1 PHJN1010CU SECTION 0400 MASONRY A. MASONRY 1. General Requirements: Division One is applicable in full hereto. 2. General: Workmanship shall be first class, with horizontal courses level, vertical joints in alternate courses aligned. Carry work up level where possible; step back for joining new work (toothing not permitted). Do not work when mean daily temperature is below 40 degrees F, or such condition is anticipated within 24 hours. Carefully stack masonry materials on platforms and cover with waterproof sheeting. Cover top of unfinished walls at end of each days work, and when rain appears imminent, with waterproof material which overhangs the wall at least 2 feet. Cover bottom of finished walls with a 4 foot wide strip of plastic to prevent staining. Keep cavity type walls clean of mortar droppings and debris by use of a wood lift-strip placed on ties and raised with every 16" lift. Hose test effectiveness of flashing, weeps, etc. as walls are erected. 3. Built-in Work: Build in anchors, inserts, door frames, lintels, duct opening sleeves, etc. shown or required. Fill in solid with mortar behind hollow metal door frames and in first cell adjacent to frame. 4. Typical Exposed Brick: Modular size face brick meeting ASTM C-216, as selected. Include in bid allowance of $ per thousand for purchase, sales tax, delivery and unloading. If brick selected cost more or less than allowance, contract price will be adjusted. Secure with order sufficient solids for use where sides are exposed, and arrange for delivery on banded pallets and premixed from all kiln runs for job. Submit sample panel for approval indicating range, flashing, etc. as producer proposes to supply. Submit in writing the estimated quantity of brick required to facilitate contract adjustment. Cull out chipped brick, which will be obvious in finish work. Lay in running bond so that 3 courses equal 8" (to align with backup), joint faces concave tooled. Lay out courses in advance on story rod. Shove each brick into place producing solid and uniform bed and head joints. Lay out horizontal coursed dry before actual laying begins to check dimensions and to insure that full courses will check in with openings, pilasters, etc. Use no face brick less than half-brick unless approved by Architect and cut to size with masonry saw. Provide solid brick at screen wall. Lay in pattern shown. 5. Concrete Block: Steam-cured hollow lightweight load-bearing concrete masonry units meeting ASTM C-90, Grade N-1. Faces smooth and dense, uniform in texture and free of any defect detrimental to finish appearance. Furnish jamb, lintel, corner, cap blocks and other special shape required. All 8" units shall meet International Building Code requirements for 2-hour fire resistance rating, and all 12" units shall meet 4-hour requirements. PH&J Architects, Inc. - All rights reserved Page
2 PHJA/1010CU Cut dry and do not wet or allow to become wet before or during laying of wall. Lay in running bond so that one course equals 8" in height, 16" in length. Where possible lay out work to course block horizontally and vertically, taking care that masonry will course up through openings, etc. V-tool exposed joints. 6. Mortar: Mix typical mortar as one part Magnolia Masons Mix to 2% parts sand and meeting ASTM C-144, mixed in mechanical mixer to produce ASTM C-270 Type N mortar. For masonry below grade employ Type M mortar mixed as 1 part masonry cement, 1 part portland cement and 2% parts sand; do not use in exposed work. Where new work joins existing work, select a masonry cement brand which will produce color matching existing mortar. Run trial batches to secure approval of selection. 7. Fill In Masonry Below Grade: Fill wall cavity and cells of all masonry units below grade with concrete as soon as practical after laying. Pour in levels not exceeding two feet. See Concrete Division for mix. B. MASONRY REINFORCING AND BONDING 1. At Brick Veneered Steel Stud Walls: Anchor veneer to stud wall backup with system meeting ACI Code 530 and equal to Dur-0-Wal Series D/A 213 adjustable anchor assembly with hot-dip galvanized finish. Anchor plates shall be 14 gauge with legs sized to extend thru the cavity insulation. Secure each anchor plate thru sheathing into stud with two #8 stainless steel self-drilling, self-tapping TEK screws with neoprene washer. Anchor ties shall be double leg pintle type of 3/16" cold drawn wire sized to extend to the midpoint of the veneer but with at least 1" mortar coverage. Space ties 16" ocew, as accurately as practical to permit pintle legs to be inserted fulf depth into anchor plate legs. C. MISCELLANEOUS REQUIREMENTS 1. Lintels: Provide over all openings in masonry work, including doors, windows, ducts, wall vents, access doors, etc. Bear minimum 8" onto jambs. Fill concrete block voids solid with concrete (not mortar) for 3 courses below lintel (see Concrete Division for mix). At brick work install steel angles or plates as specified in Metals Division. Where lintels are not indicated, provide steel lintels engineered for load arid span encountered. 2. Weep Holes: Open vertical joints approximately 2 feet apart directly above flashing courses and elsewhere indicated. After wall is constructed but before finishing, run water into cavity and open any joints that are plugged. 3. Cleaning: Remove excess mortar with wood paddles and fiber brush. Clean brick with product of ProSoCo, or equal, in strict accordance with manufacturer's instructions. Clean block with wire brushes. PH&J Architects, Inc. - All rights reserved Page
3 PHJN1010CU D. CALCIUM SILICATE MASONRY UNITS 1. Calcium Silicate Masonry Units: Provide calcium silicate units equal to Arriscraft, at front entry and at window type "B" in profiles as indicated as "Cast Stone" on drawings. Provide manufacturer's recommended mortar and anchorage for a complete system. Colors shall be selected for units and mortar from the manufacturer's full range of colors. End of Section PH&J Architects, Inc. - All rights reserved Page
