EXPLORATORY SIMULATED WIND UPLIFT PRESSURE TESTING OF PANELCRAFTTM STANDING SEAM METAL ROOF SYSTEMS

Size: px
Start display at page:

Download "EXPLORATORY SIMULATED WIND UPLIFT PRESSURE TESTING OF PANELCRAFTTM STANDING SEAM METAL ROOF SYSTEMS"

Transcription

1 ,... ) RESEARCH REPORT EXPLORATORY SIMULATED WIND UPLIFT PRESSURE TESTING OF PANELCRAFTTM STANDING SEAM METAL ROOF SYSTEMS Prepared For: BUILDING RESEARCH SYSTEMS INC. 247 N. BROADWAY SUITE 203 EDMOND, OK D7A7.AM Class 4471 Date: December 31, 1998 FACTORY MUTUAL

2 Factory Mutual Research Corporation 1151 Boston-Providence Turnpike P.O. Box 9102 Norwood. MA D7A7.AM (4471 ) December 31, 1998 EXPLORATORY SIMULATED WIND UPLIFT PRESSURE TESTING OF PANELCRAFTTM STANDING SEAM METAL ROOF SYSTEMS for BUILDING RESEARCH SYSTEMS INC. 247 N. BROADWAY SUITE 203 EDMOND, OK INTRODUCTION 1.1 Building Research Systems Inc. submitted their PanelCraftTM Standing Seam Metal Roof Systems for exploratory simulated wind uplift pressure testing. Examination included simulated wind uplift pressure testing and resistance to foot traffic testing as described in the Factory Mutual Research Corporation (FMRC) Standard 4471 (1995) Approval requirements for Class 1 Panel Roofs. 1.2 The client requested wind uplift pressure testing and resistance to foot traffic testing on the products. 1.3 The material tested is not manufactured under the Factory Mutual Research Corporation follow-up inspection and reexamination program; therefore, the manufacturer cannot use the Factory Mutual Research name for marking or advertising the material. 1.4 The manufacture of the test sample components was not monitored by FMRC and all descriptions of test sample components were supplied by the client. 1.5 Tests show that the Building Research Systems Inc. PanelCraftTM Standing Seam Metal Roof System test samples, as tested, met the FMRC Windstorm Classifications as specified in the CONCLUSIONS of this report. 1.6 This test program was not intended to, nor does it, grant FMRC Approval for the Building Research Systems Inc. PanelCraftTM Standing Seam Roof System. The purpose of this program was to determine the windstorm classification of the submitted roof constructions in accordance with FMRC Class 4471 (1995) windstorm classification requirements only.

