GROUND SOURCE HEAT PUMPS Analysing the Brine Flow in Boreholes, Mariehäll M A R A L K A S S A B I A N

Size: px
Start display at page:

Download "GROUND SOURCE HEAT PUMPS Analysing the Brine Flow in Boreholes, Mariehäll M A R A L K A S S A B I A N"

Transcription

1 GROUND SOURCE HEAT PUMPS Analysing the Brine Flow in Boreholes, Mariehäll M A R A L K A S S A B I A N Master of Science Thesis Stockholm, Sweden 2007

2 GROUND SOURCE HEAT PUMPS Analysing the Brine Flow in Boreholes, Mariehäll Maral Kassabian Master of Science Thesis Refrigeration 2007:412 KTH School of Energy and Environmental Technology Division of Applied Thermodynamic and Refrigeration SE STOCKHOLM

3 Master of Science Thesis EGI 2007/ETT:412 GROUND SOURCE HEAT PUMPS Analysing the Brine Flow in Boreholes, Mariehäll Approved 15 April 2007 Examiner Björn Palm Commissioner Maral Kassabian Supervisor Peter Hill Contact person Tommy Nilsson Abstract The brine flow through the boreholes of a 2 heat pump system in Stockholm, Sweden was examined. The objective was to identify the behaviour of the flow in order to optimise the use of the boreholes, heat pumps, and extra pump included in the system. The amount of energy extracted by the system was a function of the brine flow. Reynolds number and disturbances greatly affected the flow. It was seen to absorb the most energy during the first 15m of the borehole, and at the bottom of the borehole, after turning 180. There were large amounts of energy lost in the last m of the borehole. This was due to Re as well as the ground- and brine-temperatures. The flow appeared turbulent during the first 15m of the borehole, and seemed to transition to laminar as it travelled down the borehole. After passing the bend, it appeared to possess turbulent properties once again. An extra brine pump was used to increase the brine flow and thereby extract more energy from the boreholes. This was the case when two heat pumps were operational; net energy extraction with the extra pump was higher than without it. When a single heat pump was running, there was less energy extracted with the extra pump. This was attributed to the difference in ground- and brine-temperatures, as well as the number of boreholes open. Determining the optimal number of boreholes to operate was difficult as there were many variables such as dissimilar flows in boreholes, different borehole lengths, changing demand from the heat pump, varying ambient conditions. Some general conclusions have been drawn. Recommendations include insulating the pipes exiting and entering the house to the point where the boreholes begin. In addition, the last 30-40m of borehole on the up-flow side should be insulated to avoid energy dissipation to the surroundings. For more accurate studies, flow meters must be installed in each borehole. Heat pump manufacturers must label heat pumps with regards to the flow rate required to optimize energy extraction. 3

4 TABLE OF CONTENTS 1 INTRODUCTION HEAT PUMPS COEFFICIENT OF PERFORMANCE BOREHOLE CONFIGURATIONS LAMINAR AND TURBULENT FLOW REYNOLDS NUMBER EXTRACTED HEAT MARIEHÄLL OBJECTIVES METHODOLOGY STEP STEP STEP EQUIPMENT TECHNICAL DETAILS PRACTICAL BACKGROUND PIPE DIMENSIONS TA METER DATA ACQUISITION SYSTEM HEAT PUMP CONTROL EXPERIMENTAL UNCERTAINTIES ERRORS IN MASS FLOW Flow Measurement Methods Flow Comparison TIME ERROR Time Error Averaging Temperature Values OTHER ERRORS RESULTS BRINE PROPERTIES GROUND TEMPERATURES Ground Temperature Stabilization Time FLOW REGIME IN BOREHOLE

5 6.4 EFFECTS OF THE EXTRA BRINE PUMP One Heat Pump Two Heat Pumps EFFECT OF OPENING ONE EXTRA BOREHOLE TOTAL COP DISCUSSION BRINE PROPERTIES GROUND TEMPERATURE FLOW REGIME IN BOREHOLE Meter Depth First 5 Meters EFFECTS OF THE EXTRA BRINE PUMP EFFECT OF OPENING ONE EXTRA BOREHOLE CONCLUSIONS BRINE PROPERTIES GROUND TEMPERATURE FLOW REGIME IN BOREHOLE EFFECTS OF THE EXTRA BRINE PUMP EFFECT OF OPENING ONE EXTRA BOREHOLE TOTAL COP RECOMMENDATIONS REFERENCES...47 APPENDIX 1: BOREHOLE DIAGRAMS...49 APPENDIX 2: EFFECTS OF EXTRA BRINE PUMP...59 APPENDIX 3: OPENING ONE EXTRA BOREHOLE...61 APPENDIX 4: SECONDARY APPENDICES

6 INDEX OF TABLES Table 4,1: Table 5,1: Table 6,1: Table 6,2: Table 6,3: Table 6,4: Table 6,5: Table 7,1: Table 7,2: Table B1: Table B2: Table B3: Table B4: Table B5: Table B6: Table B7: Table C1: Borehole depths Error analysis of total brine flow calculation methods. Viscosity comparison between brine and ethyl alcohol 23%weight. Energy extracted from boreholes with 2 heat pumps. Total COP, with and without extra brine pump. Running time, with and without extra brine pump. Total COP, with extra brine pump. Effect of temperature difference and flow on total heat extraction. Overall energy gained and lost. Total energy extracted from 7 boreholes. Effect of temperature and flow on energy extraction. Amount of extra energy extracted with extra brine pump on. Total energy extracted from 7 boreholes Effect of temperature and flow on energy extraction. Amount of extra energy extracted with extra brine pump on. Comparison of total energy extracted on different days. Amount of extra energy extracted opening one extra borehole. Table B1: Raw brine properties, given by Åke Melinder, Table B2: Ball and brine information for viscosity measurements. Table B3: Falling Ball Viscometer readings. Table B4: Detailed brine data Table C1: Brine flow measurement comparison, 06 March Table D1: Calculations to obtain performance curve for TOP-S 25/7,5 Table D2: Accurate flow values for ethyl alcohol, 23%-w, 5 C. Table E1: Effects of time averaging. Table G1: Sample excel spreadsheet including calculation, 11 Dec Table H1: Thermal Resistance calculations. Table I1: Trendline equations for detailed brine data Table I2: Detailed brine data Table J1: Recommended roughness values for commercial ducts [White, 2003]. 6

7 INDEX OF FIGURES Fig 1,1: Temperature-Entropy diagram of the Carnot Cycle. Fig 1,2: Temperature-Entropy diagram of a refrigerant. Fig 1,3: Two main configurations of ground source heat pumps, horizontal, vertical. Fig 1,4: Fully developed velocity flow profiles, laminar and turbulent. Fig 4,1: Schematic of borehole depths. Fig 4,2: Schematic of thermocouple mounting. Fig 4,3: Schematic of heat pump side ( hot side ) of the system. Fig 4,4: Pipe dimensions, borehole pipe on left, total flow pipe on right. Fig 5,1: Difference in Reynolds number as a function of waiting time. Fig 5,2: Difference in heat extraction values as a function of waiting time. Fig 5,3: Difference in heat extraction as a function of waiting time. Fig 6,1: Borehole 7 temperature profile at various depths and flows. Fig 6,2: Temperature profile at varying depths in borehole 7. Fig 6,3: Borehole 7 temperature profile at 15 m depth, 29 Jan Fig 6,4: Borehole 7 diagram, Reynolds number and energy extraction. Fig 6,5: Borehole 7 diagram, XX44444, 2 heat pumps + extra, flow 0,65 L/s. Fig 6,6: High heat transfer regions in borehole. Fig 6,7: Total heat extracted opening extra boreholes, 16 Feb Fig 6,8: Total heat extracted opening extra boreholes, 19 Feb Fig 6,9: Total heat extracted opening extra boreholes, 06 March Fig 6,10: Total energy extracted from boreholes, 24 hours. Fig A1: Re and energy extraction from BH7, 2HP+E, V, 05 Feb Fig A2: Re and energy extraction from BH7, 2HP+E, V, 02 Feb Fig A3: Re and energy extraction from BH7, 2HP+E, V, 11 Dec Fig A4: Re and energy extraction from BH7, 2HP+E, XX4444V, 05 Feb Fig A5: Re and energy extraction from BH7, 2HP+E, XX4444V, 02 Feb Fig A6: Re and energy extraction from BH7, 2HP+E, XXX444V, 05 Feb Fig A7: Re and energy extraction from BH7, 2HP+E, XXX444V, 02 Feb Fig A8: Re and energy extraction from BH7, 1HP+E, V, 29 Jan Fig A9: Re and energy extraction from BH7, 1HP, V, 11 Dec Fig A10: Re and energy extraction from BH7, HP, XX4444V, 11 Dec Fig C1: Re and energy extraction from BH7, 2HP+E, 19 Feb Fig C2: Re and energy extraction from BH7, 2HP+E, 19 Feb Fig A1: Nusselt number as a function of Reynolds number Fig B1: Data plot, trendline, and accuracy plot of trendline for density Fig B2: Data plot, trendline, and accuracy plot of trendline for thermal conductivity Fig B3: Data plot, trendline, and accuracy plot of trendline for specific heat Fig B4: Data plot, trendline, and accuracy plot of trendline for dynamic viscosity Fig B5: Data plot, trendline, and accuracy plot of trendline for kinematic viscosity Fig F1: Temperature profile at 5m depth, 29 January, Fig F2: Temperature profile at 15m depth, 29 January, Fig F3: Temperature profile at 75m depth, 29 January, Fig F4: Temperature profile at 160m depth, 29 January, Fig F5: Temperature profile at 5m depth, 31 October Fig F6: Temperature profile at 15m depth, 31 October Fig F7: Temperature profile at 75m depth, 31 October Fig F8: Temperature profile at 160m depth, 31 October Fig H1: Illustration of violation of 2 nd law of thermodynamics. Fig J1: The Moody chart for pipe friction with smooth and rough pipe walls. 7

8 NOMENCLATURE Notation: E energy [kw] V volume flow [m 3 /hr, m 3 /s, l/s] Nu Nusselt number [-] Q heat [kw] Re Reynolds number [-] ρ density [kg/m 3 ] v kinematic viscosity [m 2 /s] μ dynamic viscosity [Pa*s] Units: Kg kpa kw l/s m 3 /hr MVP kilo gram kilo pascals kilo watts litres per second meters cubed per hour meter-vatten-pellare (pressure below 1m height of water) Measuring Tools: ARMATEC DA system TA meter TC digital measuring instrument data acquisition system Tour-Andersson measuring instrument thermocouple Other: BH COP borehole coefficient of performance 8

9 1 INTRODUCTION 1.1 Heat Pumps A vapour compression heat pump is a system that is able to absorb heat from a lower temperature level and reject it to a higher temperature level. It consists of 4 components: the evaporator, compressor, condenser, and expansion valve. The vapour compression cycle is the same cycle used for refrigeration, the main difference being the purpose of the application, either heating or cooling [Boyle, 2005]. The ideal heat pump cycle is represented by the Carnot Cycle, shown in figure 1,1 below. Heat is absorbed at the lower temperature (T C ), compressed, and rejected at the higher temperature (T H ). There is a need for energy input, since the overall system is opposing the second law of thermodynamics which states that heat cannot naturally pass from a colder to a hotter place. Fig 1,1: Temperature-Entropy diagram of the Carnot Cycle [Wikipedia, 2006].. Energy is represented by the areas between the plotted lines. The white and pink areas combined indicate the amount of heat rejected by the system, while the pink area indicates the amount of energy required by the system. As mentioned above, a vapour compression heat pump consists of an evaporator, compressor, condenser, and expansion valve. A refrigerant circulates through the heat pump, and experiences the following transformations (see figure 1,2). At point 1, the refrigerant is a saturated vapour at low pressure and low temperature. As it travels to point 2, it becomes compressed and obtains a higher pressure and temperature level. The superheated vapour is cooled and condensed by the condenser, as it moves to point 4. Through an expansion valve, the refrigerant decreases pressure and temperature to achieve a liquid-vapour state (point 5). The refrigerant runs through an evaporator and absorbs heat from the heat source to become a saturated vapour again. 9

10 In real cycles, the refrigerant experiences an entropy increase between points 1 and 2, which results in a higher temperature superheated vapor. Fig 1,2: Temperature-Entropy diagram of a refrigerant [Wikipedia, 2006]. Considering the second law of thermodynamics, energy input is required by the system shown in figure 1,2. The energy is used by the compressor, which compresses the vapour from low to high pressure and temperature (point 1 to 2). The amount of energy used by the compressor is important in relation to the amount of energy out of the system. This is defined by the coefficient of performance. 1.2 Coefficient of Performance The coefficient of performance (COP) is valuable to understand the efficiency of the system. The COP for the ideal Carnot Cycle is defined by equation 1,1. This efficiency is never attained in practice, as there are always irreversibilities encountered, such as the loss of heat. COP carnot T1 = T T 1 2 EQ 1,1 For practical applications, COP 1 can be defined as the ratio of the heat output from the system (Q 1 ) to the operating energy of the system (E). [Granryd, 2005]. Components that consume energy include the compressor, as well as pumps to increase the flow in the system. COP 1 = Q1 E EQ 1,2 10

11 1.3 Borehole Configurations Depending on the heat demand, a ground source heat pump system consists of one or more heat pumps and boreholes. There are two main configurations of boreholes; shallow coils arranged horizontally or vertical tubes placed in the rock. It has been noted that both give in practice roughly the same heat source characteristics (roughly equal temperatures on the fluid) with the normally used dimensioning criteria. [Granryd, 2005] However, horizontal ground coils require a much larger land area, and are practical for properties such as farmland. Vertical boreholes require much less surface area, and tend to be in the order of m deep for a single-family house [Granryd,2005]. Fig 1,3: Two main configurations of ground source heat pumps; horizontal (left), vertical (right). [Natural Resources Canada, 2005] Ground condition must also be taken into consideration. The type of rock affects the transfer of heat to the borehole. Thermal conductivity values are highest for hard rock and lower for unconsolidated rock, with a difference of 1.5 W/mK between the two [Boyle, 2005]. Clearly, the rock type with higher thermal conductivity will yield a higher energy value per meter. 1.4 Laminar and Turbulent Flow The amount of heat absorbed by borehole is very much dependant on the type of flow of the brine fluid through the boreholes. Turbulent flow, characterized by random and chaotic fluid motion, absorbs more heat from its surroundings than laminar flow, where the flow progresses in a smooth and orderly manner. [Caughey et al., 2001]. When operating a heat pump system where the flow regime is laminar, a higher temperature difference is required in the boreholes compared to the same case with turbulent flow. A fully developed, incompressible flow through a pipe will have a different velocity profile depending on whether it is laminar or turbulent. Profiles are shown in figure 1,4 below. The laminar flow profile is parabolic, while the turbulent flow profile is flatter at the centre of the pipe. According to the no-slip condition, zero velocity exists at the pipe walls. The flow develops as a function of the radius, where it is fastest in the centre of the pipe, the furthest point from the wall. In turbulent flow, the existence of eddies due to velocity and pressure changes disturb the natural flow and cause the profile not to achieve the parabolic characteristic [Sabersky, 1989]. 11

12 Fig 1,4: Fully developed velocity flow profiles, laminar (left), turbulent (right) [Nuclear Power Fundamentals, 1998]. 1.5 Reynolds Number Osborne Reynolds conducted experiments and found that in general, flow transitions from laminar to turbulent following a pattern. He defined a dimensionless parameter, the Reynolds Number (Re), which is used to determine whether a flow is laminar or turbulent. The Reynolds number is a ratio between dynamic and viscous forces, as defined in equation 1.3. u avg d Re = EQ 1,3 ν where u avg = average velocity (m/s) d = diameter of pipe (m) ν = kinematic viscosity (m 2 /s) It must be noted that the kinematic viscosity, ν, is directly related to the dynamic viscosity in the following manner. μ ν = EQ 1,4 ρ where μ = dynamic viscosity (kg/m-s) ρ = density (kg/m 3 ) While operating ground source heat pumps, it is desirable to have turbulent flow through the boreholes in order to achieve efficient heat transfer from the surroundings to the brine fluid. In current pipe flow theory, it is generally accepted that the transition from the former to the latter occurs at a Reynolds number of The Moody chart is a useful chart which displays Re as a function of pipe roughness. Based on relative roughness of the pipe and Re, it is possible to see in which regime the flow lies. According to Moody, the following is true. 1 Laminar flow occurs below Re Re 2300 the critical zone begins and remains until over Re

