MODULE 5 HVAC FUNDAMENTALS OF MODERN LABORATORY DESIGN
|
|
- Aldous Morrison
- 5 years ago
- Views:
Transcription
1 MODULE 5 HVAC FUNDAMENTALS OF MODERN LABORATORY DESIGN Module 5 PG1
2 MODULE 5 GOAL Provide a fundamental understanding of Laboratory Heating, Ventilating and Air Conditioning Concepts and Systems Module 5 PG2
3 Module 6 Outline Issues Drivers Concepts Systems Module 5 PG3
4 Module 5 Issues Some of the most common concerns of laboratory facility users are relative to the HVAC system, including: It s too hot and humid in my lab! It s too cold and dry in my lab! It s like a tornado in my lab! Module 5 PG4
5 Module 5 Drivers Laboratory Equipment Heat Generation Air Change Rates Containment Equipment Occupant Gowning Requirements Type of Laboratory and Science Module 5 PG5
6 Module 5 Drivers Laboratory Equipment Heat Generation Heat Generation Information Heat is expressed in BTU/Hour 1 Watt = BTU/Hour Sensible Heat: Energy Required to Change Temperature Latent Heat: Energy Required to Remove Moisture One Ton of Air Conditioning: 12,000 BTU/Hour or 3,515 Watts 135 cfm of outside air equals 1 ton of cooling (Kansas City weather) Module 5 PG6
7 Module 5 Drivers Laboratory Equipment Heat Generation Loads for Bench Mounted Equipment (low density) Item Bench L.F. Btuh Optical Microscope Analytical balance 2 24 Computer & Monitor Rotary Evaporator Total Btuh Per Linear Foot 87 Watts per linear foot 26 Sources: ASHRAE 2001 Fundamentals Handbook Labconco Catalog Revco Freezer Data Sheets NOTE: This is heat release, not equipment nameplate electrical data Module 5 PG7
8 Module 5 Drivers Laboratory Equipment Heat Generation Loads for Bench Mounted Equipment (high density) Item Bench L.F. Btuh Optical Microscope Small Centrifuge Thermal Cycler Fluorescent Microscope Flame Photometer Rotary Evaporator Total Btuh Per Linear Foot 189 Watts per linear foot 55 Sources: ASHRAE 2001 Fundamentals Handbook Labconco Catalog Revco Freezer Data Sheets Module 5 PG8
9 Module 5 Drivers Laboratory Equipment Heat Generation Loads for Floor Mounted Equipment (high density) Item Floor L.F. Btuh Ultra Low Freezer Large Centrifuge Large Incubator Refrigerator Total Btuh Per Linear Foot 924 Watts per linear foot 271 Sources: ASHRAE 2001 Fundamentals Handbook Labconco Catalog Revco Freezer Data Sheets Module 5 PG9
10 Module 5 Drivers Laboratory Equipment Heat Generation Two Module Lab Example (484 SF): 16 feet of space allocated for floor mounted equipment 48 feet of bench space Assume half the bench is full 24 of equipment Heat Generated using moderate density: Bench: 138 btuh/ft X 24 = 3312 btuh Floor: 662 btuh/ft X 16 = 10,592 btuh Total: *13,904 btuh More than 1 ton of A/C Using 100% outside air in Kansas City: 57,300 btuh (4.75 tons) *There is no diversity in this number Module 5 PG10
11 Module 5 Drivers Laboratory Equipment Heat Generation When figuring equipment heat gain: Use published or measured heat release information, not electrical nameplate Apply diversity carefully based on expected lab use Consider sub-metering loads in similar buildings prior to planning a new lab The answer is not 10 watts/sq.ft. Module 5 PG11
12 Module 5 Drivers Air Change Rates 1 Air Change per Hour The Amount of Air in Cubic Feet per Minute (CFM) it Takes to Completely Replace the Air in a Laboratory once in One Hour CFM = (Floor Area x Ceiling Height x Air Change Rate)/ CFM per One Ton of Cooling Standards and Guidelines Vary from 4 to 12 AC/hr Module 5 PG12
13 Module 5 Drivers Air Change Rates 2 Module Laboratory (22 x 22 ); 484 SF CFM Requirement for varying ceiling heights and air change rates MORE IS NOT NECESSARILY BETTER Airflow in CFM at Given Air Change Rate Ceiling Height Module 5 PG13
14 Module 5 Drivers Air Change VS. Fume Hoods 2 Module Laboratory (22 x 22 ); 484 SF CFM Requirement for varying ceiling heights and air changes Airflow in CFM at Given Air Change Rate Ceiling Height Nominal Fume Hood CFM 5' Fume Hood 6' Fume Hood 8' Fume Hood 960* 1180* 1660* 610** 750** 1060** * Sash full open; face velocity 100 fpm ** Sash at 18 ; face velocity 100 fpm Module 5 PG14
15 Module 5 Drivers Containment Equipment Approximate Exhaust CFM for 6 BSC Class II Type A2 Cabinet without canopy: 0 cfm Class II Type A2 Cabinet with canopy: cfm Class II Type B2 Cabinet : 1150 cfm (requires a dedicated exhaust fan Select the correct cabinet for the application Cabinets that use ECM motors have significantly lower heat gain and higher efficiency than PSC motors Module 5 PG15
16 Module 5 Drivers Air Changes VS. Containment Equipment *Laboratories often use 4 to 6 times more energy per sq. ft. than a typical office building *Nearly half of electrical energy used in a laboratory building can be attributed to ventilation The decision on air exchange rates and fume hood sash position affect both first cost and lifetime building energy costs Annual electricity use in Louis Stokes Laboratory, National Institutes of Health, Bethesda, MD Courtesy of Labs 21 *Courtesy of Labs 21 Module 5 PG16
