COMPLIANCE MONITORING REPORT OF MAFUBE LOCAL MUNICIPALITY

Size: px
Start display at page:

Download "COMPLIANCE MONITORING REPORT OF MAFUBE LOCAL MUNICIPALITY"

Transcription

1 COMPLIANCE MONITORING REPORT OF MAFUBE LOCAL MUNICIPALITY Monitoring Date: 06 May 2014

2 All enquiries and correspondence to be directed to the Head of Department unless indicated otherwise by means of a formal letter signed by the head of department: Electricity Licensing, Compliance and Dispute Resolution. Tel: National Energy Regulator of South Africa Kulawula House 526 Madiba Street Arcadia Pretoria PO Box Arcadia 0007 Tel: +27 (0) Fax: +27 (0) DISCLAIMER This is a final report considered a true reflection of the implementation of the CAP based on information and evidence obtained from both the licensee and site verification of plant condition conducted during the monitoring process. Page 2 of 20

3 TABLE OF CONTENTS EXECUTIVE SUMMARY INTRODUCTION METHODOLOGY NERSA AND MAFUBE LOCAL MUNICIPALITY DELEGATES GENERAL INFORMATION ON MAFUBE LOCAL MUNICIPALITY AUDIT FINDINGS MAFUBE S PERFORMANCE ON NERSA COMMUNICATION PROGRESS ON THE IMPLEMENTATION OF THE CORRECTIVE ACTION PLAN PLANT CONDITION DURING AUDIT VS. MONITORING TIME CONCLUSIONS RECOMMENDATIONS NEXT STEP Page 3 of 20

4 EXECUTIVE SUMMARY The National Energy Regulator (NERSA) conducted a compliance audit on Mafube Local Municipality ( the Licensee ) from 27 to 28 November 2012 to determine their level of compliance with the licence conditions. The objective was to determine the compliance of Mafube Local Municipality with the legal, financial and technical conditions of the electricity distribution licence. During the audit, Mafube Management highlighted that all electricity related business activities of Mafube are completely ring-fenced from the Municipality s other businesses and are held separate and administered by a company called Rural Maintenance (Pty) Ltd. Mafube Local Municipality entered into a service level agreement with Rural Maintenance (Pty) Ltd on 15 December 2011, hence Rural Maintenance (Pty) Ltd is responsible for all Mafube s electricity business activities. In February 2012, Rural Maintenance started its activities in Mafube area of supply as per the agreement with the municipality. After the audit, findings were recorded in a draft report and forwarded to the Licensee for management comments with regard to the correctness of the findings in order to make the report final. On 11 January 2013, Mafube Local Municipality through Rural Maintenance (Pty) Ltd sent the management comments to NERSA. These were received well within the prescribed time frame. The report was then considered final by NERSA and Mafube Local Municipality was then requested to send NERSA a signed time-bound corrective action plan (CAP) to address the highlighted instances of non-compliance. On 16 May 2013, Rural Maintenance (Pty) Ltd on behalf of Mafube Local Municipality sent a CAP for NERSA s perusal and this was found to be acceptable as they addressed the issues highlighted by the audit. The National Energy Regulator instituted a monitoring regime to ensure and enforce the implementation of the CAP. On 06 May 2014, the National Energy Regulator conducted a monitoring exercise on the implementation of the CAP at Mafube Local Municipality. The monitoring exercise was conducted in order to determine progress made in the implementation of the CAP. The National Energy Regulator is of the view that addressing issues raised during an audit will help Mafube Local Municipality to be a more efficient and effective licensee. This report depicts all the findings as per the audit and presents the status quo in terms of progress made at the time of the monitoring to address the noncompliances highlighted during the audit. During the monitoring exercise, NERSA conducted site inspections to verify progress made in the implementation of the CAP. It must be noted that there is significance progress made by Rural Maintenance (Pty) Ltd to improve the network condition and business systems of the Mafube Local Municipality. The level of improvement is depicted in detail in section seven of the report. Page 4 of 20

5 1. INTRODUCTION 1.1 Overview The National Energy Regulator (NERSA) is required to monitor and assess whether the electricity suppliers comply with the conditions of their licences. The Energy Regulator approved a compliance monitoring framework for electricity distributors in 2011, which acts as a guide on how compliance audits and monitoring must be conducted. The framework is also supported by the Electricity Regulation Act, 2006 (Act No. 4 of 2006), Chapter 4 (a) (vii), which states that the Regulator must enforce performance and compliance; and take appropriate steps in the case of nonperformance. The National Energy Regulator conducts the compliance audits on licensed electricity distributors annually. The National Energy Regulator regulates the energy industry in accordance with Government laws and policies, standards and international best practices in support of sustainable development. The organisation issues licences to electricity distributors and therefore requires audits to be conducted against key licence obligations. It is the National Energy Regulator s mandate to monitor and enforce compliance with the licence conditions as per the Act. This monitoring process enforces and ensures improvement and sustainability of the licensees for the betterment of the Electricity Supply Industry (ESI), which will lead to improved quality of supply and service to customers. 1.2 Monitoring and Enforcement Objectives The key objectives of the compliance monitoring and enforcement of the corrective action plans are to: a) enforce implementation of the corrective action plans; b) help the licensee not to lose sight of critical matters that need to be corrected; c) help the licensee to start doing self-monitoring in terms of their performance against licence conditions; d) help the licensee to ensure that the quality of service and supply does not decline; and e) inform the Energy Regulator of the progress made by the licensee in the implementation of the corrective action plans. Page 5 of 20

6 2. METHODOLOGY A corrective action plan template was developed and sent to the licensee to populate all the non-compliances highlighted during the audit, together with the intended corrective action plan (CAP) with target dates of implementation. This is to be used by the National Energy Regulator to monitor the progress made and to establish whether the timelines on the CAP were realistic and addressing the issues highlighted during the audit. The CAP was sent to the National Energy Regulator after being signed by the relevant officials of the Licensee. The National Energy Regulator agreed on the CAP and instigated a monitoring process which robustly monitors progress. Progress is checked against target dates and remedial actions are implemented on an ongoing basis. Proof and supporting documents are requested and presented to the National Energy Regulator s officials during the monitoring process. Site verification was also done to compare the current plant condition against the plant condition during the audit. 3. NERSA AND MAFUBE LOCAL MUNICIPALITY DELEGATES NERSA was represented by the following officials: Mr B Nhlabathi Mr B van Heerden Ms V Poswa Mr V Malaza Compliance Monitoring Technician Financial Compliance Officer Dispute Resolution Officer Senior Distribution Compliance Engineer Mafube Local Municipality was represented by the following persons through the service level agreement (SLA): Mr C Bosch C Niemand G Goldner G Mokoena W van Oudtshoorn Engineer Rural Maintenance (Pty) Ltd Project Manager Rural Maintenance (Pty) Ltd Area Manager Rural Maintenance (Pty) Ltd Tech Admin Manager Rural Maintenance (Pty) Ltd Control Rural Maintenance (Pty) Ltd 4. GENERAL INFORMATION ON MAFUBE LOCAL MUNICIPALITY Mafube Local Municipality is the licensed electricity distributor (Licence No NER/D/FS205) located in the Free State Province with offices in Frankfort. This is a small municipality with only five intake bulk points and has a total Page 6 of 20

