Evaluation and Repair of Post-Tensioned Concrete
|
|
- Julius Long
- 5 years ago
- Views:
Transcription
1 Evaluation and Repair of Post-Tensioned Concrete Tank and Thin Shell Roof by Keith Kesner, Ph.D., PE P.E. Randall W. Poston, Ph.D., P.E. (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 1 of 24
2 Post-Tensioned Structures Corrosion Evaluation - Thin Shell Roof Bonded reinforcement electrochemical methods Unbonded reinforcement limited assessment methods Repair Design Concrete Tank Maintain integrity of existing structure Existing i PT needs to be considered d (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 2 of 24
3 Thin Shell Evaluation (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 3 of 24
4 Thin Shell Evaluation Concrete shell structure Hyperbolic paraboloid 5 inch thick shell Post-tensioned perimeter beams 30 Years Old Water leakage Staining Corrosion?? Post-tensioning system?? (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 4 of 24
5 Thin Shell Evaluation (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 5 of 24
6 Corrosion Assessment Electro-chemical methods Measure electrical activity associated with corrosion process Half-cell potential (ASTM C876) Concrete resistivity Corrosion rate (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 6 of 24
7 Corrosion Assessment Half-cell potential (ASTM C876) When bar is corroding, charge flow through concrete is associated with an electrical field Measure the electrical potential (voltage) of the field at the concrete surface Magnitude of the measured voltage, relative to a standard half-cell, is indicative of corrosion activity Provides only indication of likelihood of active corrosion (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 7 of 24
8 Corrosion Assessment Concrete resistivity Rate of corrosion is controlled by ease with which ions move from anodic to cathodic sites Concrete resistivity is, therefore, an important factor in rate of corrosion Resistivity, ρ Numerically equal to resistance, R, of a unit cube of material R = ρ L A (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 8 of 24
9 Corrosion Assessment Polarization resistance Measure of corrosion current Based upon evaluation of polarization resistance of reinforcing bar Allows measurement of rate of corrosion (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 9 of 24
10 Thin Shell Evaluation Corrosion testing on 3 bad and 2 good shells Assess reinforcement condition Materials testing Electro-chemical corrosion measurements Analysis Model effect of corrosion damage Evaluate reserve capacity (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 10 of 24
11 Thin Shell Evaluation Results Bad Shells Shell Corrosion Potential (mv) Resistivity (Ohm-cm) Corrosion Rate (μa/cm 2 ) 1 High Average 2 Low Average 3 High Average , ,000 1,000, , Average value from three tests at locations with highest corrosion potentials 2.Average of 84, 42 and 90 individual tests on Shells 1, 5 and 6, respectively 3.Average of 56, 42 and 90 individual tests on Shells 1, 5 and 6, respectively (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 11 of 24
12 Thin Shell Evaluation Probe Openings Verify integrity of strands Evaluate grease condition (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 12 of 24
13 Thin Shell Evaluation Electrochemical Isolated corrosion damage expected based upon corrosion rates in bad shells No chlorides or carbonation Good shells high concrete resistivity Post-tensioningtensioning Water intrusion apparent Strands intact (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 13 of 24
14 Thin Shell Summary Summary Isolated corrosion damage likely in 2 to 5 years Generally high resistivity (dry) concrete No accelerating factors Repair recommendations Address water leakage Isolated repairs to deck supports Corrosion inhibitor Grease reinjection (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 14 of 24
15 Wire Wrapped Tank Dome ring failure (1 of 3 surge tanks) Dome ring added to original design Accommodate dome installation (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 15 of 24
16 Wire Wrapped Tank Dome ring failure (1 of 3 surge tanks) Water intrusion and lack of bond Lack of positive connection (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 16 of 24