17 Module 5 Drivers Gowning/PPE Impact of Gowning/PPE in Laboratory May require reduction in Laboratory Design Temperature Reducing Design Temperature from 72 deg. F to 70 deg. F results in: A 12% increase in cooling airflow A 12% increase in cooling capacity Module 5 PG17
18 Module 5 Drivers Type of Laboratory/Type of Science Animal Holding Rooms 10 to 15 Air Changes per hour Module 5 PG18
19 Module 5 Drivers Type of Laboratory/Type of Science Instrument/Computational Laboratories High Equipment Heat Loads Module 5 PG19
20 Module 5 Drivers Type of Laboratory/Type of Science Chemistry/Analytical Laboratories High Fume Hood Density Module 5 PG20
21 MODULE 5 BASIC CONCEPTS Laboratory Hazards Containment Flexibility & Redundancy Module 5 PG21
22 Module 5 Concepts Laboratory Hazards Health Hazards Irritants Corrosive Substances Allergens Asphyxiants Carcinogens Reproductive Toxins Neurotoxins Flammability Hazards Reactivity Hazards Explosive Hazards Biohazards Radioactive Hazards Module 5 PG22
23 Module 5 Concepts Containment Primary Containment First Level of Containment; typically a containment device: chemical fume hood, biological safety cabinet, etc. Module 5 PG23
24 Module 5 Concepts Containment Secondary Containment Second Level of Containment: Laboratory Envelope Directional Airflow 100% Outside Air Differential Pressure or Volumetric Offset Doors must be kept closed Exhaust fans run continuously Best Practices: Use Primary and Secondary Containment to Protect Personnel from Exposure to Hazards ANSI Z9.5 requires air movement from lower hazard to higher hazard Module 5 PG24
25 Module 5 Concepts Containment Primary Containment Devices - Chemical Fume Hoods Bench Mounted Chemical Fume Hoods Each Fume Hood uses as much energy as an entire house* * From Labs 21 Module 5 PG25
26 Module 5 Concepts Containment Primary Containment Devices - Chemical Fume Hoods Floor Mounted Chemical Fume Hoods or Ventilated Enclosures Module 5 PG26
27 Primary Containment Devices - Chemical Fume Hoods Floor Mounted Hood Location is Critical Module 5 PG27
28 Module 5 Concepts Containment Primary Containment Devices - Chemical Fume Hoods Radioisotope Hood Stainless steel interior Requires dedicated exhaust fan Coved corners for decontamination May need HEPA filters Consult your Radiation Safety Officer Module 5 PG28
29 Module 5 Concepts Containment Primary Containment Devices - Chemical Fume Hoods Perchloric Acid Hood Acid resistant interior Dedicated acid resistant ran Acid resistant sealed ductwork Washdown system Treat wastewater from washdown Do NOT manifold these hoods Module 5 PG29
30 Module 5 Concepts Containment Primary Containment Devices - Chemical Fume Hoods Variable Volume Fume Hood Face velocity is maintained constant as sash is raised and lowered Requires pressure independent control device Requires variable control usually exhaust air bypass damper Must maintain a minimum flow when sash is fully closed (ANSI Z9.5 no longer specifies how much) Module 5 PG30
31 Module 5 Concepts Containment Primary Containment Devices - Chemical Fume Hoods High Performance Fume Hood Hood provides containment at lower face velocity Each manufacturer uses a different design Apply with caution Low Flow does not necessarily equate to High Performance More sensitive to cross drafts Labconco Lawrence Berkeley Labs Module 5 PG31
32 Module 5 Concepts Containment Primary Containment Devices - Chemical Fume Hoods Ductless Fume Hood Uses activated carbon and/or HEPA filters Use only in tightly controlled conditions NFPA 45 allows only for nuisance vapors & dusts Module 5 PG32
33 Module 5 Concepts Containment Primary Containment Devices Biological Safety Cabinets Personnel protection Environmental protection Can provide product protection Not a chemical fume hood!!!! Used for biological/microbiological work Module 5 PG33
34 Module 5 Concepts Containment Biological Safety Cabinets (BSC s) Class I: Ventilated cabinet for personnel and environmental protection. No product protection Class II: Ventilated cabinet for personnel, product, and environmental protection. Type A1, A2, B1, and B2 Class III: Totally enclosed ventilated cabinet of leak-tight construction. Operations conducted through attached rubber gloves. Sometimes called glove boxes. Select the correct cabinet for the application Module 5 PG34
35 Module 5 Concepts Other Devices (Non Containment) Other Devices Not Chemical Fume Hoods Canopy Hoods Snorkels Slot Hoods Module 5 PG35
36 Module 5 Concepts Other Devices (Non Containment) Other Devices Canopy Hoods Not appropriate for fumes Hot applications only (ovens, GC/MS, non-hazardous hot tanks, glassware washing, cage washing, etc.) Must have mass of hot moving air to contain Module 5 PG36
37 Module 5 Concepts Other Devices (Non Containment) Other Devices Snorkel Hoods Bench top activities that require exhaust Ideal containment device for dissections Good for bench top soldering, etc. Module 5 PG37
