Study on the dc flashover performance of standard suspension insulator with ringshaped non-uniform pollution

Size: px
Start display at page:

Download "Study on the dc flashover performance of standard suspension insulator with ringshaped non-uniform pollution"

Transcription

1 High Voltage Research Article Study on the dc flashover performance of standard suspension insulator with ringshaped non-uniform pollution ISSN Received on 28th June 2017 Revised 1st October 2017 Accepted on 18th October 2017 doi: /hve Zhijin Zhang 1, Jiayao Zhao 1, Dongdong Zhang 1, Xingliang Jiang 1, Yongfu Li 2, Bin Wu 2, Jian Wu 2 1 State Key Laboratory of Power Transmission Equipment & System Security and New Technology, Chongqing University, Shapingba District, Chongqing , People's Republic of China 2 State Grid Chongqing Electric Power Co., Yuzhong District, Chongqing , People's Republic of China zhangzhijing@cqu.edu.cn Abstract: Under dc electric field, pollution may be more easily deposited around insulator string caps and pins, distributing nonuniformly on its inner and outer parts, and presenting ring-like shape. dc Flashover tests of 7-unit XHP-160 insulator string were carried out. During the tests, the ring-shaped non-uniform pollution was simulated using solid-layer method by changing the ratio I/O of inner-to-outer surface salt deposit density (SDD) and radius (r) of the heavily polluted area (the inner part). On the basis of the test data, the effects of ring-shaped non-uniform pollution on dc flashover characteristics were studied. Then, the relative variation trend of flashover voltage, surface pollution layer resistance, and leakage current were discussed. Research results show that the ratio I/O affects the dc flashover performance of the insulator string. The flashover voltage increases with the increase of I/O. With the increase of the radius r, the flashover voltage will increase at first and then decrease. Under ringshaped non-uniform pollution, surface pollution layer resistance of insulator will increase, which results in lower leakage current and higher flashover voltage. The results will be of certain value in providing references for outdoor insulation selection. 1 Introduction It is known that the success rate of transmission line lightning flashover re-closing is higher than that of pollution flashover, and so the loss caused by pollution flashover fault of external insulation is far greater than the lightning fault [1 3]. In recent years, along with the rapid development of industry and economy, the air quality is getting worst, making the pollution flashover still a threat to electric power system security [3]. The non-uniformity of the natural contamination can be divided into four ways: between the top and bottom surfaces of insulator, along the periphery, along the insulator length, and among the different insulator units of the same string [3 5]. To make the artificial test more comparable with the actual situation, relevant institutes have made a lot of studies on the flashover performance and mechanism under non-uniform pollution flashover. For instance, as is presented in the literature [6], insulator nonuniform pollution between top and bottom surfaces will affect flashover voltage, and this effect is associated with insulator shed structure. The literature [7] indicated that the ratio of non-uniform pollution from top to bottom surfaces (T/B) is in the range of 1/5 1/10. The literature [8] shows that the flashover voltage increases by 30 and 50%, when T/B changes from 1/1 to 1/5 and 1/10. Benchmarked against the salt deposit density (SDD) of bottom surface of insulator, Electric Power Research Institute (EPRI) [9] raised a formula K = U 2 U 1 = 1 C log T B for the correction of dc flashover voltage under non-uniform pollution, and got that the correction coefficient (C) was in the range of In the literature [10], another research was done to study on the influence of non-uniform pollution distribution on ac flashover voltage of standard suspension insulators, which found that the formula of EPRI is also applicable in ac case and the value of C was obtained as Moreover, some researches about other kinds of insulators non-uniform pollution were reported recently. For example, in [11], the researchers studied the fan-shaped non-uniform pollution (1) between windward and leeward sides of insulator string and its effects on dc flashover performance. The results indicated that flashover voltage may decrease by 28% under certain situation [11]. Researchers in [12] investigated the dielectric performance of a plane model using wavelet transform with respect to the position and width of pollution layer. Another research in [13] presented the effects of discontinuous non-uniform pollution on the flashover of polluted insulator under impulse voltage. In [14], the estimation of the effective pollution thickness was proposed when studying the effects of pollution layer linear non-uniformity on insulator flashover. Moreover in [15], effects of pollution distribution class on insulators flashover were studied, which leads to a conclusion that the insulator with non-uniform transverse distribution pollution will have a higher withstand voltage than those with uniform contamination. So far, works on T/B non-uniform pollution has been done around the world and the related results are applied in insulation coordination by designers. However, in operating lines, especially under dc electric field and variable wind directions, contaminants may get more easily deposit around insulator string's caps and pins, forming like a ring-shaped non-uniform distribution. As shown in Fig. 1, the observations of Figs. 1a c are obtained from the 1 year non-energised insulator strings suspended in Xuefeng Mountain Test Station, where it features a continental climate. The observations of Fig. 1d are obtained from the 18 months nonenergised insulator string on the rooftop of the high-voltage laboratory in urban area. The observations of Figs. 1e f are obtained from the 1 year dc-energised insulator string located on the 500 kv dc Jinsu line, where also features a continental climate. It may have some effects on its flashover voltage. So, the research on it is referable and valuable not only for the further insight of insulator flashover performance, but also for the better design of outdoor insulation coordination. 2 Sample, experimental setups, and procedure 2.1 Sample The samples were XHP-160 standard suspension insulators. The technical parameters are shown in Table 1, in which H is the 1

2 Fig. 1 Field insulators with ring-shaped non-uniform pollution Fig. 2 Schematic diagram of the dc test circuit The test circuit is shown in Fig. 2. In the circuit, the 10 kv/ac source offers a power rating of 300 kw, S 1 and S 2 are the front switch and post-switch, respectively, B represents a power transformer of 150 kv/900 kva, C 1, C 1, C 2, and C 2 are capacitors (the capacitance μf, voltage rating 213 kv), D is highvoltage silicon stack, Silicon Controlled Rectifier (SCR) is the silicon control elements, R 0 is a current limiting resistor (10 kω), r is a current sampling resistor (1 Ω), G is the discharge tube used for protecting the acquisition system (voltage rating 5 V), H is a 330 kv wall bushing, R 1 and R 2 are the resistors of the resistance divider F (voltage division ratio 15:1, input resistance 1800 MΩ, and voltage rating 600 kv), and the accuracy of F is 0.5%. E is the artificial climate chamber. Fig. 3 Ring-shaped non-uniform distribution diagram configuration height, L is the leakage distance, and D is the diameter of insulators. 2.2 Experimental setups The tests were carried out in the multi-function artificial climate chamber. The artificial climate chamber, which is with a diameter of 7.8 m and a height of 11.6 m, can simulate complex atmospheric environments such as fog, rain, ice, and high altitude [16 20]. The dc power supply is a 600 kv/0.5 A cascade rectifier circuit controlled by the thyristor voltage current feedback system which ensures that the voltage ripple factor is <3.0% when the load current is 0.5 A. The dynamic voltage drop of the power supply is no more than 5%, and the relative voltage overshoot due to load release is <8%. The test power supply satisfies the requirements recommended by [16 20]. Table 1 Parameters of the insulator sample Type Material H, mm D, mm L, mm XHP-160 porcelain Test procedure Preparation: Before the tests, all the samples were carefully cleaned by Na 2 PO 3 solution, so that all traces of dirt and grease were removed. Then, the samples were thoroughly rinsed with tap water, and let to dry naturally indoor to avoid dust or other pollution Polluting: The soluble contaminants were calculated by SDD. SDD represents the weight of sodium chloride (NaCl) per unit area of insulator, in mg/cm 2. Moreover, non-soluble material Kieselguhr was calculated by non-soluble deposit density (NSDD). SDD was selected for 0.06, 0.10, and 0.25 mg/cm 2 to represent three different levels of pollutions. The ratio of NSDD to SDD was 6 in all the tests. The contamination ratio of the inner-to-outer surface of the ring-shaped of the 7-unit XHP-160 insulator strings was generally selected for 1:1, 3:1, 8:1, and 15:1 to represent four different degrees of pollutions. The method of simulating ring-shaped non-uniform pollution is described as below. Through observing insulator natural contamination, it was found that the inner position of surface was more seriously polluted as shown in Fig. 1. Thus, the diagram of ring-shaped non-uniform pollution is shown in Fig. 3b, where region 1 is the steel cap of the insulator, region 2 is the heavily polluted area, named the inner part, and region 3 is the lightly polluted area, named the outer part. To enable artificial nonuniform pollution, the edges on the bottom surface of the insulator were regarded as the boundary of selecting the radius (r) of the inner part, as shown in Fig. 3c, and thus the radii (r) of the inner part were 8, 11, and 12.5 cm, respectively. The ring shape on the top surface and the bottom surface was divided by the same r. 2

