1 Structural Support 1212 Main Street April 15, 2013 Belmar NJ New Jersey Department of Community Affairs Division of Codes and Standards 101 South Broad Street PO Box 802 Trenton NJ Subject: Design & Construction For Flood Loads Within Coastal A Zone Tens of thousands (perhaps more than 100,000) buildings in New Jersey will have to be raised in the next four years to comply with the "substantial damage" rule (NFIP & building code) as well as to reduce NFIP flood insurance premiums which will otherwise increase dramatically. There is currently substantial risk of a major problem developing due to deficient design of support systems for new or modified (raised) existing buildings at locations within Coastal A Zones. DCA should address this issue now, before tens of thousands of buildings are supported on deficient support systems. Based on recent discussions with several architects and builders, it appears that houses recently raised in Coastal A Zones are being supported on plain and reinforced block walls with grossly inadequate design capacity to resist lateral forces from flood water. Definition & Meaning of Coastal A Zones Coastal A Zone is defined on FEMA flood maps as an area, within the more general A Zone, that is adjacent to the V Zone. Coastal A Zone, described as an area with "moderate" wave action, is defined by a light brown color and dashed black line on updated flood maps available online. Unfortunately, use of the term "moderate" tends to reduce concern when the focus should be on the fact that wave action must be considered for design in this zone. During phone discussion on April 12, 2012, staff member with Code Enforcement unit of DCA explained that, within past two weeks, NJDEP has officially adopted new flood maps published by FEMA as of December 12, He explained further that this means new flood maps must be used for building design in New Jersey, whether or not a municipality has passed an ordinance to adopt updated flood maps. However, even if new maps are not used, many building locations are still in Coastal A Zone on prior maps. John F Mann, PE Page 1
2 Lack of Design For Lateral Flood Water Forces Key problem is that many designers are not aware of the very large lateral forces from flood water that must be used for design of buildings within Coastal A Zone. This problem appears to be occurring for the following reasons; 1. Vast majority of architects and engineers in New Jersey have never had to design buildings for lateral forces from flood water. Many (perhaps the majority) are incorrectly using prescriptive provisions of IRC 2009 NJ for design of exterior support walls, not the provisions of ASCE IRC 2009 NJ does not include clear requirements for designers to determine lateral forces from flood water. Even though the general code provision for structural design requires design for such forces, code provisions focused on flood zone conditions tend to make designers think that design for floodwater is not necessary at all. Due to lack of any clear, specific requirements, designers tend to neglect design for flood water forces. Such neglect is somewhat understandable when considering lack of provisions for flood water compared to extensive, detailed provisions for wind and even seismic loads in the building code. 3. Within V-Zone, buildings must be supported only on piles (extending above grade) or columns (usually on grade beams supported on piles). In general, lateral loads from flood water against individual piles or columns are relatively small (typically 500 pounds or less). Therefore, even when (as is very often the case) lateral forces from flood water are not calculated by building designer, there is usually no major design deficiency. Since, except for unusual cases, lateral-force calculations are typically not performed for V-Zone conditions, designers tend to neglect such calculations for Coastal A-Zone conditions. 4. Code provisions for flood vents incorrectly imply that use of flood vents eliminates unbalanced water pressure against walls for all conditions. 5. Code officials are generally not knowledgeable about nature and scale of lateral forces due to wave action compared to other lateral forces. Code officials therefore do not recognize grossly deficient design. Failure to design for lateral force due to flood water and wave-action results in grossly deficient structural design. Significance of this deficiency can be realized by comparing design forces due to flood water for Coastal A Zone to other typical lateral forces, as summarized in example in this report. John F Mann, PE Page 2
3 Building Code Requirements Vast majority of existing buildings that must be raised are single-family houses. Design is governed by the Rehabilitation Subcode of the New Jersey Uniform Construction Code (UCC). Work is considered alterations and reconstruction. For design of new foundation elements for new and existing houses, IRC 2009 NJ is generally the applicable building subcode. IRC 2009 NJ briefly notes [R301.1] the need to design buildings for flood loads. Hovever, IRC 2009 NJ does not include any provisions that specify how loads from flood water are to be determined. IBC 2009 NJ governs design of buildings that do not comply with conditions for use of IRC 2009 NJ. For design to resist flood loads, IBC 2009 NJ [1612.4] specifies use of ASCE Problems With Use of IRC 2009 NJ For Flood Loads Per R , buildings at locations where design wind speed is 100 mph or greater must be designed using one of the alternate "methods" listed. As I have noted in previous letters to DCA, this provision has always been ambiguous since it does not clearly state whether the provision is limited to design for wind only. However, as written, it is most reasonably taken to mean that the alternate method should be used for the entire design, even if that was not intended by code authors. ASCE 7-05 is listed as only one of the alternate methods in R Other than R there is no other code provision that addresses design flood loads for buildings in flood zones. Per R , IRC 2009 NJ directs the designer to Section 322. R322.2 and associated provisions govern design of houses in Coastal A Zone. Foundation design is briefy noted in R , which states only that foundations "shall meet the requirements of Chapter 4". Yet, per R401.1, Chapter 4 just refers back to "Section R322", forming an interminable loop of instructions seemingly designed to maximize frustration. If R does in fact mean that entire design of buildings subject to design wind speed of 100 mph or greater must be performed using an alternate method, then the confusion of R and Chapter 4 can be at least partially resolved within current code provisions. John F Mann, PE Page 3
