1 AC R2 8 May 23, 2007 ICC Evaluation Service, Inc Workman Mill Road Whittier, California Attention: David Pereg, P.E. - Staff Engineer Re: Proposed Acceptance Criteria for Stay-in-place, Foam Plastic Insulating Concrete Form (ICF) Systems for Solid Concrete Walls, Subject AC R2 (DP/RK) ECO-Block, LLC has reviewed the above referenced document and is in full support of the document as written. We look forward to the implementation of this document in order to further advance the Insulating Concrete Form industry. ECO-Block, LLC Sheldon Warman, P.Eng. Technical Director Grader Street, Suite 700 ~ Dallas, TX Tel ~ Fax ~ Toll-Free

2 AC R2 8 May 22, 2007 ICC-ES Evaluation Committee ICC Evaluation Service, Inc Workman Mill Road Whittier, California Reference: Subject: AC353 Proposed Acceptance Criteria for Stay-in-place, Foam Plastic Insulating Concrete Form (ICF) Systems for Solid Concrete Walls (AC R2 (DP/RK) Objections to Proposed Structural Design Provisions Dear Sir or Madam, AC353 as proposed for the June 2007 hearing differs significantly from the proposed acceptance criteria presented at the June 2006 hearing. The cover letter dated May 1, 2007 is misleading when it excluded from the list of technical revisions in its introduction the revisions to the structural design provisions. The structural design provisions described on page 2 of the cover letter do not indicate that a significant revision has been proposed. For convenience of the Committee, the pertinent text from both cover letters, one from the June 2006 hearing and the recent letter for the June 2007 hearing, are presented here for comparison: May 1, 2006 Letter (for the June 2006 hearing): The proposed criteria is applicable to both flat and waffle-grid, solid-wall ICFs complying with IRC dimensional specification, and sets forth material test requirements and design provisions for those ICFs when they are used for construction under the IRC, International Building Code, BOCA National Building Code/1999, 1999 Standard Building Code and the 1997 Uniform Building Code. May 1, 2007 Letter (for the June 2007 hearing): The criteria is applicable to solid, flat wall ICFs complying with IRC dimensional specifications, and sets forth material test requirements and design provisions for those ICFs when they are used for construction under the IRC, the International Building Code (IBC), the BOCA National Building Code/1999 (BNBC), the 1999 Standard Building Code (SBC) and the 1997 Uniform Building

3 May 22, 2007 Page 2 ICC-ES Evaluation Committee June 6, 2007 Public Hearing Comment Submittal AC R2 (DP/RK) Code (UBC). The criteria is also applicable to waffle-grid, solid-wall ICFs complying with IRC dimensional specifications, and sets forth material test requirements and prescriptive design provisions for those ICFs when they are used for construction under the IRC, SBC and UBC. The notable difference is the waffle-grid, solid-wall ICF has been limited to the prescriptive design provisions. If the waffle-grid formed concrete wall design exceeds the applicable limits imposed on the prescriptive provisions there is no allowance to permit the use of the design provisions for concrete walls provided by the IBC and/or ACI 318. This exclusion will effectively prohibit the use of waffle-grid ICFs in large residential structures and non-residential applications. The new limitation imposed on the wafflegrid ICF is throughout the acceptance criteria; specifically in Section 1.2 and Sections , , , , and The following criterion was moved out of Structural Design - Section 3.9 (now Section 3.10). When required by the code official, calculations showing compliance with the general design requirements of Chapter 16, 18 and 19 of the IBC, BNBC or UBC, as applicable, shall be submitted to the code official for approval, except that calculations are not required when the building design is based on Section or of this criteria, or foundation design is based on IRC Section R404 or SBC Section The calculations and details shall be prepared by a registered design professional where required by the statutes of the jurisdiction in which the project is to be constructed. This statement is re-located to Section (Section 6.0 Evaluation Report Recognition) as part of Section 6.1 which states The evaluation report shall include the following information: Although the ESR report may include this wording, the proposed limitation of waffle-grid ICFs to the prescriptive provisions makes it unclear if ACI 318 can be used to design waffle-grid formed walls. The prescriptive provisions of the IRC, the SBC, and the Prescriptive Method for ICFs in Residential Construction (publication #EB118) were based on the design provisions of ACI 318 and/or the IBC. The applicability limits imposed on buildings using ICFs and the prescriptive provisions was necessary to ensure the safe use of ICF formed concrete walls in residential design. If the residential design exceeds the applicability limits or if the project is a non-residential design, the building official should require that project specific calculations be prepared to show compliance with the design requirements of the applicable code. As currently written, AC353 will limit the use of waffle-grid ICFs to residential projects which do not exceed the applicability limits of the prescriptive provisions. There is no engineering justification to exclude the waffle-grid ICF formed solid concrete wall from the design provisions allowed for the flat-wall ICF formed solid concrete wall. The same engineering design provisions used to develop the prescriptive provisions for the flat-wall and waffle-grid ICF formed walls are applicable for nonprescriptive designs.

4 May 22, 2007 Page 3 ICC-ES Evaluation Committee June 6, 2007 Public Hearing Comment Submittal AC R2 (DP/RK) The proposed wording of AC353 in regards to the structural design of waffle-grid ICFs conflicts with or lacks clarity with two current ICC and ICC-ES documents. 1. In the 2006 IRC, Section R404.4 and Section R611.1 state: Insulating Concrete Form (ICF) walls shall be designed and constructed in accordance with the provisions of this section or in accordance with the provisions of ACI 318. When ACI 318 or the provisions of this section are used to design insulating concrete form walls, project drawings, typical details and specifications are not required to bear the seal of the architect or engineer responsible for design, unless otherwise required by the state law of the jurisdiction having authority. 2. A recently issued ICC-ES report for the waffle-grid form eform TM by Reward Wall Systems, ESR 1552 dated January 1, 2007, includes structural provisions for a waffle-grid formed wall. ESR 1552 is in compliance with the 2006 IBC and 2006 IRC. In Section it states: When the eform waffle-grid ICF forms are components of buildings that do not conform to the applicability limits of Sections R and R611.2 of the IRC, or Section and of the SBC, or the structure is regulated by the IBC, BNBC, or UBC, the structural analysis and design of the concrete must be prepared in accordance with ACI 318 and Chapter 19 of the IBC, BNBC, SBC or UBC, as applicable. The structural design professional is responsible to determine the structural adequacy of a flat-wall or waffle-grid formed concrete wall in designs that are residential that exceed the applicability limits of the prescriptive provisions or for non-residential structures. If the building official is concerned for the structural adequacy of a waffle-grid formed concrete wall, they should require that a qualified design professional prepare the calculations and details in accordance with ACI 318. The waffle-grid ICF form has been used successfully for over 30-years in residential and non-residential concrete building construction. American PolySteel requests the Evaluation Committee to instruct the ICC-ES Staff to undo the revisions to the structural design provisions of AC353 to allow both the flat-wall and waffle-grid ICF formed concrete walls the same opportunity to use current code accepted design provisions when the prescriptive provisions are deemed non-applicable. Sincerely, David R. Jarmul, P.E. Director of Engineering American PolySteel, LLC Albuquerque, New Mexico