4 202
5 PHJN1010CU SECTION 0425 MASONRY POINTING AND CLEANING A. POINTING AND CLEANING 1. General Requirements: Division One is applicable in full hereto. 2. Protection: Cover, coat or mask all adjacent work before proceeding to protect surfaces from damage during cleaning operations. Flood off any surfaces which inadvertently are spotted with cleaning solvents. 3. Pointing: Remove mortar drippings and carefully fill all voids with mortar. Rebed any masonry units which are not bonded. 4. Exposed Brick, Etc.: Do not proceed until masonry is thoroughly dry (minimum of three weeks after laying). Remove excess mortar with wood paddles and fiber brush. Then clean small areas at a time with appropriate product from the list below, and stiff fiber brushes, flushing wall with water from hose before and after washing. Avoid scrubbing joints. Replace solution when it becomes dirty. Masonry cleaning agents shall be as selected from the following list or shall be an equal product by American Building Restoration or others. TYPE OF MASONRY Tan, pinks, glazed brick, structural tile, exposed aggregate-general masonry surfaces: Red and other dark colored brick: Soft burned white, gray or brown and all other brick subject to metallic staining: CLEANER ProSoCo No. 600 Detergent ProSoCo No. 101 Lime Solvent ProSoCo Vana Trot Use products in strict conformance with manufacturer's printed instructions. Before full scale operations are begun, test clean a section of wall to establish proper technique, to ascertain possible damage to adjacent surfaces and to determine an acceptable degree of cleaning. Obtain the Architect's approval before proceeding further. End of Section PH&J Architects, Inc. - Atl rights reserved Page
6 204
7 PHJN1010CU SECTION 0484 A. GENERAL THIN BRICK VENEER 1. Summary Related Documents: General and Supplementary Conditions of the Contract, Division 1 General Requirements, and Drawings are applicable to this Section. Section Includes: Manufactured thin brick veneer for exterior individual unit application, includes mortar bed on metal lath over moisture barrier over sheathing over metal studs. Related Sections: Section 0541 "Cold Formed Metal Framing" for exterior wall framing. Section 0610 "Rough Carpentry" for exterior sheathing. Section 0790 "Sealants" for sealants at control joints and intersections with dissimilar materials. Section 0925 "Gypsum Board Assemblies". 2. Submittals Submit following in accordance with Section Product Data: Submit for all specified products. Include all applicable physical and performance data. Samples: Submit 4 samples of thin brick veneer units to illustrate color, texture, and size range of each type unit. Manufacturer's detailed installation instructions. 3. Field Samples General: Comply with Section Sample Installation: Construct thin brick to 3 feet by 4 feet panel size, including sub-framing, sheathing, moisture barrier, metal lath, mortar, fasteners, adhesive bonding, joint work, grout color, expansion joints and control joints. Obtain Architect's approval before beginning work. Protect and retain sample as a basis on which the quality of the work will be judged. Do not remove until Substantial Completion. Accepted Field Sample: May remain as part of completed Work. 4. Quality Assurance lnstaijer: Experienced in similar types of work of similar scope and be able to furnish list of previous jobs and references if requested by Architect. Expansion Joints: Provide expansion joints as indicated on Drawings or, if not indicated, install at frequency and in accordance with details and as PH&J Architects, Inc.- All rights reserved 205 Page
8 PHJA/1010CU recommended by manufacturer. Confirm locations and frequency with Architect before beginning work. Certifications: Provide written documentation that products have met or exceeded at least one of the following certifications for a minimum of 10 years: FHA-HUD. 5. Proiect Conditions Environmental Requirements: Minimum air temperature of 40 degrees F {4 degrees C) prior to, during, and for 48 hours after completion of work; and Cold Weather Requirements: IMIAC (International Masonry Industry All-Weather Council) - Recommended Practices and Guide Specifications for Cold Weather Masonry Construction. 6. Delivery, Storage, and Handling Deliver, store, handle, and protect materials in accordance with Section Store mortar materials on pallets in dry place. Protect materials from rain, moisture, and freezing temperatures. Store manufactured thin brick veneer above ground on level platforms, which allow air circulation under stacked units. Handle units on pallets or flat bed barrows. 7. Warranty Special Warranty: Prepare and submit in accordance with Section Provide a 20-year warranty against manufacturing defects in manufactured thin brick veneer products. B. PRODUCTS 1. ACCEPTABLE THIN BRICK VENEER PRODUCT Subject to compliance with requirements, provide the following product: Thin Brick as equal to brick manufactured by Owensboro Ewing Road, Owensboro, Kentucky 42301, {270) , (270) or equal by others. Thin Brick Veneer color and texture to match selected brick in Section Thin brick veneer size: ~ thick to match face dimensions of selected brick. PH&J Architects, Inc. - All rights reserved 206 Page0484-2