4 However, if R is considered to be limited to design for wind resistance, a major problem exists with code requirements relative to design for flood water loads. The only provision that hints of loads from flood water is R which requires that design must consider "structural loads and stresses from flooding equal to the design flood elevation." However, provisons for flood vents per R confuse this issue since designers tend to think (incorrectly) that flood vents equalize pressure from flood water on both sides of a wall, negating any necessity to consider lateral loads from flood water. Unfortunately, flood vents do not negate very large lateral forces from wave action that must be considered for proper design. R starts with the following statement (with underline made for this discussion); "When a building of otherwise conventional construction contains structural elements exceeding the limits of Section R301 or otherwise not conforming to this code, these elements shall be designed in accordance with accepted engineering practice." R301.1 states the following; "Buildings and structures, and all parts thereof, shall be constructed to safely support all loads, including dead loads, live loads, roof loads, flood loads, snow loads, wind loads and seismic loads as prescribed by this code." Since flood loads are not defined in IRC 2009 NJ (unless R is considered applicable for entire design) the most reasonable conclusion is that; (1) Structural elements required to resist flood loads must be considered "not conforming to this code" per R , and (2) Such element must be designed per "accepted engineering practice". R also states that "engineered design" may be performed by using the "International Building Code", which is IBC 2009 NJ. John F Mann, PE Page 4
5 Flood Water Design Forces per ASCE 7-05 Chapter 5 of ASCE 7-05 includes detailed provisions for determining design forces due to flood water, including wave action. Complete discussion of the provisions of Chapter 5 is outside the scope of this report. However, when wave action is considered, the following key points should be understood; 1. Total lateral force is the sum of hydrostatic force and dynamic force from wave action. Dynamic force from wave action is generally greater than hydrostatic force. 2. BFE includes water from "incident" waves. In the absence of waves, height of flood water ("stillwater") is much lower than BFE. 3. Use of flood vents to equalize water level on opposite sides of wall reduces total inward lateral water pressure by a very small (essentially insignificant) amount. Flood vents only allow water to rise to the "stillwater" elevation, which does not include waves. 4. For design [per Equation (5-3), Figure 5-1 and Figure 5-2], top of water pressure against wall (for hydrostatic and dynamic force) is taken as 1.43 times the difference between base flood elevation (BFE) and grade (ground surface) adjacent to the wall. Top of water pressure for design is generally higher than BFE. The code allows for consideration of wave direction, which may be considered along a line perpendicular to shoreline of the body of water that is the source of flood water. Only those walls impacted directly by waves must be designed to resist specified flood loads. Loads may also be reduced by considering skew angle of wave direction relative to plane of wall. However, conservative approach should be taken when considering wave direction, especially when shoreline geometry is not clearly or easily defined. John F Mann, PE Page 5
6 FEMA Techinal Bulletin 9 The following is from discussion of wave forces in FEMA publication about breakaway walls; "The effect is quite different when a breaking wave hits a wider, relatively continuous, vertical surface, such as a wall. When the crest of a breaking wave impacts a wall, a pocket of air is trapped and compressed by the wave (see Figure 2). As the air pocket collapses, an exceedingly high-pressure burst (i.e., shock wave) impacts the wall, with the force centered around the stillwater level. Peak pressures from a 5-foot breaking wave can be 100 times higher than the safe loading resistance of 10 to 20 psf that is specified for breakaway walls in the NFIP regulations." FEMA P-55 Coastal Construction Manual In the Coastal Construction Manual, FEMA includes the following; "As explained in Chapters 1 and 3 of this Manual, the NFIP regulations do not differentiate between the Coastal A Zone and the portion of Zone A that is landward of the LiMWA. Because Coastal A Zones may be subject to the types of hazards present in Zone V, such as wave effects, velocity flows, erosion, scour, and high winds, this Manual recommends that buildings in Coastal A Zones meet the NFIP regulatory requirements for Zone V buildings (i.e., the performance requirements concerning resistance to flotation, collapse, and lateral movement and the prescriptive requirements concerning elevation, foundation type, engineering certification of design and construction, enclosures below the lowest floor, and use of structural fill see Section )." "LiMWA" is abbreviation for "Limit of Moderate Wave Action". Although this FEMA recommendation is not mandatory, it does highlight the importance of considering forces from wave action in the Coastal A Zone. John F Mann, PE Page 6
