1.0 EXECUTIVE SUMMARY:
|
|
- Mark Cannon
- 6 years ago
- Views:
Transcription
1 1.0 EXECUTIVE SUMMARY: ASHRAE Standard was used to evaluate the required outdoor air requirement for The Jack S. Blanton Museum of Art in. This report outlines that the museum does meet ASRAE Standard To evaluate the standard some assumptions had to be made for space criteria that were not designated in ASHRAE Standard 62.89, these assumption are outline in Section 3.0. Using the multiple space equation outlined in Section 4.0, the critical fraction of outdoor air for the building was found to be for a conference room space. The required amount of outdoor air calculated for the building is approximately 83, 840 CFM. The amount of fresh air being brought into the building is approximately 90, 000 CFM. This indicates that the museum does meet the ventilation standard for acceptable air quality. ASHRAE Standard 62: Report Page 1 of 7 11/13/2002
2 2.0 BUILDING DATA: 2.1 Building Base Information The Jack S. Blanton Museum of Art is a 135, 000 sq. ft. facility mostly consisting of art gallery space. The museum also includes educational space, office space, preparation space for exhibits and conservation laboratory. The building has been divided into sections that best represent the type and use of spaces within the building. The divisions are defined in Figure 2.1. For example, all of the art galleries are grouped under the section Gallery Space. The supporting calculations for the assignment are done with respect to the sections. The sections also represent differences in air flow and space conditions within the building. The building sections with respect to area are represented in Figure 2.2. Space Divisions Division Definition A Public Area Public spaces in the building B Gallery Space Art display areas in the building C Prints & Drawings Gallery Space Art space specifically for prints D Education Classroom spaces in the building E Prints & Drawings Area Storage and prep areas, museum curators and curators offices F Preparation Area Preparation and shops for building of exhibits in the museum G Collection Area Collection Storage H Conservation Area Space for restoration and conservation of art work I Support Services Support for the building Building Area Distribution 3,998 2,107 2, ,772 1, ,738 Public Area Gallery Space Prints & Draw ings Gallery Space Education Prints & Draw ing Area Preparation Area Collection Area Conservation Area 36,709 Support Services Figure 2.2 Building Area Distribution according to section ASHRAE Standard 62: Report Page 2 of 7 11/13/2002
3 2.2 Building Air System The mechanical system for the museum features one large air handling unit which feeds all spaces. The air is fed to each space through a dual duct system. Zone humidification is also present in the air system. All calculations are done with respect to the one large air handling unit. ASHRAE Standard 62: Report Page 3 of 7 11/13/2002
4 3.0 ANALYSIS The following section discusses the analysis used to evaluate the building for ASHRAE Standard All supporting calculations and spreadsheets are located in Appendix A. 3.1 Assumptions ASHRAE does not offer occupancy values and outdoor air requirements specific for art museums. As a result, an assumption had to perform design calculations. The assumptions made are based on past experience with art museums at a previous summer internship. The assumptions made for the assignment are outlined below Occupancy Assumptions The following occupancy assumptions were made for calculation purposes: Gallery spaces: 50 sq.ft./person Lobby spaces 50 sq.ft./person Collection Storage: 200 sq.ft/person Prep and Shop area: 100 sq.ft./person Conservation area: 100 sq.ft./person Fresh Air Requirement Assumptions The following ventilation rate assumptions were made for calculation purposes: Gallery spaces: 15 CFM/person Lobby spaces: 15 CFM/person Collection Storage: 20 CFM/person Prep and Shop area: 15 CFM/person Conservation area: 15 CFM/person Classroom: 50 CFM/person Note: the classroom is designed in the format of a conference room and could be used as a conference room, so the value of the conference room was used for calculations 3.2 Calculation of Outdoor Air Requirement The outdoor air requirement for the building was calculated using a series of spreadsheets to perform the analysis. The space characteristics are defined in Table 1, Appendix A. The table is organized by division within the museum to represent what activities occur in each section. The space characteristics define a space within the building, the use of the space, the space area and the design occupancy for each space. Next, the amount of outdoor air required for the space was calculated using the recommendations given in ASHRAE Standard The supply air for each space was ASHRAE Standard 62: Report Page 4 of 7 11/13/2002
