ENERGY RECOVERY, CALCULATION METHODS

Size: px
Start display at page:

Download "ENERGY RECOVERY, CALCULATION METHODS"

Transcription

1 ENERGY RECOVERY ENERGY RECOVERY, CALCULATION METHODS 19/10/2016 DOCUMENT PETER SUNDELIN

2 Efficiency of a recovery system? Supply air temp. efficiency, for 0C out doors Supply air dry temp. efficiency (0 C) Supply air temp. efficiency according to EN308 Supply air dry temp. eff. equal air flows (Winter dim.) Supply air wet temp. eff. (Winter dim.) Supply air dry temp. eff. (Winter dim.) Supply air temp. efficiency, due to frost protection -27 C -22 C -17 C etz Exhaust air temp. efficiency Entalpy efficiency Humidity efficiency Sensible, latent efficiency Supply air efficiency, summer Annual temp. efficiency Annual energy efficiency Etc efficiencies are too much!! 2

3 What performance of a recovery system is important? Example of a print out: 1) 2) 3) 4) 5) 6) 7) 8) 9) 10) 11) 12) 13) 14) 15) 16) 17) 17 st different efficiencies of the recovery system (RAR in this case) 3

4 Temperature efficiency for dim. Winter, no freezing protection -13 C 100% (1 g/kg) To low exhaust air temp. -20 C (0,5 g/kg) 22 C,30% (5 g/kg) 1 m³/s 16 C 1 m³/s 5 20 C kw Ƞ = 85% Ƞ = t supply t out t extract t out Ƞ = 16 (-20) 22 (-20) Is this realistic?? 4 g/kg of water dissapears? Right calculation crusial for sizing the heating coil. From energy usage point of view, not important, Stockholm -16 C, 0 h per år (MeteoNorm) 4

5 Temperature efficiency for dim. Winter, with frost protection activated -6 C 22 C,30% (5 g/kg) 1 m³/s -20 C (0,5 g/kg) 8 C 1 m³/s Ƞ = t supply t out t extract t out C kw Ƞ = 8 (-20) 22 (-20) Ƞ = 67% not 85% To deliver desired air flow, continiously To deliver desired supply air temp, continiously Calulations/dimensioning for a real conditions, frost protection active if needed. All other statements/calculations are fictive 5

6 Temperature efficiency at lowest winter, frost protection activated 0 C 22 C,30% 1 m³/s +4 C 1 m³/s -20 C Ƞ = t supply t out t extract t out C kw Ƞ = 4 (-20) 22 (-20) Applies for both RAR and PHE systems Ƞ ~ 57% For all indirect recovery systems applies: If extract air is humid, condensation occurs in the recovery system and exhaust air can not be below < 0 C

7 The new high efficient HRS requires an advanced frost protection When we get frost in the heat recovery we get problems!

8 The new high efficient HRS requires an advanced frost protection (cold climates < -10 C) The wheel: no frost protection? The plate heat exchanger: Out door air reg. norm. ~ -7 C GT -7C or Cold corner GT The run around coil system: Liquid temp. 0.5 C GT +5C Traditional frost protection methods are not good enough anymore: Today most HRS are very efficient and the focus on energy savings are of high importance. 8

9 Advanced frost protection AFP 1) Dry conditions 22 C, 10% 2) Humid conditions 22 C, 40% The advanced frost protection activates, depending on the need. Extract air Temperature Humidity Exhaust air Temperature (several) Out door air Temperature 1) -7 C 2) 0 C, 100%

10 For what situation shall I optimize the recovery system? Stockholm Out door air <-10 C = 100 h/a (1,5%) Out door air C = 3400 h/a (50%) Out door air C = 6900 h/a

11 Energy costs? Energy = Power (kwh) x time (h) Winter Heating power: 17 kw (4 times) Tid: 5h 0 C out doors, normal cond. 5 kw 303 h (60 times) Energy/cost: 85 kwh = 17 /a 0 C -16 C Ƞ = 55% 1515 kwh = 303 /a 22 C,30% 1 m³/s +6 C C 1 m³/s kw 22 C,30% 1 m³/s 16 C 5 20 C 1 m³/s kw 0 C Ƞ = 73%

12 What is the optimum heat recovery system? 4,5,6,7,8 C 19 C 0 C Ƞ = t till t ute t från t ute 22 C,30% 18 C 17 C 16 C 15 C ƞ ~ 86 % ƞ ~ 82 % ƞ ~ 77 % ƞ ~ 73 % ƞ ~ 68 % 20 C 19 C 18 C 17 C 16 C /a *) /a +200 /a +100 /a The desired supply air temperature has a huge impact on the choice of the HRS 12 *) Additional cost for 1 m³/s, 8760 h/a, 0,2 /kwh

13 Standard, performance out puts from selection programme Temp. eff. EN308: 67,2% SFPv: 2,11 Annual energy efficiency: Office,Stockholm Ƞ = 89,1 % Customer: For comparance, Yes but is it enough?? Energy consumption? Running costs? Calculation of annual energy efficiency = 100 x Q energy recovery Q total heating energy 13

14 The energy calculation module in Acon / Fläkt Woods Climate data for the whole world (MeteoNorm) Possibility to modify climate data Several user levels, depending on inputs Air temperatures Air flows Energy costs for: Heating, cooling, electricity and reheater CO2 emissions Cost for installed power Energy cost for other equipment (damper/pumps etc.) Water consumption for humidifier LCC (Life cycle costs) Constant/variable pressure Energy calculation CAV Average air flow VAV Night Pressure loss in duct work Curve for supply air temp. Cooling to either temp. or humidity Exhaust air winter/summer, both temp and humidity. Supply air for run. night. Operating time, tender sum, rent etc. Comparison Comparison between FWG solutions Comparison between FWG and external solutions The most complete energy calculation module available on the HVAC market14

15 The energy calculation module in Acon / Fläkt Woods High lights: Climate data for the whole world (MeteoNorm) Possibility to modify climate data Several user levels, depending on inputs Air temperatures Curve for supply air temperature Cooling to either temp. or humidity Exhaust air winter/summer, both temp and humidity. Supply air for run. night. Air flows CAV Average air flow VAV Night Pressure loss in duct work Energy calculation Energy costs for: heating,cooling,electricity and reheater CO2 emissions Cost for installed power Energy cost for other equipment (damper/pumps etc.) Water consumption for humidifier LCC (Life cycle costs) Constant/variable pressure Operating time, tender sum, rent etz Comparison Comparison between FWG solutions Comparison between FWG and external solutions The most complete energy calculation module available on the HVAC market15

