PRODUCT EVALUATION REPORT
|
|
- June Hunter
- 6 years ago
- Views:
Transcription
1 28 September 2016 Page No. 1 of 6 PRODUCT EVALUATION REPORT Client: HUNTER PRODUCTS Address: LEVEL 2, 424 WARRIGAL ROAD MOORABBIN VIC 3189 Subject: Client Reference: Client s Order No.: PORTABLE POOL FENCE SYSTEM MR DALE MCCLEARY DM2001 Correlation/Report No.: Rev INTRODUCTION It was requested that ALS perform a series of tests on a portable, flexible steel swimming pool fencing system in accordance with AS Swimming Pool Safety Part 1: Safety Barriers for Swimming Pools The supplied system consisted of three fence panels fixed to four steel posts (1400mm high, 2700mm long with 25mm diam. steel posts) and a gate system. The posts were fitted with removable steel ground spikes which for the purposes of qualification were encapsulated in a framework to simulate rigid installation. The middle of each panel was also fitted with an eyelet on the bottom border to allow for a tent peg to fix the barrier to the ground. 2.0 STRENGTH OF POSTS AND FOOTINGS The as supplied fence system was assembled as per the manufacturer s instructions and set for the strength of post and footings as per AS appendix B. The following test parameters were used to generate the test results listed; Fence system: 2700mm x 1400mm with 4 x 25mm diam. steel posts Test locations: 1200mm up from bottom of post as installed Test item: 105mm diam. flat faced bar Load cell: A1771 (50kg 0.01kg resolution) Date of test: 02/08/2016 Result: Nil permanent deflection after 33.7 kg (330N) for 30 seconds No evidence of breaks, loosening or damage impairing the effectiveness of the fence was observed- Complies Rev 1 issued to include gate testing All work is subject to our standard terms and conditions available on our website: Chris Vines Senior Metallurgical Engineer Victoria, AUSTRALIA ADDRESS 450 Dynon Rd, West Melbourne VIC 3003 Australia PHONE FAX ALS INDUSTRIAL PTY LTD ABN Part of the ALS Laboratory Group An ALS Limited Company
2 3.0 STRENGTH OF FLEXIBLE BARRIERS Page No. 2 of 6 The as supplied fence system was assembled as per the manufacturer s instructions and set for the strength of flexible barriers as per AS appendix D. The following test parameters were used to generate the test results listed; Fence system: Test object: Test height: Swing arm: Swing height: 2700mm x 1400mm with 4 x 25mm diam. poles 9.1kg mass with 50mm diameter impact face bottom, mid panel and top (both sides) 1440mm 40 o from vertical Date of test: 02/08/2016 Results: No evidence of breakage, fracture, loosening of components or permanent deflection: - Complies 4.0 MESH BARRIERS The mesh barrier system was assessed for its top pull down resistance by placing a 25kg load in the top centre of the barrier. With the load applied the barrier top edge was 1205mm high and hence complies with section (e)(i). The mesh barrier system was assessed for its bottom pull up resistance by applying a 10kg vertical load to the bottom of the barrier between the pole and the peg. With the load applied the barrier bottom edge was 80mm high and hence complies with section (e)(ii). 5.0 GATE UNIT 5.1 Strength Tests The as suppled gate section was submitted for the strength tests as per AS appendix E. The following test parameters were used to generate the test results listed below; Test locations: Centre of gate and all four corners (both sides) Test force: 330 N (33.7 kg) Date of test: 08/03/2016 Results: Latch remained intact, frame bent less than 3mm - Complies Test location: Top edge of open gate Test force: 250 N (25.5 kg) Result: Gate closes and latches - Complies
3 5.2 Gate Durability Page No. 3 of 6 The as suppled gate section was submitted for the durability tests as per AS appendix F. The following test parameters were used to generate the test results listed below; Initial latching force: 0.21 kg Gate cycles: 10,000 Gate swing: Final latching force: Gate position: Test force: Test direction: Result: 6.0 RESULTS 90 o 0.20 kg Closed 250 N (25.5 kg) Vertical down (from top) and vertical up (from bottom) Gate still self closes and latching force less than 50N. No evidence of unhinging or unlatching and gate dimensions remained - Complies The portable pool fence and gate as supplied complied with the mechanical testing requirements of AS sections (e), 3.2, 3.3.2, 3.4, 3.5 and 3.6.
4 Page No. 4 of 6 Figure: 1 Subject: Pool fence as submitted (shown in test frame with spikes). Figure: 2 Subject: Pool fence spike encapsulation used.
