Flue Pipe Considerations

Size: px
Start display at page:

Download "Flue Pipe Considerations"

Transcription

1 Flue Pipe Considerations Objective The application summary outlined here will communicate the necessary flue piping arrangement for EnergyLogic (EL) furnaces and boilers and give a fundamental understanding of the restrictions. Also, tools will be introduced that help alleviate draft concerns and make installations more flexible. Description For a waste-oil furnace, the air-to-fuel ratio is critical. If the combustion air flow is lower than required to fully combust the oil, the used oil will not only pool in the bottom of the chamber causing post-combustion smoking, but will mix with fly ash and form coke. Coking can present a quick down-hill slide for the combustion as it negatively impacts atomization. As such, it is necessary that the combustion air flow be held constant at a flow rate above a minimum threshold (above 25% excess air for EL furnaces and boilers). The combustion air flow rate is dictated by two factors. On the burner end, the rotation of the burner squirrel cage and the air shutter inlet setting induce a pressurization of air at the burner head. On the exhaust end of the furnace, the exhaust gases rising out of the heat exchanger create suction through the furnace. The combination of induced draft at the burner and natural draft from the exhaust gases yield the overall furnace draft. This total draft sets the combustion air-flow rate. Natural draft is primarily a function of the installed flue pipe. If the flue pipe is installed incorrectly, the overall furnace draft will be compromised and the combustion air flue rate will be low. Low draft will result in, at least, shorter and more involved maintenance intervals and hard light-offs. At most, low draft will result in smoking and coke build-up in less than 100 hours of run-time. Problem Avoidance To run properly, the EL furnace and boiler should maintain a minimum of 0.05 inch WC draft. A few key guidelines are presented in the Flue Pipe Installation Guide that will help insure a proper draft is achieved: 1 of 2

2 Flue Pipe Considerations Straight Vertical Stack (Figure 1) 1) Install flue pipe of appropriate diameter for the EL boiler or furnace that is being used. For an EL-140H, EL-200H, EL-200B or EL-340H, the appropriate diameter is 8 inches. For an EL-500B, the diameter is 10 inches. 2) Flue stack recommendations should run a minimum of six feet and should extend four feet above the roof and any point within 20 feet of the flue. Note: For additional requirements, refer to NFPA guidelines and your local codes. 3) The Flue Pipe Installation Guide provides other specifics for an appropriate vertical stack installation. Stack Offsets without Inducers (Figure 3) At times, it is necessary to jog the flue stack slightly to hit an existing roof penetration or to place the furnace in a more desirable location. The suggestions below will aid in those circumstances: 1) Offsets should be no greater than 45 o from vertical. 2) The overall vertical flue length should be twice the length of the horizontal run. 3) The total horizontal length should not exceed 10 feet. 4) If the barometric damper is set at an angle, the damper pins must be parallel to the floor. Special Applications In most installations, the above restrictions should be held. Since achieving 0.05 inch WC draft is the goal, the installer may find that he is able to achieve a sufficient natural draft without strictly following these guidelines, but without careful attention and a systematic approach, an installer will eventually find himself with a furnace that will not run per specification of draft. It is not uncommon for a customer to want the flue stack to exit out a sidewall and not to penetrate the roof. With very low ceilings, it is impossible to position the furnace eight feet above the floor and still run a 45 o bend through the sidewall. For these installations that necessitate a 90 o elbow, EL offers an in-line draft inducer for supplementing the natural draft. Figure 2 and 4 outline two options to induce draft. In Figure 2, the draft inducer is intended to supplement the natural draft. Upon exiting the building, the stack must still terminate above the roof-line. While a roof penetration is shown, the stack can exit a sidewall. EL offers a draft inducer kit (PN ) for installations like those shown in Figure 2. Figure 4 illustrates a direct vented application using a QuickDraft Q8 draft inducer. It generates considerably more draft, but is significantly more expensive than the EL version. 2 of 2

3 For questions, visit or contact EnergyLogic Technical Services at Flue Pipe Installation Guide Vertical

4 For questions, visit or contact EnergyLogic Technical Services at Flue Pipe Installation Guide 45 Angle to Vertical

5 For questions, visit or contact EnergyLogic Technical Services at Flue Pipe Installation Guide Horizontal to Vertical

6 3' Draft Inducer Flue Pipe Installation Guide Horizontal Flue For questions, visit or contact EnergyLogic Technical Services at

APPENDIX "B" November 5, 2002 Page 1 of 6 BOILERSMITH LTD. STACKS AND BREECHING

APPENDIX B November 5, 2002 Page 1 of 6 BOILERSMITH LTD. STACKS AND BREECHING APPENDIX "B" November 5, 2002 Page 1 of 6 BOILERSMITH LTD. STACKS AND BREECHING NOTE The Stack and Breeching shall be installed in conformance with national, regional and local codes and standards and/or

More information

STACK AND BREECHING GUIDELINE

STACK AND BREECHING GUIDELINE TECHNICAL BULLETIN 1004 DECEMBER 1, 2007 STACK AND BREECHING GUIDELINE Common stacks and breechings can be designed as follows: 1. Determine volume of flue gases from Chart 1. Chart shows flue gas CFM

More information

RECOMMENDED STANDARDS for the INSTALLATION of WOODBURNING STOVES

RECOMMENDED STANDARDS for the INSTALLATION of WOODBURNING STOVES RECOMMENDED STANDARDS for the INSTALLATION of WOODBURNING STOVES Prepared By Office of State Fire Marshal Maine Office of Energy Resources 52 State House Station 55 Capital Street Augusta, ME 04333 Augusta,

More information

female pipe. A Wall Support must be installed just above the tee and at least every 8 feet thereafter. If the pipe is to be run through a roof overhang then a Flashing, Storm Collar and Vertical Rain Cap