5 From: Kelvin L Doerr [mailto:kdoerr@rewardwalls.com] Sent: Tuesday, May 22, :19 AM To: Michael Beaton; David Pereg; Kurt Stochlia Cc: djarmul@polysteel.com; Vera Novak ICFA; EJ Parks; EJ Parks; Hank Pfeiffer; Edward L. Storm Subject: June 2007 ICC ES Hearing - AC353 Importance: High Gentlemen, I have noticed that the ICF waffle-grid systems have not been included in the proposed AC353 to be allowed to be designed in accordance to ACI 318. ACI 318 is referenced as the concrete design code in the 2006 IBC and IRC. A previous draft of AC353 allowed waffle-grid ICF walls to be designed in accordance to ACI 318. The most recent draft appears to have eliminated the option of designing waffle-grid ICF walls to ACI 318. This was done silently without any communication between ICC ES and the ICFA. This seems odd as the ICFA and ICC ES had been working closely together to create this AC353 proposal. There is nothing within ACI 318 that would not allow the design of waffle-grid ICF walls. Waffle-grid systems are a solid monolithic concrete wall. They are much different in that regard to screen grid and post and beam concrete walls they are continuously solid. There is no reason to exclude the design of the waffle-grid walls from ACI 318 for the following reasons. 1. ESR-1552, dated January 1, 2007, and in compliance to 2006 IBC and IRC already states that the eform waffle-grid wall can be designed in accordance to ACI Since the waffle-grid wall is a solid concrete wall, one method of design can be accomplished by using the actual cross sectional geometry and using a one foot wall cross section to develop a bending and axial interaction diagram. 3. Back in the late 90s, I visited ICBO along with other industry leaders on the behalf of the limitation of the design of waffle-grid walls to 10 feet. We successfully demonstrated to ICBO (Peter Bahlo and others) that 10 feet should not be a limit as one can design waffle-grid walls to any height according to ACI 318 within the ACI 318 limits, not a 10 foot limit. This situation or issue is no different today. 4. There is simply nothing within ACI 318 that does not permit the design of waffle-grid walls. I don t see anything within the ACI 318 design code that would not allow for design of waffle-grids to ACI 318. Structural engineers are daily always designing concrete structures with different geometries (non-rectangular) and this does not limit them. ACI does not limit solid concrete geometries. Please use this as documentation for support of designing waffle-grid ICFs to ACI 318 and this inclusion within AC353 at the upcoming June 2007 hearing. If you have any questions, please contact me. Thank you in advance for your support. Sincerely, Kelvin Doerr, P.E. AC R2 8

6 AC R2 8 THERMOMASS P.O. Box 950 BUILDING INSULATION SYSTEMS B y Com p o si te Te chnolog ies C o r p o r a tio n Date: 5/23/2007 David Pereg, P.E. Staff Engineer ICC Evaluation Service 5360 Workman Mill Road Whittier, CA Boone, IA D D Re: Proposed AC Stay-in-place Foam Plastic ICF for Solid Concrete Walls Dear Mr. Pereg, We would like to offer the following comments to the proposed AC Line number 11 includes only the material properties of the ICF and their components. We believe that some of the physical properties, especially for waffle grid ICFs, should be included in the evaluation and the report. These physical properties are required to design the walls using IBC or ACI 318. Two of the properties that are required in the design per ACI 318, chapter 14 are effective wall thickness and effective moment of inertia for waffle grid ICF. 2. Line number 71, NFPA should be referenced rather than NFPA since NFPA was approved as the American National Standard on August 18, Line number 136 refers to IRC table R611.4(2) and we do believe that it should reference to table R Section 3.3 Surface Burning Characteristics, Line number 143: Please add "(foam plastic with embedded cross ties)" after the words "foam plastic panels". The reason is that we believe cross-tie inclusion is necessary during ASTM E84 testing. The test specimen should be made of both foam insulation and cross-ties flanges since the surface burning characteristics are different with the cross-ties, which is the intended end use. 5. We believe that "room corner test" is not an optional test per section 3.5 and hence section should be removed from section 3.8 which is an optional requirement. We recommend that section be included in section 3.5 which deals with the thermal barrier. 6. Line number 236 states; "since the thermal barrier is attached to the wall using proprietary methods... " therefore we believe the material properties of the fasteners used to attach the thermal barrier should be listed and tested in Section 3.0. We believe this section should also outline the minimum number of fasteners required to secure the thermal barrier in position. 7. Section : Typically, in ICF construction the electrical outlets and chases are placed directly within field fabricated cavities made in the foam insulation. We recommend that this section include discussion on isolating the plastic foam insulation from electrical components. We also recommend that this section contain discussion on how the creation of air cavities within the foam insulation influence the flame spread characteristics of the ICF. 8. The plastic foam insulation used in ICF construction will begin to soften at 200 F, liquefy at 300 F, and ignite at 650 F. Molten and liquefied plastic are often credited with injuring both the fleeing and the rescuers. We recommend that this issue be addressed in section 3.8 by requiring the details be provided showing how egress points may be constructed to prevent the passage of molten or liquefied plastic insulation during a fire event. D TOLL FREE : D LOCAL: D FAX: D