9 PHJN1010CU Thin Brick Veneer: Kiln fired thin brick, composed of following materials: Clay, shale, fire clay, sand or mixtures thereof, kiln fired to fusion to produce clay masonry units per ASTM C1088, Type Durability: ASTM C1088, Grade Exterior. Freeze and Thawing: No break~ge and not greater than 0.5% loss in dry weight. when tested in accordance with ASTM C Thin brick special shapes: Corner units. 2. THIN BRICK VENEER ACCESSORIES a. Mortar Mixes: For Brick Veneer Grout Joints: Mix as 1 part Type N masonry cement to 2% parts damp loose sand so as to produce ASTM C-270 (Property Specification) Type N mortar. Add water repellent admixture. Mix to match existing. For Scratch Coat : Mix as 1 part Type S masonry cement to 2* parts damp loose sand so as to produce ASTM C-270 (Property Specification) Type S mortar. b. Moisture Barrier: Tyvek Stucco Wrap, by E.l. Dupont, or comparable product as approved by Architect. Provide tape to seal joints, seams, and tears, of same permeance as membrane as recommended by the moisture barrier manufacturer. c. Metal Lath (over moisture barrier & sheathing): Minimum 2.5 lb galvanized expanded metal lath (Diamond Mesh) meeting the requirements of ASTM C 847. d. Fasteners: Corrosion-resistant, self-drilling, self-tapping pancake-head screw with 7/16" head, of length to required obtain 3/8" penetration beyond inside surface of metal (used for installing to metal surfaces or metal framing) e. Cleaner: Nonacid cleaner as recommended by thin brick veneer manufacturer. C. EXECUTION 1. EXAMINATION AND PREPARATION : Verify that field conditions are acceptable and are ready to receive work in accordance with the manufacturers written installation instructions. PH&J Architects, Inc. - All rights reserved Page
10 PHJA/1010CU Verify that built-in items are in proper location and ready for roughing into masonry work. Consult Architect if deficiencies exist. Correct deficiencies in accordance with requirements of thin brick veneer manufacturer's written installation instructions. Protect surrounding area from possible damage during installation work. Initiating installation constitutes Installer's acceptance of substrates. 2. INSTALLATION : a. Moisture Barrier: Apply sheets horizontally, starting at the base of the wall, and lapping each successive upper sheet over the previous lower sheet. Lap horizontal and vertical joints 6 inches and taped. Cut and seal joints, penetrations, openings, and projections with manufacturer's recommended tape. Install with corrosion-resistant staples. Install metal lath over moisture barrier. b. Applying Mortar to Prepared Substrate: Using a plasterer's or mason's trowel, apply mortar %" to %" thick to prepared surface area. Do not spread more than a workable area (5 to 10 sf) so that mortar will not "set up" before brick is applied. c. Setting the Bricks: Press each brick into the mortar setting bed firmly enough to squeeze some mortar out around brick's edges. Apply pressure to the brick to ensure a good bond. Ensure complete coverage between the mortar bed and back surface of the brick. When brick is installed correctly, lath will not be visible. Install mortar to thin brick veneer joints using a tuck pointing tool, metal tipped mortar bag or a grout setting machine in accordance with the manufacturers written installation instructions. Place thin brick pieces in position level, with 3/8 inch joint spacing, plumb with surrounding units. Apply firm pressure to bed. d. Bond Pattern: Running bond, or as indicated on the Drawings. Install outside corner return units with short and long lengths alternated. Plan work to minimize jobsite cutting. Perform necessary cutting with proper tools to provide uniform edges; take care to prevent breaking unit comers or edges. e. Install Flat Brick: Keep courses level and plumb. Keep mortar joints consistent and uniform. PH&J Architects, Inc. - All rights reserved 208 Page0484-4
11 PHJN1010CU Fill joints completely with mortar. Remove excess mortar; do not allow mortar to dry on face of units. Tool exposed joints slightly concave when thumbprint hard, using a jointer larger than joint thickness, unless otherwise indicated. Clean and finish joints in accordance with manufacturer's instruct~ons. f. Control Joints: Size in accordance as detailed, see Section 0790 for sealant, but in no case larger than adjacent mortar joints in exposed thin brick veneer units. g. Expansion Joints: Provide where indicated on Drawings or as recommended by system manufacturer. h. Built-in Work: As work progresses, build in door and window frames, nailing strips, anchor bolts, plates, and other items specified in various sections. Build in items plumb and level. Do not build in organic materials subject to deterioration. i. Adiusting Cutting and Fitting: Cut and fit for chases, pipes, conduit, sleeves, and grounds. Cooperate with other sections of work to provide correct size, shape, and location. j. Cleaning and Sealing Cleaning: Remove excess mortar and smears using brush or steel wool. Replace defective mortar. Match adjacent work. Clean soiled surfaces with non-acidic solution, acceptable to the thin brick veneer manufacturer, which will not harm masonry or adjacent materials. Leave surfaces thoroughly clean and free of mortar and other soiling. Use nonmetallic tools in cleaning operations. END OF SECTION PH&J Architects, Inc. - All rights reserved Page
12 210
SUNY GENESEO RED JACKET DINING HALL RENOVATION THIN BRICK MASONRY
SUNY GENESEO 042113.13-1 SECTION 042113.13 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationSECTION BRICK MASONRY ASSEMBLIES
PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following: 1. Face brick. 2. Mortar and grout. 3. Ties and anchors. 4. Miscellaneous masonry accessories. 1.2 SUBMITTALS A. Product Data: For each type
More informationSECTION UNIT MASONRY
SECTION 04200 UNIT MASONRY PART 1 GENERAL 1.01 SUMMARY A. Furnish labor, materials, and equipment and perform functions required in the installation and maintenance of the work covered by this Section.
More informationSECTION MORTAR
PART l - SCOPE SECTION 04100 - MORTAR A. This Section includes all labor, materials, equipment, and related items required for the work of mortar as shown on the Drawings and specified herein. The work
More informationSECTION UNIT MASONRY ASSEMBLIES
PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Concrete masonry units. 2. Decorative masonry units. 3. Mortar and grout. 4. Steel reinforcing bars. 5. Masonry joint reinforcement. 6. Ties and anchors.
