the weidt group Implementation Rates of Energy Conservation Measures for Health Care Buildings collaboration analysis research
|
|
- Dwight Ellis
- 6 years ago
- Views:
Transcription
1 Implementation Rates of Energy Conservation Measures for Health Care Buildings the weidt group collaboration analysis research HIGH PERFORMANCE BUILDINGS PAGE 1 THE WEIDT GROUP TH NATIONAL CONFERENCE ON BUILDING COMMISSIONING 2 MAY 2007
2 Energy Consulting Process Schematic Design Design Development Construction Documents Construction Occupancy Energy Measure Development DOE-2 Energy Modeling Cost Analysis Selection of Measures Draft CD Review Final CD Review Draft Verification Final Verification Energy Design Assistance Design Review and Verification PAGE 2 THE WEIDT GROUP 2007 IMPLEMENTATION RATES OF ENERGY CONSERVATION MEASURES 2 MAY 2007
3 Data Resources at The Weidt Group 554 Completed EDA Projects 100,000,000 Square Feet 428 Field Verified Projects One third of these done by The Weidt Group PAGE 3 THE WEIDT GROUP 2007 IMPLEMENTATION RATES OF ENERGY CONSERVATION MEASURES 2 MAY 2007
4 Design Review Process Construction Documents Windows Wall and roof insulation Daylighting control and other lighting control Lighting design Mechanical equipment Mechanical controls Look for specification of glass type Verify key parameters (U, SHGC, VT) Calculate overall U-value and compare with expected values Locate sensors and wiring on plans Review control sequences Count fixtures Check lamp and ballast types Check for fixture Watts Calculate W/sq ft Check for equipment types and efficiencies Check plans and schedules for key components Review control sequences PAGE 4 THE WEIDT GROUP 2007 IMPLEMENTATION RATES OF ENERGY CONSERVATION MEASURES 2 MAY 2007
5 Verification Process Submittals and Site Visits Windows Wall and roof insulation Daylighting control and other lighting control Lighting design Mechanical equipment Mechanical controls Look for specification of glass type in Submittals Verify key parameters (U, SHGC, VT) Check construction in Submittals Recalculate overall U-value, if needed Locate sensors in site visit Do functional test Do logging of lighting power to show trends Count fixtures on-site; check lamps and ballasts Determine Watts of representative fixtures Calculate W/sq ft Locate equipment in submittals and on-site Record nameplate efficiencies Check Submittals for key components Review control sequences in Submittals Conduct functional test where possible Do logging where possible to verify operation PAGE 5 THE WEIDT GROUP 2007 IMPLEMENTATION RATES OF ENERGY CONSERVATION MEASURES 2 MAY 2007
6 Implementation Rate Defined Implementation = Energy Savings at Stage Energy Savings at Selection Four Stages: Draft CD Review (DCD) Final CD Review (CD) Draft Verification (DV) Final Verification (V) PAGE 6 THE WEIDT GROUP 2007 IMPLEMENTATION RATES OF ENERGY CONSERVATION MEASURES 2 MAY 2007
7 Implementation Rates Reasons to Study How much falls out between modeling effort and release of CDs? How much can be restored by each stage of the Design Review and Verification process? PAGE 7 THE WEIDT GROUP 2007 IMPLEMENTATION RATES OF ENERGY CONSERVATION MEASURES 2 MAY 2007
8 Implementation Rates Reasons to Study What is the relative importance of CD review and post construction verification? How does this vary by measure type? PAGE 8 THE WEIDT GROUP 2007 IMPLEMENTATION RATES OF ENERGY CONSERVATION MEASURES 2 MAY 2007
9 Previous Implementation Rate Study by The Weidt Group Number of buildings 105 New construction; total Project scope building or addition Floor area per building 20,000 to 900,000 sq ft Location Iowa Office K-12 School College/ University Building types Lab Health Care Mixed Use Source: Measuring the Success Rate of ECMs in New Construction; Greden, et al; ACEEE 2006 Summer Study PAGE 9 THE WEIDT GROUP 2007 IMPLEMENTATION RATES OF ENERGY CONSERVATION MEASURES 2 MAY 2007
10 Implementation Rates By Stage From Previous Study 120% 110% 38 Buildings 5 Building Types Implementation Rate 100% 90% 80% 70% 15 % Drop 2% Rise 4% Rise 1% Drop 60% Selection DCD CD DV V PAGE 10 THE WEIDT GROUP 2007 IMPLEMENTATION RATES OF ENERGY CONSERVATION MEASURES 2 MAY 2007
11 Final Implementation Rates By Building Type from Previous Study Schools must follow state mandate for energy measures Schools have high repeat participation by owners and design team 57 Projects % kwh Savings Implementation Rate at Verification 110% 100% 90% 80% 70% College School Hospital Office (8 projects) (34) (5) (10) Building Type (No. of Projects) PAGE 11 THE WEIDT GROUP 2007 IMPLEMENTATION RATES OF ENERGY CONSERVATION MEASURES 2 MAY 2007