7 Example of Flood Water Design Load; Crawlspace Summary results for example with exterior walls around crawlspace, from actual house within Coastal A Zone, illustrates the problem; Top of support wall 11.0 feet BFE 10.0 feet Grade 6.0 feet *** Top of water pressure feet Total hydrostatic force Total dynamic force Total lateral force 1,021 PLF (along length of wall) 1,300 PLF 2,321 PLF *** Per provisions of ASCE 7-05 Even for this relatively low wall (5 feet above grade), total lateral force is very large relative to capacity of "conventional" construction intended by IRC 2009 NJ. With top of water pressure about 9 inches above top of wall, total lateral force against foundation wall is 2,273 PLF. Lateral resistance required along top of wall (1,053 PLF) is much greater than shear capacity of standard nailed connections for wood-framed construction and even greater than shear capacity provided by enhanced methods such as light-gage steel connectors. Structural steel angle with two 1/2-inch bolts through joist would be required for each floor joist. Steel angle would also have to be connected to foundation wall with bolts. Comparison of design flood water force (per ASCE 7-05) to other lateral forces (for same 5- feet height of wall above grade) highlights the very large difference between flood water force and other forces typically encountered by designers; Condition Hydrosatic; Water at top of wall Backfill; Soil at top of wall (120 pcf; Ke = 0.33) Wind at 25 psf Lateral Force 780 PLF 525 PLF 125 PLF John F Mann, PE Page 7
8 Flood Water Forces For High Walls For many houses, lower-level space will be used as a garage, such that height of walls supporting the lifted house will be 8 feet or more. For height of wall 8.0 feet above grade, and BFE 1.0 foot below top of wall, total lateral force from flood water is 6,685 PLF (against wall). Only a thick reinforced concrete wall could resist such large lateral force. Even then, unless the wall was designed as cantilever retaining wall with large base, there would be no practical way to provide required lateral resistance (3,262 PLF) along top of wall without concrete floor slab or structural steel framing. Incorrect Information Published by State Agencies The following (from NJDEP web site) is an example of incorrect and misleading information being published by state agencies; "Wet flood-proofing refers to measures that allow floodwaters to enter a building, and thereby balance hydrostatic pressure on the structure during a flood. A non-residential building that cannot feasibly be dry flood-proofed can be wet flood-proofed. Wet flood-proofing generally includes using flood-resistant materials, protecting mechanical and utility equipment, and using openings or breakaway walls. A garage or crawl space with flood vents is an example of a wet flood-proofed area. Note: although wet flood-proofing is allowable in limited circumstances, it may have significant ramifications on flood insurance costs." This statement is misleading (at best) since it does not directly address wave action in Coastal A Zone. The mere noting of "breakaway walls" is not sufficient, especially when the incorrect claim is made that flood vents for "garage or crawl space" is adequate. As previously discussed in this report, flood vents do not equalize very large lateral pressure from wave action. John F Mann, PE Page 8
9 Recommendations After investigation of as-built and planned construction within Coastal A Zone areas as may be warranted, DCA should take the following actions as soon as feasible; Issue letter to construction officials and building subcode officials emphasizing the importance of plan review, focusing on need for designers to use ASCE 7-05 for design of elements to resist flood water. Highight this issue in Construction Code Communicator. Issue letters to New Jersey Board of Architects and New Jersey Builders Association, highlighting need for careful design if exterior walls are to be used for support of house within Coastal A Zone. Emphasize that an architect should obtain advice from qualified professional engineer if the architect is not qualified to perform structural design of such elements, especially when such exterior walls are more than 3 feet above grade. Consider modifications to NJ version of current and future model building code, specifically addressing flood water design loads. Copies; New Jersey Board of Architects New Jersey Board of Professional Engineers & Land Surveyors New Jersey Builders Association John F Mann, PE Page 9
Showing Only Sections Changed 6 th Edition FBC (2017) from 5 th Edition FBC (2015) [changes shown with underline and strike-through]
Showing Only Sections Changed 6 th Edition FBC (2017) from 5 th Edition FBC (2015) [changes shown with underline and strike-through] This publication reproduces excerpts from the Florida Building Code,
More informationFloodplain Determination
Field Inspections Floodplain Determination Posted Permit and Signoff Card Permit Types of Flood Proofing Elevation of grade Flood walls and Levees Dry Flood Proofing Wet Flood Proofing FEMA NFIP Regulation;
More informationN.J.A.C. 5:23-2. Administrative and Enforcement Provisions
This document contains excerpts of the flood provisions from the 2015 editions of the New Jersey Uniform Construction Code: Administrative Provisions (N.J.A.C. 5:23-2.14), Building Subcode (N.J.A.C. 5:23-3.14),
More informationR CODE CHANGE PROPOSAL FORM (See instructions on page 2)
CODE CHANGE PROPOSAL FORM (See instructions on page 2) Code: IRC 12/13 Sections 301.2.2.2.1 Proponent: Charles S. Bajnai, Chesterfield County, VA, ICC Building Code Action Committee 1. Delete as shown
More informationThe following are details of the code requirements of the 2015 International Residential Code for single-story decks.
The following are details of the code requirements of the 2015 International Residential Code for single-story decks. The 2015 International Residential Code Section R507 contains additional information
More informationSTRUCTURAL ISSUES IN RESIDENTIAL CONSTRUCTION. Presented by: Susan L. Lasecki P.E., S.E.
STRUCTURAL ISSUES IN RESIDENTIAL CONSTRUCTION Presented by: Susan L. Lasecki P.E., S.E. Presentation Outline Gravity Design Load Paths from Roof to Foundation Roof Framing Floor Framing Wall Framing Lateral
More information2. Does not require, involve or include any additions to, or repair or modification of, the existing foundation.
