Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various Pollution Conditions at Costal Regions
|
|
- Jared Conley
- 6 years ago
- Views:
Transcription
1 Volume 114 No , 1-9 ISSN: (printed version); ISSN: (on-line version) url: ijpam.eu Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various Pollution Conditions at Costal Regions N.Sumathi 1 R.Srinivasa Rao 2 V.S.N.K.Chaitanya 3 1 EEE Department, University College of Engineering (A), JNTU Kakinada, Andhra Pradesh, India. eeesuma@gmail.com 2 EEE Department, University College of Engineering (A), JNTU Kakinada, Andhra Pradesh, India. srinivas.jntueee@gmail.com 3 EEE Department, University College of Engineering (A), JNTU Kakinada, Andhra Pradesh, India. chaitu824@gmail.com Abstract Pollution on the surface of insulator reduces reliability and quality of power system. Due to the pollutions contaminations on the surface of insulator leakage current will increase and breakdown voltage will decrease. In this paper, it is proposed to study experimentally the effect of different types of artificial pollutions on 33 kv outdoor porcelain and polymeric insulators for their performance at Indian coastal regions. The types of pollutants used are sea-salt, cement and urea. The pollutions are made artificially and are sprayed on to the insulator according to IEC 657. After spraying, it was left for 24 hours completely to dry naturally. This process was repeated for seven days till a thick visible layer is formed on the surface of insulator. Electrical tests were performed to measure leakage current and breakdown voltage to predict the effect caused by pollution on the insulators. The experimental results proved that polymeric and porcelain insulators are greatly affected by salt and urea contamination compared to cement contamination. Due to water molecule reabsorbing property of urea maximum leakage currents are high in urea pollutions and salt pollution. It is also proved that compared to porcelain, polymer insulators has high breakdown strength. Key Words: Ceramic Insulator; ; dust; Leakage Current (); Polymer Insulator; sea salt; urea pollution 1 Introduction Electrical insulators are used to separate power lines from ground structures and to provide mechanical support to power lines. They are placed at different places like high altitude sites, substations, traction substations, near industrial fields and train roofs. Insulators placed in polluted areas get contaminated uniformly or non-uniformly with local dust, natural dust, bird feces etc. The dust particles on the surface of insulator along with pollutants mix up with moisture, fog, rain and dew and get contaminated. When the insulators are 1
2 energized even at rated voltage leakage current increases gradually degradation takes place on the surface of insulator and finally leads to flashover. Hence pollution accumulation on the surface of insulators reflects the characteristics of insulator [1-4]. In outdoor, pollution distribution on the insulators may be uniform or nonuniform because transmission and distribution lines run along and across the road, factories, sea shores, and fertilizers [5-8]. The main pollutants that affect the properties of insulator are sea-salt, cement and urea [9-1]. The effect of pollution on insulator surface depends on type of material used to make the insulator. Ever since porcelain insulators were used for insulation, transmission and distribution lines. But nowadays these are replaced by polymer silicone insulators especially for ultra high voltages because of their advantages like light weight, hydrophobicity, easy handling and non-breakable [11-12]. In ceramic insulators increase of pollution deposits gradually increases the leakage current and finally it may leads to flashover. While for composite insulators made of polymeric materials, leakage current depends on the surface resistance which depends on hydrophobicity. At polluted conditions these insulators make themselves hydrophobic by transfer of low molecular weight components and hence leakage current does not increase continuously. However in polymeric insulators temporary variations in leakage currents due to pollutions are similar to that for ceramic ones. Standard laboratory tests to evaluate the performance of insulators in outdoor contamination have been developed by IEEE and IEC 657 [13]. Specific pollution tests to evaluate the polymeric insulators performance is under considerations as per IEC [14]. In this paper, an artificial pollution experiments were carried on both 33kV polymer and porcelain insulators each type four specimens, to investigate the influence of pollution on the insulators. The tests were done for three types of pollutions cement, urea and salt. From experimental tests, breakdown voltage and maximum leakage current were recorded. A comparison was made between the porcelain and polymer insulators to predict which type of insulator is more affected by these pollutants. The effect of different contaminations on insulators is also analyzed. The research results are useful to design the insulators operated in severe pollution conditions and can be used as a guide for design of external insulation. 2 Experimental Evaluation 2.1 Geometrical configurations and conditiong of test specimens: The experimental investigations were carried out on 33kV polymer and porcelain insulator specimens for four numbers of each type. The polymeric insulator specimens are named as A, B, C and D whereas porcelain specimens as a, b, c and d. The geometrical configuration of the test specimens are tabulated in Table I. 2