12 Final Implementation Rate By Participation Rate from Previous Study Implementation Rate at Verification 110% % kwh Savings 100% 90% 80% 70% Firm A Firm B Firm C Others (3 projects) (3) (2) (1 proj. each, 16 firms) Architect (no. of projects) PAGE 12 THE WEIDT GROUP 2007 IMPLEMENTATION RATES OF ENERGY CONSERVATION MEASURES 2 MAY 2007
13 Health Care Buildings Current Study Number of buildings 16 Project scope New construction; total building or addition Floor area per building 50,000 to 500,000 sq ft Location Iowa, Minnesota, Colorado Building Type Health Care PAGE 13 THE WEIDT GROUP 2007 IMPLEMENTATION RATES OF ENERGY CONSERVATION MEASURES 2 MAY 2007
14 Modeled Energy Savings for Selected Measures Average of 16 Health Care Buildings Annual Dollars Electric Energy kwh Peak Electric kw Gas Energy Savings 23% 30% 28% 6% PAGE 14 THE WEIDT GROUP 2007 IMPLEMENTATION RATES OF ENERGY CONSERVATION MEASURES 2 MAY 2007
15 Implementation Rate By Stage for 16 Health Care Buildings 140% 120% Implementation Rate 100% 80% 60% 40% 20% 0% Selection DCD CD DV V PAGE 15 THE WEIDT GROUP 2007 IMPLEMENTATION RATES OF ENERGY CONSERVATION MEASURES 2 MAY 2007
16 Average Implementation Rate By Stage for Health Care Buildings 120% 110% Implementation Rate 100% 90% 80% 70% 19 % Drop 6% Rise 5% Rise 1% Rise 60% Selection DCD CD DV V PAGE 16 THE WEIDT GROUP 2007 IMPLEMENTATION RATES OF ENERGY CONSERVATION MEASURES 2 MAY 2007
17 Average Implementation Rate By Stage for Health Care Buildings $0.50 Annual Energy Savings, $/sq ft $0.45 $0.40 $0.35 $0.30 $0.25 $0.12/sf Drop $0.023/sf Rise $0.023/sf Rise $0.003/sf Rise $0.20 Selection DCD CD DV V PAGE 17 THE WEIDT GROUP 2007 IMPLEMENTATION RATES OF ENERGY CONSERVATION MEASURES 2 MAY 2007
18 Comparison with Previous Study 120% 110% Previous Study (38 buildings) Health Care Study (16 buildings) Implementation Rate 100% 90% 80% 70% 60% Selection DCD CD DV V PAGE 18 THE WEIDT GROUP 2007 IMPLEMENTATION RATES OF ENERGY CONSERVATION MEASURES 2 MAY 2007
19 Implementation Rates By Strategy Type for Envelope and Lighting Lighting Power Density Lighting Control Envelope Switched Daylighting Dimming Daylighting 140% 120% Implementation Rate 100% 80% 60% 40% 20% 0% Model CD Review Verified PAGE 19 THE WEIDT GROUP 2007 IMPLEMENTATION RATES OF ENERGY CONSERVATION MEASURES 2 MAY 2007
20 Implementation Rates By Strategy Type Mechanical Heating and Cooling Equipment Motor Efficiency and VFDs 120% Outside Air Control 100% Implementation Rate 80% 60% 40% 20% 0% Model CD Review Verified PAGE 20 THE WEIDT GROUP 2007 IMPLEMENTATION RATES OF ENERGY CONSERVATION MEASURES 2 MAY 2007
21 Conclusions Trends for Health Care buildings are similar to other building types Highest loss of savings occurs between Selection of Measures and release of CDs CD review stages show highest savings potential Verification savings show significant savings for some projects PAGE 21 THE WEIDT GROUP 2007 IMPLEMENTATION RATES OF ENERGY CONSERVATION MEASURES 2 MAY 2007
22 Conclusions Controls oriented measures are much more likely to have lost savings than equipment measures Avg 70% loss for dimming daylighting Avg 62% loss for outside air control PAGE 22 THE WEIDT GROUP 2007 IMPLEMENTATION RATES OF ENERGY CONSERVATION MEASURES 2 MAY 2007
23 Thank you the weidt group collaboration analysis research DOUG MADDOX PAGE 23 THE WEIDT GROUP 2007 IMPLEMENTATION RATES OF ENERGY CONSERVATION MEASURES 2 MAY 2007
BUSINESS NEW CONSTRUCTION Energy Design Assistance Energy Efficient Buildings
BUSINESS NEW CONSTRUCTION Energy Design Assistance Energy Efficient Buildings Add energy efficiency to your new construction plans Business New Construction is a FREE, comprehensive approach to energy
More informationAppendix E-1f: Small Building Methodology for Pre-SB2030 Projects
Appendix E-1f: Small Building Methodology for Pre-SB2030 Projects Prescriptive Bundle Option Method for Office Buildings less than 30,000 GSF This section describes energy strategy requirements for three
More informationCommunity Energy Code Enforcement Policy
GWINNETT COUNTY Community Energy Code Enforcement Policy The design and construction of buildings in Gwinnett County for the effective use of energy are regulated by the Georgia State Minimum Standard
More informationMaking Daylighting Work Applying Cx to Improve the Design and Implementation Process
Making Daylighting Work Applying Cx to Improve the Design and Implementation Process the weidt group collaboration analysis research Jason Steinbock jasons@twgi.com The Deringer Group Joseph Deringer,
More informationBoth components are available to non-residential customers in Public Service s electric and natural gas service territory.
