1 THE GUIDE TO GOOD LEADWORK This booklet has been produced to promote and encourage the correct use of lead sheet flashings, weatherings and gutter linings in building. Nobody knows more about lead than Calder!

2 Lead sheet has been in use as a building material for centuries. Lead sheet adorns the roofs of churches, offices, factories, public buildings and homes throughout the United Kingdom because of its durability and ease of use. 2

3 3

4 This booklet is a guide to the correct detailing and fixing of lead sheet flashings, weatherings and gutter linings. The following information conforms with the British Standard for leadwork and the recommendations of the Lead Sheet Association. For more detailed technical information, reference should be made to the LSA s publication entitled The Complete Manual which covers the many applications of lead sheet in building. IMPORTANT Lead sheet is a proven, long-life building material. It is extremely malleable and can be readily dressed to fit the multi-curved contours of many modern building materials, particularly roofing tiles. To ensure this longevity, however, it is essential to follow a few basic rules: Individual pieces of lead sheet must not exceed the recommendations set out on page 5. In particular, each piece of flashing must be no longer than 1.5m. Fixings should hold the lead securely in position without restricting thermal movement. With flashings, regular expansion joints (laps) will overcome the restriction caused by lead wedging along one side. Nails and screws should have a similar life expectancy to that of the lead, therefore use copper, brass or stainless steel, never galvanised or aluminium fixings. Joints must allow for thermal movement but also remain weathertight for the position where they are used. For example, do not use laps or welts to join pieces of gutter lining. The correct joint is a drip, as illustrated on page 16. Remember, lead sheet is a fine, longlife material but only when used correctly. CONTENTS Thickness & weight chart 5 Borra Fixing Clip 6 Lead Sheet Sealant 7 Patination Oil 8 Geotec Underlay, Wood Core Roll and Clips 9 Clips 10/11 Cover flashings 12/13 Abutment flashings 14/15 Roll ends and drips 16 Ridges and hips 17 Chimney flashings 18 Pitched valley gutters 19 Box and tapered gutters 20 Secret gutters 21 Flat roof coverings 22 Window flashings 23 Note: BS EN12588 replaced BS1178 in August Calder lead sheet and flashing conforms to the new European Standard. 4

5 The Calder Guide to Good Leadwork Table 1 Range of thicknesses and weights Kg per square metre: Thickness in mm: LEAD SHEET BS EN12588 Thicknesses to BS EN12588 tolerances of ±5% Code No Code No Code No Code No Code No Code No Table 2 Thickness of lead sheet for various purposes Use BS EN12588 Code No. Soakers 3 or 4 Apron and cover flashings Hip and ridge flashings Pitched valley gutters Weatherings to cornices, parapets etc. 4 or 5 Lead slates Chimney flashings - back gutters, apron and side flashings Parapet, box and tapered gutters 5 to 8 Table 3 Sizing - guidelines to good practice Recommended maximum sizes of individual pieces of lead for the following applications: 3a Flashings - apron and cover. Also pitched valley gutter linings BS EN12588 Uses Maximum Code No. length mm 3 Soakers and 5 Flashings and pitched 1500 valley gutters 3b Gutters - box, tapered and parapet BS EN12588 Maximum length Overall girth Code No. between drips mm Max. mm

6 BORRA FIXING CLIP the answer to fastening lead flashing For busy lead installers, time is money. These easy to use fixing clips will result in time saved. Using the clip will securely fasten the lead flashing in place in accordance to BS6915. The standard recommends that fixings are fixed at 450mm maximum centres. Roger Bisby March 2002, says: These two products will transform the way lead is fixed. I was amazed by just how well the clips work. I doubt that anyone who cares about their professional reputation and wants to avoid callbacks will be using lead wedges in another five years. 6

7 LEAD SHEET SEALANT the answer to pointing problems! Why is it that so many water penetration problems occur at abutments? The answer often is that mortar is not a satisfactory long-term pointing where lead flashings turn into joints in brickwork or masonry. The mortar is unable to adhere to both the brick and the lead when subject to changes in temperature. It soon cracks, particularly in sunny exposures, allowing water to penetrate, causing dampness below. In many cases the problem is made worse by poor cleaning out of the joint which results in a wedge-shaped pointing which quickly cracks away from the brickwork. Now there is a practical, long-term alternative to mortar pointing - Lead Sheet Sealant. This one-part, neutral-cure, high-performance silicone-based sealant has been specially formulated for use with lead sheet flashings and its elastic properties make it ideally suited for pointing between lead and brickwork or masonry. Lead Sheet Sealant - The Experts Choice! The sealant specifically designed for pointing joints between lead and brickwork or masonry. Provides a long term, flexible joint, which can absorb temperature changes. Avoids the problems of pointing with wet mortar, particularly in hot or frosty conditions. Quicker, cleaner and easier to use than mortar. The Lead Sheet Association recommends sealant. 7

8 PATINATION OIL protective coating for new lead NEW FORMULATION Lead sheet continues to be popular as an architectural feature on buildings because of its ease of use, durability and the pleasing grey colour of its protective patina. Patination oil specifically developed for the industry by Calder on behalf of the Lead Sheet Association, minimises unsightly staining and imparts a pleasing appearance to newly applied lead sheet and flashings. Occasionally the patina formed on lead Roof tiles spoiled by run-off staining. looks patchy and unattractive. In rainy or damp conditions new lead will quickly develop an uneven powdery white, non-adherent coating of lead carbonate, a corrosion product, which is aesthetically unacceptable. The staining of tiles and brickwork spoils the overall appearance of the building. Patination oil will minimise this uncontrolled formation of carbonate, improve the hygiene on the job AND impart a pleasing appearance to the lead both before and after the formation of its final patina. IMPORTANT Shake the oil vigorously before use. Apply the oil evenly with a soft absorbent cloth. Work horizontally from top to bottom maintaining a wet lower edge. Do not use a circular scrubbing motion. Apply the oil to all newly installed lead items - large or small. Apply the oil before any rain and at the end of the day s work. One coat is all that is needed. Lift flashings and coat the underside of the lead for about 50mm from the edge. Coat the lead before turning up clips around the edges. Remember to coat between laps. Untreated Treated NB: Because of the solvents it contains it is important to keep patination oil away from roof areas where bituminous felt has been laid, any spillage will dissolve the bitumen. A comprehensive LSA data sheet is available on request. 8

9 GEOTEC UNDERLAY, WOOD CORE ROLL & CLIPS ➁ ➀ GEOTEC UNDERLAY prevents wear due to thermal movement Geotec 220PY underlay is used to isolate sheet metal roofing from substrates allowing metal sheet to expand and contract with temperature changes. ➂ ➀ GEOTEC UNDERLAY ➁ WOOD CORE ROLL ➂ CLIPS ➂ Geotec 220PY is a non-woven, needle punched, polyester textile underlay, weighing 220g/m2, conforming to the Lead Sheet Association s requirements. WOOD CORE ROLL as used on ridges, hips and flat roofing Wood core roll is to be used to allow for the expansion and contraction in lead sheet and flashing. Wood core roll is used for joining bays of lead roofing, also on steeply pitched roofs and lead cladding where a bold joint appearance is preferred. It is shaped to prevent wind lift. CLIPS to hold lead permanently in position Cut to the required length fixing clips are recommended in rolls, welts, standing seams and for the clipping of lap joints and flashings. Available in copper, tinned copper and terne coated stainless steel. 9

