BUSHFIRE ATTACK LEVEL

Size: px
Start display at page:

Download "BUSHFIRE ATTACK LEVEL"

Transcription

1 BUSHFIRE ATTACK LEVEL FOR FUTURE DWELLINGS AT STAGE 1 BOUNDARY ROAD MEDOWIE Prepared by: Firebird ecosultants Pty Ltd ABN PO Box 354 Newcastle NSW 2300 Mob: Ph: Fax: sarah@firebirdeco.com.au

2 Site Details: Prepared by: Stage 1 at Boundary Road, Medowie Sarah Jones B.Env.Sc.,G.Dip.DBPA (Design in Bushfire Prone Areas) Firebird ecosultants Pty Ltd ABN PO Box 354, Newcastle NSW 2300 M: sarah@firebirdeco.com.au T: Fax: Prepared for: Reference No. Document Status & Date: McCloy Medowie Pty Ltd Medowie McCloy Draft for Client Review 14 September 2016 Disclaimer Not withstanding the precautions adopted within this report, it should always be remembered that bushfires burn under a wide range of conditions. An element of risk, no matter how small always remains, and although the standard is designed to improve the performance of such buildings, there can be no guarantee, because of the variable nature of bushfires, that any one building will withstand bushfire attack on every occasion. Bushfire Attack Levels Stage 1 at Boundary Road, Medowie i

3 Executive Summary This report provides an assessment of the Bushfire Attack Level (BAL) for Stage 1 at Boundary Road Medowie, in accordance with AS3959 (2009) Construction of Buildings in Bushfire Prone Areas Appendix A - Method 1. This report and mapping are not to be used to place wholesale restrictions on lots reflecting the resulting BAL mapping presented within. This BAL report has shown that any future dwellings within the site will be able to meet the requirements of both AS and the addendum to Appendix 3 of Planning PBP 2006 (NSW Rural Fire Service NSW). Sarah Jones Ecologist / Bushfire Planner BPAD-A Certified Practitioner (BPD-PA-26512) B.Env.Sc., G.Dip.DBPA (Design for Bushfire Prone Areas) Disclaimer: The BALs as depicted within this report and mapping have been determined by management of vegetation to the east where land will be cleared for future stages. It should be noted that conditions may change over time that may result in different BALs for the lots. Although every care has been taken in the preparation of this BAL Report, Medowie McCloys Pty Ltd and the author accept no responsibility in errors in this report or damaged resulting from the information. It should be noted that upon lodgement of a Development Application (DA) with Council or Rural Fires Service they may recommend additional construction requirements (BALs). Bushfire Attack Levels Stage 1 at Boundary Road, Medowie ii

4 Terms & Abbreviations Abbreviation APZ AS AS BAL BCA BPA BPL Map BPMs Meaning Asset Protection Zone Australian Standard Fire Hydrant Installations Australian Standard Construction of Buildings in Bush Fire Prone Areas Bushfire Attack Level Building Code of Australia Bush Fire Prone Area (Also Bushfire Prone Land) Bush Fire Prone Land Map Bush Fire Protection Measures EPA Act NSW Environmental Planning and Assessment Act 1979 FDI FMP ha IPA LGA OPA Fire Danger Index Fuel Management Plan Hectare Inner Protection Area Local Government Area Outer Protection Area PBP Planning for Bushfire Protection 2006 PSC Port Stephens Council RF Act Rural Fires Act 1997 RF Regulation Rural Fires Regulation Bushfire Attack Levels Stage 1 at Boundary Road, Medowie iii

5 CONTENTS 1 INTRODUCTION Site Particulars 1 2 METHODOLOGY Vegetation Assessment Slope Assessment 2 3 SITE ASSESSMENT Vegetation and Slope Assessment 3 4 BUSHFIRE ATTACK ASSESSMENT Bushfire Attack Assessment Determination of Bushfire Attack Levels 4 5 CONCLUSION 1 6 BIBLIOGRAPHY 2 APPENDIX A SALE PLAN A-1 APPENDIX B SUMMARY OF AS CONSTRUCTION REQUIREMENTS B-1 APPENDIX C ADDENDUM TO APPENDIX 3 OF PBP 2006 ADDITIONAL BUILDING REQUIREMENTS C-1 TABLES Table 3-1: Vegetation & Slope Assessment 3 Table 4-1: Bushfire Attack Level Assessment 4 FIGURES Figure 4-1: BAL Map 1 Bushfire Attack Levels Stage 1 at Boundary Road, Medowie iv

6 1 INTRODUCTION Firebird ecosultants Pty Ltd has been engaged by McCloy Medowie Pty Ltd to undertake a Bushfire Attack Level (BAL) report for Stage 1 at Boundary Road, Medowie (hereafter referred to as the site ). Refer to Appendix A for Sales Plan. This BAL report assess the application of Australian Standard AS Construction of Buildings on Bushfire Prone Land and Appendix 3 of Planning for Bushfire Protection 2006 (PBP, 2006). AS3959 (2009) Appendix A Method 1 and Appendix B - Detailed Method 2 has been used in this assessment. Assessment Method 2 provides for a site specific and accurate determination of the hypothetical radiant heat flux levels a bushfire could be expected to generate under certain environmental conditions. Assessment Method 2 is an approved methodology for bushfire risk assessment as per AS This report has been prepared to provide guidance to prospective purchasers of what Bushfire Attack Levels (BALs) may be required for future dwellings within the site. Site Particulars Locality: Stage 1 at Boundary Road, Medowie LGA: Forest Danger Index: Current Land Use: Port Stephens 100 Approved residential subdivision Bushfire Attack Levels Stage 1 at Boundary Road, Medowie Page 1

7 2 METHODOLOGY The Australian Standard for assessing the BAL and providing the detailed requirements for construction has been reviewed and amended with the latest version being adopted for use in bushfire prone areas of NSW in May This version is titled AS Construction of Buildings in Bushfire Prone Areas (standards Australia 2009, incorporating amendment 1 (November 2009) and amendment 2 (February 2011), with amendment 2 being used in this assessment. In addition, the NSW method of determining the bushfire attack level, found in Appendix 3 of the document Planning for Bushfire Protection 2006 (NSW Rural Fire Service 2006), has also been reviewed and amended to come into line with the process within AS Therefore, in NSW the methodology in AS 3959 is to be used to determine the bushfire attack level. AS3959 (2009) Appendix A Method 1 has been used in this BAL assessment. 2.1 Vegetation Assessment Vegetation surveys and vegetation mapping carried out on the site has been undertaken as follows: Aerial Photograph Interpretation to map vegetation cover and extent. Confirmation of the vegetation assemblage typology present via a site inspection. 2.2 Slope Assessment Slope assessment has been undertaken as follows: Aerial Photograph Interpretation in conjunction with analysis of electronic contour maps with a contour interval of 10m. On site confirmation of slope measurements. Bushfire Attack Levels Stage 1 at Boundary Road, Medowie Page 2

8 3 SITE ASSESSMENT A site inspection was undertaken on the site. The following assessment has been undertaken in accordance with the requirements of PBP (RFS, 2006) and AS Vegetation and Slope Assessment An assessment of the slope affecting the bushfire behaviour was undertaken for a distance of 100m from the edge of the lot boundaries, in the direction of the bushfire hazard. The slopes leading away from the site have been evaluated to identify both the average slope and by identifying the maximum slope present. These values help determine the level of gradient which will most significantly influence the fire behaviour of the site. Refer to Table 1 for Vegetation and Slope Assessment. Table 3-1: Vegetation & Slope Assessment Direction from Site North East South Vegetation Classification Managed Land as an IPA until such time that development occurs. Managed Land as an IPA until such time that development occurs. Open Forest and Managed Land associated with existing residential development. Effective Slope 0 degrees 0 degrees 0 degrees West Open Forest 0 degrees Bushfire Attack Levels Stage 1 at Boundary Road, Medowie Page 3

9 4 BUSHFIRE ATTACK ASSESSMENT 4.1 Bushfire Attack Assessment To determine the bush fire attack and required Bushfire Attack Level (BAL) for the proposed subdivision the following steps were followed: 1. Determination of the vegetation types within 100m of the site, as assessed in section 3 of this report. 2. Determination of the distance between the vegetation and future dwellings has been assessed in section 4.2 of this report. 3. Determination of the effective slope as assessed in section 3 of this report. 4. A FDI of 100 was determined for Port Stephens LGA. 4.2 Determination of Bushfire Attack Levels The results from the above steps were used to calculate the required BAL in accordance with Method 1 of AS The results from this bush fire attack assessment are detailed below in Table 4-1 Bushfire Attack Level Assessment and Figure 4-1 Bushfire Attack Level Map. Table 4-1: Bushfire Attack Level Assessment Vegetation Type within 100m & Direction from future dwellings Average Slope of Land (degrees) Separation Distance from Identified Vegetation Bushfire Attack Level (BAL) Construction Section 25-<35m BAL-29 Sect 3 & 7 of AS3959 and Sect A3.7 of PBP Addendum Appendix 3 Open Forest 0 degrees 35-<48m BAL-19 Sect 3 & 6 of AS3959 and Sect A3.7 of PBP Addendum Appendix 3 48-<100m BAL-12.5 Sect 3 & 5 of AS3959 and Sect A3.7 of PBP Addendum Appendix 3 Bushfire Attack Levels Stage 1 at Boundary Road, Medowie Page 4

10 Vegetation Type within 100m & Direction from future dwellings Average Slope of Land (degrees) Separation Distance from Identified Vegetation Bushfire Attack Level (BAL) Construction Section >100m BAL-LOW No requirement *To Note: The construction requirements for the next lower BAL than that determined for the site may be applied to an elevation of the building where the elevation is not exposed to the source of the bushfire attack. An elevation is deemed to be not exposed to the source of bushfire attack if all the straight lines between that elevation and the source of bushfire attack are obstructed by another part of the building. However, this does not apply to BAL-12. No BALs applies to any future dwelling built greater than 100m from vegetation determined as a bushfire hazard. This report and mapping are not to be used to place wholesale restrictions on lots reflecting the resulting BAL mapping presented within. Building location and design will influence the application of the required BALs. For example, a lot indicated as being affected by BAL-29 may have those facades that are not exposed to the bushfire threat constructed to a lower BAL (i.e. BAL-19), reducing the costs of construction and providing more flexibility in choice of external building materials. Refer to Appendix B for Summary of AS Construction Standards and Appendix C for Additional Building Requirements. Bushfire Attack Levels Stage 1 at Boundary Road, Medowie Page 5

