Exterior Research & Design, L.L.C. Building Science and Envelope Consultants

Size: px
Start display at page:

Download "Exterior Research & Design, L.L.C. Building Science and Envelope Consultants"

Transcription

1 Exterior Research &, L.L.C. Building Science and Envelope Consultants Certificate of Authorization #9503 Evaluation Report Evaluation of Roofing s for Florida Product Approval #FL7508 Prepared for: Johns Manville Corporation th Street Denver, CO Prepared by: Robert J.M. Nieminen, P.E. Florida Registration Florida DCA ANE1983 Date of Issuance: September 19, 2006 ERD East: 2 Mattoon Road Waterbury, CT Voice (203) Fax (203) Main Office: 80 Yesler Way Suite 200 Seattle, WA Voice (206) Fax (206) Laboratory: 600 W. Nickerson St Seattle, WA Voice (206) Fax (206)

2 Certificate of Page 2 of 4 Authorization #9503 Manufacturer: Product Category: Sub-Category: Evaluation Method: Compliance Statement: Johns Manville Roofing s th Street Denver, CO Roofing Single Ply Roof s Method 1: Products specifically addressed in the FBC through performance criteria and standardized testing or comparative rational analysis methods. single-ply roof systems, as produced by Johns Manville Roofing s, have demonstrated compliance with the following sections of the Florida Building Code through testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein. Standards: Section Property Standard Year Wind FM Impact FM Physical Properties ASTM D References: Entity Examination Reference Date FM Approvals FM /15/01 FM Approvals FM /13/01 FM Approvals FM /02/02 FM Approvals FM /04/02 FM Approvals FM /28/02 FM Approvals FM /27/03 FM Approvals FM /09/04 FM Approvals FM /28/05 FM Approvals FM /02/06 FM Approvals FM /01/06 FM Approvals FM /02/06 IRT-Arcon TAS 114(J) PC /26/01 IRT-Arcon TAS 114(D) /12/01 MTi ASTM D6878 EX30M3B 06/17/04 Underwriters Labs Quality Assurance R9334 Current Product / Description: 45 & 60 membranes are nominal 45-mil (1.1 mm) or 60-mil (1.5-mm) thick respectively, internally reinforced thermoplastic polyolefin roof covers. Membrane is supplied in rolls 37.5, 48, 60, 75, 96, 120 ft or inch wide by 100 ft long. Side and end laps are sealed using hot air welding. The roof cover is mechanically or fully-adhered to Approved substrates, as outlined in the Limitations of Use herein. 72 & 80 membranes are nominal 72-mil (1.8 mm) or 80-mil (2.0-mm) thick, internally reinforced thermoplastic polyolefin roof covers. Membrane is supplied in rolls 48 ft or 96 inches wide by 75 ft long. Side and end laps are sealed using hot air welding. The roof cover is mechanically or fullyadhered to Approved substrates, as outlined in the Limitations of Use herein. ERD East: 2 Mattoon Road Waterbury, CT Voice (203) Fax (203) Main Office: 80 Yesler Way Suite 200 Seattle, WA Voice (206) Fax (206) Laboratory: 600 W. Nickerson St Seattle, WA Voice (206) Fax (206)

3 Certificate of Page 3 of 4 Authorization #9503 QA Documentation: 1. Listing through Underwriters Laboratories, Inc. (QUA 1743). Continued QA documentation comes in the form of the UL Mark on all product containers. 2. Non-JM materials used in the system shall be manufactured under a quality assurance program administered by a Florida DCA Approved Quality Assurance Entity, and materials and/or packaging shall carry the appropriate labeling from the Quality Assurance Entity. Installation Requirements: 1. roof covers shall be installed in accordance with Johns Manville published installation instructions, subject to the Limitations / Conditions of Use noted below. 2. attachment requirements for wind load resistance are set forth in Appendix For mechanically fastened membrane installations over profiled steel deck, membrane shall be installed running perpendicular to steel deck flutes. Limitations / Conditions of Use: 1. This Evaluation Report is not for use within the HVHZ. 2. Refer to a current Approved Roofing Materials Directory for fire rating. 3. For steel deck installations, foam plastic insulation shall be separated from the building interior in accordance with FBC Section unless the exceptions stated in FBC Sections and apply. 3. Unless otherwise noted in Appendix 1, roof decking and its attachment shall be specified and installed to meet project design criteria to the satisfaction of the AHJ. 4. For recover installations, the existing roof shall be examined in accordance with FBC Section For mechanically insulation or membrane, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC Chapter 16. Zones 2 and 3 shall employ a tighter membrane or insulation attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are RAS 117, RAS 137 and FM LPDS For adhered insulation, the maximum design pressure for the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16. No rational analysis is permitted for these systems 7. For mechanically insulation or membrane over existing roof decks, fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the minimum requirements for the system. Testing and analysis shall be in accordance with TAS For existing substrates in a re-roof (tear off) or recover installation, the existing deck or existing roof surface shall be examined for compatibility with the membrane or insulation adhesive to be installed. If any surface conditions exist that bring system performance into question, field uplift testing in accordance with ASTM E907 or FM LPDS 1-52 shall be conducted on mock-ups of the proposed new roof assembly. 9. For existing substrates in a recover installation, the existing roof system shall be capable of resisting project design pressures on its own merit to the satisfaction of the AHJ, as documented ERD East: 2 Mattoon Road Waterbury, CT Voice (203) Fax (203) Main Office: 80 Yesler Way Suite 200 Seattle, WA Voice (206) Fax (206) Laboratory: 600 W. Nickerson St Seattle, WA Voice (206) Fax (206)

4 Certificate of Page 4 of 4 Authorization #9503 through field uplift testing in accordance with ASTM E907 or FM LPDS Certification of Independence: 1. ERD East does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or distributing products it evaluates. 2. ERD East is not owned, operated or controlled by any company manufacturing or distributing products it evaluates. 3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for which the evaluation reports are being issued. 4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the product. Continued Compliance: Evaluation for compliance is valid until such time as the named product(s) changes, the referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this Evaluation Report by the named client constitutes agreement to notify ERD or Robert Nieminen, P.E. if the product changes or the referenced Quality Assurance documentation changes. Respectfully submitted, Robert Nieminen, P.E. Vice President Florida Reg robertn@exdesign.com The facsimile seal appearing on this document was authorized by Robert Nieminen, P.E on 09/19/2006 This does not serve as an electronically signed document Original, signed & sealed hardcopies forthcoming via courier - 10 PAGES THAT FOLLOW FORM PART OF THIS EVALUATION REPORT - ERD East: 2 Mattoon Road Waterbury, CT Voice (203) Fax (203) Main Office: 80 Yesler Way Suite 200 Seattle, WA Voice (206) Fax (206) Laboratory: 600 W. Nickerson St Seattle, WA Voice (206) Fax (206)