More information

County of Yolo Development Services Building Inspection Division

County of Yolo Development Services Building Inspection Division County of Yolo Development Services Building Inspection Division 292 W. Beamer Street Woodland, CA. 95695 www.yolocounty.org (530) 666-8775 Mechanical Plan Review Comments Plan Review No. Owners Name Job

More information

INSTALLATION INSTRUCTIONS OPERATION AND MAINTENANCE MANUAL Models event SD, event, Event Plus, and event Plus2 (Condensing Boiler Systems)

INSTALLATION INSTRUCTIONS OPERATION AND MAINTENANCE MANUAL Models event SD, event, Event Plus, and event Plus2 (Condensing Boiler Systems) C US INSTALLATION INSTRUCTIONS OPERATION AND MAINTENANCE MANUAL Models event SD, event, Event Plus, and event Plus2 (Condensing Boiler Systems) A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE TO MAINTAIN

More information

Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard

Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard Introduction SRU s (Sulfur Recovery Units) are critical pieces of equipment in refineries and gas plants. SRUs remove sulfur compounds from certain

More information

EXCELPrime 18 Clearance Stove Pipe INSTALLATION AND MAINTENANCE INSTRUCTIONS

EXCELPrime 18 Clearance Stove Pipe INSTALLATION AND MAINTENANCE INSTRUCTIONS EXCELPrime 18 Clearance Stove Pipe INSTALLATION AND MAINTENANCE INSTRUCTIONS A MAJOR CAUSE OF CHIMNEY RELATED FIRES IS FAILURE TO MAINTAIN REQUIRED CLEARANCES (AIR SPACE) TO COMBUSTIBLE MATERIALS. IT IS

More information

Optimization of Combustion Efficiency: Kilns and Dryers

Optimization of Combustion Efficiency: Kilns and Dryers Optimization of Combustion Efficiency: Kilns and Dryers 1 2 Firing is the most cost intensive part in any ceramic industry, whether it may be using oil or natural gas. Slightest deviation from the scientific

More information

BuildingName The Description of the Project P DOCUMENTS

BuildingName The Description of the Project P DOCUMENTS ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION

More information

SAFETY PRECAUTIONS. Do not operate your stove if you smell smoke coming from it. Turn it off, monitor it, and call your dealer.

SAFETY PRECAUTIONS. Do not operate your stove if you smell smoke coming from it. Turn it off, monitor it, and call your dealer. SAFETY PRECAUTIONS Do not operate your stove if you smell smoke coming from it. Turn it off, monitor it, and call your dealer. Never use gasoline, gasoline-type lantern fuel, kerosene, charcoal lighter

More information

ATTENTION INSTALLING PERSONNEL

ATTENTION INSTALLING PERSONNEL DCVK-20 & DCVK-30 CONCENTRIC VENT TERMINATION KIT INSTALLATION INSTRUCTIONS Goodman Manufacturing Company, L.P. 2003-2007 5151 San Felipe, Suite 500, Houston, TX 77056 www.goodmanmfg.com -or- www.amana-hac.com

More information

Chimney Lining Systems

Chimney Lining Systems R Chimney Lining Systems Gas or Propane Fired Appliances Table of Contents 1. General Instructions and Warnings U.L. and Manufacturers Specifi cations...2 2. Types of Liner Systems...3 3. FLEXJET Installation

More information

Gas Fireplaces. P33 Zero Clearance Direct Vent Gas Fireplace. *** Important: Framing height requires consideration of the hearth

Gas Fireplaces. P33 Zero Clearance Direct Vent Gas Fireplace. *** Important: Framing height requires consideration of the hearth P33 Zero Clearance Direct Vent Gas Fireplace P33 WITH THE FLUSH OR BAY FRONT Model P33-NG4 P33-LP4 Fuel Type Natural Gas Propane Minimum Supply Pressure 5 W.C. (1.25 kpa) 12 W.C. (3.00 kpa) Manifold Pressure

More information

Technical and Dimensional Data. Saf-T Vent SC

Technical and Dimensional Data. Saf-T Vent SC Technical and Dimensional Data Saf-T Vent SC 3"/5" & 4"/7" Concentric Reduced Clearance Double Wall for Special Gas Vent and/or Sealed Combustion Systems Copyright 2003 Saf-T Vent is a registered trademark

More information

40CDi conventional. RD 537i. Installation Instructions for Flue Duct Kit AZB 873/1 Vertical Flue Terminal Assembly Ø 60/100 mm Ø135

40CDi conventional. RD 537i. Installation Instructions for Flue Duct Kit AZB 873/1 Vertical Flue Terminal Assembly Ø 60/100 mm Ø135 Installation Instructions for Flue Duct Kit AZB 873/1 Vertical Flue Terminal Assembly Ø 60/100 mm 7 719 002 430 Ø100 Ø62 1140 116 3x Ø135 2x Ø100 4x 6 720 611 739-00.1O for Gas Condensing Boilers: R 29

More information

Lecture (6) on. Schematic of a Thermal Power Plant. By Dr. Emad M. Saad. Mechanical Engineering Dept. Faculty of Engineering.

