RESIDENTIAL HVAC SYSTEM DESIGN REPORT

Size: px
Start display at page:

Download "RESIDENTIAL HVAC SYSTEM DESIGN REPORT"

Transcription

1 RESIDENTIAL HVAC SYSTEM DESIGN REPORT

2 Table of Contents PE LOAD CALCS, LLC ) HVAC System Design Disclaimer 2) Equipment Selection Form 3) Heat Pump Balance Point Diagram 4) Examiner Review Form 5) Building Analysis Report 6) Project Summary Report 7) Manual J Worksheets 8) Duct System Summary 9) Friction Rate Worksheet 1) Duct Distribution Drawing 11) Air Volume Balance Report Form 12) Equipment Bill of Materials 13) ASHRAE 62.2 Report

3 HVAC System Design Disclaimer PE LOAD CALCS, LLC The following pages summarizes the load calculations, equipment selection, and duct design of a residence using ACCA/ASHRAE procedures (J, S, D, 62.2) and current codes (IRC, IECC). All calculations are based on information given to PE Load Calcs LLC in the form of surveys, drawings, sketches, pictures, and meetings. In certain cases, PE Load Calcs may make reasonable assumptions about design conditions and construction materials that may or may not be accurate for the building of concern. It is the responsibility of the installing HVAC contractor to verify the design conditions, construction materials, and compatibility with existing equipment before equipment purchase and installation. All HVAC system design work provided in the following pages are based upon information provided by the particular party submitting a particular project to PE Load Calcs. PE Load Calcs has not and does not independently verify that the data provided to us is correct or complete, and any design made by PE Load Calcs are based upon the information provided by third parties. PE Load Calcs makes no claim that the information given to us is correct or complete. PE Load Calcs utilizes the latest Wrightsoft s Right-Suite Universal 215 which is an ACCA Certified and ASHRAE recommended HVAC system design software. The mathematical model and design of the HVAC system, designed by PE Load Calcs, is only as accurate as the input provided. PE Load Calcs makes every attempt possible to be as detailed and accurate as possible, however, there is no reasonable means to mathematically model an HVAC system that has not been properly installed, or has had after-the-fact building modifications or HVAC system component alterations or substitutions. If there is any construction modifications (floor plan, roofing material, window types/sizes, insulation characteristics, or any other change that will alter the load calculation results), HVAC equipment substitutions, duct sizing or layout changes, which is not noted in this report, and therefore not provided to PE Load Calcs for consideration for the HVAC system design, then PE Load Calcs may not guarantee the performance of the HVAC system design, and all design standards and procedures performed for this HVAC system design, including this report, may no longer be valid. PE Load Calcs will not guarantee the performance of the HVAC system design if the equipment selection and/or duct design has been performed by another party. Also, PE Load Calcs will not guarantee the performance of the HVAC system design that has not been properly installed or tested to verify performance has conformed to manufacturer specifications and design criteria provided in this report. It is up to the installing HVAC contractor to properly install, test, and verify all components of the HVAC system. All installing HVAC contractors are expected to follow ACCA Standards 5 and 9 for quality HVAC equipment installation. All information on any existing HVAC equipment (prior to design) to remain with an existing structure must be provided to PE Load Calcs prior to the design for appropriate selection of new and compatible equipment. It is up to the installing HVAC contractor to verify equipment compatibility between with the newly installed equipment (per design) and any existing equipment remaining, via manufacture specifications and airflow/static pressure measurements. PE Load Calcs does not provide architectural or engineering plans or diagrams for the public or for use by contractors or construction companies as final construction documents. PE Load Calcs works with architectural and engineering firms and with contractors in connection with their designs of HVAC systems. Copies of this report, including the completed balance report (and any other documents that need to be completed by the installing HVAC contractor verifying equipment performance meeting design requirements and manufacturer specifications), must be kept on file by the installing HVAC contractor, and also a copy given to the homeowner to remain attached to the HVAC equipment, and to any other party of specific interest (i.e., code official, county, builder/architect). Page 1 of 1

4 Equipment Selection Form From ACCA s Manual S PE LOAD CALCS, LLC anthony.amadio@peloadcalcs.com PROJECT INFORMATION Building Address: City, State and Zip: ASHRAE Location: 77 Lystra Road Harrison TN Chattanooga TN HDD/CDD:.65 Altitude: 689 ACF:.97 COOLING EQUIPMENT Design Conditions Outdoor Design DB: 92 F Total Gain: Btuh Design Airflow: 15 CFM Outdoor Design WB: 75 F Latent Gain: 5975 Btuh Entering Coil DB: 75 F Indoor Design DB: 75 F Sensible Gain: Btuh Entering Coil WB: 63 F Indoor RH: 5 % JSHR:.8 Manufacturer's Performance Data at Actual Design Conditions Equipment Type: Packaged Air Source Heat Pump Condition A or B: A (Applicable to Heat Pumps Only) Manufacturer: Goodman Manufacturing Company Model: GPH14H36H41C Sensible Capacity: 2425 Btuh Total Capacity (TC): 314 Btuh 15 % of Total Gain (TG) 115% TC/TG 9% Y Latent Capacity (LC): 715 Btuh 117 % of Latent Gain (LG) 15% LC/LG 1% Y Adj. Sensible (SC): Btuh 98 % of Sensible Gain (SG) SC/SG 9% Y HEATING EQUIPMENT Design Conditions Outdoor Design DB: 22 F Heat Loss: Btuh Design Airflow: 15 CFM Indoor Design DB: 7 F Humidification: Btuh Entering Coil DB: 69 F Manufacturer s Performance Data at Actual Design Conditions Equipment Type: Manufacturer: Packaged Air Source Heat Pump Goodman Manufacturing Company Model: GPH14H36H41C Output Capacity: 2366 Btuh Supplemental Heat Required: 2481 Btuh Thermal Balance Point: 37 F Backup Equipment Type: Manufacturer: Output Capacity: 1st Stage Supplement: 2nd Stage Supplement: Reserve Heat: Electric Strip - 15 kw Electrical Heat Kit (3 stages of 5 kw) Goodman Manufacturing Company Model: HKR-5 (Qt. 3) 5684 Btuh 127 % load Temp Rise: 5.8 F 5. kw 1st Stage Lock-Out Temp: 37 F 5. kw 2nd Stage Lock-Out Temp: 25 F 5. kw The above equipment was selected in accordance with ACCA Manual S. Page 1 of 1

5 Heat Pump Balance Point Diagram From ACCA s Manual S PE LOAD CALCS, LLC anthony.amadio@peloadcalcs.com Page 1 of 1

6 Residential Plans Examiner Review Form for HVAC System Design (Loads, Equipment, Ducts) Form RPER 1 15 Mar 9 Contractor: Mechanical license: Building plan #: Home address (Street or Lot#, Block, Subdivision): Hamilton County Header Information REQUIRED ATTACHMENTS Manual J1 Form (and supporting worksheets): or MJ1AE Form* (and supporting worksheets): OEM performance data (heating, cooling, blower): Manual D Friction Rate Worksheet: Duct distribution sketch: 77 Lystra Rd, Entire House ATTACHED Yes No Yes No Yes No Yes No Yes No HVAC LOAD CALCULATION (IRC M141.3) Design Conditions Building Construction Information Winter Design Conditions Outdoor temperature: 22 F Indoor temperature: 7 F Total heat loss: Btuh Summer Design Conditions Outdoor temperature: 92 F Indoor temperature: 75 F Grains difference: 38 5% RH Sensible heat gain: Btuh Latent heat gain: 6154 Btuh Total heat gain: 3337 Btuh Building Orientation: Front Door faces North North, East, West, South, Northeast, Northwest, Southeast, Southwest Number of bedrooms: 3 Conditioned floor area: 1679 ft² Number of occupants: 4 Windows Eave overhang depth: Internal shade: Blinds, drapes, etc. Number of skylights: 6.5 ft blinds,drapes HVAC EQUIPMENT SELECTION (IRC M141.3) Heating Equipment Data Cooling Equipment Data Blower Data Equipment type: Furnace, Heat pump, Boiler, etc. Model: Heating output capacity: Pkg ASHP Goodman Mfg. GPH1436H41C Btuh Heat pumps - capacity at winter design outdoor conditions Aux. heating output capacity: Btuh Equipment type: Air Conditioner, Heat pump, etc. Model: Total cooling capacity: Sensible cooling capacity: Latent cooling capacity: Pkg ASHP Goodman Mfg. GPH1436H41C+ 314 Btuh 2425 Btuh 715 Btuh Heating cfm: Cooling cfm: Static pressure: in H2O Fan's rated external static pressure for design airflow HVAC DUCT DISTRIBUTION SYSTEM DESIGN (IRC M161.1) Design airflow: Equipment design ESP: Total device pressure losses: Available static pressure (ASP): cfm in H2O in H2O in H2O Longest supply duct: Longest return duct: Total effective length (TEL): Friction rate: Friction Rate = ASP (TEL x 1) ft ft ft in/1ft Duct Materials Used Trunk duct: Branch duct: Sheet metal Sheet metal I declare the load calculation, equipment, equipment selection and duct design were rigorously performed based on the building plan listed above. I understand the claims made on these forms will be subject to review and verification. Contractor's printed name: Contractor's signature: Anthony Amadio, Deisgner of PE Load Calcs, LLC Date: Reserved for County, Town Municipality or Authority having jurisdiction use. *Home qualifies for MJ1AE Form based on Abridged Edition Checklist Right-Suite Universal RSU18218