5 also calculated. The fraction of outdoor air required to supply air can now be calculated as Z (Eq. 1). Z = V oc /V sc (Eq. 1) V oc = the outdoor flow rate required V sc = supply flow rate in the critical space When the value of Z has been caculated, the highest Z defines the critical space or Z c. Table 2, Appendix A summarizes supply air flow, required outdoor air flow, and Z for each space. Table 3, Appendix A lists a summary of the airflow required for each space within the building. The resulting Z c for the building was calculated as for Study Room in the building. The study room is a small conference room where the museum curators can meet to discuss information about specific pieces of art work. Knowing Z c the corrected outdoor air flow rate can be calculated using the multiple spaces equation (Eq 2) found in ASHRAE Standard Y = X/{1 + X Z] (Eq. 2) X = uncorrected fraction of outdoor air in the system supply Z = the fraction of outdoor air in the critical space The supporting calculations for the multiple spaces equation can be found in Table 4, Appendix A. The resulting value for the corrected outdoor air flow rate was 83,840 CFM. The outdoor flow rate for the building is 90, 000 CFM. The building does meet ASHRAE Standard because the outdoor air brought into the building (90, 000 CFM) is greater than the required amount of outdoor air for the building, (83,840 CFM). ASHRAE Standard 62: Report Page 5 of 7 11/13/2002
6 4.0 DISCUSSION: The Ventilation Rate Procedure was used to determine the amount of fresh air required for the museum. The Ventilation Rate Procedure is driven by calculating the required the adjusted fraction of outdoor air required for the building. The Ventilation Rate procedure was used for the design of the museum by the MEP engineer. Another method than can be used to determine interior space conditions is the Indoor Air Quality Procedure. The indoor air quality procedure is based on measuring the indoor air quality in the space through sensors. The sensors communicate through a controls sequence to the air handling system. The sensor signal indicates when more fresh air is needed for a particular space. The use of the Indoor Air Quality Procedure can also have a higher first cost. The additional sensors required are expensive and also require an elaborate controls sequence. With an elaborate controls sequence, it will also require a knowledgeable facilities team to operate the system. The Indoor Air Quality Procedure will not work correctly if the facilities team does not understand how to properly operate and maintain the system. Due to the strict tolerances needed for gallery spaces, the Indoor Air Quality Procedure would not be likely to be used. The air system in a museum needs to operate smoothly as to not have large fluctuations in the space conditions. The low tolerances guarantee that the gallery controls are tighter. Therefore, the use of the ventilation rate procedure produces a more accurate result for the case of an art museum. ASHRAE Standard 62: Report Page 6 of 7 11/13/2002
7 5.0 REFERENCES: 1. ASHRAE Standard 62.89, Ventilation for Acceptable Indoor Air Quality 2. Ove, Arup & Partners, Project design documents and assumptions for calculation of gallery spaces ASHRAE Standard 62: Report Page 7 of 7 11/13/2002
Outdoor Airflow Control Fixed point and DCV. Presented by: David S. Dougan, President EBTRON
Outdoor Airflow Control Fixed point and DCV Presented by: David S. Dougan, President EBTRON OUTSIDE AIR Pressure Changes Damper Issues Intake Flow Rates (Fixed Min or DCV) OUTSIDE AIR Intake Flow Rate
More informationTechnical Assignment #1. ASHRAE Standard Ventilation Compliance Evaluation Report
Technical Assignment #1 ASHRAE Standard 62.1-2004 Ventilation Compliance Evaluation Report Photo by Fred Martin Clemson University Advanced Material Research Laboratory Anderson, SC David Anderson Mechanical
More informationImplementing Demand Controlled Ventilation to Meet ASHRAE Standard By KlasC. Haglid, P.E., R.A., CEM
Implementing Demand Controlled Ventilation to Meet ASHRAE Standard 62.1-2010 By KlasC. Haglid, P.E., R.A., CEM 1 Klas C. Haglid, P.E., R.A., CEM - Bio ASHRAE Distinguished Service Award 2011 ASHRAE Handbook,
More informationASHRAE Standard 62.1 Ventilation Report
Mechanical Technical Report 1 ASHRAE Standard 62.1 Ventilation Report The nue New York, NY 10022 Faculty Advisor: Dr. Jelena Srebric October 5, 2005-1 - Table of Contents 1.0 Executive Summary 2.0 Building
More informationASHRAE Standard Ventilation Compliance Evaluation Mechanical Technical Report #1. Bronx School for Law, Government, & Justice Bronx, NY
ASHRAE Standard 62.1 2004 Ventilation Compliance Evaluation Mechanical Technical Report #1 Bronx, NY Prepared By: Yulien Wong Faculty Advisor: Dr. Jelena Srebric October 4, 2005 TABLE OF CONTENTS 1.0 EXECUTIVE
More informationVentilation. Demand-controlled ventilation (DCV) Demand-Controlled. With ASHRAE Standard Based
CO Demand-Controlled 2 -Based Ventilation With ASHRAE Standard 62.1 Though not as straightforward as it once was, remains a practical way to reduce costs Editor s note: Following is an update of the November
More informationDEA Clandestine Laboratory Training Center Quantico Marine Corps Base, Quantico, VA
Student: David M. Potchak Mechanical Option Faculty Consultant: Jae-Weon Jeong October 5, 2006 DEA Clandestine Laboratory Training Center Quantico Marine Corps Base, Quantico, VA Mechanical Technical Report
More informationMechanical Technical Assignment One ASHRAE Standard Compliance Evaluation
Mechanical Technical Assignment One ASHRAE Standard 62.1-2007 Compliance Evaluation The Prepared By: Maxwell S. Chien October 5 th, 2007 Prepared For: Dr. William P. Bahnfleth, Ph.D., P.E., Professor Department
More informationChapter 6. Space heating load
Chapter 6 Space heating load 1 Outdoor Design Conditions Heating systems should provide just enough heat to match the heat loss from the structure. Local knowledge should be obtained for design conditions.