Lecture (6) on. Schematic of a Thermal Power Plant. By Dr. Emad M. Saad. Mechanical Engineering Dept. Faculty of Engineering. 1 2 Lecture (6) on Schematic of a Thermal Power Plant By Dr. Emad M. Saad Mechanical Engineering Dept. Faculty of Engineering Fayoum University Faculty of Engineering Mechanical Engineering Dept. 2015-2016

More information

Contemporary Collection

Contemporary Collection HZ5E Gas Fireplace Model HZE-NG HZ5E-LP Fuel Type Natural Gas Propane Gas Minimum Supply Pressure 5 W.C.(1.5 kpa) 1 W.C. (.9 kpa) Manifold Pressure - High 3.5 W.C. (.7 kpa) 1 W.C. (.9 kpa) Manifold Pressure

More information

Gas Combustion Figure 31-13 (A) Primary air is induced into the air shutter by the velocity of the gas stream from the orifice. (B) Ignition of the gas is on top of the burner. (C) Incomplete combustion

More information

P36 - P36D Zero Clearance Direct Vent Gas Fireplace. 12 W.C. (3.00 kpa) 11 W.C. (2.74 kpa) 2.9 W.C. (0.72 kpa) 15,000 BTU/h (3.

P36 - P36D Zero Clearance Direct Vent Gas Fireplace. 12 W.C. (3.00 kpa) 11 W.C. (2.74 kpa) 2.9 W.C. (0.72 kpa) 15,000 BTU/h (3. P36 - P36D Zero Clearance Direct Vent Gas Fireplace Model P36-NG4 P36-LP4 P36D-NG1 P36D-LP1 Fuel Type Natural Gas Propane Natural Gas Propane Minimum Supply Pressure 5 W.C. (1.25 kpa) 12 W.C. (3. kpa)

More information

Following contains common verbiage found in major model building codes and has been edited for the purpose of inclusion on this CD.

Following contains common verbiage found in major model building codes and has been edited for the purpose of inclusion on this CD. Following contains common verbiage found in major model building codes and has been edited for the purpose of inclusion on this CD. Included are selected sections of codes taken directly from: 1997 Uniform

More information

ADC. The Greenbook of Flex. Flexible Duct Performance & Installation Standards (5 th Edition) Characteristics of flexible duct

ADC. The Greenbook of Flex. Flexible Duct Performance & Installation Standards (5 th Edition) Characteristics of flexible duct ADC Flexible Duct Performance & Installation Standards (5 th Edition) The Greenbook of Flex Provides information about Characteristics of flexible duct Testing, Listing, Reporting, and Certifying Installation

More information

P36 / P36E Gas Fireplace. 11 W.C. (2.74 kpa) 10 W.C. (2.49 kpa) 6.4 W.C. (1.59 kpa) 22,000 BTU/h (6.44 kw) 28,500 BTU/h (8.35 kw)

P36 / P36E Gas Fireplace. 11 W.C. (2.74 kpa) 10 W.C. (2.49 kpa) 6.4 W.C. (1.59 kpa) 22,000 BTU/h (6.44 kw) 28,500 BTU/h (8.35 kw) P36 / P36E Gas Fireplace Model P36-NG10 P36-LP10 P36E-NG10 P36E-LP10 Fuel Type Natural Gas Propane Natural Gas Propane Minimum Supply Pressure 5 W.C. (1.25 kpa) 12 W.C. (3.00 kpa) 5 W.C. (1.25 kpa) 11

More information

Incinerator Systems NFPA 82 Inspection Form

Incinerator Systems NFPA 82 Inspection Form Incinerator Systems NFPA 82 Inspection Form PART 1 INCINERATORS DESIGN AND AUXILIARY FUEL ELECTRICAL SUPPLY AIR FOR COMBUSTION AND VENTILATION SPARK ARRESTERS 1. Are gas-burning installations designed

More information

Regency Horizon HZ30E Gas Fireplace

Regency Horizon HZ30E Gas Fireplace Specifications: Framing Dimensions: Model HZ3E-NG HZ3E-LP Fuel Type Natural Gas Propane Gas Minimum Supply Pressure Manifold Pressure - High Approved Venting Systems Flex Vent Systems: Rigid Pipe Vent

More information

Gas Fireplaces. P33-10/P33E-10 Gas Fireplace P33 DIMENSIONS WITH VIGNETTE FACEPLATE CLEARANCES WITH VIGNETTE FACEPLATE

Gas Fireplaces. P33-10/P33E-10 Gas Fireplace P33 DIMENSIONS WITH VIGNETTE FACEPLATE CLEARANCES WITH VIGNETTE FACEPLATE Model P33-NG10 P33-LP10 P33E-NG10 P33E-LP10 Fuel Type Natural Gas Propane Natural Gas Propane Minimum Supply Pressure 5 W.C. (1.25 kpa) 11 W.C. (2.74 kpa) 5 W.C. (1.25 kpa) 11 W.C. (2.74 kpa) Manifold

More information

Chimney and Fireplace Inspection Report

Chimney and Fireplace Inspection Report Chimney and Fireplace Inspection Report 91406 Inspection prepared for: Mr. and Mrs. Client Inspector: Greg Butler 27943 Seco Canyon Road, 560, Santa Clarita, CA 91350 NOTICE TO THIRD PARTIES: This report

More information

Electric Furnace Off-Gas Cleaning Systems Installation at PT Inco ABSTRACT

Electric Furnace Off-Gas Cleaning Systems Installation at PT Inco ABSTRACT Electric Furnace Off-Gas Cleaning Systems Installation at PT Inco Paykan Safe and Matt Russell WorleyParsons Gas Cleaning, Irving, Texas USA ABSTRACT PT Inco is a ferronickel smelter in Soroako, Sulawesi,

More information

This presentation covers process steam energy reduction projects supported by the Ameren Illinois ActOnEnergy program.

This presentation covers process steam energy reduction projects supported by the Ameren Illinois ActOnEnergy program. This presentation covers process steam energy reduction projects supported by the Ameren Illinois ActOnEnergy program. 1 2 Before we get started, here are four questions to find out what you already know

More information

P36-10 / P36E-10 Gas Fireplace. 11 W.C. (2.74 kpa) 10 W.C. (2.49 kpa) 6.4 W.C. (1.59 kpa) 22,000 BTU/h (6.44 kw) 28,500 BTU/h (8.