38 Module 5 Concepts Flexibility and Redundancy Three truths for the Laboratory HVAC Designer What s happening in the laboratory tomorrow will be different than what s happening today Fume hood density nearly always increases over time The amount of heat generating equipment will increase over time Module 5 PG38
39 Module 5 Concepts Flexibility and Redundancy Plan for flexibility and future growth Allow extra space in the mechanical room to add equipment (chiller, boiler, air handler, exhaust fans) Allow for additional shaft and ceiling space Size ducts and pipe for spare capacity (inexpensive if done initially) Module 5 PG39
40 MODULE 5 SYSTEMS HVAC Module 5 PG40
41 Module 5 Systems HVAC Laboratory HVAC Look at three different criteria and choose worst case: Cooling load (primarily heat generating equipment) Minimum air change rate Exhaust requirement Consider supplemental cooling for high density loads (freezer rooms, etc.) Module 5 PG41
42 Module 5 Systems HVAC Laboratory HVAC Design Considerations The effect of room air challenge is significant and of the same order of magnitude as the effect of face velocity Consequently, improper design of replacement air supply can have a disastrous effect on the efficiency of a laboratory hood. ASHRAE RP-70, Caplan and Knutson, 1977 Module 5 PG42
43 Module 5 Systems HVAC Laboratory HVAC Design Considerations Supply air distribution shall be designed to keep air jet velocities less than half, preferably less than one-third of the capture velocity or the face velocity of the laboratory chemical hoods at their face opening. ANSI/AIHA Z , section Module 5 PG43
44 Module 5 Systems HVAC Laboratory Exhaust Systems Fan discharge design must minimize risk of re-entrainment Stack/Intake separation Stack height Stack effective height/momentum Stack discharge velocity must be 3,000 fpm, minimum Module 5 PG44
45 Module 5 Systems HVAC Laboratory Exhaust Systems Heat Recovery Air to air plate heat exchanger Run around loop Molecular sieve enthalpy wheel Module 5 PG45
46 Module 5 Systems HVAC Laboratory Exhaust Systems ANSI/ASHRAE/IESNA Prescriptive path requires some combination of VAV and/or heat recovery for most lab HVAC systems Alternative is Energy Cost Budget Method Module 5 PG46
47 Module 5 Systems HVAC Laboratory Exhaust Systems ANSI/ASHRAE January, 2011 interpretation precludes using any technology for laboratory fume hood or chemical storage room exhaust heat recovery that results in any amount of cross contamination This appears to disallow the use of total energy recovery wheels Addendum K is out for public review Module 5 PG47
48 Module 5 Systems HVAC COURTESY OF LABS 21 Module 5 PG48
49 Module 5 Systems HVAC How Much Mechanical Space? Between 8 and 20% of gross building square footage 8% for simpler academic buildings 20% for complex labs or buildings with animal areas Vivariums or BSL containment labs may require 50% of the gross building area for mechanical space Module 5 PG49
50 Module 5 Systems HVAC Applicable Standards and Guidelines Module 5 PG50
Forum M: Top 10 Cost Reduction Strategies for Science Facility Operations and Maintenance
Forum M: Top 10 Cost Reduction Strategies for Science Facility Operations and Maintenance Forum M: Top 10 Cost Reduction Strategies for Science Facility Operations and Maintenance Presentation Outline
More informationStandard Operating Procedures for Servicing Laboratory Exhaust Systems
Standard Operating Procedures for Servicing Laboratory Exhaust Systems Policy Statement The following procedures were developed to protect Facilities & Services (F&S) personnel and University laboratory
More informationAchieving Near Net-Zero Energy Usage in Laboratory
Page 1 of 8 Published on www.tradelineinc.com (http://www.tradelineinc.com) Home > Achieving Near Net-Zero Energy Usage in Laboratory Facilities Achieving Near Net-Zero Energy Usage in Laboratory Facilities
More informationLocal Exhaust Ventilation
Local Exhaust Ventilation University of Tennessee Safety Guide IH-001 Document Contact: EHS Date effective: August 1, 2014 Revision Date: July 1, 2016 Purpose The purpose of this document is to provide
More informationDIVISION 11 - EQUIPMENT FOOD SERVICE EQUIPMENT LABORATORY FUME HOODS. A. Design Considerations
DIVISION 11 - EQUIPMENT 11400 FOOD SERVICE EQUIPMENT A. Design Considerations 1. The A/E shall use the services of a food service equipment specialist in preparation of kitchen areas and other food preparation
More informationAPPENDIX W (Combined Appendix N and W) 2006 Edition, Published January 1, 2006; Document Revision Date: October 16, 2017
(Combined Appendix N and W) 2006 Edition, Published January 1, 2006; Document Revision Date: October 16, 2017 LABORATORY HOODS, SAFETY CABINETS AND VENTILATION SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. This
More informationThe bitterness of poor quality is remembered long after the sweetness of low price is forgotten!
Heat Pump Sizing Using ACCA Manual J8 It s s a Building Code Requirement Size the Equipment BEFORE You Build The bitterness of poor quality is remembered long after the sweetness of low price is forgotten!