3 1D7A7.AM FACTORY MUTUAL RESEARCH CORPORATION Page 3 of 5 III TESTS AND PROCEDURES 3.1 Tests conducted were as requested by the sponsor of this program. 3.2 FMRC Windstorm Classification Tests Tests were conducted using the FMRC Uplift Pressure Test Apparatus to evaluate the ability of the components of the panel roof assembly to resist simulated wind uplift pressures without failure of the assemblies The simulated wind uplift pressure tests utilized a 12 ft (3.7 m) wide by 24 ft (7.3 m) long by 8 in. (203 mm) deep steel pressure vessel arranged to apply air pressure at preestablished standard rates to the underside of the test panel which formed the top of the pressure vessel. The vessel was pressurized with air A net pressure of 30 psf (1.4 kpa) was applied to the test sample and maintained for 1 minute. The pressure was released until no upward pressure was acting on the roof. The pressure was then increased to 45 psf (2.2 kpa), maintained. and exhausted as above. This procedure was repeated with each successive pressure increased by 15 psf (0.7 kpa) increments until failure occurred. 3.3 FMRC Resistance to Foot Traffic Tests Tests were conducted using the FMRC Resistance to Foot Traffic Test Apparatus to evaluate the ability of the panel roof to resist simulated foot traffic without damage. There must be no puncture of the roof panel or disengagement of the laps A 200 Ib (91 kg) load which incorporates a 3 in. (76 mm) square steel plate with rounded corners was imposed on the sample. The load was placed in the approximate center of the sample (midspan) and adjacent to the side lap. The load was then removed. This cycle was repeated four additional times. The roof panels were inspected for damage after the last cycle at the steel plate interface. IV TEST SAMPLES 4.1 FMRC Windstorm Classification Test Panels Two 12 ft by 24 ft (3.7 m by 7.3 m) test specimens were constructed as follows: Samole NO.1: Building Research Systems Inc. PanelCraftTM Standing Seam -Roof System consisting of PC218 panels, 18 in. (457 mm) wide panels of 24 gauge ( in., 0.59 mm) AZ50 galvalume steel produced from A792, Gr. 50 steel having a min yield strength of 50 ksi (345 N/mm2). The panels were secured to clips fastened to 16 ga ( in., 1.49 mm) thick steel purlins produced from A792, Gr. 50 steel having a min yield strength of 50 ksi (345 N/mm2) spaced 5 ft (1.5 m) o.c. with 2 - ITW Buildex 1/4-14 Hex Washer Head (HWH) Traxx/3 self-drilling fasteners per clip on one-half of the test assembly and 2 - Construction Fasteners 1/4-14 Hex Washer Head (HWH) IMPAX self-drilling fasteners per clip on the other half of the test assembly. Adjacent panel's were seamed together along side laps with an Building Research Systems electric roof seaming tool., --/.

4 Page 2 of 5 FACTORY MUTUAL RESEARCH CORPORATION 1D7A7.AM II MATERIALS TESTED 2.1 Building Research Systems Inc. PanelCraftTM Standing Seam Roof System consists of standing seam roof panels, floating clips, and associated components PanelCraftTM standing seam roof panels are roll-formed 22 ga. (min in., 0.70 mm) or 24 ga. (min in., 0.59 mm) AZ50 Galvalume or G90 Galvanized steel panels joined together by an interlocking seam and secured to the structure with interlocking Floating clips. The panels are produced from ASTM A792, Gr. 50 steel having a min yield strength of 50 ksi (345 N/mm2). The panels are available in. ( mm) wide, with seams 2-3 in. (51-76 mm) high, and are available with flat pan, striated pan or beaded pan options. The panels are designated with the initials "PC" followed by the seam height followed by the panel width, and are known as PC212, PC216, PC218 and PC318. The panels are either coated with a aluminum-zinc alloy, (galvalume) or coated with a zinc (galvanized) coating. The galvalume coating designation is AZ50, equivalent to a theoretical coating thickness of in. (0.04 mm) total for both sides. The galvanized coating designation is G90. For the PC212, PC216 and PC218 panels, one side of the panel has a 0.10 in. (2.5 mm)high rib plus a 1.9 in. (48 mm) high seam, forming a 2.0 in. (51 mm) overall panel height. The other side of the panel has a 0.10 in. (2.5 mm) high rib plus a 1.96 in. (50 mm) high seam, forming a 2-1/16 in. (52 mm) overall panel height. Forthe PC318 panels, one side of the panel has a 0.10 in. (2.5 mm) high rib plus a 2.9 in. (74 mm) high seam, forming a 3.0 in. (76 mm) overall panel height. The other side of the panel has a 0.10 in. (2.5 mm) high rib plus a 2.96 in. (75 mm) high seam, forming a 3-1/16 in. (78 mm) overall panel height. For each of the panels, the higher seam fits over the lower seam, and the adjacent panels are interfocked with a Building Research Systems electric roof seaming apparatus which provides a TripleLok 90 seam. The finished seam includes the interlocking Floating clips The floating clips consist of a 16 ga (min in., 1.49 mm) steel base with an interlocking 22 ga (min in., 0.70 mm) steel tab. The base and tab are produced from ASTM A446 Grade D, G-90 galvanized steel having a min yield strength of 50 ksi (345 N/mm2). The base is 2 in. (51 mm) wide and the tab is 4-1/4 (108 mm) wide. The tab has two notches that keeps the base centered until the clip is secured. 2.2 ITW Buildex 1/4-14 Hex Washer Head (HWH) Traxx/3 self-drilling fasteners are a 1/4 in. (6.4 mm) diameter screw with 14 threads per inch, a Traxx 3 Radius Milled Point, with a 5/16 in. (8 mm) Hex Washer Head. They are 1-1/2 in. (38 mm) long. The fasteners are made from type 1022 carbon steel coated with grey "Climaseal" coating. They are used to fasten the clips to the steel supporting members. 2.3 Construction Fasteners 1/4-14 Hex Washer Head (HWH) IMPAX self-drilling fasteners are a 1/4 in. (6.4 mm) diameter screw with 14 threads per inch, various milled points, with a 5/16 in. (8 mm) Hex Washer Head. They are 1-1/2 in. (38 mm) long. The fasteners are made from type 1022 carbon steel coated with galvanized coating. They are used to fasten the clips to the steel supporting members. 2.4 Steel supporting members (purlins) are roll-formed from min 16 ga ( in., 1.49 mm) thick ASTM A792, Gr. 50 steel having a min yield strength of 50 ksi (345 N/mm2).

