780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS

Size: px
Start display at page:

Download "780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS"

Transcription

1 780 CMR: MASSACHUSETTS AMENDMENTS TO THE INTERNATIONAL EXISTING BUILDING CODE 2009 CHAPTER 34: EXISTING STRUCTURES Replace as follows: Title. These regulations shall be known as e Existing Building Code of Massachusetts, hereinafter referred to as "is code." Replace as follows: Scope. The provisions of is code shall apply to e repair, alteration, change of occupancy, addition, and relocation of existing buildings. See Table below which includes, but is not limited to, applicable laws and specific use of oer regulations. TABLE APPLICABLE LAWS AND REGULATIONS Unless directed oerwise in is code, reference to: Shall mean to use e requirements found in: International Plumbing Code International Property Maintenance Code International Fire Code (IFC) International Electrical Code International Energy Conservation Code (IECC) International Mechanical Code (IMC) International Fuel Gas Code International Residential Code (IRC) International Building Code (IBC) or 780 CMR Construction in flood areas Accessibility Elevators and lifts 248 CMR: Board of Plumbers and Gas Fitters Regulations 780 CMR 1.00: Scope and Administration Reference to sections of e International Fire Code (IFC) for fire prevention requirements shall be considered reference to 527 CMR: Board of Fire Prevention Regulations. The fire official enforces e provisions of 527 CMR. Reference to sections of e International Fire Code (IFC) 2009 Edition for building code requirements are adopted, except at retroactive requirements of e IFC are not adopted. The building official enforces 780 CMR and all adopted IFC requirements. Also see MGL c. 148, CMR 12.00: Massachusetts Electrical Code (Amendments) 780 CMR 13 and 51 (IECC wi MA amendments) Reference to e IMC shall apply to all mechanical systems except for at which is defined as sheet metal work by M.G.L. c. 112, 237. The provisions of 271 CMR shall apply to all sheet metal work as defined by M.G.L. c.112, 237. Note: 527 CMR may cover certain fire protection requirements of e IMC. 248 CMR: Board of Plumbers and Gas Fitters Regulations 780 CMR 51.00: Residential Volume (IRC 2009 Edition wi MA amendments). 780 CMR Base Volume a.k.a. IBC wi MA amendments. 780 CMR: Appendix G: Flood-resistant Construction 521 CMR: Architectural Access Board Regulations 524 CMR: Board of Elevator Regulations Sprinkler Systems This code (780 CMR 34.00) or if applicable M.G.L. c. 148, 26A, 26A½, 26G, 26G½, 26H or 26I, or M.G.L. c rough 86d Oer requirements for Carbon Monoxide Protection in all R-Uses Refer to: 780 CMR 9.00: Fire Protection Systems for A-2 Nightclubs Use 780 CMR 1.00, 3.00, 9.00 and /11/ CMR - Eigh Edition - 133

2 Add subsections: Compliance Alternatives. Where compliance wi e provisions of e code for new construction, required by is code, is impractical because of construction difficulties or regulatory conflicts, compliance alternatives may be accepted by e building official. The building official may accept ese compliance alternatives, archaic materials and assemblies in Resource A of is code, or oers proposed. If e compliance alternative involves fire protection systems e building official shall consult wi e fire official Add subsection: Submittals. The application for a permit shall be in accordance wi 780 CMR 1.00: Scope and Administration and identify all items of non- or partial compliance wi e requirements of is code, and compliance alternatives, if any are proposed, for approval by e building official. The building official shall respond to e acceptability of any proposed compliance alternatives wiin 30 days of e filing of e permit application. Where proposed compliance alternatives are, in e opinion of e building official, unacceptable, or where issues of non-compliance remain, e permit applicant shall have e remedies prescribed by 780 CMR, section Investigation and Evaluation. For any proposed work regulated by is code and subject to 780 CMR, section 107, as a condition of e issuance of a permit e building owner shall cause e existing building (or portion ereof) to be investigated and evaluated in accordance wi e provisions of is code The investigation and evaluation shall be in sufficient detail to ascertain e effects of e proposed work on at least ese systems: structural, means of egress, fire protection, energy conservation, lighting, hazardous materials, and ventilation for e space under consideration and, where necessary, e entire building or structure and its foundation if impacted by e proposed work. The results of e investigation and evaluation, along wi any proposed compliance alternatives, shall be submitted to e building official in written report form CMR using 100% of e prescribed forces. For existing buildings wi seismic force resisting systems found in Table , e values of R, 0, and C dfrom is table shall be used in e analysis. For seismic force resisting systems not found in Table , e values of R, 0, and C dused for analysis in accordance wi 780 CMR 16.00: Structural Design shall be ose specified for structural systems classified as "Ordinary" in accordance wi Table of ASCE 7, unless it can be demonstrated at e structural system satisfies e proportioning and detailing requirements for systems classified as "Intermediate" or "Special" Insert Table TABLE BASIC SEISMIC-FORCE-RESISTING SYSTEM R 0 Cd Bearing Wall Systems 3 Steel concentrically braced frame (CBF) wi diagonal or X-bracing CBF per 6 Edition SBC except for section 9.5 of 1992 AISC Seismic Provisions Oerwise Steel CBF wi V, Inverted V or K bracing V or Inverted V bracing per 6 Edition SBC V or Inverted V bracing, oerwise K bracing Reinforced concrete shear walls wi boundary elements and wiout coupling beams, in accordance wi 780 CMR a, 5 Edition Reinforced concrete shear walls wi reinforcing steel less an required by, or wi spacing greater an permitted by Section of ACI Unreinforced concrete shear walls Reinforced masonry shear walls 5 Class A Class B Class C Unreinforced masonry shear walls /11/ CMR - Eigh Edition - 134

3 Table continued Light-framed walls sheaed wi wood structural panels or diagonal sheaing Oer light-framed walls Building Frame Systems 3 Steel concentrically braced frame (CBF) wi diagonal or X-bracing CBF per 6 Edition SBC except for section 9.5 of 1992 AISC Seismic Provisions Oerwise Steel CBF wi V, Inverted V or K bracing V or Inverted V bracing per 6 Edition SBC V or Inverted V bracing, oerwise K bracing Reinforced concrete shear walls wi boundary elements and wiout coupling beams, in accordance wi 780 CMR a, 5 Edition Reinforced concrete shear walls wi reinforcing steel less an required by, or wi spacing greater an permitted by section of ACI Unreinforced concrete shear walls Reinforced masonry shear walls 5 Class A Class B Class C Unreinforced masonry shear walls Light-framed walls sheaed wi wood structural panels or diagonal sheaing Oer light-framed walls Moment Resisting Frame Systems Steel moment frames Special Moment Frame per 6 Edition SBC Ordinary Moment Frame per 6 Edition SBC Moment frame, oerwise Reinforced concrete moment frames 8 Class A Class B Dual Systems (See ASCE 7, Section ) Steel concentrically braced frame (CBF) wi steel moment frames (MF) CBF and Special Moment Frame, per 6 Edition SBC st CBF and Moment Frame per 1 rough 5 Editions SBC, except V, Inverted V or K Braced Frames st CBF and Moment Frame per 1 rough 5 Editions SBC, wi V, Inverted V or K Braced Frames Oerwise Reinforced concrete shear walls wi boundary elements and wiout coupling beams, in accordance wi 780 CMR a, 5 Edition, wi reinforced concrete moment frames, Class A 8 Ordinary reinforced concrete shear walls, as defined in 8 Edition SBC, wi reinforced concrete moment frames, Class A /11/ CMR - Eigh Edition - 135