7 Building Analysis Entire House Job: 1 Date: Nov 24, 214 By: PE Load Calcs, LLC For: Project Information Joe Chen, Homeowner 77 Lystra Rd, Harrison, TN Phone: (423) tiu Design Conditions Location: Indoor: Heating Cooling Chattanooga Lovell Field AP, TN, US Indoor temperature ( F) 7 75 Elevation: 689 ft Design TD ( F) Latitude: 35 N Relative humidity (%) 5 5 Outdoor: Heating Cooling Moisture difference (gr/lb) Dry bulb ( F) Infiltration: Daily range ( F) - 19 ( M ) Method Blower door Wet bulb ( F) - 75 Shielding / stories 1 (no shielding) / 1 Wind speed (mph) Pressure / AVF 5 Pa / 27 cfm Heating Component Walls Glazing Doors Ceilings Floors Infiltration Ducts Piping Humidification Ventilation Adjustments Total Btuh/ft² Btuh % of load Glazing Doors Ceilings Walls Floors Ducts Infiltration Cooling Component Walls Glazing Doors Ceilings Floors Infiltration Ducts Ventilation Internal gains Blower Adjustments Total Btuh/ft² Btuh % of load Glazing Doors Ceilings Walls Internal Gains Floors Ducts Infiltration Latent Cooling Load = 5975 Btuh Overall U-value =.169 Btuh/ft²- F Data entries checked. 214-Dec-19 13:5:27 Right-Suite Universal RSU18218 Page 1...anian\Documents\Wrightsoft HVAC\77 Lystra.rup Calc = MJ8 Front Door faces: N

8 Project Summary Entire House Job: 1 Date: Nov 24, 214 By: PE Load Calcs, LLC Project Information For: Notes: Joe Chen, Homeowner 77 Lystra Rd, Harrison, TN Phone: (423) tiu Homeowner is also interested in attic duct design should he later decide to abandon his existing old duct system in small unconditioned crawlspace. Design Information Weather: Chattanooga Lovell Field AP, TN, US Winter Design Conditions Summer Design Conditions Outside db 22 F Outside db 92 F Inside db 7 F Inside db 75 F Design TD 48 F Design TD 17 F Daily range M Relative humidity 5 % Moisture difference 38 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh Structure 2129 Btuh Ducts 4622 Btuh Ducts 2272 Btuh Central vent ( cfm) Btuh Central vent ( cfm) Btuh Humidification Btuh Blower Btuh Piping Btuh Equipment load Btuh Use manufacturer's data n Rate/swing multiplier.97 Infiltration Equipment sensible load 228 Btuh Method Blower door Latent Cooling Equipment Load Sizing Shielding / stories 1 (no shielding) / 1 Pressure / AVF 5 Pa / 27 cfm Structure 4372 Btuh Ducts 163 Btuh Heating Cooling Central vent ( cfm) Btuh Area (ft²) Equipment latent load 5975 Btuh Volume (ft³) Air changes/hour Equipment total load Btuh Equiv. AVF (cfm) Req. total capacity at.7 SHR 2.7 ton Heating Equipment Summary Cooling Equipment Summary Make Goodman Mfg. Make Goodman Mfg. Trade GOODMAN, JANITROL, AMANA DISTI... Trade GOODMAN, JANITROL, AMANA DISTI... Model GPH1436H41C Cond GPH1436H41C AHRI ref Coil AHRI ref Efficiency 8 HSPF Efficiency 11.5 EER, 14 SEER Heating input Sensible cooling 252 Btuh Heating output F Latent cooling 18 Btuh Temperature rise 29 F Total cooling 36 Btuh Actual air flow 15 cfm Actual air flow 15 cfm Air flow factor.24 cfm/btuh Air flow factor.45 cfm/btuh Static pressure.56 in H2O Static pressure.56 in H2O Space thermostat Load sensible heat ratio.8 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. Right-Suite Universal RSU anian\Documents\Wrightsoft HVAC\77 Lystra.rup Calc = MJ8 Front Door faces: N 214-Dec-19 13:5:27 Page 1

9 Right-J Worksheet Entire House Job: Date: By: 1 Nov 24, 214 PE Load Calcs, LLC 1 Room name Entire House Guest1 2 Exposed wall 16.5 ft 29.5 ft 3 Room height 8. ft 8. ft heat/cool 4 Room dimensions 15. x 14.5 ft 5 Room area ft² ft² Ty Construction U-value Or HTM Area (ft²) Load Area (ft²) Load number (Btuh/ft²- F) (Btuh/ft²) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12B-bw.97 ne G 1A-w.82 ne G 4A4-2ov.32 ne W 12B-bw.97 se G 4A4-2ov.32 se W 12B-bw.97 sw G 4A4-2ov.32 sw G 4A4-2ov.32 sw G 4A4-2ov.32 sw D 11G.54 sw W 12B-bw.97 nw P 12B-sw D 11G.54 n P 12B-sw C 16B-19ad F 19A-cvcp c) AED excursion -84 Envelope loss/gain a) Infiltration b) Room ventilation 13 Internal gains: Appliances/other 26 Subtotal (lines 6 to 13) Less external load Less transfer Redistribution 14 Subtotal Duct loads 12% 11% % 11% Total room load Air required (cfm) Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 214-Dec-19 13:5:27 Right-Suite Universal RSU18218 Page 1...anian\Documents\Wrightsoft HVAC\77 Lystra.rup Calc = MJ8 Front Door faces: N

10 Right-J Worksheet Entire House Job: Date: By: 1 Nov 24, 214 PE Load Calcs, LLC 1 Room name Master Guest2 2 Exposed wall 33.5 ft 17. ft 3 Room height 8. ft heat/cool 8. ft heat/cool 4 Room dimensions 1. x 273. ft 1. x ft 5 Room area 273. ft² ft² Ty Construction U-value Or HTM Area (ft²) Load Area (ft²) Load number (Btuh/ft²- F) (Btuh/ft²) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12B-bw.97 ne G 1A-w.82 ne G 4A4-2ov.32 ne W 12B-bw.97 se G 4A4-2ov.32 se W 12B-bw.97 sw G 4A4-2ov.32 sw G 4A4-2ov.32 sw G 4A4-2ov.32 sw D 11G.54 sw W 12B-bw.97 nw P 12B-sw D 11G.54 n P 12B-sw C 16B-19ad F 19A-cvcp c) AED excursion Envelope loss/gain a) Infiltration b) Room ventilation 13 Internal gains: 23 Appliances/other Subtotal (lines 6 to 13) Less external load Less transfer Redistribution 14 Subtotal Duct loads 12% 11% % 11% Total room load Air required (cfm) Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 214-Dec-19 13:5:27 Right-Suite Universal RSU18218 Page 2...anian\Documents\Wrightsoft HVAC\77 Lystra.rup Calc = MJ8 Front Door faces: N

11 Right-J Worksheet Entire House Job: Date: By: 1 Nov 24, 214 PE Load Calcs, LLC 1 Room name Mbath Hall 2 Exposed wall 6. ft 6. ft 3 Room height 8. ft heat/cool 8. ft heat/cool 4 Room dimensions 6. x 13.5 ft 1. x 139. ft 5 Room area 81. ft² 139. ft² Ty Construction U-value Or HTM Area (ft²) Load Area (ft²) Load number (Btuh/ft²- F) (Btuh/ft²) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12B-bw.97 ne G 1A-w.82 ne G 4A4-2ov.32 ne W 12B-bw.97 se G 4A4-2ov.32 se W 12B-bw.97 sw G 4A4-2ov.32 sw G 4A4-2ov.32 sw G 4A4-2ov.32 sw D 11G.54 sw W 12B-bw.97 nw P 12B-sw D 11G.54 n P 12B-sw C 16B-19ad F 19A-cvcp c) AED excursion 5-61 Envelope loss/gain a) Infiltration b) Room ventilation 13 Internal gains: 23 Appliances/other Subtotal (lines 6 to 13) Less external load Less transfer Redistribution 14 Subtotal Duct loads 12% 11% % 11% Total room load Air required (cfm) Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 214-Dec-19 13:5:27 Right-Suite Universal RSU18218 Page 3...anian\Documents\Wrightsoft HVAC\77 Lystra.rup Calc = MJ8 Front Door faces: N