13 3 At Re 3500 the transition zone begins and remains until over Re Beyond Re occurs completely turbulent flow All the types of flow considered in this report lie within the critical zone or the transition zone. The Moody chart can be seen in secondary appendix J. According to a study done by Björn Kyrk, the transition of flow regimes occurs at approximately Re 3000 for undisturbed flow and 2300 for disturbed flow. This value was found experimentally, by plotting the Re against the Nusselt number (Nu), a dimensionless parameter used to measure the rate of convective heat transfer. The change in gradient suggested the transition point of the flow from laminar to turbulent. This diagram can be seen in secondary appendix A. 1.6 Extracted Heat The amount of heat extracted (Q) from the borehole is of primary importance. It is characterized by the type of rock the borehole is drilled into, the activity around the hole (such as water movement), the temperature of the ground, the depth of the borehole, as well as the type of brine fluid used. The amount of heat extracted can be estimated using the following equation. Q = V ρ c T EQ 1,5 p Δ where V dot = volume flow (m 3 /s) ρ = density (kg/m 3 ) c p = specific heat capacity (J/kgK) ΔT = temperature difference (K) The temperature difference is measured between two consecutive thermocouples. 1.7 Mariehäll Heat pumps are used in many applications; industrial, commercial, as well as residential. In the residential sector, heat pump systems are commonly used to heat water for domestic use such as tap water and space heating. Space heating is achieved through floor heating or installation of wall radiators. This report deals with an apartment complex located in Mariehäll, Sweden. There were 13 units in the building. The location included a ground source heat pump system that was used to heat domestic hot water and provide floor heating. The heat pump system at Mariehäll included 2 Viessmann heat pumps and 7 boreholes. The holes varied in depth from 90 m to 170 m, and the pumps had a rated capacity of 17.6 kw each. There was an extra brine pump which, under normal conditions, ran while both heat pumps were operating. The extra pump was used to increase the flow of the brine through the boreholes when necessary. The brine used was ethyl alcohol, containing a 13

14 small percentage of additives isopropanol and n-butanol (less than 11% combined). Each borehole had a thermocouple at the top, which could read the ground temperature at the top of each borehole. Borehole 7 had seven additional thermocouples, at depths of 5 m, 15 m, 75 m, and 160 m, on both the down flow side and up flow side. The boreholes were drilled into rock that was primarily gneiss, with a small portion of silt and red granite, the first 6-12 m being silt. The rock that lay below the silt was thought to be unconsolidated, and according to borehole driller Brage Broberg, may once have been a lake [Broberg, 2006]. While drilling, ground water was met 2-4 meters deep. 14

15 2 OBJECTIVES The motivation for this research was to gain an understanding of what was occurring with the flow inside the boreholes. Once this was understood, the objective was to draw conclusions on how to run the system most effectively. The objectives of this report are clearly defined below. 1. Identify the type of flow in borehole 7 considering different flows and borehole configurations. 2. Determine the feasibility of running an extra pump loop in order to increase the Re and heat extraction in the boreholes, with one and two heat pumps running. 3. Determine the optimal number of boreholes to operate by investigating the extra heat extraction of opening one extra. 15

16 3 METHODOLOGY 3.1 Step 1 The first objective was to identify the nature of the flow in borehole 7. This was done by investigating the power output of the boreholes at varying Re-values and pressure drops, with different borehole combinations. Both two and one heat pumps were running, in conjunction with the extra brine pump. The following steps were conducted in order to obtain required results. a) Take a sample of brine for composition testing. b) Measure how the temperature in the boreholes changes, and when it stabilizes after turning off the circulation. Measure ground temperatures with no borehole circulation. c) Investigate the energy out of the boreholes (W/m) and how it changes with different Re-values, in order to estimate the spread of swirling, turbulent and laminar flow. 3.2 Step 2 The second step was to investigate the difference in total energy out of the borehole with and without the extra brine pump running, in the case of both one and two heat pumps in operation. This addressed the feasibility of running the extra pump loop to extend the length of turbulent flow in the boreholes. The following steps were taken. d) Close different number of boreholes and compare how large the power output is with one vs. two heat pumps running, with and without the extra pump running. e) Investigate the output energy from the borehole vs. the heat pumps, and estimate how many boreholes ought to be operating so that the extra pump circulation in the boreholes will be profitable. 3.3 Step 3 Next, it was necessary to optimize the number of boreholes operating. This was done by studying how large the energy contribution from opening one extra borehole became. The total COP of the system was examined. f) Study the power out from one vs. two heat pumps, with different numbers of boreholes open. Compare the difference when an additional borehole is opened. g) Examine COP TOTAL with and without the extra brine pump running. 16

17 4 EQUIPMENT 4.1 Technical Details The system at Mariehäll contained the following equipment at the noted specifications. 2 Viessmann Vitocal 300 heat pumps, rated power 13-17,6 kw 2 WILO TOP-S 25/7,5 brine pumps 1 WILO IPL 50/115-0,75/2 extra brine pump (750 W) 7 STA-D 40 valves 3 water tanks Note that the heat pumps were connected in parallel. The boreholes were also connected in parallel, and borehole 2 consisted of 2 boreholes. The boreholes were not drilled directly perpendicular into the ground, but rather on a slight angle of o. This was to avoid as much contact with each other as possible, as it could have affected the heat transfer and temperature difference in the boreholes [Hill, 2006]. The depths included in table 4,1 are the absolute lengths of the boreholes. Borehole # Depth (m) Fig 4,1: Schematic of borehole depths. Table 4,1: Borehole depths There were three water tanks that were kept at different temperatures, one used for floor heating, another for domestic hot water, and the third as an accumulator tank. The heating priority was to the floor heating first, and secondarily to the hot water tank. The floor heating tank was maintained up to 50 o C, so that floor heating could be provided at 30 o C (the difference was due to losses in the circulation system). The domestic hot water tank was kept at a maximum of 65 o C. 17

18 The system contained 12 active thermocouples (TC), measuring temperature at the following locations. A comprehensive diagram is presented in figure 4,3. TC1-5m deep on the down-flow side of borehole 7 TC2-15 m deep on the up-flow side of borehole 7 TC3-75 m deep on the down-flow side of borehole 7 TC4-160 m deep in borehole 7 (AFTER the bend) TC5-75 m deep on the up-flow side of borehole 7 TC6-15 m deep on the down-flow side of borehole 7 TC7-5 m deep on the up-flow side of borehole 7 TC8 - exit of borehole 7 TC9 - just before the extra brine pump TC10 - just after the extra brine pump TC11 - at the entrance of borehole 7 TC12 - after the heat pumps, before entrance into the boreholes Fig 4,2: Schematic of thermocouple mounting. A diagram of the thermocouple mounting is seen in figure 4,2 thermocouple. The thermocouples were mounted on the outside of the pipe (excluding thermocouples 8 and 11 which were on the inside). They were covered with a thin layer of aluminium foil, followed by 2 cm of insulation. The outermost layer was outer piping which had been shrunk to fit the form of the bulge, and to keep the thermocouple tightly placed. The distance from the centre of the thermocouple to the end of the insulation along the borehole wall was 20 cm. In other words, the pipe was insulated for 40 cm wherever there was a thermocouple. Since the thermocouple mounting took up space, the thermocouples of the same height level were offset by at least 40 cm. Measurements were taken by opening and closing certain boreholes, as well as adjusting the flows in the boreholes, focusing on borehole 7. Experiments were defined with a 7-digit notation, such as XXX444V. The letters and numbers represented boreholes 1 through 7 respectively, from left to right. An X denoted that the borehole was fully closed. A number (1-4) denoted the STA-D 40 valve position of that borehole. A V denoted variable, where the borehole valve position changed throughout the experiment. In the case mentioned, XXX444V, boreholes 1, 2, and 3 were closed, while boreholes 4, 5, and 6 were fully open. Borehole 7 had a varying valve position. 18

19 4.2 Practical Background The first step was to learn about the system; the arrangement of the system and how to take measurements. A schematic of the borehole side of the system is presented below in figure 4,3. Fig 4,3: Schematic of heat pump side ( hot side ) of the system. The brine exited the boreholes into a common pipe of approximately 74 mm inner diameter. The extra brine pump was located before the heat pumps and allowed the flow to go through, whether it was on or off. The flow continued to the slave heat pump, then the master heat pump where the heat was extracted. Upon exiting the heat pumps, the brine continued along a common pipe, and flowed into the seven boreholes, with borehole 7 first. Since the boreholes were of different lengths, they had unique pressure drop and volume flow values. At the exit of each borehole, there was a STA-D 40 valve which was rotated from position 0 to position 4, where 4 meant fully open. The valve controlled the pressure in the borehole, and consequently, the flow. As the brine flowed up the pipe, it changed from high pressure to low pressure upon passing the valve. There were two measuring points located here, one which read high pressure flow (red) and the other reading low pressure flow (blue). 19

20 4.3 Pipe Dimensions The piping was PVC, and pipe dimensions were as shown below. The first figure refers to the borehole piping, while the second refers to the pipe containing the total flow. Fig 4,4: Pipe dimensions, borehole pipe on left, total flow pipe on right. 4.4 TA meter One method of measuring the pressure difference over the boreholes and the volume flow through each respective borehole was by using a TA-CMI meter, supplied by Tour and Andersson. It contained a high and a low pressure sensor which were hooked up to the system. The TA meter was calibrated with STA-D 40 type valve, brine concentration of 22.8% by weight, and varying valve positions and brine temperatures. It is important to note that the TA-CMI meter was inaccurate when the pressure drop is less than 3kPa (error of 30%). When the pressure drop was more than 3kPa, the error could have been greater than 10% [Sednert, 2006]. 4.5 Data Acquisition System The brine flow was also measured with a flow meter which recorded the number of litres passing through the pipe in a set increment of time in borehole 7. This data was recorded by a data acquisition system (DA system), along with the thermocouple readings, the amount of time passed, and whether the heat pumps were on or off. This method was the most accurate and reliable way to measure volume flow. 4.6 Heat Pump Control For the purposes of this investigation, the heat pumps were manually controlled using the control panel. The primary control was of the master heat pump. The master and slave pumps, as well as their respective compressors, were turned on and off. The Viessman software, Vitocalc, was a good background to understand the workings of the heat pumps. With Vitocalc, the performance of the heat pumps could be observed under different conditions such as brine temperature or pump power. 20

21 5 EXPERIMENTAL UNCERTAINTIES 5.1 Errors in Volume Flow The total volume flow running through the heat pumps was calculated using 3 different methods; the TA meter, data acquisition system, and the WILO CD. The three methods were compared to observe the errors between them Flow Measurement Methods The flow measured by the data acquisition (DA) system was the most accurate. It gave a pulse each time one litre passed through. It was situated at the exit of borehole 7, thus it was able to read only the volume flow of borehole 7. Values were collected and displayed on a computer. The TA meter directly read the volume flow through the STA-D valves on each borehole exit. Although it read the values to three decimal places, there was a lot of noise when trying to obtain the data. As much as 0,5 m 3 /hr of noise was present. The total flow was obtained by adding the separate volume flows together. By measuring the pressure drop over the extra brine pump, and the two small WILO pumps, the total flow was determined. The WILO CD provided performance curves for each pump, based on the properties of the liquid used (concentration and temperature). The liquid defined was ethyl alcohol with concentration of 23%-weight, and 5 C as the most commonly used temperature. The performance curve would read flow (m 3 /hr) on the x-axis, and pressure head (m) on the y-axis. Sven Franzén of WILO Sverige AB quoted an error of +/- 5% for the performance curves [Franzén, 2007]. Determining the total volume flow with the two small WILO pumps was more difficult than for the large extra pump. The performance curve available for the small pumps was for water at 20 C. Using another pump, values for water at 5 C were obtained, as well as ethyl alcohol at 5 C, 23%w. These values were used to estimate the performance curve of ethyl alcohol for the appropriate pump. Details are found in secondary appendix D. This was a large source of error Flow Comparison A comparison between the three flow methods was conducted, the results seen in table 5,1 below. Four cases were considered, with 7, 6, 5 and 4 boreholes open. The flow from each borehole was taken using the TA meter. Simultaneously, the DA system recorded the flow through borehole 7 (the most accurate flow reading). The total flow was found by applying the same difference between the DA system s reading and the TA meter for borehole 7 to all the borehole readings from the TA meter. The WILO CD was used to obtain total flow from the pressure drop over the extra brine pump. 21

22 Flow (m3/hr) BH1 BH2 BH3 BH4 BH5 BH6 BH7 TOTAL % Accuracy TA meter 2,31 2,37 2,42 2,35 2,36 2,11 2,07 16,00 0,98 DA system 2,36 2,42 2,47 2,40 2,41 2,15 2,11 16,32 1,00 WILO 21,10 1,29 X m3/hr TA meter 2,54 2,65 2,50 2,36 2,19 2,21 14,46 0,99 DA system 2,56 2,67 2,51 2,38 2,21 2,22 14,56 1,00 WILO 17,00 1,17 XX m3/hr TA meter 2,63 2,56 2,42 2,39 2,27 12,26 0,97 DA system 2,71 2,64 2,49 2,47 2,34 12,65 1,00 WILO 14,60 1,15 XXX m3/hr TA meter 2,70 2,57 2,41 2,26 9,94 0,94 DA system 2,87 2,73 2,56 2,40 10,55 1,00 WILO 14,30 1,36 Table 5,1: Error analysis of total brine flow calculation methods. The highlighted column shows the percent accuracy of the total flows, as compared with the DA system. The TA instrument was fairly close, with 94% - 99% accuracy. The results from the WILO CD had significantly more error, in the range of 15% - 36 % error. This error was very large, and consequently the calculations were performed using the other methods wherever possible. In the case of no extra pump running, the WILO CD had to be used because flows were too low to be read by the TA meter. Readings from the WILO CD could be the cause of some strange results found in further sections. The same investigation performed on another occasion can be seen in secondary appendix C. 5.2 Time Error Time Error It took approximately 7 minutes for the brine to circulate once through the entire system [Hill, 2007]. After making a change to the system, the amount of time required to wait was important, in order for the system to stabilize and achieve a steady state once again. The case of was considered. A measurement was taken 20 minutes after changing the system from A second measurement was taken 55 minutes after the change. Figures 5,1 and 5,2 display the results. 22

23 Reynolds Number: ,0 Re Thermocouple Location T=20 min T=54.7 min Fig 5,1: Difference in Reynolds number as a function of waiting time. Heat Extracted per Meter: ,0 Q (W/m) Sections along borehole T=20 min T=54,7 min Fig 5,2: Difference in heat extraction values as a function of waiting time. Re was found to have increased by approximately 250 for the second measurement. This change was very small, and did not influence the energy extracted energy per meter significantly, seen in figure 5,2. The total energy extracted was 783 W for the first case, and 803 W for the second case, a difference of only 20 watts. It could be concluded that a 20 minute waiting period between measurements was sufficient time for the system to stabilize, without significantly altering the data. All data was taken with at least 20 minutes waiting time. In contrast, the same study was conducted for a 15 minute waiting period. The energy extracted per meter varied significantly, especially for the first and last sections of the borehole. The difference was as high as 20 watts per meter, resulting in the total heat extracted to be 180 W higher for the longer waiting 23

24 period. This is viewed in figure 5.3 below. Re had no significant difference for the two cases. It was concluded that a 15 minute waiting period was too short. Energy Extracted per Meter: , Energy Extracted (W/m) T = 16 min T = 52 min -55 Section along borehole 7 Fig 5,3: Difference in heat extraction as a function of waiting time Averaging Temperature Values To investigate the signal noise on the temperature readings, the average of 7 consecutive temperature readings was taken. It was repeated in several cases, and was found that the difference between logged values and averaged values was between 0,01 C to 0,03 C. Further values are included in secondary appendix E. The difference was insignificant for the purposes of this report. 5.3 Other Errors The amount of energy extracted from the boreholes was a function of how much heat the heat pumps require. This effected the data taken, and could not be controlled. The weather and habits of tenants affected the data collected. The ARMATEC instrument took power measurements (kwh) once every 2 minutes and 10 seconds. Having 20 minutes between readings meant that errors would be 10%. This was eliminated by taking kilowatt-hour values over a 24-hour period. Results can be seen in section 6.6. The temperature measurements taken by the ARMATEC would fluctuate minimally. The flow and energy measurements would fluctuate significantly, often as much as 3%, and a middle value was taken. The thermocouples were offset from each other along the pipes, so they could fit into the boreholes. The shortest possible distance between thermocouples 24

25 was 40 cm, while the longest could have been 1 m. This distance could have had a significant impact for the readings in the first 5 m of borehole 7. All thermocouples (except for TC8 and TC11) were placed on the outside of the pipe and covered with aluminium foil, 20 mm of insulation, and finally outer piping. Thermocouples 8 and 11 were placed inside the pipe, and thus gave the most accurate temperature readings. Thermocouple 4 was situated after the bend at the bottom of borehole 7. The velocity profile through the pipe varied depending on where the flow was. It could have been laminar and fully developed, not fully developed, heavily swirling, or perhaps turbulent. The temperatures read by the thermocouples were the temperature close to the wall, not the average temperature. The temperature profile of the flow was not considered. This may have had an effect on temperature readings. The uncertainties using the TA instrument were high. If the pressure was below 3kPa, the error was as high as 30% [Sednert, 2006]. The flow and pressure values would fluctuate by as much as 20%, and a middle value had to be taken. The time between each measurement was 20 minutes. The results of a having a longer waiting period are discussed in section above, and concludes that 20 minutes was sufficient waiting time between measurements. While the flow may have stabilized, the ground may have needed a longer time to stabilize. This could have had an effect on data taken. It must be noted that all data was taken in different orders to eliminate coincidental errors. Data was taken in one direction, then the reverse direction, and sometimes in random order as well. 25

