TECHNICAL SPECIFICATIONS FOR AERIAL BUNCHED CABLES FOR OVERHEAD DISTRIBUTION
|
|
- Cordelia Reed
- 6 years ago
- Views:
Transcription
1 TECHNICAL SPECIFICATIONS FOR AERIAL BUNCHED CABLES FOR OVERHEAD DISTRIBUTION 1 INTRODUCTION Aerial Bunched Cable (ABC) is a very novel concept for Over Head power distribution. When compared to the conventional bare conductor over head distribution system, ABC provides higher safety and reliability, lower power losses and ultimate system economy by reducing installation, maintenance and operative cost. This system is ideal for rural distribution and specially attractive for installation in difficult terrains such as hilly areas, forest areas, coastal areas etc. ABC is also considered to be the best choice for power distribution congested urban areas with narrow lanes and by-lanes. In developing urban complex, ABC is the better choice because of flexibility for rerouting as demanded by changes in urban development plan. 2 CONSTRUCTION OF ABC XLPE/HDPE insulated power conductors of Aluminum (Neutral conductor and, street lighting conductors if and when necessary) are laid together (twisted) around a high tensile stranded and galvanized steel (Aluminum Alloy may be used) insulated or bare messenger wire to form the Aerial Bunched Cable. This assembly is directly strung on to distribution pole/towers by means of standard hard wares available in the market but care shall be taken to render the messenger wire completely insulated from earthing at any point of distribution in case of HT ABC. The XLPE (Cross-linked Polyethylene) insulation is black in colour and is stabilized against deterioration caused by exposure to direct sunlight and ultraviolet radiation. XLPE is cross-linkable low density polyethylene which is made thermoset by special formation from base polymer of thermoplastic low density polyethylene. XLPE combines the best electrical properties of LDPE and superior thermo mechanical properties. 3 MATERIALS (i) Aluminium conductors conform to IS:8130 (Class-II) (ii) Stranded high tensile galvanized steel messenger wire conforms to IS:398 (Part-2). Alternatively Aluminium Alloy messenger wire conforms to IS:398 (Part-IV) (iii) XLPE and HDPE insulation of power conductors conform to IS: 7098 (Part I & II) and IS: 6474 respectively. Since, the tension -from the current carrying conductor is totally removed by introduction of messenger. wire the operating temperature of the conductor is 90 C as against 75 C of the bare conductor under tension thereby allowing ABC to carry current equivalent to that of bare conductor of the same size. 4 STRINGING No difficulty is envisaged during stringing of ABC in the conventional method but care shall be taken that insulated conductors do not get damaged during installation. Dragging the ABC on the ground is to be avoided. Tension to be applied during stringing shall be % of the breaking load of the messenger wires. This will allow line to have sag within specified limit of 1.5% of the span at the lowest ambient temperature. 5 JOINTING While mid-span jointing permissible for L T ABC system by conventional technique, our recommendation will be to draw the line in such a way as to bring the joints at the supports. Mid-span jointing is not at all recommended in the case of HT lines our recommendation is for outdoor type HV terminations only. Under unavoidable circumstances, line tapping at the support points may be allowed through suitably designed clamp connectors/pg clamps. The semi-conducting screen continuity shall be maintained at all joints as far as possible to avoid fluctuations during system disturbances. The 3-phase screens may be shorted and earthed through suitable non-linear surge arrestor. Attempting to make a tap off from power conductors in the region where catenary is under tension is not recommended. 6 RELIABILITY, SAFETY AND FLEXIBILITY: ABC Cables are highly reliable and insulation has been developed to withstand heat, cold and intense sunlight. Disturbance and faults occur five to ten times more often in open wire lines than in ABC lines. There is no risk in touching the live cable and the insulation reduces the number of short circuits and over-voltages in overhead cables during thunder-stones. Few hardware accessories are needed as each one can be used with many different sizes of cable. This makes installation and storage easier. Streets can easily be get lit at little extra cost by using the ABC cables that have an extra conductor for lighting. The cable can be supplied with one or two insulated conductors for street lighting. The hardware and accessories for AB cables are made by various reputed manufacturer and is easily available in India. They are similar to the standard hardware available for Bare conductor overhead distribution lines.
2 7 APPROVAL & CERTIFICATION (i) BIS License for 1S for 1l00V Wires & Cables. (ii) BIS License for IS (iii) BIS License for I_ 7098 PART 1 & II (iv) BIS License for Overhead Aluminium Conductor (18-398) and Copper Conductor (1S-282) and for other Conductors. (v) Quality System Certification upgradation from ISO to' ISO 9001 by Underwriters Laboratories, in final stage. (vi) Safety Certification for various conductors as per BASEC are under finalization. TECHNICAL PARTICULARS LT Aerial Bunched Cable 1100 Volts (4 crore) Reference standard: Generally to IS:7098(1)88
3 QUALITY SETUP Conductors are generally the only means to transport current or signals with required safety norms. Therefore the material of its construction, purity and other important aspects of metallurgy are the critical factors to source the wire rods. We have latest 3-D profile die checking and refurbishment system. The sourcing of wire drawing, lubricant is from company like Houghton Italy and intensive inspection testing Conductor to ensure quality. QA IN PLANNING Customer requirements, alongwith the orders are taken into quality planning with due care for designing, manufacturing, testing and performance aspects QA IN RAW MATERIALS The raw materials are procured from the best sources from the domestic and global market These sources are selected on the based on the company's stringent quality vendor evaluation/ continuous assessment and testing. QA ONLINE The company has online computerised control system on all its critical processes and a team of on line testing engineers to ensure the consistency in quality TESTING Each consignment of conductor & wires is exhaustively tested before dispatch clearance, by highly qualified, Experienced and dedicated testing team. The testing setup is broadly classified as follows 1) RM. Testing Labs. 2) Routine Testing for Conductor, LT wires & Cables 3) Type Testing Labs include FR/FS/FRLS testing All the laboratories are equipped with the modern testing Instruments. All the instruments are under strict Calibration and environment control.