12 Right-J Worksheet Entire House Job: Date: By: 1 Nov 24, 214 PE Load Calcs, LLC 1 Room name Dining Kitchen 2 Exposed wall 11. ft 1. ft 3 Room height 8. ft heat/cool 8. ft heat/cool 4 Room dimensions 11. x 12.5 ft 1. x 12.5 ft 5 Room area ft² 125. ft² Ty Construction U-value Or HTM Area (ft²) Load Area (ft²) Load number (Btuh/ft²- F) (Btuh/ft²) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12B-bw.97 ne G 1A-w.82 ne G 4A4-2ov.32 ne W 12B-bw.97 se G 4A4-2ov.32 se W 12B-bw.97 sw G 4A4-2ov.32 sw G 4A4-2ov.32 sw G 4A4-2ov.32 sw D 11G.54 sw W 12B-bw.97 nw P 12B-sw D 11G.54 n P 12B-sw C 16B-19ad F 19A-cvcp c) AED excursion Envelope loss/gain a) Infiltration b) Room ventilation 13 Internal gains: Appliances/other 12 Subtotal (lines 6 to 13) Less external load Less transfer Redistribution 14 Subtotal Duct loads 12% 11% % 11% Total room load Air required (cfm) Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 214-Dec-19 13:5:27 Right-Suite Universal RSU18218 Page 4...anian\Documents\Wrightsoft HVAC\77 Lystra.rup Calc = MJ8 Front Door faces: N

13 Right-J Worksheet Entire House Job: Date: By: 1 Nov 24, 214 PE Load Calcs, LLC 1 Room name Laundry Living 2 Exposed wall 6. ft 29. ft 3 Room height 8. ft heat/cool 8. ft heat/cool 4 Room dimensions 6. x 9. ft 29. x 13. ft 5 Room area 54. ft² 377. ft² Ty Construction U-value Or HTM Area (ft²) Load Area (ft²) Load number (Btuh/ft²- F) (Btuh/ft²) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12B-bw.97 ne G 1A-w.82 ne G 4A4-2ov.32 ne W 12B-bw.97 se G 4A4-2ov.32 se W 12B-bw.97 sw G 4A4-2ov.32 sw G 4A4-2ov.32 sw G 4A4-2ov.32 sw D 11G.54 sw W 12B-bw.97 nw P 12B-sw D 11G.54 n P 12B-sw C 16B-19ad F 19A-cvcp c) AED excursion Envelope loss/gain a) Infiltration b) Room ventilation 13 Internal gains: Appliances/other 5 9 Subtotal (lines 6 to 13) Less external load Less transfer Redistribution 14 Subtotal Duct loads 12% 11% % 11% Total room load Air required (cfm) Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 214-Dec-19 13:5:27 Right-Suite Universal RSU18218 Page 5...anian\Documents\Wrightsoft HVAC\77 Lystra.rup Calc = MJ8 Front Door faces: N

14 Right-J Worksheet Entire House Job: Date: By: 1 Nov 24, 214 PE Load Calcs, LLC 1 Room name Bath 2 Exposed wall 12.5 ft 3 Room height 8. ft heat/cool 4 Room dimensions 8. x 13.5 ft 5 Room area 18. ft² Ty Construction U-value Or HTM Area (ft²) Load Area Load number (Btuh/ft²- F) (Btuh/ft²) or perimeter (ft) (Btuh) or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12B-bw.97 ne G 1A-w.82 ne G 4A4-2ov.32 ne W 12B-bw.97 se G 4A4-2ov.32 se W 12B-bw.97 sw G 4A4-2ov.32 sw G 4A4-2ov.32 sw G 4A4-2ov.32 sw D 11G.54 sw W 12B-bw.97 nw P 12B-sw D 11G.54 n P 12B-sw C 16B-19ad F 19A-cvcp c) AED excursion -12 Envelope loss/gain a) Infiltration b) Room ventilation 13 Internal gains: 23 Appliances/other Subtotal (lines 6 to 13) Less external load Less transfer Redistribution 14 Subtotal Duct loads 12% 11% Total room load Air required (cfm) Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 214-Dec-19 13:5:27 Right-Suite Universal RSU18218 Page 6...anian\Documents\Wrightsoft HVAC\77 Lystra.rup Calc = MJ8 Front Door faces: N

15 Duct System Summary Entire House Job: 1 Date: Nov 24, 214 By: PE Load Calcs, LLC For: Project Information Joe Chen, Homeowner 77 Lystra Rd, Harrison, TN Phone: (423) tiu Heating Cooling External static pressure.56 in H2O.56 in H2O Pressure losses.3 in H2O.3 in H2O Available static pressure.26 in H2O.26 in H2O Supply / return available pressure.25 /.55 in H2O.25 /.55 in H2O Lowest friction rate.94 in/1ft.94 in/1ft Actual air flow 15 cfm 15 cfm Total effective length (TEL) 277 ft Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh) (cfm) (cfm) FR (in) (in) Matl Ln (ft) Ln (ft) Trunk Bath Dining-A Dining-B Guest1-A Guest1-B Guest2-A Hall-A Kitchen-A Laundry-A Living-A Living-B Master-A Master-B Mbath-A h c c h h h h c c c c h h h st2 st2 st2a st3 st3a st2 st2 st2b st2b st2 st2a st3 st3 st2 Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st2 Peak AVF x 18 ShtMetl st1 st3 Peak AVF x 1 ShtMetl st1 st1 Peak AVF x 24 ShtMetl st2a Peak AVF x 12 ShtMetl st2 st2b Peak AVF x 8 ShtMetl st2a st3a Peak AVF x 8 ShtMetl st3 Bold/italic values have been manually overridden Right-Suite Universal RSU anian\Documents\Wrightsoft HVAC\77 Lystra.rup Calc = MJ8 Front Door faces: N 214-Dec-19 13:5:28 Page 1

16 Return Branch Detail Table Grill Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Matl Trunk rb2 22x x Right-Suite Universal RSU anian\Documents\Wrightsoft HVAC\77 Lystra.rup Calc = MJ8 Front Door faces: N 214-Dec-19 13:5:28 Page 2

17 Friction Rate Worksheet From ACCA s Manual D PE LOAD CALCS, LLC anthony.amadio@peloadcalcs.com Step 1) Manufacturer s Blower Data External static pressure (ESP) =.56 IWC Cfm = 1,5 Step 2) Component Pressure Losses (CPL) Direct expansion refrigerant coil Electric resistance heating coil Hot water coil Heat exchanger Low efficiency filter High or mid-efficiency filter Electronic filter Humidifier, UV lights, other Supply outlet Return grille Balancing damper Zone damper (full open) Total component losses (CPL) IWC Step 3) Available Static Pressure (ASP) ASP = (ESP - CPL) = ( ) =.26 IWC Step 4) Total Effective Length (TEL) Supply-side TEL + Return-side TEL = ( ) = 278 Feet Step 5) Friction Rate Design Value (FR) FR value from friction rate chart =.94 IWC/1 FR = 1 x ASP / TEL

18 N Sheet cfm, cfm 4"x1" 35 cfm, 38 2"x12" cfm 56 cfm, 65 cfm 2"x14" 42 cfm, 2"x12" 42 cfm, 2"x12" 48 cfm 48 cfm Master Bath 6 " Mbath 4 " 5 " 56 cfm 6 cfm 2"x14" Kitchen 5 " Dining 5 " 5 " 14 cfm, 6"x1" 4 x 8 1 x 8 VD VD 6 " 77 cfm, 87 cfm 4"x1" VD VD VD VD VD VD VD 18 x 8 12 x 8 VD VD VD VD VD Hall T 6 x 8 7 " 134 cfm Garage 5 " 15 cfm, 24"x3" 5 " cfm 4"x8" Guest1 5 " 18 " 24 x 8 6 " Guest2 7 " Living cfm, 6"x14" 7 " 15 cfm 6"x14" 163 cfm cfm 2"x12" Laundry 6374 cfm, cfm4"x8" 9 cfm, 13 4"x12" cfm All Isolated Rooms shall have 8"x14" Transfer Grills above Doors in order to allow mixed room air flow to the Central Return. Place edge of Floor Registers at about 9" - 1" from finished wall. Recommended Central Thermostat location in the Dining Room, far from windows, on interior wall and 5' above floor. Plenum should extend 12"-15" beyond last run-out. Job #: 1 Performed by Anthony Amadio for: Joe Chen 77 Lystra Rd Harrison, TN Phone: (423) PE Load Calcs, LLC Scale: 1 : Bridge Drive Collierville, TN 3817 Phone: (91) anthony.amadio@peloadcalcs.com All Metal Duct Dimensions are Inner Dimensions. Page 1 Right-Suite Universal RSU Dec-19 16:39:14...\Wrightsoft HVAC\77 Lystra.rup