7 installed capacity of 44MVA. At the time of the audit it had 8948 customers, which were categorised as follows: 8123 prepaid domestic; 287 domestic credit meters; 287 commercial and 23 industrial customers with only km² supply area. At the time of the monitoring it was highlighted that the Licensee managed to connect 500 additional new customers to the network. 5. AUDIT FINDINGS At the time of the audit, the following was highlighted to the Licensee as areas that need attention and improvement: a) The Protection Relay setting provided was for the wrong substation (Mwanza South). b) The disconnection notice was in compliance with the municipality s by-laws (Clause 16 paragraph 6 but not in compliance with NRS (Paragraph 4.3.7) as it gave the client only 48 hours to pay the outstanding account. c) The actual areas of supply were not exactly the same as those stated on the licence schedule 1. d) The power quality management system was installed and was in the process of being commissioned. This was not yet fully operational at the time of the audit. e) A substandard network was prevalent in Tweeling Township largely due to the prevalence of high voltage (HV) bundle conductors historically located under the low voltage (LV) network. f) One switch gear at Villiers Substation was not in commission. g) Housekeeping at Tweeling substation s switch room was not acceptable. h) No asset management policy was submitted and the network asset register was not appropriate. i) Substandard LV boards in certain sub stations. j) Certain transformers had old silica gels and minor oil leaks. k) Magnefix switches were still in use, which poses an increased safety hazard and is not ideal. l) Low Voltage (LV) and Medium Voltage (MV) network upgrade project was under way. 6. MAFUBE S PERFORMANCE ON NERSA COMMUNICATION In November 2012, the National Energy Regulator conducted a compliance audit on Mafube Local Municipality to determine its level of compliance with its licence conditions. This audit was followed by a number of s from the National Energy Regulator to Mafube Local Municipality. All this Page 7 of 20

8 communication was sent to Rural Maintenance (Pty) Ltd as the custodian of the Mafube Local Municipality s Electricity Distribution Licence according to the SLA. In all this communication, Rural Maintenance (Pty) Ltd cooperated and responded in a satisfactory manner as indicated below. NERSA REQUEST DATE OF REQUEST LICENSEE RESPONSE DATE OF RESPONS E 11/01/2013 Request of Management comments on draft report 14/12/2012 Management comments sent Request for Corrective Action 18/01/2013 CAP sent 16/05/2013 Plan Progress report 06/02/2014 Progress report sent 14/02/2014 Monitoring notification 15/04/2014 Positive response 15/04/2014 Monitoring exercise 06/05/2014 Positive response 06/05/ PROGRESS ON THE IMPLEMENTATION OF THE CORRECTIVE ACTION PLAN Mafube Local Municipality and Rural Maintenance Pty (Ltd) displayed a high level of commitment during the monitoring exercise as all the instances of non-compliance highlighted during the audit were attended to. At the time of the monitoring exercise it was observed that most of the issues highlighted by the audit were completely addressed with some new additional work that was done to improve the network condition of the Mafube Local Municipality. The table below depicts the progress made at the time of the monitoring of the implementation of the CAP that was submitted to NERSA to address the instances of non-compliance. Unit affected Non-compliance Corrective action Mwanza South Protection Relay setting provided is for a different substation. General Disconnection notice payment period of 48 hours is not in compliance with NRS 047 of 2 weeks. RWW to provide quotation to do relay reprogramming and use correct parameters. Due diligence to be done to determine impact on operations Priority Progress Condition during monitoring day High Complete 100% compliant. Low Resolved 100% compliant. Customer bills give 14 Page 8 of 20

9 General General Tweeling (Mafahlaneng) Villiers Substation Actual Areas of supply different than stated in Schedule 1 of the Licence. Power quality management system not yet fully operational. MV and LV bundle next to each other. One Switchgear unit out of order and needs to be fixed, no spare units available, ASAP. and future possibilities to put this in place. Licence documents to be updated, particularly Schedule 1, and sent to NERSA for approval. 7 more QOS400 units to be installed, monthly data to be collected. Yearly report to be submitted to NERSA when 6 months of data is available. Remove the MV ABC and put on separate poles. This will be done ASAP from 18 February. Spare feeder breaker which is currently not operational will be repaired and upgraded by RWW with order having been placed Medium Low High High Letter for licence amendme nt dated 29 October 2013 was sent to NERSA. QoS meters are installed in the Mafube network to monitor the QoS parameter s. MV and MV network has been reconfigur ed. Spare breaker repaired and the switch room was extended to improve space constraint in the days notice. 50% NERSA to respond. 90% of the network is monitored for QoS via Net-view. 100% Complete. 100% completed. Page 9 of 20

10 Tweeling Switch room General General General Housekeeping Asset management register needs to be implemented on GIS. LV MCBs in FSB2,FSB7, FSB8, FLL2, Cornelia Main Sub, Rethabile Sub (urgent one) and Meule Sub 2 to be rehoused in proper LV cabinets/boards and chipboard housings to be replaced. Tariffs to be placed on Mafube LM's website as well. on 26 November with delivery expected mid April Remove oil drums to store, clean. Software purchased and currently being installed. The following priority: 1) Complete MV infrastructure 2) LV infrastructure 3) Individual Customers All panels have been ordered and delivered, installation to proceed. Contacted Service Provider, Medium Low High Low switch room. Oil drum removed from the switch room, switch room was cleaned and open covers replaced and closed. Asset managem ent system is continuous ly being implement ed. This is coupled with the fault reporting system via Netdesk system. Majority of the LV MCBs has been installed and still in progress. Awaiting Council. 100% completed. 50% Systems now in place. 90% complete. 50% Page 10 of 20

11 Villiers Substation General General Frankfort Main Substation Frankfort Main Substation DSM (Demand Side Management): Powerfactor Correction to be implemented. Maintenance plan to be updated to show Progress indication. Mafube control centre with SCADA to be implemented. Battery levels were low, batteries to be checked now if fully charged, if not then replace batteries. Termite infestation to be handled before it enters the substation. discussions taking place. Project for Powerfactor Correction at Villiers Main Sub in planning. Equipment being bought. Add columns to show progress for each subsection. Low Medium New Power Factor Correction system installed and resulted to reduction in Demand at the substation. Resolved. The maintenan ce plan continuous ly updated to indicate the maintenan ce done and the date it was done. TBC Low Not yet started. Batteries checked and found to be fine (30-32V). Indicator light was blown and will be replaced. Termites have been cleared with Landex inside sub and they will create a barrier High Completed. 100% Completed. 100% compliant. 100% resolved. High Completed 100% resolved. Page 11 of 20

12 around the sub with the same. FSB2 FSB7 FSB6 FLL2 Rethabile Sub Meule Sub 2 Tweeling Sub Villiers Substation Villiers Waterworks MSS Magnifix CB to be replaced. Clean oil spills on the floor. Transformer service due (previous service 2009). Transformer service due, oil leaks evident. Plinth under transformer not sufficient. LV Terminal cover to be replaced/put back Trench covers to be replaced/put back, oil cans to be moved to proper store, decent cleaning due. Space limitation problems Vegetation growing around MSS, MSS4 replace warning Replace with T Switch Gordon Sub: Used BREM638 cleaner, need some adjustment to cater for old transformer oil. Plan maintenance, get quotations. Plan maintenance, get quotations. RFQ, order and plan outage. Completed (New L panel ordered as well). Trench covers being manufactured 3 weeks ETC. Expand Substation design in progress for PFC Plant. Planned completion mid to end Spray Round-up and clean High Completed 100% Medium Completed 100% Low Planned 20% Low Planned 20% Medium Planned 08 May % High Completed 100% resolved. High Replaced and cleaned. 100% Low Completed 100% resolved and switch room has sufficient space High Completed 100% Vegetation removed Page 12 of 20