7 Mr. David Pereg, P.E. May 23,2007 Page 2 of 2 9. Section refers to IBC, UBC or BNBC method for flat ICFs and do not reference that this section is applicable to waffle grid ICFs. If not applicable to waffle grid, an exclusion statement should be added to make it clear. 10. Section refers to Fastener Strength in plastic cross-ties. We believe that ASTM D 1761 which is designed for the mechanical fasteners in wood will not give a representative values for fasteners in the intended application unless modifications are specified. Section refers to lateral strength testing procedure and cites ASTM D In ASTM D 1761, the lateral strength of the fastener is determined by attaching two pieces of wood in lap joint configuration. We believe that this criteria should be more descriptive of performing the testing since ASTM standard is not available for this condition. Similarly, the withdrawal load strength per ASTM D 1761 will not give representative results. We also recommend that a section be added requiring fastener tests in "hot cond ition" since metallic fasteners conduct heat much faster and softens and melts the plastic cross tie flange, thus reducing the capacity of the fasteners considerably. 11. We request ICC-ES to research as to the validity of NFPA 286 for this application. r\ifpa section states that "This method does not provide data that can be generalized to apply to rooms or spaces of different shapes, sizes, and ventilation ". Since the test chamber of NFPA 286 is 12' x 8' x 8' high, and most buildings are much larger than this, will this method predict the true response of the ICF with wall covering? Section 4.3 is titled "Room Corner Fire Test" while the NFPA 286 is for a room of 4 sides and ceiling. NFPA section states "This fire test method is not intended for the evaluation of fire endurance of assemblies, nor is it intended for the evaluation of the effect of fires that originate within a wall assembly" and yet the section of this criteria uses the endurance of the thermal barrier as the acceptable condition. If NFPA 286 is the choice, then suitable modifications to the test method and specimen mounting should be added to the criteria. We recommend that the specimen mounting to the test frame should be before the wall covering are applied and also the wall covering should be mounted about W' above the floor as typically constructed in buildings. This test should also include the PVC electrical outlet box and PVC clad electric wiring which is a common practice in the building industry. 12. Line number : We recommend modifying the sentence to..."a room corner test shall be conducted in accordance with NFPA 286 for each assernbly of cross-tie and fastener for which recognition is sought". We believe this procedure should specify that ICF assemblies with plastic cross-tie flanges be tested and evaluated separately from ICF with steel cross-tie flanges. 13. Section 6.1.3: Since the fasteners are used to install the wall covering to the flanges which is a proprietary method, fastener size, type and manufacturer should be provided in addition to the loads. Sincerely, Composite Technologies Corporation \j~~~fta Venkatesh Seshappa, P.E. & S.E. Director of Engineering

October 12, Yours very truly, Gary G. Nichols, P.E., SECB Vice President. GGN/md Enclosure Evaluation Committee

October 12, Yours very truly, Gary G. Nichols, P.E., SECB Vice President. GGN/md Enclosure Evaluation Committee October 12, 2010 TO: SUBJECT: PARTIES INTERESTED IN EVALUATION REPORTS ON STAY-IN-PLACE, FOAM PLASTIC INSULATING CONCRETE FORM (ICF) SYSTEMS FOR SOLID CONCRETE WALLS Revisions to the Acceptance Criteria

More information

June 9, 2008 PARTIES INTERESTED IN EVALUATION REPORTS ON TERMITE- RESISTANT FOAM PLASTICS

June 9, 2008 PARTIES INTERESTED IN EVALUATION REPORTS ON TERMITE- RESISTANT FOAM PLASTICS ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect June 9, 2008 TO: PARTIES INTERESTED IN EVALUATION REPORTS ON TERMITE- RESISTANT FOAM PLASTICS SUBJECT: Acceptance Criteria for Termite-resistant

More information

July 23, 2010 PARTIES INTERESTED IN REFLECTIVE FOIL INSULATION

July 23, 2010 PARTIES INTERESTED IN REFLECTIVE FOIL INSULATION July 23, 2010 TO: SUBJECT: PARTIES INTERESTED IN REFLECTIVE FOIL INSULATION Revisions to the Acceptance Criteria for Reflective Foil Insulation, Subject AC02-0610-R1 (LS/RB) Dear Madam or Sir: In June

More information

DIVISION: CONCRETE SECTION: INSULATING CONCRETE FORMING REPORT HOLDER: DIVERSIFOAM PRODUCTS EVALUATION SUBJECT:

DIVISION: CONCRETE SECTION: INSULATING CONCRETE FORMING REPORT HOLDER: DIVERSIFOAM PRODUCTS EVALUATION SUBJECT: 0 ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org Most Widely Accepted and Trusted ESR 1815 Reissued 10/2018 Revised 11/2018 This report is subject to renewal 10/2020.

More information

June 1, 2010 PARTIES INTERESTED IN EVALUATION REPORTS ON REFLECTIVE FOIL INSULATION

June 1, 2010 PARTIES INTERESTED IN EVALUATION REPORTS ON REFLECTIVE FOIL INSULATION June 1, 2010 TO: PARTIES INTERESTED IN EVALUATION REPORTS ON REFLECTIVE FOIL INSULATION SUBJECT: Proposed Revisions to the Acceptance Criteria for Reflective Foil Insulation, Subject AC02-0610-R1 (LS/RB)

More information

ESR ICC Evaluation Service, Inc. Issued June 1, 2005 This report is subject to re-examination in one year.

ESR ICC Evaluation Service, Inc.   Issued June 1, 2005 This report is subject to re-examination in one year. ESR-1182 Issued June 1, 2005 This report is subject to re-examination in one year. ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office # 5360 Workman Mill Road, Whittier, California 90601

More information

ACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) PREFACE

ACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) PREFACE ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect ACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) AC191 Approved May 2008 Effective June 1, 2008 Previously approved February 2008, October 2007,

More information

June 7, 2012 PARTIES INTERESTED IN HVAC DUCT ENCLOSURE ASSEMBLIES

June 7, 2012 PARTIES INTERESTED IN HVAC DUCT ENCLOSURE ASSEMBLIES June 7, 2012 TO: PARTIES INTERESTED IN HVAC DUCT ENCLOSURE ASSEMBLIES SUBJECT: Revisions to the Acceptance Criteria for Metallic HVAC Duct Enclosure Assemblies, Subject AC179-0612-R1 (MB/CA) Dear Colleague:

More information

(800) (562) A Subsidiary of the International Code Council

(800) (562) A Subsidiary of the International Code Council ICC-ES Evaluation Report ESR-1479 Issued July 1, 2009 This report is subject to re-examination in one year. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council DIVISION:

More information

International Code Council. ICC XX Public Input Agenda based on input received on Initial Draft

International Code Council. ICC XX Public Input Agenda based on input received on Initial Draft International Code Council ICC 1100-20XX Public Input Agenda based on input received on Initial Draft For April 25 26 (revised), 2017 Public Meeting in Schiller Park, IL April 2017 - Copyright 2017 International

More information

December 3, 2012 PARTIES INTERESTED IN INTUMESCENT FIRE-RESISTANT COATINGS FIELD-APPLIED TO PREFABRICATED WOOD I-JOISTS

December 3, 2012 PARTIES INTERESTED IN INTUMESCENT FIRE-RESISTANT COATINGS FIELD-APPLIED TO PREFABRICATED WOOD I-JOISTS December 3, 2012 TO: PARTIES INTERESTED IN INTUMESCENT FIRE-RESISTANT COATINGS FIELD-APPLIED TO PREFABRICATED WOOD I-JOISTS SUBJECT: Proposed Acceptance Criteria for Intumescent Fire-resistant Coatings

