Acoustic Testing of CLT and Glulam Floor Assemblies Nordic Engineered Wood Report No. A August 2016 CONSTRUCTION
|
|
- Elvin McBride
- 6 years ago
- Views:
Transcription
1 CONSTRUCTION Acoustic Testing of CLT and Glulam Floor Assemblies Nordic Engineered Wood Report No. A August 2016 The results in this report only apply to the specimen that was tested Page 1 of 103
2
3
4 Construction Acoustics Laboratory Client Report A This page was intentionally left blank Page 2 of 101
5 Client Report A Construction Acoustics Laboratory Table of Contents Summary... 4 Summary Table of Full Floor Assemblies... 5 Summary Table of Flooring Patches Tested on Floor Assemblies... 8 Analysis... 9 Bare CLT vs. bare glulam... 9 Same toppings on CLT and glulam Precast concrete toppings vs. dry toppings Precast concrete toppings vs. OSB raft topping vs. OSB raft topping with concrete topping Floor patches improving impact ratings Other Considerations Standard Test Reports APPENDIX: ASTM E APPENDIX: ASTM E Page 3 of 101
6 Construction Acoustics Laboratory Client Report A Summary This report contains the transmission loss (TL) results measured in accordance with ASTM E90-09 and the normalized impact sound pressure level (NISPL) results measured in accordance with ASTM E of 13 cross-laminated timber (CLT) floor assemblies and 5 glulam floor assemblies. The report also contains the nonstandard impact sound pressure level results measured on 6 different small patch specimens. Summary tables containing the specimen number, sketch, short description, the sound transmission class (STC) and impact isolation class (IIC) ratings, as well as, the page number of the detailed test reports are provided starting on page 5. A brief analysis of the floors tested as part of this test series is provided after the summary tables on page 9. The standard test reports of the tested floor assemblies begin on page 16. The floor assemblies were built and tested between January and April Page 4 of 101
7 Client Report A Construction Acoustics Laboratory Table of Full Floor Assemblies Specimen ID Sketch and Short Description STC Rating IIC Rating Page Number A F Bare CLT 5 ply (131 mm) A F SonoDeck on CLT 5 ply (131 mm) A F Fermacell 2E31 on CLT 5 ply (131 mm) A F mm precast concrete slab on 25 mm SonusWave placed on top of a CLT 5 ply (131 mm) A F mm precast concrete slab on 25 mm SonusWave placed on top of a CLT 5 ply (131 mm) A F mm precast concrete slab on 32 mm Roxul ComfortBoard IS placed on top of a CLT 5 ply (131 mm) A F Bare glulam decking (89 mm) A F Fermacell 2E31 on glulam decking (89 mm) A F mm precast concrete slab on 25 mm SonusWave placed on top of a glulam decking (131 mm) Page 5 of 101
8 Construction Acoustics Laboratory Client Report A Specimen ID Sketch and Short Description STC Rating IIC Rating Page Number A F mm precast concrete slab placed directly on a OSB wood raft with sand on top of a CLT 5 ply (131 mm) A F mm precast concrete slab on 17 mm SonusWave placed on a OSB wood raft with sand on top of a CLT 5 ply (131 mm) A F OSB wood raft with sand on top of a CLT 5 ply (131 mm) A F Fermacell 2E31 placed on OSB wood raft with sand on top of a CLT 5 ply (131 mm) A F SonoDeck placed on OSB wood raft with sand on top of a CLT 5 ply (131 mm) A F mm precast concrete slab on 17 mm SonusWave placed on a OSB wood raft (no sand) on top of a CLT 5 ply (131 mm) A F mm precast concrete slab on 17 mm SonusWave placed on a OSB wood raft (no sand) with glass fiber batts on top of a CLT 5 ply (131 mm) Page 6 of 101
9 Client Report A Construction Acoustics Laboratory Specimen ID Sketch and Short Description STC Rating IIC Rating Page Number A F OSB wood raft with sand on top of glulam decking (89 mm) A F mm precast concrete slab on 17 mm SonusWave placed on a OSB wood raft on top of glulam decking (89 mm) Page 7 of 101
10 Construction Acoustics Laboratory Client Report A Table of Flooring Patches Tested on Floor Assemblies Specimen ID Sketch and Short Description STC Rating IIC Rating Page Number A SF N/A Small patch of Fermacell 2E31 on 70 mm precast concrete slab on 25 mm SonusWave placed on top of a CLT 5 ply (131 mm) A SF N/A Small patch of laminate floor on AcoustiTech Premium on 70 mm precast concrete slab on 32 mm Roxul ComfortBoard IS placed on top of a CLT 5 ply (131 mm) A SF N/A Small patch of laminate floor on Roberts Soft Stride on 70 mm precast concrete slab on 32 mm Roxul ComfortBoard IS placed on top of a CLT 5 ply (131 mm) A SF N/A Small patch of premium laminate floor on Roberts Soft Stride 70 mm precast concrete slab on 32 mm Roxul ComfortBoard IS placed on top of a CLT 5 ply (131 mm) A SF N/A Small patch of laminate floor on Roberts Soft Stride on 38 mm precast concrete slab on 17 mm SonusWave placed on a OSB wood raft (no sand) with glass fiber batts on top of a CLT 5 ply (131 mm) A SF N/A Small patch of laminate floor on Roberts Soft Stride on 38 mm precast concrete slab on 17 mm SonusWave placed on a OSB wood raft on top of glulam decking (89 mm) Page 8 of 101
11 Client Report A Construction Acoustics Laboratory Analysis The objective of this testing series was to obtain a set of floors with good airborne sound insulation rating (STC +) and good impact sound insulation rating (IIC +). A test matrix of CLT and glulam floors with various precast and dry toppings was established. This brief analysis section compares the 1/3-octave airborne transmission loss (TL) and normalized impact sound pressure levels (NISPL), as well as the single number ratings (STC and IIC) to identify toppings and coverings that perform the best on CLT and glulam floor assemblies. Bare CLT vs. bare glulam Graph 1: Airborne TL 100 Graph 2: Light Impact NISPL Airborne Sound Transmission Loss, TL, in db Normalized Impact Sound Pressure Levels, NISPL, in db Frequency, f, in Hz Frequency, f, in Hz Legend Specimen Number STC IIC 1 CLT131 A F GLAM89 A F The TL and the NISPL of the bare 131 mm CLT and the bare 89 mm glulam floor assemblies are compared in Graph 1 and 2. The blue curves in the above graphs show that the CLT outperforms the glulam bare floor assembly. Looking at the legend below the graphs, the CLT floor is 4 STC points and 2 IIC points better than the glulam floor. The higher STC and IIC rating of the CLT floor correspond to the increase in the bare floor thickness and consequently a greater area density and stiffness. Page 9 of 101
12 Construction Acoustics Laboratory Client Report A Same toppings on CLT and glulam Graph 3: Airborne TL Graph 4: Light Impact NISPL Airborne Sound Transmission Loss, TL, in db Normalized Impact Sound Pressure Levels, NISPL, in db Frequency, f, in Hz Frequency, f, in Hz Legend Specimen Number STC IIC 1 CLT131 A F GLAM89 A F OSB18_WB64(610)_RUB10_SAND_CLT131 A F OSB18_WB64(610)_RUB10_SAND_GLAM89 A F PCON38_SonusWave17_OSB18_WB64(610)_RUB10_SAND_CLT13 A F 66 6 PCON38_SonusWave17_OSB18_WB64(610)_RUB10_SAND_GLAM A F The TL and the NISPL of the bare CLT, the bare glulam, the CLT with two toppings and the glulam with two toppings (38 mm precast concrete and OSB raft) are shown in Graph 3 and 4. In the above graphs, there are three pairs of curves which correspond to the pair of CLT and glulam floors with no topping, with the precast concrete topping and with the OSB raft. There are slight differences in the individual TL and NISPL curves of the CLT and the glulam with the same topping. The TL curves of the CLT base floor (aqua, green and blue) are above those with a glulam base floor (orange, purple and red respectively). The STC and IIC ratings of the CLT and glulam floors with the same topping (heavy and/or decoupled) achieve similar values (±1 STC or IIC) as seen in the legend below the graphs. Although the TL and NISPL curves of both type of floors with the same toppings follow the same trend, they are not superimposed. The single number ratings (STC and IIC) of both floor types with the same topping indicate that the rated overall performance is similar (±1 STC or IIC). Page 10 of 101
13 Client Report A Construction Acoustics Laboratory Precast concrete toppings vs. dry toppings Graph 5: Airborne TL Graph 6: Light Impact NISPL Airborne Sound Transmission Loss, TL, in db Normalized Impact Sound Pressure Levels, NISPL, in db Frequency, f, in Hz Frequency, f, in Hz Legend Specimen Number STC IIC 1 PCON38_SonusWave25_CLT131 A F PCON70_SonusWave25_CLT131 A F PCON70_ComfortBoardIS32_CLT131 A F SonoDeck_CLT131 A F Fermacell[2E31]_CLT131 A F The TL and NISPL of CLT floor assemblies with a precast concrete topping (38 mm or 70 mm) and with dry panelized toppings are compared in Graph 5 and 6. TL curves of the CLT floors with a concrete precast topping on a resilient membrane (blue, green and red) are higher that the curves of the CLT floors with dry panelized toppings (purple and aqua). The difference in TL between the different precast concrete thicknesses (blue vs red) or the type of interlayer (red vs green) is not significant. For the NISPL curves, the floors with the precast concrete topping (blue, green and red) are better than those with the dry panelized toppings (purple and aqua). In terms of IIC rating, as shown in the legend below the graph, the best floor assembly is the one with the 38 mm precast concrete on the SonusWave 25 mm rubber mat with IIC 49. The mass of precast concrete toppings of 38 mm (98.6 kg/m 2 ) and 70 mm (165.8 kg/m 2 ) outweigh the mass of the SonoDeck (13.5 kg/m 2 ) and that of the Fermacell (26.0 kg/m 2 ). For poured or precast concrete slabs (06F vs. 07F), the increase from the 38 mm to the 70 mm precast is not noticeable for STC rating (STC 56 each) and has a unexpected, possibly unrepeatable, negative effect for the IIC rating (IIC 49 to 46). Page 11 of 101
14 Construction Acoustics Laboratory Client Report A Precast concrete toppings vs. OSB raft topping vs. OSB raft topping with concrete topping Graph 7: Airborne TL Graph 8: Light Impact NISPL Airborne Sound Transmission Loss, TL, in db Normalized Impact Sound Pressure Levels, NISPL, in db Frequency, f, in Hz Frequency, f, in Hz Legend Specimen Number STC IIC 1 CLT131 A F PCON38_SonusWave25_CLT131 A F PCON70_SonusWave25_CLT131 A F OSB18_WB64(610)_RUB10_SAND_CLT131 A F PCON38_OSB18_WB64(610)_RUB10_SAND_CLT131 A F PCON38_SonusWave17_OSB18_WB64(610)_RUB10_GFB65_CLT131 A F 54 7 PCON38_SonusWave17_OSB18_WB64(610)_RUB10_SAND_CLT13 A F 66 A set of CLT floors with precast concrete toppings and various OSB raft configurations are compared in Graph 7 and 8. Comparing all the TL and NISPL results of the floors tested, the best floor assembly is the one with the OSB raft topping which includes a 38 mm precast concrete topping on top of 17 mm SonusWave (A F the light blue curve) and achieves STC 66 and IIC as shown in the legend below the graph. Removing the sand fill from the best assembly (26F) and substituting it with glass fiber batts (A F) or removing the SonusWave from the best assembly (26F) (A F) achieves lower TL and NISPL results. The installation of the OSB raft is beneficial since it highly decouples the rigid CLT floor. The mass of the sand also increases the area density. Page 12 of 101
15 Client Report A Construction Acoustics Laboratory Floor patches improving impact ratings 80 Graph 9: Light Impact NISPL 70 Normalized Impact Sound Pressure Levels, NISPL, in db Frequency, f, in Hz Legend Specimen Number STC IIC 1 PCON70_ComfortBoardIS32_CLT131 A F *Small Patch*LAM8_SoftStride_PCON70_ComfortBoardIS32_CLT13 A SF N/A 51 3 PCON38_SonusWave17_OSB18_WB64(610)_RUB10_GFB65_CLT131 A F 54 4 *Small Patch*LAM8_SoftStride_PCON38_SonusWave17_OSB18_WB A SF N/A 58 The NISPL results of non-standard light impact tests of laminate flooring with panelized toppings on select CLT floor assemblies are shown in Graph 9. The best CLT floor assembly (in purple) with the lowest NISPL curve is composed of a patch of laminate flooring on a 38 mm precast concrete topping on 17 mm SonusWave rubber membrane on top of the OSB raft. The addition of laminate flooring to the bare concrete surfaces improves the NISPL curves; moving from the blue to the red curve, or from the green to the purple curve. The IIC improves by 6 or 4 points respectively for those two set of curves as shown in the legend under the graph. In general, the improvement of IIC ratings due to the addition of coverings will be more noticeable for floors where the IIC ratings are limited at mid to high frequencies and for reference floors that have lower IIC ratings. Page 13 of 101
16 Construction Acoustics Laboratory Client Report A Other Considerations Varying the thickness of the CLT or glulam floor One CLT floor thickness (131 mm) and one glulam floor thickness (89 mm) were evaluated as part of this floor test series. As seen in Graph 3 and 4, the test results show that CLT or glulam floors with the same topping achieve similar TL and NISPL values as well as STC and IIC ratings (±2). It is expected that an increase in the thickness of the base floor assembly will not degrade the TL or NISPL values. Precast vs. poured concrete toppings As part of this test series, no comparisons were performed for precast vs. poured concrete toppings. In referring to report A and the floor tests reported there, it is expected that STC ratings will remains the same or improve for poured toppings (vs. precast), whereas it is expected that IIC ratings will decrease. The improvement or deterioration of the STC and IIC is strongly dependent on the mass of the topping and the resiliency of the underlayment. Specifications for sand fill For this project, silica sand #71 was used as fill under the OSB raft but any other sand or fill with a density varying between 1400 kg and 1700 kg could be used as a substitute without significant change to IIC and STC ratings. It is important that the sand or fill be dry, remains loose and that only sand types approved to be installed in buildings are used. In-situ vs. laboratory results The laboratory sound insulation results measured according to ASTM E90 and ASTM E492 represent an upper limit of the direct sound insulation that can be measured in-situ. A number of factors influence the in-situ performance, for example: flanking sound transmission, specimen size, specimen coupling and construction workmanship. Page 14 of 101
17 Client Report A Construction Acoustics Laboratory This page is intentionally left blank Page 15 of 101