26 6 RESULTS 6.1 Brine Properties The specific properties of the brine were obtained by taking a sample of the brine, obtaining its density at a specific temperature using a mercury meter, and finally inputting this data into a spreadsheet composed by Åke Melinder, a lecturer at KTH researching property trends of fluids. The brine solution used was ethyl alcohol with ethanol concentration of 22,84% by weight, and freezing point at -13,5 o C. Additives were n-butanol (2%) and isopropanol (7-9%), as specified by the supplier Masons Kem. Tekn. AB. The properties at seven different brine temperatures were determined, and graphs were composed of these properties as a function of the brine temperature. A trendline was fitted to each graph, and all were found to fit with greater than 99% accuracy. The trendline equations were used to interpolate more detailed brine properties, which were used for further calculations. The graphs, trendlines, equations, and specific brine properties can be found in secondary appendix B. The additives in the brine, namely isopropanol and n-butanol, composed as much as 11% of the solution. The brine properties described above were determined based on values that considered no additives. Viscosity tests were conducted to check the accuracy of the calculated brine properties. The dynamic viscosity of the brine was compared with the dynamic viscosity of an ethyl alcohol solution of 23 %-weight concentration, at 20 o C. The ethyl alcohol had a higher viscosity than the brine solution. The values are shown in Table 6,1. The similarity between the measurements was found to be 83%, making the error 17%. Dynamic Viscosity μ (mpa*s) Ethyl Alc. Brine %difference 2,40 1,98 0,8261 Table 6,1: Viscosity comparison between brine and ethyl alcohol 23%weight. The dynamic viscosity of the ethyl alcohol solution was 100% in accordance with the values given by Åke Melinder. It must be noted that the brine concentration was changed in November The concentration was reduced from 27%-weight to 23%-weight, in order to increase the Re values. The change resulted in a 20% decrease in kinematic viscosity, and a 2% increase in specific heat of the brine fluid in the temperature range considered. This lead to increased Re values. 26

27 6.2 Ground Temperatures Ground Temperature Plots of the temperature in borehole 7 at different height levels running at various flows can be seen in figure 6,1. Note that the legend refers to the valve rotation position of borehole 7, and there was only 1 heat pump running. Temperature Profiles as a funtion of depth, BH7, XXXXXXv 4,5 4 3,5 Temperature (deg C) 3 2,5 2 1,5 1 0, Length travelled in borehole (m) Position 3 Position 2 Position 1 Fig 6,1: Borehole 7 temperature profile at various depths and flows. The temperature constantly rose until reaching the 15m thermocouple on the way up. There was an abrupt heat loss experienced at this point, which was unexpected. Concurrently, the first 15 m absorbed very much heat. As the valve was adjusted from position 1 to position 3, the temperature profile in figure 6,1 was seen to increase. Position 3 produced a lower pressure drop across the borehole and higher volume flow. Higher flow resulted in less heat being transferred from the ground to the borehole, thus the ground temperatures remained at higher values. Borehole 7 was closed for more than two days in order to obtain an accurate measure of the ground temperature at the different thermocouple levels. The temperature profile taken in October 2006 and again in January 2007 can be seen in figure 6,2 below. The x-axis denoted the length that the fluid had travelled in the pipe, and it must be remembered that the deepest length was 160m after which the flow turned and flowed back up. The total difference of temperatures thorough the length of the borehole was 1 o C to 2 o C. 27

28 Ground Temperatures, Borehole 7 Temperature (deg C) Distance along Borehole 7 (m) 19-Feb 24-Oct Fig 6,2: Temperature profile at varying depths in borehole 7. By comparing the plots, it was seen that the ambient temperature affected the borehole temperature as deep as 75 m into the ground. Snow and frozen ground also may have had an effect. In October, the borehole temperatures were much warmer for the first 75 m, exceeding the temperature of the deepest part of the borehole by almost 1,5 o C. In January, the temperature profile increased and decreased by less than 0,5 o C from ground level to 75 m deep. From the 75 m point, the trend was the same for both cases, with temperature increasing until 160 m, and decreasing on the route back up Stabilization Time After turning off the circulation, it was noted how the temperatures at each level of borehole 7 behaved. In theory, the temperatures of the same levels should have met each other. At all ground depths, the temperatures of the down and up flow at the same level met each other within the first minutes. Deeper levels took longer time to reach the same temperature. During operation, the ground temperatures on the down-flow side were lower than that on the up-flow side, this could have been due to the thermocouple offset. Within 30 minutes or less, the temperatures met each other, and the down-flow side obtained a higher temp than the up-flow side, about 0,1 o C. The temperatures on both sides continued to rise, but the rate that they did so was approximately the same. The case at 15 meters depths can be seen in figure 6,3. Refer to secondary appendix F for corresponding plots at other depths. 28

29 Stabilization Time, 15m, T2 & T6 Temperature (deg C) T6 T Time (min) Fig 6,3: Borehole 7 temperature profile at 15 m depth, 29 Jan This comparison was a good method to check the accuracy of the thermocouples. The thermocouples of the same height should have tended towards the same temperature after some time, which they did do. This suggested that there was no break or error in the thermocouple readings. 6.3 Flow Regime in Borehole 7 The flow through borehole 7 was examined via 7 thermocouples placed in the borehole as described earlier. The objective was to examine the behaviour of the flow within the boreholes, in order to optimize the flow to extract the most energy from the hole with the least power input. Higher volume flow corresponded to higher Reynolds number. This in turn yielded more energy extracted from the boreholes. The pressure in the borehole was inversely proportional to the flow, thus when the flow increased the pressure consequently decreased. Consider the case XX44444 with 2 heat pumps and the extra pump running, shown in figure 6,4. The STA-D valve for borehole 7 was open to 0,5 in the first case (red) and 1,0 in the second case (green). The Re values increased as the flow travelled along the borehole. They continued to increase until they reached the 5m level on the up-flow side, where they decreased slightly. The temperatures followed the same trend, as Re values were directly proportional to the temperature readings. It was interesting to note the decrease of temperature in the last section of the borehole. 29

30 Fig 6,4: Borehole 7 diagram, Reynolds number and energy extraction. 30

31 Energy extracted from the borehole was directly related to the temperature difference between thermocouples. The temperature difference on the downflow side was greater than the temperature difference on the up-flow side by a few tenths of a degree. This could be due to the thermocouple offset. The difference between temperatures is generally 0,2 o C to 0,5 o C. It can be seen that the energy extracted decreased as the flow travelled down the borehole. After turning 180 o to travel back up, the flow extracted much more energy. The energy again decreased on the path up the borehole, becoming negative for the final section. It is of interest to note that after the bend (160 m deep), the extracted energy was significantly higher. Consider the case in figure 6,5. The energy extraction values were average values taken over the length of the section. The bottom most section was 85 m long, which was a significant length to average over. If one considered the energy extraction in the previous section of borehole 7, assumptions could be made as to a probable heat extraction value (seen in red). Please note these were not calculated figures, rather rough estimates. On the down-flow side, Q must have been much higher than 4,7 W/m close to 75 m depth, and much lower closer to 160 m depth, following the decreasing trend. On the opposite side, the converse was true. Focusing on the bend, it was clear that there was significantly more energy extraction after the bend than before it. This suggested turbulence. Fig 6,5: Borehole 7 diagram, XX44444, 2 heat pumps + extra, flow 0,65 L/s. Following research by Björn Kyrk, for all cases that had Re over 2000, the trend described above was seen in regards to the behaviour of the flow. The remaining cases followed a trend where heat extraction continued to decrease as the flow moved along the borehole. It was difficult to note when precisely 31

32 the trend changed. Without the extra brine pump in operation, Re was less than With the extra brine pump in operation, Re was greater than Thus, it was unclear exactly when the transition in behaviour occurred. For the first fifteen meters of the borehole on the down-flow side, the amount of energy extracted per meter was very large. This could have been due to turbulent flow as a result of the bends in the pipe coming from the building. In the same region on the up-flow side, the energy extraction values were negative. Negative values denoted heat dispensed to the surroundings rather than being absorbed by the brine. This was seen in 100% of the cases. Why there was so much heat absorbed and dispensed within the first fifteen meters was an interesting point to consider, and will be further discussed in section 7.3. There was more energy lost with higher Reynolds numbers. This was due to increased flow. The regions of highest heat transfer are detailed in the figure to the left. The inlet and exit of each borehole had the potential to loose energy due to the disturbed nature of flow in the pipes. The 85 m section after the bend gained much energy. This energy gain was continued up to the next section. How far it travelled was a function of Re. Fig 6,6: High heat transfer regions in borehole. Following the flow on the down-flow side, the energy extraction value decreased. This suggested transition from turbulent to laminar flow. Cases considering the following variables can be seen in appendix 1. 1 varying STA-D valve positions (0,5 through to 4) 2 one or two heat pumps functioning 3 with and without the extra pump running 6.4 Effects of the Extra Brine Pump The effect of the extra brine pump was determined by investigating the amount of energy extracted from the boreholes while it was functioning and while it was off. The flow played a critical role as it was directly proportional to the amount of energy extracted. The temperature difference between thermocouples was also a large influence. 32

33 The total flow was obtained by noting the pressure drop across the extra brine pump. When this pump was off, the flow was found by the pressure drops over the small pumps at the entrance of each heat pump. The pressure-head versus mass flow curves provided by the WILO CD were used to estimate the total mass flow across the pumps. Errors in this method are discussed in section 5.1. Various cases were considered, with different numbers of boreholes in operation. Data was obtained in varying orders, to eliminate the possibility of systematic errors One Heat Pump The results using 1 heat pump with and without the extra brine pump can be seen in table 6,1. Three separate cases were considered. The energy extracted from the boreholes with the extra pump was less that that extracted without the extra pump, as seen by the highlighted values. This result was curious, and will be further investigated in the discussion section. With the extra pump running, the flow was higher (approximately twice as fast), while the temperature drop across the system was substantially lower (2 to 5 times in magnitude). It must be noted that the energy values with and without the extra pump were very close to one another. Errors in flow estimates could have played a significant role in calculated energy values. The energy extracted from borehole 7 was greater with the extra heat pump operational, as can be seen in the third column in table 6,1. This gave an indication that perhaps flow values had a large effect on Q values, a larger effect than the temperature difference. Diagrams of the flow and energy extracted in borehole 7 for this case can be seen in appendix 2. pumps case ΔT (t9-t12) Total Flow TC 5 BH 7 BH total (deg C) (L/s) (deg C) P (kw) P (kw) HP+extra XX XXX HP XX XXX Table 6,1: Energy extracted from boreholes with 1 heat pump. The results seen are a function of the temperature difference between the ground and the brine, as well as the number of boreholes open. The total flow values for 1 heat pump are the same due to the pressure drop (MVP) over the small pumps on each heat pump. The same pressure drop yielded the same total flow value based on the pump s performance curve. 33

34 6.4.2 Two Heat Pumps When two heat pumps were operating, the result was different. Highlighted values in table 6,2 showed that more energy was extracted when the extra brine pump was operational. With the extra pump running, the flow was approximately 1,5 to 2,5 times faster than without the extra pump. The temperature difference across the system was approximately the same in magnitude, but slightly lower. This indicated that while the flow was higher with the extra brine pump on, the temperature difference caused by the flow was the important factor to be considered. The temperature difference would help to conclude whether the extra pump should be operated. pumps case ΔT (t9-t12) Total Flow TC 5 BH 7 BH total (deg C) (L/s) (deg C) P (kw) P (kw) HP+extra XX XXX HP XX XXX Table 6,2: Energy extracted from boreholes with 2 heat pumps. In the case seen by table 6,2, the faster flow induced by the extra brine pump increased energy extraction by 3-10%. In other words, 1 2,5 kw extra were extracted with the extra pump on. The extra pump operated at 750 W, indicating that the net energy extracted was larger with the extra pump on rather than without. A few days were allowed to pass between taking data with the extra brine pump on and with it off. The objective was to note if there was any error due to ground temperature instability. Perhaps the ground temperatures had not had enough time to stabilize between readings when there was only 20 minutes between measurements. The results can be seen in appendix 2 and show that there was no significant difference between the two readings. 6.5 Effect of Opening One Extra Borehole There was more energy extracted from the system when more boreholes were open. The most energy should have been extracted when all 7 boreholes were open. The aim was to see how much more heat was extracted by consecutive boreholes being opened. In order to reduce errors, the data was taken starting with 2 boreholes open and opening 1 more consecutively, as well as the reverse direction (7 boreholes open, closing 1 consecutively). Consider the case shown in figure 6,7. The amount of energy extracted increased as more boreholes were open, as was logical. It can be seen that the most drastic change occurred between having two and three boreholes open. The amount of extra energy extracted in this case was 13 kw. The energy extracted in the other cases ranged between 1,5 5 kw. There was 34

35 no pattern where opening a consecutive hole yielded a lower or higher amount of extra energy than opening the next one. This was perhaps due to the varying depths and flows of the boreholes. Energy extraction differences are shown in appendix 3. The reasons for such high energy extraction opening 2-3 boreholes were as follows. There was almost 50% more borehole surface area to absorb energy. In addition, the pressure head over the extra pump was high for this region. The performance curve was flat in regions of high pressure head, and dropped significantly thereafter, following a fairly consistent trend. The pressure heads recorded in these cases fell in this region of the performance curve. Heat Out as a funtion of number of boreholes open 30 TC5 ( o C): 3,24 3,80 3,81 4,46 4,53 Heat Out (kw) Q Number of Boreholes OPEN Fig 6,7: Total heat extracted opening extra boreholes, 16 Feb The same trend can be seen in figure 6,8 below. It is curious to note the temperature drop when a 6 th borehole is opened. Referring to the borehole diagram in appendix 3, it can be seen that Re and the heat extracted from borehole 7 were higher with 5 boreholes open than with 6. This meant that borehole 7 was consistent with the trend (total energy out increased when more boreholes are open). The other boreholes must have been contributing to the loss of energy in this case. A similar case can be seen in the second figure below. 35

36 Heat Out as a function of number of boreholes open 30 TC5 ( o C): 4,30 3,97 4,59 4,48 5,11 4,98 Heat Out (kw) Q Number of Boreholes OPEN Fig 6,8: Total heat extracted opening extra boreholes, 19 Feb Heat Out (kw) Heat Out as a function of number of Boreholes open (2HP + E) TC5 ( o C): 4,35 4,70 4,95 5, Number of Boreholes Open Q Fig 6,9: Total heat extracted opening extra boreholes, 06 March Although there are some exceptions, the general trend was that the total energy out increased when more boreholes were open. Surely, the two graphs above must be exceptions. Perhaps the system did not reach equilibrium between measurements which yielded inconsistent results. Consecutively opening (or closing) one more boreholes requires more research to be done, with more time in between measurements to assure the system obtains equilibrium. 6.6 Total COP In order to obtain an accurate COP total, measurements were taken with a 24 hour waiting period. The difference in kwh recorded by the ARMATEC corresponded to the amount of energy output from the heat pump system. The difference in kwh recorded by the electrical meter corresponded to the amount of energy input into the system as well as the lights and computer. 36

37 The first law of thermodynamics states the conservation of energy for a closed system. In other words, EQ 6,1 Q = Q E out in + The values obtained from the ARMATEC should have equalled the amount of energy from the heat pumps plus the energy used to run the compressor. Losses were considered insignificant and were ignored. The results were as shown in table 6,3 below. The COP total was interesting to note. The energy values (in kw) were an hourly average over a 24-hour period. The actual energy fluctuated between kw with 2 heat pumps running, and kw with one heat pump running. There were 2 cases considered. The system was not running continuously, rather, the heat pumps turned on and off to meet the demand. There could have been 2 heat pumps running, or 1 heat pump, or no heat pumps at any given time. The cases examined differed as follows. In the Normal case, the extra pump was on when 2 heat pumps were in operation. In the No Extra case, the extra pump was off when 2 heat pumps were in operation, in other words, the extra pump was never on. NORMAL NO EXTRA El Meter kwh ARMATEC kwh COP Table 6,3: Total COP, with and without extra brine pump. In table 6,4 below, the amount of time that each heat pump ran over 24 hours can be seen. It is clear that both heat pumps ran for longer time in the Normal case. This means that they also extracted more energy as is seen in table 6,3 above. The electrical meter also used more energy. The total COP was lower in the normal case. This is curious, since it was established earlier that when 2 heat pumps run with the extra pump, they extracted more energy than without the extra pump. The amount of extra energy was more than the energy required to run the extra pump. It would be logical that the Normal case would have a higher COP than the No Extra case. This is not what was seen, and further testing must be done. The results could be due to the fact that the brine temperature was higher with the extra pump operational, which meant that less total energy would be extracted from the ground, since the difference between brine and ground temperatures would be smaller. NORMAL NO EXTRA Right HP minutes Left HP minutes Table 6,4: Running time, with and without extra brine pump. Time intervals of 15 minutes were taken to construct the graph seen below. The system was running under normal conditions, with 7 boreholes fully open. 37