5 Page 4 of 5 FACTORY MUTUAL RESEARCH CORPORATION 1D7A7.AM Samole NO.2: Building Research Systems Inc. PanelCraft Standing Seam Roof System consisting of PC218 panels, 18 in. (457 mm) wide panels of 22 gauge ( in., 0.70 mm) AZ50 galvalume steel produced from A792, Gr. 50 steel having a min yield strength of 50 ksi (345 N/mm2). The panels were secured to clips fastened to 16 ga ( in., 1.49 mm) thick steel purlins produced from A792, Gr. 50 steel having a min yield strength of 50 ksi (345 N/mm2) spaced 2 ft 6 in. (0.75 m) o.c. with 2 - ITW Buildex 1/4-14 Hex Washer Head (HWH) Traxx/3 self-drilling fasteners per clip on one-half of the test assembly and 2 - Construction Fasteners 1/4-14 Hex Washer Head (HWH) IMPAX self-drilling fasteners per clip on the other half of the test assembly. Adjacent panels were seamed together along side laps with an Building Research Systems electric roof seaming tool. 4.2 FMRC Resistance to Foot Traffic Test Panels Sample NO.1 described in above was also tested for foot traffic resistance. V RESULTS 5.1 FMRC Windstorm Classification Tests Sample NO.1 described in above met the 90 psf (4.4 kpa) min FMRC requirements for Class 90 Windstorm Classification. Mode of failure was seam disengagement from clip tab during incremental pressure increase to 105 psf (5.1 kpa) Sample NO.2 described in above met the 165 psf (7.9 kpa) min FMRC requirements for Class 165 Windstorm Classification. No failure occurred during testing. 5.2 FMRC Resistance to Foot Traffic Tests No damage to the roof panels or disengagement described in 4.2 above was observed after the test. of the side lap on the test panel VI CONCLUSIONS 6.1 Test results indicate that the Building Research Systems Inc. PanelCraftTM Standing Seam Roof System would meet the FMRC Class 4471 (1995) Windstorm Classification requirements for simulated wind uplift when installed as summarized below: Steel supporting members, min (16 ga ( in., 1.49 mm)) thick ASTM A792, Gr. 50 steel having a min yield strength of 50 ksi (345 N/mm2) are max 5 ft (1.5 m) o.c. PanelCraftTM Standing Seam Roof System consisting of min 24 ga. ( in., 0.59 mm) thick PC218 panels having a min yield strength of 50 ksi (345 N/mm2) are secured to clips secured to each supporting member with 2 - ITW Buildex 1/4-14 Hex Washer Head (HWH) Traxx/3 selfdrilling fasteners or 2 - Construction Fasteners 1/4-14 Hex Washer Head (HWH) IMPAX selfdrilling fasteners per clip. Adjacent panels are seamed together along side laps with a Building Research Systems electric seaming tool. Meets Class 90 Windstorm Classification.

