Evaluation and Repair of Post-Tensioned Concrete

Size: px
Start display at page:

Download "Evaluation and Repair of Post-Tensioned Concrete"

Transcription

1 Evaluation and Repair of Post-Tensioned Concrete Tank and Thin Shell Roof by Keith Kesner, Ph.D., PE P.E. Randall W. Poston, Ph.D., P.E. (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 1 of 24

2 Post-Tensioned Structures Corrosion Evaluation - Thin Shell Roof Bonded reinforcement electrochemical methods Unbonded reinforcement limited assessment methods Repair Design Concrete Tank Maintain integrity of existing structure Existing i PT needs to be considered d (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 2 of 24

3 Thin Shell Evaluation (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 3 of 24

4 Thin Shell Evaluation Concrete shell structure Hyperbolic paraboloid 5 inch thick shell Post-tensioned perimeter beams 30 Years Old Water leakage Staining Corrosion?? Post-tensioning system?? (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 4 of 24

5 Thin Shell Evaluation (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 5 of 24

6 Corrosion Assessment Electro-chemical methods Measure electrical activity associated with corrosion process Half-cell potential (ASTM C876) Concrete resistivity Corrosion rate (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 6 of 24

7 Corrosion Assessment Half-cell potential (ASTM C876) When bar is corroding, charge flow through concrete is associated with an electrical field Measure the electrical potential (voltage) of the field at the concrete surface Magnitude of the measured voltage, relative to a standard half-cell, is indicative of corrosion activity Provides only indication of likelihood of active corrosion (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 7 of 24

8 Corrosion Assessment Concrete resistivity Rate of corrosion is controlled by ease with which ions move from anodic to cathodic sites Concrete resistivity is, therefore, an important factor in rate of corrosion Resistivity, ρ Numerically equal to resistance, R, of a unit cube of material R = ρ L A (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 8 of 24

9 Corrosion Assessment Polarization resistance Measure of corrosion current Based upon evaluation of polarization resistance of reinforcing bar Allows measurement of rate of corrosion (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 9 of 24

10 Thin Shell Evaluation Corrosion testing on 3 bad and 2 good shells Assess reinforcement condition Materials testing Electro-chemical corrosion measurements Analysis Model effect of corrosion damage Evaluate reserve capacity (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 10 of 24

11 Thin Shell Evaluation Results Bad Shells Shell Corrosion Potential (mv) Resistivity (Ohm-cm) Corrosion Rate (μa/cm 2 ) 1 High Average 2 Low Average 3 High Average , ,000 1,000, , Average value from three tests at locations with highest corrosion potentials 2.Average of 84, 42 and 90 individual tests on Shells 1, 5 and 6, respectively 3.Average of 56, 42 and 90 individual tests on Shells 1, 5 and 6, respectively (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 11 of 24

12 Thin Shell Evaluation Probe Openings Verify integrity of strands Evaluate grease condition (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 12 of 24

13 Thin Shell Evaluation Electrochemical Isolated corrosion damage expected based upon corrosion rates in bad shells No chlorides or carbonation Good shells high concrete resistivity Post-tensioningtensioning Water intrusion apparent Strands intact (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 13 of 24

14 Thin Shell Summary Summary Isolated corrosion damage likely in 2 to 5 years Generally high resistivity (dry) concrete No accelerating factors Repair recommendations Address water leakage Isolated repairs to deck supports Corrosion inhibitor Grease reinjection (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 14 of 24

15 Wire Wrapped Tank Dome ring failure (1 of 3 surge tanks) Dome ring added to original design Accommodate dome installation (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 15 of 24

16 Wire Wrapped Tank Dome ring failure (1 of 3 surge tanks) Water intrusion and lack of bond Lack of positive connection (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 16 of 24

17 Wire Wrapped Tank Dome ring failure (1 of 3 surge tanks) Water intrusion and lack of bond Lack of positive connection (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 17 of 24

18 Wire Wrapped Tank Corrosion damage Brittle failure of wires (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 18 of 24

19 Wire Wrapped Tank Analysis Two Cases Failed dome ring Intact dome ring Loading and Geometry Inside diameter: 150 ft Wall height: 26.2 ft Wall thickness: 6.5 in Dome radius: 195 ft Dome thickness: 4 in Capacity: 3.3 MG (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 19 of 24

20 Wire Wrapped Tank Evaluation results failed dome ring Dead load only - unfilled Dome thrust ~ 4.7 kip / ft. circ. Prestress in top 4 ft. of tank resists dome thrust Prestress ~ 1.2 kip / ft. circ. Options need to replace dome ring External post-tensioning Waterproofing limit further corrosion (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 20 of 24

21 Wire Wrapped Tank Evaluation results intact dome ring Original design was adequate Stresses are within limits Repair options External post-tensioning tensioning Supplement existing dome ring Waterproofing limit further corrosion (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 21 of 24

22 External PR Repair Details (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 22 of 24

23 Wire Wrapped Tank External post-tensioning Staged allow limited use during repair Retrofit angles increase dome ring support (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 23 of 24

24 Summary Evaluation Methods Bonded reinforcement Electro-chemical Unbonded reinforcement More limited, more conservative Repair Options Consider stresses Worker safety Prevent cracking Limit water ingress (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 24 of 24

Evaluation of Corrosion Damage in Unbonded Post-Tensioned Concrete Structures:

Evaluation of Corrosion Damage in Unbonded Post-Tensioned Concrete Structures: Evaluation of Corrosion Damage in Unbonded Post-Tensioned Concrete Structures: Misunderstandings, Misinformation and Moving Forward by Keith Kesner Randall W. Poston Introduction 16 Years Ago Corrosion

More information

EVALUATION & REPAIR OF CORROSION DAMAGED ROOF LIFT SLAB WITH WIRE POST-TENSIONING SYSTEM (BUTTON HEADS)

EVALUATION & REPAIR OF CORROSION DAMAGED ROOF LIFT SLAB WITH WIRE POST-TENSIONING SYSTEM (BUTTON HEADS) EVALUATION & REPAIR OF CORROSION DAMAGED ROOF LIFT SLAB WITH WIRE POST-TENSIONING SYSTEM (BUTTON HEADS) (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHT RESERVED 1 of 23 The following presentation discusses

