INSULATOR REQUERIMENTS:

Size: px
Start display at page:

Download "INSULATOR REQUERIMENTS:"

Transcription

1 2017 INMR WORLD CONGRESS SITGES-BARCELONA, INSULATOR REQUERIMENTS: DESIGN CRITERIA, OPERATION PARAMETERS AND STANDARDS REVIEW JAVIER GARCÍA TECHNICAL AND PRODUCTION MANAGER

2 CONTENTS q INTRODUCTION q MECHANICAL CONSIDERATIONS q ELECTRICAL CONSIDERATIONS q SELECTION IN POLLUTED AREAS q POLLUTION TESTS STANDARDS q INSULATORS TESTING STATIONS q INSULATORS CORROSION q OPERATION PARAMETERS q ESTIMATED END OF LIFE q CONCLUSIONS Page 2

3 INTRODUCTION In the market, it could be found many different types of insulators for OHTL: - Glass or porcelain string insulators, - Long-rog insulators, - Composite insulators. Inside of each insulator type there is a wide range of: - Designs, - Qualities, - Materials, - Prices. Besides the market offers different alternatives to improve the performance of the insulator on polluted areas: - Different profiles: Antipollution, Open-profile, Outerib - Silicone coated insulators. -, 3 Page 3 \

4 INTRODUCTION What is the best material? What is the best design for a particular environment? What criteria could be taken into account in the selection of the material?, What parameter could be taken into account for service evaluation? How to estimate the end of life of the insulator? THERE IS NO SIMPLE ANSWER TO THESE QUESTIONS. But it is possible, at least, to establish the different steps to be considered for evaluation and comparison of the different solutions. INSULATOR SELECTION OPERATIONS PARAMETERS END OF LIFE STUDIES 4 Page 4 \

5 MECHANICAL CONSIDERATIONS Loss of leakage distance Consequences of a mechanical failure Conductor fall This depends on the design of the insulator. Specified Mechanical Load (SML) > 2 x maximum working load IEC & IEC Mechanical test, such as Type & sample test. IEC stablishes the mechanical residual test methods and acceptance criteria for glass or porcelain string insulators with the dielectric broken part. FUTURE WORK: IEC ongoing revision: Include mechanical residual test, like a type test. 5 Page 5 \

6 ELECTRICAL CONSIDERATIONS Arcing distance Creepage distance Insulator diameter Shed inclination / Shed diameter / Shed spacing impulse withstand/ flashover and dry power frequency characteristics IEC recommends the associated withstand voltages with the highest voltage for the equipment 6 Page 6 \

7 SELECTION IN POLLUTED AREAS Last edition of series IEC TS has developed new techniques for the selection and dimensioning of high voltage insulators in polluted areas. AIM Determinate the most efficient insulation Three approaches recommend to select suitable insulators based on system requirements and environmental conditions: Approach 1: Use past experience Approach 2: Measure and test Approach 3: Measure and design 1 st step. Determination of SPS (Site Pollution Severity) From ESDD & NSDD for type A pollution From SES (Site Equivalent Salinity) for type B pollution 2 nd step. Determination of the Unified Specific Creepage Distance (USCD) reference. The applicability of each approach depends on available data, time and economics involved in the project. 7 Page 7 \

8 SELECTION IN POLLUTED AREAS Choice of profile glass and porcelain insulators Different types of insulators and even different positions of the same insulator type may accumulate pollution at different rates in the same environment. In addition, variations in the nature of the pollutant may make some shapes of insulators more effective than others. IEC TS Table 1 shows a brief summary of the principal advantages and disadvantages of the main profile types with respect to pollution performance. 8 Page 8 \

9 SELECTION IN POLLUTED AREAS Profile suitability glass and porcelain insulators IEC IEC TS Tables 2 & 3 give simple merit values for porcelain and glass insulator profiles. 9 Page 9 \

10 SELECTION IN POLLUTED AREAS Choice of profile glass and porcelain insulators IEC TS & IEC TS give profiles parameters to take into account for glass and porcelain, and polymer insulators respectively: Alternating sheds and shed overhang; Creepage distance versus clearances; Minimum distance between sheds; Spacing versus shed overhang; Shed angle; Creepage factor. 10 Page 10 \

11 POLLUTION TESTS STANDARDS IEC IEC Pollution tests on glass and porcelain insulators on a laboratory could be carried out for two main objectives: To obtain information about the pollution performance of insulators (comparison of different insulator types/profiles) To check the performance in a configuration as close as possible to the in-service one. Two categories of pollution test methods are recommended: Salt fog method, in which the insulators are subjected to a defined pollution degree. Solid layer method, in which a fairly uniform layer of a defined solid pollution is deposited on the insulators surface. 11 Page 11 \

12 POLLUTION TESTS STANDARDS IEC IEC61245 IMPORTANT: These IEC laboratory standardized pollution test methods are not applicable for: composite (polymeric) or RTV-coated insulators. A proposal for a test method for artificially polluted polymer insulators i s covered by the recent CIGRE TB Page 12 \ In the case of naturally polluted insulators removed from the service, a recent CIGRE TB 691 (WG D1.44) Pollution Test of Naturally and Artificially contaminated insulators summarizes the recent experience with so-called rapid flashover test methods: Rapid Flashover Test (RFO, based on IEC solid layer test). Quick Flashover (QF, based on IEC salt fog test).

13 INSULATORS TESTING STATIONS Many variable environmental parameters which influence an insulator s behavior over its lifetime are difficult to simulate artificially and, moreover, to accelerate. Thus, the validity of laboratory tests is often questioned as the procedures adopted may not take into account significant factors which would be encountered in service or others may be over-emphazised. The evaluation of insulator performance in naturally polluted outdoor test stations is becoming more important and popular - Involving a longer test duration. Requiring care in the correct interpretation of the test data. 13 Page 13 \ + The results tend to be accepted with more confidence. It is also a good tool for new insulation technologies, in which there is yet no technical or normative specifications for its testing or characterization.