16 Running costs: Additional value for the customer Annual energy efficiency, ECONET, RAR According to Swedish Ventilation: 89,1% (EN308: 67,2%) Customer value: Heating energy: Heating costs: 37,5 MWh 3760 /a Fan energy : Electricity costs: 67,9 MWh /a Cooling energy: Cooling costs: 29,8 MWh 1480 /a Other equiment: Costs: 4,0 MWh 600 /a (El: 0,15 /kwh, Heating 0,1 /kwh, Cooling 0,05 /kwh) Total running costs: /a 16

17 Real or project based inputs has a huge impact on the result Energy/running cost calculation by using ACon Climate data, Stockholm, Meteonorm ECONET,RAR (EN308: 67,2%) Case 1: (SWE Vent) Case 2 Case 3 Supply air temperature 18 C 18 C/15 C Exhaust air temperature 22 C 22 C/24 C Add hum/extract air +1 g/kg +1 g/kg Running hours 5 d 06:00-18:00 day 14 h (100% flow) night 6 h (50% flow) 16 C 22 C/24 C +1 g/kg day 10 h (60% flow) Air flow Heating limit Energy costs VAV (60%) No restriction 0,15/0,1/0,05 CAV Out door air < +15C 0,15/0,1/0,05 CAV (2 flow) No restriction 0,2/0,15/0,065 (electr., heating, cooling) 17 /kwh

18 Indata / result case 2 18

19 Real or project based inputs has a huge impact on the result Energy/running cost calculation by using ACon Climate data, Stockholm, Meteonorm ECONET,RAR (EN308: 67,2%) Case 1 Case 2 Case 3 Supply air temperature 18 C 18 C/15 C Exhaust air temperature 22 C 22 C/24 C Add hum/exhaust air +1 g/kg +1 g/kg Running hours 5 d 06:00-18:00 day 14 h (100% flow) night 6 h (50% flow) 16 C 22 C/24 C +1 g/kg day 10 h (60% flow) Air flow Heating limit Energy costs VAV (60%) No restriction 0,15/0,1/0,05 /kwh CAV Out door air < +15C 0,15/0,1/0,05 CAV (2 flows) No restriction 0,2/0,15/0,065 (electr., heating, cooling) Total running costs: Case /a Annual energy efficiency: AHU cost (investment) 89,1% Case /a 90,4% Case /a 96,6%

20 The total costs for an AHU during it s life time (LCC) Energy costs 85% Investment costs 5 10% 20

21 Always ask Flakt Woods first SFPv and temperature efficiency, yes, but.,,,,,, The real truth You get with a LCC calculation

EQ ENERGY SAVING PRODUCTS

EQ ENERGY SAVING PRODUCTS FW ENERGY DAY EQ ENERGY SAVING PRODUCTS 19/10/2016 DOCUMENT X Energy efficient Ecodesign compliant LCC in focus Integrated functions Quick and reliable installation Flexible Hygiene Robust casing Fläkt

More information

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1 Air System Design Load Summary for Zona 6 DESIGN COOLING DESIGN HEATING COOLING DATA AT Feb 1600 HEATING DATA AT DES HTG COOLING OA DB / WB 34.5 C / 23.7 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible Latent

More information

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1 Air System Design Load Summary for Zona 9 DESIGN COOLING DESIGN HEATING COOLING DATA AT Jan 1400 HEATING DATA AT DES HTG COOLING OA DB / WB 34.5 C / 23.7 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible Latent

More information

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1 Air System Design Load Summary for Zona 3 Project Name: Av. Cabildo 3067, 4 piso 02/13/2011 DESIGN COOLING DESIGN HEATING COOLING DATA AT Feb 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 34.9 C / 23.8

More information

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1 Air System Design Load Summary for Zona 8 DESIGN COOLING DESIGN HEATING COOLING DATA AT Dec 1700 HEATING DATA AT DES HTG COOLING OA DB / WB 33.1 C / 23.5 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible Latent

More information

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1 Air System Design Load Summary for Zona 11 DESIGN COOLING DESIGN HEATING COOLING DATA AT Dec 1700 HEATING DATA AT DES HTG COOLING OA DB / WB 33.1 C / 23.5 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible

More information

HVAC SYSTEM CONFIGURATIONS, AN ENERGY ASPECT

HVAC SYSTEM CONFIGURATIONS, AN ENERGY ASPECT HVAC SYSTEM CONFIGURATIONS, AN ENERGY ASPECT Y Zhang 1,*, JA Wright 2 and VI Hanby 1 1 Institute of Energy and Sustainable Development, De Montfort University, Leicester, LE1 9BH, UK 2 Department of Civil

More information

2-Pipe fan coil terminal units were selected as the parallel system to handle the remaining sensible cooling load.

2-Pipe fan coil terminal units were selected as the parallel system to handle the remaining sensible cooling load. Redesign Introduction This report is an in depth analysis of the mechanical systems of the Outreach Innovation Building located in University Park, PA and the impact these changes had on other systems

More information

APPLICATIONS Air-to-Air Energy Recovery

APPLICATIONS Air-to-Air Energy Recovery APPLICATIONS Air-to-Air Energy Recovery Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application

More information

A building controls strategy based on fundamental engineering principles

A building controls strategy based on fundamental engineering principles How is a healthcare facility like a chemical plant? Lessons from chemical engineering for HVAC optimization Edward George & Associates Leslie R. Schulte, PhD Valerie Coulter Eddie McLaughlin A better way

More information

Operating Engineers Seminar Bob Ford Jeff Volovsek

Operating Engineers Seminar Bob Ford Jeff Volovsek Operating Engineers Seminar 2017 Bob Ford Jeff Volovsek Overview Annual energy consumption to demand Heat recovery updated requirements Process cooling best practices How does District Energy compare?