11 Figure 4-1: BAL Map Bushfire Attack Levels Stage 1 at Boundary Road, Medowie Page 1

12 ME E WI DO A RO STAGE D BOU NDA RY 52m ROA 13m 5m D Note: Boundaries are not survey accurate. Although all reasonable care has been taken to ensure the information shown on this map is up to date and accurate, no guarantee is given that the information portrayed is free from error or omission. Please verify the accuracy of all information prior to use. FIGURE 1-1:BUSHFIRE ATTACK LEVELS MAP CLIENT SITE DETAILS DATE McCloy Group Pty Ltd Stage 1 Boundary Road Medowie 15 September 2016 Ref No 1836 C Legend Subject Site 100m Buffer 10m APZ 50m Temporary APZ Open Forest Managed Land BAL 29 BAL 19 BAL 12.5 DISCLAIMER 0 SCALE A This docment and the information shown shall remain the property of Firebird ecosultants Pty Ltd. The document may only be used for the purpose for which it was supplied and in accordance with the terms of engagement for the commission. Unauthorised use of this document in any way is prohibited

13 5 CONCLUSION This report provides an assessment of the Bushfire Attack Level (BAL) in accordance with AS Construction of Buildings in Bushfire Prone Areas for Stage 1 at Boundary Road Medowie. This BAL report assesses the application of Australian Standard AS Construction of Buildings in Bushfire Prone Land and Appendix 3 of Planning for Bushfire Protection 2006 (PBP, 2006). This report and mapping are not to be used to place wholesale restrictions on lots reflecting the resulting BAL mapping presented within. Future development of surrounding stages may result in lower BALs than detailed in this report. This BAL report has shown that any future dwellings within the site will be able to meet the requirements of both AS and the addendum to Appendix 3 of Planning PBP 2006 (NSW Rural Fire Service NSW). Sarah Jones Ecologist / Bushfire Planner FPA BPAD-A Certified Practitioner (BPD-PA-26512) B.Env.Sc. G.Dip.DBPA (Design for Bushfire Prone Areas) Disclaimer: The BALs as depicted within this report and mapping have been determined by vegetation within 100m of Stage 1, at the time of the assessment July It should be noted that conditions may change over time that may result in different BALs for the lots. Bushfire Attack Levels Stage 1 at Boundary Road, Medowie Page 1

14 6 BIBLIOGRAPHY NSW Rural Fire Service (RFS) Planning for Bushfire Protection: A guide for Councils, Planners, Fire Authorities, Developers and Home Owners. Australian Government Publishing Service, Canberra. Standards Australia Construction of buildings in bushfire-prone Ares, AS3959, Third Edition 2009, Incorporating Amendment 1, Standards Australia International Ltd Sydney Bushfire Attack Levels Stage 1 at Boundary Road, Medowie Page 2

15 APPENDIX A SALE PLAN Bushfire Attack Levels Stage 1 at Boundary Road, Medowie Page A-1

16

17 APPENDIX B SUMMARY OF AS CONSTRUCTION REQUIREMENTS Bushfire Attack Levels Stage 1 at Boundary Road, Medowie Page B-1

18 TABLE F.8.2 CONSTRUCTION REQUIREMENTS FOR BAL LOW, BAL 12.5, BAL 19, BAL 29, BAL 40 and BAL FZ SITES FLOORING SYSTEMS 1. BAL Low A flooring system must comply with one or a combination of the following: (a) A concrete slab-on-ground. (b) A suspended concrete floor. (c) A framed floor where, if the underside is greater than 600mm above finished ground or paving level, the sub-floor space is enclosed with (i) a non-combustible sheet material. If fibre-cement sheets are used for this purpose, the sheets must have a minimum thickness of 6mm; or (ii) a wall that extends around the perimeter of the floor from the underside of the lowest framing member to finished ground or paving level and is constructed of one or a combination of the following: (aa) a non-combustible material, such as full masonry, brick veneer, mud brick, concrete or aerated concrete. (bb) a timber or steel-framed wall that is sarked on the outside of the frame with sarking-type-material having a flammability index of not more than 5, and clad with (A) fibre-cement external sheeting with a minimum thickness of 6mm; or (B) steel sheet; or (C) bushfire-resisting-timber; or (D) a combination of (A), (B) or (C). (cc) a combination of (aa) and (bb). (iii) a vertical non-combustible sheet material that extends around the perimeter of the floor from the underside of the lowest framing member to finished ground or paving level. If fibre-cement sheets are used for this purpose, the sheets must have a minimum thickness of 6mm. (d) a framed floor where, if any joist and/or bearer is less than 600mm above finished ground or paving level, the subfloor space is (i) if unenclosed, constructed from flooring material, including bearers, joists and flooring that is (A) non-combustible; or (B) bushfire-resisting-timber; or (C) particleboard or plywood flooring where the underside is lined with sarking-type-material or mineral wool insulation; or (D) a system complying with AS ; or (E) a combination of (A), (B), (C) or (D). (ii) enclosed with a wall complying with (c)(ii). (iii) enclosed with a mesh or perforated sheet made from corrosion-resistant steel, bronze or aluminium with a maximum aperture size of 2mm. (iv) enclosed with non-combustible sheet material that extends not less than 400mm above finished ground or paving level and to the bottom of the wall sheeting material. If fibre reinforced cement sheets are used for this purpose, the sheets must have a minimum thickness of 6mm. Refer Figure F A flooring system complying with (c) or (d) must have all joints in the external surface of walls covered, sealed, overlapped, backed or butt-jointed to prevent gaps greater than 3mm. Alternatively, sarking-type-material can be applied over the frame prior to fixing any external sheeting. 2. BAL As per the BAL Low requirements of this table 3. BAL 19 As per the BAL Low requirements of this table 4. BAL 29 As per the BAL Low requirements of this table 5. BAL 40 As per the BAL Low requirements of this table with the following variation A framed floor where the sub-floor space is unenclosed, must be constructed from flooring materials, including bearers, joists and flooring that are (i) non-combustible; or (ii) have the underside of the combustible elements of the floor system protected with a non-combustible material; or (iii) a system complying with AS ; or (iv) a combination of (i), (ii) or (iii). 17 of 40

19 6. BAL FZ As per the BAL Low requirements of this table with the following variation A framed floor where the sub-floor space is unenclosed, must be constructed from flooring materials, including bearers, joists and flooring that (i) have an FRL of at least 30/30/30 and the surface material must be non-combustible; or (ii) have the underside of the combustible elements of the floor system protected with a 30 minute resistance to the incipient spread of fire; or (iii) comply with AS when tested from the underside; or (iv) a combination of (i), (ii) or (iii). SUPPORTING POSTS, COLUMNS, STUMPS, PIERS AND POLES 1. BAL Low Supporting posts, columns, stumps, piers and poles must comply with one or a combination of the following: (a) A non-combustible material. (b) A bushfire-resisting-timber for not less than 400mm above finished ground or paving level. (c) Timber mounted on metal stirrups with a clearance of not less than 75mm above finished ground or paving level. Refer Figure F BAL 12.5 As per the BAL Low requirements of this table 3. BAL 19 As per the BAL Low requirements of this table 4. BAL 29 Supporting posts, columns, stumps, piers and poles must comply with one or a combination of the following: A non-combustible material; or Bushfire-resisting-timber. 5. BAL 40 Supporting posts, columns, stumps, piers and poles must comply with one or a combination of the following: (a) A non-combustible material; or (b) A system complying with AS BAL FZ Supporting posts, columns, stumps, piers and poles must comply with one or a combination of the following: (a) Have an FRL of at least 30/-/- and must be non-combustible; or (b) A system complying with AS EXTERNAL WALLS 1. BAL Low No requirements 2. BAL External walls must comply with one or a combination of the following: (a) A non-combustible material such as full masonry, brick veneer, mud brick, concrete or aerated concrete. (b) A timber or steel-framed wall that (i) is sarked on the outside of the frame with sarking-type-material having a flammability index of not more than 5; and (ii) clad within 400mm of finished ground or paving level, or any balcony or deck with solid flooring with (A) non-combustible material; or (B) steel sheet; or (C) fibre-cement external sheeting with a minimum thickness of 6mm; or (D) bushfire-resisting-timber; or (E) a combination of (A), (B), (C) or (D). All joints in the external surface of walls must be covered, sealed, overlapped, backed or butt-jointed to prevent gaps greater than 3mm. Alternatively, sarking-type-material can be applied over the frame prior to fixing any external sheeting. 3. BAL- 19 As per the BAL 12.5 requirements of this table 4. BAL- 29 As per the BAL 12.5 requirements of this table with the following variation (a) All external cladding (less than and greater than 400mm above finished ground or paving level) must comply with (b) (ii)(a), (B), (C), (D) or (E) of the BAL 12.5 requirements. 18 of 40