Page 122 of 507 New Construction A. Description The New Construction product influences building owners, architects, and engineers to include energy efficient systems and equipment in their design for
More informationMEASUREMENT AND VERIFICATION GUIDELINES FOR RETROFIT AND NEW CONSTRUCTION PROJECTS
EL PASO ELECTRIC COMPANY S LARGE COMMERCIAL AND INDUSTRIAL STANDARD OFFER PROGRAM MEASUREMENT AND VERIFICATION GUIDELINES FOR RETROFIT AND NEW CONSTRUCTION PROJECTS This document includes detailed information
More informationNext Connecticut Energy Code
Connecticut Chapter Association of Energy Engineers Next Connecticut Energy Code 1 Next Connecticut State Building Code n 2012 International Building Code n 2012 International Existing Building Code n
More informationUniversity of Minnesota Duluth Civil Engineering Building
Energy Data Attachment University of Minnesota Duluth Civil Engineering Building LEED Energy Modeling The energy modeling for LEED NC 2.2 was performed against ASHRAE 9.1-24 Appendix using equest version
More informationEnergy Strategies That Work
Energy Strategies That Work Emmy Presenter s Riley, Building name Professional Energy Specialist Title (eg. architect/energy Illini Center specialist..) 10-10-12 Smart Energy Design Assistance Center (SEDAC),
More informationENERGY ANALYSIS AND ENERGY CONSERVATION OPTION FOR THE WAREHOUSE FACILITY AT THE HUMAN SERVICES CENTER COMPLEX DRAFT REPORT.
ESL-TR-86/09-03 ENERGY ANALYSIS AND ENERGY CONSERVATION OPTION FOR THE WAREHOUSE FACILITY AT THE HUMAN SERVICES CENTER COMPLEX DRAFT REPORT Submitted by Mohsen Farzad Dennis O'Neal Prepared For Energy
More informationNew Jersey s Clean Energy Program
New Jersey s Clean Energy Program Opportunities for Commercial, Industrial and Institutional Buildings Doug Shattuck, P.E. TRC Energy Services c/o EAM Associates October 18, 2012 Making the Business Case
More informationDuke Energy Corporation
Commercial Audit for Account: 12345-56789 Thank you for completing the Duke Energy Corporation Business Energy Check. We hope the information and recommendations provided will assist you in managing your
More informationBuilding Performance Evaluation Guide
Building Performance Evaluation Guide Version 1.6 April 2012 1. Schematic Design & Design Development Phase Requirements Whole building energy simulation shall be used to determine the basis for the designed
More informationGreenStep Cities Workshop Xcel Energy Rebates: Commercial Program Overview
GreenStep Cities Workshop Xcel Energy Rebates: Commercial Program Overview Mike Meyers, Xcel Energy Commitment from Leadership Our energy conservation programs are especially valuable because they give
More informationthe weidt group DAVID A. EIJADI, FAIA collaboration analysis research HIGH PERFORMANCE BUILDINGS THE WEIDT GROUP
the weidt group collaboration analysis research + WWW.TWGI.COM HIGH PERFORMANCE BUILDINGS DAVID A. EIJADI, FAIA PAGE 1 2009 ASHRAE MN 2008 Building Performance Expectations How and When to Set Them and
More informationCost Benefits of SunGuard SN 54
Cost Benefits of SunGuard SN 54 Guardian Industries recently introduced SunGuard SN 54 low-e glass. This new low-e glass is clear in appearance and has optimal energy performance for commercial building
More informationTitle 24: Where We're Headed with the 2013 Standards. Featuring: Martyn C. Dodd EnergySoft, LLC
Title 24: Where We're Headed with the 2013 Standards Featuring: Martyn C. Dodd EnergySoft, LLC www.energysoft.com Overall Changes in Scope and Application Welcome Overall Changes in Scope and Application
More informationSuccess with MEASUREMENT & VERIFICATION
2016 Success with MEASUREMENT & VERIFICATION Prepared for the North Carolina Department of Environmental Quality. Project funded by the U.S. Department of Energy, Office of Energy Efficiency and Renewable
More informationThe Low Hanging Fruit Energy Efficient Lighting
The Low Hanging Fruit Energy Efficient Lighting John Noel, President Energy & Environment, LLC 2121-B Hollywood Rd., NW Atlanta, GA 30318 p.404.794.2023 john@energyandenvironment.com www.energyandenvironment.com
More informationEnergy Efficiency in Multi-Tenant Office Buildings
Energy Efficiency in Multi-Tenant Office Buildings Presented by David Herman, PE, LEED AP Principal, EnerG Associates, LLC 3/10/2015 1 Learning Objectives 1. List the principal sources and uses of energy
More informationSonoma County Green Building Ordinance Energy Cost-Effectiveness Study
Sonoma County Green Building Ordinance Energy Cost-Effectiveness Study June 30, 2009 Report prepared for: DeWayne Starnes, P.E., C.B.O., Deputy Director Sonoma County Permit and Resource Management 2550
More informationCommercial Retro-Commissioning Program Manual for 2015 SECTION 1
Commercial Retro-Commissioning Program Manual for 2015 SECTION 1 Introduction The Commercial Retro-Commissioning Program (RCx) is designed to achieve demand and energy savings in commercial facilities.