More information

NEW REQUIREMENTS FOR AIR HANDLING UNITS IN COMPLIANCE WITH ERP DIRECTIVE

NEW REQUIREMENTS FOR AIR HANDLING UNITS IN COMPLIANCE WITH ERP DIRECTIVE Bulletin of the Transilvania University of Braşov Vol. 10 (59) Special Issue No. 1-2017 Series I: Engineering Sciences NEW REQUIREMENTS FOR AIR HANDLING UNITS IN COMPLIANCE WITH ERP DIRECTIVE C. G. POPOVICI

More information

UNDERFLOOR AIR DISTRIBUTION INTEGRATED WITH AN INDIRECT AND DIRECT EVAPORATIVE COOLING ASSISTED 100% OUTDOOR AIR SYSTEM

UNDERFLOOR AIR DISTRIBUTION INTEGRATED WITH AN INDIRECT AND DIRECT EVAPORATIVE COOLING ASSISTED 100% OUTDOOR AIR SYSTEM UNDERFLOOR AIR DISTRIBUTION INTEGRATED WITH AN INDIRECT AND DIRECT EVAPORATIVE COOLING ASSISTED 100% OUTDOOR AIR SYSTEM YJ Seok, HJ Cho, SK Han and JW Jeong Department of Architectural Engineering, Sejong

More information

Energy Recovery Process Cooling Example. Presentation - Overview. Air Change Australia Pty Ltd. Air Change Energy Recovery Range

Energy Recovery Process Cooling Example. Presentation - Overview. Air Change Australia Pty Ltd. Air Change Energy Recovery Range 2 Presentation - Overview Energy Recovery Range + Designing Plant Rooms for Energy Efficiency The Company and the Technology Energy Recovery Product Range Product Range Pre-conditioners vs ERV-AHU s Energy

More information

Energy Recovery Ventilation & ERV Basics The New Custom Express Tool

Energy Recovery Ventilation & ERV Basics The New Custom Express Tool Energy Recovery Ventilation & ERV Basics The New Custom Express Tool Presented by: Dinesh Patel dinesh.patel@nationalgrid.com David Gaudet david.gaudet2@nationalgrid.com 1 What is and Why ERV? The recovery

More information

Integrated Design. Architectural Design v/s HVAC Design. HVAC Design after Architectural design

Integrated Design. Architectural Design v/s HVAC Design. HVAC Design after Architectural design Integrated Design A necessity for sustainable buildings Architectural Design v/s HVAC Design or HVAC Design after Architectural design or Integration of Concept, Location, Esthetic and Technical Design

More information

Grunenwald Science and Technology Building

Grunenwald Science and Technology Building Grunenwald Science and Technology Building Clarion University- Clarion, PA AE 482 Mechanical Project Proposal: Proposal for Alternative Designs Shane Helm The Pennsylvania State University Architectural

More information

Practical research on effective use of simulation for HVAC systems in the retro-commissioning process H. Tanaka 1, S. Ito 2, Y. Morikawa 3, Y. Akashi

Practical research on effective use of simulation for HVAC systems in the retro-commissioning process H. Tanaka 1, S. Ito 2, Y. Morikawa 3, Y. Akashi Practical research on effective use of simulation for HVAC systems in the retro-commissioning process H. Tanaka, S. Ito, Y. Morikawa, Y. Akashi, and M. Yamaha Campus Planning&Environment Management Office,

More information

ENERGY AND ECONOMIC ANALYSIS OF AN AUDITORIUM S AIR CONDITIONING SYSTEM WITH HEAT RECOVERY IN VARIOUS CLIMATIC ZONES

ENERGY AND ECONOMIC ANALYSIS OF AN AUDITORIUM S AIR CONDITIONING SYSTEM WITH HEAT RECOVERY IN VARIOUS CLIMATIC ZONES S933 ENERGY AND ECONOMIC ANALYSIS OF AN AUDITORIUM S AIR CONDITIONING SYSTEM WITH HEAT RECOVERY IN VARIOUS CLIMATIC ZONES Introduction by Konstantinos T. PAPAKOSTAS *, Ioannis TIGANITIS, and Agis M. PAPADOPOULOS

More information

Air distribution and temperature control in classrooms

Air distribution and temperature control in classrooms Air distribution and temperature control in classrooms Jarek Kurnitski D.Sc., Docent HELSINKI UNIVERSITY OF TECHNOLOGY Laboratory of Heating, Ventilation and Air Conditioning Swegon Air Academy 11.6.2008

More information

ENERGY CONSERVATION STRATEGIES FOR HVAC SYSTEMS

ENERGY CONSERVATION STRATEGIES FOR HVAC SYSTEMS ENERGY CONSERVATION STRATEGIES FOR HVAC SYSTEMS Heating ventilation and airconditioning systems consumes nearly 50 to 60% of the total power consumption in any building and thus, offers huge potential

More information

Eurovent Association Eurovent Certification Activities related to ENERGY EFFICIENCY

Eurovent Association Eurovent Certification Activities related to ENERGY EFFICIENCY Eurovent Association Eurovent Certification Activities related to ENERGY EFFICIENCY INTRODUCTION Eurovent Association: Working Groups Eurovent Certification: For a fair competition on the market Energy

More information

Georgetown University New Science Center

Georgetown University New Science Center Georgetown University New Science Center Final Thesis Proposal PENN STATE UNIVERSITY Prepared For: Dr. William P. Bahnfleth Department of Architectural Engineering Prepared By: Kevin M Edstrom Mechanical

More information

Water Bottling Facility

Water Bottling Facility TECHNICAL REPORT 2 Water Bottling Facility Mid-Atlantic, US Building and Plant Energy Analysis Report The Pennsylvania State University Author: Justyne Neborak Architectural Engineering Advisor: Dr. William

More information

LIFE CYCLE COSTS FOR INDOOR CLIMATE SYSTEMS WITH REGARDS TO SYSTEM CHOICE, AIRFLOW RATE AND PRODUCTIVITY IN OFFICES

LIFE CYCLE COSTS FOR INDOOR CLIMATE SYSTEMS WITH REGARDS TO SYSTEM CHOICE, AIRFLOW RATE AND PRODUCTIVITY IN OFFICES LIFE CYCLE COSTS FOR INDOOR CLIMATE SYSTEMS WITH REGARDS TO SYSTEM CHOICE, AIRFLOW RATE AND PRODUCTIVITY IN OFFICES Dennis Johansson 1,2 1 Research and Development, Swegon AB, Tomelilla, Sweden 2 Building

More information

Next Generation: High Efficiency Energy Recovery Ventilator (ERV) 11/14/11 Dais Analytic Corporation

