PS2: Lifetime management, deterioration and ageing of substation equipment
|
|
- Mitchell Norris
- 5 years ago
- Views:
Transcription
1 PS2: Lifetime management, deterioration and ageing of substation equipment Ageing and deterioration of composite post insulators exposed to high electric field in 220 kv and 400 kv switchyards in Swedish network M. RADOSAVLJEVIC 1, I. GUTMAN 2, C. AHLHOLM 2, P. SIDENVALL 2 1 SVENSKA KRAFTNÄT, 2 STRI SWEDEN SUMMARY The majority of station post insulators in the world are porcelain insulators. However, based on in general positive service experience of line composite insulators, and especially composite apparatus insulators, composite station post insulators are also used on lower scale. However, it is important that the requirements for such insulators to ensure their long-term performance shall be the same as for line/apparatus composite insulators. It is well-known for line composite insulators that it is very important to limit the levels of E-field to avoid permanent corona from the metal parts and water drop corona located on insulator surface. Based on historical use of porcelain post insulators for substations, the need for corona/grading rings is underestimated for composite post insulators. Comprehensive 3D electric field calculations on different composite post insulators (few designs/manufacturers with/without corona/grading rings) at Swedish TSO revealed that in many cases the levels of E-field are well above the internationally accepted criteria. Deviation from these criteria varied depending on the specific design. Due to concern for life time of the exposed to high electric field composite post insulators a comprehensive test program was launched, which included: field inspections using IR/UV cameras and visual inspections and laboratory investigation of some removed from service insulators 220 kv and 400 kv. The laboratory investigations included switching and steep-front electrical tests, evaluation of adhesion, dissection of insulators, etc. The results of inspections/investigations revealed for some insulators weak adhesion between the silicone rubber and fibreglass core, which in combination with too high electric field in some cases led to the punctures of silicone rubber housing in service. Another new type of internal deterioration as a result of combination of weak adhesion and high electric field was revealed. The paper describes in details results of investigations and recommendations for further improvement of representative tests and calculations to be considered by CIGRÉ/IEC. This is to avoid low quality insulators to reach the service. Keyword Composite post insulator, simulation, high voltage, life expectancy, ageing Milan Radosavljevic, Milan.radosavljevic@svk.se 1
2 INTRODUCTION AND GOAL General service experiences of both line and apparatus composite insulators are rather positive at present. This is summarized in few CIGRÉ Technical Brochures [1], [2], [3]. According to [2] based on preliminary and sparse information an exponential increase of installations of line composite insulators can be seen (Figure 1). It is discussed in [1] that if not considering the failures of the first generation of composite insulators their reliability at present can be comparable with the strings of glass insulators. Figure 1. Estimated growth in composite insulator use in AC overhead transmission lines (adopted from [2]). Swedish TSO Svenska kraftnät (Svk) uses apparatus composite insulators with success for a number of years. Field inspection of about 30 silicone rubber circuit breakers performed after years in service did not reveal any significant deterioration and the hydrophobicity of this insulators was still very good (Hydrophobicity Class, HC 1-2, i.e. hydrophobic). This paper concentrates on specific experience with composite station post insulators, which rather recently came into the Swedish network (a few years in service). Even having positive service experience in general, composite insulators in the market can be of rather different quality and the issue of quality is not fully covered by the existing IEC standards relating to such insulators. The basic IEC standard [4] was issued in 2012 and a product standard for station post composite insulators IEC [5] mostly follows this standard. It is well known that it takes about 3-4 years to issue a new standard and it is based on the results of earlier performed research, thus it can be considered that the present standards were developed based on a decade old data. The goal of this paper is to summarise shortly the results of the comprehensive investigation of composite station post insulators including E-field calculations, service inspections and after-service laboratory tests. This is to evaluate the quality of insulators and to identify and highlight the needs for further improvement of the specifications (via CIGRE/IEC work) to prevent insulators with lower quality to reach the network. The comprehensive test program included: E-field calculations performed for 11 types of insulators with/without corona/grading rings and intended for kv Service inspections of insulators under voltage (IR and UV observation techniques) Service inspections of insulators without voltage (close visual observations and hydrophobicity measurements) 2
3 After-service laboratory investigations using IEC standard and specially developed new tests E-FIELD CALCULATIONS It can be concluded that at present there are three main criteria for a composite insulator for the maximum electric field (to prevent corona from the metal parts and water drop corona on surface). These are based on comprehensive research performed by STRI and EPRI independently of each other about 10 years ago [6]. The industry practice is that most of manufacturers and utilities are using similar criteria when accepting a new design. The criteria are listed in Table 1 and have been verified by STRI numerously for more than 30 different insulator designs [7]. Further in this paper the criteria are presented using kv/mm units. Table 1. Criteria for electric field on composite insulators [6]. Part of insulator Criterion [kv/cm] End fitting, grading ring and arcing horn 18 End fitting seal (the so called triple point) 3.5 Sheath of insulator housing 4.2 (max average along 10 mm) The first criterion is for corona from metal, thus applicable on end fittings and hardware (such as yoke, grading ring, arcing horn, etc.) both at HV side and at grounded side. This criterion is slightly more conservative than the CIGRÉ recommendation 2.1 kv/mm [8] because it considers minor manufacturing flaws and ageing of the hardware in service. Such reduction was proposed by some power utilities during discussions at the working groups based on practical service experience. The use of this criterion is for dry conditions. The second and the third criteria are for the maximum electric field along the housing material, i.e. in the direction of the surface. The calculations are made in dry conditions as a dry