6 1D7A7.AM FACTORY MUTUAL RESEARCH CORPORATION Page 5 of Steel supporting members (16 ga ( in., 1.49 mm)) thick ASTM A792. Gr. 50 steel having a min yield strength of 50 ksi (345 N/mm2) are max 2 ft 6 in. (0.75 m) o.c. PanelCraftTM Standing Seam Roof System consisting of min 22 ga. ( in., 0.70 mm) thick PC218 panels having a min yield strength of 50 ksi (345 N/mm2) are secured to clips secured to each supporting member with 2 - ITW Buildex 1/4-14 Hex Washer Head (HWH) Traxx/3 selfdrilling fasteners or 2 - Construction Fasteners 1/4-14 Hex Washer Head (HWH) IMPAX selfdrilling fasteners per clip. Adjacent panels are seamed together along side laps with a Building Research Systems electric seaming tool. Meets Class 165 Windstorm Classification. 6.2 Based upon an engineering analysis, PC212, PC216 and PC318 panels would be expected to reach the same level of performance as described in the above constructions. 6.3 Factory Mutual Research Corporation makes no judgement of product uniformity solely as a result of the tests performed in this program. Product uniformity depends in part on manufacturing facilities and procedures which would be inspected under the Factory Mutual Research Corporation Audit Inspection and Reexamination Program provides a means to assess these conditions. 6.4 This test program was not intended to, nor does it, grant FMRC Approval for the Building Research Systems Inc. PanelCraftTM Standing Seam Roof System. The purpose of this program was to determine the windstorm classification of the submitted roof constructions in accordance with FMRC Class 4471 (1995) windstorm classification requirements only. The products cannot bear the FMRC name in their advertising unless they are included in FMRC's Quality Audit Inspection Program as a result of one or more separate Approval test programs. VII MARKING 7.1 The material tested is not manufactured under the Factory Mutual Research Corporation Audit Inspection and Reexamination Program; therefore, the manufacturer cannot use the Factory Mutual Research name for marking or advertising the material. VIII LABORATORY REQUIREMENTS 8.1 Factory Mutual makes no judgement of product suitability for its intended end-use based entirely on Windstorm Classification Test results. This decision is usually the prerogative of the local authority having jurisdiction. TESTS AND REPORT BY: REPORT APPROVED BY: flfti 4 M. D. Tyrol Project Engineer Attached: ;o.~~l~ P. J. Ith Senior Engineer Materials Section Appendix A - Panel Details Appendix B - Clip Details Appendix C - Fastener Details

Code Compliance Research Report CCRR-0228

Code Compliance Research Report CCRR-0228 Code Compliance Research Report CCRR-0228 Issue Date: 05-09-2017 Renewal Date: 05-11-2018 Revision Date: 06-23-2017 DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION Section: 07 40 00 Roofing and Siding

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS REPORT HOLDER: METAL SALES MANUFACTURING CORPORATION

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS REPORT HOLDER: METAL SALES MANUFACTURING CORPORATION 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (0) 3-87 (562) 699-03 www.icc-es.org ESR-23 Reissued 08/2017 This report is subject to renewal 08/2019. DIVISION: 07 00 00 THERMAL

More information

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: KINGSPAN INSULATED PANELS, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: KINGSPAN INSULATED PANELS, INC. 0 Most Widely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1143 Reissued 04/2017 This report is subject to renewal 04/2018. DIVISION: 07 00 00 THERMAL