More information

Issue Date: April 2003 Release: I. Product Specifications

Issue Date: April 2003 Release: I. Product Specifications Issue Date: April 2003 Release: I Product Specifications Forming System Components Standard System Commercial System Issue Date: April 2003 Release: I 1.1 Issue Date: April 2003 Release: I 1.2 Specification

More information

ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER PREFACE

ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER PREFACE ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER AC51 Approved February 2008 Effective March 1, 2008 Previously approved October 2007, January 2001,

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 4 6587 (562) 699 0543 www.icc es.org ESR 3152 Reissued 08/2017 This report is subject to renewal 08/2018. DIVISION: 07 00 00

More information

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR ANCHORED MASONRY VENEER SYSTEM WITH POLYSTYRENE FOAM PLASTIC BACKING EC 021-2014 (Adopted

More information

DIVISION: CONCRETE SECTION: INSULATING CONCRETE FORMING REPORT HOLDER: SUPERFORM PRODUCTS LTD. EVALUATION SUBJECT:

DIVISION: CONCRETE SECTION: INSULATING CONCRETE FORMING REPORT HOLDER: SUPERFORM PRODUCTS LTD. EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3466 Reissued 08/2018 This report is subject to renewal 08/2019. DIVISION: 03 00

More information

DIVISION: THERMAL AND MOISTURE SECTION: THERMAL INSULATION REPORT HOLDER: CERTAINTEED CORPORATION

DIVISION: THERMAL AND MOISTURE SECTION: THERMAL INSULATION REPORT HOLDER: CERTAINTEED CORPORATION 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-2668 Reissued 11/2017 This report is subject to renewal 11/2018. DIVISION: 07 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: CERTAINTEED CORPORATION

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: CERTAINTEED CORPORATION 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2668 Reissued 11/2017 This report is subject to renewal 11/2018. DIVISION: 07 00

More information

ICC-ES Evaluation Report Reissued September 1, 2010 This report is subject to renewal in two years.

ICC-ES Evaluation Report Reissued September 1, 2010 This report is subject to renewal in two years. ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-9 Reissued September, 200 This report is subject to renewal in two years. A Subsidiary of the International Code Council DIVISION:

More information

DIVISION: METALS SECTION: METAL FABRICATIONS REPORT HOLDER: QUALITY WAY PRODUCTS, LLC 407 HADLEY STREET HOLLY, MICHIGAN 48442

DIVISION: METALS SECTION: METAL FABRICATIONS REPORT HOLDER: QUALITY WAY PRODUCTS, LLC 407 HADLEY STREET HOLLY, MICHIGAN 48442 0 ICC ES Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 Most Widely Accepted and Trusted ESR 1729 Reissued 10/2016 This report is subject to renewal 10/2018. DIVISION: 05 00 00 METALS SECTION:

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: ENERCEPT, INC.

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: ENERCEPT, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1780 Reissued 11/2017 This report is subject to renewal 11/2019. DIVISION: 06 00

More information

Sept 30, 2004 Page 1 PRODUCT DESCRIPTION PRODUCT FEATURES

Sept 30, 2004 Page 1 PRODUCT DESCRIPTION PRODUCT FEATURES Sept 30, 2004 Page 1 PRODUCT FEATURES BASIC USES / RELATED USES LOGIX Insulated Concrete Forms are stackable, interlocking expanded polystyrene (EPS) blocks that serve as permanent formwork to create solid

More information

ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER

ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER AC51 Approved February 2008 Effective March 1, 2008 (Editorially

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIBER CEMENT SIDING REPORT HOLDER: RIEDER FASERBETON ELEMENTE GmbH

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIBER CEMENT SIDING REPORT HOLDER: RIEDER FASERBETON ELEMENTE GmbH 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2810 Reissued 02/2018 This report is subject to renewal 07/2018. DIVISION: 07 00

More information

June 22, 2009 PARTIES INTERESTED IN EVALUATION REPORTS ON COMPOSITE COLD-FORMED LIGHT GAGE STEEL AND CONCRETE MASONRY LINTELS

June 22, 2009 PARTIES INTERESTED IN EVALUATION REPORTS ON COMPOSITE COLD-FORMED LIGHT GAGE STEEL AND CONCRETE MASONRY LINTELS June 22, 2009 TO: SUBJECT: PARTIES INTERESTED IN EVALUATION REPORTS ON COMPOSITE COLD-FORMED LIGHT GAGE STEEL AND CONCRETE MASONRY LINTELS Acceptance Criteria for Composite Cold-formed Light Gage Steel

More information

Originally Issued: 11/06/2017 Valid Through: 11/30/2018

Originally Issued: 11/06/2017 Valid Through: 11/30/2018 ACCELLA POLYURETHANE SYSTEMS, LLC. SEALTITE CC+ SPRAY-APPLIED POLYURETHANE FOAM PLASTIC INSULATION CSI Section: 07 21 00 Thermal Insulation 1.0 RECOGNITION insulations described in this report have been

More information

February 1, SUBJECT: Proposed Revisions to the Acceptance Criteria for Staples, Subject AC R1 (EL/JF)

February 1, SUBJECT: Proposed Revisions to the Acceptance Criteria for Staples, Subject AC R1 (EL/JF) February 1, 2018 TO: PARTIES INTERESTED IN STAPLES SUBJECT: Proposed Revisions to the Acceptance Criteria for Staples, Subject AC201-0218-R1 (EL/JF) Dear Colleague: We are seeking your comments on proposed

More information

Advantage ICF System Product Information Bulletin

Advantage ICF System Product Information Bulletin Advantage ICF System Product Information Bulletin BULLETIN NO. ISSUED: REPLACES: 220 August 25, 2017 February 12, 2016 Intertek Code Compliance Research Report CCRR-1006 Intertek Code Compliance Research

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: FOUR SEASONS BUILDING PRODUCTS, LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: FOUR SEASONS BUILDING PRODUCTS, LLC 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2229 Reissued 05/2018 This report is subject to renewal 05/2019. DIVISION: 07 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: FUNDERMAX GMBH

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: FUNDERMAX GMBH 0 Most Widely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3340 Reissued 05/2017 This report is subject to renewal 05/2018. DIVISION: 07 00 00 THERMAL

More information

Originally Issued: 11/04/2016 Revised: 11/28/2017 Valid Through: 11/30/2018

Originally Issued: 11/04/2016 Revised: 11/28/2017 Valid Through: 11/30/2018 HUBER ENGINEERED WOODS ZIP SYSTEM R-SHEATHING CSI Section: 06 12 00 Structural Panels 06 16 00 Sheathing 1.0 RECOGNITION ZIP System R-Sheathing panels, manufactured by Huber Engineered Woods, LLC, were

