1 26 International Conference on Power System Technology Voltage Stability Analysis of Wind Farm Integration into Transmission Network Yongning Chi, Yanhua Liu, Weisheng Wang, Member IEEE, Huizhu Dai I. NOMENCLATURE Abstract In some regional grids in China, wind power penetration will increase rapidly because of the abundant wind resources in those areas and the government policy impetus. However, the power system security and stability may be affected due to the higher wind power penetration. Because majority of the wind farms with higher installed capacity intends to be connected into the transmission network of 22kV voltage level, their impacts are becoming more widespread. In the grid impact studies of wind power integration, voltage stability is the mostly concerned problem that will affect the operation and security of wind farms and power grid. In this paper, the detailed wind turbines steadystate model and dynamic model are used to explore the wind power integration impact on voltage stability of the power system; the load flow calculation (PV curve and VQ curve) and dynamic contingency study are conducted; the different impacts on voltage stability of integrating wind farms based on different wind turbines technologies are illustrated and the following conclusions are presented: a. Wind turbines equipped with simple induction generator are not provided with reactive power regulation capability. Voltage stability deterioration is mainly due to the large amount of reactive power absorbed by the wind turbine generators during the continuous operation and system contingencies. b. Wind turbines equipped with doubly fed induction generator (DFIG) controlled by the PWM converters are provided with reactive power regulation capability; can absorb or supply reactive power during normal operation. The adverse affect on local network voltage stability is mitigated so that more wind power installed capacity can be incorporated into the grid. c. The transient voltage stability characteristics of wind turbines with DFIG are better than wind turbines with induction generator because of the voltage control capability of the DFIG based wind turbines; The DFIG based wind turbines have a better voltage recovery performance than the IG based wind turbines with same rating. Index Terms Wind power integration; Wind turbines; Induction generator (IG); Doubly Fed Induction Generator (DFIG); Dynamic model; Load flow; Voltage stability. This work was supported in part by the SinoGerman Project "China Wind Power Center". Yongning Chi is with China Electric Power Research Institute. Beijing, China. ( chiyn@epri.ac.cn). Yanhua Liu is with North China Electric Power University. Beijing, China. ( liuyh@epri.ac.cn) Weisheng Wang is with China Electric Power Research Institute. Beijing, China. ( wangwsqepri.ac.cn) Huizhu Dai is with China Electric Power Research Institute. Beijing, China. ( daihz@epri.ac.cn) /6/$2.(c26 IEEE. Downloaded from DM,DG Er HM,HG u i Ks s Turbine rotor and generator rotor damping coefficient Voltage behind the transient impedance Turbine and generator shaft inertia Voltage Current Shaft stiffness coefficient Shaft twist angle CG Synchronous speed, wind turbine rotor speed, generator rotor speed Pulsewidth modulation factor Pm P, Q Active and reactive power R Resistance Req r Xeq Equivalent resistance and reactance Rotor slip s X, X', X Steadystate, transient, and magnetizing reactance Rotor circuit time constant Electromagnetic and mechanical torque TE, TM V, I Phase voltage and phase current Symbols Differential operator p Suffices, Superscripts ac, dc Alternating current, Direct current d, q Direct and quadrature axis components Generator's stator and rotor components s, r Cos C II. INTRODUCTION Following the issue of the Renewable Energy Law to give impetus to the development of renewable energy by government in China; a large number of wind farms are currently interconnected into transmission network of 22kV voltage level with higher installed capacity. Being connected to higher voltage level, their impacts are becoming more widespread. There are several technical constraints that may limit wind power integration to a transmission power system, either steadystate or dynamic. A majority of large wind farms in China, including proposed large wind projects, are geographically far away from load centers and connected into relatively weak transmission network. The presence of wind
2 2 farms in such weak transmission network incurs serious concerns about system security and stability. Power system utilities concerns are shifting focus from the power quality issues to the stability problems caused by the wind power integration. In the grid impact studies of wind power integration, the voltage stability issue is a key problem because a large proportion of wind farms in China are based on fixed speed wind turbines equipped with simple induction generator (IG). Induction generators consume reactive power and behave similar to induction motors in the duration of system contingency, which will deteriorate the local grid voltage stability. Also variable speed wind turbines equipped with doubly fed induction generator (DFIG) are becoming more widely used for its advanced reactive power and voltage control capability. DFIG make use of power electronic converters and are thus able to regulate their own reactive power, so as to operate at a given power factor, or to control grid voltage; But because of the limited capacity of the PWM converter [1][4], the voltage control capability of DFIG can't catch up with that of the synchronous generator. When the voltage control requirement is beyond the capability of the DFIG, the voltage stability of the grid is also affected. In this paper the voltage stability of power system with large wind farm is studied in an actual wind farm interconnection project in china. Both steadystate voltage stability analysis and transient voltage stability analysis are conducted. Wind turbines model used in load flow calculation and dynamic simulation is implemented in the power system simulation tool DIgSILENT/PowerFactory [5] [6]. The continuation power flow approaches such as PV curve and VQ curve and dynamic contingency simulation are used to explore the mechanism of the voltage stability of the power system with high wind power penetration. The difference of the impacts on power system voltage stability with wind farms based on different wind turbine technologies is presented. stator is directly connected to the grid, but the three phase rotor windings are connected through slip rings to the grid via a partially rated power electronics converter. A typical configuration of a DFIG is shown schematically in Figure 1. The DFIG can be regarded as a traditional induction generator with a nonzero rotor voltage. For representation of DFIG models in power system stability studies [2] [4] [7], the stator flux transients are neglected in the voltage relations. By eliminating the rotor currents and expressing the rotor flux linkages in terms of Ed and E' the dynamic equations of DFIG are derived:, q RIsds Vs'qs +Ed Uqs siqs + ls'ds +Eq Uds TOPEd Ed (Xs s +sruqr+sw]si'eq ]op]eq Eq+ (Xsss)ds sosrs)r7isred TE Udids +Uq!iqs Where Udr UdrXm /(Xr +Xm); Uqr UqXm /(Xr +Xm), The converter in such wind turbines only deals with slip therefore the converter rating can be kept fairly low, approximately 2% of the total generator power. The PWM converter inserted in the rotor circuit allows for a flexible and fast control of the generator by modifying magnitude and phase angle of the rotor voltage. The controllability of reactive power power, power help DFIG equipped wind turbines play a similar role to that of synchronous generators. Under steadystate conditions, the flux transient's items disappear. In figure 2, the steadystate equivalent circuit of the DFIG is given [2] [7]. RS Rr X X III. MODELS OF WIND TURBINES Wind turbines model based on different generator technologies such as simple induction generator or doubly fed induction generator with identical rated power (1.5MW) are presented in this work. As in Figure 1, a simple configuration of different types of wind turbines concept is shown. 1s a' Fig.2. Steadystate equivalent circuit of doubly fed induction generator tn Generator Inuction ~~~Low Btade S GUnit Transformer Bo pref High Vottage Vot1tage DFtIG. Rotor Side A D Converter ~~~~~~~~MediumVottage, Substation External Transformer Grid D CGrid Side Qref Converter Fig. 1. Configuration of IG based wind turbines and DFIG based wind turbines and interconnection to the grid A. Doublyfed induction generator model The DFIG is a woundrotor induction generator whose During normal steadystate operation the wind turbines or the wind farm can be considered as a PQ node or a PV node depending on the control strategy that the wind farm adopted [8]. B. Induction generator model The rotor of induction generator is a woundrotor or a squirrelcage rotor with a short circuit winding not connecting to an external voltage source [9] [ 11]. The dynamic equations of IG can be obtained by eliminating the u' items in equations. The steadystate equivalent circuit of the induction generator is given in Figure 3.