Next Generation: High Efficiency Energy Recovery Ventilator (ERV) 11/14/11 Dais Analytic Corporation Next Generation: High Efficiency Energy Recovery Ventilator (ERV) 11/14/11 Dais Analytic Corporation Why use an ERV? Required by code in many states (ASHRAE & IBC) Pre-condition incoming fresh air using

More information

Energy aspects of HVAC system configurations problem definition and test cases

Energy aspects of HVAC system configurations problem definition and test cases Loughborough University Institutional Repository Energy aspects of HVAC system configurations problem definition and test cases This item was submitted to Loughborough University's Institutional Repository

More information

Whole Building Energy Performance Evaluation through. Similar Control Strategies

Whole Building Energy Performance Evaluation through. Similar Control Strategies Whole Building Energy Performance Evaluation through Similar Control Strategies S.H. Cheon 1, Y.H. Kwak 1, C.Y. Jang 2, and J.H. Huh 1* 1 Department of Architectural Engineering, University of Seoul, Seoul

More information

Jonas Strautnikas T6614KA ANALYSIS OF EXHAUST AIR-SOURCE HEAT PUMP. Bachelor s Thesis Double Degree Programme in Building Services Engineering

Jonas Strautnikas T6614KA ANALYSIS OF EXHAUST AIR-SOURCE HEAT PUMP. Bachelor s Thesis Double Degree Programme in Building Services Engineering Jonas Strautnikas T6614KA ANALYSIS OF EXHAUST AIR-SOURCE HEAT PUMP Bachelor s Thesis Double Degree Programme in Building Services Engineering January 2015 Date of the bachelor's thesis January 2015 Author(s)

More information

INCENTIVE ESTIMATOR HVAC USER GUIDE CONTENTS FLORIDA CUSTOM INCENTIVE PROGRAM

INCENTIVE ESTIMATOR HVAC USER GUIDE CONTENTS FLORIDA CUSTOM INCENTIVE PROGRAM INCENTIVE ESTIMATOR HVAC USER GUIDE FLORIDA CUSTOM INCENTIVE PROGRAM CONTENTS 1. Getting Started... 2 2. Measure Tool Description... 3 2.1. Appropriate Use of the Tool... 3 2.2. Applicable Types of Air

More information

THE USE OF HEAT RECOVERY DEVICES FOR REDUCING ENERGY CONSUMPTION OF TREATING VENTILATION AIR IN A TROPICAL OPERATING THEATRE

THE USE OF HEAT RECOVERY DEVICES FOR REDUCING ENERGY CONSUMPTION OF TREATING VENTILATION AIR IN A TROPICAL OPERATING THEATRE T13-O-15: Air conditioning components Proceedings: EERB-BEPH 2009 THE USE OF HEAT RECOVERY DEVICES FOR REDUCING ENERGY CONSUMPTION OF TREATING VENTILATION AIR IN A TROPICAL OPERATING THEATRE Y.H. Yau *

More information

ECONOMIC HEATING SYSTEMS FOR LOW ENERGY BUILDINGS IN SWEDEN

ECONOMIC HEATING SYSTEMS FOR LOW ENERGY BUILDINGS IN SWEDEN Numbers of Abstract/Session (given by NOC) - 1 - ECONOMIC HEATING SYSTEMS FOR LOW ENERGY BUILDINGS IN SWEDEN Svein, Ruud, Senior expert, Department of Energy Technology, SP Technical Research Institute

More information

AMENDMENT NO. 4 AUGUST 2010 TO IS 1391 (PART 1) : 1992 ROOM AIR CONDITIONERS SPECIFICATION

AMENDMENT NO. 4 AUGUST 2010 TO IS 1391 (PART 1) : 1992 ROOM AIR CONDITIONERS SPECIFICATION AMENDMENT NO. 4 AUGUST 2010 TO IS 1391 (PART 1) : 1992 ROOM AIR CONDITIONERS SPECIFICATION PART 1 UNITARY AIR CONDITIONERS ( Second Revision ) (Page 9, clause 11.1.1) Substitute the following for the existing:

More information

Valent Packaged Rooftop Units A Fresh Choice for High-Percentage Outdoor Air Designs. Valent is a business of Unison Comfort Technologies.

Valent Packaged Rooftop Units A Fresh Choice for High-Percentage Outdoor Air Designs. Valent is a business of Unison Comfort Technologies. Valent Packaged Rooftop Units A Fresh Choice for High-Percentage Outdoor Air Designs Valent is a business of Unison Comfort Technologies. When your HVAC system design calls for high-percentage or 100%

More information

Energy Efficiency in Building Active Design Part II

Energy Efficiency in Building Active Design Part II Energy Efficiency in Building Active Design Part II Presented by: CK Tang BSEEP Component 4 Manager Veritas Enviornment Sdn Bhd ck.tang@veritas.com.my Air Conditioning System System Sizing 1 Current Industry

More information

Ministerio Público Fiscal de la Ciudad de Buenos Aires Fiscalía General Departamento de Infraestructura y Apoyo Operativo

Ministerio Público Fiscal de la Ciudad de Buenos Aires Fiscalía General Departamento de Infraestructura y Apoyo Operativo Air System Design Load Summary for Zona 1 Project Name: Av. Cabildo 3076, 4 piso 04/05/2011 DESIGN COOLING DESIGN HEATING COOLING DATA AT Feb 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 34.9 C / 23.8

More information

FLEXY EC HIGH EFFICIENCY ROOFTOP kw AIR COOLED COOLING ONLY/HEAT PUMP/ GAS/ DUAL FUEL

FLEXY EC HIGH EFFICIENCY ROOFTOP kw AIR COOLED COOLING ONLY/HEAT PUMP/ GAS/ DUAL FUEL FLEXY EC HIGH EFFICIENCY ROOFTOP AIR COOLED COOLING ONLY/HEAT PUMP/ GAS/ DUAL FUEL 85-234 kw Energy savings through innovations Guaranteed sustainable performance with edrive With a rooftop, the major

More information

CASE STUDIES OF SYSTEMS INTEGRATION THROUGH ENERGY SIMULATION DURING EARLY DESIGN PHASE

CASE STUDIES OF SYSTEMS INTEGRATION THROUGH ENERGY SIMULATION DURING EARLY DESIGN PHASE CASE STUDIES OF SYSTEMS INTEGRATION THROUGH ENERGY SIMULATION DURING EARLY DESIGN PHASE Kapil Upadhyaya David McLean Energy modeler Project Manager Kirksey CHPA kapilu@kirksey.com, dmaclean@chpengr.com,

