Lab Ventilation Safety & Energy Efficiency. Agenda & Objectives

Size: px
Start display at page:

Download "Lab Ventilation Safety & Energy Efficiency. Agenda & Objectives"

Transcription

1 Lab Ventilation Safety & Energy Efficiency Methods to Achieve Safe and Energy Efficient Laboratory Ventilation Systems Thomas C. Smith Agenda & Objectives Introduction Laboratory Safety & Risks Demand for Ventilation Airflow Specifications Commissioning & Routine Tests Lab Hoods Lab Environment Lab Ventilation Systems Lab Ventilation Optimization Copyright

2 Goal: High Performance Laboratories Chemistry Labs Radiological Labs Nanotechnology Labs Biology Labs (high containment) Animal Vivariums Cleanrooms Safe Compliant with Codes & Standards Productive (Flexible) Energy Efficient Sustainable Risk & Potential for Adverse Health Effects Inhalation Hazards Type of Airborne Materials Toxicity Generation Rate & Concentration Duration of Exposure Physical Hazards Dermal Exposure Fire & Explosion Dose = Concentration x Duration Copyright

3 Primary Objective: Lab Safety and Personnel Protection Laboratory Hoods & Ventilation Systems DUCTS FILTER STACK FAN Proper Performance = Protection Proper Performance = Compliance Operation 60% Utility Costs Cost = $ 3 to $ 9 per cfm-yr ROOF AIR SUPPLY Lab hoods are the primary means LAB OFFICE THINK SAFETY of protecting lab personnel Copyright

4 Evaluating Fume Hood Safety ANSI/ASHRAE 110 Method of Testing Performance of Laboratory Fume Hoods PWGSC - MD15128 Laboratory Fume Hoods Determine Operating Conditions Hood and Lab Inspection Face Velocity Measurements Cross Draft Velocity Tests VAV Response and Stability Tracer Gas Ejector Mannequin Tracer Gas Detector Computer & DAQ Determine Performance (Containment ) Flow Visualization Smoke Tests Tracer Gas Containment Tests Face Velocity Probe Cross Draft Probe Methods to Evaluate Containment Performance and Ensure Safe Hoods Laboratory Hood Safety & Performance ECT, Inc. has conducted more than 30,000 ASHRAE 110 Tracer Gas Containment Tests Test Results Demonstrate > 15% Failure Primary Factors Affecting Performance Hood design - 20% Lab Design System Operation 55% Work practices - 25% Copyright

5 Know the Operating Limits Utility Costs for Laboratories & Fume Hoods One of the highest energy users by building type Average Annual Energy Cost for a Lab Building = $700,000 (100,000 ft 2 ) Laboratory Buildings have 10 to 250 fume hoods Average Annual Energy Cost for a Traditional Fume Hood = $5,000 Equivalent to Three 2500 sq. ft. Houses Estimated lifetime cost of operation $150,000 (30 yrs) Building Type Average Utility Cost Commercial/Office $ 1 / ft 2 Lab Energy Use Lights 10% Hospital $ 3 / ft 2 Laboratory $ 7 / ft 2 Specialty Labs & Cleanrooms $ 15 / ft 2 HVAC 60% 30% Plug/Misc. Copyright

6 ANSI/AIHA Z American National Standard for Laboratory Ventilation Newly Revised & Published September 2012 Minimum Requirements and Best Practices Protect People Ensure Dependable Operation Operate Energy Efficient Labs Recommendations & Specifications for New and Renovated Laboratories Hood Design & Operation Laboratory Design Ventilation System Design Commissioning and Routine Testing Work Practices and Training Preventative Maintenance Airflow Specifications for Laboratories Minimum Flow and Range of Modulation Required to Meet the Functional Requirements of the Lab Safety Hood Exhaust Flow Laboratory Pressurization Dilution (ACH) Comfort & Productivity Temperature Demand for Ventilation Humidity Occupancy & Utilization Copyright

7 Bench-Top Types of Laboratory Fume Hoods Traditional Bypass Low Velocity / High Performance VAV Restricted Bypass Distillation Floor Mounted (Walk-in) Fume Hood Operation and Specifications Sash Opening Configuration 100% Full Open Design Opening User Opening Average Face Velocity 100 fpm (0.51 m/s) Traditional 60 fpm (0.3 m/s) High Performance Exhaust Flow CAV VAV o Minimum Flow ( ACH) Copyright

8 Bench-Top Fume Hood Vertical Sash Opening Horizontal Sash Opening Laboratory Hood Test Methods ASHRAE or ASHRAE EPA NIH PWGSC Copyright

9 Laboratory Hood and System Tests Pre-Purchase Factory Acceptance Tests Mock Up Tests As Manufactured Tests Commissioning Tests As Installed Tests ASHRAE 110 Hood Tests Lab Environment Tests System Operating Mode Tests Routine Performance Tests As Used Tests Maintenance Management Continuous Commissioning Fume Hood Tests ANSI/ASHRAE 110 Method of Testing Performance of Laboratory Fume Hoods Operating Tests Hood and Lab Inspection Face Velocity Measurements Cross Draft Velocity Tests VAV Response and Stability Performance (Containment ) Tests Flow Visualization Smoke Tests Tracer Gas Containment Tests Copyright

10 Hood Survey and Inspection Monitor Baffle Panels Access Panel Sash Airfoil Cabinet Cross Draft Measurement Non-directional Anemometer Determine Imaginary Hood Zone Identify Sources of Cross Draft Measure Velocity of Cross Draft Determine Direction with Smoke Left Top View Center Right Vertical Horizontal Design opening Perpendicular Mid-point Front View Side View Copyright

11 A1 A2 A3 B1 B2 B3 C1 C2 C3 D1 D2 D3 E1 E2 E3 Velocity - fpm Safe. Dependable and Energy Efficient Laboratories April 2014 Face Velocity Test Divide Opening Into Grids < 1 ft 2 Mount Anemometer Probe at Grid Center Record readings (~1 per second) Calculate Overall Average & Variation Face Velocity Traverse Qe 6" Vertical Sash H Vf 6" 6" W ows Face Velocity Grids Columns A B C D E 1 2 Probe Stand Number of rows and columns depends on opening Height (H) and Width (W) H - Height from work surface to sash W - Interior opening width in plane of sash Vfavg = sum (Vfmean)/No. of Grids Face Velocity Traverse Spacial vs. Temporal Variation fpm 35 fpm Traverse Grid - 30 Readings per Location Analog Velocity - fpm Digital 131 fpm Average = 102 fpm Max = 145 fpm Min = 35 fpm Copyright

12 Flow Monitors and VAV Controls Hood Monitors (Flow Measuring Device) Flow Velocity Pressure Flow Control Types Through the Wall Velocity Sash Position Occupancy Manual Monitors are required on all fume hoods TTW Velocity Sensor and Hood Monitor VAV Modes Two State Full VAV VAV Hybrid VAV Fume Hood Flow Control Sash Open Qex = Vf x Af Sash Closed Qex = Minimum? Flow Reduction = Energy Reduction Flow Terminal Questions? 1. Average Face Sash Open? 2. Minimum Sash Closed? 60 fpm fpm 3. Containment 4. Sash Management Copyright