3 Table 2 SDD I and SDD O r, cm SDD, mg/cm 2 I/O 1:1 3:1 8:1 15:1 SDD I SDD O SDD I SDD O SDD I SDD O SDD I SDD O Fig. 4 Flow chart for the test procedure The insulators were polluted using solid-layer method by pasting. The SDD of the inner part (SDD I ) and the outer part (SDD O ), and the average SDD of the porcelain insulators can be expressed as (2), and the data of SDD I and SDD O in this paper are shown in Table 2 SDD = SDD I S I + SDD O S O S I + S O I O = SDD (2) I SDD O where S I, S O are areas of the inner part and outer part of the surface, I/O represents the ratio of inner-to-outer surface SDD Flashover test: The predicted flashover voltage level should be obtained for the first up-and-down evaluation. First, a small voltage was applied on the insulator string, and then the steam fog, for which the rate was 0.05 ± 0.01 kg/h m 3, was supplied. The degree of wetness of the insulator surface was judged by observing the surface water film situation as well as the variation of recorded leakage current waveform. When the surface water films were formed and connected with each other, or the leakage current reached the maximum value and then started decreasing, the insulator pollution surface was treated as wholly wetted. Then, the voltage was raised until flashover. The final voltage value was taken as the expected flashover voltage U 50. In the tests, up-and-down method was adopted [16 20]. Each contaminated sample was subjected to at least ten valid individual tests. The applied voltage level in each test was varied according to the up-and-down method. The voltage step was 5% of the expected U 50. The first valid individual test was selected as being the first one that yields a result different from the preceding ones. Only the individual test and at least nine following individual tests were taken as useful tests to determine U 50. The U 50 and standard deviation (σ) are calculated as follows: σ = U 50 = (U in i ) N (3) N U i U 2 50 / N 1 /U % (4) i = 1 where U i is an applied voltage level, n i is the number of tests carried out at the same applied voltage U i, and N is the total number of valid tests. The test procedure of the up-and-down method has been summarised as shown in Fig Test results and analysis 3.1 dc Flashover test results Following the procedures above, dc flashover tests of 7-unit XHP-160 insulator strings polluted under different SDDs, r, and ratio (I/O) were carried out. The results are shown in Table 3. According to the test results, conclusions can be made as follows: 3

4 Table 3 Test results of 7-unit XHP-160 insulator string r, cm SDD, mg/cm 2 I/O 1:1 3:1 8:1 15:1 U 50, kv σ, % U 50, kv σ, % U 50, kv σ, % U 50, kv σ, % i. The standard deviations of these results are all <7%, which means that the dispersion of the test results is slight. ii. The flashover voltage of insulator string decreases with the increase of SDD. For example, when I/O is 3/1, r is 11 cm, and the values of SDD is 0.06, 0.10, and 0.25 mg/cm 2, the corresponding U 50 is 106.1, 97.1, and 85.2 kv, respectively. From the data above, it can be seen that the voltage decreases by 8.5 and 19.7% when the SDD increases from 0.06 to 0.10 and 0.25 mg/cm 2. iii. The ratio (I/O) of the inner-to-outer surface SDD has significant influence on U 50. Moreover, the flashover voltage U 50 of the insulator string increases with the increase of I/O. For example, the U 50 is 85.4, 97.1, 100.5, and kv when SDD is 0.10 mg/cm 2, r is 11 cm, and I/O changes in the range of 1/1, 3/1, 8/1 15/1. The data indicate that there is an increase of 13.7, 17.7, and 25.2% when the ratio I/O increases from 1/1 3/1, 8/1, and 15/1. iv. With the radius (r) of heavily polluted area increases, the flashover voltage of the insulator strings may experience an increasing trend at first and then decrease. For example, when SDD is 0.1 mg/cm 2, the ratio I/O is 8/1, and the value of r is 8, 11, and 12.5 cm, the corresponding U 50 is 94.8, 100.5, and 90.8 kv, respectively. Compared to the value of r = 11 cm that the voltage decreases by 5.7 and 9.7% when the r is 8 and 12.5 cm. The disparity between the data was slight, but the trend does exist according to repeated tests. 3.2 Relationship between U 50 and SDD A large number of experiment results indicate that the relationship between U 50 and SDD can be expressed as follows [21, 22]: U 50 = a SDD n (5) where a is a constant related to insulator material, structure, power type, pressure etc. Moreover, n is a characteristic index which reflects the influence of SDD on U 50. This formula is suitable for predicting the U 50 of insulator string with a known SDD. However, there is no idea that whether the formula is also proper for calculating the U 50 under ring-shaped non-uniform pollution. According to Table 3, the relationship between U 50 and SDD is shown in Fig. 5, where the curves are all fitted by exponential function as is expressed in (5). The fitting results were presented in Table 4. It can be seen from Fig. 5 and Table 4 that: i. The exponential curve fitting between U 50 and SDD is good, because all the fitting degrees R 2 are nearly 1. ii. The results from the curve shapes in Fig. 5 show that the influence of SDD on U 50 is similar under different I/O and r. In Table 4, the value of n which is in the range of is relatively changeless under any conditions. iii. Taking r = 8 cm as an example, when I/O increases from 1/1 3/1, 8/1, and 15/1, the a values increase from , 64.7, and 72.6, respectively, increased by 12.2, 28.9, and 44.6%, 29.0% in average, whereas n values decrease by 8.7, 26.1 and 39.1%, 24.6% in average. It indicates that ring-shaped nonuniform pollution will affect both a and n obviously. 4 Effects of non-uniform pollution on the dc flashover performance 4.1 Effects on critical leakage current The ratio (I/O) of insulator string affects its pollution flashover voltage. For example, when r = 11 cm, the relationship between I/O and U 50 is shown in Fig. 6. It can be seen from Fig. 6 that: the values of U 50 increase with the increase of I/O. This result may be associated with critical leakage current. Leakage current signal contains a wealth of information in reflecting the operational status of the insulators. In this paper, the leakage current just before flashover, namely the critical leakage current I CR, was selected as the characteristic parameter of discharge process. Fig. 7 shows the leakage current waveform when the insulator flashover occurs, generally, the peak value before flashover is defined as critical leakage current I CR. During the test, I CR of each flashover test were recorded, and the average values corresponding to each pollution condition were obtained and shown in Fig. 8. Fig. 8 shows that, in a certain SDD, the insulator surface critical leakage current decreases with increase of I/O. For example, when SDD=0.06 mg/cm 2, the critical leakage current values are 0.27, 0.20, 0.14, and 0.10 A when the I/O ratio increases from 1/1, 3/1, 8/1 15/1. This change is due to the non-uniform distribution of the insulator surface contamination, which causes the variation of its surface conductivity. 4.2 Effects on surface pollution layer resistance The radius (r) of heavily polluted area of insulator affects its flashover voltage. For example, when I/O = 8/1, the relationship between them is shown in Fig. 9. It can be seen from Fig. 9 that: with the increase of r, the flashover voltage of insulator string will increase at first and then decrease. This result is inseparable with the surface pollution layer resistance. During the artificial tests, the samples were polluted by NaCl uniformly in each section, so the surface pollution layer conductivity (γ) is directly proportional to the SDD when they are at the same temperature and saturated enough. Moreover, (2) shows that when I/O > 1, SDDO < SDD, SDDI > SDD, namely an increase of I/O will cause the surface layer conductivity of the outer part to decrease; in return, the contamination layer resistance will increase; for the inner part of the surface the situation will be opposite, its contamination layer resistance will decrease. On the basis of the series resistance model of insulator pollution flashover, under ring-shaped non-uniform pollution the surface 4