More information

SOLUTIONS OF ENERGY OPTIMISATION IN INDUSTRIAL PLANTS

SOLUTIONS OF ENERGY OPTIMISATION IN INDUSTRIAL PLANTS Bulletin of the Transilvania University of Braşov CIBv 2014 Vol. 7 (56) Special Issue No. 1-2014 SOLUTIONS OF ENERGY OPTIMISATION IN INDUSTRIAL PLANTS A. RETEZAN 1 S. Z. GEYER EHRENBERG 1 C. PĂCURAR 1

More information

Oklahoma University Children s Medical Office Building

Oklahoma University Children s Medical Office Building Oklahoma University Children s Medical Office Building Oklahoma City, O.K., BAE Advisor: Laura Miller Presentation Outline VRF System Dedicated Outdoor Air System Evaluation VRF Indoor Units Design Criteria

More information

Reducing Hospital Energy Use and Maintaining Savings. Glen Anderson, PE

Reducing Hospital Energy Use and Maintaining Savings. Glen Anderson, PE Reducing Hospital Energy Use and Maintaining Savings Glen Anderson, PE AIA Quality Assurance The Building Commissioning Association is a Registered Provider with The American Institute of Architects Continuing

More information

ASHRAE s LowDown Showdown

ASHRAE s LowDown Showdown ASHRAE s LowDown Showdown Presented to the Building Energy Simulation Forum 14 February 2018 James Cullin, PhD, PE Overview Project Approach Existing Building Modeling/Calibration Proposed Design Proposed

More information

Xavier Energy Initiative

Xavier Energy Initiative Xavier Energy Initiative By Ron Perkins Report of August Site Visit To paraphrase Blaise Pascal, if I had more time I would have written a shorter report. In deference to those who do not share my enthusiasm

More information

3 Mechanical System Redesign

3 Mechanical System Redesign 3 Mechanical System Redesign 3.1 Considered Alternatives The MAC building offered many opportunities to change the existing design and explore an alternative different than the solution the original design

More information

GATES-HILLMAN CENTERS

GATES-HILLMAN CENTERS GATES-HILLMAN CENTERS CARNEGIE MELLON UNIVERSITY CASE STUDY ENERGY EFFICIENCY CARNEGIE MELLON UNIVERSITY Carnegie Mellon University looked to SEMCO to provide solutions for their energy efficiency goals.

More information

EFFECTS OF WEATHERS AND INDOOR TEMPERATURES ON PERFORMANCE OF ENERGY RECOVERY VENTILATOR. Yanping Zhou, Jingyi Wu, Ruzhu Wang

EFFECTS OF WEATHERS AND INDOOR TEMPERATURES ON PERFORMANCE OF ENERGY RECOVERY VENTILATOR. Yanping Zhou, Jingyi Wu, Ruzhu Wang EFFECTS OF WEATHERS AND INDOOR TEMPERATURES ON PERFORMANCE OF ENERGY RECOVERY VENTILATOR Yanping Zhou, Jingyi Wu, Ruzhu Wang (Institute of Refrigeration and Cryogenics, Shanghai Jiaotong University, Shanghai,

More information

Coupling night ventilative and active cooling to reduce energy use in supermarkets with high refrigeration loads

Coupling night ventilative and active cooling to reduce energy use in supermarkets with high refrigeration loads Coupling night ventilative and active cooling to reduce energy use in supermarkets with high refrigeration loads ABSTRACT Zoi Mylona *1, Maria Kolokotroni 1 and Savvas Tassou 1 1 RCUK National Centre for

More information

After refurbishment, heat recovery and demand control of the air flow were installed and the use of the systems were optimized.

After refurbishment, heat recovery and demand control of the air flow were installed and the use of the systems were optimized. Property name: Nordstan Nordstan Objekt 6 Property owner: Vasakronan AB Consultants: GICON Total Concept method Step 1. Creating the action package Building and its use Year built: 1968 Area: 48 600 m²

More information

The optimization of the mechanical night cooling system in the office building

The optimization of the mechanical night cooling system in the office building The optimization of the mechanical night cooling system in the office building Milos Lain 1, Jan Hensen 2 1 Department of Environmental Engineering, Faculty of Mechanical Engineering, Czech Technical University

More information

Strategies for energy efficiency improvement in residential and office buildings: their role at building and country scale

Strategies for energy efficiency improvement in residential and office buildings: their role at building and country scale The Future Role of Energy Storage in South Eastern Europe Enlargement and Integration Action Workshop Strategies for energy efficiency improvement in residential and office buildings: their role at building

More information

Sample Reports. for. HAP v4.80 Example Problem

Sample Reports. for. HAP v4.80 Example Problem Sample Reports for HAP v4.80 Example Problem October, 2013 Carrier Software Systems Copyright 2013 Carrier Corporation, All Rights Reserved Introduction This document contains reports generated using the

More information

DesignTools Software Energy Analyzer User Manual

DesignTools Software Energy Analyzer User Manual DesignTools Software Energy Analyzer User Manual Table of Contents Introduction...1 Installing Energy Analyzer...3 Getting Started...4 General...4 Project Details (Energy Analyzer Wizard Application)...5

More information

University of Minnesota Duluth Civil Engineering Building

University of Minnesota Duluth Civil Engineering Building Energy Data Attachment University of Minnesota Duluth Civil Engineering Building LEED Energy Modeling The energy modeling for LEED NC 2.2 was performed against ASHRAE 9.1-24 Appendix using equest version

More information

Developing Exhaust Air Energy Recovery Credits for the Florida Energy Code

Developing Exhaust Air Energy Recovery Credits for the Florida Energy Code Developing Exhaust Air Energy Recovery Credits for the Florida Energy Code FSEC-CR-2003-15 Final Report May 27, 2015 Submitted to Department of Business and Professional Regulation Office of Codes and

More information

The baseline building system for compliance with Senate Bill 668 is defined by Appendix G,

The baseline building system for compliance with Senate Bill 668 is defined by Appendix G, Project: North Carolina A&T State University New Student Health Center SCO #: 08-08109-01A 1.0 Heating, Ventilating and Air Conditioning (HVAC) Baseline Building Systems Senate Bill 668 Compliance The