4 Table continued Notes: 1. Systems of previous editions of e State Building Code at meet e ductility requirements of e 8 Edition of e Code are not included in is table. 2. SBC refers to 780 CMR Commonweal of Massachusetts State Building Code. 3. A diagonal brace is one at frames from a beam-to-column connection diagonally to anoer beam-to-column connection or to a column at its base plate. 4. The seismic resistance of e frame shall be based on its seismic connections being subject to two times e computed forces and moments resulting from seismic load. 5. Class A reinforced masonry shear walls have a minimum total area of reinforcement in e vertical and horizontal direction at least times e gross cross-sectional area of e wall, wi a minimum area in each direction at least times e gross cross-sectional area of e wall. Maximum spacing of reinforcing steel bars in grouted cells or bond courses is 6'-0" in one direction and 4'-0" in e oer direction, but not more an a of e leng or height of e wall, whichever is less, in each direction. Class A walls satisfy oer requirements for reinforced masonry of e base code. 6. Class B reinforced masonry shear walls satisfy all requirements for Class A walls, except at spacing limits for reinforcing steel bars are exceeded. 7. Class C reinforced masonry shear walls satisfy all requirements for reinforced masonry of e base code. 8. Class A reinforced concrete moment frames satisfy requirements of Sections , , and of 780 CMR 5 Edition and Sections and of ACI for reinforcing of beam to column joints. 9. Class B reinforced concrete moment frames do not satisfy requirements for Class A reinforced concrete moment frames. 10. Wood siding over horizontal or diagonal boards, plaster on wood or metal la, and stucco on metal la may be used to resist in-plane shear, where e walls are anchored to floors and to e floor or roof construction above such at ey can transfer e shear between floors and to e foundation. Gypsum sheaing, la, wall board, drywall, fiberboard and particle board are not permitted to resist in-plane shear unless originally designed in accordance wi 780 CMR for at purpose Add ese exceptions to Item Add subsection: Exceptions: CMR using 50% of prescribed forces when directed here by section CMR using eier a. 50 % of prescribed forces when directed here by section and when e vertical addition increases e building area less an or equal to 30% or, b. 75% of prescribed forces when directed here by section and when e vertical addition increases e building area more an 30% but less an 50% Cumulative Effects of Alterations, Additions, or Changes of Occupancy on Structural Elements. As noted in several sections of is code, evaluation of structural elements and eir connections shall consider e cumulative effects of alterations, additions, or changes of occupancy since original construction. Exception. When structural work: 1. does not involve more an 2% of e total tributary area of horizontal framing members of any existing framed floor or roof and, 2. does not alter shear walls above e foundation and, 3. does not alter columns or diagonal braces and, 4. does not create an opening in any framed floor or roof at has an area more an 2% of e framed floor or roof and, 5. does not alter any floor or roof diaphragm and its connections such at in-plane shear resistance is reduced by more an 5% and, 6. does not remove or reconfigure lateral load resisting frames, or foundations supporting em. 4/11/ CMR - Eigh Edition - 136

5 102.2 Replace as follows: Oer Laws and Specialty Codes. See 780 CMR 1.00: Scope and Administration. PART 2 - ADMINISTRATION AND ENFORCEMENT and all sections contained wiin it, replace wi: PART 2 - ADMINISTRATION AND ENFORCEMENT. For administration and enforcement provisions refer to 780 CMR Replace two and add two definitions as follows: CODE OFFICIAL. See BUILDING OFFICIAL in 780 CMR 2.00: Definitions. COMPLIANCE ALTERNATIVE. An alternative life-safety construction feature which meets or exceeds e requirements or intent of a specific provision of 780 CMR. The building official is auorized to approve or disapprove compliance alternatives. Compliance alternatives are allowed only for existing buildings. HOUSE MUSEUM. A house museum is an historic building or structure. The principal use of such must be as an exhibit of e building or e structure itself which is open to e public not less an 12 days per year, alough additional uses, original and/or ancillary to e principal use shall be permitted wiin e same building up to maximum of 40% of e gross floor area. All entries into e house museum list shall be certified by e Massachusetts Historical Commission. The list can be found at REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE. REGISTERED DESIGN PROFESSIONAL in 780 CMR 2.00: Definitions. See Add a last sentence as follows: Addition or replacement of roofing or replacement of equipment shall comply wi section and as applicable After e first sentence, add is sentence: The cumulative effect of e load increase since original construction shall be considered After e first sentence, add is sentence: Add Section: The cumulative effect of e load increase since original construction shall be considered Seismic Hazards. Compliance wi is section is required where e work area exceeds 50% of e aggregate area of e building Wall Anchors for Concrete and Masonry Buildings. For any building assigned to Seismic Design Category B, C, D, E or F wi a structural system consisting of concrete or reinforced masonry walls wi flexible roof or floor diaphragms or unreinforced masonry walls wi any type of roof or floor diaphragm, e alteration work shall include installation of wall anchors at e roof and floor levels to resist e reduced IBC-level seismic forces specified in section , unless an evaluation demonstrates compliance of existing wall anchorage Bracing for Unreinforced Masonry Parapets. Parapets constructed of unreinforced masonry in buildings assigned to Seismic Design Category B, C, D, E or F shall have bracing installed as needed to resist e reduced IBC-level seismic forces specified in section , unless an evaluation demonstrates compliance of such items. Parapet corrective work shall be performed in conjunction wi e installation of tension roof anchors. The minimum height of a parapet above any wall anchor shall be 12 inches. Exception: If e maximum height of an unbraced unreinforced masonry parapet above e lower of eier e level of tension anchors or e roof sheaing does not exceed a height-to-ickness ratio of 2.5, en bracing is not required. 4/11/ CMR - Eigh Edition - 137

6 606.2 To exceptions 1 and 2, add a second sentence as follows: The cumulative effect of e load increase since original construction shall be considered Add is exception: Exception: If e maximum height of an unbraced unreinforced masonry parapet above e lower of eier e level of tension anchors or e roof sheaing does not exceed a height-to-ickness ratio of 2.5, en bracing is not required Modify as follows: Roof Diaphragms Resisting Wind Loads in High Wind Regions. Where roofing materials are removed from e entire roof diaphragm of a building located where e basic wind speed is 115 mph or greater and e occupancy category is type IV as defined in Table of 780 CMR, roof diaphragms and connections at are part of e main wind-force resisting system shall be evaluated for e wind loads specified in 780 CMR, including wind uplift. If e diaphragms and connections in eir current condition do not comply wi ose wind provisions, ey shall be replaced or strengened in accordance wi e loads specified in 780 CMR Replace e exception as follows: Exception. Buildings in which e reconfiguration is exclusively e result of compliance wi e accessibility requirements of e Architectural Access Board at 521 CMR Add is exception: Exception. R-2 structures of ree units, undergoing Level 2 renovations, are exempt from e requirements of is section provided at: 1. The work area is on a single unit and, 2. No oer permits for Level 2 work have been issued for e building in e previous two years Item 3., , and Item 2. Delete e word 'municipal' Replace as follows: Supervision. Fire sprinkler systems required by is section shall be supervised in accordance wi 780 CMR 9.00: Fire Protection Systems rough , and Replace International Fire Code wi 780 CMR 9.00: Fire Protection Systems Delete Exception Insert after e '100' text as follows: 'and Nightclubs wi an occupant load of 50 or greater' Add is as a second sentence to Exception 1: The cumulative effect of e stress increase since original construction shall be considered for e purposes of is exception Add subsection: Irregularities. Where e alteration results in a structural irregularity as defined in ASCE 7, e lateral load-resisting structural elements shall comply wi e structural requirements specified in section /11/ CMR - Eigh Edition - 138