13 General signage, labelling to be added at LV side. The following transformers were found to be in need of maintenance: 1) TP25/3 Silica 2) TP26 Silica 3) TP10 Earthing and Silica 4) TP4 Silica 5) TM10/18/5 Silica 6) TT17 Silica 7) TT14/11 Silica 8) TT40/6 Silica 9) TH55 Silica 10) Mukaba Silica 11) Rethabile Sub Plinth 12) FSB7 Silica 13) FLL2 Silica area of vegetation. 1) TP25/3 Silica Replaced 2) TP26 Silica Replaced 3) TP10 Earthing fixed and Silica replaced 4) TP4 -Silica Replaced 5) TM10/18/5 Silica Replaced 6) TT17 Silica Replaced 7) TT14/11 Silica Replaced 8) TT40/6 Silica Replaced 9) TH55 Silica Replaced 10) Mukaba Silica Replaced 11) Rethabile Sub Plinth to be recasted and MSS barricaded with palisade fence. High Completed 100% Attended and resolved. The table above indicates that Mafube Local Municipality, with the help of Rural Maintenance (Pty) Ltd, has drastically improved its level of compliance with the distribution licence conditions. A high level of efficiency has also been noticed at Mafube Local Municipality since their tariff is planned to not increase beyond the NERSA tariff guideline increase of 7.39% in the 2014/15 financial year. The turnaround in Mafube Local Page 13 of 20

14 Municipality s Electricity business under the service level agreement with Rural Maintenance (Pty) Ltd has seen its revenue growing from R3.2m to R6.85m, while the Eskom Bulk account decreased from R4.2m to R4.07m. During the office session of the monitoring, the supporting documentation to substantiate the feedback on what was done to address the issues highlighted by the audit was provided to NERSA officials. According to the CAP developed and submitted by Rural Maintenance (Pty) Ltd on behalf of Mafube Local Municipality to the National Energy Regulator, it was indicated that some of the instances of non-compliance were already being addressed, while others were scheduled for future dates. At the time of the monitoring exercise this was evident from the network condition that was observed during site inspection and the systems that were already in place. The bulk account of Mafube Local Municipality was also up-to-date and this is an area that some licensees are battling with. 8. PLANT CONDITION DURING AUDIT VS. MONITORING TIME The photos below depict the condition of the network equipment during the audit compared to the condition during the monitoring process. Meule Sub 2 LV terminal cover missing during audit New silica gel and LV terminal cover replaced during monitoring Page 14 of 20

15 Old LV MCBs against a wall replaced with a new LV MCB panel properly closed during monitoring Page 15 of 20

16 Rosenberg Switching Station (FLL2) Transformer with oil leaks and old silica gel in 2012 Repaired oil leaks and new silica gel during the monitoring LV MCB board made of chipboard against the wall during audit New upgraded LV MCBs panel during the monitoring Page 16 of 20

17 Tweeling Substation Open cable trench covers and meter cubicle during the audit Closed trench covers and meter cubicle during monitoring Tweeling Overhead Network Substandard line with MV underneath the LV line in 2012 New line with street light proper clearance between MV and LV line in 2014 Page 17 of 20

18 Villiers Substation Switch room extension due to space problem after audit. Extended building with newly installed PF correction unit in Spare indoor breaker out of commission in Villiers substation during audit Repaired spare breaker during the monitoring Page 18 of 20

19 Villiers Overhead Network Newly refurbished LV and MV lines in Villiers Town and Suburb during the monitoring The photos indicate that the condition of Mafube Local Municipality s network has improved since the audit. A great amount of work has been done to correct the substandard network configuration in Tweeling Township. The magnefix switches has been replaced with the new compact T-switches at various parts of the network for safe and easy switching. A power quality management system and instruments are now in place for the proper monitoring of the quality of supply. The old overhead lines have also been upgraded and refurbished in most of the network highlighted by the previous audit. 9. CONCLUSIONS Mafube Local Municipality, with the assistance of Rural Maintenance (Pty) Ltd, has managed to turn around their level of compliance with their licence conditions. The high level of dedication and commitment to improve the compliance level and network condition of Mafube Local Municipality s network is shown through their dedication to attend to each and every issue raised by the previous audit as seen in their CAP. The progress made to implement the CAP at the time of the monitoring testifies to the dedication to comply with licence conditions. 10. RECOMMENDATIONS It is recommended that Mafube Local Municipality should maintain the high level of dedication and commitment to improve the level of compliance with licence conditions and impose a self-monitoring regime to ensure that it does not deteriorate back to non-compliance. Page 19 of 20

20 11. NEXT STEP There are still instances of non-compliance that need to be addressed by the licensee. As a result, the Energy Regulator expects the licensee to implement the corrective action plan until all the instances of noncompliance have been fully addressed in order to improve the licensee s level of compliance. The National Energy Regulator will continue to monitor the licensee s implementation of the corrective action plan on an ongoing basis to ensure that all the findings are addressed. Once the remaining projects in the CAP have been concluded, the Licensee must send a closeout report to the National Energy Regulator. It is expected that the licensee will now implement a self-monitoring regime to ensure that the improved areas do not deteriorate back to a situation of non-compliance. Further monitoring exercises to be conducted by the Energy Regulator on the licensee will be communicated to the Licensee in due course. All communication should be forwarded to the Head of Department unless indicated otherwise by means of a formal letter signed by the head of department: The Head of Department Licensing, Compliance and Dispute Resolution: Electricity National Energy Regulator of South Africa PO Box Arcadia 0007 Fax: +27 (0) Page 20 of 20

COMPLIANCE MONITORING REPORT OF UMHLATHUZE LOCAL MUNICIPALITY

COMPLIANCE MONITORING REPORT OF UMHLATHUZE LOCAL MUNICIPALITY COMPLIANCE MONITORING REPORT OF UMHLATHUZE LOCAL MUNICIPALITY Monitoring Date: 08 September 2014 All enquiries and correspondence to be directed to the Head of Department unless indicated otherwise by

More information

COMPLIANCE MONITORING REPORT OF MOOKGOPHONG LOCAL MUNICIPALITY

COMPLIANCE MONITORING REPORT OF MOOKGOPHONG LOCAL MUNICIPALITY COMPLIANCE MONITORING REPORT OF MOOKGOPHONG LOCAL MUNICIPALITY Monitoring Date: 13 May 2014 All enquiries and correspondence to be directed to the Head of Department unless indicated otherwise by means

More information

COMPLIANCE MONITORING REPORT OF PHUMELELA LOCAL MUNICIPALITY

COMPLIANCE MONITORING REPORT OF PHUMELELA LOCAL MUNICIPALITY COMPLIANCE MONITORING REPORT OF PHUMELELA LOCAL MUNICIPALITY Monitoring Date: 27 October 2015 All enquiries and correspondence to be directed to the Head of Department, unless indicated otherwise, by means

More information

COMPLIANCE MONITORING REPORT OF BLUE CRANE ROUTE MUNICIPALITY

COMPLIANCE MONITORING REPORT OF BLUE CRANE ROUTE MUNICIPALITY COMPLIANCE MONITORING REPORT OF BLUE CRANE ROUTE MUNICIPALITY Monitoring Date: 05 July 2016 All enquiries and correspondence to be directed to the Head of Department unless indicated otherwise by means