5 Fig. 5 Relationships between SDD and U 50 (a) r = 8 cm, (b) r = 11 cm, (c) r = 12.5 cm Table 4 Fitting results of U 50 -SDD under non-uniform pollution I/O r, cm a n R 2 a n R 2 a n R 2 1: : : : Fig. 6 Relationship between U 50 and I/O (r = 11 cm) pollution layer of insulator string can be equivalent to (Fig. 10), where L Ii is the creepage distance of inner part of the ith insulator string unit under a certain r (red lines in Fig. 3a); L Oi is the corresponding outer part creepage distance (yellow lines in Fig. 3a); and a is the effective insulator diameter which can be calculated as follows [23 26]: a = L c / f (6) Fig. 7 Waveform of leakage current along the surface of insulator where L c is the creepage distance of insulator string, f is the shape coefficient or form factor of the insulator, which can be expressed by f = 0 L dl πd(l) So, the equivalent surface pollution layer resistance (R eq_non ) under ring-shaped non-uniform pollution can be obtained (7) 5

6 Fig. 8 Relationship between I CR and I/O of 7-unit XHP-160 insulator string (r = 11 cm) Fig. 11 Relationship between L I /L C, I/O, and η a certain L C (total creepage distance). η Values under different I/O and L I /L O are shown in Fig. 11. It can be seen from Fig. 11 that: with the increase of L I /L C, the value of η will increase at first and then decrease. This explains that when r increases, the surface pollution layer resistance will change, which affects flashover voltage. Also with the increase of I/O, η will keep increasing. This is consistent with the experimental data, because the leakage current decreases with the increment of pollution layer resistance, making the dry band less easily form on insulator surface than before, and a higher voltage will be needed to maintain the ignition of partial arcs and flashover. Fig. 9 Relationship between U 50 and r Fig. 10 Pollution layer equivalent model under ring-shaped non-uniform pollution R eq_non = R O + R I = 1 a L O L Oi γ O + L I L Ii γ I = 1 a L O γ O + L I γ I (8) where L O and L I are the creepage distances of outer part and inner part, respectively, and L c = L O + L I ; γ O and γ I are the surface pollution layer conductivity of outer part and inner part, respectively. Given the surface pollution layer conductivity (γ) proportional to SDD, and by (2) and (8), the relationship of the insulator surface contamination resistance under uniform pollution (R eq_uni ) and under non-uniform pollution (R eq_non ) can be expressed by (9) η = R eq_non = L O/L C R eq_uni γ O /γ + L I/L C γ I /γ = L O 2 + L I 2 + I/O + I/O 1 L O L I L C 2 According to (9) it can be seen that when I/O > 1, η is always larger than 1, meaning that ring-shaped non-uniform pollution will cause pollution layer resistance to increase, thus impact flashover voltage. The bigger the inner part radius r is, the larger L I /L O under (9) 5 Conclusions In this paper, the flashover performance of 7-unit XHP-160 insulator strings polluted by different SDD, I/O, and r was studied. Through analysis the following conclusions can be obtained: i. The flashover voltage U 50 of the insulator string increases with the increase of I/O, and may increase by nearly 36% under certain condition. With the increase of radius (r) of heavily polluted area, the flashover voltage will experience an increasing trend at first and then decrease. ii. The variation of insulator surface pollution layer resistance well explains the effects of different ring-shaped nonuniformity conditions (I/O and r) on insulator pollution flashover performances. With the increase of r, L I /L C will increase, causing the change of surface pollution layer resistance, thus affecting flashover voltage. Also with the increase of I/O, η will keep increasing, which rises surface pollution layer resistance, making the dry band more hardly form on the pollution layer surface, and a higher voltage will be needed for flashover. iii. It is obtained through the systematical research of this paper that insulator flashover voltage will increase if under ringshaped non-uniform pollution. Therefore, the current external insulation configuration of transmission line has sufficient safety margin according to existing standards. However, if insulators in certain area are ring-shaped non-uniform polluted all the time, it is recommended to properly reduce insulator units to save insulation space. 6 Acknowledgments This work was supported by the State Grid Corporation of China (CN: SGTYHT/14-JS-188, SGCQJX00YJJS ). The authors thank all members of external insulation research team in the Chongqing University for their hard work to obtain the experimental data in this paper. 6

7 7 References [1] Leclerc, M., Bouchard, R.P., Gervais, Y., et al.: Wetting processes on a contaminated insulator surface, IEEE Trans. Power Appl. Syst., 1982, 101, pp [2] Zhang, Z.J., Jiang, X.L., Cao, Y.F., et al.: Influence of low atmospheric pressure on AC pollution flashover performance of various types insulators, IEEE Trans. Dielectr. Electr. Insul., 2010, 17, pp [3] Chakravorti, S., Mukherjee, P.K.: Power frequency and impulse field calculation around a HV insulator with uniform or non-uniform surface pollution, IEEE Trans. Electr. Insul., 1993, 28, pp [4] Naito, K., Hasegawa, Y., Imakoma, T.: Improvement of the DC voltage insulation efficiency of suspension insulators under contaminated conditions, IEEE Trans. Electr. Insul., 1988, 23, pp [5] Koshairy, M.A.E., Rizk, F.A.M.: Comportement des isolateurs des lignes de transport de très haute tension dans les conditions désertiques. Rapport 33-05, CIGRE, Paris, France, 1970 [6] Zhang, Z.J., Liu, X.H., Jiang, X.L., et al.: Study on AC flashover performance for different types of porcelain and glass insulators with nonuniform pollution, IEEE Trans. Power Deliv., 2013, 28, pp [7] Jiang, X.L., Wang, S.H., Zhang, Z.J., et al.: Investigation of flashover voltage and non-uniform pollution correction coefficient of short samples of composite insulator intended for ±800 kv UHVDC, IEEE Trans. Dielectr. Electr. Insul., 2010, 17, pp [8] Ye, H., Zhang, J., Ji, Y., et al.: Contamination accumulation and withstand voltage characteristics of various types of insulators. IEEE Seventh Int. Conf. Properties and Applications of Dielectric Materials (ICPADM), Nagoya, Japan, 2003, pp [9] EPRI: HVDC transmission line insulation performance Report EL24618 EPRI, USA, 1986 [10] Sima, W., Yuan, T., Yang, Q.: Effect of non-uniform pollution on the withstand characteristics of extra high voltage (EHV) suspension ceramic insulator string, IET Gener. Transm. Distrib., 2010, 4, pp [11] Zhang, Z.J., Zhang, D.D., Zhang, W., et al.: DC flashover performance of insulator string with fan-shaped non-uniform pollution, IEEE Trans. Dielectr. Electr. Insul., 2015, 22, pp [12] Douar, M.A., Mekhaldi, A., Bouzidi, M.C.: Flashover process and frequency analysis of the leakage current on insulator model under non-uniform pollution conditions, IEEE Trans. Dielectr. Electr. Insul., 2010, 17, pp [13] Slama, M.E., Beroual, A., Hadi, H.: The effect of discontinuous non-uniform pollution on the flashover of polluted insulators under lightning impulse voltage Int. Conf. High Voltage Engineering and Application, Shanghai, China, 2012, pp [14] Slama, M.E., Beroual, A., Hadi, H.: Influence of the linear non-uniformity of pollution layer on the insulator flashover under impulse voltage estimation of the effective pollution thickness, IEEE Trans. Dielectr. Electr. Insul., 2011, 18, pp [15] Boudissa, R., Bayadi, A., Haddad, A., et al.: Effect of pollution distribution class on insulators flashover under AC voltage. 47th Int. Universities Power Engineering Conf. (UPEC), 2012, pp. 1 6 [16] Jiang, X.L., Yuan, J.H., Zhang, Z.J., et al.: Study on pollution flashover performance of short samples of composite insulators intended for ±800 kv UHV DC, IEEE Trans. Dielectr. Electr. Insul., 2007, 14, pp [17] Jiang, X., Yuan, J., Shu, L., et al.: Comparison of DC pollution flashover performances of various types of porcelain, glass, and composite insulators, IEEE Trans. Power Deliv., 2008, 23, pp [18] Jiang, X., Yuan, J., Shu, L., et al.: Study on ac pollution flashover performance of composite insulators at high altitude sites of m, IEEE Trans. Dielectr. Electr. Insul., 2009, 16, pp [19] Jiang, X., Yuan, J., Shu, L., et al.: Study on AC artificial-contaminated flashover performance of various types of insulators, IEEE Trans. Power Deliv., 2007, 22, pp [20] Zhang, Z., Jiang, X., Cao, Y., et al.: Study on DC pollution flashover performance of various types of long string insulators under low atmospheric pressure conditions, IEEE Trans. Dielectr. Electr. Insul., 2010, 17, pp [21] Sundararajan, R.: Effect of insulator pro files on dc flashover voltage under polluted conditions, IEEE Trans. Dielectr. Electr. Insul., 1994, 1, pp [22] Farzaneh, M., Farokhi, S., Chisholm, W.A.: Electrical design of overhead power transmission lines (McGraw-Hill Professional, New York, 2013, 1st edn.) [23] Holtzhausen, J.P., Vosloo, W.L.: The pollution flashover of ac energized post type insulators, IEEE Trans. Dielectr. Electr. Insul., 2001, 8, pp [24] Slama, M.A., Beroual, A., Hadi, H.: Analytical computation of discharge characteristic constants and critical parameters of flashover of polluted insulators, IEEE Trans. Dielectr. Electr. Insul., 2010, 17, pp [25] Rizk, F.A.M.: Modeling of altitude effects on AC flashover of polluted high voltage insulators, IEEE Trans. Power Deliv., 1997, 12, pp [26] Sundararajan, R., Gorur, R.S.: Dynamic arc modeling of pollution flashover of insulators under DC voltage, IEEE Trans. Electr. Insul., 1993, 28, pp