13 Minimum Flow for VAV Fume Hoods Containment Dilution Removal 1990s - EPA 50 cfm / ft of Wh Duct Conc. (Cd) NFPA cfm / sq. ft. ws Defers to ANSI Z ANSI Z9.5 (must be appropriate) - Internal ACH (150 ACH to 375 ACH) ACH ~ 10 cfm / sq. ft. ws Internal Conc. (Ci) ACH ~ 25 cfm / sq. ft. ws Caution: Minimum Flow is Hood & System Dependent VAV Flow Response and Stability Good Control & Containment DAQ Poor Control & Containment Copyright

14 Average Face Velocity (fpm) Safe. Dependable and Energy Efficient Laboratories April 2014 Controls & Building Automation System (BAS) Fume Hood Face Velocity Tests 140 Syngenta Fume Hood Average Face Velocity Low 39% High 34% Average Face Velocity (fpm) Min fpm = Avg - 10% Max fpm = Avg + 10% 0 Fume Hood ID Copyright

15 Typical Accuracy of VAV Airflow Controls Percent Error - % 100% 90% 80% 70% 60% 50% 40% 30% 20% 10% 0% -10% -20% -30% -40% -50% -60% -70% -80% -90% -100% LET - VAV Terminals - Measured vs BAS Reported - % Error VAV Terminal ID Quality Data - Accuracy and Precision Not Accurate and Not Precise VAV Controls Can degrade Precise but not Accurate 30-50% within 5 years EPA RTP Flow Sensors (Pre LVOP) = 20% to 65% Error Flow Sensors (Post LVOP) = 5% Error Accurate and Precise Copyright

16 VAV Retrofit & Component Upgrades Lab Exhaust to Exhaust Plenum VAV Controller Pressure Transducer Damper Duct Inlet Damper Actuator Flow Grid Flow Connections Grid Lab Flow Damper Actuator Damper Shaft Pressure Transducer Airflow Visualization - Smoke Test Generate Visible Smoke Smoke Tubes, Sticks, Candles Dry Ice Nontoxic Fog Generator Evaluate Air Flow Patterns Qualitatively Evaluate Performance Copyright

17 Airflow Visualization Ratings Fail Visible Escape Poor Reverse Flow at Sash Opening Fair Reverse flow inside Hood within 6 inches. Good No Reverse Flow PWGSC Airflow Visualization Test Standardized Smoke Challenge Controlled Release at Several Locations Mimics Tracer Gas Test Copyright

18 Tracer Gas Containment Test Sulfur Hexafluoride or NO 2 released at 4 LPM with ASHRAE ejector Measure Concentrations in breathing zone of mannequin Test at Center, Left and Right Positions Control Level 4 AM <0.05 ppm 4 AI <0.05 ppm 4 AU < 0.1 ppm Demand for Laboratory Ventilation Operating Mode Min and Max Flow Temperature Control Room Pressure Dilution (ACH) Air Change Effectiveness Qs - Supply Qe - Exhaust Room Pressure Qt = Qe Qs Qt = Constant + - Copyright

19 Typical ACH Guidelines Agency ASHRAE Lab Guides UBC 1997 IBC 2003 IMC 2003 U.S. EPA AIA NFPA NRC Prudent Practices OSHA 29 CFR Part ACGIH 24 th Edition, 2001 Ventilation Rate 4-12 ACH 1 cfm/ft2 1 cfm /ft2 1 cfm/ft2 4 ACH Unoccupied Lab - 8 ACH Occupied Lab 4-12 ACH 4 ACH Unoccupied Lab - 8 ACH Occupied Lab 4-12 ACH Recommends 4-12 ACH Ventilation depends on the generation rate and toxicity of the contaminant and not the size of the room. ANSI/AIHA Z9.5 Prescriptive ACH is not appropriate. Rate shall be established by the owner! Emissions in Labs Requiring Dilution Escape from Lab Hoods Improper Bench Top Procedures Unventilated Equipment Fugitive Emissions Chemical Bottles & Containers Gas Cylinders Accidental Spills Typical Generation Rates <0.1 lpm to 10 lpm Catastrophic Failure of a Gas Cylinder 1400 lpm Copyright

20 Lab Airflow Specifications Control Bands Parameters and Weighting Adapted for Unique Research Labs Specify ACH & Risks of Recirculating Lab Air Evaluate Lab Construction, Pressurization, Need for Monitoring Total Score Control Band ACH Recirculation of Lab Air Lab Isolation & Pressurization < 4 Allowable Neutral Filtered or DCV < w.g Investigate < w.g No >31 5 > 10 No < w.g. Critical w/ Monitor = > w.g. Critical w/anteroom (airlocks) & Monitor Airflow Rates for Labs (ACH?) Survey Laboratories & Evaluate Hazards Sources Exposure Control Devices Supply Diffusers Airflow Effectiveness Determine Generation Emission Scenarios Apply Control Band Matrix Determine Minimum ACH Determine Room Volume Specify Minimum Airflow Copyright

21 System Operating Specifications Max and Min Flows AHUs and Ex. Fans Manifolds Redundancy Emergency Power System Static Pressure Duct Transport Velocity Exhaust Stack Discharge Control Capabilities VAV Diversity VAV Sensitivity Energy Savings Require Reducing Total Building Flow System Flow Controls Outside Air Bypass Inlet Variable Speed Drives Copyright

22 Flow Modulation & VAV Sensitivity Low Flow (Sash Closed) = 1,400 cfm High Flow (Sashes Open) = 7,000 cfm Range of Modulation = 5,600 cfm VAV Sensitivity =? Gex Low = 0 cfm Sash High = 500 cfm Sash Open = 1000 cfm Sash Closed = 200 cfm System Operating Mode Tests (SOMT) SOMT Data Collection Operating Modes o o Sashes Closed - Unoccupied Sashes Open Occupied Measure Total Flow and SP BAS Trend AHUs & Ex. Fans Record Terminal Boxes o o Flow Set Point BAS Flow o Damper % Copyright