38 The extra pump ran when 2 heat pumps were operating, and was off when only 1 heat pump was in operation. Data was recorded every minute. From this data, it was seen that the system was on for minutes at a time (generally between minutes), and off for roughly the same amount of time. When the system was running, both heat pumps were in operation; however the slave heat pump usually turned off approximately 5 minutes before the master. Total Energy Out, 24 hours, Normal Operation 30 Energy Out (kw) Q Time (hours) Fig 6,10: Total energy extracted from boreholes, 24 hours. When 1 heat pump was in operation the flow was 1,3 l/s, while with 2 heat pumps and the extra pump running the flow was 5,6 l/s. It must be noted that the flow changed with the changing brine temperature, but the effects of this were so small that they were negligible (less than 0.01 m3/hr for 5 degrees change). Since the temperature difference was less than 2 degrees, the flow value was assumed to be constant while the pumps were working. The COP total was calculated again based on average hourly values from the graph constructed (table 6,5). The COP total found in this case was lower than that seen in the previous section. This can be attributed to averaging errors. The graph uses one data point each 15 minutes within the 24 hour period. Graph Avg kw Elec meter 5.71 kw Difference: 8.54 kw COP: 2.50 Table 6,5: Total COP, with extra brine pump. Although the system was running under normal conditions, the outdoor temperature greatly effected the operation of the system. During measurements, the ambient temperature was between -2 o C to +4 o C. Under colder conditions such as -10 o C or less, the system would operate for longer periods off time, and consequently extract more energy from the ground. 38

39 7 DISCUSSION 7.1 Brine Properties The brine solution used was ethyl alcohol with ethanol concentration of 22,84% by weight, and freezing point at -13,5 o C. Additives were n-butanol (2%) and isopropanol (7-9%), as specified by the supplier Masons Kem. Tekn. AB. Detailed brine properties were interpolated using values for ethyl alcohol 23%- weight concentration, given by Åke Melinder. Additives were not considered. Viscosity tests were conducted to observe the effect of the additives on the brine properties. The dynamic viscosity of the brine was compared with the dynamic viscosity of an ethyl alcohol solution of 23 %-weight concentration. The error was found to be 17%. Calculated values were altered accordingly. 7.2 Ground Temperature The ground temperature was determined by analyzing temperatures in borehole 7 with no circulation running through the borehole for more than 48 hours. Two sets of data (taken in October 2006 and January 2007) corresponded with each other from 75 m and deeper. The highest temperature was at the bottom of borehole 7, 160 m deep. Above 75 m, the ground temperatures increased in the case of October, and decreased in the case of January. This was due to ambient conditions. With flow circulation, the temperatures in borehole 7 were considered. When flow values were higher, the borehole temperatures were higher. The same trend was seen for various flows. The borehole temperature increased rapidly for the first 15 m, dropped slightly at 160 m deep, and dropped quite drastically for the last 15 m. These results are consistent with the energy extraction seen in sections above. The time it took for the ground temperatures to stabilize after circulation was turned off was minutes. The amount of time to stabilize was proportional to the depth. The deeper parts took longer to stabilize. After stabilization, the ground temperatures on the up-flow side were lower than those on the down-flow side by approximately 0,1 C. This could have indicated errors in the thermocouple mounting. It could also have been the result of the thermocouple location, as the thermocouples of the same level were offset by 0,4-1 meters. 39

40 7.3 Flow Regime in Borehole Meter Depth In the majority of cases, there was much more energy extracted by the brine after the bend at the bottom of the borehole, 160 m deep. The absorption of extra heat suggested a change in the type of flow existing in the pipe. It was suggested that the bend caused the flow to become turbulent, and thus through its random and sporadic motion absorbed more heat [Beaumont, 2006]. It can be agreed that something happened to the flow after the bend. It experienced disturbance which caused it to lose some of its laminar properties, such as the laminar profile. The amount of energy extraction suggested turbulent flow. Alternatively, it perhaps had begun a swirling motion, and absorbed more heat from the surroundings due to heavy swirling. Palne Mogensen, an experienced heat energy consultant suggested that the flow was heavily swirling but somewhat predictable, rejecting it as turbulent. The behaviour described in the paragraph above was not seen for flows with Re lower than The flows in this Re range were considered laminar. Although the 180 bend caused disturbance in the flow, the flow mostly maintained its laminar properties. The brine was not travelling fast enough to cause significant disturbances while passing through the bend, and consequently the energy absorption trend was consistent with the rest of the borehole. While the Re range where transition occurred was not precisely seen, in can be concluded that it occurred somewhere between Re 2000 and First 15 Meters The first fifteen meters of borehole 7 were puzzling. There was a lot of energy absorbed by the brine on the down-flow side, and much energy dissipated on the up-flow side. The energy values per meter were much higher in this section compared with any other section, often more than four times in magnitude. Consider the down-flow side. Since the flow was coming from the heat pumps, it experienced some disturbances in the form of pipe bends, which may have caused flow disturbance and extra energy uptake as a result. Although a factor, this was not the main contributing cause. The thermocouples were not placed exactly 10 meters apart. As described in section 5, the thermocouples could be offset as much as 1 meter. Considering a total length of 10 meters between thermocouples, this offset could have a significant effect on the energy values. Looking at the up-flow side, there was much energy dissipated from the brine to the borehole and surroundings. Some heat may have been absorbed by the down-side, resulting in a thermal shortcut; however this was not where most of the energy went. Calculations of heat transfer and thermal resistances suggested that the energy could not possibly be lost through a thermal shortcut, as this would violate the second law of thermodynamics. Refer to 40

41 secondary appendix H for detailed calculations. Most of the energy seemed to be lost to the surroundings. The amount of energy lost was directly proportional to the brine flow. Higher Re yielded more energy loss. The ground temperature was close to the brine temperature, which facilitated energy dissipation. The precise length over which energy loss occurred was unknown. Higher Re resulted in a longer length of energy loss. It was known that energy was lost within the first 15 meters, after that the length of energy loss was a function of Re Turbulent to laminar transition The energy extraction on the down-flow side of the borehole consistently decreased, even though Re was increasing. This occurred with Re as high as After the bend, there was a significant increase in energy extraction. This suggested transition from turbulent to laminar flow on the down-flow side. Although the difference between ground and brine temperatures had an effect on the amount of energy absorbed by the system, having turbulent flow yielded a larger effect. Turbulent flow is desired through the boreholes. 7.4 Effects of the Extra Brine Pump In the case of a single heat pump, there was less energy extracted from the system without the extra brine pump running compared to with it. The amount of extra heat extracted was in the range of 1,4-4 kw. Errors in flow could have had a significant effect with energy calculations. The flow was obtained by reading pressure drops over the small pumps for each heat pump, and using the WILO CD. The errors in flow calculation can be considered a large contributing factor to the results found. Shown in table 7,1 are the ratios with and without the extra brine pump for temperature difference and flow. As seen in the highlighted column, the temperature difference in the borehole had a larger effect on heat extraction than the increase in flow for the case of a single heat pump. pumps case HP / HP+E HP+E / HP Temp/Flow Temp Flow HP XX XXX HP XX XXX Table 7,1: Effect of temperature difference and flow on total heat extraction. As a result of the temperature difference, there was less heat extracted when the extra pump was operational, as seen in the highlighted section in table 41

42 7,2. These values denote the amount of energy gained (positive) or lost (negative) in the cases mentioned. The most energy was lost when there were 7 boreholes functioning, with less heat lost as fewer boreholes were used. Further experiments to support this are included in appendix 2.The loss of energy in the case of 1 heat pump was attributed to the very small temperature difference, along with errors in flow values. It can be generally stated that the results seen in table 7,1 are a function of the difference in temperature between the ground and the brine, as well as the number of boreholes open. With less boreholes open, there could be a feasible use for the extra pump. pumps case Power Difference (%) (kw) HP XX XXX HP XX XXX Table 7,2: Overall energy gained and lost. When 2 heat pumps and the extra pump were operational, the increased flow had a larger effect, and the temperature drop decreased (table 7,2 above). There was more heat extracted while the extra brine pump was running. Extra energy extracted from the boreholes was in the range of 1-2,5 kw. Since the extra brine pump required 700 W to operate, it was a net gain to run the extra brine pump. The extra pump extracted the most amount of energy in the cases of all 7 boreholes open and 5 boreholes open. These experiments were repeated, and the same trends were found. Further results can be seen in appendix Effect of Opening One Extra Borehole Opening one extra borehole yielded extra energy out from the system as a whole. While the system extracted more energy from the ground, borehole seven extracted less energy as was expected. The highest amount of extra energy extracted was by opening a third borehole. This was due to the percentage of extra area available to absorb energy, as well as the pressure drop over the extra pump. Thirteen kilowatts of extra energy was obtained. Opening the other boreholes yielded 1,5-5 kw of extra energy per hole. There was no trend that showed decreasing amounts of extra energy extracted when more boreholes were opened, or the reverse. This could be due to the varying lengths of the boreholes, as well as the flow within each hole. As one more borehole was opened, the amount of energy extracted from each borehole decreased slightly, while the total energy extracted increased. This resulted in higher ground temperatures in the boreholes. Having many 42

43 boreholes open and opening one more (ie: 6 to 7 boreholes open) had less effect than having few boreholes open and opening one more (ie: 3 to 4 boreholes open). This was because the energy out of each borehole was less with many boreholes open. 7.6 Total COP The COP TOTAL lay between 2,5 and 3,1. It was curious that COP TOTAL had a lower value when the extra pump was running in conjunction with 2 heat pumps, compared to the case when it was not running with the 2 heat pumps. Further investigations must be done in this regard. 43

44 8 CONCLUSIONS 8.1 Brine Properties The brine solution had the following specifications: 1 Ethyl alcohol, C 2 H 5 OH 2 22,84 %-weight concentration 3 Freezing point: -13,5 o C 4 Additives: n-butanol (2%), isopropanol (7-9%) Detailed brine properties were interpolated using values for ethyl alcohol 23%- weight concentration, given by Åke Melinder. Additives were not considered. Viscosity tests were conducted to observe the effect of the additives on the brine properties at 20 o C. The ethyl alcohol solution was found to be more viscous than the brine solution, and falling ball viscometer tests demonstrated a difference of 83% between the two. 8.2 Ground Temperature The highest temperature was at the bottom of the borehole, at 160 m. The coldest temperatures were at 75 m depth. Temperatures above 75 m increased in data taken in October 2006, and decreased in data taken in January This can be attributed to ambient conditions. Stabilization time, the time for thermocouples at the same height to reach the same value when circulation was turned off, was minutes. Time required to stabilize increased with depth. After stabilization the up-flow side temperatures were 0,1 o C lower than the down-flow side. This can be attributed to an offset in the thermocouple locations, or an error in thermocouple readings. 8.3 Flow Regime in Borehole 7 With Reynolds numbers greater than 3000 there was more energy extracted after the bend 160 m deep in borehole 7. This was due to disturbance of the flow by the bend. The flow became heavily swirling, perhaps turbulent, and extracted larger amounts of energy. There are two possibilities. The flow may have transitioned from laminar to turbulent due to the bend. Alternatively, it may have been heavily swirling yet still predictable. Transition occurred between Re 2000 and There were unusually high amounts of heat transfer in the first 15 meters of borehole 7, for every case considered. On the down-flow side, the high amounts of energy absorbed by the brine could have been due to a heavily swirling flow, as well errors in thermocouple placement. On the up-flow side, energy was dissipated to the surroundings. This was a function of Re, which had a greater effect on extracted energy than the ground temperature, as 44

45 ground temperatures were close to brine temperatures. This section of borehole should be insulated to increase energy gains. Regarding the decreasing energy extraction on the down-flow side, it can be suggested that flow transitions from turbulent to laminar in this region. 8.4 Effects of the Extra Brine Pump In the case of a single heat pump running, there was less energy extracted when the extra pump was running. This was due to the low ground to brine temperature difference in the boreholes. The number of boreholes was too many to make the extra pump feasible. With fewer boreholes open there would be use for an extra pump. With two heat pumps and extra pump operational, there was more energy extracted from the boreholes. Considering the energy required by the extra brine pump, the net energy gain was higher with the extra pump on. The extra brine pump should be in operation when both heat pumps are running. 8.5 Effect of Opening One Extra Borehole Opening one extra borehole yielded more energy extracted from the boreholes. Consequently, each borehole extracted less energy, and the ground temperatures around the boreholes were higher. The highest amount of extra energy extracted was by opening a third borehole. This was due to the percentage of extra surface area available to absorb energy, as well as the pressure drop over the extra pump. Thirteen kilowatts of extra energy was obtained. Opening the other boreholes yielded 1,5-5 kw of extra energy per hole. The amount of energy extracted from the boreholes is a function of how much energy the heat pumps require, demanded by the domestic hot water and floor heating tanks. This varies with time. The optimum number of boreholes open is a function of this demand. 8.6 Total COP The COP total for the whole system, under normal operation was between 2,5 and 2,8. When the extra brine pump was turned off, COP total was 3,11. 45

46 9 RECOMMENDATIONS The extra brine pump should operate only when two heat pumps are running. To extract more energy, flow should be maintained with Re 4500 or higher when two heat pumps are operating. To avoid energy losses, it is recommended to insulate sections of borehole piping at Mariehäll. All piping from the building to the borehole site should be insulated, as well as the piping from the boreholes back to the building. Furthermore meters of the piping on the up-flow side should be insulated. This is to eliminate the large heat dissipation that is occurring in this section. To obtain more accurate readings and results, water meters should be placed for each borehole. An accurate total flow reading can thus be taken, and the behaviour inside each borehole can be better examined. It would be good to have the water meters a size larger so the pressure drop will decrease. Heat pump manufacturers must label the heat pumps in regards to the best flow conditions for operating the heat pump. In this way, the heat pump owner can optimize the amount of energy extracted from the ground by using the optimal flow rate. An extra pump may have to be purchased. 46

47 10 REFERENCES Beaumont, Sam; 2006 In site measurements regarding laminar and turbulent flow in heat pump boreholes Department of Energy, KTH, Stockholm. Sweden. Boyle, G.; 2004 Renewable Energy: Power for a Sustainable Future Oxford University Press, Oxford, UK, ISBN Broberg, B.; 2006 Private communication, 12 October Caughey, D.A.; Liggett, J.A.; 2001 "Fluid mechanics" McGraw-Hill, New York, USA, DOI / Franzén, Sven; 2007 Private communication, 06 February 2007 Gnielinski, V.; 1976 New Equations for Heat and Mass Transfer in Turbulent Pipe and Channel Flow Int. Chem Eng., Vol 16, pp Granryd, E.; 2005 Refrigeration Engineering, Part II Division of Applied Thermodynamics and Refrigeration, Royal Institute of Technology, Stockholm, Sweden. Hill, Peter; 2006, 2007 Private Communication, 03 November 2006 Private Communication, 31 January 2007 Kyrk, Björn; 1989 Forskningsrapport R18:1989 BFR Natural Resources Canada, 2005 What is a heat pump and how does it work? 12 Oct 2006 Nowacki, J.E.; 2006 Private communication, 05 October 2006 Nuclear Power Fundamentals, 1998 Velocity Profiles 14 Dec

48 Sabersky, R.H. et al.; 1989 Fluid Flow, A First Course in Fluid Mechanics Macmillan Publishing Company, New York, USA, ISBN Sednert, Ove; 2006 Private communication, 09 November 2006 and 14 November 2006 Sibulkin, M.; 1962 Transition from turbulent to laminar pipe flow Phys.of Fluids 5, White, Frank M.; 2003 Fluid Mechanics, fifth edition McGraw Hill, New York, NY, USA, ISBN X Wikipedia, 2006 Carnot Cycle 12 Oct 2006 Wikipedia, 2006 Refrigeration 10 March

49 APPENDIX 1: BOREHOLE DIAGRAMS Diagrams are arranged in order number of pumps and boreholes operating. Refer to top right corner for borehole specifics. 2 Heat Pumps + Extra Pump, V : Fig A1: Re and energy extraction from BH7, 2HP+E, V, 05 Feb

50 Fig A2: Re and energy extraction from BH7, 2HP+E, V, 02 Feb

51 Fig A3: Re and energy extraction from BH7, 2HP+E, V, 11 Dec

52 2 Heat Pumps + Extra Pump, XX4444V : Fig A4: Re and energy extraction from BH7, 2HP+E, XX4444V, 05 Feb

53 Fig A5: Re and energy extraction from BH7, 2HP+E, XX4444V, 02 Feb

54 2 Heat Pumps + Extra Pump, XXX444V : Fig A6: Re and energy extraction from BH7, 2HP+E, XXX444V, 05 Feb

55 Fig A7: Re and energy extraction from BH7, 2HP+E, XXX444V, 02 Feb

56 1 Heat Pump + Extra Pump, V : Fig A8: Re and energy extraction from BH7, 1HP+E, V, 29 Jan

57 1 Heat Pump, V & XX4444V : Fig A9: Re and energy extraction from BH7, 1HP, V, 11 Dec