More informationSustainability + Learning an equation for success at RVC
Sustainability + Learning an equation for success at RVC ILLINOIS COMMUNITY COLLEGE CHIEF FINANCIAL OFFICERS SPRING 2010 MEETING Dominick Demonica, AIA, LEED AP 2008 Campus Master Plan Sustainability Goals
More informationExample LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal
Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal The following documentation provides an example submittal for the LEED-NC v2.1 Energy & Atmosphere Credit 1 (EAc1). This sample EAc1 submittal
More informationArchitect and Engineer Lunch and Learn
Architect and Engineer Lunch and Learn September 30, 2014 The Team Kristi Hardy, CenterPoint Energy Energy Efficiency Program Manager Michael Sciortino, CLEAResult Program Consultant August Vega, CLEAResult
More informationNavigating Vermont s New Core Performance Guide. Session Overview 2/18/2008
Navigating Vermont s New Core Performance Guide Jonathan Kleinman, Efficiency Vermont Mark Frankel, New Buildings Institute Better Buildings by Design Conference Burlington, VT February 13, 2008 1 Session
More information[DLCX] UNIQUENESS OF COMMISSIONING DAYLIGHTING: WHOLE BUILDING INTEGRATION REQUIRED
[DLCX] UNIQUENESS OF COMMISSIONING DAYLIGHTING: WHOLE BUILDING INTEGRATION REQUIRED Joseph Deringer, AIA, LEED AP Building Science Analytics LLC 21 st National Conference on Building Commissioning AIA
More informationSolar Architecture re in Minnesota:
Solar Architecture re in Minnesota: Toward Zero Energy Housing Mary Guzowski Department of Architecture William Weber Center for Sustainable Building Research UNIVERSITY OF MINNESOTA Acknowledgements:
More informationwattsmart Business Utah
Incentives for lighting system retrofits Measure Category Eligibility Requirements Incentive Full fixture replacement Advanced controls $0.15/kWh annual Basic controls $0.12/kWh annual Interior lighting
More informationItalcementi Center for Research and Innovation
Italcementi Center for Research and Innovation Bergamo, Italy LEED-NC v2.1 EAc1 A. Project Narrative (Viridian) analyzed the energy use of the proposed Italcementi Center for Research and Innovation located
More informationPROPOSED APPROACH ENERGY-EFFICIENCY AND DSM RULES FOR PENNSYLVANIA S ALTERNATIVE ENERGY PORTFOLIO STANDARD
PROPOSED APPROACH ENERGY-EFFICIENCY AND DSM RULES FOR PENNSYLVANIA S ALTERNATIVE ENERGY PORTFOLIO STANDARD Offered by Citizens for Pennsylvania s Future (PennFuture) March 14, 2005 Objectives and Principles
More informationIECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST
IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST ENVELOPE REQUIREMENTS Project: Date: Instructions RECOMMENDED: List performance values, note exceptions that were applied, or provide other
More informationCLARK BROCKMAN, SERA ARCHITECTS
CLARK BROCKMAN, SERA ARCHITECTS TOOLS: ENERGY WORKSHEET BASELINE ENERGY USE: EXAMPLE: Living Building Financial Study UNIVERSITY CLASSROOM IN PORTLAND Normalized Baseline Energy Use Intensity (kbtu/sf)
More informationThe Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma
LEED Green Building Certification The purpose of the LEED Green Building Rating is to provide a national standard that aims to improve environmental, health and economic performance of buildings using
More information2010 CA Higher Education Sustainability Conference
2010 CA Higher Education Sustainability Conference Energy Efficiency Partnership Program Best Practice Awards Application Project Category 11 Rendering Used Courtesy of Cannon Design I. Contact Information
More informationHighlights of What s New with the 2016 Nonresidential Energy Code
2016 Title 24, Part 6 Highlights of What s New with the 2016 Nonresidential Energy Code Gary Shushnar, SCE with compliments to: - Gina Rodda, Gabel Energy - Martyn Dodd, EnergySoft June 15, 2016 Statewide
More informationDTE Energy Commercial & Industrial Energy Optimization Program. Trade Ally Meeting. Guardian Plumbing & Heating January 20, 2011
DTE Energy Commercial & Industrial Energy Optimization Program Trade Ally Meeting Guardian Plumbing & Heating January 20, 2011 Agenda Introduction DTE Energy Your Energy Savings Program Overview 2011 Program