P36-10 / P36E-10 Gas Fireplace. 11 W.C. (2.74 kpa) 10 W.C. (2.49 kpa) 6.4 W.C. (1.59 kpa) 22,000 BTU/h (6.44 kw) 28,500 BTU/h (8. Model P36-NG10 P36-LP10 P36E-NG10 P36E-LP10 Fuel Type Natural Gas Propane Natural Gas Propane Gas Fireplaces P36-10 / P36E-10 Gas Fireplace Minimum Supply Pressure 5 W.C. (1.25 kpa) 12 W.C. (3.00 kpa)

More information

INFORMATIONAL HANDOUT FOR FINISHING A BASEMENT

INFORMATIONAL HANDOUT FOR FINISHING A BASEMENT 7100 147 th Street West Telephone (952) 953-2588 Apple Valley, MN 55124-9016 Fax (952) 953-2515 www.cityofapplevalley.org INFORMATIONAL HANDOUT FOR FINISHING A BASEMENT 1. Submit plan showing the proposed

More information

CHIMNEYS AND FIREPLACES

CHIMNEYS AND FIREPLACES CHAPTER 10 CHIMNEYS AND FIREPLACES SECTION R1001 MASONRY FIREPLACES R1001.1 General. Masonry fireplaces shall be constructed in accordance with this section and the applicable provisions of Chapters 3

More information

Spec-Tech-Sales September 15, 2014

Spec-Tech-Sales September 15, 2014 Page 1 of 6 Spec-Tech-Sales September 15, 2014 Integrated Boiler Room Solutions Commercial Technical Sales and Service For the Rocky Mountain Region 14652 West Vassar Drive Lakewood, CO 80228 Colorado

More information

SI T T FST

SI T T FST SI 440-600-700-700T-780-780T-900-1100 Freestanding TAPER TOP Open Fire - Wood Burner Installation Instructions Note: FLUE SYSTEMS Casing. Flue System may require to be Doubled Lined to Comply. Ref ASNZS:2918:2001

More information

Code Change No: FS43-06/07

Code Change No: FS43-06/07 CODE CHANGES RESOURCE COLLECTION INTERNATIONAL MECHANICAL CODE PART III IBC MEANS OF EGRESS Approved as Submitted Committee Reason: The revised language in Sections 1021.3 and 1022.2. would provide consistency

More information

Regulations of Connecticut State Agencies

Regulations of Connecticut State Agencies This document was prepared by the Connecticut State Library and is provided for the convenience of the reader. This is not the official version of the regulations. The official regulations are published

More information

SI T T FSS/FSTT Open Fire

SI T T FSS/FSTT Open Fire SI 440-600-700-700T-780-780T-900-1100 FSS/FSTT Open Fire Freestanding Solid Fuel Burner - Indoor Open Wood Fire Available in Square Top or Taper Top Options Installation Instructions Note: Flue System

More information

SPECIFIC APPLICATION ATTIC SPRINKLERS

SPECIFIC APPLICATION ATTIC SPRINKLERS 4077 Airpark Dr. Standish, MI 48658 989-846-4583 www.globesprinkler.com Technical Support 989-414-2600 techservice@globesprinkler.com SPECIFIC APPLICATION ATTIC SPRINKLERS GENERAL DESCRIPTION The Globe

More information

Rinnai Infinity XR26/HD200 Internal Flueing

Rinnai Infinity XR26/HD200 Internal Flueing Flueing Options and Rinnai Flue Kits Available Rinnai have developed two flueing kits to make installation of Rinnai Infinity XR26i/XR26ia and HD200i Internal units as easy as possible. Use the kit options

More information

DVL. DuraBlack. Double-wall interior close clearance stovepipe for connecting woodstoves to chimney. ULC S641.

DVL. DuraBlack. Double-wall interior close clearance stovepipe for connecting woodstoves to chimney. ULC S641. DVL Double-wall interior close clearance stovepipe for connecting woodstoves to chimney. ULC S641. Duralack Single-wall interior stovepipe for connecting woodstoves to chimney. Specifications DVL pplications

More information

APPLICATION FOR FINISHED BASEMENT PERMIT

APPLICATION FOR FINISHED BASEMENT PERMIT APPLICATION FOR FINISHED BASEMENT PERMIT REAL ESTATE TAX I.D. #: - - _ - _ 7607 W College Drive Ph: (708) 361-1804 Fax: (708) 923-7112 building@palosheights.org APPLICANTS: COMPLETE ALL ITEMS AND SUBMIT

More information

SOUTHERN NEVADA AMENDMENTS TO THE 2018 UNIFORM MECHANICAL CODE

SOUTHERN NEVADA AMENDMENTS TO THE 2018 UNIFORM MECHANICAL CODE SOUTHERN NEVADA AMENDMENTS TO THE 2018 UNIFORM MECHANICAL CODE PREFACE This document was developed by the Southern Nevada Building Officials Uniform Mechanical Code (UMC) Committee and presents recommended

More information

SPECIFIC APPLICATION ATTIC SPRINKLERS

SPECIFIC APPLICATION ATTIC SPRINKLERS 4077 Airpark Dr. Standish, MI 48658 989-846-4583 www.globesprinkler.com Technical Support 989-414-2600 techservice@globesprinkler.com SPECIFIC APPLICATION ATTIC SPRINKLERS GENERAL DESCRIPTION The Globe

More information

SPECIFIC APPLICATION ATTIC SPRINKLERS

SPECIFIC APPLICATION ATTIC SPRINKLERS 4077 Airpark Dr. Standish, MI 48658 989-846-4583 www.globesprinkler.com Technical Support 989-414-2600 techservice@globesprinkler.com SPECIFIC APPLICATION ATTIC SPRINKLERS GENERAL DESCRIPTION The Globe

More information

Please consult the manufacturer s installation manual for all details and requirements before making a final design layout decision.