4 TECHNICAL PARTICULARS LT Aerial Bunched Cable 1100 Volts (3 1/2 crore) Reference standard: Generally to IS:71098(1)88
5 FINISHED AERIAL BUNCHED CABLE TESTING Prior to despatch cable is subjected to rigorous testing. Test procedures followed at our works are according to various national & International specifications and are covered in this paper. Following tests are performed on Aerial Bunched Cables: 1. Test on Phase/Street lighting conductor TESTS METHOD OF TESTING a) Tensile test IS: pt -2 b) Wrapping test IS: pt -3 c) Conductor Resistant Test IS: pt - 5 d) Test for thickness of insulation IS: pt -6 e) Physical test for polyethylene insulation (i) Tensile strength & Elong Test IS: pt -7 (ii) Melt flow index IS: pt -23 (iii) Vicat softening Point IS: pt - 22 (iv) Carbon Black Content & IS: pt - 32 dispersion (v) Colour factness IS: pt - 18 (vi) Environmental stress cracking IS: pt - 29 (vii) Bleeding & Blooming IS: pt -19 (viii) Volume Resistivity test IS: pt -43 (f) High Voltage test including water IS : 1596 immersion test. 2. Test for messenger conductor a) Breaking load test IS:398 (pt - IV) b) Elongation test IS: 398 ( pt - IV) c) Resistance test IS: 398 (pt - IV) 3. Dimensional test as per the parameters specified in the technical particulars 4. Bending test on completed cable shall also as performed. The diameter of mandrel shall be 10 (Dd) Where D = Overall diameter of the cable d = Dia over conductor
6 TECHNICAL PARTICULARS LT Aerial Bunched Cable 1100 Volts (4 crore) Reference standard: Generally to IS: S.No Description 3 x 1 x 3 x 1 x 3 x 35 1 x 3 x 50 1 x Power/ Neutral Core : Conductors a) Nom.cross sectional area (i) Power cores (mm2) (ii) Neutral conductor (mm2) b) Max D C resistance conductor at 20 c (i) Phase conductor (Ohm/Km) (ii) Neutral Conductor (Ohm/Km) c) Approx. diameter of Conductor (Compacted) (i) Phase conductor (mm) (ii) Neutral conductor (mm) Insulation: Minimum thickness (i) Phase conductor (mm) Messenger Wire (Bare): (i) Nom. Cross sectional area (Sq mm) 35 (ii) Approx Tensile Strength (KN) Current ratings: Continuous current carrying capacity of cable in Air at Ambient temp. 40 c (AMP) Approx weight (Kg/Km) Number of cores: (i) Power cores (No.) : 3 (ii) Neutral Messenger Core (No.) : 1 6 Derating factor: Derating factors for variation In air Temp Air Temp ( C) Rating factor (i) Identification of Power core: (ii)laying: 8 Details of the Power/Neutral core: (i) Conductor (a)material (b)flexibility class as per IS:8130/84 (c)form of conductor (ii) Insulation (a) Material (b) Colour of Insulation By providing ridges on the insulation Three power cores and one neutral core shall be suitably twisted around bare AAAC Messenger. Aluminium to IS: 8130/84 Class 2 Compacted circular High Density Polyethylene to IS: Black 9 Details of the Messenger wire (Bare) (a) Material (b) Form of conductor All alloy aluminium Conductor to IS:398 (IV) Stranded compacted circular
7 TECHNICAL PARTICULARS LT Aerial Bunched Cable 1100 Volts (5 Crore) with Street Lighting Conductor - Reference Standard: Generally to IS: S. No Description 3 x 1 x 1 x 3 x x 1 x 3 x 35 1 x 1 x 3 x 50 1 x 1 x 35 3 x 70 1 x 1 x 50 3 x 95 1 x 1 x 70 3 x x 1 x Power/ Neutral Core : Conductors a) Nom.cross sectional area (i) Phase Conductor (mm2) (ii) Street Lighting conductor (mm2) b) Max D C resistance conductor at 20 c (i) Phase conductors (Ohm/Km) (ii) Street Lighting (Ohm/Km) c) Approx. diameter of Conductor (i) Phase conductor (m m) (ii) Street Lighting conductor (mm) Insulation: Minimum thickness (i) Phase conductor (mm) (ii) Street Lighting Conductor (mm) Messenger Wire (Bare): (i) Nom. Cross sectional area (Sq mm) (ii) Approx breaking load (KN) Current ratings: Continuous current carrying capacity of cable in Air at Ambient temp. 40 c (AMP) Approx weight (Kg/Km) Number of cores: (i) Power cores (No.) : 3 (ii) Neutral Core (No.) : 1 (iii) Bare Messenger (No.) : 1 6 Derating factor: Derating factors for variation In air Temp Air Temp ( C) Rating factor (i) Identification of Power core: (ii) Laying: 8 Details of the Power/Neutral core: (i) Conductor (a) Material (b) Flexibility class as per IS:8130/84 (c) Form of conductor (ii) Insulation (a) Material (b) Colour of Insulation By providing ridges on the insulation Three power cores and one neutral core shall be suitably twisted around bare AAAC Messenger. Aluminium to IS: 8130/84 Class 2 Compacted circular High Density Polyehylene to IS: Black 9 Details of the Messenger wire (Bare) (c) Material (ii) Form of conductor All alloy aluminium Conductor to IS:398 (IV) Stranded compacted circular
8 TECHNICAL SPECIFICATION FOR LV AERIAL BUNCHED CABLES (I) SCOPE This specification covers design, engineering, manufacture, assembly, stage testing, inspection and testing before supply and delivery at site of HIGH DENSITY POLYETHYLENE Insulated (HDPE) Aluminum Cables twisted over central bare aluminum messenger' wire. The sizes are lx sq.mm and 2x Sqmm. (II) STANDARDS The materials shall conform in all respects to the relevant Indian Standard Specifications with latest amendments thereto. Indian Title International & Standard Internationally ecognised standard IS /1984 Aluminium conductors for Insulated electric cables IS /1984 Polyethylene Insulation for cables for voltage upto and including 1000 V IS-398/Part-IV/ All Aluminium Alloy IEC - 228/ Conductors (AAAC) for overhead Transmission purposes Conductors of Insulated Cables IS 10418/1982 Drums for electric cables IS - 656/1988 Specification for logs for BS148/ASTMD plywood 1275, D1533, D 1934, IEC PUB Material conforming to other internationally accepted standards, which ensure equal or higher quality than the standards mentioned above would also be acceptable. In case the Bidders who wish to offer material conforming to the other standards, salient points of difference between the standards adopted and the specific standards shall be clearly brought out in relevant schedule. Four copies of such standards with authentic English Translations shall be furnished along With the offer. (III) TECHNICAL REQUIREMENTS a. General: The insulated phase conductor shall be twisted round bare aluminium alloy messenger wire, which shall take all the mechanical stress. The messenger shall also serve as the earth-cumneutral. The typical arrangement of the phase conductors and messenger wire shall be as per relevant standards. The typical arrangements of cables straight run, Angle and Dead end shall be (IV) as per relevant standards. PHASE CONDUCTOR The sq.mm. phase conductor shall be of aluminium solid round; outer diameter shall be within the limits. The phase conductor shall be insulated with black weather resistant high-density polyethylene (HDPE) suitable to 1100 V insulation. The insulated conductors shall generally conform to the relevant standards. Conductors: The properties of the aluminium wires before stranding shall be: Tensile strength not less than 90 N/Sq.mm. Resistivity at 20 Deg. C not exceeding ohm / Sq.mm / m (V) INSULATION a. Material: The