23 System Operating Mode Tests (SOMT) Operating Mode Sashes Closed - Unoccupied 100% Sashes Open - Occupied Flow BAS Flow BAS Damper Terminal Serves Sash Ht. Damper% Sash Ht. Setpoint Flow Setpoint Flow % EVAV1 LFH EVAV2 Gex1 n/a n/a EVAV3 LFH EVAV4 LFH BAS Trend 797 of Combined 765 Flow for 28 AHUs 11&12,13&14,15&16,19&20 EVAV5 Gex3 n/a n/a 100 (Week September September 9, 2012) EVAV6 LFH EVAV7 Gex2 n/a n/a EVAV8 LFH EVAV9 LFH EVAV10 LFH Aggregate Terminal Flow n/a n/a Total BAS Flow Measured Flow VFD% OABD% BAS System SP Meas. System SP Flow - cfm /1/12 12:00:00 AM PDT 9/1/12 6:00:00 AM PDT 9/1/12 12:00:00 PM PDT 9/1/12 5:30:00 PM PDT 9/1/12 11:00:00 PM PDT 9/2/12 5:00:00 AM PDT 9/2/12 11:00:00 AM PDT 9/2/12 5:00:00 PM PDT 9/2/12 11:00:00 PM PDT 9/3/12 5:00:00 AM PDT 9/3/12 11:00:00 AM PDT 9/3/12 5:00:00 PM PDT 9/3/12 11:00:00 PM PDT 9/4/12 5:30:00 AM PDT 9/4/12 11:30:00 AM PDT 9/4/12 5:00:00 PM PDT 9/4/12 11:00:00 PM PDT 9/5/12 5:00:00 AM PDT 9/5/12 11:00:00 AM PDT 9/5/12 4:30:00 PM PDT 9/5/12 10:30:00 PM PDT 9/6/12 4:30:00 AM PDT 9/6/12 10:30:00 AM PDT 9/6/12 4:00:00 PM PDT 9/6/12 10:00:00 PM PDT 9/7/12 4:00:00 AM PDT 9/7/12 10:00:00 AM PDT 9/7/12 3:30:00 PM PDT 9/7/12 9:30:00 PM PDT 9/8/12 3:30:00 AM PDT 9/8/12 9:30:00 AM PDT 9/8/12 3:30:00 PM PDT 9/8/12 9:30:00 PM PDT 9/9/12 3:30:00 AM PDT 9/9/12 9:30:00 AM PDT 9/9/12 3:00:00 PM PDT 9/9/12 9:00:00 PM PDT Average Minimum Flow - cfm Maximum Flow - cfm Aggregate AHU Flow - cfm Building Pressurization Copyright

24 Optimize Stack Discharge and Dispersion Re-entrainment Stack Height > 10 ft. Stack Velocity? (3000 fpm) Optimum Design Lab Safety and Energy Programs Lab Safety and Energy Assessment Quick, Low Cost, Low Risk Audit Evaluate Safety & Code Compliance Determine Performance Improvement Measures (PIMs) Determine Energy Conservation Measures (ECMs) Determine Benefits, Potential Energy Reduction, Cost and Payback Lab Ventilation Optimization Project (LVOP TM ) Engineer & Implement PIMs and ECMs TAB Commission Systems Lab Ventilation Management Plan (LVMP) Maintain Safe & Efficient Operation Ensure Compliance Conduct Routine Test and Maintenance Protect Return on Energy Investment Plan Assess Optimize Sustain Copyright

25 Assess and Profile Laboratory Buildings Qualify Facility and Buildings Select & Prioritize Best Projects First Key Metrics & Weighting Factors Size & Space Allocation Energy Use & Operating Costs State of the Systems Energy Reduction Potential Lab Safety and Energy Profile Building Classification Assessment of Energy Reduction Estimated Project Costs & Payback Attribute Lab Building Profile Category State of the Systems Energy Reduction Potential Project LOE & Complexity Return on Investment (Payback) Class A Class B Class C Class D Class E Lab Safety and Energy Optimization Project Phase 1 Project Engineering Determine Operating Specifications Control Band Hoods & Labs Design Upgrades & System Modifications Develop TAB & Cx Plans Phase 2 Upgrade/Renovation Project Implement Selected PIMs & ECMs Verify Performance and Energy Savings Copyright

26 Lab Safety & Energy Optimization Projects RELSA = Rapid Energy & Lab Safety Assessment SOW = Scope of Work PIM = Performance Improvement Measure ECM = Energy Conservation Measures TA = Technical Assistance Vendor TAB = Test, Adjust and Balance Cx = Commissioning Tests LVMP = Lab Ventilation Management Program Assessment Profile and Optimization Tasks Attribute Building Profile Profile State of the Systems Building Operating Cost Energy Reduction Potential Energy Project Complexity (LOE) A B C D E (New) ROI - Project Payback < 3 < 5 < 10 > 10 N/A Planning RELSA & TA Study X X X X Safety & Energy Optimization Project Sustainability Program Minor Engineering X X Major Engineering X X Component Repair Maintenance X X X X Retrofits & Component Upgrades X X X Component Replacement X X New Equipment Installation Project Phase & Task TAB X X X X CX X X X X LVMP X X X X X Training X X X X X Routine T&M Services X X X X X X Copyright

27 Demand Based Optimization - LVOP Success Building Baseline Airflow cfm Annual Operating Cost $ Final Airflow cfm Flow Reduction cfm % Flow Reduction Annual Cost Savings $4.50/cfm-yr GHG Reduction tons/yr Gov 1 (5 bldgs) 773,000 3,478, , ,000 33% 1,147,500 15,300 Gov 2 ( 1 bldg) 66, ,000 37,000 29,000 44% 130, Gov 3 (1 bldg) 71, ,500 56,000 15,000 21% 67, Gov 4 (2 bldgs) 144, , ,000 43,000 30% 193, Gov 5 (1 bldg) 51, ,500 35,000 16,000 31% 72, Gov 6 (1 bldg) 47, ,500 33,000 14,000 30% 63, Biotek 1 (1 bldg) 11,000 49,500 7,000 4,000 36% 18, Pharma 1 ( 4 bldgs) 628,000 2,826, , ,000 26% 711,000 9,720 Pharma 2 (1 bldg) 168, , ,000 48,000 28% 216, University 1 (1 bldg) 394,000 1,773, ,000 62,000 16% 279, University 2 (1 bldg) 180, , ,000 45,000 25% 202, Summary 2,533,000 $11,398,500 1,844, ,808 29% $3,100,500 41,700 Safe Sustainable Energy Use Ensure ROI Campus Wide Aggregate Energy Reduction Billion BTUs Energy Baseline Energy Target Reduction 14.7% $900,975 4th Q rd Q nd Q st Q nd Q st Q th Q rd Q 2005 Copyright

28 Laboratory Ventilation Management Program (LVMP) System Management and Sustainability Plan Organization and Responsibilities Lines of Communication (Reporting) SOP s for Surveys, Testing and Maintenance Metrics, Monitoring & BAS Utilization Ventilation Standards Management of Change Personnel Training Required By ANSI Z Responsible Person Ventilation Maintenance and Test Schedule Copyright

29 Training of Personnel Lab Personnel Facility Maintenance Building Operators Lab Safety and Energy Efficiency Plan Assess Optimize Safe Energy Efficient Dependable Sustainable Sustain Copyright

30 END QUESTIONS? Thomas C. Smith 231-C East Johnson St. Cary, NC Copyright

Demand for Laboratory Ventilation

Demand for Laboratory Ventilation Demand for Laboratory Ventilation Operating Mode Min and Max Flow Temperature Control Dilution ACH Air Change Effectiveness Room Pressure Transfer Volume Qe - Exhaust Qt = Qe Qs Qt = Constant Room Pressure

More information

New Methods and Standards for Improving Safety & Reducing Energy Use in Laboratory Buildings. Introduction & Agenda

New Methods and Standards for Improving Safety & Reducing Energy Use in Laboratory Buildings. Introduction & Agenda New Methods and Standards for Improving Safety & Reducing Energy Use in Laboratory Buildings Thomas C. Smith Robert Lukens LabHoodPro tcsmith@labhoodpro.com Laboratory Hood Products rlukens@labhoodpro.com

More information

Recommended Methods to Evaluate Performance of Variable Air Volume Fume Hood Systems