58 Fig A10: Re and energy extraction from BH7, HP, XX4444V, 11 Dec

59 APPENDIX 2: EFFECTS OF EXTRA BRINE PUMP This appendix includes data which suggests the effect of using the extra brine pump. Experimental trials were repeated, data is seen below. 22 Feb It is seen that there is less energy out with the extra pump running. Temperature difference has much larger effect than flow increase. Negative kw extracted out with extra pump running. BH 7 extracted more heat (in general) with extra pump. pumps case ΔT (t9-t12) Total Flow BH 7 BH total (deg C) (L/s) P (kw) P (kw) HP+extra XX XXX HP XX XXX Table B1: Total energy extracted from 7 boreholes. pumps case HP / HP+E HP+E / HP Temp/Flow Temp Flow HP XX XXX Table B2: Effect of temperature and flow on energy extraction. pumps case Power Difference (%) (kw) HP XX XXX Table B3: Amount of extra energy extracted with extra brine pump on. 59

60 23 Feb Results were taken in a different order to eliminate systematic errors. Flow has larger effect than temp increase. In general, more heat extracted when extra pump running BH7 extracted more heat with extra pump running pumps case ΔT (t9-t12) Total Flow BH 7 BH total (deg C) (L/s) P (kw) P (kw) HP+extra XX XXX HP XX XXX Table B4: Total energy extracted from 7 boreholes. pumps case HP / HP+E HP+E / HP Temp/Flow Temp Flow HP XX XXX Table B5: Effect of temperature and flow on energy extraction. pumps case Power Difference (%) (kw) HP XX XXX Table B6: Amount of extra energy extracted with extra brine pump on. 06 March Results for 2HP+E taken, the other taken on 23 Feb Compared to see the result of taking readings on diff days (perhaps ground temperature is not stabilized). The table shows that ground temperature is more or less stabilized. pumps case ΔT (t9-t12) Total Flow BH 7 BH total (deg C) (L/s) P (kw) P (kw) HP+extra XX XXX HP XX XXX Table B7: Comparison of total energy extracted on different days. 60

61 APPENDIX 3: OPENING ONE EXTRA BOREHOLE Seen below is a table including the difference in energy extraction obtained when opening one extra borehole. Further down are borehole diagrams to investigate effects in borehole 7. 2 heat pumps + extra pump running: Borehole Extra Enegy Extraction (kw) Section 16 Feb. 19 Feb. 07 Mar. 1 to 2 2 to 3 12,88 13,30 3 to 4 3,54 1,51 4 to 5 2,50 4,36 3,25 5 to 6 4,36-0,56 2,82 6 to 7 3,37-2,70 Table C1: Amount of extra energy extracted opening one extra borehole. 61

62 Fig C1: Re and energy extraction from BH7, 2HP+E, 19 Feb

63 Fig C2: Re and energy extraction from BH7, 2HP+E, 19 Feb

64 APPENDIX 4: SECONDARY APPENDICES APPENDIX A: Transition From Laminar to Turbulent Seen below is a plot of Nusselt number (Nu) as a function of Reynold s number (Re). A sharp turn occurs in the curve at approximately Re This indicates the transition of flow from laminar to turbulent [Kyrk, 1989]. Disturbed flow Undisturbed flow Fig A1: Nusselt number as a function of Reynold s number 64

65 APPENDIX B: Brine Calculations In this appendix, the following can be found. The raw ethyl alcohol properties given by Åke Melinder, the plots made from this data, and the accuracy check of the plots. Detailed brine data is seen at the end of the appendices. In addition, the results from the viscosity tests between the actual brine and ethyl alcohol (23%weight concentration) are seen. Brine: Composition: Ethyl Alcohol, C 2 H 5 OH Concentration: 22,84 %weight Freezing Point: -13,5 o C Brine Temp Density ρ Sp. Heat Cp Th. Cond k Dyn. Visc μ Dyn. Visc μ Kin. Vis ν Kin. Vis ν (deg C) (kg/m3) (J/kgK) (W/mK) (mpa*s) (Pa*s) (mm2/s) (m2/s) , ,425 10,65 0, ,92 0, , ,429 7,73 0, ,93 0, , ,433 5,79 0, ,95 0, , ,437 4,46 0, ,59 0, , ,441 3,52 0, ,63 0, , ,445 2,84 0, ,93 0, , ,45 2,34 0, ,42 0, Table B1: Raw brine properties, given by Åke Melinder, Density as a function of brine temperature 978 Density (kg/m3) y = -0,0049x 2-0,2957x + 973,04 R 2 = 0,9999 Rho EQ check Poly. (Rho) Brine Temperature (dec C) Fig B1: Data plot, trendline, and accuracy plot of trendline for density 65

66 Thermal Conductivity as a function of brine temperature 0,455 Thermal Conductivity (W/mK) 0,45 0,445 0,44 0,435 0,43 0,425 y = 0,0008x + 0,433 R 2 = 0,9989 k EQ check Linear (k) 0, Brine Temperature (deg C) Fig B2: Data plot, trendline, and accuracy plot of trendline for thermal conductivity Specific Heat as a function of brine temperature 4340 Specific Heat (J/kgK) y = -0,0176x 2-0,7452x ,1 R 2 = 0,9931 Cp EQ check Poly. (Cp) Brine Temperature (deg C) Fig B3: Data plot, trendline, and accuracy plot of trendline for specific heat 66

67 Dynamic Viscosity as a function of brine temperature 0,012 Dynamic Viscosity (Pa*s) 0,01 0,008 0,006 0,004 0,002 y = 9E-06x 2-0,0004x + 0,006 R 2 = 0,9957 my EQ check Poly. (my) Brine Temperature (deg C) Fig B4: Data plot, trendline, and accuracy plot of trendline for dynamic viscosity Kinematic Viscosity as a function of brine temperature 0, Kinematic Viscosity (m2/s) 0, , , , , y = 9E-09x 2-4E-07x + 6E-06 R 2 = 0,9957 v EQ check Poly. (v) Brine Temperature (deg C) Fig B5: Data plot, trendline, and accuracy plot of trendline for kinematic viscosity The following figures are the results of the viscosity test performed to note the effect of additives in the brine. Table B4shows the differences in viscosity between the brine sample, and ethyl alcohol with concentration 23% by weight. The accuracy was approximately 85%. Mass Density Konstant W+Etanol Brine Ball # (g) (g/cm3) mpacm3/g (g/cm3) (g/cm3) 1 4,599 2,228 0, ,9367 0, ,816 2,411 0,0755 0,9367 0,9652 Table B2: Ball and brine information for viscosity measurements. Water+Ethanol (23 % w) (2) Brine (22.8 % w) (1) Ball # time1 (s) time2 (s) avg time1 (s) time2 (s) avg 1 207,38 206,5 206,94 165,35 168,06 166, ,62 21,68 21,65 19,09 19,06 19,075 67

68 Table B3: Falling Ball Viscometer readings. dynamic viscosity μ W+Etanol Brine (Pa*s) (Pa*s) 0, , , , , , Table B4: Detailed brine data APPENDIX C: Brine Flow Measurement Comparison A comparison between the TA meter, DA meter and WILO methods of obtaining total flow is found below. Flow (m3/hr) BH1 BH2 BH3 BH4 BH5 BH6 BH7 TOTAL % Error TA meter 2,41 2,50 2,10 2,36 2,24 2,04 2,08 15,72 0,98 DA system 2,46 2,54 2,15 2,40 2,29 2,08 2,12 16,03 1,00 WILO 20,80 1,30 XX m3/hr TA Meter 2,60 2,62 2,50 2,29 2,25 12,25 0,99 DA system 2,62 2,65 2,52 2,31 2,27 12,37 1,00 WILO 14,70 1,19 XXX m3/hr TA Meter 2,76 2,56 2,40 2,30 10,02 0,96 DA system 2,87 2,66 2,50 2,39 10,42 1,00 WILO 11,80 1,13 Table C1: Brine flow measurement comparison, 06 March APPENDIX D: WILO Pump Curve The pump curve for WILO pump TOP-S 25/7,5 is shown below, for ethyl alcohol at 23%-weight concentration and 5 C. It was obtained from given data 68

69 of water at 20 C, and compared with performance curves of TOP-S 25/7 3~ with water and ethyl alcohol. TOP-S 25/7,5 Ethyl Alcohol, 5 deg C, 23 %w head (m) y = 0,0061x 3-0,1394x 2-0,3329x + 7,4429 R 2 = 0, flow (m3/hr) Ethyl Alcohol Poly. (Ethyl Alcohol) Figure D1: Performance curve constructed from given information and calculations. flow head (m) 25/7,5 25/7 3~ 25/7 3~ 25/7,5 water water 7,5/7 ethyl alc W/EA ethyl alc m3/hr 20 deg 20 deg 23% 5 deg 23% 5 deg 0,00 7,40 6,74 1,10 6,81 0,99 7,40 0,50 7,30 6,67 1,09 6,70 1,00 7,30 1,00 7,00 6,66 1,05 6,62 1,01 7,00 1,50 6,60 6,48 1,02 6,44 1,01 6,60 2,00 6,30 6,30 1,00 6,26 1,01 6,30 2,50 5,80 6,05 0,96 6,01 1,01 5,80 3,00 5,40 5,79 0,93 5,72 1,01 5,40 3,50 4,80 5,47 0,88 5,36 1,02 4,80 4,00 4,30 5,10 0,84 5,00 1,02 4,30 4,50 3,60 4,71 0,76 4,60 1,02 3,60 5,00 3,10 4,20 0,74 4,09 1,03 3,10 5,50 2,40 3,76 0,64 3,62 1,04 2,40 6,00 1,70 3,22 0,53 3,08 1,05 1,70 6,50 1,20 2,68 0,45 2,50 1,07 1,20 7,00 0,30 2,03 0,15 1,88 1,08 0,30 Table D1: Calculations to obtain performance curve for TOP-S 25/7,5 69

70 NEW VALUES Ethyl Alc, 23%, 5deg NEW VALUES Ethyl Alc, 23%, 5deg NEW VALUES Ethyl Alc, 23%, 5deg NEW VALUES Ethyl Alc, 23%, 5deg head flow head flow head flow head flow m m3/hr m m3/hr m m3/hr m m3/hr 7,44 0,00 6,43 1,80 4,72 3,60 2,54 5,40 7,41 0,10 6,35 1,90 4,61 3,70 2,41 5,50 7,37 0,20 6,27 2,00 4,50 3,80 2,28 5,60 7,33 0,30 6,19 2,10 4,39 3,90 2,15 5,70 7,29 0,40 6,10 2,20 4,27 4,00 2,01 5,80 7,24 0,50 6,01 2,30 4,16 4,10 1,88 5,90 7,19 0,60 5,93 2,40 4,04 4,20 1,74 6,00 7,14 0,70 5,83 2,50 3,92 4,30 1,61 6,10 7,09 0,80 5,74 2,60 3,80 4,40 1,47 6,20 7,03 0,90 5,65 2,70 3,68 4,50 1,34 6,30 6,98 1,00 5,55 2,80 3,56 4,60 1,20 6,40 6,92 1,10 5,45 2,90 3,43 4,70 1,06 6,50 6,85 1,20 5,35 3,00 3,31 4,80 0,93 6,60 6,79 1,30 5,25 3,10 3,18 4,90 0,79 6,70 6,72 1,40 5,15 3,20 3,06 5,00 0,65 6,80 6,65 1,50 5,05 3,30 2,93 5,10 0,51 6,90 6,58 1,60 4,94 3,40 2,80 5,20 0,37 7,00 6,50 1,70 4,83 3,50 2,67 5,30 Table D2: Accurate flow values for ethyl alcohol, 23%-w, 5 C. APPENDIX E: Time Averaging The data taken on 03 March 2007 were considered here. The first row shows the averaged values of 7 consecutive temperature readings, the second row displays the exact value of the 3 rd or 5 th reading, and the final row shows the difference. T1 T2 T3 T4 T5 T6 T7 T8 T9 AVERAGE: 4,43 5,31 4,83 5,00 5,19 4,68 5,20 5,36 5,27 time 20,22 4,53 5,40 4,83 5,02 5,11 4,75 5,34 5,49 5,29 difference: 0,10 0,10 0,00 0,02-0,08 0,08 0,14 0,12 0,01 AVERAGE: 3,74 4,88 4,35 4,54 4,79 4,10 4,67 4,76 4,61 time 20,73 3,73 4,86 4,35 4,52 4,78 4,10 4,64 4,74 4,60 difference: -0,01-0,02 0,00-0,02-0,01 0,00-0,03-0,02-0,02 AVERAGE: 3,40 5,38 4,60 5,14 5,45 3,91 5,29 5,41 5,39 time 20,17 3,27 5,36 4,67 5,12 5,45 3,79 5,27 5,42 5,37 difference: -0,13-0,02 0,07-0,02 0,01-0,12-0,02 0,01-0,02 AVERAGE: 2,86 5,17 3,94 4,46 5,06 3,35 4,90 5,02 4,88 time 20,67 2,82 5,14 3,91 4,45 5,01 3,30 4,89 5,00 4,88 difference: -0,04-0,03-0,03-0,01-0,05-0,05-0,01-0,02-0,01 Table E1: Effects of time averaging. 70

71 APPENDIX F: Stabilization Time Thermocouples at the same level do tend towards the same temperature, which suggests there is no break or error with thermocouple readings. Measurements taken 29 January 2007: Stabilization Time, 5m, T1 & T7 Temperature (deg C) Time (min) T1 T7 Fig F1: Temperature profile at 5m depth, 29 January, Stabilization Time, 15m, T2 & T6 Temperature (deg C) Time (min) T6 T2 Fig F2: Temperature profile at 15m depth, 29 January,

72 Stabilization Time, 75m, T3 & T5 Temp (deg C) T3 T5 Time (min) Fig F3: Temperature profile at 75m depth, 29 January, Stabilization Time, 160m, T4 Temp (deg C) Time (min) T4 Fig F4: Temperature profile at 160m depth, 29 January, Measurements taken on 31 October, This is to compare the effect the ambient has on stabilization time. It can be seen that it took longer than 1 hour for the temperatures to meet. NOTE: Borehole 7 was shut off after 10 minutes (0.167 hours) 72

73 Temperature Profile as a function of Time: 5m depth 8 7 Temperature (deg C) TC 1 TC ,00 0,20 0,40 0,60 0,80 1,00 1,20 Time (hr) Fig F5: Temperature profile at 5m depth, 31 October Temperature Profile as a function of Time: 15 m depth 8 7 Temperature (deg C) TC 6 TC ,00 0,20 0,40 0,60 0,80 1,00 1,20 Time (hrs) Fig F6: Temperature profile at 15m depth, 31 October

74 Temperature Profile as a function of Time: 75 m depth Temp (deg C) 6,9 6,8 6,7 6,6 6,5 6,4 6,3 6,2 6,1 6 5,9 5,8 0,00 0,20 0,40 0,60 0,80 1,00 1,20 Time (hr) TC 3 TC 5 Fig F7: Temperature profile at 75m depth, 31 October Temperature Profile as a function of Time: 160 m 7,1 7 Temp (deg C) 6,9 6,8 6,7 TC 4 6,6 6,5 0,00 0,20 0,40 0,60 0,80 1,00 1,20 Time (hr) Fig F8: Temperature profile at 160m depth, 31 October

75 APPENDIX G: Excel Calculations Seen below is a sample of a calculation conducted in the excel spreadsheet. A step-by-step explanation is included below. Given ID m Area m2 TA meter Data Acquisition Check knob rotn P (kpa) m (m3/hr) m(m3/s) v(m/s) m (m3/hr) m(m3/s) v(m/s) (%) n/a n/a n/a E n/a E E E E E E XX4444 3,0 TC T ν ρ Re length (m) ΔT Q (W) Q (W/m) E E E E E E E E sum Q: E Q t8&t density kg/m cp J/kgK Table G1: Sample excel spreadsheet including calculation, 11 Dec Insert the pressure and flow data from the TA meter and the DA system. Calculate the volume flow and velocity as shown. 3 3 m 1hr m flow = = hr 3600s s EQ G1 3 m 1 m velocity = = s area s EQ G2 2. Insert appropriate thermocouple temperatures, and obtain corresponding density and kinematic viscosity values from brine property table. Calculate Reynolds number using equation 1,3 from the introduction. 3. Calculate average density for thermocouples 1-7, and find corresponding specific heat value from brine property table. 4. Calculate Q using equation 1,5, with ΔT = T 2 T1, for example. 5. Sum all Q values. Divide Q values with corresponding length to obtain W/m. 6. Calculate Q values based on temperature difference across T8 & T11. 75

76 The flow was also calculated using the number of pulses per increment of time recorded by the DA system. In this case, the time increment was 60 seconds. Assume that x number of pulses were taken in 60 seconds. 3 3 xpulses 1L 1m m = 60s pulse 1000L s EQ G3 76