5 Page No. 5 of 6 Figure: 3 Subject: Pool fence top pull down test Figure: 4 Subject: Pool fence bottom pull up test.
6 Figure: 5 Subject: Pool gate as tested. Page No. 6 of 6
BE SAFE POOL FENCE SYSTEM HUNTER PRODUCTS LEVEL WARRIGAL ROAD MOORABBIN 3189 Mr DALE MCCLEARY DM Rev 1 18 January 2018
450 Dynon Rd West Melbourne VIC 3003 T +61 3 8398 5900 F +61 3 9687 6990 21 006 353 046 BE SAFE POOL FENCE SYSTEM HUNTER PRODUCTS LEVEL 2 424 WARRIGAL ROAD MOORABBIN 3189 Mr DALE MCCLEARY DM2001 040157-5
More informationLICENCE. for. Click on the red box above to activate the Licence Agreement scroll bar.
LICENCE for Licensee: Date: Click on the red box above to activate the Licence Agreement scroll bar. See publications covering the same Subject Area Subscribe to our Free Newsletters about Australian Standards
More informationDispute regarding the compliance of outward opening doors to a pool area at 19 Wright Road, Point Chevalier
Determination 2011/071 Dispute regarding the compliance of outward opening doors to a pool area at 19 Wright Road, Point Chevalier 1. The matter to be determined 1.1 This is a Determination under Part
More informationTEST REPORT. Rendered to: KEYLINK FENCING & RAILING, INC. For: PRODUCT: Lancaster Series. TYPE: Aluminum Level Guardrail System
TEST REPORT Rendered to: KEYLINK FENCING & RAILING, INC. For: PRODUCT: Lancaster Series TYPE: Aluminum Level Guardrail System Report No: Report Date: 07/05/13 130 Derry Court York, PA 17406-8405 phone:
More informationNutex Coatings. Nuclad Cladding System Grade-M EPS Foam Board Structural Test Report AS1562.1:1992 Region N2 Non-Cyclonic
Grade-M EPS Foam Board AS1562.1:1992 Region N2 Non-Cyclonic Vipac Engineers & Scientists Ltd 279 Normanby Road, Private Bag 16 Document No. Port Melbourne VIC 3207 30B-12-0015-TRP-264454-2 Australia t.
More informationSECTION CHAIN LINK FENCES
SECTION 02 44 40 PART 1 - GENERAL 1.1 DESCRIPTION A. Work included: Provide chain link fence system where shown on the Drawings, as specified herein, and as needed for a complete and proper installation.
More informationITEM 555 CHAIN LINK FENCING
ITEM 555 AFTER MARCH 1, 2012 CHAIN LINK FENCING 555.1 Description. This item shall govern for furnishing the quantities of chain link fencing and gates as shown on the plans, including all posts, bracing
More informationBear Exhibit Fence Upgrades. The following modifications are hereby made part of the contract documents:
ADDENDUM TO BID T2017-04 Metropolitan Park District Department of Planning, Design and Development 4702 South 19 th Street Tacoma WA 98405 Date Prepared: November 17, 2017 Bid Number: T2017-04 Addendum
More informationCONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY DISTRIBUTION ENGINEERING DISTRIBUTION EQUIPMENT
CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DISTRIBUTION EQUIPMENT SPECIFICATION EO-1124 REVISION 3 November 2013 EFFECTIVE DATE November 11,
More informationPrepared for: American Frame Manufacturing Co Bristow Court, Unit B San Diego, CA Phone: Web:
TESTING LISTING EVALUATION 257 EAST RANDOLPH STREET NAPPANEE, INDIANA 46550 PHONE: 574-773-7975 WWW.NTAINC.COM TESTLAB@NTAINC.COM FAX: 574-773-2260 NEGATIVE WIND PRESSURE TEST ON EXTERIOR SHEATHING FOR
More informationPrepared for: American Frame Manufacturing Co Bristow Court, Unit B San Diego, CA Phone: Web:
TESTING LISTING EVALUATION 257 EAST RANDOLPH STREET NAPPANEE, INDIANA 46550 PHONE: 574-773-7975 WWW.NTAINC.COM TESTLAB@NTAINC.COM FAX: 574-773-2260 NEGATIVE WIND PRESSURE TEST ON EXTERIOR SHEATHING FOR