background electric field; however, they are applied for wet conditions (water drop corona). The reason for this is that corona from water droplets may deteriorate the housing. The second criterion is for the triple point, i.e. where the metal end fitting, housing material and air joins. This is a vital part of the insulator which makes it crucial not to have any corona at this position. The third criterion is the maximum average electric field along 10 mm of the surface of the insulator. It is an average due to the fact that minor calculation flaws (such as sharp angles) can be neglected. All criteria are applicable regardless if it is a line insulator, station post or apparatus insulator. Deterioration from corona has not been considered in the past and therefore only audible noise and RIV were the driving forces to test insulators from corona point of view. The first criterion can be thus verified with a standard RIV and corona test according to the IEC [9]. There was no test available to verify the second and the third criteria. However, recently this test method called Water Drop Corona Induced (WDCI) has been developed [10]. The WDCI test method has been evaluated thorough a Round Robin Test during 2016 in five laboratories (four in Europe and one in Asia). The preliminary results from the electric field calculations for two set-ups are presented in Figure 2, showing that the first test set-up should not suffer from any corona, but the second test set-up should lead to corona. The results from the Round Robin test, shown in Table 2 and example images in Figure 3, solidly verified the results predicted by the calculations in all participating laboratories. 3
4 Figure 2. Table 2. Left : Test set-up 1 which should pass the test based on electric field calculations. Right : Test set-up 2 which should not pass the test based on electric field calculations. Summary of results from Round Robin test of water induced corona test method (green = accepted, red = not accepted) [10]. Laboratory Water drop corona on housing (Yes/No) Correct grading ring Incorrect grading ring position position 1 No Yes 2 No Yes 3 No Yes 4 No Yes 5 No Yes Figure 3. Left : example of accepted test (no corona on insulator housing). Right : example of failed test (corona on insulator housing). The developed criteria for water drop corona have also been verified by service observations. For example the electric filed calculations for one of the insulators of interest ended with maximum electric field along 10 mm of 1.3 kv/mm and the criterion is 0.42 kv/mm, which is shown in Figure 4 (left). This should lead to corona on the insulator in service. This prediction was confirmed by service inspection in wet conditions (Figure 4, middle) and the close up inspection revealed even deterioration from corona activity on the housing on the first shed to the HV end. The corona activity was so intensive that a crack in the sealing could be found, shown to the right in Figure 4. 4
5 Figure 4. Left: electric field along insulator (dark red = above 0,5 kv/mm). Middle : daylight UV camera showing corona activity on insulator in wet service conditions. Right: deterioration of the first shed of the insulator. The example shown in Figure 4 started the process of checking of all installed composite station post insulators in service at Svk from the electric field point of view. Calculations of these revealed that only three insulators out of eleven were properly graded (two 220 kv and one 400 kv). A summary of the results of the electric field calculations is shown in Table 3. The codes in Table 3 mean that e.g. A- 220 is insulator type A of 220 kv without grading ring, while B-400C kv is insulator type B of 400 kv rating with grading/corona ring. All products having at least one grading/corona ring are designated with suffice C. To summarize, eight out of eleven insulators were found overstressed which led to further investigations. These were conducted via service inspections and laboratory investigations. Table 3. Summary of calculations of composite station post insulators (green = accepted by the criterion; yellow = close to the criterion; red = not accepted by the criterion). Maximum average electric field along 10 mm of insulator Maximum electric field at triple point (end fitting/housing/air) Insulator (kv/mm) (kv/mm) NN Criteria (kv/mm) A B C-400C D E F G G-400C H-220C I J-220C SERVICE INSPECTIONS OF INSULATORS WITH VOLTAGE Service inspections of the insulators overstressed electrically revealed that the intensive corona can be observed on the insulators in service close to the HV end. It is important to note that the corona was not observed in the same conditions on apparatus composite insulators installed at the same substations, thus it can be concluded that the apparatus insulators were designed properly from this point of view. In the worst cases the corona was also observed along the insulator away from the HV end. Inspection of the same insulators by IR revealed hot spots in the same places along the insulator where corona was detected, see Figure 5. 5
6 Figure 5. Left: example of corona along the insulators detected by UV; right: example of corona along the insulators detected by IR. SERVICE INSPECTIONS OF INSULATORS WITHOUT VOLTAGE The close inspection of the de-energized insulators revealed that in the locations where UV/IR detection showed corona and hot spots, punctures or cracks of the housing were observed (see example in Figure 6, left). Depending on the level of electrical overstress at the HV end, deterioration of the housing (close to the HV end) due to intensive corona was also observed; see example Figure 6, right. The hydrophobicity of insulators was good in general, except the parts affected by corona, which were hydrophilic. Figure 6. Left: example of puncture; right: example of deterioration due to intensive corona. AFTER-SERVICE LABORATORY INVESTIGATIONS Test program The main objective of the after-service laboratory testing and analysis was to determine the severity of the deterioration of the punctured insulators. The results of the tests together with service observations were intended to quantify the risk for reduced life expectancy or even failure. Thus, the test program contained the following tests: Standard switching impulse test. Non-standard adhesion test. Standard steep-front impulse test. Dissection and visual observation. Standard dye penetration test. 6