More informationEvaluating Alternative Fume Hood System Technologies Using Advanced Building Simulation
Evaluating Alternative Fume Hood System Technologies Using Advanced Building Simulation William J. Kosik, P.E., C.E.M. 1 Karl Aveard, AIA Associate 2 Heather R. Beaudoin, P.E., C.E.M. 3 Erik L. Olsen 3
More information1.0 Purpose, Applicability, and Scope
Policy Subject: Local Exhaust Ventilation Policy Effective: 8/1/2014 Affected Area/Department: All Departments who use Local Exhaust Ventilation Systems Reviewed/Revised: 8/1/2014 1.0 Purpose, Applicability,
More informationHow to Reduce Energy Use in Your Labs by Up to 50%
How to Reduce Energy Use in Your Labs by Up to 50% Illinois Chapter of ASHRAE April 11, 2017 Dan Doyle, Chairman Grumman/Butkus Associates 1 Course Description Labs have high exhaust requirements and large
More informationThesis Proposal. Clemson University Advanced Material Research Laboratory Anderson, SC. David Anderson Mechanical Option. Photo by Fred Martin
Thesis Proposal Photo by Fred Martin Clemson University Advanced Material Research Laboratory Anderson, SC David Anderson Mechanical Option Friday, December 15, 2006 Table of Contents 1. Executive Summary
More informationA Paradigm Shift in ERV Technology. Paul Ehrlich, PE President Building Intelligence Group PLLC
A Paradigm Shift in ERV Technology Paul Ehrlich, PE President Building Intelligence Group PLLC August 9, 2013 Existing Buildings and Energy Existing buildings: Floor space: Floor space per building: Energy
More informationSECTION LABORATORY FUME HOODS
PART 1 - GENERAL 1.1 DESCRIPTION: SECTION 11 53 13 LABORATORY FUME HOODS SPEC WRITER NOTE: Delete between // // if not applicable to project. Delete other items or paragraphs in the section that are not
More informationSustainable Laboratory Design: Challenges and Solutions
Sustainable Laboratory Design: Challenges and Solutions Stephen P. Mead Ph.D. College of Engineering Northern Arizona University U.S.A. Abstract: This paper provides a case study analysis of a biohazard
More informationSouth Jefferson High School Huyett Road Charles Town, WV 25414
Thesis Proposal Mechanical System Redesign Report Charles Town, WV 25414 Prepared for Dr. Jelena Srebric The Pennsylvania State University By Jonathon Gridley Friday, December 15, 2006 1.0 Table of Contents
More informationPlanning for Biomed Facility Puts Energy Efficiency Under Microscope
Planning for Biomed Facility Puts Energy Efficiency Under Microscope Chilled beams, runaround-loop ERV system included May 19, 2014 By DAN VASTYAN, Common Ground, Manheim, Pa. HPAC Engineering Constructing
More informationMity, relative static pressure, air motion, air cleanliness, sound,
CHAPTER 14 LABORATORIES Laboratory Types... 14.1 Hazard Assessment... 14.2 Design Parameters... 14.2 LABORATORY EXHAUST AND CONTAINMENT DEVICES... 14.3 Fume Hoods... 14.3 Biological Safety Cabinets...
More informationAir-Water Systems. Chilled Ceilings and Beams TROX USA. Principle of Operation. Radiant Effect on Occupants. Early 1980 s. Chilled Ceiling Panels
Air-Water Systems and Beams Early 1980 s 1980 1990 2005 Buildings well insulated for heating Advent of personal computers Need to remove heat from space Limited space available TROX USA 1 2 Principle of
More information15020 LABORATORIES. C. Section Building Automation and Control System Guidelines
15020 LABORATORIES PART 1: GENERAL 1.01 RELATED SECTIONS A. Section 01004 Energy Guidelines B. Section 01008 Energy Modeling Guidelines C. Section 15955 Building Automation and Control System Guidelines
More informationFixed equipment shall generally be furnished and installed by the General Contractor as part of the construction contract.