17 Wire Wrapped Tank Dome ring failure (1 of 3 surge tanks) Water intrusion and lack of bond Lack of positive connection (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 17 of 24
18 Wire Wrapped Tank Corrosion damage Brittle failure of wires (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 18 of 24
19 Wire Wrapped Tank Analysis Two Cases Failed dome ring Intact dome ring Loading and Geometry Inside diameter: 150 ft Wall height: 26.2 ft Wall thickness: 6.5 in Dome radius: 195 ft Dome thickness: 4 in Capacity: 3.3 MG (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 19 of 24
20 Wire Wrapped Tank Evaluation results failed dome ring Dead load only - unfilled Dome thrust ~ 4.7 kip / ft. circ. Prestress in top 4 ft. of tank resists dome thrust Prestress ~ 1.2 kip / ft. circ. Options need to replace dome ring External post-tensioning Waterproofing limit further corrosion (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 20 of 24
21 Wire Wrapped Tank Evaluation results intact dome ring Original design was adequate Stresses are within limits Repair options External post-tensioning tensioning Supplement existing dome ring Waterproofing limit further corrosion (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 21 of 24
22 External PR Repair Details (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 22 of 24
23 Wire Wrapped Tank External post-tensioning Staged allow limited use during repair Retrofit angles increase dome ring support (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 23 of 24
24 Summary Evaluation Methods Bonded reinforcement Electro-chemical Unbonded reinforcement More limited, more conservative Repair Options Consider stresses Worker safety Prevent cracking Limit water ingress (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 24 of 24
Evaluation of Corrosion Damage in Unbonded Post-Tensioned Concrete Structures:
Evaluation of Corrosion Damage in Unbonded Post-Tensioned Concrete Structures: Misunderstandings, Misinformation and Moving Forward by Keith Kesner Randall W. Poston Introduction 16 Years Ago Corrosion
More informationEVALUATION & REPAIR OF CORROSION DAMAGED ROOF LIFT SLAB WITH WIRE POST-TENSIONING SYSTEM (BUTTON HEADS)
EVALUATION & REPAIR OF CORROSION DAMAGED ROOF LIFT SLAB WITH WIRE POST-TENSIONING SYSTEM (BUTTON HEADS) (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHT RESERVED 1 of 23 The following presentation discusses
More informationCondition of US Bridges and Present Corrosion Technologies Used for Bridge Structures
Condition of US Bridges and Present Corrosion Technologies Used for Bridge Structures Seung-Kyoung Lee 1 and Paul Virmani 2 1. SK Lee & Associates, Inc. 2. Federal Highway Administration Workshop on Corrosion
More information1. CORROSION OF REINFORCEMENT
MAB 1033 Structural Assessment and Repair 1. CORROSION OF REINFORCEMENT Professor Dr. Mohammad bin Ismail C09-313 Learning Outcome At the end of the course students should be able to understand Mechanism
More information9.6 Circular Prestressing
9.6 Circular Prestressing This section covers the following topics. Introduction General Analysis and Design Prestressed Concrete Pipes Liquid Storage Tanks Ring Beams Conclusion 9.6.1 Introduction When
More informationTECHNIACL SPECIAL PROVISION FOR NON-STRUCTURAL AND STRUCTURAL INTEGRAL PILE JACKET WITH SACRIFICIAL CATHODIC PROTECTION
TECHNIACL SPECIAL PROVISION FOR NON-STRUCTURAL AND STRUCTURAL INTEGRAL PILE JACKET WITH SACRIFICIAL CATHODIC PROTECTION Financial Project ID 429140-1-52-01, 429140-2-52-01 & 428267-1-52-01 The official
More informationNDT in Grouted PT Inspection for Bridges
NDT in Grouted PT Inspection for Bridges PTI Technical Conference & Exhibition Miami, FL May 8, 2007 Hong-gang gang Cao CTLGroup (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 1 of 37
More informationAssessment of Long-Time Behavior for Bridge Girders Retrofitted with Fiber Reinforced Polymer
Journal of Civil Engineering and Architecture 9 (2015) 1034-1046 doi: 10.17265/1934-7359/2015.09.003 D DAVID PUBLISHING Assessment of Long-Time Behavior for Bridge Girders Retrofitted with Fiber Reinforced
More informationEvaluation and Repair of Existing Post- Tensioned Buildings with Paper Wrapped Tendons Experiencing Corrosion Damage
Evaluation and Repair of Existing Post- Tensioned Buildings with Paper Wrapped Tendons Experiencing Corrosion Damage K. Dirk Bondy, S.E. President Seneca Structural Engineering, Inc. The Great American