More information

Geothermal Systems: Harnessing Earth s Energy

Geothermal Systems: Harnessing Earth s Energy Geothermal Systems: Harnessing Earth s Energy 4 November 2014 Ground Source Heating and Cooling What is It? How does it Work? What makes it Unique? Why all systems are not Equal? 1 Building Owner Expectations

More information

SMART HVAC & LIGHTING SYSTEMS. Savings From Two Major C&I End Uses

SMART HVAC & LIGHTING SYSTEMS. Savings From Two Major C&I End Uses SMART HVAC & LIGHTING SYSTEMS Savings From Two Major C&I End Uses September 21, 2016 PRESENTATION OVERVIEW Why this focus? Significant savings potential Smart controls coupled with more efficient technologies

More information

Impacts of Increased Outdoor Air Flow Rates on Annual HVAC Energy Costs

Impacts of Increased Outdoor Air Flow Rates on Annual HVAC Energy Costs Impacts of Increased Outdoor Air Flow Rates on Annual HVAC Energy Costs David Mudarri, U.S. EPA, Indoor Environments Division John D. Hall, ICF Kaiser Consulting Group Eric Werling, ICF Kaiser Consulting

More information

Smart Labs: Building Next Generation Labs While Maintaining Safety and Comfort

Smart Labs: Building Next Generation Labs While Maintaining Safety and Comfort Smart Labs: Building Next Generation Labs While Maintaining Safety and Comfort JAVIER NAVAR PAYAN, MSME, PE (MINNESOTA), CEM Senior Energy Engineer University of Minnesota AIA Quality Assurance The Building

More information

Air-Water Systems. Chilled Ceilings and Beams TROX USA. Principle of Operation. Radiant Effect on Occupants. Early 1980 s. Chilled Ceiling Panels

Air-Water Systems. Chilled Ceilings and Beams TROX USA. Principle of Operation. Radiant Effect on Occupants. Early 1980 s. Chilled Ceiling Panels Air-Water Systems and Beams Early 1980 s 1980 1990 2005 Buildings well insulated for heating Advent of personal computers Need to remove heat from space Limited space available TROX USA 1 2 Principle of

More information

Demand Controlled Ventilation. A Detailed Study of Energy Usage by Simulation

Demand Controlled Ventilation. A Detailed Study of Energy Usage by Simulation Demand Controlled Ventilation. A Detailed Study of Energy Usage by Simulation B.R. Sørensen Narvik University College, Building Science, NO-8514 Narvik, Norway, e-mail: brs@hin.no ABSTRACT Detailed mathematical

More information

Three Case Studies of the Application of Energy Systems Optimization Best Practices for Automatic Demand Response

Three Case Studies of the Application of Energy Systems Optimization Best Practices for Automatic Demand Response Three Case Studies of the Application of Energy Systems Optimization Best Practices for Automatic Demand Response Yifu Shi Kelly Guiberteau Carlos Yagua, P.E. James Watt, P.E. Energy Systems Laboratory,

More information

ECODESIGN by FLÄKTGROUP.» ErP REGULATION 1253 AND 1254/2014 FOR RESIDENTIAL AND NON-RESIDENTIAL VENTILATION UNITS

ECODESIGN by FLÄKTGROUP.» ErP REGULATION 1253 AND 1254/2014 FOR RESIDENTIAL AND NON-RESIDENTIAL VENTILATION UNITS ECODESIGN by FLÄKTGROUP» ErP REGULATION 1253 AND 1254/2014 FOR RESIDENTIAL AND NON-RESIDENTIAL VENTILATION UNITS 2 All our research, development and testing activities are singularly focused to provide

More information

EMD SERONO RESEARCH CENTER EXISTING

EMD SERONO RESEARCH CENTER EXISTING EMD SERONO RESEARCH CENTER EXISTING BILLERICA, MA SHIYUN (SHARON) CHEN MECHANICAL AE SENIOR THESIS Building System Dedicated Outdoor Air System/ Systems Breadth Building Design Team Building: EMD Serono

More information

Application of Advanced Energy Technologies

Application of Advanced Energy Technologies GLOBALCON 2002 Philadelphia, Pennsylvania March 27, 2002 Application of Advanced Energy Technologies Michael K. West, Ph.D., P.E. Building Systems Scientist Advantek Consulting, Inc. www.advantekinc.com

More information

ENERGY PERFORMANCE MODELLING AND HEAT RECOVERY UNIT EFFICIENCY ASSESSMENT OF AN OFFICEBUILDING

ENERGY PERFORMANCE MODELLING AND HEAT RECOVERY UNIT EFFICIENCY ASSESSMENT OF AN OFFICEBUILDING ENERGY PERFORMANCE MODELLING AND HEAT RECOVERY UNIT EFFICIENCY ASSESSMENT OF AN OFFICEBUILDING Norbert L. HARMATI a*, Radomir J. FOLIĆ a, Zoltán MAGYAR b a University of Novi Sad, Faculty of Technical

More information

Thesis Proposal. Clemson University Advanced Material Research Laboratory Anderson, SC. David Anderson Mechanical Option. Photo by Fred Martin

Thesis Proposal. Clemson University Advanced Material Research Laboratory Anderson, SC. David Anderson Mechanical Option. Photo by Fred Martin Thesis Proposal Photo by Fred Martin Clemson University Advanced Material Research Laboratory Anderson, SC David Anderson Mechanical Option Friday, December 15, 2006 Table of Contents 1. Executive Summary

More information

Technical Report Three Mechanical Systems Existing Conditions Evaluation

Technical Report Three Mechanical Systems Existing Conditions Evaluation 09 10 Technical Report Three Mechanical Systems Existing Conditions Evaluation WESTINGHOUSE ELECTRIC CO. NUCLEAR ENGINEERING HEADQUARTERS CAMPUS Pittsburgh, PA Daniel P. Aughenbaugh Mechanical Dr. Bahnfleth

More information

How to Reduce Energy Use in Your Labs by Up to 50%

How to Reduce Energy Use in Your Labs by Up to 50% How to Reduce Energy Use in Your Labs by Up to 50% Illinois Chapter of ASHRAE April 11, 2017 Dan Doyle, Chairman Grumman/Butkus Associates 1 Course Description Labs have high exhaust requirements and large