SECTION 11 00 00 - EQUIPMENT GENERAL INFORMATION Fixed equipment shall generally be furnished and installed by the General Contractor as part of the construction contract. Movable equipment shall, as a
More informationGreen for green s sake: Energy-efficient design can help reduce laboratory operating costs
Energy Conservation article originally published in the ISPE Delaware Valley Chapter Summer 2009 newsletter Green for green s sake: Energy-efficient design can help reduce laboratory operating costs Companies
More informationIECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST
IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST ENVELOPE REQUIREMENTS Project: Date: Instructions RECOMMENDED: List performance values, note exceptions that were applied, or provide other
More informationModular Active Chilled Beams
Modular Active Chilled Beams Presented by: Darren Alexander, P.Eng. Modular Active Chilled Beams Current System Solutions Fan Coil Units - Medium/High energy, medium noise solution. Output = 100-200 w/m
More informationGood indoor air quality (IAQ) management has become paramount in the construction industry as study
Creating and Maintaining Good Indoor Air Quality Good indoor air quality (IAQ) management has become paramount in the construction industry as study after study shows that employee productivity and health
More informationUNIVERSITY OF NORTH DAKOTA
UNIVERSITY OF NORTH DAKOTA Safety & Environmental Health Office Standard Practice RSP 7 Testing and Maintenance of Radioisotope Fume Hoods Effective Date January 31, 1999 I. PURPOSE The purpose of this
More informationSection 6.6 BSL3 & ABSL3 Biocontainment
NIH Design Requirements Manual 8-22-12 Section 6.6 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 Section 6.6
More informationENERGY CONSERVATION STRATEGIES FOR HVAC SYSTEMS
ENERGY CONSERVATION STRATEGIES FOR HVAC SYSTEMS Heating ventilation and airconditioning systems consumes nearly 50 to 60% of the total power consumption in any building and thus, offers huge potential
More informationPART 30: LABORATORIES
PART 30: LABORATORIES GENERAL REQUIREMENTS Definitions 30.7.1 In sections 30.8 to 30.11: laboratory fume hood operational face opening sash Laboratory fume hoods means an enclosed and mechanically ventilated
More informationGrunenwald Science and Technology Building
Grunenwald Science and Technology Building Clarion University- Clarion, PA AE 482 Mechanical Project Proposal: Proposal for Alternative Designs Shane Helm The Pennsylvania State University Architectural
More informationThe Safety and Sustainability Factors of FILTERED FUME HOODS, DUCTLESS FUME HOODS, AND DUCTED FUME HOODS. By Kenneth Crooks
The Safety and Sustainability Factors of FILTERED FUME HOODS, DUCTLESS FUME HOODS, AND DUCTED FUME HOODS By Kenneth Crooks Fume hoods are a central component in most laboratories. Whether you are designing
More informationDepth: Mechanical Redesign
Depth: Mechanical Redesign Redesign Objectives The most important objective of the mechanical redesign is to provide Greenbriar East with ventilation that meets the requirements of ASHRAE Standard 62-2001.
More informationNext Generation: High Efficiency Energy Recovery Ventilator (ERV) 11/14/11 Dais Analytic Corporation
Next Generation: High Efficiency Energy Recovery Ventilator (ERV) 11/14/11 Dais Analytic Corporation Why use an ERV? Required by code in many states (ASHRAE & IBC) Pre-condition incoming fresh air using
More informationChilled Beams Selection BY DAN INT-HOUT, FELLOW ASHRAE; AND LILLI WILBAR
This article was published in ASHRAE Journal, November 2014. Copyright 2014 ASHRAE. Reprinted here by permission from ASHRAE at www.krueger-hvac.com This article may not be copied nor distributed in either
More informationLab Ventilation Safety & Energy Efficiency. Agenda & Objectives
Lab Ventilation Safety & Energy Efficiency Methods to Achieve Safe and Energy Efficient Laboratory Ventilation Systems Thomas C. Smith tcsmith@labhoodpro.com Agenda & Objectives Introduction Laboratory
More informationChilled Beams. The new system of choice?
Chilled Beams The new system of choice? Presented By: Kevin M. Pope P.E. Jason Leffingwell Hammel Green And Abrahamson, Inc. and Ken Bauer, P.E., LEED AP Butters-Fetting Co., Inc. History of Chilled Beams
More informationSECTION (SECTION 15700) CENTRAL HEATING, VENTILATING, & AIR CONDITIONING (HVAC) EQUIPMENT
This is a guidance document with sample specification language intended to be inserted into project specifications on this subject as appropriate to the agency's environmental goals. Certain provisions,
More informationPresenter: Wayne Wood, CIH, ROH, MScA. Director EHS, McGill University
Presenter: Wayne Wood, CIH, ROH, MScA Director EHS, McGill University 1 Our agenda CSA - the standard-setting process The stakeholders The Z316.5-15 technical subcommittee Content of Z316.5-15 Z316.5-04
More informationDISPLACEMENT VENTILATION
DISPLACEMENT VENTILATION D3 OVERVIEW The fundamental approach to displacement ventilation utilizes the natural buoyancy forces created by the convective flows from heat sources in the space. As supply
More informationGeorgetown University New Science Center
Georgetown University New Science Center Final Thesis Proposal PENN STATE UNIVERSITY Prepared For: Dr. William P. Bahnfleth Department of Architectural Engineering Prepared By: Kevin M Edstrom Mechanical
More informationVariable Air Volume (VAV) For Laboratories
Variable Air Volume (VAV) For Laboratories by Steven G. Liescheidt, PE, CCS, CCPR Overview: Variable Air Volume (VAV) systems have been used for many years in commercial HVAC systems for a variety of reasons.
More informationNew Methods and Standards for Improving Safety & Reducing Energy Use in Laboratory Buildings. Introduction & Agenda
New Methods and Standards for Improving Safety & Reducing Energy Use in Laboratory Buildings Thomas C. Smith Robert Lukens LabHoodPro tcsmith@labhoodpro.com Laboratory Hood Products rlukens@labhoodpro.com
More informationEMD SERONO RESEARCH CENTER EXISTING
EMD SERONO RESEARCH CENTER EXISTING BILLERICA, MA SHIYUN (SHARON) CHEN MECHANICAL AE SENIOR THESIS Building System Dedicated Outdoor Air System/ Systems Breadth Building Design Team Building: EMD Serono
More informationASHRAE 62.2: What s New in 2016
ASHRAE 62.2: What s New in 2016 Rick Karg 2016 Residential Energy Dynamics, LLC What We Will Talk About Overview of mechanics of 62.2-2016. Logic behind the Standard. Sizing local ventilation (exhaust-only).