SECTION 3109 STRUCTURES SEAWARD OF A COASTAL CONSTRUCTION CONTROL LINE 3109.1 General. The provisions of this section shall apply to the design and construction of habitable structures, and substantial
More informationFoundations in Coastal Areas
Foundations in Coastal Areas HOME BUILDER S GUIDE TO COASTAL CONSTRUCTION FEMA 499/August 2005 Technical Fact Sheet No. 11 Purpose: To describe foundation types suitable for coastal environments. Key Issues
More information5.0 Elevating Your Home
5.0 Elevating Your Home One of the most common retrofitting methods for homes is elevation. When a home is properly elevated, the living area should be above most flood levels. Several elevation techniques
More informationCity of Republic Community Development Girder and Header Spans for Exterior Walls
City of Republic Community Development Girder and Header Spans for Exterior Walls Revision Date: January 2017 2012 IRC Table R502.5(1) Girder Spans a and Header Spans a for Exterior Bearing Walls (Maximum
More informationBROCHURE # 108 CONSTRUCTION PLAN COMPONENTS
BROCHURE # 108 CONSTRUCTION PLAN COMPONENTS Please note: This construction plan component list is to be used as a guide to assist you with your project. There may be elements unique to your project not
More informationCity of Bemidji Building Office City Hall 317 4th Street NW Bemidji, Minnesota Phone Fax emi mn s
City of Bemidji Building Office City Hall 317 4th Street NW Bemidji, Minnesota 56601-3116 Phone 218-759-3573 Fax 218-759-3590 emi mn s Residential Header and Girder Spans Requirements 2015 MSBC Chapter
More informationFLOOD HAZARD MANAGEMENT SPECIFIC PLAN GUIDELINES (Code Sections: L.A. Ordinance 172,081; LAMC Appendix Chapter 34)
INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: See Below Effective: 10-09-80 DOCUMENT NO. P/BC 2002-064 Revised: 03-07-03 Previously Issued As: MGD 63 FLOOD HAZARD MANAGEMENT SPECIFIC PLAN
More informationSee the IRC for additional information. See CPD-DS Information Bulletin 100 for Requirements for 1 & 2 Family Dwelling plan submittals.
As a customer service initiative, the Kansas City, Missouri, City Planning and Development Department/Development Services, in cooperation with the Greater Kansas City Home Builders Association, has developed
More informationIn preparation for constructing buildings on a property, the builder. Site Preparation CHAPTER
CHAPTER 3 Site Preparation In preparation for constructing buildings on a property, the builder must consider a number of factors related to code requirements. The buildings must be located according to
More informationLoads and Load Paths. "Architecture is inhabited sculpture." -Constantin Brancusi
Loads and Load Paths "Architecture is inhabited sculpture." -Constantin Brancusi Loads and Load Paths Structural Design Design Loads Dead Load Live Load Snow Load Lateral Loads Load Types Load Combinations
More informationResidential Wood Deck Design
Residential Wood Deck Design EARN 0.1 ICC Continuing Education Unit (CEU) and/or AIA/CES HSW 1 Learning Unit (LU) BCD303-A Residential Wood Deck Design Description: Deck and balcony collapses injure occupants
More informationINTERNATIONAL BUILDING CODE - ADOPTION AND AMENDMENTS Effective July 1, 2004
CITY OF MERCER ISLAND 9611 SE 36 th Street, Mercer Island, Washington 98040-3732 PHONE (206) 236-5300 FAX (206) 236-3645 TDD (206) 232-9598 www.ci.mercer-island.wa.us INTERNATIONAL BUILDING CODE - ADOPTION
More information90% Design Submittal Structural Calculations Parking Garage CDRL
NORTH METRO RAIL LINE PROJECT Thornton Crossroads at 104 th Avenue Station 90% Design Submittal Structural Calculations Parking Garage CDRL 03-037.11.06 June 2, 2017 Prepared by: Regional Rail Partners
More informationStructural Redesign Gravity System
Redesign Gravity System Design Considerations A composite floor system was used for this design to maximize the efficiency of the material being used. This type of system requires less material and provides
More informationFEMA P-593 STEP-BY STEP PRESCRIPTIVE RETROFIT FOR CRIPPLE WALL BRACING & ANCHORAGE TO FOUNDATION
INTRODUCTION Objective of provisions: The provisions of IEBC Appendix Chapter A3 are intended to reduce hazard of earthquake-induced damage (IEBC A301.1). These provisions are not intended to eliminate
More informationDetails for Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses
Details for Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses Released May 20, 2009 Updated March 9, 2011 Introduction: Wood frame structures with attached brick masonry veneer
More information111 MORGAN ST. Ryan Friis
Technical Report No. 1 September 30, 2002 Executive Summary: 111 Morgan St. is a 9 story cast-in-place concrete condominium building being constructed in Chicago, Illinois. The building s floor system
More informationSnow load design using the 2003 International Building Code
Snow load design using the 2003 International Building Code By John R. Henry, P.E. Early model building codes transcribed design provisions from various sources and standards. More recent editions of the
More informationWhat is Conventional Construction?