More informationSECTION UNIT MASONRY SYSTEM
SECTION 04320 UNIT MASONRY SYSTEM PART 1 GENERAL 1.01 SECTION INCLUDES A. Concrete masonry and face brick units. B. Reinforcement, anchorage, and accessories. 1.03 SUBMITTALS A. Submit product data under
More informationThin Architectural Splitface Block Veneer Specification Guide
Thin Architectural Splitface Veneer System with AccuTab Technology R Thin Architectural Splitface Block Veneer Specification Guide Section 04711: Manufactured Concrete Veneer Use this specification guide
More informationInstallation Guide Wall Panels
Installation Guide Wall Panels Jointless or Dry-Stacked Installation (Read Prior to installation) The MStone system is a jointless / dry-stacked installation where panels and corners fit tightly together
More informationSpec Master 5/7/ For each product requiring color and texture selection, provide full size samples.
SECTION 04812 (042012) MECHANICALLY ATTACHED BRICK PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationProduct Guide Specification
Product Guide Specification SECTION 04850 (04 40 00) NATURAL THIN VENEER STONE PART 1 GENERAL 1.1 SECTION INCLUDES Specifier Notes: Edit the following as required. A. Natural thin veneer stone for [exterior]
More informationSPECIFICATION GUIDELINE
Environmental StoneWorks specification guideline should be used to assist design professionals in the preparation of projects. Edit and delete items that may not be applicable. Verify all referenced section
More informationREINFORCED CONCRETE MASONRY SECTION
SECTION 04 22 02 - REINFORCED CONCRETE MASONRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 01 Specification
More informationA. ASTM C190 - Test Method for Tensile Strength of Hydraulic Cement Mortars
SECTION 04850 (04 40 00) MSI PRECAST STONE VENEER SYSTEM PART 1 GENERAL 1.1 SECTION INCLUDES A. MSI Precast Stone Veneer for exterior and interior vertical surfaces. 1.2 RELATED SECTIONS Specifier Notes:
More informationDENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MORTAR AND MASONRY GROUT
SECTION 04110 MORTAR AND MASONRY GROUT PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. In the absence of other information, the methods and recommendations of the National Concrete Masonry Association
More informationSPECIFICATION GUIDELINE
SPECIFICATION GUIDELINE Environmental Stoneworks Corporate Office 6300 East Stapleton Drive South Denver, CO 80216 Phone (303) 309-3040 Fax (303) 309-3059 www.estoneworks.com Environmental Stoneworks specification
More informationSECTION GLASS UNIT MASONRY ASSEMBLIES
PART 1 GENERAL 1.01 SCOPE OF WORK A. The Contractor shall furnish and install all materials, labor, equipment and incidentals required to install glass unit masonry as shown on the contract drawings and
More informationOLD BRICK ORIGINALS KILN-FIRED THIN BRICK VENEER Installation Guide. RobinsonBrick.com
OLD BRICK ORIGINALS KILN-FIRED THIN BRICK VENEER Installation Guide RobinsonBrick.com OLD BRICK ORIGINALS THIN BRICK VENEER Page 2 INTRODUCTION Check local building codes for proper installation guidelines
More informationParagraph Description Page No General Materials Concrete Masonry Work Altitude Valve Vault Cover 25-4
City of Columbia Engineering Regulations PART 25: SPECIFICATIONS FOR ALTITUDE VALVE VAULT Table of Contents Paragraph Description Page No. 25.1 General 25-1 25.2 Materials 25-1 25.3 Concrete Masonry Work
More informationDIVISION 04 MASONRY CAST STONE. A. Design Considerations. 1. Cast stone shall comply with ASTM C1364, Standard Specification for Cast Stone.
DIVISION 04 MASONRY 04720 CAST STONE A. Design Considerations 1. Cast stone shall comply with ASTM C1364, Standard Specification for Cast Stone. 2. Care must be taken in the design of individual units
More informationGENERAL SHALE NATURAL THIN ROCK VENEER Installation Guide. GeneralShale.com
GENERAL SHALE NATURAL THIN ROCK VENEER Installation Guide GeneralShale.com GENERAL SHALE NATURAL THIN ROCK VENEER Page 2 INTRODUCTION - TABLE OF CONTENTS Check local building codes for proper installation
More informationINSULATED CONCRETE MASONRY UNITS Section 04220
INSULATED CONCRETE MASONRY UNITS Section 04220 PART 1 GENERAL 1.01 Summary A. Section Includes 1. Insulated masonry wall units (CMU's) 2. Decorative insulated masonry wall units 1.02 SUBMITTALS A. Samples:
More informationPART 1-SAWN THIN VENEER GENERAL
PART 1-SAWN THIN VENEER GENERAL WORK INCLUDED: All labor and material for the furnishing and installing of exterior or interior stone building veneer. RELATED WORK: Masonry Contractor shall include building
More informationSECTION INSTALLATION AND/OR REPLACEMENT OF MASONRY UNITS AND REPOINTING
SECTION 04210 INSTALLATION AND/OR REPLACEMENT OF MASONRY UNITS AND REPOINTING PART I GENERAL 1.1 SUMMARY A. Provide installation of new or replacement of masonry units and/or repointing of masonry units
More informationPART 1 GENERAL MANUFACTURED STONE MASONRY
SECTION 04 73 00 (04730) PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Simulated Stone B. Products installed, but not furnished, under this Section include the following: 1. Steel Lintel and Shelf
More informationSECTION BRICKWORK PART I GENERAL
SECTION 04210 BRICKWORK PART I GENERAL 101 Scope General: supply and build the brickwork shown on the drawings or needed to complete the brickwork, including but not limited to the following: Provide all
More informationSECTION (04730) - MANUFACTURED STONE MASONRY
1.01 SUMMARY SECTION 04 73 00 (04730) - MANUFACTURED STONE MASONRY A. Section Includes: 1. Cast Stone Standard Units, Chamfer Units and Custom stone trim, minimum 3 ¾ thick, layed up with brick masonry
More informationSECTION ARCHITECTURAL CONCRETE UNIT MASONRY
SECTION 04 2223 PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Split-face concrete unit masonry, burnished concrete unit masonry, and polished concrete unit masonry. 2. Split-face concrete unit masonry.