More informationEnergy Auditing for Schools. Maryland Energy Administration Eric Oliver, EMO Energy Solutions, LLC May 10, 2007
Energy Auditing for Schools Maryland Energy Administration Eric Oliver, EMO Energy Solutions, LLC May 10, 2007 Schools Consumption breakdown 19% 6% 9% Space Heating 46% Water Heating Lighting Cooling 20%
More informationEnergy Upgrade California
Energy Upgrade California Layering Programs and Incentives for Deeper Energy Savings in Multifamily Properties Introductions The Heschong Mahone Group, Inc (HMG) Consulting on energy efficiency for buildings
More informationSelecting Energy Efficient New Windows in Tennessee
Selecting Energy Efficient New Windows in Tennessee www.efficientwindows.org January 06 STAR Zones. Meet the Energy Code & Look for the STAR Windows must comply with your local energy code. Windows that
More informationSelecting Energy Efficient New Windows in Nevada
Selecting Energy Efficient New Windows in Nevada www.efficientwindows.org January 06 STAR Zones. Meet the Energy Code & Look for the STAR Windows must comply with your local energy code. Windows that are
More informationArizona Healthcare Pollution Prevention Workshop April 28, 2005 Jim Westberg
Arizona Healthcare Pollution Prevention Workshop April 28, 2005 Jim Westberg Why is Commerce Interested in Energy Efficiency? Healthy Economy and Jobs! Energy-Efficient Companies are more profitable. They
More informationDemand Reduction and Energy Savings Potential of Integrated Dimming Ballast Controls in Mid-Size Retail Facilities: PetSmart Stores
Design & Engineering Services Demand Reduction and Energy Savings Potential of Integrated Dimming Ballast Controls in Mid-Size Retail Facilities: Customer Report Prepared by: Design & Engineering Services
More informationCOMMISSIONING, OPERATION AND MAINTENANCE
CHAPTER 9 COMMISSIONING, OPERATION AND MAINTENANCE THIS CHAPTER IS PROVIDED FOR REFERENCE ONLY. IT IS NOT ADOPTED AS A REQUIREMENT OF THE CODE. SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter
More informationSelecting Energy Efficient New Windows in Illinois
Selecting Energy Efficient New Windows in Illinois www.efficientwindows.org January 016 ENERGY STAR Zones 1. Meet the Energy Code & Look for the ENERGY STAR Windows must comply with your local energy code.
More informationATS Le Grandiose, Sector 150 Noida. Energy Conservation Building Code (ECBC) Compliance Report
Energy Conservation Building Code (ECBC) Compliance Report ATS Le Grandiose, Sector 150 Noida Energy Conservation Building Code (ECBC) Compliance Report For M/s. Nobility Estates Pvt. Ltd. ECBC CONTENTS
More informationThe baseline building system for compliance with Senate Bill 668 is defined by Appendix G,
Project: North Carolina A&T State University New Student Health Center SCO #: 08-08109-01A 1.0 Heating, Ventilating and Air Conditioning (HVAC) Baseline Building Systems Senate Bill 668 Compliance The
More informationSection 2: Estimating Energy Savings and Incentives
Section 2: Estimating Energy and Incentives 2.1 Estimating Energy and Incentives... 2 2.2 Customized Measures - Estimation Software... 2 2.2.1 AC&R I - High Efficiency Chiller... 4 2.2.2 AC&R I - Split/Packaged
More informationSelecting Energy Efficient Replacement Windows in Arizona
Selecting Energy Efficient Replacement Windows in Arizona www.efficientwindows.org January 016 ENERGY STAR Zones 1. Meet the Energy Code & Look for the ENERGY STAR Windows must comply with your local energy
More informationPennsylvania Watt Watchers. Business Programs
Pennsylvania Watt Watchers Business Programs Why does a utility company want me to reduce electricity usage? Pennsylvania Act 129 Signed into law by Governor Rendell - October 2008. Establishes new requirements
More informationIECC 2006 with Hawaii Amendments
IECC 2006 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST ENVELOPE REQUIREMENTS Instructions RECOMMENDED: List performance values, note exceptions that were applied, or provide other notes to the reviewer.