More information

Condition of US Bridges and Present Corrosion Technologies Used for Bridge Structures

Condition of US Bridges and Present Corrosion Technologies Used for Bridge Structures Condition of US Bridges and Present Corrosion Technologies Used for Bridge Structures Seung-Kyoung Lee 1 and Paul Virmani 2 1. SK Lee & Associates, Inc. 2. Federal Highway Administration Workshop on Corrosion

More information

1. CORROSION OF REINFORCEMENT

1. CORROSION OF REINFORCEMENT MAB 1033 Structural Assessment and Repair 1. CORROSION OF REINFORCEMENT Professor Dr. Mohammad bin Ismail C09-313 Learning Outcome At the end of the course students should be able to understand Mechanism

More information

9.6 Circular Prestressing

9.6 Circular Prestressing 9.6 Circular Prestressing This section covers the following topics. Introduction General Analysis and Design Prestressed Concrete Pipes Liquid Storage Tanks Ring Beams Conclusion 9.6.1 Introduction When

More information

TECHNIACL SPECIAL PROVISION FOR NON-STRUCTURAL AND STRUCTURAL INTEGRAL PILE JACKET WITH SACRIFICIAL CATHODIC PROTECTION

TECHNIACL SPECIAL PROVISION FOR NON-STRUCTURAL AND STRUCTURAL INTEGRAL PILE JACKET WITH SACRIFICIAL CATHODIC PROTECTION TECHNIACL SPECIAL PROVISION FOR NON-STRUCTURAL AND STRUCTURAL INTEGRAL PILE JACKET WITH SACRIFICIAL CATHODIC PROTECTION Financial Project ID 429140-1-52-01, 429140-2-52-01 & 428267-1-52-01 The official

More information

NDT in Grouted PT Inspection for Bridges

NDT in Grouted PT Inspection for Bridges NDT in Grouted PT Inspection for Bridges PTI Technical Conference & Exhibition Miami, FL May 8, 2007 Hong-gang gang Cao CTLGroup (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 1 of 37

More information

Assessment of Long-Time Behavior for Bridge Girders Retrofitted with Fiber Reinforced Polymer

Assessment of Long-Time Behavior for Bridge Girders Retrofitted with Fiber Reinforced Polymer Journal of Civil Engineering and Architecture 9 (2015) 1034-1046 doi: 10.17265/1934-7359/2015.09.003 D DAVID PUBLISHING Assessment of Long-Time Behavior for Bridge Girders Retrofitted with Fiber Reinforced

More information

Evaluation and Repair of Existing Post- Tensioned Buildings with Paper Wrapped Tendons Experiencing Corrosion Damage

Evaluation and Repair of Existing Post- Tensioned Buildings with Paper Wrapped Tendons Experiencing Corrosion Damage Evaluation and Repair of Existing Post- Tensioned Buildings with Paper Wrapped Tendons Experiencing Corrosion Damage K. Dirk Bondy, S.E. President Seneca Structural Engineering, Inc. The Great American

More information

MONITORING CORROSION ACTIVITY IN CHLORIDE CONTAMINATED CONCRETE WRAPPED WITH FIBER REINFORCED PLASTICS. Abstract. Introduction

MONITORING CORROSION ACTIVITY IN CHLORIDE CONTAMINATED CONCRETE WRAPPED WITH FIBER REINFORCED PLASTICS. Abstract. Introduction MONITORING CORROSION ACTIVITY IN CHLORIDE CONTAMINATED CONCRETE WRAPPED WITH FIBER REINFORCED PLASTICS Emily W. Berver, James. O. Jirsa, Ph.D., David. W. Fowler, Ph.D., and Harovel. G. Wheat, Ph.D., The

More information

Elimination of Deck Joints Using a Corrosion Resistant FRP Approach

Elimination of Deck Joints Using a Corrosion Resistant FRP Approach Elimination of Deck Joints Using a Corrosion Resistant FRP Approach Louisiana Transportation Conference February 2009 Aziz Saber, Ph.D., P.E. Chair of Civil Engineering Louisiana Tech University LTRC LA

More information

PRESTRESSED CONCRETE STRUCTURES. Amlan K. Sengupta, PhD PE Department of Civil Engineering, Indian Institute of Technology Madras

PRESTRESSED CONCRETE STRUCTURES. Amlan K. Sengupta, PhD PE Department of Civil Engineering, Indian Institute of Technology Madras PRESTRESSED CONCRETE STRUCTURES Amlan K. Sengupta, PhD PE Department of Civil Engineering, Indian Institute of Technology Madras Module 9: Special Topics Lecture 40: Circular Prestressing, Conclusion Welcome

More information

1. Cast-in-place concrete is specified in Section

1. Cast-in-place concrete is specified in Section SECTION 03 38 00 PART 1 - GENERAL 1.01 DESCRIPTION A. This Section describes the requirements for furnishing and installing post-tensioned slabs, jacks, jacking and anchors at Parking Structure, and record

More information

PRESENTED AT NATIONAL BRIDGE PRESERVATION PARTNERSHIP CONFERENCE ORLANDO, FLORIDA 2014 AUTHORS ROBERT WALDE, SURTREAT HOLDING, LLC PRESENTER RICH

PRESENTED AT NATIONAL BRIDGE PRESERVATION PARTNERSHIP CONFERENCE ORLANDO, FLORIDA 2014 AUTHORS ROBERT WALDE, SURTREAT HOLDING, LLC PRESENTER RICH PRESENTED AT NATIONAL BRIDGE PRESERVATION PARTNERSHIP CONFERENCE ORLANDO, FLORIDA 2014 AUTHORS ROBERT WALDE, SURTREAT HOLDING, LLC PRESENTER RICH LAMPO, U.S. ARMY CORPS OF ENGINEERS RESEARCH LABORATORY

More information

Corrosion Monitoring of Steel Bars in Port Concrete Structures

Corrosion Monitoring of Steel Bars in Port Concrete Structures Corrosion Monitoring of Steel Bars in Port Concrete Structures Mitsuyasu IWANAMI 1*, Ema KATO 2, Yuichiro KAWABATA 2, Takahiro NISHIDA 1 1 Tokyo Institute of Technology, Japan 2 Port and Airport Research