More informationDIVISION 4 MASONRY DIVISION 4 - MASONRY
DIVISION 4 MASONRY DIVISION 4 - MASONRY 85 SECTION 04000 - MASONRY 04000 - MASONRY PART 1 - GENERAL 1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary
More informationTechnical Notes 11B - Guide Specifications for Brick Masonry, Part 3 Rev [Feb. 1972] (Reissued Sept. 1988) INTRODUCTION
Technical Notes 11B - Guide Specifications for Brick Masonry, Part 3 Rev [Feb. 1972] (Reissued Sept. 1988) INTRODUCTION This Technical Notes contains the guide specifications in CSI format for Part III
More informationWEIGHT PER PIECE (LBS.)
PRODUCT DESCRIPTION DATA SHEET 04 73 19-US BASIC USE ProGUARD DP is intended to be installed over sheathing and waterproofing over steel or wood studs or over concrete masonry units or poured concrete
More informationDIVISION 04 MASONRY. Section Title Number MASONRY Maintenance of Masonry Masonry Mortaring Masonry Accessories
04 00 00 MASONRY 04 01 00 Maintenance of Masonry 04 01 20 Maintenance of Masonry 04 05 13 Masonry Mortaring 04 05 23 Masonry Accessories 04 20 00 UNIT MASONRY 04 21 00 Clay Unit and Brick Veneer 04 22
More informationDesign and Construction Standards SECTION REINFORCED UNIT MASONRY
SECTION 04810 REINFORCED UNIT MASONRY PART 1 GENERAL 1.1 SECTION INCLUDES: A. Concrete masonry or brick units B. Reinforcement, anchorage, and accessories C. Parged masonry surfaces 1.2 REFERENCES A. ACI
More informationMANUFACTURER S SPECIFICATIONS Section LIMESTONE PLASTER
MANUFACTURER S SPECIFICATIONS Section 09220 LIMESTONE PLASTER LE DÉCOR LIMESTONE PART 1 GENERAL 1.1 General A. This section describes the requirements for furnishing and installing Limestone Plaster. 1.2
More information2002 Advanced Building Products, Inc., P.O. Box 98, Springvale, Maine TEL: ; FAX: ; WEBSITE:
SECTION 07651 FLEXIBLE COPPER SHEET FLASHINGS Advanced Building Products, Inc. manufacturer many types of flexible copper sheet flashings. Due to their ductility, high tensile strength, and resistance
More informationOCS ONE COAT STUCCO A custom blend of Portland cement, sand, extenders, fiber reinforcement and modifiers.
OCS ONE COAT STUCCO A custom blend of Portland cement, sand, extenders, fiber reinforcement and modifiers. Designed to save material by functioning as an exterior cladding in thicknesses ranging from 3/8
More informationConditions of the Contract and Division 1 General Requirements are a part of this section.
NOTES TO SPECIFIER General notes about the specifications and the reasons for them are listed here in general statements. Use this as a guide when choosing the correct selection of statements that apply
More informationNOVABRIK MORTARLESS CONCRETE BRICK VENEER SPECIFICATION. MASTERFORMAT SECTION (Mortarless Concrete Brick Veneer)
NOVABRIK MORTARLESS CONCRETE BRICK VENEER SPECIFICATION MASTERFORMAT SECTION 04818 (Mortarless Concrete Brick Veneer) Spec_USA_En_18102005.doc 12/1/2005 Novabrik Page 2 Section 04818 NOVABRIK MORTARLESS
More informationTABLE OF CONTENTS IMPORTANT INFORMATION. INSTALLATION GUIDELINES Revised 5/5/2017 REFERENCES...2
TABLE OF CONTENTS REFERENCES...2 PROJECT PLANNING...2 Verify Site Conditions...2 Building Code Requirements...2 Estimating Quantities Needed...2 SURFACE PREPARATION...3-5 Weather Resistive Barrier...3-4
More informationSECTION Fiber Reinforced Stucco 1
CSI SECTION 09200 FIBER REINFORCED STUCCO PART 1 GENERAL 1.01 SUMMARY A. Section Description: Provided lath and plaster where shown on the Drawings, as specified herein, and as needed for complete and
More informationSECTION FLEXIBLE FLASHING SYSTEM FOR MASONRY VENEER
PART 1 - GENERAL 1.01 SUMMARY SECTION 07 65 00 FLEXIBLE FLASHING SYSTEM FOR MASONRY VENEER A. Section includes through wall masonry flashing system components for installation over sheathing where spray
More informationSECTION GYPSUM BOARD & SHEATHING SYSTEMS
PART 1!GENERAL! 1.01! SECTION INCLUDES SECTION 09260 GYPSUM BOARD & SHEATHING SYSTEMS! Metal stud wall framing. Metal channel ceiling framing.! Gypsum board.! Sheathing.! Taped and sanded joint treatment.!