What is Conventional Construction? Copyright This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation without written permission
More informationStructural System. Design Criteria Fire Resistance Concrete designed for 2 HR rating (worst case) Geotechnical Report Allowable Bearing Capacity
System Codes and Criteria Design Codes and Standards The design code used is the Wisconsin Administrative Code along with the State of Wisconsin Department of Commerce-Safety & Buildings Chapters Comm
More informationREINFORCING TABLES INSTALLATION MANUAL
REINFORCING TABLES 201 REINFORCING TABLES Design Limitations Introduction The structural wall reinforcing and lintel design tables contained within the Appendix of NUDURA s Installation Manual have been
More informationU.S. General Services Administration Progressive Collapse Design Guidelines Applied to Concrete Moment-Resisting Frame Buildings
2004 ASCE Structures Congress Nashville, Tennessee May 18-22, 2004 U.S. General Services Administration Progressive Collapse Design Guidelines Applied to Concrete Moment-Resisting Frame Buildings By David
More informationAdministrative Changes
Revised 11/29/06 Knox County Residential Building Codes Significant Changes From The 1995 CABO One And Two Family Dwelling Code To The 2006 International Residential Code All one and two family dwellings
More informationChapter 2 EARTHQUAKE-RESISTANCE REQUIREMENTS
Chapter 2 EARTHQUAKE-RESISTANCE REQUIREMENTS This chapter explains the International Residential Code s (IRC s) general earthquake-resistance requirements as well as specific IRC requirements concerning
More informationORDINANCE. APPROVED EMERGENCY: (Yes) (No) VETOED: Date
ORDINANCE AN ORDINANCE OF THE COMMISSION OF KNOX COUNTY, TENNESSEE RESCINDING ARTICLE III. CABO ONE- AND TWO-FAMILY DWELLING CODE, SEC. 10-56, SEC. 10-57 AND SEC. 10-58 AND ADOPTING THE 2006 INTERNATIONAL
More information4.6 Procedures for Connections
4.6 Procedures for Connections This section provides Tier 2 evaluation procedures that apply to structural connections: anchorage for normal forces, shear transfer, vertical components, interconnection
More informationBUILDING CODES Presented by CORUM ENGINEERING
BUILDING CODES Presented by CORUM ENGINEERING AGENDA I. The Basics of Foundations A. Footer Designs B. Foundation Walls 1. Non-Backfilled Walls 2. Backfilled Walls (Retaining Walls) C. Slabs vs. Crawl
More informationWall bracing panel requirements
Wall bracing panel requirements Building Inspections Exterior and interior walls must be braced in accordance with Minnesota State Building Code section R602 to resist wind loads and racking. Locations,
More informationBUILDING CODES & DESIGN CRITERIA
BUILDING CODES & DESIGN CRITERIA Adopted Building Codes: 2006 International Building Code (IBC) 2006 International Residential Code (IRC) 2006 International Mechanical Code (IMC) 2006 International Plumbing
More informationAnchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi
STRUCTURAL NOTES MATERIAL STRENGTHS Structural Steel Reinforcing Steel Concrete Masonry Structural Lumber Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel
More informationBUILDING A STRUCTURE IN THE FLOODPLAIN. IMPORTANT REQUIREMENTS Of Warren County Floodplain Management Ordinance
BUILDING A STRUCTURE IN THE FLOODPLAIN When you apply for a zoning permit to build a home or other structure and it is determined your land is in the floodplain, the following procedures will apply: 1.
More informationMinimum Requirements For One & Two Family Structures FBC 6 th Edition (2017)
Pinellas County Building Department Reviewed : Date: Phone: Owner s Name: Permit Number: CB_ - Property Address: Contractor: Phone: Minimum Requirements For One & Two Family Structures FBC 6 th Edition
More informationPOST AND FRAME STRUCTURES (Pole Barns)
POST AND FRAME STRUCTURES (Pole Barns) Post and frame structures. The following requirements serve as minimum standards for post and frame structures within all of the following structural limitations:
More informationR Code and Commentary for 2012 NC Residential Code final 03/06/13
R602.10 Code and Commentary for 2012 NC Residential Code final 03/06/13 Commentary italicized and printed in red 1. Section R602.10 -- provides charging language for two simplified bracing approaches (isolated
More informationFoundation/Site Work Code Requirements
Q: What is a Foundation Only permit and why did I receive one when I filed for a full Building Permit? All Building Permits for new construction and additions are reviewed for zoning compliance. This review
More informationACCESSORY STRUCTURE Building permit information For 1 & 2-family dwellings
ACCESSORY STRUCTURE Building permit information For 1 & 2-family dwellings Building Safety Department 400-2 nd Street South St. Cloud, MN 56301 (320) 255-7239 A building permit is required for any accessory
More informationChapter 1: Application and Administration
Chapter 1: Application and Administration General Comments This chapter provides provisions regarding the purpose, scope, application, and administration of subsequent requirements of ICC 500. In addition
More informationHILLSBOROUGH TOWNSHIP CODE ENFORCEMENT
HILLSBOROUGH TOWNSHIP CODE ENFORCEMENT SAMPLE GUIDE FOR RESIDENTIAL DECKS revised 7 16 Call before you dig! 1 800 272 1000 New Jersey One Call. Utility Mark Out. THIS GENERIC GUIDE IS NOT ALL INCLUSIVE
More informationPlan Check No. Checked by: An Appointment Is Required for Verification
SUPPLEMENTAL CORRECTION SHEET UNREINFORCED MASONRY (URM) RETROFIT ( 2002 LABC ) Plan Check No. Checked by: Permit Appl. # An Appointment Is Required for Verification Job Address: For appt. call: APPLICATION
More informationSection 17 Flood Hazard Zone
January 1, 2018 TOWN OF CLINTON 1701 Section 17 Flood Hazard Zone 17.1 Statutory Authorization, Findings of Fact, Purpose and Objective: 17.1.1 Statutory Authorization: The Legislature of the State of
More informationGreg Wilson FEMA Building Science Rebecca Quinn, CFM RCQuinn Consulting, Inc.