Please consult the manufacturer s installation manual for all details and requirements before making a final design layout decision. Please consult the manufacturer s installation manual for all details and requirements before making a final design layout decision. 72" Direct Vent Gas Fireplace MODEL FRONT HEIGHT WIDTH FRONT BACK WIDTH

More information

FLUE KIT INSTALLATION MANUAL

FLUE KIT INSTALLATION MANUAL FLUE KIT INSTALLATION MANUAL 7 76 9 55 ROOM SEALED TELESCOPIC FLUE 7 76 9 086 PLUME MANAGEMENT SYSTEM GREENSTAR 60/00 HORIZONTAL FLUE FOR USE WITH WORCESTER GREENSTAR GAS-FIRED APPLIANCES: Greenstar FS

More information

Flue gas systems for oil and gas condensing boilers. Flue gas kit DN60 rigid in the duct. Accessories DN60 (additionally available to gas flue kit)

Flue gas systems for oil and gas condensing boilers. Flue gas kit DN60 rigid in the duct. Accessories DN60 (additionally available to gas flue kit) Flue gas kit DN60 rigid in the duct 100193 Flue gas kit No Outlet set plastic 1 x Set 100193 39.10 (Quantities in the image differ from the set) 1003253 1001938 Spacer set * ( pieces) Top inspection opening

More information

2015 IBC Inspection of Fire-Resistance Rated Floors, Ceilings and Roofs

2015 IBC Inspection of Fire-Resistance Rated Floors, Ceilings and Roofs Class Outline Inspection of Fire-Resistance-Rated Floors, Ceilings and Roofs Based on 2015 International Building Code, (IBC ) Introduction Determining fire resistance Test standards Definitions Alternate

More information

2012 IBC Inspection of Fire-resistance Rated Walls

2012 IBC Inspection of Fire-resistance Rated Walls Accreditation 2012 IBC Inspection of Fire-resistance Rated Walls Based on the 2012 International Building Code (IBC ) The International Code Council has been accredited as an Authorized Provider by the

More information

HEATING SOLUTIONS LTD. Cascade Flue Systems

HEATING SOLUTIONS LTD. Cascade Flue Systems HEATING SOLUTIONS LTD Cascade Flue Systems 01256 587 800 Cascade Flue Systems The two types of Vertical Cascade Flue Systems from Gemtex prevent multiple flue penetrations through roofs or walls by allowing

More information

Product catalogue. Socket cast iron pipe system

Product catalogue. Socket cast iron pipe system Product catalogue Socket cast iron pipe system GALLERY ADVANTAGES OF SOCKET PIPE SYSTEM Classic form: Fits well the architecture of renovated buildings. Wide range of products: Pipes, siphons, stormwater

More information

Gas Fireplaces. P36D-10 Gas Fireplace. Unit Dimensions With Vignette Faceplate. *** Important: Framing height requires consideration of the hearth

Gas Fireplaces. P36D-10 Gas Fireplace. Unit Dimensions With Vignette Faceplate. *** Important: Framing height requires consideration of the hearth 28-15/16 (735mm) Model P36D-NG10 P36D-LP10 Fuel Type Natural Gas Propane Gas Fireplaces Minimum Supply Pressure Manifold Pressure - High Manifold Pressure - Low 5 W.C. (1.25 kpa) 3.8 W.C. (0.95 kpa) 1.1

More information

CHIMNEYS AND FIREPLACES

CHIMNEYS AND FIREPLACES SECTION R1001 MASONRY FIREPLACES R1001.1 General. Masonry fireplaces shall be constructed in accordance with this section and the applicable provisions of Chapters 3 and 4. R1001.2 Footings and foundations.

More information

Installation Instructions

Installation Instructions Installation Instructions SAVE THESE INSTRUCTIONS Please read this entire manual before you install and use your room heater. Failure to follow instructions may result in property damage, bodily injury,

More information

Gas Fireplaces. B41XTE-10 Gas Fireplace. Framing Dimensions: Unit Dimensions: Non-Combustible 1012mm Requirements: V Opening for gas connection

Gas Fireplaces. B41XTE-10 Gas Fireplace. Framing Dimensions: Unit Dimensions: Non-Combustible 1012mm Requirements: V Opening for gas connection 1XTE-1 Gas Fireplace Model 1XTE-NG1 1XTE-LP1 Fuel Type Natural Gas Propane Gas Minimum Supply Pressure Manifold Pressure - High Manifold Pressure - Low 5 W.C. (1.5 kpa) 3.5 W.C. (.7 kpa) 1. W.C. (. kpa)

More information

RADON WELLISUMP BASIN FOR NEW HOME CONSTRUCTION

RADON WELLISUMP BASIN FOR NEW HOME CONSTRUCTION RADON WELLISUMP BASIN FOR NEW HOME CONSTRUCTION Paul V. Jennemann Maryland Radon Laboratory, Inc. Ellicott City, MD ABSTRACT This paper will describe a radon-well/sump-basin (patent applied for) for installation

More information

Z-Vent Model SVE Series III

Z-Vent Model SVE Series III Special Stainless Steel Venting System for Gas Burning Appliances Category I, II, III, & IV Tested and Listed By Underwriters Laboratories Inc. UL 1738 & BH636 Note the following before installation of