Recommended Methods to Evaluate Performance of Variable Air Volume Fume Hood Systems AIHEC VENT 2006 Recommended Methods to Evaluate Performance of Variable Air Volume Fume Hood Systems Thomas C. Smith Exposure Control Technologies, Inc. Safety is the Primary Objective Lab Occupancy 26%

More information

UNIVERSITY OF NORTH DAKOTA

UNIVERSITY OF NORTH DAKOTA UNIVERSITY OF NORTH DAKOTA Safety & Environmental Health Office Standard Practice RSP 7 Testing and Maintenance of Radioisotope Fume Hoods Effective Date January 31, 1999 I. PURPOSE The purpose of this

More information

How to Reduce Energy Use in Your Labs by Up to 50%

How to Reduce Energy Use in Your Labs by Up to 50% How to Reduce Energy Use in Your Labs by Up to 50% Illinois Chapter of ASHRAE April 11, 2017 Dan Doyle, Chairman Grumman/Butkus Associates 1 Course Description Labs have high exhaust requirements and large

More information

Advantages and Disadvantages of using the ASHRAE Tracer Gas Test Method for the Chemical Laboratory Hood Certification

Advantages and Disadvantages of using the ASHRAE Tracer Gas Test Method for the Chemical Laboratory Hood Certification CASE Case Western Reserve University Advantages and Disadvantages of using the ASHRAE 110-1995 Tracer Gas Test Method for the Chemical Laboratory Hood Certification Mahdi Fahim, MS Chicago, IL 2006 ASHRAE

More information

15020 LABORATORIES. C. Section Building Automation and Control System Guidelines

15020 LABORATORIES. C. Section Building Automation and Control System Guidelines 15020 LABORATORIES PART 1: GENERAL 1.01 RELATED SECTIONS A. Section 01004 Energy Guidelines B. Section 01008 Energy Modeling Guidelines C. Section 15955 Building Automation and Control System Guidelines

More information

PART 30: LABORATORIES

PART 30: LABORATORIES PART 30: LABORATORIES GENERAL REQUIREMENTS Definitions 30.7.1 In sections 30.8 to 30.11: laboratory fume hood operational face opening sash Laboratory fume hoods means an enclosed and mechanically ventilated

More information

LABORATORIES 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS. A. Section Accessibility for People with Disabilities

LABORATORIES 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS. A. Section Accessibility for People with Disabilities 230540 LABORATORIES PART 1 GENERAL 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS A. Section 013010 Accessibility for People with Disabilities B. Section 018120 Energy Guidelines C. Section 018130

More information

MODULE 5 HVAC FUNDAMENTALS OF MODERN LABORATORY DESIGN

MODULE 5 HVAC FUNDAMENTALS OF MODERN LABORATORY DESIGN MODULE 5 HVAC FUNDAMENTALS OF MODERN LABORATORY DESIGN Module 5 PG1 MODULE 5 GOAL Provide a fundamental understanding of Laboratory Heating, Ventilating and Air Conditioning Concepts and Systems Module

More information

Second Stakeholder Meeting for Variable Exhaust Flow Control

Second Stakeholder Meeting for Variable Exhaust Flow Control Second Stakeholder Meeting for Variable Exhaust Flow Control March 7, 2017 Jared Landsman Jlandsman@integralgroup.com Agenda 1. Background 2. Proposed Code Changes 3. Technical and Market Barriers 4. Compliance

More information

Designing for Actual Not Theoretical HVAC Requirements in Laboratory Facilities

Designing for Actual Not Theoretical HVAC Requirements in Laboratory Facilities October 4, 2007 Charleston, SC Designing for Actual Not Theoretical HVAC Requirements in Laboratory Facilities J. Patrick Carpenter, PE Principal V a n d e r w e i l E n g i n e e r s What Are Laboratory

More information

Demand-Based Control of Laboratory Air Change Rates

Demand-Based Control of Laboratory Air Change Rates Demand-Based Control of Laboratory Air Change Rates Gordon P. Sharp Chairman Aircuity,, Inc. Aircuity Project: Bank of America Tower, NYC Research Laboratory Energy: Why Do We Care? Lab Energy Usage: 5

More information

Forum M: Top 10 Cost Reduction Strategies for Science Facility Operations and Maintenance

Forum M: Top 10 Cost Reduction Strategies for Science Facility Operations and Maintenance Forum M: Top 10 Cost Reduction Strategies for Science Facility Operations and Maintenance Forum M: Top 10 Cost Reduction Strategies for Science Facility Operations and Maintenance Presentation Outline

More information

Project Name: SEP 2010-Exhaust Stack Discharge Velocity Reduction I3363 I3345 Project No.: / Contract No.

Project Name: SEP 2010-Exhaust Stack Discharge Velocity Reduction I3363 I3345 Project No.: / Contract No. SCOPE OF WORK: Introduction The University of California, Irvine (UCI) is requesting proposals to provide engineering and wind tunnel testing to support energy saving retrofit projects for certain laboratory

More information

APPENDIX W (Combined Appendix N and W) 2006 Edition, Published January 1, 2006; Document Revision Date: October 16, 2017

APPENDIX W (Combined Appendix N and W) 2006 Edition, Published January 1, 2006; Document Revision Date: October 16, 2017 (Combined Appendix N and W) 2006 Edition, Published January 1, 2006; Document Revision Date: October 16, 2017 LABORATORY HOODS, SAFETY CABINETS AND VENTILATION SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. This

More information

Evaluating Alternative Fume Hood System Technologies Using Advanced Building Simulation

Evaluating Alternative Fume Hood System Technologies Using Advanced Building Simulation Evaluating Alternative Fume Hood System Technologies Using Advanced Building Simulation William J. Kosik, P.E., C.E.M. 1 Karl Aveard, AIA Associate 2 Heather R. Beaudoin, P.E., C.E.M. 3 Erik L. Olsen 3

More information

Indoor Air Quality Solutions

Indoor Air Quality Solutions Indoor Air Quality Solutions Ultimate Solutions for Indoor Air Quality Investigation Demand for quality indoor air continues to increase as we are spending more time indoors than ever before. Indoor air

More information

Overview of Dynamic Control of Lab ACH s

Overview of Dynamic Control of Lab ACH s A Comprehensive Review of the Indoor Environmental Quality and Energy Impacts of Dynamically Varying Air Change Rates at Multiple Laboratory Facilities Overview of Dynamic Control of Lab ACH s Background

More information

Shannon Horn P.E., AHJ, LEED A.P. Timothy Lockhart CIH, CHMM

Shannon Horn P.E., AHJ, LEED A.P. Timothy Lockhart CIH, CHMM Shannon Horn P.E., AHJ, LEED A.P. Timothy Lockhart CIH, CHMM Participants will be able to: 1. Provide a convincing argument to Authorities Having Jurisdiction (AHJ) and Environmental Health and Safety

More information

Local Exhaust Ventilation

Local Exhaust Ventilation Local Exhaust Ventilation University of Tennessee Safety Guide IH-001 Document Contact: EHS Date effective: August 1, 2014 Revision Date: July 1, 2016 Purpose The purpose of this document is to provide

More information

Georgetown University New Science Center

Georgetown University New Science Center Georgetown University New Science Center Final Thesis Proposal PENN STATE UNIVERSITY Prepared For: Dr. William P. Bahnfleth Department of Architectural Engineering Prepared By: Kevin M Edstrom Mechanical

More information

Underf loor For Schools

Underf loor For Schools The following article was published in ASHRAE Journal, May 2008. Copyright 2008 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes

More information

1.0 Purpose, Applicability, and Scope

1.0 Purpose, Applicability, and Scope Policy Subject: Local Exhaust Ventilation Policy Effective: 8/1/2014 Affected Area/Department: All Departments who use Local Exhaust Ventilation Systems Reviewed/Revised: 8/1/2014 1.0 Purpose, Applicability,

More information

Saving Energy in Lab Exhaust Systems

Saving Energy in Lab Exhaust Systems This article was published in ASHRAE Journal, June 211. Copyright 211 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Reprinted here by permission from ASHRAE at www.cppwind.com.