More informationMechanical Testing. Tensile Compression Bend Flexure Proof Load Structures Fasteners Composites Concrete Fatigue Scaffolds Formwork Force Calibrations
Delivery Address: Postal Address: 1/15 Pickering Road PO Box 5111 Mulgrave Vic 3170 Brandon Park Vic 3150 Telephone: 61 3 9560 2759 Facsimile: 61 3 9560 2769 Email Address: info@melbtest.com.au Web Address:
More informationCity of Wheaton Building and Code Enforcement FENCES
FENCES This guideline has been assembled to assist you with the design, permit application process, and installation of a new or replacement fence. A permit is required before a new fence is installed
More informationTable of contents Our products We are offering three product groups: Quality and Service Our product groups Basic products-panels EURO, Light Version, Compensatory, Round Top Gates and Pedestrian Gates
More informationUpdated May BALUSTRADE & FENCE DESIGN
Updated May 2009 13.23 BALUSTRADE & FENCE DESIGN A glass balustrade is a modern and stylish safety barrier, which provides strength and safety in conjunction with maximum unobstructed views. Glass balustrades
More informationCITY OF MOUNT DORA LIFT STATION CHAINLINK FENCE AND GATE SPECIFICATIONS
CITY OF MOUNT DORA LIFT STATION CHAINLINK FENCE AND GATE SPECIFICATIONS PART 1 - GENERAL 1.01 SUMMARY A. Section Includes furnishing and installing chain-link fabric fence, gate, and appurtenances. 1.02
More informationSECTION CHAIN LINK FENCES AND GATES (PARK)
SECTION 02821 CHAIN LINK FENCES AND GATES (PARK) PART I GENERAL 1.1 SECTION INCLUDES A. Installation of chain link fences, and gate units provided by single source including erection accessories, fittings,
More informationJONES NICHOLSON PTY LTD CONSULTING ENGINEERS
JONES NICHOLSON PTY LTD CONSULTING ENGINEERS For New Advertising Signage Structures Eastern Creek and Dean Park November 5, 2010 Our SYDNEY ABN 51003316032 WOLLONGONG - Tel: 0242280570 PO Box 477, SUTHERLAND
More informationANTI RAM SECURITY CHAIN LINK FENCE - 4, MPH SECTION
ANTI RAM SECURITY CHAIN LINK FENCE - 4,000 LB @ 20 MPH SECTION 32 31 13.53 2015
More informationSECTION CHAIN LINK FENCES AND GATES
SECTION 32 31 13 CHAIN LINK FENCES AND GATES SPEC WRITER NOTE: 1. Delete text between // // not applicable to project. Edit remaining text to suit project. 2. Use this section in specifying permanent chain
More informationCITY OF FRIENDSWOOD TECHNICAL SPECIFICATIONS DOCUMENT 00085B ADDENDUM ADDENDUM NO. 1
ADDENDUM Date of Addendum: December 30 th, 2015 PROJECT NAME: Fencing for Sportspark PROJECT NO: GO1507 BID DATE: Tuesday, January 5 th, 2016 FROM: City of Friendswood Department of Public Works 1306 Deepwood
More informationAppraisal Report for. Building Product Accreditation. For the. NuCLAD. polystyrene exterior insulation and finishing system
Appraisal Report for Building Product Accreditation For the NuCLAD polystyrene exterior insulation and finishing system (an external wall cladding system for Class 1a & 10 buildings) Report prepared by
More informationTEST REPORT. Rendered to: SENTINEL FENCE AND RAIL. For: 120 in by 42 in Fully-Welded Aluminum Guardrail Assembly with Intermediate Support Post
TEST REPORT Rendered to: SENTINEL FENCE AND RAIL For: 120 in by 42 in Fully-Welded Aluminum Guardrail Assembly with Intermediate Support Post Report No: Report Date: 10/23/12 130 Derry Court York, PA 17406-8405
More informationMACHINERY GUARDING SECTION
SECTION MACHINERY GUARDING De-fence is designed to comply with AS4024.1 when used as machinery guarding. Alternatively, its flexible design lends itself to many applications, including forklift separation.