More information

Load Estimation. Ir. Dr. Sam C. M. Hui Faculty of Science and Technology

Load Estimation. Ir. Dr. Sam C. M. Hui Faculty of Science and Technology SPD4121 HVAC Technology for Plumbing Engineers http://ibse.hk/spd4121/ Load Estimation Ir. Dr. Sam C. M. Hui Faculty of Science and Technology E-mail: cmhui@vtc.edu.hk Jul 2016 Contents Basic Concepts

More information

Energy Auditing for Schools. Maryland Energy Administration Eric Oliver, EMO Energy Solutions, LLC May 10, 2007

Energy Auditing for Schools. Maryland Energy Administration Eric Oliver, EMO Energy Solutions, LLC May 10, 2007 Energy Auditing for Schools Maryland Energy Administration Eric Oliver, EMO Energy Solutions, LLC May 10, 2007 Schools Consumption breakdown 19% 6% 9% Space Heating 46% Water Heating Lighting Cooling 20%

More information

HEATING AND COOLIND G DEMANDS IN BUILDINGS CALCULATIONS

HEATING AND COOLIND G DEMANDS IN BUILDINGS CALCULATIONS HEATING AND COOLIND G DEMANDS IN BUILDINGS CALCULATIONS Annual energy efficiency of the heat recovery of ventilation q se1 q se2 Kuva: Ympäristöministeriön moniste 122 Aki Valkeapää / Martti Veuro Mikkeli

More information

US1 IEA. Renovation of Wausau West High School, Wisconsin, United States of America

US1 IEA. Renovation of Wausau West High School, Wisconsin, United States of America IEA Energy Conservation in Buildings and Community Systems, Annex 36 Case studies overview Renovation of Wausau West High School, Wisconsin, 1 Photos Figure 1: Wausau West High School 2 Project summary

More information

Fresh air pre-cooling and energy recovery by using indirect evaporative cooling in hot and humid region a case study in Hong Kong

Fresh air pre-cooling and energy recovery by using indirect evaporative cooling in hot and humid region a case study in Hong Kong Available online at www.sciencedirect.com ScienceDirect Energy Procedia 61 (2014 ) 126 130 The 6 th International Conference on Applied Energy ICAE2014 Fresh air pre-cooling and energy recovery by using

More information

Energy Reduction in Hospitals

Energy Reduction in Hospitals Energy Reduction in Hospitals OSBORN ENGINEERING DAVE CHOUINARD, CBCP, LEED AP, DIRECTOR HEALTHCARE CARL SCHULTZ, PE, DIRECTOR ENERGY AND FACILITY SYSTEMS MARK WUTZ, PE, DIRECTOR ENERGY & COMMISSIONING

More information

A new application of an old idea

A new application of an old idea Thermal Energy Storage A new application of an old idea As the second-most populated country on this planet, India s ever-growing demand for energy has shown no signs of dwindling. A clearly strained electricity

More information

Energy-Efficient Passive House using thermal mass to achieve high thermal comfort

Energy-Efficient Passive House using thermal mass to achieve high thermal comfort Energy-Efficient Passive House using thermal mass to achieve high thermal comfort Loa Andersson Managing Director RLI Byggdata AB rli@termodeck.com Alexander Engström Technical Director RLI Byggdata AB

More information

COOLING COIL (35% ETHYLENE GLYCOL)

COOLING COIL (35% ETHYLENE GLYCOL) APPENDIX Contents A1.1 Existing Mechanical Equipment Schedules A1.2 Existing Mechanical System Schematic Drawings A2. Building Design Loads, Energy Loads and Cost Data Tables A3. Standard 62n-2001 Ventilation

More information

Ventilation Why and How

Ventilation Why and How Ventilation Why and How Mich Swainson BRE HVAC Engineering swainsonm@bre.co.uk 21 st June 2017 Part of the BRE Trust Ventilation why? Provision of fresh air Removal of odours Removal of pollutants Removal

More information

ANALYSIS OF EXERGY OF MOIST AIR AND ENERGY SAVING POTENTIAL IN HVAC BY EVAPORATIVE COOLING OR ENERGY RECOVERY

ANALYSIS OF EXERGY OF MOIST AIR AND ENERGY SAVING POTENTIAL IN HVAC BY EVAPORATIVE COOLING OR ENERGY RECOVERY , Volume 2, Number 4, p.113-117, 2001 ANALYSIS OF EXERGY OF MOIST AIR AND ENERGY SAVING POTENTIAL IN HVAC BY EVAPORATIVE COOLING OR ENERGY RECOVERY C.Q. Ren, G.F. Tang, N.P. Li, G.F. Zhang and J. Yang

More information

Proceedings of BS2013: 13th Conference of International Building Performance Simulation Association, Chambéry, France, August 26-28

Proceedings of BS2013: 13th Conference of International Building Performance Simulation Association, Chambéry, France, August 26-28 HVAC CONTROL SIMULATION STUDY FOR AUSTRALIAN OFFICE BUILDINGS Hongsen Zhang and Paul Bannister Exergy Australia Pty Ltd, Canberra, Australia hongsen@xgl.com.au; paul@xgl.com.au ABSTRACT This paper presents

More information

CONTINUOUS COMMISSIONING OF SALT LAKE COMMUNITY COLLEGE SOUTH CITY CAMPUS

CONTINUOUS COMMISSIONING OF SALT LAKE COMMUNITY COLLEGE SOUTH CITY CAMPUS CONTINUOUS COMMISSIONING OF SALT LAKE COMMUNITY COLLEGE SOUTH CITY CAMPUS Song Deng, P.E. and Dan Turner, P.E., Ph.D., Energy Systems Laboratory, Texas A&M University System, College Station, Texas Jim

More information

A Paradigm Shift in ERV Technology. Paul Ehrlich, PE President Building Intelligence Group PLLC

A Paradigm Shift in ERV Technology. Paul Ehrlich, PE President Building Intelligence Group PLLC A Paradigm Shift in ERV Technology Paul Ehrlich, PE President Building Intelligence Group PLLC August 9, 2013 Existing Buildings and Energy Existing buildings: Floor space: Floor space per building: Energy

More information

ROOF TOP SPACE. SELF-CONTAINED REVERSIBLE AIR-AIR UNITS OF 23 TO 281 kw EVERY EFFICIENT SOLUTION FOR UNIVERSAL COMFORT NA C