14 INSULATORS TESTING STATIONS - Goals To compare the performance of insulators of different design. To compare the performance of insulators from different manufacturers. To dimension insulators for a particular environment or application. To examine the behavior of insulators of different dielectric materials. To compare the performance of insulators in different orientations. To explore the effects of specific parameters, such as profile geometries or insulators diameters. To identify possible weaknesses or failure mechanisms of an insulator design. To estimate the life expectancy of various insulators. To serve as a qualification test for potential suppliers. To establish the effectiveness and life of insulator treatments, such as washing, greasing, silicone rubber coating, shed extenders, etc. To assess the performance of other outdoor equipment insulation, such as transformer bushings, surge arresters, cable terminations, etc. La Granja Insulators tests - Permanent insulator research station at Martigues 14 Page 14 \

15 INSULATORS TESTING STATIONS 4 types Research station Simplified, on-line station Monitored: Leakage current activity Climatic effects and Pollution severity are usually Inspection: Visual examination Hydrophobicity In-service test structure Mobile test stations 15 Page 15 \

16 INSULATORS CORROSION Chapter 26 IEC standardizes the minimum average coating mass for the metal fitting of the insulators: 600g/m2 (85µm). This value could increase until 140µm for insulators to be installed on very high corrosion areas. This permits to increase the estimated end of life. Zinc thickness vs. service live 16 Page 16 \

17 INSULATORS PIN CORROSION The zinc sleeve is galvanically positive and has a large potential difference from iron. It works like a sacrificial electrode at the cement boundary where the current flows. Pin without zinc sleeve on high corrosion area a8er several years in service FUTURE WORK: IEC ongoing revision : Include Zinc sleeve test similar to current mentioned on IEC (DC suspension insulators). Bonded area Z i n c purity IEC requirements 17 Page 17 \ Improved requirements 80% 95% 99,8% 99.95% Zinc sleeve posi1on

18 OPERATION PARAMETERS DATABASE Type / Sub-type of string; Type of insulation: Glass, porcelain, composite, coated glass, etc. Sub-type of insulator: Standard profile, pollution profile Number of insulators per string; Insulation manufacturer; Insulator traceability data (Production order, production date ) Standard; Installation year; Silicone manufacture / applicator; Estimated end of life Degradation environment: Normal, hard and very hard. MAINTENANCE INDICATORS Number of faults Insulator breakage rate Washing frequency - MAINTENANCE DECISIONS - REPLACEMENT OF THE INSULATION - COMPARISON OF THE DIFFERENT TYPES OF MATERIALS, PROFILES AND MANUFACTURERS QUALITY. 18 Page 18 \

19 ESTIMATED END OF LIFE GLASS AND PORCELAIN INSULATORS (1) Balanced design parameter Choice of material Control / Mastering of quality & manufacturing processes required to ensure high long term reliability This document stablishes a testing sequence with a number of nondestructive tests as: Visual tests (e.g. degree of corrosion), Dimensional test, Thermal test, Thermal-mechanical tests. These first series of tests are followed by destructive mechanical tests. 19 Page 19 \

20 ESTIMATED END OF LIFE GLASS AND PORCELAIN INSULATORS (2) A probability diagram based on normal distribution is used to analyze the failing load test results and compare with several reference scenarios The failing load characteristics are represented by: A dashed insulators sample tested when new. A solid line insulators as-received from the line. A dashed/dotted line insulators submitted to the Thermal-Mechanical Test (TMP-test) The SFL (Specified Failing Load) solid vertical line. Example: reference scenario F1 The reductions in strength are not representative of good quality products. Age and TMP-test have only negligible influence on good products. 20 Page 20 \

21 ESTIMATED END OF LIFE COMPOSITE INSULATORS Different methods, philosophies and tools are describe. They enable a conclusion regarding the residual lifetime of composite insulators of the same age and design family. The document also gives guidelines in case of a failure investigation, a unit recognized as high risk, and the evaluation of units for research. Recommended sequence of tes1ng 21 Page 21 \

22 CONCLUSIONS The selection of the insulator type is not a simple job, especially if the insulator will be installed in a high polluted area. Numerous documentations (IEC Standards, CIGRE Technical Brochures, papers ) are available to help on the selection of the most appropriate insulator, on the monitoring of the behavior in operation and on the determination of the estimated end of life. Different solutions are available to improve the insulator performance on high corrosion areas. Several factors must be taken into account on the insulator type selection: More effective design/material; Maintenance costs: Inspection cost, cleaning cost, replacement costs, Expected service breakage rate to be guaranteed/certified by the supplier; Severity of consequences in case of failure (mechanical breakage, electrical failure, ); Expected end of life. 22 Page 22 \

23 2017 INMR WORLD CONGRESS SITGES-BARCELONA, THANK YOU FOR YOUR ATTENTION! JAVIER GARCÍA TECHNICAL AND PRODUCTION MANAGER

Cigré WG C Topics: The selection of insulators with respect to polluted conditions

Cigré WG C Topics: The selection of insulators with respect to polluted conditions Cigré Guide for the selection of insulators with respect to contamination conditions Chris Engelbrecht: Convener Topics: The selection of insulators with respect to polluted conditions Present practise

More information

POLLUTION PERFORMANCE OF SILICONE AND EPDM INSULATOR PROFILES

POLLUTION PERFORMANCE OF SILICONE AND EPDM INSULATOR PROFILES Clive LUMB 22/09/05 Originally presented to CIGRE C4.3.03, submitted to 36-WG11 to illustrate: Importance of insulating length Importance of worst case and best case testing of composites. 36-WG11/Paris/216

More information

Composite Insulator Components

Composite Insulator Components Composite Insulator Components Composite insulator components A composite insulator is made of at least two insulating parts a core and housing. It is equipped with end fittings. Core. The core is the

More information

Polluted Outdoor Insulators Maintenance and Washing

Polluted Outdoor Insulators Maintenance and Washing Polluted Outdoor Insulators Maintenance and Washing Ali Naderian, PhD, PEng, SM IEEE Toronto, Canada February 2018 ali.naderian@ieee.org 1 برگزار کنندگان ایکهربا سامانه تجهیزات صنعت برق ایران کارشناسان

More information

Comments on Document from Richard Martin, Canada

Comments on Document from Richard Martin, Canada Comments on Document 60815-1 from Richard Martin, Canada Please find the comments on the Acrobat document Nuremberg/235a. The commented document contains only the pages where there are some comments or

More information

GROUP A. Polymeric Insulators.