18 Construction Acoustics Laboratory Client Report A Client Nordic Engineered Wood 1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2 Specimen Bare CLT 5 ply (131 mm) Specimen ID A F Construction Date: January 22, 2016 Specimen Description CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3 ) long spaced 5 mm (12 ) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT. Specimen Properties Element Cross-section of A F Actual thickness (mm) Mass (kg) Mass/length, area or volume 131 mm CLT 5 ply kg/m 2 Total kg/m 2 Test Specimen Installation The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was m 2 (4.71 m x 3.79 m). The total area of the floor assembly resting on top of the lip was m 2 (4.88 m x 3.96 m). The mass per area of the elements above the lip was calculated using the total area (19.32 m 2 ). Page 16 of 101
19 Client Report A Construction Acoustics Laboratory This page is intentionally left blank Page 17 of 101
20 Construction Acoustics Laboratory Client Report A ASTM E90 Test Results Airborne Sound Transmission Loss Client: Nordic Engineered Wood Test ID: TLF Specimen ID: A F Date of Test: January 25, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 34.7 Area S of test specimen: m 2 Lower to to 38.1 Mass per unit area: 69.5 kg/m 2 f (Hz) Airborne TL (db) 100 STC Airborne Sound Transmission Loss, TL, in db Sound Transmission Class (STC) Sum of Deficiencies (db) 24 Max. Deficiency (db) 6 db at 400 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E The dotted line (may be above the displayed range) is 10 db below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss. Page 18 of 101
21 Client Report A Construction Acoustics Laboratory ASTM E492 Test Results Normalized Impact Sound Pressure Levels Client: Nordic Engineered Wood Test ID: IIF Specimen ID: A F Date of Test: January 12, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 31.5 Area S of test specimen: m 2 Lower to to 38.9 Mass per unit area: 69.5 kg/m 2 f (Hz) NISPL (db) 100 IIC Impact Insulation Class (IIC) 22 Normalized Impact Sound Pressure Level, NISPL, in db Sum of Positive Differences (db) 26 Max. Positive Difference (db) 7 db at 10 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine with the exception that the temperature the lower room fell below 17 ºC. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 db above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E The reported values of NISPL have been corrected according to the procedure outlined in ASTM E Page 19 of 101
22 Construction Acoustics Laboratory Client Report A Client Nordic Engineered Wood 1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2 Specimen SonoDeck on CLT 5 ply (131 mm) Specimen ID A F Construction Date: January 29, 2016 to February 1, 2016 Specimen Description Topping: SonoDeck engineered acoustic panels from InsulFloor measuring 800 mm x 1220 mm x 25 mm (31.5 x 48 x 1 ) are composed of two layers of 9.5 mm (3/8 ) OSB glued together with 6 mm (1/4 ) fiberglass mat on the bottom. The 25 mm (1 ) overlapping joints of the panels were glued and stapled using 18 Ga. ¼ x ¾ narrow crown staples along the joints every 5 mm (12 ). Each row of SonoDeck panels was offset by half a panel length (400 mm). The gap between the SonoDeck and the test frame was filled with closed cell polyethylene foam. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3 ) long spaced 5 mm (12 ) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT. Specimen Properties Element Cross-section of A F Actual thickness (mm) Mass (kg) Mass/length, area or volume 25 mm SonoDeck engineered acoustic panels kg/m mm CLT 5 ply kg/m 2 Total kg/m 2 Test Specimen Installation The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was m 2 (4.71 m x 3.79 m). The total area of the floor assembly resting on top of the lip was m 2 (4.88 m x 3.96 m). The mass per area of the elements above the lip was calculated using the total area (19.32 m 2 ). Page 20 of 101
23 Client Report A Construction Acoustics Laboratory This page is intentionally left blank Page 21 of 101
24 Construction Acoustics Laboratory Client Report A ASTM E90 Test Results Airborne Sound Transmission Loss Client: Nordic Engineered Wood Test ID: TLF Specimen ID: A F Date of Test: February 2, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 32.3 Area S of test specimen: m 2 Lower to to 41.0 Mass per unit area: 83.0 kg/m 2 f (Hz) Airborne TL (db) 100 STC Airborne Sound Transmission Loss, TL, in db Sound Transmission Class (STC) Sum of Deficiencies (db) Max. Deficiency (db) 8 db at 200 and 2 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E The dotted line (may be above the displayed range) is 10 db below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss. Page 22 of 101
25 Client Report A Construction Acoustics Laboratory ASTM E492 Test Results Normalized Impact Sound Pressure Levels Client: Nordic Engineered Wood Test ID: IIF Specimen ID: A F Date of Test: February 2, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 32.6 Area S of test specimen: m 2 Lower to to 40.9 Mass per unit area: 83.0 kg/m 2 f (Hz) NISPL (db) 100 IIC Normalized Impact Sound Pressure Level, NISPL, in db c c * Impact Insulation Class (IIC) 38 Sum of Positive Differences (db) 21 Max. Positive Difference (db) 8 db at 200 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 db above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E The reported values of NISPL have been corrected according to the procedure outlined in ASTM E Page 23 of 101
26 Construction Acoustics Laboratory Client Report A Client Nordic Engineered Wood 1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2 Specimen Fermacell 2E31 on CLT 5 ply (131 mm) Specimen ID A F Construction Date: February 9, 2006 to February 10, 2016 Specimen Description Topping: Fermacell panels type 2E31 (EE20+WF10) measuring 0 mm wide x 10 m long x mm thick were installed on top of the CLT floor. The rabbeted edges of the Fermacell panels were glued using the Fermacell floor glue and screwed together using Fermacell floor screws 3.9 mm x 19 mm spaced at a minimum of 200 mm on centre along the joints. Each row of Fermacell panels was offset from the adjoining rows. Perimeter strips were installed all around the floor to decouple the Fermacell panels from the test frame. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3 ) long spaced 5 mm (12 ) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT. Specimen Properties Element Cross-section of A F Actual thickness (mm) Mass (kg) Mass/length, area or volume mm Fermacell 2E31 (EE20+WF10) kg/m mm CLT 5 ply kg/m 2 Total kg/m 2 Test Specimen Installation The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was m 2 (4.71 m x 3.79 m). The total area of the floor assembly resting on top of the lip was m 2 (4.88 m x 3.96 m). The mass per area of the elements above the lip was calculated using the total area (19.32 m 2 ). Page 24 of 101
27 Client Report A Construction Acoustics Laboratory This page is intentionally left blank Page 25 of 101
28 Construction Acoustics Laboratory Client Report A ASTM E90 Test Results Airborne Sound Transmission Loss Client: Nordic Engineered Wood Test ID: TLF Specimen ID: A F Date of Test: February 9, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 42.1 Area S of test specimen: m 2 Lower to to 38.6 Mass per unit area: 96.1 kg/m 2 f (Hz) Airborne TL (db) 100 STC Airborne Sound Transmission Loss, TL, in db Sound Transmission Class (STC) Sum of Deficiencies (db) 28 Max. Deficiency (db) 6 db at 2 and 315 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E The dotted line (may be above the displayed range) is 10 db below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss. Page 26 of 101
29 Client Report A Construction Acoustics Laboratory ASTM E492 Test Results Normalized Impact Sound Pressure Levels Client: Nordic Engineered Wood Test ID: IIF Specimen ID: A F Date of Test: January 12, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to.1 Area S of test specimen: m 2 Lower to to 34.3 Mass per unit area: 96.1 kg/m 2 f (Hz) NISPL (db) 100 IIC Normalized Impact Sound Pressure Level, NISPL, in db Impact Insulation Class (IIC) Sum of Positive Differences (db) 32 Max. Positive Difference (db) 5dB at 200, 2, 315, 400 and 0Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 db above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E The reported values of NISPL have been corrected according to the procedure outlined in ASTM E Page 27 of 101
30 Construction Acoustics Laboratory Client Report A Client Nordic Engineered Wood 1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2 Specimen Specimen ID 38 mm precast concrete slab on 25 mm SonusWave placed on top of a CLT 5 ply (131 mm) A F Construction Date: March 10, 2016 to March 11, 2016 Specimen Description Topping: A 38 mm (1-1/2 ) precast concrete slab was placed on 25 mm Regupol SonusWave which was placed on the CLT floor. The edge of the precast concrete slab was filled with insulation and taped. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3 ) long spaced 5 mm (12 ) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT. Specimen Properties Element Cross-section of A F Actual thickness (mm) Mass (kg) Mass/length, area or volume 38 mm Precast Concrete Slab kg/m 2 25 mm Regupol SonusWave kg/m mm CLT 5 ply kg/m 2 Total kg/m 2 Test Specimen Installation The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was m 2 (4.71 m x 3.79 m). The total area of the floor assembly resting on top of the lip was m 2 (4.88 m x 3.96 m). The mass per area of the elements above the lip was calculated using the total area (19.32 m 2 ). Page 28 of 101
31 Client Report A Construction Acoustics Laboratory This page is intentionally left blank Page 29 of 101
32 Construction Acoustics Laboratory Client Report A ASTM E90 Test Results Airborne Sound Transmission Loss Client: Nordic Engineered Wood Test ID: TLF Specimen ID: A F Date of Test: March 11, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 34.0 Area S of test specimen: m 2 Lower to to 37.2 Mass per unit area: kg/m 2 f (Hz) Airborne TL (db) 100 STC Airborne Sound Transmission Loss, TL, in db c * * * * Sound Transmission Class (STC) Sum of Deficiencies (db) 28 Max. Deficiency (db) 7 db at 200 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E The dotted line (may be above the displayed range) is 10 db below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss. Page of 101
33 Client Report A Construction Acoustics Laboratory ASTM E492 Test Results Normalized Impact Sound Pressure Levels Client: Nordic Engineered Wood Test ID: IIF Specimen ID: A F Date of Test: March 11, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 34.3 Area S of test specimen: m 2 Lower to to 37.2 Mass per unit area: kg/m 2 f (Hz) NISPL (db) 100 IIC Normalized Impact Sound Pressure Level, NISPL, in db Impact Insulation Class (IIC) 49 Sum of Positive Differences (db) 29 Max. Positive Difference (db) 4 db at 125 and 1 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 db above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E The reported values of NISPL have been corrected according to the procedure outlined in ASTM E Page 31 of 101
34 Construction Acoustics Laboratory Client Report A Client Nordic Engineered Wood 1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2 Specimen Specimen ID 70 mm precast concrete slab on 25 mm SonusWave placed on top of a CLT 5 ply (131 mm) A F Construction Date: February 29, 2016 Specimen Description Topping: A 70 mm (2-3/4 ) precast concrete slab was placed on 25 mm Regupol SonusWave which was placed on the CLT floor. The edge of the precast concrete slab was filled with insulation and taped. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3 ) long spaced 5 mm (12 ) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT. Specimen Properties Element Cross-section of A F Actual thickness (mm) Mass (kg) Mass/length, area or volume 70 mm Precast Concrete Slab kg/m 2 25 mm Regupol SonusWave kg/m mm CLT 5 ply kg/m 2 Total kg/m 2 Test Specimen Installation The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was m 2 (4.71 m x 3.79 m). The total area of the floor assembly resting on top of the lip was m 2 (4.88 m x 3.96 m). The mass per area of the elements above the lip was calculated using the total area (19.32 m 2 ). Page 32 of 101
35 Client Report A Construction Acoustics Laboratory This page is intentionally left blank Page 33 of 101
36 Construction Acoustics Laboratory Client Report A ASTM E90 Test Results Airborne Sound Transmission Loss Client: Nordic Engineered Wood Test ID: TLF Specimen ID: A F Date of Test: March 1, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 32.3 Area S of test specimen: m 2 Lower to to 36.2 Mass per unit area: kg/m 2 f (Hz) Airborne TL (db) 100 STC Airborne Sound Transmission Loss, TL, in db c * * * c Sound Transmission Class (STC) Sum of Deficiencies (db) 31 Max. Deficiency (db) 7 db at 315 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E The dotted line (may be above the displayed range) is 10 db below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss. Page 34 of 101
37 Client Report A Construction Acoustics Laboratory ASTM E492 Test Results Normalized Impact Sound Pressure Levels Client: Nordic Engineered Wood Test ID: IIF Specimen ID: A F Date of Test: February 29, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 32.8 Area S of test specimen: m 2 Lower to to 38.1 Mass per unit area: kg/m 2 f (Hz) NISPL (db) 100 IIC Impact Insulation Class (IIC) 46 Sum of Positive Differences (db) 23 Max. Positive Difference (db) 5 db at 2 Hz Normalized Impact Sound Pressure Level, NISPL, in db Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine with the exception that the temperature in the lower room fell below 17 ºC. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 db above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E The reported values of NISPL have been corrected according to the procedure outlined in ASTM E Page 35 of 101
38 Construction Acoustics Laboratory Client Report A Client Nordic Engineered Wood 1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2 Specimen Specimen ID 70 mm precast concrete slab on 32 mm Roxul ComfortBoard IS placed on top of a CLT 5 ply (131 mm) A F Construction Date: March 3, 2016 Specimen Description Topping: A 70 mm (2-3/4 ) precast concrete slab was placed on Roxul ComfortBoard IS which was placed on the CLT floor. The edge of the precast concrete slab was filled with insulation and taped. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3 ) long spaced 5 mm (12 ) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT. Specimen Properties Element Cross-section of A F Actual thickness (mm) Mass (kg) Mass/length, area or volume 70 mm Precast Concrete Slab kg/m 2 32 mm Roxul ComfortBoard IS kg/m mm CLT 5 ply kg/m 2 Total kg/m 2 Test Specimen Installation The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was m 2 (4.71 m x 3.79 m). The total area of the floor assembly resting on top of the lip was m 2 (4.88 m x 3.96 m). The mass per area of the elements above the lip was calculated using the total area (19.32 m 2 ). Page 36 of 101