More informationMONITORING CORROSION ACTIVITY IN CHLORIDE CONTAMINATED CONCRETE WRAPPED WITH FIBER REINFORCED PLASTICS. Abstract. Introduction
MONITORING CORROSION ACTIVITY IN CHLORIDE CONTAMINATED CONCRETE WRAPPED WITH FIBER REINFORCED PLASTICS Emily W. Berver, James. O. Jirsa, Ph.D., David. W. Fowler, Ph.D., and Harovel. G. Wheat, Ph.D., The
More informationElimination of Deck Joints Using a Corrosion Resistant FRP Approach
Elimination of Deck Joints Using a Corrosion Resistant FRP Approach Louisiana Transportation Conference February 2009 Aziz Saber, Ph.D., P.E. Chair of Civil Engineering Louisiana Tech University LTRC LA
More informationPRESTRESSED CONCRETE STRUCTURES. Amlan K. Sengupta, PhD PE Department of Civil Engineering, Indian Institute of Technology Madras
PRESTRESSED CONCRETE STRUCTURES Amlan K. Sengupta, PhD PE Department of Civil Engineering, Indian Institute of Technology Madras Module 9: Special Topics Lecture 40: Circular Prestressing, Conclusion Welcome
More information1. Cast-in-place concrete is specified in Section
SECTION 03 38 00 PART 1 - GENERAL 1.01 DESCRIPTION A. This Section describes the requirements for furnishing and installing post-tensioned slabs, jacks, jacking and anchors at Parking Structure, and record
More informationPRESENTED AT NATIONAL BRIDGE PRESERVATION PARTNERSHIP CONFERENCE ORLANDO, FLORIDA 2014 AUTHORS ROBERT WALDE, SURTREAT HOLDING, LLC PRESENTER RICH
PRESENTED AT NATIONAL BRIDGE PRESERVATION PARTNERSHIP CONFERENCE ORLANDO, FLORIDA 2014 AUTHORS ROBERT WALDE, SURTREAT HOLDING, LLC PRESENTER RICH LAMPO, U.S. ARMY CORPS OF ENGINEERS RESEARCH LABORATORY
More informationCorrosion Monitoring of Steel Bars in Port Concrete Structures
Corrosion Monitoring of Steel Bars in Port Concrete Structures Mitsuyasu IWANAMI 1*, Ema KATO 2, Yuichiro KAWABATA 2, Takahiro NISHIDA 1 1 Tokyo Institute of Technology, Japan 2 Port and Airport Research
More informationCorrosion Mitigation Systems for Concrete Structures
Corrosion Mitigation Systems for Concrete Structures By J. Christopher Ball and David W. Whitmore According to a recently completed study by the U.S. Federal Highway Administration, the annual direct cost
More informationPRODUCT DATA SHEET Sika FerroGard -675
PRODUCT DATA SHEET DISCRETE EMBEDDED GALVANIC ANODE PRODUCT DESCRIPTION is a zinc based discrete sacrificial anode placed inside a concrete repair area in reinforced concrete structures which are corroding
More informationBridge Preservation Corrosion Mitigation Option in Concrete Repair Systems
Bridge Preservation Corrosion Mitigation Option in Concrete Repair Systems September 29, 2010 Northeast Bridge Preservation Partnership Meeting TSP-2 TODAY WE WILL DISCUSS Corrosion of Bridge Decks Surface
More informationCorrosion Performance of Prestressing Strands in Contact with Dissimilar Grouts
Report No. KS-12-4 FINAL REPORT January 2013 Corrosion Performance of Prestressing Strands in Contact with Dissimilar Grouts Matthew O Reilly, Ph.D. David Darwin, Ph.D., P.E. JoAnn Browning, Ph.D., P.E.
More informationREFURBISHMENT Sika FerroGard GALVANIC AND HYBRID ANODE TECHNOLOGIES
Sika FerroGard GALVANIC AND HYBRID ANODE TECHNOLOGIES CONCRETE CORROSION CONTROLLED FOR UP TO 50 YEARS REDUCING MAINTENANCE COSTS AND EXTENDING THE LIFE OF REINFORCED CONCRETE REINFORCED CONCRETE IS A
More informationEuropean Standard En 1504
BS EN 1504 Products and Systems for the protection and repair of concrete structures Definitions, requirements, quality control and evaluation of conformity John Drewett Concrete Repairs Ltd 25% of the
More informationSeismic Behavior of Low Strength RC Columns with Corroded Plain Reinforcing Bars
Seismic Behavior of Low Strength RC Columns with Corroded Plain Reinforcing Bars C. Goksu 1, B. Demirtas 2, C. Demir 1, A. Ilki 3 and N. Kumbasar 4 1 PhD Candidate, Civil Engineering Faculty, Istanbul
More informationThe Assessment of Concrete Structures affected by Steel Corrosion
THE HIGHWAYS AGENCY BA 51/95 THE SCOTTISH OFFICE DEVELOPMENT DEPARTMENT THE WELSH OFFICE Y SWYDDFA GYMREIG THE DEPARTMENT OF THE ENVIRONMENT FOR NORTHERN IRELAND The Assessment of Concrete Structures affected
More informationCONSTRUCTION PROCEDURES. AWWA D110 Type I Prestressed Concrete Tanks
