Air Conditioning. Technical Data EEDEN RXS-L

Size: px
Start display at page:

Download "Air Conditioning. Technical Data EEDEN RXS-L"

Transcription

1 Air Conditioning Technical Data EEDEN RXS-L

2

3 TABLE OF CONTENTS RXS-L 1 Features Specifications Capacity and Power input Capacity and Power input Capacity and Power input Capacity and Power input Capacity and Power input Capacity and Power input Capacity and Power input Capacity and Power input Capacity and Power input Capacity and Power input Capacity and Power input Technical Specifications Electrical Specifications Electrical data Capacity tables Cooling/Heating Capacity Tables Dimensional drawings Centre of gravity Piping diagrams Wiring diagrams Wiring Diagrams - Single Phase Sound data Sound Pressure Spectrum - Cooling Sound Pressure Spectrum - Heating Operation range Split - Sky Air RXS-L 1

4 k i n - r o t o i d - l t p u 1 Features Outdoor Unit RXS-L S U 1 L S X O RS Outdoor unit silent operation: "silent" button on the remote control lowers the operation sound of the outdoor unit by dba to ensure a quiet environment for the neighbourhood. Energy saving during standby mode: reduces current consumption by about 80% when operating In standby. If no people are detected for more than 20 minutes, the system will automatically switch to the current-saving mode. Outdoor units for pair application Daikin outdoor units are neat, sturdy and can easily be mounted on a roof or terrace or simply placed against an outside wall Outdoor units are fitted with a swing compressor, renowned for its low noise and high energy efficiency Anti-corrosion treated outdoor heat exchanger fin Inverter Energy saving Powerful mode during standby mode Auto coolingheating changeover Outdoor unit silent operation 2 Split - Sky Air RXS-L

5 2 Specifications Outdoor Unit RXS-L 2-1 Capacity and Power input FTXS42K/RXS42L FTXS50K/RXS50L Indoor unit FTXS42K FTXS50K Outdoor unit RXS42L RXS50L Cooling capacity Min. kw 1.7 Btu/h 5,800 kcal/h 1,460 Nom. kw 4.20 (1) 5.00 (1) Btu/h 14,00 (1) 17,100 (1) kcal/h,610 (1) 4,00 (1) Max. kw Btu/h 17,100 18,100 kcal/h 4,00 4,560 Heating capacity Min. kw 1.7 Btu/h 5,800 kcal/h 1,460 Nom. kw 5.40 (1) 5.80 (1) Btu/h 18,400 (1) 19,800 (1) kcal/h 4,640 (1) 4,990 (1) Max. kw Btu/h 20,500 22,200 kcal/h 5,160 5,590 Power input Cooling Min. kw Nom. kw 1.25 (1) (1) Max. kw Heating Min. kw Nom. kw 1.10 (1) (1) Max. kw Seasonal efficiency Cooling Energy label A++ (according to Pdesign kw EN14825) SEER 6.80 Annual energy consumption kwh Heating (Average Energy label A+ climate) Pdesign kw SCOP 4.20 Annual energy consumption kwh 1,4 1,55 Piping connections Liquid OD mm 6.5 Gas OD mm 12.7 Drain OD mm 18 Heat insulation Both liquid and gas pipes Current Nominal running Cooling A 6.7 (2) / 6.05 () / 5.84 (4) 7.05 (2) / 6.7 () / 6.41 (4) current (RLA) - 50Hz Heating A 6.6 (2) / 6. () / 6.0 (4) 6.8 (2) / 6.5 () / 6.2 (4) Nominal efficiency EER.5 (5).2 (5) COP 4.12 (5) 4.00 (5) Annual energy consumption kwh Energy label Cooling A Heating A 2 Notes (1) Nominal efficiency: cooling at 5 /27 nominal load, heating at 7 /20 nominal load (2) 220V () 20V (4) 240V (5) EER/COP according to Eurovent 2012, for use outside EU only Split - Sky Air RXS-L

6 2 Specifications Outdoor Unit RXS-L Capacity and Power input FTXS60G/RXS60L Cooling capacity Min. kw 1.7 Btu/h 5,800 kcal/h 1,460 Nom. kw 6.0 Btu/h 20,500 kcal/h 5,160 Max. kw 6.7 Btu/h 22,900 kcal/h 5,760 Heating capacity Min. kw 1.7 Btu/h 5,800 kcal/h 1,460 Nom. kw 7.0 Btu/h 2,900 kcal/h 6,020 Max. kw 8.0 Btu/h 27,00 kcal/h 6,880 Power input Cooling Min. kw Nom. kw Max. kw Heating Min. kw Nom. kw Max. kw Seasonal efficiency Cooling Energy label A (according to Pdesign kw 6.00 EN14825) SEER 5.58 Annual energy kwh 76 consumption Heating (Average Energy label A climate) Pdesign kw 4.80 SCOP.89 Annual energy kwh 1,728 consumption Piping connections Liquid OD mm 6.5 Gas OD mm 12.7 Drain OD mm 18 Heat insulation Both liquid and gas pipes Current Nominal running Cooling A 9.2 (1) / 8.8 (2) / 8.4 () current (RLA) - 50Hz Heating A 9.4 (1) / 9.0 (2) / 8.6 () Nominal efficiency EER.02 COP.4 Annual energy consumption kwh 995 Energy label Cooling B Heating B Notes (1) 220V (2) 20V () 240V EER/COP according to Eurovent 2012, for use outside EU only Nominal efficiency: cooling at 5 /27 nominal load, heating at 7 /20 nominal load 4 Split - Sky Air RXS-L

7 2 Specifications Outdoor Unit RXS-L 2- Capacity and Power input FVXS50F/RXS50L Cooling capacity Min. kw 1.4 Btu/h 4,800 kcal/h 1,200 Nom. kw 5.0 Btu/h 17,100 kcal/h 4,00 Max. kw 5.6 Btu/h 19,100.0 kcal/h 4,820.0 Heating capacity Min. kw 1.4 Btu/h 4,800 kcal/h 1,200 Nom. kw 5.8 Btu/h 19,800 kcal/h 4,990 Max. kw 8.1 Btu/h 27,600 kcal/h 6,970 Power input Cooling Min. kw Nom. kw Max. kw Heating Min. kw Nom. kw Max. kw Seasonal efficiency Cooling Energy label A+ (according to Pdesign kw 5.00 EN14825) SEER 5.89 Annual energy kwh 297 consumption Heating (Average Energy label A climate) Pdesign kw 4.20 SCOP.80 Annual energy kwh 1,546 consumption Piping connections Liquid OD mm 6.5 Gas OD mm 12.7 Drain OD mm 20 Heat insulation Both liquid and gas pipes Current Nominal running Cooling A 7.2 (1) / 6.8 (2) / 6.6 () current (RLA) - 50Hz Heating A 7. (1) / 7.0 (2) / 6.7 () Nominal efficiency EER.2 COP.6 Annual energy consumption kwh 775 Energy label Cooling A Heating A 2 Notes (1) 220V (2) 20V () 240V EER/COP according to Eurovent 2012, for use outside EU only Cooling: indoor temp. 27 CDB, 19.0 CWB; outdoor temp. 5 CDB, 24 CWB; equivalent piping length: 5m Heating: indoor temp. 20 CDB; outdoor temp. 7 CDB, 6 CWB; equivalent refrigerant piping: 5m Nominal efficiency: cooling at 5 /27 nominal load, heating at 7 /20 nominal load Split - Sky Air RXS-L 5

8 2 Specifications Outdoor Unit RXS-L Capacity and Power input FLXS50B/RXS50L Cooling capacity Min. kw 0.9 Btu/h,070 kcal/h 770 Nom. kw 4.9 Btu/h 16,70 kcal/h 4,210 Max. kw 5. Btu/h 18,090 kcal/h 4,560 Heating capacity Min. kw 0.9 Btu/h,070 kcal/h 770 Nom. kw 6.1 Btu/h 20,80 kcal/h 5,250 Max. kw 7.5 Btu/h 18,090 kcal/h 6,450 Power input Cooling Min. kw Nom. kw Max. kw Heating Min. kw 0.10 Nom. kw Max. kw.540 Seasonal efficiency Cooling Energy label A (according to Pdesign kw 4.90 EN14825) SEER 5.25 Annual energy kwh 26 consumption Heating (Average Energy label A climate) Pdesign kw 4.20 SCOP.80 Annual energy kwh 1,546 consumption Piping connections Liquid OD mm 6.5 Gas OD mm 12.7 Drain OD mm 20 Heat insulation Both liquid and gas pipes Current Nominal running Cooling A 8.0 (1) / 7.6 (2) / 7. () current (RLA) - 50Hz Heating A 8.4 (1) / 8.0 (2) / 7.7 () Nominal efficiency EER 2.85 COP.5 Annual energy consumption kwh 860 Energy label Cooling C Heating C Notes (1) 220V (2) 20V () 240V EER/COP according to Eurovent 2012, for use outside EU only Cooling: indoor temp. 27 CDB, 19.0 CWB; outdoor temp. 5 CDB, 24 CWB; equivalent piping length: 5m Heating: indoor temp. 20 CDB; outdoor temp. 7 CDB, 6 CWB; equivalent refrigerant piping: 5m Nominal efficiency: cooling at 5 /27 nominal load, heating at 7 /20 nominal load 6 Split - Sky Air RXS-L

9 2 Specifications Outdoor Unit RXS-L 2-5 Capacity and Power input FDXS50F9/RXS50L Cooling capacity Min. kw 1.7 Btu/h 5,800 kcal/h 1,460 Nom. kw 5.0 Btu/h 17,100 kcal/h 4,00 Max. kw 5. Btu/h 18,100 kcal/h 4,560 Heating capacity Min. kw 1.7 Btu/h 5,800 kcal/h 1,460 Nom. kw 5.8 Btu/h 19,800 kcal/h 4,990 Max. kw 6.0 Btu/h 20,500 kcal/h 5,160 Power input Cooling Nom. kw Heating Nom. kw Seasonal efficiency Cooling Energy label A+ (according to Pdesign kw 5.00 EN14825) SEER 5.72 Annual energy kwh 06 consumption Heating (Average Energy label A climate) Pdesign kw 4.00 SCOP.9 Annual energy kwh 1,425 consumption Piping connections Liquid OD mm 6.5 Gas OD mm 12.7 Drain OD mm VP20 (External dia.26 / Internal dia. 20) Heat insulation Both liquid and gas pipes Current Nominal running Cooling A 7.1 (1) current (RLA) - 50Hz Heating A 8. (1) Nominal efficiency EER.0 COP.10 Annual energy consumption kwh 825 Energy label Cooling B Heating D 2 Notes (1) 20V EER/COP according to Eurovent 2012, for use outside EU only Nominal efficiency: cooling at 5 /27 nominal load, heating at 7 /20 nominal load 2-6 Capacity and Power input FDXS60F/RXS60L Cooling capacity Min. kw 1.7 Btu/h 5,800 kcal/h 1,460 Nom. kw 6.0 Btu/h 20,500 kcal/h 5,160 Max. kw 6.5 Btu/h 22,200 kcal/h 5,590 Split - Sky Air RXS-L 7