5 Certificate of Authorization #9503 Appendix 1: Page 1 of 10 WIND UPLIFT PERFORMANCE TABLES: The following notes apply to the systems outlined herein: 1. Roof deck shall be specified and installed in accordance with FBC requirements to the satisfaction of the AHJ. 2. For insulations not specifically called-out by trade name, the insulation may be any polyisocyanurate, polystyrene, fiberboard, perlite or gypsum-based insulation board that meets the quality assurance requirements of F.A.C. Rule 9B-72 and is documented as meeting FBC and, for foam plastic, FBC or , when installed with the roof cover. 3. Minimum fastener engagement are as follows: Wood Deck: Minimum ¾-inch plywood penetration or minimum 1-inch wood plank embedment. Steel Deck: Minimum ¾-inch steel penetration and engage the top flute of the steel deck. Concrete Deck: Minimum 1-inch embedment into pilot hole in accordance with the fastener manufacturer s published installation instructions. 4. Preliminary insulation attachment for Type D: Minimum four fasteners per 4 x 8 ft board or minimum two fasteners per 4 x 4 ft board. 5. Unless otherwise noted, insulation adhesive application rates are as follows: Hot asphalt: 25 lbs/square. If applying hot asphalt to deck; deck shall be primed with ASTM D41 primer. Pourable Foam Insulation Adhesive: ( ): Continuous ½ to ¾-inch wide ribbons, 12-inch One Step Foamable Adhesive ( ): Continuous ½ to ¾-inch wide ribbons, 12-inch 6. Bonded polyisocyanurate insulation boards shall be maximum 4 x 4 ft. 7. Tapered polyisocyanurate may be substituted for the flat stock board referenced in Tables 2A, 4A and 5A with the following Maximum (MDP) limitations: Pourable Foam Insulation Adhesive: ( ): Maximum One Step Foamable Adhesive ( ): Maximum 8. For mechanically components, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC Chapter 16, and Zones 2 and 3 shall employ a tighter attachment density designed by a qualified design professional to resist the elevated pressure criteria. 9. For bonded assemblies, the maximum design pressure for the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16, and no rational analysis is permitted. 10. For mechanically components over existing decks, fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the minimum requirements for the system. Testing and analysis shall be in accordance with TAS For existing substrates in a bonded recover installation, the existing roof system shall be capable of resisting project design pressures on its own merit to the satisfaction of the AHJ, as documented through field uplift testing in accordance with ASTM E907 or FM LPDS Adhered seams are 3-inch wide, with a min. 1.5-inch heat-weld.

6 Certificate of Authorization #9503 Appendix 1: Page 2 of 10 TABLE 1A: STEEL OR CONCRETE DECKS NEW CONSTRUCTION, REROOF (Tear-Off) or RECOVER SYSTEM TYPE C: MECHANICALLY ATTACHED INSULATION, BONDED MEMBRANE Roof Deck Base Insulation Top Insulation Layer Roof Cover Layer Type Fasteners Attach Membrane Application S-1 22 ga., type B, Grade 33 steel or more, loose laid ½-inch UltraFast #12 (steel only) or All Purpose Fastener with UltraFast AccuTrac Flat Bottom Plates 1 per 4 ft 2 Bonding Adhesive (Solvent Based), 2-sided psf S-2 22 ga., type B, Grade 33 steel or more, loose laid ¼-inch UltraFast #12 (steel only) or All Purpose Fastener with UltraFast AccuTrac Flat Bottom Plates 1 per 2.7 ft 2 Bonding Adhesive (Solvent Based), 2-sided S-3 22 ga., type B, Grade 80 steel or more, loose laid 1.5-inch ACFoam II, ENRGY 3 All Purpose Fastener with UltraFast AccuTrac Flat Bottom Plates 1 per 1.8 ft 2 Bonding Adhesive (Solvent Based), 2-sided psf S-4 22 ga., type B, Grade 80 steel or more, loose laid 2.0-inch ACFoam II, ENRGY 3 All Purpose Fastener with UltraFast AccuTrac Flat Bottom Plates 1 per 1.8 ft 2 Bonding Adhesive (Solvent Based), 2-sided psf S-5 22 ga., type B, Grade 80 steel or more, loose laid 5/8-inhc All Purpose Fastener with UltraFast AccuTrac Flat Bottom Plates 1 per 1.6 ft 2 Bonding Adhesive (Solvent Based), 2-sided psf S-6 22 ga., type B, Grade 80 steel or more, loose laid ¼-inhc All Purpose Fastener with UltraFast AccuTrac Flat Bottom Plates 1 per 1.3 ft 2 Bonding Adhesive (Solvent Based), 2-sided psf

7 Certificate of Authorization #9503 Appendix 1: Page 3 of 10 TABLE 1B: STEEL OR CONCRETE DECKS NEW CONSTRUCTION, REROOF (Tear-Off) or RECOVER SYSTEM TYPE D: MECHANICALLY ATTACHED MEMBRANE Roof Deck Insulation Layer Type Attach Membrane Fasteners Roof Cover Fastener Width Seam Weld S-7 Roofgrip, JM Extra High Load Fastener or JM High 18-inch 5-inch 70-inch 2.0-inch psf S-8 Roofgrip, JM Extra High Load Fastener or JM High 18-inch 90-inch dual weld or psf S-9 S-10 S-11 S-12 S-13 Roofgrip, JM Extra High Load Fastener or JM High Fastener with JM Extra Fastener with JM Super High Load 3 Plates Fastener with JM Extra Roofgrip, JM Extra High Load Fastener or JM High 12-inch 18-inch 12-inch 12-inch 12-inch 5-inch 114-inch 114-inch inch dual weld psf psf psf psf psf

8 Certificate of Authorization #9503 Appendix 1: Page 4 of 10 TABLE 1B: STEEL OR CONCRETE DECKS NEW CONSTRUCTION, REROOF (Tear-Off) or RECOVER SYSTEM TYPE D: MECHANICALLY ATTACHED MEMBRANE Roof Deck Insulation Layer Type Attach Membrane Fasteners Roof Cover Fastener Width Seam Weld S-14 Roofgrip, JM Extra High Load Fastener or JM High 12-inch 114-inch psf S-15 S-16 Roofgrip, JM Extra High Load Fastener or JM High Fastener with JM Extra 12-inch 12-inch 90-inch 90-inch dual weld or S-17 Roofgrip, JM Extra High Load Fastener or JM High 114-inch S-18 Fastener with JM Extra 12-inch 114-inch S-19 Fastener with JM Extra or JM Extra High Load Fastener with JM Super High Load 3 Plates S-20 JM High Load Fasteners with JM S-21 Load Fastener with ¾ 12-inch 4.5- inch 1.5-inch dual weld