GROUP A. Polymeric Insulators. GROUP A Polymeric Insulators PYUNGIL Bldg., 1475-10, Gwanyang 2-dong, Dongan-gu, Anyang-si, Gyeonggi-do, 431-808, Korea Tel : 82-31-420-6650~3 FAX : 82-31-424-7300 www.pyungil.com Silicone Railway

More information

Predicting Contamination Flashover of Insulators: Successes and Shortcomings of Tests and Simulations

Predicting Contamination Flashover of Insulators: Successes and Shortcomings of Tests and Simulations Predicting Contamination Flashover of Insulators: Successes and Shortcomings of Tests and Simulations Ravi S. Gorur and S. Venkataraman (Ph. D Student), Arizona State University Perhaps no single area

More information

HIGH VOLTAGE INSULATORS. By JP Holtzhausen. Glass. Bushings & hollow core insulators. Cap & pin insulators

HIGH VOLTAGE INSULATORS. By JP Holtzhausen. Glass. Bushings & hollow core insulators. Cap & pin insulators HIGH VOLTAGE INSULATORS By JP Holtzhausen The principal dielectric used on overhead power lines is air at atmospheric pressure. The air, surrounding the bare high voltage aluminium or steel- cored aluminium

More information

Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various Pollution Conditions at Costal Regions

Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various Pollution Conditions at Costal Regions Volume 114 No. 9 217, 1-9 ISSN: 1311-88 (printed version); ISSN: 1314-3395 (on-line version) url: http://www.ijpam.eu ijpam.eu Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various

More information

Effect of UV-Rays and Salt Contamination on 33kV Silicon Composite Insulators

Effect of UV-Rays and Salt Contamination on 33kV Silicon Composite Insulators IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 11, Issue 6 Ver. II (Nov. Dec. 2016), PP 45-55 www.iosrjournals.org Effect of UV-Rays and

More information

Energy Division Insulators

Energy Division  Insulators Energy Division http://energy.tycoelectronics.com Insulators R Insulators Tyco Electronics Energy Division covers a wide range of polymeric, hybrid and porcelain insulators. For decades all these products

More information

COMPARISON OF THE SPECIFIC SURFACE CONDUCTIVITY AND ESDD APPROACHES TO ASSESSMENT OF SALT DEPOSITS ON NATURALLY POLLUTED INSULATORS. 1.

COMPARISON OF THE SPECIFIC SURFACE CONDUCTIVITY AND ESDD APPROACHES TO ASSESSMENT OF SALT DEPOSITS ON NATURALLY POLLUTED INSULATORS. 1. E. A. Solomonik 36-WG11/Nberg/158 19/06/03 L. L. Vladimirsky, E. A. Solomonik HVDC Power Transmission Research Institute (NIIPT) COMPARISON OF THE SPECIFIC SURFACE CONDUCTIVITY AND ESDD APPROACHES TO ASSESSMENT

More information

Vijendra Singh Parihar 1, Prof. Anil Kumar Kori 2 1

Vijendra Singh Parihar 1, Prof. Anil Kumar Kori 2 1 Effects of Creepage distance on Leakage Current of 220kV Long Rod Insulators at Different Severity Level of Salt Contamination Vijendra Singh Parihar 1, Prof. Anil Kumar Kori 2 1 PG Student 2 Associate

More information

Selection between indoor or outdoor DC yards D. WU*, U. ÅSTRÖM, L. ARÉVALO, R. MONTAÑO, B. JACOBSON ABB HVDC SWEDEN

Selection between indoor or outdoor DC yards D. WU*, U. ÅSTRÖM, L. ARÉVALO, R. MONTAÑO, B. JACOBSON ABB HVDC SWEDEN 21, rue d Artois, F-75008 PARIS B3-115 CIGRE 2014 http : //www.cigre.org Selection between indoor or outdoor DC yards D. WU*, U. ÅSTRÖM, L. ARÉVALO, R. MONTAÑO, B. JACOBSON ABB HVDC SWEDEN SUMMARY In an

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION IEC/TS 60815-2 TECHNICAL SPECIFICATION Edition 1.0 2008-10 Selection and dimensioning of high-voltage insulators intended for use in polluted conditions Part 2: Ceramic and glass insulators for a.c. systems

More information

CHAPTER 6 HIGH VOLTAGE ELECTRICAL TESTING RESULTS

CHAPTER 6 HIGH VOLTAGE ELECTRICAL TESTING RESULTS CHAPTER 6 HIGH VOLTAGE ELECTRICAL TESTING RESULTS 6.1 Introduction An electrical porcelain insulator plays an eminent role in electrical power system. As the insulators have high resistance path so it

More information

Development of Composite Line Spacers for Distribution Lines

Development of Composite Line Spacers for Distribution Lines Development of Composite Line Spacers for Distribution Lines Ichiro Sumitani / Toshiko Kurosawa TOKYO ELECTRIC POWER COMPANY 4-1 Egasaki-Cho, Tsurumi-Ku, Yokohama, 230-8510JAPAN Tel : +81 45 585 8561 Fax

More information

Artificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester

Artificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester Artificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester W. Payakcho, J. Grasaesom, S. Thong-om and B. Marungsri* Abstract This paper presents the experimental results

More information

Sediver toughened glass insulators for HVAC applications. Experts & Pioneers USA

Sediver toughened glass insulators for HVAC applications. Experts & Pioneers USA Sediver toughened glass insulators for HVAC applications Experts & Pioneers USA Sediver, Experts and Pioneers in insulation technology This catalog presents a selection of the Sediver toughened glass insulator

More information

Performance investigation of composite and RTV SIR coated insulators at a coastal test station

Performance investigation of composite and RTV SIR coated insulators at a coastal test station Performance investigation of composite and RTV SIR coated insulators at a coastal test station K. Siderakis High Voltage Laboratory, Technological and Educational Institute of Crete D. Pylarinos High Voltage

More information

Research methodology for the life evaluation of Hollow polymer insulators for High Voltage Applications

Research methodology for the life evaluation of Hollow polymer insulators for High Voltage Applications 16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 687 Research methodology for the life evaluation of Hollow polymer insulators for High Voltage Applications 1. S.Farook, Research scholar,

More information

Data Sheet 110kV TP123-II Porcelain Insulator Outdoor Termination

Data Sheet 110kV TP123-II Porcelain Insulator Outdoor Termination 3 Data Sheet 110kV TP123-II Porcelain Insulator Outdoor Termination 1 Product Description 3M 110kV TP123-II termination meets requirements of IEC60840 and GB11017.3 standards. The porcelain insulator is

More information

Polymer Insulators and Coatings in the Cretan Power System. The Transmission Line Case

Polymer Insulators and Coatings in the Cretan Power System. The Transmission Line Case Polymer Insulators and Coatings in the Cretan Power System. The Transmission Line Case D. Pylarinos Hellenic Electricity Distribution Network Operator dpylarinos@yahoo.com K. Siderakis Technological Educational

More information

INSULATORS. Industry photo: should be a the same image as larger industry photo. Either a different crop or different angle.