10 2 Specifications Outdoor Unit RXS-L Capacity and Power input FDXS60F/RXS60L Heating capacity Min. kw 1.7 Btu/h 5,800 kcal/h 1,460 Nom. kw 7.0 Btu/h 2,900 kcal/h 6,020 Max. kw 8.0 Btu/h 27,00 kcal/h 6,880 Power input Cooling Nom. kw Heating Nom. kw Seasonal efficiency Cooling Energy label A (according to Pdesign kw 6.00 EN14825) SEER 5.51 Annual energy kwh 81 consumption Heating (Average Energy label A climate) Pdesign kw 4.60 SCOP.80 Annual energy kwh 1,69 consumption Piping connections Liquid OD mm 6.5 Gas OD mm 12.7 Drain OD mm VP20 (External dia.26 / Internal dia. 20) Heat insulation Both liquid and gas pipes Current Nominal running Cooling A 9.2 (1) current (RLA) - 50Hz Heating A 10.0 (1) Nominal efficiency EER 2.91 COP.21 Annual energy consumption kwh 1,00 Energy label Cooling C Heating C Notes (1) 20V EER/COP according to Eurovent 2012, for use outside EU only Nominal efficiency: cooling at 5 /27 nominal load, heating at 7 /20 nominal load 2-7 Capacity and Power input FCQG50F/RXS50L FCQG60F/RXS60L Cooling capacity Min. kw 1.7 Btu/h 5,800 kcal/h 1,460 Nom. kw Btu/h 17,060 19,450 kcal/h 4,00 4,900 Max. kw Btu/h 18,100 19,450 kcal/h 4,560 4,900 Heating capacity Min. kw 1.7 Btu/h 5,800 kcal/h 1,460 Nom. kw Btu/h 20,472 2,890 kcal/h 5,160 6,020 Max. kw Btu/h 20,500 2,890 kcal/h 5,160 6,020 8 Split - Sky Air RXS-L

11 2 Specifications Outdoor Unit RXS-L 2-7 Capacity and Power input FCQG50F/RXS50L FCQG60F/RXS60L Power input Cooling Nom. kw Heating Nom. kw Seasonal efficiency Cooling Energy label A++ (according to Pdesign kw EN14825) SEER Annual energy consumption kwh Heating (Average Energy label A++ A+ climate) Pdesign kw SCOP Annual energy consumption kwh 1,426 1,646 Piping connections Liquid OD mm 6.5 Gas OD mm Drain OD mm VP25 (External dia.2 / internal dia. 25) Heat insulation Both liquid and gas pipes Current Nominal running Cooling A 6.6 (1) / 6. (2) / 6.0 () 7.8 (1) / 7.4 (2) / 7.0 () current (RLA) - 50Hz Heating A 7.6 (1) / 7. (2) / 6.9 () 9. (1) / 8.9 (2) / 8.5 () Nominal efficiency EER COP.7.52 Annual energy consumption kwh Energy label Cooling A Heating A B 2 Notes (1) 220V (2) 20V () 240V EER/COP according to Eurovent 2012, for use outside EU only Nominal efficiency: cooling at 5 /27 nominal load, heating at 7 /20 nominal load 2-8 Capacity and Power input FFQ50C/RXS50L FFQ60C/RXS60L Cooling capacity Min. kw 1.7 Btu/h 5,800 kcal/h 1,460 Nom. kw Btu/h 17,060 19,450 kcal/h 4,00 4,900 Max. kw Btu/h 18,100 22,200 kcal/h 4,560 5,590 Heating capacity Min. kw 1.7 Btu/h 5,800 kcal/h 1,460 Nom. kw Btu/h 19,790 2,900 kcal/h 4,990 6,020 Max. kw Btu/h 20, ,00 kcal/h 5, ,880 Power input Cooling Nom. kw Heating Nom. kw Split - Sky Air RXS-L 9

12 2 Specifications Outdoor Unit RXS-L Capacity and Power input FFQ50C/RXS50L FFQ60C/RXS60L Seasonal efficiency Cooling Energy label A+ (according to Pdesign kw EN14825) SEER Annual energy consumption kwh Heating (Average Energy label A A+ climate) Pdesign kw SCOP Annual energy consumption kwh 1,78 1,7 Piping connections Liquid OD mm 6.5 Gas OD mm 12.7 Drain OD mm VP20 (External dia.26 / Internal dia. 20) Heat insulation Both liquid and gas pipes Current Nominal running Cooling A 7.2 (1) / 6.9 (2) / 6.6 () 8.6 (1) / 8. (2) / 8.0 () current (RLA) - 50Hz Heating A 7.6 (1) / 7. (2) / 7.0 () 9. (1) / 9.0 (2) / 8.7 () Nominal efficiency EER COP Annual energy consumption kwh Energy label Cooling A B Heating B Notes (1) 220V (2) 20V () 240V EER/COP according to Eurovent 2012, for use outside EU only Nominal efficiency: cooling at 5 /27 nominal load, heating at 7 /20 nominal load 2-9 Capacity and Power input FBQ50D/RXS50L FBQ60D/RXS60L Indoor unit FBQ50D FBQ60D Outdoor unit RXS50L RXS60L Cooling capacity Nom. kw 5.0 (1) 5.7 (1) Heating capacity Nom. kw 5.50 (1) 7.00 (1) Power input Cooling Nom. kw 1.42 (1) 1.65 (1) Heating Nom. kw 1.44 (1) 1.89 (1) Seasonal efficiency Cooling Energy label A++ A+ (according to Pdesign kw EN14825) SEER Annual energy consumption kwh Heating (Average Energy label A+ climate) Pdesign kw SCOP Annual energy consumption kwh 1,517 1,606 Nominal efficiency EER.52 (2).45 (2) COP.8 (2).71 (2) Annual energy consumption kwh Energy label Cooling A Heating A Notes (1) Nominal efficiency: cooling at 5 /27 nominal load, heating at 7 /20 nominal load (2) EER/COP according to Eurovent 2012, for use outside EU only 10 Split - Sky Air RXS-L

13 2 Specifications Outdoor Unit RXS-L 2-10 Capacity and Power input FHQ50C/RXS50L FHQ60C/RXS60L Cooling capacity Min. kw 1.7 Btu/h 5,800 kcal/h 1,460 Nom. kw Btu/h 17,060 19,450 kcal/h 4,00 4,900 Max. kw Btu/h 18,100 19,450 kcal/h 4,560 4,900 Heating capacity Min. kw 1.7 Btu/h 5,800 kcal/h 1,460 Nom. kw Btu/h 20,472 24,570 kcal/h 5,160 6,190 Max. kw Btu/h 20,500 24,570 kcal/h 5,160 6,190 Power input Cooling Nom. kw Heating Nom. kw Seasonal efficiency Cooling Energy label A+ (according to Pdesign kw EN14825) SEER Annual energy consumption kwh Heating (Average Energy label A climate) Pdesign kw SCOP Annual energy consumption kwh 1,578 1,705 Piping connections Liquid OD mm 6.5 Gas OD mm 12.7 Drain OD mm VP20 (External dia.26 / Internal dia. 20) Heat insulation Both liquid and gas pipes Current Nominal running Cooling A 7.5 (1) / 7. (2) / 7.0 () 8.1 (1) / 7.8 (2) / 7.5 () current (RLA) - 50Hz Heating A 8. (1) / 8.0 (2) / 7.7 () 9.9 (1) / 9.6 (2) / 9. () Nominal efficiency EER COP.5.2 Annual energy consumption kwh Energy label Cooling B A Heating C 2 Notes (1) 220V (2) 20V () 240V EER/COP according to Eurovent 2012, for use outside EU only Nominal efficiency: cooling at 5 /27 nominal load, heating at 7 /20 nominal load 2-11 Capacity and Power input FNQ50A/RXS50L FNQ60A/RXS60L Cooling capacity Nom. kw Heating capacity Nom. kw Power input Cooling Nom. kw Heating Nom. kw Split - Sky Air RXS-L 11

14 2 Specifications Outdoor Unit RXS-L Capacity and Power input FNQ50A/RXS50L FNQ60A/RXS60L Seasonal efficiency Cooling Energy label A+ A (according to Pdesign kw EN14825) SEER Annual energy consumption kwh Heating (Average Energy label A+ climate) Pdesign kw SCOP Annual energy consumption kwh 1,69 1,548 Nominal efficiency EER.5 (1) 2.68 (1) COP.4 (1).11 (1) Annual energy consumption kwh 746 1,119 Energy label Cooling A D Heating C D Notes (1) EER/COP according to Eurovent 2012, for use outside EU only Nominal efficiency: cooling at 5 /27 nominal load, heating at 7 /20 nominal load 2-12 Technical Specifications RXS42L RXS50L RXS60L Capacity control Method Inverter controlled Casing Colour Ivory white Dimensions Unit Height mm Width mm Depth mm Packed unit Height mm Width mm Depth mm Weight Unit kg Packed unit kg Packing Weight kg 6 - Heat exchanger Length mm Rows Quantity 2 Fin pitch mm Stages Quantity 24 2 Tube type ø8 Hi-XD ø8 Hi-XA Fin Type Precoat Fin Waffle louvered fin Compressor Model 2YC6BXD#C Type Hermetically sealed swing compressor Output W 1,100 Fan Type Propeller fan Air flow rate Cooling High m³/min cfm 1,17 1,797 1,798 Super m³/min low cfm 1,080 1,727 1,589 Heating High m³/min cfm 1,105 1,589 1,65 Super m³/min low cfm 960 1,522 1,65 12 Split - Sky Air RXS-L

15 2 Specifications Outdoor Unit RXS-L 2-12 Technical Specifications RXS42L RXS50L RXS60L Fan motor Model D50R-28 KFD D Output W 50 5 Speed Cooling High rpm Super rpm low Heating High rpm Low rpm Super low rpm Sound power level Cooling dba Heating dba Sound pressure level Cooling High dba Low dba Silent operation dba 44 - Heating High dba Low dba Silent operation dba 45 - Operation range Cooling Ambien Min. CDB -10 t Max. CDB 46 Heating Ambien Min. CWB -15 t Max. CWB 18 Refrigerant Type R-410A Charge kg TCO 2 eq GWP 2,087.5 Refrigerant oil Type FVC50K Charged volume l Piping connections Liquid OD mm Gas OD mm Drain ID mm - OD mm - 18 VP20 (External dia.26 / Internal dia. 20) Piping length OU - IU Max. m - 0 Additional refrigerant charge kg/m (for piping length exceeding 10m) Level difference IU - OU Max. m Heat insulation - Both liquid and gas pipes Electrical Specifications RXS42L RXS50L RXS60L Power supply Name V1 Phase 1~ Frequency Hz 50 Voltage V Current Nominal running Cooling A 5.89 / 5.59 / / 6.18 / current (RLA) Heating A 6.46 / 6.16 / / 6.6 / Starting current Cooling A Heating A Current - 50Hz Maximum fuse amps (MFA) A - Current - 60Hz Maximum fuse amps (MFA) A - Wiring connections For power supply Quantity - For connection with indoor Quantity - 4 Notes 220V 20V 240V Contains fluorinated greenhouse gases Split - Sky Air RXS-L 1