CONSTRUCTION PROCEDURES AWWA D110 Type I Prestressed Concrete Tanks 2-3 4-5 6-7 8-9 10-11 12-13 14-15 16-17 Site Preparation Floor & Footings Wall Construction Roof Options Vertical Prestressing Abrasive
More informationPERFORMANCE OF AN IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM FOR A REINFORCED CONCRETE TANK
PERFORMANCE OF AN IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM FOR A REINFORCED CONCRETE TANK Dr. S. Ehtesham Hussain & Dr. Hamed A. Al-Ghamdi (Hamed Al-Ghamdi Consulting Engineers (CONTEC) Khobar, Saudi
More informationGUIDELINES FOR EXECUTION OF ADAPT-PT 1
Structural Concrete Software System GUIDELINES FOR EXECUTION OF ADAPT-PT 1 Update: December 09, 2004 TN172 guide_to_run_pt_12 120904 The guidelines presented will assist you in the selection of design
More informationSPECIAL SPECIFICATION 4401 Prestressed Ground Anchors
2004 Specifications CSJ 0581-02-121 & 0200-11-100 SPECI SPECIFICATION 4401 Prestressed Ground Anchors 1. Description. Install post-tensioned permanent ground anchors in place, with grouting as required
More informationEffects of Corrosion on Reinforced Concrete Beams with Silica Fume and Polypropylene Fibre
Effects of Corrosion on Reinforced Concrete Beams with Silica Fume and Polypropylene Fibre S.Shanmugam, V.G. Srisanthi, and S.Ramachandran Abstract Reinforced concrete has good durability and excellent
More informationACI MANUAL OF CONCRETE PRACTICE-2009
ACI MANUAL OF CONCRETE PRACTICE-2009 The ACI Manual of Concrete Practice is a six-part compilation of current ACI standards and committee reports. -ACI117-06 to ACI224.3R-95(08) Part 2-ACI 225-99(05) to
More informationWhen the Unexpected Occurs: Tendon Failures in the Construction of a New 2 MG Prestressed Concrete Reservoir
When the Unexpected Occurs: Tendon Failures in the Construction of a New 2 MG Prestressed Concrete Reservoir Nancy Kraushaar, P.E., Oregon City Patrick Van Duser, P.E., Black & Veatch Presentation Overview
More informationRusty Boicourt, P.G. NDE & Materials Specialist Materials Testing & Inspection
Corrosion Damaged Concrete Causes & Repair Presented by Rusty Boicourt, P.G. NDE & Materials Specialist Materials Testing & Inspection Examples of Corrosion Damage Examples of Corrosion Damage Examples
More informationTECHNICAL ASSISTANCE REPORT EFFECT OF CONCRETE REMOVAL EQUIPMENT AND METHODS ON THE CONDITION OF DECK CONCRETE LEFT IN PLACE
TECHNICAL ASSISTANCE REPORT EFFECT OF CONCRETE REMOVAL EQUIPMENT AND METHODS ON THE CONDITION OF DECK CONCRETE LEFT IN PLACE Michael M. Sprinkel, P.E. Research Manager (The opinions, findings, and conclusions
More informationPost-Tech PTI Impregnation System. Corrosion Protection System for Bonded Post-Tension Tendons
Post-Tech PTI Impregnation System Corrosion Protection System for Bonded Post-Tension Tendons Post-Tech PTI Impregnation System Corrosion Protection System for Bonded Post-Tension Tendons Post-Tech PTI
More informationCorrosion Investigation for Contra Costa Community College District - Brentwood Campus
August 2, 2017 Ref AJ 2017-032 RMA Group, Inc. 3150 Fitzgerald Rd. Rancho Cordova, CA 95742 Attn: Mr. Josh Summers, PE Subject: Corrosion Investigation for Contra Costa Community College District - Brentwood
More information5. CONCLUSIONS, RECOMMENDATIONS, COST ESTIMATES
5. CONCLUSIONS, RECOMMENDATIONS, COST ESTIMATES 5.1 CONCLUSIONS In general, Pier 40 is in overall Poor condition. The allowable uniform live load rating for the pier has been significantly reduced from
More informationSTRENGTHENING OF UNBONDED POST-TENSIONED CONCRETE SLABS USING EXTERNAL FRP COMPOSITES
STRENGTHENING OF UNBONDED POST-TENSIONED CONCRETE SLABS USING EXTERNAL FRP COMPOSITES F. El M e s k i 1 ; M. Harajli 2 1 PhD student, Dept. of Civil and Environmental Engineering, American Univ. of Beirut;
More informationTECHNIQUES, MATERIALS AND DESIGN CONSIDERATIONS: REHABILITATION & STRENGTHENING OF WATER AND WASTEWATER PIPELINES. Solutions & Case Studies
TECHNIQUES, MATERIALS AND DESIGN CONSIDERATIONS: REHABILITATION & STRENGTHENING OF WATER AND WASTEWATER PIPELINES Solutions & Case Studies Mike Larsen Senior Manager Pipeline Solutions 972-210-9511 mlarsen@structuraltec.com
More informationWHAT ABOUT STRAY CURRENTS WITH STEEL FIBRE REINFORCED CONCRETE
Dramix WHAT ABOUT STRAY CURRENTS WITH STEEL FIBRE REINFORCED CONCRETE Stray Currents: Definition (1) Stray currents arise from rail transit systems, cathodic protection systems, or high-voltage power lines.