19 *Air Volume Balance Report Form For Quality Installation Verification PE LOAD CALCS, LLC PROJECT INFORMATION Building Address: 77 Lystra Road City, State and Zip: Harrison TN Construction Type: E New or Existing R Residential or Commercial Technician Name: Date and Time: Testing Methods: Make and Models: Serial Numbers: Calibration Dates: Additional Notes: Temp: Altitude: HEAT EXCHANGER - 1st Floor HVAC Equipment: Goodman Packaged Heat Pump GPH1436H41C Total Design Airflow per Manual J Design Report: Design Blower Speed per Manual J Design Report: 15 cfm T2 Design ESP ("wc):.56 *Measured Total CFM through the Heat Exchanger: **Measured ESP: * The Technician should follow all Manufacturer s installation instructions, local codes, as well as follow the guidelines from ACCA Standards 5 & 9. Before measuring any airflow, a thorough inspection of the duct system must be completed which includes: 1. Visual inspection to see that all ducts have been connected, sealed and are sized and laid out correctly per design report, all branch dampers and supply terminals are installed and in the fully open position, and a new clean air filter has been installed. 2. A duct leakage test (via duct blower) that meets the more stringent of the of either the (a) 212 IECC leakage requirements, (b) ACCA Standard 5 requirements, or (c) local code. **If the measured total CFM through the heat exchanger is less than 85% of the design, or the ESP greater than 25% of design, at the selected design speed. Stop and go back and repeat the duct system inspection. Remember, all dampers & supply grilles should be fully open, and air filter and coils and fan should all be clean. If the problem still cannot be determined, then increase to the next blower speed setting and repeat the heat exchanger airflow measurement. Please note that it is desirable to have a 1-15% excess CFM measurement through the heat exchanger for this allows a margin for balancing the supplies since damper adjustments from the fully-open position will increase the resistance (ESP) thereby reducing the total heat exchanger airflow. Page 1 of 2

20 PE LOAD CALCS, LLC SUPPLY BRANCHES Per ACCA Standard 5, individual room CFM are to be within ± 1%, or 25 CFM, whichever is greater, of its target CFM for the supply and return ducts. For existing construction, and existing ductwork without contractor modification, terminal CFM balancing is not required, unless otherwise specified by local code. Room / Duct Terminal Location Target Airflow Test 1/ Final Test 2 / Final Test 3 / Final % Target Living Room 1 15 Living Room 2 15 Dining Room 1 42 Dining Room 2 42 Hall 56 Kitchen 14 Laundry 47 Master 1 77 Master 2 77 MBath 35 Bath 56 Guest Guest Guest2 9 Total Airflow: 1,52 Final Total: % Target Total: Where % Target = 1 1 X ( Final CFM / Target CFM ) *** The Target Airflow may not necessarily be the design airflow from the design report, which was used solely for the purpose of sizing the duct design. The Target Airflow may be the averaged, or normalized average, of the design heating and cooling airflow values. Page 2 of 2

21 Equipment Bill of Materials Page 1 of 2 PE LOAD CALCS, LLC anthony.amadio@peloadcalcs.com Equipment Qty GPH1436H41C 1 5 kw Heat Kit w/ Circuit Breaker 3 Nest Thermostat 1 Duct System Equipment Qty 14" x 8" Return Grilles above Room Doors 12 End cap for rectangular metal duct, 8"x8" 2 Floor horiz boot from round duct, size 4" 1 Floor horiz boot from round duct, size 5" 7 Floor horiz boot from round duct, size 6" 3 Floor horiz boot from round duct, size 7" 3 Manual Round Balance Damper, 4" 1 Manual Round Balance Damper, 5" 7 Manual Round Balance Damper, 6" 3 Manual Round Balance Damper, 7" 3 Plenum rect tapered take off, size 24"x8" 1 Plenum side round take off, size 18" 1 Rect tee, size Rect tee, size Rect to rect transition, size 1" x 8"-8" x 8" 1 Rect to rect transition, size 12" x 8"-8" x 8" 1 Rect to rect transition, size 18" x 8"-12" x 8" 1 Rect wye, size Rectangular metal duct, 1" x 8" 16 Rectangular metal duct, 12" x 8" 11 Rectangular metal duct, 14" x 8" 4 Rectangular metal duct, 18" x 8" 21 Rectangular metal duct, 24" x 8" 2 Rectangular metal duct, 8" x 8" 12 All Duct Dimensions are Inner Duct Dimensions. Page 1 of 2

22 Equipment Bill of Materials Page 2 of 2 PE LOAD CALCS, LLC anthony.amadio@peloadcalcs.com Duct System Equipment cont Qty Rectangular metal floor two way grill, 1" x 6" 1 Rectangular metal floor two way grill, 1"x4" 2 Rectangular metal floor two way grill, 12" x 2" 4 Rectangular metal floor two way grill, 12"x4" 1 Rectangular metal floor two way grill, 14" x 2" 2 Rectangular metal floor two way grill, 14"x6" 2 Rectangular metal floor two way grill, 8"x4" 2 Return boot from round duct, size 18" 1 Return duct plenum, size = 25"x19", len = 18" 1 Round 5-piece elbow, size 18" 1 Round 5-piece elbow, size 4" 1 Round 5-piece elbow, size 5" 7 Round 5-piece elbow, size 6" 3 Round 5-piece elbow, size 7" 3 Round metal duct, D = 18" 14 Round metal duct, D = 4" 11 Round metal duct, D = 5" 65 Round metal duct, D = 6" 27 Round metal duct, D = 7" 34 Round tee, size Side round transition take off, size 4" 1 Side round transition take off, size 5" 7 Side round transition take off, size 6" 2 Side round transition take off, size 7" 1 All Duct Dimensions are Inner Duct Dimensions. Page 2 of 2

23 ASHRAE 62.2 Report PE LOAD CALCS, LLC PROJECT INFORMATION Name: Company: Phone: Building Address: City, State and Zip: New or Existing: Joe Chen Homeowner tiu 77 Lystra Rd Harrison TN Existing ASHRAE 62.2 DATA Floor Area (Square Feet): # of Bedrooms: *Combustion CFM Threshold: *If the sum of the highest flow rate of the two largest fans exceeds the Combustion CFM Threshold, then makeup air must be supplied to any atmospherically vented appliance. Whole Building Ventilation Type: None Continuous or Intermittent Control: NA ASHRAE Weather Location: Chattanooga TN Target CFM-5 (.35 ACH): 1585 Blower Door (CFM-5): ACH-5: 11.7 ACH-N:.6 27 New Building CFM Required: Existing Building CFM Required: 24 Measured Mechanical Ventilation Flow: NA Designer Notes: Homeowner declines to have a new mechanical ventilation system installed at this time. These calculations were made to determine the correct mechanical ventilation flow rate based on the ASHRAE Standard.

Report SEG W / March 2014 Right-Sized Residence Manual J Street, Oak Park, IL Prepared by: Tracy Savoy

Report SEG W / March 2014 Right-Sized Residence Manual J Street, Oak Park, IL Prepared by: Tracy Savoy Report SEG 314-77W / March 214 Right-Sized Residence Manual J Street, Oak Park, IL 631 Preparedd by: Tracy Savoy Report SEG 213-27W Page 2 DISCLAIMER The following pages summarize the heat gain and heat

More information

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1 Air System Design Load Summary for Zona 11 DESIGN COOLING DESIGN HEATING COOLING DATA AT Dec 1700 HEATING DATA AT DES HTG COOLING OA DB / WB 33.1 C / 23.5 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible

More information

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1 Air System Design Load Summary for Zona 8 DESIGN COOLING DESIGN HEATING COOLING DATA AT Dec 1700 HEATING DATA AT DES HTG COOLING OA DB / WB 33.1 C / 23.5 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible Latent

More information

Compliance Certificate

Compliance Certificate REScheck Software Version 4.6.4 Compliance Certificate Project RESIDENCE Energy Code: 2009 IECC Location: Perkasie, Pennsylvania Construction Type: Single-family Project Type: New Construction Conditioned

More information

Energy Efficiency Programs

Energy Efficiency Programs Program Overviews Efficiency Programs Description Delivery Model Audit Requirement/ Multifamily - Existing Building Efficiency Alliant Services include free energy assessments, rebates for property owners

More information

ASHRAE 62.2: What s New in 2016

ASHRAE 62.2: What s New in 2016 ASHRAE 62.2: What s New in 2016 Rick Karg 2016 Residential Energy Dynamics, LLC What We Will Talk About Overview of mechanics of 62.2-2016. Logic behind the Standard. Sizing local ventilation (exhaust-only).