INSULATORS. Industry photo: should be a the same image as larger industry photo. Either a different crop or different angle. Industry photo: should be a the same image as larger industry photo. Either a different crop or different angle. Human photo. Can be environmental/ documentaty style or portrait of engineer. industry photo.

More information

Mitigating Contamination Related Issues on T&D Equipment. Lily Hoyer Simon Chan

Mitigating Contamination Related Issues on T&D Equipment. Lily Hoyer Simon Chan Mitigating Contamination Related Issues on T&D Equipment Lily Hoyer Simon Chan Substation Insulator Pollution Contamination Management PRESENTED BY LILY HOYER T&D ASSET MANAGEMENT ENMAX POWER CORPERATION

More information

fire Charcoat Charcoat IC Passive Protection

fire Charcoat Charcoat IC Passive Protection Charcoat fire Protection Passive insulator protection Coating for the protection of pollution flashover on exterior and interior high voltage insulators Charcoat IC General information CharCoat IC is a

More information

Effect of Metal Ring on the Field Distribution of Outdoor Polymeric Insulator

Effect of Metal Ring on the Field Distribution of Outdoor Polymeric Insulator Effect of Metal Ring on the Field Distribution of Outdoor Polymeric Insulator Veeresh A G Meenakshendra A Khamitkar MTech(Power System Engineering) MTech(Power System Engineering) SDM College Of Engineering

More information

Technical Specification for. Insulators. Part 1. Insulators for High and Extra-High Voltage Overhead Lines

Technical Specification for. Insulators. Part 1. Insulators for High and Extra-High Voltage Overhead Lines Page: 1 / 18 for Insulators Part 1 Insulators for High and Extra-High Voltage Overhead Lines 1.2 Cap-and-pin insulators made of pre-stressed glass This technical specification is valid for the business

More information

ENGINEERING SPECIFICATION EE SPEC

ENGINEERING SPECIFICATION EE SPEC /. Company Directive ENGINEERING SPECIFICATION EE SPEC : 84/1 Relating to Surge Arresters EE SPEC : 84/1 20 December 2013-1 of 7 - IMPLEMENTATION PLAN Introduction This document defines the surge arresters

More information

Panagiotis Charalampidis

Panagiotis Charalampidis Textured Insulators for Overhead Lines and Substations I. INTRODUCTION Panagiotis Charalampidis High Voltage Energy Systems Group, School of Engineering, Cardiff University, The Parade, Cardiff CF24 3AA,

More information

Pins Insulator. Composite/Polymers Insulators

Pins Insulator. Composite/Polymers Insulators Composite/Polymers Insulators Electric network in India operates under very harsh environments. Industrial pollution, marshy land, hilly and unfriendly terrain, extreme weather, coastal region etc. make

More information

PERFORMANCE ANALYSIS OF OVERHEAD PORCELAIN INSULATOR UNDER DIFFERENT CONTAMINATIONS

PERFORMANCE ANALYSIS OF OVERHEAD PORCELAIN INSULATOR UNDER DIFFERENT CONTAMINATIONS International Journal of Mechanical Engineering and Technology (IJMET) Volume 8, Issue 10, October 2017, pp. 241 245, Article ID: IJMET_08_10_028 Available online at http://www.iaeme.com/ijmet/issues.asp?jtype=ijmet&vtype=8&itype=10

More information

Different Characteristics of Artificially Polluted High Voltage Composite Insulators

Different Characteristics of Artificially Polluted High Voltage Composite Insulators Different Characteristics of Artificially Polluted High Voltage Composite Insulators Farhad Shahnia 1 and Ghasem Ahrabian 2 1 Eastern Azarbayjan Electric Power Distribution Company, Tabriz, Iran 2 Faculty

More information

Evaluation Test Procedures for Distribution Crossarms. Southeastern Electric Exchange November, 2018

Evaluation Test Procedures for Distribution Crossarms. Southeastern Electric Exchange November, 2018 Evaluation Test Procedures for Distribution Crossarms Southeastern Electric Exchange November, 2018 What: Research, Testing and Applications Center in the School of Electrical & Computer Engineering at

More information

COMPARATIVE LABORATORY PERFORMANCE CHARACTERISATION OF SILICONE RUBBER TEXTURED INSULATORS

COMPARATIVE LABORATORY PERFORMANCE CHARACTERISATION OF SILICONE RUBBER TEXTURED INSULATORS COMPARATIVE LABORATORY PERFORMANCE CHARACTERISATION OF SILICONE RUBBER TEXTURED INSULATORS BY ADNAN SALAMA KRZMA B.SC., M.SC., ELECTRICAL ENGINEERING Thesis submitted to Cardiff University In candidature

More information

Failure of a suspension or tension insulator

Failure of a suspension or tension insulator Failure of a suspension or tension insulator Abstract:Failure of a suspension or tension insulator is clearly something that every utility or insulator manufacturer wishes would never occur. However, it

More information

DL/T Translated English of Chinese Standard: DL/T

DL/T Translated English of Chinese Standard: DL/T Translated English of Chinese Standard: DL/T627-2012 www.chinesestandard.net Sales@ChineseStandard.net GB ELECTRIC POWER INDUSTRY STANDARD OF THE PEOPLE S REPUBLIC OF CHINA ICS 29.080.10 K 48 Reference

More information

Station Post Insulators (SPI), an Emerging Application for Composite Hollow Core Insulators PETER STAHL

Station Post Insulators (SPI), an Emerging Application for Composite Hollow Core Insulators PETER STAHL Station Post Insulators (SPI), an Emerging Application for Composite Hollow Core Insulators PETER STAHL Composite Hollow Core Station Post Insulators (SPI) Peter Stahl, July 2015 Applications for composite