9 Certificate of Authorization #9503 Appendix 1: Page 5 of 10 TABLE 1B: STEEL OR CONCRETE DECKS NEW CONSTRUCTION, REROOF (Tear-Off) or RECOVER SYSTEM TYPE D: MECHANICALLY ATTACHED MEMBRANE S-22 Roof Deck Insulation Layer Type Attach Membrane Fasteners Fasteners with 1-inch Roof Cover Fastener Width 4.5- inch inch Seam Weld 1.5-inch dual weld psf S-23 S-24 Load Fastener with ¾ Fasteners with JM Extra 114-inch 90-inch 1.0-inch inside and 1.25-inch 1.5-inch psf psf S-25 Load Fastener with 1-inch 4.5- inch 1.5-inch dual weld psf S or 80 mil Load Fastener with ¾ 69-inch 1.0-inch inside and 1.5-inch psf S or 80 mil 90-inch 1.5-inch psf S-28 Load Fastener with 1-inch 4-inch 1.25-inch dual weld psf S-29 S or 80 mil 72 or 80 mil Fasteners with JM Extra 69-inch 90-inch 1.5-inch 1.5-inch psf psf

10 Certificate of Authorization #9503 Appendix 1: Page 6 of 10 TABLE 1B: STEEL OR CONCRETE DECKS NEW CONSTRUCTION, REROOF (Tear-Off) or RECOVER SYSTEM TYPE D: MECHANICALLY ATTACHED MEMBRANE Roof Deck Insulation Layer Type Attach Membrane Fasteners Roof Cover Fastener Width Seam Weld S-31 Load Fastener with ¾ 4.5- inch inch 1.0-inch inside and 1.25-inch psf S-32 Load Fastener with 1-inch 5-inch 1.5-inch dual weld psf S or 80 mil Row: ITW Bldx Large Head #15 Roofgrip or Fastener with JM High Load Plates Intermediate Row Between s: ITW Bldx Large Head #15 Roofgrip or Fastener with ¾ Polymer Batten Strip Row: 6- inch Intermediate Row: 90-inch : 1.5-inch Intermediate Row: 5-inch coverstrip with 1.5-inch weld on each side of bar psf

11 Certificate of Authorization #9503 Appendix 1: Page 7 of 10 C-1 C-2 C-3 C-4 C-5 C-6 C-7 C-8 TABLE 2A: CONCRETE DECKS NEW CONSTRUCTION or REROOF (Tear-Off) SYSTEM TYPE A: BONDED INSULATION, BONDED MEMBRANE Base Insulation Layer Top Insulation Layer Roof Cover Roof Deck Type Attach Type Attach Membrane Application layers ACFoam II, ENRGY 3 or H-Shield (Optional) layers ACFoam II, ENRGY 3 or H-Shield layers ACFoam II, ENRGY 3 or H-Shield (Optional) layers ACFoam II, ENRGY 3 or H-Shield layers ACFoam II, ENRGY 3 or H-Shield (Optional) layers ACFoam II, ENRGY 3 or H-Shield layers ACFoam II, ENRGY 3 or H-Shield (Optional) layers ACFoam II, ENRGY 3 or H-Shield Hot asphalt Hot asphalt (Optional) ½-inch Knight Celotex Structodek HD Fiberboard ½-inch Knight Celotex Structodek HD Fiberboard (Optional) ¼-inch DensDeck ¼-inch DensDeck (Optional) ¼-inch DensDeck or ¼-inch DensDeck or (Optional) ¼-inch DensDeck or or min. ½-inch Knight Celotex Structodek HD Fiberboard ¼-inch DensDeck or or min. ½-inch Knight Celotex Structodek HD Fiberboard Hot asphalt Hot asphalt Bonding Adhesive Bonding Adhesive Bonding Adhesive Bonding Adhesive Bonding Adhesive Bonding Adhesive Bonding Adhesive Bonding Adhesive psf psf psf psf psf psf psf psf

12 Certificate of Authorization #9503 Appendix 1: Page 8 of 10 TABLE 3A: LIGHTWEIGHT CONCRETE DECKS NEW CONSTRUCTION or REROOF (Tear-Off) SYSTEM TYPE F: BONDED MEMBRANE Roof Deck Roof Cover Structural Deck Lightweight Concrete Membrane Application LWC psi Elastizell LWIC. Top surface treated with roller-applied sodium silicate and allowed to dry, then primed with Membrane Adhesive at 120 ft 2 /gal and allowed to dry Bonding Adhesive (Solvent Based), 2-sided application, 65 ft 2 /gal psf TABLE 3B: LIGHTWEIGHT CONCRETE DECKS NEW CONSTRUCTION, REROOF (Tear-Off) or RECOVER SYSTEM TYPE D: MECHANICALLY ATTACHED MEMBRANE Roof Deck Lightweight Concrete Membrane Fasteners Roof Cover Fastener Width Seam Weld LWC psi cellular lightweight with minimum 2-inch thick top coat Load Fastener with 4.5- inch inch 0.75-inch inside and 1.0-inch psf

13 Certificate of Authorization #9503 Appendix 1: Page 9 of 10 G-1 G-2 G-3 G-4 TABLE 4A: GYPSUM DECKS REROOF (Tear-Off) SYSTEM TYPE A: BONDED INSULATION, BONDED MEMBRANE Base Insulation Layer Top Insulation Layer Roof Cover Roof Deck Type Attach Type Attach Membrane Application Existing gypsum deck Existing gypsum deck Existing gypsum deck Existing gypsum deck layers ACFoam II, ENRGY 3 or H-Shield more layers ACFoam II, ENRGY 3 or H- Shield layers ACFoam II, ENRGY 3 or H-Shield more layers ACFoam II, ENRGY 3 or H- Shield (Optional) ½- inch Knight Celotex Structodek HD Fiberboard ½-inch Knight Celotex Structodek HD Fiberboard (Optional) ¼- inch DensDeck or ¼-inch DensDeck or Bonding Adhesive Bonding Adhesive Bonding Adhesive Bonding Adhesive psf psf psf psf

14 Certificate of Authorization #9503 Appendix 1: Page 10 of 10 TABLE 5A: RECOVER APPLICATIONS SYSTEM TYPE A: BONDED INSULATION, BONDED MEMBRANE Substrate Base Insulation Layer Top Insulation Layer Roof Cover Type Attachment Type Attachment Membrane Application R-1 Existing asphaltic BUR or mineral surface cap sheet layers ACFoam II, ENRGY 3 or H-Shield (Optional) ½- inch Knight Celotex Structodek HD Fiberboard Bonding Adhesive psf R-2 Existing asphaltic BUR or mineral surface cap sheet (Optional) layers ACFoam II, ENRGY 3 or H-Shield ½-inch Knight Celotex Structodek HD Fiberboard Bonding Adhesive psf R-3 Existing asphaltic BUR or mineral surface cap sheet layers ACFoam II, ENRGY 3 or H-Shield (Optional) ¼- inch DensDeck Bonding Adhesive psf R-4 Existing asphaltic BUR or mineral surface cap sheet (Optional) layers ACFoam II, ENRGY 3 or H-Shield ¼-inch DensDeck Bonding Adhesive psf R-5 Existing asphaltic BUR or mineral surface cap sheet layers ACFoam II, ENRGY 3 or H-Shield (Optional) ¼- inch DensDeck or Bonding Adhesive psf R-6 Existing asphaltic BUR or mineral surface cap sheet (Optional) layers ACFoam II, ENRGY 3 or H-Shield ¼-inch DensDeck or Bonding Adhesive psf