More informationRebel commercial packaged rooftop systems
Rebel commercial packaged rooftop systems Advanced technologies propel performance and energy savings to uncommon levels 3-28 tons Rebel features and benefits 18 13 6 5 3 6 4 43% Energy Savings 5 11 12
More informationRebel commercial packaged rooftop systems
Rebel commercial packaged rooftop systems Advanced technologies propel performance and energy savings to uncommon levels 3-28 tons Capitalize with 43% more energy savings If you are a commercial building
More information1. PREINSPECTION RESIDENTIAL ENERGY EFFICIENCY 7
Chapter 4 Residential Energy Efficiency [Residential structures include R-3 buildings; R-2 and R-4 buildings three stories or less in height built to the International Building Code (see IBC classifications)]
More information+ IQ/OQ Protocol Installation Qualification/ Operation Qualification
+ IQ/OQ Protocol Installation Qualification/ Operation Qualification Purifier Logic Series Biological Safety Cabinets Labconco o: 1058602 Rev. - Available at www.labconco.com or by e-mail in Word 2000
More informationChanges to the Minnesota Commercial Energy Code. Presented by: Andy Thielen, PE
Changes to the Minnesota Commercial Energy Code Presented by: Andy Thielen, PE Warning! The following is an outline of proposed code changes. There is no guarantee that the final code adopted by the State
More informationUnderf loor For Schools
The following article was published in ASHRAE Journal, May 2008. Copyright 2008 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes
More informationMechanical Systems Proposal
Mechanical Systems Proposal Prepared for: Dr. William Bahnfleth, Professor The Pennsylvania State University, Department of Architectural Engineering Prepared by: Chris Nicolais Mechanical Option December
More informationFUNDAMENTALS OF CHILLED BEAMS ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS
FUNDAMENTALS OF CHILLED BEAMS ANSI/ASHRAE STANDARD 200-2015, METHODS OF TESTING CHILLED BEAMS NEMIC 2017 Hello! I am Davor Novosel I am here because I love to share what I know about chilled beams with
More informationItalcementi Center for Research and Innovation
Italcementi Center for Research and Innovation Bergamo, Italy LEED-NC v2.1 EAc1 A. Project Narrative (Viridian) analyzed the energy use of the proposed Italcementi Center for Research and Innovation located
More informationNext Connecticut Energy Code
Connecticut Chapter Association of Energy Engineers Next Connecticut Energy Code 1 Next Connecticut State Building Code n 2012 International Building Code n 2012 International Existing Building Code n
More informationIECC Commercial Significant Changes Summary Tier I
2009-2015 IECC Commercial Significant Changes Summary Tier I The first change is in the layout of the book. Instead of having Chapters 1-3 that applied to all projects and then having Chapter 4 Residential
More information2. The requirements of Sections 502, 503, 504 and 505. In addition, commercial buildings shall comply with either Section 506.2, or
Public Comment 3: Dave Hewitt, representing New Buildings Institute, Jessyca Henderson, representing American Institute of Architects, Ron Majette, representing U.S. Department of Energy requests Approval
More informationIECC 2006 with Hawaii Amendments
IECC 2006 with Hawaii Amendments COMMERCIAL PLAN REVIEW CHECKLIST ENVELOPE REQUIREMENTS Instructions This form is intended for use by energy code plan reviewers. Please see also a separate set of checklists
More informationIllinois Sustainable Technology Center, University of Illinois at Urbana-Champaign
Topic B14: Policy, standards, and regulations ASHRAE STANDARD 62.2: WHAT S NEW AND WHY Paul W FRANCISCO,* Illinois Sustainable Technology Center, University of Illinois at Urbana-Champaign *Corresponding
More informationASHRAE 62.2: What s New in 2016
ASHRAE 62.2: What s New in 2016 Rick Karg 2018 Residential Energy Dynamics, LLC What We Will Talk About Overview of mechanics of 62.2-2016. Logic behind the Standard. Sizing local ventilation (exhaust-only).
More information1. Scientific Apparatus Makers Association Standard for Laboratory and Hospital Service Fittings
SECTION 11 53 13 - CHEMICAL FUME HOODS PART I - GENERAL 1.1 SECTION INCLUDES A. Chemical Fume Hoods, Benchtop Type 1. Constant Volume 2. Variable Air Volume (VAV) 3. High Performance 4. Radioisotope 5.
More informationEnergy Efficiency Baselines for LABORATORIES. PG&E s Customized New Construction and Customized Retrofit Incentive Programs.