More informationCAPABILITY STATEMENT
CAPABILITY STATEMENT GEOTECHNICAL // ENVIRONMENTAL // TESTING SERVICES SERVICING AUSTRALIA WIDE WITH MOBILE & ANNEX LABORATORIES admin@protestengineering.com Ph: (07) 5568 0180 1/9 Greg Chappell Drive,
More informationCity of Kingston Report to Administrative Policies Committee Report Number AP
To: From: Resource Staff: Date of Meeting: July 10, 2014 Subject: Executive Summary: City of Kingston Report to Administrative Policies Committee Report Number AP-14-017 Chair and Members of Administrative
More informationSystem Overview. Calcium Sulphate Interlock System
System Overview Calcium Sulphate Interlock System Calcium Sulphate Interlock System The SNA Series CS-IL is an access floor system that has been designed for applications where stone or tile finishes are
More informationType: Bar stool Length: 440 mm Width: 370 mm Height: 790 mm Weight: 7,15 kg Materials: Ø 25 mm steel chair
HAY/Nine United Denmark A/S Havnen 1 DK-8700 Horsens Appendices 3 Initials laha/prni/hbs Test Report Material: Model: Palissade Barstool Type: Bar stool Length: 440 mm Width: 370 mm Height: 790 mm Weight:
More informationTITLE: CAMP JOHNSON OVERPASS / HWY 17 BYPASS SECURITY FENCE UPGRADES
CONTRACT # N40085-15B-0457 PROJECT # 15R036CN MACC # 15-0457 MAXIMO# 4608934 TITLE: CAMP JOHNSON OVERPASS / HWY 17 BYPASS SECURITY FENCE UPGRADES ATTACHMENTS: 1. 15-0457 CJ OVERPASS SECURITY UPGRADES Site
More informationORDINANCE NO * * * THE BOARD OF SUPERVISORS OF THE COUNTY OF SAN JOAQUIN, STATE OF CALIFORNIA, DOES ORDAIN AS FOLLOWS:
ORDINANCE NO. 4339 AN ORDINANCE FOR THE PROTECTION OF THE PUBLIC HEALTH AND SAFETY OF THE UNINCORPORATED PORTION OF SAN JOAQUIN COUNTY, STATE OF CALIFORNIA, PRESCRIBING REGULATIONS GOVERNING CONDITIONS
More informationPARTITION PERFORMANCE AUTOCLAVED LIGHTWEIGHT CONCRETE (ALC) WALL PANEL
Note: This report is issued subject to TÜV SÜD PSB's "Terms and Conditions Governing Technical Services". The terms and conditions governing the issue of this report are set out as attached within this
More information2006 INTERNATIONAL RESIDENTIAL CODE
DOCUMENTATION 2006 INTERNATIONAL RESIDENTIAL CODE Code Change No: RB33-06/07 Original Proposal Sections: R301.1.1, Chapter 43; IBC 2301.2, Chapter 35 THIS PROPOSAL IS ON THE AGENDA OF THE IRC BUILDING/ENERGY
More informationARCHIVED. Compliance Document for New Zealand Building Code Clause F4 Safety from Falling Second Edition
Compliance Document for New Zealand Building Code Clause F4 Safety from Falling Second Edition Prepared by the Department of Building and Housing This Compliance Document is prepared by the Department
More informationCONSTRUCTION SPECIFICATION FOR CHAIN LINK FENCE
ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 541 DECEMBER 1990 CONSTRUCTION SPECIFICATION FOR CHAIN LINK FENCE 541.01 SCOPE 541.02 REFERENCES 541.03 DEFINITIONS 541.05 MATERIALS TABLE OF CONTENTS
More informationHEBEI KESHI METAL WIRE MESH CO., LTD. HORSE FENCE PANEL EASILY ASSEMBLED AND DISASSEMBLED PORTABLE AND PERMANENT FENCING
HEBEI KESHI METAL WIRE MESH CO., LTD. HORSE FENCE PANEL EASILY ASSEMBLED AND DISASSEMBLED PORTABLE AND PERMANENT FENCING SAFETY OF ANIMALS AND PEOPLE UTILITY AND VERSATILITY KESHI Horse Fence Panel About
More informationSpecial Provision No. 541S01 October OPSS 541, Construction Specifications for Chain Link Fence, is deleted and replaced with the following:
CHAIN LINK FENCE - Item No. GATES - Item No. Special Provision No. 541S01 October 1998 AMENDMENT TO OPSS 541, DECEMBER 1990 OPSS 541, Construction Specifications for Chain Link Fence, is deleted and replaced
More informationColorado River Aqueduct Pumping Plants 230 kv Disconnect Switches Replacement
DATE: July 15, 2011 ADDENDUM NUMBER: 2 MODIFYING: Specifications No. 1698 PROJECT: Colorado River Aqueduct Pumping Plants 230 kv Disconnect Switches Replacement BID TIME AND DATE: 2:00 p.m., July 19, 2011
More informationAcoustic boundary walls & fencing
1 Acoustic boundary walls & fencing Acoustic boundary walls & fencing Housing Developments Schools & Childcare Centres Aged Care Facilities Shopping Centres & Service Stations Feature Walls & Pool Areas
More informationSECTION ORNAMENTAL WELDED STEEL FENCING
SECTION 032300 ORNAMENTAL WELDED STEEL FENCING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01
More informationAcoustic boundary walls & fencing
1 Acoustic boundary walls & fencing Acoustic boundary walls & fencing Housing Developments Schools & Childcare Centres Aged Care Facilities Shopping Centres & Service Stations Feature Walls & Pool Areas
More informationPERFORMANCE TEST REPORT. Rendered to: SIMTEK FENCE. TYPE: SimTek Privacy Fence System
Architectural Testing PERFORMANCE TEST REPORT Rendered to: SIMTEK FENCE TYPE: SimTek Privacy Fence System Report No: Report Date: 12/13/07 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax: 717-764-4129
More informationSECTION CHAIN LINK FENCES AND GATES
SECTION 32 31 13 CHAIN LINK FENCES AND GATES PART 1 GENERAL 1.1 SUMMARY A. This Section includes materials applicable for commercial/industrial and security vinyl coated chain link fence and framework.