3 Table.I Geometrical configurations S.No Particulars Polymer Porcelain 1 Length of the insulator (mm) Dry Arcing Distance (mm) Creepage Distance(mm) Specific Creepage Distance (mm/kv) Shed Diameter (mm) Number of Sheds Core diameter (mm) Shed Thickness(mm) Shed Spacing (mm) Fig 1. Test Specimens at Polluted Conditions All specimens are cleaned so that all traces of dirt and grease are removed from the surface of insulator. Then insulator is rinsed with de-mineralized (DM) water to clean and free from any grease, and it is dried naturally. Before every subsequent contamination the insulator was washed with DM water to remove all traces of pollution and then dried for 24 hours. Then the insulators were polluted by spraying the contamination on the surface of insulator by spraying method as per IEC 657. The contaminated solution was sprayed on the surface of insulator totally and specimen are left to dry naturally for 24 hours. This process was repeated for seven days till a uniform layer is formed on the surface. Similarly urea and cement contaminations were prepared and sprayed on test specimens as per the above procedure till a pollution layer is deposited. Figures 1a, 1b shows insulator during test under urea condition, 1c, 1d under cement pollution and 1e, 1f under salt pollution. 2.2 Test arrangement and test procedure: Insulator specimen are mounted in vertical position and energized as per the circuit diagram shown in Fig.2. One end of the test specimen is connected to high voltage terminal and the other end connected to ground with a ground clearance of 2 meters. From control panel, voltage is applied in steps and appropriate leakage current is recorded. Voltage is increased until breakdown takes place. 3
4 Fig 2. Experimental setup. 3 Test Results In order to predict the performance of insulators, leakage current and breakdown voltage are measured for all the specimens of polymer and porcelain. 3.1 Measurement of and : Leakage current () and Breakdown voltage () were measured for the following cases: 1. Four specimens of 33kV polymer insulators under dry, salt, cement and urea pollution. 2. Four specimens of 33kV porcelain insulators under dry, salt, cement and urea pollution Measurement of and for 33kV polymer insulators: All 33kV polymeric insulator specimens are conditioned and pollution is applied by spraying method for several days till a thick layer is observed. Then the samples are energized as per the above test procedure. The specimen during test with flashover was shown in Fig 3.Leakage current and breakdown voltage were recorded and tabulated in Table II. and are measured for all the polluted contaminated specimens. Fig.3 Specimen during testing Table II and of 33kV Polymer Insulators Condition A B C D Dry
5 With the help of these test results performance polymer insulator under pollutions were evaluated. Performance characteristics are shown in Fig.4. From Fig 4, for specimen A it is observed that among all pollutions leakage current values are high in salt and cement contamination compared to urea and in specimen B the values are almost same in all contaminations. In case of specimen C values under salt and urea are similar with a little difference but higher compared to cement. For specimen D, values are higher in salt pollution compared to urea and cement, and values of are same in urea and cement contaminations. Leakage current(µa ) Sample A Applied Voltage Lekage current(µa) Sample B Applied Voltage 6 5 Sample C Lekage current(µa) Applied Voltage Fig.4 Performance Characteristics of polymer Insulators This shows that the effect of salt contamination is more on polymer material compared to urea and cement. However the mixture of salt, urea and cement can cause a great increase of leakage current and finally degrades insulator surface and finally leads to breakdown. Because urea is highly soluble in water and it is having a property to reabsorb the water. Hence the presence of carbamide molecules on the surface of insulator when mixed with wet molecules increases leakage current thereby degrading the insulator surface. From Table II, by calculating average breakdown voltage of all specimens, it is observed that among all contaminations breakdown voltage is low in salt and cement compared to urea. This shows that salt and cement molecules degrades the insulator surface fast compared to urea however under urea pollution the leakage currents are higher. From the results of leakage current with respect to applied voltage it is also observed that for polymeric insulators the average leakage current of four specimens is more in urea contamination compared to salt and cement contaminations. In case of individual specimens maximum leakage current for all the specimens is varied in between 38.1 to 51 µa under salt condition. While under cement it is varied between 32 to 53.6 µa and for urea it is 42 to 5.5 µa. Hence it is conclude that the effect of silica SiO2, alumina, sodium chloride, iron and fly ash is more on polymer material which 5
6 affects the characteristics breakdown voltage and it also depends on ionic compounds Measurement of and for 33kV Porcelain insulators: All 33kV porcelain insulator specimens are conditioned and pollution is applied by spraying method for several days till a thick layer is observed. Then the samples are energized as per the above test procedure. Leakage current and breakdown voltage were recorded and tabulated in Table III. Table III and of 33kV Porcelain Insulators a b c d Condition Dry Leakage current(µa) Sample a Leakage current(µa) Sample b Applied Voltage Applied Voltage Leakage current(µa ) Sample c Leakage current(µa) Sampe d Applied Voltage Applied Voltage Fig.5 Performance Characteristics of porcelain Insulators and are measured for all the polluted contaminated specimens. With the help of these test results performance porcelain insulator under pollutions were evaluated. Performance characteristics are shown in Fig.5. From Table III for all the specimens a, b, c, d, it was observed that the average is low in cement and urea contaminations compared to salt. This shows that there is an effect of urea, cement and salt contaminations on the characteristics of porcelain insulators. Hence urea and cement together can cause a great damage to porcelain insulators. From these test results it is concluded that the effect of fertilizers and sea salt is more on porcelain insulators when insulators are located nearer to these pollution sources. Hence from the results, it concluded 6