More information3. INSPECTION FINDINGS
3. INSPECTION FINDINGS Pier 40 is in overall Poor condition with 22% of the H-piles rated Major and 35% of the H-piles rated Severe, primarily due to severe corrosion within the splash zone at the top
More informationORGANOFUNCTIONAL SILANE CORROSION INHIBITOR SURFACE TREATMENT OF CONCRETE TO MITIGATE CORROSION DUE TO CHLORIDES OR CARBONATION ABSTRACT
Paper No. 9130 ORGANOFUNCTIONAL SILANE CORROSION INHIBITOR SURFACE TREATMENT OF CONCRETE TO MITIGATE CORROSION DUE TO CHLORIDES OR CARBONATION Neal S. Berke, Ph.D., FNACE Tourney Consulting Group, LLC
More informationHickam Air Force Base Headquarters
Hickam Air Force Base Headquarters Crawl-space Column Repairs and Corrosion Mitigation By Tore O. Arnesen and J. Christopher Ball The Hickam Air Force Base Headquarters Pacific Air Forces (PACAF) Building
More informationSilicon Valley Mid-Summer Emergency: Santa Clara Addresses Peak-Demand Repair of 96-inch Pipeline Mike Larsen Anna Pridmore, PhD, PE
Silicon Valley Mid-Summer Emergency: Santa Clara Addresses Peak-Demand Repair of 96-inch Pipeline Mike Larsen Anna Pridmore, PhD, PE BACKGROUND Santa Clara Valley Water District: Primary Water Source for
More informationSECTION 1 INTRODUCTION TO POST-TENSIONED CONCRETE DEVELOPED BY THE PTI EDC-130 EDUCATION COMMITTEE
SECTION 1 INTRODUCTION TO POST-TENSIONED CONCRETE DEVELOPED BY THE PTI EDC-130 EDUCATION COMMITTEE NOTE: MOMENT DIAGRAM CONVENTION In PT design, it is preferable to draw moment diagrams to the tensile
More informationSUNSHINE SKYWAY BRIDGE
SUNSHINE SKYWAY BRIDGE Retrofit of the Post-Tensioned Precast Transition Pier Columns on the Sunshine Skyway Bridge Presented by: Antonio Ledesma, P.E. May 7, 2012 SUNSHINE SKYWAY BRIDGE, FLORIDA Presentation
More informationAtkinson Engineering, Inc.
Atkinson Engineering, Inc. Atkinson Engineering, Inc. One of the problems in underpinning a typical post-tensioned foundation is support for the slab part that spans between the stiffening beams. An example
More informationRepairs to the Primary Tanks at a Wastewater Treatment Plant
Repairs to the Primary Tanks at a Wastewater Treatment Plant Edited by Kelly M. Page As part of the City of Grand Rapids, Michigan, Capital Improvement Plan, the city required an assessment of the condition
More informationComprehensive condition assessment program on the fire damaged structure a project case in Singapore
Comprehensive condition assessment program on the fire damaged structure a project case in Singapore Gunawan Budi Wijaya 1,* 1 Petra Christian University, Department of Civil Engineering, Indonesia Abstract.
More informationColumn: Part 2 Courtesy of Dr. Latifee s IMI research group, Text books and others
Column: Part 2 Courtesy of Dr. Latifee s IMI research group, Text books and others Design for Axial Load: With negligible moment and considerable amount of concentric axial load, failure occurs when the
More informationGuidelines for the Design of Post-Tensioned Floors
5.2 Guidelines for the Design of Post-Tensioned Floors BY BIJAN O. AALAMI AND JENNIFER D. JURGENS his article presents a set of guidelines intended to T assist designers in routine post-tensioning design,
More informationSPECIAL SPECIFICATION 4492 Tie Back Anchors
2004 Specifications CSJ 0504-02-022 SPECI SPECIFICATION 4492 Tie Back Anchors 1. Description. This Item shall govern for the installation of tie-back anchors in place, with grouting as required in accordance
More informationTECHNICAL SPECIAL PROVISION FOR CONCRETE REPAIRS. Financial Project ID , &
TECHNICAL SPECIAL PROVISION FOR CONCRETE REPAIRS Financial Project ID 429140-1-52-01, 429140-2-52-01 & 428267-1-52-01 The official record of this Technical Special Provision is the electronic file signed
More informationCORROSION MITIGATION OF PRECAST CONCRETE PARKING GARAGES
CORROSION MITIGATION OF PRECAST CONCRETE PARKING GARAGES BY TORE O. ARNESEN AND LEO WHITELEY Fig. 1: Typical precast parking garage The use of precast concrete for constructing parking garages is very
More informationDesigning Bridges for a 100-year Service Life. TEAM Conference 2016