77 Appendix H: Violation of 2 nd Law of Thermodynamics The amount of heat transferred in the first five meters of the borehole was unusually large. This caught the attention of Palne Mogensen, an experienced heat energy consultant. His thoughts were as follows. Calculations are shown below, as well as a visual to illustrate his concern. The thermocouples T1, T2, T6, and T7 could show anything from the bulk fluid temperature to the undisturbed external pipe temperature, depending on the quality of the insulation over the thermocouple. The thermocouples TC 11 and TC 8 are immersed in the fluid and should show the true fluid temperatures. Readings from T1 and T2 are close to TC 11 and similarly for T6 and T7 in relation to TC 8. Thus we can assume that readings from T1, T2, T6 and T8 are close to the fluid temperatures. The calculated average heat flows are very high between 5 and 15 m and the temperature drops in the pipe wall amounts to 5,1 and -3,3 K respectively assuming symmetrical heat flow around the pipe wall periphery. See calculations below. In the real case there is certainly some asymmetry, aggravating the situation. Since the fluid temperatures in the two pipes are close within less than 1 Kt this means that the heat flow from the outside of the return pipe must flow uphill to the outside of the inlet pipe, which is clearly a violation of the second law of thermodynamics. A situation in which one side of the borehole is at some 10+ degc and the other side at close to 0 deg C to provide the source and sink for the heat flows in certainly not something we could believe in. Where is the catch? Palne Mogensen, 13 Feb 2007 Formula for heat transfer in pipes [Gnielinski, 1976]: 2 Xi = (1,82 10log Re 1,64) Xi NuO = (Re 1000) (1 + 12,7 Nu = NuO Pr Xi 8 (Pr Pr Prw 0,11 NuO k α = innerwall Di 1 R TH, innerwall = απ Di LN( Do Di) R TH, pipewall = 2 π PEM = R R R total TH, innerwall + TH, pipewall ΔT = Q R total 1) EQ H1 EQ H2 EQ H3 [ W / Km 2 ] EQ H4 [ Km / W ] EQ H5 [ Km / W ] EQ H6 [ Km / W ] EQ H7 [ K ] EQ H8 77

78 Where Pr w is the Prandtl number at the wall, and Xi, Nu, Nu0 are dimensionless parameters. The Xi is the friction factor (not the Fanning friction factor, f, which is f=xi/4) Conditions are: 2300+>Re>1e6 reasonable turbulent conditions length / Di > 50 Geometry Pipe O.D. Pipe I.D. Center dist [m] [m] [m] Materials (Data for pure etehanol from Åke Melinder's report) Thermal Specific Visco- Density cond. heat capac sity Pr Fluid at 5 degc [kg/m3] [W/Km] [J/kgK] [Pas] 22 % ethanol E Polyethylene (PEM) 0.36 Pipe [mm] 40/35,2 Water temp. [degc] 5 Water flow [l/s] 0.7 Water flow [m3/s] Heat capacity flow [W/K] Heat transfer at inner wall length [m] 0.5 U [m/s] Re [-] Xi [-] Nu0 [-] Alfa [W/Km2] Alfa*Pi*Di [W/Km] Thermal resistance [Km/W] Conduction through pipe wall [W/Km] Thermal resistance [Km/W] Total Thermal Res. from fluid to outer wall Rtot [Km/W] Calculated temperature drop between fluid and pipe outside assuming symmetrical heat flow and lengthwise constant heat inflow Inlet pipe Return pipe Specific heat flow [W/m] DeltaT [K] DeltaT [K] Table H1: Thermal Resistance calculations. 78

79 Figure H1: Illustration of violation of 2 nd law of thermodynamics. 79

80 APPENDIX I: Detailed Brine Properties This section contains the equations used to obtain detailed brine data, and the detailed brine data. Equations Table I1: Trendline equations for detailed brine data R2 value Density Specific Heat Termal Conductivity Dynamic Viscosity Kinematic Viscosity y=(-0,0049*x^2)-(0,2957*x)+(973,04) y=(-0,0176*x^2)-(0,7452*x)+(4330,1) y=(0,0008*x)+(0,433) y=(9e-06*x^2)-(0,0004*x)+(0,006) y=(9e-09*x^2)-(4e-07*x)+(6e-06) 0,9999 0,9931 0,9989 0,9957 0,

81 Table I2: Detailed brine data Brine Temp Density ρ Sp. Heat Cp Th. Cond k Dyn. Visc μ Kin. Vis ν (deg C) (kg/m3) (J/kgK) (W/mK) (Pa*s) (m2/s) 20,0 965, ,16 0,4490 0, ,60E-06 19,0 965, ,59 0,4482 0, ,65E-06 18,0 966, ,98 0,4474 0, ,72E-06 17,0 966, ,35 0,4466 0, ,80E-06 16,0 967, ,67 0,4458 0, ,90E-06 15,0 967, ,96 0,4450 0, ,03E-06 14,0 967, ,22 0,4442 0, ,16E-06 13,0 968, ,44 0,4434 0, ,32E-06 12,0 968, ,62 0,4426 0, ,50E-06 11,0 969, ,77 0,4418 0, ,69E-06 10,0 969, ,89 0,4410 0, ,90E-06 9,0 969, ,97 0,4402 0, ,13E-06 8,0 970, ,01 0,4394 0, ,38E-06 7,9 970, ,11 0,4393 0, ,40E-06 7,8 970, ,22 0,4392 0, ,43E-06 7,7 970, ,32 0,4392 0, ,45E-06 7,6 970, ,42 0,4391 0, ,48E-06 7,5 970, ,52 0,4390 0, ,51E-06 7,4 970, ,62 0,4389 0, ,53E-06 7,3 970, ,72 0,4388 0, ,56E-06 7,2 970, ,82 0,4388 0, ,59E-06 7,1 970, ,92 0,4387 0, ,61E-06 7,0 970, ,02 0,4386 0, ,64E-06 6,9 970, ,12 0,4385 0, ,67E-06 6,8 970, ,22 0,4384 0, ,70E-06 6,7 970, ,32 0,4384 0, ,72E-06 6,6 970, ,42 0,4383 0, ,75E-06 6,5 970, ,51 0,4382 0, ,78E-06 6,4 970, ,61 0,4381 0, ,81E-06 6,3 970, ,71 0,4380 0, ,84E-06 6,2 971, ,80 0,4380 0, ,87E-06 6,1 971, ,90 0,4379 0, ,89E-06 6,0 971, ,00 0,4378 0, ,92E-06 5,9 971, ,09 0,4377 0, ,95E-06 5,8 971, ,19 0,4376 0, ,98E-06 5,7 971, ,28 0,4376 0, ,01E-06 5,6 971, ,37 0,4375 0, ,04E-06 5,5 971, ,47 0,4374 0, ,07E-06 5,4 971, ,56 0,4373 0, ,10E-06 5,3 971, ,66 0,4372 0, ,13E-06 81

82 Brine Temp Density ρ Sp. Heat Cp Th. Cond k Dyn. Visc μ Kin. Vis ν 5,2 971, ,75 0,4372 0, ,16E-06 5,1 971, ,84 0,4371 0, ,19E-06 5,0 971, ,93 0,4370 0, ,23E-06 4,9 971, ,03 0,4369 0, ,26E-06 4,8 971, ,12 0,4368 0, ,29E-06 4,7 971, ,21 0,4368 0, ,32E-06 4,6 971, ,30 0,4367 0, ,35E-06 4,5 971, ,39 0,4366 0, ,38E-06 4,4 971, ,48 0,4365 0, ,41E-06 4,3 971, ,57 0,4364 0, ,45E-06 4,2 971, ,66 0,4364 0, ,48E-06 4,1 971, ,75 0,4363 0, ,51E-06 4,0 971, ,84 0,4362 0, ,54E-06 3,9 971, ,93 0,4361 0, ,58E-06 3,8 971, ,01 0,4360 0, ,61E-06 3,7 971, ,10 0,4360 0, ,64E-06 3,6 971, ,19 0,4359 0, ,68E-06 3,5 971, ,28 0,4358 0, ,71E-06 3,4 971, ,36 0,4357 0, ,74E-06 3,3 972, ,45 0,4356 0, ,78E-06 3,2 972, ,54 0,4356 0, ,81E-06 3,1 972, ,62 0,4355 0, ,85E-06 3,0 972, ,71 0,4354 0, ,88E-06 2,9 972, ,79 0,4353 0, ,92E-06 2,8 972, ,88 0,4352 0, ,95E-06 2,7 972, ,96 0,4352 0, ,99E-06 2,6 972, ,04 0,4351 0, ,02E-06 2,5 972, ,13 0,4350 0, ,06E-06 2,4 972, ,21 0,4349 0, ,09E-06 2,3 972, ,29 0,4348 0, ,13E-06 2,2 972, ,38 0,4348 0, ,16E-06 2,1 972, ,46 0,4347 0, ,20E-06 2,0 972, ,54 0,4346 0, ,24E-06 1,9 972, ,62 0,4345 0, ,27E-06 1,8 972, ,70 0,4344 0, ,31E-06 1,7 972, ,78 0,4344 0, ,35E-06 1,6 972, ,86 0,4343 0, ,38E-06 1,5 972, ,94 0,4342 0, ,42E-06 1,4 972, ,02 0,4341 0, ,46E-06 1,3 972, ,10 0,4340 0, ,50E-06 1,2 972, ,18 0,4340 0, ,53E-06 1,1 972, ,26 0,4339 0, ,57E-06 1,0 972, ,34 0,4338 0, ,61E-06 0,9 972, ,42 0,4337 0, ,65E-06 0,8 972, ,49 0,4336 0, ,69E-06 0,7 972, ,57 0,4336 0, ,72E-06 0,6 972, ,65 0,4335 0, ,76E-06 0,5 972, ,72 0,4334 0, ,80E-06 0,4 972, ,80 0,4333 0, ,84E-06 0,3 972, ,87 0,4332 0, ,88E-06 0,2 972, ,95 0,4332 0, ,92E-06 0,1 973, ,03 0,4331 0, ,96E-06 0,0 973, ,10 0,4330 0, ,00E-06 82

83 Brine Temp Density ρ Sp. Heat Cp Th. Cond k Dyn. Visc μ Kin. Vis ν 0,0 973, ,10 0,4330 0, ,00E-06-0,1 973, ,17 0,4329 0, ,04E-06-0,2 973, ,25 0,4328 0, ,08E-06-0,3 973, ,32 0,4328 0, ,12E-06-0,4 973, ,40 0,4327 0, ,16E-06-0,5 973, ,47 0,4326 0, ,20E-06-0,6 973, ,54 0,4325 0, ,24E-06-0,7 973, ,61 0,4324 0, ,28E-06-0,8 973, ,68 0,4324 0, ,33E-06-0,9 973, ,76 0,4323 0, ,37E-06-1,0 973, ,83 0,4322 0, ,41E-06-1,1 973, ,90 0,4321 0, ,45E-06-1,2 973, ,97 0,4320 0, ,49E-06-1,3 973, ,04 0,4320 0, ,54E-06-1,4 973, ,11 0,4319 0, ,58E-06-1,5 973, ,18 0,4318 0, ,62E-06-1,6 973, ,25 0,4317 0, ,66E-06-1,7 973, ,32 0,4316 0, ,71E-06-1,8 973, ,38 0,4316 0, ,75E-06-1,9 973, ,45 0,4315 0, ,79E-06-2,0 973, ,52 0,4314 0, ,84E-06-3,0 973, ,18 0,4306 0, ,28E-06-4,0 974, ,80 0,4298 0, ,74E-06-5,0 974, ,39 0,4290 0, ,23E-06 83

84 APPENDIX J: Moody Diagram Figure J1: The Moody chart for pipe friction with smooth and rough pipe walls [White, 2003]. Table J1: Recommended roughness values for commercial ducts [White, 2003]. 84

Effect of Twisted Tape Inserts On Heat Transfer in A Concentric Tube Heat Exchanger

Effect of Twisted Tape Inserts On Heat Transfer in A Concentric Tube Heat Exchanger Effect of Twisted Tape Inserts On Heat Transfer in A Concentric Tube Heat Exchanger Mukesh P. Mangtani, Prof. K. M. Watt ME Scholar, Professor Department of Mechanical Engineering, Prof. Ram Meghe Institute

More information

EVALUATION OF A HIGH TEMPERATURE SOLAR THERMAL SEASONAL BOREHOLE STORAGE

EVALUATION OF A HIGH TEMPERATURE SOLAR THERMAL SEASONAL BOREHOLE STORAGE EVALUATION OF A HIGH TEMPERATURE SOLAR THERMAL SEASONAL BOREHOLE STORAGE Johan Heier 1, Chris Bales 1, Artem Sotnikov 2 and Ganna Ponomarova 2 1 Solar Energy Research Center (SERC), Dalarna University,

More information

Local Conduction Heat Transfer in U-pipe Borehole Heat Exchangers

Local Conduction Heat Transfer in U-pipe Borehole Heat Exchangers Excerpt from the Proceedings of the COMSOL Conference 2009 Milan Local Conduction Heat Transfer in U-pipe Borehole Heat Exchangers J. Acuña, B. Palm The Royal Institute of Technology KTH Brinellvägen 68,

More information

CLOSED-LOOP HEAT EXCHANGER FOR GROUND COUPLED HEAT PUMPS

CLOSED-LOOP HEAT EXCHANGER FOR GROUND COUPLED HEAT PUMPS Bulletin of the Transilvania University of Braşov Vol. () - 0 Series : Special Issue No. CLOSED-LOOP HEAT EXCHANGER FOR GROUND COUPLED HEAT PUMPS G. DRAGOMIR I. BOIAN V. CIOFOAIA Abstract: Hydraulic imbalances

More information

Fluid Mechanics, Heat Transfer, Thermodynamics Design Project. Production of Ethylbenzene

Fluid Mechanics, Heat Transfer, Thermodynamics Design Project. Production of Ethylbenzene Fluid Mechanics, Heat Transfer, Thermodynamics Design Project Production of Ethylbenzene We continue to investigate the feasibility of constructing a new, grass-roots, 80,000 tonne/y, ethylbenzene facility.

More information

Performance Analysis for Natural Draught Cooling Tower & Chimney through Numerical Simulation

Performance Analysis for Natural Draught Cooling Tower & Chimney through Numerical Simulation Performance Analysis for Natural Draught Cooling Tower & Chimney through Numerical Simulation Kanteyya A 1, Kiran Kumar Rokhade 2 Assistant Professor, Department of Mechanical Engineering, HKESSLN College

More information

Copper Micro-channel Loop Thermosyphon. A thesis presented to. the faculty of. the Russ College of Engineering and Technology of Ohio University

Copper Micro-channel Loop Thermosyphon. A thesis presented to. the faculty of. the Russ College of Engineering and Technology of Ohio University 1 Copper Micro-channel Loop Thermosyphon A thesis presented to the faculty of the Russ College of Engineering and Technology of Ohio University In partial fulfillment of the requirements for the degree

More information

Air Cycle Refrigeration Systems Nagendra M CBM Engineer, Hindusthan Zink.Ltd The specific objectives of the lesson This lesson discusses various gas cycle refrigeration systems based on air, namely: 1.