More informationThe Palestra Building London, England
Architectural Renderings compliments of Alsop Architects Ventilation Report Becca Allen The Pennsylvania State University Architectural Engineering AE 481W, Fall 2005 Table of Contents I. Executive Summary
More informationFreetown Elementary School
Building and Plant Energy Analysis Technical Report 2 Freetown Elementary School Glen Burnie, MD Matthew R. Buda The Pennsylvania State University Architectural Engineering Mechanical Option Advisor: Dr.
More informationnewsletter The significance of 62n
engineers volume 33 1 newsletter providing insights for today s hvac system designer Addendum 62n breathes new life into ASHRAE Standard 62 PRECIS Addendum 62n revises the entire Ventilation Rate Procedure,
More informationASHRAE Standard : Ventilation Rate Procedure
engineers newsletter live Course Outline ASHE Standard 62.1-2004: Ventilation Rate Procedure This presentation covers the Ventilation Rate Procedure for calculating zone and system ventilation airflow,
More informationYou Can t Afford Discomfort. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas
You Can t Afford Discomfort Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Where We Are Today: So You Want To Save Money? Things to consider: 1. First Cost 2. Energy cost 3. Occupant Salary costs
More informationMeeting the Variable Needs of Energy- Efficient Mechanical Ventilation When and Where You Need It
Meeting the Variable Needs of Energy- Efficient Mechanical Ventilation When and Where You Need It Charles Withers Jr. 1 Introduction Effectively providing mechanical ventilation in commercial buildings
More informationASHRAE STANDARD 62.1 VENTILATION COMPLIANCE
HEALTHCARE CENTER VERONA, PENNSYLVANIA TECHNICAL ASSIGNMENT I ASHRAE STANDARD 62.1 VENTILATION COMPLIANCE Prepared by Tyler Lobb October 2, 2007 The Pennsylvania State University Department of Architectural
More informationCompliance Evaluation: ASHRAE Standard Ventilation for Acceptable Indoor Air Quality
Compliance Evaluation: ASHRAE Standard 62.1-2001 Ventilation for Acceptable Indoor Air Quality Photo rendering courtesy of Hooper Shiles Architects Philadelphia School District Administration Headquarters
More informationSeminar 4 Energy Performance of Active Chilled Beam Installations
Paul Christy Superintendent Clark County Public Schools paul.christy@clark.kyschools.us Seminar 4 Energy Performance of Active Chilled Beam Installations Successful Application of Chilled Beams in a High
More informationOff-Peak Building Control Considerations Utilizing CO 2 Based Demand-Controlled Ventilation (DCV) with Large Packaged Rooftop Units
Off-Peak Building Control Considerations Utilizing CO 2 Based Demand-Controlled Ventilation (DCV) with Large Packaged Rooftop Units By: Bill Timmons Mark Tozzi Carrier Corporation Syracuse, New York September,
More informationTechnical Report #1 ASHRAE Standard 62: Ventilation Compliance Evaluation
Mechanical Option Technical Report #1 Technical Report #1 ASHRAE Standard 62: Ventilation Compliance Evaluation Instructor: Dr. Srebric 10.06.04 Building Sponsors: CCG Facilities Integration Table of Contents
More informationASHRAE 62.2: What s New in 2016
ASHRAE 62.2: What s New in 2016 Rick Karg 2016 Residential Energy Dynamics, LLC What We Will Talk About Overview of mechanics of 62.2-2016. Logic behind the Standard. Sizing local ventilation (exhaust-only).
More informationNew Science & Technology Center The Chestnut Hill Academy
New Science & Technology Center The Chestnut Hill Academy Philadelphia PA Philadelphia, Technical Report 1: ASHRAE Standard 62.1 Ventilation and Standard 90.1 Energy Design Evaluations September p 29,
More informationDISPLACEMENT VENTILATION
DISPLACEMENT VENTILATION D3 OVERVIEW The fundamental approach to displacement ventilation utilizes the natural buoyancy forces created by the convective flows from heat sources in the space. As supply
More informationTechnical Report Two: Building and Plant Energy Analysis Report
The American Swedish Institute Minneapolis, MN Technical Report Two: Building and Plant Energy Analysis Report Name: Option: Mechanical Advisor: Stephen Treado Date: 10.19.11 Table of Contents Executive
More informationDynamic Reset for Multiple-Zone Systems
This article was published in ASHRAE Journal, March 2010. Copyright 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not be
More informationDepth: Mechanical Redesign
Depth: Mechanical Redesign Redesign Objectives The most important objective of the mechanical redesign is to provide Greenbriar East with ventilation that meets the requirements of ASHRAE Standard 62-2001.