More information

Installation Instructions

Installation Instructions Installation Instructions Flue Gas System Basic Kit HT-K - Horizontal Flue Gas System For GB125 Oil Condensing Boiler For trained and certified Installers Please read carefully prior to installation. 6

More information

2012 IBC Inspection of Fire-Resistance Rated Floors, Ceilings and Roofs

2012 IBC Inspection of Fire-Resistance Rated Floors, Ceilings and Roofs Class Outline Inspection of Fire-resistance-Rated Floors, Ceilings and Roofs Based on 2012 International Building Code (IBC) Introduction Determining fire resistance Test standards Definitions Alternate

More information

B41XTCE Gas Fireplace

B41XTCE Gas Fireplace B1XTCE Gas Fireplace Model B1XTCE-NG1 B1XTCE-LP1 Fuel Type Natural Gas Propane Minimum Supply Pressure 5 W.C./C.E. (1.5 kpa) 11 W.C./C.E. (.7 kpa) Manifold Pressure - High 3.5 W.C./C.E. (.7 kpa) 1 W.C./C.E.

More information

Public Input No. 4-NFPA [ Global Input ]

Public Input No. 4-NFPA [ Global Input ] of 18 7/28/2014 12:10 PM Public Input No. 4-NFPA 32-2013 [ Global Input ] Note: This Proposal originates from Tentative Interim Amendment 32-11-1 (TIA 999) issued by the Standards Council on October 20,

More information

Siphonic Roof Drainage & Design Process. Presentation by

Siphonic Roof Drainage & Design Process. Presentation by Siphonic Roof Drainage & Design Process Presentation by What is Siphonic Roof Drainage? Siphonic Roof Drainage is an innovative solution which utilises the power of a natural siphon to create a high-performance

More information

Level III Chapter 1 Worksheet

Level III Chapter 1 Worksheet Chapter 1 Worksheet 1. For applicability requirements of the Plumbing Code, refer to: a. Building Code b. Administration and Enforcement Code c. Plumbing Code d. Residential Code 2. The provisions of the

More information

KINETICS Pipe & Duct Seismic Application Manual

KINETICS Pipe & Duct Seismic Application Manual S1.1 Introduction: As with any task in the design and construction of buildings, there are certain terms, definitions, and standards of practice that must be understood and employed in order to maintain

More information

SOUTHERN NEVADA AMENDMENTS TO THE 2018 UNIFORM MECHANICAL CODE

SOUTHERN NEVADA AMENDMENTS TO THE 2018 UNIFORM MECHANICAL CODE SOUTHERN NEVADA AMENDMENTS TO THE 2018 UNIFORM MECHANICAL CODE PREFACE This document was developed by the Southern Nevada Building Officials Uniform Mechanical Code (UMC) Committee and presents recommended

More information

CHAPTER 1 INTRODUCTION

CHAPTER 1 INTRODUCTION 1 CHAPTER 1 INTRODUCTION 1.1 GENERAL Rapid economic growth and industrialisation has led to significant reduction in ambient air quality. There is an ever increasing demand for power and to meet this demand

More information

Building Codes and Ordinances ARC 227

Building Codes and Ordinances ARC 227 Building Codes and Ordinances ARC 227 Week 6 Fire Resistive Construction 03.02.10 Instructor: Rick Staub, AIA Email: staub@pointonearchitects.com Phone: 860-434-7707 Fire Resistive Construction Passive

More information

GCI60 Hampton Cast Iron Pellet Insert

GCI60 Hampton Cast Iron Pellet Insert CI60 Hampton Cast Iron Pellet Insert 26 7 8 24 ¾ 16 3 8 43 3 16 33 9 16 41 7 8 11 ¾ 22 15 16 12 ¾ FI60 Wood Pellet Insert INSTALLED AS A FIREPLACE INSERT STOVE MODEL (FPI) / A INSTALLE COMME UN MODELE

More information

Honeywell Thermal Solutions. Engineering Guide

Honeywell Thermal Solutions. Engineering Guide Engineering Guide Honeywell Thermal Solutions Engineering Guide Copyright 2017 by Honeywell Thermal Solutions All Rights Reserved CONTENTS 1. Orifices & Flows Coefficients of Discharge for Various Types

More information

2012 IBC Inspection of Fire-Resistance Rated Floors, Ceilings and Roofs

2012 IBC Inspection of Fire-Resistance Rated Floors, Ceilings and Roofs Accreditation 2012 IBC Inspection of Fire-resistance-Rated Floors, Ceilings and Roofs Based on 2012 International Building Code The International Code Council has been accredited as an Authorized Provider

More information

PROJECT: PREPARED BY: PREPARED FOR: Boiler Breeching and Stack Generator Engine Exhaust Fume Venting Fireplace Venting

PROJECT: PREPARED BY: PREPARED FOR: Boiler Breeching and Stack Generator Engine Exhaust Fume Venting Fireplace Venting M&G DURAVENT DURASTACK PRO POSITIVE PRESSURE SYSTEMS MODELS DAS1 1 INCH AIR INSULATED DIS1 1 INCH CERAMIC FIBER INSULATED DIS2 2 INCH CERAMIC FIBER INSULATED DIS4 4 INCH CERAMIC FIBER INSULATED DCL SINGLE

More information

FIREBLOCK/DRAFTSTOPPING INFORMATION CODE INFORMATION FOR 1 & 2-FAMILY DWELLINGS FOR WOOD-FRAMED CONSTRUCTION FIREBLOCK

FIREBLOCK/DRAFTSTOPPING INFORMATION CODE INFORMATION FOR 1 & 2-FAMILY DWELLINGS FOR WOOD-FRAMED CONSTRUCTION FIREBLOCK Building Safety Department 400-2 nd Street South St. Cloud, MN 56301 (320) 255-7239 FIREBLOCK/DRAFTSTOPPING INFORMATION CODE INFORMATION FOR 1 & 2-FAMILY DWELLINGS FOR WOOD-FRAMED CONSTRUCTION FIREBLOCK