More informationSpecialists in perimeter security and vehicular access control systems. Product Range
Specialists in perimeter security and vehicular access control systems Product Range 20+ years in operation Leda offers an array of innovative products for commercial and government buildings, utilities
More informationFence SpecCheck. A53/A53M-12 Schedule 40 & Schedule 80 Pipe: Specification for Pipe, Steel, Black
Fence SpecCheck ASTM Specifications (December 2017) www.astm.org A53/A53M-12 Schedule 40 & Schedule 80 Pipe: Specification for Pipe, Steel, Black and Hot-Dipped, Zinc Coated, Welded and Seamless Schedule
More informationCW 3550 Chain Link and Drift Control Fence TABLE OF CONTENTS
January 2014 SPECIFICATION CW 3550 R3 CW 3550 Chain Link and Drift Control Fence TABLE OF CONTENTS 1. GENERAL CONDITIONS... 1 3. DESCRIPTION... 1 5. MATERIALS... 1 5.1 Drift Control Fence... 1 5.1.1 Approved
More informationCorrect. On-site truss erection and handling
Correct On-site truss erection and handling For more information on Erecting Trusses consult the Australian Standard AS4440 - Installation of nailplated timber truss and the Multinail publication The Guide.
More informationCONSTRUCTION SPECIFICATION FOR EMBEDDED WORK IN STRUCTURES FOR ELECTRICAL SYSTEMS
ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 913 NOVEMBER 2006 CONSTRUCTION SPECIFICATION FOR EMBEDDED WORK IN STRUCTURES FOR ELECTRICAL SYSTEMS TABLE OF CONTENTS 913.01 SCOPE 913.02 REFERENCES
More informationHouston Community College 3200 Main Parking Garage November 15, 2010 Houston Community College
SECTION 323113 - CHAIN LINK FENCES AND GATES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationMATERIAL SPECIFICATION FOR CHAIN-LINK FENCE COMPONENTS
ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 1541 NOVEMBER 2005 (Reissued November 2010) MATERIAL SPECIFICATION FOR CHAIN-LINK FENCE COMPONENTS TABLE OF CONTENTS 1541.01 SCOPE 1541.02 REFERENCES
More informationRHINO-STOP Modular Vehicle Impact Barriers
RHINO-STOP Product Manual Ref: PM 019/05 Leading Safety Full-scale crash tested systems Compliance to AS/NZS 2890.1 Parking Facilities Compliance to AS/NZS 1170.1 Structural Design Actions BCA compliant
More informationDURApanel. Fencing was the best we have seen very nice to use, brilliant finish, the boss is pleased, we re stoked and will be always recommending it.
DURApanel Smart fencing for homes, pools, and schools Fencing was the best we have seen very nice to use, brilliant finish, the boss is pleased, we re stoked and will be always recommending it. Nelson
More informationSECTION CHAIN LINK FENCING
SECTION 02835 - CHAIN LINK FENCING 1.0 GENERAL 1.1 Furnish and install chain link fencing complete in place with gates and accessories as specified herein and as shown on the Contract Drawings. 1.2 Reference
More informationA better way to build a better home. Permanent Insulated Concrete Formwork
POLYWALL by Polyfoam A better way to build a better home Permanent Insulated Concrete Formwork VICTORIA TASMANIA QUEENSLAND NEW SOUTH WALES 32 Dandenong Street 113 Cove Hill Road 43 Proprietary Street
More informationTEST REPORT. Rendered to: FAIRWAY BUILDING PRODUCTS, LP. For: Solutions Aluminum Guardrail System with Glass Balustrades
TEST REPORT Rendered to: FAIRWAY BUILDING PRODUCTS, LP For: Solutions Aluminum Guardrail System with Glass Balustrades Report No: Report Date: 09/15/10 Revision 1: 09/23/10 130 Derry Court York, PA 17406-8405
More informationCHAIN LINK FENCES AND GATES
SECTION 02831 CHAIN LINK FENCES AND GATES PART 1 GENERAL 1.01 SUMMARY A. Alternate Material for Fence Post and Framing Material: Where schedule 40 galvanized steel is specified, the following will be accepted:
More informationWILTON MANORS, Island City 2020 WILTON DRIVE, WILTON MANORS, FLORIDA 33305
FENCES FENCES This checklist is designed to expedite permit application processing by ensuring that all required documentation is submitted with your permit application. REQUIRED PERMIT APPLICATION(S)
More informationDENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION CHAIN LINK FENCING
PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Requirements vary. A/E shall consult with DPS project manager to determine extent and type of permanent site fencing to be employed. B. Provide