39 Client Report A Construction Acoustics Laboratory This page is intentionally left blank Page 37 of 101
40 Construction Acoustics Laboratory Client Report A ASTM E90 Test Results Airborne Sound Transmission Loss Client: Nordic Engineered Wood Test ID: TLF Specimen ID: A F Date of Test: March 3, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 32.0 Area S of test specimen: m 2 Lower to to 34.9 Mass per unit area: kg/m 2 f (Hz) Airborne TL (db) 100 STC Airborne Sound Transmission Loss, TL, in db c * * * Sound Transmission Class (STC) Sum of Deficiencies (db) 29 Max. Deficiency (db) 7 db at 1 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E The dotted line (may be above the displayed range) is 10 db below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss. Page 38 of 101
41 Client Report A Construction Acoustics Laboratory ASTM E492 Test Results Normalized Impact Sound Pressure Levels Client: Nordic Engineered Wood Test ID: IIF Specimen ID: A F Date of Test: March 3, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 32.5 Area S of test specimen: m 2 Lower to to 35.2 Mass per unit area: kg/m 2 f (Hz) NISPL (db) 100 IIC Normalized Impact Sound Pressure Level, NISPL, in db Impact Insulation Class (IIC) 45 Sum of Positive Differences (db) 22 Max. Positive Difference (db) 4 db at 12 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 db above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E The reported values of NISPL have been corrected according to the procedure outlined in ASTM E Page 39 of 101
42 Construction Acoustics Laboratory Client Report A Client Nordic Engineered Wood 1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2 Specimen Bare glulam decking (89 mm) Specimen ID A F Construction Date: January 26, 2016 Specimen Description Glulam Decking: The specimen was composed of 13 glued-laminated timber (glulam) decking panels nominally 384 mm wide x 89 mm thick x 3890 mm long (15 x 3-1/2 x 153 ). The combined panels filled the entire floor opening of the test frame. The glulam decking panels were joined using 90 mm (3-1/2 ) long common nails spaced 0 mm (12 ) on centre along the joints. The glulam decking floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the glulam decking floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the glulam. Cross-section of A F Fastening details of glulam decking Specimen Properties Element Actual thickness (mm) Mass (kg) Mass/length, area or volume 89 mm Glulam Decking kg/m 2 Total kg/m 2 Test Specimen Installation The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was m 2 (4.71 m x 3.79 m). The total area of the floor assembly resting on top of the lip was m 2 (4.88 m x 3.96 m). The mass per area of the elements above the lip was calculated using the total area (19.32 m 2 ). Page 40 of 101
43 Client Report A Construction Acoustics Laboratory This page is intentionally left blank Page 41 of 101
44 Construction Acoustics Laboratory Client Report A ASTM E90 Test Results Airborne Sound Transmission Loss Client: Nordic Engineered Wood Test ID: TLF Specimen ID: A F Date of Test: January 28, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 38.5 Area S of test specimen: m 2 Lower to to 39.2 Mass per unit area:.2 kg/m 2 f (Hz) Airborne TL (db) 80 STC Airborne Sound Transmission Loss, TL, in db Sound Transmission Class (STC) Sum of Deficiencies (db) 23 Max. Deficiency (db) 4 db at 12 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E The dotted line (may be above the displayed range) is 10 db below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss. Page 42 of 101
45 Client Report A Construction Acoustics Laboratory ASTM E492 Test Results Normalized Impact Sound Pressure Levels Client: Nordic Engineered Wood Test ID: IIF Specimen ID: A F Date of Test: January 28, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 40.4 Area S of test specimen: m 2 Lower to to 39.4 Mass per unit area:.2 kg/m 2 f (Hz) NISPL (db) 100 IIC Normalized Impact Sound Pressure Level, NISPL, in db Impact Insulation Class (IIC) 20 Sum of Positive Differences (db) 29 Max. Positive Difference (db) 7 db at 10 and 2000 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 db above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E The reported values of NISPL have been corrected according to the procedure outlined in ASTM E Page 43 of 101
46 Construction Acoustics Laboratory Client Report A Client Nordic Engineered Wood 1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2 Specimen Fermacell 2E31 on glulam decking (89 mm) Specimen ID A F Construction Date: February 3, 2016 Specimen Description Topping: Fermacell panels type 2E31 (EE20+WF10) measuring 0 mm wide x 10 mm long x mm thick were installed on top of the glulam decking. The rabbeted edges of the Fermacell panels were glued using the Fermacell floor glue and screwed together using Fermacell floor screws 3.9 mm x 19 mm spaced at a minimum of 200 mm on centre along the joints. Each row of Fermacell panels was offset from the adjoining rows. Perimeter strips were installed all around the floor to decouple the Fermacell panels from the test frame. Glulam Decking: The specimen was composed of 13 glued-laminated timber (glulam) decking panels nominally 384 mm wide x 89 mm thick x 3890 mm long (15 x 3-1/2 x 153 ). The combined panels filled the entire floor opening of the test frame. The glulam decking panels were joined using 90 mm (3-1/2 ) long common nails spaced 0 mm (12 ) on centre along the joints. The glulam decking floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the glulam decking floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the glulam. Specimen Properties Element Cross-section of A F Actual thickness (mm) Mass (kg) Mass/length, area or volume mm Fermacell 2E31 (EE20+WF10) kg/m 2 89 mm Glulam Decking kg/m 2 Total kg/m 2 Test Specimen Installation The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was m 2 (4.71 m x 3.79 m). The total area of the floor assembly resting on top of the lip was m 2 (4.88 m x 3.96 m). The mass per area of the elements above the lip was calculated using the total area (19.32 m 2 ). Page 44 of 101
47 Client Report A Construction Acoustics Laboratory This page is intentionally left blank Page 45 of 101
48 Construction Acoustics Laboratory Client Report A ASTM E90 Test Results Airborne Sound Transmission Loss Client: Nordic Engineered Wood Test ID: TLF Specimen ID: A F Date of Test: February 9, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 31.4 Area S of test specimen: m 2 Lower to to 40.7 Mass per unit area: 76.8 kg/m 2 f (Hz) Airborne TL (db) 100 STC Airborne Sound Transmission Loss, TL, in db Sound Transmission Class (STC) 47 Sum of Deficiencies (db) 31 Max. Deficiency (db) 6 db at 315 and 400 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E The dotted line (may be above the displayed range) is 10 db below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss. Page 46 of 101
49 Client Report A Construction Acoustics Laboratory ASTM E492 Test Results Normalized Impact Sound Pressure Levels Client: Nordic Engineered Wood Test ID: IIF Specimen ID: A F Date of Test: February 8, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 33.2 Area S of test specimen: m 2 Lower to to 38.5 Mass per unit area: 76.8 kg/m 2 f (Hz) NISPL (db) 100 IIC Normalized Impact Sound Pressure Level, NISPL, in db Impact Insulation Class (IIC) 37 Sum of Positive Differences (db) 26 Max. Positive Difference (db) 4 db at 400, 0 and 6 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 db above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E The reported values of NISPL have been corrected according to the procedure outlined in ASTM E Page 47 of 101
50 Construction Acoustics Laboratory Client Report A Client Nordic Engineered Wood 1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2 Specimen Specimen ID 70 mm precast concrete slab on 25 mm SonusWave placed on top of a glulam decking (131 mm) A F Construction Date: February 17, 2016 to February 24, 2016 Specimen Description Topping: A 70 mm (2-3/4 ) precast concrete slab was placed on 25 mm Regupol SonusWave which was placed on the glulam decking. The edge of the precast concrete slab was filled with insulation and taped. Glulam Decking: The specimen was composed of 13 glued-laminated timber (glulam) decking panels nominally 384 mm wide x 89 mm thick x 3890 mm long (15 x 3-1/2 x 153 ). The combined panels filled the entire floor opening of the test frame. The glulam decking panels were joined using 90 mm (3-1/2 ) long common nails spaced 0 mm (12 ) on centre along the joints. The glulam decking floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the glulam decking floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the glulam. Specimen Properties Element Cross-section of A F Actual thickness (mm) Mass (kg) Mass/length, area or volume 70 mm Precast Concrete Slab kg/m 2 25 mm Regupol SonusWave kg/m 2 89 mm Glulam Decking kg/m 2 Total kg/m 2 Test Specimen Installation The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was m 2 (4.71 m x 3.79 m). The total area of the floor assembly resting on top of the lip was m 2 (4.88 m x 3.96 m). The mass per area of the elements above the lip was calculated using the total area (19.32 m 2 ). Page 48 of 101
51 Client Report A Construction Acoustics Laboratory This page is intentionally left blank Page 49 of 101
52 Construction Acoustics Laboratory Client Report A ASTM E90 Test Results Airborne Sound Transmission Loss Client: Nordic Engineered Wood Test ID: TLF Specimen ID: A F Date of Test: February 25, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 35.6 Area S of test specimen: m 2 Lower to to 37.7 Mass per unit area: kg/m 2 f (Hz) Airborne TL (db) 100 STC Airborne Sound Transmission Loss, TL, in db c * * * Sound Transmission Class (STC) 54 Sum of Deficiencies (db) 27 Max. Deficiency (db) 7 db at 315 and 400 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E The dotted line (may be above the displayed range) is 10 db below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss. Page of 101
53 Client Report A Construction Acoustics Laboratory ASTM E492 Test Results Normalized Impact Sound Pressure Levels Client: Nordic Engineered Wood Test ID: IIF Specimen ID: A F Date of Test: February 26, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to.7 Area S of test specimen: m 2 Lower to to 40.3 Mass per unit area: kg/m 2 f (Hz) NISPL (db) 100 IIC Normalized Impact Sound Pressure Level, NISPL, in db Impact Insulation Class (IIC) Sum of Positive Differences (db) 32 Max. Positive Difference (db) 6 db at 1 and 200 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 db above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E The reported values of NISPL have been corrected according to the procedure outlined in ASTM E Page 51 of 101
54 Construction Acoustics Laboratory Client Report A Client Nordic Engineered Wood 1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2 Specimen Specimen ID 38 mm precast concrete slab placed directly on a OSB wood raft with sand on top of a CLT 5 ply (131 mm) A F Construction Date: March 17, 2016 to March 21, 2016 Specimen Description Topping: A 38 mm (1-1/2 ) precast concrete slab was installed directly on top of OSB sheeting. The 18 mm (23/32 ) OSB sheeting was screwed down with the long side perpendicular to 38 mm x 64 mm (2x3) wood battens, with the narrow side down, using mm (2 ) long #10 wood screws spaced 1 mm (6 ) o.c. along the edges and 200 mm (8 ) o.c in the field. Wood battens running along the short direction (3978 mm) and spaced at 610 mm (24 ) o.c. and glued to strips of 10 mm thick rubber membranes at the bottom. Fill: A 6 mil polyethylene sheet was placed on the CLT and the wood battens with rubber membrane were installed directly on top (floating). mm (2 ) of dry silica sand (#71) filled the cavity of the battens leaving a 12 mm (1/2 ) air gap between the sand and the OSB. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3 ) long spaced 5 mm (12 ) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT. Specimen Properties Element Cross-section of A F Actual thickness (mm) Mass (kg) Mass/length, area or volume 38 mm Precast Concrete Slab kg/m 2 18 mm OSB Tongue and Groove Sheeting kg/m 2 38 mm x 64 mm Wood Battens kg/m 10 mm Rubber Membrane kg/m 2 mm Silica Sand (#71) * kg/m 2 6 mil Polyethylene Sheeting kg/m mm CLT 5 ply kg/m 2 Total kg/m 2 * The thickness of the sand is not included in the total specimen thickness. Page 52 of 101
55 Client Report A Construction Acoustics Laboratory Test Specimen Installation The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was m 2 (4.71 m x 3.79 m). The total area of the floor assembly resting on top of the lip was m 2 (4.88 m x 3.96 m). The mass per area of the elements above the lip was calculated using the total area (19.32 m 2 ). Page 53 of 101
56 Construction Acoustics Laboratory Client Report A ASTM E90 Test Results Airborne Sound Transmission Loss Client: Nordic Engineered Wood Test ID: TLF Specimen ID: A F Date of Test: March 22, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 31.6 Area S of test specimen: m 2 Lower to to 38.8 Mass per unit area: kg/m 2 f (Hz) Airborne TL (db) 100 STC c Airborne Sound Transmission Loss, TL, in db c c c c c Sound Transmission Class (STC) Sum of Deficiencies (db) 29 Max. Deficiency (db) 7 db at 125 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E The dotted line (may be above the displayed range) is 10 db below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss. Page 54 of 101
57 Client Report A Construction Acoustics Laboratory ASTM E492 Test Results Normalized Impact Sound Pressure Levels Client: Nordic Engineered Wood Test ID: IIF Specimen ID: A F Date of Test: March 22, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 32.1 Area S of test specimen: m 2 Lower to to 38.7 Mass per unit area: kg/m 2 f (Hz) NISPL (db) 100 IIC Normalized Impact Sound Pressure Level, NISPL, in db Impact Insulation Class (IIC) 53 Sum of Positive Differences (db) Max. Positive Difference (db) 6 db at 10 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 db above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E The reported values of NISPL have been corrected according to the procedure outlined in ASTM E Page 55 of 101