3 3 R, Xv Rr up Xr by sixpulse bridges illustrated in figure 4. V a': R,q Xeq Rotor side Grid side Fig.4. VSCPWM converter configuration Fig.3. Steadystate equivalent circuit of induction generator From the equivalent circuit of induction generator in Figure 3, the active power and reactive power expression are easily derived. V2Req,I Vacd 2,.2 acq 2\/S7 v2 Qe Req Xeq Assuming an ideal DCvoltage and PWM modulation, the fundamental frequency line to line AC voltage and the DC voltage can be related to each other as follows: 2eq Req +Xeq +Xeq2 PmdV m dc It can be seen that the induction generator active power and reactive power is closely related to the terminal voltage V and the slip s of the induction generator. C. Shaft system model During transient voltage stability study of wind farm integration, the shaft system model of wind turbines should be taken into account. Under normal operating conditions, variable speed generators are "decoupled" from the grid; torsional shaft oscillations are filtered by the converters with appropriate controls. However, during heavy faults such as 3 phase short circuit fault in the network, generator and turbine acceleration can only be simulated with sufficient accuracy of shaft models. Shaft characteristics of wind generators are quite different from other types of generators due to the relatively low stiffness of the turbine shaft. This results in torsional resonance frequencies in a range of about.5 to 2 Hz. The proposed shaft model is described by a twomass model, represented by turbine and generator inertia [1] [5]. The twomass model represents the shaft torsional twist is given by the following equations: mq (,1J1+ dc The ACvoltage phase angle is defined by the PWM Pm is the control variable of the PWM converter which is valid for < Pm < 1 The converter model is completed by the power conservation equation: converter. The pulsewidth modulation factor. VdC IdC + (5) Re(Vac Iac ) This equation assumes a lossless converter. Because the switching frequency of PWM converters is usually very high (typically several hundreds Hz), switching losses are the predominant type of losses. Since the average switching losses are basically proportional to V', switching losses can be considered by a resistance between the two DCpoles in a fundamental frequency model [4]. E. Control strategy of DFIG based wind turbines DFIG make use of power electronic converters and are thus able to regulate their own reactive power, so as to operate at a given power factor, or to control grid voltage. The rotorside converter is controlled by a two stage controller in figure 5. The first stage consists of fast current 2HM d TM KsOs Dmcom controllers regulating the generator rotor currents to reference dt values that are specified by a slower powercontroller which is the second stage controller. There are two independent PI 2HG dg KsOs TE controllers, one for the daxis component, and one for the qaxis component. The output of the current controller defines dit ( C& the pulsewidth modulation factor Pm in stator voltage orientation. D. Converter model Voltage control can also be realized by replacing the The converter consists of two voltage source converters reactive power controller by a voltage controller defining the connected backtoback and enables variable speed operation daxis current reference. Up to now, this feature of the DFIG of the wind turbines by decoupling control that controls the based wind turbine is mainly used to keep the generator active power and reactive power of the generator separately [2] reactive power neutral. However, as wind power penetration [6]. The rotorside and gridside converters are usually setin power systems is increasing, it will probably be desirable DGC3 dl C) C%G
4 4 for wind turbines to provide voltage control. The controller shown in Fig. 5 can regulate either the voltage or the power factor, but the maximum possible reactive power production is defined by the converter ratings. P,1 Id 1rfsT V7 Fig.5. Rotor side converter control strategy diagram model is a 5% const impedance and 5% motor model. The models and the parameters of the power system are all given by the utility. V. STEADYSTATE VOLTAGE STABILITY ANYLYSIS Wind farms based on different generator technologies would have a distinctive impact on the power system voltage stability [11] [13]. In this section, the steadystate voltage stability limit of wind farms based on different wind turbine technologies is assessed. Three cases are conducted: case wind turbines equipped with noload compensated induction generator; case wind turbines equipped with fullload compensated induction generator; case wind turbines equipped with DFIG controlling the POI as a PQ node with Q OMVar. All these cases simulation results are compared to discover the wind power integration impact on voltage The control concept of the gridside converter is very similar to the rotorside controller concept. Further describe stability. seen in paper [1] [4]. A. PV curve analysis ofwindfarm with different generator Wind farms based on different types of wind turbines are F. Windfarm model interconnected into the transmission grid. When the active In order to reduce the complexity of the analysis, a group of wind farm is low, the POI voltage does not power output of identical generators comprising each wind farm can be affected but when wind power injects into the significantly replaced by an equivalent generator. This aggregated wind POI then the voltage decreases fast. The increasing largely farm model must have the same voltage, current and power PV curves of the wind farms as wind farm active power response at the point of interconnection. The normalized (per in Figure 7. are output increasing plotted unit) parameters of the aggregated model are the same as that of an individual generator, but the rated power is the sum of Induction Machine Based Wind Farm with No Load Compensation 1.2 the whole group of generators. Induction Machine Based Wind Farm with Full Load Compensation 1.15 IV. DESCRIPTION OF STUDIED SYSTEM The power system simulation software PowerFactory 13.1 is used in this study. The studied system is an actual regional power grid integrating a large wind farm into 22kV transmission network via bus 1 (POI: point of interconnection). The single line diagram of this studied grid is illustrated in Figure 6. A I 1.1 a ) DFIG Based Wind Farm with Constant Power Factor Control 95 mn Wind Farm Active Power Output [MW] Fig.7. PV curves of wind farms based on different wind turbines technology It can be seen from Figure 7 that the steadystate voltage stability limits of induction generator based wind farm with noload compensation is only 213MW. When more real wind power injects into the POI than 213MW, the voltage will collapse. When the DFIG based wind farm with constant power factor control that control the POI as a PQ bus with Q MW, the steadystate voltage stability limits are increased largely to 424MW. When 35MW real wind power injects into the grid, the voltage stability margin can be acceptable. tig.6. Single line diagram ot the studied systems It must be noted that induction generator based wind farm The local grid incorporating wind power is in the with fullload compensation can enhance the voltage stability peripheral of the regional grid. The synchronous generator limit, but not very obviously; the fullload shunt capacitor models in the grid consist of AVR and prime mover model. compensation should not be put into use in low wind power The six order synchronous generator model considering the output totally or else that will arise bus voltage higher than variation of E1" 1E" Ed> E>is adopted. The load acceptable voltage level such as the curve. In actual