Study on AC Flashover Performance for Different Types of Porcelain and Glass Insulators With Non-Uniform Pollution

Study on AC Flashover Performance for Different Types of Porcelain and Glass Insulators With Non-Uniform Pollution IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 28, NO. 3, JULY 2013 1691 Study on AC Flashover Performance for Different Types of Porcelain and Glass Insulators With Non-Uniform Pollution Zhijin Zhang, Xiaohuan

More information

Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various Pollution Conditions at Costal Regions

Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various Pollution Conditions at Costal Regions Volume 114 No. 9 217, 1-9 ISSN: 1311-88 (printed version); ISSN: 1314-3395 (on-line version) url: http://www.ijpam.eu ijpam.eu Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various

More information

Study on Pollution Flashover Performance of Short Samples of Composite Insulators Intended for ±800 kv UHV DC

Study on Pollution Flashover Performance of Short Samples of Composite Insulators Intended for ±800 kv UHV DC 1192 Study on Pollution Flashover Performance of Short Samples of Composite Insulators Intended for ±800 kv UHV DC Xingliang Jiang, Jihe Yuan, Zhijin Zhang, Jianlin Hu and Lichun Shu Chongqing University

More information

Potential and E-Field Calculation Along an Ice- Covered Composite Insulator with Finite Element Method

Potential and E-Field Calculation Along an Ice- Covered Composite Insulator with Finite Element Method Potential and E-Field Calculation Along an Ice- Covered Composite Insulator with Finite Element Method Qing Yang, Caixin Sun, Wenxia Sima, Lichun Shu, Ji Yang, Jianlin Hu The Key Laboratory of High Voltage

More information

The Effect of Severity and Location of Pollution on Leakage Current Characteristics of Porcelain Insulators under Different Humidity Condition

The Effect of Severity and Location of Pollution on Leakage Current Characteristics of Porcelain Insulators under Different Humidity Condition The Effect of Severity and Location of Pollution on Leakage Current Characteristics of Porcelain Insulators under Different Humidity Condition Ali Azizi Tousi Mohammad Mirzaie Babol University of Technology,

More information

A Study of Critical Positive Impulse Flashover of 24 kv Contaminated Insulators

A Study of Critical Positive Impulse Flashover of 24 kv Contaminated Insulators The 5 th PSU-UNS International Conference on Engineering and 467 Technology (ICET-2011), Phuket, May 2-3, 2011 Prince of Songkla University, Faculty of Engineering Hat Yai, Songkhla, Thailand 90112 Study

More information

Pollution Performance of HVDC SiR Insulators at Extra Heavy Pollution Conditions

Pollution Performance of HVDC SiR Insulators at Extra Heavy Pollution Conditions IEEE Transactions on Dielectrics and Electrical Insulation Vol. 21, No. 2; April 2014 721 Pollution Performance of HVDC SiR Insulators at Extra Heavy Pollution Conditions A. Abbasi, A. Shayegani and K.

More information

Journal of Operation and Automation in Power Engineering. Vol. 1, No. 2, Summer & Fall 2013, Pages:

Journal of Operation and Automation in Power Engineering. Vol. 1, No. 2, Summer & Fall 2013, Pages: Journal of Operation and Automation in Power Engineering Vol. 1, No. 2, Summer & Fall 2013, Pages: 74-83 http://journals.uma.ac.ir/joape Impact of Pollution Location on Time and Frequency Characteristics

More information

The Reliability Study of the Statistical Method on Insulator Dimensioning of (U)HVDC Lines with Regard to Pollution Conditions

The Reliability Study of the Statistical Method on Insulator Dimensioning of (U)HVDC Lines with Regard to Pollution Conditions 1 The Reliability Study of the Statistical Method on Insulator Dimensioning of (U)HVDC Lines with Regard to Pollution Conditions Ying Long 1, Yan Xiao 1, Zhiyi Su 2, Dong Wu 3, Urban Astrom 3 Abstract--The

More information

Study of Pre-polluting Methods on Artificial Icing Flashover Characteristics of Composite Insulators

Study of Pre-polluting Methods on Artificial Icing Flashover Characteristics of Composite Insulators IWAIS XIII, Andermatt, September 8 to 11, 2009 Study of Pre-polluting Methods on Artificial Icing Flashover Characteristics of Composite Insulators Lichun Shu 1, Xiaolin Li 2, Xingliang Jiang 1, Jianlin

More information

Vijendra Singh Parihar 1, Prof. Anil Kumar Kori 2 1

Vijendra Singh Parihar 1, Prof. Anil Kumar Kori 2 1 Effects of Creepage distance on Leakage Current of 220kV Long Rod Insulators at Different Severity Level of Salt Contamination Vijendra Singh Parihar 1, Prof. Anil Kumar Kori 2 1 PG Student 2 Associate

More information

Panagiotis Charalampidis

Panagiotis Charalampidis Textured Insulators for Overhead Lines and Substations I. INTRODUCTION Panagiotis Charalampidis High Voltage Energy Systems Group, School of Engineering, Cardiff University, The Parade, Cardiff CF24 3AA,

More information

Performance investigation of composite and RTV SIR coated insulators at a coastal test station

Performance investigation of composite and RTV SIR coated insulators at a coastal test station Performance investigation of composite and RTV SIR coated insulators at a coastal test station K. Siderakis High Voltage Laboratory, Technological and Educational Institute of Crete D. Pylarinos High Voltage

More information

Predicting Contamination Flashover of Insulators: Successes and Shortcomings of Tests and Simulations

Predicting Contamination Flashover of Insulators: Successes and Shortcomings of Tests and Simulations Predicting Contamination Flashover of Insulators: Successes and Shortcomings of Tests and Simulations Ravi S. Gorur and S. Venkataraman (Ph. D Student), Arizona State University Perhaps no single area

More information

Cigré WG C Topics: The selection of insulators with respect to polluted conditions

Cigré WG C Topics: The selection of insulators with respect to polluted conditions Cigré Guide for the selection of insulators with respect to contamination conditions Chris Engelbrecht: Convener Topics: The selection of insulators with respect to polluted conditions Present practise

More information

Selection between indoor or outdoor DC yards D. WU*, U. ÅSTRÖM, L. ARÉVALO, R. MONTAÑO, B. JACOBSON ABB HVDC SWEDEN

Selection between indoor or outdoor DC yards D. WU*, U. ÅSTRÖM, L. ARÉVALO, R. MONTAÑO, B. JACOBSON ABB HVDC SWEDEN 21, rue d Artois, F-75008 PARIS B3-115 CIGRE 2014 http : //www.cigre.org Selection between indoor or outdoor DC yards D. WU*, U. ÅSTRÖM, L. ARÉVALO, R. MONTAÑO, B. JACOBSON ABB HVDC SWEDEN SUMMARY In an

More information

Comparison of effects of Various Contaminations on SiR insulators

Comparison of effects of Various Contaminations on SiR insulators Volume 120 No. 6 2018, 609-620 ISSN: 1314-3395 (on-line version) url: http://www.acadpubl.eu/hub/ http://www.acadpubl.eu/hub/ Comparison of effects of Various Contaminations on SiR insulators Satheesh

More information

Flashover Performance of Pre-contaminated and Ice-covered Composite Insulators to be Used in 1000 kv UHV AC Transmission Lines