7 802.1 Replace is section as follows: High-rise Buildings. High-rise buildings as defined by 780 CMR 2.00: Definitions shall comply wi e requirements of section Delete e word 'municipal' which occurs in two locations Delete Exception At e end of is section add ese two sentences: Add sections: For e purposes of calculating demand-capacity ratios, e demand shall consider applicable load combinations wi design lateral loads or forces in accordance wi 780 CMR, sections 1609 and For purposes of is section, comparisons of demand-capacity ratios and calculation of design lateral loads, forces, and capacities shall account for e cumulative effects of additions and alterations since original construction Seismic Hazards. Compliance wi is section is required only when e work area exceeds 50% of e aggregate area of e building Wall Anchors for Concrete and Masonry Buildings. For any building assigned to Seismic Design Category B, C, D, E or F wi a structural system consisting of concrete or reinforced masonry walls wi flexible roof or floor diaphragms or unreinforced masonry walls wi any type of roof or floor diaphragm, e alteration work shall include installation of wall anchors at e roof and floor levels to resist e reduced IBC-level seismic forces specified in section , unless an evaluation demonstrates compliance of existing wall anchorage Bracing for Unreinforced Masonry Parapets. Parapets constructed of unreinforced masonry in buildings assigned to Seismic Design Category B, C, D, E or F shall have bracing installed as needed to resist e reduced IBC-level seismic forces specified in section , unless an evaluation demonstrates compliance of such items. Parapet corrective work shall be performed in conjunction wi e installation of tension roof anchors. The minimum height of a parapet above any wall anchor shall be 12 inches. Exception: If e maximum height of an unbraced unreinforced masonry parapet above e lower of eier e level of tension anchors or e roof sheaing does not exceed a height-to-ickness ratio of 2.5, en bracing is not required Add items 10. and 11. and e note as follows: 10. Day care. (see 780 CMR for classification) 11. Group homes. Note. Also see section 912 when change of occupancy classification occurs Add is as a second sentence to e exception: The cumulative effect of e stress increase since original construction shall be considered for e purpose of is exception Replace first paragraph and Exception 1 as follows: Delete Compliance wi e International Building Code Level Seismic Forces. Where a building or portion ereof is subject to a change of occupancy at results in e building being assigned to a higher occupancy category based on 780 CMR Table , e building shall comply wi seismic forces as specified in section for e new occupancy category. Exceptions: 1. Any occupancy being changed to Group A, E, I-1, R-1, R-2 or R-4 occupancies for buildings less an six stories in height and in Seismic Design Category A, B or C. 4/11/ CMR - Eigh Edition - 139

8 To exception 1 add a second sentence as follows: The cumulative effect of e stress increase since original construction shall be considered for e purpose of is exception Add a second sentence as follows: Where e addition increases e building area less an 50%, e evaluation and analysis shall demonstrate compliance wi reduced seismic force levels as specified in section To exception 1 add a second sentence as follows: The cumulative effect of e stress increase since original construction shall be considered for e purpose of is exception Replace is section as follows: Scope. It is e intent of is chapter to provide means for e preservation of historic buildings as certified by e Massachusetts Historical Commission. There is no obligation for owners of historic buildings to use e provisions of is chapter. This chapter shall preempt all oer regulations of 780 CMR governing e reconstruction, renovation, alteration, change of use and occupancy, repair, maintenance and additions for e conformity of historic buildings and structures to 780 CMR, wi e exception of 780 CMR, section 113 for appeals, or unless oerwise specified. In case of fire or oer casualty to a historic building, said building may be rebuilt, in total or in part, using such techniques and materials as are necessary to restore it to its original condition and use group. If a building or structure as a result of proposed work would become eligible for certification as a historic building and e Massachusetts Historical Commission so certifies by affidavit, and such affidavit is submitted to e building official wi e permit application, en e building official shall have e auority to allow e work to proceed under e provisions of is chapter Replace all references to 'museum' wi 'house museum' Add a second paragraph as follows: Where one or more floors of a house museum are limited to one means of egress, e occupancy load shall be computed as follows: 1. Floors below e First Story. Not more an one occupant per 100 square feet of gross floor area wi a maximum occupancy of First Story. Not more an one occupant per 50 square feet of gross floor area. 3. Second Story and Above. Not more an one occupant per 100 square feet of gross floor area, or 30 occupants per 22 inch unit of egress wid, whichever condition results in e lesser occupancy load Replace as follows: Fire Protection Equipment. Fire protection equipment shall be provided for house museums according to e following requirements: 1. Manual Fire Extinguishing Equipment. All use groups, oer an R-3 and R-4, shall have approved manual fire extinguishing equipment, as determined by e head of e local fire department. 2. Fire Alarm Systems. Use groups R-1, R-2 and R-3 shall conform to e requirements of 780 CMR 907, as applicable. All oer use groups shall comply wi section items 2.(a) and (b). (a) Locations. Provide smoke detectors in accordance wi manufacturers listing and spacing requirements, but not less an one, for every 1200 square feet of floor area per level. In addition, all lobbies, common corridors, hallways and exitway access and discharge routes shall be provided wi approved smoke detectors installed in accordance wi e manufacturers listing and spacing requirements but not more an 30 feet spacing between detectors. All required smoke detectors shall have an alarm audible roughout e structure or building. (b) Single Station and Multiple Station Smoke Detection Devices. As required by 780 CMR 9.00: Fire Protection Systems. 4/11/ CMR - Eigh Edition - 140

9 3. Manual Pull Stations. A manual fire alarm pull station shall be provided in e natural pa of egress in all use groups except R-3 and R-4. Manual pull stations shall be connected to e building fire warning system in conformance wi NFPA 72. Exception. House museums which are provided wi an approved automatic fire-extinguishing system roughout shall not be required to be provided wi manual fire extinguishing equipment. Smoke detection devices shall not be required in occupancies oer an Use Groups R-1, R-2, and R Supervision. Fire alarm systems required by is section shall be supervised in accordance wi e requirements 780 CMR 9.00: Fire Protection Systems. Exception. Residential single and multiple station smoke detectors Add a second exception as follows: Exceptions 2. House museums need not comply wi e wind load and seismic load requirements of is code Delete e first sentence of is section Add section: Peer Review. At e discretion of e building official, e owner shall engage a registered design professional to review e performance compliance evaluation and meodologies proposed to determine compliance wi is section. The registered design professional shall prepare a written report to e building official summarizing e results of eir review. Items identified by e registered design professional as needing modification in order to be in compliance wi is section shall be addressed to e satisfaction of e building official prior to e issuance of a building permit Add note as follows: Note. Automatic sprinklers required by M.G.L. c G need not be considered "Required sprinklers" for e purposes of is section Add two notes at e end of is section: Add section: Note 1. As applicable, Department of Environmental Protection (DEP) Regulations, 310 CMR 7.09: U: Dust, Odor, Construction and Demolition, and e requirements of M.G.L. c A, addressing disposal of demolition debris, must be satisfied. Note 2. As applicable, 527 CMR, in conjunction wi M.G.L. c A must be satisfied if fire protection systems are to be dismantled, shut-off, or modified Removal of Waste Material. Material shall not be dropped by gravity or rown outside e exterior walls of a building during demolition or erection, chutes shall be provided for e removal of such materials. Where e removal of any material will cause an excessive amount of dust, such material shall be wet down to prevent e creation of a nuisance. Exception. The requirements of is section may be waived based on site conditions if approved by e building official Replace 'e International Plumbing Code' wi 'e requirements of e Department of Public Heal and 248 CMR, as applicable' Replace 'section 110.3' wi 780 CMR 1.00: Scope and Administration Delete is section. 4/11/ CMR - Eigh Edition - 141

10 Appendix A106.2 Add subsection 4 as follows: 4. The values contained in Table A106.2 shall be used as material property values of e existing material listed erein, unless values are specified by oer provisions in is chapter, or values are used, based on available historical information for a particular type of masonry construction, prevailing codes, and assessment of existing conditions. A106.2 Insert TABLE A106.2 MATERIAL PROPERTY VALUES TABLE A106.2 MATERIAL PROPERTY VALUES Symbol/Notat ion Description Maximum Value Notes f m See section A psi Per section A108.3 E Elastic Modulus in Compression 550,000 psi Based on f = 1,000 psi m f sp See section A104 0 psi - v m Masonry wi running bond lay-up 20 psi - m v m Masonry, fully grouted, wi a lay-up oer an running bond 20 psi - v m Masonry, partially grouted or ungrouted, wi a lay-up oer an running bond 10 psi - (PAGES 143 THROUGH 146 ARE RESERVED FOR FUTURE USE.) 4/11/ CMR - Eigh Edition - 142

101.1 Title. These regulations shall be known as the Existing Building Code of Massachusetts, hereinafter referred to as this code.