20 5. BAL- 40 As per the BAL 12.5 requirements of this table with the following variation (a) All external cladding for timber or steel-framed walls (less than and greater than 400mm above finished ground or paving level) must be - (i) fibre-cement sheeting with a minimum thickness of 9mm; or (ii) steel sheet; or (iii) a combination of (i) and (ii). 6. BAL FZ External walls must be one or a combination of the following: (a) A non-combustible material such as full masonry, brick veneer, mud brick, concrete or aerated concrete with a minimum thickness of 90mm. (b) A system complying with AS when tested from the outside. (c) A system with an FRL of 30/30/30 or -/30/30 when tested from the outside. WINDOWS 1. BAL Low No requirements 2. BAL Window assemblies, and shutters and screens, must comply with one or a combination of the following: (a) Window assemblies must be completely protected by a bushfire shutter that complies with F.8.2(g) and is made from - (i) a non-combustible material; or (ii) bushfire-resisting-timber; or (iii) a combination of (i) and (ii). (b) Window assemblies must be completely protected externally by screens complying with F.8.2(h). (c) Window assemblies must comply with the following (i) For window assemblies less than 400mm from the ground or less than 400mm above decks, carport roofs, awnings and similar elements or fittings having an angle less than 18 degrees to the horizontal and extending more than 110mm in width from the window frame, window frames and window joinery must be one of the following: (A) bushfire-resisting-timber; or (B) metal; or (C) metal-reinforced PVC-U. The reinforcing members must be made from aluminium, stainless steel or corrosion-resistant steel and the frame and sash must satisfy the design load, performance and structural strength of the member. (ii) Externally fitted hardware that supports the sash in its functions of opening and closing must be metal. (iii) Where glazing is less than 400mm from the ground or less than 400mm above decks, carport roofs, awnings and similar elements or fittings having an angle less than 18 degrees to the horizontal and extending more than 110mm in width from the window frame, the glazing must be Grade A safety glazing with a minimum thickness of 4mm or glass blocks with no restriction on glazing methods. Note: Where double glazing is used, the above requirements apply to the external face of the window assembly only. (iv) Where glazing is other than that specified in (iii) above, annealed glass may be used. (v) The openable portions of windows must be screened internally or externally with screens that comply with F.8.2(h). 3. BAL- 19 As per the BAL 12.5 requirements of this table with the following variations (a) Where glazing is less than 400mm from the ground or less than 400mm above decks, carport roofs, awnings and similar elements or fittings having an angle less than 18 degrees to the horizontal and extending more than 110mm in width from the window frame, the glazing must be toughened glass with a minimum thickness of 5mm, or glass blocks with no restriction on glazing methods. Note: Where double glazing is used, the above requirements apply to the external face of the window assembly only. (b) Where glazing is other than that specified in (iii) above, annealed glass may be used. Where annealed glass is used, the fixed and openable portions of windows must be screened externally with screens that comply with the F.8.2(h), with the exception that aluminium mesh must not be used in the window screens. (c) Where leadlight windows are installed, they must be protected with non-combustible shutters or toughened glass. (d) Where toughened glass is used, it must have a minimum thickness of 5mm and the openable portions of the windows must be screened internally or externally with screens that comply with the F.8.2(h). (e) Glazed elements that are designed to take internal screens must use toughened glass with a minimum thickness of 5mm and the openable portion must be screened with screens that comply with the F.8.2(h). 19 of 40

21 4. BAL- 29 Window assemblies, and shutters and screens, must comply with one or a combination of the following: (a) Window assemblies must be completely protected by a bushfire shutter that complies with F.8.2(g) and is made from - (i) a non-combustible material; or (ii) bushfire-resisting-timber; or (iii) a combination of (i) and (ii). (b) Window assemblies must comply with the following: (i) Window frames and window joinery must be made from one of the following: (A) bushfire-resisting-timber; or (B) metal; or (C) metal-reinforced PVC-U. The reinforcing members must be made from aluminium, stainless steel or corrosion-resistant steel and the frame and sash must satisfy the design load, performance and structural strength of the member. (ii) Externally fitted hardware that supports the sash in its functions of opening and closing must be metal. (iii) Glazing must be toughened glass with a minimum thickness of 5mm. (iv) The openable portion of windows must be screened internally or externally with screens that comply with F.8.2(h), with the exception that aluminium mesh must not be used in the window screens. 5. BAL- 40 Window assemblies, and shutters and screens, must comply with one or a combination of the following: (a) Window assemblies must be completely protected by a bushfire shutter that complies with F.8.2(g) and is made from a non-combustible material. (b) Window assemblies must comply with the following: (i) Window frames and hardware must be metal; and (ii) Glazing must be toughened glass with a minimum thickness of 6mm; and (iii) Both the openable and the fixed portions of the window must be screened externally with screens that comply with F.8.2(h), with the exception that aluminium mesh must not be used in the window screens and the frame supporting the mesh or perforated sheet must be metal (iv) Seals to stiles, heads and sills or thresholds must be manufactured from materials having a flammability index of not more than 5 or from silicone. 6. BAL FZ Window assemblies, and shutters and screens, must comply with one or a combination of the following: (a) Window assemblies must be completely protected by a bushfire shutter that complies with F.8.2(g), with the exception that perforations are not acceptable over the door system, and AS when tested from the outside. (b) The openable portion of the window must be screened internally or externally with screens that comply with F.8.2(i), with the exception that aluminium mesh must not be used in the window screens and the frame supporting the mesh or perforated sheet must be metal, and either (i) the window system must have an FRL of at least -/30/-; or (ii) the window system must comply with AS when tested from the outside. EXTERNAL DOORS (including side-hung external doors such as French doors, panel fold and bi-fold doors, sliding doors and garage doors) 1. BAL Low No requirements 20 of 40

22 2. BAL SIDE HUNG DOORS Side-hung external doors must comply with one or a combination of the following: (a) They must be completely protected by a bushfire shutter that complies with F.8.2(g) and is made from - (i) non-combustible material; or (ii) bushfire-resisting-timber; or (iii) a combination of (i) and (ii). (b) They must be completely protected externally by screens complying with F.8.2(h). (c) They must comply with the following (i) Doors must be - (A) non-combustible; or (B) a solid timber door with a minimum thickness of 35mm for the first 400mm above the threshold; or (C) a door, including a hollow core door, with a non-combustible kick-plate on the outside for the first 400mm above the threshold; or (D) a fully framed glazed door, where the framing is made from materials required for bushfire shutters. (ii) Where doors incorporate glazing, the glazing must comply with the glazing requirements for windows. (iii) Doors must be tight-fitting to the door frame and to an abutting door, if applicable. (iv) Where any part of the door frame is less than 400mm from the ground or less than 400mm above decks, carport roofs, awnings and similar elements or fittings having an angle less than 18 degrees to the horizontal and extending more than 110mm in width from the door, that part of the door frame must be made from one of the following: (A) bushfire-resisting-timber; or (B) metal; or (C) metal-reinforced PVC-U. The reinforcing members must be made from aluminium, stainless steel or corrosion-resistant steel and the frame and sash must satisfy the design load, performance and structural strength of the member. (v) Weather strips, draught excluders or draught seals must be installed at the base of side-hung external doors. SLIDING DOORS Sliding doors must comply with one or a combination of the following: (a) They must be completely protected by a bushfire shutter that complies with F.8.2(g) and is made from - (i) non-combustible material; or (ii) bushfire-resisting-timber; or (iii) a combination of (i) and (ii). (b) They must be completely protected externally by screens complying with F.8.2(h). (c) They must comply with the following (i) Any glazing incorporated in sliding doors must be Grade A safety glass complying with AS (ii) Both the door frame supporting the sliding door and the framing surrounding any glazing must be (A) bushfire-resisting-timber; or (B) metal; or (C) metal-reinforced PVC-U. The reinforcing members must be made from aluminium, stainless steel or corrosion-resistant steel and the frame and sash must satisfy the design load, performance and structural strength of the member. (iii) If the openable part of the sliding door is screened, the screens must comply with F.8.2(h). (iv) Sliding doors must be tight-fitting in the frames. VEHICLE ACCESS DOORS Vehicle access doors must comply with the following: (a) The portion of the vehicle access door that is within 400mm of the finished ground or paving when the door is closed must be made from - (i) non-combustible material; or (ii) bushfire-resisting-timber; or (iii) fibre-cement sheet with a minimum thickness of 6mm; or (iv) a combination of (i), (ii) or (iii). (b) Panel lift, tilt doors or side-hung doors must be fitted with suitable weather strips, draught excluders, draught seals or guide tracks, as appropriate to the door type, with a maximum gap no greater than 3mm. (c) Roller doors must have guide tracks with a maximum gap no greater than 3mm and must be fitted with a nylon brush that is in contact with the door. (d) Vehicle access doors must not include ventilation slots. 21 of 40

23 3. BAL 19 SIDE HUNG DOORS As per the BAL 12.5 requirements of this table with the following variations (a) Aluminium mesh must not be used in the door screens. (b) Where the doors incorporate glazing, the glazing must be toughened glass with a minimum thickness of 5mm. SLIDING DOORS As per the BAL 12.5 requirements of this table with the following variations (a) Aluminium mesh must not be used in the door screens. (b) Any glazing incorporated in sliding doors must be toughened glass with a minimum thickness of 5mm. VEHICLE ACCESS DOORS Vehicle access doors must comply with the BAL 12.5 requirements of this table. 4. BAL 29 SIDE HUNG DOORS Side-hung external doors must comply with one or a combination of the following: (a) They must be completely protected by a bushfire shutter that complies with F.8.2(g) and is non-combustible. (b) They must be completely protected externally by screens complying with F.8.2(h), with the exception that aluminium mesh must not be used in the door screens. (c) They must comply with the following (i) Doors must be - (A) non-combustible; or (B) a solid-core door with a minimum thickness of 35mm (ii) Externally fitted hardware that supports the panel in its functions of opening and closing must be metal. (iii) Where doors incorporate glazing, the glazing must be toughened glass with a minimum thickness of 6mm. (iv) Door frames must be made from one of the following: (A) bushfire-resisting-timber; or (B) metal; or (C) metal-reinforced PVC-U. The reinforcing members must be made from aluminium, stainless steel or corrosion-resistant steel and the frame and sash must satisfy the design load, performance and structural strength of the member. (v) Doors must be tight-fitting to the door frame and to an abutting door, if applicable. (vi) Weather strips, draught excluders or draught seals must be installed at the base of side-hung external doors. SLIDING DOORS Sliding doors must comply with one or a combination of the following: (a) They must be completely protected by a bushfire shutter that complies with F.8.2(g) and is made from noncombustible material. (b) They must be completely protected externally by screens complying with F.8.2(h), with the exception that aluminium mesh must not be used in the door screens. (c) They must comply with the following: (i) Both the door frame supporting the sliding door and the framing surrounding any glazing must be (A) bushfire-resisting-timber; or (B) metal; or (C) metal-reinforced PVC-U. The reinforcing members must be made from aluminium, stainless steel or corrosion-resistant steel and the frame and sash must satisfy the design load, performance and structural strength of the member. (ii) Externally fitted hardware that supports the panel in its functions of opening and closing must be metal. (iii) Where doors incorporate glazing, the glazing must be toughened glass with a minimum thickness of 6mm, except where both the fixed and openable portions of doors are screened externally with screens that comply with F.8.2(h), with the exception that aluminium mesh must not be used in the door screens. (iv) Sliding doors must be tight-fitting in the frames. VEHICLE ACCESS DOORS Vehicle access doors must comply with the BAL 12.5 requirements of this table. 22 of 40