insulation shall be black weatherresistant special high-density polyethylene. b. Messenger (Neutral conductor): The messenger shall be an All Aluminium Alloy Conductor composed of 7 wires each of 2.34 mm. Dia. drawn from rod, which is manufactured in a continuous casting and rolling procedure. The properties for the individual wires before stranding shall be: Tensile strength not less than 294 N / sq.mm. Elongation at 0 mm gauge length not less than 4%. Density at 20 Deg. C not exceeding ohm /sq.mm./m. Density at 20 De"g. C 2.7 Kg./Cubic-dm No joints are allowed in the messenger except those made on the base rod or wire before final drawing within the standard length of 2 km. The messenger shall be round, stranded and compacted to have smooth round surface. The messenger takes all the mechanical stress and also serves as a neutral conductor. Neutral conductor over all dia (max.)6.5 mm DC resistance at 20 ego C(Max) 1.38 ohm / km Minimum breaking load 7.4 kn. c. Design: The cable consists of one black weather resistant special high-density polyethylene (HDPE) insulated Aluminium phase conductor, stranded around a bare All Aluminium Alloy messenger, which is also the neutral conductor. The construction data
9 is specified below: No. of cross sectional area of conductor (sq.mm) Phase Conductor Messenger Complete cable No and Diameter Insulation Overa Diameter of Tensile Overall Total cross of un - thickness ll dia uninsulated strength diameter mass sectional area insulated cond uctor (mm) of condu conductor Max (mm) (approx) Min (Kg) (approx) (mm) (approx) (Kg/Km) (sq.mm) Max (mm) ctor (mm) 1 x 1 x d. The resistance of the phase conductor and the messenger are determined with direct current the same are corrected to 20 Deg. C using the formula and co-efficients given in clause 5 of standard IEC228. The values obtained shall not exceed the resistance, given below: Nominal Cross sectional area of conductor (sq.mm) No. of strands DC Resistance at 20 C Ohm/Km (Max) Insulation thickness average in (mm) Phase Neutral conductor conductor Aluminium Aluminium alloy Bare Note: The average value of thickness of the insulation shall not be less than the specified average value' The thickness at any place may be less than the specified average value, provided that the difference not exceed 0.1 mm. For thickness of insulation six measurements are made readily on a piece of insulation as far as possible equally spaced around the circumference but not on the ridges. e. Polyethylene Insulation: The polyethylene insulation shall generally conform to relevant Standards. The.following properties shall be guaranteed by the supplier. For methods of testing IS-I086 (relevant parts) may be referred. Density of HDPE (ST4) 0.95 to 0.96 g/cu.cm Melt flow index max 3.0 Tensile strength Not less than 10 N/sq.mm Percentage elongation Not less than 300 Carbon black contents Between 2 and 3% Vicat softening point Not less than 85 Deg. C At 70 Deg 1 x 1013 Ohm cm (min) Environmental stress cracking No cracks shall be visible to the naked eye (VI) TESTING a. Type Tests: The material offered shall be fully type tested by the Bidder or his collaborator as per the relevant standards. The bidder shall furnish four sets of type test reports along with bid. The bids received without type test reports shall be treated as non-responsive. Tests for phase conductor Tensile test (IS:8130) Wrapping test (IS:8130) Conductor resistance test Test for thickness of insulation Tensile strength and elongation at break of insulation Physical tests for polyethylene insulation Ageing in air oven Shrinkage test Hot deformation Loss of mass in air oven Heat shock test Thermal stability Test for bleeding and blooming of pigment (IS:6474) Insulation resistance test High voltage test including water immersion test (IS: 1596) High voltage test at room temperature Flammability test b. Test for messenger Breaking load test (to be made on the finished conductors (IS 398/Part IV) Elongation test (IS-398/part IV). Resistance test (IS-398/part-IV) c. Acceptance and Routine Tests: All the acceptance and routine tests shall be conducted as per the relevant standards in the presence of purchaser's representative. The values shall conform to guaranteed values. Immediately after finalization of the Programme of acceptance/routine testing, the manufacturer shall give 15 days advance intimation to the purchaser, to enable him to depute his representative for witnessing the tests. d. Bending test on the complete cable: The test shall be performed on a sample of complete: cable. The sample shall be bent around a test mandrel at room temperature for at least one complete turn. It
10 shall then be unwound and the process shall be repeated after turning the sample around its axis 180 Deg. The cycle of these operations shall then be repeated twice more. The diameter of the mandrel shall be 10 (Dd), where D-= Actual diameter of the cable (i.e. minimum circumscribing circle diameter in mm) d= actual diameter of the conductor in mm. No cracks visible to the naked eye should take place. (VII) PACKING & FORWARDING: a. The AB Cable shall be wound on non-returnable wooden drums conforming to IS-I 0418/ 1982 with latest amendments thereof. The ends of the cable shall be sealed by means of non-hygroscopic sealing material. The drum shall be marked with the following. Manufacturers name Trademark, if any Drum number or identification number Size of conductors Size of messenger Voltage grade Number and lengths of pieces of cable in each drum Gross mass including packing ISI mark if any Direction of rotation of the drum by marking an arrow b. The drums shall be of such construction as to assure delivery of cable in the field free from displacement and damage and should be able to withstand all stresses due to handling and the stringing operation so that cable surface is not dented, scratched or damaged in any way during transport and erection. The cable shall be properly lagged on the drums. c. The cable drum should be suitable for wheel mounting d. The mass of finished cable in a drum (without mass of drum) of various designation shall not exceed by more than 10% of the following values. Designation lxi6 Sq. mm 2xl6 Sq. mm Gross mass 800 Kg 1000 Kg e. The minimum length of each cable shall be 2km. While longer lengths shall be acceptable, shorterlengths not less than 1 kilometers shall be acceptable to the extent of 10% of the ordered quantity only. (VIII) MARKING OF CABLES: - All the cable shall have the following marking embossed on the insulated phase conductor for identification DHBVNL in intervals of not more than 1 meter. a. The packing shall be done as per the manufacturers standard practice. However, he should ensure the packing is such that the material should not get damaged during transit by Rai1/ Road. b. The marking on each package shall be as per the relevant IS (IX) GUARANTEED TECHNICAL PARTICULARS The Contractor shall furnish the guaranteed technical particulars and submit the same along with his tender.