58 Construction Acoustics Laboratory Client Report A Client: Nordic Engineered Wood 1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2 Specimen: Specimen ID: 38 mm precast concrete slab on 17 mm SonusWave placed on a OSB wood raft with sand on top of a CLT 5 ply (131 mm) A F Construction Date: March 23, 2016 Specimen Description Topping: A 38 mm (1-1/2 ) precast concrete slab was placed on 17 mm Regupol SonusWave on top of OSB sheeting. The 18 mm (23/32 ) OSB sheeting was screwed down with the long side perpendicular to 38 mm x 64 mm (2x3) wood battens, with the narrow side down, using mm (2 ) long #10 wood screws spaced 1 mm (6 ) o.c. along the edges and 200 mm (8 ) o.c in the field. Wood battens running along the short direction (3978 mm) and spaced at 610 mm (24 ) o.c. and glued to strips of 10 mm thick rubber membranes at the bottom. Fill: A 6 mil polyethylene sheet was placed on the CLT and the wood battens with rubber membrane were installed directly on top (floating). mm (2 ) of dry silica sand (#71) filled the cavity of the battens leaving a 12 mm (1/2 ) air gap between the sand and the OSB. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3 ) long spaced 5 mm (12 ) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT. Specimen Properties Element Cross-section of A F Actual thickness (mm) Mass (kg) Mass/length, area or volume 38 mm Precast Concrete Slab kg/m 2 17 mm Regupol SonusWave kg/m 2 18 mm OSB Tongue and Groove Sheeting kg/m 2 38 mm x 64 mm Wood Battens kg/m 10 mm Rubber Membrane kg/m 2 mm Silica Sand (#71) * kg/m 2 6 mil Polyethylene Sheeting kg/m mm CLT 5 ply kg/m 2 Total kg/m 2 * The thickness of the sand is not included in the total specimen thickness. Page 56 of 101
59 Client Report A Construction Acoustics Laboratory Test Specimen Installation The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was m 2 (4.71 m x 3.79 m). The total area of the floor assembly resting on top of the lip was m 2 (4.88 m x 3.96 m). The mass per area of the elements above the lip was calculated using the total area (19.32 m 2 ). Page 57 of 101
60 Construction Acoustics Laboratory Client Report A ASTM E90 Test Results Airborne Sound Transmission Loss Client: Nordic Engineered Wood Test ID: TLF Specimen ID: A F Date of Test: March 23, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 43.8 Area S of test specimen: m 2 Lower to to 40.2 Mass per unit area: kg/m 2 f (Hz) Airborne TL (db) 100 STC Airborne Sound Transmission Loss, TL, in db c * c c c Sound Transmission Class (STC) Sum of Deficiencies (db) 31 Max. Deficiency (db) 7 db at 1 and 200 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E The dotted line (may be above the displayed range) is 10 db below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss. Page 58 of 101
61 Client Report A Construction Acoustics Laboratory ASTM E492 Test Results Normalized Impact Sound Pressure Levels Client: Nordic Engineered Wood Test ID: IIF Specimen ID: A F Date of Test: March 23, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 47.5 Area S of test specimen: m 2 Lower to to 40.7 Mass per unit area: kg/m 2 f (Hz) NISPL (db) 80 IIC * Normalized Impact Sound Pressure Level, NISPL, in db * * * Impact Insulation Class (IIC) Sum of Positive Differences (db) 26 Max. Positive Difference (db) 5 db at 125, 1 and 200 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 db above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E The reported values of NISPL have been corrected according to the procedure outlined in ASTM E Page 59 of 101
62 Construction Acoustics Laboratory Client Report A Client Nordic Engineered Wood 1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2 Specimen OSB wood raft with sand on top of a CLT 5 ply (131 mm) Specimen ID A F Construction Date March 29, 2016 Specimen Description Topping: The 18 mm (23/32 ) OSB sheeting was screwed down with the long side perpendicular to 38 mm x 64 mm (2x3) wood battens, with the narrow side down, using mm (2 ) long #10 wood screws spaced 1 mm (6 ) o.c. along the edges and 200 mm (8 ) o.c in the field. Wood battens running along the short direction (3978 mm) and spaced at 610 mm (24 ) o.c. and glued to strips of 10 mm thick rubber membranes at the bottom. Fill: A 6 mil polyethylene sheet was placed on the CLT and the wood battens with rubber membrane were installed directly on top (floating). mm (2 ) of dry silica sand (#71) filled the cavity of the battens leaving a 12 mm (1/2 ) air gap between the sand and the OSB. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3 ) long spaced 5 mm (12 ) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT. Specimen Properties Element Cross-section of A F Actual thickness (mm) Mass (kg) Mass/length, area or volume 18 mm OSB Tongue and Groove Sheeting kg/m 2 38 mm x 64 mm Wood Battens kg/m 10 mm Rubber Membrane kg/m 2 mm Silica Sand (#71) * kg/m 2 6 mil Polyethylene Sheeting kg/m mm CLT 5 ply kg/m 2 Total kg/m 2 * The thickness of the sand is not included in the total specimen thickness. Page of 101
63 Client Report A Construction Acoustics Laboratory Test Specimen Installation The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was m 2 (4.71 m x 3.79 m). The total area of the floor assembly resting on top of the lip was m 2 (4.88 m x 3.96 m). The mass per area of the elements above the lip was calculated using the total area (19.32 m 2 ). Page 61 of 101
64 Construction Acoustics Laboratory Client Report A ASTM E90 Test Results Airborne Sound Transmission Loss Client: Nordic Engineered Wood Test ID: TLF Specimen ID: A F Date of Test: March 29, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 33.7 Area S of test specimen: m 2 Lower to to 41.1 Mass per unit area: kg/m 2 f (Hz) Airborne TL (db) 100 STC Airborne Sound Transmission Loss, TL, in db Sound Transmission Class (STC) Sum of Deficiencies (db) 27 Max. Deficiency (db) 7 db at 1 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E The dotted line (may be above the displayed range) is 10 db below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss. Page 62 of 101
65 Client Report A Construction Acoustics Laboratory ASTM E492 Test Results Normalized Impact Sound Pressure Levels Client: Nordic Engineered Wood Test ID: IIF Specimen ID: A F Date of Test: March 29, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 33.8 Area S of test specimen: m 2 Lower to to 41.8 Mass per unit area: kg/m 2 f (Hz) NISPL (db) 80 IIC Normalized Impact Sound Pressure Level, NISPL, in db c * Impact Insulation Class (IIC) 47 Sum of Positive Differences (db) 29 Max. Positive Difference (db) 6 db at 1 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 db above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E The reported values of NISPL have been corrected according to the procedure outlined in ASTM E Page 63 of 101
66 Construction Acoustics Laboratory Client Report A Client Nordic Engineered Wood 1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2 Specimen Specimen ID Fermacell 2E31 placed on OSB wood raft with sand on top of a CLT 5 ply (131 mm) A F Construction Date March 29, 2016 Specimen Description Topping: Fermacell panels type 2E31 (EE20+WF10) measuring 0 mm wide x 10 mm long x mm thick were installed on top of OSB subfloor. The rabbeted edges of the Fermacell panels were glued using the Fermacell floor glue and screwed together using Fermacell floor screws 3.9 mm x 19 mm spaced at a minimum of 200 mm on centre along the joints. Each row of Fermacell panels was offset from the adjoining rows. Perimeter strips were installed all around the floor to decouple the Fermacell panels from the test frame. The 18 mm (23/32 ) OSB sheeting was screwed down with the long side perpendicular to 38 mm x 64 mm (2x3) wood battens, with the narrow side down, using mm (2 ) long #10 wood screws spaced 1 mm (6 ) o.c. along the edges and 200 mm (8 ) o.c in the field. Wood battens running along the short direction (3978 mm) and spaced at 610 mm (24 ) o.c. and glued to strips of 10 mm thick rubber membranes at the bottom. Fill: A 6 mil polyethylene sheet was placed on the CLT and the wood battens with rubber membrane were installed directly on top (floating). mm (2 ) of dry silica sand (#71) filled the cavity of the batten leaving a 12 mm (1/2 ) air gap between the sand and the OSB. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3 ) long spaced 5 mm (12 ) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT. Specimen Properties Element Cross-section of A F Actual thickness (mm) Page 64 of 101 Mass (kg) Mass/length, area or volume mm Fermacell 2E31 (EE20+WF10) kg/m 2 18 mm OSB Tongue and Groove Sheeting kg/m 2 38 mm x 64 mm Wood Battens kg/m 10 mm Rubber Membrane kg/m 2 mm Silica Sand (#71) * kg/m 2 6 mil Polyethylene Sheeting kg/m mm CLT 5 ply kg/m 2 Total kg/m 2
67 Client Report A * The thickness of the sand is not included in the total specimen thickness. Construction Acoustics Laboratory Test Specimen Installation The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was m 2 (4.71 m x 3.79 m). The total area of the floor assembly resting on top of the lip was m 2 (4.88 m x 3.96 m). The mass per area of the elements above the lip was calculated using the total area (19.32 m 2 ). Page 65 of 101
68 Construction Acoustics Laboratory Client Report A ASTM E90 Test Results Airborne Sound Transmission Loss Client: Nordic Engineered Wood Test ID: TLF Specimen ID: A F Date of Test: March, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 33.4 Area S of test specimen: m 2 Lower to to 37.7 Mass per unit area: kg/m 2 f (Hz) Airborne TL (db) 100 STC Airborne Sound Transmission Loss, TL, in db c c * * * Sound Transmission Class (STC) Sum of Deficiencies (db) 27 Max. Deficiency (db) 6 db at 125 and 315 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E The dotted line (may be above the displayed range) is 10 db below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss. Page 66 of 101
69 Client Report A Construction Acoustics Laboratory ASTM E492 Test Results Normalized Impact Sound Pressure Levels Client: Nordic Engineered Wood Test ID: IIF Specimen ID: A F Date of Test: March, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 34.2 Area S of test specimen: m 2 Lower to to 37.6 Mass per unit area: kg/m 2 f (Hz) NISPL (db) 80 IIC * Normalized Impact Sound Pressure Level, NISPL, in db * * * Impact Insulation Class (IIC) Sum of Positive Differences (db) 26 Max. Positive Difference (db) 8 db at 125 and 1 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 db above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E The reported values of NISPL have been corrected according to the procedure outlined in ASTM E Page 67 of 101
70 Construction Acoustics Laboratory Client Report A Client Nordic Engineered Wood 1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2 Specimen SonoDeck placed on OSB wood raft with sand on top of a CLT 5 ply (131 mm) Specimen ID A F Construction Date March 31, 2016 Specimen Description Topping: SonoDeck engineered acoustic panels from InsulFloor measuring 800 mm x 1220 mm x 25 mm (31.5 x 48 x 1 ) are composed of two layers of 9.5 mm (3/8 ) OSB glued together with 6 mm (1/4 ) fiberglass mat on the bottom. The SonoDeck was placed on top of the OSB subfloor. The 25 mm (1 ) overlapping joints of the panels were glued and stapled using 18 Ga. ¼ x ¾ narrow crown staples along the joints every 5 mm (12 ). Each row of SonoDeck panels was offset by half a panel length (400 mm). The gap between the SonoDeck and the test frame was filled with closed cell polyethylene foam. The 18 mm (23/32 ) OSB sheeting was screwed down with the long side perpendicular to 38 mm x 64 mm (2x3) wood battens, with the narrow side down, using mm (2 ) long #10 wood screws spaced 1 mm (6 ) o.c. along the edges and 200 mm (8 ) o.c in the field. Wood battens running along the short direction (3978 mm) and spaced at 610 mm (24 ) o.c. and glued to strips of 10 mm thick rubber membranes at the bottom. Fill: A 6 mil polyethylene sheet was placed on the CLT and the wood battens with rubber membrane were installed directly on top (floating). mm (2 ) of dry silica sand (#71) filled the cavity of the battens leaving a 12 mm (1/2 ) air gap between the sand and the OSB. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3 ) long spaced 5 mm (12 ) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT. Specimen Properties Element Cross-section of A F Actual thickness (mm) Page 68 of 101 Mass (kg) Mass/length, area or volume 25 mm SonoDeck engineered acoustic panels kg/m 2 18 mm OSB Tongue and Groove Sheeting kg/m 2 38 mm x 64 mm Wood Battens kg/m 10 mm Rubber Membrane kg/m 2 mm Silica Sand (#71) * kg/m 2 6 mil Polyethylene Sheeting kg/m mm CLT 5 ply kg/m 2 Total kg/m 2
71 Client Report A * The thickness of the sand is not included in the total specimen thickness. Construction Acoustics Laboratory Test Specimen Installation The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was m 2 (4.71 m x 3.79 m). The total area of the floor assembly resting on top of the lip was m 2 (4.88 m x 3.96 m). The mass per area of the elements above the lip was calculated using the total area (19.32 m 2 ). Page 69 of 101
72 Construction Acoustics Laboratory Client Report A ASTM E90 Test Results Airborne Sound Transmission Loss Client: Nordic Engineered Wood Test ID: TLF Specimen ID: A F Date of Test: March 31, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 35.9 Area S of test specimen: m 2 Lower to to 40.2 Mass per unit area: kg/m 2 f (Hz) Airborne TL (db) 100 STC Airborne Sound Transmission Loss, TL, in db c * * * * Sound Transmission Class (STC) Sum of Deficiencies (db) 28 Max. Deficiency (db) 6 db at 125 and 315 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E The dotted line (may be above the displayed range) is 10 db below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss. Page 70 of 101
73 Client Report A Construction Acoustics Laboratory ASTM E492 Test Results Normalized Impact Sound Pressure Levels Client: Nordic Engineered Wood Test ID: IIF Specimen ID: A F Date of Test: March 31, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 35.7 Area S of test specimen: m 2 Lower to to 40.3 Mass per unit area: kg/m 2 f (Hz) NISPL (db) 80 IIC c * * Normalized Impact Sound Pressure Level, NISPL, in db * * * Impact Insulation Class (IIC) Sum of Positive Differences (db) 24 Max. Positive Difference (db) 8 db at 125 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 db above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E The reported values of NISPL have been corrected according to the procedure outlined in ASTM E Page 71 of 101