More informationCHAIN LINK FENCES AND GATES
SECTION 02831 CHAIN LINK FENCES AND GATES PART 1 GENERAL 1.01 REFERENCES AND CODES A. Florida Department of Education, Office of Educational Facilities - State Requirements for Educational Facilities -
More informationSECTION CHAIN LINK FENCES AND GATES
SECTION 02831 CHAIN LINK FENCES AND GATES PART 1 GENERAL 1.01 REFERENCES AND CODES A. Florida Department of Education, Office of Educational Facilities - State Requirements for Educational Facilities -
More informationSCHCADS Award 2010 (depending on experience)
Communication Rights Australia Job title: Hours: Salary range: Location: Region: Reports to: Human Rights Advocate 22.8 hours per week SCHCADS Award 2010 (depending on experience) 4/3 Tuck Street, Moorabbin
More informationA. ASTM A121 Specification for Metallic-Coated Carbon Steel Barbed Wire. B. ASTM A392 Specification for Zinc-Coated Steel Chain-Link Fence Fabric
SECTION 32 31 13 CHAIN LINK FENCE AND GATES 2015 PART 1 GENERAL 1.1 RELATED DOCUMENTS A. DIVISION 01 - GENERAL REQUIREMENTS: Drawings, quality, product and performance requirements, general and supplemental
More informationInfrastructure Mining Rail Water Domestic
Infrastructure Mining Rail Water Domestic ABOUT Tycon Group Pty Ltd is a vibrant construction company with operations in Victoria and Queensland focusing on a broad range of projects in civil infrastructure,
More informationREPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF BAILEY INTERIORS EXPOSED NU SHADEX PERFORATED PLASTER CEILING TILES (600MM
RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON
More informationMERCHANTS METALS. A. ASTM F552 Standard Terminology Relating to Chain Link Fencing
MERCHANTS METALS SECTION 32 31 13 COLORBOND CHAIN LINK FENCE AND GATES 2014 PART 1 GENERAL 1.1 RELATED DOCUMENTS A. DIVISION 01 - GENERAL REQUIREMENTS: Drawings, quality, product and performance requirements,
More informationTEST REPORT. Fire resistance load-bearing test of a 136mm thick Ozone Panels wall system tested in accordance with AS
TEST REPORT Fire resistance load-bearing test of a 136mm thick Ozone Panels wall system tested in accordance with AS 1530.4 2005. EWFA Report No: 2758400 Report Sponsor: Ozone Panels Level 31, 367 Collins
More informationANTI-PERSONNEL SECURITY FENCE RIGID WELDED MESH (RWM)
ANTI-PERSONNEL SECURITY FENCE RIGID WELDED MESH (RWM) Al Kuhaimi Metal Industries ltd. (KMI) is pleased to announce the newly product launched the Rigid Welded Mesh (RWM) system on rolls and panels. Both
More informationThrough-glass patch fittings supporting cantilevered glass panels
Through-glass patch fittings supporting cantilevered glass panels design elements F8 190 (rise) 38 domestic grade patch fittings used. 190 (rise) 38 domestic grade patch fittings used. Through-glass patch
More informationFeature Truss. design elements
Feature Truss design elements T1 Floor to floor structural rise Floor to floor covered rise Feature Truss T1 design Eliminating the traditional distinctions between stringer, handrail and stanchion, the
More informationIdentifying Strip Drains Behind Concrete Medians:
CMD Civil Pty Ltd PO Box 1119 Huntingdale VIC 3166 +61 3 9544 8833 info@cmdcivil.com www.cmdcivil.com Case Study: Identifying Strip Drains Behind Concrete Medians: This application note demonstrates an
More informationMechanical Testing. Tensile Compression Bend Flexure Proof Load Structures Fasteners Composites Concrete Fatigue Scaffolds Formwork Force Calibrations
Delivery Address: Postal Address: 1/15 Pickering Road PO Box 5111 Mulgrave Vic 3170 Brandon Park Vic 3150 Telephone: 61 3 9560 2759 Facsimile: 61 3 9560 2769 Email Address: info@melbtest.com.au Web Address:
More informationSAFETY ACCESSORIES. Accessories can help you to enhance safety in your warehouse
SAFETY ACCESSORIES Accessories can help you to enhance safety in your warehouse Safety Accessories PROTECTORS Ensuring your warehouse is safe and complies with the latest legislation is critical. CSI
More informationCHAPTER 26 FENCES. Corner lot means a lot which has two or more adjoining sides, each of which abut the right-of-way of a different street or highway.