5 5 operation of wind farm with fullload compensation, the shunt capacitor should be switched on gradually along with the active power output increasing. Due to the shunt capacitors compensation, the voltage collapse value in case equal to.95 pu is higher than that in case or case equal to.85 pu. Because the reactive power output of shunt capacitors is proportional to V2 as the grid voltage decreasing, the capacitors cannot provide the rating reactive power. The shunt capacitor's reactive power capability is limited in case of lower voltage and cannot improve the voltage stability of the local grid fundamentally. B. VQ curve analysis ofwindfarm with different generator VQ curve is a powerful tool to analysis the steadystate voltage stability limits and reactive power margins of the grid by describing the relationship between the bus voltage and the injected reactive power into the same node [12]. It illustrates the reactive power distance from the normal operation point to the voltage collapse point. In this studies, the VWQ curves of different active power output of wind farms based on different types of wind turbines are shown in figure 8 to figure 1. In the case of induction generator based wind farm with noload compensation, there is a 13MVar reactive power margin when the wind farm active power output is 2MW; in the case of DFIG based wind farm, there is a 12MVar reactive power margin when the wind farm active power output is 4MW. The acceptable injected real wind power in case double than that in case because the DFIG based wind turbines can provide the reactive power to keep a constant power factor of the whole wind farm and reactive power exchange zero in the POI. This characteristic of DFIG based wind farms would enhance the voltage stability of the local grid integrating wind power. High demand of reactive power is the major characteristic of large wind farms that causes voltage problems to power networks. The larger the wind farm, the more severe this effect could be. If the network is not able to meet the wind farm reactive power requirement, the wind power penetration into the power system should be limited. 25 Wind Farm VQ Curve > 2 15(5) o 5MW 1MW 15MW 2MW (5) 25MW s 6 5 z D (l.5 C. a1) 2MW 25MW (5) 3MW 1MW (5) > 1 5MW Wind Farm VQ Curve Bus Voltage of POI [pu] Fig.9. VQ curve of wind farm based on IG with fullload compensation 25 2 Wind Farm VQ Curve 15 (5) 1 5MW 2MW 3MW 4MW (5) 45MW ~ c) >D D 1 "I Bus Voltage of POI [pu] Fig.lO. VQ curve of DFIG based wind farm VI. TRANSIENT VOLTAGE STABILITY ANYLYSIS In the transient voltage stability analysis of wind power integration, the voltage recovery issue of gridconnected wind turbines after the clearance of an external shortcircuit fault is a basic topic. If the terminal voltage of the gridconnected wind turbines can be restored, the wind turbines can still be connected into the grid and keep in service. If the voltage cannot be restored, the wind turbines need to be tripped or it will collapse the local grid voltage. For transient voltage stability study in this paper, the three phase shortcircuit fault on the line from bus 3 to bus 6 is simulated at the simulation time t Is. After the fault clearance, the transmission line will be tripped simultaneously. A. Transient voltage stability of IG based windfarm In the case of wind farm with induction generator, the fault critical clearing time is calculated with the wind farm installed capacity increasing. The simulation results are shown in table 1. TABLE 1 FAULT CRITICAL CLEARING TIME OF IG BASED WIND FARM 1 15 Bus Voltage of PI [pu] Fig.8. VQ curve of wind farm based on IG with noload compensation Wind farm installed capacity (MW) critical clearing time(s)
6 6 Along with the wind farm installed capacity increasing, the fault critical clearing time is reduced significantly. When the wind farm installed capacity is above 15MW, the fault critical clearing time is reduced to s. Which means even if the fault clearing time is infinite small, the induction generator terminal voltage cannot be restored because the network is weakened due to the tripped line. The transmission network should not meet the reactive power demand of the wind farm with high output and the local loads so that the voltage collapse is occurred. When the power system relay protection is considered, the line with 3 phase shortcircuit fault will be tripped in. Is. The wind turbines generator terminal voltage profile; speed and reactive power consumption is given in figure 11 and figure 12. The wind turbines protection system doesn't be taken into account D.9 U) E D 5 U).4 CO C.3 (D.2 3 a,) (9) 5MW 1MW 15MW 2MW U Fig.1 1. Voltage recovery of IG based wind farm B. Transient voltage stability ofdfig based windfarm In the case of wind farm with doubly fed induction generator, the fault critical clearing time is calculated with the wind farm installed capacity increasing. The simulation results are shown in table 2. TABLE 2 FAULT CRITICAL CLEARING TIME OF DFIG BASED WIND FARM Wind farm installed capacity critical clearing (MW) time(s) 2 > When the wind farm installed capacity is lower than 2MW, the fault critical clearing time is larger than 1 s; the transient voltage stability of local grid is greatly larger than in the case of induction generator. More wind power installed capacity increasing; the fault critical clearing time is also reduced demonstrating that the transient voltage stability is deteriorated. When the wind farm installed capacity reaches 3MW, the fault critical clearing time is reduced to s. When the power system relay protection is considered, the line with 3 phase shortcircuit fault will be tripped in. Is. The wind turbines generator terminal voltage profile; speed and reactive power consumption is given by figure 13 and figure 14. The wind turbines protection system doesn't be taken into account D.9 7).8 C.6.E_ D 5.4 CO (D / Fig. 13. Voltage recovery of DFIG based wind farm I V 1i&&& f ) 5MW 1MW 2MW 3MW Fig. 12. IG speed and reactive power after 3 phase shortcircuit fault It can be seen that when the wind farm installed capacity exceed 15 MW, the wind farm's voltage cannot be restored after the fault clearance; the wind turbine generator speed is accelerated up to overspeeding. Because wind turbines based on induction generator still need reactive power consumptions during the voltage recovery period and the tripped line weakens the network configuration, the local network transient voltage stability will be destroyed. Q Uo U) U) U1) 4 Fig. 14. DFIG speed and reactive power after 3 phase shortcircuit fault