TECHNICAL SPECIFICATION A.B. CABLE
TECHNICAL SPECIFICATION A.B. CABLE 1.0 NATURE OF WORK The work covered by this Specification is for L.T lines in A.B cable as specified herein and in the attached Schedules. The overhead distribution lines
More informationNUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0
REVISION NO. 0 NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0 PAGE NO. 1 OF 24 DATE OF ISSUE (MONTH/YEAR) TOTAL NO. OF PAGES (Including cover
More informationP.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT
CEB SPECIFICATION 005-1: 2012 P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS PAGE 1. Scope 03
More informationSPECIFICATION FOR ALL ALUMINIUM ALLOY STRANDED CONDUCTOR
003: 2008 CEB SPECIFICATION SPECIFICATION FOR ALL ALUMINIUM ALLOY STRANDED CONDUCTOR CEYLON ELECTRICITY BOARD SRI LANKA Specification for Specification For All Aluminium Alloy Stranded Conductor CEB Specification
More informationP.V.C. INSULATED UNARMOURED COPPER CABLES
083 : 2007 CEB SPECIFICATION P.V.C. INSULATED UNARMOURED COPPER CABLES CEYLON ELECTRICITY BOARD SRI LANKA Specification for P.V.C. INSULATED UNARMOURED COPPER CABLES CEB Specification 083 : 2007 CEYLON
More informationMESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITH METALLIC SCREEN
Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED Version: 1 Issued: March 2014 Owner: Electrical Networks Asset
More informationTECHNICAL SPECIFICATION FOR CONDUCTORS
TECHNICAL SPECIFICATION FOR CONDUCTORS SEAL & SIGNATURE OF THE TENDERER PAGE 1 OF 9 TECHNICAL SPECIFICATION FOR CONDUCTORS SPECIFYING TECHNICAL PARAMETERS OF THE CONDUCTOR SPECIFICATION NO. RE/ II/ ACSR
More informationNPS/002/020 Technical Specification for 11 & 20kV Power Cables
Version:- 3.1 of Issue:- Nov - 09 Page 1 of 11 NPS/002/020 Technical Specification for 11 & 20kV Power Cables 1. Purpose The purpose of this document is to detail Northern Powergrid (the Company) requirements
More informationTECHNICAL SPECIFICATIONS
TECHNICAL SPECIFICATIONS PAGODA CABLES PVT. LTD. 1/58, STREET NO: 3, VISHWAS NAGAR, SHAHDARA, DELHI 110 032. (INDIA) TEL/FAX : 91-11-22392801, 22385391. Email : pagoda @del2.vsnl.net.in CONTENTS: 1. 2.
More informationMESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 70mm 2 FLEXIBLE TINNED COPPER CONDUCTOR 3.3kV EPR INSULATED WITHOUT METALLIC SCREEN
Engineering Specification Electrical Networks MESP 030000-04 TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 70mm 2 FLEXIBLE TINNED COPPER CONDUCTOR 3.3kV EPR INSULATED WITHOUT METALLIC SCREEN Version: 1 Issued:
More informationTECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132/220/400 KV SUB-STATION
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132/220/400 KV SUB-STATION GETCO/E/TS-C&C
More informationTECHNICAL SPECIFICATIONS LAYING OF DIFFERENT WIRES & CABLES MOUNTED ON POLES FOR BRPL/BYPL
TECHNICAL SPECIFICATIONS OF LAYING OF DIFFERENT WIRES & CABLES MOUNTED ON POLES FOR BRPL/BYPL SPECIFICATION NO- GN101-03-SP-13-02 INDEX 1.0 SCOPE 4 2.0 DESIGN..4 3.0 REQUIREMENT...5 4.0 DESIGN ( DISTRIBUTION
More informationXLPE CABLE (11KV - Aluminium)
XLPE CABLE (11KV - Aluminium) September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091.
More informationCONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE
ONTARIO PROVINCIAL STANDARD SPECIFICATION OPSS.PROV 604 NOVEMBER 2017 CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE TABLE OF CONTENTS 604.01 SCOPE 604.02 REFERENCES 604.03 DEFINITIONS - Not Used
More informationTECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 400/220 KV SUB-STATION
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 400/220 KV SUB-STATION GETCO/E/TS C&C057/R0 DT.
More informationU.V resistance UL Sunlight Resistance. Flame retardant IEC
Cable for underground power distribution and subtransmission. Description Application Underground power distribution and subtransmission. As transformer feeders in substations. In power plants, industrial
More informationTECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132 KV SUB-STATION
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132 KV SUB-STATION GETCO/E/TS C&C057/R0 DT.
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60502-1 Second edition 2004-04 Power cables with extruded insulation and their accessories for rated voltages from 1 kv (U m = 1,2 kv) up to 30 kv (U m = 36 kv) Part 1: Cables
More informationSTANDARD FOR EXTRUDED INSULATION POWER CABLES RATED ABOVE 46 THROUGH 345 KV. Approved by AMERICAN NATIONAL STANDARDS INSTITUTE.