CHAPTER 26 FENCES 26.01 PURPOSE. The purpose of this chapter is to regulate the construction and maintenance of fences in the Village. Fences erected and maintained in the Village may be constructed and
More informationFor children ages 3-12 For outdoor domestic use only.
Forde double swing & Glider For children ages 3-12 For outdoor domestic use only. - Not suitable for children under 36 months due to small parts, cords and the design of the product. - Suffocation hazard:
More informationType: Chair Length: 580 mm Width: 460 mm Height: 800 mm Weight: 7 kg Materials: Metal chair Ø 25 mm tubes
HAY/Nine United Denmark A/S Havnen 1 DK-8700 Horsens Order no. 677359-9 rev 2 Appendices 3 Initials laha/prni/hbs Test Report Material: Model: Palissade Chair Type: Chair Length: 580 mm Width: 460 mm Height:
More informationSECTION ALUMINUM GATES
P.O. Box 1058 370 South Athol Rd. Athol, Massachusetts 01331 Phone: (978) 249-7924 Fax: (978) 249-3072 SECTION ALUMINUM GATES PART 1 GENERAL 1.01 SCOPE OF WORK A. The CONTRACTOR shall furnish all labor,
More informationASSESSMENT REPORT. The fire resistance performance of UltraMgO - Partition 20 Party Wall System if tested in accordance with AS1530.
ASSESSMENT REPORT The fire resistance performance of UltraMgO - Partition 20 Party Wall System if tested in accordance with AS1530.4-2014 EWFA Report No: RIR 46975500.2 Report Sponsor: Fireproof Cladding
More informationOptional & Reto-fit Extras
Optional & Reto-fit Extras Divider Nets Roof Netting Ball-Stop Netting Anti-Climb Systems Acoustic & Perimeter Fencing Retro-Fit Gates & Kick Boards DIVIDERNETS Maximise Your Space Sports pitch divider
More informationSHELVING.
SHELVING m-span shelving specs & application guide The all new M-Span shelf is designed to be easy to clean and last a lifetime for an affordable price. Made by over moulding a sub frame with Food Grade
More informationMetro Trains Melbourne Pty Ltd. Access Arrangement
Metro Trains Melbourne Pty Ltd Access Arrangement Contents 1 INTRODUCTION 2 1.1 Purpose of this Document 2 1.2 Commencement Date and Term 2 1.3 Composition of the Access Arrangement 2 1.4 Definitions and
More informationPORTABILITY The Kee Dome range has been designed in component form to ensure that it can be easily transported both to site and up to roof level.
O&M - KEE DOME Kee Dome INTRODUCTION The Kee Dome range of modular systems has been designed specifically to prevent falls through rooflights. UNIQUE DESIGN These innovative products provide protection
More informationMiller Collective Safety at Height Solutions EPIC ULTRA Barrier System EPIC Post-N-Barrier System EPIC Basic Barrier System
For over 65 years the Miller brand has been synonymous with personal fall protection products and services. As the global leader in safety at height solutions, Honeywell Safety Products introduces a new
More informationA. Product Data shall be provided for each type of product indicated.
32 31 13 CHAIN LINK FENCES AND GATES SECTION 1 GENERAL 1.1 SUMMARY This Section includes the following: 1. Chain Link Fences 2. Gates for Chain Link Fences. See electrical specifications for electrical
More informationFence Requirements Permits and Inspections Division 151 W Church Street, Lewisville, Texas Phone: Fence Requirements
151 W Church Street, Lewisville, Fence Requirements General Information Any new fence or replacement fence exceeding 20 feet in length requires a permit. If a contractor is used, that contractor must be
More informationIAN BENNIE AND ASSOCIATES TEST REPORT NO R1 EVERBRIGHT E610 CLEAR POLYCARBONATE CLADDING SYSTEM. IMPACT TESTS to AS
IAN BENNIE AND ASSOCIATES TEST REPORT NO. 2009-128-R1 EVERBRIGHT E610 CLEAR POLYCARBONATE CLADDING SYSTEM IMPACT TESTS to AS1562.3-2006 for Everbright Roofing Systems P/L February 2010 Accredited Laboratory
More informationFoamular Metric XPS in Precast Applications
Foamular Metric XPS in Precast Applications Foamular Metric XPS Insulation and HK low conductivity ties are specifically designed for use in site cast or precast insulated concrete sandwich panels. These