7 that for porcelain insulators the leakage current is more in urea and salt contaminations compared to cement contamination because the breakdown takes place early in cement pollution compared to salt and urea. 3.2 Test Results comparison for polymer and porcelain insulators: By comparing the characteristics of both polymeric and porcelain insulators in all polluted conditions it observed that the effect of pollution on porcelain insulators is higher compare to polymer insulators. The influence of salt, cement and urea pollution is less in case of polymer compared to porcelain insulators. Based on the experimental data the breakdown voltage of polymer insulators in cement and urea contaminations it is 23% higher than that porcelain insulators, while for salt is 1%. Fig 6 shows the comparison of breakdown voltage at various conditions for both the porcelain and polymer insulators. Among all the pollutions in porcelain insulators the breakdown takes place early in cement contamination compared to salt and urea POLYMER PORCELIAN 12 1 PORCELIAN POLYMER FOV Leakage Current(µA) SALT CEMENT UREA SALT CEMENT UREA Fig.6 Comparision Fig.7 Comparision Fig 7 gives the comparison of leakage current for polymer and porcelain insulators at salt, cement and urea pollution conditions. Under urea contamination leakage current for porcelain insulator is 58% higher the polymer insulators and for salt condition it is 57%. While for cement contamination it is 1%. It is noticed that urea contamination will affect more on the performance of porcelain insulators. From results it is concluded that polymer insulators are able to withstand for higher voltages compared to porcelain in salt and urea contaminations. Further the effect of cement contamination on polymer and porcelain is less. Conclusion The main pollutants found on the surface of insulator under practical conditions are salts, cement and local dust. The characteristics of insulators are dependent on pollutants. In this paper a research has been conducted on polymer and porcelain specimens under different polluted conditions. Leakage current and breakdown voltage under polluted conditions are examined to predict the performance of insulator. Based on the data measured it can be concluded that polluted porcelain insulators have of 57%, 1% and 58% high leakage currents respectively for salt, cement and urea contaminations compared to polymer insulators and among salt, cement and urea pollutions flashover takes place early in cement pollution. The breakdown voltage is high in contaminated areas compared to non-polluted. 7
8 Acknowledgment We would like to gratitude University College of Engineering, JNTU Kakinada for their support in completion of this work. References [1]. H. Terrab, A. Bayadi, Experimental study using design of experiment of pollution layer effect on insulator performance taking into account the presence of dry bands, IEEE Transactions on Dielectric and electrical insulation, Vol. 21, pp , 214. [2]. M.El-A.Slama, A.Beroul and H.Hadi, Influence of the linear Non-uniformity of pollution layer on the insulator flashover under impulse voltage estimation of the effective pollution thickness, IEEE Transactions on Dielectric and electrical insulation, Vol. 18, pp , 211. [3]. R.Boudissa, S.Djafri, A.Haddad, R.Belaicha and R.Bearschi, Effect of insulator shape on surface discharges and flashover under polluted conditions, IEEE Transactions on Dielectric and electrical insulation, Vol. 12, pp , 25. [4]. P.Wilkins, Breakdown voltage of high-voltage insulators with uniform surfce-pollution films, IEE proceedings, Vol. 116, pp , [5]. Zhijin Zhang, Xiaohuan Liu, Xingliang jiang, Jianlin Hu and David Wenzhong Gao, Study on AC flashover performance for different types of porcelain and glass insulators with non-uniform pollution, IEEE Transactions on Power Delivery, Vol. 28, pp , 213. [6]. J.A.Eeir, Road salt on outdoor insulators, IEEE Electrical Insulation Conference, pp , 214. [7]. M.A.Douar, A.Mekhaldi and M.C.Bouzidi, Flashover process and frequency analysis of the leakage current on insulator model under non-uniform pollution conditions, IEEE Transactions on Dielectric and electrical insulation, Vol. 17, pp , 21. [8]. Xingliang Jiang, Shaohua Wang, Zhijin Zhang, Jianlin Hu and Qin Hu, Investigations of breakdown voltage and non-uniform pollution correction of short specimens of composite insulator intended for 8kV UHVDC, IEEE Transactions on Dielectric and electrical insulation, Vol. 18, pp. 71-8, 21. [9]. Kunikazu Izumi and Kenzo Kadotani, Applications of Polymeric Outdoor Insulation in Japan, IEEE Transactions on Dielectric and electrical insulation, Vol. 6, pp , Oct [1]. Reuben Hackam, Outdoor HV Composite Polymeric Insulators, IEEE Transactions on Dielectric and electrical insulation, Vol. 6, pp , [11]. J. F.Hall, History and Bibolography of Polymeric Insulators, IEEE Transactions on Power Delivery, Vol. 8, pp , [12]. T.Kikuhi, S.Nishimura, M.Nagao, KIzumi, Y.Kubota, and M.Sakata, Survey on the Use of Non-Ceramic Composite Insulators, IEEE Transactions on Dielectric and electrical insulation, Vol. 6, pp , [13]. IEC 657: Artificial pollution test on high voltage insulators to be used on AC systems,, [14]. IEC Standard 62217: Polymer insulators for indoor and outdoor use with a nominal voltage >1V-general definitions, test methods and acceptance criteria,
9 9
10 1
HIGH VOLTAGE INSULATORS. By JP Holtzhausen. Glass. Bushings & hollow core insulators. Cap & pin insulators
HIGH VOLTAGE INSULATORS By JP Holtzhausen The principal dielectric used on overhead power lines is air at atmospheric pressure. The air, surrounding the bare high voltage aluminium or steel- cored aluminium
More informationPins Insulator. Composite/Polymers Insulators
Composite/Polymers Insulators Electric network in India operates under very harsh environments. Industrial pollution, marshy land, hilly and unfriendly terrain, extreme weather, coastal region etc. make
More informationStudy on the dc flashover performance of standard suspension insulator with ringshaped non-uniform pollution
High Voltage Research Article Study on the dc flashover performance of standard suspension insulator with ringshaped non-uniform pollution ISSN 2397-7264 Received on 28th June 2017 Revised 1st October
More informationArtificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester
Artificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester W. Payakcho, J. Grasaesom, S. Thong-om and B. Marungsri* Abstract This paper presents the experimental results
More informationInvestigation of leakage current flow through wooden poles structures on overhead distribution system
Proceedings of the 7th WSEAS International Conference on Power Systems, Beijing, China, September 15-17, 2007 120 Investigation of leakage current flow through wooden poles structures on overhead distribution
More informationEnergy Division Insulators
Energy Division http://energy.tycoelectronics.com Insulators R Insulators Tyco Electronics Energy Division covers a wide range of polymeric, hybrid and porcelain insulators. For decades all these products
More informationMidsun HVIC silicone is not affected by UV light, temperature, corrosive environments, or ATH pitting from dry band arcing.