More information

Date Rater Verified. Rater Verified. Slab / Pre-Drywall / Thermal Inspection

Date Rater Verified. Rater Verified. Slab / Pre-Drywall / Thermal Inspection Slab on Grade & Basements: A capillary break is installed on top of all footings Slab / Pre-Drywall / Thermal Inspection A minimum of 4" of clean or washed gravel (0.5" diameter or greater) is placed over

More information

Guide to Heating and Cooling Load Calculations in High Performance Homes

Guide to Heating and Cooling Load Calculations in High Performance Homes Guide to Heating and Cooling Calculations in High Performance Homes Prepared by: Arlan Burdick 2214 Liberty Avenue Pittsburgh, PA 15222 www.ibacos.com 1-800-611-7052 IBACOS, Inc. 2011 The information contained

More information

The Participants in this GreenON Rebates Program are homeowners and landlords.

The Participants in this GreenON Rebates Program are homeowners and landlords. Program Name: GreenON Rebates Program 1. Program Description The GreenON Rebates Program is designed to encourage homeowners to invest in building envelope and HVAC upgrades to help reduce energy costs,

More information

THE GEORGIA ENERGY CODE: 2009 IECC + AMENDMENTS

THE GEORGIA ENERGY CODE: 2009 IECC + AMENDMENTS THE GEORGIA ENERGY CODE: 2009 IECC + AMENDMENTS For the Georgia Association of Home Inspectors Bourke Reeve ABOUT SOUTHFACE 1 EARTHCRAFT Regional Green Building Program HISTORY OF ENERGY CODES MEC 1992,

More information

C H A P T E R 3. Completing the Residential Analysis Worksheet STEP 1: WINDOWS AND OTHER GLASS AREAS

C H A P T E R 3. Completing the Residential Analysis Worksheet STEP 1: WINDOWS AND OTHER GLASS AREAS C H A P T E R 3 Completing the Residential Analysis Worksheet The Residential Analysis Worksheet is designed to help the reader in making the preliminary calculations necessary to complete Forms 600A-04,

More information

2018 Smart Energy New Homes Program Manual

2018 Smart Energy New Homes Program Manual 2018 Smart Energy New Homes Program Manual Reduce the Use: Residential Table of Contents Section 1 Introduction... 1-1 1.1 Program Overview... 1-1 1.2 Program Administrator... 1-1 1.3 Program Contact Information...

More information

CERTIFICATE OF FIELD VERIFICATION & DIAGNOSTIC TESTING (Page 1 of 8)

CERTIFICATE OF FIELD VERIFICATION & DIAGNOSTIC TESTING (Page 1 of 8) CERTIFICATE OF FIELD VERIFICATION & DIAGNOSTIC TESTING (Page 1 of 8) Builder or Installer Name Builder or Installer Contact Telephone Plan/Permit (Additions or Alterations) Number Compliance Method (Prescriptive)

More information

Oregon High Performance Home Requirements

Oregon High Performance Home Requirements Oregon High Performance Home Requirements A Business Energy Tax Credit for Homebuilders Homebuilders who construct homes to the Oregon High Performance Home (HPH) standard are now eligible for the Business

More information

Homes. Plan Review Input Form. Office Use: P l an Rev iew Contro l Nu mb er

Homes. Plan Review Input Form. Office Use: P l an Rev iew Contro l Nu mb er Office Use: P l an Rev iew Contro l Nu mb er Homes Plan Review Input Form PLEASE SEND WITH HOUSE PLAN AND LOAD CALC. TO: Advanced Energy Corporation, Attention: Maria Mauceri 909 Capability Drive Suite

More information

Energy Savers: Air-Source Heat Pumps

Energy Savers: Air-Source Heat Pumps 1 of 5 4/25/2009 8:55 AM U.S. Department of Energy - Energy Efficiency and Renewable Energy Energy Savers Air-Source Heat Pumps An air-source heat pump can provide efficient heating and cooling for your

More information

SAN MIGUEL COUNTY & TOWN OF MOUNTAIN VILLAGE BUILDING DEPARTMENTS PRESCRIPTIVE ENERGY CODE & GREEN BUILDING STANDARD

SAN MIGUEL COUNTY & TOWN OF MOUNTAIN VILLAGE BUILDING DEPARTMENTS PRESCRIPTIVE ENERGY CODE & GREEN BUILDING STANDARD SAN MIGUEL COUNTY & TOWN OF MOUNTAIN VILLAGE BUILDING DEPARTMENTS PRESCRIPTIVE ENERGY CODE & GREEN BUILDING STANDARD The Prescriptive Energy Code & Green Building Standard requirements for San Miguel County

More information

Is Yours? Homes Across Missouri are Being Built to the Latest National Energy Efficiency Standards

Is Yours? Homes Across Missouri are Being Built to the Latest National Energy Efficiency Standards Homes Across Missouri are Being Built to the Latest National Energy Efficiency Standards Is Yours? A home buyers guide to the energy efficiency requirements of the 2012 International Energy Conservation

More information

COMMERCIAL LOAD ESTIMATING. Load Estimating Level 3: Block and Zone Loads. Technical Development Program

COMMERCIAL LOAD ESTIMATING. Load Estimating Level 3: Block and Zone Loads. Technical Development Program COMMERCIAL LOAD ESTIMATING Load Estimating Level 3: Block and Zone Loads Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design,

More information

Questar ThermWise Duct Technical Specifications

Questar ThermWise Duct Technical Specifications Questar ThermWise Duct Technical Specifications 1. Introduction and Scope: This document sets forth the specifications for duct sealing and duct insulation in accordance to Questar ThermWise Weatherization

More information

CHAPTER 1: OVERVIEW OF ENERGY EFFICIENT CONSTRUCTION

CHAPTER 1: OVERVIEW OF ENERGY EFFICIENT CONSTRUCTION Chapter 1: Overview of Energy Efficient Construction 1 CHAPTER 1: OVERVIEW OF ENERGY EFFICIENT CONSTRUCTION Chapter 1 is a quick reference guide that discusses the key components and features of energy

More information

Chapter 2: Foundation

Chapter 2: Foundation Chapter 2: Foundation Crawlspace [V502.1.2] [V502.1.2] [V502.1.3] Vents. Vents in the crawlspace help keep floor insulation and floor framing dry. Crawlspace vents also reduce the potential for radon buildup

More information

ABSTRACT I. INTRODUCTION II. METHODS AND MATERIAL

ABSTRACT I. INTRODUCTION II. METHODS AND MATERIAL 2017 IJSRSET Volume 3 Issue 2 Print ISSN: 2395-1990 Online ISSN : 2394-4099 Themed Section: Engineering and Technology Chiller and AHU Design for A commercial Usage S M Azfar Hashmi, Mirza Muneer Baig,

More information

ENERGY EFFICIENCY CERTIFICATION

ENERGY EFFICIENCY CERTIFICATION ENERGY EFFICIENCY CERTIFICATION This form must be completed for developments that qualified for competitive points in the Energy Efficient Design category. Complete Part A for single-family and multifamily

More information

BUILDING CODES & DESIGN CRITERIA

BUILDING CODES & DESIGN CRITERIA BUILDING CODES & DESIGN CRITERIA Adopted Building Codes: 2006 International Building Code (IBC) 2006 International Residential Code (IRC) 2006 International Mechanical Code (IMC) 2006 International Plumbing

More information

AGREEMENT CONCERNING EXISTING AS BUILT CONSTRUCTION

AGREEMENT CONCERNING EXISTING AS BUILT CONSTRUCTION AGREEMENT CONCERNING EXISTING AS BUILT CONSTRUCTION Building Permit Number: Date Received: By: I,, as owner of record of the above property, hereby request a permit for and final inspection of the installation

More information

B. ASHRAE 1991 HVAC Applications Handbook: Chapter 34--Testing, Adjusting and Balancing.

B. ASHRAE 1991 HVAC Applications Handbook: Chapter 34--Testing, Adjusting and Balancing. PART 1 GENERAL 1.1 RELATED DOCUMENTS SECTION 230593 TESTING, ADJUSTING, AND BALANCING A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification

More information

2017 Incentive Policies for Housing and Economic Development. Notice of Revision

2017 Incentive Policies for Housing and Economic Development. Notice of Revision 2017 Incentive Policies for Housing and Economic Development Notice of Revision MLGW Incentive Policy for Housing and Economic Development - 2017 Introduction Since 1939, Memphis Light, Gas and Water (MLGW)

More information

Plan Check & Field Inspection Guide

Plan Check & Field Inspection Guide Plan Check & Field Inspection Guide 1992 MEC, 1993 MEC, and 1995 MEC Inside This Guide Plan Check Field Inspection Plan Check Building plans and specifications must be submitted with each building application

More information

Fenestration Components: Mechanical Summary. Water heater energy factor: Ef Fuel type: Gas Electric Other

Fenestration Components: Mechanical Summary. Water heater energy factor: Ef Fuel type: Gas Electric Other This information must be on the drawing documents not attached to plans. The following Compliance statements must be on the drawings: 2009 International Energy Conservation Code Statement of acknowledgement

More information

Energy Efficiency: Designing Wood-Frame Buildings for Occupant Comfort

Energy Efficiency: Designing Wood-Frame Buildings for Occupant Comfort Please add relevant logo here Energy Efficiency: Designing Wood-Frame Buildings for Occupant Comfort Presented by: Peter J. Arsenault, FAIA, NCARB, LEED-AP Disclaimer: This presentation was developed by

More information

2012 CLEAResult All rights reserved. Residential Energy Efficiency

2012 CLEAResult All rights reserved. Residential Energy Efficiency Residential Energy Efficiency Presenter Bio Jaymar Davis, PE, CEM, CLEP, CMVP, CEA Sr. Field Engineering Manager 10 Years experience in energy efficiency Johnson Controls, Kohler Co. Certifications: Licensed

More information

Great Ocean Rd Ice Creamery

Great Ocean Rd Ice Creamery Great Ocean Rd Ice Creamery BCA Section J - JV3 Compliance Report Revision: 01 Job No: 2171 Date: 7 July 2015 ADP Consulting Pty Ltd Level 10, 10 Queens Rd, Melbourne Vic 3004 www.adpconsulting.com.au

More information

Instructions for the Residential Building Data Collection Checklist 2009 International Energy Conservation Code with 2011 Georgia Amendments

Instructions for the Residential Building Data Collection Checklist 2009 International Energy Conservation Code with 2011 Georgia Amendments Instructions for the Residential Building Data Collection Checklist 2009 International Energy Conservation Code with 2011 Georgia Amendments Use of these instructions with a residential data collection

More information

NW Natural Washington Residential, Contractor Install

NW Natural Washington Residential, Contractor Install Want your incentive faster? Apply online. Visit www.energytrust.org/now Steps to completion: 1 Learn about energy saving potential with Energy Trust s Payback Estimator. 2 Make an energy efficiency improvement.

More information

APPROVED. Acceptable to the code official for compliance with the provisions of the applicable Code or referenced Standard.

APPROVED. Acceptable to the code official for compliance with the provisions of the applicable Code or referenced Standard. Chapter 1 101.1 Title. These regulations shall be known as the North Carolina Energy Conservation Code as approved by the North Carolina Building Code Council on March 11, 2008, to be effective January

More information

Florida HERO Program Residential Eligible Product List All Products

Florida HERO Program Residential Eligible Product List All Products All Products In addition to the HERO Product Eligibility Specifications listed below, it is the sole responsibility of the HERO Contractor and property owner (Project Stakeholders) to meet or exceed applicable

More information

White Paper ENVELOPE-FIRST APPROACH TO NET-ZERO ENERGY BUILDINGS

White Paper ENVELOPE-FIRST APPROACH TO NET-ZERO ENERGY BUILDINGS BOULDER CHICAGO NASHVILLE SALT LAKE CITY SAN FRANCISCO SPRINGFIELD, MO WASHINGTON, DC 2540 Frontier Avenue, Suite 100 Boulder, Colorado 80301 303.444.4149 White Paper ENVELOPE-FIRST APPROACH TO NET-ZERO

More information

ENERGY AUDITOR STUDY GUIDE

ENERGY AUDITOR STUDY GUIDE ENERGY AUDITOR STUDY GUIDE COURSE OVERVIEW The Building Analyst and HERS Rater course is based upon a broad building science curriculum. It presents a solid scientific foundation upon which inspectors

More information

Boulder City NV Prepared by (Print Name) Signature Date

Boulder City NV Prepared by (Print Name) Signature Date City of Boulder City Community Development Department Building & Safety Division 401 California Avenue Boulder City, NV 89005-2600 702-293-9282 (Main Line) 702-293-9392 (Fax) 2009 International Energy

More information

Fundamentals of Test & Balance for Engineers, Cx & Energy Providers Course Number: CXENERGY1619

Fundamentals of Test & Balance for Engineers, Cx & Energy Providers Course Number: CXENERGY1619 AABC Commissioning Group AIA Provider Number 50111116 Fundamentals of Test & Balance for Engineers, Cx & Energy Providers Course Number: CXENERGY1619 Jim Hall, PE, TBE, CxA Systems Management & Balancing,

More information

Advanced Ventilation for Residential applications FBC Res 2010.

Advanced Ventilation for Residential applications FBC Res 2010. Advanced Ventilation for Residential applications FBC Res 2010. Course Description Review of the Residential Ventilation requirements in the Florida Building Code, Residential 2010. I. Introduction Dean

More information

LEED v4 for Homes, Residential Project Summary and Checklist One and Two Family New Construction

LEED v4 for Homes, Residential Project Summary and Checklist One and Two Family New Construction LEED v4 for Homes, Residential Project Summary and Checklist One and Two Family New Construction Summary Date of Application Path Project Project Address Owner Architect Third Party Third Party Provider

More information

IECC Commercial Significant Changes Summary Tier I

IECC Commercial Significant Changes Summary Tier I 2009-2015 IECC Commercial Significant Changes Summary Tier I The first change is in the layout of the book. Instead of having Chapters 1-3 that applied to all projects and then having Chapter 4 Residential

More information

ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS

ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS ANSI/ASHRAE STANDARD 200-2015, METHODS OF TESTING CHILLED BEAMS NEMIC 2017 Agenda 1. Foreword 2. Purpose & Scope 3. Definitions 4. Instrumentation & Facilities 5. Test Methods 6. Reporting 7. Normative

More information

Connecticut 2011 Baseline Study of Single-Family Residential New Construction. Final Report

Connecticut 2011 Baseline Study of Single-Family Residential New Construction. Final Report Connecticut 2011 Baseline Study of Single-Family Residential New Construction Final Report October 1, 2012 Submitted to: Connecticut Energy Efficiency Board Submitted by: Group, Inc. KEMA, Inc. Cadmus

More information

Sample Duct Design. Prepared by Victor Carroll: 7401 Alabama St. Louis, MO

Sample Duct Design. Prepared by Victor Carroll: 7401 Alabama St. Louis, MO Sample Duct Design Prepared by Victor Carroll: 7401 Alabama St. Louis, MO. 63111 800-527-0896 victor@unicosystem.com www.unicosystem.com/yourplans -Page 2 DISCLAIMER The attached sizing and layout design

More information

Compliance to the IgCC. September 29, 2011

Compliance to the IgCC. September 29, 2011 Bringing Outcome-Based Compliance to the IgCC September 29, 2011 Outcome-Based Codes: Any code requirement or code enforcement mechanism based on actual outcomes in buildings after they have been occupied.