7 Test results The punctured insulators passed the switching impulse test with no indication that the impulse voltage level was reduced. Thus it was considered that the probability to fail in short term is low. However, it was also considered that the test with the simulation of humid service conditions by short-term water immersion might not properly simulate the actual service environment. In the frame of this project there were developed and applied two very practically methods for the evaluation of adhesion, i.e. the so-called stripe-test and square-test. Stripe test: Two parallel cuts with a parallel distance of 10 mm are made. Then a single cut perpendicular with the two earlier cut is made. All cuts need to be fully conducted through the silicon rubber. The 10 mm stripe is then pulled out with pliers from the edge of the perpendicular cut. Square test: Squares of roughly 100 mm 2 were made. As for the stripe test it is very important that all cuts are fully conducted through the silicon rubber. The squares are then pulled with pliers. This simple non-standard adhesion test clearly revealed areas of low level on tested insulators, see example in Figure 7, left. The low level of adhesion is considered as the primarily cause of the damage of the punctured insulators. The overstress by the E-field just accelerated the process. The experience with standard IEC steep-front test showed that this test was not able to reveal insulators with low level of adhesion. The dissection followed by visual inspection and dye penetration test confirmed that the damage under the silicon rubber is extensive, see Figure 7, right. The tracking (conductive path) in the glass fibre rod makes the epoxy resin to erode, leaving only glass fibres. The damaged part of the glass fibre rod is also conductive. This means that the punctured insulator can fail in long-term either mechanically or electrically. Figure 7. Left: example of weak adhesion revealed by simple home-made test; right: example of deterioration in the interface rod/housing penetrating the rod. DISCUSSION AND RECOMMENDATIONS In contradiction to in general positive experience with composite insulators world-wide, the comprehensive test program applied for some composite station post insulators revealed that some of them have very weak adhesion between the rod and the hosing. This is considered as the main reason for punctures and cracks observed in service. These insulators were also electrically overstressed, which made the process of the degradation even faster. This leads ultimately to shorter live expectancy of the insulators. The standard steep-front test is intended for revealing of internal defects in ceramic and composite insulators often in the form of different voids and intrusions. It was believed by international community that this test would also be able to reveal low level of adhesion. Unfortunately, this was not a case and the insulators with clearly low level of adhesion detected by adhesion test passed the 7
8 standard steep-front test and even one trial at higher steepness that recommended by the IEC. The results show that a modification of the test is needed to reveal low adhesion. The simple non-standard adhesion tests presented in this paper clearly revealed the weakness of some insulators. Such tests do not exist in the present IEC standards, however are applied by many manufacturers in-house. This issue should be a topic of interest for CIGRE/IEC in the future, i.e. to develop new representative test methods to evaluate the level of adhesion (might be both sample and design tests) and to revise relevant IEC. Similar proposals can be found in recent publications [11]- [13]. The criteria for the limitation of electric field proposed in IEEE paper [6] and backed by service experience reported in this paper should also be of interest for CIGRE/IEC (recently they were presented to CIGRÉ WG B2.57). BIBLIOGRAPHY [1] CIGRÉ WG B2.21, Guide for the Assessment of Composite Insulators in the Laboratory after their Removal from Service, CIGRÉ TB 481, December 2011 [2] CIGRÉ WG B2.21, Assessment of in-service Composite Insulators by using Diagnostic Tools, CIGRÉ TB 545, August 2013 [3] CIGRÉ WG A3.21, Aspects for the Application of Composite Insulators to High Voltage ( 72kv) Apparatus, CIGRÉ TB 455, April 2011 [4] IEC 62217, Ed. 2.0, Polymeric HV insulators for indoor and outdoor use General definitions, test methods and acceptance criteria, 2012 [5] IEC , Ed. 1.0, Composite station post insulators for substations with AC voltages greater than V up to 245 kv Part 1: Dimensional, mechanical and electrical characteristics, 2015 [6] A.J. Philips, A.J. Maxwell, C.S. Engelbrecht, I. Gutman: Electric Field Limits for the Design of Grading Rings for Composite Line Insulators, IEEE Transactions on Power Delivery, Vol. 30, No. 3, June 2015, p.p [7] P. Sidenvall, I. Gutman, L. Carlshem, J. Bartsch, R. Kleveborn: Development of the Water Drop Induced Corona WDIC Test Method for Composite Insulators, IEEE Electrical Insulation Magazine, November/December 2015, Vol. 31, No. 6, p.p [8] CIGRÉ WG B2.03, Use of corona rings to control the electrical field along transmission line composite insulators, CIGRÉ TB 284, December 2005 [9] IEC Standard, Overhead lines Requirements and tests for fittings, IEC Standard 61284, Second edition, [10] P. Sidenvall, I. Gutman, L. Carlshem, J. Bartsch: A Round Robin Test of the Water Induced Corona Test, ICOLIM-2017, Strasbourg, France, April 2017, paper 0017 [11] C. Ahlrot, J. Lundengård, I. Gutman, Need of standardized adhesion test for composite insulators: lessons learned from service experience, 20 th ISH-2017, Buenos Aires, Argentina, August 28 September 01, 2017, paper 145 (to be published) [12] I. Gutman, P. Sidenvall, T. Condon: Evaluation of composite insulators with internal deterioration: lessons learned from service and after-service testing, CIGRÉ Winnipeg 2017 International Colloquium & Exhibition, Winnipeg, Canada, September 30 October 6, 2017, paper 142 (to be published) [13] F. Zhang, Z. He, Y. Liao, G. Wang, B. Luo, Research on the adhesiveness between core rod and sheath for composite insulators on the transmission lines, INSUKON-2017, Birmingham, UK, May 2017, p.p
Polluted Outdoor Insulators Maintenance and Washing
Polluted Outdoor Insulators Maintenance and Washing Ali Naderian, PhD, PEng, SM IEEE Toronto, Canada February 2018 ali.naderian@ieee.org 1 برگزار کنندگان ایکهربا سامانه تجهیزات صنعت برق ایران کارشناسان
More informationPaper 078: Innovative insulated cross-arm: requirements, testing and construction
Paper 078: Innovative insulated cross-arm: requirements, testing and construction Introduction First inquiry for new tower designs was launched by Elia (the Belgian TSO) in the beginning of 2008. The requirements
More informationDiagnostic Techniques of Composite Insulators
Diagnostic Techniques of Composite Insulators to learn more - join CITI Those which are considered low cost turn into pricy. This statement applies to various aspects but in particular to power lines NCI
More informationHIGH VOLTAGE INSULATORS. By JP Holtzhausen. Glass. Bushings & hollow core insulators. Cap & pin insulators
HIGH VOLTAGE INSULATORS By JP Holtzhausen The principal dielectric used on overhead power lines is air at atmospheric pressure. The air, surrounding the bare high voltage aluminium or steel- cored aluminium
More informationGeneral Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Substation Insulators (63 kv- 400 kv)
Islamic Republic of Iran Vice Presidency for Strategic Planning and Supervision General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Substation Insulators