More information

SECTION STRUCTURAL RETROFIT ROOF SUB-FRAMING SYSTEM

SECTION STRUCTURAL RETROFIT ROOF SUB-FRAMING SYSTEM SECTION 13 34 21 - STRUCTURAL RETROFIT ROOF SUB-FRAMING SYSTEM PART 1 - GENERAL 1.1 DESCRIPTION A. The structural retrofit roof sub-framing system will provide support for a new metal roofing system constructed

More information

Specifications. When specifying metal panel roof systems, roof. system designers and specifiers need to be aware

Specifications. When specifying metal panel roof systems, roof. system designers and specifiers need to be aware 32 www.professionalroofing.net OCTOBER 2012 When specifying metal panel roof systems, roof system designers and specifiers need to be aware of specific standards. Sometimes, the standards applicable to

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 NOTICE OF ACCEPTANCE

More information

SHEET METAL ROOF TEST REPORT

SHEET METAL ROOF TEST REPORT SHEET METAL ROOF TEST REPORT Introduction The time tested performance of the double lock standing seam and batten seam metal roofing is demonstrated by thousands of squares successfully installed by SMACNA

More information

THE SITUATION WITH STEEL DECKS

THE SITUATION WITH STEEL DECKS THE SITUATION WITH STEEL DECKS Steel roof deck design can affect roof system selection and design by Mark S. Graham 32 www.professionalroofing.net MARCH 2017 teel roof decks commonly are encountered in

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 4 6587 (562) 699 0543 www.icc es.org ESR 3152 Reissued 08/2017 This report is subject to renewal 08/2018. DIVISION: 07 00 00

More information

SECTION METAL ROOF PANELS

SECTION METAL ROOF PANELS SECTION 07 41 13 PART 1 GENERAL 1.1 SECTION INCLUDES A. Standing-seam roof panels. B. Metal roofing accessories. 1.2 RELATED SECTIONS A. Section 07 62 00 - Sheet Metal Flashing. B. Section 07 72 00 - Roof

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL WALL PANELS DIVISION: SIDING REPORT HOLDER: VM ZINC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL WALL PANELS DIVISION: SIDING REPORT HOLDER: VM ZINC 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1733 Issued 02/2017 This report is subject to renewal 02/2018. DIVISION: 07 00 00 THERMAL AND

More information

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

SL175 Panel Technical Data Guide

SL175 Panel Technical Data Guide Description SL175 is a integral snap-lock standing seam roofing panel used on commercial and residential applications. The panel is factory formed in continuous lengths up to 60-0 long. Attachment to either

More information

Through-Fastener Panel UL Listing documentation

Through-Fastener Panel UL Listing documentation Through-Fastener Panel UL Listing documentation Class-4 Impact Rating Class-90 Fire Rating Tensile Strength: Grade 80/E Coil Thickness Range for 29 ga.: 0.0142 0.015 Coil Thickness Range for 26 ga.: 0.0182

More information

SECTION 1043 FENCE MATERIAL

SECTION 1043 FENCE MATERIAL SECTION 1043 FENCE MATERIAL 1043.1 Scope. This specification covers the material required in the construction of chainlink fence and woven wire fence. 1043.2 Basis of Acceptance. The basis of acceptance

More information

TRIAD CORRUGATED METAL, INC.

TRIAD CORRUGATED METAL, INC. TRIAD CORRUGATED METAL, INC. C O M M E R C I A L R E S I D E N T I A L A G R I C U L T U R A L Snap Loc Panel Guide Snap Loc metal panels are a perfect fit for residential, architectural and commercial

More information

CITY OF RICHMOND PINE CAMP COMMUNITY CENTER ROOF REPLACEMENT PROJECT RCS PROJECT NO

CITY OF RICHMOND PINE CAMP COMMUNITY CENTER ROOF REPLACEMENT PROJECT RCS PROJECT NO SECTION 07220 - ROOF INSULATION PART 1 - GENERAL 1.01 DESCRIPTION A. Work included: The Roofing Contractor will provide all polyisocyanurate insulation and high density wood fiber roof insulation (tapered

More information

ATI Evaluation Service A Division of Architectural Testing Certification Services

ATI Evaluation Service A Division of Architectural Testing Certification Services ATI Evaluation Service A Division of Architectural Testing Certification Services Subject to Renewal: 08/09/2014 Issued: 08/09/2013 Visit www.ati-es.com for current status Revised: 08/12/2013 Page 1 of

More information

The Contractor is responsible for quality control, including workmanship and materials furnished by his subcontractors and suppliers.