Flashover Performance of Pre-contaminated and Ice-covered Composite Insulators to be Used in 1000 kv UHV AC Transmission Lines IEEE Transactions on Dielectrics and Electrical Insulation Vol. 14, No. 6; December 2007 1347 Flashover Performance of Pre-contaminated and Ice-covered Composite Insulators to be Used in 1000 kv UHV AC

More information

PERFORMANCE ANALYSIS OF OVERHEAD PORCELAIN INSULATOR UNDER DIFFERENT CONTAMINATIONS

PERFORMANCE ANALYSIS OF OVERHEAD PORCELAIN INSULATOR UNDER DIFFERENT CONTAMINATIONS International Journal of Mechanical Engineering and Technology (IJMET) Volume 8, Issue 10, October 2017, pp. 241 245, Article ID: IJMET_08_10_028 Available online at http://www.iaeme.com/ijmet/issues.asp?jtype=ijmet&vtype=8&itype=10

More information

INSULATOR REQUERIMENTS:

INSULATOR REQUERIMENTS: 2017 INMR WORLD CONGRESS SITGES-BARCELONA, INSULATOR REQUERIMENTS: DESIGN CRITERIA, OPERATION PARAMETERS AND STANDARDS REVIEW JAVIER GARCÍA TECHNICAL AND PRODUCTION MANAGER CONTENTS q INTRODUCTION q MECHANICAL

More information

Different Characteristics of Artificially Polluted High Voltage Composite Insulators

Different Characteristics of Artificially Polluted High Voltage Composite Insulators Different Characteristics of Artificially Polluted High Voltage Composite Insulators Farhad Shahnia 1 and Ghasem Ahrabian 2 1 Eastern Azarbayjan Electric Power Distribution Company, Tabriz, Iran 2 Faculty

More information

Measurement of surface resistance of silicone rubber sheets under polluted and dry band conditions

Measurement of surface resistance of silicone rubber sheets under polluted and dry band conditions Electr Eng (2018) 100:1729 1738 https://doi.org/10.1007/s00202-017-0652-x ORIGINAL PAPER Measurement of surface resistance of silicone rubber sheets under polluted and dry band conditions Arshad 1 A. Nekahi

More information

Polluted Outdoor Insulators Maintenance and Washing

Polluted Outdoor Insulators Maintenance and Washing Polluted Outdoor Insulators Maintenance and Washing Ali Naderian, PhD, PEng, SM IEEE Toronto, Canada February 2018 ali.naderian@ieee.org 1 برگزار کنندگان ایکهربا سامانه تجهیزات صنعت برق ایران کارشناسان

More information

Effect of Metal Ring on the Field Distribution of Outdoor Polymeric Insulator

Effect of Metal Ring on the Field Distribution of Outdoor Polymeric Insulator Effect of Metal Ring on the Field Distribution of Outdoor Polymeric Insulator Veeresh A G Meenakshendra A Khamitkar MTech(Power System Engineering) MTech(Power System Engineering) SDM College Of Engineering

More information

Effect of UV-Rays and Salt Contamination on 33kV Silicon Composite Insulators

Effect of UV-Rays and Salt Contamination on 33kV Silicon Composite Insulators IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 11, Issue 6 Ver. II (Nov. Dec. 2016), PP 45-55 www.iosrjournals.org Effect of UV-Rays and

More information

Comments on Document from Richard Martin, Canada

Comments on Document from Richard Martin, Canada Comments on Document 60815-1 from Richard Martin, Canada Please find the comments on the Acrobat document Nuremberg/235a. The commented document contains only the pages where there are some comments or

More information

HIGH VOLTAGE INSULATORS. By JP Holtzhausen. Glass. Bushings & hollow core insulators. Cap & pin insulators

HIGH VOLTAGE INSULATORS. By JP Holtzhausen. Glass. Bushings & hollow core insulators. Cap & pin insulators HIGH VOLTAGE INSULATORS By JP Holtzhausen The principal dielectric used on overhead power lines is air at atmospheric pressure. The air, surrounding the bare high voltage aluminium or steel- cored aluminium

More information

Investigation of leakage current flow through wooden poles structures on overhead distribution system

Investigation of leakage current flow through wooden poles structures on overhead distribution system Proceedings of the 7th WSEAS International Conference on Power Systems, Beijing, China, September 15-17, 2007 120 Investigation of leakage current flow through wooden poles structures on overhead distribution

More information

Natural Contamination and Surface Flashover on Silicone Rubber Surface under Haze Fog Environment

Natural Contamination and Surface Flashover on Silicone Rubber Surface under Haze Fog Environment energies Article Natural Contamination and Surface Flashover on Silicone Rubber Surface under Haze Fog Environment Ang Ren 1,2 ID, Hongshun Liu 1,2, *, Jianchun Wei 1,2 and Qingquan Li 1,2 1 Department

More information

Reprinted from the Proceedings of the 2001 IEEE/PES Transmission and Distribution Conference and Exposition, Atlanta, Georgia.

Reprinted from the Proceedings of the 2001 IEEE/PES Transmission and Distribution Conference and Exposition, Atlanta, Georgia. Copyright 21 IEEE. Reprinted from the Proceedings of the 21 IEEE/PES Transmission and Distribution Conference and Exposition, Atlanta, Georgia. This material is posted here with permission of the IEEE.

More information

Simulation Study of the Pollution Deposition Characteristics of the Insulators on High-Voltage DC Transmission Lines

Simulation Study of the Pollution Deposition Characteristics of the Insulators on High-Voltage DC Transmission Lines 1177 A publication of CHEMICAL ENGINEERING TRANSACTIONS VOL. 62, 2017 Guest Editors: Fei Song, Haibo Wang, Fang He Copyright 2017, AIDIC Servizi S.r.l. ISBN 978-88-95608-60-0; ISSN 2283-9216 The Italian

More information

COMPARATIVE LABORATORY PERFORMANCE CHARACTERISATION OF SILICONE RUBBER TEXTURED INSULATORS

COMPARATIVE LABORATORY PERFORMANCE CHARACTERISATION OF SILICONE RUBBER TEXTURED INSULATORS COMPARATIVE LABORATORY PERFORMANCE CHARACTERISATION OF SILICONE RUBBER TEXTURED INSULATORS BY ADNAN SALAMA KRZMA B.SC., M.SC., ELECTRICAL ENGINEERING Thesis submitted to Cardiff University In candidature

More information

Risk assessment of pollution on a 66kV composite insulator using ANSYS

Risk assessment of pollution on a 66kV composite insulator using ANSYS Risk assessment of pollution on a 66kV composite insulator using ANSYS Ms. N H M Netravati 1, Mrs. Sunitha N.S 2, Dr.Shivakumara Aradhya R.S. 3, Dr. K.N Ravi 4 M.Tech. student 1, Assistant Professor 2,

More information

ILMOS Insulator Leakage Current Monitor

ILMOS Insulator Leakage Current Monitor ILMOS Insulator Leakage Current Monitor Author: Eugenio Concha G Psptechnologies Inc. econcha@psptechnologies.com 1) Introduction increasing the leakage length of the insulators in the most vulnerable

More information

POLLUTION PERFORMANCE OF SILICONE AND EPDM INSULATOR PROFILES

POLLUTION PERFORMANCE OF SILICONE AND EPDM INSULATOR PROFILES Clive LUMB 22/09/05 Originally presented to CIGRE C4.3.03, submitted to 36-WG11 to illustrate: Importance of insulating length Importance of worst case and best case testing of composites. 36-WG11/Paris/216

More information

Experimental Techniques to Simulate Naturally Polluted High Voltage Transmission Line Insulators

Experimental Techniques to Simulate Naturally Polluted High Voltage Transmission Line Insulators IEEE Transactions on Dielectrics and Electrical Insulation Vol. 21, No. 5; October 14 2199 Experimental Techniques to Simulate Naturally Polluted High Voltage Transmission Line Insulators O. E. Gouda Cairo

More information

ESDD PREDICTION OF OUTDOOR POLYMER INSULATORS. Abdelrahman Khaled

ESDD PREDICTION OF OUTDOOR POLYMER INSULATORS. Abdelrahman Khaled ESDD PREDICTION OF OUTDOOR POLYMER INSULATORS by Abdelrahman Khaled A Thesis Presented to the Faculty of the American University of Sharjah College of Engineering in Partial Fulfillment of the Requirements

More information

Artificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester

Artificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester Artificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester W. Payakcho, J. Grasaesom, S. Thong-om and B. Marungsri* Abstract This paper presents the experimental results