16 Electrical data - 1 Electrical Data Outdoor Unit RXS-L RXS42 60L Unit combination restrictions Indoor Outdoor FTXS42KV1B FTXS50KV1B FFQ50C2VEB FFQ60C2VEB RXS42L2V1B RXS50L2V1B RXS50L2V1B RXS60L2V1B COMP OFM IFM A B C MCA MFA RHz RLA kw FLA kw FLA Power supply MAX. 50Hz 264V 6, MIN. 50Hz 198V , , MAX. 50Hz 264V 6, MIN. 50Hz 198V 15,5 20 6, , MAX. 50Hz 264V 6, MIN. 50Hz 198V 19, , , MAX. 50Hz 264V 8, , ,40 MIN. 50Hz 198V 19, , ,050 0,2 0,02 0, ,05 0,27 0,02 0,15 0,05 0,27 0,050 0,4 0,2 0,050 0,6 Notes 1 The RLA is based on the following conditions. Indoor temperature 27 C DB / 19 C WB Outdoor temperature 5 C DB 2 Select the wire size according to the MCA. The maximum allowable voltage that is unbalanced between phases is 2%. 4 Use a circuit breaker instead of a fuse. A B C MCA MFA RLA Symbols Hz Voltage Voltage range Minimum Circuit Ampere (A) Maximum Fuse Ampere (A) Rated load amps [A] OFM IFM FLA kw RHz Outdoor fan motor Indoor fan motor Full Load Ampere (A) Fan motor rated output [kw] Rated operating frequency [Hz] D Split - Sky Air RXS-L

17 Electrical data - 1 Electrical Data Outdoor Unit RXS-L Split - Sky Air RXS-L 15

18 Electrical data - 1 Electrical Data Outdoor Unit RXS-L 16 Split - Sky Air RXS-L

19 Electrical data - 1 Electrical Data Outdoor Unit RXS-L RXS50 60L Unit combination restrictions Indoor Outdoor COMP OFM IFM 1 2 MCA MFA RHz RLA kw FLA kw FLA Power supply Notes The RLA is based on the following conditions. Indoor temperature 27 C DB / 19 C WB Outdoor temperature 5 C DB Select the wire size according to the MCA. The maximum allowable voltage that is unbalanced between phases is 2%. Use a circuit breaker instead of a fuse. Symbols Hz MCA MFA RLA Voltage Voltage range Minimum Circuit Ampere (A) Maximum Fuse Ampere (A) Rated load amps [A] OFM IFM FLA kw RHz COMP Outdoor fan motor Indoor fan motor Full Load Ampere (A) Fan motor rated output [kw] Rated operating frequency [Hz] Compressor D09486B Split - Sky Air RXS-L 17

20 Electrical data - 1 Electrical Data Outdoor Unit RXS-L RXS50 60L Unit combination restrictions Indoor Outdoor COMP OFM IFM 1 2 MCA MFA RHz RLA kw FLA kw FLA Power supply Notes The RLA is based on the following conditions. Indoor temperature 27 C DB / 19 C WB Outdoor temperature 5 C DB Select the wire size according to the MCA. The maximum allowable voltage that is unbalanced between phases is 2%. Use a circuit breaker instead of a fuse. MCA MFA RLA Symbols Hz Voltage Voltage range Minimum Circuit Ampere (A) Maximum Fuse Ampere (A) Rated load amps [A] OFM IFM FLA kw RHz COMP Outdoor fan motor Indoor fan motor Full Load Ampere (A) Fan motor rated output [kw] Rated operating frequency [Hz] Compressor D09615C 18 Split - Sky Air RXS-L

21 4 Capacity tables 4-1 Cooling/Heating Capacity Tables FTXS42KV1B + RXS42L2V1B Cooling V 50Hz A B AFR 11,2 BF 0, TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 20 14,1 2,50 0,89,1 2,50 1,01,1 2,50 1,14,1 2,50 1,18,1 2,50 1,24,1 2,50 1, ,19 2,89 0,96 4,19 2,89 1,05 4,11 2,85 1,15 4,0 2,81 1,19,91 2,75 1,24,71 2,66 1, ,69,16 0,98 4,49,07 1,06 4,0 2,98 1,16 4,22 2,95 1,20 4,10 2,90 1,25,91 2,81 1, ,79,2 0,98 4,59,2 1,07 4,40,15 1,16 4,2,11 1,20 4,20,06 1,25 4,00 2,98 1, ,08,19 0,99 4,88,12 1,07 4,69,04 1,17 4,61,01 1,21 4,49 2,97 1,26 4,29 2,90 1, ,27,10 0,99 5,07,0 1,08 4,88 2,97 1,18 4,80 2,94 1,21 4,68 2,90 1,26 4,49 2,8 1,6 C 4 Heating V 50Hz AFR 12,4 A TC PI TC PI TC PI TC PI TC PI TC PI 15 2,57 0,84,09 0,89,61 0,9 4,85 1,22 5,59 1,28 6,07 1,2 20 2,41 0,87 2,9 0,91,45 0,95 4,67 1,25 5,40 1,1 5,89 1,5 22 2,5 0,88 2,87 0,92,9 0,96 4,59 1,26 5, 1,2 5,81 1,6 24 2,29 0,89 2,80 0,9,2 0,97 4,52 1,27 5,25 1, 5,74 1,8 25 2,25 0,89 2,77 0,9,29 0,98 4,48 1,27 5,21 1,4 5,65 1,8 27 2,19 0,90 2,71 0,94,2 0,99 4,41 1,29 5,14 1,5 5,2 1,5 D Notes The capacities are based on the following conditions: Corresponding refrigerant piping length: 5.0 m Level difference: 0m The bold cells indicate the standard conditions. Rated operating frequency [Hz] Symbols TC: PI: SHC: AFR: BF: Total capacity [kw] Power input [kw] Sensible heat capacity [kw] Air flow rate [m³/min] Bypass factor A B C D Indoor air temperature [ C DB] Indoor air temperature [ C WB] Outdoor air temperature [ C DB] Outdoor air temperature [ C WB] D Split - Sky Air RXS-L 19

22 4 Capacity tables 4-1 Cooling/Heating Capacity Tables 4 FTXS50KV1B + RXS50L2V1B Cooling V 50Hz A B AFR 11,9 BF 0, TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 20 14,41 2,72 1,05,41 2,72 1,21,41 2,72 1,6,41 2,72 1,42,41 2,72 1,48,41 2,72 1, ,56,14 1,12 4,56,14 1,26 4,56,14 1,8 4,56,14 1,4 4,56,14 1,50 4,42,07 1, ,58,66 1,16 5,5,55 1,28 5,12,45 1,9 5,02,40 1,4 4,88,4 1,51 4,65,24 1, ,70,8 1,17 5,47,72 1,28 5,2,62 1,40 5,14,58 1,44 5,00,52 1,51 4,77,42 1, ,04,68 1,19 5,81,59 1,29 5,58,50 1,41 5,49,46 1,45 5,5,40 1,52 5,11,2 1, ,27,57 1,19 6,04,49 1,0 5,81,40 1,41 5,72,7 1,45 5,58,2 1,5 5,4,24 1,6 C Heating V 50Hz AFR 1, A TC PI TC PI TC PI TC PI TC PI TC PI 15 2,76 0,9,2 0,98,88 1,0 5,21 1,5 6,00 1,42 6,52 1, ,59 0,96,15 1,01,71 1,05 5,01 1,8 5,80 1,45 6,2 1, ,52 0,97,08 1,02,64 1,07 4,9 1,9 5,72 1,46 6,24 1, ,46 0,98,01 1,0,57 1,08 4,85 1,40 5,64 1,48 6,16 1, ,42 0,99 2,98 1,0,54 1,08 4,81 1,41 5,60 1,48 6,12 1,5 27 2,5 1,00 2,91 1,04,47 1,09 4,7 1,42 5,52 1,50 6,04 1,54 D Notes The capacities are based on the following conditions: Corresponding refrigerant piping length: 5.0 m Level difference: 0m The bold cells indicate the standard conditions. Rated operating frequency [Hz] Symbols TC: PI: SHC: AFR: BF: Total capacity [kw] Power input [kw] Sensible heat capacity [kw] Air flow rate [m³/min] Bypass factor A B C D Indoor air temperature [ C DB] Indoor air temperature [ C WB] Outdoor air temperature [ C DB] Outdoor air temperature [ C WB] D Split - Sky Air RXS-L

23 4 Capacity tables 4-1 Cooling/Heating Capacity Tables 4 Split - Sky Air RXS-L 21

24 4 Capacity tables 4-1 Cooling/Heating Capacity Tables 4 22 Split - Sky Air RXS-L

25 4 Capacity tables 4-1 Cooling/Heating Capacity Tables 4 Split - Sky Air RXS-L 2

26 4 Capacity tables 4-1 Cooling/Heating Capacity Tables 4 24 Split - Sky Air RXS-L

27 4 Capacity tables 4-1 Cooling/Heating Capacity Tables 4 Split - Sky Air RXS-L 25

28 4 Capacity tables 4-1 Cooling/Heating Capacity Tables 4 26 Split - Sky Air RXS-L

29 4 Capacity tables 4-1 Cooling/Heating Capacity Tables 4 Split - Sky Air RXS-L 27

30 4 Capacity tables 4-1 Cooling/Heating Capacity Tables 4 28 Split - Sky Air RXS-L

31 4 Capacity tables 4-1 Cooling/Heating Capacity Tables 4 Split - Sky Air RXS-L 29

32 4 Capacity tables 4-1 Cooling/Heating Capacity Tables 4 0 Split - Sky Air RXS-L

33 4 Capacity tables 4-1 Cooling/Heating Capacity Tables 4 Split - Sky Air RXS-L 1