74 Construction Acoustics Laboratory Client Report A Client Nordic Engineered Wood 1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2 Specimen Specimen ID 38 mm precast concrete slab on 17 mm SonusWave placed on a OSB wood raft (no sand) on top of a CLT 5 ply (131 mm) A F Construction Date April 5, 2016 Specimen Description Topping: 38 mm (1-1/2 ) precast concrete slab was placed on 17 mm Regupol SonusWave on top of OSB sheeting. The 18 mm (23/32 ) OSB sheeting was screwed down with the long side perpendicular to 38 mm x 64 mm (2x3) wood battens, with the narrow side down, using mm (2 ) long #10 wood screws spaced 1 mm (6 ) o.c. along the edges and 200 mm (8 ) o.c in the field. Wood battens running along the short direction (3978 mm) and spaced at 610 mm (24 ) o.c. and glued to strips of 10 mm thick rubber membranes at the bottom. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3 ) long spaced 5 mm (12 ) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT. Specimen Properties Element Cross-section of A F Actual thickness (mm) Mass (kg) Mass/length, area or volume 38 mm Precast Concrete Slab kg/m 2 17 mm Regupol SonusWave kg/m 2 18 mm OSB Tongue and Groove Sheeting kg/m 2 38 mm x 64 mm Wood Battens kg/m 10 mm Rubber Membrane kg/m mm CLT 5 ply kg/m 2 Total kg/m 2 Page 72 of 101
75 Client Report A Construction Acoustics Laboratory Test Specimen Installation The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was m 2 (4.71 m x 3.79 m). The total area of the floor assembly resting on top of the lip was m 2 (4.88 m x 3.96 m). The mass per area of the elements above the lip was calculated using the total area (19.32 m 2 ). Page 73 of 101
76 Construction Acoustics Laboratory Client Report A ASTM E90 Test Results Airborne Sound Transmission Loss Client: Nordic Engineered Wood Test ID: TLF Specimen ID: A F Date of Test: April 5, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 33.3 Area S of test specimen: m 2 Lower to to 38.3 Mass per unit area: kg/m 2 f (Hz) Airborne TL (db) 100 STC Airborne Sound Transmission Loss, TL, in db c c * * * Sound Transmission Class (STC) Sum of Deficiencies (db) 29 Max. Deficiency (db) 6 db at 200 and 2 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E The dotted line (may be above the displayed range) is 10 db below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss. Page 74 of 101
77 Client Report A Construction Acoustics Laboratory ASTM E492 Test Results Normalized Impact Sound Pressure Levels Client: Nordic Engineered Wood Test ID: IIF Specimen ID: A F Date of Test: March 31, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 36.7 Area S of test specimen: m 2 Lower to to 38.2 Mass per unit area: kg/m 2 f (Hz) NISPL (db) 90 IIC c Normalized Impact Sound Pressure Level, NISPL, in db * * * Impact Insulation Class (IIC) Sum of Positive Differences (db) 31 Max. Positive Difference (db) 7 db at 400 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 db above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E The reported values of NISPL have been corrected according to the procedure outlined in ASTM E Page 75 of 101
78 Construction Acoustics Laboratory Client Report A Client Nordic Engineered Wood 1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2 Specimen Specimen ID 38 mm precast concrete slab on 17 mm SonusWave placed on a OSB wood raft (no sand) with glass fiber batts on top of a CLT 5 ply (131 mm) A F Construction Date April 7, 2016 Specimen Description Topping: A 38 mm (1-1/2 ) precast concrete slab was placed on 17 mm Regupol SonusWave on top of OSB sheeting. The 18 mm (23/32 ) OSB sheeting was screwed down with the long side perpendicular to 38 mm x 64 mm (2x3) wood battens, with the narrow side down, using mm (2 ) long #10 wood screws spaced 1 mm (6 ) o.c. along the edges and 200 mm (8 ) o.c in the field. Wood battens running along the short direction (3978 mm) and spaced at 610 mm (24 ) o.c. and glued to strips of 10 mm thick rubber membranes at the bottom. 65 mm (2-1/2 ) glass fibre insulation batts were placed in the cavity. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3 ) long spaced 5 mm (12 ) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT. Specimen Properties Element Cross-section of A F Actual thickness (mm) Mass (kg) Mass/length, area or volume 38 mm Precast Concrete Slab kg/m 2 17 mm Regupol SonusWave kg/m 2 18 mm OSB Tongue and Groove Sheeting kg/m 2 38 mm x 64 mm Wood Battens kg/m 65 mm Glass Fibre Insulation Batts * kg/m 2 10 mm Rubber Membrane kg/m mm CLT 5 ply kg/m 2 Total kg/m 2 * The thickness of the glass fibre insulation batts is not included in the total specimen thickness. Page 76 of 101
79 Client Report A Construction Acoustics Laboratory Test Specimen Installation The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was m 2 (4.71 m x 3.79 m). The total area of the floor assembly resting on top of the lip was m 2 (4.88 m x 3.96 m). The mass per area of the elements above the lip was calculated using the total area (19.32 m 2 ). Page 77 of 101
80 Construction Acoustics Laboratory Client Report A ASTM E90 Test Results Airborne Sound Transmission Loss Client: Nordic Engineered Wood Test ID: TLF Specimen ID: A F Date of Test: April 7, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 34.0 Area S of test specimen: m 2 Lower to to 43.8 Mass per unit area: kg/m 2 f (Hz) Airborne TL (db) 100 STC Airborne Sound Transmission Loss, TL, in db c * * * * Sound Transmission Class (STC) Sum of Deficiencies (db) Max. Deficiency (db) 6 db at 200 and 2 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements with the exception that the humidity variation in the lower room was greater than 3%. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E The dotted line (may be above the displayed range) is 10 db below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss. Page 78 of 101
81 Client Report A Construction Acoustics Laboratory ASTM E492 Test Results Normalized Impact Sound Pressure Levels Client: Nordic Engineered Wood Test ID: IIF Specimen ID: A F Date of Test: April 8, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to.3 Area S of test specimen: m 2 Lower to to 36.7 Mass per unit area: kg/m 2 f (Hz) NISPL (db) 90 IIC * Normalized Impact Sound Pressure Level, NISPL, in db * * * Impact Insulation Class (IIC) 54 Sum of Positive Differences (db) 26 Max. Positive Difference (db) 6 db at 400 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 db above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E The reported values of NISPL have been corrected according to the procedure outlined in ASTM E Page 79 of 101
82 Construction Acoustics Laboratory Client Report A Client Nordic Engineered Wood 1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2 Specimen OSB wood raft with sand on top of glulam decking (89 mm) Specimen ID A F Construction Date April 11, 2016 to April 12, 2016 Specimen Description Topping: The 18 mm (23/32 ) OSB sheeting was screwed down with the long side perpendicular to 38 mm x 64 mm (2x3) wood battens, with the narrow side down, using mm (2 ) long #10 wood screws spaced 1 mm (6 ) o.c. along the edges and 200 mm (8 ) o.c in the field. Wood battens running along the short direction (3978 mm) and spaced at 610 mm (24 ) o.c. and glued to strips of 10 mm thick rubber membranes at the bottom. Fill: A 6 mil polyethylene sheet was placed on the CLT and the wood battens with rubber membrane were installed directly on top (floating). mm (2 ) of dry silica sand (#71) filled the cavity of the battens leaving a 12 mm (1/2 ) air gap between the sand and the OSB. Glulam Decking: The specimen was composed of 13 glued-laminated timber (glulam) decking panels nominally 384 mm wide x 89 mm thick x 3890 mm long (15 x 3-1/2 x 153 ). The combined panels filled the entire floor opening of the test frame. The glulam decking panels were joined using 90 mm (3-1/2 ) long common nails spaced 0 mm (12 ) on centre along the joints. The glulam decking floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the glulam decking floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the glulam. Specimen Properties Element Cross-section of A F Actual thickness (mm) Mass (kg) Mass/length, area or volume 18 mm OSB Tongue and Groove Sheeting kg/m 2 38 mm x 64 mm Wood Battens kg/m 10 mm Rubber Membrane kg/m 2 mm Silica Sand (#71) * kg/m 2 6 mil Polyethylene Sheeting kg/m 2 89 mm Glulam Decking kg/m 2 Total kg/m 2 * The thickness of the sand is not included in the total specimen thickness. Page 80 of 101
83 Client Report A Construction Acoustics Laboratory Test Specimen Installation The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was m 2 (4.71 m x 3.79 m). The total area of the floor assembly resting on top of the lip was m 2 (4.88 m x 3.96 m). The mass per area of the elements above the lip was calculated using the total area (19.32 m 2 ). Page 81 of 101
84 Construction Acoustics Laboratory Client Report A ASTM E90 Test Results Airborne Sound Transmission Loss Client: Nordic Engineered Wood Test ID: TLF Specimen ID: A F Date of Test: April 12, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 31.6 Area S of test specimen: m 2 Lower to to 34.6 Mass per unit area: kg/m 2 f (Hz) Airborne TL (db) 100 STC Airborne Sound Transmission Loss, TL, in db Sound Transmission Class (STC) Sum of Deficiencies (db) 29 Max. Deficiency (db) 7 db at 200 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E The dotted line (may be above the displayed range) is 10 db below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss. Page 82 of 101
85 Client Report A Construction Acoustics Laboratory ASTM E492 Test Results Normalized Impact Sound Pressure Levels Client: Nordic Engineered Wood Test ID: IIF Specimen ID: A F Date of Test: April 12, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 32.5 Area S of test specimen: m 2 Lower to to 34.1 Mass per unit area: kg/m 2 f (Hz) NISPL (db) 90 IIC Normalized Impact Sound Pressure Level, NISPL, in db * * Impact Insulation Class (IIC) Sum of Positive Differences (db) Max. Positive Difference (db) 6 db at 1 and 200 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 db above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E The reported values of NISPL have been corrected according to the procedure outlined in ASTM E Page 83 of 101
86 Construction Acoustics Laboratory Client Report A Client Nordic Engineered Wood 1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2 Specimen Specimen ID 38 mm precast concrete slab on 17 mm SonusWave placed on a OSB wood raft on top of glulam decking (89 mm) A F Construction Date April 13, 2016 Specimen Description Topping: A 38 mm (1-1/2 ) precast concrete slab was placed on 17 mm Regupol SonusWave on top of OSB sheeting. The 18 mm (23/32 ) OSB sheeting was screwed down with the long side perpendicular to 38 mm x 64 mm (2x3) wood battens, with the narrow side down, using mm (2 ) long #10 wood screws spaced 1 mm (6 ) o.c. along the edges and 200 mm (8 ) o.c in the field. Wood battens running along the short direction (3978 mm) and spaced at 610 mm (24 ) o.c. and glued to strips of 10 mm thick rubber membranes at the bottom. Fill: A 6 mil polyethylene sheet was placed on the CLT and the wood battens with rubber membrane were installed directly on top (floating). mm (2 ) of dry silica sand (#71) filled the cavity of the battens leaving a 12 mm (1/2 ) air gap between the sand and the OSB. Glulam Decking: The specimen was composed of 13 glued-laminated timber (glulam) decking panels nominally 384 mm wide x 89 mm thick x 3890 mm long (15 x 3-1/2 x 153 ). The combined panels filled the entire floor opening of the test frame. The glulam decking panels were joined using 90 mm (3-1/2 ) long common nails spaced 0 mm (12 ) on centre along the joints. The glulam decking floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the glulam decking floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the glulam. Specimen Properties Element Cross-section of A F Actual thickness (mm) Mass (kg) Mass/length, area or volume 38 mm Precast Concrete Slab kg/m 2 17 mm Regupol SonusWave kg/m 2 18 mm OSB Tongue and Groove Sheeting kg/m 2 38 mm x 64 mm Wood Battens kg/m 10 mm Rubber Membrane kg/m 2 mm Silica Sand (#71) * kg/m 2 6 mil Polyethylene Sheeting kg/m 2 89 mm Glulam Decking kg/m 2 Total kg/m 2 * The thickness of the sand is not included in the total specimen thickness. Page 84 of 101
87 Client Report A Construction Acoustics Laboratory Test Specimen Installation The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was m 2 (4.71 m x 3.79 m). The total area of the floor assembly resting on top of the lip was m 2 (4.88 m x 3.96 m). The mass per area of the elements above the lip was calculated using the total area (19.32 m 2 ). Page 85 of 101
88 Construction Acoustics Laboratory Client Report A ASTM E90 Test Results Airborne Sound Transmission Loss Client: Nordic Engineered Wood Test ID: TLF Specimen ID: A F Date of Test: April 13, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 32.5 Area S of test specimen: m 2 Lower to to 37.3 Mass per unit area: kg/m 2 f (Hz) Airborne TL (db) 100 STC Airborne Sound Transmission Loss, TL, in db c * * * * Sound Transmission Class (STC) Sum of Deficiencies (db) 29 Max. Deficiency (db) 7 db at 200 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E The dotted line (may be above the displayed range) is 10 db below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss. Page 86 of 101
89 Client Report A Construction Acoustics Laboratory ASTM E492 Test Results Normalized Impact Sound Pressure Levels Client: Nordic Engineered Wood Test ID: IIF Specimen ID: A F Date of Test: April 13, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 33.4 Area S of test specimen: m 2 Lower to to 37.8 Mass per unit area: kg/m 2 f (Hz) NISPL (db) 90 IIC * Normalized Impact Sound Pressure Level, NISPL, in db * * * Impact Insulation Class (IIC) 59 Sum of Positive Differences (db) 29 Max. Positive Difference (db) 4 db at 125, 200, 315 and 400 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 db above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E The reported values of NISPL have been corrected according to the procedure outlined in ASTM E Page 87 of 101