ANSI/ICEA S-108-720-2012 STANDARD FOR EXTRUDED INSULATION POWER CABLES RATED ABOVE 46 THROUGH 345 KV Approved by AMERICAN NATIONAL STANDARDS INSTITUTE November 27, 2012 Publication # ANSI/ICEA S-108-720-2012
More informationNotes Changed note Date. 1 (A) Changed template 09 / 07 / 2008
Revisions Notes Changed note Date 1 (A) Changed template 09 / 07 / 2008 2 Changed template. Clause 12.5.4.1 hot-rolled steel added. Clause 12.5.4.2, 12.5.2.4, 12.5.3.4, 12.5.4.4, 12.5.5.4, 12.5.6.4, 12.5.7.4
More informationSPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: -
SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: - 1. SCOPE: - This specification covers 11KV Disc Type & 11KV/ 22KV Pin Type Insulators for 11/22KV H.T. over head power lines. 2. APPLICABLE
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60502-2 Second edition 2005-03 Power cables with extruded insulation and their accessories for rated voltages from 1 kv (U m = 1,2 kv) up to 30 kv (U m = 36 kv) Part 2: Cables
More informationTechnical Specification for Single Core 38/66kV TR-XLPE Insulated Underground Cable
Ergon Energy Corporation Limited Technical Specification for Single Core 38/66kV TR-XLPE Insulated Underground Cable ETS04-03-01 Specification ETS04-03-01 Ver 1 Contents 1. Purpose and Scope... 1 1.1 General...
More informationTechnical Specification for Live Line Tap Connectors
Ergon Energy Corporation Limited Technical Specification for Live Line Tap ETS-06-01-01 Check this is the latest Process Zone version before use. Specification ETS 06-01-01 Ver 1 Contents 1. Purpose and
More informationBIS or used as Amendment to STANDARD comments is 15 Nov. 2008
Doc: MTD 4 (4730) For comments only BUREAU OF INDIAN STANDARDS Modified draft Indian Standard HOT ROLLED CARBON STEEL SHEET AND STRIP (Sixth Revision of IS 1079) ICS 77.140.50 Not to be reproduced without
More informationALUMINIUM CONDUCTORS FOR OVERHEAD TRANSMISSION PURPOSES
DRAFT Doc No.: SM/IS 398 (Pt.1) PRODUCT MANUAL FOR ALUMINIUM CONDUCTORS FOR OVERHEAD TRANSMISSION PURPOSES PART 1 ALUMINIUM STRANDED CONDUCTORS ACCORDING TO IS 398 (Part 1):1996 (with Amendment No.01 APR
More informationIEEE 1580 Type P MOR Polyrad XT-125 Multi Conductor
TABLE OF CONTENTS SECTION SUBJECT PAGE I. SCOPE...1 II. APPLICABLE DOCUMENTS...1 III. CONDUCTOR...2 IV. SEPARATOR...2 V. INSULATION...2 A. Physical Properties...2 B. Electrical Properties...3 C. Qualification
More informationTYPE TEST REPORT OF 11 KV 3 x 240 mm² CU/XLPE/SWA/PVC CABLE. Kinectrics International Inc. Report No.: K RC-0001-R00.
To: National Cables Industry P.O Box 27472 Al Dhaid Road, Al Sajja Industrial Area Sharjah U.A.E TYPE TEST REPORT OF 11 KV 3 x 240 mm² CU/XLPE/SWA/PVC CABLE Kinectrics International Inc. Report No.: K-422341-RC-0001-R00
More information2. TEST RECORDS: All records of tests and analysis shall be kept in suitable forms approved by the Bureau.
SCHEME OF TESTING AND INSPECTION FOR CERTIFICATION OF CARBON STEEL BILLETS, BLOOMS, SLABS AND BARS FOR FORGINGS ACCORDING TO IS:1875-1992 (Fifth Revision) 1. LABORATORY: A laboratory shall be maintained
More informationTechnical Specification for LV ABC Fuse Switch Disconnectors
Ergon Energy Corporation Limited Technical Specification for LV ABC Fuse ETS-06-02-02 Check this is the latest Process Zone version before use. Specification ETS 06-02-02 Ver 3 Contents 1. Purpose and
More informationNPS/001/007 Technical Specification for Overhead Line Conductors
Version:- 7.0 Date of Issue:- September 2016 Page 1 of 27 NPS/001/007 Technical Specification for Overhead Line s 1. Purpose The purpose of this document is to detail the range and technical performance
More informationDMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)
DELHI METRO RAIL CORPORATION LIMITED DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) SPECIFICATION NO. DMES- T/0018/ DMRC-E-TR-CABLE-2 SPECIFICATIONS FOR 33 kv CABLES FOR ELEVATED AND Issued on: Date Stage
More informationTECHNICAL SPECIFICATIONS
SPEC.NO. MSEDCL/ DIST:MSC-III/SPRING LOADED CONNECTOR BOX/05/10/R0/ 200510 TECHNICAL SPECIFICATIONS FOR TAMPER PROOF SERVICE CONNECTION BOX FOR L.T. LINES / CONSUMER MAINS (20.05.2010) Page 1 of 14 Clause
More informationA Study on Analysis of Transmission Line Tower and Design of Foundation
A Study on Analysis of Transmission Line Tower and Design of Foundation 1 B. Bharath Kumar Reddy, 2 K. Rasagnya, 3 V. Sanjay Gokul 1,2 Under Graduates, 3 Assistant Professor Abstract - The Transmission
More informationTECHNICAL SPECIFICATION OF MS TOR BARS FOR TRANSMISSION LINES
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION OF MS TOR BARS FOR TRANSMISSION LINES GETCO/E/TS-MS024/R2 DT08-02-2012 TECHNICAL
More informationTECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT
TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT 1.1 General 1.1.1 These Special Conditions of Contract supplement the General Instructions.