More information

A Review of Thermal and Ignition Barrier Requirements for Spray Foam Insulation

A Review of Thermal and Ignition Barrier Requirements for Spray Foam Insulation A Review of Thermal and Ignition Barrier Requirements for Spray Foam Insulation Agenda Why Do Codes Require Thermal or Ignition Barriers? What is a Thermal Barrier? Where is it required? What is an Ignition

More information

April 2, 2018 PARTIES INTERESTED IN CROSS LAMINATED TIMBER PANELS USED AS COMPONENTS IN FLOOR AND ROOF DECKS

April 2, 2018 PARTIES INTERESTED IN CROSS LAMINATED TIMBER PANELS USED AS COMPONENTS IN FLOOR AND ROOF DECKS April 2, 2018 TO: PARTIES INTERESTED IN CROSS LAMINATED TIMBER PANELS USED AS COMPONENTS IN FLOOR AND ROOF DECKS SUBJECT: Proposed Revisions to the ICC-ES Acceptance Criteria for Cross-laminated Timber

More information

Legacy report on the 1997 Uniform Building Code, the 2000 International Building Code and the 2000 International Residential Code

Legacy report on the 1997 Uniform Building Code, the 2000 International Building Code and the 2000 International Residential Code LEGACY REPORT ER-4203 Reissued June 1, 2004 ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office # 5360 Workman Mill Road, Whittier, California 90601 # (562) 699-0543 Regional Office #

More information

June 1, 2012 PARTIES INTERESTED IN COLD-FORMED STEEL FRAMING MEMBERS

June 1, 2012 PARTIES INTERESTED IN COLD-FORMED STEEL FRAMING MEMBERS June 1, 2012 TO: PARTIES INTERESTED IN COLD-FORMED STEEL FRAMING MEMBERS SUBJECT: Proposed Revisions to the Acceptance Criteria for Cold-formed Steel Framing Members, Subject AC46-0612-R1 (WM/DM) Dear

More information

ESR ICC Evaluation Service, Inc. Reissued July 1, 2006 This report is subject to re-examination in two years.

ESR ICC Evaluation Service, Inc. Reissued July 1, 2006 This report is subject to re-examination in two years. ESR-1178 Reissued July 1, 2006 This report is subject to re-examination in two years. ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office # 5360 Workman Mill Road, Whittier, California

More information

DIVISION: MASONRY SECTION: CONCRETE UNIT MASONRY REPORT HOLDER: 3B CONSTRUCTION SOLUTIONS, INC.

DIVISION: MASONRY SECTION: CONCRETE UNIT MASONRY REPORT HOLDER: 3B CONSTRUCTION SOLUTIONS, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3788 Reissued 11/2017 This report is subject to renewal 11/2018. DIVISION: 04 00

More information

AC R1 # Triangle Parkway Suite 100 Norcross, Ga Phone: Fax: AC R1. September 11, 2012

AC R1 # Triangle Parkway Suite 100 Norcross, Ga Phone: Fax: AC R1. September 11, 2012 AC70-1012-R1 #12 AC70-1012-R1 #12 AC70-1012-R1 September 11, 2012 Mr. Brian Gerber Ms. Elyse Levy International Code Council Evaluation Service (ICC ES) 5360 Workman Mill Road Whittier, CA 90601 2256 RE:

More information

ESR-1061 Reissued May 1, 2011 This report is subject to renewal in two years.

ESR-1061 Reissued May 1, 2011 This report is subject to renewal in two years. ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION Section: 07 21 00 Thermal Insulation Section: 07 25 00 Water-Resistive Barriers/Weather

More information

SECTION FABRICATED WALL PANEL ASSEMBLIES. A. American Institute of Steel Construction (A.I.S.C.) "Manual of Steel Construction.

SECTION FABRICATED WALL PANEL ASSEMBLIES. A. American Institute of Steel Construction (A.I.S.C.) Manual of Steel Construction. SECTION 07 42 63 FABRICATED WALL PANEL ASSEMBLIES PART 1 GENERAL 1.1 SECTION INCLUDES A. Provide ACCEL-E steel thermal-efficient-panel wall system. 1.2 RELATED SECTIONS A. Section 05 40 00 - Cold Formed

More information

Deer Ridge Consulting, Inc.

Deer Ridge Consulting, Inc. Deer Ridge Consulting, Inc. Code Compliance Research Report 505 Deer Ridge Lane Ararat, VA 24053 Office: 276-755-9162 Fax: 866-441-1054 www.deer-ridge-consulting.com Subject: NCFI 12-008 Spray Polyurethane

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: TRESPA NORTH AMERICA, LTD.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: TRESPA NORTH AMERICA, LTD. 0 ICC ES Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 Most Widely Accepted and Trusted ESR 1687 Reissued 02/2016 This report is subject to renewal 02/2017. DIVISION: 07 00 00 THERMAL

More information

Code Compliance Research Report CCRR-0194

Code Compliance Research Report CCRR-0194 Code Compliance Research Report CCRR-0194 Issued: 09-16-2013 Renewal Due: 09-16-2018 Revised: 10-12-2017 DIVISION: 06 00 00 WOOD, PLASTICS AND COMPOSITES Section: 06 05 23 Wood, Plastic, and Composite

More information

June 1, 2009 PARTIES INTERESTED IN EVALUATION REPORTS ON STRUCTURAL WOOD-BASED PRODUCTS USED AS STUDS

June 1, 2009 PARTIES INTERESTED IN EVALUATION REPORTS ON STRUCTURAL WOOD-BASED PRODUCTS USED AS STUDS June 1, 2009 TO: PARTIES INTERESTED IN EVALUATION REPORTS ON STRUCTURAL WOOD-BASED PRODUCTS USED AS STUDS SUBJECT: Proposed Revisions to the Acceptance Criteria for Wood-based Studs, Subject AC202-0609-R1

More information

DIVISION: CONCRETE SECTION: SPECIALTY PLACED CONCRETE REPORT HOLDER: EMMEDUE S.P.A.

DIVISION: CONCRETE SECTION: SPECIALTY PLACED CONCRETE REPORT HOLDER: EMMEDUE S.P.A. 0 ICC-ES Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 Most Widely Accepted and Trusted ESR-2037 Reissued 07/2016 This report is subject to renewal 07/2018. DIVISION: 03 00 00 CONCRETE

More information

ICC ES SYSTEM SYSTEM. Trusted DIVISION: 07 SECTION: AND FINISH REPORT HOLDER: ICC-ES Evaluation. Reissued 08/2016.