More informationRhode Island Commercial Codes FAQs
Rhode Island Commercial Codes FAQs When does the new code go into effect? The new suite of building codes (including the new state energy conservation code, SBC-8) was adopted on July 1, 2013. A brief
More informationPresentation to Appalachian State University
Presentation to Appalachian State University Boone, NC NC Commercial Energy Code Overview Renee Hutcheson, AIA, LEED AP, PEM Reid Conway, PEM North Carolina State Energy Office Department of Commerce January
More informationThe Top 10 Approach to Commercial Energy Code Compliance
The Top 10 Approach to Commercial Energy Presenter: Shaunna Mozingo Tuesday, September 12, 2017 1:30 PM - 4:30 PM A Top 10 Approach to Energy Code Compliance Colorado Energy Office and Colorado Code Consulting
More information179D Tax Deductions for Architects & Engineers
179D Tax Deductions for Architects & Engineers Presented by: CJ Aberin, CCSP, Electrical Engineer Senior Manager 877-525-4462 x148 cj@kbkg.com www.kbkg.com Overview History Section 179D Energy Efficient
More informationReducing Costs with Energy Efficiency
Reducing Costs with Energy Efficiency Presented to Pennsylvania Demand Side Response Working Group February 9, 2007 2/9/2007 1 Austin Energy Municipally-owned 700,000 population Area > 400 sq. miles Generation
More informationBringing Savings to Life: Net-Zero Design and Performance Bill Maclay, Maclay Architects Andy Shapiro, Energy Balance, Inc.
Bringing Savings to Life: Net-Zero Design and Performance Bill Maclay, Maclay Architects Andy Shapiro, Energy Balance, Inc. BBBD 2010 11 February 2010 Putney Field House and NRG Addition Learn from NRG
More informationFOR ADDITIONS and REMODELS Before filling out this application, read Green Building & Green Points Guideline Booklet for more in-depth information.
City of Boulder Residential Building Guide Green Building & Green Application Resource Conservation Ordinance 7565 www.bouldergeenpoints.com FOR ADDITIONS and REMODELS Before filling out this application,
More informationUnits. Lighting quantity is primarily expressed in three types of units.
Lighting Efficiency Units Lighting quantity is primarily expressed in three types of units. Watts measure of electrical power that defines the rate of energy consumption. Lumens output of a lamp, how much
More informationEnergy Efficiency, GeoExchange Systems and Renewable Energy MiAPPA Winter 2010
GETTING TO NET-ZERO Energy Efficiency, GeoExchange Systems and Renewable Energy MiAPPA Winter 2010 Jan Culbertson, AIA, LEED AP Sr. Principal A3C Collaborative Architecture James Hardin, P.E. Sr. VP of
More informationNational Grid USA Service Company. Impact Evaluation Of 2006 Design2000plus Custom Comprehensive Projects. Final Report
National Grid USA Service Company Impact Evaluation Of 2006 Design2000plus Custom Comprehensive Projects Final Report July 11, 2010 Submitted to: National Grid USA Service Corporation Waltham, MA Submitted
More informationIFMA Central Pennsylvania Chapter August 20, 2014
IFMA Central Pennsylvania Chapter August 20, 2014 Facility Managers Roundtable: Sustainability Practices Alan Brunner, Project Manager for the Financer Department, PSECU Michele Sinadinos, Facility Manager,
More informationSouth Carolina Society for Hospital Engineers
South Carolina Society for Hospital Engineers Selecting Energy Partners: Criteria & Pitfalls and the Top 10 Ways to Reduce Energy in a Hospital Presented by Jon Dierking, PE, CEM, LEED AP Director of Energy
More informationEnergy Project Measurement and Verification Procedures
PDHonline Course E335 (8 PDH) Energy Project Measurement and Verification Procedures Instructor: George E. Thomas, PE 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone &
More informationSTATE OF NEW JERSEY Honorable Jon S. Corzine, Governor
SCOPE OF WORK FACILITY ENERGY AUDIT New Lisbon Developmental Center Woodland Twp, Burlington County, N.J. PROJECT NO. A1085-00 STATE OF NEW JERSEY Honorable Jon S. Corzine, Governor DEPARTMENT OF THE TREASURY
More informationImplementing Low-Cost Energy Savings Projects & Conducting Energy Audits
AEP Ohio Customer Seminar Implementing Low-Cost Energy Savings Projects & Conducting Energy Audits Presented by: Julie Birchfield Customer Manager Energy Optimizers, USA May, 2018 Test your Energy IQ 11
More informationFirstEnergy s Pennsylvania Utilities. Energy Efficiency Programs for Business
FirstEnergy s Pennsylvania Utilities Energy Efficiency Programs for Business 2018 TODAY S AGENDA Introduction to Sodexo Summary of Pennsylvania Act 129 Overview of program website Overview of Application
More informationICTA 2015: Cinema Design & Construction Compliance with the New Energy Code
ICTA 2015: Cinema Design & Construction Compliance with the New Energy Code John Wolski Vice President, Exhibitor Services Deluxe Digital Cinema Michael A. Cummings, AIA LEED AP Principal TK Architects,
More informationThe energy benefits of View Dynamic Glass
Workplace demonstration Energy monitoring over a period of 12 months resulted in the commercial office room installed with View Dynamic Glass saving 39 percent of the total energy consumed compared to