More information

COMPLIANCE MONITORING REPORT OF NKOMAZI LOCAL MUNICIPALITY

COMPLIANCE MONITORING REPORT OF NKOMAZI LOCAL MUNICIPALITY COMPLIANCE MONITORING REPORT OF NKOMAZI LOCAL MUNICIPALITY Monitoring Date: 12 August 2015 Page 1 of 18 All enquiries and correspondence to be directed to the Head of Department, unless indicated otherwise,

More information

GUIDELINES ON ELECTRICITY RESALE

GUIDELINES ON ELECTRICITY RESALE GUIDELINES ON ELECTRICITY RESALE Issued by The National Energy Regulator 526 Madiba Street Arcadia, Pretoria 0007 Contact Details: Tel: +27 (0)12 401 4600 Fax: +27 (0)12 401 4700 www.nersa.org.za Contents

More information

Distribution Information Exchange Code

Distribution Information Exchange Code Distribution Information Exchange Code Version 5.1 Approved September 2007 Comments to this document can be forwarded to: The RSA Grid Code Secretariat Attention: Mr. Bernard Magoro Eskom, Transmission

More information

Consolidated Report on the Audit Findings of the Electricity Generation Industry Compliance Audits Conducted in 2013

Consolidated Report on the Audit Findings of the Electricity Generation Industry Compliance Audits Conducted in 2013 Consolidated Report on the Audit Findings of the Electricity Generation Industry Compliance Audits Conducted in 2013 Audit date: Year 2013 All enquiries and correspondence to be directed to the Head of

More information

Consolidated Report on the Findings of the Electricity Generation Industry Compliance Audits Conducted in 2016/17 Financial Year

Consolidated Report on the Findings of the Electricity Generation Industry Compliance Audits Conducted in 2016/17 Financial Year Consolidated Report on the Findings of the Electricity Generation Industry Compliance Audits Conducted in 2016/17 Financial Year I All enquiries and correspondence to be directed to the Head of Department

More information

Alan Tait Managing Director Pragma Africa

Alan Tait Managing Director Pragma Africa Alan Tait Managing Director Pragma Africa Ekurhuleni Energy Department A Model for Electricity Distribution Infrastructure Asset Management Ekurhuleni Metropolitan Municipality Energy Department The Energy

More information

CONSOLIDATED REPORT ON THE FINDINGS OF THE ELECTRICITY DISTRIBUTION INDUSTRY COMPLIANCE AUDITS CONDUCTED IN 2013/14

CONSOLIDATED REPORT ON THE FINDINGS OF THE ELECTRICITY DISTRIBUTION INDUSTRY COMPLIANCE AUDITS CONDUCTED IN 2013/14 CONSOLIDATED REPORT ON THE FINDINGS OF THE ELECTRICITY DISTRIBUTION INDUSTRY COMPLIANCE AUDITS CONDUCTED IN 2013/14 FEBRUARY 2014 1 All inquiries and correspondence should be directed to the Head of Department:

More information

Distribution System Operating Code

Distribution System Operating Code Distribution System Operating Code Draft Rev 5 Approved September 2007 Comments to this document can be forwarded to: RSA Grid Code Secretariat Attention: Mr. Bernard Magoro Eskom, Transmission System

More information

CONSOLIDATED REPORT ON THE FINDINGS OF THE ELECTRICITY DISTRIBUTION INDUSTRY COMPLIANCE AUDITS CONDUCTED IN 2016/17

CONSOLIDATED REPORT ON THE FINDINGS OF THE ELECTRICITY DISTRIBUTION INDUSTRY COMPLIANCE AUDITS CONDUCTED IN 2016/17 CONSOLIDATED REPORT ON THE FINDINGS OF THE ELECTRICITY DISTRIBUTION INDUSTRY COMPLIANCE AUDITS CONDUCTED IN 2016/17 MARCH 2017 All inquiries and correspondence should be directed to the Head of Department:

More information

Distribution Code Definitions

Distribution Code Definitions Distribution Code Definitions Version 5 Approved September 2007 Comments to this document can be forwarded to: RSA Grid Code Secretariat Attention: Mr. Bernard Magoro Eskom, Transmission System Operator

More information

Distribution Tradesperson (Jobsplus Permit No. 706/2017)

Distribution Tradesperson (Jobsplus Permit No. 706/2017) CAREER OPPORTUNITIES Enemalta plc is the leading energy service provider in the Maltese Islands, entrusted with the generation and distribution of electricity and the development of the national electricity

More information

Technical Guideline for. Section 8. Inspection and Approval of Construction

Technical Guideline for. Section 8. Inspection and Approval of Construction Technical Guideline for Section 8. Inspection and Approval of Construction Ontario Regulation 22/04 Electrical Distribution Safety January 12, 2005 Technical Guideline Section 8 General Legal Disclaimer

More information

Performance Reporting Criteria

Performance Reporting Criteria Revision Date: February 2012 Revision No.: 2 Document No.: DOC-131102-ADV Status: Approved by CER Date: 01/03/2012 ESB Networks Ltd. Contents 1. Background... 3 2. Report Headings... 4 3. Criteria... 5

More information

Regulatory Audit Of Compliance Reporting For The Ord Hydro Transmission Network

Regulatory Audit Of Compliance Reporting For The Ord Hydro Transmission Network Regulatory Audit Of Compliance Reporting For The Ord Hydro Transmission Network Final 26 March 2007 Regulatory Audit Of Compliance Reporting For The Ord Hydro Transmission Network Final 26 March 2007 Sinclair

More information

TRANSMISSION COMPLIANCE MONITORING FRAMEWORK FOR THE SOUTH AFRICAN ELECTRICITY INDUSTRY

TRANSMISSION COMPLIANCE MONITORING FRAMEWORK FOR THE SOUTH AFRICAN ELECTRICITY INDUSTRY TRANSMISSION COMPLIANCE MONITORING FRAMEWORK FOR THE SOUTH AFRICAN ELECTRICITY INDUSTRY TABLE OF CONTENTS 1. PURPOSE...2 2. OBJECTIVE...2 3. BACKGROUND...2 3.1 REGULATORY INTERFACE AND COMMUNICATION CHANNELS...2

More information

Electricity Networks Corporation (t/a Western Power)

Electricity Networks Corporation (t/a Western Power) Networks Corporation (t/a Western Power) Transmission Licence (ETL 2) Performance Audit Report January 2013 Grant Thornton Australia Ltd. All rights reserved. Contents Acronym List 2 1. Introduction 5

More information

TECHNICAL INDICATOR DESCRIPTIONS 2012/ /15

TECHNICAL INDICATOR DESCRIPTIONS 2012/ /15 TECHNICAL INDICATOR DESCRIPTIONS 2012/13 2014/15 INDEX Page 1. Executive Summary 1 2. Electricity Industry Regulation 3 3. Piped-Gas Industry Regulation 17 4. Petroleum Pipelines Industry Regulation 30

More information

ROLE OF THE NATIONAL ENERGY REGULATOR (SOUTH AFRICA) Lambert du Plessis: Senior Regulatory Specialist