Midsun 570 Midsun HVIC silicone is not affected by UV light, temperature, corrosive environments, or ATH pitting from dry band arcing. Because the coating is highly water repellent, contaminant s cannot
More informationAnalysis of Leakage Current to Predict Insulator Flashover Using Artificial Neural Network
Journal of Computer Science 7 (2): 167-172, 2011 ISSN 1549-3636 2011 Science Publications Analysis of Leakage Current to Predict Insulator Flashover Using Artificial Neural Network 1 N. Narmadhai and 2
More informationPorcelain Insulator Performance under Different Condition of Installation around Aligarh
Porcelain Insulator Performance under Different Condition of Installation around Aligarh Asfar Ali Khan and Ekram Husain Abstract Modern Society is strongly dependent on a reliable power supply. The availability
More informationAPEC 2016 Component Level Safety Certification in Systems- IEC /UL1577. MARK CANTRELL Senior Applications Engineer
APEC 2016 Component Level Safety Certification in Systems- IEC60747-17/UL1577 MARK CANTRELL Senior Applications Engineer 3/20/2016 Agenda What is safety isolation Isolation Concepts Regulatory Landscape
More informationPolymer Cutout Testing Recommendations
1 Polymer Cutout Testing Recommendations High Voltage Fuse Subcommittee May 2012 Frank Lambert Recommended Tests 1. Water Diffusion Tests (CAN/CSA 310 09 7.3) 2. DyePenetration (ANSI C29.13 Section 7.3)
More informationCOASTAL INDIA. Supply & Application of: Epsilon Midsun 570 Gen-4 RTV HVIC (High Voltage Insulator Coating) and
Supply & Application of: Epsilon Midsun 570 Gen-4 RTV HVIC (High Voltage Insulator Coating) and Epsilon Midsun 579 RTV Anti-Corrosion Coating In COASTAL INDIA Supply & Application of 8,000kg of Epsilon
More informationLaboratory Investigation on Hydrophobicity and Tracking performance of Field Aged Composite Insulators
Laboratory Investigation on Hydrophobicity and Tracking performance of Field Aged Composite Insulators N. Mavrikakis Faculty of Engineering Aristotle University of Thessaloniki nmavrika@auth.gr K. Siderakis
More informationMapping HV Insulators Pollution in the Mediterranean Island of Crete
1 Mapping HV Insulators Pollution in the Mediterranean Island of Crete D. Pylarinos, K. Siderakis, N. Mavrikakis, E. Thalassinakis Abstract The reliability of High Voltage insulators is rather important
More informationLaboratory Investigation on Hydrophobicity of New Silicon Rubber Insulator under Different Environmental Conditions
International Journal of Electrical & Computer Sciences IJECS-IJENS Vol: 12 No: 03 1 Laboratory Investigation on Hydrophobicity of New Silicon Rubber Insulator under Different Environmental Conditions
More informationThe Reliability Study of the Statistical Method on Insulator Dimensioning of (U)HVDC Lines with Regard to Pollution Conditions
1 The Reliability Study of the Statistical Method on Insulator Dimensioning of (U)HVDC Lines with Regard to Pollution Conditions Ying Long 1, Yan Xiao 1, Zhiyi Su 2, Dong Wu 3, Urban Astrom 3 Abstract--The
More informationStudy of Pre-polluting Methods on Artificial Icing Flashover Characteristics of Composite Insulators
IWAIS XIII, Andermatt, September 8 to 11, 2009 Study of Pre-polluting Methods on Artificial Icing Flashover Characteristics of Composite Insulators Lichun Shu 1, Xiaolin Li 2, Xingliang Jiang 1, Jianlin
More informationComparative study on field collected samples of aged silicon rubber composite coatings for high voltage insulators
DOI: 10.2478/achi-2013-0009 ACTA CHEMICA IASI, 21_2, 93-106 (2013) Comparative study on field collected samples of aged silicon rubber composite coatings for high voltage insulators I.V. Tudose, 1,4 M.
More informationPolymer Suspension Insulators 69kV to 765kV
CATALOG Polymer Suspension Insulators 69kV to 765kV NGK Locke Polymer Insulators, Inc. Virginia Beach, Virginia, U.S.A. TABLE of CONTENTS Table of Contents... 1 Design Features... 2 Material... 2 Definition
More informationGeneral Requirements. Technical Specifications for Insulators of Transmission Lines
Islamic Republic of Iran Vice Presidency for Strategic Planning and Supervision General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Insulators of Transmission
More informationVolcanic Ash Contamination of High Voltage Insulators
Volcanic Ash Contamination of High Voltage Insulators Revising Insulator Design to Aid the Electrostatic Repulsion of Volcanic Ash EEA Conference & Exhibition 2012, 20-22 June, Auckland Authors: M.J. Mee
More informationInstruction guide Medium Voltage equipment on sites exposed to high humidity and/or heavy pollution. Recommendations for installation and use
Medium Voltage equipment on sites exposed to high humidity and/or heavy pollution Recommendations for installation and use Contents Introduction 2 Use of MV equipment 2 Normal service conditions for indoor
More informationTRANSMISSION & DISTRIBUTION SILICONE INSULATORS InterPhase Spacers 15 kv to 400 kv
K-LINE INSULATORS LIMITED Catalogue TD-IPS TORONTO, ONTARIO, CANADA TRANSMISSION & DISTRIBUTION SILICONE INSULATORS InterPhase Spacers 15 kv to 400 kv ISO9001 SAI GLOBAL FILE No. 000117 Transmission &
More informationDISTRIBUTION SILICONE INSULATORS Deadend / Suspension 15 kv to 69 kv
K-LINE INSULATORS LIMITED TORONTO, ONTARIO, CANADA Catalogue D-DS DISTRIBUTION SILICONE INSULATORS Deadend / Suspension 15 kv to 69 kv ISO9001 SAI GLOBAL FILE No. 000117 Distribution Silicone Insulators
More informationComparative Investigation of Silicone Rubber Composite and RTV Coated Glass Insulators Installed in Coastal Overhead Transmission Lines
Comparative Investigation of Silicone Rubber Composite and RTV Coated Glass Insulators Installed in Coastal Overhead Transmission Lines Key words: glass insulators, RTV coated, leakage current, silicone
More informationInsulating Covers. Insulators: EPBI: Light Weight Polymeric Post Insulator. EPBI: Light Weight Polymeric Stand Off Insulator
Exit Catalogue Return to Contents Energy Division http://energy.tycoelectronics.com Section 6: Insulators & Insulating Covers. Insulators: EPBI: Light Weight Polymeric Post Insulator EPBI: Light Weight
More informationElectric Field and Potential Distribution in a 420 kv Novel Unibody Composite Cross-Arm
4 th Nordic Insulation Symposium on Materials, Components and Diagnostics Electric Field and Potential Distribution in a 4 kv Novel Unibody Composite Cross-Arm Jahangiri, Tohid ; Bak, Claus Leth ; Faria
More informationChemical analysis of insulator contaminants and Reliability improvement of T&D line for smart operation of grid under chemically polluted environment
Chennai and Dr.MGR University Second International Conference on Sustainable Energy and Intelligent System (SEISCON 2011), Dr. M.G.R. University, Maduravoyal, Chennai, Tamil Nadu, India. July. 20-22, 2011.