More informationSECTION CEMENT BOARD SUPPORTED ADHERED MASONRY VENEER. 2. Installation materials including adhesives, mortars, and pointing mortars.
(Specifier Note: The purpose of this guide specification is to assist the Specifier in correctly specifying cement board supported adhered masonry. The Specifier needs to edit these guide specifications
More informationCONCRETE MASONRY VENEERS TEK 3-6C
An information series from the national authority on concrete masonry technology CONCRETE MASONRY VENEERS TEK 3-6C Construction (2012) INTRODUCTION In addition to its structural use or as the exterior
More informationSECTION Vitrified Clay Wall Coping 2014
SECTION 04220 2014 PART 1 GENERAL 1.1 DESCRIPTION A. SCOPE OF WORK 1. Provide new coping as indicated on Drawings. B. RELATED SECTIONS 1. Section 02050: Selective Demolition. 2. Section 07650: Metal Flashing.
More informationSECTION NATURAL STONE VENEER
SECTION 04 43 00 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the
More informationMARQUIS Tualatin FIBER-CEMENT SIDING June 15, rev
PART 1 - GENERAL 1.1 SUMMARY A. This Section includes: 1. Reinforced fiber-cement shingle panel siding, 2. Reinforced fiber-cement lap siding. B. Related Sections: 1. Division 1 Section "Quality Requirements"
More information1.02 STANDARD REFERENCES: The following standard specifications shall apply to the Work of this Section as indicated:
SECTION 04220 CONCRETE UNIT MASONRY PART 1 - GENERAL 1.01 SCOPE: A. The CONTRACTOR shall furnish all labor, materials and equipment necessary for the masonry construction as shown on the drawings or as
More informationDURRELL DESIGN GROUP, PLLC ROOF REPLACEMENT BARR ELEMENTARY SCHOOL JACKSON PUBLIC SCHOOL DISTRICT JACKSON, MISSISSIPPI.
DURRELL DESIGN GROUP, PLLC 500-G E. WOODROW WILSON AVENUE JACKSON, MISSISSIPPI 39216 PHONE: 601.708.4788 FAX: 601.488.4717 ROOF REPLACEMENT BARR ELEMENTARY SCHOOL JACKSON PUBLIC SCHOOL DISTRICT JACKSON,
More informationSECTION BRICKWORK
SECTION 04210 BRICKWORK THERE ARE NOTES AND CLAUSES IN THE SUSTAINABILITY GUIDE ON THIS TRADE. THIS TRADE SECTION DEPENDS ON COORDINATION BETWEEN THIS SPECIFICATION AND THE FINISHES SCHEDULE AS WELL AS
More informationStone and Masonry Veneer
Stone and Masonry Veneer R703.7 Stone and masonry veneer, general. Stone and masonry veneer shall be installed in accordance with this chapter, Table R703.4 and Figure R703.7. These veneers installed over
More informationSECTION PORTLAND CEMENT PLASTER (STUCCO) WITH ACRYLIC FINISH
SECTION 09 24 23 - PORTLAND CEMENT PLASTER (STUCCO) WITH ACRYLIC FINISH PART I - GENERAL 1.01 SECTION INCLUDES A. Building paper B. Lath and accessories C. Plaster materials D. Acrylic finish E. Exterior
More informationBRICKWORK 3.5 BRICKWORK 1 GENERAL
BRICKWORK 1 GENERAL 1.1 INSPECTION Notice Give sufficient notice so that inspection may be made of the following: - Set out of brickwork to lintels, arches and other architectural features. - Damp-proof
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-04 21 26 (November 2009) ----------------------------- Preparing Activity: USACE Superseding UFGS-04 21 26 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS References
More informationMANUFACTURER S SPECIFICATION
MANUFACTURER S SPECIFICATION Eldorado Stone Corporation PO Box 489 Carnation, WA 98014 Tel: (800) 925-1491 Fax: (425) 333-4755 e-mail: general@eldoradostone.com website: www.eldoradostone.com SECTION 04730
More informationGYPSUM BOARD AND PLASTER
CHAPTER 25 SECTION 2501 GENERAL 2501.1 Scope. 2501.1.1 General. Provisions of this chapter shall govern the materials, design, construction and quality of gypsum board, lath, gypsum plaster and cement
More informationGensler 2014/06/16 Hertz Global Headquarters ISSUE FOR BUILDING PERMIT Estero, Florida SECTION
SECTION 072700 VAPOR PERMEABLE AIR BARRIER LIQUID MEMBRANE PART 1 GENERAL 1.1 GENERAL REQUIREMENTS A. The Work of this Section, as shown or specified, shall be in accordance with the requirements of the
More informationINTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES
INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR ANCHORED MASONRY VENEER SYSTEM WITH POLYSTYRENE FOAM PLASTIC BACKING EC 021-2014 (Adopted
More informationSECTION FIBER CEMENT SIDING. A. Furnish and install CERACLAD fiber cement rain screen siding system.