24 5. BAL 40 SIDE HUNG DOORS Side hung doors must comply with one or a combination of the following: (a) They must be protected by a shutter that complies with F.8.2(g) and is non-combustible. (b) They must comply with the following: (i) Doors must be (A) non-combustible; or (B) a solid-core door with a minimum thickness of 35mm. (ii) Externally fitted hardware that supports the panel in its functions of opening and closing must be made of materials that have an FRL of at least -/30/-. (iii) Where doors incorporate glazing, the glazing must be toughened glass with a minimum thickness of 6mm and both the fixed and openable portions of doors must be screened externally with screens that comply with F.8.2(h), with the exception that aluminium mesh must not be used in the door screens. (iv) Seals to stiles, heads and sills or threshold must be manufactured from materials with a flammability index no greater than 5 or from silicone. (v) Door frames must be metal. (vi) Doors must be tight-fitting to the door frame and to an abutting door, if applicable. (vii) Weather strips, draught excluders or draught seals must be installed at the base of side-hung external doors. SLIDING DOORS Sliding doors must be one or a combination of the following: (a) They must be protected by a shutter that complies with F.8.2(g) and is non-combustible. (b) They must comply with the following: (i) Both the door frame supporting the sliding door and the framing surrounding any glazing must be metal. (ii) Externally fitted hardware that supports the panel in its functions of opening and closing must be metal. (iii) Where sliding doors incorporate glazing, the glazing must be toughened glass with a minimum thickness of 6mm and both the fixed and openable portions of doors must be screened externally with screens that comply with F.8.2(h), with the exception that aluminium mesh must not be used in the door screens. (iv) Seals to stiles, heads and sills or threshold must be manufactured from materials with a flammability index no greater than 5 or from silicone. (v) Sliding doors must be tight-fitting in the frames. VEHICLE ACCESS DOORS Vehicle access doors must comply with the BAL 12.5 requirements of this table with the following variation: (a) They must be non-combustible. 6. BAL- FZ SIDE HUNG DOORS Side hung doors must comply with one or a combination of the following: (a) They must be protected by a shutter that complies with F.8.2(g) with the exception that perforations are not acceptable over the door system, and AS when tested from the outside. (b) They must comply with the following: (i) All door systems, including door frames and doors with glazed panels, must (A) have an FRL of at least -/30/-; or (B) comply with AS when tested from the outside. (ii) Doors must be tight-fitting to the door frame and to an abutting door, if applicable. (iii) Weather strips, draught excluders or draught seals must be installed at the base of side-hung external doors. (iv) Seals must not compromise the FRL or the performance achieved in AS SLIDING DOORS Sliding doors must comply with one or a combination of the following: (a) They must be protected by a shutter that complies with F.8.2(g) with the exception that perforations are not acceptable over the door system, and AS when tested from the outside. (b) They must comply with the following: (i) All sliding door systems, including those with glazed panels must (A) have an FRL of at least -/30/-; or (B) comply with AS when tested from the outside. (ii) Sliding doors must be tight-fitting in the frames. VEHICLE ACCESS DOORS Vehicle access doors must comply with the BAL 40 requirements of this table with the following variation - (a) Where the garage is attached to the building, the requirements of F.8.2(b)(ii) must apply. 23 of 40

25 VENTS AND WEEPHOLES (including vents and weepholes located in external walls and sub-floor spaces) 1. BAL- Low Vents to sub-floor spaces and weepholes must be fitted with ember guards made from corrosion-resistant steel, bronze or aluminium mesh or perforated sheet with a maximum aperture size of 2mm. 2. BAL 12.5 As per the BAL Low requirements of this table 3. BAL 19 As per the BAL 12.5 requirements of this table with the following variation (a) Aluminium mesh or perforated sheet must not be used for the ember guards. 4. BAL 29 As per the BAL 19 requirements of this table 5. BAL 40 As per the BAL 19 requirements of this table 6. BAL FZ As per the BAL 19 requirements of this table ROOFS (including verandahs and attached carport roofs, eaves linings, fascias, gables) 1. BAL Low No requirements 2. BAL Roofs must comply with one or a combination of the following: (a) Roof tiles, roof sheets and roof-covering accessories must be non-combustible. (b) The roof/wall junction must be sealed to prevent openings greater than 3mm, either by the use of fascia and eaves linings or by sealing between the top of the wall and the underside of the roof and between the rafters at the line of the wall. Refer Figure F (c) Roof ventilation openings, such as gable and roof vents, must be fitted with ember guards made from corrosionresistant steel or bronze mesh or perforated sheet with a maximum aperture of 2mm. (d) Tiled roofs must be (i) fully sarked over the entire roof area, including the ridge. The sarking-type-material must have a flammability index of not more than 5; and (ii) located directly below the roof battens; and (iii) cover the entire roof area including the ridge; and (iii) installed so that there are no gaps that will allow entry of embers where the sarking-type-material meets fascias, gutters, valleys and the like. (e) Sheets roofs (metal or fibre-cement sheet) must be (i) fully sarked in accordance with (d)(i); or (ii) have any gaps greater than 3mm, under corrugations or ribs of sheet roofing and between roof components, sealed at the fascia or wall line and at valleys, hips and ridges by (A) corrosion-resistant steel or bronze mesh or perforated sheet with a maximum aperture of 2mm; or (B) mineral wool; or (C) other non-combustible material; or (D) a combination of (A), (B) or (C). (f) A verandah, carport or awning roof (i) forming part of the main roof space, must meet all the requirements of the main roof. (ii) separated from the main roof space by an external wall complying with the BAL 12.5 requirements of this table, must have a non-combustible roof covering. (g) Gables must comply with the BAL 12.5 requirements of this table for external walls. (h) Eaves penetrations must be protected in accordance with the BAL 12.5 requirements of this table for roof penetrations. (i) Eaves ventilation openings greater than 3mm must be fitted with ember guards made from non-combustible material or corrosion-resistant steel or bronze mesh or perforated sheet with a maximum aperture of 2mm. (j) Joints in eaves linings, fascias and gables may be sealed with plastic joining strips or timber storm moulds. 24 of 40

26 3. BAL 19 As per the BAL 12.5 requirements of this table with the following variations (a) Sheet roofs (metal or fibre-cement sheet) must be fully sarked in accordance with (d)(i). (b) A verandah, carport or awning roof (i) forming part of the main roof space, must meet all the requirements of the main roof. (ii) separated from the main roof space by an external wall complying with the BAL 19 requirements of this table, must have a non-combustible roof covering. (c) Gables must comply with the BAL 19 requirements of this table for external walls. (d) Eaves penetrations must be protected in accordance with the BAL 19 requirements of this table for roof penetrations. (e) Eaves linings must be (i) fibre-cement sheet, with a minimum thickness of 4.5mm; or (ii) bushfire-resisting-timber; or (iii) a combination of (i) and (ii). (f) Joining strips in eaves linings, fascias and gables strips must be of bushfire-resisting-timber. (g) Fascias and bargeboards must be (i) non-combustible or; (ii) bushfire-resisting timber; or (iii) a combination of (i) and (ii). 4. BAL 29 As per the BAL 19 requirements of this table with the following variations (a) A pipe or conduit that penetrates the roof covering must be non-combustible. (b) Sarking-type-material installed in tiled roofs must extend into gutters and valleys. (c) A verandah, carport or awning roof (i) forming part of the main roof space, must meet all the requirements of the main roof. (ii) separated from the main roof space by an external wall complying with the BAL 29 requirements of this table, must have a non-combustible roof covering and the support structure must be (A) non-combustible material; or (B) bushfire-resisting-timber; or (C) timber rafters lined on the underside with fibre-cement sheeting with a minimum thickness of 6mm, or with material complying with AS ; or (D) a combination of (A), (B) or (C). (d) Gables must comply with the BAL 29 requirements of this table for external walls. (e) Eaves penetrations must be protected in accordance with the BAL 29 requirements of this table for roof penetrations. (f) Fibre-reinforced cement or aluminium must not be used for roof sheeting or fascias. (g) Aluminium must not be used for eaves linings. 5. BAL 40 As per the BAL 29 requirements of this table with the following variations (a) A verandah, carport or awning roof (i) forming part of the main roof space, must meet all the requirements of the main roof. (ii) separated from the main roof space by an external wall complying with the BAL 40 requirements of this table, must have a non-combustible roof covering and the support structure must be (A) non-combustible material; or (B) timber rafters lined on the underside with fibre-cement sheeting with a minimum thickness of 6mm, or with material complying with AS ; or (C) a system complying with AS ; or (D) a combination of (A), (B) or (C). (b) Gables must comply with the BAL 40 requirements of this table for external walls. (c) Fascias and bargeboards must comply with AS (d) Eaves penetrations must be protected in accordance with the BAL 40 requirements of this table for roof penetrations. (e) Eaves linings must be (i) fibre-cement sheet with a minimum 6mm thickness; or (ii) calcium silicate sheet with a minimum 6mm thickness; or (iii) a combination of (i) and (ii). Note: Roof-mounted evaporative coolers are excluded from the BAL 40 level. 25 of 40

27 6. BAL FZ As per the BAL 40 requirements of this table with the following variations - (a) The roof or roofing system must comply with AS when tested from the outside. (b) A pipe or conduit that penetrates the roof covering must be metal, excluding aluminium. (c) A verandah, carport or awning roof (i) forming part of the main roof space, must meet all the requirements of the main roof. (ii) separated from the main roof space by an external wall complying with the BAL FZ requirements of this table, must have a non-combustible roof covering and the support structure must be (A) non-combustible material; or (B) timber rafters lined on the underside with fibre-cement sheeting with a minimum thickness of 6mm, or with material complying with AS ; or (C) a system complying with AS ; or (D) a combination of (A), (B) or (C). (d) Gables must comply with the BAL FZ requirements of this table for external walls. (e) Fascias and bargeboards must comply with AS (f) Eaves penetrations must be protected in accordance with the BAL FZ requirements of this table for roof penetrations. (g) Eaves linings must be (i) a system with an FRL of -/30/30; or (ii) a system complying with AS ; or (iii) a combination of (i) and (ii). Note: Roof-mounted evaporative coolers are excluded from the BAL FZ level. ROOF LIGHTS (including vented roof lights and skylights) 1. BAL Low No requirements 2. BAL 12.5 (a) Roof lights and associated shafts through the roof space must be sealed (i) with a non-combustible sleeve or lining; and (ii) at the roof penetration with non-combustible material to prevent gaps greater than 3mm. (b) Openings in vented roof lights must be fitted with ember guards made from corrosion-resistant steel or bronze mesh or perforated sheet with a maximum aperture of 2mm (c) All overhead glazing must be Grade A safety glazing complying with AS (d) Glazed elements in roof lights and skylights may be of polymer provided a Grade A safety glass diffuser, complying with AS 1288, is installed under the glazing. Where glazing is an insulating glazing unit (IGU), a minimum 4mm Grade A toughened safety glass, must be used in the outer pane of the IGU. (e) Flashing elements of tubular skylights may be of fire-retardant material, provided the roof integrity is maintained byan under-flashing of a material having a flammability index not more than BAL 19 As per the BAL 12.5 requirements of this table 4. BAL 29 As per the BAL 12.5 requirements of this table with the following variation (a) Where roof lights are installed in roofs having a pitch of less than 18 degrees to the horizontal, the glazing must be protected with ember guards made from corrosion-resistant steel or bronze mesh or perforated sheet with a maximum aperture of 2mm. 5. BAL 40 (vented roof lights not permitted) As per the BAL 29 requirements of this table with the following variation (a) glazed assemblies for roof lights and skylights must have an FRL of -/30/-. 6. BAL FZ As per the BAL 40 requirements of this table with the following variations- (a) Roof lights and associated shafts must be sealed at the roof penetration with mineral fibre to prevent gaps greater than 3mm. (b) Roof lights must be one of the following - (i) a system complying with AS when tested from the outside; or (ii) a system with an FRL of 30/30/30 or -/30/30 when tested from the outside. 26 of 40