34 4 Capacity tables 4-1 Cooling/Heating Capacity Tables FBQ50D2VEB + RXS50L2V1B 4 Cooling 50Hz V AFR 15,0 BF 0,1 Indoor Outdoor temperature [ C DB] EWB EDB 20,0 25,0 0,0 2,0 5,0 40,0 C C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14,0 20,0 5,12,84 1,09 4,89,72 1,19 4,66,61 1,0 4,56,56 1,4 4,42,49 1,40 4,19,8 1,51 16,0 22,0 5,5,77 1,10 5,12,66 1,20 4,89,55 1,1 4,79,51 1,5 4,65,45 1,41 4,42,4 1,52 18,0 25,0 5,58,95 1,10 5,5,85 1,21 5,12,75 1,1 5,02,71 1,5 4,88,66 1,42 4,65,56 1,52 19,0 27,0 5,70 4,18 1,11 5,47 4,08 1,21 5,2,98 1,2 5,14,94 1,6 5,00,89 1,42 4,77,79 1,52 22,0 0,0 6,04 4,0 1,11 5,81,94 1,22 5,58,86 1,2 5,49,82 1,7 5,5,77 1,4 5,11,69 1,5 24,0 2,0 6,27,92 1,12 6,04,85 1,2 5,81,77 1, 5,72,74 1,7 5,58,69 1,44 5,4,62 1,54 Heating 50Hz V AFR 15,0 Indoor Outdoor temperature [ C WB] EDB 10,0 5,0 0,0 6,0 10,0 C TC PI TC PI TC PI TC PI TC PI 15,0,70 1,22 4,2 1,28 4,94 1,4 5,69 1,41 6,19 1,46 20,0,51 1,25 4,1 1,1 4,75 1,7 5,50 1,44 6,00 1,49 22,0,44 1,26 4,06 1,2 4,68 1,8 5,42 1,45 5,92 1,50 24,0,6 1,28,98 1,4 4,60 1,9 5,5 1,47 5,84 1,51 25,0,2 1,28,94 1,4 4,56 1,40 5,1 1,47 5,81 1,52 27,0,25 1,0,87 1,5 4,49 1,41 5,2 1,49 5,7 1,5 Symbols AFR: Air flow rate [m³/min] BF: Bypass factor EWB: Entering wet bulb temperature ( C WB) EDB: Entering dry bulb temperature ( C DB) TC: Total capacity [kw] SHC: Sensible heat capacity [kw] PI: Power input [kw] Notes 1) The ratings shown are net capacities which include a deduction for indoor fan motor heat. 2) The bold cells indicate the standard conditions. ) The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table (figures not in the table may not be used in the calculation). 4) In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values in direct proportion. 5) The capacities are based on the following conditions: Corresponding refrigerant piping length: 5 m Level difference: 0m 6) The air flow rate and bypass factor are mentioned in the table. D09519A 2 Split - Sky Air RXS-L

35 4 Capacity tables 4-1 Cooling/Heating Capacity Tables FBQ60D2VEB + RXS60L2V1B Cooling 50Hz V 4 AFR 18,0 BF 0,15 Indoor Outdoor temperature [ C DB] EWB EDB 20,0 25,0 0,0 2,0 5,0 40,0 C C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14,0 20,0 5,84 4,42 1,27 5,57 4,28 1,9 5,1 4,16 1,51 5,20 4,10 1,56 5,04 4,0 1,6 4,78,90 1,76 16,0 22,0 6,10 4,4 1,27 5,84 4,22 1,40 5,57 4,09 1,52 5,47 4,05 1,57 5,1,97 1,64 5,04,86 1,76 18,0 25,0 6,6 4,56 1,28 6,10 4,44 1,40 5,8 4, 1,5 5,7 4,29 1,58 5,57 4,22 1,65 5,0 4,11 1,77 19,0 27,0 6,50 4,82 1,29 6,2 4,71 1,41 5,97 4,60 1,5 5,86 4,56 1,58 5,70 4,49 1,65 5,4 4,9 1,77 22,0 0,0 6,89 4,65 1,0 6,62 4,55 1,42 6,6 4,46 1,54 6,25 4,42 1,59 6,09 4,6 1,66 5,8 4,27 1,79 24,0 2,0 7,15 4,5 1,0 6,89 4,44 1,4 6,62 4,6 1,55 6,52 4,2 1,60 6,6 4,27 1,67 6,09 4,18 1,79 Heating 50Hz V AFR 18,0 Indoor Outdoor temperature [ C WB] EDB 10,0 5,0 0,0 6,0 10,0 C TC PI TC PI TC PI TC PI TC PI 15,0 4,71 1,60 5,50 1,67 6,29 1,75 7,24 1,84 7,87 1,91 20,0 4,47 1,64 5,26 1,72 6,05 1,79 7,00 1,89 7,6 1,95 22,0 4,7 1,66 5,16 1,7 5,95 1,81 6,90 1,90 7,54 1,97 24,0 4,28 1,67 5,07 1,75 5,86 1,8 6,81 1,92 7,44 1,98 25,0 4,2 1,68 5,02 1,76 5,81 1,84 6,76 1,9 7,9 1,99 27,0 4,1 1,70 4,92 1,78 5,71 1,85 6,66 1,95 7,29 2,01 Symbols AFR: Air flow rate [m³/min] BF: Bypass factor EWB: Entering wet bulb temperature ( C WB) EDB: Entering dry bulb temperature ( C DB) TC: Total capacity [kw] SHC: Sensible heat capacity [kw] PI: Power input [kw] Notes 1) The ratings shown are net capacities which include a deduction for indoor fan motor heat. 2) The bold cells indicate the standard conditions. ) The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table (figures not in the table may not be used in the calculation). 4) In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values in direct proportion. 5) The capacities are based on the following conditions: Corresponding refrigerant piping length: 5 m Level difference: 0m 6) The air flow rate and bypass factor are mentioned in the table. D095140B Split - Sky Air RXS-L

36 4 Capacity tables 4-1 Cooling/Heating Capacity Tables FNQ50A2VEB + RXS50L2V1B 4 Cooling 50Hz 20V AFR 16,0 BF 0,12 Indoor Outdoor temperature [ C DB] EWB EDB 20,0 25,0 0,0 2,0 5,0 40,0 C C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14,0 20,0 5,12,94 1,15 4,89,8 1,26 4,66,71 1,7 4,56,67 1,41 4,42,60 1,48 4,19,49 1,59 16,0 22,0 5,5,87 1,15 5,12,77 1,26 4,89,66 1,7 4,79,62 1,42 4,65,56 1,48 4,42,45 1,59 18,0 25,0 5,58 4,08 1,16 5,5,98 1,27 5,12,88 1,8 5,02,84 1,42 4,88,78 1,49 4,65,69 1,60 19,0 27,0 5,70 4,2 1,16 5,47 4,22 1,27 5,2 4,1 1,8 5,14 4,09 1,4 5,00 4,04 1,49 4,77,94 1,60 22,0 0,0 6,04 4,17 1,17 5,81 4,09 1,28 5,58 4,00 1,9 5,49,97 1,44 5,5,92 1,50 5,11,84 1,61 24,0 2,0 6,27 4,07 1,18 6,04,99 1,29 5,81,92 1,40 5,72,89 1,44 5,58,84 1,51 5,4,77 1,62 Heating 50Hz 20V AFR 16,0 Indoor Outdoor temperature [ C WB] EDB 10,0 5,0 0,0 6,0 10,0 C TC PI TC PI TC PI TC PI TC PI 15,0,90 1,47 4,56 1,54 5,21 1,61 6,00 1,70 6,52 1,76 20,0,70 1,51 4,6 1,58 5,01 1,65 5,80 1,74 6,2 1,79 22,0,62 1,52 4,28 1,60 4,9 1,67 5,72 1,75 6,24 1,81 24,0,54 1,54 4,20 1,61 4,85 1,68 5,64 1,77 6,16 1,8 25,0,50 1,55 4,16 1,62 4,81 1,69 5,60 1,78 6,12 1,8 27,0,42 1,56 4,08 1,6 4,7 1,71 5,52 1,79 6,04 1,85 Symbols AFR: Air flow rate [m³/min] BF: Bypass factor EWB: Entering wet bulb temperature ( C WB) EDB: Entering dry bulb temperature ( C DB) TC: Total capacity [kw] SHC: Sensible heat capacity [kw] PI: Power input [kw] Notes 1) The ratings shown are net capacities which include a deduction for indoor fan motor heat. 2) The bold cells indicate the standard conditions. ) The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table (figures not in the table may not be used in the calculation). 4) In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values in direct proportion. 5) The capacities are based on the following conditions: Corresponding refrigerant piping length: 7 m Level difference: 0m 6) The air flow rate and bypass factor are mentioned in the table. D Split - Sky Air RXS-L

37 4 Capacity tables 4-1 Cooling/Heating Capacity Tables FNQ60A2VEB + RXS60L2V1B Cooling 50Hz 20V 4 AFR 16,0 BF 0,12 Indoor Outdoor temperature [ C DB] EWB EDB 20,0 25,0 0,0 2,0 5,0 40,0 C C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14,0 20,0 5,78 4,27 1,72 5,78 4,27 1,88 5,59 4,17 2,05 5,48 4,11 2,11 5,1 4,0 2,21,58,21 2,08 16,0 22,0 6,42 4,8 1,7 6,14 4,24 1,89 5,86 4,11 2,06 5,75 4,06 2,12 5,59,98 2,22,78,17 2,08 18,0 25,0 6,70 4,57 1,74 6,42 4,44 1,90 6,14 4,2 2,07 6,0 4,27 2,1 5,86 4,20 2,2,97,41 2,08 19,0 27,0 6,84 4,80 1,74 6,56 4,68 1,91 6,28 4,56 2,07 6,17 4,51 2,14 6,00 4,44 2,24 4,07,67 2,08 22,0 0,0 7,25 4,62 1,76 6,97 4,52 1,92 6,69 4,41 2,09 6,58 4,7 2,15 6,41 4,1 2,25 4,5,58 2,08 24,0 2,0 7,5 4,50 1,77 7,25 4,40 1,9 6,97 4,0 2,10 6,86 4,26 2,16 6,69 4,21 2,26 4,54,52 2,08 Heating 50Hz 20V AFR 16,0 Indoor Outdoor temperature [ C WB] EDB 10,0 5,0 0,0 6,0 10,0 C TC PI TC PI TC PI TC PI TC PI 15,0 4,71 1,90 5,50 2,00 6,29 2,09 7,24 2,20 7,87 2,27 20,0 4,47 1,95 5,26 2,05 6,05 2,14 7,00 2,25 7,6 2, 22,0 4,7 1,97 5,16 2,07 5,95 2,16 6,90 2,27 7,54 2,5 24,0 4,28 1,99 5,07 2,09 5,86 2,18 6,81 2,29 7,44 2,7 25,0 4,2 2,01 5,02 2,10 5,81 2,19 6,76 2,0 7,9 2,8 27,0 4,1 2,0 4,92 2,12 5,71 2,21 6,66 2,2 7,29 2,40 Symbols AFR: Air flow rate [m³/min] BF: Bypass factor EWB: Entering wet bulb temperature ( C WB) EDB: Entering dry bulb temperature ( C DB) TC: Total capacity [kw] SHC: Sensible heat capacity [kw] PI: Power input [kw] Notes 1) The ratings shown are net capacities which include a deduction for indoor fan motor heat. 2) The bold cells indicate the standard conditions. ) The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table (figures not in the table may not be used in the calculation). 4) In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values in direct proportion. 5) The capacities are based on the following conditions: Corresponding refrigerant piping length: 7 m Level difference: 0m 6) The air flow rate and bypass factor are mentioned in the table. D09657 Split - Sky Air RXS-L 5

38 5 Dimensional drawings 5-1 Dimensional Drawings 5 6 Split - Sky Air RXS-L

39 6 Centre of gravity 6-1 Centre of Gravity Outdoor Unit RXS-L 6 Split - Sky Air RXS-L 7

40 7 Piping diagrams 7-1 Piping Diagrams Outdoor Unit RXS-L 7 8 Split - Sky Air RXS-L

41 8 Wiring diagrams 8-1 Wiring Diagrams - Single Phase 8 Split - Sky Air RXS-L 9