More informationASHRAE Region VI CRC Track III: Session 1 Ventilation & IAQ Fundamentals. Steven T. Taylor, PE Principal Taylor Engineering
ASHRAE Region VI CRC Track III: Session 1 Ventilation & IAQ Fundamentals Steven T. Taylor, PE Principal Taylor Engineering This program is registered with the AIA/CES for continuing professional education.
More informationExecutive Summary 2 o Introduction o System Summary o Mechanical Design Goals 3. Passive Mechanical Solutions 4 o Building Envelope 4
Submission Category: Mechanical Systems Date: 23 January Content The requirements of a typical elementary school, in conjunction with the socioeconomic conditions of the Reading school district necessitated
More informationOptiNet Applications. A Healthier, More Energy Efficient Approach to Demand Control Ventilation. White Paper Series
OptiNet Applications A Healthier, More Energy Efficient Approach to Demand Control Ventilation White Paper Series A Healthier, More Energy Efficient Approach to Demand Control Ventilation Conventional
More informationA MODEL-BASED METHOD FOR THE INTEGRATION OF NATURAL VENTILATION IN INDOOR CLIMATE SYSTEMS OPERATION
Ninth International IBPSA Conference Montréal, Canada August 15-18, 2005 A MODEL-BASED METHOD FOR THE INTEGRATION OF NATURAL VENTILATION IN INDOOR CLIMATE SYSTEMS OPERATION Ardeshir Mahdavi and Claus Pröglhöf
More informationSample Reports. for. HAP v4.90 Example Problem
Sample Reports for HAP v4.90 Example Problem December, 2014 Carrier Software Systems Copyright 2014 Carrier Corporation, All Rights Reserved Introduction This document contains reports generated using
More informationJanuary 20, Mr. Marty Foutch Facilities Director Bixby Public Schools 109 N. Armstrong Bixby, OK 74008
January 0, 0 Mr. Marty Foutch Facilities Director Bixby Public Schools 09 N. Armstrong Bixby, OK 0 RE: Bixby th, th, and 6 th Elementary Indoor Air Quality CO and % Liberty OHM File Number 0-09 Dear Mr.
More informationBuilding Load and Energy Estimates Analysis. Instructor: Dr. Mumma. October 28, Thesis Building Sponsor s: INOVA Fairfax Hospital
David Peterson Penn State AE, Mechanical INOVA Fairfax Hospital The INOVA Heart Institute David J. Peterson Mechanical Option Mechanical Technical Report #2b The INOVA HEART INSTITUTE AT INOVA Fairfax
More information1 Exam Prep Manual J Residential Load Calculation 8 th Edition Tabs and Highlights
1 Exam Prep Manual J Residential Load Calculation 8 th Edition Tabs and Highlights These 1 Exam Prep tabs are based on the Manual J Residential Load Calculation for Small Commercial Buildings, 8 th Edition.
More informationAN INNOVATIVE DEDICATED OUTDOOR AIR APPLICATION FOR A GOVERNMENT OFFICE TOWER. MICHAEL HALLENBECK, PE, CEM Southland Industries
AN INNOVATIVE DEDICATED OUTDOOR AIR APPLICATION FOR A GOVERNMENT OFFICE TOWER MICHAEL HALLENBECK, PE, CEM Southland Industries BRAC 133 OVERVIEW PROJECT OVERVIEW FAN POWERED INDUCTION UNIT CENTRAL UTILITY
More informationOccupancy-Based Control of Indoor Air Ventilation: A Theoretical and Experimental Study
ScienceAsia 27 (2001) : 279-284 Occupancy-Based Control of Indoor Air Ventilation: A Theoretical and Experimental Study T Leephakpreeda*, R Thitipatanapong, T Grittiyachot, V Yungchareon School of Industrial
More informationMEMORIAL SLOAN-KETTERING CANCER CENTER
MEMORIAL SLOAN-KETTERING CANCER CENTER SENIOR THESIS PRESENTATION THE PENNSLYVANIA STATE UNIVERSITY DEPARTMENT OF ARCHITECTURAL ENGINEERING PRESENTATION OUTLINE INTRODUCTION BUILDING DESCRIPTION EXISTING
More informationDavid S. Dougan, President Leonard A. Damiano, V.P. Sales & Marketing. EBTRON, Inc.
David S. Dougan, President Leonard A. Damiano, V.P. Sales & Marketing EBTRON, Inc. It should be clear to the design professional that the dynamic nature of mechanical ventilation requires dynamic control.