More information

AAETI. Anil Agarwal Environment Training Institute. Understanding ZigZagKilns

AAETI. Anil Agarwal Environment Training Institute. Understanding ZigZagKilns Anil Agarwal Environment Training Institute Understanding ZigZagKilns Schematic illustration of operations and firing zones of an FCBTK Problems With FCBTK Technology Problems With FCBTK Technology Air

More information

READ ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter X X X Adopt Entire Chapter as amended (amended sections listed below) X X X X X X

READ ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter X X X Adopt Entire Chapter as amended (amended sections listed below) X X X X X X CALIFORNIA PLUMBING CODE MATRIX ADOPTION TABLE CHAPTER 9 - VENTS (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state agency authority and building application.)

More information

Watch the gasification action video at

Watch the gasification action video at HIGHLY EFFICIENT SCOTCH MARINE TUBE HEAT EXCHANGER EPA QUALIFIED The Economizer IDM 100 is specifically designed for installation inside outdoor buildings such as shops, barns, sheds or garages. 250 All

More information

WASTE TYRE RECYCLING PLANT

WASTE TYRE RECYCLING PLANT WASTE TYRE RECYCLING PLANT The whole pyrolysis system is mainly composed by 14 parts, which are reactor, insulation layer, furnace, transmission device, oil-water separator, depositing tank, cooling pool,

More information

A Quick Check Method For The Design Of Pneumatic Conveying Systems

A Quick Check Method For The Design Of Pneumatic Conveying Systems A Quick Check Method For The Design Of Pneumatic Conveying Systems by Dr David Mills, Pneumatic Conveying Consultant, Old Wives Lees, England INTRODUCTION The design of pneumatic conveying systems is usually

More information

GREENSTAR OILFIT FLUE RS

GREENSTAR OILFIT FLUE RS FLUE KIT INSTALLATION INSTRUCTIONS 7 76 90 06 ROOM SEALED 80/mm STANDARD TELESCOPIC FLUE 7 76 90 06 ROOM SEALED 80/mm SHORT TELESCOPIC FLUE 7 76 90 09 80mm PLUME MANAGEMENT SYSTEM 7 76 90 0 ROOM SEALED

More information

FIRE-RESISTANCE-RATED CONSTRUCTION

FIRE-RESISTANCE-RATED CONSTRUCTION CHAPTER 7 FIRE-RESISTANCE-RATED CONSTRUCTION SECTION BC 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials and assemblies used for structural fire resistance and fire-resistance-rated

More information

Rediflow Concrete Gas Flue System

Rediflow Concrete Gas Flue System Rediflow Concrete Gas Flue System Rediflow Concrete Gas Flue System Rediflow the complete gas flue block system Red Bank s range of Rediflow pre-cast concrete gas flue block system manufactured to BS EN

More information

B36XTCE Gas Fireplace

B36XTCE Gas Fireplace Model B3XTCE-NG1 B3XTCE-LP1 Fuel Type Natural Gas Propane Minimum Supply Pressure 5 W.C./C.E. (1.5 kpa) 11 W.C./C.E. (.7 kpa) Manifold Pressure - High 3.5 W.C./C.E. (.7 kpa) 1 W.C./C.E. (.9 kpa) Manifold

More information

Radon Vent Pipe System. Labeling Performance Indicators

Radon Vent Pipe System. Labeling Performance Indicators Section 6 Radon Vent Pipe Labeling Performance Indicators Radon Vent Pipe System Connected after sub-grade system installed Pipe cannot be trapped Provide space in chases Support at each floor level Discharge

More information

Flue Accessories & Fitting Guide Ø 60/100 Flue Systems Ø 80/125 Flue Systems Ø 80/80 Twin Flue Systems Plume Displacement Kit (Ø 60/100 Flue Systems)

Flue Accessories & Fitting Guide Ø 60/100 Flue Systems Ø 80/125 Flue Systems Ø 80/80 Twin Flue Systems Plume Displacement Kit (Ø 60/100 Flue Systems) GUIDANCE NOTES Flue Accessories & Fitting Guide Ø 6/1 Flue Systems Ø 8/125 Flue Systems Ø 8/8 Twin Flue Systems Plume Displacement Kit (Ø 6/1 Flue Systems) READ THESE INSTRUCTIONS IN CONJUNCTION WITH THE

More information

Installation Instructions

Installation Instructions Installation Instructions Flue Gas System Basic Kit GA-K - Chimney Flue Gas System for GB125 Oil Condensing Boiler For trained and certified installers Please read carefully prior to installation. 6 720

More information

Sentron Low Amp Busway

Sentron Low Amp Busway Sentron Low Amp Busway Sentron Low Amp Busway is a member of the Siemens Sentron Busway family. Sentron Low Amp Busway specifically addresses the needs of low amp power distribution applications, with

More information

LOGIC FLUE & ACCESSORIES GUIDE.

LOGIC FLUE & ACCESSORIES GUIDE. & ACCESSORIES GUIDE. COMBI C COMBI ESP1 + COMBI C SYSTEM S + SYSTEM S HEAT H + HEAT H CODE COMBI ESP1 WWW.IDEALBOILERS.COM This manual is for guidance only and must be read in conjunction with the Installation

More information

DuraFlex. Flexible stainless steel relining for masonry chimney. UL 1777 and ULC S635.