More information

Corrosion Mitigation Systems for Concrete Structures

Corrosion Mitigation Systems for Concrete Structures Corrosion Mitigation Systems for Concrete Structures By J. Christopher Ball and David W. Whitmore According to a recently completed study by the U.S. Federal Highway Administration, the annual direct cost

More information

PRODUCT DATA SHEET Sika FerroGard -675

PRODUCT DATA SHEET Sika FerroGard -675 PRODUCT DATA SHEET DISCRETE EMBEDDED GALVANIC ANODE PRODUCT DESCRIPTION is a zinc based discrete sacrificial anode placed inside a concrete repair area in reinforced concrete structures which are corroding

More information

Bridge Preservation Corrosion Mitigation Option in Concrete Repair Systems

Bridge Preservation Corrosion Mitigation Option in Concrete Repair Systems Bridge Preservation Corrosion Mitigation Option in Concrete Repair Systems September 29, 2010 Northeast Bridge Preservation Partnership Meeting TSP-2 TODAY WE WILL DISCUSS Corrosion of Bridge Decks Surface

More information

Corrosion Performance of Prestressing Strands in Contact with Dissimilar Grouts

Corrosion Performance of Prestressing Strands in Contact with Dissimilar Grouts Report No. KS-12-4 FINAL REPORT January 2013 Corrosion Performance of Prestressing Strands in Contact with Dissimilar Grouts Matthew O Reilly, Ph.D. David Darwin, Ph.D., P.E. JoAnn Browning, Ph.D., P.E.

More information

REFURBISHMENT Sika FerroGard GALVANIC AND HYBRID ANODE TECHNOLOGIES

REFURBISHMENT Sika FerroGard GALVANIC AND HYBRID ANODE TECHNOLOGIES Sika FerroGard GALVANIC AND HYBRID ANODE TECHNOLOGIES CONCRETE CORROSION CONTROLLED FOR UP TO 50 YEARS REDUCING MAINTENANCE COSTS AND EXTENDING THE LIFE OF REINFORCED CONCRETE REINFORCED CONCRETE IS A

More information

European Standard En 1504

European Standard En 1504 BS EN 1504 Products and Systems for the protection and repair of concrete structures Definitions, requirements, quality control and evaluation of conformity John Drewett Concrete Repairs Ltd 25% of the

More information

Seismic Behavior of Low Strength RC Columns with Corroded Plain Reinforcing Bars

Seismic Behavior of Low Strength RC Columns with Corroded Plain Reinforcing Bars Seismic Behavior of Low Strength RC Columns with Corroded Plain Reinforcing Bars C. Goksu 1, B. Demirtas 2, C. Demir 1, A. Ilki 3 and N. Kumbasar 4 1 PhD Candidate, Civil Engineering Faculty, Istanbul

More information

The Assessment of Concrete Structures affected by Steel Corrosion

The Assessment of Concrete Structures affected by Steel Corrosion THE HIGHWAYS AGENCY BA 51/95 THE SCOTTISH OFFICE DEVELOPMENT DEPARTMENT THE WELSH OFFICE Y SWYDDFA GYMREIG THE DEPARTMENT OF THE ENVIRONMENT FOR NORTHERN IRELAND The Assessment of Concrete Structures affected

More information

CONSTRUCTION PROCEDURES. AWWA D110 Type I Prestressed Concrete Tanks

CONSTRUCTION PROCEDURES. AWWA D110 Type I Prestressed Concrete Tanks CONSTRUCTION PROCEDURES AWWA D110 Type I Prestressed Concrete Tanks 2-3 4-5 6-7 8-9 10-11 12-13 14-15 16-17 Site Preparation Floor & Footings Wall Construction Roof Options Vertical Prestressing Abrasive

More information

PERFORMANCE OF AN IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM FOR A REINFORCED CONCRETE TANK

PERFORMANCE OF AN IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM FOR A REINFORCED CONCRETE TANK PERFORMANCE OF AN IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM FOR A REINFORCED CONCRETE TANK Dr. S. Ehtesham Hussain & Dr. Hamed A. Al-Ghamdi (Hamed Al-Ghamdi Consulting Engineers (CONTEC) Khobar, Saudi

More information

GUIDELINES FOR EXECUTION OF ADAPT-PT 1

GUIDELINES FOR EXECUTION OF ADAPT-PT 1 Structural Concrete Software System GUIDELINES FOR EXECUTION OF ADAPT-PT 1 Update: December 09, 2004 TN172 guide_to_run_pt_12 120904 The guidelines presented will assist you in the selection of design

More information

SPECIAL SPECIFICATION 4401 Prestressed Ground Anchors

SPECIAL SPECIFICATION 4401 Prestressed Ground Anchors 2004 Specifications CSJ 0581-02-121 & 0200-11-100 SPECI SPECIFICATION 4401 Prestressed Ground Anchors 1. Description. Install post-tensioned permanent ground anchors in place, with grouting as required

More information

Effects of Corrosion on Reinforced Concrete Beams with Silica Fume and Polypropylene Fibre

Effects of Corrosion on Reinforced Concrete Beams with Silica Fume and Polypropylene Fibre Effects of Corrosion on Reinforced Concrete Beams with Silica Fume and Polypropylene Fibre S.Shanmugam, V.G. Srisanthi, and S.Ramachandran Abstract Reinforced concrete has good durability and excellent

More information

ACI MANUAL OF CONCRETE PRACTICE-2009

ACI MANUAL OF CONCRETE PRACTICE-2009 ACI MANUAL OF CONCRETE PRACTICE-2009 The ACI Manual of Concrete Practice is a six-part compilation of current ACI standards and committee reports. -ACI117-06 to ACI224.3R-95(08) Part 2-ACI 225-99(05) to

More information

When the Unexpected Occurs: Tendon Failures in the Construction of a New 2 MG Prestressed Concrete Reservoir