ICC ES SYSTEM SYSTEM. Trusted DIVISION: 07 SECTION: AND FINISH REPORT HOLDER: ICC-ES Evaluation. Reissued 08/2016. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.orgg ESR 2562 Reissued 08/206 This report is subject to renewal 08/208. DIVISION: 07 00 00

More information

Originally Issued: 08/03/2017 Revised: 02/01/2019 Valid Through: 08/31/2019

Originally Issued: 08/03/2017 Revised: 02/01/2019 Valid Through: 08/31/2019 ACCELLA POLYURETHANE SYSTEMS, LLC. 100 Enterprise Drive Cartersville, GA 30120 Phone: (770) 607-0755 www.accellapolyurethane.com BAYSEAL CC X AND BAYSEAL CC XP SPRAY-APPLIED POLYURETHANE FOAM PLASTIC INSULATION

More information

ICBO Evaluation Service, Inc Workman Mill Road, Whittier, California

ICBO Evaluation Service, Inc Workman Mill Road, Whittier, California Reissued June 1, 2002 ICBO Evaluation Service, Inc. 5360 Workman Mill Road, Whittier, California 90601 www.icboes.org Filing Category: DESIGN Concrete DURISOL WALL FORMS FOR CONCRETE CONSTRUCTION DURISOL

More information

Code Compliance Research Report CCRR-0118

Code Compliance Research Report CCRR-0118 Code Compliance Research Report CCRR-0118 Issue Date: 12-15-2009 Revision Date: 04-30-2018 Renewal Date: 04-15-2019 DIVISION: 06 00 00 WOOD, PLASTIC, AND COMPOSITES Section: 06 63 00 - Plastic Railings

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: PARKLEX USA

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: PARKLEX USA 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3462 Reissued 09/2017 This report is subject to renewal 09/2018. DIVISION: 07 00

More information

February 1, 2018 PARTIES INTERESTED IN DECK BOARD SPAN RATINGS AND GUARDRAIL SYSTEMS (GUARDS AND HANDRAILS)

February 1, 2018 PARTIES INTERESTED IN DECK BOARD SPAN RATINGS AND GUARDRAIL SYSTEMS (GUARDS AND HANDRAILS) February 1, 2018 TO: SUBJECT: PARTIES INTERESTED IN DECK BOARD SPAN RATINGS AND GUARDRAIL SYSTEMS (GUARDS AND HANDRAILS) Proposed Revisions to the ICC-ES Acceptance Criteria for Deck Board Span Ratings

More information

DIVISION: CONCRETE SECTION: INSULATING CONCRETE FORMING REPORT HOLDER: AMVIC INCORPORATED

DIVISION: CONCRETE SECTION: INSULATING CONCRETE FORMING REPORT HOLDER: AMVIC INCORPORATED 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1269 Reissued 05/2017 This report is subject to renewal 05/2018. DIVISION: 03 00 00 CONCRETE

More information

Signage Code. H101.2 Signs exempt from permits. The following signs are exempt from the requirements to obtain a permit before erection:

Signage Code. H101.2 Signs exempt from permits. The following signs are exempt from the requirements to obtain a permit before erection: Signage Code ICC Code: Appendix H: Signs SECTION H101 GENERAL H101.1 General. A sign shall not be erected in a manner that would confuse or obstruct the view of or interfere with exit signs required by

More information

DIVISION: METALS SECTION: METAL FABRICATIONS REPORT HOLDER: AKRON PRODUCTS COMPANY

DIVISION: METALS SECTION: METAL FABRICATIONS REPORT HOLDER: AKRON PRODUCTS COMPANY 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1767 Reissued 04/2018 This report is subject to renewal 04/2020. DIVISION: 05 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: PRODEMA USA INC. EVALUATION SUBJECT:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: PRODEMA USA INC. EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3439 Reissued 07/2018 This report is subject to renewal 07/2019. DIVISION: 07 00

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: EVALUATION SUBJECT: STRUCTURAL PANELS

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: EVALUATION SUBJECT: STRUCTURAL PANELS 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2182 Reissued 08/2018 This report is subject to renewal 06/2019. DIVISION: 06 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: THE DOW CHEMICAL COMPANY

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: THE DOW CHEMICAL COMPANY 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2670 Reissued 07/2017 This report is subject to renewal 07/2019. DIVISION: 07 00

More information

Trusted ICC ES DIVISION: 07 LTD. PLASTI FAB CANADAA PLASTISPAN. Look. Conformity! Evaluation. ICC-ES Evaluation

Trusted ICC ES DIVISION: 07 LTD. PLASTI FAB CANADAA PLASTISPAN. Look. Conformity! Evaluation. ICC-ES Evaluation 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.orgg ESR 1587 Reissued 09/2017 This report is subject to renewal 09/2019. DIVISION: 07 00

More information

DIVISION: SPECIALTIES SECTION: DEMOUNTABLE PARTITIONS REPORT HOLDER: TEKNION LIMITED

DIVISION: SPECIALTIES SECTION: DEMOUNTABLE PARTITIONS REPORT HOLDER: TEKNION LIMITED 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1598 Reissued 12/2017 This report is subject to renewal 12/2019. DIVISION: 10 00

More information

~ 100 R~~UU~]ION ~ 9RIMIOS Most Wiael>: AcceBtedana Trusted

~ 100 R~~UU~]ION ~ 9RIMIOS Most Wiael>: AcceBtedana Trusted ~ ~ 100 R~~UU~]ION ~ 9RIMIOS Most Wiael>: AcceBtedana Trusted ICC-ES Evaluation Report I (800) 423-6587 I (562) 699-0543 ESR-1668* Reissued March 1, 2009 This report is subject to re-examination in two

More information

3.0 DESCRIPTION. Division: Thermal and Moisture Protection Section: Thermal Insulation

3.0 DESCRIPTION. Division: Thermal and Moisture Protection Section: Thermal Insulation Division: 07 00 00 Thermal and Moisture Protection Section: 07 21 00 Thermal Insulation Report Holder: Icynene Inc. 6747 Campobello Rd. Mississauga, Ontario L5N 2L7 CANADA (905)363-4040 www.icynene.com

More information

International Code Council ICC XX Public Input Agenda based on input received on Initial Draft

International Code Council ICC XX Public Input Agenda based on input received on Initial Draft International Code Council ICC 1100-20XX Public Input Agenda based on input received on Initial Draft For October, 2018 Public Teleconference Meeting October 2018 - Copyright 2018 International Code Council,

More information

Originally Issued: 03/31/2017 Revised: 03/15/2018 Valid Through: 03/31/2018

Originally Issued: 03/31/2017 Revised: 03/15/2018 Valid Through: 03/31/2018 OLDCASTLE ARCHITECTURAL INSULTECH CSI Sections: 04 22 00 Concrete Unit Masonry 04 22 00.13 Concrete Unit Veneer Masonry 1.0 RECOGNITION Oldcastle Architectural Insultech insulated concrete masonry unit

More information

Prescriptive Engineering Helix TM Above Grade Tables

Prescriptive Engineering Helix TM Above Grade Tables Prescriptive Engineering Helix TM Above Grade Tables TECHNICAL BULLETIN. ENGINEERING DESIGN 1.05.05 Fox Blocks in collaboration with Helix Steel has developed alternative prescriptive reinforcement tables

More information

DIVISION: FINISHES SECTION: GYPSUM BOARD REPORT HOLDER: PANEL REY, S.A.