More informationPolymer Station Post Insulators for 69 to 345 kv Applications
CATALOG 143 Polymer for 69 to 34 kv Applications NGK-Locke Polymer Insulators, Inc. Virginia Beach, Virginia, U.S.A. TABLE of CONTENTS Polymer... 1 Application Guidelines for Polymer Station Posts (SP)...
More informationMeasurement of Leakage Current for Monitoring the Performance of Outdoor Insulators in Polluted Environments
F E A T U R E A R T I C L E Measurement of Leakage Current for Monitoring the Performance of Outdoor Insulators in Polluted Environments Key words: insulators, pollution, leakage current, diagnostic techniques,
More informationSurge arrester 3EB4. with polymeric composite housing for operating aboard traction units
Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited. Offenders
More informationAnalysis of the possibilities of using dielectric foam in the construction of composite high voltage postinsulators
IOP Conference Series: Materials Science and Engineering PAPER OPEN ACCESS Analysis of the possibilities of using dielectric foam in the construction of composite high voltage postinsulators To cite this
More informationYEARS WATER PROOFING AND PERFORMANCE WARRANTY*
502, 5th Floor, Boston House, Suren Road, Behind Cinemax Theatre, Chakala, Andheri (E), Mumbai - 400 093 Office: +91 226787 2100 Fax: +91 22 26848920 www.jotun.in 10 YEARS WATER PROOFING AND PERFORMANCE
More informationIndustrial Coatings: HIGHLY DURABLE, SUPERHYDROPHOBIC AND OLEOPHOBIC. (White Paper) NeverWet LLC
Industrial Coatings: HIGHLY DURABLE, SUPERHYDROPHOBIC AND OLEOPHOBIC (White Paper) NeverWet LLC Background: Metal surfaces have high surface energy, are negatively charged, and hydrophilic as shown by
More informationTHERMAL IMAGE, PARTIAL DISCHARGE AND LEAKAGE CURRENT CORRELATION OF CERAMIC INSULATOR UNDER DIFFERENT CONTAMINATION LEVEL
THERMAL IMAGE, PARTIAL DISCHARGE AND LEAKAGE CURRENT CORRELATION OF CERAMIC INSULATOR UNDER DIFFERENT CONTAMINATION LEVEL Darwison 1.3, Syukri Arief 3, Hairul Abral 2, Ariadi Hazmi 1, M. H. Ahmad 4 and
More informationDr.M.Swaroopa Rani Associate Professor, Civil Engineering Depatrment JNTUK, Kakinada Andhra Pradesh, India
A Study on Compressive Strength of Normal Curing Concrete and Self Curing Concrete by Partial Replacement of Fine Aggregate with Crushed Spent Fire Brick Dr.M.Swaroopa Rani Associate Professor, Civil Engineering
More informationHistory of Electrical Precipitation
History of Electrical Precipitation Date 1600 1745 1824 1878 1885 Significance William Gilbert, English court physician, publishes De Magnete Benjamin Franklin describes the effects of points in drawing
More informationSURGE ARRESTERS kv in silicone shield
SURGE ARRESTERS 10-24 kv in e shield The surge arresters 12 kv produced in Electotechnical Institute Division in Wroclaw (nominal discharge capability 10kA, 8/20µs) are presented on the picture. Advantages
More informationSubstation Bus Design: Current Methods Compared with Field Results
Electrical Transmission and Substation Structures Conference 2009 ASCE 143 Substation Bus Design: Current Methods Compared with Field Results Keith Malmedal Ph.D. P.E. P.Eng. 1 and John Wendelburg P.E.
More informationSTUDY ON MECHANICAL PROPERTIES OF LIGHT TRANSMITTING CONCRETE
International Research Journal of Engineering and Technology (IRJET) e-issn: 239-6 STUDY ON MECHANICAL PROPERTIES OF LIGHT TRANSMITTING CONCRETE B.YAMINI NIRMAL 1, Mr. K.NEHEMIYA 2, Sri.G.GIRI PRASAD 3,
More informationResin impregnated paper bushings. Product information
Resin impregnated paper bushings Product information This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any
More informationROLINX Laminated Busbar. Design Rules Version 01 (12/2015)
ROLINX Laminated Busbar Design Rules Version 01 (12/2015) Content 1. Introduction... 03 7. Features... 13 2. Configuration...03 8. Thermal parameters... 14 3. Products... 04 9. General parameters... 14
More informationThe Next Step In The World Of Transformers
The Next Step In The World Of Transformers Envirotran TM Transformers Set Higher Environmental, Fire Safety and Performance Standards Envirotran TM Transformers Advance the Evolution of Electrical Distribution
More informationDurability Evaluation of Highly Reflective Coating Materials for Roofing
Durability Evaluation of Highly Reflective Coating Materials for Roofing Kenji Motohashi 1 Masataka Tamura 2 ABSTRACT Highly reflective coating materials for roofing (cool roof paints) are becoming popular
More informationOffshore Wind Turbines Power Electronics Design and Reliability Research
Offshore Wind Turbines Power Electronics Design and Reliability Research F. P. McCluskey CALCE/Dept. Of Mechanical Engineering University of Maryland, College Park, MD (301) 405-0279 mcclupa@umd.edu 1
More informationINSULATORS NEW. See page J-4 for more information.