101.1 Title. These regulations shall be known as the Existing Building Code of Massachusetts, hereinafter referred to as this code. This file incorporates comment from numerous stakeholders and building officials, staff, two BBRS advisory committees (SAC and C34AC), and others into the original redline code proposal approved by the

More information

780 CMR CHAPTER 34 EXISTING BUILDINGS STRUCTURES

780 CMR CHAPTER 34 EXISTING BUILDINGS STRUCTURES 780 CMR CHAPTER 34 EXISTING BUILDINGS STRUCTURES SECTION 3401 GENERAL 3401.1 Scope. Chapter 34 of the International Building Code 2009 is deleted in its entirety. The provisions of the International Existing

More information

Sponsored by The Boston Association of Structural Engineers and the Structural Engineers Association of Massachusetts

Sponsored by The Boston Association of Structural Engineers and the Structural Engineers Association of Massachusetts Commonwealth of Massachusetts State Building Code 780-CMR 9 th Edition Renovation of Existing Buildings Using The International Existing Building Code IEBC 2015 with Massachusetts Amendments Sponsored

More information

CODE ANALYSIS REPORT SECOND FLOOR

CODE ANALYSIS REPORT SECOND FLOOR CODE ANALYSIS REPORT SECOND FLOOR 384 DWIGHT STREET HOLYOKE, MA Prepared by Dietz & Company Architects, Inc. 17 Hampden Street Springfield, MA March 2014 INTRODUCTION The following report is a preliminary

More information

Code Requirements for Existing Buildings. R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617)

Code Requirements for Existing Buildings. R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) Code Requirements for Existing Buildings R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) 523-8227 www.rwsullivan.com R.W. Sullivan Engineering (RWS) was established in 1945 and currently

More information

CHAPTER 34 EXISTING BUILDINGS

CHAPTER 34 EXISTING BUILDINGS CHAPTER 34 EXISTING BUILDINGS SECTION 3401 GENERAL 3401.1 Scope. Provisions of this chapter shall govern the application of this code to existing buildings. Exception: Buildings and structures located

More information

&02.1. Level 3 Alterations. Level 3 Alterations shall comply with Sections & and &

&02.1. Level 3 Alterations. Level 3 Alterations shall comply with Sections & and & &01 GENERAL To be developed. All of the exceptions have to be coordinated. &02 SPECIAL USE AND OCCUPANCY &02.1. Level 3 Alterations. Level 3 Alterations shall comply with Sections &02.1.1 and &02.1.2.

More information

City of Tacoma Planning and Development Services

City of Tacoma Planning and Development Services City of Tacoma Planning and Development Services ORDINANCE NO. 28155 Adopt and Amend the City s Building Code; amending Title 2 of the Tacoma Municipal Code, implement the 2012 International Building,

More information

Table 3. Detailed Comparison of Structural Provisions of IRC 2000 and 1997 NEHRP (Continued)

Table 3. Detailed Comparison of Structural Provisions of IRC 2000 and 1997 NEHRP (Continued) 2000 IRC 1997 NEHRP Section Provision Section Provision Comments CHAPTER 3 BUILDING PLANNING R301 DESIGN CRITERIA R301.2.2 Seismic Provisions R301.2.2.1 Determination of Seismic Design Category R301.2.2.1.1

More information

2012 IEBC Fundamentals 12/11/2017. Copyright 2012 International Code Council 1

2012 IEBC Fundamentals 12/11/2017. Copyright 2012 International Code Council 1 Overview 2012 IEBC Fundamentals The purpose of the IEBC is to encourage the use and re-use of existing buildings while requiring reasonable upgrades and improvements Based on the 2012 International Existing

More information

Code Requirements for Existing Buildings. R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617)

Code Requirements for Existing Buildings. R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) Code Requirements for Existing Buildings R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) 523-8227 www.rwsullivan.com R.W. Sullivan Engineering (RWS) was established in 1945 and currently

More information

2003 International Building Code Errata

2003 International Building Code Errata 2003 International Building Code Errata EDITORIAL CHANGES SECOND PRINTING Page 12, CERAMIC FIBER BLANKET: Section reference now reads... 721.1.1 Page 13, CONCRETE CARBONATE AGGREGATE: now reads... See

More information

Prescriptive and Engineered Design Provisions of the Massachusetts One- and Two-Family Dwelling Code

Prescriptive and Engineered Design Provisions of the Massachusetts One- and Two-Family Dwelling Code Prescriptive and Engineered Design Provisions of the Massachusetts One- and Two-Family Dwelling Code Released July 27, 2009 Introduction: Buildings in the United States are designed to withstand the loads

More information

635 BUREAU OF BUILDING CODES AND STANDARDS MAINE UNIFORM BUILDING AND ENERGY CODE - COMMERCIAL BUILDING CODE OF MAINE

635 BUREAU OF BUILDING CODES AND STANDARDS MAINE UNIFORM BUILDING AND ENERGY CODE - COMMERCIAL BUILDING CODE OF MAINE 16 DEPARTMENT OF PUBLIC SAFETY 635 BUREAU OF BUILDING CODES AND STANDARDS Chapter 3: MAINE UNIFORM BUILDING AND ENERGY CODE - COMMERCIAL BUILDING CODE OF MAINE SUMMARY: This chapter establishes the Commercial

More information

Narrative Summary of Changes to PA UCC

Narrative Summary of Changes to PA UCC Narrative Summary of Changes to PA UCC 401.1. Definitions. This section changes the definitions for the IBC, the IECC, the IEBC, the IFC, the IFGC, the IMC, the International Performance Code, the IPC,

More information

Supplemental Plan Check List for Unreinforced Masonry (URM) Retrofit

Supplemental Plan Check List for Unreinforced Masonry (URM) Retrofit Supplemental Plan Check List for Unreinforced Masonry (URM) Retrofit Plan Check/PCIS App #: Job Address: P.C. Engineer: Phone: (E -mail: first name.last name@ lacity.org) For instructions and other information,

More information

Project Address: Name of Person Completing Form:

Project Address: Name of Person Completing Form: Statement of Inspections This form is provided as a way to list aspects of the project that require special inspection and testing in accordance with IBC Sections 107.1, 1704, and 1705 and define duties

More information

Mandatory Wood Frame Soft-story Retrofit Program STRUCTURAL DESIGN GUIDELINES

Mandatory Wood Frame Soft-story Retrofit Program STRUCTURAL DESIGN GUIDELINES INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LAMC Division 93 Effective: 11/22/15 DOCUMENT NO.: P/BC 2014-137 Revised: 06/07/16 Previously Issued As: N/A Mandatory Wood Frame Soft-story

More information

SPECIAL INSPECTION AND OBSERVATION PROGRAM City of Walnut Creek Building Division. Project Address:

SPECIAL INSPECTION AND OBSERVATION PROGRAM City of Walnut Creek Building Division. Project Address: SPECIAL INSPECTION AND OBSERVATION PROGRAM City of Walnut Creek Building Division Permit Application #: Project Address: Purpose: To meet the requirements of City of Walnut Creek Municipal Code Section

More information

NOTE: For construction other than new commercial or additions (renovations), only those areas below describing the scope of work will be applicable.