More information

TOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION Ext. 395 Needed to Obtain Permit:

TOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION Ext. 395 Needed to Obtain Permit: TOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION 355-7575 Ext. 395 Needed to Obtain Permit: 1. Building Permit Application, and/or residential plumbing permit application, as applicable, to be

More information

Less energy, more savings and comfort year-round

Less energy, more savings and comfort year-round COMPANION GUIDE: Air-Source Heat Pump Less energy, more savings and comfort year-round Designed for Electrically-Heated Homes 02 How do air-source heat pumps work? 03 What are the rebates? 04 Why it pays

More information

Building & Ductwork Airtightness Standards

Building & Ductwork Airtightness Standards Building & Ductwork Airtightness Standards Version 1.02, August 2013 Standard Reference Technical Body Title ICS (International Classification for Standards) Scope Door and Windows EN 12207:1999 Windows

More information

New Hampshire Residential Energy Code

New Hampshire Residential Energy Code CHAIRMAN STATE OF NEW HAMPSHIRE EXECUTIVE DIRECTOR Thomas B. Getz AND SECRETARY COMMISSIONERS Debra A. Howland Susan S. Geiger TDD Access: Relay NH Nancy Brockway 1-800-735-2964 Tel. (603) 271-2431 FAX

More information

1. When using the REScheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is.

1. When using the REScheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is. Energy Conservation Code Residential Building CHAPTER 4 WORKSHEET 1. When using the REScheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is _

More information

Infrared Inspection Report

Infrared Inspection Report Infrared Inspection Report 716 Glen Oaks Dr., Franklin, TN. David A. Andersen & Associates Building Science Thermographer #33784 TN HI Lic#40 4772 Chester Harris Rd Woodlawn Tennessee 37191 (615)406-6808

More information

PERFORMANCE OF SIDE-BY-SIDE SOUTH TEXAS HOMES Isolating the Contribution of Spray Polyurethane Foam Insulation

PERFORMANCE OF SIDE-BY-SIDE SOUTH TEXAS HOMES Isolating the Contribution of Spray Polyurethane Foam Insulation PERFORMANCE OF SIDE-BY-SIDE SOUTH TEXAS HOMES Isolating the Contribution of Spray Polyurethane Foam Insulation INTRODUCTION As the use of spray polyurethane foam (SPF) insulation is increasing in both

More information

Energy Code Basics for Residential Buildings. Presented by Newport Ventures NEWPORT VENTURES

Energy Code Basics for Residential Buildings. Presented by Newport Ventures NEWPORT VENTURES Energy Code Basics for Residential Buildings Presented by Newport Ventures Course Overview / Introduction 1. Overview of definitions and compliance changes 2. Building envelope requirements including air

More information

Interpretation Variables and Common Areas of Confusion. Of the 2009 IECC

Interpretation Variables and Common Areas of Confusion. Of the 2009 IECC Interpretation Variables and Common Areas of Confusion Of the 2009 IECC 1. (Mandatory) provisions vs. (Prescriptive) provisions: The IECC contains flexibility by allowing different approaches to achieve

More information

Montana Homebuilder Brief: Residential Energy Code 1

Montana Homebuilder Brief: Residential Energy Code 1 1 Montana homebuyers appreciate the comfort and warmth of the energyefficient homes based on the energy code. All new houses in Montana must meet the minimum requirements of the 2012 International Energy

More information

Energy-Efficient Passive House using thermal mass to achieve high thermal comfort

Energy-Efficient Passive House using thermal mass to achieve high thermal comfort Energy-Efficient Passive House using thermal mass to achieve high thermal comfort Loa Andersson Managing Director RLI Byggdata AB rli@termodeck.com Alexander Engström Technical Director RLI Byggdata AB

More information

Procedures for Verification of International Energy Conservation Code (IECC) Performance Path Calculation Tools

Procedures for Verification of International Energy Conservation Code (IECC) Performance Path Calculation Tools Procedures for Verification of International Energy Conservation Code (IECC) Performance Path Calculation Tools RESNET Publication No. 003-14 March, 2014 Published by: Residential Energy Services Network,

More information

Energy modeling in IDA ICE according to ASHRAE , app. G

Energy modeling in IDA ICE according to ASHRAE , app. G Energy modeling in IDA ICE according to ASHRAE 90.1-2007, app. G About this document This document is a user s guide for a relatively experienced IDA ICE operator for using the 90.1 add-in and for performing

More information

INTRODUCTION TO WUFI PASSIVE & PHIUS+ 2015

INTRODUCTION TO WUFI PASSIVE & PHIUS+ 2015 INTRODUCTION TO WUFI PASSIVE & PHIUS+ 2015 Lisa White: lisa@passivehouse.us 2017 Passive House Institute US PHIUS 1 PASSIVE BUILDING PRINCIPLES 2016 PHIUS 2017 Passive House Institute US PHIUS 2 PHIUS+

More information

Installation address City State ZIP. Complete all fields for each piece of equipment purchased and installed. Natural Gas Furnace Information

Installation address City State ZIP. Complete all fields for each piece of equipment purchased and installed. Natural Gas Furnace Information HEATING AND COOLING 2018 ILLINOIS FOR YOUR HOME REBATE APPLICATION Instructions: Fill out application completely and sign. Attach supporting documentation: itemized invoice(s), SAVE test results/contractor

More information

Chilled Beams. The new system of choice?

Chilled Beams. The new system of choice? Chilled Beams The new system of choice? Presented By: Kevin M. Pope P.E. Jason Leffingwell Hammel Green And Abrahamson, Inc. and Ken Bauer, P.E., LEED AP Butters-Fetting Co., Inc. History of Chilled Beams

More information

Business Energy Rebates Application

Business Energy Rebates Application Business Energy Rebates Application Business Energy Rebates make it easy and affordable for you to select energy efficient products for your business. In-store and mail-in rebates are available for energy

More information

Italcementi Center for Research and Innovation

Italcementi Center for Research and Innovation Italcementi Center for Research and Innovation Bergamo, Italy LEED-NC v2.1 EAc1 A. Project Narrative (Viridian) analyzed the energy use of the proposed Italcementi Center for Research and Innovation located

More information

Corridor Pressurization System Performance in Multi-Unit Residential Buildings

Corridor Pressurization System Performance in Multi-Unit Residential Buildings Corridor Pressurization System Performance in Multi-Unit Residential Buildings Lorne Ricketts Student Member ASHRAE John Straube, PhD, P.Eng. Associate Member ASHRAE ABSTRACT Corridor pressurization based

More information

RESIDENTIAL BUILDING REQUIREMENTS

RESIDENTIAL BUILDING REQUIREMENTS RESIDENTIAL BUILDING REQUIREMENTS Residential Building Requirements This is an informational booklet with some of the general residential construction requirements taken from the codes adopted by Campbell

More information

LEED for Homes Project Checklist

LEED for Homes Project Checklist LEED for Homes Project Checklist Builder Name: Project Team Leader: Home Address (Street/City/State): Project Description Adjusted Certification Thresholds Building Type: Project type: Certified: 45.0

More information

!"#!$%&'(%)*+,-./(0."1-+1)(234,)(5(6)7#/(!38,-.41-)9(23:)($;":<#)( (

!#!$%&'(%)*+,-./(0.1-+1)(234,)(5(6)7#/(!38,-.41-)9(23:)($;:<#)( ( !"#!$%&'%)*+,-./0."1-+1)234,)56)7#/!38,-.41-)923:)$;":34,)C!3:

More information

NB Power s Home Insulation Energy Savings Program as of August 1, PROGRAM INTRODUCTION PROGRAM OVERVIEW ELIGIBILITY...

NB Power s Home Insulation Energy Savings Program as of August 1, PROGRAM INTRODUCTION PROGRAM OVERVIEW ELIGIBILITY... NB Power s Home Insulation Energy Savings Program as of August 1, 2017 Program Guidelines Table of contents 1 PROGRAM INTRODUCTION 2 2 PROGRAM OVERVIEW 2 3 ELIGIBILITY 3 ELIGIBLE HOMES 3 INELIGIBLE BUILDINGS

More information

2001 National Workshop on State Building Energy Codes July th, 2001 Burlington, Vermont

2001 National Workshop on State Building Energy Codes July th, 2001 Burlington, Vermont 2001 National Workshop on State Building Energy Codes July 16-19 th, 2001 Burlington, Vermont A Systems Engineering Approach to the Design of Energy and Resource Efficient Homes Presented By: Mark LaLiberte

More information

Field Accuracy of Temperature Measurements in TAB Work Andrew P. Nolfo, PE

Field Accuracy of Temperature Measurements in TAB Work Andrew P. Nolfo, PE Field Accuracy of Temperature Measurements in TAB Work Andrew P. Nolfo, PE The purpose of this article is to discuss the measuring and reporting of temperatures at heat transfer equipment during the Testing

More information

Single Family Residence Building Permits

Single Family Residence Building Permits Village of Northbrook Department of Building & Development Guide to: Designing, Documenting & Inspecting For Energy Code Compliance Single Family Residence Building Permits New Construction Additions Alterations

More information

Application of Advanced Energy Technologies

Application of Advanced Energy Technologies GLOBALCON 2002 Philadelphia, Pennsylvania March 27, 2002 Application of Advanced Energy Technologies Michael K. West, Ph.D., P.E. Building Systems Scientist Advantek Consulting, Inc. www.advantekinc.com

More information

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma LEED Green Building Certification The purpose of the LEED Green Building Rating is to provide a national standard that aims to improve environmental, health and economic performance of buildings using

More information

HOUSE REPAIRS & RENOVATIONS BUILDING PERMIT REQUIREMENTS

HOUSE REPAIRS & RENOVATIONS BUILDING PERMIT REQUIREMENTS St. Louis County Department of Public Works Division of Code Enforcement HOUSE REPAIRS & RENOVATIONS BUILDING PERMIT REQUIREMENTS This guide is intended to provide the homeowner or contractor with the