More informationTESTING PTE EARTHING
1 SCOPE This section of the Power Systems Live Working Manual details the procedures to be followed to achieve Safety from the System when carrying out examination, testing and remedial work on PTE (Pole
More informationEngineering Data for Copper and Aluminum Conductor Electrical Cables
2018 Edition Engineering Data for Copper and Aluminum Conductor Electrical Cables THE OKONITE COMPANY Okonite Cables...A higher Standard! The Okonite Company, 2018 Okonite Cables Table of Contents SECTION
More informationTECHNICAL SPECIFICATION FOR 11mtr. LONG STEEL TUBULAR POLE
Annexure-A TECHNICAL SPECIFICATION FOR 11mtr. LONG STEEL TUBULAR POLE 1.0 SCOPE 1.1 This specification covers the design, manufacture, testing at works, supply / delivery & transportation of 11 mtr long
More informationHOT ROLLED STEEL FLAT PRODUCTS FOR STRUCTURAL FORMING AND FLANGING PURPOSES SPECIFICATION (Third Revision of IS 5986)
For Comments Only Draft Indian Standard Doc: MTD 4(4939) HOT ROLLED STEEL FLAT PRODUCTS FOR STRUCTURAL FORMING AND FLANGING PURPOSES SPECIFICATION (Third Revision of IS 5986) ICS 77.140.50 Not to be reproduced
More informationTECHNICAL SPECIFICATION OF HIGH AMPACITY ALLOY CONDUCTOR ZEBRA/MOOSE CONDUCTOR FOR TRANSMISSION LINE
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION OF HIGH AMPACITY ALLOY CONDUCTOR ZEBRA/MOOSE CONDUCTOR FOR TRANSMISSION LINE
More informationPHOTOVOLTAIC SOLAR ENERGY POLYCRYSTALLINE MODULES - SI-ESF-M-P156-60
Solar Innova uses the latest materials to manufacture photovoltaic modules. Our modules are ideal for any application that uses the photoelectric effect as a clean energy source because of its minimal
More informationHPC-9DJ
Manual Distribution Design Manual Volume 2: Low Voltage Aerial Bundle Cable Standard Number: HPC-5DC-07-0002-2014 Document Control Author Name: Anthony Seneviratne Position: Standards Engineer Document
More informationDraft Indian Standard Galvanized Steel Sheets (Plain and Corrugated)- Specification (Seventh Revision of IS 277) ICS
FOR BIS Use Only Doc: No. MTD 4 (5207) Draft Indian Standard Galvanized Steel Sheets (Plain and Corrugated)- Specification (Seventh Revision of IS 277) ICS 77.140.50 Not be reproduced without the permission
More informationGeneral Requirements. Technical Specifications for Insulators of Transmission Lines
Islamic Republic of Iran Vice Presidency for Strategic Planning and Supervision General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Insulators of Transmission
More informationDATA SHEET. EM1000 Fine Ribbed Electrical Safety Matting, rated to IEC61111:2009 Class 0
DATA SHEET EM1000 Fine Ribbed Electrical Safety Matting, rated to IEC61111:2009 Class 0 Unit 21 Priory Industrial Park Airspeed Road Christchurch Dorset BH23 4HD Tel: 01425 278011 Fax: 01425 278012 www.deltarubber.co.uk
More informationTECHNICAL SPECIFICATION FOR MS BEAMS 116X100 11MTR LONG FOR SUB-STATIONS
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION FOR MS BEAMS 116X100 11MTR LONG FOR SUB-STATIONS GETCO/E/TS-MS024/R0DT01-04-2008
More informationENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD. ANSI/SCTE (Formerly IPS SP 100)
ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 15 2006 (Formerly IPS SP 100) Specification for Trunk, Feeder and Distribution Coaxial Cable NOTICE The Society
More informationConstruction guideline
1/6 1) SUMMARY OF ABBREVIATIONS FOR CABLE CONSTRUCTION ELEMENTS MSR - : EUPEN code for INSTRUMENTATION CABLES JE - : cable for INDUSTRIAL ELECTRONICS RD - : cable for CONTROL SYSTEMS INSULATION MATERIALS:
More informationAn Insight into Design, Development & Testing of Insulation Piercing Connectors for LV Application
An Insight into Design, Development & Testing of Insulation Piercing Connectors for LV Application Introduction Designed for Indoor and outdoor applications Non-tension tap and splice applications Used
More informationSECTION HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS (PRESSURE PIPE)
SECTION 02623 HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS (PRESSURE PIPE) PART 1 - GENERAL 1.1 SCOPE OF WORK A. Furnish all labor, materials, equipment and incidentals required and install high density
More informationServ. Low-Voltage Cable Insulated Conductors for Overhead and Underground Distribution
Serv Low-Voltage Cable Insulated Conductors for Overhead and Underground Distribution General Cable offers a complete line of insulated cable designs and sizes to meet utility requirements for exceptional
More informationCables for Railway Signalling Applications General Requirements
Discipline: Engineering (Signalling) Category: Procedure Cables for Railway Signalling Applications General Requirements ESA-11-01 Applicability ARTC Network Wide Primary Source ESA-02-01 Document Status
More informationGUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS. 66 kv LIGHTNING ARRESTORS
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 66 kv LIGHTNING ARRESTORS GETCO/ENGG/TECH SPECI.- 66 KV LA/R4/Jan11 Sign
More informationRBK-ILS-125 SCOPE. This Quality Assurance Specification establishes the quality standard for RBK-ILS-125.
RK 6638 Revision 9 Page 1 of 22 Date Printed 30-Apr-10 RK 6638 Revision 9 RBK-ILS-125 SCOPE This Quality Assurance Specification establishes the quality standard for RBK-ILS-125. The objective of this
More informationNPS/002/001 Technical Specification for Earthing Materials
Version:- 6.0 Date of Issue:- October 2017 Page 1 of 14 NPS/002/001 Technical Specification for Earthing Materials 1. Purpose The purpose of this document is to detail the requirements of Northern Powergrid
More informationSECTION REINFORCING STEEL
SECTION REINFORCING STEEL 1. DESCRIPTION This specification shall govern the furnishing and placing of reinforcing steel, deformed and smooth, of the size and quantity designated on the plans and in accordance
More informationSEAL & SIGNATURE OF THE TENDERER
MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO. LTD. SCHEDULE - `A' TECHNICAL SPECIFICATION FOR 11 kv & 22 kv A.B. SWITCH. SPECIFICATION NO:RE/II/A.B.SWITCH/2005 INDEX -----------------------------------------------------------------------------------------------------------------------
More informationQuality Standard for ACR Copper Tubes in LWC
Quality Standard for ACR Copper Tubes in LWC Foreword cuproclima is a protected tradename for high-quality seamless copper tubes in levelwound coils (LWC) supplied to manufacturers of heat exchangers for
More information1.1 All testing apparatus shall be periodically checked and calibrated records of such checks/calibration shall be maintained.