90 Construction Acoustics Laboratory Client Report A Client Nordic Engineered Wood 1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2 Specimen Specimen ID Small patch of Fermacell 2E31 on 70 mm precast concrete slab on 25 mm SonusWave placed on top of a CLT 5 ply (131 mm) A SF Construction Date April 13, 2016 Specimen Description Covering (small patch): Fermacell panels type 2E31 (EE20+WF10) measuring 0 mm wide x 10 mm long x mm thick were installed on top of OSB subfloor. The rabbeted edges of the Fermacell panels were not glued or screwed. The patch covered an approximate area of 4 m 2 in the middle of the floor. Topping: A 70 mm (2-3/4 ) precast concrete slab was placed on 25 mm Regupol SonusWave which was placed on the CLT floor. The edge of the precast concrete slab was filled with insulation and taped. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3 ) long spaced 5 mm (12 ) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT. Specimen Properties Element Cross-section of A SF Actual thickness (mm) Mass (kg) Mass/length, area or volume mm Fermacell 2E31 (EE20+WF10) * 26.6 kg/m 2 70 mm Precast Concrete Slab kg/m 2 25 mm Regupol SonusWave kg/m mm CLT 5 ply kg/m 2 Total 256 * kg/m 2 * Mass of small patch not added to total floor mass. Test Results Normalized Impact Sound Pressure Levels (Non-Standard) Page 88 of 101
91 Client Report A Construction Acoustics Laboratory Client: Nordic Engineered Wood Test ID: IIF Specimen ID: A SF Date of Test: March 10, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 33.8 Area S of test specimen: m 2 Lower to to 37.7 Mass per unit area: kg/m 2 f (Hz) NISPL (db) 90 IIC c c * * Normalized Impact Sound Pressure Level, NISPL, in db * * * Impact Insulation Class (IIC) 52 Sum of Positive Differences (db) Max. Positive Difference (db) 8 db at 200 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted following ASTM E492-09, Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine but had a small patch of covering material instead of full surface coverage. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 db above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E The reported values of NISPL have been corrected according to the procedure outlined in ASTM E Client Nordic Engineered Wood Page 89 of 101
92 Construction Acoustics Laboratory 1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2 Client Report A Specimen Specimen ID Small patch of laminate floor on AcoustiTech Premium on 70 mm precast concrete slab on 32 mm ROXUL ComfortBoard IS placed on top of a CLT 5 ply (131 mm) A SF Construction Date March 4, 2016 Specimen Description Covering (small patch): 8 mm click laminate flooring installed on AcousticTech Premium felt membrane. The patch covered an approximate area of 4 m 2 in the middle of the floor. Topping: A 70 mm (2-3/4 ) precast concrete slab was placed on Roxul ComfortBoard IS which was placed on the CLT floor. The edge of the precast concrete slab was filled with insulation and taped. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3 ) long spaced 5 mm (12 ) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT. Specimen Properties Element Cross-section of A SF Actual thickness (mm) Mass (kg) Mass/length, area or volume 8 mm Click Laminate Flooring 8 * 8.6 kg/m 2 3 mm AcoustiTech Premium 3 * 0.5 kg/m 2 70 mm Precast Concrete Slab kg/m 2 32 mm ROXUL ComfortBoard IS kg/m mm CLT 5 ply kg/m 2 Total 244 * kg/m 2 * Mass of small patch not added to total floor mass. Page 90 of 101
93 Client Report A Construction Acoustics Laboratory Test Results Normalized Impact Sound Pressure Levels (Non-Standard) Client: Nordic Engineered Wood Test ID: IIF Specimen ID: A SF Date of Test: March 4, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to.3 Area S of test specimen: m 2 Lower to to 34.6 Mass per unit area: kg/m 2 f (Hz) NISPL (db) 90 IIC c * * * * * * Impact Insulation Class (IIC) 51 Normalized Impact Sound Pressure Level, NISPL, in db Sum of Positive Differences (db) 28 Max. Positive Difference (db) 8 db at 100 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted following ASTM E492-09, Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine but had a small patch of covering material instead of full surface coverage. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 db above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E The reported values of NISPL have been corrected according to the procedure outlined in ASTM E Page 91 of 101
94 Construction Acoustics Laboratory Client Report A Client Nordic Engineered Wood 1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2 Specimen Specimen ID Small patch of laminate floor on Roberts Soft Stride on 70 mm precast concrete slab on 32 mm ROXUL ComfortBoard IS placed on top of a CLT 5 ply (131 mm) A SF Construction Date March 4, 2016 Specimen Description Covering (small patch): 8 mm click laminate flooring was installed on Roberts Soft Stride closed cell foam. The patch covered an approximate area of 4 m 2 in the middle of the floor. Topping: A 70 mm (2-3/4 ) precast concrete slab was placed on Roxul ComfortBoard IS which was placed on the CLT floor. The edge of the precast concrete slab was filled with insulation and taped. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3 ) long spaced 5 mm (12 ) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT. Specimen Properties Element Cross-section of A SF Actual thickness (mm) Mass (kg) Mass/length, area or volume 8 mm Click Laminate Flooring 8 * 8.6 kg/m 2 2 mm Roberts Soft Stride Closed Cell Foam 2 * 0.1 kg/m 2 70 mm Precast Concrete Slab kg/m 2 32 mm ROXUL ComfortBoard IS kg/m mm CLT 5 ply kg/m 2 Total 243 * kg/m 2 * Mass of small patch not added to total floor mass. Page 92 of 101
95 Client Report A Construction Acoustics Laboratory Test Results Normalized Impact Sound Pressure Levels (Non-Standard) Client: Nordic Engineered Wood Test ID: IIF Specimen ID: A SF Date of Test: March 4, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 28.9 Area S of test specimen: m 2 Lower to to 34.8 Mass per unit area: kg/m 2 f (Hz) NISPL (db) 90 IIC c * * * * * Impact Insulation Class (IIC) 51 Normalized Impact Sound Pressure Level, NISPL, in db Sum of Positive Differences (db) 24 Max. Positive Difference (db) 8 db at 100 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted following ASTM E492-09, Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine but had a small patch of covering material instead of full surface coverage. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 db above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E The reported values of NISPL have been corrected according to the procedure outlined in ASTM E Page 93 of 101
96 Construction Acoustics Laboratory Client Report A Client Nordic Engineered Wood 1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2 Specimen Specimen ID Small patch of laminate floor on Roberts Soft Stride on 70 mm precast concrete slab on 32 mm ROXUL ComfortBoard IS placed on top of a CLT 5 ply (131 mm) A SF Construction Date March 4, 2016 Specimen Description Covering (small patch): 10 mm Torlys Everest Premier Hardwood with attached cork underlay was installed on top of a 2 mm Roberts Soft Stride closed cell foam. The patch covered an approximate area of 4 m 2 in the middle of the floor. Topping: A 70 mm (2-3/4 ) precast concrete slab was placed on Roxul ComfortBoard IS which was placed on the CLT floor. The edge of the precast concrete slab was filled with insulation and taped. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3 ) long spaced 5 mm (12 ) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT. Specimen Properties Element Cross-section of A SF Actual thickness (mm) Mass (kg) Mass/length, area or volume 10 mm Torlys Everest Premier Hardwood 10 * 7.3 kg/m 2 2 mm Roberts Soft Stride Closed Cell Foam 2 * 0.1 kg/m 2 70 mm Precast Concrete Slab kg/m 2 32 mm ROXUL ComfortBoard IS kg/m mm CLT 5 ply kg/m 2 Total 245 * kg/m 2 * Mass of small patch not added to total floor mass. Page 94 of 101
97 Client Report A Construction Acoustics Laboratory Test Results Normalized Impact Sound Pressure Levels (Non-Standard) Client: Nordic Engineered Wood Test ID: IIF Specimen ID: A SF Date of Test: March 7, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 29.2 Area S of test specimen: m 2 Lower to to 35.7 Mass per unit area: kg/m 2 f (Hz) NISPL (db) 90 IIC c * * * * * Impact Insulation Class (IIC) 51 Normalized Impact Sound Pressure Level, NISPL, in db Sum of Positive Differences (db) 27 Max. Positive Difference (db) 8 db at 100 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted following ASTM E492-09, Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine but had a small patch of covering material instead of full surface coverage. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 db above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E The reported values of NISPL have been corrected according to the procedure outlined in ASTM E Page 95 of 101
98 Construction Acoustics Laboratory Client Report A Client Nordic Engineered Wood 1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2 Specimen Specimen ID Small patch of laminate floor on Roberts Soft Stride on 38 mm precast concrete slab on 17 mm SonusWave placed on a OSB wood raft (no sand) with glass fiber batts on top of a CLT 5 ply (131 mm) A SF Construction Date April 8, 2016 Specimen Description Covering (small patch): 8 mm click laminate flooring was installed on Roberts Soft Stride closed cell foam. The patch covered an approximate area of 4 m 2 in the middle of the floor. Topping: A 38 mm (1-1/2 ) precast concrete slab was placed on 17 mm Regupol SonusWave on top of OSB sheeting. The 18 mm (23/32 ) OSB sheeting was screwed down with the long side perpendicular to 38 mm x 64 mm (2x3) wood battens, with the narrow side down, using mm (2 ) long #10 wood screws spaced 1 mm (6 ) o.c. along the edges and 200 mm (8 ) o.c in the field. Wood battens running along the short direction (3978 mm) and spaced at 610 mm (24 ) o.c. and glued to strips of 10 mm thick rubber membranes at the bottom. 65 mm (2-1/2 ) glass fibre insulation batts were placed in the cavity. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3 ) long spaced 5 mm (12 ) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT. Specimen Properties Element Cross-section of A SF Actual thickness (mm) Page 96 of 101 Mass (kg) Mass/length, area or volume 8 mm Click Laminate Flooring 8 * 8.6 kg/m 2 2 mm Roberts Soft Stride Closed Cell Foam 2 * 0.1 kg/m 2 38 mm Precast Concrete Slab kg/m 2 17 mm Regupol SonusWave kg/m 2 18 mm OSB Tongue and Groove Sheeting kg/m 2 38 mm x 64 mm Wood Battens kg/m 65 mm Glass Fibre Insulation Batts * kg/m 2 10 mm Rubber Membrane kg/m mm CLT 5 ply kg/m 2 Total 288 * kg/m 2 * Mass of small patch not added to total floor mass.
99 Client Report A Construction Acoustics Laboratory Test Results Normalized Impact Sound Pressure Levels (Non-Standard) Client: Nordic Engineered Wood Test ID: IIF Specimen ID: A SF Date of Test: April 8, 2016 Room Volume (m³) Air Temperature ( C) Humidity (%) Upper to to 29.2 Area S of test specimen: m 2 Lower to to 36.9 Mass per unit area: kg/m 2 f (Hz) NISPL (db) 80 IIC * * * * * * * Impact Insulation Class (IIC) 58 Normalized Impact Sound Pressure Level, NISPL, in db Sum of Positive Differences (db) 29 Max. Positive Difference (db) 5 db at 100, 125, 1 and 200 Hz Frequency, f, in Hz For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted following ASTM E492-09, Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine but had a small patch of covering material instead of full surface coverage. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 db above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked c indicate that the measured background level was between 5 db and 10 db below the combined receiving room level and background level. Values marked * indicate that the measured background level was less than 5 db below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E The reported values of NISPL have been corrected according to the procedure outlined in ASTM E Page 97 of 101
100 Construction Acoustics Laboratory Client Report A Client Nordic Engineered Wood 1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2 Specimen Specimen ID Small patch of laminate floor on Roberts Soft Stride on 38 mm precast concrete slab on 17 mm SonusWave placed on a OSB wood raft on top of glulam decking (89 mm) A SF Construction Date April 14, 2016 Specimen Description Covering (small patch): 8 mm click laminate flooring was installed on Roberts Soft Stride closed cell foam. The patch covered an approximate area of 4 m 2 in the middle of the floor. Topping: A 38 mm (1-1/2 ) precast concrete slab was placed on 17 mm Regupol SonusWave on top of 18 mm (23/32 ) OSB sheeting. The OSB sheets screwed down with the long side perpendicular to the 38 mm x 64 mm (2x3) wood battens, with the narrow side down, using mm (2 ) long #10 wood screws spaced 1 mm (6 ) o.c. along the edges and 200 mm (8 ) o.c in the field. Wood battens spaced at 610 mm (24 ) o.c. and glued to 10 mm rubber membrane were installed at the bottom. Fill: A 6 mil polyethylene sheet was put down on the CLT and the wood batten and resilient layer were installed directly on top (floating). mm (2 ) of dry silica sand (#71) filled the cavity of the batten leaving a 12 mm (1/2 ) air gap between the OSB and the sand. Glulam Decking: The specimen was composed of 13 glued-laminated timber (glulam) decking panels nominally 384 mm wide x 89 mm thick x 3890 mm long (15 x 3-1/2 x 153 ). The combined panels filled the entire floor opening of the test frame. The glulam decking panels were joined using 90 mm (3-1/2 ) long common nails spaced 0 mm (12 ) on centre along the joints. The glulam decking floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the glulam decking floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the glulam. Specimen Properties Element Cross-section of A SF Actual thickness (mm) Page 98 of 101 Mass (kg) Mass/length, area or volume 8 mm Click Laminate Flooring 8 * 8.6 kg/m 2 2 mm Roberts Soft Stride Closed Cell Foam 2 * 0.1 kg/m 2 38 mm Precast Concrete Slab kg/m 2 17 mm Regupol SonusWave kg/m 2 18 mm OSB Tongue and Groove Sheeting kg/m 2 38 mm x 64 mm Wood Battens kg/m 10 mm Rubber Membrane kg/m 2 mm Silica Sand (#71) * kg/m 2 6 mil Polyethylene Sheeting kg/m 2 89 mm Glulam Decking kg/m 2 Total 246 * kg/m 2 * Mass of small patch not added to total floor mass.