ROLE OF THE NATIONAL ENERGY REGULATOR (SOUTH AFRICA) Lambert du Plessis: Senior Regulatory Specialist ROLE OF THE NATIONAL ENERGY REGULATOR (SOUTH AFRICA) Lambert du Plessis: Senior Regulatory Specialist OUTLINE OF PRESENTATION Regulatory Principles South African Energy Regulation Legal framework NERSA

More information

Site Quality Assurance Inspection Regime for Connections Extension Assets

Site Quality Assurance Inspection Regime for Connections Extension Assets Site Quality Assurance Inspection Regime for Connections Extension Assets Background Northern Powergrid undertakes sample quality assurance inspections of assets installed by Independent Connection Providers

More information

Customer Capital Contributions Policy

Customer Capital Contributions Policy TasNetworks Customer Capital Contributions Policy Effective 1 July 2014 Tasmanian Networks Pty Ltd ABN 24 167 357 29 Page 1 of 25 Tasmanian Networks Pty Ltd ABN 24 167 357 299 1-7 Maria Street Lenah Valley

More information

AGREEMENT FOR CONNECTION TO [EASTERN /LONDON / SOUTH EASTERN] POWER NETWORKS PLC S DISTRIBUTION SYSTEM

AGREEMENT FOR CONNECTION TO [EASTERN /LONDON / SOUTH EASTERN] POWER NETWORKS PLC S DISTRIBUTION SYSTEM AGREEMENT FOR CONNECTION TO [EASTERN /LONDON / SOUTH EASTERN] POWER NETWORKS PLC S DISTRIBUTION SYSTEM BETWEEN AND (1) [Eastern / London / South Eastern] Power Networks plc Company Number [02366906 / 03929195

More information

ERONGO RED CUSTOMER SERVICE CHARTER

ERONGO RED CUSTOMER SERVICE CHARTER ERONGO RED CUSTOMER SERVICE CHARTER VISION Electricity for all by 2020 MISSION The distribution and supply of electricity within the Erongo Region VALUES Integrity Accountability Commitment Customer Focus

More information

Electricity Industry Act Electricity Distribution Licence Performance Reporting Handbook

Electricity Industry Act Electricity Distribution Licence Performance Reporting Handbook Electricity Industry Act 2004 Electricity Distribution Licence Performance Reporting Handbook April 2018 Economic Regulation Authority 2018 This document is available from the Economic Regulation Authority

More information

NERSA. National Energy Regulator of South Africa

NERSA. National Energy Regulator of South Africa NERSA National Energy Regulator of South Africa 1 Making Regulation Work 2 AGENDA Regulatory Framework From Law to Grid Code From Experience Concluding Remarks 3 Understanding Regulation as an Activity

More information

Scorecard - Midland Power Utility Corporation 9/28/2018

Scorecard - Midland Power Utility Corporation 9/28/2018 Scorecard - Midland Power Utility Corporation 9/28/218 Performance Outcomes Performance Categories Measures 213 214 215 216 217 Trend Industry Distributor Target Customer Focus Services are provided in

More information

Electric Distribution Reliability PUCO Staff

Electric Distribution Reliability PUCO Staff Electric Distribution Reliability PUCO Staff Reliability Standards and Major Storms/Events Exclusions Historical vs. Current Methodology for Setting Reliability Standards An electric utility s reliability

More information

SUMMARY OF TRANSMISSION BUSINESS

SUMMARY OF TRANSMISSION BUSINESS Filed: September, 0 EB-0-00 Schedule Page of SUMMARY OF TRANSMISSION BUSINESS.0 INTRODUCTION 0 Hydro One Networks Inc. is licensed by the Ontario Energy Board (the OEB or the Board ) to own, operate and

More information

GPI Conditions of Service - Revision History The following is a summary of key changes made to the document.

GPI Conditions of Service - Revision History The following is a summary of key changes made to the document. Identification of Grimsby Power 1.1 Added licence number. and Service Area 1.1.1 Distribution Overview Added Niagara West Municipal Transformer Station. Added section with general information about servicing,

More information

THE DISTRIBUTION SYSTEM SECURITY AND PLANNING STANDARDS. Asset Management & Regulation, ESB Networks

THE DISTRIBUTION SYSTEM SECURITY AND PLANNING STANDARDS. Asset Management & Regulation, ESB Networks THE DISTRIBUTION SYSTEM SECURITY AND PLANNING STANDARDS. Issued by: Review Cycle: Asset Management & Regulation, ESB Networks Three years Contents 1.0 Introduction....3 1.1 Definitions...3 1.2 Aim of Planning...5

More information

Solar Rooftop PV Municipal regulation, application, approval etc. processes. GIZ - All rights reserved

Solar Rooftop PV Municipal regulation, application, approval etc. processes. GIZ - All rights reserved Solar Rooftop PV Municipal regulation, application, approval etc. processes Hardcopies participants will need: Full AMEU resource pack Process flow diagram Application process checklist Filled in application

More information

THE LESOTHO ELECTRICITY AUTHORITY. Presentation by the LEA Chief Executive on the occasion of the Launch 04 May 2006

THE LESOTHO ELECTRICITY AUTHORITY. Presentation by the LEA Chief Executive on the occasion of the Launch 04 May 2006 THE LESOTHO ELECTRICITY AUTHORITY Presentation by the LEA Chief Executive on the occasion of the Launch 04 May 2006 1 Structure of the Presentation Issues concerning the Power Sector of Lesotho Power Sector

More information

NRS049 ADVANCED METERING INFRASTRUCTURE (AMI) FOR RESIDENTAIL AND COMMERCIAL CUSTOMERS

NRS049 ADVANCED METERING INFRASTRUCTURE (AMI) FOR RESIDENTAIL AND COMMERCIAL CUSTOMERS NRS049 ADVANCED METERING INFRASTRUCTURE () FOR RESIDENTAIL AND COMMERCIAL CUSTOMERS Author and presenter: HPD Groenewald Pr. Eng. (E/E) Chief Engineer Measurements, Eskom, Industry Association Resource

More information

NERSA Consultation Paper

NERSA Consultation Paper NERSA Consultation Paper Renewable Energy Feed - In Tariff December 2008 Page 1 of 14 TABLE OF CONTENTS ABBREVIATIONS...3 1. INTRODUCTION AND BACKGROUND...4 2. SOUTH AFRICAN RENEWABLE ENERGY FEED IN TARIFF

More information

Rottnest Island Authority. ERA Electricity Licence Performance Audit and Asset Management System Review Audit Report

Rottnest Island Authority. ERA Electricity Licence Performance Audit and Asset Management System Review Audit Report Rottnest Island Authority ERA Electricity Licence Performance Audit and Asset Management System Review Audit Report November 2017 Executive summary The Rottnest Island Authority (RIA or the licensee) holds

More information

The Distribution System Security and Planning Standards

The Distribution System Security and Planning Standards The Distribution System Security and Planning Standards (Demand customers only) Date: September 2003 Status: Approved Distribution System Operator ESB Networks Revision 1 September 2003, Page 1 of 26 Contents

More information

CEOP CONNECTION POLICY CONNECTION CHARGES. 1 July 2015

CEOP CONNECTION POLICY CONNECTION CHARGES. 1 July 2015 CEOP2513.06 CONNECTION POLICY CONNECTION CHARGES 1 July 2015 Contents 1. Introduction... 3 1.1. General approach to funding connections... 3 1.1.1. Third party fees and charges... 3 1.1.2. Network Augmentations...