28 ROOF-MOUNTED EVAPORATIVE COOLING UNITS 1. BAL Low No requirements 2. BAL Evaporative coolers must be (a) sealed at the roof penetration with non-combustible material to prevent gaps greater than 3mm; and (b) fitted with (i) butterfly closers at or near the ceiling level; or (ii) non-combustible covers made from corrosion-resistant steel or bronze mesh or perforated sheet with a maximum aperture of 2mm. 3. BAL 19 As per the BAL 12.5 requirements of this table 4. BAL 29 As per the BAL 12.5 requirements of this table 5. BAL 40 Evaporative coolers must not be used installed in BAL BAL FZ Evaporative coolers must not be used installed in BAL FZ OTHER ROOF PENETRATIONS (including roof ventilators, aerials, vent pipes and supports for solar collectors) 1. BAL Low No requirements 2. BAL (a) All components of roof ventilators (including rotary ventilators), aerials, vent pipes and supports for solar collectors must be (i) of non-combustible material; and (ii) be sealed at the roof penetration with non-combustible material to prevent gaps greater than 3mm. (b) Openings in roof ventilators and vent pipes must be fitted with ember guards made from corrosion-resistant steel or bronze mesh or perforated sheet with a maximum aperture of 2mm. (c) Vent pipes made from PVC are permitted. 3. BAL 19 As per the BAL 12.5 requirements of this table - not including (c) 4. BAL 29 As per the BAL 12.5 requirements of this table 5. BAL 40 (a) All components of roof ventilators (including rotary ventilators), aerials, vent pipes and supports for solar collectors must be (i) of non-combustible material; and (ii) be sealed at the roof penetration with non-combustible material to prevent gaps greater than 3mm. 6. BAL FZ (a) All components of aerials, vent pipes and supports for solar collectors must be (i) of non-combustible material; and (ii) be sealed at the roof penetration with non-combustible material to prevent gaps greater than 3mm. (b) Roof ventilators must be one of the following - (i) a system complying with AS when tested from the outside; or (ii) a system with an FRL of 30/30/30 or -/30/30 when tested from the outside. GUTTERS AND DOWNPIPES 1. BAL Low No requirements 2. BAL (a) Gutter and valley leaf guards must be non-combustible. (b) Box gutters must be non-combustible and flashed at the junction with the roof with non-combustible material. 3. BAL 19 As per the BAL 12.5 requirements of this table 27 of 40

Timber in Bushfire Prone Areas

Timber in Bushfire Prone Areas In many parts of Australia, the construction of new buildings and additions to existing buildings will be assessed as being in a Bushfire-prone Area. The relevant Australian Standard AS 959 provides six

More information

Building with Timber in Bushfire-prone Areas

Building with Timber in Bushfire-prone Areas 04 Building with Timber in Bushfire-prone Areas BCA Compliant Design and Construction Guide Technical Design Guide issued by Forest and Wood Products Australia Technical Design Guide issued by Forest and

More information

CB04. Outback House. Case Study. Creative Spaces Australia. by Casey Brown Architecture

CB04. Outback House. Case Study. Creative Spaces Australia. by Casey Brown Architecture CB04 Case Study Outback House by Casey Brown Architecture Creative Spaces Australia E : info@creativespacesaustralia.com.au www.creativespacesaustralia.com.au Introduction Inspired by the big sheds of

More information

Windows & Doors Bushfire & Energy Efficient Solutions Tony Paarhammer Paarhammer Pty. Ltd

Windows & Doors Bushfire & Energy Efficient Solutions Tony Paarhammer Paarhammer Pty. Ltd Windows & Doors Bushfire & Energy Efficient Solutions Tony Paarhammer Paarhammer Pty. Ltd. 1300 655 920-03 5368 1999 www.paarhammer.com.au Bushfire The new Australian Standard 3959-2009 has now been adopted

More information

CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures

CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE - 268-5161 Residential Accessory Structures This information has been compiled for the benefit of any person

More information

Steel Floor Framing Solutions

Steel Floor Framing Solutions Steel Floor Framing Solutions Complete packages for domestic floors, decks and additions Product Manual & General Information Individually designed solutions Full design and quote service Drawings and

More information

TW50. Insulation STANDARD DETAILS FOR 50 MM INSULATION BOARD IN A 100 MM CAVITY. Low Energy Low Carbon Buildings. Wall lining. Inner leaf blockwork

TW50. Insulation STANDARD DETAILS FOR 50 MM INSULATION BOARD IN A 100 MM CAVITY. Low Energy Low Carbon Buildings. Wall lining. Inner leaf blockwork Insulation CI/SfB (21.9) Rn7 M2 First Issue May 2017 e with retaining clip TW50 STANDARD DETAILS FOR 50 MM INSULATION BOARD IN A 100 MM CAVITY 25 mm / 50 mm residual cavity Kingspan Thermawall TW50 Outer

More information

WILDLAND URBAN INTERFACE (WUI) PRODUCTS

WILDLAND URBAN INTERFACE (WUI) PRODUCTS CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL WILDLAND URBAN INTERFACE (WUI) PRODUCTS Published by CAL-FIRE WILDLAND FIRE PREVENTION ENGINEERING Revised 12/17/07

More information

CHAPTER 26 PLASTIC SECTION BC 2601 SECTION BC 2603 GENERAL FOAM PLASTIC INSULATION

CHAPTER 26 PLASTIC SECTION BC 2601 SECTION BC 2603 GENERAL FOAM PLASTIC INSULATION CHAPTER 26 PLASTIC SECTION BC 2601 GENERAL 2601.1 Scope. These provisions shall govern the materials, design, application, construction and installation of foam plastic, foam plastic insulation, plastic

More information

SOL UTIONS LIVING SOLUTIONS LIVING SOLUTIONS

SOL UTIONS LIVING SOLUTIONS LIVING SOLUTIONS Buyer s Guide HOMES 1300 985 110 LIVING SUPPORT SOLUTIONS 2 BCDS0868 Contents Just imagine the space you can create 4 More reasons to choose SmartSpace 8 SmartSpace Project Planner 9 Design your SmartSpace

More information

Insulwhite. Insulation WHITE-FACED THERMO REFLECTIVE INSULATION

Insulwhite. Insulation WHITE-FACED THERMO REFLECTIVE INSULATION Insulation A4/6 TB055W AW2244 Issue 6 Oct 2017 WHITE-FACED THERMO REFLECTIVE INSULATION Innovative cross-linked closed cell insulation core 3-in-1 Insulation, vapour barrier and radiant barrier Helps achieve

More information

Administrative Changes

Administrative Changes Revised 11/29/06 Knox County Residential Building Codes Significant Changes From The 1995 CABO One And Two Family Dwelling Code To The 2006 International Residential Code All one and two family dwellings

More information

BENCHMARK Evolution Axis

BENCHMARK Evolution Axis Sheet List EVO VT 00 B DIRECTION OF PREVAILING WIND VERTICAL PANEL JOINT & FASTENER LOCATIONS DIRECTION OF LAY FACTORY APPLIED WEATHER SEAL CONCEALED PANEL FIXING NOTE: FASTENER NUMBERS DEPEND ON THE ACTUAL

More information

One and Two Family Additions

One and Two Family Additions One and Two Family Additions An addition to a house, duplex, garage, or an accessory structure requires a building permit prior to performing any construction. Building Department & Permit Office Mon-Fri

More information

Stage 10 Design & Building Guidelines

Stage 10 Design & Building Guidelines Stage 10 Design & Building Guidelines DESIRED CHARACTER/VISION The development of The Rivergums presents the opportunity to create a high quality and more sustainable living environment by providing an

More information

Report for CSR Hebel. Impact of various wall and floor construction options on 5 star compliance for two houses. by Tony Isaacs Consulting Pty Ltd

Report for CSR Hebel. Impact of various wall and floor construction options on 5 star compliance for two houses. by Tony Isaacs Consulting Pty Ltd Tony Isaacs Consulting Pty Ltd Sustainable Buildings Specialist Report for CSR Hebel Impact of various wall and floor construction options on 5 star compliance for two houses by Tony Isaacs Consulting

More information

2003 International Residential Building Code

2003 International Residential Building Code 2003 International Residential Building Code Section R305 Ceiling Height Habitable rooms, hallways, corridors, bathrooms, toilet rooms, laundry rooms and basements shall have a ceiling height of not less

More information

Insulation Installation

Insulation Installation passive design 108 4.8 INSULATION INSTALLATION Insulation Installation Installing insulation or additional insulation in an existing dwelling can make a significant difference to the performance of the

More information

11 FLAT ROOF CONSTRUCTION

11 FLAT ROOF CONSTRUCTION CARPENTRY & JOINERY FCA CARPENTRY & JOINERY THEORY 11 FLAT ROOF Flat Roofs The definition of a flat roof is any roof which has a slope of less than 10 degrees or a fall ratio of 1:6. This type of roof

More information

1.1.2 All window frames will be Kite marked to indicate compliance with these standards.

1.1.2 All window frames will be Kite marked to indicate compliance with these standards. PVC-u WINDOWS Specification 1.1 General Spcification 1.1.1 All products supplied will fully comply with current editions of all relevant British Standards and Codes of Practice, and in particular all profiles

More information

The great Aussie shed deserves great Australian insulation

The great Aussie shed deserves great Australian insulation polyair unicell The great Aussie shed deserves great Australian insulation FULLY COMPLIANT TO THE BCA Extra heavy duty Commercial grade Australian made 15 year warranty Why choose Bradford Polyair Unicell?