10 The Calder Guide to good Leadwork Clips Lead clips are only suitable for sheltered exposures. For most situations tinned copper or stainless steel should be used. Use a minimum of 0.6mm copper or 0.4mm stainless steel for clips. Use thicker material for exposed positions. But why do so many clips fail in high wind conditions? Mainly because the fixing position is not suited to the exposure. Although the spacing of clips is important and the material used should relate to the exposure it is likely to receive, the main consideration must always be the position of the fixing points. Clips and Clipping The diagrams on the right, illustrate the simple principle: The lower the fixing, the stronger the clip. Top fixing to batten. Fixing at top. For sheltered exposures. Additional fixing. Essential for both moderate and severe exposures. 50 Additional fixing to batten through joint in top tile. Lower tile drilled. Screws are preferable to nails when fixing clips to battens. 100 min. 500 max. centres Exposed situations Max. length (each piece) min. Apply patination treatment to lead before turning clips. See page 8. 10

11 A few basic rules... Space clips at 300mm to 500mm intervals to suit the exposure. Don t fix clips with galvanised steel nails. Use copper or stainless steel. Lead clips should only be used in sheltered situations. If in any doubt about exposure, use additional fixings. Where extra fixings cannot be used, e.g. flashings over glazing, use a thicker gauge clip material. (When using lead dome fixings, ensure there is no restriction of thermal movement.) Clips to single lap tile roofs 75 min. Fixings at 450mm centres approx. 150 min. 25 min. Clip for sheltered exposures only. Clip for moderate and severe exposures. Must be tinned copper. Fixings at each step. Copper shaped to fit sidelap of tile Lap Lap min. 50 Clip for raking abutments. For all exposures. 11

12 Cover Flashings Cover flashings are used where a felt or similar roof covering turns up against a wall. Code 4 lead sheet is normally used for this work and it is important that the length of each piece of flashing does not exceed 1.5m. Laps between pieces should not be less than 100mm. Use a straight piece of batten to mark a line 25mm from the top edge of each flashing piece and then bend the lead with the use of the dresser to form a 25mm turn into the brickwork. Each piece of flashing is secured into a joint in the brickwork as per BS6915 at 450mm maximum centres, see page 6. Mortar is not a satisfactory long term pointing. The mortar is unable to adhere to both the brick and the lead - when subject to changes of temperature it cracks allowing water to penetrate. The Lead Sheet Association recommends the use of a silicon sealant for pointing. Copper or stainless steel clips are positioned along the lower edge of the flashing to suit the exposure of the building, see pages 10 and 11. At internal and external corners the turn-in is cut and the flashing folded. Note that the lap joint is adjacent to the corner and NOT in the corner. The turn-in on the external corner is simply folded as shown whereas it is necessary to insert a small piece of lead in the internal corner to ensure a weathertight joint. This can be achieved by either lead welding or soldering. Cover flashings 25 min. 75 min. Lap 100 min max. 25 min. External Corner Internal Corner 25 min. 100 min. 75 min. Apply patination treatment. See page 8. Point all flashings with Lead Sheet Sealant. See page 7. 12

13 Where the roof incorporates an expansion joint the flashings are detailed as shown. Without the timber fillet the lead would sag onto the top of the kerb. This will create a section of horizontal lap through which water will seep into the area below. The timber fillet also provides a positive fixing for the clips. Important basic rules... Individual pieces of lead must be no longer than 1.5 metres. Fixings should hold the lead securely in position without restricting thermal movement. Nails and screws should have a similar life expectancy to that of the lead, therefore use copper, brass or stainless steel, never galvanised or aluminium fixings. The turn-in at internal corners requires a small gusset to ensure a weathertight joint. Use Lead Sheet Sealant for pointing. Apply patination treatment to all surfaces including under lap joints. Lift flashings and coat the underside of the lead for about 50mm from the edge. Cover flashings Supporting fillet 25 min. Clips to suit exposure Apply patination treatment. See page 8. Point all flashings with Lead Sheet Sealant. See page 7. 13

14 Abutment flashings Horizontal and raking abutment flashings should extend out over the tiles - or slates - for not less than 150mm. Where plain (uncontoured) concrete tiles are used at low pitches, a cover of 200mm is preferable, particularly in exposed positions. Alternatively, a secret gutter can be used. See page 21. Space fixings at about 450mm centres for cover flashings and at each step for raking abutment flashings. Abutment flashings Point all flashings with Lead Sheet Sealant. See page 7. Turn flashings at least 25mm into mortar joints Fixings at each step Form corner correctly min Clips not shown. These must be spaced to suit exposure. See pages 10 & 11 Remember to... Turn all lead flashings at least 25mm into mortar joints. Clip free edges of flashings to suit exposure (see pages 10 & 11) Apply patination treatment. See page 8. 14

15 Soakers and step flashings are used to weather a raking abutment where the roof is covered with slates or plain tiles. While Code 3 is suitable for soakers, Code 4 is the minimum thickness to use for all flashings. The setting-out and cutting of the steps (see below) is the same for both flashings with soakers and for combined step-and-cover flashings over single-lap tiling. An alternative method for more exposed situations is a single-step flashing which can be used over soakers, cover flashings or secret gutters. Abutment flashings with soakers Soaker Cut to waste Fold Waterline No cuts are made below this line max. Single steps with cover flashing 25mm turn-in 75 min Flashing set out and cut Soakers Point all flashings with Lead Sheet Sealant. See page 7. Fixings at each step Single steps with secret gutter Cover flashing Fixings at each step 50 min 15 max 75 min overlap 75 min 15

16 Roll ends and drips Roll ends and drips can be formed either by bossing or leadwelding. When a wood-cored roll is used to divide a wide gutter, the undercloak should only be nailed, using copper or stainless steel nails, to the roll for the upper third of its length. The end of the wood roll is usually splayed and it is important for the base of the roll to finish at the drip edge, thereby avoiding a horizontal lap in front of the roll, through which water could penetrate. Drip undercloaks should be rebated into the decking, otherwise rainwater will pond near the front edge of the drip. Splash laps can be omitted if an adequate lap is maintained at roll ends and drip abutments. Roll ends and drips Fixings, using copper or stainless steel nails, to the undercloak - upper third of roll length only 3-5 BS EN12588 Code No Min drip height h 55mm 55mm 55mm 60mm 60mm Splashlap can be omitted for codes 6,7, and 8 5 min. h 50mm min. drip height for narrow gutters without roll Splashlap optional for gutter linings Alternative overcloak detail for Codes 4 and 5 Extend undercloak 40mm min. when splashlap on roll overcloak is omitted Apply patination treatment. See page 8. 16