Energy Efficiency Baselines for LABORATORIES PG&E s Customized New Construction and Customized Retrofit Incentive Programs October 1, 2010 Funded By: Written By: 427 13 th Street Oakland, CA 94612 510.663.2070
More informationLABORATORIES 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS. A. Section Accessibility for People with Disabilities
230540 LABORATORIES PART 1 GENERAL 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS A. Section 013010 Accessibility for People with Disabilities B. Section 018120 Energy Guidelines C. Section 018130
More informationUBC Technical Guidelines Section Edition Fume Hoods Page 1 of 5
Page 1 of 5 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 12 35 53 Laboratory Casework.2 Section 23 38 16 Fume Hood Exhaust Systems.3 Section 20 00 08 Mechanical Identification for the details for fume
More informationSECTION AIR-TO-AIR ENERGY RECOVERY EQUIPMENT
SECTION 23 72 00 AIR-TO-AIR ENERGY RECOVERY EQUIPMENT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 02/06/2013 BUILDING SURVEY DATE
0067 1110 WEST GREEN STREET URBANA, ILLINOIS 61801 SYSTEM CONDITION INDEX.810 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 18,640,900 OFFICE BUILDING GROSS SQUARE FEET 175,513
More informationAppendix E-1f: Small Building Methodology for Pre-SB2030 Projects
Appendix E-1f: Small Building Methodology for Pre-SB2030 Projects Prescriptive Bundle Option Method for Office Buildings less than 30,000 GSF This section describes energy strategy requirements for three
More informationUNIVERSITY POLICY STATEMENT S3/14 FUME CUPBOARDS. 1. Introduction
UNIVERSITY SAFETY OFFICE 10 Parks Road, Oxford OX1 3PD General Enquiries Tel: +44 (0)1865 270811 Fax: +44 (0)1865 270816 Web: www.admin.ox.ac.uk/safety/ UNIVERSITY POLICY STATEMENT S3/14 1. Introduction
More informationExample LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal
Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal The following documentation provides an example submittal for the LEED-NC v2.1 Energy & Atmosphere Credit 1 (EAc1). This sample EAc1 submittal
More informationSection Gas, Chemical, Hazardous Material Storage
1 2 Gas, Chemical, Hazardous Material Storage 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 4.4.1 General Comply with the design and safety guidelines
More informationReport on Safe, Appropriate Uses for Filtered Self-Contained Enclosures
Report on Safe, Appropriate Uses for Filtered Self-Contained Enclosures The need for alternatives to fume hoods Until the past decade, laboratory directors and safety officers have had only one option
More informationUNILAB MODULAR CLEAN LABS
Sized to suit your space requirements, pre-engineered for prompt on site assembly. Equipped with HVAC system, lighting & electrical service to specs. HEPA filtered supply air to suit your modular clean
More informationThe Milton S. Hershey Medical Center Academic Support Building. AE Senior Thesis Kari Anne Donovan Mechanical Option
The Milton S. Hershey Medical Center Academic Support Building AE Senior Thesis Kari Anne Donovan Mechanical Option Presentation Outline Existing Conditions Distributed Chilled Water Feasibility Study
More informationFSU Specifications for Systems and Safety Equipment associated with Laboratories and Hazardous Materials Storage or Usage Areas
FSU Specifications for Systems and Safety Equipment associated with Laboratories and Hazardous Materials Storage or Usage Areas The Florida State University (FSU) requires construction or renovation projects
More informationLarge University Central Chiller Plant Design Considerations
Carrier Engineering Newsletter Volume 5, Issue 3 Large University Central Chiller Plant Design Considerations Large campus chilled water plants have unique constraints and need careful evaluation for successful
More informationIndoor Air Quality and Mechanical Ventilation (Page 1 of 5)
Indoor Air Quality and Mechanical Ventilation (Page 1 of 5) Title 24, Part 6, Section 150.0(o) Ventilation for Indoor Air Quality. All dwelling units shall meet the requirements of ANSI/ASHRAE Standard62.2.
More informationMODULE #5 MECHANICAL, ELECTRICAL, PLUMBING II
MODULE #5 MECHANICAL, ELECTRICAL, PLUMBING II MICHAEL WALSH PRINCIPAL, R.G. VANDERWEIL ENGINEERS, LLP 274 Summer Street, Boston, MA 02210 (T) 617-423-7423 (F) 617-423-7401 mwalsh@vanderweil.com Module
More informationField Accuracy of Temperature Measurements in TAB Work Andrew P. Nolfo, PE
Field Accuracy of Temperature Measurements in TAB Work Andrew P. Nolfo, PE The purpose of this article is to discuss the measuring and reporting of temperatures at heat transfer equipment during the Testing
More informationCHAPTER 3. BUILDING THERMAL LOAD ESTIMATION
CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION 3.1 Purpose of Thermal Load Estimation 3.2 Heating Load versus Cooling Load 3.3 Critical Conditions for Design 3.4 Manual versus Computer Calculations 3.5 Heating
More informationNC State University Design and Construction Guidelines Division 00 Planning & Design - Laboratory Design
1.0 Purpose A. This section discusses the safety features that must be included in university laboratories and the design standards for various classifications of laboratories and laboratory equipment.
More information780 CMR: 9 th Edition Massachusetts State Building Code. Presented to: BSA Codes Committee. DATE: January 20, 2016
780 CMR: 9 th Edition Massachusetts State Building Code Presented to: BSA Codes Committee DATE: January 20, 2016 This course is registered with AIA CES for continuing professional education. Credit(s)
More informationSHIYUN CHEN ADVISOR: DR. BAHNFLETH. 1 Executive Summary Building Summary 3. 3 Existing Mechanical System. 4
Table of Contents 1 Executive Summary... 1 2 Building Summary 3 3 Existing Mechanical System. 4 4 Mechanical Design Objectives..... 4 5 Mechanical System Evaluation. 5 5.1 Air Distribution System Evaluation....