More information

Quality Control Inspection Checklist. WX Contractor: BWR: Yes / No DCF: Yes / No Work Order: Yes / No

Quality Control Inspection Checklist. WX Contractor: BWR: Yes / No DCF: Yes / No Work Order: Yes / No Quality Control Inspection Checklist Date of Quality Control Inspection: Date Unit Completed: Client Name: Address: City: Quality Control Inspector: Energy Auditor: Job#: HVAC Contractor: WX Contractor:

More information

2012 Fiscal Impact International Mechanical Code

2012 Fiscal Impact International Mechanical Code 2012 Section No. 306.5 Item 2 2012 Code Information - bold text = new text found in 2012 strike out = text deleted and not found in the 2012 Equipment and appliances on roofs or elevated structures: Item

More information

2010 Standard for Performance Rating of Variable Refrigerant Flow (VRF) Multi-Split Air-Conditioning and Heat Pump Equipment

2010 Standard for Performance Rating of Variable Refrigerant Flow (VRF) Multi-Split Air-Conditioning and Heat Pump Equipment ANSI/AHRI Standard 1230 with Addendum 2 2010 Standard for Performance Rating of Variable Refrigerant Flow (VRF) Multi-Split Air-Conditioning and Heat Pump Equipment Approved by ANSI on 2 August 2010 ANSI/AHRI

More information

ASHRAE 90.2 Kuwait What Can be Learned From It?

ASHRAE 90.2 Kuwait What Can be Learned From It? ASHRAE 90.2 Kuwait What Can be Learned From It? Prof. Walid Chakroun Kuwait University Sixth "Zayed Seminar" on Green Economy: Success Stories from the GCC May 8-9, 2013 Today s building designs mortgage

More information

2016 Residential HVAC Rebate Application

2016 Residential HVAC Rebate Application Instructions for Use STEP1 Determine Eligibility Verify the utility company listed on the rebate application is your electric utility. Applications for other participating utility service providers can

More information

Indoor Building Survey and Product Inventory

Indoor Building Survey and Product Inventory Indoor Building Survey and Product Inventory Preparer s Name Date/Time Prepared Preparer s Affiliation Phone No. Purpose of Investigation 1. OCCUPANT: Interviewed: Y / N Last Name: First Name: Address:

More information

GENERAL PLAN REVIEW REQUIREMENTS

GENERAL PLAN REVIEW REQUIREMENTS GENERAL PLAN REVIEW REQUIREMENTS Cover Letter A letter (or an authorized pre-printed form) authorizing CCIS to perform the Plan Review is required. CCIS performs plan reviews for the ICC International

More information

PIKES PEAK REGIONAL BUILDING DEPARTMENT

PIKES PEAK REGIONAL BUILDING DEPARTMENT PIKES PEAK REGIONAL BUILDING DEPARTMENT Manufactured Residential Buildings - WOODLAND PARK (CITY LIMITS) Pikes Peak Regional Building Department issues permits and performs inspections of manufactured

More information

A GUIDE TO REACH SYSTEM RELIABILITY. Commercial HVAC Buyers Guide

A GUIDE TO REACH SYSTEM RELIABILITY. Commercial HVAC Buyers Guide A GUIDE TO REACH SYSTEM RELIABILITY Commercial HVAC Buyers Guide How to confidently select your HVAC contractor, compare options and quotes, and enjoy system reliability. If you are reading this document,

More information

2018 APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES)

2018 APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES) 2018 APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES) (Reproduce the following data on the building plans sheet 1 or 2) Name of Project: Address:

More information

BCA Section J Compliance Report. Alterations & Additions to Cottage at St Johns College 10 Missenden Road Camperdown

BCA Section J Compliance Report. Alterations & Additions to Cottage at St Johns College 10 Missenden Road Camperdown BCA Section J Compliance Report Alterations & Additions to Cottage at St Johns College 10 Missenden Road Camperdown Prepared by: Gradwell Consulting ABN 68 872 791 784 Sustainability Consultants PO Box

More information

HOUSING ENERGY- EFFICIENCY INSPECTION FIELD MANUAL

HOUSING ENERGY- EFFICIENCY INSPECTION FIELD MANUAL HOUSING ENERGY- EFFICIENCY INSPECTION FIELD MANUAL CONTENTS PREFACE.................................. 2 ACKNOWLEDGMENTS.........................2 DISCLAIMER................................ 2 REFERENCES...............................2

More information

The Mirenda Center for Sports, Spirituality, and Character Development

The Mirenda Center for Sports, Spirituality, and Character Development prepared by: Zachary Heilman MECHANICAL OPTION prepared for: James Freihaut, PhD Technical Report 3: (Mechanical Systems Existing Conditions Evaluation) Due Date: November 29, 2010 The Mirenda Center for

More information

Michigan Energy Code Training and Implementation Program

Michigan Energy Code Training and Implementation Program Michigan Energy Code Training and Implementation Program 1.0 Hour Advanced Program Course Number 16201 Residential Energy Air Sealing School of Planning, Design & Construction Michigan State University

More information

BASEMENT FINISH CONSTRUCTION PLANS REFERENCE: 2015 INTERNATIONAL RESIDENTIAL CODE. PERMITS

BASEMENT FINISH CONSTRUCTION PLANS REFERENCE: 2015 INTERNATIONAL RESIDENTIAL CODE. PERMITS BASEMENT FINISH REFERENCE: 2015 INTERNATIONAL RESIDENTIAL CODE. PERMITS A construction permit is required. A homeowner may perform the construction work on his own property where he resides, without a

More information

Energy Audits. Presented By. Eugene Hoyt Professional Inspector TREC # IECC Energy Inspector/Plans Examiner ICC #

Energy Audits. Presented By. Eugene Hoyt Professional Inspector TREC # IECC Energy Inspector/Plans Examiner ICC # Energy Audits Presented By Eugene Hoyt Professional Inspector TREC # 10117 IECC Energy Inspector/Plans Examiner ICC # 8100852 Real Horizons Inspection Services, LLC To Sam Houston State University Huntsville,

More information

Basement Renovation Guide For Residential Dwellings

Basement Renovation Guide For Residential Dwellings 1 Development Services Department Building Permit & Inspection Services Basement Renovation Guide For Residential Dwellings This document is a guide for home owners and does not cover all possible conditions.

More information

Size: length ft., bay width ft., number of bays: Square feet of floor space: Sq. ft. of bench/floor space covered by crops:

Size: length ft., bay width ft., number of bays: Square feet of floor space: Sq. ft. of bench/floor space covered by crops: Greenhouse Energy Conservation Checklist/Audit (Adapted by A.J. Both, Rutgers University, and Paul Fisher, University of Florida from a checklist developed by John W. Bartok Jr., Professor Emeritus, University

More information

The ENERGY DETECTIVE. Where Is Your Home Losing Money? Find out with The Energy Detective Call Home Energy Analysis Program

The ENERGY DETECTIVE. Where Is Your Home Losing Money? Find out with The Energy Detective Call Home Energy Analysis Program The ENERGY DETECTIVE Where Is Your Home Losing Money? Find out with The Energy Detective Call 800-858-5522 Home Energy Analysis Program What Is a Home Energy Analysis? You probably know that upgrading

More information

Storm Damage Assessment Report For: 1234 Example Street., Houston, TX 77002

Storm Damage Assessment Report For: 1234 Example Street., Houston, TX 77002 Storm Damage Assessment Report For: 1234 Example Street., Houston, TX 77002 Prepared For: Miriam Saliba nspection Date: 9/6/2017 Prepared By: Adam Wells TREC License # 21140 105 E Spreading Oaks Ave, Friendswood,

More information

Training Certification Categories

Training Certification Categories Training Certification Categories Residential Residential Building Inspector structures are free from hazardous structural conditions and comply with the UCC. Duties include inspection of footings and

More information

Personal: Residential Grant Table for ecoenergy Retrofit

Personal: Residential Grant Table for ecoenergy Retrofit 1 of 9 7/27/11 7:07 AM NRCan > OEE > Grant Table ecoenergy Retrofit Homes Personal: Residential Grant Table for ecoenergy Retrofit Homes Save NOW with a home retrofit grant Save later on your energy bills.

More information

Inspection Report Summary

Inspection Report Summary Inspection Report Summary Prepared for: Property Location: XXXXXXXXXXXXXXXX XXXXXXXXXXXXX Dallas, Texas 75XXX Contact Info: Home Phone: XXXXXXXXXXXX E-mail: XXXXXXXXXXXXXXXX Date of Inspection: October

More information