More information

Cleveland State University Office of Environmental Health & Safety. Standard Operating Procedures For Chemical Fume Hoods

Cleveland State University Office of Environmental Health & Safety. Standard Operating Procedures For Chemical Fume Hoods Cleveland State University Office of Environmental Health & Safety Standard Operating Procedures For Chemical Fume Hoods Cleveland State University, in its efforts to provide for the health and safety

More information

Variable Air Volume (VAV) For Laboratories

Variable Air Volume (VAV) For Laboratories Variable Air Volume (VAV) For Laboratories by Steven G. Liescheidt, PE, CCS, CCPR Overview: Variable Air Volume (VAV) systems have been used for many years in commercial HVAC systems for a variety of reasons.

More information

Laboratory Hoods Use and Evaluation

Laboratory Hoods Use and Evaluation Laboratory Hoods Use and Evaluation Caoimhín P. Connell Forensic Industrial Hygienist Forensic Applications, Inc. 185 Bounty Hunter Lane Bailey, CO www. www.forensic-applications.com Topics of Discussion

More information

How LEED & The Retro-Commissioning Credits Produce Energy Savings. James Vallort Vice President Environmental Systems Design, Inc.

How LEED & The Retro-Commissioning Credits Produce Energy Savings. James Vallort Vice President Environmental Systems Design, Inc. How LEED & The Retro-Commissioning Credits Produce Energy Savings James Vallort Vice President Environmental Systems Design, Inc. Retro-Commissioning Today s session will focus on the following items:

More information

Outdoor Airflow Control Fixed point and DCV. Presented by: David S. Dougan, President EBTRON

Outdoor Airflow Control Fixed point and DCV. Presented by: David S. Dougan, President EBTRON Outdoor Airflow Control Fixed point and DCV Presented by: David S. Dougan, President EBTRON OUTSIDE AIR Pressure Changes Damper Issues Intake Flow Rates (Fixed Min or DCV) OUTSIDE AIR Intake Flow Rate

More information

Karl Helmink, P.E., CEM Retrocommissioning Manager University of Illinois. Retrocommissioning Saving the Planet One Building at a Time

Karl Helmink, P.E., CEM Retrocommissioning Manager University of Illinois. Retrocommissioning Saving the Planet One Building at a Time Karl Helmink, P.E., CEM Retrocommissioning Manager University of Illinois Retrocommissioning Saving the Planet One Building at a Time AIA Quality Assurance Portland Energy Conservation, Inc is a registered

More information

You Can t Afford Discomfort. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

You Can t Afford Discomfort. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas You Can t Afford Discomfort Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Where We Are Today: So You Want To Save Money? Things to consider: 1. First Cost 2. Energy cost 3. Occupant Salary costs

More information

43% reduction in water use below code maximum 100% 100% 14% reduction in lighting power density. 56% of offices have thermal comfort controls 100%

43% reduction in water use below code maximum 100% 100% 14% reduction in lighting power density. 56% of offices have thermal comfort controls 100% Insert school or unit logo Nocera Lab LEED CI v3.0 12 Oxford Street, Cambridge, MA GOLD Project Profile Laboratories are typically regarded as an energy intensive building typology. Many of these buildings

More information

SMART LABS. Reduce Energy Consumption, Improve Lab Safety, and Lower Deferred Maintenance

SMART LABS. Reduce Energy Consumption, Improve Lab Safety, and Lower Deferred Maintenance SMART LABS Reduce Energy Consumption, Improve Lab Safety, and Lower Deferred Maintenance From 1999 to 2016 The Georgia Institute of Technology constructed six laboratory buildings in its Bio- Quad region

More information

UMA LSL Retrocommissioning Project

UMA LSL Retrocommissioning Project UMA LSL Retrocommissioning Project University of Massachusetts Amherst Design and Construction Management Physical Plant Research and Engagement Environmental Health and Safety 3/27/2018 Name Company /

More information

Local Exhaust Ventilation Improvement Efforts at a Global Specialty Chemical Manufacturer

Local Exhaust Ventilation Improvement Efforts at a Global Specialty Chemical Manufacturer Local Exhaust Ventilation Improvement Efforts at a Global Specialty Chemical Manufacturer Richard Hirsh, MPH CIH Rohm and Haas Company rhirsh@rohmhaas.com (510) 784-5728 Global Expectations and Requirements

More information

DIVISION 11 - EQUIPMENT FOOD SERVICE EQUIPMENT LABORATORY FUME HOODS. A. Design Considerations

DIVISION 11 - EQUIPMENT FOOD SERVICE EQUIPMENT LABORATORY FUME HOODS. A. Design Considerations DIVISION 11 - EQUIPMENT 11400 FOOD SERVICE EQUIPMENT A. Design Considerations 1. The A/E shall use the services of a food service equipment specialist in preparation of kitchen areas and other food preparation

More information

V entilation control using carbon dioxide

V entilation control using carbon dioxide REAL-TIME VENTILATION Operational control of ventilation systems using sensors that measure concentrations Editors Note: A longer version of this article is available at no cost on HPAC Engineering s Website

More information

Fixed equipment shall generally be furnished and installed by the General Contractor as part of the construction contract.

Fixed equipment shall generally be furnished and installed by the General Contractor as part of the construction contract. SECTION 11 00 00 - EQUIPMENT GENERAL INFORMATION Fixed equipment shall generally be furnished and installed by the General Contractor as part of the construction contract. Movable equipment shall, as a

More information

Fume Hood Equipment Service and Maintenance Policy

Fume Hood Equipment Service and Maintenance Policy Fume Hood Equipment Service and Maintenance Policy Objective: The objective of this policy is to establish fume hood equipment inspection, testing, and maintenance procedures to: Ensure the safety of students,

More information

Using CFD to Wring Out Energy Efficiency in Laboratory Settings

Using CFD to Wring Out Energy Efficiency in Laboratory Settings Using CFD to Wring Out Energy Efficiency in Laboratory Settings Energy Conservation Strategies for Cornell University Laboratories Primary focus is on controls to reduce outside air use Occupancy sensors

More information

Fundamentals of Test & Balance for Engineers, Cx & Energy Providers Course Number: CXENERGY1619

Fundamentals of Test & Balance for Engineers, Cx & Energy Providers Course Number: CXENERGY1619 AABC Commissioning Group AIA Provider Number 50111116 Fundamentals of Test & Balance for Engineers, Cx & Energy Providers Course Number: CXENERGY1619 Jim Hall, PE, TBE, CxA Systems Management & Balancing,

More information

Mity, relative static pressure, air motion, air cleanliness, sound,

Mity, relative static pressure, air motion, air cleanliness, sound, CHAPTER 14 LABORATORIES Laboratory Types... 14.1 Hazard Assessment... 14.2 Design Parameters... 14.2 LABORATORY EXHAUST AND CONTAINMENT DEVICES... 14.3 Fume Hoods... 14.3 Biological Safety Cabinets...