More information

THERMAL IMAGE, PARTIAL DISCHARGE AND LEAKAGE CURRENT CORRELATION OF CERAMIC INSULATOR UNDER DIFFERENT CONTAMINATION LEVEL

THERMAL IMAGE, PARTIAL DISCHARGE AND LEAKAGE CURRENT CORRELATION OF CERAMIC INSULATOR UNDER DIFFERENT CONTAMINATION LEVEL THERMAL IMAGE, PARTIAL DISCHARGE AND LEAKAGE CURRENT CORRELATION OF CERAMIC INSULATOR UNDER DIFFERENT CONTAMINATION LEVEL Darwison 1.3, Syukri Arief 3, Hairul Abral 2, Ariadi Hazmi 1, M. H. Ahmad 4 and

More information

Data Sheet 110kV TD123II dry type outdoor termination

Data Sheet 110kV TD123II dry type outdoor termination 3 Data Sheet 110kV TD123II dry type outdoor termination 1. Product Description: 3M 110kV TD123II dry type outdoor termination meets requirement of test and product according to IEC60840 and GB11017.3,

More information

Laboratory Investigation on Hydrophobicity of New Silicon Rubber Insulator under Different Environmental Conditions

Laboratory Investigation on Hydrophobicity of New Silicon Rubber Insulator under Different Environmental Conditions International Journal of Electrical & Computer Sciences IJECS-IJENS Vol: 12 No: 03 1 Laboratory Investigation on Hydrophobicity of New Silicon Rubber Insulator under Different Environmental Conditions

More information

Mitigating Contamination Related Issues on T&D Equipment. Lily Hoyer Simon Chan

Mitigating Contamination Related Issues on T&D Equipment. Lily Hoyer Simon Chan Mitigating Contamination Related Issues on T&D Equipment Lily Hoyer Simon Chan Substation Insulator Pollution Contamination Management PRESENTED BY LILY HOYER T&D ASSET MANAGEMENT ENMAX POWER CORPERATION

More information

COMPARISON OF THE SPECIFIC SURFACE CONDUCTIVITY AND ESDD APPROACHES TO ASSESSMENT OF SALT DEPOSITS ON NATURALLY POLLUTED INSULATORS. 1.

COMPARISON OF THE SPECIFIC SURFACE CONDUCTIVITY AND ESDD APPROACHES TO ASSESSMENT OF SALT DEPOSITS ON NATURALLY POLLUTED INSULATORS. 1. E. A. Solomonik 36-WG11/Nberg/158 19/06/03 L. L. Vladimirsky, E. A. Solomonik HVDC Power Transmission Research Institute (NIIPT) COMPARISON OF THE SPECIFIC SURFACE CONDUCTIVITY AND ESDD APPROACHES TO ASSESSMENT

More information

Composite Insulator Components

Composite Insulator Components Composite Insulator Components Composite insulator components A composite insulator is made of at least two insulating parts a core and housing. It is equipped with end fittings. Core. The core is the

More information

Porcelain versus Polymer Insulator- A Changing Era in Transmission Lines

Porcelain versus Polymer Insulator- A Changing Era in Transmission Lines Porcelain versus Polymer Insulator- A Changing Era in Transmission Lines K. R. Suri a, A. Gupta b, Y. Anand b, S. Anand b General Manager (Retd.), Power Grid Corporation of India Limited School of Energy

More information

Development of Composite Line Spacers for Distribution Lines

Development of Composite Line Spacers for Distribution Lines Development of Composite Line Spacers for Distribution Lines Ichiro Sumitani / Toshiko Kurosawa TOKYO ELECTRIC POWER COMPANY 4-1 Egasaki-Cho, Tsurumi-Ku, Yokohama, 230-8510JAPAN Tel : +81 45 585 8561 Fax

More information

Ageing Deterioration of Silicone Rubber Polymer Insulator under Salt Water Dip Wheel Test

Ageing Deterioration of Silicone Rubber Polymer Insulator under Salt Water Dip Wheel Test Ageing Deterioration of Silicone Rubber Polymer Insulator under Salt Water Dip Wheel Test J. Grasaesom, S. Thong-om, W. Payakcho and B. Marungsri* Abstract This paper presents the experimental results

More information

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Substation Insulators (63 kv- 400 kv)

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Substation Insulators (63 kv- 400 kv) Islamic Republic of Iran Vice Presidency for Strategic Planning and Supervision General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Substation Insulators

More information

Analysis of Leakage Current to Predict Insulator Flashover Using Artificial Neural Network

Analysis of Leakage Current to Predict Insulator Flashover Using Artificial Neural Network Journal of Computer Science 7 (2): 167-172, 2011 ISSN 1549-3636 2011 Science Publications Analysis of Leakage Current to Predict Insulator Flashover Using Artificial Neural Network 1 N. Narmadhai and 2

More information

Research methodology for the life evaluation of Hollow polymer insulators for High Voltage Applications

Research methodology for the life evaluation of Hollow polymer insulators for High Voltage Applications 16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 687 Research methodology for the life evaluation of Hollow polymer insulators for High Voltage Applications 1. S.Farook, Research scholar,

More information

DL/T Translated English of Chinese Standard: DL/T

DL/T Translated English of Chinese Standard: DL/T Translated English of Chinese Standard: DL/T627-2012 www.chinesestandard.net Sales@ChineseStandard.net GB ELECTRIC POWER INDUSTRY STANDARD OF THE PEOPLE S REPUBLIC OF CHINA ICS 29.080.10 K 48 Reference

More information

Effect of pollution severity and dry band location on the flashover characteristics of silicone rubber surfaces

Effect of pollution severity and dry band location on the flashover characteristics of silicone rubber surfaces DOI 10.1007/s00202-016-0473-3 ORIGINAL PAPER Effect of pollution severity and dry band location on the flashover characteristics of silicone rubber surfaces Arshad 1 A. Nekahi 1 S. G. McMeekin 1 M. Farzaneh

More information

Effect of pollution severity and dry band location on the flashover characteristics of silicone rubber surfaces

Effect of pollution severity and dry band location on the flashover characteristics of silicone rubber surfaces Electr Eng (2017) 99:1053 1063 DOI 10.1007/s00202-016-0473-3 ORIGINAL PAPER Effect of pollution severity and dry band location on the flashover characteristics of silicone rubber surfaces Arshad 1 A. Nekahi

More information

C Pollution measurement based on DDG method for different type s of insulator profile

C Pollution measurement based on DDG method for different type s of insulator profile 21, rue d'artois, F-75008 Paris http://www.cigre.org C4-401 Session 2004 CIGRÉ Pollution measurement based on DDG method for different type s of insulator profile M.R.Shariati *, A.R.Moradian, M.R.Ghaemi,

More information

Electrical Field Simulation for Different Cases of Polymer Insulators Using FEM

Electrical Field Simulation for Different Cases of Polymer Insulators Using FEM J. Basic. Appl. Sci. Res., 2(10)10203-10208, 2012 2012, TextRoad Publication ISSN 2090-4304 Journal of Basic and Applied Scientific Research www.textroad.com Electrical Field Simulation for Different Cases

More information

CO 2 Cleaning and Its Effectiveness in Cleaning Energized Medium-Voltage Equipment

CO 2 Cleaning and Its Effectiveness in Cleaning Energized Medium-Voltage Equipment CO 2 Cleaning and Its Effectiveness in Cleaning Energized Medium-Voltage Equipment Abstract This paper provides an overview of how CO 2 cleaning works on energized electrical equipment. It also presents

More information

Instruction guide Medium Voltage equipment on sites exposed to high humidity and/or heavy pollution. Recommendations for installation and use

Instruction guide Medium Voltage equipment on sites exposed to high humidity and/or heavy pollution. Recommendations for installation and use Medium Voltage equipment on sites exposed to high humidity and/or heavy pollution Recommendations for installation and use Contents Introduction 2 Use of MV equipment 2 Normal service conditions for indoor

More information

Pins Insulator. Composite/Polymers Insulators

Pins Insulator. Composite/Polymers Insulators Composite/Polymers Insulators Electric network in India operates under very harsh environments. Industrial pollution, marshy land, hilly and unfriendly terrain, extreme weather, coastal region etc. make

More information

CONDITION MONITORING OF INSULATORS UNDER POLLUTION ABSTRACT

CONDITION MONITORING OF INSULATORS UNDER POLLUTION ABSTRACT CONDITION MONITORING OF INSULATORS UNDER POLLUTION ABSTRACT Cheap and reliable supply of electrical energy has been identified as an indicator of economic development and social welfare of any modern society.