More information

TRANSMISSION NEW PROJECTS DEPARTMENT TRANSMISSION LINES TOWER DESIGN AND SPECIFICATIONS SECTION ATHENS - GREECE SPECIFICATION TR-1

TRANSMISSION NEW PROJECTS DEPARTMENT TRANSMISSION LINES TOWER DESIGN AND SPECIFICATIONS SECTION ATHENS - GREECE SPECIFICATION TR-1 I NDEPENDE N T POWER TR ANSM ISSION OP ER AT O R S.A. TRANSMISSION NEW PROJECTS DEPARTMENT TRANSMISSION LINES TOWER DESIGN AND SPECIFICATIONS SECTION ATHENS - GREECE SPECIFICATION TR-1 STRING INSULATOR

More information

CS type composite silicone insulators up to 750 kv overhead lines for all pollution of the atmosphere levels

CS type composite silicone insulators up to 750 kv overhead lines for all pollution of the atmosphere levels Climate test equipment. Allows to perform test in various temperature and humidity conditions. CS type composite silicone insulators up to overhead lines for all pollution of the atmosphere levels Insulators

More information

094: 2000 CEB STANDARD. MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA

094: 2000 CEB STANDARD. MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA 094: 2000 CEB STANDARD MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA Specification for MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEB Standard

More information

FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE APPLICATIONS

FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE APPLICATIONS FBRE RENFORCED PLASTCS N HGH VOLTAGE APPLCATONS Volker Bergmann, Reinhausen Power Composites GmbH Page 1 OVERVEW 1. ntroduction 2. Hollow core composite insulators and their application 3. Dielectric and

More information

INSULATION, ASSET AND WILDLIFE PROTECTION Steve Parker, Business Development

INSULATION, ASSET AND WILDLIFE PROTECTION Steve Parker, Business Development INSULATION, ASSET AND WILDLIFE PROTECTION Steve Parker, Business Development MARKET FORCES THAT INFLUENCE RAYCHEM SALES PUBLIC UTILITY COMMISSIONS (System Reliability) SALES US FISH & WILDLIFE (Avian Electrocutions)

More information

ESDD MEASUREMENTS IN THE POWER SYSTEM OF CRETE

ESDD MEASUREMENTS IN THE POWER SYSTEM OF CRETE ESDD MEASUREMENTS IN THE POWER SYSTEM OF CRETE Dionisios PYLARINOS Consultant, Hellenic Electricity Distribution Network Operator S.A., Greece dpylarinos@yahoo.com Kiriakos SIDERAKIS Assistant Professor,

More information

APEC 2016 Component Level Safety Certification in Systems- IEC /UL1577. MARK CANTRELL Senior Applications Engineer

APEC 2016 Component Level Safety Certification in Systems- IEC /UL1577. MARK CANTRELL Senior Applications Engineer APEC 2016 Component Level Safety Certification in Systems- IEC60747-17/UL1577 MARK CANTRELL Senior Applications Engineer 3/20/2016 Agenda What is safety isolation Isolation Concepts Regulatory Landscape

More information

New designed XLPE-insulated cables substituting paper-insulated pipe type cables

New designed XLPE-insulated cables substituting paper-insulated pipe type cables MODERN CABLE SYSTEMS IN STEEL PIPES New designed XLPE-insulated cables substituting paper-insulated pipe type cables Volker AUE, Nexans Deutschland Industries, Germany, Volker.Aue@nexans.com Wilfried ROSEBROCK,

More information

Transmission Silicone Insulators Line Post 69 kv to 230 kv

Transmission Silicone Insulators Line Post 69 kv to 230 kv K-LINE INSULATORS LIMITED Catalogue T-LP Transmission Silicone Insulators Line Post 69 kv to 230 kv ISO9001 SAI GLOBAL FILE No. 000117 Transmission Silicone Insulators Line Post Today transmission lines

More information

Laboratory Investigation on Hydrophobicity and Tracking performance of Field Aged Composite Insulators

Laboratory Investigation on Hydrophobicity and Tracking performance of Field Aged Composite Insulators Laboratory Investigation on Hydrophobicity and Tracking performance of Field Aged Composite Insulators N. Mavrikakis Faculty of Engineering Aristotle University of Thessaloniki nmavrika@auth.gr K. Siderakis

More information

TEMPERED GLASS INSULATORS

TEMPERED GLASS INSULATORS TEMPERED GLASS INSULATORS SUSPENSION-TYPE» Non-conducing support composed of an insulating glass piece and iron fittings allowing other units to be connected in series. A fastening iron fitting is included

More information

ESDD PREDICTION OF OUTDOOR POLYMER INSULATORS. Abdelrahman Khaled

ESDD PREDICTION OF OUTDOOR POLYMER INSULATORS. Abdelrahman Khaled ESDD PREDICTION OF OUTDOOR POLYMER INSULATORS by Abdelrahman Khaled A Thesis Presented to the Faculty of the American University of Sharjah College of Engineering in Partial Fulfillment of the Requirements

More information

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Substation Insulators (63 kv- 400 kv)

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Substation Insulators (63 kv- 400 kv) Islamic Republic of Iran Vice Presidency for Strategic Planning and Supervision General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Substation Insulators

More information

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 220, 132 & 66 COMPOSITE SOLIDCORE STATION POST INSULATORS GETCO/E/2,1,6

More information

B2-00. SPECIAL REPORT FOR SC B2 (Overhead Lines) V. NAIDOO J. IGLESIAS S. ANSORGE. Special Reporters

B2-00. SPECIAL REPORT FOR SC B2 (Overhead Lines) V. NAIDOO J. IGLESIAS S. ANSORGE. Special Reporters CIGRE 2016 B2-00 SPECIAL REPORT FOR SC B2 (Overhead Lines) V. NAIDOO J. IGLESIAS S. ANSORGE Special Reporters Introduction Study Committee B2 covers the design, construction and operation of overhead lines.