When the Unexpected Occurs: Tendon Failures in the Construction of a New 2 MG Prestressed Concrete Reservoir When the Unexpected Occurs: Tendon Failures in the Construction of a New 2 MG Prestressed Concrete Reservoir Nancy Kraushaar, P.E., Oregon City Patrick Van Duser, P.E., Black & Veatch Presentation Overview

More information

Rusty Boicourt, P.G. NDE & Materials Specialist Materials Testing & Inspection

Rusty Boicourt, P.G. NDE & Materials Specialist Materials Testing & Inspection Corrosion Damaged Concrete Causes & Repair Presented by Rusty Boicourt, P.G. NDE & Materials Specialist Materials Testing & Inspection Examples of Corrosion Damage Examples of Corrosion Damage Examples

More information

TECHNICAL ASSISTANCE REPORT EFFECT OF CONCRETE REMOVAL EQUIPMENT AND METHODS ON THE CONDITION OF DECK CONCRETE LEFT IN PLACE

TECHNICAL ASSISTANCE REPORT EFFECT OF CONCRETE REMOVAL EQUIPMENT AND METHODS ON THE CONDITION OF DECK CONCRETE LEFT IN PLACE TECHNICAL ASSISTANCE REPORT EFFECT OF CONCRETE REMOVAL EQUIPMENT AND METHODS ON THE CONDITION OF DECK CONCRETE LEFT IN PLACE Michael M. Sprinkel, P.E. Research Manager (The opinions, findings, and conclusions

More information

Post-Tech PTI Impregnation System. Corrosion Protection System for Bonded Post-Tension Tendons

Post-Tech PTI Impregnation System. Corrosion Protection System for Bonded Post-Tension Tendons Post-Tech PTI Impregnation System Corrosion Protection System for Bonded Post-Tension Tendons Post-Tech PTI Impregnation System Corrosion Protection System for Bonded Post-Tension Tendons Post-Tech PTI

More information

Corrosion Investigation for Contra Costa Community College District - Brentwood Campus

Corrosion Investigation for Contra Costa Community College District - Brentwood Campus August 2, 2017 Ref AJ 2017-032 RMA Group, Inc. 3150 Fitzgerald Rd. Rancho Cordova, CA 95742 Attn: Mr. Josh Summers, PE Subject: Corrosion Investigation for Contra Costa Community College District - Brentwood

More information

5. CONCLUSIONS, RECOMMENDATIONS, COST ESTIMATES

5. CONCLUSIONS, RECOMMENDATIONS, COST ESTIMATES 5. CONCLUSIONS, RECOMMENDATIONS, COST ESTIMATES 5.1 CONCLUSIONS In general, Pier 40 is in overall Poor condition. The allowable uniform live load rating for the pier has been significantly reduced from

More information

STRENGTHENING OF UNBONDED POST-TENSIONED CONCRETE SLABS USING EXTERNAL FRP COMPOSITES

STRENGTHENING OF UNBONDED POST-TENSIONED CONCRETE SLABS USING EXTERNAL FRP COMPOSITES STRENGTHENING OF UNBONDED POST-TENSIONED CONCRETE SLABS USING EXTERNAL FRP COMPOSITES F. El M e s k i 1 ; M. Harajli 2 1 PhD student, Dept. of Civil and Environmental Engineering, American Univ. of Beirut;

More information

TECHNIQUES, MATERIALS AND DESIGN CONSIDERATIONS: REHABILITATION & STRENGTHENING OF WATER AND WASTEWATER PIPELINES. Solutions & Case Studies

TECHNIQUES, MATERIALS AND DESIGN CONSIDERATIONS: REHABILITATION & STRENGTHENING OF WATER AND WASTEWATER PIPELINES. Solutions & Case Studies TECHNIQUES, MATERIALS AND DESIGN CONSIDERATIONS: REHABILITATION & STRENGTHENING OF WATER AND WASTEWATER PIPELINES Solutions & Case Studies Mike Larsen Senior Manager Pipeline Solutions 972-210-9511 mlarsen@structuraltec.com

More information

WHAT ABOUT STRAY CURRENTS WITH STEEL FIBRE REINFORCED CONCRETE

WHAT ABOUT STRAY CURRENTS WITH STEEL FIBRE REINFORCED CONCRETE Dramix WHAT ABOUT STRAY CURRENTS WITH STEEL FIBRE REINFORCED CONCRETE Stray Currents: Definition (1) Stray currents arise from rail transit systems, cathodic protection systems, or high-voltage power lines.

More information

3. INSPECTION FINDINGS

3. INSPECTION FINDINGS 3. INSPECTION FINDINGS Pier 40 is in overall Poor condition with 22% of the H-piles rated Major and 35% of the H-piles rated Severe, primarily due to severe corrosion within the splash zone at the top

More information

ORGANOFUNCTIONAL SILANE CORROSION INHIBITOR SURFACE TREATMENT OF CONCRETE TO MITIGATE CORROSION DUE TO CHLORIDES OR CARBONATION ABSTRACT

ORGANOFUNCTIONAL SILANE CORROSION INHIBITOR SURFACE TREATMENT OF CONCRETE TO MITIGATE CORROSION DUE TO CHLORIDES OR CARBONATION ABSTRACT Paper No. 9130 ORGANOFUNCTIONAL SILANE CORROSION INHIBITOR SURFACE TREATMENT OF CONCRETE TO MITIGATE CORROSION DUE TO CHLORIDES OR CARBONATION Neal S. Berke, Ph.D., FNACE Tourney Consulting Group, LLC

More information

Hickam Air Force Base Headquarters

Hickam Air Force Base Headquarters Hickam Air Force Base Headquarters Crawl-space Column Repairs and Corrosion Mitigation By Tore O. Arnesen and J. Christopher Ball The Hickam Air Force Base Headquarters Pacific Air Forces (PACAF) Building

More information

Silicon Valley Mid-Summer Emergency: Santa Clara Addresses Peak-Demand Repair of 96-inch Pipeline Mike Larsen Anna Pridmore, PhD, PE

Silicon Valley Mid-Summer Emergency: Santa Clara Addresses Peak-Demand Repair of 96-inch Pipeline Mike Larsen Anna Pridmore, PhD, PE Silicon Valley Mid-Summer Emergency: Santa Clara Addresses Peak-Demand Repair of 96-inch Pipeline Mike Larsen Anna Pridmore, PhD, PE BACKGROUND Santa Clara Valley Water District: Primary Water Source for