17 Ridges and hips Lead ridges and hips are normally used on slated roofs. A wood roll is required and should be fixed as shown in the diagram below. The flashings must extend over the slates or tiles a minimum of 150mm on each side. A practical method of fitting the flashings that will avoid thinning at the corners is to form the lead into a trough. The lead is pressed down over the roll to fit closely to both the roll and the roof surfaces. Use a minimum of Code 4 lead sheet for both ridge and hip flashings and again, the maximum length of each piece should not exceed 1.5m. Laps between pieces should not be less than 150mm - although for pitches below 30 the hip laps should be increased to 200mm. It is important to fix the top of each piece of hip flashing to the wood roll with copper or stainless steel clout nails. Nails are not required at the ridge laps. Clip fixings along the sides of the flashings are absolutely essential and should be spaced to suit the exposure of the building - see pages 10 and 11. Note the extra fixings in the clips shown on both the ridge and hip laps. In all but very sheltered exposures these fixings will be required. At the junction between ridge and hip flashings and also where the roll terminates at the hip end, the lead will need to be dressed to fit or alternatively can be formed by leadwelding or soldering. Ridges and hips 150 min Roll fixed 5mm min. above slate A 150 min. 150 min. Fixings at top of each hip flashing C B A Lap to suit roof pitch 150 min. B Apply patination treatment. See page 8. C 17

18 Chimney flashings Flashings for a chimney consist of a front apron, side flashings and a back gutter with cover flashings. When a chimney is sited at the ridge, the back gutter is replaced by a saddle at each side. Depending upon the type of tiles or slates, the side flashings will either be detailed with soakers or as step-and-cover flashings. (See pages 14 & 15). Chimney flashings can be fabricated by leadwelding or bossing. Code 4 is the minimum thickness to use, but if bossing is the method used, then Code 5 is preferable for the back gutter. For roof pitches above 30 (or above 20 in sheltered or moderate exposures) the side flashings can be finished 10mm back from the front corner (see figure A). When this detail is used, however, it is essential that the front apron is properly turned at the corner so that an adequate lap is provided where the side flashing covers the apron. Chimney flashings 25 min. turn-in Fixings not shown (but still required) See page 12 Back gutter 150 min Step and cover flashing 150 min Figure A Apron Clips at front (depending on exposure) Clip See pages 10 & min Saddle at ridge Point all flashings with Calder Lead Sheet Sealant. See page 7. Edge welted Note: Minimum cover over tile = 150mm Apply patination treatment. See page 8. 18

19 Pitched valley gutters To provide a weathering life equal to that of the tiles or slates which overhang on each side, lead sheet pitched valley gutter linings should be fixed in lengths not exceeding 1.5m. Each piece should be fixed across the top with two rows of copper or stainless steel clout nails. Valley boards should be level with the tops of the rafters so that tiling battens and tilting fillets are the same height. With traditional roofing the valley boards can be recessed into the rafters; but when roof trusses are used the boards must be cut to fit between the rafters. For pitches of 30 and above the lap between pieces should be 150mm, increasing to 220mm for a pitch of 20. Some important points... Don t nail down the sides as this will restrict free thermal movement and result in failure. Don t lay sarking felt under the lead. It will cause the lead to stick to the boards in hot weather. Use copper or stainless steel nails to fix the lead - not galvanized steel or aluminium. Pitched valley gutters Saddle piece 2 rows of fixings at head of underlap (first row 25mm from top of gutter) 150 min. No fixings down sides 125 min Separators 150 min Tilting fillet Apply patination treatment. See page 8. 19

20 Box and tapered gutters For these gutters the joints between each piece of lining must always be formed by drips. Welts or lap joints are not suitable. Use copper or stainless steel nails to fix the underlap across the top of the drip and, if necessary, along the top third(s) only at the sides. Never fix them completely at the sides as this will restrict thermal movement which, in turn, will cause cracking. For tapered gutters where the overall girth exceeds the maximum shown in Table 3b, page 5, use a wood-cored roll to divide the bay longitudinally. Check the fall before laying the lining. It must be at least 1:80 (25mm in 2m), otherwise ponding will occur. Remember that cover flashings (see page 12) must lap gutter upstands by at least 75mm. Do not exceed the bay sizes shown on page 22. Box gutter Apply patination treatment. See page 8. Point all flashings with Lead Sheet Sealant. See page 7. Tapered gutter For maximum bay length details see page Wood-cored roll divides bays when girth exceeds maximum shown in Table 3, page min. Minimum Dimensions Girth Undercloak nailed into rebate 20

21 Secret gutters Renewal of roof coverings on terraced housing often results in a situation where different tiles abut over a party wall. A practical method of weathering these intersections is to use a secret gutter. The sizing and fixing of the linings is similar to that for pitched valley gutters, as shown on page 19. The methods shown below are superior alternatives to the bedded hip tiles commonly used. The use of lead sheet in these situations gives the following advantages: It allows for both structural and thermal movement between adjacent properties without risk of water penetration. Tiles and slates on either side of the junction can be readily repaired or renewed without disturbance to the adjoining property. Properly detailed and installed, the leadwork will have a durability at least equal to that of the best tiles or slates. Secret gutter over party wall Gutter lining max. length 1.5m max. gap between tiles Copper or stainless steel clout nails 75 min. gutter width Board spanning party wall Nail details Note spacing. Do not create a perforated edge. 21

22 Flat roof coverings Lead sheet is the ideal material for weathering projections and canopies over windows and doors. Large lengths and areas can be divided into bays by wood-cored rolls so that no piece of lead exceeds the recommended dimensions. Front and side edges should be clipped to suit the exposure. A few tips... Don t use an underlay which could cause adhesion to the substrate during hot weather. Use a building paper or a geotextile underlay. Don t nail or tack the edges to prevent wind lift. Use clips. Never oversize the bays. Divide them with wood-cored roll or, alternatively, use a thicker sheet. Flat roof coverings Recommended maximum dimensions. Illustrations are diagrammatic Apply patination treatment. See page 8. BS EN12588 Code No. Maximum spacing of joints with the fall (mm) Maximum distance between drips (mm) a. Max bay size Code b. Alternative bay size Code

23 Window flashings Window flashings are most often required where windows are fixed into walls that are covered with tiles or slates but are also used with other cladding e.g. timber or PVC weatherboarding. In all cases the detailing of the flashings is similar and as with all lead flashings the maximum length when using Code 4 lead sheet is 1.5m. Although a corner can be dressed or bossed to shape it is more practical to introduce a gusset as shown which can be leadwelded or soldered before the cill flashing is placed in position. For windows that are wider than 1.5m, mm laps should be used between cill flashing pieces depending on the exposure. In cases where the window is set back from the wall covering, a jamb flashing will be required to prevent water from penetrating down behind the cill upstand. The length of flashing pieces should not exceed 1.5m. Laps between pieces of cill flashing should be 100mm - 150mm depending on the exposure and laps between jamb flashings and cill flashings should not be less than 75mm. The apron extends 150mm down the face of the wall covering and this is often cut to a scalloped pattern to suit the spacing of the tiles or slates. Window flashings Jamb flashing min. Gusset 100 Bottom of lap joint above cill level Gusset 150 Quadrant often required to weather this point Lap joint above cill Apply patination treatment. See page 8. 23

24 LEAD CONTRACTORS ASSOCIATION Health and Safety Precautions To ensure your well-being, Calder Industrial Materials Limited have produced Health and Safety Data Sheets. Ask your builders merchant to obtain copies for you. Caring for the environment Both old lead and new lead off-cuts can be recycled. Calder Industrial Materials Limited s rolled lead to BS EN12588 is manufactured using recycled lead Copies of this booklet are available FREE from your merchant with purchases of Calder Quality Lead. MEMBER OF THE LEAD SHEET ASSOCIATION 0904/ DOCSG002 Produced by Calder Industrial Materials Limited info@caldergroup.co.uk