More information

NPS/001/008 Technical Specification for Gapless Metal Oxide Surge Arresters

NPS/001/008 Technical Specification for Gapless Metal Oxide Surge Arresters Version:- 5.0 Date of Issue:- October 2017 Page 1 of 18 NPS/001/008 Technical Specification for Gapless Metal Oxide Surge Arresters 1. Purpose The purpose of this document is to detail the technical requirements

More information

ILMOS Insulator Leakage Current Monitor

ILMOS Insulator Leakage Current Monitor ILMOS Insulator Leakage Current Monitor Author: Eugenio Concha G Psptechnologies Inc. econcha@psptechnologies.com 1) Introduction increasing the leakage length of the insulators in the most vulnerable

More information

NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators

NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators Version:- 3.1 Date of Issue:- June 2014 Page 1 of 13 NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators 1. Purpose This document is the technical specification for 33kV, 66kV

More information

CONDITION ASSESSMENT OF A FIELD-AGED 150 kv HTV SIR SUSPENSION INSULATOR FOLLOWING FLASHOVER

CONDITION ASSESSMENT OF A FIELD-AGED 150 kv HTV SIR SUSPENSION INSULATOR FOLLOWING FLASHOVER The 19 th International Symposium on High Voltage Engineering, Pilsen, Czech Republic, August, 23 28, 2015 CONDITION ASSESSMENT OF A FIELD-AGED 150 kv HTV SIR SUSPENSION INSULATOR FOLLOWING FLASHOVER N.

More information

Risk assessment of pollution on a 66kV composite insulator using ANSYS

Risk assessment of pollution on a 66kV composite insulator using ANSYS Risk assessment of pollution on a 66kV composite insulator using ANSYS Ms. N H M Netravati 1, Mrs. Sunitha N.S 2, Dr.Shivakumara Aradhya R.S. 3, Dr. K.N Ravi 4 M.Tech. student 1, Assistant Professor 2,

More information

Comparative Investigation of Silicone Rubber Composite and RTV Coated Glass Insulators Installed in Coastal Overhead Transmission Lines

Comparative Investigation of Silicone Rubber Composite and RTV Coated Glass Insulators Installed in Coastal Overhead Transmission Lines Comparative Investigation of Silicone Rubber Composite and RTV Coated Glass Insulators Installed in Coastal Overhead Transmission Lines Key words: glass insulators, RTV coated, leakage current, silicone

More information

A-PDF PPT TO PDF DEMO: Purchase from to remove the watermark

A-PDF PPT TO PDF DEMO: Purchase from   to remove the watermark EMERGING TECHNOLOGIES SILIDRIL - Polymeric Coating & SHRIJI - CONDUCTIVE SILICON GEL By: Surat Prestech Pvt. Limited Prepared By Mr. Nitin Oza, M.E. & Dr. Rafael Mier, PhD. A-PDF PPT TO PDF DEMO: Purchase

More information

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH SPECIFICATIONS FOR LOAD BREAK SWITCH This specification is property of SEC and subject to change or modification without any notice TABLE OF CONTENTS 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE CODES

More information

SPECIFICATION FOR 11 & 33kV COMPOSITE INSULATORS Part 1: Pin Type

SPECIFICATION FOR 11 & 33kV COMPOSITE INSULATORS Part 1: Pin Type Doc. KPLC1/3CB/TSP/04/017/1 1 Page 1 of 7 TABLE OF CONTENTS 0.1 Circulation List 0.2 Amendment Record FOREWORD 1. SCOPE 2. REFERENCES 3. TERMS AND DEFINITIONS 4. REQUIREMENTS 5. TESTS AND INSPECTION 6.

More information

Data Sheet 110kV TD123II dry type outdoor termination

Data Sheet 110kV TD123II dry type outdoor termination 3 Data Sheet 110kV TD123II dry type outdoor termination 1. Product Description: 3M 110kV TD123II dry type outdoor termination meets requirement of test and product according to IEC60840 and GB11017.3,

More information

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008 Revisions Notes Changed note Date 1 (A) Changed template 09 / 07 / 2008 2 Changed template. Clause 12.5.4.1 hot-rolled steel added. Clause 12.5.4.2, 12.5.2.4, 12.5.3.4, 12.5.4.4, 12.5.5.4, 12.5.6.4, 12.5.7.4

More information

C Pollution measurement based on DDG method for different type s of insulator profile

C Pollution measurement based on DDG method for different type s of insulator profile 21, rue d'artois, F-75008 Paris http://www.cigre.org C4-401 Session 2004 CIGRÉ Pollution measurement based on DDG method for different type s of insulator profile M.R.Shariati *, A.R.Moradian, M.R.Ghaemi,

More information

Si-COAT 570 RTV Silicone HVIC. Reliability & Beyond. Seminar Presentation

Si-COAT 570 RTV Silicone HVIC. Reliability & Beyond. Seminar Presentation Si-COAT 570 RTV Silicone HVIC Reliability & Beyond Seminar Presentation Overview Background & industry pressures Early validation of Si-COAT HVIC The science of Si-COAT Q&A Si-COAT HVIC : The Background

More information

INCLINED PLANE TESTS OF COMPOSITE, SILICONE RUBBER AND COMPOSITE SILICONE RUBBER COATED MATERIALS

INCLINED PLANE TESTS OF COMPOSITE, SILICONE RUBBER AND COMPOSITE SILICONE RUBBER COATED MATERIALS INCLINED PLANE TESTS OF COMPOSITE, SILICONE RUBBER AND COMPOSITE SILICONE RUBBER COATED MATERIALS M N R Baharom 1*, Ian Cotton 1 1 School of Electrical & Electronic Engineering, The University of Manchester,

More information

General Requirements. Technical Specifications for Insulators of Transmission Lines

General Requirements. Technical Specifications for Insulators of Transmission Lines Islamic Republic of Iran Vice Presidency for Strategic Planning and Supervision General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Insulators of Transmission

More information

A3-110 LONG TERM PERFORMANCE OF POLYMER HOUSED MO-SURGE ARRESTERS

A3-110 LONG TERM PERFORMANCE OF POLYMER HOUSED MO-SURGE ARRESTERS 21, rue d'artois, F-75008 Paris http://www.cigre.org A3-110 Session 2004 CIGRÉ LONG TERM PERFORMANCE OF POLYMER HOUSED MO-SURGE ARRESTERS B. RICHTER*, W. SCHMIDT K. KANNUS, K. LAHTI ABB SWITZERLAND LTD.