Designing Bridges for a 100-year Service Life Presented at TEAM Conference 2016 By Siva Venugopalan Principal Engineer Siva Corrosion Services, Inc siva@sivacorrosion.com In This Presentation Brief Introduction
More informationGalvanic Cathodic Protection of Concrete Structures. David Whitmore, P.Eng., FCSCE Vector Corrosion Technologies
Galvanic Cathodic Protection of Concrete Structures David Whitmore, P.Eng., FCSCE Vector Corrosion Technologies Concrete Repair Process Cause & Effect Repair required? YES Condition Survey Repair Analysis
More informationTopic Outline. Two Stage Analysis Procedure: Podium Design. Part 2: Rigid Lower Portion Philip Miller, S.E. 2/8/2018
Two Stage Analysis Procedure: Podium Design Part 2: Rigid Lower Portion Philip Miller, S.E. Topic Outline Types of Podium Construction Example Buildings PT Basics PT Analysis Modeling Tips Load Balancing
More informationPost-tensioned Structures Solutions for Repair and Protection
Post-tensioned Structures Solutions for Repair and Protection Concrete Preservation Alliance Vector Construction, Vector Corrosion Technologies, and Vector Corrosion Services are working to advance the
More informationPRO S AND CON S OF HALF-CELL POTENTIALS AND CORROSION RATE MEASUREMENTS
PRO S AND CON S OF HALF-CELL POTENTIALS AND CORROSION RATE MEASUREMENTS Thomas Frølund Oskar Klinghoffer Henrik E. Sørensen Germann Instruments A/S Force Technology Force Technology Emdrupvej 102 Park
More informationCorrosion Evaluation of Post-Tensioned Tendons on Mid-Bay Bridge
Corrosion Evaluation of Post-Tensioned Tendons on Mid-Bay Bridge by Siva Venugopalan Principal SCS, Inc. siva007@verizon.net (610) 692-6551 6551 March 7, 2007 Count on Concrete for Performance Slide 1
More informationA SIMPLIFIED METHOD TO ESTIMATE CORROSION RATES A NEW APPROACH BASED ON INVESTIGATIONS OF MACROCELLS Method to estimate corrosion rates
A SIMPLIFIED METHOD TO ESTIMATE CORROSION RATES A NEW APPROACH BASED ON INVESTIGATIONS OF MACROCELLS Method to estimate corrosion rates M. RAUPACH, Schiessl & Raupach, Consulting & Engineering, Aachen,
More informationThe past and present in concrete repair Members response: Consultant s perspective
The past and present in concrete repair Members response: Consultant s perspective Geir Horrigmoe Norut Technology, Norway geir@tek.norut.no CONREPNET Members Workshop, Prague, 22 June 2005 Performances
More informationIntroduction to Structural Analysis TYPES OF STRUCTURES LOADS AND
AND Introduction to Structural Analysis TYPES OF STRUCTURES LOADS INTRODUCTION What is the role of structural analysis in structural engineering projects? Structural engineering is the science and art
More informationIntermountain Section AWWA Conference - 2.0MG Layton Water Tank. Jake O Brien
Intermountain Section AWWA Conference - 2.0MG Layton Water Tank Jake O Brien Presentation Outline Layton City s decision process Tank Design/Construction Tendon Tanks - don t shed the good stuff Layton
More informationASSESSMENT, REPAIR AND MONITORING OF THE GENTILLY-1 CONCRETE CONTAINMENT STRUCTURE
ASSESSMENT, REPAIR AND MONITORING OF THE GENTILLY-1 CONCRETE CONTAINMENT STRUCTURE A.A. Khan, M. Gray, B. Shenton, D. Panesar and M. Elgohary Atomic Energy of Canada Limited, Mississauga, Ontario, Canada
More informationTHE FORENSIC MEDICAL CENTER
THE FORENSIC MEDICAL CENTER Image courtesy of Gaudreau, Inc. TECHNICAL REPORT #2 OCTOBER 26, 2007 KEENAN YOHE STRUCTURAL OPTION DR. MEMARI FACULTY ADVISOR EXECUTIVE SUMMARY Image courtesy of Gaudreau,
More informationRefining Corrosion Technologist NACE-RCT-001
Refining Corrosion Technologist NACE-RCT-001 NACE Cathodic Protection Specialist (CP 4) Essay Exam Exam Preparation Guide March 2018 Copyright 2016 by NACE International Institute. All rights reserved.
More informationREPAIR OF DRAPED MESH CONCRETE SLABS
REPAIR OF DRAPED MESH CONCRETE SLABS BY KIRK M. STAUFFER AND KEVIN C. POULIN D raped mesh concrete slabs (supported by hotrolled steel beams and girders) were one of the most prevalent one-way floor slab
More informationRepair Application Procedures
Repair Application Procedures I CRI s mission is:... to be a leading resource for education and information to improve the quality of repair, restoration, and protection of concrete and other structures.