42 9 Sound data 9-1 Sound Pressure Spectrum - Cooling 9 40 Split - Sky Air RXS-L

43 9 Sound data 9-1 Sound Pressure Spectrum - Cooling 9 Split - Sky Air RXS-L 41

44 9 Sound data 9-2 Sound Pressure Spectrum - Heating 9 42 Split - Sky Air RXS-L

45 9 Sound data 9-2 Sound Pressure Spectrum - Heating 9 Split - Sky Air RXS-L 4

46 10 Operation range 10-1 Operation Range Outdoor Unit RXS-L Split - Sky Air RXS-L

47 Daikin Europe N.V. participates in the Eurovent Certification programme for Liquid Chilling Packages (LCP), Air handling units (AHU), Fan coil units (FCU) and variable refrigerant flow systems (VRF) Check ongoing validity of certificate online: or using: The present leaflet is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this leaflet to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this leaflet. All content is copyrighted by Daikin Europe N.V. BARCODE Daikin products are distributed by: Naamloze Vennootschap - Zandvoordestraat 00, B-8400 Oostende - Belgium BE RPR Oostende EEDEN /15 Copyright Daikin The present publication supersedes EEDEN14-100

technical data air conditioning systems Outdoor Units RKS-F3V1B RKS-FAV1B

technical data air conditioning systems Outdoor Units RKS-F3V1B RKS-FAV1B technical data Outdoor Units RKS-F3V1B RKS-FAV1B air conditioning systems technical data Outdoor Units RKS-F3V1B RKS-FAV1B air conditioning systems Outdoor Units R-410A RKS-F3V1B_RKS-FAV1B TABLE OF CONTENTS

More information

Air Conditioners. Technical Data. Pair application EEDEN RXS-J

Air Conditioners. Technical Data. Pair application EEDEN RXS-J Air Conditioners Technical Data Pair application EEDEN11-100 RXS-J Air Conditioners Technical Data Pair application EEDEN11-100 RXS-J TABLE OF CONTENTS RXS-J 1 Features.............................................................

More information

technical data air conditioning systems RKS-F2V1B Split Sky Air

technical data air conditioning systems RKS-F2V1B Split Sky Air technical data RKS-F2VB air conditioning systems Split Sky Air Split - Sky Air The present publication is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe

More information

INDOOR UNITS FVXS25F FVXS35F FVXS50 F

INDOOR UNITS FVXS25F FVXS35F FVXS50 F Cooling Only INDOOR UNITS FVXS25F FVXS35F FVXS50 F Capacity cooling min~nom~max kw 1.3~2.5~3.0 1.4~3.5~3.8 1.4~5.0~5.6 Power input cooling min~nom~max kw 0.300~0.570~0.920 0.300~1.020~1.250 0.310~1.220~1.880

More information

MHWW-09-H-1 Chilled/Hot Water Hi-Wall Fan Coil. Heat / Cool Fan Coil 9,000 BTUH. Rev. 1.3

MHWW-09-H-1 Chilled/Hot Water Hi-Wall Fan Coil. Heat / Cool Fan Coil 9,000 BTUH. Rev. 1.3 MHWW-09-H-1 Chilled/Hot Water Hi-Wall Fan Coil Heat / Cool Fan Coil 9,000 BTUH Rev. 1.3 HVAC Guide Specifications Chilled and Hot Water Hi-Wall Fan Coil 2-Pipe Nominal Size: 9,000 BTUH Multiaqua Model

More information

CFFWA-20-1-U Chilled/Hot Water Universal Mount Fan Coil 2-Pipe Heat / Cool Fan Coil 60,000 BTUH

CFFWA-20-1-U Chilled/Hot Water Universal Mount Fan Coil 2-Pipe Heat / Cool Fan Coil 60,000 BTUH CFFWA-20-1-U Chilled/Hot Water Universal Mount Fan Coil 2-Pipe Heat / Cool Fan Coil 60,000 BTUH Rev. 1.3 HVAC Guide Specifications Chilled and Hot Water Universal Mount Fan Coil 2-Pipe Nominal Size: 60,000

More information

Learn more about Samsung air conditioner at:

Learn more about Samsung air conditioner at: 2014 SAMSUNG New Ducted Air-Conditioner Learn more about Samsung air conditioner at: www.samsung.com/global/business/system-air-conditioner CONTENTS Smart Cooling - Global Top Efficiency - Powerful Cooling

More information

Product Catalog. Variable Refrigerant Flow (VRF) System VRF-PRC008C-EN. Air Source Heat Pump and Heat Recovery Outdoor Units.

Product Catalog. Variable Refrigerant Flow (VRF) System VRF-PRC008C-EN. Air Source Heat Pump and Heat Recovery Outdoor Units. Product Catalog Variable Refrigerant Flow (VRF) System Air Source Heat Pump and Heat Recovery Outdoor Units 4TVH/4TVR0072 0192 4TVH/4TVR0216 0528 Single Unit Modules Multi-Unit Modules January 2016 VRF-PRC008C-EN

More information

Product Data. 38AUZ / 38AUD 60 Hz Air Cooled Condensing Unit Puronr (R---410A) Refrigerant 6to20NominalTons FEATURES / BENEFITS

Product Data. 38AUZ / 38AUD 60 Hz Air Cooled Condensing Unit Puronr (R---410A) Refrigerant 6to20NominalTons FEATURES / BENEFITS Z / D 60 Hz Air Cooled Condensing Unit Puronr (R---410A) Refrigerant 6to20NominalTons Product Data FEATURES / BENEFITS Z07-14 shown C09227 the environmentally sound refrigerant Carrier s air-cooled air

More information

01 Introduction TARGET. Multi Domestic. Commercial. 50, High Efficiency - High Efficiency Operation - Hot water with free of charge (HR)

01 Introduction TARGET. Multi Domestic. Commercial. 50, High Efficiency - High Efficiency Operation - Hot water with free of charge (HR) 01 Introduction TARGET POSITION FEATRE Multi Domestic EHS Mono/Split Low Temperature - Domestic, 50 water EHS High Temperature - Domestic, 80 water All-in-One More Efficient Free of Charge 50 or 80 Water

More information

ACTIVA Rooftop. YKN2open. ARC-ARG-ARH-ARD A complete range from 48 kw up to 84 kw. Nomenclature A R C 045 B B. Features

ACTIVA Rooftop. YKN2open. ARC-ARG-ARH-ARD A complete range from 48 kw up to 84 kw. Nomenclature A R C 045 B B. Features ACTIVA Rooftop ARC-ARG-ARH-ARD A complete range from 48 kw up to 84 kw YKN2open Features High efficiency EER and COP Low noise level All configurations: Cooling only, Cooling + gas, Heating, Heating +

More information

Product Data. 38AUZ Air Cooled Condensing Unit Puronr (R---410A) Refrigerant 6to12.5NominalTons FEATURES/BENEFITS. Factory-installed options (FIOPs)

Product Data. 38AUZ Air Cooled Condensing Unit Puronr (R---410A) Refrigerant 6to12.5NominalTons FEATURES/BENEFITS. Factory-installed options (FIOPs) 38AUZ Air Cooled Condensing Unit Puronr (R---410A) Refrigerant 6to12.5NominalTons Product Data Carrier s air-cooled air conditioning split systems: S provide a logical solution for commercial needs S have

More information

EFFICIENT 13 SEER 3 PHASE AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT. Nominal Btu/hr. Min. Circuit Ampacity 18.

EFFICIENT 13 SEER 3 PHASE AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT. Nominal Btu/hr. Min. Circuit Ampacity 18. ENVIRONMENTALLY SOUND REFRIGERANT H4A3 Product Specifications EFFICIENT 13 SEER 3 PHASE AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT 3 THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 3 phase, 60 Hz

More information

Product Data. (Unit shown with optional economizer.)

Product Data. (Unit shown with optional economizer.) COOLING ONLY/ELECTRIC HEAT PACKAGED ROOFTOP UNIT 15 TO 27.5 NOMINAL TONS Product Data (Unit shown with optional economizer.) C09316 Use of the AHRI Certified TM Mark indicates a manufacturer s participation

More information

Product Data. 50TC Cooling Only/Electric Heat Packaged Rooftop 15 to 25 Nominal Tons. (Unit shown with optional economizer.

Product Data. 50TC Cooling Only/Electric Heat Packaged Rooftop 15 to 25 Nominal Tons. (Unit shown with optional economizer. Cooling Only/Electric Heat Packaged Rooftop 15 to 25 Nominal Tons Product Data (Unit shown with optional economizer.) C09262 the environmentally sound refrigerant This product has been designed and manufactured

More information

Product Catalog. Variable Refrigerant Flow (VRF) Air Source Heat Pump and Heat Recovery Outdoor Units 4TVH*/4TVR* VRF-PRC008B-EN.

Product Catalog. Variable Refrigerant Flow (VRF) Air Source Heat Pump and Heat Recovery Outdoor Units 4TVH*/4TVR* VRF-PRC008B-EN. Product Catalog Variable Refrigerant Flow (VRF) ir Source Heat Pump and Heat Recovery Outdoor Units 4TVH*/4TVR* February 2015 VRF-PRC008B-EN Introduction Copyright Trane VRF variable refrigerant systems

More information

4DHP MULTI-ZONE PRODUCT SPECIFICATIONS OUTDOOR UNITS INDOOR UNITS 4DHP MULTI-ZONE DWM WALL MOUNTED CEILING CASSETTE DUCTED UNIT

4DHP MULTI-ZONE PRODUCT SPECIFICATIONS OUTDOOR UNITS INDOOR UNITS 4DHP MULTI-ZONE DWM WALL MOUNTED CEILING CASSETTE DUCTED UNIT DHP MULTI-ZONE PRODUCT SPECIFICATIONS UP TO SEER UP TO DUCTLESS HEAT PUMP SYSTEMS UNITS FORM NO. DHPMULTI-00 (0/07) DHP MULTI-ZONE 8K / 0K / 6K / 8K Mid Efficiency (- SEER) Matches with all indoor units

More information

WATER CHILLER / HEAT PUMP. The high performance packaged solutions for all your needs

WATER CHILLER / HEAT PUMP. The high performance packaged solutions for all your needs WATER CHILLER / HEAT PUMP Aquaciat / Aquaciat Power The high performance packaged solutions for all your needs The Aquaciat Range: the versatile way to sustainable comfort Available in air-cooled chiller

More information

Air-cooled Chillers with High Speed Centrifugal Compressors

Air-cooled Chillers with High Speed Centrifugal Compressors Air-cooled Chillers with High Speed Centrifugal Compressors Model -X 575-1600 kw Model -XP 720-1250 kw Model -XPG 450-1250 kw 1 Trane Sintesis excellent Air-cooled Chillers with High Speed Centrifugal

More information

Product catalogue A25s. Solar Cooling systems

Product catalogue A25s. Solar Cooling systems Product catalogue A25s Solar Cooling systems COOLING POWERED BY NATURE FLEXIBLE DESIGN The Purix Solar Cooling system helps you building a green tomorrow without compromising the basic needs for a comfortable

More information

An Integrated Solution for Commercial AC Chillers Using Variable Speed Scroll Compressors

An Integrated Solution for Commercial AC Chillers Using Variable Speed Scroll Compressors Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 An Integrated Solution for Commercial AC Chillers Using Variable Speed

More information

MV Product Specifications

MV Product Specifications MODULAR VARIABLE SPEED BLOWER CABINET 2, 3, 4, and 5 TONS FEATURES Variable Speed modular blower Supports two-stage outdoor units Dehumidification Speed: 80% Airflow Efficient low continuous fan selection:

More information

Air Cooled Packaged Air Conditioning

Air Cooled Packaged Air Conditioning Cooling Capacity 11.6kW - 193.0kW Heating Capacity 10.8kW - 213.0kW eco series Packaged Air Conditioning Giving you complete control More than just another air conditioning company. temperzone is dedicated

More information

Daikin AURORA SINGLE ZONE HEATING & COOLING SYSTEMS WALL MOUNTED UNITS Up to 20 SEER / 12.5 HSPF / 13 EER INVERTER, VARIABLE SPEED COMPRESSOR

Daikin AURORA SINGLE ZONE HEATING & COOLING SYSTEMS WALL MOUNTED UNITS Up to 20 SEER / 12.5 HSPF / 13 EER INVERTER, VARIABLE SPEED COMPRESSOR Daikin AURORA SINGLE ZONE HEATING & COOLING SYSTEMS WALL MOUNTED UNITS Up to 20 SEER / 12.5 HSPF / 13 EER INVERTER, VARIABLE SPEED COMPRESSOR Today, the air is perfect. Perfect temperature. Perfect humidity.