Exterior Research & Design, L.L.C. Building Science and Envelope Consultants

Exterior Research & Design, L.L.C. Building Science and Envelope Consultants Exterior Research & Design, L.L.C. Building Science and Envelope Consultants Certificate of Evaluation Report 3520.03.04-R2 Evaluation of Roof s for Florida Product Approval #FL2533-R2 Prepared for: CertainTeed

More information

EVALUATION REPORT ICP Adhesives and Sealants, Inc NW 44 th Street Coral Springs, FL 33065

EVALUATION REPORT ICP Adhesives and Sealants, Inc NW 44 th Street Coral Springs, FL 33065 EVALUATION REPORT ICP Adhesives and Sealants, Inc. 12505 NW 44 th Street Coral Springs, FL 33065 EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization #9503 353 CHRISTIAN STREET, UNIT 13 OXFORD,

More information

EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization # Christian Street, Unit 13 Oxford, CT (203)

EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization # Christian Street, Unit 13 Oxford, CT (203) EVALUATION REPORT Duro-Last Roofing, Inc. 525 Morley Drive Saginaw, MI 48601 (800) 248-0280 EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization #9503 353 Christian Street, Unit 13 Oxford, CT

More information

EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization # Christian Street Oxford, CT PHONE: (203) FAX: (203)

EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization # Christian Street Oxford, CT PHONE: (203) FAX: (203) EVALUATION REPORT Mule-Hide Products Co., Inc. 1195 Prince Hall Drive Beloit, WI 53511 EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization #9503 353 Christian Street Oxford, CT 06478 PHONE: (203)

More information

EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization # Christian Street Oxford, CT PHONE: (203) FAX: (203)

EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization # Christian Street Oxford, CT PHONE: (203) FAX: (203) EVALUATION REPORT Carlisle SynTec Systems P.O. Box 7000 Carlisle, PA 17013 (717) 245-7264 EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization #9503 353 Christian Street Oxford, CT 06478 PHONE:

More information

EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization # Christian Street Oxford, CT PHONE: (203) FAX: (203)

EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization # Christian Street Oxford, CT PHONE: (203) FAX: (203) EVALUATION REPORT Johns Manville Corporation P.O. Box 5108 Denver, CO 80217 EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization #9503 353 Christian Street Oxford, CT 06478 PHONE: (203) 262-9245

More information

UL Evaluation Report UL ER Issued: July 25, UL Category Code: ULFB. CSI MasterFormat

UL Evaluation Report UL ER Issued: July 25, UL Category Code: ULFB. CSI MasterFormat UL Evaluation Report UL ER10167-01 Issued: July 25, 2014 Visit UL s On-Line Certifications Directory: www.ul.com/erdirectory for current status of Report. UL Category Code: ULFB CSI MasterFormat DIVISION:

More information

DESCRIPTION: Firestone SBS and APP Modified Bitumen Roof Systems

DESCRIPTION: Firestone SBS and APP Modified Bitumen Roof Systems EVALUATION REPORT Firestone Building Products Company, LLC. 250 West 96 th treet Indianapolis, IN 46260 (800) 443-4272 EXTERIOR REEARCH & DEIGN, LLC. Certificate of Authorization #9503 353 Christian treet

More information

Florida Building Code Online Page 1 of 2 BCIS Home Log In User Registration Hot Topics Submit Surcharge Stats & Facts Publications FBC Staff BCIS Site Map Links Search Product Approval USER: Public User

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

EVALUATION REPORT Boral Roofing 7575 Irvine Center Drive Suite 100 Irvine, CA

EVALUATION REPORT Boral Roofing 7575 Irvine Center Drive Suite 100 Irvine, CA EVALUATION REPORT Boral Roofing 7575 Irvine Center Drive Suite 100 Irvine, CA. 92618 EXTERIOR RESEARCH & DESIGN, LLC. 353 CHRISTIAN STREET, UNIT #13 OXFORD, CT 06478 PHONE: (203) 262-9245 FAX: (203) 262-9243

More information

PRODUCT CONTROL SECTION

PRODUCT CONTROL SECTION MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T (786) 315-2590

More information

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

PRODUCT CONTROL SECTION

PRODUCT CONTROL SECTION MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T (786)315-2590

More information

UL Evaluation Report UL ER Issued: December 19, 2014 Revised: August 14, UL Category Code: ULFB. CSI MasterFormat

UL Evaluation Report UL ER Issued: December 19, 2014 Revised: August 14, UL Category Code: ULFB. CSI MasterFormat UL Evaluation Report UL ER9516-02 Issued: December 19, 2014 Revised: August 14, 2015 Visit UL s On-Line Certifications Directory: www.ul.com/erdirectory for current status of Report. UL Category Code:

More information

EVALUATION REPORT Soprema, Inc. 310 Quadral Drive Wadsworth, OH 44281

EVALUATION REPORT Soprema, Inc. 310 Quadral Drive Wadsworth, OH 44281 EVALUATION REPORT Soprema, Inc. 310 Quadral Drive Wadsworth, OH 44281 EXTERIOR RESEARCH & DESIGN, LLC. 353 CHRISTIAN STREET OXFORD, CT 06478 PHONE: (203) 262-9245 FAX: (203) 262-9243 Date of Issuance:

More information

EVALUATION REPORT Tarco Roofing One Information Way, Suite 225 Little Rock, AR DESCRIPTION: Tarco Roof Underlayments

EVALUATION REPORT Tarco Roofing One Information Way, Suite 225 Little Rock, AR DESCRIPTION: Tarco Roof Underlayments EVALUATION REPORT Tarco Roofing One Information Way, Suite 225 Little Rock, AR 72202 EXTERIOR RESEARCH & DESIGN, LLC. 353 CHRISTIAN STREET, UNIT #13 OXFORD, CT 06478 PHONE: (203) 262-9245 FAX: (203) 262-9243

More information

technical bulletin ROOFING CORPORATION

technical bulletin ROOFING CORPORATION ROOFING CORPORATION technical bulletin TO: All Region Managers, Plant Managers, National Account Managers, Sales Representatives, Account Executives, and Atlanta Sales FROM: Ed Todd, Director, Product

More information

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

JM PVC Fleece Backed 50 mil, JM PVC Fleece Backed 60 mil, JM PVC Fleece Backed 80 mil

JM PVC Fleece Backed 50 mil, JM PVC Fleece Backed 60 mil, JM PVC Fleece Backed 80 mil UL Evaluation Report UL ER10167-02 Issued: August 8, 2016 Revised: November 3, 2016 Visit UL s On-Line Certifications Directory: www.ul.com/erdirectory for current status of Report. UL Category Code: ULFB

More information

UL Evaluation Report UL ER Issued: December 9, Revised: September 29, UL Category Code: ULFB. CSI MasterFormat