DIVISION: FINISHES SECTION: GYPSUM BOARD REPORT HOLDER: PANEL REY, S.A. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3831 Reissued 12/2017 This report is subject to renewal 12/2018. SECTION: 09 29 00

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD I JOISTS REPORT HOLDER: STARK TRUSS COMPANY, INC.

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD I JOISTS REPORT HOLDER: STARK TRUSS COMPANY, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 2 6587 (562) 699 05 www.icc es.org ESR 2919 Reissued 11/2017 This report is subject to renewal 11/2019. DIVISION: 06 00 00 WOOD,

More information

DIVISION: CONCRETE SECTION: INSULATING CONCRETE FORMING REPORT HOLDER: NUDURA CORPORATION EVALUATION SUBJECT:

DIVISION: CONCRETE SECTION: INSULATING CONCRETE FORMING REPORT HOLDER: NUDURA CORPORATION EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2092 Reissued 11/2018 This report is subject to renewal 11/2020. DIVISION: 03 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: RHINO LININGS CORPORATION

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: RHINO LININGS CORPORATION 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-2100 Reissued 02/2017 This report is subject to renewal 02/2018. DIVISION: 07 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: WATER-RESISTIVE BARRIERS/WEATHER BARRIERS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: WATER-RESISTIVE BARRIERS/WEATHER BARRIERS 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1504 Reissued 03/2017 This report is subject to renewal 03/2018. DIVISION: 07 00

More information

Combustible Exterior Wall Cladding Systems: An ICC Perspective

Combustible Exterior Wall Cladding Systems: An ICC Perspective Combustible Exterior Wall Cladding Systems: An ICC Perspective The tragic Grenfell Tower fire in London brought extensive public focus on combustible exterior wall systems, often called cladding, prompting

More information

December 1, 2014 PARTIES INTERESTED IN STRUCTURAL WOOD-BASED PRODUCTS

December 1, 2014 PARTIES INTERESTED IN STRUCTURAL WOOD-BASED PRODUCTS December 1, 2014 TO: PARTIES INTERESTED IN STRUCTURAL WOOD-BASED PRODUCTS SUBJECT: Proposed Revision to the ICC-ES Acceptance Criteria for Structural Wood-Based Products, Subject AC47-1214-R2-2 (JF/PC)

More information

The Perfect Block OEM ICC Equivalent Product Compliance Report

The Perfect Block OEM ICC Equivalent Product Compliance Report 8960 W. Larkspur Drive, Ste. 105 Peoria AZ. 85381 Phone 888.623.ICCF (4223) Email: info@theperfectblock.com Manufacturer: The Perfect Block OEM ICC Equivalent Product Compliance Report Eco Building Systems

More information

ACCEPTANCE CRITERIA FOR WATER-RESISTIVE BARRIERS PREFACE

ACCEPTANCE CRITERIA FOR WATER-RESISTIVE BARRIERS PREFACE ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect ACCEPTANCE CRITERIA FOR WATER-RESISTIVE BARRIERS AC38 Approved June 2004 Effective July 1, 2004 Previously approved July 2000, September 1990 PREFACE

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) LLC 0 ICC ES Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 Most Widely Accepted and Trusted ESR 3210 Valid: 03/15 to 03/16 DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 21

More information

Rosalind Fazel. Comments on Criteria AC212. David A Johnston EIFS Industry Members Associat

Rosalind Fazel. Comments on Criteria AC212. David A Johnston EIFS Industry Members Associat Rosalind Fazel From: Sent: To: Subject: Attachments: djohnston@eima.com Wednesday, October 31, 2012 2:54 PM Rosalind Fazel AC212 Comments Attachment to EIMA Comments on AC212 10-30-2012.pdf; ICC-ES Ltr

More information

Session: Approving and Selecting Building Products with Confidence - What To Look for in Evaluation Reports

Session: Approving and Selecting Building Products with Confidence - What To Look for in Evaluation Reports Session: Approving and Selecting Building Products with Confidence - What To Look for in Evaluation Reports Approving and Selecting Building Products with Confidence - What To Look for in Evaluation Reports

More information

Code Compliance Research Report CCRR-1060

Code Compliance Research Report CCRR-1060 Code Compliance Research Report CCRR-1060 Issue Date: 05-06-2016 Revision Date: 02-13-2018 Renewal Date: 01-01-2019 DIVISION: 03 00 00 CONCRETE Section: 03 11 19 Insulating Concrete Forming REPORT HOLDER:

More information

REPORT HOLDER: OMEGA PRODUCTS INTERNATIONAL, INC CALIFORNIA AVENUE CORONA, CALIFORNIA EVALUATION SUBJECT:

REPORT HOLDER: OMEGA PRODUCTS INTERNATIONAL, INC CALIFORNIA AVENUE CORONA, CALIFORNIA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (00) 423-657 (562) 699-0543 www.icc-es.org ESR-2064 Reissued 11/2017 This report is subject to renewal 11/201. DIVISION: 07 00 00

More information

REPORT HOLDER: UNITED DURALUME PRODUCTS, INC. EVALUATION SUBJECT: DURACOOL COMPOSITE STRUCTURAL INSULATED PANELS

REPORT HOLDER: UNITED DURALUME PRODUCTS, INC. EVALUATION SUBJECT: DURACOOL COMPOSITE STRUCTURAL INSULATED PANELS 0 ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org Most Widely Accepted and Trusted ESR 3779 Reissued 01/2017 Revised 10/2018 This report is subject to renewal 01/2019.

More information

** REVISED BY THE CITY OF LOS ANGELES

** REVISED BY THE CITY OF LOS ANGELES ICC-ES Evaluation Report ESR-90 Reissued December, 2009 This report is subject to re-examination in two years. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council

More information

February 22, To whom it may concern. Reference: Coatings for Demilec foams.

February 22, To whom it may concern. Reference: Coatings for Demilec foams. February 22, 2011 To whom it may concern. Reference: Coatings for Demilec foams. All of Demilec s foams are totally compliant with the 2003, 2006 and 2009 editions of the International Building Codes (IBC)

More information

October 3, Section 1.2 Scope and Section 6.6 were revised to clarify interior and exterior construction types allowed.