More information

Fire Resistant: Achieves FRL levels of 90/90/90 for load bearing walls.

Fire Resistant: Achieves FRL levels of 90/90/90 for load bearing walls. ( ) is a new and innovative system designed to provide high performance separating walls between units and apartments in low-rise residential and commercial projects. provides exceptional fire and acoustic

More information

WOOD USE IN NONCOMBUSTIBLE BUILDINGS

WOOD USE IN NONCOMBUSTIBLE BUILDINGS INTRODUCTION The National Building Code of Canada (NBCC) 1 requires that some buildings be of noncombustible construction under its prescriptive requirements. Its use in certain types of buildings such

More information

Building Codes and Ordinances ARC 227

Building Codes and Ordinances ARC 227 Building Codes and Ordinances ARC 227 Week 6 Fire Resistive Construction 03.02.10 Instructor: Rick Staub, AIA Email: staub@pointonearchitects.com Phone: 860-434-7707 Fire Resistive Construction Passive

More information

CHAPTER 26 PLASTIC SECTION 2601 SECTION 2603 GENERAL FOAM PLASTIC INSULATION

CHAPTER 26 PLASTIC SECTION 2601 SECTION 2603 GENERAL FOAM PLASTIC INSULATION CHAPTER 26 PLASTIC SECTION 2601 GENERAL 2601.1 Scope. These provisions shall govern the materials, design, application, construction and installation of foam plastic, foam plastic insulation, plastic veneer,

More information

The better way to build TM. Installation Manual FOUNDATION SIPs & FROST WALLS SIPs

The better way to build TM. Installation Manual FOUNDATION SIPs & FROST WALLS SIPs The better way to build TM Installation Manual FOUNDATION SIPs & FROST WALLS SIPs November 2016 PWF FOUNDATION & FROST WALL SIPs Installation Manual Table of Contents Topics General Requirements....................................

More information

Passivhaus certified housing project with G-Brick SIP panels by Garnica

Passivhaus certified housing project with G-Brick SIP panels by Garnica Passivhaus certified housing project with G-Brick SIP panels by Garnica Prefabrication system: G-Brick panel As a result of an intense search for new applications and developments in plywood panel, Garnica

More information

Double Glazed Windows & Doors

Double Glazed Windows & Doors Double Glazed Windows & Doors FormView Profile FormView double glazed windows & doors was created to meet the need for a superior energy efficient window and door system, at an affordable price, without

More information

CABONNE COUNCIL DEVELOPMENT CONTROL PLAN NO. 15 RELOCATABLE AND TRANSPORTABLE HOMES

CABONNE COUNCIL DEVELOPMENT CONTROL PLAN NO. 15 RELOCATABLE AND TRANSPORTABLE HOMES CABONNE COUNCIL DEVELOPMENT CONTROL PLAN NO. 15 RELOCATABLE AND TRANSPORTABLE HOMES As approved by Council at the meeting of 20 June 2005 Came into effect on 14 July 2005 I, G. L. P. Fleming, General Manager,

More information

AIR BARRIER DESIGN PRINCIPLES AN OVERVIEW.

AIR BARRIER DESIGN PRINCIPLES AN OVERVIEW. AIR BARRIER DESIGN PRINCIPLES AN OVERVIEW www.stromatech.com AIR BARRIER DESIGN PRINCIPLES Building Regulations Approved Document Parts L1A & L2A currently requires that new buildings have to achieve a

More information

Building Design Data

Building Design Data Building Design Data.. 1. Building Design The KORE ICF System is designed to meet the requirements of the Building Regulations 1997-2006, in the case of two storeys, single occupancy dwellings. If the

More information

CALIFORNIA COMMERCIAL BUILDING INSPECTOR CONTENT OUTLINE 01. GENERAL ADMINISTRATION 6% Project Administration 1%

CALIFORNIA COMMERCIAL BUILDING INSPECTOR CONTENT OUTLINE 01. GENERAL ADMINISTRATION 6% Project Administration 1% CALIFORNIA COMMERCIAL BUILDING INSPECTOR CONTENT OUTLINE EXAM ID: I1 80 multiple-choice questions 3-1/2-hour time limit Open book 01. GENERAL ADMINISTRATION 6% 0101. Project Administration 1% Verify that

More information

RESIDENTIAL BUILDING PLAN REQUIREMENTS

RESIDENTIAL BUILDING PLAN REQUIREMENTS CITY OF MANSFIELD BUREAU OF BUILDING AND CODES 30 NORTH DIAMOND STREET 3RD FLOOR MANSFIELD, OHIO 44902 Phone (419) 755-9688 Fax (419) 755-9453 www.ci.mansfield.oh.us RESIDENTIAL BUILDING PLAN REQUIREMENTS

More information

C H A P T E R 3. Completing the Residential Analysis Worksheet STEP 1: WINDOWS AND OTHER GLASS AREAS

C H A P T E R 3. Completing the Residential Analysis Worksheet STEP 1: WINDOWS AND OTHER GLASS AREAS C H A P T E R 3 Completing the Residential Analysis Worksheet The Residential Analysis Worksheet is designed to help the reader in making the preliminary calculations necessary to complete Forms 600A-04,

More information

Certificate number: CM40087 Rev3

Certificate number: CM40087 Rev3 Certification Body: ABN: 80 111 217 568 JAS-ANZ Accreditation No. Z4450210AK PO Box 7144, Sippy Downs Qld 4556 +61 (07) 5445 2199 www.certmark.org Certificate Holder: ABN: 22 750 783 065 19 Lowermill Rd,

More information

Acoustic Design Criteria

Acoustic Design Criteria Apartment Acoustics Apartment Buildings Acoustic Design Criteria Building Code of Australia: - Intertenancy walls and floors - Corridor walls and doors - Floor impact isolation - Lift, stair and core walls

More information

Inspection details. Subfloor. Subfloor. Before You Buy property inspection

Inspection details. Subfloor. Subfloor. Before You Buy property inspection Before You Buy 254 Richmond Rd, Auckland, 1011, Auckland info@beforeyoubuy.co.nz www.beforeyoubuy.co.nz 29th Sep, 2015 Inspection details Property owner Joe Bloggs Address 36 Bloggs st Date 03 Jul 2015

More information

SWING DOOR SPECIFICATION

SWING DOOR SPECIFICATION SWING DOOR A1 Work included: Furnish all necessary materials, labour and equipment for the complete installation of aluminum entrance doors, door frames and hardware as detailed on the drawings and specified

More information

TECHNICAL GUIDANCE XXXX 2015 EXXON QUESTION ANSWER. page 1 of 9

TECHNICAL GUIDANCE XXXX 2015 EXXON QUESTION ANSWER. page 1 of 9 MARKINGWALLING OF SAFETY GLASS SPANDREL CURTAIN PANELS FORMED TO COLDFROM ROOFS STACKED WINDOW 7.2 /25 January ARRANGEMENTS (First Issue) XXXX EXXON QUESTION Which factors should be taken into account

More information

Roof Systems. Span Tables & Thermal Ratings. Custom Roof Panel

Roof Systems. Span Tables & Thermal Ratings. Custom Roof Panel Roof Systems Custom Roof Panel Tables & Thermal Ratings Version 2015.02 A fully customised and complete roofing solution that is quick to install with superior span and cantilever capabilities. UP TO CMA-CM40091

More information

ASSESSMENT OF AFS STRUCTURAL WALL SYSTEM FOR CBPA NSW, FEBRUARY 2008

ASSESSMENT OF AFS STRUCTURAL WALL SYSTEM FOR CBPA NSW, FEBRUARY 2008 ASSESSMENT OF AFS STRUCTURAL WALL SYSTEM FOR CBPA NSW, FEBRUARY 2008 1. Introduction This assessment of the AFS Structural Wall System is based on the following documentation provided by the supplier,

More information

City of Republic Community Development Department. Residential Roofs REVISION DATE: JANUARY 2017

City of Republic Community Development Department. Residential Roofs REVISION DATE: JANUARY 2017 City of Republic Community Development Department Residential Roofs REVISION DATE: JANUARY 2017 A residential roof permit is required for new roofs and for replacement roofs when the replacement area is

More information

N1 to N3. DuraGalPlus Domestic Construction Manual. Volume 3: DuraGalPlus RHS as floor beams (bearers)

N1 to N3. DuraGalPlus Domestic Construction Manual. Volume 3: DuraGalPlus RHS as floor beams (bearers) N1 to N3 Domestic Construction Manual Volume 3: RHS as floor beams (bearers) DuraGal Domestic Construction Manual Volume 1: Roof beams - N1 to C3 (N1 to C3 - Rafters) (N1 to N3 - Roof beams, strutting

More information

SCREEN PORCHES 101 DEVELOPMENT RESOURCES, INC Permit Requirements

SCREEN PORCHES 101 DEVELOPMENT RESOURCES, INC Permit Requirements SCREEN PORCHES 101 DEVELOPMENT RESOURCES, INC. 320-226.5189 www.101developmentresources.com While every attempt has been made to insure the correctness of this handout, no guarantees are made to its accuracy

More information

HOME DEVELOPMENT GUIDE

HOME DEVELOPMENT GUIDE HOME DEVELOPMENT GUIDE FireSmart Canada acknowledges the Institute for Business and Home Safety for providing the content for this publication. HOME DEVELOPMENT GUIDE WILDFIRE REALITY Wildfires are a natural

More information

GENERAL SITING REQUIREMENTS FOR SINGLE DWELLINGS/OUTBUILDINGS

GENERAL SITING REQUIREMENTS FOR SINGLE DWELLINGS/OUTBUILDINGS GENERAL SITING REQUIREMENTS FOR SINGLE DWELLINGS/OUTBUILDINGS INTRODUCTION The Building Regulations of Victoria prescribe a number of minimum siting requirements for single dwelling developments on lots