More informationComposite Insulator Components
Composite Insulator Components Composite insulator components A composite insulator is made of at least two insulating parts a core and housing. It is equipped with end fittings. Core. The core is the
More informationGeneral Requirements. Technical Specifications for Insulators of Transmission Lines
Islamic Republic of Iran Vice Presidency for Strategic Planning and Supervision General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Insulators of Transmission
More informationEffect of Metal Ring on the Field Distribution of Outdoor Polymeric Insulator
Effect of Metal Ring on the Field Distribution of Outdoor Polymeric Insulator Veeresh A G Meenakshendra A Khamitkar MTech(Power System Engineering) MTech(Power System Engineering) SDM College Of Engineering
More informationPI Electrical Equipment - tourse PI 30.2 INSULATION. On completion of this module the student will be able to:
Electrical Equipment - tourse PI 30.2 INSULATION OB~ECTIYES On completion of this module the student will be able to: 1. Explain. in writing, the term "leakage current" and indicate the normal range of
More informationOutdoor High Voltage Non-Ceramic Insulators
Outdoor High Voltage Non-Ceramic Insulators V.P. Karthika 1, P. Anitha 2, A. Hearty Rugesh 3 1 Teaching Fellow, 2 Assistant Professor, 3 UG Student 1, 2, 3 Department of EEE, Anna University, Thoothukudi
More informationNPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators
Version:- 3.1 Date of Issue:- June 2014 Page 1 of 13 NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators 1. Purpose This document is the technical specification for 33kV, 66kV
More informationFIBRE REINFORCED PLASTICS IN HIGH VOLTAGE APPLICATIONS
FBRE RENFORCED PLASTCS N HGH VOLTAGE APPLCATONS Volker Bergmann, Reinhausen Power Composites GmbH Page 1 OVERVEW 1. ntroduction 2. Hollow core composite insulators and their application 3. Dielectric and
More informationElectrical Field Simulation for Different Cases of Polymer Insulators Using FEM
J. Basic. Appl. Sci. Res., 2(10)10203-10208, 2012 2012, TextRoad Publication ISSN 2090-4304 Journal of Basic and Applied Scientific Research www.textroad.com Electrical Field Simulation for Different Cases
More informationEXPERIMENTAL INVESTIGATION OF EFFECT OF UV RADIATION ON FLASHOVER VOLTAGE OF POLYMERIC INSULATORS WITH AND WITHOUT CONTAMINATION
EXPERIMENTAL INVESTIGATION OF EFFECT OF UV RADIATION ON FLASHOVER VOLTAGE OF POLYMERIC INSULATORS WITH AND WITHOUT CONTAMINATION A. Majzoobi *, I. A. Joneidi, S. Mohajer, H.Mohseni and A. A. Shayegani
More informationA Deep Insight on Improvement in HV and EHV XLPE AC Cable Technology
A Deep Insight on Improvement in HV and EHV XLPE AC Cable Technology Preet Khandelwal 1, Arun Pachori 2 1 preet_27sep@yahoo.co.in Abstract: This paper highlights on continuous improvement in Extra High
More informationStudy Committee A3. High Voltage Equipment. Action Plan
Study Committee A3 High Voltage Equipment Action Plan October 2011 CIGRE Study Committee A3 - High Voltage Equipment Action Plan 1 Content 1 Content...2 2 Purpose of the Action Plan...3 3 Activities of
More informationNotes Changed note Date. 1 (A) Changed template 09 / 07 / 2008
Revisions Notes Changed note Date 1 (A) Changed template 09 / 07 / 2008 2 Changed template. Clause 12.5.4.1 hot-rolled steel added. Clause 12.5.4.2, 12.5.2.4, 12.5.3.4, 12.5.4.4, 12.5.5.4, 12.5.6.4, 12.5.7.4
More informationINCLINED PLANE TESTS OF COMPOSITE, SILICONE RUBBER AND COMPOSITE SILICONE RUBBER COATED MATERIALS
INCLINED PLANE TESTS OF COMPOSITE, SILICONE RUBBER AND COMPOSITE SILICONE RUBBER COATED MATERIALS M N R Baharom 1*, Ian Cotton 1 1 School of Electrical & Electronic Engineering, The University of Manchester,
More informationPRY-MOULD. High Voltage Accessories for Extruded Cables
PRY-MOULD High Voltage Accessories for Extruded Cables Linking the future As the worldwide leader in the cable industry, Prysmian Group believes in the effective, efficient and sustainable supply of energy
More informationNew designed XLPE-insulated cables substituting paper-insulated pipe type cables
MODERN CABLE SYSTEMS IN STEEL PIPES New designed XLPE-insulated cables substituting paper-insulated pipe type cables Volker AUE, Nexans Deutschland Industries, Germany, Volker.Aue@nexans.com Wilfried ROSEBROCK,
More informationTransmission Silicone Insulators Line Post 69 kv to 230 kv
K-LINE INSULATORS LIMITED Catalogue T-LP Transmission Silicone Insulators Line Post 69 kv to 230 kv ISO9001 SAI GLOBAL FILE No. 000117 Transmission Silicone Insulators Line Post Today transmission lines
More informationPrototype Test Report ANSI C29.17 Quadri*Sil Line Post Insulators 2.5 Dia. Rod HPS Silicone rubber R
PAGE: 1 Test Requests: R18-01-03 Report Number: R18-01-03 Prototype Test Report ANSI C29.17 Quadri*Sil Line Post Insulators 2.5 Dia. Rod HPS Silicone rubber R18-01-03 Introduction: Sample Quadri*Sil line
More informationRisk assessment of pollution on a 66kV composite insulator using ANSYS
Risk assessment of pollution on a 66kV composite insulator using ANSYS Ms. N H M Netravati 1, Mrs. Sunitha N.S 2, Dr.Shivakumara Aradhya R.S. 3, Dr. K.N Ravi 4 M.Tech. student 1, Assistant Professor 2,
More informationfire Charcoat Charcoat IC Passive Protection
Charcoat fire Protection Passive insulator protection Coating for the protection of pollution flashover on exterior and interior high voltage insulators Charcoat IC General information CharCoat IC is a
More informationEffect of UV-Rays and Salt Contamination on 33kV Silicon Composite Insulators
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 11, Issue 6 Ver. II (Nov. Dec. 2016), PP 45-55 www.iosrjournals.org Effect of UV-Rays and
More informationElectric field analysis of 132kV EPDM insulator and correlation with ageing features
2013 Electrical Insulation Conference, Ottawa, Ontario, Canada, 2 to 5 June 2013 Electric field analysis of 132kV EPDM insulator and correlation with ageing features Antonios Tzimas, Christos Zachariades
More informationCritical design, testing and manufacturing features for the selection of high quality composite insulators for transmission overhead lines
:, Lr.4 iecii 2009 ITIITtM iim i Now TerMrrkçes âi Tims,rsGq, OeJj & ConTnuniatNo A. Critical design, testing and manufacturing features for the selection of high quality composite insulators for transmission
More informationNPS/003/001 Technical Specification for 33kV, 66kV and 132kV Voltage Transformers
Version:- 5.0 Date of Issue:- February 2015 Page 1 of 25 NPS/003/001 Technical Specification for 33kV, 66kV and 132kV Voltage Transformers 1. Purpose This purpose of this document is to specify the technical
More informationCONDITION ASSESSMENT OF A FIELD-AGED 150 kv HTV SIR SUSPENSION INSULATOR FOLLOWING FLASHOVER
The 19 th International Symposium on High Voltage Engineering, Pilsen, Czech Republic, August, 23 28, 2015 CONDITION ASSESSMENT OF A FIELD-AGED 150 kv HTV SIR SUSPENSION INSULATOR FOLLOWING FLASHOVER N.