SUPERIOR LEAD PRODUCTS. Everything else is temporary

SUPERIOR LEAD PRODUCTS. Everything else is temporary SUPERIOR LEAD PRODUCTS Everything else is temporary 4 Recycling 5 Sustainability 6 Patination Oil 7 Lead-Cote 8 Hall Clips 9 Lead Pointing Sealant 10 Standard Lead Slate 11 Quickslate and Unislate 12 Underlays

More information

J41 Reinforced bitumen membrane roof coverings

J41 Reinforced bitumen membrane roof coverings J41 Reinforced bitumen membrane roof coverings To be read with Preliminaries/ General conditions. TYPES OF COVERING 115A SINGLE LAYER REINFORCED BITUMEN MEMBRANE WARM DECK ROOF COVERING warm roofing system

More information

New versatile and effective dry fix solutions for the roofline and above

New versatile and effective dry fix solutions for the roofline and above Cavity trays Access panels Loft access doors Gas barrier and damp proofing accessories Under floor and through wall ventilation Cavity closers and stops Air leakage solutions New versatile and effective

More information

Architectural Roofing

Architectural Roofing ArcTray 1. GENERAL This section deals with the supply and fixing of ArcTray overlap rigid sheet metal profiled roofing and/or cladding complete with accessories. Documents 1.1 DOCUMENTS REFERRED TO Documents

More information

Eco Slate Installation Guide

Eco Slate Installation Guide Eco Slate Installation Guide Getting Started: Please ensure that you follow the installation guidelines and the correct procedures as any variance to this will void your warranty. Before starting please

More information

Outline NBS Specification. Protec System to Felt (Waterproofing Only)

Outline NBS Specification. Protec System to Felt (Waterproofing Only) Outline NBS Specification Protec System to Felt (Waterproofing Only) This document is a guide to assist in the production of tender documents only and is not project specific. A site survey is always recommended.

More information

GRP Flat Roofing Edge Trims

GRP Flat Roofing Edge Trims GRP Flat Roofing Edge Trims Compatible with GRP, rigid and flexible polyester, polyurethane, acrylic and alkyd systems. Trim Brochure and Technical Specification Guide General Information The Easy To Use

More information

Bituminous Roofing Underlay & Valley Guard

Bituminous Roofing Underlay & Valley Guard CONTENTS SUMMARY OF FEATURES... 2 TECHNICAL INFORMATION... 2 Product Description... 2 Applications... 2 Product Information... 2 Handling & Storage... 5 Technical Data... 5 Installation Information...

More information

Outline NBS Specification. Protec System to PVC Single Ply (Waterproofing Only)

Outline NBS Specification. Protec System to PVC Single Ply (Waterproofing Only) Outline NBS Specification Protec System to PVC Single Ply (Waterproofing Only) This document is a guide to assist in the production of tender documents only and is not project specific. A site survey is

More information

LIQUID APPLIED WATERPROOF ROOF COATINGS

LIQUID APPLIED WATERPROOF ROOF COATINGS J31 LIQUID APPLIED WATERPROOF ROOF COATINGS To be read with Preliminaries/General conditions. TYPE(S) OF COATING 110 COLD DECK ROOF COATING Substrate: New / existing concrete deck / screed. o Preparation:

More information

NURAPLY 3PM ROOFING MEMBRANE INSTALLATION CHECKLISTS

NURAPLY 3PM ROOFING MEMBRANE INSTALLATION CHECKLISTS Many poor jobs are found to result from membranes being laid on top of a badly constructed substrate. Before you start work laying all Nuralite systems, you must be sure that the substrate is ready by

More information

General Fixing Guidelines

General Fixing Guidelines General Fixing Guidelines for the Imerys range of clay roof tiles Innovation for Sustainable Homes 1 These guidelines are the minimum requirements for Imerys Roof Tiles. Installing Imerys Roof Tiles The

More information

LIQUID APPLIED WATERPROOF ROOF COATINGS

LIQUID APPLIED WATERPROOF ROOF COATINGS J31 LIQUID APPLIED WATERPROOF ROOF COATINGS To be read with Preliminaries/General conditions. TYPE(S) OF COATING 120 WARM DECK ROOF COATING Substrate: Suitable structural roof deck (e.g. Plywood, OSB3,

More information

TECHNICAL INFORMATION

TECHNICAL INFORMATION TECHNICAL INFORMATION SECTION 07320 TWO-PIECE TAPERED MISSION CLAY ROOFING TILE PART 1 GENERAL 1.01 SECTION INCLUDES A. Formed clay roofing tiles, complete with components and other required accessories

More information

Classic and NB Tile Counter Batten and Batten

Classic and NB Tile Counter Batten and Batten Classic and NB Tile Counter Batten and Batten INSTALLATION GUIDE www.gerardusa.com INSTALLATION NOTIFICATION The installation procedures demonstrated in this manual are recommended methods for the installation

More information

LIQUID APPLIED WATERPROOF ROOF COATINGS

LIQUID APPLIED WATERPROOF ROOF COATINGS J31 LIQUID APPLIED WATERPROOF ROOF COATINGS To be read with Preliminaries/General conditions. TYPE(S) OF COATING 120 WARM DECK ROOF COATING Substrate: Suitable structural roof deck (e.g. plywood, OSB3,

More information

Pacific Tile Counter Batten and Batten

Pacific Tile Counter Batten and Batten Pacific Tile Counter Batten and Batten INSTALLATION GUIDE www.gerardusa.com INSTALLATION NOTIFICATION The installation procedures demonstrated in this manual are recommended methods for the installation

More information

Pacific Tile Counter Batten and Batten

Pacific Tile Counter Batten and Batten Pacific Tile Counter Batten and Batten INSTALLATION GUIDE www.gerardusa.com Page2 INSTALLATION NOTIFICATION The installation procedures demonstrated in this manual are recommended methods for the installation

More information

SPECIFICATIONS FOR PROPOSED

SPECIFICATIONS FOR PROPOSED SPECIFICATIONS FOR PROPOSED PROFILED ROOF / WALL CLADDING Client: Site address: Proposed material: Proposed profile: Rib / Seam centers: Seam height: www.archtech.co.nz 0800 252 383 info@archtech.co.nz

More information

BUILT-UP REINFORCED BITUMEN MEMBRANE WARM DECK ROOF COVERING Two layer, EXCEL/SPOT fully adhered waterproofing system

BUILT-UP REINFORCED BITUMEN MEMBRANE WARM DECK ROOF COVERING Two layer, EXCEL/SPOT fully adhered waterproofing system J41 Reinforced bitumen membrane roof coverings To be read with Preliminaries/General conditions. TYPES OF COVERING 110A BUILT-UP REINFORCED BITUMEN MEMBRANE WARM DECK ROOF COVERING Two layer, EXCEL/SPOT