More informationASHRAE 62.2: What s New in 2016
ASHRAE 62.2: What s New in 2016 Rick Karg 2018 Residential Energy Dynamics, LLC What We Will Talk About Overview of mechanics of 62.2-2016. Logic behind the Standard. Sizing local ventilation (exhaust-only).
More informationMechanical Project Proposal. Indoor Multi-Sport Facility. At Pennsylvania State University
At Pennsylvania State University Christopher Van Campen December 05, 2002 Executive summary The proposed thesis is to alleviate the of its only major problem, not enough seating capacity for the spectators
More informationIndoor Air Quality (IAQ) Requirements
University of New Hampshire University of New Hampshire Scholars' Repository Division 01 General Requirements Chapter 5 Technical Construction and Renovation Standards 1-25-2013 013560 - Indoor Air Quality
More informationSURNA Grow Facility: Systems Comparison - IEA
SURNA Grow Facility: Systems Comparison - IEA May 2016 SURNA Grow Facility This analysis provides the projected energy and associated cost comparison between the Surna proposed facility in comparison to
More informationEnergy Savings Audit
Energy Savings Audit PREPARED FOR Steve Bennett Eileen Horn City of Lawrence ASSESSMENT SITE City of Lawrence Arts Center 940 new Hampshire St. Lawrence, KS 66044 ASSESSMENT PERFORMED BY P1 Group Inc 16210
More informationTechnology and Engineering Development (TED) Building. ASHRAE Std and Std Compliance Report
Technology and Engineering Development (TED) Building Thomas Jefferson National Accelerator Facility Newport News, VA Tech Report I ASHRAE Std. 62.1-2007 and Std. 90.1-2007 Compliance Report 10/4/2010
More informationIAQ & Energy Impact of Exhaust Air Transfer Ratio
This article was published in ASHRAE Journal, November 207. Copyright 207 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission
More informationJoint-Frequency Bins versus Conventional Bin Weather Data in Analysis of HVAC System Operation
ESLIC091132 JointFrequency Bins versus Conventional Bin Weather Data in Analysis of HVAC System Operation Alaina Jones Graduate Research Assistant JuanCarlos Baltazar, Ph.D. Associate Research Engineer
More informationOUTSIDE AIR REDUCTIONS
ENERGY-SAVING STRATEGIES: OUTSIDE AIR REDUCTIONS Goal: To use only the amount of outside air necessary to prevent the build-up of gases that can pose risks for collections and human health, and keep spaces
More informationThe Ed Roberts Campus
The Ed Roberts Campus Proposal Anderson Clemenceau Mechanical Option Advisor: Donghyun Rim December 12, 2014 2 Contents Executive Summary... 3 Building Overview... 4 Existing Mechanical System... 5 Airside
More informationIllinois Sustainable Technology Center, University of Illinois at Urbana-Champaign
Topic B14: Policy, standards, and regulations ASHRAE STANDARD 62.2: WHAT S NEW AND WHY Paul W FRANCISCO,* Illinois Sustainable Technology Center, University of Illinois at Urbana-Champaign *Corresponding
More informationSecond Stakeholder Meeting for Variable Exhaust Flow Control
Second Stakeholder Meeting for Variable Exhaust Flow Control March 7, 2017 Jared Landsman Jlandsman@integralgroup.com Agenda 1. Background 2. Proposed Code Changes 3. Technical and Market Barriers 4. Compliance
More informationLoad Calculations Heat Balance Method - Example. Prof. Jeffrey D. Spitler School of Mechanical and Aerospace Engineering, Oklahoma State University
Load Calculations Heat Balance Method - Example Prof. Jeffrey D. Spitler School of Mechanical and Aerospace Engineering, Oklahoma State University Weather 20'-0" 15'-0'' 15'-0" 1 2 3 20'-0" Office Storage
More informationThe Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma
LEED Green Building Certification The purpose of the LEED Green Building Rating is to provide a national standard that aims to improve environmental, health and economic performance of buildings using
More informationWater Bottling Facility
TECHNICAL REPORT 2 Water Bottling Facility Mid-Atlantic, US Building and Plant Energy Analysis Report The Pennsylvania State University Author: Justyne Neborak Architectural Engineering Advisor: Dr. William
More informationPERCENT OUTDOOR AIR CALCULATION AND ITS USE
PERENT OUTDOOR AIR ALULATION AND ITS USE APPLIATION NOTE TSI-138 TSI s IAQ instruments calculate Percent Outdoor Air (%OA). In order to take advantage of this feature, it is important to first understand
More information2019 Title 24 Codes & Standards Enhancement (CASE) Proposal Nonresidential Ventilation & Indoor Air Quality (IAQ)
2019 Title 24 Codes & Standards Enhancement (CASE) Proposal Nonresidential Ventilation & Indoor Air Quality (IAQ) September 27, 2016 Ryan Sit Integral Group rsit@integralgroup.com Anna Brannon Integral