7 7 In all the study cases, the DFIG based wind turbines have a better voltage recovery performance than the same rating IG based wind turbines. Due to the control capability to regulate reactive power and voltage, the DFIG wind turbines will mitigate the adverse affect on voltage stability of the local transmission grid. Even if the wind farm installed capacity reaches 3MW, the control system of the DFIG also can prevent the generator speed from overspeeding after the fault clearance; but there is an imbalance between the wind turbines mechanical power and electric power because the low voltage following the fault that limits the wind farm active power output, which results in the oscillation of the speed, power and voltage of the wind farm. In actual operation, it can be resolved by tripping some wind turbines or by adopting pitch control to reduce the mechanical power of the wind turbines. VII. CONCLUSION In this paper the wind power integration impact on voltage stability are studied both in steadystate and in transient state. The differences of the impact of wind farms with different types of wind turbines are compared. The following conclusions are drawn: a. Wind turbines equipped with simple induction generator are not provided with reactive power regulation capability. Voltage stability deterioration is mainly due to the large amount of reactive power absorbed by the wind turbine generators during the continuous operation and system contingencies. b. Wind turbines equipped with doubly fed induction generator (DFIG) are capable of reactive power regulation; can absorb or supply reactive power by the PWM converters. The adverse affect on local network voltage stability is mitigated so that more wind power installed capacity base on DFIG can be incorporated into the grid. c. The transient voltage stability characteristics of wind turbines with DFIG are better than that of wind turbines with induction generator because of the voltage control capability of the DFIG; The DFIG based wind turbines have a better voltage recovery performance than the same rating IG based wind turbines. VIII. REFERENCES [1] Vladislav Akhmatov, "Analysis of Dynamic Behavior of Electric Power Systems with Large amount of Wind Power," Ph.D. dissertation, Dept. Electric Power Eng., OrstedDTU, Denmark, April 23. [2] Y. Lei, A. Mullane, G. Lightbody, R. Yacamini, "Modeling of the Wind Turbine with a Doubly Fed Induction Generator for Grid Integration Studies," IEEE Trans. Energy Conversion, vol. 21, issue 1, pp , March. 26. [3] R. Pena, J. C. Clare, G. M. Asher, "Doubly fed induction generator using backtoback PWM converters and its application to variable speed windenergy generation," IEE proc.electr. Power Appl., Volume 143, Issue 3, May 1996 Page(s): [4] Poller.M.A, "Doublyfed induction machine models for stability assessment of wind farms," Power Tech Conference Proceedings, IEEE Bologna, Volume 3, 2326 June 23 Page(s):6 pp. [5] "Dynamic Modeling of DoublyFed Induction Machine WindGenerators," Digsilent GmbH, Germany, Tech. Rep., Aug. 23. [6] [7] [8] [9] [1] [11] [12] [13] A. D. Hansen, C. Jauch, and P. Sorensen, "Dynamic Wind Turbine Models in Power System Simulation Tool Digsilent," Ris National Laboratory, Ris, Denmark, Tech. Rep. RisR4(EN), Dec. 23. A. Feijo, J. Cidrs, and C. Carrillo, "Third order model for the doublyfed induction machine," Elect. Power Syst. Res., vol. 56, pp , Mar.2. N.W. Miller, J. J. SanchezGasca, W.W. Price, "Dynamic modeling of GE 1.5 and 3.6MW wind turbine generators for stability simulations," Proc. IEEE Power Engineering Society General Meeting, vol. 3, Jul. 23, pp K. Nandigam, B. H. Chowdhury. "Power flow and stability models for induction generators used in wind turbines," IEEE Power Engineering Society General Meeting, Vol.2, 61 June 24 Page(s): P. Kunder, Power System Stability and Control, New York: McGrawHill, F.Q.Zhou, G.Joos, C.Abbey, "Voltage Stability in Weak Connection Wind Farms," Power Engineering Society General Meeting, 25. IEEE. Volume 2, 1216 June 25 Page(s): C. W. Taylor, Power system voltage stability, New York: McGrawHill, L. T. Ha, T. K. Saha, "Investigation of Power Loss and Voltage Stability Limits for Large Wind Farm Connections to a Subtransmission Network," Power Engineering Society General Meeting, 24. IEEE, 61 June 24 Page(s): Vol.2. IX. BIOGRAPHIES Yongning Chi received the B.Eng and M.Eng degrees in 1995 and 22 respectively, both from Shandong University, China, all in electrical power system engineering. He is currently a Ph.D. candidate with China Electric Power Research Institute in Beijing. His most recent research involves integration of wind power into the Jilin power grid in Northeast China. His primary fields of interest are wind power integration impact on power system and power system stability analysis. Yanhua Liu received the B.Eng degree from Taiyuan Technology University, in 1997, and M.Eng degree from North China Electric Power University in 2 with the specialty of power system engineering. She is a Lecturer in North China Electric Power University and pursuing her doctor degree in China Electric Power Research Institute in Beijing. Her primary fields of interest are wind power integration and wind power planning. Weisheng Wang received his Bachelor degree and Master degree at Xi'an University of Technology, Doctor degree at Xi'an Jiaotong University, in July 199, July 1993 and Dec. 1996, respectively, all in Electrical Engineering. Now, He is a senior engineer in China Electric Power Research Institute. His areas of research interest are power system and wind power generation. Huizhu Dai graduated from Department of Electrical Engineering, Tsinghua University in July From 1981 to 1983, she worked in Leihigh University and Cornell University, USA as a senior visiting scholar. Now, she is a professor in China Electric Power Research Institute. Her areas of research interest are power system and wind power generation.
Power Flow Control Scheme for Wind Energy Conversion System
Vol.2, Issue.3, May-June 2012 pp-644-648 ISSN: 2249-6645 Power Flow Control Scheme for Wind Energy Conversion System using FACTS Controller R. Vibin 1, K. Malarvizhi 2 1 PG Scholar, Department of EEE,
More informationComparison of Variable Speed Wind Turbine Control Strategies
Comparison of Variable Speed Wind Turbine Control Strategies S. Arnaltes Department of Electrical Engineering Escuela Politécnica Superior, Universidad Carlos III de Madrid Avda. Universidad 30, 8911 Leganés
More informationRESEARCH ON THE VIRTUAL SYNCHRONOUS GENERATOR CONTROL STRATEGY OF GRID-CONNECTED PERMANENT-MAGNET DIRECT-DRIVEN WIND POWER SYSTEM