More information

Matt Gudorf Campus Energy Manager. Page 1

Matt Gudorf Campus Energy Manager. Page 1 Matt Gudorf Campus Energy Manager Page 1 Quick Facts About UCI 7.4 Million Square Feet of Conditioned Space District High Temp and Chilled Water Campus 12kV owned and operated grid 4.5 Million Gallon Thermal

More information

Indoor Air Quality and Mechanical Ventilation (Page 1 of 5)

Indoor Air Quality and Mechanical Ventilation (Page 1 of 5) Indoor Air Quality and Mechanical Ventilation (Page 1 of 5) Title 24, Part 6, Section 150.0(o) Ventilation for Indoor Air Quality. All dwelling units shall meet the requirements of ANSI/ASHRAE Standard62.2.

More information

Standard Operating Procedures for Servicing Laboratory Exhaust Systems

Standard Operating Procedures for Servicing Laboratory Exhaust Systems Standard Operating Procedures for Servicing Laboratory Exhaust Systems Policy Statement The following procedures were developed to protect Facilities & Services (F&S) personnel and University laboratory

More information

FUNDAMENTALS OF CHILLED BEAMS ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS

FUNDAMENTALS OF CHILLED BEAMS ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS FUNDAMENTALS OF CHILLED BEAMS ANSI/ASHRAE STANDARD 200-2015, METHODS OF TESTING CHILLED BEAMS NEMIC 2017 Hello! I am Davor Novosel I am here because I love to share what I know about chilled beams with

More information

Consensus Statements

Consensus Statements Chemical Fume Hood and Laboratory Ventilation: Operation, Design and Performance Testing 2013 Consensus Statements Outcomes of Fume Hood Summit Published May 1, 2015 1 Participants of the 2013 Fume Hood

More information

EBTRON. Airflow measurement for control of building pressure and IAQ

EBTRON. Airflow measurement for control of building pressure and IAQ EBTRON Airflow measurement for control of building pressure and IAQ SPEAKER INFORMATION Mark Blauvelt, Bluefield Engineered Systems, President 32 Years experience Started in the Industry in 1985 working

More information

SECTION LABORATORY FUME HOODS

SECTION LABORATORY FUME HOODS PART 1 - GENERAL 1.1 DESCRIPTION: SECTION 11 53 13 LABORATORY FUME HOODS SPEC WRITER NOTE: Delete between // // if not applicable to project. Delete other items or paragraphs in the section that are not

More information

Index of Addenda to ANSI/ASHRAE Standard 62.1

Index of Addenda to ANSI/ASHRAE Standard 62.1 a b in 62-1989 Published in 1990. The committee withdrew this addendum from consideration, and the issue of existing buildings was addressed by Addenda 62k and 62af. Withdrawn in September 2000. The addendum

More information

What s My Baseline? ASHRAE

What s My Baseline? ASHRAE 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions (2010, vol 116,part 2). For personal use only. Additional reproduction,

More information

1.02 Related Sections A. Section Heating, Ventilation and Air Conditioning (HVAC). C. Section Pneumatic and Electric Control HVAC.

1.02 Related Sections A. Section Heating, Ventilation and Air Conditioning (HVAC). C. Section Pneumatic and Electric Control HVAC. PART 1: GENERAL 1.01 Section Includes A. Dual duct terminal units. B. Variable volume regulators. C. Integral damper motor operators. D. Integral controls. 1.02 Related Sections A. Section 23 00 00 Heating,

More information

Chemical Hygiene Plan Hobart and William Smith Colleges Geoscience Department

Chemical Hygiene Plan Hobart and William Smith Colleges Geoscience Department Fall 2012 Chemical Hygiene Plan Hobart and William Smith Colleges Geoscience Department Hobart and William Smith Colleges Geoscience Department CHEMICAL HYGIENE PLAN The Occupational Safety and Health

More information

Aircuity Installation

Aircuity Installation Aircuity Installation Project Team Project Services Allen Shiroma Asst. Director Renovations Matt Gudorf Campus Energy Manager Adam Feuerstein Project Manager EH&S Lisa Mahar - Senior Mgr, Occupational

More information

A. The purpose of this section is to specify Division 23 responsibilities in the commissioning process.

A. The purpose of this section is to specify Division 23 responsibilities in the commissioning process. SECTION 23 99 50 - (ADD#4) PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Teague Research Center

Teague Research Center Continuous Commissioning Report for the Teague Research Center Building #445 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

Energy Efficiency Opportunities in the OR

Energy Efficiency Opportunities in the OR Energy Efficiency Opportunities in the OR John D. Villani, P.E. Vice President, Grumman/Butkus Associates Laurence Steiner, P.E. Associate Vice President, Grumman/Butkus Associates BUILD. CONNECT. ACHIEVE.

More information

LABORATORY CONTROL SOLUTIONS FROM TSI

LABORATORY CONTROL SOLUTIONS FROM TSI LABORATORY CONTROL SOLUTIONS FROM TSI UNDERSTANDING, ACCELERATED SAFE, FLEXIBLE CONTROL SOLUTIONS SAFETY Research in laboratories helps advance science in many different disciplines. Professionals working

More information

NJ AIHA CIH Review Industrial Ventilation

NJ AIHA CIH Review Industrial Ventilation NJ AIHA CIH Review Industrial Ventilation Thomas Block, CIH MPH tblock@aps.rutgers.edu 848-445-2550 2016 American Industrial Hygiene Association, New Jersey Section, Inc. Course Objectives At the end of

More information

Do-It-Yourself Energy Audit. Bob Furgeson, PE CEM CBCP GBE CEA Shive-Hattery Architects+Engineering

Do-It-Yourself Energy Audit. Bob Furgeson, PE CEM CBCP GBE CEA Shive-Hattery Architects+Engineering Do-It-Yourself Energy Audit Bob Furgeson, PE CEM CBCP GBE CEA Shive-Hattery Architects+Engineering Agenda» Basic Terminology» Background» Benchmarking» Audit Types/ASHRAE Standard» Building Audit Systems

More information

Section 6.6 BSL3 & ABSL3 Biocontainment

Section 6.6 BSL3 & ABSL3 Biocontainment NIH Design Requirements Manual 8-22-12 Section 6.6 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 Section 6.6

More information

Presenter: Wayne Wood, CIH, ROH, MScA. Director EHS, McGill University

Presenter: Wayne Wood, CIH, ROH, MScA. Director EHS, McGill University Presenter: Wayne Wood, CIH, ROH, MScA Director EHS, McGill University 1 Our agenda CSA - the standard-setting process The stakeholders The Z316.5-15 technical subcommittee Content of Z316.5-15 Z316.5-04