NOTE: For construction other than new commercial or additions (renovations), only those areas below describing the scope of work will be applicable. Applicant s Name: New Commercial - Commercial Additions Renovations Permit Plan Submittal Check List Applicant s Phone Number (s): Project Address: Project Type: _New Commercial or Commercial Addition

More information

SECTION NON-STRUCTURAL SEISMIC DESIGN CRITERIA PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SECTION NON-STRUCTURAL SEISMIC DESIGN CRITERIA PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 014100 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

SPECIAL INSPECTION AGREEMENT

SPECIAL INSPECTION AGREEMENT PART 1 STATEMENT OF SPECIAL INSPECTIONS When special inspection is required to be performed in accordance with International Building Code Chapter 17, a building permit cannot be issued until a statement

More information

Virginia Existing Building Code

Virginia Existing Building Code 2015 Virginia Existing Building Code 2015 Virginia Existing Building Code First Printing: September 2018 ISBN: 978-1-60983-852-2 COPYRIGHT 2018 by INTERNATIONAL CODE COUNCIL, INC. ALL RIGHTS RESERVED.

More information

Building Code 8 th Edition

Building Code 8 th Edition Massachusetts State Building Code 8 th Edition Kevin S. Hastings, P.E., LEED AP R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) 523-8227 www.rwsullivan.com RW R.W. Sullivan Engineering

More information

Plan Check No. Checked by: An Appointment Is Required for Verification

Plan Check No. Checked by: An Appointment Is Required for Verification SUPPLEMENTAL CORRECTION SHEET UNREINFORCED MASONRY (URM) RETROFIT ( 2002 LABC ) Plan Check No. Checked by: Permit Appl. # An Appointment Is Required for Verification Job Address: For appt. call: APPLICATION

More information

Statement of Special Inspections Michigan Building Code 2012 (MBC 2012)

Statement of Special Inspections Michigan Building Code 2012 (MBC 2012) Gaines Charter Township 8555 Kalamazoo Ave SE Caledonia MI 49316 PH: 616 698-6640 Fax: 616 698-2490 www.gainestownship.org Building Department Statement of Special Inspections Michigan Building Code 2012

More information

2015 International Existing Building Code Overview Based on the International Existing Building Code (IEBC )

2015 International Existing Building Code Overview Based on the International Existing Building Code (IEBC ) Goal 2015 International Existing Building Code Overview Based on the International Existing Building Code (IEBC ) To identify and describe key provisions of the 2015 IEBC. 2015 IEBC Overview 3 Description

More information

ALTERNATE DESIGN METHODOLOGY FOR UNREINFORCED MASONRY BUILDINGS

ALTERNATE DESIGN METHODOLOGY FOR UNREINFORCED MASONRY BUILDINGS INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LABC 8808 Effective: 01-01-2011 DOCUMENT NO. P/BC 2011-053 Revised: Previously Issued As: P/BC 2008-053 I. GENERAL ALTERNATE DESIGN METHODOLOGY

More information

Statement of Special Inspection Requirements

Statement of Special Inspection Requirements Statement of Special Inspection Requirements California Building Code Chapter 17 Construction plans shall include a statement of special inspection in accordance with CBC chapter 17. The statement of special

More information

Application for a Building Permit Commercial Work Building Commissioner 37 Main Street Charlton, MA

Application for a Building Permit Commercial Work Building Commissioner 37 Main Street Charlton, MA Paid Amount: Date: Check Number: Initials 1. Owner, Applicant Information Application for a Building Permit Work Building Commissioner 37 Main Street Charlton, MA 01507 508-248-2241 Date: Approved by:

More information

STATEMENT OF SPECIAL INSPECTION FORM

STATEMENT OF SPECIAL INSPECTION FORM Project Title: Permit #: Project Address: STATEMENT OF SPECIAL INSPECTION FORM This Statement of Special Inspections is submitted in fulfillment of the requirements of CBC Sections 1704 and 1705. Special

More information

Ordinance No July 1, 2016

Ordinance No July 1, 2016 (Insert Facing Page 3 IRC) 2.02.540 Amendment to IRC Section R105.2 Work Exempt From Permit, Building and Electrical Sections. The following additional exception shall be added to R105.2 Building: Building:

More information

Summary of Key Changes

Summary of Key Changes 9 th Edition of the Massachusetts Building Code () Summary of Key Changes Below is a summary of key changes between the current 8 th and proposed 9 th editions. The 8 th edition used the 2009 model codes

More information

ORDINANCE. APPROVED EMERGENCY: (Yes) (No) VETOED: Date

ORDINANCE. APPROVED EMERGENCY: (Yes) (No) VETOED: Date ORDINANCE AN ORDINANCE OF THE COMMISSION OF KNOX COUNTY, TENNESSEE RESCINDING ARTICLE III. CABO ONE- AND TWO-FAMILY DWELLING CODE, SEC. 10-56, SEC. 10-57 AND SEC. 10-58 AND ADOPTING THE 2006 INTERNATIONAL

More information

Structural Tests and Special Inspections Form. Inspection of Fabricators (1704.2)

Structural Tests and Special Inspections Form. Inspection of Fabricators (1704.2) Inspection of Fabricators (1704.2) Furnish inspection reports (1704.2.1) - Fabricators that have not been approved Provide a Certificate of Compliance (1704.2.2) - Approved Fabricators Steel Construction

More information

Mechanical Engineer of Record: (Smoke Control Systems Only) Name & License Company. Others: Responsible Party Name & License Company

Mechanical Engineer of Record: (Smoke Control Systems Only) Name & License Company. Others: Responsible Party Name & License Company PRINCE WILLIAM COUNTY Department Development Services Building Development Division STATEMENT OF SPECIAL INSPECTIONS (Building/Other Structures other than Retaining Walls) Version 2015-12-31 Building Permit

More information

2006 to 2012 IBC. Significant Changes

2006 to 2012 IBC. Significant Changes 2006 to 2012 IBC Significant Changes 1. Addition 303.3 Assembly Group A 2. Assembly uses intended for food and/or drink consumption including, but not limited to: Banquet halls Casinos (gaming areas) added

More information

R CODE CHANGE PROPOSAL FORM (See instructions on page 2)

R CODE CHANGE PROPOSAL FORM (See instructions on page 2) CODE CHANGE PROPOSAL FORM (See instructions on page 2) Code: IRC 12/13 Sections 301.2.2.2.1 Proponent: Charles S. Bajnai, Chesterfield County, VA, ICC Building Code Action Committee 1. Delete as shown

More information

Minnesota Healthcare Engineers Association, Fall Conference. Bob Dehler, P.E. Engineering Program Manager September 14, 2017

Minnesota Healthcare Engineers Association, Fall Conference. Bob Dehler, P.E. Engineering Program Manager September 14, 2017 Minnesota Healthcare Engineers Association, Fall Conference Bob Dehler, P.E. Engineering Program Manager September 14, 2017 Categories of Rehabilitation Work in Healthcare Facilities Bob Dehler, P.E. robert.dehler@state.mn.us

More information

2015 IBC Update. Copyright 2014 International Code Council #1000PDF15 1

2015 IBC Update. Copyright 2014 International Code Council #1000PDF15 1 Goal 2015 IBC Update Based on the International Building Code (IBC ) The goal is to familiarize building officials, fire officials, plans examiners, inspectors, design professionals, contractors, and others

More information

SEISMIC DESIGN GUIDELINES

SEISMIC DESIGN GUIDELINES INTRODUCTION The purpose of these Seismic Design Guidelines is to provide additional information and clarification to Civil or Structural engineers in order to comply with Ordinance No. 18-O- 2767 for

More information

VOLUNTARY - EARTHQUAKE HAZARD REDUCTION IN EXISTING HILLSIDE BUILDINGS (Division 94 Added by Ord. No. 171,258, Eff. 8/30/96.)