SECTION 07466 FIBER CEMENT SIDING PART 1 GENERAL 1.1 SCOPE A. Furnish and install CERACLAD fiber cement rain screen siding system. 1.2 RELATED SECTIONS A. Division 06 - Wood and plastics B. Section 07210-
More informationPhone Fax
Corporate Office 955 Whitefish Stage Road Kalispell, MT 59901 406-755-5717 Phone 406-755-5718 Fax Scale: None Last Revision 10-20-10 Corporate Office 955 Whitefish Stage Road Kalispell, MT 59901 406-755-5717
More informationCorium Brick Rainscreen System Specifications
CORIUM BRICK RAINSCREEN SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. Work Included: The Work of this Section shall include but not be limited to the following: 1. Corium brick plates 2. Galvanized and coated
More informationSECTION GYPSUM BOARD SYSTEM
PART 1 GENERAL 1.1 RELATED DOCUMENTS SECTION 09 29 00 GYPSUM BOARD SYSTEM A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 specification sections,
More informationSECTION MANUFACTURED MASONRY VENEER
TM Dutch Quality Stone 18012 Dover Road Mt. Eaton, OH 44659 Tel: (330) 359-7866 Fax: (330) 359-5990 e-mail: info@dutchqualitystone.com website: www.dutchqualitystone.com SECTION 04 73 00 MANUFACTURED MASONRY
More informationSECTION MISCELLANEOUS METALS THIS SECTION TO BE INCLUDED IN SUB BID FOR SECTION MISCELLANEOUS AND ORNAMENTAL IRON
SECTION 055000 THIS SECTION TO BE INCLUDED IN SUB BID FOR SECTION 050001 MISCELLANEOUS AND ORNAMENTAL IRON PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. PART A and DIVISION 1 of PART B are hereby made a
More informationUnit Masonry
04 00 00 Unit Masonry This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes
More informationHammerStone Manufactured stone veneers for commercial & residential applications
HammerStone Manufactured stone veneers for commercial & residential applications Veneer Stone Specification Guide Section 04711: Manufactured Stone Veneer Use this specification guide for each individual
More informationSECTION ALUMINUM HANDRAIL SYSTEMS
SECTION 05520 ALUMINUM HANDRAIL SYSTEMS PART 1 - GENERAL 1.01 SUMMARY A. Section includes aluminum handrails and railings. B. Related Work: 1. Section 03300 - Cast-in-Place Concrete C. References: 1. American
More informationSECTION COMPOSITE WALL PANELS PART 1 GENERAL 1.01 SECTION INCLUDES
SECTION 07 4243 - PART 1 GENERAL 1.01 SECTION INCLUDES A. Composite wall panel system consisting of aluminum-faced composite panels in a rainscreen application as part of the assembly described below.
More informationHome Depot Page 1 of 5 HDPB Humacao, PR 10/19/09
PART 1 - GENERAL 1.01 SUMMARY A. Types of cold-formed metal framing units include the following: 1. C-shaped steel studs B. Related work specified elsewhere includes but may not be limited to: 1. Section
More informationHOTEL SPECIFICATION SECTION 08100
Part 1 General HOTEL SPECIFICATION SECTION 08100 1.01 Work Included A. The work under this section shall include the furnishing of all items shown on the drawings and as specified including, but not limited
More informationSECTION FIBERGLASS REINFORCED POLYESTER (FRP) DOORS AND ALUMINUM FRAMES
SECTION 081613 FIBERGLASS REINFORCED POLYESTER (FRP) DOORS AND ALUMINUM FRAMES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary
More informationSECTION GYPSUM BOARD SYSTEM
PART 1 GENERAL 1.1 RELATED DOCUMENTS SECTION 09 29 00 GYPSUM BOARD SYSTEM A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 specification sections,
More information0331 Brick and block construction
0331 BRICK AND BLOCK CONSTRUCTION 1 GENERAL 1.1 STANDARDS Materials and construction: To AS 4773.1 and AS 4773.2. 2 PRODUCTS 2.1 DURABILITY Exposure environment: [complete/delete] Exposure locations: To
More informationSECTION CEMENTITIOUS SHEATHING
SECTION 06 16 63 CEMENTITIOUS SHEATHING SPEC WRITER NOTES: 1. Delete text between // // not applicable to project. Edit remaining text to suit project. 2. Use this Section for exterior sheathing as a backup
More informationCopyright 2013 AIA MasterSpec Premium 12/13
SECTION 042000 - UNIT MASONRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationTerraClad TM General Specifications
TerraClad TM General Specifications PRODUCT NAMES: Terra cotta Baguettes/Louvers and Related Work MANUFACTURER: Boston Valley Terra Cotta 6860 S. Abbott Road Orchard Park, NY 14127 Phone: 888-214-3655
More informationCOLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100
COLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100 Part 1 General 1.01 Work Included A. The work under this section shall include the furnishing of all items shown on the drawings and as specified,
More informationSECTION MANUFACTURED MASONRY
SECTION 047000 MANUFACTURED MASONRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and General Provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationInsulation. First Revison October DC14 Drainage Mat INSTALLATION GUIDE FOR RESIDENTIAL & COMMERCIAL APPLICATIONS
Insulation First Revison October 2016 DC14 Drainage Mat INSTALLATION GUIDE FOR RESIDENTIAL & COMMERCIAL APPLICATIONS 1. General Information This Guide describes the use of Kingspan GreenGuard DC14 Drainage
More informationPROJECT TITLE PROJECT NO: CONTRACT TITLE GRANT NO: UNIVERSITY OF CALIFORNIA, DAVIS DAVIS, CALIFORNIA
The following standard specification is intended to be edited according to the specifics of the project. Brackets [ ] and areas shaded in gray [e.g. format] indicate requirements that are optional depending
More informationDivision 04 Masonry Section New Westminster Multi-Use Civic Facility & Office Building Project No Page 1
Project No. 210022 Page 1 1 GENERAL 1.1 REQUIREMENTS INCLUDED.1 Furnish all labour, material, services and equipment necessary for the supply, delivery and erection of brick veneer as indicated on the
More informationBrick Masonry. Best Practices Guide
Brick Masonry Best Practices Guide 1. Brick 2. Brick Blending 3. Wall Ties 4. Flashing 5. Steel Lintels 6. Weep Holes 7. General Recommendations Content The information and suggestions contained in this
More informationCommercial Flashing Details
This technical note illustrates many of the most common flashing details for commercial buildings. The purpose for flashing is to direct moisture to the exterior and in so doing, prevent moisture from
More informationPERM-FLEX ASSEMBLY DIRECT APPLICATION TO CEMENTITIOUS SUBSTRATES MANUFACTURERS SPECIFICATION / SECTION 09960
STUC-O-FLEX PERM-FLEX ASSEMBLY DIRECT APPLICATION TO CEMENTITIOUS SUBSTRATES MANUFACTURERS SPECIFICATION / SECTION 09960 PART 1 - GENERAL 1.01 DESCRIPTION Provide all labor, materials and equipment necessary
More informationMaster Specifications for Microcotta November 2017
SECTION 042130 - MICROCOTTA PART 1 - GENERAL 1.1 SUMMARY A. Provide Architectural Microcotta, cast architectural polymer resin units manufactured in accordance with the Contract Documents. 1.2 WORK INCLUDED
More informationSECTION Specification for Building Limes Specification For Building Sands from Natural Sources Methods of Tests for Paints.