More information

LIGHTNING IMPULE PERFORMANCE OF POLLUTED MEDIUM VOLTAGE INSULATORS

LIGHTNING IMPULE PERFORMANCE OF POLLUTED MEDIUM VOLTAGE INSULATORS LIGHTNING IMPULE PERFORMANCE OF POLLUTED MEDIUM VOLTAGE INSULATORS K. L. Chrzan Wroclaw University of Technology, Institute I 7, 50-370 Wroclaw, Poland Email: krystian.chrzan@pwr.wroc.pl Abstract: The

More information

PS2: Lifetime management, deterioration and ageing of substation equipment

PS2: Lifetime management, deterioration and ageing of substation equipment PS2: Lifetime management, deterioration and ageing of substation equipment Ageing and deterioration of composite post insulators exposed to high electric field in 220 kv and 400 kv switchyards in Swedish

More information

An Investigation Into The Methodology To Develop An Insulator Pollution Severity Application Map For South Africa

An Investigation Into The Methodology To Develop An Insulator Pollution Severity Application Map For South Africa > REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 1 An Investigation Into The Methodology To Develop An Insulator Pollution Severity Application Map For South Africa

More information

INSULATION, ASSET AND WILDLIFE PROTECTION Steve Parker, Business Development

INSULATION, ASSET AND WILDLIFE PROTECTION Steve Parker, Business Development INSULATION, ASSET AND WILDLIFE PROTECTION Steve Parker, Business Development MARKET FORCES THAT INFLUENCE RAYCHEM SALES PUBLIC UTILITY COMMISSIONS (System Reliability) SALES US FISH & WILDLIFE (Avian Electrocutions)

More information

Outdoor High Voltage Non-Ceramic Insulators

Outdoor High Voltage Non-Ceramic Insulators Outdoor High Voltage Non-Ceramic Insulators V.P. Karthika 1, P. Anitha 2, A. Hearty Rugesh 3 1 Teaching Fellow, 2 Assistant Professor, 3 UG Student 1, 2, 3 Department of EEE, Anna University, Thoothukudi

More information

Chemical analysis of insulator contaminants and Reliability improvement of T&D line for smart operation of grid under chemically polluted environment

Chemical analysis of insulator contaminants and Reliability improvement of T&D line for smart operation of grid under chemically polluted environment Chennai and Dr.MGR University Second International Conference on Sustainable Energy and Intelligent System (SEISCON 2011), Dr. M.G.R. University, Maduravoyal, Chennai, Tamil Nadu, India. July. 20-22, 2011.

More information

IEC Oil Filled & SF 6 Gas Current Transformers

IEC Oil Filled & SF 6 Gas Current Transformers g IEC Oil Filled & SF 6 Gas Current Transformers 72.5kV - 550kV (325kV - 1550kV BIL) with Primary Plus TM Pre-engineered solution set that digitizes XD GE primary equipment and provides factory installed

More information

ESDD MEASUREMENTS IN THE POWER SYSTEM OF CRETE

ESDD MEASUREMENTS IN THE POWER SYSTEM OF CRETE ESDD MEASUREMENTS IN THE POWER SYSTEM OF CRETE Dionisios PYLARINOS Consultant, Hellenic Electricity Distribution Network Operator S.A., Greece dpylarinos@yahoo.com Kiriakos SIDERAKIS Assistant Professor,

More information

Prediction of flashover voltage of non-ceramic insulators under contaminated conditions

Prediction of flashover voltage of non-ceramic insulators under contaminated conditions Prediction of flashover voltage of non-ceramic insulators under contaminated conditions S. Venkataraman and R. S. Gorur Department of Electrical Engineering Arizona State University Tempe, AZ, USA ABSTRACT

More information

Standard. Extra High Voltage (EHV) Post Insulators Standard R Version 1.0, June Tasmanian Networks Pty Ltd (ABN )

Standard. Extra High Voltage (EHV) Post Insulators Standard R Version 1.0, June Tasmanian Networks Pty Ltd (ABN ) Standard Extra High Voltage (EHV) Post Insulators Standard R574184 Version 1.0, June 2018 Tasmanian Networks Pty Ltd (ABN 24 167 357 299) Authorisations Action Name and title Date Prepared by Michael Verrier,

More information

Experimental analysis of hydrophobic characteristics of Silicone rubber (SiR) insulators under different climatic conditions

Experimental analysis of hydrophobic characteristics of Silicone rubber (SiR) insulators under different climatic conditions International Journal of Physical Sciences Vol. 7(47), pp. 6162-6168, 16 December, 2012 Available online at http://www.academicjournals.org/ijps DOI: 10.5897/IJPS12.508 ISSN 1992-1950 2012 Academic Journals

More information

Electric field analysis of 132kV EPDM insulator and correlation with ageing features

Electric field analysis of 132kV EPDM insulator and correlation with ageing features 2013 Electrical Insulation Conference, Ottawa, Ontario, Canada, 2 to 5 June 2013 Electric field analysis of 132kV EPDM insulator and correlation with ageing features Antonios Tzimas, Christos Zachariades

More information

fire Charcoat Charcoat IC Passive Protection

fire Charcoat Charcoat IC Passive Protection Charcoat fire Protection Passive insulator protection Coating for the protection of pollution flashover on exterior and interior high voltage insulators Charcoat IC General information CharCoat IC is a

More information

Energy Division Insulators

Energy Division  Insulators Energy Division http://energy.tycoelectronics.com Insulators R Insulators Tyco Electronics Energy Division covers a wide range of polymeric, hybrid and porcelain insulators. For decades all these products

More information

INVESTIGATION OF THE AGING CHARACTERISTICS OF CST TERMINATION MADE OF SILICONE RUBBER AT CONTAMINATION AREA

INVESTIGATION OF THE AGING CHARACTERISTICS OF CST TERMINATION MADE OF SILICONE RUBBER AT CONTAMINATION AREA INVESTIGATION OF THE AGING CHARACTERISTICS OF CST TERMINATION MADE OF SILICONE RUBBER AT CONTAMINATION AREA Tatsuya NAKAMURA, Chubu Electric Power Co. Inc., JAPAN, Nakamura.Tatsuya@chuden.co.jp Yoshihide

More information

BEHAVIOUR OF NANO SIO 2 FILLED SILICONE RUBBER NANOCOMPOSITESS

BEHAVIOUR OF NANO SIO 2 FILLED SILICONE RUBBER NANOCOMPOSITESS International Journal of Mechanical Engineering and Technology (IJMET) Volume 9, Issue 12, December 2018, pp. 575 584, Article ID: IJMET_09_12_0600 Available online at http://www.ia aeme.com/ijmet/issues.asp?jtype=ijmet&vtype=

More information

Investigation on the Process of Dry Ice Cleaning Insulators

Investigation on the Process of Dry Ice Cleaning Insulators IOP Conference Series: Materials Science and Engineering PAPER OPEN ACCESS Investigation on the Process of Dry Ice Cleaning Insulators To cite this article: Junwei Chen et al 2018 IOP Conf. Ser.: Mater.