INSULATORS INSULATORS NEW Improved 23613 Dead End/Suspension Insulator Salisbury s Improved 23613 Dead End/Suspension Insulator has aluminum end fittings. These new end fittings create a lightweight product
More informationElectrostatic Precipitators (ESPs)
EVE 402 Air Pollution Generation and Control Chapter #5 Lectures (Part 7) Electrostatic Precipitators (ESPs) The process of electrostatic precipitation involves The ionization of contaminated air flowing
More informationTapes. Reliable. Solar Industry. for the. 3M Tapes for Solar Panel Fabrication
3M Tapes for Solar Panel Fabrication Reliable Tapes for the Solar Industry More than 80 years ago, 3M invented the world s first practical pressure-sensitive tapes. Today, we are a leading manufacturer
More informationSULFATE AND CHLORIDE RESISTANCE PROPERTIES OF PORTLAND CEMENT BLENDS
Proceedings of the 4 th International Conference on Civil Engineering for Sustainable Development (ICCESD 2018), 9~11 February 2018, KUET, Khulna, Bangladesh (ISBN-978-984-34-3502-6) SULFATE AND CHLORIDE
More informationU.V resistance UL Sunlight Resistance. Flame retardant IEC
Cable for underground power distribution and subtransmission. Description Application Underground power distribution and subtransmission. As transformer feeders in substations. In power plants, industrial
More informationSILOXA-TEK 8505 TECHNICAL DATA SHEET
SILOXA-TEK 8505 TECHNICAL DATA SHEET An industrial-grade, water-based, silane/siloxane engineered to reduce water and moisture intrusion, protect concrete from deicing salts and chlorides, and resist staining
More informationTechnical Presentation on Spent Pot lining Management & Red Mud
Technical Presentation on Spent Pot lining Management & Red Mud 0 Bharat Aluminium Company Ltd, Korba & Vedanta limited, Jharsuguda & Lanjigarh OUR PRESENCE 1 Jharsuguda Smelter Capacity 3,615 MW 1.75
More informationPolymer Cutout Evaluation NEETRAC
Polymer Cutout Evaluation NEETRAC Frank C. Lambert Georgia Tech / NEETRAC High Voltage Fuses Subcommittee Calgary, Alberta October 14, 2008 1 NEETRAC Members 2008-2009 1. 3M 2. ABB 3. ACA Conductor Accessories
More informationFeb12 Rev D
Product Specification AMPSEAL* Connectors 108-1329 01Feb12 Rev D 1. SCOPE 1.1. Content This specification covers performance, tests and quality requirements for AMPSEAL* connectors. 1.2. Qualification
More informationBTM BT2K 600. Areas of Use
BTM BT2K 600 Bitumento BT2K 600 is a solvent-free, two-component, elastic, water-based, fiber reinforced, rubber and cement based bitumen waterproofing material. Areas of Use As water and moisture tight
More informationBS 6206 KM BS EN KM 51961
TM TM Welcome to our 2007 brochure. Cervoglass moves into its 5th year of manufacture of conservatory glass units in a wide range of specifications to meet all budgets. New to our product range for 2007
More informationHigh Quality Porcelain Insulators for Transmission Lines
Our Customers World Wide High Quality Porcelain Insulators for Transmission Lines 765kV KEPCO / KOREA Tangjin - Sin Ansomg 735kV H-Q / CANADA Manic - Churchill, James Bay 765kV PGCI / INDIA Kishenpur -
More informationNotes Changed note Date. 1 (A) Changed template 09 / 07 / 2008
Revisions Notes Changed note Date 1 (A) Changed template 09 / 07 / 2008 2 Changed template. Clause 12.5.4.1 hot-rolled steel added. Clause 12.5.4.2, 12.5.2.4, 12.5.3.4, 12.5.4.4, 12.5.5.4, 12.5.6.4, 12.5.7.4
More informationDissolved Gas Analysis of Transformer Oils: Effects of electric arc
Proceedings of the 6th WSEAS International Conference on Power Systems, Lisbon, Portugal, September 22-24, 26 376 Dissolved Gas Analysis of Transformer Oils: Effects of electric arc SUWARNO School of Electrical
More informationThe Role of Inorganic Fillers in Silicone Rubber for Outdoor Insulation Alumina Tri-Hydrate or Silica
F E A T U R E A R T I C L E The Role of Inorganic Fillers in Silicone Rubber for Outdoor Insulation Alumina Tri-Hydrate or Silica Key Words: Silicone rubber, fillers, alumina tri-hydrate, silica, erosion
More informationOverview of Method for Reducing Grounding Resistance of Substation Grounding System
International Symposium on Computers & Informatics (ISCI 2015) Overview of Method for Reducing Grounding Resistance of Substation Grounding System Bin Tang 1, Xu Sun 2, Jiayong Zou 3,a 1 Fujian Provincial
More informationCIGRE 16 BRUGGE Partial Discharge and Dissolved Gas Analysis In bio-degradable transformer oil. The University of New South Wales Australia
CIGRE 16 BRUGGE 2007 Partial Discharge and Dissolved Gas Analysis In bio-degradable transformer oil D. IMAMOVIC *, K.X. LAI, N.A. MUHAMAD, B.T. PHUNG and T.R. BLACKBURN # The University of New South Wales
More informationThe complete guide to transformers and packaged substations
LAND LOGICAL POWER The complete guide to transformers and packaged substations Contents Land Logical Power transformers An introduction to the complete range of Land Logical Power transformers and package