More informationGRP FENCING - MESH BARBICAN FINISHES APPLICATIONS. 4Grey RAL 7001 as standard 4Other colours available on request
WELDED MESH PANELS Operating within the fencing industry since 1947, Jacksons have forged a reputation for delivering proven perimeter security applications. Today, as part of our product portfolio the
More informationSECTION ORNAMENTAL ALUMINUM FENCING
SECTION 032300 ORNAMENTAL ALUMINUM FENCING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationFence Stone. Self locating Wall System
Fence Stone Self locating Wall System Between wall panels End of walls at gate openings etc Internal & external right angles Do it yourself No bricklaying skills required Attractive & efficient For fences
More informationsteel framing installation guide Steel Stud Drywall Framing Systems
steel framing installation guide Steel Stud Drywall Framing Systems rondo STEEL STUD & TRACK SECTIONS GENERAL INFORMATION Rondo Steel Stud Drywall Framing Systems provide designers with a versatile and
More informationFRP ECOLITE RANGE Product Information Booklet
FRP ECOLITE RANGE 2015-2016 Product Information Booklet Road Safety Grating 13 Healey Rd Dandenong South VIC 3175 PH: (03) 9238 5888 Fax: (03) 9238 5800 Email: sales@grating.com.au Web: www.grating.com.au
More informationAS/NZS 2712:2002 amdt 2 Hail Resistance Testing of an Apricus Solar Collector
AS/NZS 2712:2002 amdt 2 Hail Resistance Testing of an Apricus Solar Collector Report No. 30S-06-0026-TRP-294493-0 July 2007 Vipac Engineers & Scientists Ltd Melbourne, Australia Hail Resistance Testing
More informationTEST REPORT. Rendered to: AFCO INDUSTRIES, INC. For: PRODUCT: Redi-Rail. TYPE: Aluminum Level Guardrail System
TEST REPORT Rendered to: AFCO INDUSTRIES, INC. For: PRODUCT: Redi-Rail TYPE: Aluminum Level Guardrail System Report No: A5899.01-119-19 Report Date: 01/03/11 130 Derry Court York, PA 17406-8405 phone:
More informationSECTION CHAIN-LINK FENCES AND GATES 02821/1
SECTION 02821 - CHAIN-LINK FENCES AND GATES 02821/1 PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Chain-Link Fences: 2. Gates: horizontal slide or swing. 3. Fences installed where
More informationTECHNICAL BULLETIN 1. EHSP Field and Laboratory Testing Results. total quality total service Total Steel
TECHNICAL BULLETIN 1 EHSP Field and Laboratory Testing Results total quality total service Total Steel Darwin Phone: (08) 8984 4324 Fax: (08) 8947 4615 Email: darwin@totalsteel.com.au Brisbane Phone: (07)
More informationBERKELEY COUNTY ENGINEERING AND
BERKELEY COUNTY ENGINEERING AND BUILDING INSPECTIONS 400 West Stephen Street - Suite 202, Martinsburg, WV 25401 Telephone: 304-264-1966 Fax: 304-262-3128 Web Page: www.berkeleywv.org SWIMMING POOL REQUIREMENTS
More informationSelf Locating Wall System
From... Self Locating Wall System For fences from low gardens to 2.2 metres high The revolutionary new DIY fence system incorporating purpose made pier blocks for: v Between wall panels v End of walls
More informationPHYSICAL BARRIERS MACHINE GUARDS ROBOTIC WORK CELLS PERIMETER OR AREAS GUARDS PHYSICAL BARRIERS
PHYSICAL BARRIERS MACHINE GUARDS ROBOTIC WORK CELLS PERIMETER OR AREAS GUARDS PHYSICAL BARRIERS Quick-Ship Ships in 48 Hours The 6-2 Guard System Our barriers are a reliable, versatile, and economical
More informationAcronem Consulting Australia Pty Ltd
Acronem Consulting Australia Pty Ltd April 29, 2016 Peak Products Corporation C/- 27 Zilla Court Dandenong VIC 3175 To whom it may concern: CERTIFICATE OF COMPLIANCE: Peak Aluminium Balustrade & Peak Aluminium
More informationAs a scaffold user, Mr Scaffold recommends Method 1, but both options are suitable.
20 EASYSCAF t TM The Next Level 1300 MR SCAFFOLD (1300 677 223) 12 Lagana Place Wetherill Park NSW 2164 Fax: (02)9725 5214 ABN: 65 088 652 144 Re: Workcover Update Feb 2011 Thankyou for purchasing your
More informationPERFORMANCE EVALUATION TEST REPORT. Rendered to: CBT SUPPLY, INC. / D.B.A. SMARTDESKS
PERFORMANCE EVALUATION TEST REPORT Rendered to: CBT SUPPLY, INC. / D.B.A. SMARTDESKS PRODUCT: FFIT Floor TYPE: Fixed Height Low Profile Raised Floor System Component Report No: A9300.03-06-3 Report Date:
More information