More information

SECTION 1 INTRODUCTION TO POST-TENSIONED CONCRETE DEVELOPED BY THE PTI EDC-130 EDUCATION COMMITTEE

SECTION 1 INTRODUCTION TO POST-TENSIONED CONCRETE DEVELOPED BY THE PTI EDC-130 EDUCATION COMMITTEE SECTION 1 INTRODUCTION TO POST-TENSIONED CONCRETE DEVELOPED BY THE PTI EDC-130 EDUCATION COMMITTEE NOTE: MOMENT DIAGRAM CONVENTION In PT design, it is preferable to draw moment diagrams to the tensile

More information

SUNSHINE SKYWAY BRIDGE

SUNSHINE SKYWAY BRIDGE SUNSHINE SKYWAY BRIDGE Retrofit of the Post-Tensioned Precast Transition Pier Columns on the Sunshine Skyway Bridge Presented by: Antonio Ledesma, P.E. May 7, 2012 SUNSHINE SKYWAY BRIDGE, FLORIDA Presentation

More information

Atkinson Engineering, Inc.

Atkinson Engineering, Inc. Atkinson Engineering, Inc. Atkinson Engineering, Inc. One of the problems in underpinning a typical post-tensioned foundation is support for the slab part that spans between the stiffening beams. An example

More information

Repairs to the Primary Tanks at a Wastewater Treatment Plant

Repairs to the Primary Tanks at a Wastewater Treatment Plant Repairs to the Primary Tanks at a Wastewater Treatment Plant Edited by Kelly M. Page As part of the City of Grand Rapids, Michigan, Capital Improvement Plan, the city required an assessment of the condition

More information

Comprehensive condition assessment program on the fire damaged structure a project case in Singapore

Comprehensive condition assessment program on the fire damaged structure a project case in Singapore Comprehensive condition assessment program on the fire damaged structure a project case in Singapore Gunawan Budi Wijaya 1,* 1 Petra Christian University, Department of Civil Engineering, Indonesia Abstract.

More information

Column: Part 2 Courtesy of Dr. Latifee s IMI research group, Text books and others

Column: Part 2 Courtesy of Dr. Latifee s IMI research group, Text books and others Column: Part 2 Courtesy of Dr. Latifee s IMI research group, Text books and others Design for Axial Load: With negligible moment and considerable amount of concentric axial load, failure occurs when the

More information

Guidelines for the Design of Post-Tensioned Floors

Guidelines for the Design of Post-Tensioned Floors 5.2 Guidelines for the Design of Post-Tensioned Floors BY BIJAN O. AALAMI AND JENNIFER D. JURGENS his article presents a set of guidelines intended to T assist designers in routine post-tensioning design,

More information

SPECIAL SPECIFICATION 4492 Tie Back Anchors

SPECIAL SPECIFICATION 4492 Tie Back Anchors 2004 Specifications CSJ 0504-02-022 SPECI SPECIFICATION 4492 Tie Back Anchors 1. Description. This Item shall govern for the installation of tie-back anchors in place, with grouting as required in accordance

More information

TECHNICAL SPECIAL PROVISION FOR CONCRETE REPAIRS. Financial Project ID , &

TECHNICAL SPECIAL PROVISION FOR CONCRETE REPAIRS. Financial Project ID , & TECHNICAL SPECIAL PROVISION FOR CONCRETE REPAIRS Financial Project ID 429140-1-52-01, 429140-2-52-01 & 428267-1-52-01 The official record of this Technical Special Provision is the electronic file signed

More information

CORROSION MITIGATION OF PRECAST CONCRETE PARKING GARAGES

CORROSION MITIGATION OF PRECAST CONCRETE PARKING GARAGES CORROSION MITIGATION OF PRECAST CONCRETE PARKING GARAGES BY TORE O. ARNESEN AND LEO WHITELEY Fig. 1: Typical precast parking garage The use of precast concrete for constructing parking garages is very

More information

Designing Bridges for a 100-year Service Life. TEAM Conference 2016

Designing Bridges for a 100-year Service Life. TEAM Conference 2016 Designing Bridges for a 100-year Service Life Presented at TEAM Conference 2016 By Siva Venugopalan Principal Engineer Siva Corrosion Services, Inc siva@sivacorrosion.com In This Presentation Brief Introduction

More information

Galvanic Cathodic Protection of Concrete Structures. David Whitmore, P.Eng., FCSCE Vector Corrosion Technologies

Galvanic Cathodic Protection of Concrete Structures. David Whitmore, P.Eng., FCSCE Vector Corrosion Technologies Galvanic Cathodic Protection of Concrete Structures David Whitmore, P.Eng., FCSCE Vector Corrosion Technologies Concrete Repair Process Cause & Effect Repair required? YES Condition Survey Repair Analysis

More information

Topic Outline. Two Stage Analysis Procedure: Podium Design. Part 2: Rigid Lower Portion Philip Miller, S.E. 2/8/2018

Topic Outline. Two Stage Analysis Procedure: Podium Design. Part 2: Rigid Lower Portion Philip Miller, S.E. 2/8/2018 Two Stage Analysis Procedure: Podium Design Part 2: Rigid Lower Portion Philip Miller, S.E. Topic Outline Types of Podium Construction Example Buildings PT Basics PT Analysis Modeling Tips Load Balancing

More information

Post-tensioned Structures Solutions for Repair and Protection

Post-tensioned Structures Solutions for Repair and Protection Post-tensioned Structures Solutions for Repair and Protection Concrete Preservation Alliance Vector Construction, Vector Corrosion Technologies, and Vector Corrosion Services are working to advance the

More information

PRO S AND CON S OF HALF-CELL POTENTIALS AND CORROSION RATE MEASUREMENTS

PRO S AND CON S OF HALF-CELL POTENTIALS AND CORROSION RATE MEASUREMENTS PRO S AND CON S OF HALF-CELL POTENTIALS AND CORROSION RATE MEASUREMENTS Thomas Frølund Oskar Klinghoffer Henrik E. Sørensen Germann Instruments A/S Force Technology Force Technology Emdrupvej 102 Park

