntlaan Zuid 16-2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com Fire resistance according to EN 1634-1:2008 of a Sectional door set, type Metacon
More informationCERTIFICATE OF APPROVAL No CF 137 CET GLASS PROCESSORS LIMITED
CERTIFICATE OF APPROVAL No CF 137 This is to certify that, in accordance with CERTIFIRE s Rules for Certification The undermentioned products of Lodge Way, Lodge Farm Industrial Estate, Harleston Road
More informationCERTIFICATE OF APPROVAL No CF 769 NICO MANUFACTURING LIMITED
CERTIFICATE OF APPROVAL No CF 769 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of 109 Oxford Road, Clacton
More informationCERTIFICATE OF APPROVAL No CF 242 GEZE UK LIMITED
CERTIFICATE OF APPROVAL No CF 242 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Blenheim Way, Fradley
More informationISO 3008 INTERNATIONAL STANDARD. Fire-resistance tests Door and shutter assemblies. Essais de résistance au feu Assemblages porte et volet
INTERNATIONAL STANDARD ISO 3008 Third edition 2007-09-15 Fire-resistance tests Door and shutter assemblies Essais de résistance au feu Assemblages porte et volet Reference number ISO 2007 Provläsningsexemplar
More informationCERTIFICATE OF APPROVAL No CF 370 SAMUEL HEATH & SONS PLC
CERTIFICATE OF APPROVAL No CF 370 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Leopold Street, Birmingham,
More informationTEST REPORT. Fire resistance load-bearing test of a 136mm thick Ozone Panels wall system tested in accordance with AS
TEST REPORT Fire resistance load-bearing test of a 136mm thick Ozone Panels wall system tested in accordance with AS 1530.4 2005. EWFA Report No: 2758400 Report Sponsor: Ozone Panels Level 31, 367 Collins
More informationPilkington Pyrostop and Pilkington Pyrodur
Pilkington Pyrostop Pilkington Pyrodur FIRE PROTECTION Pilkington Pyrostop and Pilkington Pyrodur Glazing and Handling Guidelines for Finished Sizes Content 1.0 General Product Advice Page 3 2.0 Framing
More informationBRE Global Test Report
BRE Global Test Report Ad-hoc fire resistance test on a galvanised steel Tunnel Ventilation Damper employing procedures and criteria from BS 476: Part 20 : 1987. Prepared for: Betec Cad Industries Date:
More informationCERTIFICATE OF APPROVAL No CF 735 UNITY HARDWARE LTD
CERTIFICATE OF APPROVAL No CF 735 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of 14th Floor North Block,
More informationCERTIFICATE OF APPROVAL No CF 5293 SYNERGY HARDWARE LIMITED
CERTIFICATE OF APPROVAL No CF 5293 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Unit 2 Heath Mill
More informationTEST REPORT. Bushfire resistance test of an external wall system to BAL A40 in accordance with AS EWFA Report No:
TEST REPORT Bushfire resistance test of an external wall system to BAL A40 in accordance with AS1530.8.1-2007 EWFA Report No: 38031900.1 Report Sponsor: Ullrich Aluminium PO BOX 246 Carole Park QLD 4300
More informationCERTIFICATE OF APPROVAL No CF 5525 TALLERES DE ESCORIAZA S.A.U
CERTIFICATE OF APPROVAL No CF 5525 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Barrio de Ventas
More informationCERTIFICATE OF APPROVAL No CF 714 D. P. GARG & CO. PVT. LTD.
CERTIFICATE OF APPROVAL No CF 714 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of D. P. GARG & CO. PVT.