UL Evaluation Report UL ER Issued: December 9, Revised: September 29, UL Category Code: ULFB. CSI MasterFormat UL Evaluation Report UL ER9516-01 Issued: December 9, 2013 Revised: September 29, 2017 Visit UL s On-Line Certifications Directory: www.ul.com/erdirectory for current status of Report. UL Category Code:

More information

DESCRIPTION: Eagle Roof Tiles

DESCRIPTION: Eagle Roof Tiles EVALUATION REPORT Eagle Roofing Products Florida LLC. 1575 East Country Road 470 Sumterville, FL 33585 (800) 400-3245 EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization #9503 353 CHRISTIAN STREET,

More information

technical bulletin ROOFING CORPORATION

technical bulletin ROOFING CORPORATION ROOFING CORPORATION technical bulletin TO: All Region Managers, Plant Managers, National Account Managers, Sales Representatives, Account Executives, and Atlanta Sales FROM: Ed Todd, Director, Product

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: POLYVINYL CHLORIDE ROOFING REPORT HOLDER: IB ROOF SYSTEMS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: POLYVINYL CHLORIDE ROOFING REPORT HOLDER: IB ROOF SYSTEMS 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 28 Reissued 02/2018 This report is subject to renewal 02/2019. DIVISION: 07 00 00

More information

EVALUATION REPORT GAF 1361 Alps Road, Building 7-3 Wayne, NJ 07470

EVALUATION REPORT GAF 1361 Alps Road, Building 7-3 Wayne, NJ 07470 EVALUATION REPORT GAF 1361 Alps Road, Building 7-3 Wayne, NJ 07470 EXTERIOR RESEARCH & DESIGN, LLC. 353 CHRISTIAN STREET, UNIT #13 OXFORD, CT 06478 PHONE: (203) 262-9245 FAX: (203) 262-9243 Date of Issuance:

More information

CREEK Technical Services, LLC

CREEK Technical Services, LLC a CREEK Certificate of Authization 29824 17520 Edinburgh Drive Tampa, FL 33647 (813) 480-3421 EVALUATION REPORT FLORIDA BUILDING CODE 5 TH EDITION (2014) Manufacturer: JOHNS MANVILLE CORPORATION Issued

More information

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC 250 WEST 96 TH STREET INDIANAPOLIS, INDIANA EVALUATION SUBJECT:

REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC 250 WEST 96 TH STREET INDIANAPOLIS, INDIANA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2831 Reissued 08/2017 This report is subject to renewal 08/2018. DIVISION: 07 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MODIFIED BITUMINOUS SHEET ROOFING REPORT HOLDER: POLYGLASS USA, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MODIFIED BITUMINOUS SHEET ROOFING REPORT HOLDER: POLYGLASS USA, INC. 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-2018 Reissued 09/2017 This report is subject to renewal 09/2019. DIVISION: 07 00

More information

Sure-Weld (TPO) Adhered Roofing Systems Code Approval Guide January, Table of Contents

Sure-Weld (TPO) Adhered Roofing Systems Code Approval Guide January, Table of Contents (TPO) Adhered Roofing Systems Code Approval Guide January, 2017 Introduction... ii Guidelines... Mechanically Fastened or Induction Welding Roofing Systems UL Approvals NonCombustible ANSI UL Class A...

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF PERMITTING, ENVIRONMENT, AND REGULATORY

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF PERMITTING, ENVIRONMENT, AND REGULATORY MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF PERMITTING, ENVIRONMENT, AND REGULATORY AFFAIRS (PERA) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MODIFIED BITUMINOUS SHEET ROOFING REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MODIFIED BITUMINOUS SHEET ROOFING REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3909 Issued 07/2017 This report is subject to renewal 07/2018. DIVISION: 07 00 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ETHYLENE PROPYLENE DIENE MONOMER ROOFING REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ETHYLENE PROPYLENE DIENE MONOMER ROOFING REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Evaluation Rept ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.g ESR 3026 Reissued 04/207 This rept is subject to renewal 04/208. DIVISION: 07 00 00 THERMAL

More information

UL Listing: EPDM Roofing Systems

UL Listing: EPDM Roofing Systems Commercial/Industrial Roofing Systems UL Listing: EPDM Roofing Systems SINGLE PLY MEMBRANE ROOFING SYSTEMS In the fully adhered and mechanically fastened systems described below, the ".045 EPDM" membrane

More information

HALIFAX HUMANE SOCIETY BOARDING AND GROOMING FACILITY SECTION STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS

HALIFAX HUMANE SOCIETY BOARDING AND GROOMING FACILITY SECTION STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS SECTION 075216 - PART 1 - GENERAL 1.1 SUMMARY A. Section includes styrene-butadiene-styrene (SBS) modified bituminous membrane roofing. 1.2 DEFINITIONS A. Hot Roofing Asphalt: Roofing asphalt heated to

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 NOTICE OF ACCEPTANCE

More information

Thermoplastic Single Ply & Multi-Ply Roofing Systems

Thermoplastic Single Ply & Multi-Ply Roofing Systems Thermoplastic Single Ply & Multi-Ply Roofing Systems COMMERCIAL INDUSTRIAL INSTITUTIONAL RESIDENTIAL Specializing in Roof Solutions for over 25 years FlexRoofingSystems.com Thermoplastic Single Ply Roof

More information

SECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 075423 - THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including Division 00 Bidding Requirements and other Division

More information

SL175 Panel Technical Data Guide

SL175 Panel Technical Data Guide Description SL175 is a integral snap-lock standing seam roofing panel used on commercial and residential applications. The panel is factory formed in continuous lengths up to 60-0 long. Attachment to either

More information

2010 FLORIDA BUILDING CODE TEST PROTOCOLS HVHZ (TAS)

2010 FLORIDA BUILDING CODE TEST PROTOCOLS HVHZ (TAS) TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE FOR FIELD UPLIFT RESISTANCE OF EXISTING MEMBRANE ROOF SYSTEMS AND IN SITU TESTING FOR REROOF AND NEW CONSTRUCTION APPLICATIONS 1. Scope: 1.1 This

More information

FLORIDA PRODUCT APPROVAL GULFRIBTM FLORIDA PRODUCT APPROVAL NO R3. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC.