More information

Product Specifications

Product Specifications Product Specifications Models Unit Cooling Capacity kw 0.30~2.63~3.80 0.30~3.51~4.04 Btu/h. 1,023~9,000~12,966 1,023~12,000~13,785 Heating Capacity kw 0.30~3.22~6.50 0.30~3.98~6.50 Btu/h. 1,023~11,000~20,472

More information

Product Specifications

Product Specifications Product Specifications MODULAR ELECTRIC FURNACE 2, 3,4,and5TONS FEATURES S Modular Blower Cabinet, Air Conditioning or Heat Pump ready S Upflow, horizontal right or left applications S Downflow requires

More information

Eurovent certification programmes for HVAC products with verified performances

Eurovent certification programmes for HVAC products with verified performances Eurovent certification programmes for HVAC products with verified performances Rehva Annual Conference 2015 8 May 2015, Riga, Latvia Sylvain Courtey s.courtey@eurovent-certification.com 6 reference certification

More information

AVPTC. Multi-Position, Variable-Speed, ECM-Based Air Handler with Internal TXV ComfortNet Compatible 1½ to 5 Tons. Contents.

AVPTC. Multi-Position, Variable-Speed, ECM-Based Air Handler with Internal TXV ComfortNet Compatible 1½ to 5 Tons. Contents. Multi-Position, Variable-Speed, ECM-Based Air Handler with Internal TXV ComfortNet Compatible 1½ to 5 Tons Contents Air Handler Nomenclature... 2 Heater Kit Nomenclature... 2 Product Specifications...

More information

50KC Cooling Only/Electric Heat Packaged Rooftop 14 SEER 3to5NominalTons. Product Data C08613

50KC Cooling Only/Electric Heat Packaged Rooftop 14 SEER 3to5NominalTons. Product Data C08613 Cooling Only/Electric Heat Packaged Rooftop 14 SEER 3to5NominalTons Product Data C08613 TABLE OF CONTENTS PAGE FEATURES AND BENEFITS... 3 MODEL NUMBER NOMENCLATURE... 4 FACTORY OPTIONS & ACCESSORIES...

More information

VRF 50/60Hz V5 E Series

VRF 50/60Hz V5 E Series 1702-1V1701 VRF 50/60Hz V5 E Series Coercial Air Conditioners 2017/2018 VRF 50/60Hz V5 E Series Coercial Air Conditioner Division Midea Group Add.: Midea Headquarters Building, 6 Midea Avenue, Shunde,

More information

START-UP CHECKLIST. Date: Job Name: Customer Name: Address: City: State: Zip: Model Number: Serial Number: Qualified Start-up Technician:

START-UP CHECKLIST. Date: Job Name: Customer Name: Address: City: State: Zip: Model Number: Serial Number: Qualified Start-up Technician: START-UP INSTRUCTION SERIES 20 J**YC/YD 90000 To 300000 BTU S SPLIT SYSTEM CONDENSING UNITS 7.5 To 25 TON START-UP CHECKLIST Date: _ Job Name: Customer Name: Address: City: State: Zip: Model Number: Serial

More information

MIRAI SMI. Monobloc heat pump for Heating and Cooling Residential environments with plant management system integrated in the heat pump

MIRAI SMI. Monobloc heat pump for Heating and Cooling Residential environments with plant management system integrated in the heat pump MIRAI SMI Monobloc heat pump for Heating and Cooling Residential environments with plant management system integrated in the heat pump Air conditioning Technical sheet 20C GB02 Indice Monobloc heat pump

More information

DVPTC. Multi-Position, Variable-Speed, ECM-Based Air Handler with Internal TXV ComfortNet Compatible 2 to 5 Tons

DVPTC. Multi-Position, Variable-Speed, ECM-Based Air Handler with Internal TXV ComfortNet Compatible 2 to 5 Tons DVPTC Multi-Position, Variable-Speed, ECM-Based Air Handler with Internal TXV ComfortNet Compatible 2 to 5 Tons Contents Air Handler Nomenclature...2 Heater Kit Nomenclature...2 Product Specifications...3

More information

Cabinet Features Heavy-gauge, galvanizedsteel. powder-paint finish Full perimeter rail Sloped drain pan Easy to service

Cabinet Features Heavy-gauge, galvanizedsteel. powder-paint finish Full perimeter rail Sloped drain pan Easy to service DG ommercial 7½- TO ½-TON THREE-PHASE PAKAGED GAS/ ELETRI UP TO. EER / 80% AUE ooling apacity: 88,000,000 BTU/h Heating apacity (Output): 68,000 BTU/h ontents Nomenclature... Product Specifications...

More information

AIR CONDTIONERS XC16. ELITE Series R-410A - Two-Stage Compressor - SilentComfort Technology

AIR CONDTIONERS XC16. ELITE Series R-410A - Two-Stage Compressor - SilentComfort Technology AIR CONDTIONERS XC16 ELITE Series R-410A - Two-Stage Compressor - SilentComfort Technology E N G I N E E R I N G D ATA Bulletin 210465 October 2009 Supersedes March 2009 SEER up to 17.20 2 to 5 Tons Cooling

More information

AK SERIES (50Hz) ROOM AIR CONDITIONER AKY9FBSSW AKY9UBSSW. Models :

AK SERIES (50Hz) ROOM AIR CONDITIONER AKY9FBSSW AKY9UBSSW. Models : ROOM AIR CONDITIONER AK SERIES (50Hz) Models : AKY9FBSSW AKY9UBSSW CONTENTS SPECIFICATIONS.......................... CIRCUIT DIAGRAM........................ MICROCOMPUTER CONTROL CIRCUIT...... DISASSEMBLY

More information

Daikin AURORA MULTI-ZONE HEATING & COOLING SYSTEMS

Daikin AURORA MULTI-ZONE HEATING & COOLING SYSTEMS Daikin AURORA MULTI-ZONE HEATING & COOLING SYSTEMS 1.5 & 2 TON, 2 & 3 ZONE SYSTEMS Up to 17.9 SEER / 12.5 HSPF / 12.7 EER INVERTER, VARIABLE SPEED COMPRESSOR Flexible options providing high efficiency

More information

indoor air quality and energy saving TECHNICAL DATA FAI-ED H/V VENTILATION UNIT WITH HEAT RECOVERY FOR COMMERCIAL AND INDUSTRIAL BUILDINGS

indoor air quality and energy saving TECHNICAL DATA FAI-ED H/V VENTILATION UNIT WITH HEAT RECOVERY FOR COMMERCIAL AND INDUSTRIAL BUILDINGS indoor air quality and energy saving TECHNICAL DATA FAI-ED H/V VENTILATION UNIT WITH HEAT RECOVERY FOR COMMERCIAL AND INDUSTRIAL BUILDINGS FAI-ED Is a Non Residential Ventilation Unit (NRVU) EQUIPPED Equipped

More information

2010 Standard for Performance Rating of Variable Refrigerant Flow (VRF) Multi-Split Air-Conditioning and Heat Pump Equipment

2010 Standard for Performance Rating of Variable Refrigerant Flow (VRF) Multi-Split Air-Conditioning and Heat Pump Equipment ANSI/AHRI Standard 1230 with Addendum 2 2010 Standard for Performance Rating of Variable Refrigerant Flow (VRF) Multi-Split Air-Conditioning and Heat Pump Equipment Approved by ANSI on 2 August 2010 ANSI/AHRI

More information

Product Data. 48TC Gas Heat/Electric Cooling Packaged Rooftop 15 to 25 Nominal Tons. (Unit shown with optional economizer.) C09248

Product Data. 48TC Gas Heat/Electric Cooling Packaged Rooftop 15 to 25 Nominal Tons. (Unit shown with optional economizer.) C09248 Gas Heat/Electric Cooling Packaged Rooftop 15 to 25 Nominal Tons Product Data (Unit shown with optional economizer.) C09248 the environmentally sound refrigerant This product has been designed and manufactured

More information

MPE 4-76 kw. Outdoor packaged unit. Air/water chillers and heat pumps MPE. Efficiency under all operating conditions. 152 galletti.

MPE 4-76 kw. Outdoor packaged unit. Air/water chillers and heat pumps MPE. Efficiency under all operating conditions. 152 galletti. Air/water chillers and heat pumps MPE Outdoor packaged unit MPE - kw Efficiency under all operating conditions Rotary compressor Plus Scroll compressor R-0A R-0A refrigerant Cooling only Cooling / Heating

More information

New ADVANCED HYPER TROPICAL SPEC WINDOW. A new model realizes the high performance and energy saving which are more suitable for tropical climate.

New ADVANCED HYPER TROPICAL SPEC WINDOW. A new model realizes the high performance and energy saving which are more suitable for tropical climate. DVNCED HYPER TROPICL SPEC new model realizes the high performance and energy saving which are more suitable for tropical climate. New XGS18BTH / PTH / QTH XGS4BTH / PTH / QTH WINDOW High ambient 60 C operation

More information

RL SERIES. Two Stage Light Oil Burners FIRING RATES LIGHT OIL

RL SERIES. Two Stage Light Oil Burners FIRING RATES LIGHT OIL The RL series of burners covers a firing range from 154 to 2700 kw, and it has been designed for use in low or medium temperature hot water boilers, hot air or steam boilers, diathermic oil boilers. Operation

More information

NZEB: The new challenge of HVAC Manufacturers. ASTRO Tower (Archi Urbain)

NZEB: The new challenge of HVAC Manufacturers. ASTRO Tower (Archi Urbain) NZEB: The new challenge of HVAC Manufacturers ASTRO Tower (Archi Urbain) Who are we? 35 production sites units compressors refrigerants chillers Who are we? Daughter company (100%) of Daikin Europe Specialised

More information

Water-Cooled Screw Chillers and Water/Water Heat Pumps

Water-Cooled Screw Chillers and Water/Water Heat Pumps Water-Cooled Screw Chillers and Water/Water Heat Pumps Model RTWF (R134a) 940-1860 kw Model RTWF G (R1234ze) 735-1420 kw Model RTHF (R134a) 1120-3180 kw 1 Trane XStream Water-Cooled Chillers and Water/Water

More information

Air Source Heat Pumps in the Commercial Market. Thursday, February 5, :00-10:30 a.m.