SECTION 09200 PART 1 - GENERAL 1.01 DESCRIPTION A. Extent of Work: The extent of lath and plaster work is shown on the drawings and in schedules and includes interior and exterior plaster work, and fibreglass
More informationSECTION TILING
PART 1 GENERAL 1.01 SECTION INCLUDES A. Ceramic Tile for floor applications. B. Ceramic Tile for wall applications. C. Ceramic accessories. D. Ceramic trim. E. Non-ceramic trim. 1.02 RELATED REQUIREMENTS
More informationMOUNTAIN STONE Products
MOUNTAIN STONE Products PRODUCT USERS GUIDE Mountain Stone Products P.O. Box 20308 42102 4301 Industrial Road Bowling Green, KY. 42101 (270) 796-6123 (270) 796-6131 (800) 781-0277 Local Fax Nationwide
More informationSECTION UNIT MASONRY CONSTRUCTION
PART 1 GENERAL 1.01 SCOPE OF WORK A. Contractor shall furnish all labor, materials, equipment and incidentals required to provide unit masonry construction as shown and specified herein. The work shall
More informationBanyan Air Service November 18, 2011 AVE Aviation and Commerce Center Building 1 Miami, FL
SECTION 04810 - UNIT MASONRY ASSEMBLIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions apply to this Section.
More informationXTREME-BOND INSTALLATION SYSTEM
XTREME-BOND FOR THIN-STONE VENEER Weather-resistant resistant Superior bonding & flexural strengths Exceptional sag resistance Meets requirements of Type S mortar Pre-blended for quality consistency from
More informationSECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection
SECTION 13090 RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection Prepared by: 90 Dayton Avenue, Unit 4B, Suite 13 Passaic, NJ 07055 (973) 574-9077 13090-1 LOW INTENSITY RADIATION PROTECTION
More informationDIVISION 7 THERMAL AND MOISTURE PROTECTION SECTION PENETRATION FIRESTOPPING
DIVISION 7 THERMAL AND MOISTURE PROTECTION SECTION 07 84 13 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
More information1 Exam Prep Concrete Masonry Handbook Questions and Answers
1 Exam Prep Concrete Masonry Handbook Questions and Answers 1. According to Concrete Masonry Handbook, a masonry unit is considered as normal weight if it has a density or unit weight of more than pounds
More informationEDGEWATER, FLORIDA JUNE 14, 2010
SECTION 09 2400 - PORTLAND CEMENT PLASTER PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationDivision 04 - Masonry Section New Westminster Multi-Use Civic Facility & Office Building Project No Page 1
Project No. 210022 Page 1 1 GENERAL 1.1 REQUIREMENTS INCLUDED.1 Furnish all labour, material, services and equipment necessary for the supply, delivery and erection of concrete block masonry and reinforced
More informationSECTION PORTLAND CEMENT PLASTERING
SECTION 09 2400 PORTLAND CEMENT PLASTERING This section includes editing notes to assist the user in editing the section to suit project requirements. These notes are included as hidden text, and can be
More informationPolice/Emergency Service Center PSGP Grant #2007-GB-T CN
SECTION 04 22 00 - CONCRETE UNIT MASONRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationA. JANDRIS & SONS Guide Specifications in CSI Format SECTION CONCRETE UNIT MASONRY
SECTION 042200 PART 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Work Included: Provide labor, materials and equipment necessary to complete the work of this Section, including but not limited to the following:
More informationSECTION CONCRETE UNIT MASONRY. A. Section Includes: Concrete unit masonry construction as shown on Drawings and as specified.
SECTION 04220 CONCRETE UNIT MASONRY PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Concrete unit masonry construction as shown on Drawings and as specified. 1.02 SYSTEM DESCRIPTION A. Performance Requirements:
More informationSECTION UNIT PAVERS
PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following: 1. Concrete pavers. 2. Detectable warning pavers. 3. Warning stripe pavers. 1.2 SUBMITTALS A. Product Data: For the following: 1. Pavers.
More information