Overview of Training Flood Provisions of the 2012 International Residential Code Greg Wilson FEMA Building Science Gregory.Wilson2@fema.dhs.gov Rebecca Quinn, CFM RCQuinn Consulting, Inc. rcquinn@earthlink.net
More informationTOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION Ext. 395 Needed to Obtain Permit:
TOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION 355-7575 Ext. 395 Needed to Obtain Permit: 1. Building Permit Application, and/or residential plumbing permit application, as applicable, to be
More informationPOST FRAME BUILDING STANDARDS
CASS COUNTY, MISSOURI BUILDING CODES, ENVIRONMENTAL HEALTH AND ZONING DEPARTMENT 30508 S. West Outer Road, Harrisonville, MO 64701 P- (816) 380-8134 F- (816) 380-8130 POST FRAME BUILDING STANDARDS 201.3
More informationELEVATION CERTIFICATE
NATIONAL FLOOD INSURANCE PROGRAM ELEVATION CERTIFICATE AND INSTRUCTIONS NATIONAL FLOOD INSURANCE PROGRAM ELEVATION CERTIFICATE PAPERWORK REDUCTION ACT NOTICE Public reporting burden for the Elevation Certificate
More informationSTATE UNIVERSITY CONSTRUCTION FUND. UNIVERSITY CON DIRECTIVE 5-1 Issue date: October 2014
STATE STRUCTION FUND DIRECTIVE 5-1 Issue date: October 2014 STRUCTURAL STEEL 1. General: It is the Fund's policy that the design of the structural steel is the prime responsibility of the project's Structural
More informationAPPENDIX 6 (not yet reviewed by UCCS) STRUCTURAL ANALYSIS/VIBRATION CRITERIA
APPENDIX 6 (not yet reviewed by UCCS) STRUCTURAL ANALYSIS/VIBRATION CRITERIA GENERAL The purpose of this standard is to identify structural submittal requirements, as well as identify vibration design
More informationStructural Technical Report 1 Structural Concepts / Structural Existing Conditions Report
Michael A. Troxell Structural Option Advisor: Professor Parfitt College of Business Administration Oct. 5, 2005 Structural Technical Report 1 Structural Concepts / Structural Existing Conditions Report
More informationSTAFF REPORT SAUSALITO CITY COUNCIL
STAFF REPORT SAUSALITO CITY COUNCIL MEETING DATE: June 14, 2016 AGENDA TITLE: Approving a Variance from the Elevation Requirements of the Floodplain Management Section of the Sausalito Building Code for
More informationRESIDENTIAL CONSTRUCTION New Dwellings and Additions
How to Obtain a Building Permit For RESIDENTIAL CONSTRUCTION New Dwellings and Additions MIAMI COUNTY, KANSAS CODE SERVICES DEPARTMENT 201 South Pearl Street, Suite 201 Paola, Kansas 66071-1777 Phone:
More informationHeel Blocking Requirements and Capacity Analysis. Overview Revised 3/22/2017
Heel Blocking Requirements and Capacity Analysis Overview Revised 3/22/2017 SBCA has been the voice of the structural building components industry since 1983, providing educational programs and technical
More informationCase Study: Failure at an Abutting Lower Roof due to Snowdrift
Case Study: Failure at an Abutting Lower Roof due to Snowdrift Jed B. Larsen, M.E., A.M.ASCE 1 Marco A. DeLeon, M.E., P.E., M.ASCE 2 Deepak Ahuja, M.S., P.E., M.ASCE 3 1 Nelson Architectural Engineers,
More informationPrescriptive Design for Pole Barns Using the Larimer County Prescriptive Handout
Prescriptive Design for Pole Barns Using the Larimer County Prescriptive Handout Building Department 200 W. Oak Street 3 rd Floor Fort Collins, CO 80521 970-498-7700 DEFINITIONS High Wind Areas Those areas
More informationGARAGES/ONE-STORY City of Grand Rapids Building Safety Division
GARAGES/ONE-STORY City of Grand Rapids Building Safety Division 218-326-7601 www.cityofgrandrapidsmn.com This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building
More information2012 Wood Frame Construction Manual: Wind Load Distribution on Buildings Load Paths
2012 Wood Frame Construction Manual: Wind Load Distribution on Buildings Load Paths Presented by: William L. Coulbourne, PE Copyright Materials This presentation is protected by US and International Copyright
More informationWhy Decks Fail Design and New PA UCC Requirements to Improve Safety
May 10, 2016 1:00pm Why Decks Fail Design and New PA UCC Requirements to Improve Safety Chris Hine Housing and Land Development Specialist Provider #60114115 AIA Course #PHRCWEB516 Pennsylvania Housing
More informationA/E REVIEW CHECKLIST STRUCTURAL
A/E REVIEW CHECKLIST STRUCTURAL Reviewers should - Use Checklists when reviewing any type of VA construction project for the following disciplines: Site and Landscape, Architectural, Structural, Plumbing,
More informationTechnical Assignment 1 10/8/03
Executive Summary Technical Assignment 1 10/8/03 The is 55 story high-rise condominium being built off the northern Miami coast. The structural design presented in this building is a direct result of its
More informationHansen Pole Buildings Planning Guide. Toll Free / Toll Free FAX
Hansen Pole Buildings Planning Guide Toll Free 866-200-9657 / Toll Free FAX 866-200-9658 While we strive to earn your business, whether you purchase from us or not, we would hope you would utilize this
More informationPOST AND FRAME STRUCTURES (Pole Barns)
POST AND FRAME STRUCTURES (Pole Barns) Post and frame structures. The following requirements serve as minimum standards for post and frame structures within all of the following structural limitations:
More informationLINCOLN COUNTY REQUIRED INSPECTIONS (Last updated August 23, 2017)
LINCOLN COUNTY REQUIRED INSPECTIONS (Last updated August 23, 2017) It is the responsibility of the permit applicant to notify the building inspector when the work is ready for inspection. To request an
More informationOrdinance No July 1, 2016
(Insert Facing Page 3 IRC) 2.02.540 Amendment to IRC Section R105.2 Work Exempt From Permit, Building and Electrical Sections. The following additional exception shall be added to R105.2 Building: Building:
More informationWhat is Floodproofing?