More information

A GUIDE TO WINDOW AND DOOR SELECTION

A GUIDE TO WINDOW AND DOOR SELECTION Australian window association guide series A GUIDE TO WINDOW AND DOOR SELECTION An industry guide to the selection and certification of windows and doors Background Foreword As part of its commitment to

More information

SEPTEMBER construction type cavity barriers. SP Firestop Systems. The purpose-made solution for cavity fire stopping

SEPTEMBER construction type cavity barriers. SP Firestop Systems. The purpose-made solution for cavity fire stopping SP Firestop Systems The purpose-made solution for cavity fire stopping SP Firestop Systems The purpose-made solution for cavity fire stopping As part of the comprehensive FIREPRO range of fire protection

More information

Retroshield XL TM. Insulation THERMO REFLECTIVE INSULATION

Retroshield XL TM. Insulation THERMO REFLECTIVE INSULATION Insulation A4/6 TB055F AW2002 Issue 4 Sept 2015 THERMO REFLECTIVE INSULATION Innovative cross-linked closed-cell insulation core Improved Class 0 fire performance to stringent international standards 3-in-1

More information

Xtratherm Thin-R Partial Fill Cavity Wall Board (XT/CW Grade)

Xtratherm Thin-R Partial Fill Cavity Wall Board (XT/CW Grade) CERTIFICATE NO. 03/0183 DETAIL SHEET 1 Xtratherm Thin-R Partial Fill Cavity Wall Board (XT/CW Grade) PRODUCT DESCRIPTION This Detail Sheet relates to Xtratherm Thin-R Partial Fill Cavity Wall Board, as

More information

Part E robustdetails. robustdetails. January 2017 Update Pack. Dear Colleague,

Part E robustdetails. robustdetails. January 2017 Update Pack. Dear Colleague, Part E Pack Dear Colleague, This is the first 2017 update to the Part E Robust Details Handbook. In this update pack, we have focussed on clarifying the situation on incorporating underfloor heating (UFH)

More information

RESIDENTIAL NEW CONSTRUCTION PLAN REVIEW CHECKLIST

RESIDENTIAL NEW CONSTRUCTION PLAN REVIEW CHECKLIST This list is provided as a guide to help you understand the information that must be contained on the construction drawings. This list is not all-inclusive of all building codes but is used as a general

More information

N1 to N3. DuraGalPlus Domestic Construction Manual. Volume 2: DuraGalPlus RHS as lintels (garage beams, window heads)

N1 to N3. DuraGalPlus Domestic Construction Manual. Volume 2: DuraGalPlus RHS as lintels (garage beams, window heads) N1 to N3 Domestic Construction Manual Volume 2: RHS as lintels (garage beams, window heads) Domestic Construction Manual Volume 1: Roof beams - N1 to C3 (N1 to C3 - Rafters) (N1 to N3 - Roof beams, strutting

More information

TECHNICAL INFORMATION

TECHNICAL INFORMATION TECHNICAL INFORMATION SECTION 07320 TWO-PIECE TAPERED MISSION CLAY ROOFING TILE PART 1 GENERAL 1.01 SECTION INCLUDES A. Formed clay roofing tiles, complete with components and other required accessories

More information

INSPECT DIRECT. Web Page: THIS REPORT IS VALID FOR (6) MONTHS FROM THE DATE OF MOST RECENT INSPECTION.

INSPECT DIRECT. Web Page:  THIS REPORT IS VALID FOR (6) MONTHS FROM THE DATE OF MOST RECENT INSPECTION. INSPECT DIRECT Ph: 1300 133363 THIS REPORT IS VALID FOR (6) MONTHS FROM THE DATE OF MOST RECENT INSPECTION. REPORT ON DOMESTIC BUILDING WORK UNDER SECTION 137B OF THE BUILDING ACT 1993 (OWNER-BUILDER CONSTRUCTION)

More information

EMERGENCY MANAGEMENT PREPAREDNESS AND ASSISTANCE TRUST FUND ARC 4496 Evaluation Questionnaire

EMERGENCY MANAGEMENT PREPAREDNESS AND ASSISTANCE TRUST FUND ARC 4496 Evaluation Questionnaire EMERGENCY MANAGEMENT PREPAREDNESS AND ASSISTANCE TRUST FUND ARC 4496 Evaluation Questionnaire Additional Instructions and Clarifications 1. Please review ARC 4496 before beginning the project identification

More information

Stage 6 & 7 Design Guidelines

Stage 6 & 7 Design Guidelines Stage 6 & 7 Design Guidelines DESIRED CHARACTER/VISION The new release at Emerald Park Private Estate presents the opportunity to create a high quality and contemporary living environment. These Design

More information

Brick Veneer Walls. Insulation

Brick Veneer Walls. Insulation Insulation A4/8 BV AW2157 Issue 7 Nov 2016 Brick Veneer Walls Insulation guide Helps achieve a 6-star house energy rating Rigid Kingspan Kooltherm and flexible Kingspan AIR-CELL solutions available Fibre-free,

More information

60 years. of progressive development

60 years. of progressive development Dencroft has been providing a wide range of sectional buildings for over 60 years, making us one of the most experienced designers and manufacturers of quality garages in the UK. Innovation has played

More information

INDICATIVE FEASIBILITY BUDGET (RIBA STAGE 1) for ST JAMES'S CHURCH : WEYBRIDGE SURREY. June 2016

INDICATIVE FEASIBILITY BUDGET (RIBA STAGE 1) for ST JAMES'S CHURCH : WEYBRIDGE SURREY. June 2016 INDICATIVE FEASIBILITY BUDGET (RIBA STAGE 1) for INTERNAL REPAIRS AND REDECORATIONS OF THE CHURCH HALL at ST JAMES'S CHURCH : WEYBRIDGE SURREY June 2016 SAWYER & FISHER (EPSOM) LTD THOMAS FORD & PARTNERS

More information

CONTOURS HAVE BEEN GENERATED BY AUCKLAND GIS BOUNDARY. 2.5m & 45 º EXISTING GROUND LINE EAVES CONTOURS HAVE BEEN GENERATED BY AUCKLAND GIS

CONTOURS HAVE BEEN GENERATED BY AUCKLAND GIS BOUNDARY. 2.5m & 45 º EXISTING GROUND LINE EAVES CONTOURS HAVE BEEN GENERATED BY AUCKLAND GIS 27690 RIDGE 0 5 METRES CONTOURS BEYOND THIS POINT HAVE BEEN GENERATED BY AUCKLAND GIS OUTLINE OF SECOND STOREY/ ATTIC SHOWN INDICATIVELY 5 RESOURCE CONSENT COPYRIGHT of Arhiteture + Interiors Ltd. 26660

More information

CASE STUDY OF THE SOUND REDUCTION OF VARIOUS RESIDENTIAL GLAZING TREATMENTS

CASE STUDY OF THE SOUND REDUCTION OF VARIOUS RESIDENTIAL GLAZING TREATMENTS Abstract CASE STUDY OF THE SOUND REDUCTION OF VARIOUS RESIDENTIAL GLAZING TREATMENTS Greg Barry 1, Darren Jurevicius 2 and Matthew Stead 3 1 Resonate Acoustics, Adelaide SA 5082, Australia Email: greg.barry@resonateacoustics.com

More information

RAINWATER GOODS GUTTERS, FASCIA & ACCESSORIES. A Met-TECH GUIDE

RAINWATER GOODS GUTTERS, FASCIA & ACCESSORIES. A Met-TECH GUIDE RAINWATER GOODS GUTTERS, FASCIA & ACCESSORIES A Met-TECH GUIDE SEPTEMBER 2017 METROLL RAINWATER GOODS Made from COLORBOND, ZINCALUME and galvanised steels, the Metroll range of gutters, fascia and accessories

More information

EcoHome-Insulation.com. Aluminium Foil Bubble Insulation. General Purpose Insulation. Dry Lining. Cavity Wall. Insulation System.

EcoHome-Insulation.com. Aluminium Foil Bubble Insulation. General Purpose Insulation. Dry Lining. Cavity Wall. Insulation System. Suspended Timber Floor Applications Can be used with Floorboards or Tongue & Groove floor paneling Aluminium Foil Bubble Insulation Joist end Fitting General Purpose Insulation Dry Lining Insulation System

More information

General Residential Code Requirements

General Residential Code Requirements Residential building code review will be based on compliance with the requirements of the Louisiana State Uniform Construction code in accordance with ACT 12 of the 2005 First Extraordinary Session of

More information

Residential Accessory Structures & Room Additions

Residential Accessory Structures & Room Additions Residential Accessory Structures & Room Additions Planning and Development Services Department Building Safety Division 8500 Santa Fe Drive Overland Park, KS 66212 (913) 895-6225 Fax (913) 895-5016 Email:

More information

RANCHO MONTE ALEGRE SANTA BARBARA CALIFORNIA

RANCHO MONTE ALEGRE SANTA BARBARA CALIFORNIA RANCHO MONTE ALEGRE SANTA BARBARA CALIFORNIA Lot Total Acres 0 Residential Development Envelope acres Agricultural Easement and Development Envelope. acres Final SBAR Approval $,00,000 Lot Total Acres

More information

Instructions for the Residential Building Data Collection Checklist 2009 International Energy Conservation Code with 2011 Georgia Amendments

Instructions for the Residential Building Data Collection Checklist 2009 International Energy Conservation Code with 2011 Georgia Amendments Instructions for the Residential Building Data Collection Checklist 2009 International Energy Conservation Code with 2011 Georgia Amendments Use of these instructions with a residential data collection

More information

CI/SfB (23) Suspended Timber Floor Applications Can be used with Floorboards or Tongue & Groove floor paneling Joist end Fitting Aluminium Foil Bubble Insulation General Purpose Insulation Dry Lining Insulation

More information

SECTION D Masonry Wall Systems. Contents. Introduction. Design Considerations. Installation. Components. System Specifications.

SECTION D Masonry Wall Systems. Contents. Introduction. Design Considerations. Installation. Components. System Specifications. SECTION D Wall Systems. Contents. SUBJECT Introduction Design Considerations Installation Components PAGE D2 D2 D4 D5 System Specifications Stud One Side Stud Both Sides Stud and Furring Channel Resilient

More information

Ability Building Services Bill of Quantities

Ability Building Services Bill of Quantities Page 1 of 6 0001 General Notes 0001-0100 EUROPEAN HOUSE BORER 0 1 1 ************************************************************************* The Department of Housing & Works recommends that in areas

More information

GypLyner. GypLyner. Metal framed wall lining system. All our systems are covered by SpecSure when using genuine Gyproc and Isover products.