More information

Electricity Industry Act Electricity Distribution Licence Performance Reporting Handbook

Electricity Industry Act Electricity Distribution Licence Performance Reporting Handbook Electricity Industry Act 2004 Electricity Distribution Licence Performance Reporting Handbook April 2017 Economic Regulation Authority 2017 This document is available from the Economic Regulation Authority

More information

effective date 1/8/01

effective date 1/8/01 25.211. Interconnection of On-Site Distributed Generation (DG). (a) (b) (c) Application. Unless the context clearly indicates otherwise, in this section and 25.212 of this title (relating to Technical

More information

SOIL ASSOCIATION CERTIFICATION INTERNATIONAL GROUP FOREST MANAGEMENT CERTIFICATION PROCEDURES

SOIL ASSOCIATION CERTIFICATION INTERNATIONAL GROUP FOREST MANAGEMENT CERTIFICATION PROCEDURES FSC A000525 PEFC/16-44-917 SOIL ASSOCIATION CERTIFICATION INTERNATIONAL GROUP FOREST MANAGEMENT CERTIFICATION PROCEDURES Procedures for International Group Forest Management Certification 1. Enquiry When

More information

Price Application Policy ABN

Price Application Policy ABN Price Application Policy ABN 38 362 983 875 Table of Contents 1. Interpretation 4 1.1 Definitions 4 1.2 Access Code definitions apply 5 1.3 Interpretation 5 2. National Market Identifiers (NMIs) 6 2.1

More information

Capital and operating expenditure 2009/10 to 2011/12

Capital and operating expenditure 2009/10 to 2011/12 Capital and operating expenditure 2009/10 to 2011/12 September 2008 Foreword This report provides the detailed justification for Western Power s forecast capital and operating expenditures for the 3 year

More information

MODEL STANDING OFFER FOR A LOW VOLTAGE BASIC CONNECTION SERVICE. (Effective 1 December 2017)

MODEL STANDING OFFER FOR A LOW VOLTAGE BASIC CONNECTION SERVICE. (Effective 1 December 2017) MODEL STANDING OFFER FOR A LOW VOLTAGE BASIC CONNECTION SERVICE Contents 1 THE PARTIES...3 2 PURPOSE OF THIS DOCUMENT...3 3 INTERPRETATION...3 4 CONTRACT TERM...4 4.1 Commencement of contract...4 4.2 Termination

More information

DOMESTIC ELECTRICAL INSTALLATION PERIODIC INSPECTION REPORT (FOR A SINGLE DWELLING) B ADDRESS AND DETAILS OF THE INSTALLATION Address: SPECIMEN

DOMESTIC ELECTRICAL INSTALLATION PERIODIC INSPECTION REPORT (FOR A SINGLE DWELLING) B ADDRESS AND DETAILS OF THE INSTALLATION Address: SPECIMEN A DETAILS OF THE CLIENT Client / Address: C PURPOSE OF THE REPORT Purpose for which this report is required: E PARTICULARS OF THE CONTRACTOR Trading Title: Address: DOMESTIC ELECTRICAL INSTALLATION PERIODIC

More information

Newmarket-Tay Power Distribution Ltd. NT POWER COS Conditions of Service. Issue Date: July, Next Review Date: February, 2015

Newmarket-Tay Power Distribution Ltd. NT POWER COS Conditions of Service. Issue Date: July, Next Review Date: February, 2015 Newmarket-Tay Power Distribution Ltd. Number: NT POWER COS 400 00 Conditions of Service Glossary of Terms Issue Date: July, 2007 Next Review Date: February, 2015 1. Preamble These Newmarket-Tay Power Distribution

More information

SUSTAINABLE GREEN ELECTRICITY FOR RURAL DEVELOPEMNT IN TANZANIA

SUSTAINABLE GREEN ELECTRICITY FOR RURAL DEVELOPEMNT IN TANZANIA RIFT VALLEY ENERGY CUSTOMER SERVICE CHARTER Page 1 of 7 RIFT VALLEY ENERGY TANZANIA 1. SERVICE DELIVERY STANDARDS Rift Valley Energy (RVE) forms the energy division of Rift Valley Corporation (RVC), and

More information

Broadband and Phone. Code of Practice. postoffice.co.uk

Broadband and Phone. Code of Practice. postoffice.co.uk Broadband and Phone Code of Practice postoffice.co.uk Post Office Broadband and Phone Code of Practice At Post Office we aim to make our customers central to everything we do. The purpose of this Code

More information

Pre-commissioning Requirements for Independent Connection Providers Requiring New Assets to be Connected to the 11/6.6kV Network

Pre-commissioning Requirements for Independent Connection Providers Requiring New Assets to be Connected to the 11/6.6kV Network Electricity Specification 220 Issue 3 December 2016 Pre-commissioning Requirements for Independent Connection Providers Requiring New Assets to be Connected to the 11/6.6kV Network Contents 1 Introduction

More information

Water NSW Reporting Manual

Water NSW Reporting Manual Water NSW Reporting Manual Operating Licence 2017-2022 Reporting Manual Water July 2017 Independent Pricing and Regulatory Tribunal of New South Wales 2017 This work is copyright. The Copyright Act 1968

More information

Revenue Enhancement Project Naledi Local Municipality. August 2016

Revenue Enhancement Project Naledi Local Municipality. August 2016 Revenue Enhancement Project Naledi Local Municipality August 2016 Revenue Enhancement Project - Naledi (Vryburg/ Stella in the Northwest Province) Two separate projects Vryburg Grant funded Stella RMS

More information

April Code of practice for accurate bills

April Code of practice for accurate bills April 2018 Code of practice for accurate bills Contents Definitions 3 Introduction 4 Switching 6 Meter reading 7 Energy bills and statements 8 Payments and refunds 9 2 Definitions Actual meter reading

More information

Specification for UDC Electrical Testing

Specification for UDC Electrical Testing Ergon Energy Corporation Limited Specification for UDC Electrical Testing RSC10 Abstract: Electrical Testing for Underground Distribution Construction (UDC) Specification RSC10 Ver 5 Contents 1. Purpose

More information

Electricity Supply Agreement

Electricity Supply Agreement Electricity Supply Agreement 1. General 1.1 Mazoon Electricity Company SAOC (the Supplier) shall on or from the Start Date, subject to the satisfactory completion of a Supply Application Form, provide

More information

ELECTRICITY DISTRIBUTION INDUSTRY (EDI) RESTRUCTURING : 11August 2005

ELECTRICITY DISTRIBUTION INDUSTRY (EDI) RESTRUCTURING : 11August 2005 ELECTRICITY DISTRIBUTION INDUSTRY (EDI) RESTRUCTURING - 1 - : 11August 2005 PURPOSE 1. To update Council on the latest information in respect of the Electricity Distribution Industry Restructuring; 2.