More information

Roofing and Cladding. ALTERNA NT-slate APPLICATION INSTRUCTIONS 11

Roofing and Cladding. ALTERNA NT-slate APPLICATION INSTRUCTIONS 11 Roofing and Cladding ALTERNA NT-slate APPLICATION INSTRUCTIONS 11 DOUBLE COVER SLATE LAYING SYSTEM 1. GENERAL Throughout the world slates have been traditionally laid on millions of roofs in a double cover

More information

Bituminous Building Paper

Bituminous Building Paper CONTENTS SUMMARY OF FEATURES... 2 TECHNICAL INFORMATION... 2 Product Description... 2 Applications... 2 Product Information... 2 Handling & Storage... 5 Technical Data... 5 Installation... 5 Size Range

More information

J41 Reinforced bitumen membrane roof coverings

J41 Reinforced bitumen membrane roof coverings J41 Reinforced bitumen membrane roof coverings To be read with Preliminaries/General conditions. A comprehensive waterproofing system comprising two reinforced bituminous membranes fully adhered to thermal

More information

Façade Cladding systems overview Angle standing seam

Façade Cladding systems overview Angle standing seam Façade Cladding systems overview Angle standing seam Cladding systems angle standing seam for façades 3 Sistemas de revestimiento - Junta alzada para fachadas Index Main characteristics 5 Principal joints

More information

SECTION BATTEN SEAM COPPER ROOFING

SECTION BATTEN SEAM COPPER ROOFING PART 1 - GENERAL 1.1 DESCRIPTION: SECTION 07 61 16 BATTEN SEAM COPPER ROOFING SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. Also delete any other item or paragraph as required

More information

Protan Exposed Membrane Roof. Your design - Our solution

Protan Exposed Membrane Roof. Your design - Our solution Protan Exposed Membrane Roof Your design - Our solution Exposed membrane roof The principle function of a roof is to provide durable protection against the external environment to a building. Unprotected

More information

Commercial Flashing Details

Commercial Flashing Details This technical note illustrates many of the most common flashing details for commercial buildings. The purpose for flashing is to direct moisture to the exterior and in so doing, prevent moisture from

More information

Specifications. Some details shown in this document have been reproduced from CCANZ document CP 01.

Specifications. Some details shown in this document have been reproduced from CCANZ document CP 01. BRICKVENEERS Specifications Bowers Brick Veneer meets the requirements of AS/NZS 4455 as a masonry brick veneer and complies with and exceeds the 15 year durability requirements as stated in the New Zealand

More information

LIQUID APPLIED WATERPROOF ROOF COATINGS

LIQUID APPLIED WATERPROOF ROOF COATINGS J31 LIQUID APPLIED WATERPROOF ROOF COATINGS To be read with Preliminaries/General conditions. TYPE(S) OF COATING 120 WARM DECK ROOF COATING Substrate: Suitable structural roof deck (e.g. Plywood, OSB3,

More information

SHEET METAL ROOF TEST REPORT

SHEET METAL ROOF TEST REPORT SHEET METAL ROOF TEST REPORT Introduction The time tested performance of the double lock standing seam and batten seam metal roofing is demonstrated by thousands of squares successfully installed by SMACNA

More information

BARREL VAULT Tile Counter Batten and Batten Installation Guide

BARREL VAULT Tile Counter Batten and Batten Installation Guide BARREL VAULT Tile Counter Batten and Batten Installation Guide www.boral.com Page2 BARREL VAULT Tile Actual Size= 43 13/16 x 15 5/8 Exposure= 43 1/4 x 14 Weight= 5.4lbs. per panel Panels per square (100

More information

ONDULINE MINI 18. The stylish Do it Once roofing upgrade for your garden buildings.

ONDULINE MINI 18. The stylish Do it Once roofing upgrade for your garden buildings. CI SfB (4-) Nn2 ONDULINE MINI 18 The stylish Do it Once roofing upgrade for your garden buildings Exciting new low profile Proven durability low maintenance roofing www.onduline.co.uk ONDULINE MINI 18

More information

INSTALLATION GUIDE.

INSTALLATION GUIDE. INSTALLATION GUIDE www.gerardusa.com INSTALLATION NOTIFICATION The installation procedures demonstrated in this manual are recommended methods for the installation of the Gerard Canyon Shake counter batten

More information

Standing Seam Systems. NBS Specification. KingZip SF Standing Seam Roofing System

Standing Seam Systems. NBS Specification. KingZip SF Standing Seam Roofing System NBS Specification KingZip SF Standing Seam Roofing System H31 METAL PROFILED/FLAT SHEET CLADDING/COVERING To be read with Preliminaries/General conditions. TYPE OF CLADDING SYSTEM 140 METAL PROFILED CLADDING

More information

INSTALLATION INSTRUCTIONS KÖSTER TPO

INSTALLATION INSTRUCTIONS KÖSTER TPO INSTALLATION INSTRUCTIONS KÖSTER Contents Contents Basics Installation Products 4 KÖSTER Characteristics 5 Mechanical fastening 7 Full surface adhesion 8 Loose installation 9 Tools 10 Welding temperature

More information

Cavity Tray Application

Cavity Tray Application Cavity Trays Cavity Tray Block Cavity Trays Page 4 Door & Window Cavity Trays Page 8 Lead Chimney Trays Page 9 Inter-loc Horizontal Cavity Trays Page 7 Lintel Cavity Trays Page 8 Brick Cavity Trays Page

More information

Thermal insulated roofing SYSTEM

Thermal insulated roofing SYSTEM Thermal insulated roofing SYSTEM VENTILATED, LIGHTWEIGHT AND INSULATED ROOF The brand new Tejas Borja SARKING SYSTEM is a complete solution for external insulated pitched roofs, designed for use both in

More information

PRODUCT OVERVIEW. The defined rib and flat tray system provides a uniquely elegant appearance.

PRODUCT OVERVIEW. The defined rib and flat tray system provides a uniquely elegant appearance. NAIL STRIP PANEL PRODUCT OVERVIEW Architectural Panel Systems Nail Strip panels are a modern solution for contemporary and heritage style wall cladding, facades and roofing projects. The defined rib and

More information

FLATDEK II DESIGN AND INSTALLATION GUIDE

FLATDEK II DESIGN AND INSTALLATION GUIDE FLATDEK II DESIGN AND INSTALLATION GUIDE LYSAGHT FLATDEK II FLATDEK II is a long-span cladding particularly suited to home improvement projects such as room additions, carports and awnings. The underside

More information

tra-load Damp Proof Courses Product and Systems Overview

tra-load Damp Proof Courses Product and Systems Overview tra-load Damp Proof Courses Product and Systems Overview Xtra-Load DPC s and Tray Systems Icopal, one of the world s largest manufacturers of waterproofing products, has long been a pioneer in the development

More information

Creative Roofscaping. Crest concrete interlocking roof tile collection. High quality micro concrete roof tiles for every type of project.

Creative Roofscaping. Crest concrete interlocking roof tile collection. High quality micro concrete roof tiles for every type of project. ROOFING TILES Crest concrete interlocking roof tile collection High quality micro concrete roof tiles for every type of project. *Planum Concrete *Planum Duo Concrete Double Pantile Double Roman Creative

More information

Creative Roofscaping. Crest concrete interlocking roof tile collection. High quality micro concrete roof tiles for every type of project.