More information

Reprinted from the Proceedings of the 2001 IEEE/PES Transmission and Distribution Conference and Exposition, Atlanta, Georgia.

Reprinted from the Proceedings of the 2001 IEEE/PES Transmission and Distribution Conference and Exposition, Atlanta, Georgia. Copyright 21 IEEE. Reprinted from the Proceedings of the 21 IEEE/PES Transmission and Distribution Conference and Exposition, Atlanta, Georgia. This material is posted here with permission of the IEEE.

More information

Electric field analysis of 132kV EPDM insulator and correlation with ageing features

Electric field analysis of 132kV EPDM insulator and correlation with ageing features 2013 Electrical Insulation Conference, Ottawa, Ontario, Canada, 2 to 5 June 2013 Electric field analysis of 132kV EPDM insulator and correlation with ageing features Antonios Tzimas, Christos Zachariades

More information

9KV/18KV METAL OXIDE LIGHTNING ARRESTORS WITHOUT GAPS WITH STANDARD NOMINAL DISCHARGE CURRENT 5KA

9KV/18KV METAL OXIDE LIGHTNING ARRESTORS WITHOUT GAPS WITH STANDARD NOMINAL DISCHARGE CURRENT 5KA 9KV/18KV METAL OXIDE LIGHTNING ARRESTORS WITHOUT GAPS WITH STANDARD NOMINAL DISCHARGE CURRENT 5KA Technical specification for 9KV/18KV 5KA Metal oxide Lightning Arrestors without Gap. ----------------------------------------------------------------------------------------------------------------

More information

NPS/002/017 Technical Specification for 66 kv and 132 kv Cable Accessories

NPS/002/017 Technical Specification for 66 kv and 132 kv Cable Accessories Version:- 4.0 Date of Issue:- October 2016 Page 1 of 21 NPS/002/017 Technical Specification for 66 kv and 132 kv Cable Accessories 1. Purpose The purpose of this document is to detail the technical requirements

More information

Composite insulators. Features. Sicat 8WL3068, 8WL3078 and 8WL3088 for overhead contact line systems. siemens.com/rail-electrification

Composite insulators. Features. Sicat 8WL3068, 8WL3078 and 8WL3088 for overhead contact line systems. siemens.com/rail-electrification Composite insulators Sicat 8WL3068, 8WL3078 and 8WL3088 for overhead contact line systems siemens.com/rail-electrification The Sicat 8WL3068, 8WL3078 and 8WL3088 type silicone composite insulators in accordance

More information

6C-001 High-Voltage Pin-Type Insulator

6C-001 High-Voltage Pin-Type Insulator DISCLAIMER: This translation may be used for reference purpose only. This English version is not an official translation of the original Japanese document. In cases where any differences occur between

More information

MAY-16 REV B2

MAY-16 REV B2 Product Specification 108-20025 06-MAY-16 REV B2 The product described in this document has not been fully tested to ensure conformance to the requirements outlined below. Therefore, TE Connectivity (TE)

More information

SPECIFICATION FOR POLYMER DISC INSULATOR

SPECIFICATION FOR POLYMER DISC INSULATOR SPECIFICATION FOR POLYMER DISC INSULATOR Scope : This specification cover the design, manufacturing, testing at manufacturers works, transport to site, insurance, unloading & storage of 11 KV & 33 KV Polymer

More information

EXPERIMENTAL INVESTIGATION OF EFFECT OF UV RADIATION ON FLASHOVER VOLTAGE OF POLYMERIC INSULATORS WITH AND WITHOUT CONTAMINATION

EXPERIMENTAL INVESTIGATION OF EFFECT OF UV RADIATION ON FLASHOVER VOLTAGE OF POLYMERIC INSULATORS WITH AND WITHOUT CONTAMINATION EXPERIMENTAL INVESTIGATION OF EFFECT OF UV RADIATION ON FLASHOVER VOLTAGE OF POLYMERIC INSULATORS WITH AND WITHOUT CONTAMINATION A. Majzoobi *, I. A. Joneidi, S. Mohajer, H.Mohseni and A. A. Shayegani

More information

12-SDMS-01 Rev.02 SPECIFICATIONS FOR

12-SDMS-01 Rev.02 SPECIFICATIONS FOR 12-SDMS-01 Rev.02 SPECIFICATIONS FOR CABLE JOINTS, TERMINATIONS, AND ACCESSORIES UP TO 36 KV This specification is property of SEC and is subject to change or modification without any notice. TABLE OF

More information

FOREWORD SCOPE NORMATIVE REFERENCES DEFINITIONS REQUIREMENTS... 4

FOREWORD SCOPE NORMATIVE REFERENCES DEFINITIONS REQUIREMENTS... 4 INSULATORS VERTICAL & HORIZONTAL MOUNTING - SPECIFICATION Page 1 of 20 Table of Contents FOREWORD... 2 1. SCOPE... 2 2. NORMATIVE REFERENCES... 3 3. DEFINITIONS... 4 4. REQUIREMENTS... 4 4.1. SERVICE CONDITIONS...

More information

Prototype Test Report ANSI C29.17 Quadri*Sil Line Post Insulators 2.5 Dia. Rod HPS Silicone rubber R

Prototype Test Report ANSI C29.17 Quadri*Sil Line Post Insulators 2.5 Dia. Rod HPS Silicone rubber R PAGE: 1 Test Requests: R18-01-03 Report Number: R18-01-03 Prototype Test Report ANSI C29.17 Quadri*Sil Line Post Insulators 2.5 Dia. Rod HPS Silicone rubber R18-01-03 Introduction: Sample Quadri*Sil line

More information

Journal of Operation and Automation in Power Engineering. Vol. 1, No. 2, Summer & Fall 2013, Pages:

Journal of Operation and Automation in Power Engineering. Vol. 1, No. 2, Summer & Fall 2013, Pages: Journal of Operation and Automation in Power Engineering Vol. 1, No. 2, Summer & Fall 2013, Pages: 74-83 http://journals.uma.ac.ir/joape Impact of Pollution Location on Time and Frequency Characteristics

More information

Pollution Performance of HVDC SiR Insulators at Extra Heavy Pollution Conditions

Pollution Performance of HVDC SiR Insulators at Extra Heavy Pollution Conditions IEEE Transactions on Dielectrics and Electrical Insulation Vol. 21, No. 2; April 2014 721 Pollution Performance of HVDC SiR Insulators at Extra Heavy Pollution Conditions A. Abbasi, A. Shayegani and K.