More information

Chapter 6 THE SECOND LAW OF THERMODYNAMICS

Chapter 6 THE SECOND LAW OF THERMODYNAMICS Thermodynamics: An Engineering Approach, 6 th Edition Yunus A. Cengel, Michael A. Boles McGraw-Hill, 2008 Chapter 6 THE SECOND LAW OF THERMODYNAMICS Copyright The McGraw-Hill Companies, Inc. Permission

More information

The Potential and Challenges of Solar Boosted Heat Pumps for Domestic Hot Water Heating

The Potential and Challenges of Solar Boosted Heat Pumps for Domestic Hot Water Heating The Potential and Challenges of Solar Boosted Heat Pumps for Domestic Hot Water Heating Stephen Harrison Ph.D., P. Eng., Solar Calorimetry, Dept. of Mechanical and Materials Engineering, Queen s University,

More information

OUTCOME 2 TUTORIAL 2 STEADY FLOW PLANT

OUTCOME 2 TUTORIAL 2 STEADY FLOW PLANT UNIT 47: Engineering Plant Technology Unit code: F/601/1433 QCF level: 5 Credit value: 15 OUTCOME 2 TUTORIAL 2 STEADY FLOW PLANT 2 Be able to apply the steady flow energy equation (SFEE) to plant and equipment

More information

Smart Integration of Thermal Management Systems for Electronics Cooling

Smart Integration of Thermal Management Systems for Electronics Cooling Smart Integration of Thermal Management Systems for Electronics Cooling Dr. Ir. Wessel W. Wits, University of Twente, Faculty of Engineering Technology, Laboratory of Design, Production and Management,

More information

A NOVEL TECHNIQUE FOR EXTRACTION OF GEOTHERMAL ENERGY FROM ABANDONED OIL WELLS

A NOVEL TECHNIQUE FOR EXTRACTION OF GEOTHERMAL ENERGY FROM ABANDONED OIL WELLS A NOVEL TECHNIQUE FOR EXTRACTION OF GEOTHERMAL ENERGY FROM ABANDONED OIL WELLS Seyed Ali Ghoreishi-Madiseh McGill University 3450 University St., Room 125 Montreal, QC, Canada H3A2A7 e-mail: seyed.ghoreishimadiseh

More information

a. The power required to drive the compressor; b. The inlet and output pipe cross-sectional area. [Ans: kw, m 2 ] [3.34, R. K.

a. The power required to drive the compressor; b. The inlet and output pipe cross-sectional area. [Ans: kw, m 2 ] [3.34, R. K. CHAPTER 2 - FIRST LAW OF THERMODYNAMICS 1. At the inlet to a certain nozzle the enthalpy of fluid passing is 2800 kj/kg, and the velocity is 50 m/s. At the discharge end the enthalpy is 2600 kj/kg. The

More information

ENGINEERING INFORMATION Hot water and steam service

ENGINEERING INFORMATION Hot water and steam service ENGINEERING INFORMTION Hot water and steam service What is steam? Like other substances, water can exist in the form of a solid, when we call it ice; as a liquid when we call it water or as a gas when

More information

Horizontal Borehole Study

Horizontal Borehole Study Horizontal Borehole Study Richard A. Beier a and William A. Holloway b a Mechanical Engineering Technology Department b Electrical Engineering Technology Department Oklahoma State University Stillwater,

More information

Performance Comparison of Air-source Heat Pumps Using Economizer Vapor Injection and Internal Heat Exchanger in Cold Regions

Performance Comparison of Air-source Heat Pumps Using Economizer Vapor Injection and Internal Heat Exchanger in Cold Regions Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Performance Comparison of Air-source Heat Pumps Using Economizer Vapor

More information

STUDY ON THE DESIGN PROCEDURE OF GEOTHERMAL HEAT PUMPS: GEOTHERMAL HEAT PUMP SYSTEM WITH

STUDY ON THE DESIGN PROCEDURE OF GEOTHERMAL HEAT PUMPS: GEOTHERMAL HEAT PUMP SYSTEM WITH STUDY ON THE DESIGN PROCEDURE OF GEOTHERMAL HEAT PUMPS: GEOTHERMAL HEAT PUMP SYSTEM WITH DIFFERENT TYPES OF GROUND HEAT EXCHANGERS G. Yoon *1, K. Nakazawa *, H. Niwa *, H. Kitora *, M. Okumiya *1 *1 Nagoya

More information

MATHEMATICAL MODELING OF A DOUBLE PASS UNDERFLOOR HEATING SYSTEM

MATHEMATICAL MODELING OF A DOUBLE PASS UNDERFLOOR HEATING SYSTEM MATHEMATICAL MODELING OF A DOUBLE PASS UNDERFLOOR HEATING SYSTEM Nabil Beithou, Associated Prof. Thermal Fluid Sciences, Applied Science Private University, Mechanical and Industrial Engineering Department,

More information

ASME PTC Flow Measurement

ASME PTC Flow Measurement ASME PTC 19.5-2004 Flow Measurement Performance Test Codes A N A M E R I C A N N A T I O N A L S T A N D A R D ASME PTC 19.5-2004 Flow Measurement Performance Test Codes AN AMERICAN NATIONAL STANDARD Three

More information

Chapter Six{ TC "Chapter Six" \l 1 } System Simulation

Chapter Six{ TC Chapter Six \l 1 } System Simulation Chapter Six{ TC "Chapter Six" \l 1 } System Simulation In the previous chapters models of the components of the cooling cycle and of the power plant were introduced. The TRNSYS model of the power plant

More information

DIRECTIONAL-BORE GROUND SOURCE HEAT PUMP FIELD REPORT

DIRECTIONAL-BORE GROUND SOURCE HEAT PUMP FIELD REPORT PROJECT REPORT DIRECTIONAL-BORE GROUND SOURCE HEAT PUMP FIELD REPORT Rio Mondego, California August 214 WESTERN COOLING EFFICIENCY CENTER PREPARED FOR: Bruce Baccei Project Manager Sacramento Municipal

More information

This paper was presented at 12th REHVA World Congress (Clima 2016).

This paper was presented at 12th REHVA World Congress (Clima 2016). This paper was presented at 12th REHVA World Congress (Clima 2016). The correct citation for the paper is: Spitler, J. Javed, S. and Grundmann, R. 2016. Calculation Tool for Effective Borehole Thermal

More information

Ground Coupled Heat Pump Systems a Key for a Sustainable Development of Heating and Cooling Buildings

Ground Coupled Heat Pump Systems a Key for a Sustainable Development of Heating and Cooling Buildings Ground Coupled Heat Pump Systems a Key for a Sustainable Development of Heating and Cooling Buildings GABRIEL V. BENDEA*, MARCELA F. PRADA**, CODRUTA C. BENDEA*, CALIN D.SECUI* Department of Energy Engineering

More information

Thermally operated mobile air-conditioning system

Thermally operated mobile air-conditioning system Thermally operated mobile air-conditioning system Development and test of a laboratory prototype R. de Boer S.F. Smeding Paper to be presented on the International Sorption Heat Pump Conference 2008, Seoul,

More information

SOLAR COOLING: STATE OF THE ART, TECHNICAL ANALYSIS AND FIRSTS APPLICATIONS

SOLAR COOLING: STATE OF THE ART, TECHNICAL ANALYSIS AND FIRSTS APPLICATIONS SOLAR COOLING: STATE OF THE ART, TECHNICAL ANALYSIS AND FIRSTS APPLICATIONS F. Asdrubali, G. Baldinelli, A. Presciutti, M. Caporali University of Perugia - Industrial Engineering Department, Via G. Duranti

More information

ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS

ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS ANSI/ASHRAE STANDARD 200-2015, METHODS OF TESTING CHILLED BEAMS NEMIC 2017 Agenda 1. Foreword 2. Purpose & Scope 3. Definitions 4. Instrumentation & Facilities 5. Test Methods 6. Reporting 7. Normative

More information

Thermal Performance of Thermoelectric Cooler (TEC) Integrated Heat Sink and Optimizing Structure for Low Acoustic Noise / Power Consumption

Thermal Performance of Thermoelectric Cooler (TEC) Integrated Heat Sink and Optimizing Structure for Low Acoustic Noise / Power Consumption Thermal Performance of Thermoelectric Cooler () Integrated Heat Sink and Optimizing Structure for Low Acoustic Noise / Power Consumption Masami Ikeda, Toshiaki Nakamura, Yuichi Kimura, Hajime Noda The

More information

Keywords - Heat transfer, heat exchanger, wavy twisted tape, turbulent, pressure drop, friction factor, 1 P a g e

Keywords - Heat transfer, heat exchanger, wavy twisted tape, turbulent, pressure drop, friction factor, 1 P a g e Effect of Wavy (Corrugated) Twisted Tape Inserts on Heat Transfer in a double Pipe Heat Exchanger Mr. A. S.Kurhade Department of Mechanical Engineering, GSMCOE, University of Pune, India Prof. M. M. Dange

More information

Experimental Study the Performance of Aluminum Foams Condensers in the Vapor Compression Cycle

Experimental Study the Performance of Aluminum Foams Condensers in the Vapor Compression Cycle International Journal of Current Engineering and Technology E-ISSN 2277 4106, P-ISSN 2347 5161 2016 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Experimental

More information

Review Questions for the FE Examination

Review Questions for the FE Examination 110 THE FIRST LAW OF THERMODYNAMICS [CHAP. 4 4.1FE Review Questions for the FE Examination Select a correct statement of the first law if kinetic and potential energy changes are negligible. (A) Heat transfer

More information

SHRI RAMSWAROOP MEMORIAL COLLEGE OF ENGG. & MANAGEMENT B.Tech. [SEM IV (ME-41, 42,43 & 44)] QUIZ TEST-1 (Session: )

SHRI RAMSWAROOP MEMORIAL COLLEGE OF ENGG. & MANAGEMENT B.Tech. [SEM IV (ME-41, 42,43 & 44)] QUIZ TEST-1 (Session: ) QUIZ TEST-1 Q.1. In a stage of an impulse turbine provided with a single row wheel, the mean diameter of the blade ring is 80cm and the speed of the rotation is 3000rpm. The steam issues from the nozzle

More information

In this lecture... Solve problems related to First law of thermodynamics for closed and open systems Heat engines Refrigerators and heat pumps

In this lecture... Solve problems related to First law of thermodynamics for closed and open systems Heat engines Refrigerators and heat pumps 13 1 In this lecture... Solve problems related to First law of thermodynamics for closed and open systems Heat engines Refrigerators and heat pumps 2 Problem 1 A 50 kg iron block at 80 C is dropped into

More information

Simulations of a New Double U-tube Borehole Configuration with Solar Heat Injection and Ground Freezing

Simulations of a New Double U-tube Borehole Configuration with Solar Heat Injection and Ground Freezing Simulations of a New Double U-tube Borehole Configuration with Solar Heat Injection and Ground Freezing Parham Eslami Nejad 1 and Michel Bernier 2 1 Canmet Energy Technology Center, Varennes, Québec 2

More information

Estimation of Boil-off-Gas BOG from Refrigerated Vessels in Liquefied Natural Gas Plant

Estimation of Boil-off-Gas BOG from Refrigerated Vessels in Liquefied Natural Gas Plant International Journal of Engineering and Technology Volume 3 No. 1, January, 2013 Estimation of Boil-off-Gas BOG from Refrigerated Vessels in Liquefied Natural Gas Plant Wordu, A. A, Peterside, B Department

More information

Design and Analysis of Hydraulic Oil Cooler by Application of Heat Pipe

Design and Analysis of Hydraulic Oil Cooler by Application of Heat Pipe Design and Analysis of Hydraulic Oil Cooler by Application of Heat Pipe Abstract Heat pipe is an essentially passive heat transfer device having high thermal conductivity. In hydraulic power pack use of

More information

Multi-Variable Optimisation Of Wet Vapour Organic Rankine Cycles With Twin-Screw Expanders

Multi-Variable Optimisation Of Wet Vapour Organic Rankine Cycles With Twin-Screw Expanders Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2014 Multi-Variable Optimisation Of Wet Vapour Organic Rankine Cycles With Twin-Screw Expanders

More information

Fluid Mechanics, Heat Transfer, Fluid Mechanics Design Project. Production of Ethanol

Fluid Mechanics, Heat Transfer, Fluid Mechanics Design Project. Production of Ethanol Fluid Mechanics, Heat Transfer, Fluid Mechanics Design Project Production of Ethanol Your assignment is to continue evaluating the details of a process to produce 30,000 tonne/y of ethanol from ethylene.

More information

EVALUATION AND DESIGN OF DOWNHOLE HEAT EXCHANGERS FOR DIRECT APPLICATION

EVALUATION AND DESIGN OF DOWNHOLE HEAT EXCHANGERS FOR DIRECT APPLICATION EVALUATION AND DESIGN OF DOWNHOLE HEAT EXCHANGERS FOR DIRECT APPLICATION Gene Culver Oregon Institute of Technology Klamath Falls, Oregon Gordon M. Reistad Oregon State University Corvallis, Oregon ABSTRACT

More information

Fluid Mechanics, Heat Transfer, Thermodynamics. Design Project. Production of Ammonia

Fluid Mechanics, Heat Transfer, Thermodynamics. Design Project. Production of Ammonia Fluid Mechanics, Heat Transfer, Thermodynamics Design Project Production of Ammonia Your assignment is to continue evaluating the details of a process to produce 50,000 tonne/y of ammonia from a syngas

More information

Optimisation and Cost Analysis of a Lithium Bromide Absorption Solar Cooling System

Optimisation and Cost Analysis of a Lithium Bromide Absorption Solar Cooling System Optimisation and Cost Analysis of a Lithium Bromide Absorption Solar Cooling System Georgios A. Florides and Soteris A. Kalogirou Mechanical Engineering Department, Higher Technical Institute, Nicosia,

More information

COOLING TOWER DESIGN FOR CENTRAL GENERATORS OF CUET, BANGLADESH. Mohammad Sharif Khan, Golam Mainuddin, Abu Sadat Mohammad Sayem, Nadeem Nafis

COOLING TOWER DESIGN FOR CENTRAL GENERATORS OF CUET, BANGLADESH. Mohammad Sharif Khan, Golam Mainuddin, Abu Sadat Mohammad Sayem, Nadeem Nafis Proceedings of the 4 th BSME-ASME International Conference on Thermal Engineering 7-9 December, 008, Dhaka, Bangladesh COOLING TOWER DESIGN FOR CENTRAL GENERATORS OF CUET, BANGLADESH. Mohammad Sharif Khan,

More information

Thermal performance of a closed wet cooling tower for chilled ceilings: measurement and CFD simulation

Thermal performance of a closed wet cooling tower for chilled ceilings: measurement and CFD simulation INTERNATIONAL JOURNAL OF ENERGY RESEARCH Int. J. Energy Res. 2000; 24:1171}1179 Thermal performance of a closed wet cooling tower for chilled ceilings: measurement and CFD simulation Sa!a Ri!at*, Armando

More information

DISTRIBUTED TEMPERATURE MEASUREMENTS ON A MULTI-PIPE COAXIAL BOREHOLE HEAT EXCHANGER

DISTRIBUTED TEMPERATURE MEASUREMENTS ON A MULTI-PIPE COAXIAL BOREHOLE HEAT EXCHANGER 00079-1 - DISTRIBUTED TEMPERATURE MEASUREMENTS ON A MULTI-PIPE COAXIAL BOREHOLE HEAT EXCHANGER José Acuña, PhD Student Björn Palm, Professor Royal Institute of Technology KTH, Brinellvägen 68, 100 44 Stockholm,

More information

Thermal Accumulation in Solar Systems for Hot Water Abstract 1. Introduction

Thermal Accumulation in Solar Systems for Hot Water Abstract 1. Introduction Thermal Accumulation in Solar Systems for Hot Water Stanko Vl. Shtrakov, Anton Stoilov South - West University Neofit Rilski, Dept of Physics, 66 Ivan Mihailov Str., 2700 - Blagoevgrad, BULGARIA, E-mail:

More information

Heat Load Calculation for the Design of Environmental Control System of a Light Transport Aircraft

Heat Load Calculation for the Design of Environmental Control System of a Light Transport Aircraft International Journal of Scientific & Engineering Research, Volume 7, Issue 5, May-2016 249 Heat Load Calculation for the Design of Environmental Control System of a Light Transport Aircraft Rahul Mohan.P1,

More information

Evaluation of efficiency and collector time constant of a solar flat plate collector

Evaluation of efficiency and collector time constant of a solar flat plate collector Evaluation of efficiency and collector time constant of a solar flat plate collector Abhijit Devaraj 1, Abhishek Hiremath 2, Akshay R Patil 3, Krushik B N 4 Department of Mechanical Engineering, BMS College

More information

BUILDING FOR THE FUTURE

BUILDING FOR THE FUTURE BUILDING FOR THE FUTURE The following article was published in ASHRAE Journal, September 4. Copyright 4 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented

More information

Energy-Efficient Passive House using thermal mass to achieve high thermal comfort

Energy-Efficient Passive House using thermal mass to achieve high thermal comfort Energy-Efficient Passive House using thermal mass to achieve high thermal comfort Loa Andersson Managing Director RLI Byggdata AB rli@termodeck.com Alexander Engström Technical Director RLI Byggdata AB

More information

Performance of a counterflow heat exchanger with heat loss through the wall at the cold end

Performance of a counterflow heat exchanger with heat loss through the wall at the cold end Cryogenics 39 (1999) 43 5 Performance of a counterflow heat exchanger with heat loss through the wall at the cold end S. Pradeep Narayanan, G. Venkatarathnam * Department of Mechanical Engineering, Indian

More information

Heat transfer modelling of slot jet impinging on an inclined plate

Heat transfer modelling of slot jet impinging on an inclined plate Heat transfer modelling of slot jet impinging on an inclined plate A. Ramezanpour 1, H. Shirvani 1 & I. Mirzaee 2 1 School of Design and Communication Systems, APU University, UK 2 CFD Research Centre,

More information

ERT 318/4 UNIT OPERATIONS SEMESTER 1 (2013/2014)

ERT 318/4 UNIT OPERATIONS SEMESTER 1 (2013/2014) ERT 318/4 UNIT OPERATIONS SEMESTER 1 (2013/2014) WATER COOLING TOWER School of Bioprocess Engineering University Malaysia Perlis EXPERIMENT Water Cooling Tower 1.0 OBJECTIVES 1.1 To determine energy and

More information

Fluid Mechanics, Heat Transfer, Thermodynamics Design Project. Production of Styrene

Fluid Mechanics, Heat Transfer, Thermodynamics Design Project. Production of Styrene Fluid Mechanics, Heat Transfer, Thermodynamics Design Project Production of Styrene The feasibility of constructing a new, grass-roots, 100,000 tonne/y, styrene plant is being investigated. As part of

More information

Ground-Coupled Heat Pump And Energy Storage

Ground-Coupled Heat Pump And Energy Storage Ground-Coupled Heat Pump And Energy Storage By Ed Lohrenz, Member ASHRAE; and Sergio Almeida, P.Eng., Member ASHRAE Ground-coupled heat pump (GCHP) systems consume less purchased energy than an HVAC system

More information

SorTech package solution description

SorTech package solution description SorTech package solution description Version 2.0 Edited by: Jörg Rupp Lotta Koch, Edo Wiemken, Björn Nienborg Freiburg, 06.10.2009 Table of Contents 1 Introduction... 3 2 The Chiller... 4 3 System s Components...