RESEARCH ON THE VIRTUAL SYNCHRONOUS GENERATOR CONTROL STRATEGY OF GRID-CONNECTED PERMANENT-MAGNET DIRECT-DRIVEN WIND POWER SYSTEM Xiaohong Hao 1, Huimin Wang 1, Bei Peng 1,2 *, Zhi Yao 1,Yixiong Wang 1,
More informationLarge-scale Wind Power Integration and Voltage Stability Limits in Regional Networks
Large-scale Wind Power Integration and Voltage Stability Limits in Regional Networks Magni Þ. Pálsson, Trond Toftevaag, Member IEEE, Kjetil Uhlen, Member IEEE, John Olav Giæver Tande SINTEF Energy Research
More informationImpacts of the Decentralized Wind Energy Resources on the Grid
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2013 Grid of the Future Symposium Impacts of the Decentralized Wind Energy Resources on the Grid Babak Enayati, PhD, Senior
More informationLesson Learned Loss of Wind Turbines due to Transient Voltage Disturbances on the Bulk Transmission System
Lesson Learned Loss of Wind Turbines due to Transient Voltage Disturbances on the Bulk Transmission System Primary Interest Groups Balancing Authorities (BAs) Transmission Operators (TOPs) Generator Operators
More informationLARGE WIND FARM AGGREGATION AND MODEL VALIDATION MULUMBA PROSPER PANUMPABI THESIS
LARGE WIND FARM AGGREGATION AND MODEL VALIDATION BY MULUMBA PROSPER PANUMPABI THESIS Submitted in partial fulfillment of the requirements for the degree of Master of Science in Electrical and Computer
More informationSMALL GENERATOR INTERCONNECTION REQUEST (Application Form)
SMALL GENERATOR INTERCONNECTION REQUEST (Application Form) Attachment 2 Transmission Provider: Bluestem Electric Cooperative, Inc. Designated Contact Person: Kevin Heptig Address: P.O. Box 5, Wamego, Kansas
More informationWIND TURBINE PLANT CAPABILITIES REPORT
WIND TURBINE PLANT CAPABILITIES REPORT 2013 Wind Integration Studies Published by AEMO Australian Energy Market Operator ABN 94 072 010 327 Copyright 2013 AEMO AEMO 2013 WIND TURBINE PLANT CAPABILITIES
More informationIslanded Wind Energy Management System Based on Neural Networks
University of Denver Digital Commons @ DU Electronic Theses and Dissertations Graduate Studies 1-1-2015 Islanded Wind Energy Management System Based on Neural Networks Ziqiao Liu University of Denver Follow
More informationR2 TESTING GUIDELINE. PREPARED BY: Network Models Systems Capability VERSION: Final RELEASE DATE: 28 June 2013
PREPARED BY: Network Models Systems Capability VERSION: Final RELEASE DATE: 28 June 2013 Version Release History Version Date By Approved By Changes 0.1 June 2013 BB MS This document has been created by
More informationRefinement of Hydel power by implementing FACTS at Narangwal hydroelectric power plant
International Journal of Electronics Engineering Research. ISSN 0975-6450 Volume 9, Number 8 (2017) pp. 1323-1328 Research India Publications http://www.ripublication.com Refinement of Hydel power by implementing
More informationInvestigation of Impacts of Solar PV on Transmission System Voltage Stability Considering Load Characteristics and Protection
7th Solar Integration Workshop, 24-25 October 2017, Berlin, Germany Investigation of Impacts of Solar PV on Transmission System Voltage Stability Considering Load Characteristics and Protection Baheej
More informationTechnical considerations for integration of distributed renewables on the grid
Technical considerations for integration of distributed renewables on the grid A paper by Dr Charlotte Higgins, Dr Bunmi Adefajo & Kumbuyani Chisoro Kumbuyani Chisoro Manager Southern Africa TNEI Services
More informationPower quality improvement by using STATCOM control scheme in wind energy generation interface to grid
IOP Conference Series: Earth and Environmental Science PAPER OPEN ACCESS Power quality improvement by using STATCOM control scheme in wind energy generation interface to grid To cite this article: Sheeraz
More informationPhD Dissertation Defense Presentation
PhD Dissertation Defense Presentation Wednesday, September 11 th, 2013 11:00am 1:00pm C103 Engineering Research Complex ADVANCED INVERTER CONTROL FOR UNINTERRUPTIBLE POWER SUPPLIES AND GRID-CONNECTED RENEWABLE
More informationMitigation of Voltage Fluctuations in Power System Using STATCOM
RESEARCH ARTICLE OPEN ACCESS Mitigation of Voltage Fluctuations in Power System Using STATCOM M. Venkatesh & Ramakrishna Raghutu Assistant Professors, Dept. of Electrical & Electronics Engineering, GMRIT,
More informationWIND TURBINES IN WEAK GRIDS CONSTRAINTS AND SOLUTIONS. J O G Tande and K Uhlen. SINTEF Energy Research, Norway SUMMARY
WIND TURBINES IN WEAK GRIDS CONSTRAINTS AND SOLUTIONS J O G Tande and K Uhlen SINTEF Energy Research, Norway SUMMARY Cost efficient utilisation of the wind energy resource requires wind farms to be located
More information8 th Annual Electric Power Industry Conference
8 th Annual Electric Power Industry Conference STATCOM Application to Address Grid Stability and Reliability: Part I November 11 th, 2013 Authors: Donald Shoup, P.E. and Dr. Gregory Reed Support: Nick
More informationLinear Programming Approach to the Residential Load Energy Management System
Linear Programming Approach to the Residential Load Energy Management System Sunny Prakash 1, Punya 2 1,2 Department of EEE, Acharya Nagarjuna University Abstract: This paper proposes an effective method
More informationPower Quality Assessment of Large Motor Starting and Loading for the Integrated Steel-Making Cogeneration Facility
Power Quality ssessment of Large Motor Starting and Loading for the Integrated Steel-Making Cogeneration Facility Cheng-Ting Hsu, Member, IEEE Department of Electrical Engineering Southern Taiwan University
More informationSi Chen. Network reduction in power system analyses
Si Chen Network reduction in power system analyses Master project Thesis, March 2009 Si Chen Network reduction in power system analyses Master project Thesis, March 2009 Network reduction in power system
More informationThe Effect of the Volt/Var Control of Photovoltaic Systems on the Time-Series Steady-State Analysis of a Distribution Network
The Effect of the Volt/Var Control of Photovoltaic Systems on the Time-Series Steady-State Analysis of a Distribution Network Insu Kim, Ronald G. Harley, and Raeey Regassa Georgia Institute of Technology,
More informationTransient Stability Analysis of an Industrial Cogeneration System
Transient Stability Analysis of an Industrial Cogeneration System Hung-Cheng Chen Shang-Yi Chen Shun-Chung Shih Department of Electrical Engineering, National Chin-Yi University of Technology hcchen@ncut.edu.tw
More informationA non-linear Control of Power Wind Turbine Based on Doubly Fed Induction Generator
A non-linear Control of Power Wind Turbine Based on Doubly Fed Induction Generator Karima Boulaam and Akkila Boukhelifa Instrumentation Laboratory Faculty of Electronics and Computers University of Sciences
More informationModeling of Incremental Inductance Based PV System with Power Grid
Modeling of Incremental Inductance Based PV System with Power Grid B.Suryanarayana 1, Dr.B.Srinivasarao 2 1 PG Scholar, Dept. Of EEE, SVCET, Srikakulam, Andhra Pradesh, (India) 2 Assoc. Professor, Dept.