More informationHalspan Authorised Document Valid Only When Submitted With Permission Schedule
Title: Global Fire Resistance Assessment of Halspan 30 Prima Doorsets 30 Minutes Fire Resistance Valid From: 17 th December 2015 Valid Until: 11 th December 2020 WF Report No: FEA/F97174 Revision I Prepared
More informationCERTIFICATE OF APPROVAL No CF 355
CERTIFICATE OF APPROVAL No CF 355 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of The Furlong, Droitwich,
More informationTitle: WF Report No: Prepared for: International Petroleum Products Ltd Bradwell Hall Bradwell-On-Sea Essex CMO 7HX. Date: 24 th August 2015
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The fire resistance performance
More informationTitle: WF Report No: Prepared for: Alstrong Enterprises India (PVT) Limited E-40/3, Okhla Industrial Area, New Delhi, India Date: 15 th June 2015
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: A fire resistance test performed
More informationTEST REPORT FIRES-FR AUNE. Single side-hung lift landing semiautomatic door, thermally insulated with polyurethane
TEST REPORT Single side-hung lift landing semiautomatic door, thermally insulated with polyurethane This is an electronic version of a test report which was made as a copy of test report officially issued
More informationFire Rated Glazing System Guide
Fire Rated Glazing System Guide FIRE RATED GLAZING SYSTEM GUIDE Introduction Pyropanel Developments are specialists in fire rated glazing solutions, and our systems are designed for easy installation into
More informationCERTIFICATE OF APPROVAL No CF 242 GEZE UK LIMITED
CERTIFICATE OF APPROVAL No CF 242 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Blenheim Way, Fradley
More informationTitle: The Fire Resistance Performance of PRT and PRC, Side and Centre-Opening Lift Landing Doorsets. WF Assessment Report No: Prepared for: Klefer SA
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The Fire Resistance Performance
More informationCERTIFICATE OF APPROVAL No CF 339 EUROSPEC
CERTIFICATE OF APPROVAL No CF 339 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Stancliffe Street,
More informationInstallation Instructions
20 Minute Positive Pressure Fire Door WH = PP Cat A 1. Doors must be installed in a Listed and Labeled Minimum 22 gauge K-D or welded steel frame, or fire-rated aluminum frame, or fire-rated wood frames.
More informationTitle: The Fire Resistance Performance of PRT and PRC, Side and Centre-Opening, Vandal Resistant, Lift Landing Doorsets. WF Assessment Report No:
assessment report Title: The Fire Resistance Performance of PRT and PRC, Side and Centre-Opening, Vandal Resistant, Lift Landing Doorsets WF Assessment Report No: 183968A Prepared for: Klefer SA Kilkis
More informationCERTIFICATE OF APPROVAL No CF 242 GEZE UK LIMITED
CERTIFICATE OF APPROVAL No CF 242 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of LIMITED Blenheim Way,
More informationBankstraat 2 B-9770 Kruishoutem BELGIUM. Fire resistant THEUMA door set in RVS frame with three 3-D Argenta Invisible ARGENT ALU hinges
CLASSIFICATION OF THE FIRE RESISTANCE ACCORDING TO EN 13501-2: 2007 + A1:2009 OF A THEUMA DOOR SET WITH THREE 3-D ARGENTA ALU INVISIBLE HINGES AND BUILT IN DOOR CLOSER IN A TWO PIECE STAINLESS STEEL FRAME
More informationLicensed Copy: Akin Koksal, Bechtel Ltd, 28 February 2005, Uncontrolled Copy, (c) BSI
BRITISH STANDARD BS 476-23: 1987 Incorporating Amendment No. 1 Fire tests on building materials and structures Part 23: Methods for determination of the contribution of components to the fire resistance
More informationTECHNICAL NOTE No.4 Simulated Windborne Debris Impact Testing of Building Envelope Components (Version 4 Published 10 January 2017)
Cyclone Testing Station College of Science and Engineering James Cook University Townsville QLD 4811 Australia Telephone +61 7 4781 4722 Facsimile +61 7 4781 6788 Email: cts.testing@jcu.edu.au www.jcu.edu.au/cts
More informationReliability of fire Barriers NKS project FIREBAN
Reliability of fire Barriers NKS project FIREBAN Prof. Patrick van Hees LTH - Fire Safety Engineering Content Objectives Partners Problem description Example of Results for calculation of fire barriers:
More informationINNA-DOR. Stylish, contemporary and durable internal doorsets FIRE DOORS ACOUSTIC REDUCTION. Available with 60, 120 and 240 mins fire protection
INNA-DOR Stylish, contemporary and durable internal doorsets FIRE DOORS Available with 60, 120 and 240 mins fire protection TESTED TO Parts 20 & 22 BS EN 1634 CERTIFIED BY Warrington Exova Certifire ACOUSTIC
More information