More information

Ground Source Heat Pump System Performance: Measuring the COP

Ground Source Heat Pump System Performance: Measuring the COP Ground Source Heat Pump System Performance: Measuring the COP Ground Energy Support, LLC June 2013 1 Introduction This article is the second in a three-part series prepared by Ground Energy Support LLC

More information

3.17. PROCESS INTEGRATION AND PINCH TECHNOLOGY

3.17. PROCESS INTEGRATION AND PINCH TECHNOLOGY FUNDAMENTALS OF ENERGY BALANCES 111 pressure is expanded over the throttle value and fed to the condenser, to provide cooling to condense the vapour from the column. The vapour from the condenser is compressed

More information

CTD (CONDUCTIVITY-TEMPERATURE-DEPTH)

CTD (CONDUCTIVITY-TEMPERATURE-DEPTH) CTD (CONDUCTIVITY-TEMPERATURE-DEPTH) Related lesson plan Fresh and Seawater Density What is this sensor? CTD is an acronym for Conductivity, Temperature and Depth. However, this is somewhat misleading

More information

TEMPERATURE STRATIFICATION OF CIRCULAR BOREHOLE THERMAL ENERGY STORAGES

TEMPERATURE STRATIFICATION OF CIRCULAR BOREHOLE THERMAL ENERGY STORAGES - 1 - TEMPERATURE STRATIFICATION OF CIRCULAR BOREHOLE THERMAL ENERGY STORAGES Jens Penttilä, Engineer; José Acuña, Researcher; Patricia Monzó, PhD student KTH Royal Institute of Technology, Dept. of Energy

More information

Modelling of the off-gas exit temperature and slag foam depth. of an Electric Arc Furnace

Modelling of the off-gas exit temperature and slag foam depth. of an Electric Arc Furnace odelling of the off-gas exit temperature and slag foam depth of an Electric Arc Furnace Daniël Jacobus Oosthuizen ), Johannes Henning Viljoen ), Ian Keith Craig ), Petrus Christiaan Pistorius 2) ) Department

More information

Development of an Innovative 2.5 kw Water- Silica Gel Adsorption Chiller

Development of an Innovative 2.5 kw Water- Silica Gel Adsorption Chiller Development of an Innovative 2.5 kw Water- Silica Gel Adsorption Chiller E.-J. Bakker R. de Boer S. Smeding N. Sijpheer M. van der Pal September 2013 ECN-B--13-011 DEVELOPMENT OF AN INNOVATIVE 2.5 kw WATER-SILICA

More information

Modeling and analyzing solar cooling systems in Polysun

Modeling and analyzing solar cooling systems in Polysun Modeling and analyzing solar cooling systems in Polysun Seyed H. Rezaei (seyed.rezaei@velasolaris.com) 1 Andreas Witzig (andreas.witzig@velasolaris.com) 1 Michael Pfeiffer (michael.pfeiffer@velasolaris.com)

More information

PERFORMANCE ANALYSIS OF ORGANIC RANKINE CYCLES USING DIFFERENT WORKING FLUIDS

PERFORMANCE ANALYSIS OF ORGANIC RANKINE CYCLES USING DIFFERENT WORKING FLUIDS THERMAL SCIENCE, Year 015, Vol. 19, No. 1, pp. 179-191 179 PERFORMANCE ANALYSIS OF ORGANIC RANKINE CYCLES USING DIFFERENT WORKING FLUIDS by Qidi ZHU, Zhiqiang SUN *, and Jiemin ZHOU School of Energy Science

More information

White Paper. Geothermal Heating and Cooling

White Paper. Geothermal Heating and Cooling White Paper Geothermal Heating and Cooling The fundamentals of a geoexchange system (geothermal heating and cooling system) are well understood and although many factors need to be considered when designing

More information

Limitations of Using Uniform Heat Flux Assumptions in Sizing Vertical Borehole Heat Exchanger Fields

Limitations of Using Uniform Heat Flux Assumptions in Sizing Vertical Borehole Heat Exchanger Fields Limitations of Using Uniform Heat Flux Assumptions in Sizing Vertical Borehole Heat Exchanger Fields Veera Malayappan 1, Jeffrey D. Spitler 2 1,2 Mechanical and Aerospace Engineering, Oklahoma State University

More information

Experimental investigation of single-phase and twophase closed thermosyphon solar water heater systems

Experimental investigation of single-phase and twophase closed thermosyphon solar water heater systems Scientific Research and Essays Vol. 6(4), pp. 688-693, 18 February, 2011 Available online at http://www.academicjournals.org/sre DOI: 10.5897/SRE09.072 ISSN 1992-2248 2011 Academic Journals Full Length

More information

Effect of Distance between Double Glazing on the Performance of a Solar Thermal Collector Control

Effect of Distance between Double Glazing on the Performance of a Solar Thermal Collector Control Journal of Mechanics Engineering and Automation 5 (215) 161-166 doi: 117265/2159-5275/21534 D DAVID PUBLISHING Effect of Distance between Double Glazing on the Performance of a Solar Thermal Collector

More information

PORTABLE HEAT PUMP TESTING DEVICE

PORTABLE HEAT PUMP TESTING DEVICE Int. J. of Applied Mechanics and Engineering, 2015, vol.20, No.3, pp.657-662 DOI: 10.1515/ijame-2015-0044 Technical note PORTABLE HEAT PUMP TESTING DEVICE R. KŁOSOWIAK *, J. BARTOSZEWICZ and R. URBANIAK

More information

EVALUATION OF GROUND COUPLED HEAT PUMPS FOR THE STATE OF WISCONSIN

EVALUATION OF GROUND COUPLED HEAT PUMPS FOR THE STATE OF WISCONSIN EVALUATION OF GROUND COUPLED HEAT PUMPS FOR THE STATE OF WISCONSIN by Jonathan J. Giardina A thesis submitted in partial fulfillment of the requirements for the degree of MASTERS OF SCIENCE (MECHANICAL

More information

POROSITY, SPECIFIC YIELD & SPECIFIC RETENTION. Physical properties of

POROSITY, SPECIFIC YIELD & SPECIFIC RETENTION. Physical properties of POROSITY, SPECIFIC YIELD & SPECIFIC RETENTION Porosity is the the ratio of the voids to the total volume of an unconsolidated or consolidated material. Physical properties of n = porosity as a decimal

More information

Design of Experiment for Solar Water Heater Performance Analysis

Design of Experiment for Solar Water Heater Performance Analysis Design of Experiment for Solar Water Heater Performance Analysis Mr. M.V. Kulkarni 1, Dr. D. S Deshmukh 2, 1 Asst. Professor, Department of Mechanical Engineering, SSBT'S COLLEGE OF ENGINEERING AND TECHNOLOGY,

More information

Flow and Heat Transfer Characteristics in High Porosity Metal Foams

Flow and Heat Transfer Characteristics in High Porosity Metal Foams Proceedings of the World Congress on Mechanical, Chemical, and Material Engineering (MCM 2015) Barcelona, Spain July 20-21, 2015 Paper No. 333 Flow and Heat Transfer Characteristics in High Porosity Metal

More information

Low-Grade Waste Heat Recovery for Power Production using an Absorption-Rankine Cycle

Low-Grade Waste Heat Recovery for Power Production using an Absorption-Rankine Cycle Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Low-Grade Waste Heat Recovery for Power Production using an Absorption-Rankine

More information

LECTURE-15. Ideal Reverse Brayton Cycle. Figure (6) Schematic of a closed reverse Brayton cycle

LECTURE-15. Ideal Reverse Brayton Cycle. Figure (6) Schematic of a closed reverse Brayton cycle Lecturer: -Dr. Esam Mejbil Abid Subject: Air Conditioning and Refrigeration Year: Fourth B.Sc. Babylon University College of Engineering Department of Mechanical Engineering LECTURE-15 Ideal Reverse Brayton

More information

Optimization of embedded Heat Exchanger in a flat plate Integrated Collector Storage Solar Water Heater (ICSSWH), with indirect heat withdrawal.

Optimization of embedded Heat Exchanger in a flat plate Integrated Collector Storage Solar Water Heater (ICSSWH), with indirect heat withdrawal. World Renewable Energy Congress (WRECX) Editor A. Sayigh 2008 WREC. All rights reserved. 1815 Optimization of embedded Heat Exchanger in a flat plate Integrated Collector Storage Solar Water Heater (ICSSWH),

More information

ENHANCEMENT OF COEFFICIENT OF PERFORMANCE IN VAPOUR COMPRESSION REFRIGERATION CYCLE

ENHANCEMENT OF COEFFICIENT OF PERFORMANCE IN VAPOUR COMPRESSION REFRIGERATION CYCLE ENHANCEMENT OF COEFFICIENT OF PERFORMANCE IN VAPOUR COMPRESSION REFRIGERATION CYCLE Dr Venkata Ramana Reddy Mula 1, H.V.Harish 2 1 Professor and Head, Department of Aeronautical Engineering NMIT BANGALORE

More information

Design and distribution of air nozzles in the biomass boiler assembly

Design and distribution of air nozzles in the biomass boiler assembly TRANSACTIONS OF THE INSTITUTE OF FLUID-FLOW MACHINERY No. 125, 2013, 13 28 KAROL RONEWICZ, TOMASZ TURZYŃSKI, DARIUSZ KARDAŚ Design and distribution of air nozzles in the biomass boiler assembly The Szewalski

More information

Water supply components

Water supply components Water supply components Water sources structures (Dams, wells, reservoirs) Surface water Groundewater Pipelines from source Water treatment plant components Pumping stations Storage (elevated tanks) Distribution

More information

Hydro Electric Power (Hydel Power)

Hydro Electric Power (Hydel Power) Operating Principle Hydro Electric Power (Hydel Power) Hydro-electric power is generated by the flow of water through turbine, turning the blades of the turbine. A generator shaft connected to this turbine

More information

The influence of the ground parameters assumptions on the low enthalpy heat pump s energy source simulation s results

The influence of the ground parameters assumptions on the low enthalpy heat pump s energy source simulation s results The influence of the ground parameters assumptions on the low enthalpy heat pump s energy source simulation s results Ewelina Stefanowicz 1, and Natalia Fidorów-Kaprawy 1,* 1 Wrocław University of Science

More information

CEE 452/652. Week 12, Lecture 1 Cyclones. Dr. Dave DuBois Division of Atmospheric Sciences, Desert Research Institute

CEE 452/652. Week 12, Lecture 1 Cyclones. Dr. Dave DuBois Division of Atmospheric Sciences, Desert Research Institute CEE 452/652 Week 12, Lecture 1 Cyclones Dr. Dave DuBois Division of Atmospheric Sciences, Desert Research Institute Today s topics Today s topic: cyclones Read chapter 4 Homework on ch. 3, due Thurs. Select

More information

Solutions to TUTORIAL-6 (10/03/2017) Thermodynamics for Aerospace Engineers (AS1300) Second Law of Thermodynamics

Solutions to TUTORIAL-6 (10/03/2017) Thermodynamics for Aerospace Engineers (AS1300) Second Law of Thermodynamics Solutions to TUTORIAL-6 (10/03/2017) Thermodynamics for Aerospace Engineers (AS1300) Second Law of Thermodynamics Q1. An inventor claims to have developed an engine that takes in 105 MJ at a temperature

More information

Heat Pump Efficiencies simulated in Aspen HYSYS and Aspen Plus

Heat Pump Efficiencies simulated in Aspen HYSYS and Aspen Plus Heat Pump Efficiencies simulated in Aspen HYSYS and Aspen Plus Lars Erik Øi 1 Irene Yuste Tirados 1 1 Department of Process, Energy and Environmental Technology, Telemark University College, Norway lars.oi@hit.no

More information

Modeling and Investigation of Refrigeration System Performance with Two-Phase Fluid Injection in a Scroll Compressor

Modeling and Investigation of Refrigeration System Performance with Two-Phase Fluid Injection in a Scroll Compressor Marquette University e-publications@marquette Master's Theses (2009 -) Dissertations, Theses, and Professional Projects Modeling and Investigation of Refrigeration System Performance with Two-Phase Fluid

More information

Thermal Applications of Cellular Lattice Structures

Thermal Applications of Cellular Lattice Structures Materials Science Forum Vols. 539-543 (2007) pp. 242-247 online at http://www.scientific.net (2007) Trans Tech Publications, Switzerland Thermal Applications of Cellular Lattice Structures Haydn N.G. Wadley

More information

Research on Ground Source Heat Pump Design

Research on Ground Source Heat Pump Design Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Research on Ground Source Heat Pump Design Amanda Jo Pertzborn University

More information

AN ANALYSIS OF POROUS MEDIA HEAT SINKS FOR NATURAL CONVECTION COOLED MICROELECTRONIC SYSTEMS. Eric R. Savery

AN ANALYSIS OF POROUS MEDIA HEAT SINKS FOR NATURAL CONVECTION COOLED MICROELECTRONIC SYSTEMS. Eric R. Savery AN ANALYSIS OF POROUS MEDIA HEAT SINKS FOR NATURAL CONVECTION COOLED MICROELECTRONIC SYSTEMS. by Eric R. Savery Engineering Project submitted in partial fulfillment of the requirements for the degree of

More information

Pump selection: a real example

Pump selection: a real example 28 Feature WORLD PUMPS March 2010 Centrifugal pumps Pump selection: a real example Choosing the most appropriate and cost-effective centrifugal pump for a given duty requires strict adherence to a thorough

More information

Experimental analysis of heat-pump integrated with solar energy

Experimental analysis of heat-pump integrated with solar energy Experimental analysis of heat-pump integrated with solar energy André Ricardo Quinteros Panesi 1 Abstract: The objective of the present work is to analyze the performance of an equipment used in water

More information

Quenching steels with gas jet arrays

Quenching steels with gas jet arrays Quenching steels with gas jet arrays PAUL F STRATTON ANDREW P RICHARDSON BOC Rother Valley Way, Holbrook, Sheffield UNITED KINGDOM Paul.stratton@boc.com http://www.catweb.boc.com Abstract: - Single components

More information

CALIBRATION OF TURBINE GAS METER BY MATCHING REYNOLDS NUMBER AND DENSITY. Introduction

CALIBRATION OF TURBINE GAS METER BY MATCHING REYNOLDS NUMBER AND DENSITY. Introduction CALIBRATION OF TURBINE GAS METER BY MATCHING REYNOLDS NUMBER AND DENSITY PAUL W. TANG, M.Sc.,P.Eng. TERASEN GAS SURREY, BC, CANADA Introduction Accurate metering is essential to fair trading in the natural

More information

Thermal Efficiency of the Borehole Heat Exchanger Built with Drilling Mud.

Thermal Efficiency of the Borehole Heat Exchanger Built with Drilling Mud. Thermal Efficiency of the Borehole Heat Exchanger Built with Drilling Mud. Masatoshi Yamaguchi yamaguchi@jgd.jp Kiichi Numazawa numazawa@jgd.jp Masahiko Katsuragi m-katsuragi.jgd.jp Japan Ground Water

More information

Thermal Analysis and Modelling of Thermal Storage in Solar Water Heating Systems

Thermal Analysis and Modelling of Thermal Storage in Solar Water Heating Systems International Journal of Energy and Power Engineering 2016; 5(2): 48-59 http://www.sciencepublishinggroup.com/j/ijepe doi: 10.11648/j.ijepe.20160502.14 ISSN: 2326-957X (Print); ISSN: 2326-960X (Online)

More information

ENGG 3260: Thermodynamics. Home Assignment 2 (Chapter 2)

ENGG 3260: Thermodynamics. Home Assignment 2 (Chapter 2) ENGG 60: Thermodynamics Home Assignment (Chapter ) 1. A person gets into an elevator at the lobby level of a hotel together with his 0-kg suitcase, and gets out at the 10 th floor 5 m above. Determine

More information

Conceptual Design of Nuclear CCHP Using Absorption Cycle

Conceptual Design of Nuclear CCHP Using Absorption Cycle Conceptual Design of Nuclear CCHP Using Absorption Cycle International Conference on Opportunities and Challenges for Water Cooled Reactors in the 21 st Century Vienna, Austria, October 27-30, 2009 Gyunyoung

More information

AQA GCSE Physics Unit 1 Specification

AQA GCSE Physics Unit 1 Specification P1.1 The transfer of energy by heating processes and the factors that affect the rate at which that energy is transferred Energy can be transferred from one place to another by work or by heating processes.

More information

PERFORMANCE ANALYSIS OF NATURAL DRAFT WET COOLING TOWER AT OPTIMIZED INJECTION HEIGHT

PERFORMANCE ANALYSIS OF NATURAL DRAFT WET COOLING TOWER AT OPTIMIZED INJECTION HEIGHT PERFORMANCE ANALYSIS OF NATURAL DRAFT WET COOLING TOWER AT OPTIMIZED INJECTION HEIGHT 1 ALOK SINGH, 2 SANJAY SONI, 3 R. S. RANA 1 Assistant Professor, 2 Associate Professor, 3 Mechanical Engineering Department

More information

Simulation and Optimization of Vacuum Tube Solar Collector Water Heating System in Iran

Simulation and Optimization of Vacuum Tube Solar Collector Water Heating System in Iran Online available since February 2016 at www.oricpub.com (2016) Copyright ORIC Publications Journal of Science and Engineering; Vol. 07 (01), 2016, 001-019 ISSN: 2331-5172 Simulation and Optimization of

More information