More informationINTRODUCTION AND OVERVIEW OF MANUFACTURING. Manufacturing is Important. Manufacturing - Technologically Important
INTRODUCTION AND OVERVIEW OF MANUFACTURING 1. What is Manufacturing? 2. Materials in Manufacturing 3. Manufacturing Processes 4. Production Systems 5. Organization of the Book Manufacturing is Important
More informationCleaning Before Coating. Presented by Jigar Patel, Senior Process Engineer
Cleaning Before Coating Presented by Jigar Patel, Senior Process Engineer Cleaning Before Coating Influencing factors Failure mechanisms Coating failures Cleaning before coating Analytics and test methods
More informationDATA SHEET. EM1000 Fine Ribbed Electrical Safety Matting, rated to IEC61111:2009 Class 0
DATA SHEET EM1000 Fine Ribbed Electrical Safety Matting, rated to IEC61111:2009 Class 0 Unit 21 Priory Industrial Park Airspeed Road Christchurch Dorset BH23 4HD Tel: 01425 278011 Fax: 01425 278012 www.deltarubber.co.uk
More informationPackaging Technologies for SiC Power Modules
Packaging Technologies for SiC Power Modules Masafumi Horio Yuji Iizuka Yoshinari Ikeda ABSTRACT Wide bandgap materials such as silicon carbide (SiC) and gallium nitride (GaN) are attracting attention
More informationProduct specification
Product specification For capacitor tissue paper, electrolytic paper, cable paper and insulating paper The paper factory SPO was established in June 1828. Our industrial production started with the manufacture
More informationAn XPS and Atomic Force Microscopy Study of the Micro-Wetting Behavior of Water on Pure Chromium* 1
Materials Transactions, Vol. 44, No. 3 (2003) pp. 389 to 395 #2003 The Japan Institute of Metals An XPS and Atomic Force Microscopy Study of the Micro-Wetting Behavior of Water on Pure Chromium* 1 Rongguang
More informationCal-Chip Electronics, Incorporated Thick Film Chip Resistors - RM Series
Thick Film Chip Resistors - RM Series Fixed Chip Resistors manufactured for more compact electronic components and automatic mounting system. These Chip Resistors have electrical stability and mechanical
More informationProduct or Process Modifications Requiring Limited CBTL Retesting to Maintain Safety Certification
Product or Process Modifications Requiring Limited CBTL Retesting to Maintain Safety Certification This document sets forth a uniform approach to maintain the safety certification of products that have,
More informationDiescolith SOL-Silikat
Highly diffusible SOL silicate paint according to DIN 18363 Silica sol silicate base Tribrid formula Variety of applications Highly weather-resistant Highly water-repellent Highly diffusible UV-light-resistant
More informationCONTENTS. IEC Ed. 2 /CDV IEC 2 36B/ /CDV 36B-MT10/Nuremberg3/60
IEC 61109 Ed. 2 /CDV IEC 2 36B/ /CDV 36B-MT10/Nuremberg3/60 CONTENTS FOREWORD...4 INTRODUCTION...5 1 Scope and object...7 2 Normative references...7 3 Definitions...8 4 Abbreviations...9 5 Identification...9
More informationnicrom e l e c t r o n i c
G E N E R A L High Performance Thick Film Resistors C A T A L O G 3 Nicrom Electronic Via Roncaglia CH - 6883 Novazzano SWITZERLAND Phone : ++4 () 9 68 99 86 Fax : ++4 () 9 68 99 86 info@nicrom-electronic.com
More informationWeidmann Electrical Technology. Presenter Thomas A. Prevost, Weidmann-ACTI
Estimation of Insulation Life Based on a Dual Temperature Aging Model Weidmann-ACTI Inc. Fifth Annual Technical Conference Albuquerque, NM Nov. 13-15, 2006 Thomas A. Prevost, Hans Peter Gasser Weidmann
More informationCHAPTER 9. The Uses of Sulphuric Acid
CHAPTER 9 MANUFACTURED SUBSTANCES IN INDUSTRY SULPHURIC ACID The Uses of Sulphuric Acid 175 POLLUTION of Sulphur DIOXIDE Formation of Acid Rain Burning of Sulphur Burning of Sulphur Dioxide 176 Effect
More informationUltra High Barrier Coatings by PECVD
Society of Vacuum Coaters 2014 Technical Conference Presentation Ultra High Barrier Coatings by PECVD John Madocks & Phong Ngo, General Plasma Inc., 546 E. 25 th Street, Tucson, Arizona, USA Abstract Silicon
More informationNPS/002/020 Technical Specification for 11 & 20kV Power Cables
Version:- 3.1 of Issue:- Nov - 09 Page 1 of 11 NPS/002/020 Technical Specification for 11 & 20kV Power Cables 1. Purpose The purpose of this document is to detail Northern Powergrid (the Company) requirements
More informationResearch and Application Study on Accident-Based 3D Power Station Simulation Technology
International Conference on Electromechanical Control Technology and Transportation (ICECTT 2015) Research and Application Study on Accident-Based 3D Power Station Simulation Technology Tie Li, Xiaoming
More informationDeposition of Silica Aluminum Using an Alkali Solution of Fly Ash
2016 International Conference on Materials, Information, Mechanical, Electronic and Computer Engineering (MIMECE 2016) ISBN: 978-1-60595-420-2 Deposition of Silica Aluminum Using an Alkali Solution of
More informationB. Provide liquid-filled secondary substation transformers as indicated on drawings.