More information

Study on the dc flashover performance of standard suspension insulator with ringshaped non-uniform pollution

Study on the dc flashover performance of standard suspension insulator with ringshaped non-uniform pollution High Voltage Research Article Study on the dc flashover performance of standard suspension insulator with ringshaped non-uniform pollution ISSN 2397-7264 Received on 28th June 2017 Revised 1st October

More information

CERTIFICATE OF ACCREDITATION

CERTIFICATE OF ACCREDITATION CERTIFICATE OF ACCREDITATION In terms of section 22(2)(b) of the Accreditation for Conformity Assessment, Calibration and Good Laboratory Practice Act, 2006 (Act 19 of 2006), read with sections 23(1),

More information

Mapping HV Insulators Pollution in the Mediterranean Island of Crete

Mapping HV Insulators Pollution in the Mediterranean Island of Crete 1 Mapping HV Insulators Pollution in the Mediterranean Island of Crete D. Pylarinos, K. Siderakis, N. Mavrikakis, E. Thalassinakis Abstract The reliability of High Voltage insulators is rather important

More information

37-SDMS-01 REV. 03 SPECIFICATIONS FOR

37-SDMS-01 REV. 03 SPECIFICATIONS FOR 37-SDMS-01 REV. 03 SPECIFICATIONS FOR LOW VOLTAGE MOLDED CASE CIRCUIT BREAKERS FOR SERVICE CONNECTIONS This specification is property of SEC and subject to change or modification without any notice CLAUSE

More information

CONTENTS. IEC Ed. 2 /CDV IEC 2 36B/ /CDV 36B-MT10/Nuremberg3/60

CONTENTS. IEC Ed. 2 /CDV IEC 2 36B/ /CDV 36B-MT10/Nuremberg3/60 IEC 61109 Ed. 2 /CDV IEC 2 36B/ /CDV 36B-MT10/Nuremberg3/60 CONTENTS FOREWORD...4 INTRODUCTION...5 1 Scope and object...7 2 Normative references...7 3 Definitions...8 4 Abbreviations...9 5 Identification...9

More information

Potential and E-Field Calculation Along an Ice- Covered Composite Insulator with Finite Element Method

Potential and E-Field Calculation Along an Ice- Covered Composite Insulator with Finite Element Method Potential and E-Field Calculation Along an Ice- Covered Composite Insulator with Finite Element Method Qing Yang, Caixin Sun, Wenxia Sima, Lichun Shu, Ji Yang, Jianlin Hu The Key Laboratory of High Voltage

More information

Specification for Polymer Disc Insulator

Specification for Polymer Disc Insulator Specification for Polymer Disc Insulator Scope : This specification cover the design, manufacturing, testing at manufacturers works, transport to site, insurance, storage of 11 KV & 33 KV Polymer Disc

More information

Accreditation Scope by Certification Test Order

Accreditation Scope by Certification Test Order Organization NEMA MW 1000 NEMA RE-2 Section 4.11 ASTM D149 ASTM D150 ASTM D256 ASTM D257 ASTM D495 ASTM D570 ASTM D635 ASTM D638 ASTM D790 ASTM D882 ASTM D1653 ASTM D1676 ASTM D1822 ASTM D1830 ASTM D1876

More information

A Study of Critical Positive Impulse Flashover of 24 kv Contaminated Insulators

A Study of Critical Positive Impulse Flashover of 24 kv Contaminated Insulators The 5 th PSU-UNS International Conference on Engineering and 467 Technology (ICET-2011), Phuket, May 2-3, 2011 Prince of Songkla University, Faculty of Engineering Hat Yai, Songkhla, Thailand 90112 Study

More information

Effect of Some of Climatic Conditions in the Performance of Outdoor HV Silicone Rubber Insulators

Effect of Some of Climatic Conditions in the Performance of Outdoor HV Silicone Rubber Insulators Effect of Some of Climatic Conditions in the Performance of Outdoor HV Silicone Rubber Insulators By Abdelbaset Shaban Nekeb Thesis submitted to Cardiff University in candidature for the degree of DOCTOR

More information

The Effect of Severity and Location of Pollution on Leakage Current Characteristics of Porcelain Insulators under Different Humidity Condition

The Effect of Severity and Location of Pollution on Leakage Current Characteristics of Porcelain Insulators under Different Humidity Condition The Effect of Severity and Location of Pollution on Leakage Current Characteristics of Porcelain Insulators under Different Humidity Condition Ali Azizi Tousi Mohammad Mirzaie Babol University of Technology,

More information

33-SDMS-02 SPECIFICATIONS FOR

33-SDMS-02 SPECIFICATIONS FOR SPECIFICATIONS FOR MV AUTOMATIC LINE SECTIONLIZER UP TO 36 KV This specification is property of SEC and subject to change or modification without any notice TABLE OF CONTENTS SECTION T I T L E PAGE NO.

More information

GSCH004 Rev /10/2016

GSCH004 Rev /10/2016 GLOBAL STANDARD Page 1 of 28 INSULATORS Elaborated by Verified by Approved by High Voltage SDC HV SDC - M. A. Caballero HV SDC - J.A. Lama Head of NCS - F. Giammanco Global I&N NT/NCS HV SDC - T. González

More information

Study on Pollution Flashover Performance of Short Samples of Composite Insulators Intended for ±800 kv UHV DC

Study on Pollution Flashover Performance of Short Samples of Composite Insulators Intended for ±800 kv UHV DC 1192 Study on Pollution Flashover Performance of Short Samples of Composite Insulators Intended for ±800 kv UHV DC Xingliang Jiang, Jihe Yuan, Zhijin Zhang, Jianlin Hu and Lichun Shu Chongqing University

More information

Midsun HVIC silicone is not affected by UV light, temperature, corrosive environments, or ATH pitting from dry band arcing.

Midsun HVIC silicone is not affected by UV light, temperature, corrosive environments, or ATH pitting from dry band arcing. Midsun 570 Midsun HVIC silicone is not affected by UV light, temperature, corrosive environments, or ATH pitting from dry band arcing. Because the coating is highly water repellent, contaminant s cannot

More information