October 3, Section 1.2 Scope and Section 6.6 were revised to clarify interior and exterior construction types allowed. October 3, 2016 TO: PARTIES INTERESTED IN EVALAUTION REPORTS ON FIBER- REINFORCED POLYMER (FRP) COMPOSITE COLUMNS USED AS AXIAL LOAD-BEARING AND NONLOAD-BEARING ARCHITECTURAL AND DECORATIVE COLUMNS SUBJECT:

More information

ESR-1794* Reissued September 1, 2012 This report is subject to renewal November 1, 2014.

ESR-1794* Reissued September 1, 2012 This report is subject to renewal November 1, 2014. ICC-ES Evaluation Report www.icc-es.org (800) 4-6587 (56) 699-054 ESR-794* Reissued September, 0 This report is subject to renewal November, 04. A Subsidiary of the International Code Council DIVISION:

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER: 0 Most idely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-687 (62) 699-043 www.icc-es.org ESR-199 Reissued 0/2017 This report is subject to renewal 0/2019. DIVISION: 07 00 00 THERMAL AND MOISTURE

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 4073 Issued 08/2017 This report is subject to renewal 08/2018. DIVISION: 07 00 00

More information

ATI Evaluation Service A Division of Architectural Testing Certification Services

ATI Evaluation Service A Division of Architectural Testing Certification Services ATI Evaluation Service A Division of Architectural Testing Certification Services Subject to Renewal: 04/08/2014 Issued: 04/08/2013 Visit www.ati-es.com for current status Revision: 11/11/2013 Page 1 of

More information

ACCEPTANCE CRITERIA FOR ROOF UNDERLAYMENT FOR USE IN SEVERE CLIMATE AREAS PREFACE

ACCEPTANCE CRITERIA FOR ROOF UNDERLAYMENT FOR USE IN SEVERE CLIMATE AREAS PREFACE ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect ACCEPTANCE CRITERIA FOR ROOF UNDERLAYMENT FOR USE IN SEVERE CLIMATE AREAS AC48 Approved January 2000 Effective February 1, 2000 (Editorially revised

More information

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS SECTION: PRECAST STRUCTURAL CONCRETE SECTION: SITE CAST CONCRETE

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS SECTION: PRECAST STRUCTURAL CONCRETE SECTION: SITE CAST CONCRETE 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2873 Issued 09/2017 This report is subject to renewal 09/2018. DIVISION: 03 00 00

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: FOUR SEASONS SOLAR PRODUCTS

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: FOUR SEASONS SOLAR PRODUCTS 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2445 Reissued 08/2017 This report is subject to renewal 08/2018. DIVISION: 06 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: REFLECTIX INCORPORATED

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: REFLECTIX INCORPORATED 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1362 Reissued 05/2017 This report is subject to renewal 05/2018. DIVISION: 07 00 00 THERMAL

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: CHEMICAL BROTHERS INTERNATIONAL, LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: CHEMICAL BROTHERS INTERNATIONAL, LLC 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3458 Reissued 11/2016 This report is subject to renewal 11/2017. DIVISION: 07 00 00 THERMAL

More information

ESR-2847 Reissued September 1, 2013 This report is subject to renewal September 1, 2015.

ESR-2847 Reissued September 1, 2013 This report is subject to renewal September 1, 2015. ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-2847 Reissued September 1, 2013 This report is subject to renewal September 1, 2015. A Subsidiary of the International Code Council

More information

REPORT HOLDER: R.L. ADAMS PLASTICS, INC CROSSROADS COMMERCE PARKWAY WYOMING, MICHIGAN EVALUATION SUBJECT: POLYCORE BRAND INSULATION

REPORT HOLDER: R.L. ADAMS PLASTICS, INC CROSSROADS COMMERCE PARKWAY WYOMING, MICHIGAN EVALUATION SUBJECT: POLYCORE BRAND INSULATION 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3914 Reissued 10/2017 This report is subject to renewal 10/2018. DIVISION: 07 00

More information

Code Compliance Research Report CCRR 0270

Code Compliance Research Report CCRR 0270 Code Compliance Research Report CCRR 0270 Issued: 12 22 2017 Revised: 01 17 2018 Renewal Due: 12 22 2018 DIVISION: 06 WOOD, PLASTICS, AND COMPOSITES Section: 06 65 00 Plastic Trim DIVISION: 07 THERMAL

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: CHEMICAL BROTHERS INTERNATIONAL, LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: CHEMICAL BROTHERS INTERNATIONAL, LLC 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3458 Reissued 11/2016 This report is subject to renewal 11/2017. DIVISION: 07 00

More information

ATI Evaluation Service A Division of Architectural Testing Certification Services PCA-125

ATI Evaluation Service A Division of Architectural Testing Certification Services PCA-125 ATI Evaluation Service A Division of Architectural Testing Certification Services PCA-125 Subject to Renewal: 04/15/2017 Issued: 05/06/2016 Visit www.ati-es.com for current status Page 1 of 14 TAMKO Building

More information

1. ICC ES AC51 Draft Changes, Masonry Veneer Manufacturers Association (MVMA) Comments, dated September 24, 2007, compiled by John Woestman.

1. ICC ES AC51 Draft Changes, Masonry Veneer Manufacturers Association (MVMA) Comments, dated September 24, 2007, compiled by John Woestman. #15 ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect To: From: ICC-ES Evaluation Committee Elyse Levy, S.E. Date: October 5, 2007 Subject: Proposed Revisions to the Acceptance Criteria for Precast

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: AIR BARRIERS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: AIR BARRIERS REPORT HOLDER: 0 ICC ES Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 Most Widely Accepted and Trusted ESR 2717 Reissued 07/2015 This report is subject to renewal 07/2017. DIVISION: 07 00 00 THERMAL

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PLASTICS SECTION: PLASTIC RAILINGS REPORT HOLDER:

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PLASTICS SECTION: PLASTIC RAILINGS REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3415 Reissued 09/2017 This report is subject to renewal 09/2019. DIVISION: 06 00

More information

Originally Issued: 2/12/2016 Revised: 07/28/2017 Valid Through: 2/28/2018

Originally Issued: 2/12/2016 Revised: 07/28/2017 Valid Through: 2/28/2018 EVALUATION SUBJECT: FOAMSULATE 50 AND FOAMSULATE 210 SPRAY-APPLIED POLYURETHANE FOAM PLASTIC INSULATION REPORT HOLDER: Accella Polyurethane Systems 100 Enterprise Drive Cartersville, GA 30120 (770) 607-0755

More information