FLORIDA PRODUCT APPROVAL GULFRIBTM FLORIDA PRODUCT APPROVAL NO R3. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC. 26 Ga. GulfRib Roof Panel over 15/32 Plywood Florida Product Approval #11651.23 R3 Florida Building Code 2017 Per Rule 61G20-3 Method:

More information

statement: "Miami-Dade County Product Control Approved", unless otherwise noted herein.

statement: Miami-Dade County Product Control Approved, unless otherwise noted herein. MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

SECTION MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Roof

SECTION MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Roof SECTION 07550 MODIFIED BITUMINOUS MEMBRANE ROOFING Peel & Roof This section is based on the products of MFM Building Products Corp., which is located at: 525 Orange St. P. O. Box 340 Coshocton, OH 43812

More information

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

PRODUCT CONTROL SECTION

PRODUCT CONTROL SECTION MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T (786)315-2590

More information

COMMERCIAL ROOFING SYSTEMS

COMMERCIAL ROOFING SYSTEMS Flex Membrane International Corp. 2670 Leiscz s Bridge Road, Suite 400, Leesport, PA 19533 Tel: 610-916-9500 Fax: 610-916-9501 COMMERCIAL ROOFING SYSTEMS FLEX FB (Fleece Backed) ELVALOY, FLEX MF/R (Smooth

More information

Firestone Polyiso Boards

Firestone Polyiso Boards Firestone Polyiso Boards Superior energy efficiency. Superior protection. Firestone Polyiso Boards POLISOBROUK10.indd 1 1/04/10 14:26 Firestone Polyiso Boards Firestone total roofing systems Since Firestone

More information

FOAMULAR Commercial Roofing

FOAMULAR Commercial Roofing Low Slope Insulated Roof Systems Roofing Systems Single-ply roofing s are flexible sheets of compounded synthetic materials that are manufactured in a factory. Single ply roof systems provide strength,

More information

CBUCK Engineering. Product: Zee-Lock Roof Panel Material: Steel Panel Thickness: 24 gauge Panel Width: 16 Support: Wood Deck

CBUCK Engineering. Product: Zee-Lock Roof Panel Material: Steel Panel Thickness: 24 gauge Panel Width: 16 Support: Wood Deck Evaluation Report Zee-Lock With Continous Zee-Rib Clip Metal Roof Assembly Manufacturer: 1720 Maury Road Houston, TX 77026 (800) 231-8127 2333 for Florida Product Approval HVHZ # FL 15471.1 Florida Building

More information

FLORIDA PRODUCT APPROVAL GULFRIBTM FLORIDA PRODUCT APPROVAL NO R3. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC.

FLORIDA PRODUCT APPROVAL GULFRIBTM FLORIDA PRODUCT APPROVAL NO R3. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC. 26 Ga. GulfRib Roof Panel over 15/32 Plywood Florida Product Approval #11651.22 R3 Florida Building Code 2017 Per Rule 61G20-3 Method:

More information

SECTION 07530CP EPDM MEMBRANE ROOFING

SECTION 07530CP EPDM MEMBRANE ROOFING PART 1 GENERAL 1.1 SUMMARY SECTION 07530CP EPDM MEMBRANE ROOFING A. Section includes: 1. Adhered membrane roofing and flashing 2. Mechanically fastened roof insulation 3. Walkway pads 1.2 ARCHITECTURAL

More information

Residential, 26 Ga. Roof Panel over 15/32 Plywood. Florida Product Approval # R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D

Residential, 26 Ga. Roof Panel over 15/32 Plywood. Florida Product Approval # R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D Product Evaluation Report REED S METAL, INC. Residential, 26 Ga. Roof Panel over 15/32 Plywood Florida Product Approval # 12725.2 R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D Category: Roofing

More information

B.U.R., Modified & Shingle. Roofing Systems. Section 3 - Low Slope Roofing Installation Instructions

B.U.R., Modified & Shingle. Roofing Systems. Section 3 - Low Slope Roofing Installation Instructions B.U.R., Modified & Shingle Roofing Systems Section 3 - Low Slope Roofing Installation Instructions 3.1 Storage & Handling The following is a list of Malarkey basic requirements for handling and storing

More information

CBUCK Engineering. Evaluation Report Englert Series 500 Metal Roof Assembly Manufacturer: Englert, Inc Amboy Avenue Perth Amboy, NJ

CBUCK Engineering. Evaluation Report Englert Series 500 Metal Roof Assembly Manufacturer: Englert, Inc Amboy Avenue Perth Amboy, NJ Evaluation Report Englert Series 500 Metal Roof Assembly Manufacturer: 1200 Amboy Avenue Perth Amboy, NJ 08862 for Florida Product Approval # FL 11698.2 R3 Florida Building Code 5th Edition (2014) Method:

More information

LEGACY REPORT DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FLUID APPLIED ROOFING REPORT HOLDER: CONKLIN COMPANY INC.

LEGACY REPORT DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FLUID APPLIED ROOFING REPORT HOLDER: CONKLIN COMPANY INC. 0 Most Widely Accepted and Trusted ICC ES Legacy Report ICC ES 000 (800) 42 6587 (562) 699 054 www.icc es.org ER 520 Reissued 09/2017 This report is subject to renewal 09/2018. DIVISION: 07 00 00 THERMAL

More information

SPECIFICATION SUBMITTAL

SPECIFICATION SUBMITTAL 101C AWAPLAN PREMIUM INSULATED DECK TAMKO BASE PLY INSULATION 1/2 m = 50 cm = 19-11/16 inches 1 m = 100 cm = 39-3/8 inches Material Requirements TAMKO GLASS-BASE, TAM-GLASS PREMIUM, TAM- PLY IV, or BASE-N-PLY

More information

1. SUBJECT: DURO-LAST, DURO-TUFF, DURO-FLEECE, and DURO-FLEECE PLUS ROOFING MEMBRANES

1. SUBJECT: DURO-LAST, DURO-TUFF, DURO-FLEECE, and DURO-FLEECE PLUS ROOFING MEMBRANES UL Evaluation Report UL ER10128-01 Issued: January 22, 2016 Revised: September 30, 2017 Visit UL s On-Line Certifications Directory: www.ul.com/erdirectory for current status of Report. UL Category Code:

More information

SECTION STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS MEMBRANE ROOFING

SECTION STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS MEMBRANE ROOFING SECTION 075216 - STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS MEMBRANE ROOFING PART 1 - GENERAL 1.1 SUMMARY A. Section includes styrene-butadiene-styrene (SBS) modified bituminous membrane roofing.

More information

CBUCK Engineering. Evaluation Report Cee Lock Panel Metal Roof Assembly

CBUCK Engineering. Evaluation Report Cee Lock Panel Metal Roof Assembly Specialty Structural Engineering CBUCK, Inc. Certificate of Authorization #8064 Prepared by: James L. Buckner, P.E., S.E.C.B. Florida Professional Engineer # 31242 Florida Evaluation ANE ID: 1916 Project

More information

THE SITUATION WITH STEEL DECKS

THE SITUATION WITH STEEL DECKS THE SITUATION WITH STEEL DECKS Steel roof deck design can affect roof system selection and design by Mark S. Graham 32 www.professionalroofing.net MARCH 2017 teel roof decks commonly are encountered in

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

ANSI/FM Approvals March FM Approvals LLC. All rights reserved.