More informationINSULATOR REQUERIMENTS:
2017 INMR WORLD CONGRESS SITGES-BARCELONA, INSULATOR REQUERIMENTS: DESIGN CRITERIA, OPERATION PARAMETERS AND STANDARDS REVIEW JAVIER GARCÍA TECHNICAL AND PRODUCTION MANAGER CONTENTS q INTRODUCTION q MECHANICAL
More informationCHAPTER 6 HIGH VOLTAGE ELECTRICAL TESTING RESULTS
CHAPTER 6 HIGH VOLTAGE ELECTRICAL TESTING RESULTS 6.1 Introduction An electrical porcelain insulator plays an eminent role in electrical power system. As the insulators have high resistance path so it
More informationCONTENTS. IEC Ed. 2 /CDV IEC 2 36B/ /CDV 36B-MT10/Nuremberg3/60
IEC 61109 Ed. 2 /CDV IEC 2 36B/ /CDV 36B-MT10/Nuremberg3/60 CONTENTS FOREWORD...4 INTRODUCTION...5 1 Scope and object...7 2 Normative references...7 3 Definitions...8 4 Abbreviations...9 5 Identification...9
More informationDISTRIBUTION SILICONE INSULATORS Deadend / Suspension 15 kv to 69 kv
K-LINE INSULATORS LIMITED TORONTO, ONTARIO, CANADA Catalogue D-DS DISTRIBUTION SILICONE INSULATORS Deadend / Suspension 15 kv to 69 kv ISO9001 SAI GLOBAL FILE No. 000117 Distribution Silicone Insulators
More informationPotential and E-Field Calculation Along an Ice- Covered Composite Insulator with Finite Element Method
Potential and E-Field Calculation Along an Ice- Covered Composite Insulator with Finite Element Method Qing Yang, Caixin Sun, Wenxia Sima, Lichun Shu, Ji Yang, Jianlin Hu The Key Laboratory of High Voltage
More informationSelection between indoor or outdoor DC yards D. WU*, U. ÅSTRÖM, L. ARÉVALO, R. MONTAÑO, B. JACOBSON ABB HVDC SWEDEN
21, rue d Artois, F-75008 PARIS B3-115 CIGRE 2014 http : //www.cigre.org Selection between indoor or outdoor DC yards D. WU*, U. ÅSTRÖM, L. ARÉVALO, R. MONTAÑO, B. JACOBSON ABB HVDC SWEDEN SUMMARY In an
More informationArtificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester
Artificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester W. Payakcho, J. Grasaesom, S. Thong-om and B. Marungsri* Abstract This paper presents the experimental results
More informationTRANSMISSION & DISTRIBUTION SILICONE INSULATORS InterPhase Spacers 15 kv to 400 kv
K-LINE INSULATORS LIMITED Catalogue TD-IPS TORONTO, ONTARIO, CANADA TRANSMISSION & DISTRIBUTION SILICONE INSULATORS InterPhase Spacers 15 kv to 400 kv ISO9001 SAI GLOBAL FILE No. 000117 Transmission &
More informationCHAPTER 2 STRUCTURE AND CRITICAL E-FIELDS
25 CHAPTER 2 STRUCTURE AND CRITICAL E-FIELDS 2.1 INTRODUCTION Polymeric insulators have been commercially produced and utilized for more than four decades now. Their demand is still increasing rapidly
More information094: 2000 CEB STANDARD. MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA
094: 2000 CEB STANDARD MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA Specification for MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEB Standard
More informationGSCH004 Rev /10/2016
GLOBAL STANDARD Page 1 of 28 INSULATORS Elaborated by Verified by Approved by High Voltage SDC HV SDC - M. A. Caballero HV SDC - J.A. Lama Head of NCS - F. Giammanco Global I&N NT/NCS HV SDC - T. González
More informationManufacturing and Application of Cage Design High Voltage Metal Oxide Surge Arresters
Manufacturing and Application of Cage Design High Voltage Metal Oxide Surge Arresters K. Steinfeld, B. Kruska and W. Welsch Siemens Surge Arresters and Limiters, Berlin, Germany Abstract: Metal oxide surge
More informationAgeing Deterioration of Silicone Rubber Polymer Insulator under Salt Water Dip Wheel Test
Ageing Deterioration of Silicone Rubber Polymer Insulator under Salt Water Dip Wheel Test J. Grasaesom, S. Thong-om, W. Payakcho and B. Marungsri* Abstract This paper presents the experimental results
More information8. Hydrophobicity classification guide STRI guide 1.92/1 9. Radio interference characteristics of overhead power lines and high-voltage equipment
Revised in Jan 14 TECHNICAL SPECIFICATION FOR 11KV POLYMER INSULATORS (C&T) 1.0. Scope This specification covers design, manufacture, testing and supply of composite insulators for use in the 11KV overhead
More informationPanagiotis Charalampidis
Textured Insulators for Overhead Lines and Substations I. INTRODUCTION Panagiotis Charalampidis High Voltage Energy Systems Group, School of Engineering, Cardiff University, The Parade, Cardiff CF24 3AA,
More informationDesign features - Polymer-housed arresters, PEXLIM
features - Polymer-housed arresters, PEXLIM PEXLIM arresters, using the same ZnO blocks as the EXLIM arresters, match their electrical performance. Silicone as outer insulation material has been used for
More informationRESULTS OF 12 YEARS OF MODULE QUALIFICATION TO THE IEC STANDARD AND CEC SPECIFICATION 503
May -8,23 Osaka. Japan 6-B8- RESULTS OF 2 YEARS OF MODULE QUALIFICATION TO THE IEC 625 STANDARD AND CEC SPECIFICATION 53 H. Ossenbrink and T. Sample European Commission, DG Joint Research Centre Institute
More informationCigré WG C Topics: The selection of insulators with respect to polluted conditions