More informationNational Weatherization Conference. Ventilation Best Practices & airflow verification FIELD RESEARCH. Joe Nagan, Home Building Technology Services
National Weatherization Conference Ventilation Best Practices & airflow verification Presented by Joe Nagan, Home Building Technology Services Home Building Technology Services 1 Home Building Technology
More informationDISPLACEMENT VENTILATION
clever creative comfort DISPLACEMENT VENTILATION A p p l i c a t i o n G u i d e Application Guide3 Introduction to 3 Air Change Effectiveness3 Typical Applications4 Contaminant Removal4 Benefits & Limitations4
More informationSolarCity Partnership. Central Maintenance Garage 369 kwt Solar Wall Air Heating System. Technology. Monitoring. Best Practices
Central Maintenance Garage 369 kwt Solar Wall Air Heating System Final Report January 2012 Technology Monitoring Best Practices SolarCity Partnership PROJECT SNAPSHOT Address: 843 Eastern Avenue Building
More informationCoppin State University Physical Education Complex - Technical Report 2
Coppin State University Physical Education Complex - Technical Report 2 Building and Plant Energy Analysis Report Kaylee M Damico Advisor: Dr. Jelena Srebric Location: Baltimore, MD Table of Contents Contents
More informationTeague Research Center
Continuous Commissioning Report for the Teague Research Center Building #445 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory
More informationDavid H. Koch Institute for Integrative Cancer Research Senior Capstone Mechanical Option. Proposal
0 David H. Koch Institute for Integrative Cancer Research Senior Capstone Mechanical Option Proposal David H. Koch Institute for Integrative Cancer Research Massachusetts Institute of Technology Cambridge,
More informationSouth Jefferson High School Huyett Road Charles Town, WV 25414
Thesis Proposal Mechanical System Redesign Report Charles Town, WV 25414 Prepared for Dr. Jelena Srebric The Pennsylvania State University By Jonathon Gridley Friday, December 15, 2006 1.0 Table of Contents
More informationA Protocol. Advanced Air Sealing
A Protocol Advanced Air Sealing Efficiency Vermont is a Registered Provider with The American Institute of Architects Continuing Education Systems (AIA/CES). Credit(s) earned on completion of this program
More informationSECTION DESIGN REQUIREMENTS BASIS OF DESIGN GENERAL INFORMATION
BASIS OF DESIGN GENERAL INFORMATION 1.1 During the Schematic Design phase, the Consultant shall develop a Basis of Design (BOD) Document. This document shall provide a comprehensive description of the
More informationMEP's Letter of Assurance
MEP's Letter of Assurance Instructions Multifamily Residential WELL Certification is determined by onsite Performance Verification and documentation, including Letters of Assurance from the appropriate
More informationEnergyPro Building Energy Analysis. Single-story School Building
EnergyPro Building Energy Analysis Single-story School Building EnergyPro Building Energy Analysis for a single-story school bulding Project Scope The purpose of the EnergyPro energy model was to evaluate
More informationTerminal. 3 Las Vegas, NV. Technical
McCarran International port Terminal 3 Technical Assignment 1 ASHRAE Standard 62.1 2007 Compliance Evaluation October 5, 2007 Prepared By: Jason A. Witterman Faculty Advisor: Dr. William Bahnfleth, Ph.D.,
More informationRE-COMMISSIONING BY: BERNARD (BERNIE) W. NELSON P. ENG., PE., LEED AP, CEM C.E.S. GROUP. <insert your logo here> Twitter hashtag: #psforum
RE-COMMISSIONING BUILDINGS BY: BERNARD (BERNIE) W. NELSON P. ENG., PE., LEED AP, CEM THE COMMISSIONING PROCESS (Cx) The commissioning process: ASHRAE guideline 0-2005 definition: A quality-focused process
More informationOverview of Dynamic Control of Lab ACH s
A Comprehensive Review of the Indoor Environmental Quality and Energy Impacts of Dynamically Varying Air Change Rates at Multiple Laboratory Facilities Overview of Dynamic Control of Lab ACH s Background
More informationInterdisciplinary Science and Engineering Building
1 1 Senior Thesis Capstone Project Treado Thesis Proposal Interdisciplinary Science and Engineering Building University of Delaware Newark, DE 19716 2 2 Table of Contents Executive Summary 3-4 Building
More information12/20/2010. NIST Capabilities/Program Opportunities for Manufactured Housing what s up in Gaithersburg OUTLINE. NIST IAQ and Ventilation Group
NIST Capabilities/Program Opportunities for Manufactured Housing what s up in Gaithersburg Andrew Persily, andyp@nist.gov, 301 975-6418 Engineering Laboratory National Institute of Standards and Technology
More informationMechanical Depth. Redesign and Analysis
Depth Redesign and Analysis 14 Analysis Scope The scope of my mechanical redesign will include the 2 nd and 3 rd floors of the SW hospital wing which includes Semi-Private, Private and Isolations rooms.