This page was. intentionally. left blank
CONSTRUCTION Measurement of Airborne Sound Insulation of 8 Wall Assemblies Measurement of Airborne and Impact Sound Insulation of 29 Floor Assemblies Nordic Engineered Wood Report No. A1-006070.10 July
More informationKINETICS NOISE CONTROL TEST REPORT #AT001110
KINETICS NOISE CONTROL TEST REPORT #AT001110 KINETICS NOISE CONTROL PRODUCTS: o NONE ACOUSTICAL RATINGS: o STC 53 o IIC 29 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o REPORT NO. A1-010601.1 o DATED:
More informationKINETICS NOISE CONTROL TEST REPORT # AT001084
KINETICS NOISE CONTROL TEST REPORT # AT001084 KINETICS NOISE CONTROL PRODUCTS: o MODEL ISOGRID ACOUSTICAL RATINGS: o STC 63 o IIC 50 TESTING AGENCY & REPORT NUMBER: o NRC-CNRC o B-3463.6 KINETICS DRAWING
More informationKINETICS NOISE CONTROL TEST REPORT #AT001049
KINETICS NOISE CONTROL TEST REPORT #AT001049 KINETICS NOISE CONTROL PRODUCTS: o NONE ACOUSTICAL RATINGS: o STC 53 o IIC 27 TESTING AGENCY & REPORT NUMBER: o NATIONAL RESEARCH COUNCIL OF CANADA o B-3463.1
More informationC R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: Forest rx
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to Series/Model: Forest rx Specimen Type: Floor/Ceiling Assembly Overall Size: 3023 mm by 3632 mm Summary of Test Results Data File
More informationREGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT
REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E9, ASTM E492, AND ASTM E2179 TESTING ON 4X SOUNDPANEL WITH AKUSTIPRO 8 RUBBER TILE SPECIMEN TYPE Concrete Slab - 152 mm REPORT NUMBER
More informationC R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: Base 10
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to Series/Model: Base 10 Specimen Type: Floor/Ceiling Assembly Overall Size: 3023 mm by 3632 mm Summary of Test Results Data File Result
More informationC R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: Expona
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to ECORE International Series/Model: Expona Specimen Type: Floor/Ceiling Assembly Overall Size: 3023 mm by 3632 mm Summary of Test Results
More informationC R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: QT4005
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to Series/Model: QT4005 Specimen Type: Floor/Ceiling Assembly Overall Size: 3023 mm by 3632 mm Summary of Test Results Data File Result
More informationC R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: QT4002
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to Series/Model: QT4002 Specimen Type: Floor/Ceiling Assembly Overall Size: 3023 mm by 3632 mm Summary of Test Results Data File Result
More informationB Page 1 of 21-
Airborne and impact sound transmission measurements were performed on three floor assemblies which comprised the NRC 150 mm reference concrete slab and a 102 mm floating concrete slab. For report purposes,
More informationLaboratory Data Examining Impact and Airborne Sound Attenuation in Cross- Laminated Timber Panel Construction - Part 2
Laboratory Data Examining Impact and Airborne Sound Attenuation in Cross- Laminated Timber Panel Construction - Part 2 Matthew GOLDEN 1 ; Wilson BYRICK 2 1,2 Pliteq Inc., Canada ABSTRACT At INTER-NOISE
More informationKINETICS NOISE CONTROL TEST REPORT #AT001052
KINETICS NOISE CONTROL TEST REPORT #AT001052 KINETICS NOISE CONTROL PRODUCTS: o ISOMAX CLIPS ACOUSTICAL RATINGS: o STC 66 o IIC 44 TESTING AGENCY & REPORT NUMBER: o NATIONAL RESEARCH COUNCIL OF CANADA
More informationFLOOR CEILING ASSEMBLY
FLOOR CEILING ASSEMBLY DIRECT FIX TO SOLID WOOD JOIST FCWT RAL IN09-012 Toll Free (866) 774-2100 WWW.PAC-INTL.COM Fire Resistance Ratings CONSTRUCTION 3/8" HARDWOOD FLOORING VAPOR BARRIER 3/4 LT WT CONCRETE
More informationSignatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only.
ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements ASTM E 492: Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using
More informationE R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to REGUPOL AMERICA
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to REGUPOL AMERICA Series/Model: Regupol 8 mm SonusWave Impact Sound Underlayment Specimen Type: Open Web Truss - 406 mm Overall Size:
More informationD R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to REGUPOL AMERICA
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E 2179 Rendered to REGUPOL AMERICA Regupol Sonus HS300 3 mm Underlayment Specimen Type: Floor/Ceiling Assembly Overall Size: 3023 mm by 3632
More informationREGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT
REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E9 AND ASTM E492 TESTING ON 18" OPEN WEB TRUSS WITH 3MM SONUS, HARDWOOD FLOOR AND SONUSCLIP CEILING SPECIMEN TYPE Open Web Truss -
More informationKINETICS NOISE CONTROL TEST REPORT #AT001035
KINETICS NOISE CONTROL TEST REPORT #AT001035 KINETICS NOISE CONTROL PRODUCTS: o RIM I-2-16 ACOUSTICAL RATINGS: o STC 66 o IIC 63 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o B-3140.1 KINETICS DRAWING
More informationACOUSTICAL PERFORMANCE TEST REPORT
REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E9 AND ASTM E492 TESTING ON 1MM REGUPOL SONUS SOUND CONTROL UNDERLAYMENT UNDER CERAMIC TILE SPECIMEN TYPE 23 mm Concrete Slab with
More informationKINETICS NOISE CONTROL TEST REPORT #AT001067
KINETICS NOISE CONTROL TEST REPORT #AT001067 KINETICS NOISE CONTROL PRODUCTS: o FLM- NEOPRENE PAD ACOUSTICAL RATINGS: o STC 69 o IIC 61 TESTING AGENCY & REPORT NUMBER: o NATIONAL RESEARCH COUNCIL OF CANADA
More informationH R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to KOLAY FLOORING INTERNATIONAL, LLC
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to KOLAY FLOORING INTERNATIONAL, LLC Series/Model: Kolay KW 110 Specimen Type: Open Web Truss - 457 mm Overall Size: 3048 mm by 3658
More informationRSIC ACOUSTIC ASSEMBLY
RSIC ACOUSTIC ASSEMBLY FLOOR CEILING ASSEMBLY World Leader in Noise Control Solutions DIRECT FIX TO WOOD OPEN WEB TRUSS F4545.07 STC 61 IIC 54 CONSTRUCTION Hacker Industries, Inc. Firm-Fill Gypsum Concrete
More informationKINETICS NOISE CONTROL TEST REPORT #AT001021B
KINETICS NOISE CONTROL TEST REPORT #AT001021B KINETICS NOISE CONTROL PRODUCTS: o ICW ACOUSTICAL RATINGS: o STC 76 o IIC 62 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o B3463.13 KINETICS DRAWING NUMBER:
More informationD R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to PROTECTO WRAP COMPANY. Series/Model: Whisper Mat CS
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to PROTECTO WRAP COMPANY Series/Model: Whisper Mat CS Specimen Type: Sound Control & Crack Suppression Membrane Overall Size: 3023 mm
More informationE R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to REGUPOL AMERICA
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E 2179 Rendered to REGUPOL AMERICA Series/Model: 3 mm Regupol Sonus Rubber Underlayment Specimen Type: Floor/Ceiling Assembly Overall Size:
More informationE R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to REGUPOL AMERICA
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E 2179 Rendered to REGUPOL AMERICA Series/Model: 5 mm Regupol Sonus Rubber Underlayment Specimen Type: Floor/Ceiling Assembly Overall Size:
More informationH R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to AMORIM CORK COMPOSITES
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to AMORIM CORK COMPOSITES Series/Model: AcoustiCORK ECOx2 Sound Reduction Underlayment for LVT Plank Flooring Specimen Type: 152 mm
More informationRSIC ACOUSTIC ASSEMBLY
RSIC ACOUSTIC ASSEMBLY FLOOR CEILING ASSEMBLY DIRECT FIX TO SOLID WOOD JOIST FCWT RAL IN08-016 CONSTRUCTION Sheet Vinyl 1/2 Wood Underlayment 5/8 Plywood Subfloor (*L513 3/4 Ply) 2" X 10" Solid Wood Joist
More informationVULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E90 AND ASTM E492 TESTING ON ATTAIN LVT OVER 2 MM ECOSILENCE UNDERLAYMENT
VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E9 AND ASTM E492 TESTING ON ATTAIN LVT OVER 2 MM ECOSILENCE UNDERLAYMENT SPECIMEN TYPE Vulcraft 2 Gage Dove 2. Tail Steel Deck
More informationD R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to REGUPOL AMERICA
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E 2179 Rendered to REGUPOL AMERICA Series/Model: Regupol Sonus LV200 2mm Underlayment Specimen Type: Floor/Ceiling Assembly Overall Size:
More informationREGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT
REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E9 AND ASTM E492 TESTING ON 1MM REGUPOL SONUS SOUND CONTROL UNDERLAYMENT UNDER CERAMIC TILE SPECIMEN TYPE Concrete Slab - 23 mm REPORT
More informationC R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: Base 10
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to Series/Model: Base 10 Specimen Type: Floor/Ceiling Assembly Overall Size: 3023 mm by 3632 mm Summary of Test Results Data File Result
More informationSignatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only.
ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements ASTM E 492: Laboratory Measurement of Impact Sound Transmission through Floor- Ceiling Assemblies Using
More informationH R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to PROTECTO WRAP. Series/Model: Protecto Wrap Whisper Mat CS
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to PROTECTO WRAP Series/Model: Protecto Wrap Whisper Mat CS Specimen Type: Open Web Truss - 457 mm Overall Size: 3048 mm by 3658 mm
More informationINTRODUCTION SPECIMEN DESCRIPTION
INTRODUCTION SPECIMEN DESCRIPTION Airborne sound transmission measurements were performed on a wall assembly with a single layer of the product identified by the client as QuietRock QR-530 Serenity on
More informationKINETICS NOISE CONTROL TEST REPORT #AT001032
KINETICS NOISE CONTROL TEST REPORT #AT001032 KINETICS NOISE CONTROL PRODUCTS: o ICC ACOUSTICAL RATINGS: o STC 84 o IIC 70 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o B-3448.12 KINETICS DRAWING NUMBER:
More informationFOR: CEMCO - California Expanded Metal Products Co. Sound Transmission Loss Test
FOR: CEMCO - California Expanded Metal Products Co. Sound Transmission Loss Test Industry, CA ON: Bare 1 Inch Thick USG LEVELROCK Brand CSD Floor Underlayment on USG LEVELROCK SRM-25 Sound Mat on CEMCO
More informationVULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT
VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E9 AND ASTM E492 TESTING ON FUSION HYBRID OVER 2 MM ECOSILENCE UNDERLAYMENT SPECIMEN TYPE Vulcraft 2 Gage Dove Tail 3.5 Steel
More informationH R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to AMORIM CORK COMPOSITES
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to AMORIM CORK COMPOSITES Series/Model: AcoustiCORK ECOx2 Sound Reduction Underlayment for LVT Plank Flooring Specimen Type: Open Web
More informationE R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to SENECA RADIANT TECHNOLOGIES
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to SENECA RADIANT TECHNOLOGIES Series/Model: Floor/Ceiling Assembly Specimen Type: Dimensional Lumber - 2x10 Overall Size: 3023 mm by
More informationRSIC ACOUSTIC ASSEMBLY
RSIC ACOUSTIC ASSEMBLY FLOOR CEILING ASSEMBLY DIRECT FIX TO WOOD OPEN WEB TRUSS TFCSW RAL IN09-044 STC 54 IIC 52 CONSTRUCTION Hardwood Flooring 1/16" Foam Underlayment 3/4 T&G OSB Subfloor 11-1/4" Deep
More informationG R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to PROFLEX PRODUCTS, INC.