Creative Roofscaping. Crest concrete interlocking roof tile collection. High quality micro concrete roof tiles for every type of project. ROOFING TILES Crest concrete interlocking roof tile collection High quality micro concrete roof tiles for every type of project. *Planum Concrete *Planum Duo Concrete Double Pantile Double Roman Creative

More information

Roofcoat Xtra. all- weather protection To Order FREEPHONE SEALS ROOFS 10 YEARS* SAVE s TOP QUALITY

Roofcoat Xtra. all- weather protection To Order FREEPHONE SEALS ROOFS 10 YEARS* SAVE s TOP QUALITY www.roofcoatxtra.co.uk SAVE s WITH TOP QUALITY Supplies Sealing your roof just got... Easier, quicker, cheaper and better ROOFS all- weather protection To Order 0800 02 88 272 FREEPHONE JUST ONE COAT GIVES

More information

ALLMET CONTINENTAL INSTALLATION GUIDE

ALLMET CONTINENTAL INSTALLATION GUIDE ALLMET CONTINENTAL INSTALLATION GUIDE www.allmet.com INSTALLATION NOTIFICATION The installation procedures demonstrated in this manual are recommended methods for the installation of the Allmet Continental

More information

The Imerys Beauvoise 20 Clay Tile

The Imerys Beauvoise 20 Clay Tile Cl/Sfb 47 Ng 2 The Imerys Beauvoise 20 Clay Tile Economical interlocking plain tile and clay slates Interlocking plain tile or slate 30 year durability guarantee Attractive modular size Low roof pitch

More information

PREFA Aluminiumprodukte GmbH Page 1 of 21

PREFA Aluminiumprodukte GmbH Page 1 of 21 Tender Specifications 120901 PREFA Shingles_2012 ---------------------------------------------------------------------------------- 01. Text GENERAL PRELIMINARY REMARKS Roof ----------------------------------------------------------------------------------

More information

Weep vents on the outer leaf should be installed in accordance with standard masonry practice O O P P. Example load ratio 2:1-1:5

Weep vents on the outer leaf should be installed in accordance with standard masonry practice O O P P. Example load ratio 2:1-1:5 Standard Cavity Wall Lintels rior to installation: Ensure that the Lintel width matches the wall; masonry should not overhang the lintel by more than 25mm Check the Lintel is undamaged - (has not been

More information

Hi Five. Specific Profile Data Sheet BACK. Table of Contents. Technical Drawing File Downloads

Hi Five.   Specific Profile Data Sheet BACK. Table of Contents. Technical Drawing File Downloads Specific Profile Data Sheet 1 Technical Drawing formats available AutoDesk DWG Format AutoDesk RVT Format PDF Format Hi Five Table of Contents General Profile Information 2 Material Specifications Table:

More information

Roofing systems overview Double lock standing seam

Roofing systems overview Double lock standing seam Roofing systems overview Double lock standing seam Roofing systems overview Double lock standing seam 3 Sistemas de revestimiento - Junta alzada para fachadas Index Main characteristics Principal joints

More information

ROOFING CONTRACTORS GENERAL TRADE KNOWLEDGE EXAMINATION CONTENT INFORMATION

ROOFING CONTRACTORS GENERAL TRADE KNOWLEDGE EXAMINATION CONTENT INFORMATION ROOFING CONTRACTORS GENERAL TRADE KNOWLEDGE EXAMINATION CONTENT INFORMATION Revised September 14 The General Trade Knowledge portion of the examination is administered daily in Computer Based Testing (CBT)

More information

technical drawings Cutted roof tile Levelling batten Plasma roof tile Plasma eave tile (without ribs on the lower side) C Metalic batten Linkage tile

technical drawings Cutted roof tile Levelling batten Plasma roof tile Plasma eave tile (without ribs on the lower side) C Metalic batten Linkage tile technical drawings Straight bond Cross bond Cutted roof tile Levelling batten 1 Plasma eave tile (without ribs on the lower side) C Metalic batten Linkage tile Omega batten 2 Barge tile right Gable left

More information

Installation Guide. Titan Slate. Rev102606

Installation Guide. Titan Slate. Rev102606 Installation Guide Titan Slate Rev102606 Titan Manufacturing 200 bella citta blvd. Davenport, fl 33897 Phone: (920) 716-1411 Fax: (866) 601-4395 www.titanroofsystems.com This document includes the recommended

More information

DIVISION 7 THERMAL AND MOISTURE PROTECTION

DIVISION 7 THERMAL AND MOISTURE PROTECTION DIVISION 7 THERMAL AND MOISTURE PROTECTION UCSC Campus Standards Handbook Waterproofing Standards 07100 1 SECTION 07100: WATERPROOFING STANDARDS A. Guarantee 1. Provide a guarantee on Contractor's letterhead

More information

Pol-E-Base Modified Bitumen Roof System

Pol-E-Base Modified Bitumen Roof System Pol-E-Base Modified Bitumen Roof System Specification Chemicals, Inc. produces the Pol-E-Base Built-up Roofing System as the ultimate in field applied reflective insulation roofing. It has the advantages

More information

SPECIFICATION. ~ (project name) ~ (project address) ~ (owners name)

SPECIFICATION. ~ (project name) ~ (project address) ~ (owners name) SPECIFICATION of work to be done and materials to be used in carrying out the works shown on the accompanying drawings ~ (project name) ~ (project address) ~ (owners name) Job Number: ~ Date: ~ 4311M METALCRAFT

More information

Agrément Certificate 2009/367

Agrément Certificate 2009/367 Agrément Certificate 2009/367 Copyright Agrément South Africa, November 2009 The master copy of this document appears on the website: http://www.agrement.co.za Validity Users of any Agrément certificate

More information

FUNCTIONAL REQUIREMENTS

FUNCTIONAL REQUIREMENTS FUNCTIONAL REQUIREMENTS FUNCTIONAL REQUIREMENTS 7.6 BALCONIES Workmanship i. All workmanship must be within the tolerances defined in Chapter 1 of this manual. ii. All work is to be carried out by a technically

More information

roofing ROOFING Design of the base ROOFING DETAILS

roofing ROOFING Design of the base ROOFING DETAILS DETAILS The general arrangement details and the principles to be followed at skirtings, upstands, abutments, verges, gutters and expansion joints are as details illustrated. SELECTION PARAMETERS It is

More information

WS Roofing Brochure 7/10/08 2:40 pm Page 2 ROOFING ROOFING

WS Roofing Brochure 7/10/08 2:40 pm Page 2 ROOFING ROOFING 1 The lifetime of a building begins with the choice of materials and for hundreds of years, architects and designers have been inspired by the natural beauty of slate. Through its aesthetic potential and

More information

PAGE 415. Part 9. External works. 9.1 Garages. 9.2 Drives, paths and landscaping

PAGE 415. Part 9. External works. 9.1 Garages. 9.2 Drives, paths and landscaping PAGE 415 Part 9 External works 9.2 Drives, paths and landscaping Part 9 External works Chapter CONTENTS SCOPE Clause DESIGN Design standards D1 1 Statutory requirements D2 1 Garage foundations D3 1 Garage

More information

J41 Reinforced bitumen membrane roof coverings

J41 Reinforced bitumen membrane roof coverings J41 Reinforced bitumen membrane roof coverings To be read with Preliminaries/General conditions. TYPES OF COVERING 110A BUILT-UP REINFORCED BITUMEN MEMBRANE WARM DECK ROOF COVERING, EXCEL/SPOT, warm roof

More information

CHAPTER 10: Finishes CONTENTS 10.1 PLASTERWORK ND AND 3 RD FIX FINISHES

CHAPTER 10: Finishes CONTENTS 10.1 PLASTERWORK ND AND 3 RD FIX FINISHES CONTENTS 10.1 PLASTERWORK 10.2 2 ND AND 3 RD FIX FINISHES FUNCTIONAL REQUIREMENT 10.1 Plasterwork Workmanship Design Technical Manual TS-011-09-010412 i. All workmanship must be within defined tolerances

More information

SMART ROOFS AFFORDABLE HOUSING LEISURE HOUSING STORAGE BUILDINGS BARNS GARAGES & CARPORTS GARDEN OR WOOD SHEDS.