VOLUNTARY - EARTHQUAKE HAZARD REDUCTION IN EXISTING HILLSIDE BUILDINGS (Division 94 Added by Ord. No. 171,258, Eff. 8/30/96.) DIVISION 94 VOLUNTARY - EARTHQUAKE HAZARD REDUCTION IN EXISTING HILLSIDE BUILDINGS (Division 94 Added by Ord. No. 171,258, Eff. 8/30/96.) SEC. 91.9401. PURPOSE. (Amended by Ord. No. 172,592, Eff. 6/28/99,

More information

A. Are Plan Reviews Important? B. Statement of Special Inspections C. Deferred Submittals D. DFCM Requirements

A. Are Plan Reviews Important? B. Statement of Special Inspections C. Deferred Submittals D. DFCM Requirements A. Are Plan Reviews Important? B. Statement of Special Inspections C. Deferred Submittals D. DFCM Requirements Is it okay to simply accept the engineer s stamp? Some key items to consider Life safety All

More information

Seismic Design Requirements

Seismic Design Requirements City of Medford Municipal Code Chapter 9 Presented by the Building Safety Department THESE PROVISIONS PRESCRIBE THE DESIGN REQUIREMENTS OF EXISTING BUILDINGS UNDERGOING: CHANGE OF OCCUPANCY ADDITIONS ALTERATIONS

More information

Emeryville's Seismic Hazard Mitigation Ordinance

Emeryville's Seismic Hazard Mitigation Ordinance Emeryville's Seismic Hazard Mitigation Ordinance THIS IS THE CITY OF EMERYVILLE'S SEISMIC HAZARD MITIGATION ORDINANCE PASSED IN 1995 TO AMEND AND CLARIFY AN EARLIER ORDINANCE PASSED IN 1990. THIS ORDINANCE

More information

SOUTHERN NEVADA AMENDMENTS TO THE 2009 INTERNATIONAL RESIDENTIAL CODE

SOUTHERN NEVADA AMENDMENTS TO THE 2009 INTERNATIONAL RESIDENTIAL CODE SOUTHERN NEVADA AMENDMENTS TO THE 2009 INTERNATIONAL RESIDENTIAL CODE First Printing: December 17, 2010 Clark County Ronald L. Lynn 4701 W. Russell Road Las Vegas, Nevada 89118 (702) 455-3000 Inspections

More information

REINFORCING TABLES INSTALLATION MANUAL

REINFORCING TABLES INSTALLATION MANUAL REINFORCING TABLES 201 REINFORCING TABLES Design Limitations Introduction The structural wall reinforcing and lintel design tables contained within the Appendix of NUDURA s Installation Manual have been

More information

AN ORDINANCE AMENDING TITLE 10 (BUILDING REGULATIONS)

AN ORDINANCE AMENDING TITLE 10 (BUILDING REGULATIONS) 1 AN ORDINANCE AMENDING TITLE 10 (BUILDING REGULATIONS) (BUILDING REGULATIONS FOR THE CONSTRUCTION OF INDUSTRIAL, STORAGE, BUSINESS, INSTITUTIONAL, AND PUBLIC BUILDINGS AND RESIDENCES) OF THE GENEVA CITY

More information

Chapter 4-16 SPECIAL DESIGN STANDARDS FOR TYPE V CONSTRUCTION

Chapter 4-16 SPECIAL DESIGN STANDARDS FOR TYPE V CONSTRUCTION Chapter 4-16 SPECIAL DESIGN STANDARDS FOR TYPE V CONSTRUCTION Sections: 4-16-01 PURPOSE 4-16-02 APPLICABLE AREA 4-16-03 CONSTRUCTION AND OCCUPANCY 4-16-04 UPPER BUILDING AREA, HEIGHT, NUMBER OF STORIES

More information

CODE ACTION AMENDMENTS

CODE ACTION AMENDMENTS UCC Review and Advisory Council OFFICIAL Record of 2015 I-Code Review May 1, 2018 CODE ACTION AMENDMENTS 2015 ADMIN ADOPT None 2015 IWUIC ADOPT None 2015 IFC ADOPT None 2015 IBC ADOPT Delete Section 913.2.2

More information

STRUCTURAL ISSUES IN RESIDENTIAL CONSTRUCTION. Presented by: Susan L. Lasecki P.E., S.E.

STRUCTURAL ISSUES IN RESIDENTIAL CONSTRUCTION. Presented by: Susan L. Lasecki P.E., S.E. STRUCTURAL ISSUES IN RESIDENTIAL CONSTRUCTION Presented by: Susan L. Lasecki P.E., S.E. Presentation Outline Gravity Design Load Paths from Roof to Foundation Roof Framing Floor Framing Wall Framing Lateral

More information

PRESCRIPTIVE COMPLIANCE METHOD

PRESCRIPTIVE COMPLIANCE METHOD CHAPTER 3 PRESCRIPTIVE COMPLIANCE METHOD [B] SECTION 301 GENERAL 301.1 Scope. The provisions of this chapter shall control the alteration, repair, addition and change of occupancy of existing structures,

More information

Analysis of Changes for the 5 th Edition (2014) of the Florida Codes

Analysis of Changes for the 5 th Edition (2014) of the Florida Codes Analysis of Changes for the 5 th Edition (2014) of the Florida Codes Changes to the Florida Building Code, Existing Building This Analysis of Changes for the 5 th Edition (2014) of the Florida Codes is

More information

Department of Public Safety and Corrections Uniform Construction Code Council. Uniform Construction Code (LAC 55:VI.301)

Department of Public Safety and Corrections Uniform Construction Code Council. Uniform Construction Code (LAC 55:VI.301) Department of Public Safety and Corrections Uniform Construction Code Council Uniform Construction Code (LAC 55:VI.301) In accordance with the provisions of R.S. 40:1730.26 and R.S. 40:1730.28, relative

More information

INTERNATIONAL EXISTING BUILDING CODE

INTERNATIONAL EXISTING BUILDING CODE INTERNATIONAL EXISTING BUILDING CODE EB14-06/07 202 Proposed Change as Submitted: Proponent: Maureen Traxler, City of Seattle, Washington, representing Washington Association of Building Officials Revise

More information

HAMPTON ROADS AREA STATEMENT OF SPECIAL INSPECTIONS

HAMPTON ROADS AREA STATEMENT OF SPECIAL INSPECTIONS Appendix A HAMPTON ROADS AREA STATEMENT OF SPECIAL INSPECTIONS PROJECT PERMIT APPLICANT PRIMARY RDP OF RECORD STRUCTURAL ENGINEER OF RECORD This Statement of Special Inspections is submitted as a condition

More information

CHAPTER 6 BUILDING REGULATIONS ARTICLE I - BUILDING CODES

CHAPTER 6 BUILDING REGULATIONS ARTICLE I - BUILDING CODES CHAPTER 6 BUILDING REGULATIONS ARTICLE I - BUILDING CODES 6-1-1 PURPOSE. The purpose of this Article is to provide for safety, health public welfare through structural strength and stability, means of

More information

ORDINANCE NO. 16- The City Council of the City of West Hollywood does hereby ordain as follows:

ORDINANCE NO. 16- The City Council of the City of West Hollywood does hereby ordain as follows: Page 1 ORDINANCE NO. 16- AN ORDINANCE OF THE CITY OF WEST HOLLYWOOD ESTABLISHING SEISMIC STRENGTHENING REQUIREMENTS FOR FOUR CATEGORIES OF EXISTING BUILDINGS IN THE CITY AND AMENDING THE WEST HOLLYWOOD