Floodproofing Info #1 What is Floodproofing? Managing Flood Risk is Your Responsibility Many existing buildings located near rivers, streams, and lakes (and some located a surprising distance away) have
More informationCOMMUNICATION TOWER CODE COMPLIANCE CHECKLIST
GWINNETT COUNTY BUILDING PLAN REVIEW Department of Planning & Development One Justice Square 446 West Crogan Street Lawrenceville, Georgia 30046 www.gwinnettcounty.com Architectural Structural Mechanical/Plumbing
More informationTable of Contents.2. Introduction...3 Gravity Loading and Deflections..4. Existing Structural System..8
WISCONSIN PLACE RESIDENTIAL TECHNICAL ASSIGNMENT 2 OCTOBER 29, 2007 KURT KRASAVAGE THE PENNSYLVANIA STATE UNIVERSITY STRUCTURAL OPTION FACULTY ADVISOR: DR. ALI MEMARI 1 Table of Contents Table of Contents.2
More informationSuspended Metal lath and Cement Plaster. Coverings Rigid Insulation, 1/2 - in 0.75 psf. Floor Fill Lightweight Concrete, per inch 8 psf
Dead Loads Ceiling Suspended Metal lath and Cement Plaster 15 psf Coverings Rigid Insulation, 1/2 - in 0.75 psf Floor Fill Lightweight Concrete, per inch 8 psf Floor Finish Frame Partitions Ceramic or
More informationSupplemental Concrete Tilt Up Retrofit Plan Check Correction Sheet (2014 LABC)
Supplemental Concrete Tilt Up Retrofit Plan Check Correction Sheet (2014 LABC) Plan Check Submittal Date: Plan Check / PCIS App #: Job Address: Applicant: P.C. Engineer: (Print first / last name) Phone:
More informationBUILDING BULLETIN One and Two Family Dwellings Decks and Residential Access Ramps
BUILDING BULLETIN One and Two Family Dwellings Decks and Residential Access Ramps City of Virginia Beach Building Permits & Inspections Updated 4/30/09 Table of Contents I. Introduction... 1 II. Tips
More informationPRESENTATION OUTLINE MUBEC & IRC APPLICABILITY & ADMIN. 6/17/2015 RESIDENTIAL STRUCTURAL SYSTEMS. Carmen B. Bombeke, P.E.
MUBEC & IRC APPLICABILITY & ADMINISTRATION RESIDENTIAL STRUCTURAL SYSTEMS Carmen B. Bombeke, P.E. IRC FLOORS QUESTIONS & ANSWERS PRESENTATION OUTLINE Maine Uniform Building & Energy Code (MUBEC) IRC 2009
More informationCommercial Remodel Permit
Commercial Remodel Permit Zoning requirements Staff recommends always verifying the zoning requirements for your project before deciding to build. Warrensburg has eleven separate zoning districts, each
More informationPatio Cover Manufacturers and other Interested Parties
To: From: Patio Cover Manufacturers and other Interested Parties ICC-ES Date: February 6, 2009 Subject: Technical Review of Patio Cover Engineering Analysis in Accordance for Patio Covers (AC340) MEMO
More informationSJI Updates Expanded Load Tables for Noncomposite Joists / Joist Girders and Development of New Composite Joist Series
SJI Updates Expanded Load Tables for Noncomposite Joists / Joist Girders and Development of New Composite Joist Series SUMMARY David Samuelson Steel joists are growing in recognition as being a very economical
More informationREQUIREMENTS FOR SUBSTANTIALLY DAMAGED AND SUBSTANTIALLY IMPROVED STRUCTURES
REQUIREMENTS FOR SUBSTANTIALLY DAMAGED AND SUBSTANTIALLY IMPROVED STRUCTURES If your home or business incurred damage, the engineering department, in conjunction with the Flood Mitigation Officer, will
More informationCHAPTER 3 BUILDINGS WITH WOOD FRAMED EXTERIOR WALLS 301 SCOPE
CHAPTER 3 BUILDINGS WITH WOOD FRAMED EXTERIOR WALLS WOOD CHAPTER 3 301 SCOPE This chapter prescribes construction requirements for buildings where all exterior walls above the foundation are wood framed
More informationTOWN OF SOUTH KINGSTOWN REQUIREMENTS FOR BUILDING PERMITS RESIDENTIAL SINGLE FAMILY
TOWN OF SOUTH KINGSTOWN REQUIREMENTS FOR BUILDING PERMITS RESIDENTIAL SINGLE FAMILY ACCESSORY STRUCTURES (Barn, Garage, Shed) ********************************* BUILDING PERMIT APPLICATIONS FOR ACCESSORY
More informationLPI 56 Technical Guide
LPI 56 Technical Guide Floor & Roof Applications Product Specifications & Design Values 2 Floor Tables 3 Uniform Floor Load (PLF) Tables: Simple s 4 Uniform Floor Load (PLF) Tables: Continuous s 5 Uniform
More informationDIVISION: METALS SECTION: STEEL DECKING REPORT HOLDER: EPIC METALS CORPORATION 11 TALBOT AVENUE RANKIN, PENNSYLVANIA 15104
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2047 Reissued 07/207 This report is subject to renewal 07/209. DIVISION: 05 00 00
More informationCity Planning & Development - Development Services (CPD-DS) 414 E. 12th Street 5 th Floor Kansas City, Missouri Telephone (816)
The purpose of this document is to advise you of the information needed to properly evaluate a permit application for your residential project. Please submit your completed permit application at the following