Air Source Heat Pumps in the Commercial Market. Thursday, February 5, :00-10:30 a.m. Air Source Heat Pumps in the Commercial Market Thursday, February 5, 2015 9:00-10:30 a.m. 1. Commercial Equipment Applications, Benefits, Limitations 2. Case Studies 3. Efficiency Vermont Technical & Financial

More information

FRAUNHOFER INSTITUTE FOR SOLAR ENERGY SYSTEMS ISE

FRAUNHOFER INSTITUTE FOR SOLAR ENERGY SYSTEMS ISE FRAUNHOFER INSTITUTE FOR SOLAR ENERGY SYSTEMS ISE New performance requirements on conventional climatisation systems or: Know your enemy! Jochen Döll Fraunhofer Institute for Solar Energy Systems ISE IEA

More information

ASPT Series. Multi-Position, Multi-Speed, ECM-Based Air Handler with Internal TXV 1½ to 5 Tons. Contents. Product Features

ASPT Series. Multi-Position, Multi-Speed, ECM-Based Air Handler with Internal TXV 1½ to 5 Tons. Contents. Product Features Series Multi-Position, Multi-Speed, ECM-Based Air Handler with Internal TXV ½ to Tons Contents Air Handler Nomenclature... Heater Kit Nomenclature... Product Specifications... Dimensions... Airflow Data...

More information

Hybrid heating. system. Heat pump. combi boiler. Smart logic

Hybrid heating. system. Heat pump. combi boiler. Smart logic Hybrid heating system Gas combi boiler Heat pump Smart logic Daikin Altherma Hybrid heating system A hybrid gas boiler solution for efficient heating & hot water Daikin Altherma Hybrid system is the ideal

More information

GLAC BD2. Lufttechnik. GEA Heat Exchangers / HVAC Systems

GLAC BD2. Lufttechnik. GEA Heat Exchangers / HVAC Systems Energieeffizient, Energy efficient, kompakt compact, und and variantenreich versatile GLAC0524- - 1204BD2 Luftgekühlte Air cooled Kaltwassererzeuger Chiller Data Daten && Facts Fakten Lufttechnik GEA Heat

More information

ELECTRICITY OUTPUT THERMAL OUTPUT ELECTRIC EFFICIENCY THERMAL EFFICIENCY TOTAL EFFICIENCY

ELECTRICITY OUTPUT THERMAL OUTPUT ELECTRIC EFFICIENCY THERMAL EFFICIENCY TOTAL EFFICIENCY CHP Technical Data Sheet for T200 Natural Gas Indoor Canopy Cento Series Standard Features High performance electrical efficiency Fully modulating output 3 packages Open frame, Indoor Canopy, Outdoor Container

More information

120 Series Refrigeration Systems

120 Series Refrigeration Systems 120 Series Refrigeration Systems RDI Systems Air Cooled Indoor/Outdoor Condensing Units Hermetic / Scroll / Semi-Hermetic ½ thru 6 Hp s PC Refrigeration Systems The RDI PC Refrigeration system includes

More information

CI/SfB (57.7) 1st edition

CI/SfB (57.7) 1st edition CI/SfB (57.7) 1st edition Vent-Axia Sentinel Multivent Wholehouse Mechanical Extract Ventilation System Ventilation Lo-Carbon Energy saving solutions Sentinel Multivent continuous mechanical extract ventilation,

More information

Energy labelling and ecodesign requirements for heat pumps

Energy labelling and ecodesign requirements for heat pumps Prepared for the Danish Energy Agency by Pia Rasmussen, Danish Technological Institute 31 December 2011 Energy labelling and ecodesign requirements for heat pumps The following document describes adopted

More information

EHPA suggestion We thus suggest to integrate waste heat recovery into the aligned test standards.

EHPA suggestion We thus suggest to integrate waste heat recovery into the aligned test standards. EHPA review of the documents on possible requirements for air heating, cooling products and high temperature process chillers (Ecodesign ENTR Lot 6 / ENER Lot 21) EHPA, as the representative of the European

More information

St. Monica Food Pantry Testing, Adjusting, & Balancing for HVAC sys-tek No

St. Monica Food Pantry Testing, Adjusting, & Balancing for HVAC sys-tek No St. Monica Food Pantry 23 0593-1 HVAC WORK DIVISION 23 SECTION 230593 TESTING, ADJUSTING, & BALANCING FOR HVAC PART 1. GENERAL 1.1 DESCRIPTION OF WORK A. Air balancing of dedicated outside air systems

More information

ECODESIGN PREPARATORY STUDY FOR AIR-CONDITIONING AND VENTILATION SYSTEMS ENTR LOT 6

ECODESIGN PREPARATORY STUDY FOR AIR-CONDITIONING AND VENTILATION SYSTEMS ENTR LOT 6 ECODESIGN PREPARATORY STUDY FOR AIR-CONDITIONING AND VENTILATION SYSTEMS ENTR LOT 6 EPEE comments on the draft final preparatory study April 2012 Dear Mr Rivière, [Cc = Mr Biermann, Mr Kemna, Mrs Lichtenvort]

More information

B. System Design and Performance Requirements

B. System Design and Performance Requirements 15625 Water Chillers This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes

More information

Heat pumps. Oilon ChillHeat. Optimized cooling and heating performance

Heat pumps. Oilon ChillHeat. Optimized cooling and heating performance Heat pumps Oilon ChillHeat Optimized cooling and heating performance Affordable, environmentally friendly energy with heat pumps Low-temperature waste heat contains valuable energy Communities, industry,

More information

Air Cooled Condensing Units - Technical Catalog. Featuring Bitzer TM Compressors 404A and 507 Refrigerants

Air Cooled Condensing Units - Technical Catalog. Featuring Bitzer TM Compressors 404A and 507 Refrigerants N SERIES Air Cooled Condensing Units - Technical Catalog Featuring Bitzer TM s 404A and 507 Refrigerants 4492 Hunt St - Pryor, OK 74361-918.825.7222 - Fax 800.264.5329 - www.century-refrigeration.com Standard

More information

Performance Efficiency Standard for Evaporative Cooling Equipment

Performance Efficiency Standard for Evaporative Cooling Equipment Industry Recommendation / Code of Good Practice 9/12-2016 Performance Efficiency Standard for Evaporative Cooling Equipment First Edition Published on 11 October 2016 by,,, Belgium - The European Committee

More information

135 Prime Emissions level: EPA NSPS Stationary Emergency Tier 3

135 Prime Emissions level: EPA NSPS Stationary Emergency Tier 3 Generator set data sheet Model: Frequency: Fuel type: kw rating: DQGAC 60 Hz Diesel 150 Standby 135 Prime Emissions level: EPA NSPS Stationary Emergency Tier 3 Exhaust emission data sheet: Exhaust emission

More information

COOLING TECHNOLOGY INSTITUTE

COOLING TECHNOLOGY INSTITUTE PAPER NO: TP08-16 CATEGORY: DRY COOLING COOLING TECHNOLOGY INSTITUTE THE COST OF NOISE ROBERT GIAMMARUTI HUDSON PRODUCTS CORPORATION JESS SEAWELL COMPOSITE COOLING SOLUTIONS, LLC The studies and conclusions

More information

LSA 47.2 Low Voltage Alternators - 4 pole

LSA 47.2 Low Voltage Alternators - 4 pole LSA 47.2 36 to 6 kva - Hz / 46 to 7 kva - 6 Hz Electrical and mechanical data LSA 47.2-36 to 6 kva - Hz / 46 to 7 kva - 6 Hz Specially adapted to applications The LSA 47.2 alternator is designed to be

More information

Generator set data sheet. 410 Prime Emissions level: EPA Nonroad Tier 1. Fuel consumption. Engine Standby rating Prime rating Continuous rating

Generator set data sheet. 410 Prime Emissions level: EPA Nonroad Tier 1. Fuel consumption. Engine Standby rating Prime rating Continuous rating Generator set data sheet Model: Frequency: Fuel type: kw rating: DGDB 60 Hz Diesel 100 Standby 410 Prime Emissions level: EPA Nonroad Tier 1 Exhaust emission data sheet: Exhaust emission compliance sheet:

More information

Light commercial rooftop units Retail applications

Light commercial rooftop units Retail applications Light commercial rooftop units Retail applications Less to install. Less to maintain. Less to operate. installations and retrofits. Unit efficiency surpasses EER minimum by 12%. Precedent high-efficiency

More information

ANK. ANK heat pump All the heat you want more efficiency more savings more well-being

ANK. ANK heat pump All the heat you want more efficiency more savings more well-being ANK Please fill out the requested information Aermec adheres to the EUROVENT Certification Programme: LCP/A/P/R The products concerned appear in the EUROVENT web site www. eurovent-certification. com ANK

More information

Design and development of a residential gas-fired heat pump

Design and development of a residential gas-fired heat pump Design and development of a residential gas-fired heat pump Edward A Vineyard a*, Ahmad Abu-Heiba a, Isaac Mahderekal b a Oak Ridge National Laboratory, P.O. Box 2008, MS 6070, Oak Ridge, TN, 37831, USA

More information

Lubricated Rotary Screw Air Compressors. Constant Speed Drives and Variable Speed Drives kw hp

Lubricated Rotary Screw Air Compressors. Constant Speed Drives and Variable Speed Drives kw hp Lubricated Rotary Screw Air Compressors Constant Speed Drives and Variable Speed Drives 18 30 kw 25 40 hp About Sullair For more than 50 years, Sullair has been on the leading edge of compressed air solutions.

More information

TYP. SINGLE PLY ROOFING ROOF SHEETING BROAN VENT CAP #10 x 1" GASKETED SMS TYP. 4 SIDES 8" FRAMED CURB HVAC SYSTEMS "BASIS OF DESIGN" ROOF INSULATION R-19 WALL INSULATION R-13 LIGHTING EFFIECNCY PER STANDARDS

More information

YORK YVAA AIR-COOLED SCREW CHILLER. A chiller as unique as your needs.

YORK YVAA AIR-COOLED SCREW CHILLER. A chiller as unique as your needs. YORK YVAA AIR-COOLED SCREW CHILLER A chiller as unique as your needs. Efficiency Sustainability Low Sound Confidence YORK YVAA Air-Cooled VSD Screw Chillers Introducing YVAA Smart, sustainable, silent

More information

Industrial heat pumps and cooling machines Oilon ChillHeat. Optimized heating and cooling performance

Industrial heat pumps and cooling machines Oilon ChillHeat. Optimized heating and cooling performance Industrial heat pumps and cooling machines Oilon ChillHeat Optimized heating and cooling performance Affordable and environmentally friendly energy with heat pumps Low-temperature waste heat contains valuable

More information

Sullair Water Chillers. Precision Chilled Water

Sullair Water Chillers. Precision Chilled Water Sullair Water Chillers Precision Chilled Water Sullair Water Chillers What are Water Chillers? Why Choose a Sullair Water Chiller? Water chillers are used for controlled cooling of products, mechanisms

More information

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1 Air System Design Load Summary for Zona 11 DESIGN COOLING DESIGN HEATING COOLING DATA AT Dec 1700 HEATING DATA AT DES HTG COOLING OA DB / WB 33.1 C / 23.5 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible

More information

Unit Coolers SKB. 4 kw 30,5 kw.