GypLyner. GypLyner. Metal framed wall lining system. All our systems are covered by SpecSure when using genuine Gyproc and Isover products. GypLyner GypLyner Metal framed wall lining system All our systems are covered by SpecSure when using genuine Gyproc and Isover products Linings GypLyner GypLyner is a cost-effective, virtually independent

More information

PREFA Aluminiumprodukte GmbH Page 1 of 21

PREFA Aluminiumprodukte GmbH Page 1 of 21 Tender Specifications 120901 PREFA Shingles_2012 ---------------------------------------------------------------------------------- 01. Text GENERAL PRELIMINARY REMARKS Roof ----------------------------------------------------------------------------------

More information

Inspection of New One- and Two- Family Dwellings

Inspection of New One- and Two- Family Dwellings Building Safety Division 8500 Santa Fe Drive Overland Park, KS 66212 (913) 895-6225 Fax (913) 895-5016 Email: permitservices@opkansas.org Inspection of New One- and Two- Family Dwellings Planning and Development

More information

B5 for garages, equestrian and other single storey buildings

B5 for garages, equestrian and other single storey buildings Cl/SfB l (4-) l Nf9 l March 2017 l B5 for garages, equestrian and other single storey buildings Corrugated sheet and accessories www.cembrit.co.uk Cembrit companies have been manufacturing corrugated sheets

More information

Chapter 2 Understanding The Problem

Chapter 2 Understanding The Problem Chapter 2 Understanding The Problem What Causes Most Of The Problems With Stucco? EIFS was originally intended to seal and insulate the exterior of the home from the elements. Problems occur when poorly

More information

A. Source Limitations: Obtain each type of building insulation through one source.

A. Source Limitations: Obtain each type of building insulation through one source. SECTION 07210 - BUILDING INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

PART R3-L ZONE, LOW DENSITY MULTIPLE DWELLING DISTRICT

PART R3-L ZONE, LOW DENSITY MULTIPLE DWELLING DISTRICT PART 3.2 - R3-L ZONE, LOW DENSITY MULTIPLE DWELLING DISTRICT Uses 1 The following uses are permitted: (a) single family dwellings; (b) two family dwellings; (c) multiple dwellings; (d) churches; (e) public

More information

STRUCTURAL ABBREVIATIONS S-001 GENERAL NOTES CONCRETE MASONRY NOTES DESIGN NOTES SOF NSWG-10 UAS SUPPORT FACILITY FY 2016 MILCON P-225

STRUCTURAL ABBREVIATIONS S-001 GENERAL NOTES CONCRETE MASONRY NOTES DESIGN NOTES SOF NSWG-10 UAS SUPPORT FACILITY FY 2016 MILCON P-225 GENERAL NOTES DESIGN NOTES (CONTINUED) FOUNDATION NOTES STRUCTURAL ABBREVIATIONS CONCRETE MASONRY NOTES DESIGN NOTES S-001 CONCRETE NOTES COLD-FORMED STEEL FRAMING NOTES PRE-ENGINEERED METAL BUILDING NOTES

More information

Refusal of a code compliance certificate for a building with a brick veneer and monolithic cladding system at 47 San Bernadino Drive, Henderson

Refusal of a code compliance certificate for a building with a brick veneer and monolithic cladding system at 47 San Bernadino Drive, Henderson Refusal of a code compliance certificate for a building with a brick veneer and monolithic cladding system at 47 San Bernadino Drive, Henderson 1. The dispute to be determined 1.1 This is a determination

More information

FREQUENTLY ASKED QUESTIONS

FREQUENTLY ASKED QUESTIONS FREQUENTLY ASKED QUESTIONS Primary Product Uses: WAKAFLEX; primary flashing to replace traditional lead flashing in all applications, predominantly used on residential tile roofs but can also be used on

More information

Stage 11 (Release 1) Design Guidelines

Stage 11 (Release 1) Design Guidelines Stage 11 (Release 1) Design Guidelines 1. INTRODUCTION 1.1 Application (include plan) These design guidelines ( Guidelines ) apply to land known as The Rivergums Estate, Baldivis Road, Baldivis. To the

More information

Division 08 OPENINGS TABLE OF CONTENTS

Division 08 OPENINGS TABLE OF CONTENTS Division 08 OPENINGS TABLE OF CONTENTS 08 1000 GENERAL... 2 A. RELATED DIVISIONS... 2 B. GENERAL... 2 08 1000 DOORS AND FRAMES... 2... 2 B. EXTERIOR DOORS AND FRAMES... 2 C. DOOR FRAMES... 2 D. HOLLOW

More information

BC BUILDING CODE ERRATA

BC BUILDING CODE ERRATA BC BUILDING CODE ERRATA The following changes should be made to print and offline copies of the 2012 BC Codes. The 2012 BC Codes subscription products include these changes. Highlighted text is used in

More information

SHS Building Consultants. Ph Job Details. Photograph shows the front elevation of the residence.

SHS Building Consultants. Ph Job Details. Photograph shows the front elevation of the residence. Practical Completion Report Inspection date 1 st January Client Mohit Vir Job Details Address Lot 3349 Limone street Aveley. W.A. Photograph shows the front elevation of the residence. DESCRIPTION OF THE

More information

Fire Crunch. firecrunch.com.au. TECHNICAL MANUAL Installation : Fire Rate FRL Systems. Alternative Australian Certified Building Solutions

Fire Crunch. firecrunch.com.au. TECHNICAL MANUAL Installation : Fire Rate FRL Systems. Alternative Australian Certified Building Solutions Installation : Fire Rate FRL Systems CONTENTS Fire OVERVIEW... 3 Key Features... 3 Product Applications... 3 Environmental Properties... 3 Fire Protection... 3 AUSTRALIAN CERTIFICATION... 4 FIRE PROPERTIES...

More information

Fully framed glass panels

Fully framed glass panels Fully framed glass panels design elements G1 Fully framed glass panels G1 design The G1 is a fully framed balustrade solution suiting a refined and deliberate architectural style. Rather than minimising

More information

GRP Flat Roofing Edge Trims

GRP Flat Roofing Edge Trims GRP Flat Roofing Edge Trims Compatible with GRP, rigid and flexible polyester, polyurethane, acrylic and alkyd systems. Trim Brochure and Technical Specification Guide General Information The Easy To Use

More information

Viking Enviroclad Waterproofing Membrane. EC01 Enviroclad Drip Edge Specify from the above three options

Viking Enviroclad Waterproofing Membrane. EC01 Enviroclad Drip Edge Specify from the above three options *lum ngle 50x50x1.6mm min. with 20mm lum fixing bar to mechanically secure membrane Enviroclad Waterproofing Membrane Substrate to comply with current Roofspec Masterspec specification Substrate Checksheet

More information

MATERIAL & COMPONENT SPECIFICATION DATE: 1 ST FEBRUARY 2015 ISSUE NO: 19

MATERIAL & COMPONENT SPECIFICATION DATE: 1 ST FEBRUARY 2015 ISSUE NO: 19 SCANDIA-HUS FACT SHEET NO. 4 MATERIAL & COMPONENT SPECIFICATION DATE: 1 ST FEBRUARY 2015 ISSUE NO: 19 THIS FACT SHEET SHOULD BE READ IN CONJUNCTION WITH OUR SHELL ERECTION SCHEDULE FACT SHEET NO. 13 -

More information

COMP ONENT CATA LO GUE FOR B UILDING YO UR OWN HOME

COMP ONENT CATA LO GUE FOR B UILDING YO UR OWN HOME M a d e f o r b u i l d i n g b u i l t f o r l i v i n g COMP ONENT CATA LO GUE FOR B UILDING YO UR OWN HOME I M P R I N T KLH Massivholz GmbH Publisher and responsible for the content: KLH Massivholz

More information

Advanced Ventilation for Residential applications FBC Res 2010.

Advanced Ventilation for Residential applications FBC Res 2010. Advanced Ventilation for Residential applications FBC Res 2010. Course Description Review of the Residential Ventilation requirements in the Florida Building Code, Residential 2010. I. Introduction Dean

More information

Opening Roof Specialists. Builders Kit

Opening Roof Specialists. Builders Kit Opening Roof Specialists Builders Kit 1 Builders Deliver your customers control of sun, shade and light, and rain protection with the Eclipse. Now we can supply the Eclipse Opening Roof materials so that

More information

Practice Note FOR THE. Small Lot Housing Code

Practice Note FOR THE. Small Lot Housing Code Practice Note FOR THE Small Lot Housing Code AUGUST 2014 SMALL LOT HOUSING CODE PRACTICE NOTE Level 29, 35 Collins Street Melbourne Victoria 3000 Telephone: 03 9651 9600 Facsimile: 03 9651 9623 Email:

More information

Installation instructions

Installation instructions Installation instructions Holetherm Double-walled flue gas discharge system (DW) 2016 All information in this release is subject to misprints. No liability is accepted for the consequences of misprints.

More information

CERTIFICATE OF APPROVAL No CF 563 SIDERISE INSULATION LIMITED

CERTIFICATE OF APPROVAL No CF 563 SIDERISE INSULATION LIMITED CERTIFICATE OF APPROVAL No CF 563 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Forge Industrial Estate,

More information

Building Inspection Report

Building Inspection Report Building Inspection Report Sample Commercial Inspection Report Inspection Date: Prepared For: Prepared By: Professional Property Inspection Consultants 4857 Winterset Drive Columbus, OH 43220 (614) 459-5941

More information

r e s i d e n t i a l o u t s i d e v i l l a g e c e n t e r

r e s i d e n t i a l o u t s i d e v i l l a g e c e n t e r N e w A l b a n y, O h i o r e s i d e n t i a l o u t s i d e v i l l a g e c e n t e r D e s i g n G u i d e l i n e s & R e q u i r e m e n t s s e c t i o n 5 I. Overview This section applies to all

More information

Basic Information for Obtaining Permits, Submitting Plans, Scheduling Inspections, etc.

Basic Information for Obtaining Permits, Submitting Plans, Scheduling Inspections, etc. Basic Information for Obtaining Permits, Submitting Plans, Scheduling Inspections, etc. Franklin County Septic & Zoning permit application: A septic and zoning permit is required for residential or commercial

More information