SMART ROOFS AFFORDABLE HOUSING LEISURE HOUSING STORAGE BUILDINGS BARNS GARAGES & CARPORTS GARDEN OR WOOD SHEDS. SMART ROOFS AFFORDABLE HOUSING LEISURE HOUSING STORAGE BUILDINGS BARNS GARAGES & CARPORTS GARDEN OR WOOD SHEDS www.duracorroofing.com DURACOR www.duracorroofing.com DURACOR AN UNIVERSAL TYPE OF ROOFING

More information

J41 Reinforced bitumen membrane roof coverings

J41 Reinforced bitumen membrane roof coverings J41 Reinforced bitumen membrane roof coverings To be read with Preliminaries/General conditions. TYPES OF COVERING 110A BUILT-UP REINFORCED BITUMEN MEMBRANE WARM DECK ROOF COVERING, EXCEL/SPOT, warm roof

More information

Aftercare & Maintenance Guide

Aftercare & Maintenance Guide Aftercare & Maintenance Guide GENERAL MAINTENANCE & CLEANING OF WBS EXTERNAL WALL INSULATION SYSTEMS & WBS POLYMER CEMENT RENDERS ADDITION OF METALWORK Any metalwork to be added to the building such as

More information

IMERYS Environmental Statement

IMERYS Environmental Statement Uniclass IMERYS Environmental Statement L5211 The Imerys Huguenot HP10 Clay Tile Our commitment to sustainable development Cl/SfB (47) Ng2 Large format interlocking clay roof tiles IMERYS has a corporate

More information

SSL-175. Specifications

SSL-175. Specifications SSL-175 Specifications Everlast Metals 10 Enterprise Court Lebanon, PA 17042 Phone: (717) 270-6554 Fax: (717) 270-6569 www.everlastmetals.com 7410 Preformed Metal Roofing PART 1: GENERAL 1.01 SECTION INCLUDES

More information

HIGH PERFORMANCE WATERPROOFING TAPE WATERPROOFING TAPE THAT PERMANENTLY BONDS AND SEALS TO ALMOST ANY SURFACE

HIGH PERFORMANCE WATERPROOFING TAPE WATERPROOFING TAPE THAT PERMANENTLY BONDS AND SEALS TO ALMOST ANY SURFACE HIGH PERFORMANCE WATERPROOFING TAPE WATERPROOFING TAPE THAT PERMANENTLY BONDS AND SEALS TO ALMOST ANY SURFACE SIMPLE, RAPID REPAIRS FOR ROOFS Permanently bonds and seals to almost every construction material

More information

Battenless. Installation Guide BATTENLESS INSTALLATION GUIDE 1

Battenless. Installation Guide BATTENLESS INSTALLATION GUIDE 1 Battenless Installation Guide BATTENLESS INSTALLATION GUIDE 1 This manual provides general guidelines and procedures relating to the estimating and installation of Varitile roof products. It is not a training

More information

IMERYS Environmental Statement

IMERYS Environmental Statement Uniclass IMERYS Environmental Statement L5211 The Imerys Huguenot HP10 Clay Tile Our commitment to sustainable development Cl/SfB (47) Ng2 Large format interlocking clay roof tiles IMERYS has a corporate

More information

CHAPTER 10: Finishes CONTENTS 10.1 PLASTERWORK 10.2 SECOND AND THIRD FIX FINISHES. Chapter 10

CHAPTER 10: Finishes CONTENTS 10.1 PLASTERWORK 10.2 SECOND AND THIRD FIX FINISHES. Chapter 10 CONTENTS 10.1 PLASTERWORK 10.2 SECOND AND THIRD FIX FINISHES 283 Chapter 10 FUNCTIONAL REQUIREMENTS FUNCTIONAL REQUIREMENTS 10.1 PLASTERWORK Workmanship i. All workmanship must be within the tolerances

More information

Plywood (untreated or H3 treated) must not be allowed to come in contact with soil.

Plywood (untreated or H3 treated) must not be allowed to come in contact with soil. Plyfloor Advantages Superior strength Stiffness of Plyfloor is nearly three times that of particle type boards of the same thickness. This means thinner Plyfloor panels are cost effective floor panels.

More information

1 Exam Prep Architectural Sheet Metal Manual Tabs and Highlights

1 Exam Prep Architectural Sheet Metal Manual Tabs and Highlights 1 Exam Prep Architectural Sheet Metal Manual Tabs and Highlights These 1 Exam Prep tabs are based on the 2012 Sheet Metal and Air Conditioning Contractors' National Association, Inc., seventh edition.

More information

SLATE ROOFING INSTALLATION PROPOSAL [Last updated 10/08/2017]

SLATE ROOFING INSTALLATION PROPOSAL [Last updated 10/08/2017] [Change these specifications as needed. Use this sample proposal at your own risk. This is a simple, general proposal and is not meant to be a comprehensive proposal for all situations or projects. If

More information

Standard specification for the application of Danosa Two-Layer waterproof roofing membrane to plywood & concrete surfaces.

Standard specification for the application of Danosa Two-Layer waterproof roofing membrane to plywood & concrete surfaces. Standard specification for the application of Danosa Two-Layer waterproof roofing membrane to plywood & concrete surfaces. BRANZ Appraised No. 678 Ref: P3200 Rev 1 February 2016 Page 1 of 5 1.0 PREAMBLE:

More information

Roofing profiles. Technical specifications

Roofing profiles. Technical specifications Roofing profiles Technical specifications Roofing profiles Contents Introduction 2 EC 13 1 /2/3 3 MW5R Steel 4 Aluminium 6 1000/32mm forward Steel 8 Aluminium 10 1 914/38mm forward Steel 12 Aluminium

More information

11/09/2018 LBP licence classes

11/09/2018 LBP licence classes LBP licence classes Occupational Licensing aims to ensure that people in the building industry are competent and accountable so that homes and buildings are designed and built right first time. Summary

More information

AS Interpretation of External Waterproofing as it applies to Melbourne, Class 1 buildings

AS Interpretation of External Waterproofing as it applies to Melbourne, Class 1 buildings AS4654.2 Interpretation of External Waterproofing as it applies to Melbourne, Class 1 buildings Climate Zone: 6 Wind Class: N1 Membrane Types: Liquid Applied Class II and Class III as defined and tested