More informationHALF-CELL POTENTIAL MEASUREMENTS TO ASSESS CORROSION RISK OF REINFORCEMENT STEELS IN A PC BRIDGE
HALF-CELL POTENTIAL MEASUREMENTS TO ASSESS CORROSION RISK OF REINFORCEMENT STEELS IN A PC BRIDGE Eisuke Nakamura (1), Hiroshi Watanabe (1), Hirohisa Koga (1), Masayuki Nakamura (2) and Kazuhiro Ikawa (2)
More informationMarina Coast Water District Marina, CA Steel Reservoir #2
WATER TANK INSPECTION REPORT Prepared for the Marina Coast Water District Marina, CA Steel Reservoir #2 October 26, 2005 490 Industrial Park Road Deep River, CT 06417 Tel: (860) 526-2610 Fax:(860) 526-5018)
More informationGERMANN INSTRUMENTS. GalvaPulse. for Corrosion Rate, Half-Cell Potentials and Electrical Resistance
GERMANN INSTRUMENTS GalvaPulse for Corrosion Rate, Half-Cell Potentials and Electrical Resistance 1. Background The galvanostatic pulse technique was introduced for field application in 1988, ref. (1),
More informationConcrete Parking Garage Degradation
Concrete Parking Garage Degradation Concrete Parking Garage Degradation With proper care and maintenance, the life of a concrete parking garage can span several decades. The integrity and strength of structural
More informationEffect Of Age And Concrete Cover Thickness On Steel Reinforcement Corrosion At Splash Zone In Reinforced Concrete Hydraulic Structures
Effect Of Age And Concrete Cover Thickness On Steel Reinforcement Corrosion At Splash Zone In Reinforced Concrete Hydraulic Structures Nada M. Al- Galawi, Ali A. H. Al-Tameemi, Sarah H. Al-Jarrah Abstract
More informationSTAAD.pro 2007 Design of Wind Turbine Foundations
STAAD.pro 2007 Design of Wind Turbine Foundations By RAM/STAAD Solution Center 2nd November 2007 1.0 INTRODUCTION The interest in renewable energy production systems is growing with the increase in demand
More informationCOST ANALYSIS OF DOME STRUCTURE WITH RING BEAM
COST ANALYSIS OF DOME STRUCTURE WITH RING BEAM B. H. V. Pai 1 and B. Durga Prasad Baliga 2 1 Department of Civil Engineering, Manipal Institute of Technology, Manipal, Udupi, Karnataka, India 2 Department
More informationFlorida s Flexible Filler Experience. Dr. Natassia Brenkus, The Ohio State University
Florida s Flexible Filler Experience Dr. Natassia Brenkus, The Ohio State University Motivation Cost-effective method of bridge construction Prestressed Concrete Durability Issues Poor grouting practice
More informationSACoMaTiS 2008 International RILEM Conference
SACoMaTiS 2008 International RILEM Conference 1-2 September 2008 Varenna (LC) Como Lake Italy POLITECNICO DI MILANO www.sacomatis.org on Site Assessment of Concrete, Masonry and Timber HALF-CELL POTENTIAL
More informationMechanical and Corrosion Properties of a High-Strength, High Chromium Reinforcing Steel for Concrete
SD2001-05-F Connecting South Dakota and the Nation South Dakota Department of Transportation Office of Research Mechanical and Corrosion Properties of a High-Strength, High Chromium Reinforcing Steel for
More informationIncluded in our report are our visual observations, recommendations for follow-up evaluation, and conceptual repair recommendations.
Ms. Pamela J. Irwin Community Management Associates 384 Ralph McGill Blvd Atlanta, GA 30312 Re: Phase I Condition Assessment Central City Condominiums Pool Deck Atlanta, Georgia Walter P Moore Project
More informationEVALUATING MITIGATION METHODS FOR CHLORIDE INDUCED CORROSION OF REINFORCED CONCRETE STRUCTURES
EVALUATING MITIGATION METHODS FOR CHLORIDE INDUCED CORROSION OF REINFORCED CONCRETE STRUCTURES B.H.J. Pushpakumara Research Student Department of Civil and Environmental Engineering, Faculty of Engineering,
More informationSimplified Building Schematic for Typical Floor (Levels 9 through 22):
Introduction to Structural System Simplified Building Schematic for Typical Floor (Levels 9 through 22): Key: - Tower Columns - Tower Shear Walls - Parking Garage Columns - Parking Garage Shear Walls Solid
More informationCathodic Protection as a Corrosion Control Alternative
Cathodic Protection as a Corrosion Control Alternative By William T. Scannell and Ali Sohanghpurwala Corrosion of reinforcing steel in concrete is a widespread and enormously costly problem in all parts
More informationDURABILITY of CONCRETE STRUCTURES
DURABILITY of CONCRETE STRUCTURES Assist. Prof. Dr. Mert Yücel YARDIMCI This presentation covers the subjects in CEB Durable Concrete Structures Guideline and has been prepared by the graduate students
More informationGalvanic Liquid Applied Coating for the Protection of Concrete Reinforcement. Andrea Hansen Alla Furman Marlin Hansen Angel Green Jessi Meyer
Paper No. 08315 Galvanic Liquid Applied Coating for the Protection of Concrete Reinforcement Andrea Hansen Alla Furman Marlin Hansen Angel Green Jessi Meyer Cortec Corporation 4119 White Bear Parkway White
More informationChapter 8 Anchoring Structures