ANSI/FM Approvals March FM Approvals LLC. All rights reserved. American National Standard for Evaluating the Simulated Wind Uplift Resistance of Roof Assemblies Using Static Positive and/or Negative Differential Pressures ANSI/FM Approvals 4474 March 2004 2004 FM

More information

1 Firestone EPDM Roofing Systems

1 Firestone EPDM Roofing Systems 1 Firestone 1. Firestone EPDM Systems To ensure a long-lasting, trouble-free roof today, it is not sufficient to manufacture high quality roofing membranes. Experience learned that roofing membranes need

More information

A. National Roofing Contractors Association (NRCA) Roofing and Waterproofing Manual

A. National Roofing Contractors Association (NRCA) Roofing and Waterproofing Manual SECTION 07 22 16 - ROOF AND DECK INSULATION Specifier Note: There are numerous types of roof insulation, some which are installed in multiple-layer roof assemblies. Specifier to verify Project requirements

More information

Florida Product Approval # R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D

Florida Product Approval # R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D Product Evaluation Report REED S METALS, INC. Perma-Lok, 26 Ga. 16 Coverage Roof Panel over 15/32 Plywood Florida Product Approval # 12725.1 R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D Category:

More information

1.2 DEFINITIONS, REFERENCES, AND OVERALL STANDARDS Follow 07500

1.2 DEFINITIONS, REFERENCES, AND OVERALL STANDARDS Follow 07500 07503 ROOF ASSEMBLY LIGHTWEIGHT INSULATING CONCRETE (LWIC) ************************************************************************************************************* SPECIFIER: All roof-related items

More information

COMMERCIAL BUILDING APPLICATIONS

COMMERCIAL BUILDING APPLICATIONS EXPANDED POLYSTYRENE FOR COMMERCIAL BUILDING APPLICATIONS www.falconfoam.com Commercial Building Ap Expanded Polystyrene Insulation Falcon Foam leads the commercial building industry with products that

More information

Code Approval Guide. Underwriters Laboratories Factory Mutual. March 2005

Code Approval Guide. Underwriters Laboratories Factory Mutual. March 2005 Code Approval Guide Underwriters Laboratories Factory Mutual March 2005 Versico Incorporated, PO Box 1289, Carlisle, PA 17013 Phone 800-992-7663 Internet Address: http://www.versico.com Code Approval Guide

More information

CBUCK Engineering. Florida Product Approval # FL R2

CBUCK Engineering. Florida Product Approval # FL R2 Specialty Structural Engineering CBUCK, Inc. Certificate of Authorization #8064 Prepared by: James L. Buckner, P.E., SECB Florida Professional Engineer # 31242 Florida Evaluation ANE ID: 1916 Project Manager:

More information

ACFoam-II HCFC Free "Green" Polyiso Specification

ACFoam-II HCFC Free Green Polyiso Specification ACFoam-II HCFC Free "Green" Polyiso Specification To help owners and specifiers, the following specification strategies are offered as they relate to product performance when including HCFC FREE Green

More information

UltraPly TPO SA. Product Information. Description: Membrane Preparation: Method of Application: Item Description

UltraPly TPO SA. Product Information. Description: Membrane Preparation: Method of Application: Item Description Item Description.060" x 5' x 100' White.060" x 10' x 100' White.060" x 5' x 100' Tan.060" x 10' x 100' Tan.060" x 5' x 100' Gray.060" x 10' x 100' - Gray Item Number W56TSA3660 W56TSA3699 W56TSAT660 W56TSAT699

More information

PRODUCT CONTROL SECTION DEPARTMENT OF PERMITTING, ENVIRONMENT, AND REGULATORY

PRODUCT CONTROL SECTION DEPARTMENT OF PERMITTING, ENVIRONMENT, AND REGULATORY MIAMI DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF PERMITTING, ENVIRONMENT, AND REGULATORY 11805 SW 26 Street, Room 208 AFFAIRS (PERA) Miami, Florida 33175 2474 BOARD AND CODE ADMINISTRATION DIVISION

More information

Quality You Can Trust Since From North America s Largest Roofing Manufacturer

Quality You Can Trust Since From North America s Largest Roofing Manufacturer Quality You Can Trust Since 1886... From North America s Largest Roofing Manufacturer Florida Building Code Online http://floridabuilding.org/pr/pr_app_dtl.aspx?param=wgevxqwtdqsxyieb4opodtnwo... Page

More information

CITY OF RICHMOND PINE CAMP COMMUNITY CENTER ROOF REPLACEMENT PROJECT RCS PROJECT NO

CITY OF RICHMOND PINE CAMP COMMUNITY CENTER ROOF REPLACEMENT PROJECT RCS PROJECT NO SECTION 07220 - ROOF INSULATION PART 1 - GENERAL 1.01 DESCRIPTION A. Work included: The Roofing Contractor will provide all polyisocyanurate insulation and high density wood fiber roof insulation (tapered

More information

Recommended Fastening Patterns for Rmax Insulation in Low Slope Roofing Applications

Recommended Fastening Patterns for Rmax Insulation in Low Slope Roofing Applications Recommended Fastening Patterns for Rmax Insulation in Low Slope Roofing Applications INTRODUCTION Rmax recommends that any insulation which is laid over a steel or wood roof deck be attached with mechanical

More information

Design No. P922 September 26, Restrained Assembly Rating 1, 1-1/2 or 2 Hr (See Items 6, 7) Unrestrained Assembly Rating 0 Hr (See Item 6)

Design No. P922 September 26, Restrained Assembly Rating 1, 1-1/2 or 2 Hr (See Items 6, 7) Unrestrained Assembly Rating 0 Hr (See Item 6) Design No. P922 September 26, 2003 Restrained Assembly Rating 1, 1-1/2 or 2 Hr (See Items 6, 7) Unrestrained Assembly Rating 0 Hr (See Item 6) Unrestrained Beam Rating 1, 1-1/2 or 2 Hr (See Item 7) 1.

More information

SECTION CLAY BARREL TILE ROOFING. A. American Society for Testing and Materials (ASTM):

SECTION CLAY BARREL TILE ROOFING. A. American Society for Testing and Materials (ASTM): SECTION 07320 CLAY BARREL TILE ROOFING PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 02072 - Removals. 2. 07600 - Flashing and Sheet Metal. 1.02 REFERENCES A. American Society for Testing and Materials

More information

Design No. P701 October 09, Restrained Assembly Rating 3/4, 1, 1-1/2 or 2 Hr. (See Item 6) Unrestrained Assembly Rating 3/4, 1, 1-1/2 or 2 Hr.