More information

Design Specification. Underground Residential Developments. Info Zone Record Number: R Version Number: 1. Date: December 2015

Design Specification. Underground Residential Developments. Info Zone Record Number: R Version Number: 1. Date: December 2015 Design Specification Underground Residential Developments Info Zone Record Number: R0000393265 Version Number: 1 Date: December 2015 This Page is Intentionally Blank Page 2 of 27 Authorisations Action

More information

ENMAX Power Corporation

ENMAX Power Corporation Decision 22562-D01-2017 ENMAX No. 31 Substation Alteration May 25, 2017 Alberta Utilities Commission Decision 22562-D01-2017 ENMAX No. 31 Substation Alteration Proceeding 22562 Application 22562-A001 May

More information

Lesotho Electricity Authority. Rural Electricity Quality of Service and Supply Standards

Lesotho Electricity Authority. Rural Electricity Quality of Service and Supply Standards Lesotho Electricity Authority Rural Electricity Quality of Service and Supply Standards First Edition: 2008 Table of Contents 0 Abbreviations... 3 1 Definitions...3 Background and Scope...4 3 Quality of

More information

How to Apply For Electricity Connection

How to Apply For Electricity Connection How to Apply For Electricity Connection This handbook is published by SP Group September 2017 Procedures and requirements highlighted in this handbook are correct at the time of printing. Any changes that

More information

ROTTNEST ISLAND AUTHORITY OPERATION OF ELECTRICAL SERVICES CUSTOMER SERVICE CHARTER Electrical Customer Service Charter 2009 Version 3 1

ROTTNEST ISLAND AUTHORITY OPERATION OF ELECTRICAL SERVICES CUSTOMER SERVICE CHARTER Electrical Customer Service Charter 2009 Version 3 1 ROTTNEST ISLAND AUTHORITY OPERATION OF ELECTRICAL SERVICES CUSTOMER SERVICE CHARTER 2009 Electrical Customer Service Charter 2009 Version 3 1 1. Introduction... 5 1.1 Rottnest Island Mission Statement...

More information

IBM WATSON CAMPAIGN AUTOMATION SUPPORT AGREEMENT

IBM WATSON CAMPAIGN AUTOMATION SUPPORT AGREEMENT IBM WATSON CAMPAIGN AUTOMATION SUPPORT AGREEMENT This is agreement is governed by the PSC Master Services Agreement (MSA) (named 201711 Master Services Agreement ) found at: http://www.purplesquareconsulting.com/master-services-agreements.

More information

POWER QUALITY MANAGEMENT FRAMEWORK FOR THE ELECTRICITY SUPPLY INDUSTRY IN ZAMBIA

POWER QUALITY MANAGEMENT FRAMEWORK FOR THE ELECTRICITY SUPPLY INDUSTRY IN ZAMBIA POWER QUALITY MANAGEMENT FRAMEWORK FOR THE ELECTRICITY SUPPLY INDUSTRY IN ZAMBIA JUNE 2014 CONTENTS EXECUTIVE SUMMARY... ii 1. INTRODUCTION...1 1.1 Overview...1 1.2 Aims of Power Quality Management System...1

More information

HOW TO READ YOUR ELECTRICITY BILL

HOW TO READ YOUR ELECTRICITY BILL HOW TO READ YOUR ELECTRICITY BILL Systematic approach By comprehensively understanding your electricity bill, you guarantee that the utility service is effectively managed and thus make your business sustainable.

More information

Service Level Agreement

Service Level Agreement Service Level Agreement 1. Scope The scope of the present Service Level Agreement (hereinafter referred to as SLA ) is to define the quality parameters of the Service provided to the Customer by the Supplier

More information

Bluewaters Power 1 Pty Ltd

Bluewaters Power 1 Pty Ltd Bluewaters Power 1 Pty Ltd Electricity Generation Licence (EGL 4) 2014 Performance Audit (Independent Assurance) Report June 2014 Deloitte Touche Tohmatsu ABN 74 490 121 060 Woodside Plaza Level 14 240

More information

Construction Audit Process

Construction Audit Process Construction Audit Process Underground Developments Record Number: R0000389952 Version Number: 5.0 Date: September 2016 Authorisations Action Name and title Date Prepared by Project Management Works and

More information

BACKGROUND AND PURPOSE

BACKGROUND AND PURPOSE DEA AS AN ORGAN OF STATE SUBSCRIBES TO AND PROPAGATES BOTH THE NOTION OF BROAD BASED BLACK ECONOMIC EMPOWERMENT (BBBEE) ACT, No. 53 Of 2003 AND THE PREFERENTIAL PROCUREMENT POLICY FRAMEWORK ACT, No. 5

More information

Public Lighting Application and Price Guide

Public Lighting Application and Price Guide Public Lighting Application and Price Guide For the regulatory year 1 July 2014 to 30 June 2015 As approved by the AER COPYRIGHT AURORA ENERGY PTY LTD, ABN 85 082 464 622, ALL RIGHTS RESERVED This document

More information

Electrical utility distribution network capital planning

Electrical utility distribution network capital planning Electrical utility distribution network capital planning A network reliability informed approach to prioritising investment for economic sustainability Dr Clinton Carter-Brown Martin Cameron 63 rd AMEU

More information

Trade Waste Management Policy Supporting Document

Trade Waste Management Policy Supporting Document Trade Waste Management Policy Supporting Document 1. Purpose The Trade Waste Management Policy Supporting Document is written to provide information and advice on trade waste matters. 2. Scope This document

More information

Electricity Networks Corporation (Western Power) Electricity Transmission Licence (ETL 2) Performance Audit Report

Electricity Networks Corporation (Western Power) Electricity Transmission Licence (ETL 2) Performance Audit Report Networks Corporation (Western Power) Transmission Licence (ETL 2) Performance Audit Report September 2011 Grant Thornton Australia Ltd. All rights reserved. Contents Acronym List 1 1. Introduction 4 2.

More information

Training. Commercial Engineering Services. High Voltage Engineering Specialists A unique combination of experience and expertise

Training. Commercial Engineering Services. High Voltage Engineering Specialists A unique combination of experience and expertise What will you learn today? Training Commercial Engineering Services High Voltage Engineering Specialists A unique combination of experience and expertise Training Contents 02 01 Our Academy 03 02 Why Choose

More information

STATUTORY AUTHORITY: ACT no. 50 of 29 June 1990, section 7-6

STATUTORY AUTHORITY: ACT no. 50 of 29 June 1990, section 7-6 NOTE: Unofficial translation - for information only REG. no. 959 of 7 December 1990: Regulations concerning the generation, conversion, transmission, trading, distribution and use of energy etc. (The Energy

More information

LEVEL 1 Application for Interconnection and Net Metering

LEVEL 1 Application for Interconnection and Net Metering LEVEL 1 Application for Interconnection and Net Metering Use this application form only for a generating facility that is inverter based and certified by a nationally recognized testing laboratory to meet

More information

RUWACON QUALITY MANUAL

RUWACON QUALITY MANUAL RUWACON QUALITY MANUAL Rev Date Preparation Review Approved Description of Revision 1 29 June SHEQ Manager SHEQ Manager Managing 2011 Director Ruwacon (PTY) Ltd P.O. Box 13596 Noordstad 9303 THIS DOCUMENT

More information

Reliability Centered Asset Management (RCAM)

Reliability Centered Asset Management (RCAM) Reliability Centered Asset Management () Aiming at Energy Efficient Transmission & Distribution System IRFAN AHMAD (FIEEEP). Energy Management & Energy Audit Electrical Utilities Energy Management: Optimization

More information

Defining and promoting excellence in the provision of mobile money services

Defining and promoting excellence in the provision of mobile money services SAFEGUARDING OF FUNDS DATA PRIVACY AML/CFT/FRAUD PREVENTION STAFF AND PARTNER MANAGEMENT CUSTOMER SERVICE TRANSPARENCY QUALITY OF OPERATIONS SECURITY OF SYSTEMS Defining and promoting excellence in the