More information

Corrosion Evaluation of Post-Tensioned Tendons on Mid-Bay Bridge

Corrosion Evaluation of Post-Tensioned Tendons on Mid-Bay Bridge Corrosion Evaluation of Post-Tensioned Tendons on Mid-Bay Bridge by Siva Venugopalan Principal SCS, Inc. siva007@verizon.net (610) 692-6551 6551 March 7, 2007 Count on Concrete for Performance Slide 1

More information

A SIMPLIFIED METHOD TO ESTIMATE CORROSION RATES A NEW APPROACH BASED ON INVESTIGATIONS OF MACROCELLS Method to estimate corrosion rates

A SIMPLIFIED METHOD TO ESTIMATE CORROSION RATES A NEW APPROACH BASED ON INVESTIGATIONS OF MACROCELLS Method to estimate corrosion rates A SIMPLIFIED METHOD TO ESTIMATE CORROSION RATES A NEW APPROACH BASED ON INVESTIGATIONS OF MACROCELLS Method to estimate corrosion rates M. RAUPACH, Schiessl & Raupach, Consulting & Engineering, Aachen,

More information

The past and present in concrete repair Members response: Consultant s perspective

The past and present in concrete repair Members response: Consultant s perspective The past and present in concrete repair Members response: Consultant s perspective Geir Horrigmoe Norut Technology, Norway geir@tek.norut.no CONREPNET Members Workshop, Prague, 22 June 2005 Performances

More information

Introduction to Structural Analysis TYPES OF STRUCTURES LOADS AND

Introduction to Structural Analysis TYPES OF STRUCTURES LOADS AND AND Introduction to Structural Analysis TYPES OF STRUCTURES LOADS INTRODUCTION What is the role of structural analysis in structural engineering projects? Structural engineering is the science and art

More information

Intermountain Section AWWA Conference - 2.0MG Layton Water Tank. Jake O Brien

Intermountain Section AWWA Conference - 2.0MG Layton Water Tank. Jake O Brien Intermountain Section AWWA Conference - 2.0MG Layton Water Tank Jake O Brien Presentation Outline Layton City s decision process Tank Design/Construction Tendon Tanks - don t shed the good stuff Layton

More information

ASSESSMENT, REPAIR AND MONITORING OF THE GENTILLY-1 CONCRETE CONTAINMENT STRUCTURE

ASSESSMENT, REPAIR AND MONITORING OF THE GENTILLY-1 CONCRETE CONTAINMENT STRUCTURE ASSESSMENT, REPAIR AND MONITORING OF THE GENTILLY-1 CONCRETE CONTAINMENT STRUCTURE A.A. Khan, M. Gray, B. Shenton, D. Panesar and M. Elgohary Atomic Energy of Canada Limited, Mississauga, Ontario, Canada

More information

THE FORENSIC MEDICAL CENTER

THE FORENSIC MEDICAL CENTER THE FORENSIC MEDICAL CENTER Image courtesy of Gaudreau, Inc. TECHNICAL REPORT #2 OCTOBER 26, 2007 KEENAN YOHE STRUCTURAL OPTION DR. MEMARI FACULTY ADVISOR EXECUTIVE SUMMARY Image courtesy of Gaudreau,

More information

Refining Corrosion Technologist NACE-RCT-001

Refining Corrosion Technologist NACE-RCT-001 Refining Corrosion Technologist NACE-RCT-001 NACE Cathodic Protection Specialist (CP 4) Essay Exam Exam Preparation Guide March 2018 Copyright 2016 by NACE International Institute. All rights reserved.

More information

REPAIR OF DRAPED MESH CONCRETE SLABS

REPAIR OF DRAPED MESH CONCRETE SLABS REPAIR OF DRAPED MESH CONCRETE SLABS BY KIRK M. STAUFFER AND KEVIN C. POULIN D raped mesh concrete slabs (supported by hotrolled steel beams and girders) were one of the most prevalent one-way floor slab

More information

Repair Application Procedures

Repair Application Procedures Repair Application Procedures I CRI s mission is:... to be a leading resource for education and information to improve the quality of repair, restoration, and protection of concrete and other structures.

More information

HALF-CELL POTENTIAL MEASUREMENTS TO ASSESS CORROSION RISK OF REINFORCEMENT STEELS IN A PC BRIDGE

HALF-CELL POTENTIAL MEASUREMENTS TO ASSESS CORROSION RISK OF REINFORCEMENT STEELS IN A PC BRIDGE HALF-CELL POTENTIAL MEASUREMENTS TO ASSESS CORROSION RISK OF REINFORCEMENT STEELS IN A PC BRIDGE Eisuke Nakamura (1), Hiroshi Watanabe (1), Hirohisa Koga (1), Masayuki Nakamura (2) and Kazuhiro Ikawa (2)

More information

Marina Coast Water District Marina, CA Steel Reservoir #2

Marina Coast Water District Marina, CA Steel Reservoir #2 WATER TANK INSPECTION REPORT Prepared for the Marina Coast Water District Marina, CA Steel Reservoir #2 October 26, 2005 490 Industrial Park Road Deep River, CT 06417 Tel: (860) 526-2610 Fax:(860) 526-5018)

More information

GERMANN INSTRUMENTS. GalvaPulse. for Corrosion Rate, Half-Cell Potentials and Electrical Resistance

GERMANN INSTRUMENTS. GalvaPulse. for Corrosion Rate, Half-Cell Potentials and Electrical Resistance GERMANN INSTRUMENTS GalvaPulse for Corrosion Rate, Half-Cell Potentials and Electrical Resistance 1. Background The galvanostatic pulse technique was introduced for field application in 1988, ref. (1),

More information

Concrete Parking Garage Degradation

Concrete Parking Garage Degradation Concrete Parking Garage Degradation Concrete Parking Garage Degradation With proper care and maintenance, the life of a concrete parking garage can span several decades. The integrity and strength of structural

More information

Effect Of Age And Concrete Cover Thickness On Steel Reinforcement Corrosion At Splash Zone In Reinforced Concrete Hydraulic Structures