Design No. P701 October 09, Restrained Assembly Rating 3/4, 1, 1-1/2 or 2 Hr. (See Item 6) Unrestrained Assembly Rating 3/4, 1, 1-1/2 or 2 Hr. Design P701 October 09, 2003 Restrained Rating, 1, or 2 Hr. (See Item 6) Rating, 1, or 2 Hr. (See Item 6) Beam Rating 1, or 2 Hr. (See Item 6) Beam W6x16, min size or Steel Joist 12J4, 14J7 or 14K4 min

More information

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

SECTION PREPARATION FOR RE-ROOFING

SECTION PREPARATION FOR RE-ROOFING SECTION 07 01 50.19 PREPARATION FOR RE-ROOFING SPEC WRITER NOTES: 1. Delete text between // // not applicable to project. Edit remaining text to suit project. 2. Edit Summary article below after establishing

More information

Section 7 Waterproofing Roofing Standards

Section 7 Waterproofing Roofing Standards Section 7 Waterproofing Roofing Standards Section 7 Waterproofing Roofing Standards... 1 Purpose... 3 Roofing Assemblies... 3 ASTM Standards... 4 Design considerations... 7 Purpose The purpose of this

More information

LOW SLOPE ROOFING INSTALLATION

LOW SLOPE ROOFING INSTALLATION 4.1 STORAGE & HANDLING The following is a list of Malarkey basic requirements for handling and storing roof insulations, roofing products, and construction materials. Unload, handle and store all roofi

More information

Evaluation Report SkylightTube Tubular Daylight Device

Evaluation Report SkylightTube Tubular Daylight Device Evaluation Report SkylightTube Tubular Daylight Device Manufacturer U.S. Sunlight Corporation 5625 B Brisa Street Livermore, CA 94550 925 271 7614 for Florida Product Approval # FL 14564.1 Florida Building

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COATED FOAM ROOFING REPORT HOLDER: LAPOLLA INDUSTRIES, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COATED FOAM ROOFING REPORT HOLDER: LAPOLLA INDUSTRIES, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3916 Reissued 09/2017 This report is subject to renewal 09/2019. DIVISION: 07 00

More information

PRODUCT CONTROL SECTION

PRODUCT CONTROL SECTION MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T (786)315-2590

More information

ROOF ASSEMBLIES CHAPTER 9

ROOF ASSEMBLIES CHAPTER 9 CHAPTER 9 ROOF ASSEMBLIES SECTION R901 GENERAL R901.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies. SECTION R902 ROOF CLASSIFICATION

More information

PRODUCT CONTROL SECTION

PRODUCT CONTROL SECTION MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T (786) 315-2590

More information

Wood Decks Testing Reveals Best Wood Roof Deck Systems to Resist Wind-Uplift by Fulton Desler, senior engineer, APA The Engineered Wood Association

Wood Decks Testing Reveals Best Wood Roof Deck Systems to Resist Wind-Uplift by Fulton Desler, senior engineer, APA The Engineered Wood Association This article was originally published in Western Roofing January/February 2007 Wood Decks Testing Reveals Best Wood Roof Deck Systems to Resist Wind-Uplift by Fulton Desler, senior engineer, APA The Engineered

More information

Lightweight Insulating Concrete Roof Decks

Lightweight Insulating Concrete Roof Decks MeARlCrEte Tm Lightweight Insulating Concrete Roof Decks WWW.AErIXINDUsTrIEs.COm M EARLCRETETM lightweight insulating concrete is produced on the job site by mixing Portland cement -water slurry with the

More information

ROOF ASSEMBLIES CHAPTER 9

ROOF ASSEMBLIES CHAPTER 9 CHAPTER 9 ROOF ASSEMBLIES > SECTION R901 GENERAL R901.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies. Pursuant to ORS 215.730; if

More information

SECTION CLAY BARREL TILE ROOFING Removals Flashing and Sheet Metal.

SECTION CLAY BARREL TILE ROOFING Removals Flashing and Sheet Metal. SECTION 07320 CLAY BARREL TILE ROOFING PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 02072 - Removals. 2. 07600 - Flashing and Sheet Metal. 1.02 REFERENCES A. American Society for Testing and Materials

More information

Product Evaluation Report of. JELD-WEN, inc. Energy Saver/Contour Wood Edge Opaque Steel Outswing Door w/ or w/o Sidelites

Product Evaluation Report of. JELD-WEN, inc. Energy Saver/Contour Wood Edge Opaque Steel Outswing Door w/ or w/o Sidelites 127 W. Fairbanks Ave. Suite 438 Winter Park, FL 32789 407.644.6957 PH 407.644.2366 FX contact@buildingdrops.com Product Evaluation Report of Energy Saver/Contour Wood Edge Opaque Steel Outswing Door w/

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

3M TM Polyurethane Foam Insulation Adhesive CR-20

3M TM Polyurethane Foam Insulation Adhesive CR-20 3M TM Polyurethane Foam Insulation Adhesive CR-20 Product Data Sheet Product Description Key Features Supersedes: New 3M Polyurethane Foam Insulation Adhesive CR-20 is a two component elastomeric polyurethane

More information

COMMERCIAL WINDSTORM MITIGATION INSPECTION REPORT Prepared for: Boca Vista Condominium Association, Inc th Avenue Madeira Beach, FL 33708

COMMERCIAL WINDSTORM MITIGATION INSPECTION REPORT Prepared for: Boca Vista Condominium Association, Inc th Avenue Madeira Beach, FL 33708 Insurance Appraisals Reserve Studies Wind Mitigation COMMERCIAL WINDSTORM MITIGATION INSPECTION REPORT Prepared for: Boca Vista Condominium Association, Inc. 401 150th Avenue Madeira Beach, FL 33708 As

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 07 5323 - ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

adhered. Membrane: Polyglass, ELASATOFLEX SA V FR, self adhered. Base Sheet: Polyglass ELASTOFLEX SA V FR BASE, self adhered.

adhered. Membrane: Polyglass, ELASATOFLEX SA V FR, self adhered. Base Sheet: Polyglass ELASTOFLEX SA V FR BASE, self adhered. ROOF LISTINGS Foam-Control EPS is used in a wide range of UL Roof Listings, UL Roof Deck Constructions, and UL Hourly Designs. This document provides basic information on the use of Foam-Control EPS products

More information

REPORT HOLDER: CARLISLE SYNTEC POST OFFICE BOX 7000 CARLISLE, PENNSYLVANIA EVALUATION SUBJECT:

REPORT HOLDER: CARLISLE SYNTEC POST OFFICE BOX 7000 CARLISLE, PENNSYLVANIA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1184 Reissued 03/2017 This report is subject to renewal 03/2019. DIVISION: 07 00 00 THERMAL

More information

SECTION THERMOPLASTIC POLYOLEFIN (TPO) MEMBRANE ROOFING (Over Metal) A. Thermoplastic Polyolefin Membrane Roofing over metal decking.

SECTION THERMOPLASTIC POLYOLEFIN (TPO) MEMBRANE ROOFING (Over Metal) A. Thermoplastic Polyolefin Membrane Roofing over metal decking. SECTION 07556 THERMOPLASTIC POLYOLEFIN (TPO) MEMBRANE ROOFING (Over Metal) PART 1 - GENERAL 1.01 SUMMARY A. Thermoplastic Polyolefin Membrane Roofing over metal decking. B. Membrane Flashings. C. Metal

More information

Mechanically Fastened Guide Specification

Mechanically Fastened Guide Specification 1.0 General 1.01 Description A. Scope 1. Furnish and install a JM TPO Roofing Membrane with flashings and all other incidental and accessory items to comprise a roofing system. 2. All work shall be in

More information