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E 2179 Rendered to PROFLEX PRODUCTS, INC. Series/Model: 4 mm Luxury Vinyl Plank over LV200 Specimen Type: Concrete Slab - 152 mm Overall Size:
More informationH R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to URBAN SURFACES. Series/Model: Urban Surfaces Soundtec
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to URBAN SURFACES Series/Model: Urban Surfaces Soundtec Specimen Type: 152 mm Concrete Slab with Drop Ceiling Overall Size: 3048 mm
More informationVULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT
VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E9 AND ASTM E492 TESTING ON CERAMIC TILE OVER 5 MM ECOSILENCE UNDERLAYMENT SPECIMEN TYPE Vulcraft 2 Gage Dove Tail 3.5 Steel Deck
More informationKnock on Wood: Acoustical Design in Mass Timber Structures
Knock on Wood: Acoustical Design in Mass Timber Structures Denis Blount Associate Arup Acoustics, AV, Theatre (Seattle) Disclaimer: This presentation was developed by a third party and is not funded by
More informationE R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to REGUPOL AMERICA
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to REGUPOL AMERICA Series/Model: Regupol 7210C Screed Isolation Specimen Type: 203 mm Concrete Slab with Drop Ceiling Overall Size:
More informationRSIC ACOUSTIC ASSEMBLY
RSIC ACOUSTIC ASSEMBLY FLOOR CEILING ASSEMBLY DIRECT FIX TO WOOD I JOIST F4543.05 STC 62 IIC 61 CONSTRUCTION Mannington Hometown Lexington Hickory Hardwood Hacker Industries, Inc. Firm-Fill Gypsum Concrete
More informationSilencer Rubber Underlayment
Silencer Rubber Underlayment Specifications Name: Silencer Rubber Color: Beige & Silver Type: Sound + Vapor Barrier Construction: High Density Rubber & foil barrier film Coverage: 100sqft Thickness: 2mm
More informationH R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to URBAN SURFACES
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E 2179 Rendered to URBAN SURFACES Series/Model: Urban Surfaces Soundtec Specimen Type: Concrete Slab - 152 mm Overall Size: 3048 mm by 3658
More informationIntertek Testing Services
Acoustical 3933 U.S. Rt. Cortland, NY 13045 Phone: 607-753-6711 Fax: 607-756-9891 Order No. J99031102-003 December 10, 1999 REPORT NO. J99031102-003 SOUND TRANSMISSION LOSS TEST AND CLASSIFICATION OF A
More informationVULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT
VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E9 AND ASTM E492 TESTING ON CERAMIC TILE OVER 5 MM ECOSILENCE UNDERLAYMENT SPECIMEN TYPE Vulcraft 2 Gage Dove Tail 3.5 Steel Deck
More informationF R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to PROTECTO WRAP COMPANY
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to PROTECTO WRAP COMPANY Series/Model: Whisper Mat Underlayment with Everbond Adhesive Specimen Type: Concrete Slab - 152 mm Overall
More informationG R1 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to PROTECTO WRAP COMPANY
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E 2179 Rendered to PROTECTO WRAP COMPANY Series/Model: Protecto Wrap Whispermat LVT Specimen Type: Concrete Slab - 152 mm Overall Size: 3023
More informationASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements
ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements 1 of 7 TEST : Acoustical Surfaces, Inc. Report Date: May 25, 2011 Test Date: September 28, 2010 Test
More informationFLOOR CEILING ASSEMBLY
FLOOR CEILING ASSEMBLY DIRECT FIX TO I JOIST FCW-ATI-E6968.08 CONSTRUCTION Sheet Vinyl Ecore Forest FX Plywood 5/8" Waterproof Membrane (15lb Felt) Plywood 5/8" I Joist 12" Deep @ 24" OC Insulation Nominal
More informationGenieMat FF. Floating Floor Systems for Airborne & Impact Sound and Vibration Isolation. It s not magic, it s engineering. Impact Sound Control
It s not magic, it s engineering. Impact Sound Control GenieMat FF Floating Floor Systems for Airborne & Impact Sound and Vibration Isolation Patents: US 8240430, US8556029, CA 2500956, CA 2503420 GenieMat
More informationASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements
ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements 1 of 7 TEST : Acoustical Surfaces, Inc. Report Date: May 25, 2011 Test Date: September 28, 2010 Test
More informationURBAN SURFACES TEST REPORT
URBAN SURFACES TEST REPORT SCOPE OF WORK ASTM E9 AND ASTM E492 TESTING ON URBAN SURFACES SOUNDTEC REPORT NUMBER H4383.13311R TEST DATE 8/1/17 ISSUE DATE 8/16/17 RECORD RETENTION END 8/1/21 PAGES 13 DOCUMENT
More informationREPORT 3933 US ROUTE 11 CORTLAND, NEW YORK Order No October 15, REPORT NO CRT-002d3
REPORT ACCREDITATION UNDER NVLAP 3933 US ROUTE 11 CORTLAND, NEW YORK 13045 Order No. 3166866 October 15, 2013 REPORT NO. 3166866CRT-002d3 IMPACT SOUND TRANSMISSION TEST AND CLASSIFICATION OF LAMINATE FLOORING
More informationImportant Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA
Important Notice In August 1, 2013, PABCO Gypsum, a division of PABCO building products, LLC acquired the QuietRock business and operations from Serious Energy, Inc. Serious Energy, Inc. corporate structure
More informationAcoustics and Mass Timber: Room-to-Room Noise Control
Acoustics and Mass Timber: Room-to-Room Noise Control Richard McLain, PE, SE Senior Technical Director WoodWorks Photo: Corey Gaffer courtesy Perkins + Will T3 Minneapolis Architect: MGA Michael Green
More informationImportant Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA
Important Notice In August 1, 2013, PABCO Gypsum, a division of PABCO building products, LLC acquired the QuietRock business and operations from Serious Energy, Inc. Serious Energy, Inc. corporate structure
More informationE R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 492 AND ASTM E Rendered to REGUPOL AMERICA
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 492 AND ASTM E 2179 Rendered to REGUPOL AMERICA Series/Model: Regupol 6 mm SonusWave Impact Sound Underlayment Specimen Type: Concrete Slab - 152 mm Overall Size:
More informationRSIC ACOUSTIC ASSEMBLY
RSIC ACOUSTIC ASSEMBLY FLOOR CEILING ASSEMBLY DIRECT FIX TO WOOD OPEN WEB TRUSS TFCSW RAL IN09-045 STC 56 IIC 73 CONSTRUCTION Carpet and Pad 3/4 T&G OSB Subfloor 11-1/4" Deep Open Web Truss @ 24" OC R-11
More informationA L I O N Technical Center. Test Report
FOR: Lebanon, PA Impact Sound Transmission CONDUCTED: 2017-07-12 Page 1 of 8 ON: Quarry Floor Tiles and Regupol SonusPlus (underlayment) over 8 inch Concrete Slab (no Ceiling) TEST METHOD Riverbank Acoustical
More informationF R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 9, ASTM E 492, ASTM E 2179 Rendered to EXPANKO, DIVISION OF THE STONCOR GROUP INCORPORATED Series/Model: Expanko CorkCore LVT Specimen Type: 152 mm Concrete Slab
More informationRSIC-1 ACOUSTIC ASSEMBLY
RSIC-1 ACOUSTIC ASSEMBLY FLOOR/CEILING ASSEMBLY DIRECT FIX TO CONCRETE SLAB FCS5 DSWA FIIC 72 CONSTRUCTION * 3/8" Hard Wood flooring * 8" PT concrete slab Fire resistance ratings * R-8 insulation ANS/UL
More informationCopyright 2018 American Wood Council 1
for Wood Frame Assemblies BCD800 Jason Smart, P.E. Manager, Engineering Technology American Wood Council The American Wood Council is a Registered Provider with The American Institute of Architects Continuing
More informationNRC Publications Archive Archives des publications du CNRC
NRC Publications Archive Archives des publications du CNRC Acoustics: sound insulation in mid-rise wood buildings (Report to Research Consortium for wood and wood-hybrid mid-rise buildings) Schoenwald,
More informationFIRM-FILL SCM-400 can be installed under a FIRM-FILL Gypsum Concrete Floor Underlayment to produce an exceptional vibration isolation floor system.
Specify FILL SCM-400 for additional impact noise control when a thicker sound mat is needed. It helps achieve higher delta numbers than thinner mats. FILL SCM-400 is a cost-effective way to address Impact
More informationREPORT 3933 US ROUTE 11 CORTLAND, NEW YORK Order No Date: May 24, 2008 REPORT NO CRT-001
REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK 13045 Order No. 3151742 Date: May 24, 2008 REPORT NO 3151742CRT-001 IMPACT SOUND TRANSMISSION TEST AND CLASSIFICATION OF LM FLOORING ½ INCH ENGINEERED HARDWOOD
More informationSOUND INSULATION ASSESSMENT RANELAGH MULTI-DENOMINATIONAL SCHOOL, DUBLIN October 2014
SOUND INSULATION ASSESSMENT RANELAGH MULTI-DENOMINATIONAL SCHOOL, DUBLIN 6 22 October 2014 Project: Sound Insulation Assessment Ranelagh Multi-Denominational School, Dublin 6 7 Osborne Promenade Warrenpoint
More informationG R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to VENEKLASEN ASSOCIATES
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to VENEKLASEN ASSOCIATES Series/Model: Urban Luxury Vinyl 9553 Gold Line Vinyl Plank Flooring Specimen Type: 152 mm (6") Concrete Slab
More informationG R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to VENEKLASEN ASSOCIATES
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to VENEKLASEN ASSOCIATES Series/Model: Urban Luxury Vinyl 9230 Silver Line Vinyl Plank Flooring Specimen Type: 152 mm (6") Concrete
More informationSoundproofing of Wood-frame buildings
Soundproofing of Wood-frame buildings Learning objectives Basic Acoustic Principles and Definitions Impact and Airborne sounds in light wood-frame buildings Means of soundproofing light wood-frame buildings
More informationSound Control Solutions in Floor/Ceiling Assemblies
Sound Control Solutions in Floor/Ceiling Assemblies Controlling sound becomes more important every day. At SAMfloors, it is our mission to provide elegant, functional sound control solutions to meet the
More informationG R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to US ARCHITECTURAL PRODUCTS, INC.
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to US ARCHITECTURAL PRODUCTS, INC. Series/Model: Plycem CemDeck - No Floor Topping Specimen Type: 8J16 Steel Joist Assembly Overall
More informationG R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to US ARCHITECTURAL PRODUCTS, INC.
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to US ARCHITECTURAL PRODUCTS, INC. Series/Model: Plycem CemDeck with Double Layer Ceiling - No Floor Topping Specimen Type: 8J16 Steel
More informationLISTING INFORMATION OF International Beams - IB Series Joists SPEC ID: 27316
LISTING INFORMATION OF International Beams - IB Series Joists SPEC ID: 27316 International Beams Inc. 2010 Boul. St-Elzear Quest Laval, QC H7L 3N4 CANADA This report is for the exclusive use of Intertek
More informationA L I O N Technical Center. Test Report
FOR: Lebanon, PA Sound Transmission Loss CONDUCTED: 2017-07-12 Page 1 of 9 ON: Quarry Floor Tiles and Regupol SonusPlus (underlayment) over 8 inch Concrete Slab (no Ceiling) TEST METHOD Riverbank Acoustical
More informationAcoustical Characteristics of Carpet
CRI TECHNICAL BULLETIN Acoustical Characteristics of Carpet Carpet is an outstanding sound absorptive material. When properly selected, carpet absorbs airborne noise as efficiently as many specialized
More informationRSIC-1 ACOUSTIC ASSEMBLY
RSIC-1 ACOUSTIC ASSEMBLY FLOOR/CEILING ASSEMBLY DIRECT FIX TO CONCRETE SLAB FCS3 DSWA FIIC 69 PAC INTERNATIONAL Inc. Toll Free 866-774-2100 Telephone 503-649-7700 CONSTRUCTION * Ceramic Tile * 1/4" James
More informationGenieClip. Sound Isolation Clips. It s not magic, it s engineering. Impact and Airborne Sound Control
It s not magic, it s engineering. Impact and Airborne Sound Control GenieClip Sound Isolation Clips Patents: US 7895803, US 9121469, CA 2552516, AU 2007276677, CN 1011919, EPO Patent Pending GenieClip
More informationFlanking Transmission at Joints in Multi-Family Dwellings. Phase 1: Effects of Fire Stops at Floor/Wall Intersections
Flanking Transmission at Joints in Multi-Family Dwellings. Phase 1: Effects of Fire Stops at Floor/Wall Intersections Nightingale, T.R.T. and Halliwell, R.E. IRC-IR-754 www.nrc.ca/irc/ircpubs Flanking
More information1. The subfloor must be structurally sound and able to withstand live and dead loads with a deflection limitation of L/360.
HARDWOOD FLOOR Read First These suggestions represent generally accepted procedures for successful installation of Maxxon Products. These instructions may be followed, modified or rejected by the owner,
More informationG R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: MI WINDOWS AND DOORS, LLC. SERIES/MODEL: 1650 Vinyl
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E9 Rendered to: MI WINDOWS AND DOORS, LLC SERIES/MODEL: 165 Vinyl TYPE: Double Hung Window Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC
More informationREGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT
REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E90 SOUND TRANSMISSION LOSS TESTING ON A STEEL STUD WALL ASSEMBLY WITH SONUSCLIP REPORT NUMBER H7677.03-113-11-R0 TEST DATE 11/20/17
More informationThe specimen B W was identified by the client as a Skyfold Classic operable partition, with panels, seals, and clearances in configuration 4E.
TestingLaboratory: Client: Specimen: SpecimenID: Manufacturer: ConstructionDates: Testspecimenmountedby: NationalResearchCouncilCanada InstituteforResearchinConstruction 1200MontrealRoad Ottawa,OntarioK1A0R6
More informationE R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: THERMA-TRU CORPORATION
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: THERMA-TRU CORPORATION Series/Model: 3/0 x 6/8 Fiber-Classic/Smooth-Star, Full Lite Flush Glazed Type: Side-Hinged Single Door System Summary of
More informationRIVERBANK ACOUSTICAL LABORATORIES
FOR: Denver, Colorado Impact Sound Transmission RAL-IN16-035 CONDUCTED: 2016-11-01 Page 1 of 7 ON: Porcelain Tile flooring - Thinset Mortar - Whisper Mat underlayment - 8 inch Concrete Slabs - No Ceiling
More informationPlease Note: PhoneStar was previously branded as Phonewell
Soundproofing Floors Timber Joist or Concrete Floors Installation Instructions Acoustic Insulation Please Note: was previously branded as Phonewell There are two options to achieve noise reduction through
More informationE R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: THERMA-TRU CORPORATION
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: THERMA-TRU CORPORATION Series/Model: 3/0 x 6/8 Fiber-Classic/Smooth-Star, Full Lite 1" IG Impact Glass with BTS Lite Frame Type: Side-Hinged Single
More informationA few amazing facts about Acoustiblok
A few amazing facts about Acoustiblok A standard metal stud 5/8" gypsum board wall with only 1 layer of 16 oz. Acoustiblok has better sound reduction, (STC 53*, Riverbank Laboratories), than a solid 12"
More informationA L I O N Technical Center. Test Report
FOR: Beachwood, OH Impact Sound Transmission CONDUCTED: 2017-11-15 Page 1 of 8 ON: LVT flooring over Peacemaker Soundproofing Underlayment over 8" Concrete Slab No Ceiling TEST METHOD Riverbank Acoustical
More informationDIRECT FIX TO STEEL STUD Toll Free (866) RAL Assembly STC 58
WALL ASSEMBLY DIRECT FIX TO STEEL STUD Toll Free (866) 774-2100 WWW.PAC-INTL.COM RAL 05-013 Assembly STC 58 58 STC RAL 05-013 STC CONSTRUCTION * 1 layer 5/8" Gypsum * 3-5/8" Steel Stud at 24" oc. * R-19
More informationDIVISION: FINISHES SECTION: ACOUSTIC TREATMENT REPORT HOLDER: ECORE INTERNATIONAL, INC.
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1522 Reissued 09/2016 This report is subject to renewal 09/2018. DIVISION: 09 00
More informationH R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: CUSTOM VINYL PRODUCTS, LLC SERIES/MODEL: SHA4. TYPE: Single Hung Window
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: CUSTOM VINYL PRODUCTS, LLC SERIES/MODEL: SHA4 TYPE: Single Hung Window Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC
More informationGIB Quiet Clip GIB CBI March Features and Benefits
CBI - 5113 March 2002 GIB Quiet Clip Features and Benefits No special flooring systems required Easy fit Installation Significantly improves low frequency sound transmission Significantly improves low
More informationE R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: PAC INTERNATIONAL, LLC
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: PAC INTERNATIONAL, LLC TYPE: Wall, Steel (0.018" / 25 ga), RSIC-V, STC 67 DATA FILE NO: E4748.01A STC 67 OITC 56 Test Specimen Identification: (Source
More information