More informationDesign Evolution for HVAC Systems
Design Evolution for HVAC Systems What We Know Ductless Heat Pumps Reliable Efficient Having my DHP installed was as easy as falling off a log! Energy saving Can be aesthetically pleasing Give homeowners
More information1. ARI 410 Standard for chilled water, hot water and steam coils. 2. ARI 430 Central Station Air Handling Units
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationENERGY EFFICIENT AIR QUALITY CONTROL IN LABORATORIES USING BENCH EXHAUSTS
ENERGY EFFICIENT AIR QUALITY CONTROL IN LABORATORIES USING BENCH EXHAUSTS Farhad Memarzadeh 1, Jane Jiang 2, and Andy Manning 2 1 PhD, PE, National Institutes of Health, Bethesda, MD, USA 2 PhD, Flomerics,
More informationMechanical Systems Project Proposal
Mechanical Systems Project Proposal December 15, 2006 Table of Contents 1.0 Executive Summary... 2 2.0 Building Background... 3 3.0 Proposal Objectives... 5 4.0 Initial Considerations... 6 5.0 Proposed
More informationYou Can t Afford Discomfort. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas
You Can t Afford Discomfort Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Where We Are Today: So You Want To Save Money? Things to consider: 1. First Cost 2. Energy cost 3. Occupant Salary costs
More informationDesigning for Actual Not Theoretical HVAC Requirements in Laboratory Facilities
October 4, 2007 Charleston, SC Designing for Actual Not Theoretical HVAC Requirements in Laboratory Facilities J. Patrick Carpenter, PE Principal V a n d e r w e i l E n g i n e e r s What Are Laboratory
More informationFOOD INNOVATION CENTER. Nebraska Innovation Campus 2021 Transformation Dr Suite 2220 / Lincoln, NE innovate.unl.
FOOD INNOVATION CENTER Nebraska Innovation Campus 2021 Transformation Dr Suite 2220 / Lincoln, NE 68508 402.472.5535 innovate.unl.edu Tetrad Property Group 2021 Transformation Dr Suite 1100 / Lincoln,
More informationSolvent Recovery Systems
Solvent Recovery Systems Use Steam Recycling A new technique that recycles the heat normally lost during solvent recovery can cut fuel bills and reduce plant exhaust emissions. by Stanley J. Macek Compliance
More informationAN INNOVATIVE DEDICATED OUTDOOR AIR APPLICATION FOR A GOVERNMENT OFFICE TOWER. MICHAEL HALLENBECK, PE, CEM Southland Industries
AN INNOVATIVE DEDICATED OUTDOOR AIR APPLICATION FOR A GOVERNMENT OFFICE TOWER MICHAEL HALLENBECK, PE, CEM Southland Industries BRAC 133 OVERVIEW PROJECT OVERVIEW FAN POWERED INDUCTION UNIT CENTRAL UTILITY
More informationMajor Texas Energy Code Changes (CZ3) TexEnergy Solutions August 30 th, 2016
Major Texas Energy Code Changes (CZ3) TexEnergy Solutions August 30 th, 2016 Goals for today To give an overview of the Energy Code changes coming to Texas per Texas State Law. Will focus on IRC and Residential
More informationWhat s Possible? Extreme repurposing of non-lab spaces in to state-of-the-art research facilities: Tradeline Research Facilities May 9-10, 2013
Extreme repurposing of non-lab spaces in to state-of-the-art research facilities: What s Possible? Tradeline Research Facilities May 9-10, 2013 Jeff Goldberg/Esto Presenters STEVE FREI, PE, LEED AP Principal
More informationThe Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma
LEED Green Building Certification The purpose of the LEED Green Building Rating is to provide a national standard that aims to improve environmental, health and economic performance of buildings using
More informationASHRAE 90.1 The evolution continues
ASHRAE 90.1 The evolution continues 4 March 2009 Mick Schwedler, PE ASHRAE SSPC 90.1 Chair Manager, Trane Applications Engineering Historical Timeline 90.1-1980 updated 90.1-1999 major rewrite 90.1-2001
More information2012 Fiscal Impact International Mechanical Code
2012 Section No. 306.5 Item 2 2012 Code Information - bold text = new text found in 2012 strike out = text deleted and not found in the 2012 Equipment and appliances on roofs or elevated structures: Item
More informationANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS
ANSI/ASHRAE STANDARD 200-2015, METHODS OF TESTING CHILLED BEAMS NEMIC 2017 Agenda 1. Foreword 2. Purpose & Scope 3. Definitions 4. Instrumentation & Facilities 5. Test Methods 6. Reporting 7. Normative
More informationEADQUARTERS. Thesis Revised Proposal. Stephanie Kunkel Mechanical Option
EADQUARTERS 707 N. Calvert St. Mechanical System Renovation Construction Management & Lighting/Electrical Breadths Stephanie Kunkel www.engr.psu.edu/ae/thesis/portfolios/2011/slk5061 Mechanical Option
More informationWhat s My Baseline? ASHRAE
2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions (2010, vol 116,part 2). For personal use only. Additional reproduction,
More informationEnergy Efficiency in Building Active Design Part II
Energy Efficiency in Building Active Design Part II Presented by: CK Tang BSEEP Component 4 Manager Veritas Enviornment Sdn Bhd ck.tang@veritas.com.my Air Conditioning System System Sizing 1 Current Industry
More informationAssessment of Containment and Product Protection In a Class II Type B3 Biological Safety Cabinet Under As-used Laboratory Conditions
Assessment of Containment and Product Protection In a Class II Type B3 Biological Safety Cabinet Under As-used Laboratory Conditions Peter Harris and Dave Lupo B & V Testing, Inc. ABSA, 1999 Study Objective
More information