Unit Coolers SKB. 4 kw 30,5 kw. Unit Coolers SKB 4 kw 30,5 kw www.friga-bohn.com SKB range unit coolers are suitable for chilling or low temperature storage applications. 24 basic models with capacities ranging from 4 to 30.5 kw. NOMENCLATURE...

More information

Reference System & Cost Competiveness

Reference System & Cost Competiveness Reference System & Cost Competiveness Daniel Neyer University of Innsbruck Institute of Structural Engineering and Material Sciences Working Group: Energy Efficient Buildings Folie: 1 Content Introduction

More information

Innovative Solutions from Mitsubishi Electric

Innovative Solutions from Mitsubishi Electric Innovative Solutions from Mitsubishi Electric Paul Doppel Senior Director, Industry & Government Relations MITSUBISHI ELECTRIC Cooling & Heating 34 Years of Leadership Providing Unique Solutions for the

More information

VENTILATION AIR CONDITIONING AIR CLEANING HEATING

VENTILATION AIR CONDITIONING AIR CLEANING HEATING Heat Recovery Units VENTILATION AIR CONDITIONING AIR CLEANING HEATING Cross flow heat recovery units Applications New Designed for energy saving and indoor air quality control within ventilation systems.

More information

Attachment 1: RAE Corporation Technical Specification

Attachment 1: RAE Corporation Technical Specification Attachment 1: RAE Corporation Technical Specification RAE Corporation Phone: 918-825-7222, ext. 105 Steve Corbin Quote# XXXX Qty Customer Tag Technical Systems Model Number 1 ACC-4 10A0-162-S General Scope

More information

RDI Systems. Scroll Series Refrigeration System. Air Cooled Indoor/Outdoor Scroll Condensing Units 3/4 thru 6 Hp Models

RDI Systems. Scroll Series Refrigeration System. Air Cooled Indoor/Outdoor Scroll Condensing Units 3/4 thru 6 Hp Models RDI Systems Scroll Series Refrigeration System Air Cooled Indoor/Outdoor Scroll Condensing Units 3/4 thru 6 Hp Models PC Refrigeration Systems The RDI PC Refrigeration system includes an RDI condensing

More information

Mechanical Product Overview

Mechanical Product Overview Mechanical Product Overview The founding principles of Price have never changed business integrity, first class service, innovation and a commitment to people. PURPOSE BUILT FOR YOUR APPLICATION Whether

More information

VARIABLE REFRIGERANT FLOW MULTI-SPLIT AIR-CONDITIONERS AND HEAT PUMPS CERTIFICATION PROGRAM

VARIABLE REFRIGERANT FLOW MULTI-SPLIT AIR-CONDITIONERS AND HEAT PUMPS CERTIFICATION PROGRAM VARIABLE REFRIGERANT FLOW MULTI-SPLIT AIR-CONDITIONERS AND HEAT PUMPS CERTIFICATION PROGRAM VRF OM JANUARY 2018 2111 Wilson Boulevard, Suite 500 Arlington, Virginia 22201 (703) 524-8800 Sponsored and administered

More information

MUZ-GE09NAH MUZ-GE09NAH2 MUZ-GE12NAH MUZ-GE12NAH2 MUZ-GE15NAH MUZ-GE15NAH2 MUZ-GE18NAH MUY-GE18NA, - 1 MUY-GE24NA

MUZ-GE09NAH MUZ-GE09NAH2 MUZ-GE12NAH MUZ-GE12NAH2 MUZ-GE15NAH MUZ-GE15NAH2 MUZ-GE18NAH MUY-GE18NA, - 1 MUY-GE24NA SPLIT-TYPE AIR CONDITIONERS Revision F: MUZ-GE//5, MUZ-GE//5NAH and MUY-GE//5 have been added. Please void OBB549 REVISED EDITION-E. OUTDOOR UNIT PARTS CATALOG No. OBB549 REVISED EDITION-F Models MUZ-GENA

More information

AERONA 3 HEAT PUMP RANGE. Inverter driven air source heat pumps with outputs from 6kW to 16kW

AERONA 3 HEAT PUMP RANGE. Inverter driven air source heat pumps with outputs from 6kW to 16kW AERONA 3 HEAT PUMP RANGE Inverter driven air source heat pumps with outputs from 6kW to 16kW Grant Profile At Grant we have been designing and manufacturing reliable and easy to install heating products

More information

PRODUCT LAUNCH KIT. Assembled in USA

PRODUCT LAUNCH KIT. Assembled in USA PRODUCT LAUNCH KIT Assembled in USA PRODUCT LAUNCH KIT Assembled in USA CONTENTS: 1. Copy of Bulletin 2. Summary of Equipment Assembled in USA 3. Information on Assembled in USA 4. Ordering Process 5.

More information

MEMORANDUM. The Massachusetts and Rhode Island Program Administrators (PAs) commissioned Cadmus and its

MEMORANDUM. The Massachusetts and Rhode Island Program Administrators (PAs) commissioned Cadmus and its MEMORANDUM To: Massachusetts and Rhode Island Program Administrators From: COOL SMART Impact Evaluation Team Subject: Ductless Mini Split Heat Pump (DMSHP) Draft Cooling Season Results Date: April 27,

More information

Influence of dry cooler capacity on chiller efficiency

Influence of dry cooler capacity on chiller efficiency Influence of dry cooler capacity on chiller efficiency CHILLVENTA, Nurnberg 9 October 2012 Sandrine MARINHAS 2/22 Oct 2012 Influence of dry cooler capacity on chiller efficiency Overview Introduction:

More information

Large University Central Chiller Plant Design Considerations

Large University Central Chiller Plant Design Considerations Carrier Engineering Newsletter Volume 5, Issue 3 Large University Central Chiller Plant Design Considerations Large campus chilled water plants have unique constraints and need careful evaluation for successful

More information

Installation Instructions

Installation Instructions Installation Instructions AquaSnap 010-055 Chilled Water Storage Tank 50/60 Hz Part No: -900---001; -900---009; -900---010 CONTENTS INTRODUCTION.................................. 1 SAFETY CONSIDERATIONS......................

More information

ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS

ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS ANSI/ASHRAE STANDARD 200-2015, METHODS OF TESTING CHILLED BEAMS NEMIC 2017 Agenda 1. Foreword 2. Purpose & Scope 3. Definitions 4. Instrumentation & Facilities 5. Test Methods 6. Reporting 7. Normative

More information

LG HVAC SOLUTION 2017

LG HVAC SOLUTION 2017 LG HVAC SOLUTION 2017 INDEX WHY LG MULTI V 5 06 08 10 12 14 22 26 / COMPANY INTRODUCTION / ENGINEERING CAPABILITY / LG CONTROL SOLUTION / MULTI V BRAND HISTORY / 5 KEY FACTS ABOUT MULTI V 5 / BENEFITS

More information

Changes to the Minnesota Commercial Energy Code. Presented by: Andy Thielen, PE

Changes to the Minnesota Commercial Energy Code. Presented by: Andy Thielen, PE Changes to the Minnesota Commercial Energy Code Presented by: Andy Thielen, PE Warning! The following is an outline of proposed code changes. There is no guarantee that the final code adopted by the State

More information

Roof top. NEW SPACE Zen attitude NA O8.16B

Roof top. NEW SPACE Zen attitude NA O8.16B u n i v e r s a l c o m f o r t Roof top NEW SPACE Zen attitude NA O8.16B sustainable development CIAT - YOUR EXPERT IN SUSTAINABLE SOLUTIONS CIAT is an expert in environmentally sound solutions that use

More information

Installation plan. Tumble dryer. PT 8807 EL (Electrically heated) en - US Mat. NR / 02

Installation plan. Tumble dryer. PT 8807 EL (Electrically heated) en - US Mat. NR / 02 Installation plan Tumble dryer PT 8807 EL (Electrically heated) 38.15 en - US Mat. NR. 09 883 210 / 02 U.S.A. Miele, Inc. National Headquarters 9 Independence Way Princeton, NJ 08540 Phone: Fax: 800-991-9380

More information

Pressure Booster System. Hya-Eco VP. Type Series Booklet

Pressure Booster System. Hya-Eco VP. Type Series Booklet Pressure Booster System Hya-Eco VP Type Series Booklet Legal information/copyright Type Series Booklet Hya-Eco VP KSB Aktiengesellschaft Frankenthal All rights reserved. Contents provided herein must neither

More information

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1 Air System Design Load Summary for Zona 3 Project Name: Av. Cabildo 3067, 4 piso 02/13/2011 DESIGN COOLING DESIGN HEATING COOLING DATA AT Feb 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 34.9 C / 23.8

More information

ELECTRICITY OUTPUT THERMAL OUTPUT ELECTRIC EFFICIENCY THERMAL EFFICIENCY TOTAL EFFICIENCY

ELECTRICITY OUTPUT THERMAL OUTPUT ELECTRIC EFFICIENCY THERMAL EFFICIENCY TOTAL EFFICIENCY CHP Technical Data Sheet for T200 Natural Gas Containerised Cento Series Standard Features High performance electrical efficiency Fully modulating output 3 packages Open frame, Indoor Canopy, Outdoor Container

More information

SWIMMING POOL HEATING CLIMEXEL LISTEN TO THE SILENCE... APPRECIATE THE PERFORMANCE... S ERIES HEAT/COOL PUMPS. P ool & Spa Equipment

SWIMMING POOL HEATING CLIMEXEL LISTEN TO THE SILENCE... APPRECIATE THE PERFORMANCE... S ERIES HEAT/COOL PUMPS. P ool & Spa Equipment SWIMMING POOL HEATING CLIMEXEL LISTEN TO THE SILENCE... APPRECIATE THE PERFORMANCE... S ERIES PROCOPI S INDUSTRIAL STRENGTH Procopi, a leading French manufacturer of pool and spa equipment, has joined

More information

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1 Air System Design Load Summary for Zona 8 DESIGN COOLING DESIGN HEATING COOLING DATA AT Dec 1700 HEATING DATA AT DES HTG COOLING OA DB / WB 33.1 C / 23.5 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible Latent

More information

york yvwa variable-speed, water-cooled, screw chillers Infinite chiller configurations to help you achieve your goals

york yvwa variable-speed, water-cooled, screw chillers Infinite chiller configurations to help you achieve your goals york yvwa variable-speed, water-cooled, screw chillers Infinite chiller configurations to help you achieve your goals Efficiency Flexibility Sustainability Confidence YORK YVWA variable-speed, water-cooled,

More information