More informationENERGY ANALYSIS AND ENERGY CONSERVATION OPTION FOR THE WAREHOUSE FACILITY AT THE HUMAN SERVICES CENTER COMPLEX DRAFT REPORT.
ESL-TR-86/09-03 ENERGY ANALYSIS AND ENERGY CONSERVATION OPTION FOR THE WAREHOUSE FACILITY AT THE HUMAN SERVICES CENTER COMPLEX DRAFT REPORT Submitted by Mohsen Farzad Dennis O'Neal Prepared For Energy
More informationGATES-HILLMAN CENTERS
GATES-HILLMAN CENTERS CARNEGIE MELLON UNIVERSITY CASE STUDY ENERGY EFFICIENCY CARNEGIE MELLON UNIVERSITY Carnegie Mellon University looked to SEMCO to provide solutions for their energy efficiency goals.
More informationIndex of Addenda to ANSI/ASHRAE Standard 62.1
a b in 62-1989 Published in 1990. The committee withdrew this addendum from consideration, and the issue of existing buildings was addressed by Addenda 62k and 62af. Withdrawn in September 2000. The addendum
More informationCO 2 -Based DCV Using
2006 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Journal (Vol. 48, May 2006). For personal use only. Additional distribution in
More informationWEST VIRGINIA UNIVERSITY ALUMNI CENTER Morgantown, West Virginia
TECHNICAL REPORT I ASHRAE STANDARDS 62.1 AND 90.1 COMPLIANCE EVALUATION 8/29/08 WEST VIRGINIA UNIVERSITY ALUMNI CENTER Morgantown, West Virginia GREGORY SMITHMYER PENN STATE UNIVERSITY ARCHITECTURAL ENGINEERING
More informationHow LEED & The Retro-Commissioning Credits Produce Energy Savings. James Vallort Vice President Environmental Systems Design, Inc.
How LEED & The Retro-Commissioning Credits Produce Energy Savings James Vallort Vice President Environmental Systems Design, Inc. Retro-Commissioning Today s session will focus on the following items:
More informationTechnical Report 2. Bellevue Ambulatory Care Pavilion New York, NY. Building and Plant Energy Analysis
Technical Report 2 Building and Plant Energy Analysis Bellevue Ambulatory Care Pavilion New York, NY Prepared for: Dr. Jelena Srebric, PhD Department of Architectural Engineering The Pennsylvania State
More informationIndoor and Outdoor Comparisons of Particle Sizes and Concentrations
Indoor and Outdoor Comparisons of Particle Sizes and Concentrations Professor Shelly Miller Mechanical Engineering University of Colorado at Boulder Main Points of Today s Talk Particles inside commercial
More informationENSURING A PRODUCTIVE ENERGY MODELING PROCESS
ENSURING A PRODUCTIVE ENERGY MODELING PROCESS ASHRAE Rocky Mountain Technical Conference April 15, 2011 Kendra Tupper, P.E. (RMI) Sue Reilly, P.E., BEMP (Group 14) Michael Brendle, FAIA (RNL) OVERVIEW
More information1 Project Information. 2 Building Type. 3 Trade Ally/Contractor Information. HVAC Rebate Worksheet. Retrofit New Construction
HVAC Rebate Worksheet Before you start Instructions: Complete all relevant information for your project. Include with complete application package. The HVAC Worksheet should be completed for new construction
More informationThe baseline building system for compliance with Senate Bill 668 is defined by Appendix G,
Project: North Carolina A&T State University New Student Health Center SCO #: 08-08109-01A 1.0 Heating, Ventilating and Air Conditioning (HVAC) Baseline Building Systems Senate Bill 668 Compliance The
More informationV entilation control using carbon dioxide
REAL-TIME VENTILATION Operational control of ventilation systems using sensors that measure concentrations Editors Note: A longer version of this article is available at no cost on HPAC Engineering s Website
More informationA Building Commissioning Overview. Presented by: Goetting & Associates Commissioning
A Building Commissioning Overview Presented by: Goetting & Associates Commissioning www.goettingcx.com What is the Definition of Commissioning? Building Commissioning is a Quality Assurance Process of
More informationINNOVATIONS IN VENTILATION TECHNOLOGY 21ST ANNUAL INTERNATIONAL AIVC CONFERENCE THE HAGUE, NETHERLANDS, SEPTEMBER 2000
INNOVATIONS IN VENTILATION TECHNOLOGY 21ST ANNUAL INTERNATIONAL AIVC CONFERENCE THE HAGUE, NETHERLANDS, 26-29 SEPTEMBER 2000 Impact of Ventilator Parameters on System Energy Consumption Dipak J. Shah Senior
More informationAPPENDIX 2C ENERGY 1. ENERGY SUPPLY AND CONSUMPTION... 1
APPENDIX 2C ENERGY 1. ENERGY SUPPLY AND CONSUMPTION... 1 1.1 Energy Supply and Payment... 1 1.2 Recording and Monitoring of Weather Data and Energy Consumption... 1 1.3 Energy Consumption Certificate...