More information

BENCHMARK Evolution Axis

BENCHMARK Evolution Axis Sheet List EVO VT 00 B DIRECTION OF PREVAILING WIND VERTICAL PANEL JOINT & FASTENER LOCATIONS DIRECTION OF LAY FACTORY APPLIED WEATHER SEAL CONCEALED PANEL FIXING NOTE: FASTENER NUMBERS DEPEND ON THE ACTUAL

More information

A tile for your style

A tile for your style A tile for your style THE PRODUCT Lifestile is a premium brand of stone coated, steel roofing tiles manufactured by Mabati Rolling Mills (MRM) Ltd; your trusted name in innovative roofing solutions over

More information

STOPOREN FACADE SYSTEM APRON FLASHING

STOPOREN FACADE SYSTEM APRON FLASHING 10 REFER E2/AS1 TABLE 7 STOPEND TO PROJECT 10mm MIN. PAST FINISHED CLADDING STO VENTED ADJUSTABLE FOOT TRAY PRE FINISHED METAL APRON FLASHING PREFINISHED METAL ROOFING OVER UNDERLAY ROOF STRUCTURE 5mm

More information

WHATEVER THE CHALLENGE, PHILLIPS HAS YOU COVERED.

WHATEVER THE CHALLENGE, PHILLIPS HAS YOU COVERED. WHATEVER THE CHALLENGE, PHILLIPS HAS YOU COVERED. Build walls and ceilings with a strong base, sturdy reinforcements and much more with Phillips extensive line of high quality products. As a single source

More information

Double Lock Standing Seam

Double Lock Standing Seam Swimming Complex, Piscine (France), Designed By Brochet Lajus Preuyo, Finish: Quartz-zinc ROOFING Specification of details Technique information Please note: Main structure and insulation by others. Roofing

More information

J41 Reinforced bitumen membrane roof coverings

J41 Reinforced bitumen membrane roof coverings J41 Reinforced bitumen membrane roof coverings To be read with Preliminaries/General conditions. TYPES OF COVERING 110 BUILT-UP REINFORCED BITUMEN MEMBRANE WARM DECK ROOF COVERING Substrate: Plywood to

More information

DL-200. Specifications

DL-200. Specifications DL-200 Specifications Everlast Metals 10 Enterprise Court Lebanon, PA 17042 Phone: (717) 270-6554 Fax: (717) 270-6569 www.everlastmetals.com 7410 Structural Preformed Metal Roofing PART 1: GENERAL 1.01

More information

The Freudenberg Politex Group

The Freudenberg Politex Group Waterproofing easy to lay dimensionally stable waterproof resistant PATENT PENDING New-generation of waterproofing METHOD FOR LAYING is laid dry on both wooden and cement supports. Laying is easy and fast:

More information

BRICKWORK 3.5 BRICKWORK 1 GENERAL

BRICKWORK 3.5 BRICKWORK 1 GENERAL BRICKWORK 1 GENERAL 1.1 INSPECTION Notice Give sufficient notice so that inspection may be made of the following: - Set out of brickwork to lintels, arches and other architectural features. - Damp-proof

More information

Safety flooring the complete system

Safety flooring the complete system Technical Information Safety the complete system Safety the complete system Altro safety Altro Everlay Adhesive Screed Concrete sub-floor Preparation of sub-floors Sub-floors must be dry, sound and free

More information

Resysta Wall Cladding Installation Guidelines

Resysta Wall Cladding Installation Guidelines Resysta Wall Cladding Installation Guidelines NOTE: Proper planning of the wall cladding layout is essential for ease of installation of wall cladding boards and wall cladding components. Thoroughly read

More information

Onduline covers the world. More than 100 countries across the globe

Onduline covers the world. More than 100 countries across the globe Onduline covers the world Onduline was founded in 1950 to manufacture and market the now famous corrugated roofing sheets. The outstanding growth and success of Onduline in the last 60 years has seen the

More information

spandek optima LYSAGHT Trapezoidal steel cladding with longer spanning capability BlueScope LYSAGHT SINGAPORE roofing & walling Solutions

spandek optima LYSAGHT Trapezoidal steel cladding with longer spanning capability BlueScope LYSAGHT SINGAPORE roofing & walling Solutions BlueScope LYSAGHT SINGAPORE spandek optima Trapezoidal steel cladding with longer spanning capability Structural Solutions roofing & walling Solutions House Framing Solutions 2 SPANDEK OPTIMA TM Spandek

More information

Agrément Certificate 2011/384

Agrément Certificate 2011/384 Agrément Certificate 2011/384 Copyright Agrément South Africa, February 2011 The master copy of this document appears on the website: http://www.agrement.co.za Validity Users of any Agrément certificate

More information

SECTION COPPER STANDING SEAM ROOFING

SECTION COPPER STANDING SEAM ROOFING PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 61 16 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph as required and

More information

BRANZ Appraisal Certificate # 461 (2010) Internal wet areas.

BRANZ Appraisal Certificate # 461 (2010) Internal wet areas. SPECIFICATION FOR PROTECTO WRAP AFM-WM FOR INTERNAL WET AREAS BRANZ Appraisal Certificate # 461 (2010) Internal wet areas AFM/WM INTERNAL 0104 Page 1 AFM-WM INTERNAL SPECIFICATION PRODUCT DESCRIPTION Anti

More information

Construction Technology Revision Guide

Construction Technology Revision Guide Construction Technology Revision Guide Sub structures and Super structures Super structure (Wall, floors roof) Sub structure (Foundations) 2 Thermal Insulation Thermal insulation helps to prevent heat

More information

Agrément Certificate 17/5466 website: Product Sheet 1 LEADAX FLASHINGS LEADAX

Agrément Certificate   17/5466 website:   Product Sheet 1 LEADAX FLASHINGS LEADAX Leadax BV Vlijtweg 4 8191 JP Wapenveld The Netherlands Tel: +31 085 065 37 46 Agrément Certificate e-mail: info@leadax.com 17/5466 website: www.leadax.com Product Sheet 1 This Agrément Certificate Product

More information

Sarnavap 5000E SA Vapour Control Layer

Sarnavap 5000E SA Vapour Control Layer Roofing Product Data Sheet Edition 09.2008 Identification no. 02 09 01 05 402 0 000007 Version no. 02 Sarnavap 5000E SA Vapour Control Layer Product Description Sarnavap 5000E SA is a multi-layer self-adhesive

More information

Please Note: PhoneStar was previously branded as Phonewell

Please Note: PhoneStar was previously branded as Phonewell Soundproofing Floors Timber Joist or Concrete Floors Installation Instructions Acoustic Insulation Please Note: was previously branded as Phonewell There are two options to achieve noise reduction through

More information

Desmopol Application Guide onto Ply/OSB Deck

Desmopol Application Guide onto Ply/OSB Deck Board and Trim Selection and Application For new roofs or when overboarding is necessary, we recommend using an 18mm Far Eastern WBP plywood or 18mm OSB3 in line with standard roofing practice. Before

More information

FORTIFIED Home High Wind. Bronze New Roof Requirements

FORTIFIED Home High Wind. Bronze New Roof Requirements THE DECK (PREP MATERIAL, FASTENING) THE ROOF DECK SEALING THE ROOF DECK All existing roof cover and flashings shall be removed; deck shall be a clean, workable surface free from debris. Damaged or rotten

More information