Cigré Guide for the selection of insulators with respect to contamination conditions Chris Engelbrecht: Convener Topics: The selection of insulators with respect to polluted conditions Present practise
More informationComposite Outdoor High Voltage Insulators in Crete - 37 Years of Experience
Trivent Publishing The Authors, 2016 Available online at http://trivent-publishing.eu/ Engineering and Industry Series Volume Power Systems, Energy Markets and Renewable Energy Sources in South-Eastern
More informationSpecification for Polymer Disc Insulator
Specification for Polymer Disc Insulator Scope : This specification cover the design, manufacturing, testing at manufacturers works, transport to site, insurance, storage of 11 KV & 33 KV Polymer Disc
More informationSPECIFICATION FOR 11 & 33kV COMPOSITE INSULATORS Part 1: Pin Type
Doc. KPLC1/3CB/TSP/04/017/1 1 Page 1 of 7 TABLE OF CONTENTS 0.1 Circulation List 0.2 Amendment Record FOREWORD 1. SCOPE 2. REFERENCES 3. TERMS AND DEFINITIONS 4. REQUIREMENTS 5. TESTS AND INSPECTION 6.
More informationWalk through the associated design considerations associated with transmission line design
Walk through the associated design considerations associated with transmission line design Follow-up to Transmission Design 101 (2012) & Transmission Design 102 (2013) Additional design considerations
More informationSPECIFICATION FOR POLYMER DISC INSULATOR
SPECIFICATION FOR POLYMER DISC INSULATOR Scope : This specification cover the design, manufacturing, testing at manufacturers works, transport to site, insurance, unloading & storage of 11 KV & 33 KV Polymer
More informationGUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 220, 132 & 66 COMPOSITE SOLIDCORE STATION POST INSULATORS GETCO/E/2,1,6
More informationInternational Journal of Mechatronics, Electrical and Computer Technology
Effect of Corona Ring on Potential Distribution and Electric Field on Silicon Insulator in Polluted Condition Rasool Feiz Kerendian 1*, Hasan Keshavarz Ziarani 1, Javad Ebrahimi 2 1 Electrical Eng. Dept.,
More informationProject number 36B/61952/Ed2. Date of circulation Supersedes document 36B/231/MCR. Safety EMC Environment Quality assurance
IEC/TC or SC: SC 36B Title of TC/SC: Insulators for overhead lines Also of interest to the following committees TC 11 Functions concerned: Project number 36B/61952/Ed2 Date of circulation 2004-03-19 Supersedes
More informationResearch methodology for the life evaluation of Hollow polymer insulators for High Voltage Applications
16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 687 Research methodology for the life evaluation of Hollow polymer insulators for High Voltage Applications 1. S.Farook, Research scholar,
More informationNPS/001/008 Technical Specification for Gapless Metal Oxide Surge Arresters
Version:- 5.0 Date of Issue:- October 2017 Page 1 of 18 NPS/001/008 Technical Specification for Gapless Metal Oxide Surge Arresters 1. Purpose The purpose of this document is to detail the technical requirements
More informationDevelopment of Composite Line Spacers for Distribution Lines
Development of Composite Line Spacers for Distribution Lines Ichiro Sumitani / Toshiko Kurosawa TOKYO ELECTRIC POWER COMPANY 4-1 Egasaki-Cho, Tsurumi-Ku, Yokohama, 230-8510JAPAN Tel : +81 45 585 8561 Fax
More informationINVESTIGATION OF THE AGING CHARACTERISTICS OF CST TERMINATION MADE OF SILICONE RUBBER AT CONTAMINATION AREA
INVESTIGATION OF THE AGING CHARACTERISTICS OF CST TERMINATION MADE OF SILICONE RUBBER AT CONTAMINATION AREA Tatsuya NAKAMURA, Chubu Electric Power Co. Inc., JAPAN, Nakamura.Tatsuya@chuden.co.jp Yoshihide
More informationPV MODULE RELIABILITY ISSUES INCLUDING TESTING AND CERTIFICATION. Ulrike Jahn, TÜV Rheinland
PV MODULE RELIABILITY ISSUES INCLUDING TESTING AND CERTIFICATION Ulrike Jahn, TÜV Rheinland Frankfurt, 24 September 2012 Outline Introduction IEC qualification testing Statistics of laboratory test failures
More informationHigh Quality Porcelain Insulators for Transmission Lines
Our Customers World Wide High Quality Porcelain Insulators for Transmission Lines 765kV KEPCO / KOREA Tangjin - Sin Ansomg 735kV H-Q / CANADA Manic - Churchill, James Bay 765kV PGCI / INDIA Kishenpur -
More informationData Sheet 110kV TD123II dry type outdoor termination
3 Data Sheet 110kV TD123II dry type outdoor termination 1. Product Description: 3M 110kV TD123II dry type outdoor termination meets requirement of test and product according to IEC60840 and GB11017.3,
More informationStation Post Insulators (SPI), an Emerging Application for Composite Hollow Core Insulators PETER STAHL
Station Post Insulators (SPI), an Emerging Application for Composite Hollow Core Insulators PETER STAHL Composite Hollow Core Station Post Insulators (SPI) Peter Stahl, July 2015 Applications for composite
More informationBrugg Cables High Voltage Accessories. Swiss solutions for independent applications.