More information

YORK UNITIZED ENERGY RECOVERY VENTILATOR (ERV) Superior air-flow 300 6,200 CFM

YORK UNITIZED ENERGY RECOVERY VENTILATOR (ERV) Superior air-flow 300 6,200 CFM YORK UNITIZED ENERGY RECOVERY VENTILATOR (ERV) Superior air-flow 300 6,200 CFM YORK UNITIZED ENERGY RECOVERY VENTILATORS Regardless of building type or rating system, today s building must be as energy

More information

DISPLACEMENT VENTILATION

DISPLACEMENT VENTILATION DISPLACEMENT VENTILATION D3 OVERVIEW The fundamental approach to displacement ventilation utilizes the natural buoyancy forces created by the convective flows from heat sources in the space. As supply

More information

Air-Water Systems. Chilled Ceilings and Beams TROX USA. Principle of Operation. Radiant Effect on Occupants. Early 1980 s. Chilled Ceiling Panels

Air-Water Systems. Chilled Ceilings and Beams TROX USA. Principle of Operation. Radiant Effect on Occupants. Early 1980 s. Chilled Ceiling Panels Air-Water Systems and Beams Early 1980 s 1980 1990 2005 Buildings well insulated for heating Advent of personal computers Need to remove heat from space Limited space available TROX USA 1 2 Principle of

More information

THERMA-FUSER VARIABLE AIR VOLUME DIFFUSER SYSTEMS

THERMA-FUSER VARIABLE AIR VOLUME DIFFUSER SYSTEMS SUSTAINABLE DESIGN FORM 010.901 REV 1211 THERMA-FUSER VARIABLE AIR VOLUME DIFFUSER SYSTEMS SUSTAINABLE DESIGN GUIDE StopWaste.Org LEED-NC Platinum Energy Foundation LEED-CI Platinum Adobe East Tower LEED-EB

More information

South Carolina Society for Hospital Engineers

South Carolina Society for Hospital Engineers South Carolina Society for Hospital Engineers Selecting Energy Partners: Criteria & Pitfalls and the Top 10 Ways to Reduce Energy in a Hospital Presented by Jon Dierking, PE, CEM, LEED AP Director of Energy

More information

Achieving Near Net-Zero Energy Usage in Laboratory

Achieving Near Net-Zero Energy Usage in Laboratory Page 1 of 8 Published on www.tradelineinc.com (http://www.tradelineinc.com) Home > Achieving Near Net-Zero Energy Usage in Laboratory Facilities Achieving Near Net-Zero Energy Usage in Laboratory Facilities

More information

The Building Systems Detective

The Building Systems Detective Building Re-Commissioning Presented By Greg Bradshaw, CEM The Building Systems Detective Bradshaw Building Solutions, Inc. 303-475-77147714 greg@bradshawbuildingsolutions.com Introduction Re-Commissioning

More information

ENERGY EFFICIENT AIR QUALITY CONTROL IN LABORATORIES USING BENCH EXHAUSTS

ENERGY EFFICIENT AIR QUALITY CONTROL IN LABORATORIES USING BENCH EXHAUSTS ENERGY EFFICIENT AIR QUALITY CONTROL IN LABORATORIES USING BENCH EXHAUSTS Farhad Memarzadeh 1, Jane Jiang 2, and Andy Manning 2 1 PhD, PE, National Institutes of Health, Bethesda, MD, USA 2 PhD, Flomerics,

More information

Assessment of Containment and Product Protection In a Class II Type B3 Biological Safety Cabinet Under As-used Laboratory Conditions

Assessment of Containment and Product Protection In a Class II Type B3 Biological Safety Cabinet Under As-used Laboratory Conditions Assessment of Containment and Product Protection In a Class II Type B3 Biological Safety Cabinet Under As-used Laboratory Conditions Peter Harris and Dave Lupo B & V Testing, Inc. ABSA, 1999 Study Objective

More information

Proposed Addendum L to Standard , Ventilation for Acceptable Indoor Air Quality

Proposed Addendum L to Standard , Ventilation for Acceptable Indoor Air Quality BSR/ASHRAE Addendum L to ANSI/ASHRAE Standard 62.1-2016 Public Review Draft Proposed Addendum L to Standard 62.1-2016, Ventilation for Acceptable Indoor Air Quality Second Public Review (August 2018) (Draft

More information

VAV System Design Tips

VAV System Design Tips AMCA International VAV System Design Tips Steve Taylor, PE, FASHRAE Principal, Taylor Engineering LLC, Alameda, CA staylor@taylor-engineering.com Air System Engineering & Technology (ASET) Conference US

More information

Retro-Commissioning for Existing Facilities

Retro-Commissioning for Existing Facilities Retro-Commissioning for Existing Facilities Tom Meyer Director, Technical Programs National Environmental Balancing Bureau 8575 Grovemont Circle Gaithersburg, Maryland 20877 (301) 977-3698 www.nebb.org

More information

Energy Efficiency Baselines for LABORATORIES. PG&E s Customized New Construction and Customized Retrofit Incentive Programs.

Energy Efficiency Baselines for LABORATORIES. PG&E s Customized New Construction and Customized Retrofit Incentive Programs. Energy Efficiency Baselines for LABORATORIES PG&E s Customized New Construction and Customized Retrofit Incentive Programs October 1, 2010 Funded By: Written By: 427 13 th Street Oakland, CA 94612 510.663.2070

More information

Keep Beryllium at the Source. July 2018

Keep Beryllium at the Source. July 2018 Keep Beryllium at the Source July 2018 Keep Beryllium at the Source LEV Hood Source 2 Keep Beryllium At the Source - Guiding Principles Employees are not exposed to levels of particulate that causes chronic

More information

Updates to ANSI/ASHRAE/ASHE Standard , Ventilation of Health Care Facilities

Updates to ANSI/ASHRAE/ASHE Standard , Ventilation of Health Care Facilities Updates to ANSI/ASHRAE/ASHE Standard 170-2013, Ventilation of Health Care Facilities BY CHRIS P. ROUSSEAU, PE, LEED AP 30 th Annual AHCA Seminar and 52 nd Annual FHEA Meeting Orlando, Florida September

More information

Energy Recovery Ventilation & ERV Basics The New Custom Express Tool

Energy Recovery Ventilation & ERV Basics The New Custom Express Tool Energy Recovery Ventilation & ERV Basics The New Custom Express Tool Presented by: Dinesh Patel dinesh.patel@nationalgrid.com David Gaudet david.gaudet2@nationalgrid.com 1 What is and Why ERV? The recovery

More information

Report on Safe, Appropriate Uses for Filtered Self-Contained Enclosures

Report on Safe, Appropriate Uses for Filtered Self-Contained Enclosures Report on Safe, Appropriate Uses for Filtered Self-Contained Enclosures The need for alternatives to fume hoods Until the past decade, laboratory directors and safety officers have had only one option

More information

How to acquire Demand Controlled Ventilation with energy optimal functionality? John Woollett CEng Reserachers from SINTEF; Mads Mysen & Peter Schild

How to acquire Demand Controlled Ventilation with energy optimal functionality? John Woollett CEng Reserachers from SINTEF; Mads Mysen & Peter Schild How to acquire Demand Controlled Ventilation with energy optimal functionality? John Woollett CEng Reserachers from SINTEF; Mads Mysen & Peter Schild 1 John Woollett C.Eng, F.CIBSE, F.REHVA, M.ASHRAE.