Effect Of Age And Concrete Cover Thickness On Steel Reinforcement Corrosion At Splash Zone In Reinforced Concrete Hydraulic Structures Effect Of Age And Concrete Cover Thickness On Steel Reinforcement Corrosion At Splash Zone In Reinforced Concrete Hydraulic Structures Nada M. Al- Galawi, Ali A. H. Al-Tameemi, Sarah H. Al-Jarrah Abstract

More information

STAAD.pro 2007 Design of Wind Turbine Foundations

STAAD.pro 2007 Design of Wind Turbine Foundations STAAD.pro 2007 Design of Wind Turbine Foundations By RAM/STAAD Solution Center 2nd November 2007 1.0 INTRODUCTION The interest in renewable energy production systems is growing with the increase in demand

More information

COST ANALYSIS OF DOME STRUCTURE WITH RING BEAM

COST ANALYSIS OF DOME STRUCTURE WITH RING BEAM COST ANALYSIS OF DOME STRUCTURE WITH RING BEAM B. H. V. Pai 1 and B. Durga Prasad Baliga 2 1 Department of Civil Engineering, Manipal Institute of Technology, Manipal, Udupi, Karnataka, India 2 Department

More information

Florida s Flexible Filler Experience. Dr. Natassia Brenkus, The Ohio State University

Florida s Flexible Filler Experience. Dr. Natassia Brenkus, The Ohio State University Florida s Flexible Filler Experience Dr. Natassia Brenkus, The Ohio State University Motivation Cost-effective method of bridge construction Prestressed Concrete Durability Issues Poor grouting practice

More information

SACoMaTiS 2008 International RILEM Conference

SACoMaTiS 2008 International RILEM Conference SACoMaTiS 2008 International RILEM Conference 1-2 September 2008 Varenna (LC) Como Lake Italy POLITECNICO DI MILANO www.sacomatis.org on Site Assessment of Concrete, Masonry and Timber HALF-CELL POTENTIAL

More information

Mechanical and Corrosion Properties of a High-Strength, High Chromium Reinforcing Steel for Concrete

Mechanical and Corrosion Properties of a High-Strength, High Chromium Reinforcing Steel for Concrete SD2001-05-F Connecting South Dakota and the Nation South Dakota Department of Transportation Office of Research Mechanical and Corrosion Properties of a High-Strength, High Chromium Reinforcing Steel for

More information

Included in our report are our visual observations, recommendations for follow-up evaluation, and conceptual repair recommendations.

Included in our report are our visual observations, recommendations for follow-up evaluation, and conceptual repair recommendations. Ms. Pamela J. Irwin Community Management Associates 384 Ralph McGill Blvd Atlanta, GA 30312 Re: Phase I Condition Assessment Central City Condominiums Pool Deck Atlanta, Georgia Walter P Moore Project

More information

EVALUATING MITIGATION METHODS FOR CHLORIDE INDUCED CORROSION OF REINFORCED CONCRETE STRUCTURES

EVALUATING MITIGATION METHODS FOR CHLORIDE INDUCED CORROSION OF REINFORCED CONCRETE STRUCTURES EVALUATING MITIGATION METHODS FOR CHLORIDE INDUCED CORROSION OF REINFORCED CONCRETE STRUCTURES B.H.J. Pushpakumara Research Student Department of Civil and Environmental Engineering, Faculty of Engineering,

More information

Simplified Building Schematic for Typical Floor (Levels 9 through 22):

Simplified Building Schematic for Typical Floor (Levels 9 through 22): Introduction to Structural System Simplified Building Schematic for Typical Floor (Levels 9 through 22): Key: - Tower Columns - Tower Shear Walls - Parking Garage Columns - Parking Garage Shear Walls Solid

More information

Cathodic Protection as a Corrosion Control Alternative

Cathodic Protection as a Corrosion Control Alternative Cathodic Protection as a Corrosion Control Alternative By William T. Scannell and Ali Sohanghpurwala Corrosion of reinforcing steel in concrete is a widespread and enormously costly problem in all parts

More information

DURABILITY of CONCRETE STRUCTURES

DURABILITY of CONCRETE STRUCTURES DURABILITY of CONCRETE STRUCTURES Assist. Prof. Dr. Mert Yücel YARDIMCI This presentation covers the subjects in CEB Durable Concrete Structures Guideline and has been prepared by the graduate students

More information

Galvanic Liquid Applied Coating for the Protection of Concrete Reinforcement. Andrea Hansen Alla Furman Marlin Hansen Angel Green Jessi Meyer

Galvanic Liquid Applied Coating for the Protection of Concrete Reinforcement. Andrea Hansen Alla Furman Marlin Hansen Angel Green Jessi Meyer Paper No. 08315 Galvanic Liquid Applied Coating for the Protection of Concrete Reinforcement Andrea Hansen Alla Furman Marlin Hansen Angel Green Jessi Meyer Cortec Corporation 4119 White Bear Parkway White

More information

Chapter 8 Anchoring Structures

Chapter 8 Anchoring Structures Chapter 8 Anchoring Structures 8-1. General Structural anchors are often used to improve the stability of existing structures but, generally, should not be used as a primary means to stabilize new, large

More information

SPECIAL SPECIFICATION 4900 Sacrificial Cathodic Protection Pile Jacket

SPECIAL SPECIFICATION 4900 Sacrificial Cathodic Protection Pile Jacket 1993 Specifications CSJ 0331-04-045 SPECIAL SPECIFICATION 4900 Sacrificial Cathodic Protection Pile Jacket 1. Description. This Item shall govern for the furnishing, installing and energizing a sacrificial

More information

SECTION FACILITY LIGHTNING PROTECTION

SECTION FACILITY LIGHTNING PROTECTION PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 41 00 FACILITY LIGHTNING PROTECTION SPEC WRITER NOTE: Delete between //----//if not applicable to project. Also delete any other item or paragraph not applicable

More information

COST ACTION 534. WG 2: New system. Internal reference electrode to detect steel corrosion. CMIC Giulio Natta - Politecnico di Milano