ROOF TOP SPACE. SELF-CONTAINED REVERSIBLE AIR-AIR UNITS OF 23 TO 281 kw EVERY EFFICIENT SOLUTION FOR UNIVERSAL COMFORT NA C C O M F O R T A I R Q U A L I T Y E N E R G Y O P T I M I S A T I O N ROOF TOP SPACE SELF-CONTAINED REVERSIBLE AIR-AIR UNITS OF 23 TO 281 kw EVERY EFFICIENT SOLUTION FOR UNIVERSAL COMFORT NA. 0816 C SPACE

More information

SYSTEM SETBACKS ENERGY-SAVING STRATEGIES: Description of Potential

SYSTEM SETBACKS ENERGY-SAVING STRATEGIES: Description of Potential ENERGY-SAVING STRATEGIES: SYSTEM SETBACKS Goal: To use appropriate, risk-managed mechanical system set point setbacks in temperature or relative humidity to achieve energy savings with minimal impact on

More information

Building Control Strategies That Work to Improve Your Energy Bottom Line

Building Control Strategies That Work to Improve Your Energy Bottom Line Building Control Strategies That Work to Improve Your Energy Bottom Line William D. (Skip) Milton MBA, CEM, CEA Assistant Director of Facilities Operations Texas Children s Hospital Objective: Learn how

More information

OUTDOOR AIR, HEAT WHEELS AND JCPENNEY: A NEW APPROACH TO RETAIL VENTILATION

OUTDOOR AIR, HEAT WHEELS AND JCPENNEY: A NEW APPROACH TO RETAIL VENTILATION OUTDOOR AIR, HEAT WHEELS AND JCPENNEY: A NEW APPROACH TO RETAIL VENTILATION Christopher S. Smith, E.I.T. and Thomas A. Bartlett, P.E. JCPenney Company, Inc. Construction Services Mechanical Engineering

More information

University of Saskatchewan Education Building Mechanical Controls Re-Design

University of Saskatchewan Education Building Mechanical Controls Re-Design MECHANICAL ENGINEERING DEPARTMENT University of Saskatchewan Education Building Mechanical Controls Re-Design Group 3 By: Jay Brockmann Luke Deobald Tanner Deobald Dacey Schentag February 2015 MECHANICAL

More information

Retrocommissioning: A Persistence Study

Retrocommissioning: A Persistence Study Retrocommissioning: A Persistence Study Umamaheswar Krishnan and Aniruddha Duttagupta, Nexant, Inc Alan Ahrens, CenterPoint Energy ABSTRACT Retrocommissioning (RCx) projects have become more commonplace

More information

Mechanical Depth. Redesign and Analysis

Mechanical Depth. Redesign and Analysis Depth Redesign and Analysis 14 Analysis Scope The scope of my mechanical redesign will include the 2 nd and 3 rd floors of the SW hospital wing which includes Semi-Private, Private and Isolations rooms.

More information

indoor air quality and energy saving TECHNICAL DATA JD/JD ENTHALPIC HEAT RECOVERY VENTILATION UNITS for RESIDENTIAL BUILDINGS

indoor air quality and energy saving TECHNICAL DATA JD/JD ENTHALPIC HEAT RECOVERY VENTILATION UNITS for RESIDENTIAL BUILDINGS indoor air quality and energy saving TECHNICAL DATA JD/JD ENTHALPIC HEAT RECOVERY VENTILATION UNITS for RESIDENTIAL BUILDINGS JD Remotable high efficiency heat recovery module without fans. To be interfaced

More information

Building Retro-Commissioning

Building Retro-Commissioning Building Retro-Commissioning Greg Swiss SEDAC Building Energy Specialist Smart Energy Design Assistance Center (SEDAC), University of Illinois at Urbana Champaign WHAT IS RETRO-COMMISSIONING? Commissioning

More information

Energy Efficiency. best in class

Energy Efficiency. best in class Page 1 The impact of Building Automation on Energy Efficiency Siemens with DESIGO and Synco best in class Energy is a major issue for the European Union Primary energy use in Europe Dependency Without

More information

Acknowledgements 4. Executive Summary 5

Acknowledgements 4. Executive Summary 5 Table of Contents Acknowledgements 4 Executive Summary 5 Building Overview.. 6 Building Summary.. 6 Site. 6 Evaluation of Existing Mechanical System. 7 Mechanical System Overview 7 Design Objective 7 Outdoor

More information

Pinch Analysis of an Industrial Milk Evaporator with Vapour Recompression Technologies

Pinch Analysis of an Industrial Milk Evaporator with Vapour Recompression Technologies Pinch Analysis of an Industrial Milk Evaporator with Vapour Recompression Technologies Energy Research Centre University of Waikato New Zealand Dr Tim Walmsley A.Prof Michael Walmsley Dr James Neale Dr

More information

2. The requirements of Sections 502, 503, 504 and 505. In addition, commercial buildings shall comply with either Section 506.2, or

2. The requirements of Sections 502, 503, 504 and 505. In addition, commercial buildings shall comply with either Section 506.2, or Public Comment 3: Dave Hewitt, representing New Buildings Institute, Jessyca Henderson, representing American Institute of Architects, Ron Majette, representing U.S. Department of Energy requests Approval

More information

Sample Reports. for. HAP v4.90 Example Problem

Sample Reports. for. HAP v4.90 Example Problem Sample Reports for HAP v4.90 Example Problem December, 2014 Carrier Software Systems Copyright 2014 Carrier Corporation, All Rights Reserved Introduction This document contains reports generated using

More information

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya (vahid.vakiloroaya@engineer.com) ABSTRACT: The overall attainable reduction in energy consumption and enhancement of

More information

Heat recovery units. One can live 3 weeks without food, 3 days without water, 3 minutes without air!

Heat recovery units. One can live 3 weeks without food, 3 days without water, 3 minutes without air! Heat recovery units The air we breathe is important for our life! One can live 3 weeks without food, 3 days without water, 3 minutes without air! People in industrialized countries spend indoor, on average

More information

FUNDAMENTALS OF CHILLED BEAMS ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS

FUNDAMENTALS OF CHILLED BEAMS ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS FUNDAMENTALS OF CHILLED BEAMS ANSI/ASHRAE STANDARD 200-2015, METHODS OF TESTING CHILLED BEAMS NEMIC 2017 Hello! I am Davor Novosel I am here because I love to share what I know about chilled beams with

More information