DOC: STI//1 SCHEME OF TESTING AND INSPECTION FOR CERTIFICATION OF ACCORDING TO IS/IEC:2003 1. LABORATORY A laboratory shall be maintained which shall be suitably equipped and staffed, where different tests
More informationProfile No.: 4 NIC Code: ELECTRICAL CABLES (SINGLE AND MULTICORE)
Profile No.: 4 NIC Code: 27320 ELECTRICAL CABLES (SINGLE AND MULTICORE) 1. INTRODUCTION: Electrical Cables and wires are used for power distribution in electrical systems in housing sector as well as in
More informationDETAIL SPECIFICATION SHEET CABLE, ELECTRICAL, -20 C TO +105 C, 1000 VOLTS, TYPE LSFSGU
INCH-POUND MIL-DTL-24643/17F 1 October 2009 SUPERSEDING MIL-DTL-24643/17E 22 August 2002 DETAIL SPECIFICATION SHEET CABLE, ELECTRICAL, -20 C TO +105 C, 1000 VOLTS, TYPE LSFSGU This specification is approved
More informationSPECIFICATION: LINE TAPS FOR ALUMINIUM/ACSR AND COPPER CONDUCTORS
Page no. :1 of 11 SPECIFICATION: LINE TAPS FOR ALUMINIUM/ACSR AND COPPER CONDUCTORS Prepared by: Eng. T. Lev (-חתום-) Checked by: I. Bester (-חתום (- Approved by: Eng. Y. Samoocha (-חתום (- 1 Page no.
More informationSection 906. STRUCTURAL STEEL
906.01 Section 906. STRUCTURAL STEEL 906.01. General Requirements. Finished rolled shapes must be free from imperfections that affect strength and durability in accordance with ASTM A 6. Rolled shapes
More informationMILITARY SPECIFICATION. PLASTIC MOLDING and EXTRUSION MATERIAL, POLYETHERETHERKETONE (PEEK)
20 June l984 1. SCOPE MILITARY SPECIFICATION PLASTIC MOLDING and EXTRUSION MATERIAL, POLYETHERETHERKETONE (PEEK) This specification is approved for use by all Departments and Agencies of the Department
More informationMineral Insulated Platinum Resistance Thermometer PT100 Sensor - Available in 3mm or 6mm diameter x 150mm or 250mm probe lengths
Datasheet ENGLISH Mineral Insulated Platinum Resistance Thermometer PT100 Sensor - Available in 3mm or 6mm diameter x 150mm or 250mm probe lengths High temperature, rugged, flexible Pt100 probe Suitable
More information15 kv EPR Insulated, Jacketed, URD Cable
15 kv EPR Insulated, Jacketed, URD Cable 1000 kcm Copper Conductor with Tape Shield Page 1 of 11 Table Of Contents 1 GENERAL... 3 2 STANDARDS... 3 3 APPROVED CABLE MANUFACTURERS... 3 4 REEL SPECIFICATIONS...
More informationPHOTOVOLTAIC SOLAR ENERGY POLYCRYSTALLINE MODULES - SI-ESF-M-BIPV-SM-P125-36
Solar Innova uses the latest materials to manufacture photovoltaic modules. Our modules are ideal for any application that uses the photoelectric effect as a clean energy source because of its minimal
More information3M Cold Shrink Silicone Rubber Connector Insulators 8440 Series
3M Cold Shrink Silicone Rubber Connector Insulators 8440 Series Data Sheet May 2014 Product Description 3M Cold Shrink Connector Insulators 8440 Series are open-ended, silicone rubber, tubular sleeves.
More informationBARE OVERHEAD CONDUCTORS
BARE OVERHEAD CONDUCTORS BARE OVERHEAD CONDUCTORS MISSION De Angeli Prodotti aspires to be the manufacturing leader - in terms of quality and innovation - of both insulated and enameled wires for electromechanical
More informationBUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466
BUSWAY LOW VOLTAGE (POW-R-WAY III) PART 1 GENERAL 1.01 1.02 SCOPE The Contractor shall furnish and install the busway system including all necessary fittings, hangers and accessories as specified herein
More informationTechnical Specification for Aluminium Castings, Pole Caps and Pressed Symbols
Ergon Energy Corporation Limited Technical Specification for Aluminium Castings, Pole Caps and Pressed Symbols ETS-01-05-01 Check this is the latest Process Zone version before use. Specification ETS 01-05-01
More informationSCHEDULE-III TECHNICAL SPECIFICATION OF 11 KV CTPT METERING SETS AGAINST TN-2134
Common Spec-2134.doc - 1-3.01 SCOPE: SCHEDULE-III TECHNICAL SPECIFICATION OF 11 KV CTPT METERING SETS AGAINST TN-2134 This specification covers the design, manufacture, assembly, testing and delivery of
More informationB-LINE SERIES. DURA-BLOK rooftop supports BRTS-17 DURA-BLOK. A complete rooftop support solution
DURA-BLOK rooftop supports BRTS-17 B-LINE SERIES DURA-BLOK A complete rooftop support solution DURA-BLOK rooftop solutions support DURA-BLOK supports are made of 100% recycled rubber and are designed to
More informationITEM L-119 AIRPORT OBSTRUCTION LIGHTS DESCRIPTION
SECTION 74 AIRPORT OBSTRUCTION LIGHTS (FAA L-119) 74-1 GENERAL The Contractor shall perform all work required by the plans and specifications for construction of obstruction lights in accordance with the
More informationThermocouple cable and assemblies ENCLAD
Thermocouple cable and assemblies ENCLAD ENCLAD thermocouples Introduction BASF ENCLAD thermocouple products are a precise and rigorously controlled combination of select precious and base metal sheaths,
More informationcatalog Copper Wires
catalog Copper Wires ASWire Aerial Service Wire Self Supporting Multi-pair Pair Count 1-18P Multi-pair, self-supporting Aerial Service Wires (ASW) are used for subscriber lines in exchange plant; single-pair
More information*** Supercedes: BECO E and COM , , & ***
7/27/09 Page 1 of 9 R5 *** Supercedes: BECO E2.9-27.4 and COM 1-0696, 2-0196, & 5-0385 *** 1.0 Scope #2 AWG to 1000 KCMIL CONCENTRIC NEUTRAL JACKETED CABLES RATED 5-35 kv These Specifications cover single
More informationA. Product Data shall be provided for each type of product indicated.
32 31 13 CHAIN LINK FENCES AND GATES SECTION 1 GENERAL 1.1 SUMMARY This Section includes the following: 1. Chain Link Fences 2. Gates for Chain Link Fences. See electrical specifications for electrical
More informationTechnical Specifications of 8 M and 9 M PCC Poles (F.O.S.-2.5) with working load 200 Kg.