Brugg Cables High Voltage Accessories. Swiss solutions for independent applications. Fact Book High Voltage Accessories Brugg Cables Business Unit High Voltage Accessories Dr. Ruben Vogelsang Head of Product
More informationAPDRP SCHEME, WESCO. Technical Specification for 33KV Air Break Switch PART 1: SCOPE AND CONDITIONS
PART 1: SCOPE AND CONDITIONS 1. SCOPE This specification covers the design, engineering, manufacture, testing, supply, delivery, off-loading and performance requirements of 33kV, 200 amp, triple pole Gang
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 62217 First edition 2005-10 Polymeric insulators for indoor and outdoor use with a nominal voltage >1 000 V General definitions, test methods and acceptance criteria Reference
More informationNecessary Check Points & Testing for Screening the Quality of Insulators
Necessary Check Points & Testing for Screening the Quality of Insulators J.M. George, E. Brocard, S. Prat, F. Virlogeux, D. Lepley Sediver Research Center, France Introduction The increasing demand for
More informationDesign of MO Surge Arresters with Polymeric Housings
Design of MO Surge Arresters with Polymeric Housings Kai Steinfeld (Director R&D Surge Arresters) High Voltage Surge Arrester s Voltages in Electric Power Systems Voltage Limiting Effect of Surge Arresters
More informationQuality requirements for wafers, cells and PV modules
Outdoor test-site PI Berlin Quality requirements for wafers, cells and PV modules Intersolar 2008 in Munich, 12th of June 2008 Stefan Krauter, Paul Grunow, Sven Lehmann PI Photovoltaik-Institut Berlin
More information093 : 2000 CEB STANDARD MEDIUM VOLTAGE PIN POST INSULATORS AND HARDWARE CEYLON ELECTRICITY BOARD SRI LANKA
093 : 2000 CEB STANDARD MEDIUM VOLTAGE PIN POST INSULATORS AND HARDWARE CEYLON ELECTRICITY BOARD SRI LANKA Specification for MEDIUM VOLTAGE PIN POST INSULATORS AND HARDWARE CEB Standard 093 : 2000 CEYLON
More informationACOUSTIC EXAMINATION OF EPOXY-GLASS INSULATOR MATERIAL P. RANACHOWSKI, Z. RANACHOWSKI, F. REJMUND J. STANKIEWICZ
ARCHIVES OF ACOUSTICS 30, 1, 121 130 (2005) ACOUSTIC EXAMINATION OF EPOXY-GLASS INSULATOR MATERIAL P. RANACHOWSKI, Z. RANACHOWSKI, F. REJMUND Institute of Fundamental Technological Research Polish Academy
More informationIntroduction to Substation Design TADP 542
Introduction to Substation Design TADP 542 Design Principles- General Framework Instructor: Richard Snell Transmission & Distribution Program Module 2 Outline Presentation 1: General Framework Presentation
More informationPolymer Cutout Testing Recommendations
1 Polymer Cutout Testing Recommendations High Voltage Fuse Subcommittee May 2012 Frank Lambert Recommended Tests 1. Water Diffusion Tests (CAN/CSA 310 09 7.3) 2. DyePenetration (ANSI C29.13 Section 7.3)
More informationSPECIFICATION FOR DISC INSULATORS (Standard Type)
Doc. KPLC1/3CB/TSP/04/015 1 Page 1 of 6 TABLE OF CONTENTS 0.1 Circulation List 0.2 Amendment Record FOREWORD 1. SCOPE 2. REFERENCES 3. TERMS AND DEFINITIONS 4. REQUIREMENTS 5. TESTS AND INSPECTION 6. MARKING,
More informationPolymer Suspension Insulators 69kV to 765kV
CATALOG Polymer Suspension Insulators 69kV to 765kV NGK Locke Polymer Insulators, Inc. Virginia Beach, Virginia, U.S.A. TABLE of CONTENTS Table of Contents... 1 Design Features... 2 Material... 2 Definition
More informationData Sheet 110kV TP123-II Porcelain Insulator Outdoor Termination
3 Data Sheet 110kV TP123-II Porcelain Insulator Outdoor Termination 1 Product Description 3M 110kV TP123-II termination meets requirements of IEC60840 and GB11017.3 standards. The porcelain insulator is
More information3M Cold Shrink Joint, SC145-II/SS145-II
3M Cold Shrink Joint, SC145-II/SS145-II Data Sheet June 2011 Description Features 3M Cold Shrink Joint, SC145-II/SS145-II meets requirements of IEC60840-2004 and GB11017.3 standards. Ideal electrode design
More information30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH
SPECIFICATIONS FOR LOAD BREAK SWITCH This specification is property of SEC and subject to change or modification without any notice TABLE OF CONTENTS 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE CODES
More informationCONSULTATIONS TECHNICAL GUIDELINE. HVDC extruded cable
UNIT, BU1SNESS AREA OUR REFERENCE TR14-02-2E DATE 2018-01-24 CONSULTATIONS TECHNICAL GUIDELINE EDITION 1 APPROVED HVDC extruded cable This technical guideline describes the basic design and construction
More informationStudy on Pollution Flashover Performance of Short Samples of Composite Insulators Intended for ±800 kv UHV DC
1192 Study on Pollution Flashover Performance of Short Samples of Composite Insulators Intended for ±800 kv UHV DC Xingliang Jiang, Jihe Yuan, Zhijin Zhang, Jianlin Hu and Lichun Shu Chongqing University
More informationIEEE T&D Insulators 101
Insulators 101 Section A Introduction Presented by Andy Schwalm IEEE Chairman, Lightning and Insulator Subcommittee IEEE/PES 2010 Transmission and Distribution Conference and Exposition New Orleans, Louisiana
More informationTECHNICAL SPECIFICATION