DuraFlex. Flexible stainless steel relining for masonry chimney. UL 1777 and ULC S635. DuraFlex Flexible stainless steel relining for masonry chimney. UL 1777 and ULC S635. Specifications DuraFlex SW Applications DuraFlex SW smooth wall flexible relining for masonry chimney. Use with gas,

More information

2009 International Building Code Errata (Portions of text and tables not shown are unaffected by the errata)

2009 International Building Code Errata (Portions of text and tables not shown are unaffected by the errata) TWELFTH PRINTING (Updated December 6, 2016) Note for 706.5.1: This is an erratum in the 8 th, 9 th, 10 th and 11 th printing only. The reference is correct in other editions. 706.5.1 Exterior walls. Where

More information

Quality Inspection 8618 London Heights San Antonio, TX Phone: (210)

Quality Inspection 8618 London Heights San Antonio, TX Phone: (210) Quality Inspection 8618 London Heights San Antonio, TX 78254 Phone: (210) 240-0476 PRE DRYWALL INSPECTION REPORT Prepared For: DELETED (Name of Client) Concerning: DELETED, San Antonio, TX 78258 (Address

More information

SECURE STACK PRO POSITIVE PRESSURE SYSTEMS MODELS

SECURE STACK PRO POSITIVE PRESSURE SYSTEMS MODELS SECURITY CHIMNEYS INTERNATIONAL SECURE STACK PRO POSITIVE PRESSURE SYSTEMS MODELS Boiler Breeching and Stack Generator Engine Exhaust Fume Venting Fireplace Venting CAX1 1 INCH AIR INSULATED CIX1 1 INCH

More information

TC54. for architects & designers. Dimensions Clearances Venting

TC54. for architects & designers. Dimensions Clearances Venting for architects & designers TC54 Series D Dimensions Clearances enting IMPORTANT This booklet is intended as a basic specification guide for architects, designers and builders. Please refer to the Instruction

More information

Forward-looking and energy efficient Biomass heating

Forward-looking and energy efficient Biomass heating Forward-looking and energy efficient Biomass heating Large buildings Hotel complexes Housing estate projects 1 Competence is our success... 40 YEARS EXPERIENCE IN HEATING THE WORLD! With over 40 years

More information

InoxSabiana 25 Flues. Stainless Steel Double Wall

InoxSabiana 25 Flues. Stainless Steel Double Wall Cert. n 0545/5 Flues Stainless Steel Double Wall Introduction and main constructional characteristics Double Wall, Stainless Steel Flues The is the result of innovative development based on over 0 years

More information

DIVISION: SPECIALTIES SECTION: MANUFACTURED FIREPLACES REPORT HOLDER: FIRE ROCK PRODUCTS LLC

DIVISION: SPECIALTIES SECTION: MANUFACTURED FIREPLACES REPORT HOLDER: FIRE ROCK PRODUCTS LLC 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2599 Reissued 04/2018 This report is subject to renewal 04/2020. DIVISION: 10 00

More information

STATUTORY AUTHORITY: NMSA 1978 Sections and [ NMAC - Rp, NMAC, ]

STATUTORY AUTHORITY: NMSA 1978 Sections and [ NMAC - Rp, NMAC, ] TITLE 14 CHAPTER 9 PART 2 HOUSING AND CONSTRUCTION MECHANICAL CODES 2006 NEW MEXICO MECHANICAL CODE 14.9.2.1 ISSUING AGENCY: Construction Industries Division (CID) of the Regulation and Licensing Department.

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Boiler and Engine Exhaust Chimney Systems Grease Duct Systems (CIX only) Double Wall Construction Positive Pressure Chimney Systems P/N 506065-03 REV. N 02/2015 MODELS CIX / CAX

More information

Outer Skin Kit & Flue: IB600, IB850, IB1100 Installation Manual

Outer Skin Kit & Flue: IB600, IB850, IB1100 Installation Manual Outer Skin Kit & Flue: IB600, IB850, IB1100 Installation Manual Please see IB series product installation guide for details of installing the gas fire into this preformed metal cavity. Important: The appliance

More information

Gas Fireplaces. B36XTE Gas Fireplace. Unit Dimensions with Vignette: Model B36XTE-NG10 B36XTE-LP10 M O S S. V Opening for gas connection

Gas Fireplaces. B36XTE Gas Fireplace. Unit Dimensions with Vignette: Model B36XTE-NG10 B36XTE-LP10 M O S S. V Opening for gas connection Model B36XTE-NG10 B36XTE-LP10 Fuel Type Natural Gas Propane Gas Fireplaces B36XTE Gas Fireplace Minimum upply Pressure Manifold Pressure - High Manifold Pressure - Low 5 W.C. (1.5 kpa) 3.5 W.C. (0.87 kpa)

More information

HIGH EFFICIENCY POSITIVE PRESSURE VENTING SYSTEMS FOR CONDENSING APPLIANCES, CATEGORIES II, III AND IV Single & Double Wall Construction

HIGH EFFICIENCY POSITIVE PRESSURE VENTING SYSTEMS FOR CONDENSING APPLIANCES, CATEGORIES II, III AND IV Single & Double Wall Construction HIGH EFFICIENCY POSITIVE PRESSURE VENTING SYSTEMS FOR CONDENSING APPLIANCES, CATEGORIES II, III AND IV Single & Double Wall Construction Models HEP HEPL HEPL2 28 KJ This symbol shows that CHEMINÉE LINING.E

More information

LOGIC FLUE & ACCESSORIES GUIDE.

LOGIC FLUE & ACCESSORIES GUIDE. & ACCESSORIES GUIDE. COMBI C COMBI ESP1 + COMBI C SYSTEM S + SYSTEM S HEAT H + HEAT H CODE COMBI ESP1 WWW.IDEALBOILERS.COM This manual is for guidance only and must be read in conjunction with the Installation

More information