More informationPermanent Magnet Synchronous Generator Based Energy Conversion System: A Review
Permanent Magnet Synchronous Generator Based Energy Conversion System: A Review Bhawna Gupta 1, Gagan Deep Yadav 2 1 M-Tech Scholar, EE Department, YIET, Gadhauli, India 2 Assistant Professor, EE Department,
More informationElectricity generation, electricity consumption, system integration, production and consumption balance
Prof. Dr. Andrej Gubina University of Ljubljana, Faculty of Electrical Engineering Electricity generation, electricity consumption, system integration, production and consumption balance Maribor, Slovenia,
More informationWind Energy Conversion Using Shunt Active Power Filter
Quatrième onférence Internationale sur le Génie Electrique IGE 1, 34 Novembre 21, Université de echar, lgérie Wind Energy onversion Using Shunt ctive Power Filter Samira Dib, rahim Ferdi, hellali enachaiba
More informationValidation of dynamic models of wind farms (Erao-3)
ECN-E 07-006 Validation of dynamic models of wind farms (Erao-3) Executive summary, benchmark results and model improvements J.T.G. Pierik (ECN) J. Morren (TUD) 1 January 2007 Validation of dynamic models
More informationPower-Flow Analysis of Large Wind Power Plant Collector Systems With Remote Voltage Control Capability
1 Power-Flow Analysis of Large Wind Power Plant Collector Systems With Remote Voltage Control Capability Mohamed Zakaria Kamh and Reza Iravani Abstract This paper presents and develops a new powerflow
More informationH AND REPETITIVE CONTROL
H AND REPETITIVE CONTROL OF GRID-CONNECTED INVERTERS Qing-Chang Zhong zhongqc@ieee.org Electrical Drives, Power and Control Group Dept. of Electrical Eng. & Electronics The University of Liverpool United
More informationDistributed Generation Placement Design and Contingency Analysis with Parallel Computing Technology
JOURNAL OF COMPUTERS, VOL. 4, NO. 4, APRIL 9 347 Distributed Generation Placement Design and Contingency Analysis with Parallel Computing Technology Wenzhong Gao and Xi Chen Tennessee Technological University,
More informationConnection of generation plant to distribution networks. Guidance on completing the application form
Connection of generation plant to distribution networks It is possible to connect almost any generation plant to the distribution network and in order for the connection to meet the requirements of a new
More informationMATHEMATICAL MODELLING AND SIMULATION OF INDUCTION GENERATOR BASED WIND TURBINE IN MATLAB/SIMULINK
MATHEMATICAL MODELLING AND SIMULATION OF INDUCTION GENERATOR BASED WIND TURBINE IN MATLAB/SIMULINK Md. Rasel Sarkar, Sabariah Julai, Chong Wen Tong, Ong Zhi Chao and Mahmudur Rahman Department of Mechanical,
More informationIntegration of Wind Power Plants in The Electric Power System: A Case Study in Piauí Brazil
International OPEN ACCESS Journal Of Modern Engineering Research (IJMER) Integration of Wind Power Plants in The Electric Power System: A Case Study in Piauí Brazil Bartolomeu Ferreira Dos Santos Junior
More informationMulti-objective reactive power support from wind farms for network performance enhancement
University of Wollongong Research Online Faculty of Engineering and Information Sciences - Papers: Part A Faculty of Engineering and Information Sciences 2013 Multi-objective reactive power support from
More informationPerformance Analysis of grid connected PV Wind Hybrid Power System
Performance Analysis of grid connected PV Wind Hybrid Power System Aditi M.Tech Research Scholar, Department of Electrical Engineering Madan Mohan Malviya University of Technology, Gorakhpur E-mail: aditi.151291@gmail.com
More information5-MW Downwind Wind Turbine Demonstration and Work Toward Smart Operation Control
FEATURED ARTICLES Next-generation Energy Solutions Aimed at Symbiosis with the Global Environment 5-MW Downwind Wind Turbine Demonstration and Work Toward Smart Operation Control Already becoming a major
More informationResearch and Application Study on Accident-Based 3D Power Station Simulation Technology
International Conference on Electromechanical Control Technology and Transportation (ICECTT 2015) Research and Application Study on Accident-Based 3D Power Station Simulation Technology Tie Li, Xiaoming
More informationImproved control strategy for the three-phase grid-connected inverter Yao, Zhilei; Xiao, Lan; Guerrero, Josep M.
Aalborg Universitet Improved control strategy for the three-phase grid-connected inverter Yao, Zhilei; Xiao, Lan; Guerrero, Josep M. Published in: IET Renewable Power Generation DOI (link to publication
More informationPower control of a photovoltaic system connected to a distribution frid in Vietnam
Power control of a photovoltaic system connected to a distribution frid in Vietnam Xuan Truong Nguyen, Dinh Quang Nguyen, Tung Tran To cite this version: Xuan Truong Nguyen, Dinh Quang Nguyen, Tung Tran.
More informationConsequence and Impact of Electric Utility Industry Restructuring on Transient Stability and Small-Signal Stability Analysis
Consequence and Impact of Electric Utility Industry Restructuring on Transient Stability and Small-Signal Stability Analysis VIJAY VITTAL, FELLOW, IEEE Invited Paper The electric utility industry is undergoing
More informationImplementation of adaptive fuzzy controller on the variable speed wind turbines in comparison with conventional methods
388 Ciência enatura, Santa Maria, v. 37 Part 1 2015, p. 388 396 ISSN impressa: 0100-8307 ISSN on-line: 2179-460X Implementation of adaptive fuzzy controller on the variable speed wind turbines in comparison
More informationANTICIPATING AND ADDRESSING SECURITY CHALLENGES IN AN EVOLVING POWER SYSTEM
ANTICIPATING AND ADDRESSING SECURITY CHALLENGES IN AN EVOLVING POWER SYSTEM January 2017 PRESENTED BY JENNY RIESZ SLIDE 1 AGENDA 1. Introduction to the NEM 2. Future Power System Security Program 3. Identifying
More informationAdjoint wind turbine modeling with ADAMS, Simulink and PSCAD/EMTDC
NORDIC WIND POWER CONFERENCE, 1- MARCH, 4, CHALMERS UNIVERSITY OF TECHNOLOGY 1 Adjoint wind turbine modeling with ADAMS, Simulink and PSCAD/EMTDC Sanna Uski, Bettina Lemström, Juha Kiviluoma, Simo Rissanen
More informationModeling of the Dynamic Behavior of the Island Power System of Cyprus
Transmission System Operator CYPRUS Modeling of the Dynamic Behavior of the Island Power System of Cyprus Andreas G. Petoussis Stavros Stavrinos Session 6: Modeling and Power Quality Friday, 24 September
More informationSCHEDULE 12 Transmission Enhancement Charges. Establishment of Transmission Enhancement Charges.
SCHEDULE 12 Transmission Enhancement Charges (a) Establishment of Transmission Enhancement Charges. (i) Establishment of Transmission Enhancement Charges by Transmission Owners and Entities That Will Become
More informationEnergy Processing for Smart Grid (4.4)
Energy Processing for Smart Grid (4.4) PV Option Charge Transmission lines Synchronize Wind Power Option Charge Controller Storage Technologies PMU Smart Meter Switching Logic James Momoh Howard University
More informationWWSIS - 3: Western Frequency Response and Transient Stability Study
WWSIS - 3: Western Frequency Response and Transient Stability Study GE Energy Nicholas W. Miller (PM) Miaolei Shao Slobodan Pajic Rob D Aquila NREL Kara Clark (PM) NERC ERSTF Briefing Atlanta December
More informationPERMANENT MAGNET SYNCHROUNOUS GENERATOR WIND TURBINE PITCH ANGLE CONTROL BY FUZZY AND PID CONTROL
PERMANENT MAGNET SYNCHROUNOUS GENERATOR WIND TURBINE PITCH ANGLE CONTROL BY FUZZY AND PID CONTROL B.Chinna Rao 1, M.Durga Prasada Rao 2, 1Pg scholar, Department of EEE, Bapatla engineering college, Andhra
More informationDynamic Models of Wind Turbines
THESIS FOR THE DEGREE OF DOCTOR OF PHILOSOPHY Dynamic Models of Wind Turbines A Contribution towards the Establishment of Standardized Models of Wind Turbines for Power System Stability Studies ABRAM PERDANA
More informationStandard TPL Transmission System Planning Performance Requirements
A. Introduction 1. Title: Transmission System Planning Performance Requirements 2. Number: TPL-001-4 3. Purpose: Establish Transmission system planning performance requirements within the planning horizon
More informationAdvice on Power Factor and Accuracy of Temperature Dependant Outputs
Advice on Power Factor and Accuracy of Temperature Dependant Outputs REPORT WP03749-EE-RP-0001 Rev. 1 3 September 2009 Advice on Power Factor and Accuracy of Temperature Dependant Outputs REPORT WP03749-EE-RP-0001
More informationANALYSIS OF THE BEHAVIOR FOR REACTIVE POWER COMPENSATION USING SVC CONTROLLED HYBRID SOLAR/WIND POWER GENERATING SYSTEMS
ANALYSIS OF THE BEHAVIOR FOR REACTIVE POWER COMPENSATION USING SVC CONTROLLED HYBRID SOLAR/WIND POWER GENERATING SYSTEMS Shadab Shakeel 1, Ameenuddin Ahmed 2 1 Student, M.Tech, 2 Asst. Prof., Department
More informationTransmission Competitive Solicitation Questions Log Question / Answer Matrix Delaney to Colorado River 2014
No. Comment Submitted ISO Response Date Q&A Posted 1 Can the CAISO provide a line rating methodology (similar to a NERC FAC-008 standard) or include a requirement of using any The ISO does not provide
More informationAORC Technical meeting 2014
http : //www.cigre.org B4-053 AORC Technical meeting 204 Optimized Operation of Hydropower Plant with VSC HVDC Unit Connection Xiaobo Yang, Chao Yang, Chengyan Yue, Dawei Yao, Chunming Yuan Corporate Research,
More informationMaster Thesis Department of Electrical Engineering. The Effect of a Short- Circuit Current in a High Voltage Installation With a Synchronous Machine.