IEC/TS 62371 TECHNICAL SPECIFICATION Edition 1.0 2008-05 Characteristics of hollow pressurised and unpressurised ceramic and glass insulators for use in electrical equipment with rated voltages greater
More informationV. Design, Application, Maintenance & Operation Technical Requirements
V. Design, Application, Maintenance & Operation Technical Requirements V.A PJM Design & Application of Overhead Transmission Lines 69 kv & Above These design criteria have been established to assure acceptable
More informationSafety Concerns with New
Safety Concerns with New PV Polymeric Materials Crystal Vanderpan Underwriters Laboratories Inc. October 17, 2010 Copyright 1995-2007 Underwriters Laboratories Inc. All rights reserved. No portion of this
More informationTRANSMISSION NEW PROJECTS DEPARTMENT TRANSMISSION LINES TOWER DESIGN AND SPECIFICATIONS SECTION ATHENS - GREECE SPECIFICATION TR-1
I NDEPENDE N T POWER TR ANSM ISSION OP ER AT O R S.A. TRANSMISSION NEW PROJECTS DEPARTMENT TRANSMISSION LINES TOWER DESIGN AND SPECIFICATIONS SECTION ATHENS - GREECE SPECIFICATION TR-1 STRING INSULATOR
More informationA3-110 LONG TERM PERFORMANCE OF POLYMER HOUSED MO-SURGE ARRESTERS
21, rue d'artois, F-75008 Paris http://www.cigre.org A3-110 Session 2004 CIGRÉ LONG TERM PERFORMANCE OF POLYMER HOUSED MO-SURGE ARRESTERS B. RICHTER*, W. SCHMIDT K. KANNUS, K. LAHTI ABB SWITZERLAND LTD.
More informationB2-00. SPECIAL REPORT FOR SC B2 (Overhead Lines) V. NAIDOO J. IGLESIAS S. ANSORGE. Special Reporters
CIGRE 2016 B2-00 SPECIAL REPORT FOR SC B2 (Overhead Lines) V. NAIDOO J. IGLESIAS S. ANSORGE Special Reporters Introduction Study Committee B2 covers the design, construction and operation of overhead lines.
More informationLaboratory Investigation on Hydrophobicity and Tracking performance of Field Aged Composite Insulators
Laboratory Investigation on Hydrophobicity and Tracking performance of Field Aged Composite Insulators N. Mavrikakis Faculty of Engineering Aristotle University of Thessaloniki nmavrika@auth.gr K. Siderakis
More informationPerformance Analysis of 33 kv Polymer and Porcelain Insulators under Various Pollution Conditions at Costal Regions
Volume 114 No. 9 217, 1-9 ISSN: 1311-88 (printed version); ISSN: 1314-3395 (on-line version) url: http://www.ijpam.eu ijpam.eu Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various
More informationAnalysis of Polymer Surface Modifications due to Discharges Initiated by Water Droplets under High Electric Fields
Analysis of Polymer Surface Modifications due to Discharges Initiated by Water Droplets under High Electric Fields Michael G. Danikas, Ramanujam Sarathi, Pavlos Ramnalis, and Stefanos L. Nalmpantis Abstract
More informationSGC switchgears compatible with real service conditions : Solutions that address on-site conditions Pieter Himpens
SGC switchgears compatible with real service conditions : Solutions that address on-site conditions Pieter Himpens Pieter.Himpens@switchgearcompany.eu Frederik Delobelle Frederik.Delobelle@switchgearcompany.eu
More informationINSULATORS NEW. See page J-4 for more information.
INSULATORS INSULATORS NEW Improved 23613 Dead End/Suspension Insulator Salisbury s Improved 23613 Dead End/Suspension Insulator has aluminum end fittings. These new end fittings create a lightweight product
More informationSILICONE RUBBER INSULATORS WITH NOTCHED SURFACE
SILICONE RUBBER INSULATORS WITH NOTCHED SURFACE K. L. Chrzan Wroclaw University of Technology, Institute I 7, 5-37 Wroclaw, Poland Email: krystian.chrzan@pwr.wroc.pl Abstract: A modification of an insulator
More informationPV module durability testing under high voltage biased damp heat conditions
Available online at www.sciencedirect.com Energy Procedia 8 (2011) 6 384 389 1 5 SiliconPV: 17-20 April 2011, Freiburg, Germany PV module durability testing under high voltage biased damp heat conditions
More informationUHS 10kA Arrester. Certified Test Report IEC
CP No.: CP0606 Page 1 of 10 UHS 10kA Arrester Certified Test Report IEC 60099-4 2004 CERTIFICATION Statements made and data shown are, to the best of our knowledge and belief, correct and within the usual
More informationOverview of Silicone Elastomers, Gels & Auxiliary Materials for Cable Accessory Applications
Overview of Silicone Elastomers, Gels & Auxiliary Materials for Cable Accessory Applications Authors: Dr. Jens Lambrecht, Dr. Konrad Hindelang Wacker Chemie AG Munich, Germany 1. INTRODUCTION The first
More informationPERFORMANCE ANALYSIS OF OVERHEAD PORCELAIN INSULATOR UNDER DIFFERENT CONTAMINATIONS
International Journal of Mechanical Engineering and Technology (IJMET) Volume 8, Issue 10, October 2017, pp. 241 245, Article ID: IJMET_08_10_028 Available online at http://www.iaeme.com/ijmet/issues.asp?jtype=ijmet&vtype=8&itype=10
More informationCOMPOSITE INSULATORS
Maharashtra State Electricity Distribution Co. Ltd. SPECIFICATION NO.MSEDCL/ DIST: MM-III/07/2007 SPECIFICATION FOR 11 KV/22 KV/33 KV COMPOSITE INSULATORS 1 TECHNICAL SPECIFICATION FOR 11 KV/22 KV/33 KV
More information