COST ACTION 534. WG 2: New system. Internal reference electrode to detect steel corrosion. CMIC Giulio Natta - Politecnico di Milano COST ACTION 534 New materials, systems, methods and concepts for durable prestressed concrete structures WG 2: New system Internal reference electrode to detect steel corrosion L. Lazzari,, M. Ormellese,

More information

APPENDIXB PHOTOGRAPHS B - 1

APPENDIXB PHOTOGRAPHS B - 1 APPENDIXB PHOTOGRAPHS B - 1 Photo B-1: Overall view of Pier 40, looking southeast. Photo B-2: Overall view of the Finger Pier Extension with one-story shed, looking southeast. B-2 Photo B-3: View of typical

More information

REPAIR OF DELAMINATED PRESTRESSED CONCRETE CYLINDERS USING POST-INSTALLED ANCHORS: PART I RADIAL TENSION DEMAND AND FEM ANALYSIS

REPAIR OF DELAMINATED PRESTRESSED CONCRETE CYLINDERS USING POST-INSTALLED ANCHORS: PART I RADIAL TENSION DEMAND AND FEM ANALYSIS Transactions, SMiRT-22 REPAIR OF DELAMINATED PRESTRESSED CONCRETE CYLINDERS USING POST-INSTALLED ANCHORS: PART I RADIAL TENSION DEMAND AND FEM ANALYSIS Shen Wang 1, Javeed A. Munshi 2 1 Ph.D., P.E., Senior

More information

Stay-Cable Replacement Design

Stay-Cable Replacement Design Stay-Cable Replacement Design Mississippi River Bridge Luling, Louisiana Christopher Ligozio CTLGroup Copyright Post-Tensioning Institute all rights reserved. Page 1 of 35 Luling Bridge Copyright Post-Tensioning

More information

Carbon fibre fabric used for combined flexural strengthening and cathodic protection anode for reinforced concrete beams

Carbon fibre fabric used for combined flexural strengthening and cathodic protection anode for reinforced concrete beams Carbon fibre fabric used for combined flexural strengthening and cathodic protection anode for reinforced concrete beams NGUYEN, C, MANGAT, Pal , LAMBERT, Paul, O'FLAHERTY,

More information

ADAPT PT7 TUTORIAL FOR BEAM FRAME 1

ADAPT PT7 TUTORIAL FOR BEAM FRAME 1 ADAPT PT7 TUTORIAL FOR BEAM FRAME 1 Technical Note Structural Concrete Software System TN189_PT7_tutorial_beam_frame 012705 1 BEAM FRAME The objective of this tutorial is to demonstrate the step-by-step

More information

Shin Shin Apparels Ltd. (9615) Dag RS. 228, JL 73, Gorat, East Norshinghapur, Zirabo, Savar ( N, E) 27.MAY.2014

Shin Shin Apparels Ltd. (9615) Dag RS. 228, JL 73, Gorat, East Norshinghapur, Zirabo, Savar ( N, E) 27.MAY.2014 Shin Shin Apparels Ltd. (9615) Dag RS. 228, JL 73, Gorat, East Norshinghapur, Zirabo, Savar (+23.94071N, 90.30929E) 27.MAY.2014 Identified Priority 1 Concerns 1 st Priority 1 Concern Based on the Detail

More information

Modal-spectral analysis of a gas storage tank.

Modal-spectral analysis of a gas storage tank. Modal-spectral analysis of a gas storage tank. Description of the structure: A Spherical tank gas storage is formed by: 1.- S-355 steel sphere plate elements of 1.5 cm thickness. 2.- Eight vertical posts

More information

A new approach for the patch repair of car parks using galvanic anodes

A new approach for the patch repair of car parks using galvanic anodes Loughborough University Institutional Repository A new approach for the patch repair of car parks using galvanic anodes This item was submitted to Loughborough University's Institutional Repository by

More information

FINAL REPORT. Gerardo G. Clemeña, Ph.D. Research Scientist Virginia Transportation Research Council

FINAL REPORT. Gerardo G. Clemeña, Ph.D. Research Scientist Virginia Transportation Research Council FINAL REPORT TESTING OF SELECTED METALLIC REINFORCING BARS FOR EXTENDING THE SERVICE LIFE OF FUTURE CONCRETE BRIDGES: TESTING IN OUTDOOR CONCRETE BLOCKS Gerardo G. Clemeña, Ph.D. Research Scientist Virginia

More information

Applications of sustainable post-tensioned concrete slabs

Applications of sustainable post-tensioned concrete slabs Innov. Infrastruct. Solut. (2017) 2:42 DOI 10.1007/s41062-017-0075-6 TECHNICAL PAPER Applications of sustainable post-tensioned concrete slabs Amr A. Abdelrahman 1 Received: 4 May 2017 / Accepted: 2 June

More information

DESIGN STANDARDS DEVELOPMENT REPORT FOR CORROSION RESISTANT PRESTRESSED CONCRETE PILES (INDEX No Series FY Design Standards)

DESIGN STANDARDS DEVELOPMENT REPORT FOR CORROSION RESISTANT PRESTRESSED CONCRETE PILES (INDEX No Series FY Design Standards) FDOT Design Standards Development Report Proposed Index No. 22600 DESIGN STANDARDS DEVELOPMENT REPORT FOR CORROSION RESISTANT PRESTRESSED CONCRETE PILES (INDEX No. 22600 Series FY2016-17 Design Standards)

More information

Rak Production Technology of Concrete Structures (2015) Concrete Reinforcement

Rak Production Technology of Concrete Structures (2015) Concrete Reinforcement Rak-82-2121 Production Technology of Concrete Structures (2015) Concrete Reinforcement 09.10.2015 1 Learning Outcomes To acquaint the student with concrete reinforcement 2 Reinforcement The of concrete

More information

Seismic Evaluation and Retrofit of Beam- Column Joints of Mid-America Bridges Part 2: Steel Sheet and Plate Retrofit

Seismic Evaluation and Retrofit of Beam- Column Joints of Mid-America Bridges Part 2: Steel Sheet and Plate Retrofit Seismic Evaluation and Retrofit of Beam- Column Joints of Mid-America Bridges Part 2: Steel Sheet and Plate Retrofit Genda Chen, Ph.D., P.E. Associate Professor of Civil Engineering Department of Civil,

More information