More information

Building a Net Zero Lab in the United Arab Emirates: Mission Impossible?

Building a Net Zero Lab in the United Arab Emirates: Mission Impossible? Building a Net Zero Lab in the United Arab Emirates: Mission Impossible? Texas Children s Hospital, NRI: Masdar Institute, UAE Penn Medicine New Apple HQ Grand Mosque, Mecca MGM Macau Casino Gordon P.

More information

Mitigating Chemical Risks in Laboratories & the Good Laboratory Practices

Mitigating Chemical Risks in Laboratories & the Good Laboratory Practices Mitigating Chemical Risks in Laboratories & the Good Laboratory Practices Joseph Chan Evangelist for Workplace Safety Team Medical & Scientific Sdn. Bhd. joseph@tms-lab.com PART 1: SAFETY REQUIREMENTS

More information

THE LEADER IN PERFORMANCE INDOOR AIR QUALITY MEASUREMENTS

THE LEADER IN PERFORMANCE INDOOR AIR QUALITY MEASUREMENTS THE LEADER IN PERFORMANCE INDOOR AIR QUALITY MEASUREMENTS INDOOR AIR QUALITY INSTRUMENTS UNDERSTANDING, ACCELERATED BREATHE A LITTLE EASIER WITH TSI Indoor air quality is a growing concern. With the increasing

More information

Ventilation. Demand-controlled ventilation (DCV) Demand-Controlled. With ASHRAE Standard Based

Ventilation. Demand-controlled ventilation (DCV) Demand-Controlled. With ASHRAE Standard Based CO Demand-Controlled 2 -Based Ventilation With ASHRAE Standard 62.1 Though not as straightforward as it once was, remains a practical way to reduce costs Editor s note: Following is an update of the November

More information

ASSESSMENT, CLEANING & RESTORATION OF HVAC SYSTEMS (ACR-2002)

ASSESSMENT, CLEANING & RESTORATION OF HVAC SYSTEMS (ACR-2002) ASSESSMENT, CLEANING & RESTORATION OF HVAC SYSTEMS (ACR-2002) C Cochrane * and T Yacobellis National Air Duct Cleaners Association ACR 2002 Committee, Washington, DC, USA ABSTRACT In the fall of 2001 NADCA

More information

Acutherm was spec d here. Building Automation Guide for Therma-Fuser Systems

Acutherm was spec d here. Building Automation Guide for Therma-Fuser Systems Building Automation Guide for Therma-Fuser Systems Acutherm was spec d here BUILDING AUTOMATION OPTIONS FOR THERMA-FUSER SYSTEMS As energy costs continue to rise, the management of energy while balancing

More information

Community Collaborative Questions. American University Hall of Science. August 7, 2017

Community Collaborative Questions. American University Hall of Science. August 7, 2017 Community Collaborative Questions American University Hall of Science August 7, 2017 The following questions and issues have been raised for discussion: 1. LEED rating: Is it possible to achieve Platinum

More information

SECTION AIR TERMINAL UNITS

SECTION AIR TERMINAL UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

10 Thorough examination and test

10 Thorough examination and test 10 Thorough examination and test Key points Every employer s LEV system requires statutory thorough examination and testing by a competent person. The examination and testing report should have a prioritised

More information

Fume Cupboard Management Policy

Fume Cupboard Management Policy Fume Cupboard Management Policy 1.0 Purpose & Scope This policy serves to provide procurement, installation, maintenance, and management guidance for ducted fume cupboards either maintained by KCL estates

More information

Dynamic Reset for Multiple-Zone Systems

Dynamic Reset for Multiple-Zone Systems This article was published in ASHRAE Journal, March 2010. Copyright 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not be

More information

Fume Cupboard Management Policy

Fume Cupboard Management Policy Fume Cupboard Management Policy 1.0 Purpose & Scope This policy serves to provide procurement, installation, maintenance, and management guidance for ducted fume cupboards either maintained by KCL estates

More information

Implementing Demand Controlled Ventilation to Meet ASHRAE Standard By KlasC. Haglid, P.E., R.A., CEM

Implementing Demand Controlled Ventilation to Meet ASHRAE Standard By KlasC. Haglid, P.E., R.A., CEM Implementing Demand Controlled Ventilation to Meet ASHRAE Standard 62.1-2010 By KlasC. Haglid, P.E., R.A., CEM 1 Klas C. Haglid, P.E., R.A., CEM - Bio ASHRAE Distinguished Service Award 2011 ASHRAE Handbook,

More information

FACILITIES MANAGEMENT

FACILITIES MANAGEMENT FACILITIES MANAGEMENT Planning, Design & Construction November 26, 2014 Re: Request for Qualifications - Commissioning Services Bowen Science Building Modernize Building Systems University of Iowa The

More information

Indoor Air Quality. Dr. Iain S. Walker NSF BEST Center National Workshop January 8, 2015

Indoor Air Quality. Dr. Iain S. Walker NSF BEST Center National Workshop January 8, 2015 Indoor Air Quality Dr. Iain S. Walker NSF BEST Center National Workshop January 8, 2015 Current Work at LBNL Building America Program - a DOE/National Lab/Industry Partnership On-line high performance

More information

A Holistic Overview of Technologies and Strategies to Achieve Deep Energy Reductions in Laboratories

A Holistic Overview of Technologies and Strategies to Achieve Deep Energy Reductions in Laboratories A Holistic Overview of Technologies and Strategies to Achieve Deep Energy Reductions in Laboratories New Apple HQ Masdar City, UAE Grand Mosque, Mecca ASU: Biodesign Institute UHN: MaRS TMDT MGM Macau

More information

Air distribution and temperature control in classrooms

Air distribution and temperature control in classrooms Air distribution and temperature control in classrooms Jarek Kurnitski D.Sc., Docent HELSINKI UNIVERSITY OF TECHNOLOGY Laboratory of Heating, Ventilation and Air Conditioning Swegon Air Academy 11.6.2008

More information

TASK SHEET 1D MODELING FOR EXTERNAL EXAUST SYSTEMS. A Paper for the University of Washington written by:

TASK SHEET 1D MODELING FOR EXTERNAL EXAUST SYSTEMS. A Paper for the University of Washington written by: TASK SHEET 1D MODELING FOR EXTERNAL EXAUST SYSTEMS A Paper for the University of Washington written by: Michael A. Ratcliff, Ph.D., P.E. Jason Slusarczyk, B.Sc., P.Eng. of Rowan Williams Davies & Irwin,

More information

EXETER TOWNSHIP HOOD AND DUCT SYSTEMS FOR COMMERCIAL KITCHENS

EXETER TOWNSHIP HOOD AND DUCT SYSTEMS FOR COMMERCIAL KITCHENS HOOD AND DUCT SYSTEMS FOR COMMERCIAL KITCHENS POLICY STATEMENT This policy applies to NEW Hood and Duct systems. The Authority Having Jurisdiction will not waive major criteria in the applicable standards

More information