44 The Effect of a Short- Circuit Current in a High Voltage Installation With a Synchronous Machine. Background Short circuit in a power plant leads to large short-circuit currents and causes large mechanical
More informationOptimum Return Period of an Overhead Line Considering Reliability, Security and Availability with Respect to Extreme Icing Events
IWAIS XIV, China, May 0 Optimum Return Period of an Overhead Line Considering Reliability, Security and Availability with Respect to Extreme Icing Events Asim Haldar, Ph.D, P.Eng. ahaldar@nalcorenergy.com
More informationPOWER SYSTEM STABILITY GUIDELINES
PREPARED BY: DOCUMENT REF: Planning PSSG-02 VERSION: 1.0 DATE: 25 May 2012 FINAL Final Matt Zema CEO Date 25/ 5 /2012 Version Release History VERSION DATE AUTHOR PEER REVIEW APPROVED COMMENTS 1.0 25/5/12
More informationDynamic modeling and characterization of a wind turbine system leading to controls development
Rochester Institute of Technology RIT Scholar Works Theses Thesis/Dissertation Collections 8-1-2010 Dynamic modeling and characterization of a wind turbine system leading to controls development Greg Semrau
More informationNERC Reliability Initiatives and Smart Grid
NERC Reliability Initiatives and Smart Grid IEEE PES Late Breaking News July 28, 2009 Robert W. Cummings Director of Event Analysis & Information Exchange System Protection and Control Performance Improvement
More informationImproved Wind Turbine Control Strategies for Maximizing Power Output and Minimizing Power Flicker
University of Wisconsin Milwaukee UWM Digital Commons Theses and Dissertations 5-1-2014 Improved Wind Turbine Control Strategies for Maximizing Power Output and Minimizing Power Flicker Quan Chen University
More informationInternational ejournals
ISSN 2249 5460 Available online at www.internationalejournals.com International ejournals International Journal of Mathematical Sciences, Technology and Humanities 21 (2011) 205 212 ENERGY CONTROL CENTER
More informationContribution of PV Power Plants to Flicker Severity in Power Distribution Grids
Contribution of PV Power Plants to Flicker Severity in Power Distribution Grids Denisa G. Rusinaru, Leonardo G. Manescu, Adelaida, M. Duinea and Cristian C. Bratu Abstract This paper presents some results
More informationELECTRIC ARC FURNACE WITH STATIC VAR COMPENSATOR PLANNING AND OPERATIONAL EXPERIENCE
GERHARD HACKL 1 HERWIG RENNER 2 MANFRED KRASNITZER 3 CHRISTIAN HOFBAUER 1 ELECTRIC ARC FURNACE WITH STATIC VAR COMPENSATOR PLANNING AND OPERATIONAL EXPERIENCE Abstract The paper describes the process of
More informationENERGY HARVESTING. Energy Conversion Systems. Solar, Wind, and Ocean. Omer C. Onar. Alireza Khaligti
ENERGY HARVESTING Solar, Wind, and Ocean Energy Conversion Systems Alireza Khaligti Omer C. Onar Energy, Power Electronics, and Machines Series AH Emadi, Series Editor TECHNiSCHE INFOF.MATIONSBIBLIOTHEK
More informationFlexibility services in the electrical system
Flexibility services in the electrical system Sébastien Mathieu March 02, 2016 S. Mathieu Flexibility services in the electrical system 2/50 Outline The European electrical system Flexibility in electrical
More informationHydro-Quebec s experience with HYPERSIM Real-time Power System Simulator
Hydro-Quebec s experience with HYPERSIM Real-time Power System Simulator Christian Larose, Power System Simulation, Hydro-Québec (CANADA) June 26, 2013 Presentation overview > Application of Hypersim at
More informationWind farm models and control strategies
Risø-R-1464(EN) Wind farm models and control strategies Poul Sørensen, Anca D. Hansen, Florin Iov, Frede Blaabjerg and Martin H. Donovan Risø National Laboratory Roskilde Denmark August 2005 Author: Poul
More informationH REPETITIVE CURRENT CONTROLLER FOR
H REPETITIVE CURRENT CONTROLLER FOR GRID-CONNECTED INVERTERS Tomas Hornik and Qing-Chang Zhong Dept. of Electrical Eng. & Electronics The University of Liverpool UK Email: Q.Zhong@liv.ac.uk Acknowledgement
More informationCentralized wind power plant voltage control with optimal power flow algorithm
Graduate Theses and Dissertations Graduate College 2011 Centralized wind power plant voltage control with optimal power flow algorithm Jared Andrew Kline Iowa State University Follow this and additional
More informationGrid Connection and Power Quality Optimization of Wind Power Plants
Grid Connection and Power Quality Optimization of Wind Power Plants Fikri Baris UZUNLAR 1, Onder GULER 2, Ozcan KALENDERLI 3 1, 2 Istanbul Technical University, Energy Institute, Istanbul, Turkey barisuzunlar@hotmail.com,
More informationAssessment of the Steady State Voltage Stability of the Ghanaian Transmission System with the Integration of Renewable Energy Sources
Assessment of the Steady State Voltage Stability of the Ghanaian Transmission System with the Integration of Renewable Energy Sources M. W. Asmah, R. Baisie, B. K. Ahunu, J. M. A. Myrzik Abstract--The
More informationImpact study of PV integration in Bornholm power system
Downloaded from orbit.dtu.dk on: Jan 31, 2018 Impact study of PV integration in Bornholm power system Korompili, Asimenia; Zimmermann, Jakob Kjær; Wu, Qiuwei Publication date: 2014 Document Version Publisher's
More informationThermal Management of Densely-packed EV Battery Set
EVS28 KINTEX, Korea, May 3-6, 2015 Thermal Management of Densely-packed EV Battery Set Abstract Z. Lu 1, X.Z. Meng 1, W.Y. Hu 2, L.C. Wei 3, L.Y. Zhang 1, L.W. Jin 1* 1 Building Environment and Equipment
More informationETAP PowerStation 4.0
ETAP PowerStation 4.0 User Guide Copyright 2001 Operation Technology, Inc. All Rights Reserved This manual has copyrights by Operation Technology, Inc. All rights reserved. Under the copyright laws, this
More informationStandard PRC-002-NPCC-01 Disturbance Monitoring
A. Introduction 1. Title: Disturbance Monitoring 2. Number: PRC-002-NPCC-01 3. Purpose: Ensure that adequate disturbance data is available to facilitate Bulk Electric System event analyses. All references
More informationSummary of Studies on Rate of Change of Frequency events on the All-Island System