More informationProposed Addendum L to Standard , Ventilation for Acceptable Indoor Air Quality
BSR/ASHRAE Addendum L to ANSI/ASHRAE Standard 62.1-2016 Public Review Draft Proposed Addendum L to Standard 62.1-2016, Ventilation for Acceptable Indoor Air Quality Second Public Review (August 2018) (Draft
More informationREDUCED-ORDER ENERGY MODELING IN RETRO-COMMISSIONING: A CASE STUDY OF AN ACADEMIC BUILDING
2018 Building Performance Analysis Conference and SimBuild co-organized by ASHRAE and IBPSA-USA Chicago, IL September 26-28, 2018 REDUCED-ORDER ENERGY MODELING IN RETRO-COMMISSIONING: A CASE STUDY OF AN
More information[TECHNICAL REPORT 1]
2010 Geoffrey Kim Penn State University Geoffrey Kim Mechanical Option Advisor: Dr. Srebric [TECHNICAL REPORT 1] ASHRAE Standard 62.1 Ventilation and Standard 90.1 Energy Design Evaluations for Hotel Felix
More informationMechanical Technical Report Three Mechanical Systems Existing Conditions Evaluation
Mechanical Technical Report Three Mechanical Systems Existing Conditions Evaluation 2900 Fairview Park Drive, Prepared By: Charles Haack Mechancial Option November 21, 2008 Prepared For: Dr. William P.
More informationMeasurement and Analysis of Vitiation of Secondary Air in Air Distribution Systems (RP-1276)
University of Nebraska - Lincoln From the SelectedWorks of David Yuill Spring May, 2008 Measurement and Analysis of Vitiation of Secondary Air in Air Distribution Systems (RP-1276) David P Yuill, University
More informationIndoor Air Quality Tools for Schools
CT School Indoor Environment Resource Team 2nd Training Session: Walkthrough Investigations Indoor Air Quality Tools for Schools Agenda: Welcome, Introductions Show and Tell: Presentation of Blueprints,
More informationGeorgetown University New Science Center
Georgetown University New Science Center Final Thesis Proposal PENN STATE UNIVERSITY Prepared For: Dr. William P. Bahnfleth Department of Architectural Engineering Prepared By: Kevin M Edstrom Mechanical
More informationPROJECT HIGHLIGHTS 49% 74% 15% 51% 45% CLASS OF 1959 MEMORIAL CHAPEL HARVARD BUSINESS SCHOOL HARVARD UNIVERSITY
HARVARD UNIVERSITY HARVARD BUSINESS SCHOOL CLASS OF 1959 MEMORIAL CHAPEL 49% 74% 15% 51% 45% reduction in the Chapel s Energy Use Index (EUI) since May of 2008. reduction in electric consumption from lighting
More informationMEP Engineer's Letter of Assurance
Instructions MEP Engineer's Letter of Assurance WELL Building Standard, Jan 2016 WELL Certification and WELL Core and Shell Compliance are determined by onsite Performance Verification and Documentation,
More informationCooling Load Calculations
2103-454 Ventilation and Air Conditioning Cooling Load Calculations by Assist. Prof. Dr. Tul Manewattana. Chulalongkorn University Bangkok, THAILAND November 2010 1 Principles of Cooling Load 2 Principles
More informationSpending Through the Roof: Tall Building Energy Wasted Through Passive Vents. Building Energy 2017 A presentation by: Jamie Kleinberg & Robin Neri
Spending Through the Roof: Tall Building Energy Wasted Through Passive Vents Building Energy 2017 A presentation by: Jamie Kleinberg & Robin Neri Project Objective: Develop and test methods for estimating
More informationIndoor Air Quality and Mechanical Ventilation (Page 1 of 5)
Indoor Air Quality and Mechanical Ventilation (Page 1 of 5) Title 24, Part 6, Section 150.0(o) Ventilation for Indoor Air Quality. All dwelling units shall meet the requirements of ANSI/ASHRAE Standard62.2.
More information35% reduction in water use below code maximum 100% 100% 32% reduction in lighting power density 100%
Ni Lab leed ci v3.0 12 oxford street, Cambridge, ma leed gold Project Profile 2014 Laboratories are typically regarded as an energy intensive building typology. Many of these buildings have extended occupancy
More information