More informationCase Study Network Based Lighting Management Systems for Intelligent and Smart Buildings. Client NetApp India Pvt Limited Bangalore
Case Study Network Based Lighting Management Systems for Intelligent and Smart Buildings Client NetApp India Pvt Limited Bangalore NetApp, Inc. (NetApp), incorporated in April 1992, is a provider of storage
More informationEnergy Efficiency / Renewable Energy (EE/RE) Projects in Texas Public Schools
Energy Efficiency / Renewable Energy (EE/RE) Projects in Texas Public Schools Jeff Haberl, Hyojin Kim, Jaya Mukhopadhyay, Juan-Carlos Baltazar-Cevantes, Sung Lok Do, Kee Han Kim, Cyndi Lewis, Bahman Yazdani
More informationENERGY AS SERVICES COMPANY ESCO. Jamal E. Alostaz. Projects Engineer Al-Salem Johnson Controls
ENERGY AS SERVICES COMPANY ESCO Jamal E. Alostaz Projects Engineer Al-Salem Johnson Controls AGENDA About Johnson Controls Introduction to ESCO Case Study: Empire State Building, USA Project Information
More informationThe American Council for an Energy-Efficient Economy Emerging Technologies Report. Integrated Daylighting Systems (Dimming Ballasts) June, 2006
The American Council for an Energy-Efficient Economy Emerging Technologies Report Integrated Daylighting Systems (Dimming Ballasts) June, 2006 Summary Definition Basecase New Measure: Digital network of
More informationEnergy Audits: Lessons Learned Over 30 Million Square Feet
Energy Audits: Lessons Learned Over 30 Million Square Feet Presented to: Environment, Energy Security & Sustainability By: Corry W Freeman, CEM AMEC Earth & Environmental, Inc. Midwest Plaza Building 800
More informationESTIMATED SAVINGS FROM TURNING OFF UNNECESSARY ELECTRICAL LOADS DURING UNOCCUPIED PERIODS AT THE LANGFORD ARCHITECTURE CENTER
ESL-TR-96/10-03 ESTIMATED SAVINGS FROM TURNING OFF UNNECESSARY ELECTRICAL LOADS DURING UNOCCUPIED PERIODS AT THE LANGFORD ARCHITECTURE CENTER REPORT Prepared by: V. I. Soebarto J. S. Haberl L.O. Degelman
More informationRECOMMENDATIONS FOR 15% ABOVE-CODE ENERGY EFFICIENCY MEASURES FOR COMMERCIAL OFFICE BUILDINGS
ESL-TR-7-9-2 RECOMMENDATIONS FOR 15% ABOVE-CODE ENERGY EFFICIENCY MEASURES FOR COMMERCIAL OFFICE BUILDINGS A Project for Texas Senate Bill 5 Legislation For Reducing Pollution in Nonattainment and Affected
More informationACHIEVE MULTI-BENEFITS USING THE. COMMISSIONING PROCESS FOR RETRO- COMMISSIONING OF BUILDINGS CLIMA 2005 Lausanne, Switzerland Paper Dorga274s
1 ACHIEVE MULTI-BENEFITS USING THE COMMISSIONING PROCESS FOR RETRO- COMMISSIONING OF BUILDINGS CLIMA 2005 Lausanne, Switzerland Paper Dorga274s Authors Chad B. Dorgan, PE, PhD, CxAP, CCP Director, Facilities
More informationWhite Paper ENVELOPE-FIRST APPROACH TO NET-ZERO ENERGY BUILDINGS
BOULDER CHICAGO NASHVILLE SALT LAKE CITY SAN FRANCISCO SPRINGFIELD, MO WASHINGTON, DC 2540 Frontier Avenue, Suite 100 Boulder, Colorado 80301 303.444.4149 White Paper ENVELOPE-FIRST APPROACH TO NET-ZERO
More informationHow To Attack Lighting Energy Waste
How To Attack Lighting Energy Waste Article supplied by OSRAM Sylvania Energy is today s hottest topic, and with good reason. The demand for energy continues to grow as our population grows. Many people
More informationCustom Application 2018 Retrofit Program
The Retrofit Program is designed for Commercial and Industrial (C&I) customers to help replace aging and inefficient equipment and systems with more energy efficient technologies. Tailored to a customer's
More informationLED Lighting & Network Lighting Controls Upgrade Smart Lighting Controls Cheshire School District Case Study
LED Lighting & Network Lighting Controls Upgrade Smart Lighting Controls Cheshire School District Case Study Who We Are Cheshire Public Schools Vincent Masciana Director of Management Services Dan Marseglia
More informationRetail Effects of ANSI/ASHRAE/IES Standard
Retail Effects of ANSI/ASHRAE/IES Standard 90.1-2016 Prepared by Dialectic Inc. INTRODUCTION Background ANSI/ASHRAE/IES 90.1-2016 Energy Standard for Buildings Except Low-Rise Residential Buildings replaces
More informationMinnesota Conservation
Program Information MN Minnesota Conservation Programs Summary We offer solutions for business customers in a suite of energy conservation and energy management products that will help you increase your
More informationCONTENTS. 71 Section 01352, #7 (Life Cycle Cost and Life Cycle Assessment) 2/1/12 Modified entire section 72 Section 01352, #8 (Sustainability
01352 Sustainable Design Requirements This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications
More informationVeterans Administration Medical Center San Diego. Advanced Lighting Control System Assessment Final Report
Veterans Administration Medical Center San Diego Advanced Lighting Control System Assessment Final Report December 15 th, 2010 PREFACE PROJECT TEAM This project is sponsored by San Diego Gas & Electric
More informationRECOMMENDED LANGUAGE FOR THE STANDARDS DOCUMENT, ACM MANUALS,
RECOMMENDED LANGUAGE FOR THE STANDARDS DOCUMENT, ACM MANUALS, AND THE REFERENCE APPENDICES SECTION 131 INDOOR LIGHTING CONTROLS THAT SHALL BE INSTALLED (a) Area Controls. (b) Multi Level Lighting Controls.