Summary of Studies on Rate of Change of Frequency events on the All-Island System August 212 Authored by: Salim Temtem & Karen Creighton Checked by: David Cashman & Raymond Skillen Approved by: Jonathan
More informationGRID CODE FOR ISOLATED SYSTEMS
1 GRID CODE FOR ISOLATED SYSTEMS Susana Ludovino REDE ELÉCTRICA NACIONAL, S.A., 1749-061 Lisboa, PORTUGAL (e-mail: susana.ludovino@ren) Abstract The aim of this study is to verify the application of an
More informationIntegrating Building Automation Systems with Microgrid Controls. Mingguo Hong, Associate Professor Case Western Reserve University Cleveland, OH
1 Integrating Building Automation Systems with Microgrid Controls Mingguo Hong, Associate Professor Case Western Reserve University Cleveland, OH 2 The Typical Commercial Buildings Are aggregates of generation,
More informationCase Metrics 2015 Summer Base Case Quality Assessment Phase I Powerflow and Dynamics Case Quality Metrics FINAL
Case s 2015 Summer Base Case Quality Assessment Phase I Powerflow and Dynamics Case Quality s FINAL Introduction Powerflow and dynamics cases are the foundation of virtually all power system studies. Calculations
More informationFacility Interconnection Requirements
Facility Interconnection Effective 1/1/2016 1. Purpose Facility Interconnection Facility Interconnection (FAC-001-2) To avoid adverse impacts on the reliability of the Bulk Electric System (BES), RPU documents
More informationPOTOMAC ELECTRIC POWER COMPANY
POTOMAC ELECTRIC POWER COMPANY FERC Form 715 (Part 4) - Transmission Planning Study Guidelines Transmission Reliability Guidelines 1. General Overview The reliability guidelines used to plan the transmission
More informationPerformance Improvement in Distribution Network with DG
The 23 224 nd International 25 Power Engineering and Optimization Conference (PEOCO2008), Shah Alam, Selangor, MALAYSIA. 4-5 June 2008. Performance Improvement in Distribution Network with DG 1 Siti Rafidah
More informationCSIRO CLUSTER PROJECT #3
CSIRO CLUSTER PROJECT #3 Milestone 5 Optimal Sitting and Dispatch of Distributed generation A software development and simulation of generation and cost optimised controller By Dilan Jayaweera, Syed Islam,
More informationStability Analysis of DFIG based Wind Energy System
ISSN (Print) : 319-8613 ISSN (Online) : 0975-404 Stability Analysis of DFIG based Wind Energy System K. Latha Shenoy #**1, C. Gurudas Nayak *, Rajashekar P Mandi **3 # Department of E&E Engineering, NMAM
More informationSecurity, protection, and control of power systems with large-scale wind power penetration
Graduate Theses and Dissertations Graduate College 2010 Security, protection, and control of power systems with large-scale wind power penetration Naresh Acharya Iowa State University Follow this and additional
More informationWestern Wind & Solar Integration Studies
Western Wind & Solar Integration Studies Kara Clark, Greg Brinkman, NREL Nick Miller, Miaolei Shao, Slobodan Pajic, Rob D Aquila, Bruno Leonardi, GE 3/22/17 NREL is a national laboratory of the U.S. Department
More informationAdaptive Fuzzy Logic Control of Wind Turbine Emulator
International Journal of Power Electronics and Drive System (IJPEDS) Vol. 4, No., June 14, pp. ~4 ISSN: 88-8694 Adaptive Fuzzy Logic Control of Wind Turbine Emulator Bouzid Mohamed Amine*, Zine Souhila**,
More informationStandard Development Timeline
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard is adopted by the NERC Board of Trustees (Board).
More informationFull electrical LNG-plant: Highest availability and energy efficiency trough overall system design
Full electrical LNG-plant: Highest availability and energy efficiency trough overall system design Dr. Edwin Lerch Principal Expert Power System Dynamics Siemens AG Erlangen, Germany edwin.lerch@siemens.com
More informationHierarchical Frequency Control Scheme for Islanded Multi-Microgrids Operation
Hierarchical Frequency Control Scheme for Islanded Multi-Microgrids Operation Nuno José Gil, and J. A. Peças Lopes, Senior Member, IEEE Abstract This paper presents a new hierarchical approach to deal
More informationPSS E. High-Performance Transmission Planning Application for the Power Industry. Answers for energy.
PSS E High-Performance Transmission Planning Application for the Power Industry Answers for energy. PSS E architecture power flow, short circuit and dynamic simulation Siemens Power Technologies International
More informationOptimal Control and Operation Strategy for Wind Turbines Contributing to Grid Primary Frequency Regulation
applied sciences Article Optimal Control and Operation Strategy for Wind Turbines Contributing to Grid Primary Frequency Regulation Mun-Kyeom Kim School Energy System Engineering, Chung-Ang University,
More informationThe Impact of Grid Connected Photovoltaic Generation System to Voltage Rise in Low Voltage Network
The Impact of Grid Connected Photovoltaic Generation System to Voltage Rise in Low Voltage Network ASNAWI MOHD. BUSRAH 1, VIGNA KUMARAN R. 2 1 Energy System Group TNB Research Kajang, Selangor MALAYSIA
More informationThe Power Quality of Wind Turbines
THESIS FOR THE DEGREE OF DOCTOR OF PHILOSOPHY The Power Quality of Wind Turbines ÅKE LARSSON Department of Electric Power Engineering CHALMERS UNIVERSITY OF TECHNOLOGY Göteborg, Sweden 2000 The Power Quality
More informationCharacterisation of gas turbine dynamics during frequency excursions in power networks
University of Wollongong Research Online Faculty of Engineering and Information Sciences - Papers: Part A Faculty of Engineering and Information Sciences 2014 Characterisation of gas turbine dynamics during
More informationValue-based Transmission Investment and Operations. Marija Ilic Invited Panel, IEEE PES 2014 Washington DC
Value-based Transmission Investment and Operations Marija Ilic milic@ece.cmu.edu Invited Panel, IEEE PES 2014 Washington DC 2 Outline The evolving role of on-line T&D management Basic definition of an
More informationStudy on the evaluation index of active power reserve
IOP Conference Series: Earth and Environmental Science PAPER OPEN ACCESS Study on the evaluation index of active power reserve To cite this article: Xiaorui Guo et al 2018 IOP Conf. Ser.: Earth Environ.
More information