More information

Quantitative assessment of the local leakage current in PV modules for degradation prediction

Quantitative assessment of the local leakage current in PV modules for degradation prediction Presented at the 31 st European PV Solar Energy Conference and Exhibition, 14-19 September 15, Hamburg, Germany Quantitative assessment of the local leakage current in PV modules for degradation prediction

More information

SILICONE RUBBER INSULATORS WITH NOTCHED SURFACE

SILICONE RUBBER INSULATORS WITH NOTCHED SURFACE SILICONE RUBBER INSULATORS WITH NOTCHED SURFACE K. L. Chrzan Wroclaw University of Technology, Institute I 7, 5-37 Wroclaw, Poland Email: krystian.chrzan@pwr.wroc.pl Abstract: A modification of an insulator

More information

EXPERIMENTAL INVESTIGATION OF EFFECT OF UV RADIATION ON FLASHOVER VOLTAGE OF POLYMERIC INSULATORS WITH AND WITHOUT CONTAMINATION

EXPERIMENTAL INVESTIGATION OF EFFECT OF UV RADIATION ON FLASHOVER VOLTAGE OF POLYMERIC INSULATORS WITH AND WITHOUT CONTAMINATION EXPERIMENTAL INVESTIGATION OF EFFECT OF UV RADIATION ON FLASHOVER VOLTAGE OF POLYMERIC INSULATORS WITH AND WITHOUT CONTAMINATION A. Majzoobi *, I. A. Joneidi, S. Mohajer, H.Mohseni and A. A. Shayegani

More information

International Journal of Mechatronics, Electrical and Computer Technology

International Journal of Mechatronics, Electrical and Computer Technology Effect of Corona Ring on Potential Distribution and Electric Field on Silicon Insulator in Polluted Condition Rasool Feiz Kerendian 1*, Hasan Keshavarz Ziarani 1, Javad Ebrahimi 2 1 Electrical Eng. Dept.,

More information

6C-001 High-Voltage Pin-Type Insulator

6C-001 High-Voltage Pin-Type Insulator DISCLAIMER: This translation may be used for reference purpose only. This English version is not an official translation of the original Japanese document. In cases where any differences occur between

More information

Polymer Cutout Testing Recommendations

Polymer Cutout Testing Recommendations 1 Polymer Cutout Testing Recommendations High Voltage Fuse Subcommittee May 2012 Frank Lambert Recommended Tests 1. Water Diffusion Tests (CAN/CSA 310 09 7.3) 2. DyePenetration (ANSI C29.13 Section 7.3)

More information

Data Sheet 110kV TP123-II Porcelain Insulator Outdoor Termination

Data Sheet 110kV TP123-II Porcelain Insulator Outdoor Termination 3 Data Sheet 110kV TP123-II Porcelain Insulator Outdoor Termination 1 Product Description 3M 110kV TP123-II termination meets requirements of IEC60840 and GB11017.3 standards. The porcelain insulator is

More information

General Requirements. Technical Specifications for Insulators of Transmission Lines

General Requirements. Technical Specifications for Insulators of Transmission Lines Islamic Republic of Iran Vice Presidency for Strategic Planning and Supervision General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Insulators of Transmission

More information

TEMPERED GLASS INSULATORS

TEMPERED GLASS INSULATORS TEMPERED GLASS INSULATORS SUSPENSION-TYPE» Non-conducing support composed of an insulating glass piece and iron fittings allowing other units to be connected in series. A fastening iron fitting is included

More information

Measurement of Leakage Current for Monitoring the Performance of Outdoor Insulators in Polluted Environments

Measurement of Leakage Current for Monitoring the Performance of Outdoor Insulators in Polluted Environments F E A T U R E A R T I C L E Measurement of Leakage Current for Monitoring the Performance of Outdoor Insulators in Polluted Environments Key words: insulators, pollution, leakage current, diagnostic techniques,

More information

Performance Improvement on Water-cooled Cold-Plate

Performance Improvement on Water-cooled Cold-Plate Proceedings of the 4th WSEAS International Conference on Heat and Mass Transfer, Gold Coast, Queensland, Australia, January 17-19, 2007 104 Performance Improvement on Water-cooled Cold-Plate SHYAN-FU CHOU,

More information

Scientific Journal Impact Factor: (ISRA), Impact Factor: 2.114

Scientific Journal Impact Factor: (ISRA), Impact Factor: 2.114 IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY Based Smart Sensor for Condition Monitoring of Overhead Insulators Hamid Naseem, Md. Mamoon Rashid* Lecturer, Department of Electrical

More information

Factors Contributing to Haze Formation and the Influence on Power Equipments External Insulation

Factors Contributing to Haze Formation and the Influence on Power Equipments External Insulation Factors Contributing to Haze Formation and the Influence on Power Equipments External Insulation Zhicheng Zhou 1, Song Gao1, a, Linjun Yang2,b, Yong Liu2, Fengbo Tao1, Long Zhang1 1 Jiangsu Electric Power

More information

Laboratory Investigation on Hydrophobicity and Tracking performance of Field Aged Composite Insulators

Laboratory Investigation on Hydrophobicity and Tracking performance of Field Aged Composite Insulators Laboratory Investigation on Hydrophobicity and Tracking performance of Field Aged Composite Insulators N. Mavrikakis Faculty of Engineering Aristotle University of Thessaloniki nmavrika@auth.gr K. Siderakis

More information

INCLINED PLANE TESTS OF COMPOSITE, SILICONE RUBBER AND COMPOSITE SILICONE RUBBER COATED MATERIALS

INCLINED PLANE TESTS OF COMPOSITE, SILICONE RUBBER AND COMPOSITE SILICONE RUBBER COATED MATERIALS INCLINED PLANE TESTS OF COMPOSITE, SILICONE RUBBER AND COMPOSITE SILICONE RUBBER COATED MATERIALS M N R Baharom 1*, Ian Cotton 1 1 School of Electrical & Electronic Engineering, The University of Manchester,

More information

Lightning impulse (LI) breakdown testing of a rubber-epoxy interface

Lightning impulse (LI) breakdown testing of a rubber-epoxy interface Lightning impulse (LI) breakdown testing of a rubber-epoxy interface Cecilia Forssén, Anna Christerson, Daniel Borg ABB AB Corporate Research, Sweden Abstract The lightning impulse (LI) breakdown strength

More information

A3-110 LONG TERM PERFORMANCE OF POLYMER HOUSED MO-SURGE ARRESTERS

A3-110 LONG TERM PERFORMANCE OF POLYMER HOUSED MO-SURGE ARRESTERS 21, rue d'artois, F-75008 Paris http://www.cigre.org A3-110 Session 2004 CIGRÉ LONG TERM PERFORMANCE OF POLYMER HOUSED MO-SURGE ARRESTERS B. RICHTER*, W. SCHMIDT K. KANNUS, K. LAHTI ABB SWITZERLAND LTD.

More information

SPECIFICATION FOR DISC INSULATORS (Standard Type)

SPECIFICATION FOR DISC INSULATORS (Standard Type) Doc. KPLC1/3CB/TSP/04/015 1 Page 1 of 6 TABLE OF CONTENTS 0.1 Circulation List 0.2 Amendment Record FOREWORD 1. SCOPE 2. REFERENCES 3. TERMS AND DEFINITIONS 4. REQUIREMENTS 5. TESTS AND INSPECTION 6. MARKING,

More information

Study with Magnetic Property Measurement of Amorphous HB1 Material and its Application in Distribution Transformer

Study with Magnetic Property Measurement of Amorphous HB1 Material and its Application in Distribution Transformer Study with Magnetic Property Measurement of Amorphous HB1 Material and its Application in Distribution Transformer Yeong-Hwa Chang a, Chang-Hung Hsu a,b, Ching-Pei Tseng c a Department of Electrical Engineering,

More information

NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators

NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators Version:- 3.1 Date of Issue:- June 2014 Page 1 of 13 NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators 1. Purpose This document is the technical specification for 33kV, 66kV

More information

OUTDOOR insulation is contaminated by natural or industrial

OUTDOOR insulation is contaminated by natural or industrial 466 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 1, JANUARY 2007 Concentrated Discharges and Dry Bands on Polluted Outdoor Insulators Krystian Leonard Chrzan and Federico Moro Abstract This paper

More information

FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE APPLICATIONS

FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE APPLICATIONS FBRE RENFORCED PLASTCS N HGH VOLTAGE APPLCATONS Volker Bergmann, Reinhausen Power Composites GmbH Page 1 OVERVEW 1. ntroduction 2. Hollow core composite insulators and their application 3. Dielectric and

More information

A Superconducting Magnet System for Whole-Body Metabolism Imaging

A Superconducting Magnet System for Whole-Body Metabolism Imaging A Superconducting Magnet System for Whole-Body Metabolism Imaging Q. Wang, Y. Dai, B. Zhao, S. Song, C. Wang, L. Li, J. Cheng, S. Chen, H. Wang, Z. Ni, Y. Li, C. Cui, X. Hu, H. Wang, Y. Lei, K. Chan, L.

More information

TEMPERATURE FIELD SIMULATION RESEARCH ON THE LEAKAGE INDUCTANCE TRANSFORMER

TEMPERATURE FIELD SIMULATION RESEARCH ON THE LEAKAGE INDUCTANCE TRANSFORMER S649 TEMPERATURE FIELD SIMULATION RESEARCH ON THE LEAKAGE INDUCTANCE TRANSFORMER by Li DING a,b, Xiaoying MAN c, Yumin ZHANG a, Hailin CAO b, Xiaohong HAO d, and Weihua XIE a,* a Science and Technology

More information