DAKSHIN HARYANA BIJLI VITRAN NIGAM LIMITED Specification No. S-95/DD-177 Technical Specifications of 8 M and 9 M PCC Poles (F.O.S.-2.5) with working load 200 Kg. Chief Engineer/P&D, DHBVN, Hisar. Issue
More informationNSP/004/105 (OHI 5) - Guidance on the selection, erection and sagging of O/H line conductors
Version:- 4.0 Date of Issue:- January 2018 Page 1 of 21 NSP/004/105 (OHI 5) - Guidance on the selection, erection and sagging of O/H line conductors 1. Purpose The purpose of this document is to provide
More informationSuperastic Flex Cable 450 / 750V Exceeds all the specifications in its category.
Superastic Flex Cable 450 / 750V Exceeds all the specifications in its category. Superastic Flex Extra sliding for extra easy installation. Superastic Flex cables are ideal for those who want to save installation
More informationQQ-A-250F September 25, 1978 SUPERSEDING QQ-A-250E October 19, 1970 (See 6.3) FEDERAL SPECIFICATION
September 25, 1978 SUPERSEDING QQ-A-250E October 19, 1970 (See 6.3) FEDERAL SPECIFICATION ALUMINUM AND ALUMINUM ALLOY PLATE AND SHEET: GENERAL SPECIFICATION FOR This specification was approved by the commissioner,
More informationDESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7
DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7 1.1. REFERENCE STANDARDS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of this specification
More informationTECHNICAL SPECIFICATIONS
TECHNICAL SPECIFICATIONS PAGODA CABLES PVT. LTD. 1/58, STREET NO: 3, VISHWAS NAGAR, SHAHDARA, DELHI 1 32. (INDIA) TEL/FAX : 91-11-2239281, 22385391. Email : pagoda @del2.vsnl.net.in CONTENTS: 1. ABOUT
More informationSection ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR
PART 1 - GENERAL Section 26 05 15 SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR 1.1 Cable shall be 15 kv, shielded, three conductor with ground, stranded copper, with continuously welded and corrugated
More informationPTFE BELLOWS POLY FLUORO LTD. POLY FLUORO LTD.260A. Bommasandra Industrial Area, Hosur Road, Bangalore TECHNICAL SPECIFICATION
PTFE BELLOWS TECHNICAL SPECIFICATION 1. MATERIALS 1.1 PTFE Only virgin (not reprocessed) PTFE conforming to ASTM D 1457, type III, IV or V shall be used for the production of bellows; the PTFE raw material
More information600 VOLT 600V, 3 CONDUCTOR (WITH GROUND), FR-EPR OR FR-XLPE INSULATION, PVC JACKET SPECIFICATIONS (FLAME RETARDANT POWER CABLE) (UL TYPE TC-ER) TYPE C3 SPEC 70.0100 PROJECT 196116 REFERENCE: LATEST EDITIONS
More informationSPECIFICATION RW-2514 Document Number NBC MARKER SYSTEM (Ladder Form) NBC-SCE
SPECIFICATION: RW 2514 THIS ISSUE: ISSUE 2 DATE: February 2014 SPECIFICATION RW-2514 Document Number 108-121017 NBC MARKER SYSTEM (Ladder Form) NBC-SCE 1. SCOPE NBC-SCE Markers are designed for use where
More informationV. Design, Application, Maintenance & Operation Technical Requirements
V. Design, Application, Maintenance & Operation Technical Requirements V.A PJM Design & Application of Overhead Transmission Lines 69 kv & Above These design criteria have been established to assure acceptable
More informationType FLX Freezer Floor Frost Heave Protection DESIGN GUIDE
Type FLX Freezer Floor Frost Heave Protection DESIGN GUIDE Commercial Products Type FLX TM Freezer Floor Frost Heave Protection DESIGN GUIDE Contents Introduction...2 Application Information... 2-3 Product
More informationSECTION ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck)
SECTION 13125 ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck) PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
More informationPT. KABELINDO MURNI Tbk SHIPBOARD CABLE WIRE AND CABLE MANUFACTURER. No. EMS No. OSH No. QCS 00152
PT. KABELINDO MURNI Tbk WIRE AND CABLE MANUFACTURER No. QCS 00152 No. OSH 00971 No. EMS 00151 Introduction of company The Company s history was marked by the founding of PT. Kabel Indonesia (Kabelindo)
More information2. TEST RECORDS - All records of tests, inspection and calibration shall be kept in suitable forms approved by the Bureau.
SCHEME OF TESTING AND INSPECTION FOR CERTIFICATION OF HAND-OPERATED CHAIN PULLEY BLOCKS ACCORDING TO IS 3832:2005 (Third Revision) (Incorporating Amendment No. 1) DOC:STI:3832/3 1. LABORATORY A laboratory
More informationP.G student, Civil Engineering department, Saraswati College of Engineering, Maharashtra, India 1
International Journal of Scientific & Engineering Research, Volume 6, Issue 1, December-15 145 Analysis and Design of kv transmission line tower with hot rolled and cold formed section Supriya Khedkar1,
More informationDynamic Analysis of Transmission Tower
Dynamic Analysis of Transmission Tower Sk.Musthafa Department of Civil Engineering, Amara Institute of Engineering and Technology. Sk.Yusuf Basha Department of Civil Engineering, Amara Institute of Engineering
More informationThe Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999
CANADIAN ELECTRICAL CODE 1 The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999 Repealed by Chapter E-6.3 Reg 8 (effective June 24, 2003). Formerly Chapter E-6.3 Reg 6 (effective March
More informationHigh-Strength Aluminum Wires for Low-Voltage Automotive Engine Wiring Harnesses
AUTOMOTIVE High-Strength Aluminum Wires for Low-Voltage Automotive Engine Wiring Harnesses Kinji TAGUCHI*, Takanobu SHIMADA, Jun YOSHIMOTO, Tetsuya KUWABARA and Yasuhiro AKASOFU ----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
More informationBUREAU OF INDIAN STANDARDS CENTRAL MARKS DEPARTMENT-III
BUREAU OF INDIAN STANDARDS CENTRAL MARKS DEPARTMENT-III Our Ref: CMD-III/16:814 31 January 2006 Subject: Implementation of Amendment No 1 to IS 814:2004 for Covered Electrodes For Manual Metal Arc Welding
More informationSECTION CHAIN-LINK FENCES AND GATES 02821/1
SECTION 02821 - CHAIN-LINK FENCES AND GATES 02821/1 PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Chain-Link Fences: 2. Gates: horizontal slide or swing. 3. Fences installed where
More information