Chapter 8 Anchoring Structures 8-1. General Structural anchors are often used to improve the stability of existing structures but, generally, should not be used as a primary means to stabilize new, large
More informationSPECIAL SPECIFICATION 4900 Sacrificial Cathodic Protection Pile Jacket
1993 Specifications CSJ 0331-04-045 SPECIAL SPECIFICATION 4900 Sacrificial Cathodic Protection Pile Jacket 1. Description. This Item shall govern for the furnishing, installing and energizing a sacrificial
More informationSECTION FACILITY LIGHTNING PROTECTION
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 41 00 FACILITY LIGHTNING PROTECTION SPEC WRITER NOTE: Delete between //----//if not applicable to project. Also delete any other item or paragraph not applicable
More informationCOST ACTION 534. WG 2: New system. Internal reference electrode to detect steel corrosion. CMIC Giulio Natta - Politecnico di Milano
COST ACTION 534 New materials, systems, methods and concepts for durable prestressed concrete structures WG 2: New system Internal reference electrode to detect steel corrosion L. Lazzari,, M. Ormellese,
More informationAPPENDIXB PHOTOGRAPHS B - 1
APPENDIXB PHOTOGRAPHS B - 1 Photo B-1: Overall view of Pier 40, looking southeast. Photo B-2: Overall view of the Finger Pier Extension with one-story shed, looking southeast. B-2 Photo B-3: View of typical
More informationREPAIR OF DELAMINATED PRESTRESSED CONCRETE CYLINDERS USING POST-INSTALLED ANCHORS: PART I RADIAL TENSION DEMAND AND FEM ANALYSIS
Transactions, SMiRT-22 REPAIR OF DELAMINATED PRESTRESSED CONCRETE CYLINDERS USING POST-INSTALLED ANCHORS: PART I RADIAL TENSION DEMAND AND FEM ANALYSIS Shen Wang 1, Javeed A. Munshi 2 1 Ph.D., P.E., Senior
More informationStay-Cable Replacement Design
Stay-Cable Replacement Design Mississippi River Bridge Luling, Louisiana Christopher Ligozio CTLGroup Copyright Post-Tensioning Institute all rights reserved. Page 1 of 35 Luling Bridge Copyright Post-Tensioning
More informationCarbon fibre fabric used for combined flexural strengthening and cathodic protection anode for reinforced concrete beams
Carbon fibre fabric used for combined flexural strengthening and cathodic protection anode for reinforced concrete beams NGUYEN, C, MANGAT, Pal , LAMBERT, Paul, O'FLAHERTY,
More informationADAPT PT7 TUTORIAL FOR BEAM FRAME 1
ADAPT PT7 TUTORIAL FOR BEAM FRAME 1 Technical Note Structural Concrete Software System TN189_PT7_tutorial_beam_frame 012705 1 BEAM FRAME The objective of this tutorial is to demonstrate the step-by-step
More informationShin Shin Apparels Ltd. (9615) Dag RS. 228, JL 73, Gorat, East Norshinghapur, Zirabo, Savar ( N, E) 27.MAY.2014
Shin Shin Apparels Ltd. (9615) Dag RS. 228, JL 73, Gorat, East Norshinghapur, Zirabo, Savar (+23.94071N, 90.30929E) 27.MAY.2014 Identified Priority 1 Concerns 1 st Priority 1 Concern Based on the Detail
More informationModal-spectral analysis of a gas storage tank.
Modal-spectral analysis of a gas storage tank. Description of the structure: A Spherical tank gas storage is formed by: 1.- S-355 steel sphere plate elements of 1.5 cm thickness. 2.- Eight vertical posts
More informationA new approach for the patch repair of car parks using galvanic anodes
Loughborough University Institutional Repository A new approach for the patch repair of car parks using galvanic anodes This item was submitted to Loughborough University's Institutional Repository by
More informationFINAL REPORT. Gerardo G. Clemeña, Ph.D. Research Scientist Virginia Transportation Research Council
FINAL REPORT TESTING OF SELECTED METALLIC REINFORCING BARS FOR EXTENDING THE SERVICE LIFE OF FUTURE CONCRETE BRIDGES: TESTING IN OUTDOOR CONCRETE BLOCKS Gerardo G. Clemeña, Ph.D. Research Scientist Virginia
More informationApplications of sustainable post-tensioned concrete slabs
Innov. Infrastruct. Solut. (2017) 2:42 DOI 10.1007/s41062-017-0075-6 TECHNICAL PAPER Applications of sustainable post-tensioned concrete slabs Amr A. Abdelrahman 1 Received: 4 May 2017 / Accepted: 2 June
More informationDESIGN STANDARDS DEVELOPMENT REPORT FOR CORROSION RESISTANT PRESTRESSED CONCRETE PILES (INDEX No Series FY Design Standards)
FDOT Design Standards Development Report Proposed Index No. 22600 DESIGN STANDARDS DEVELOPMENT REPORT FOR CORROSION RESISTANT PRESTRESSED CONCRETE PILES (INDEX No. 22600 Series FY2016-17 Design Standards)
More informationRak Production Technology of Concrete Structures (2015) Concrete Reinforcement
Rak-82-2121 Production Technology of Concrete Structures (2015) Concrete Reinforcement 09.10.2015 1 Learning Outcomes To acquaint the student with concrete reinforcement 2 Reinforcement The of concrete
More informationSeismic Evaluation and Retrofit of Beam- Column Joints of Mid-America Bridges Part 2: Steel Sheet and Plate Retrofit
Seismic Evaluation and Retrofit of Beam- Column Joints of Mid-America Bridges Part 2: Steel Sheet and Plate Retrofit Genda Chen, Ph.D., P.E. Associate Professor of Civil Engineering Department of Civil,
More information