More information

SPECIAL INSPECTION AND TESTING AGREEMENT

SPECIAL INSPECTION AND TESTING AGREEMENT COUNTY OF MENDOCINO DEPARTMENT OF PLANNING AND BUILDING SERVICES 860 NORTH BUSH STREET UKIAH CALIFORNIA 95482 120 WEST FIR STREET FT. BRAGG CALIFORNIA 95437 STEVE DUNNICLIFF, DIRECTOR PHONE: 707-234-6650

More information

Structural Engineering

Structural Engineering Structural Engineering 4 4.0 TABLE OF CONTENTS 4.1 General Approach 115 Submission Requirements 4.2 Codes and Standards 116 Structural Design of New Buildings 116 Use of Recycled Materials 4.3 Structural

More information

Brent Ellmann Structural Option 200 Minuteman Park, Andover, MA Structural Consultant: Dr. Hanagan

Brent Ellmann Structural Option 200 Minuteman Park, Andover, MA Structural Consultant: Dr. Hanagan Brief Building Overview: 200 Minuteman Park stands as a 200,000 square foot Class A office building in Andover, Massachusetts, worth roughly $15,000,000. Although the building has a large square footage,

More information

2015 Proposed Residential Code with Amendments

2015 Proposed Residential Code with Amendments 2015 Proposed with Amendments A resolution of the recommending adoption the 2015 edition of the International, regulating and governing the construction, alteration, movement, enlargement, replacement,

More information

A BILL FOR AN ORDINANCE

A BILL FOR AN ORDINANCE A BILL FOR AN ORDINANCE ORDINANCE NO: 23 SERIES OF 2013 INTRODUCED BY: COUNCILMEMBER ROEMER AN ORDINANCE REPEALING AND REENACTING ARTICLES 2 THROUGH 8 OF CHAPTER 18 OF THE GREENWOOD VILLAGE CODE TO ADOPT

More information

International Building Code/International Residential Code Inspection & Quality Assurance Requirements for Metal Plate Connected Wood Trusses

International Building Code/International Residential Code Inspection & Quality Assurance Requirements for Metal Plate Connected Wood Trusses International Building Code/International Residential Code Inspection & Quality Assurance Requirements for Metal Plate Connected Wood Trusses Released May 7, 2008 Introduction: WTCA has developed this

More information

BOARD OF COUNTY COMMISSIONERS SARPY COUNTY, NEBRASKA

BOARD OF COUNTY COMMISSIONERS SARPY COUNTY, NEBRASKA 2016-449 BOARD OF COUNTY COMMISSIONERS SARPY COUNTY, NEBRASKA RESOLUTION AMENDING THE SARPY COUNTY BUILDING CODE THROUGH THE ADOPTION OF THE FOLLOWING REVISED CODES: THE INTERNATIONAL BUILDING CODE, 2012

More information

Statement of Special Inspections 2013 CBC

Statement of Special Inspections 2013 CBC BUILDIG & SAFET DIVISIO 2729 Prospect Park Drive Rancho Cordova, CA 95670 Phone: (916) 851-8760 Fax: (916) 851-8762 Statement of Special Inspections 2013 CBC PERMIT #: PROJECT ADDRESS: This Statement of

More information

SPECIAL INSPECTION AGREEMENT

SPECIAL INSPECTION AGREEMENT DEVELOPMENT SERVICES DEPARTMENT BUILDING AND SAFETY DIVISION 156 S. BROADWAY, SUITE 130 TURLOCK, CALIFORNIA 95380 PHONE 209-668-5560 FAX 209-668-5107 SPECIAL INSPECTION AGREEMENT PERMIT NUMBER: DATE: OWNER:

More information

9th Edition Residential Volume with MA Amendments - Flood Standards Only DRAFT. 9th Edition Massachusetts Residential Code Requirements in Floodplains

9th Edition Residential Volume with MA Amendments - Flood Standards Only DRAFT. 9th Edition Massachusetts Residential Code Requirements in Floodplains 9th Edition Massachusetts Residential Code Requirements in Floodplains This unofficial document was prepared to serve as a guide for using the flood standards in the Massachusetts Building Code 9th Edition

More information

EFFECTIVE USE OF THE IBC/CBC

EFFECTIVE USE OF THE IBC/CBC Distilling the code review process down to a methodical, sequential list of considerations is generally problematic. In many cases, related provisions from various chapters of the code must be considered

More information

Fill out all sections or mark with N/A (not applicable)

Fill out all sections or mark with N/A (not applicable) TOWN of PLAINVILLE 142 South St Plainville, MA. 02762 508-695-3010 ext#12 / fax # 508-695-1857 Commercial Building Permit BUILDING PERMIT INSTRUCTIONS and APPLICATION Please be advised that any incomplete

More information

CALIFORNIA BUILDING CODE

CALIFORNIA BUILDING CODE FINAL STATEMENT OF REASONS FOR PROPOSED BUILDING STANDARDS OF THE DIVISION OF THE SATATE ARCHTECT REGARDING THE CALIFORNIA BUILDING CODE CALIFORNIA CODE OF REGULATIONS, TITLE 24, PART 2 The Administrative

More information

Danielle Shetler - Structural option Courtyard by Marriott Lancaster, PA

Danielle Shetler - Structural option Courtyard by Marriott Lancaster, PA Structural Analysis Overview: During the structural analysis of the in Lancaster, Pa, a redesign of the lateral and gravity system from masonry bearing and shear walls to a staggered truss system was performed.

More information

ICBO Evaluation Service, Inc Workman Mill Road, Whittier, California

ICBO Evaluation Service, Inc Workman Mill Road, Whittier, California Reissued June 1, 2002 ICBO Evaluation Service, Inc. 5360 Workman Mill Road, Whittier, California 90601 www.icboes.org Filing Category: DESIGN Concrete DURISOL WALL FORMS FOR CONCRETE CONSTRUCTION DURISOL

More information

Structural Observation Program Based on the 2013 California Building Code (CBC) Chapter 17 Published 2013

Structural Observation Program Based on the 2013 California Building Code (CBC) Chapter 17 Published 2013 Structural Observation Program Based on the 2013 California Building Code (CBC) Chapter 17 Published 2013 City of Pismo Beach, Building Division 760 Mattie Road Pismo Beach, CA 93449 (805) 773-7040 Fax:

More information

CBC SECTION/TABLE NUMBER NEW -CHANGE COMMENTARY. X Flexible and Rigid definitions removed and found in ASCE 7-10

CBC SECTION/TABLE NUMBER NEW -CHANGE COMMENTARY. X Flexible and Rigid definitions removed and found in ASCE 7-10 2016 Chapter 16 Structural Design- Changes include new plan content requirements for Photovoltaic Panel Systems as well as guidance on how to determine the dead and live loads. For mid- and high-rise designs

More information

Fill out all sections or mark with N/A (not applicable)

Fill out all sections or mark with N/A (not applicable) TOWN of PLAINVILLE 142 South St Plainville, MA. 02762 508-695-3010 ext#12 / fax # 508-695-1857 Commercial Building Permit BUILDING PERMIT INSTRUCTIONS and APPLICATION Please be advised that any incomplete

More information

Borough of Doylestown Building and Zoning Department

Borough of Doylestown Building and Zoning Department Borough of Doylestown Building and Zoning Department 57 West Court Street, Doylestown, PA 18901 215.345.4140 RESIDENTIAL BUILDING AND ZONING PERMIT APPLICATION PACKAGE BACKGROUND A building permit is required

More information

THE PEOPLE OF THE CITY OF LOS ANGELES DO ORDAIN AS FOLLOWS:

THE PEOPLE OF THE CITY OF LOS ANGELES DO ORDAIN AS FOLLOWS: DRAFT ORDINANCE FIRE SAFETY V3 06-26-2017 An ordinance amending Subsections SEC. 91.703 of Article I of Chapter IX of the Los Angeles Municipal Code to address FIRE SAFETY of residential use structures

More information

Appendix M : Life Safety and Fire Protection Assessment

Appendix M : Life Safety and Fire Protection Assessment Appendix M : Life Safety and Fire Protection Assessment STATE OF WYOMING JOINT LEGISLATIVE AND EXECUTIVE TASK FORCE DEPARTMENT OF ADMINISTRATION & INFORMATION CONSTRUCTION MANAGEMENT WYOMING STATE CAPITOL

More information

2007/2008 ICC CODE DEVELOPMENT CYCLE

2007/2008 ICC CODE DEVELOPMENT CYCLE 2007/2008 ICC CODE DEVELOPMENT CYCLE ERRATA TO THE 2007/2008 FINAL ACTION AGENDA 1 st Posting August 12, 2008 2 nd Posting August 22, 2008 (see page 14) 3 rd Posting August 25 (see page 1) Introductory

More information

Originally Issued: 03/31/2017 Revised: 03/15/2018 Valid Through: 03/31/2018

Originally Issued: 03/31/2017 Revised: 03/15/2018 Valid Through: 03/31/2018 OLDCASTLE ARCHITECTURAL INSULTECH CSI Sections: 04 22 00 Concrete Unit Masonry 04 22 00.13 Concrete Unit Veneer Masonry 1.0 RECOGNITION Oldcastle Architectural Insultech insulated concrete masonry unit

More information

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR THE TESTING AND ANALYSIS OF STEEL SHEET SHEATHING FOR WOOD AND COLD FORMED STEEL LIGHT

More information

0306 SEISMIC LOADS GENERAL

0306 SEISMIC LOADS GENERAL 0306 SEISMIC LOADS 0306.1 GENERAL Every structure, and portion thereof, including nonstructural components such as architectural, mechanical, and electrical components, shall be designed and constructed

More information

05/16/2016 1:36:13 PM

05/16/2016 1:36:13 PM 1223 Mineral Spring Avenue North Providence, RI 02904 STRUCTURAL EXISTING CONDITIONS REPORT Prepared for: Jonathan Levi Architects 266 Beacon Street Boston, Massachusetts, 02116 May 16, 2016Draft WESTPORT,

More information

SPECIAL INSPECTIONS AND TESTS

SPECIAL INSPECTIONS AND TESTS CHAPTER 17 SPECIAL INSPECTIONS AND TESTS SECTION 1701 GENERAL 1701.1 Scope. The provisions of this chapter shall govern the quality, workmanship and requirements for materials covered. Materials of construction

More information

North Shore at Canton Baltimore, MD Beau Menard Technical Report 1

North Shore at Canton Baltimore, MD Beau Menard Technical Report 1 North Shore at Canton Baltimore, MD Beau Menard Technical Report 1 Structural Schneider 10/05/05 Structural Concepts Executive Summary North Shore at Canton is a 4 story town home and parking garage structure

More information

Statement of Special Inspections

Statement of Special Inspections Statement of Special Inspections SUCF Project No: Project Title: Registered Design Professionals in Responsible Charge: (Name) (Address) Architect: Structural Engineer: Mechanical Engineer: Identification

More information

STRUCTURAL OBSERVATION

STRUCTURAL OBSERVATION INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: 91.1702 Effective: 8-15-95 DOCUMENT NO. P/BC 2002-024 Revised: 11-12-02 Previously Issued As: MGD 110 STRUCTURAL OBSERVATION I. INTRODUCTION

More information

International Journal of Advance Engineering and Research Development REVISION OF IS: A REVIEW (PART 2)

International Journal of Advance Engineering and Research Development REVISION OF IS: A REVIEW (PART 2) Scientific Journal of Impact Factor (SJIF): 4.72 International Journal of Advance Engineering and Research Development Volume 5, Issue 01, January -2018 REVISION OF IS: 13920 A REVIEW (PART 2) Dr. Archana

More information

SFR SUBMITTAL REQUIREMENTS

SFR SUBMITTAL REQUIREMENTS A. FEES DUE AT TIME OF PERMIT APPLICATION The following non-refundable fees will be collected at the time of application for all residential projects. 1. Building Plan Check Fee B. CODES The City of Oak

More information

2015 IBC Chapters 1 and 35

2015 IBC Chapters 1 and 35 Study Session 1 2015 IBC Chapters 1 and 35 Administration OBJECTIVE: To obtain an understanding of the administrative provisions of the International Building Code Ò (IBC Ò ), including the scope and purpose

More information

fifteen design for lateral loads Lateral Load Resistance Load Direction Lateral Load Resistance

fifteen design for lateral loads Lateral Load Resistance Load Direction Lateral Load Resistance APPLIED ARCHITECTURAL STRUCTURES: STRUCTURAL ANALYSIS AND SYSTEMS DR. ANNE NICHOLS FALL 2013 lecture fifteen design for lateral loads Lateral Load Resistance stability important for any height basic mechanisms

More information

STRUCTURAL TESTS AND SPECIAL INSPECTIONS

STRUCTURAL TESTS AND SPECIAL INSPECTIONS CHAPTER 17 STRUCTURAL TESTS AND SPECIAL INSPECTIONS SECTION 1701 GENERAL 1701.1 Scope. The provisions of this chapter shall govern the quality, workmanship and requirements for materials covered. Materials

More information

JC Code & Construction Consultants, Inc. Advanced 2010 FBC Update Ch. 1 to 16

JC Code & Construction Consultants, Inc. Advanced 2010 FBC Update Ch. 1 to 16 JC Code & Construction Consultants, Inc. Advanced 2010 FBC Update Ch. 1 to 16 Welcome! This course is designed to provide an overview of the most significant changes to the 2010 edition of the Florida

More information

ICC/NSSA STANDARD FOR THE DESIGN AND CONSTRUCTION OF STORM SHELTERS

ICC/NSSA STANDARD FOR THE DESIGN AND CONSTRUCTION OF STORM SHELTERS ICC/NSSA STANDARD FOR THE DESIGN AND CONSTRUCTION OF STORM SHELTERS ICC 500-2013 edition Public Comment Draft #2 The ICC Consensus Committee on Storm Shelters has held 1 public meetings to develop the

More information

Table 1. Detailed Comparison of Structural Provisions of 2000 IBC to 1997 NEHRP (continued)

Table 1. Detailed Comparison of Structural Provisions of 2000 IBC to 1997 NEHRP (continued) 1997 NEHRP 2000 IBC Section Provision Section Provision Comments 1 GENERAL PROVISIONS 1.1 PURPOSE No corresponding provision The lack of a purpose statement does not make IBC 1.2 SCOPE AND APPLICATION

More information

[TECHNICAL REPORT 3] Lateral System Analysis

[TECHNICAL REPORT 3] Lateral System Analysis Science Center Research Park 3711 Market St. The Pennsylvania State University Department of Architectural Engineering Senior Thesis 2009-2010 Prepared by: November 30, 2009 [TECHNICAL REPORT 3] Lateral

More information

CALIFORNIA BUILDING PLANS EXAMINER CONTENT OUTLINE 01. GENERAL ADMINISTRATION 3 % Project Administration 3%

CALIFORNIA BUILDING PLANS EXAMINER CONTENT OUTLINE 01. GENERAL ADMINISTRATION 3 % Project Administration 3% CALIFORNIA BUILDING PLANS EXAMINER CONTENT OUTLINE EXAM ID: I6 80 multiple-choice questions 3-1/2-hour time limit Open book 01. GENERAL ADMINISTRATION 3 % 0101. Project Administration 3% Verify that plans,

More information