SECTION 26 12 13 PART 1 - GENERAL 1.01 WORK INCLUDED A. Comply with the provisions of Sections 26 05 00. B. Provide liquid-filled secondary substation transformers as indicated on drawings. 1.02 RELATED
More informationCompact Substation Design. Kobus Coetzer TGOOD Africa
Compact Substation Design Kobus Coetzer TGOOD Africa 1. 2. 3. 4. TGOOD Electric Compact Substation Design Considerations Project Reference Agenda 1. TGOOD Electric Key Facts Sino German Joint Venture Leading
More informationApplication Note. Capacitor Selection for Switch Mode Power Supply Applications
Application Note AN37-0013 Capacitor Selection for Switch Mode Power Supply Applications 1. Introduction Faced with the availability of multiple capacitor options for use in high reliability SMPS applications,
More informationSediver High Resistivity insulators for HVDC applications
Sediver High Resistivity insulators for HVDC applications USA/Canada 2013 Introduction to Sediver HRTG insulators At the end of the 1950 s Sediver was among the first manufacturers to develop insulators
More informationSPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: -
SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: - 1. SCOPE: - This specification covers 11KV Disc Type & 11KV/ 22KV Pin Type Insulators for 11/22KV H.T. over head power lines. 2. APPLICABLE
More informationInsulator pollution in transmission lines
Insulator pollution in transmission lines Ramos Hernanz, José A. 1, Campayo Martín, José J. 1 Motrico Gogeascoechea, Joseba 1, Zamora Belver, Inmaculada. 2 Departamento de Ingeniería Eléctrica 1 Escuela
More informationThe Release of Base Metals During Acidic Leaching of Fly Ash
The Release of Base Metals During Acidic Leaching of Fly Ash George Kazonich and Ann G. Kim U.S. Department of Energy Federal Energy Technology Center P.O. Box 19 Pittsburgh, PA 153 ABSTRACT Since 199,
More informationStudy on Coefficient of Permeability of Copper slag when admixed with Lime and Cement
IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) e-issn: 2278-1684,p-ISSN: 2320-334X, Volume 7, Issue 6 (Jul. - Aug. 2013), PP 19-25 Study on Coefficient of Permeability of Copper slag when
More informationSEAL & SIGNATURE OF THE TENDERER
MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO. LTD. SCHEDULE - `A' TECHNICAL SPECIFICATION FOR 11 kv & 22 kv A.B. SWITCH. SPECIFICATION NO:RE/II/A.B.SWITCH/2005 INDEX -----------------------------------------------------------------------------------------------------------------------
More informationPART MATERIAL REMARK Metal Case with Pig-tail. Brass (Metal Case) Copper (Pig-tail) Star Contact Copper Silver Plated
1. SCOPE This specification defines the technical requirements of TZ-D series thermal-link with PROFFUSE brand that are produced according to IEC 60691, UL 60691,GB 9816. 2. APPLICABLE STANDARDS IEC 60691,
More informationASTM D7877 Standard Guide for Electronic Methods for Detecting and Locating Leaks in Waterproof Membranes
ASTM D7877 Standard Guide for Electronic Methods for Detecting and Locating Leaks in Waterproof Membranes David Vokey Detec Systems ASTM D5957 Standard Guide for Flood Testing Horizontal Waterproofing
More informationAccelerated Aging and Life Time Prediction for Solar Concentrators
Chart 1 Accelerated Aging and Life Time Prediction for Solar Concentrators CSP Today 2015, Sevilla J. Wette, F. Sutter (DLR) A. Fernandez (CIEMAT) Chart 2 Contents Motivation/Solar mirrors Outdoor testing
More informationCHEMICAL METAL PRE-TREATMENT
Protection upgraded CHEMICAL METAL PRE-TREATMENT Basics and New Developments April 2017 April 18, 2017-1 - AGENDA 1 Basics about Chemical Metal Pre-Treatment 2 Cleaning and Pickling 3 Conversion Coating
More informationTitle: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards
Change History Date Description of Change Pages / Sections Modified Change Approver Initials 6/15/16 Updated division section from 16124 to 2605 - mgl44 13, removed references to other section 10/17/14
More informationChemistry 145 Exam number 4 name 11/19/98 # Faraday s constant is 96,500 c/mole of electrons.
Chemistry 145 Exam number 4 name 11/19/98 # Faraday s constant is 96,500 c/mole of electrons. A.(16) An electrochemical cell is prepared with a strip of manganese metal dipping in to a 1.0 M MnSO 4 solution
More informationMar11 Rev B
Product Specification 108-1163-7 11Mar11 Rev B Inverted Six and Eight Position Surface Mount Shielded Modular Jack Assembly 1. SCOPE 1.1. Content This specification covers performance, tests and quality
More informationCENELEC EN /A1 EUROPEAN STANDARD NORME EUROPEENNE. EUROPÄISCHE NORM October Uncontrolled copy when printed
EUROPEAN STANDARD NORME EUROPEENNE EN 50124-1/A1 EUROPÄISCHE NORM October 2003 ICS 29.080.00; 45.020 English version Railway applications - Insulation coordination Part 1: Basic requirements - Clearances
More informationCar and Counterweight Frames
Car and Counterweight Frames CAR FRAME (SLING) AND PLATFORM COUNTERWEIGHT FRAME Every attempt has been made to ensure that this documentation is as accurate and up-to-date as possible. However, Vertical
More informationFriday, May 29, Update on Testing Medium Voltage Cable and Switchgear Systems
Update on Testing Medium Voltage Cable and Switchgear Systems Friday, May 29, 2015 Presented by: Ashley Harkness Ashley.Harkness@Emerson.com Electrical Reliability Services Value--- When we find the one
More information