More information

Residential Heat Pump Rebate Programme

Residential Heat Pump Rebate Programme Residential Heat Pump Rebate Programme Information session 18 February 2011 Agenda Item Residential heat pump rebate programme Opening Technology and welcome Who Andrew Etzinger Conditions of participation

More information

on supervision of significant branches

on supervision of significant branches EBA/GL/2017/14 16/02/2018 Guidelines on supervision of significant branches 1. Compliance and reporting obligations Status of these guidelines 1. This document contains guidelines issued pursuant to Article

More information

NIGERIA ELECTRICITY TRANSMISSION PROJECT (NETAP)

NIGERIA ELECTRICITY TRANSMISSION PROJECT (NETAP) NIGERIA ELECTRICITY TRANSMISSION PROJECT (NETAP) TERMS OF REFERENCE (TOR) For TECHNICAL ASSISTANCE FOR ENGINEERING SUPERVISION AND SITE MANAGEMENT OF REHABILITATION & REINFORCEMENT OF 330/132kV & 132/33kV

More information

CONSULTATION PAPER COST OF SUPPLY FRAMEWORK FOR LICENSED ELECTRICITY DISTRIBUTORSIN SOUTH AFRICA

CONSULTATION PAPER COST OF SUPPLY FRAMEWORK FOR LICENSED ELECTRICITY DISTRIBUTORSIN SOUTH AFRICA CONSULTATION PAPER COST OF SUPPLY FRAMEWORK FOR LICENSED ELECTRICITY DISTRIBUTORSIN SOUTH AFRICA Issued by: The National Energy Regulator 526 Madiba Street Arcadia,Pretoria 0007 Contact Details: Tel: +27(0)12

More information

Annexure 1: Scope of work for the Information Service Management Tool (Help desk Tool)

Annexure 1: Scope of work for the Information Service Management Tool (Help desk Tool) Annexure 1: Scope of work for the Information Service Management Tool (Help desk Tool) The purpose of the University acquiring the solution/system is to satisfy the following objectives: Have a single

More information

IMP/001/010 Code of Practice for Standard Arrangements for Customer Connections

IMP/001/010 Code of Practice for Standard Arrangements for Customer Connections Version:- 6.1 Date of Issue:- August 2017 Page 1 of 59 IMP/001/010 Code of Practice for Standard Arrangements for Customer Connections 1 Purpose The purpose of this document is to state Northern Powergrid

More information

Electricity Distribution Network Code. made under the Electricity Act 1994

Electricity Distribution Network Code. made under the Electricity Act 1994 Electricity Distribution Network Code made under the Electricity Act 1994 CHAPTER 1: THIS CODE 4 1.1 Introduction 4 1.1.1 Code objective 4 1.1.2 Scope of the Code 4 1.1.3 Authority 4 1.1.4 Date of effect

More information

LEVEL 2 Application For Interconnection And Net Metering

LEVEL 2 Application For Interconnection And Net Metering LEVEL 2 Application For Interconnection And Net Metering Use this Application form when generating facility is not inverter-based or is not certified by a nationally recognized testing laboratory to meet

More information

PETROLEUM PIPELINES REGULATION

PETROLEUM PIPELINES REGULATION PETROLEUM PIPELINES REGULATION Information to assist licence applicants to file licence applications in terms of the Petroleum Pipelines Act, 2003 (Act No. 60 of 2003) Version 1 November 2013 DISCLAIMER:

More information

Service Standards for Western Power Corporation s South West Interconnected System

Service Standards for Western Power Corporation s South West Interconnected System Service Standards for Western Power Corporation s South West Interconnected System Report prepared for Economic Regulation Authority Western Australia Contents 1 Executive summary 3 2 Introduction 7 2.1

More information

Jemena Electricity Networks (Vic) Ltd

Jemena Electricity Networks (Vic) Ltd Jemena Electricity Networks (Vic) Ltd 2016-20 Electricity Distribution Price Review Regulatory Proposal User-requested services explanatory statement Public 30 April 2015 TABLE OF CONTENTS TABLE OF CONTENTS

More information

EDB Information Disclosure Requirements Information Templates for Schedules 11a 13

EDB Information Disclosure Requirements Information Templates for Schedules 11a 13 EDB Information Disclosure Requirements Information Templates for Schedules 11a 13 Disclosure Date 31 March 2014 Start Date (first day) 1 April 2014 Templates for Schedules 11a 13 (Asset Management Plan)

More information

SALGA South African Local Government association

SALGA South African Local Government association www.salga.org.za SALGA South African Local Government association Driving Energy Efficiency and Renewable Energy in Municipalities: Energy Performance Contracting: Experiences from the City of Cape Town

More information

SCHEDULE SS STANDBY SERVICE

SCHEDULE SS STANDBY SERVICE SCHEDULE SS STANDBY SERVICE SHEET NO. 69 A. APPLICABILITY: Applicable to customers with alternate regular source(s) of energy other than electricity from the Company when such sources are connected to

More information

- Commissioning process and sign off - GIZ All rights reserved

- Commissioning process and sign off - GIZ All rights reserved - Commissioning process and sign off - 1 Commissioning Section process Heading and sign off Agenda 1. Is commissioning necessary? 2. Commissioning part of application process 3. Responsibilities and liabilities

More information

Utility Licence Annual Technical Report

Utility Licence Annual Technical Report Utility Licence Annual Technical Report 2016-17 This compliance report is required to be completed by Distribution and approved by the General Manager Networks or the Chief Executive Officer of Distribution

More information

DISTRIBUTION NETWORK OPERATOR CONNECTION CHARGING METHODOLOGY

DISTRIBUTION NETWORK OPERATOR CONNECTION CHARGING METHODOLOGY DISTRIBUTION NETWORK OPERATOR CONNECTION CHARGING METHODOLOGY Prishtina 2017 Contents 1. Purpose... 4 1.1 Scope... 4 1.2 Definitions and Terms... 4 2. Introduction and Background... 7 2.1 Legal and Regulatory

More information

Audit Follow-Up. Water Infrastructure (Report #0919 issued September 30, 2009) As of March 31, Summary

Audit Follow-Up. Water Infrastructure (Report #0919 issued September 30, 2009) As of March 31, Summary Audit Follow-Up As of March 31, 2010 Sam M. McCall, Ph.D., CPA, CGFM, CIA, CGAP City Auditor Water Infrastructure (Report #0919 issued September 30, 2009) Report #1018 June 7, 2010 Summary Thirteen of

More information

Energy Coordination Act Gas Distribution Licence Performance Reporting Handbook

Energy Coordination Act Gas Distribution Licence Performance Reporting Handbook Energy Coordination Act 1994 Gas Distribution Licence Performance Reporting Handbook April 2018 2018 This document is available from the website at www.erawa.com.au. For further information, contact: Perth,

More information

IMP/001/010 Code of Practice for Standard Arrangements for Customer Connections

IMP/001/010 Code of Practice for Standard Arrangements for Customer Connections Version:- 6.0 Date of Issue:- August 2015 Page 1 of 62 IMP/001/010 Code of Practice for Standard Arrangements for Customer Connections 1 Purpose The purpose of this document is to state Northern Powergrid

More information

AEL.NP.001 New Connections and Extensions Policy

AEL.NP.001 New Connections and Extensions Policy AEL.NP.001 New Connections and Extensions Policy 10 February 2014 Version 3 Contents Introduction... 3 Amendment Record... 5 1. Technical Requirements for New Connections to the Network... 6 1.1 Method

More information