More information2015 WSEC: Electrical and Lighting Systems
2015 WSEC: Electrical and Lighting Systems Presented by: Andrew Pultorak, LC, MIES Senior Energy Management Engineer, Puget Sound Energy January 19, 2017 Agenda Reading and Interpreting Code Section C406:
More informationENERGY MODELING GUIDELINES. D. Section Building Automation and Control System Guidelines
018130 ENERGY MODELING GUIDELINES PART 1: GENERAL 1.01 RELATED SECTIONS A. Section 018110 Green Building Guidelines B. Section 230000 Basic HVAC Requirements C. Section 230540 Laboratories D. Section 230900
More informationIntroduction ABSTRACT
Drill, Baby, Drill! Mining More Energy Savings after Twelve Years of Efficiency Measures Josh Kelman, Vermont Energy Investment Corporation Jim Welch, Husky Injection Molding Systems Ltd. ABSTRACT Efficiency
More informationMeasurement & Verification for Performance Contracts Through Rebuild Colorado. January Rebuild Colorado
Measurement & Verification for Performance Contracts Through Rebuild Colorado January 2005 Rebuild Colorado A Program of the Governor's Office of Energy Management and Conservation 225 East 16th Avenue
More informationEstablishing a Baseline, Energy Audits and Energy Star s Portfolio Manager
Establishing a Baseline, Energy Audits and Energy Star s Portfolio Manager Glenn Barnes Environmental Finance Center University of North Carolina at Chapel Hill 919-962-2789 glennbarnes@sog.unc.edu Energy
More informationGEW1-14 Chapter 6, , 302.1, 903.1, 904.3, , , , , , , , A106
GEW1-14 Chapter 6, 302.1.1, 302.1, 903.1, 904.3, 1007.3, 1007.3.1, 1007.3.2, 1007.3.3, 1007.3.3.1, 1007.3.3.2, 1007.3.3.3, A106 Proponent: Shaunna Mozingo, Colorado Code Consulting, LLC, representing Colorado
More informationBUILDING ENERGY CODES PROGRAM. DOE Draft Proposals for the 2018 IECC - Commercial Session. David Cohan, U.S. Department of Energy.
BUILDING ENERGY CODES PROGRAM DOE Draft Proposals for the 2018 IECC - Commercial Session December 1, 2015 David Cohan, U.S. Department of Energy 1 DOE Participation in IECC The Department seeks to advance
More informationELECTRICAL SYSTEMS. TEST YOURSELF QUESTIONS: Answer Key. CHAPTER 1: Sustainability in Electrical Systems
ELECTRICAL SYSTEMS TEST YOURSELF QUESTIONS: Answer Key CHAPTER 1: Sustainability in Electrical Systems 1. What are the benefits of sustainability in green building design? The benefits of sustainability
More informationGreen Buildings Make Cents
Green Buildings Make Cents Jay Moore, Vice President, AIA Carrie Webster, Environmental Analyst, LEED AP Virginia Association of Counties Annual Conference November 10, 2008 PERCEPTION REALITY Third Creek
More informationInterim report 2016 progress on the 5-Year Energy Management Plan
Waypoint Centre for Mental Health Care 500 Church Street, Penetanguishene ON L9M 1G3 705-549-3181 www.waypointcentre.ca Interim report 2016 progress on the 5-Year Energy Management Plan Waypoint Centre
More informationTOP 10 STRATEGIES FOR NEW AND EXISTING BUILDINGS
TOP 10 STRATEGIES FOR NEW AND EXISTING BUILDINGS Kristine Chalifoux Management Engineer Facility and Services, University of Illinois Big10 & Friends October 10, 2016 WHAT IS HIGH PERFORMANCE DESIGN? What
More informationCASE STUDY 1: Ten-Story Building
CASE STUDY 1: Ten-Story Building OVERVIEW A government building in Texas was retrofitted as part of an initiative to increase energy efficiency and cost savings while reducing the green house gas emissions
More informationCOMMERCIAL ENERGY EFFICIENCY
COMMERCIAL ENERGY EFFICIENCY Commercial buildings are all buildings that are not detached one- or two-family dwellings, multiple single-family dwellings (townhouses), or Group R-2, R-3 or R-4 buildings
More information