More informationStructural Requirements
Structural (for the design Engineer of Record) Presented by: Lindsay Anderson Consultant Structural Plan Examiner and Dixit Patel Structural Plan Examiner 1 Overview 1. Department Clarification Memorandums
More informationDESIGN CALCULATIONS INSTA-FOOTING LOAD BEARING CAPACITIES ON CONCRETE SLAB. January 14, 2017 Rev -
DESIGN CALCULATIONS INSTA-FOOTING LOAD BEARING CAPACITIES ON CONCRETE SLAB January 14, 2017 Rev - Projection Name: Owner: Prepared by: Insta-Footing Design Calculations Insta-footing, LLC Richard Nolan,
More informationINFORMATIONAL PACKAGE ACCESSORY RESIDENTIAL BUILDINGS (INCLUDING DETACHED GARAGES, STORAGE BUILDINGS & WORKSHOPS)
1102 4 th Street Telephone: 306-634-1819 Estevan, Saskatchewan, Canada Fax: 306-636-2199 S4A 0W7 INFORMATIONAL PACKAGE ACCESSORY RESIDENTIAL BUILDINGS (INCLUDING DETACHED GARAGES, STORAGE BUILDINGS & WORKSHOPS)
More informationStructural Engineering
Structural Engineering 4 4.0 TABLE OF CONTENTS 4.1 General Approach 115 Submission Requirements 4.2 Codes and Standards 116 Structural Design of New Buildings 116 Use of Recycled Materials 4.3 Structural
More informationAdd Flood Provisions to the 2010 FBC, Building
Add Flood Provisions to the 2010 FBC, Building (Adopted Unanimously by the Workgroup May 29, 2009) Proposal to modify section added/modified in FBC 102.7 Relocation of manufactured buildings. 1. Relocation
More informationLATERAL LOADS ON BRICK VENEER RESIDENTIAL STRUCTURES
LATERAL LOADS ON BRICK VENEER RESIDENTIAL STRUCTURES W. Mark McGinley 1, PhD, PE and Eric N. Johnson 2, PE ABSTRACT In North American residential construction, brick veneer is typically used as a cladding
More informationDIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER:
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 4 6587 (562) 699 0543 www.icc es.org ESR 3152 Reissued 08/2017 This report is subject to renewal 08/2018. DIVISION: 07 00 00
More informationDETAIL DRAWINGS. RASTRA is a stay-in-place insulated concrete. form that is structurally strong, energy-efficient,
DETAIL DRAWINGS RASTRA is a stay-in-place insulated concrete form that is structurally strong, energy-efficient, soundproof, resistant to fire, high wind, mold and rodents and is made from 85% recycled
More informationOrdinance No Lot Surface Drainage
Ordinance No. 35-2008 - Lot Surface Drainage The Township has adopted a new Lot Surface Drainage Ordinance which amends Chapter 170, Article IX, Subdivision and Site Plan Review by adding a new Section
More informationProject Address: Name of Person Completing Form:
Statement of Inspections This form is provided as a way to list aspects of the project that require special inspection and testing in accordance with IBC Sections 107.1, 1704, and 1705 and define duties
More informationPRESCRIPTIVE COMPLIANCE METHOD
CHAPTER 3 PRESCRIPTIVE COMPLIANCE METHOD [B] SECTION 301 GENERAL 301.1 Scope. The provisions of this chapter shall control the alteration, repair, addition and change of occupancy of existing structures,
More informationTHE FORENSIC MEDICAL CENTER
THE FORENSIC MEDICAL CENTER Image courtesy of Gaudreau, Inc. TECHNICAL REPORT #1 OCTOBER 5, 2007 KEENAN YOHE STRUCTURAL OPTION DR. MEMARI FACULTY ADVISOR EXECUTIVE SUMMARY Image courtesy of Gaudreau, Inc.
More informationPart III Building Planning and Construction BUILDING PLANNING CHAPTER 3
Part III Building Planning and Construction CHPTER 3 BUIDING PNNING SECTION R300 SITE DRINGE R300.1 Storm water drainage and retention during construction. Projects which disturb less than one acre of
More informationRB213-06/07 Table R
RB213-06/07 Table R602.10.5 Proposed Change as Submitted: Proponent: Scott Beard, SE, City of Tacoma, WA Revise as follows: TABLE R602.10.5 a, b, c LENGTH REQUIREMENTS FOR BRACED WALL PANELS IN A CONTINUOUSLY
More informationFLOODPLAIN DEVELOPMENT AND BUILDING ORDINANCE
Town of Rye 10 Central Road Rye, NH 03870-0429 FLOODPLAIN DEVELOPMENT AND BUILDING ORDINANCE Item I. Definitions of Terms Item II. Permit Requirement Item III. Building Safety Review Item IV. Sanitary
More informationMAT109: Introduction to the Wood Frame Construction Manual
MAT109: Introduction to the Wood Frame Construction Manual One of the documents published by AF&PA is the Wood Frame Construction Manual for One- & Two-Family Dwellings. The WFCM is referenced in the IRC
More information2012 IBC Flood Provisions
Provisions Presented by: William C. Bracken, PE, SI, CFM Outline The National Insurance Program (NFIP) The Building Code & ASCE A Zone Requirements V Zone Requirements 2 plain Basics Types of plaines:
More information