The Contractor is responsible for quality control, including workmanship and materials furnished by his subcontractors and suppliers. SECTION 05 31 33 - STEEL FORM DECKING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the contract, including General and Supplementary Conditions and Division 01 - Specification

More information

The Contractor is responsible for quality control, including workmanship and materials furnished by his subcontractors and suppliers.

The Contractor is responsible for quality control, including workmanship and materials furnished by his subcontractors and suppliers. SECTION 05 31 23 - STEEL ROOF DECKING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the contract, including General and Supplementary Conditions and Division 01 - Specification

More information

ROOFING APPLICATION STANDARD (TAS) No. 102(A)-95

ROOFING APPLICATION STANDARD (TAS) No. 102(A)-95 ROOFING APPLICATION STANDARD (TAS) No. 102(A)-95 TEST PROCEDURE FOR STATIC UPLIFT RESISTANCE OF MECHANICALLY ATTACHED, CLIPPED, RIGID, ROOF SYSTEMS (For Methods of Mechanical Attachment Excluding Clips,

More information

Force Engineering & Testing Inc Ramblewood Drive. Humble,TX Product Evaluation Report SENTRIGARD METAL ROOFING SYSTEMS

Force Engineering & Testing Inc Ramblewood Drive. Humble,TX Product Evaluation Report SENTRIGARD METAL ROOFING SYSTEMS Force Engineering & Testing Inc. Product Evaluation Report SENTRIGARD METAL ROOFING SYSTEMS Sentrigard ML 200 24 Ga. 18 7/8" Wide Roof Panel over open framing Florida Product Approval # 9864.2 R4 Florida

More information

PRODUCT EVALUATION Effective Date: June 1, 2013 GDR-40

PRODUCT EVALUATION Effective Date: June 1, 2013 GDR-40 TEXAS DEPARTMENT OF INSURANCE Engineering Services Program / MC 103-3A 333 Guadalupe Street P.O. Box 149104 Austin, Texas 78714-9104 Phone No. (512) 322-2212 Fax No. (512) 463-6693 PRODUCT EVALUATION Effective

More information

SECTION STEEL DECKING

SECTION STEEL DECKING SECTION 05 31 00 STEEL DECKING SPEC WRITER NOTE: 1. Delete text between // // not applicable to project. Edit remaining text to suit project. 2. Refer to Section 05 36 00, COMPOSITE METAL DECKING for floor

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER: 0 Most idely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-687 (62) 699-043 www.icc-es.org ESR-199 Reissued 0/2017 This report is subject to renewal 0/2019. DIVISION: 07 00 00 THERMAL AND MOISTURE

More information

POST FRAME BUILDING STANDARDS

POST FRAME BUILDING STANDARDS CASS COUNTY, MISSOURI BUILDING CODES, ENVIRONMENTAL HEALTH AND ZONING DEPARTMENT 30508 S. West Outer Road, Harrisonville, MO 64701 P- (816) 380-8134 F- (816) 380-8130 POST FRAME BUILDING STANDARDS 201.3

More information

FLORIDA PRODUCT APPROVAL GULFRIBTM FLORIDA PRODUCT APPROVAL NO R3. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC.

FLORIDA PRODUCT APPROVAL GULFRIBTM FLORIDA PRODUCT APPROVAL NO R3. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC. 26 Ga. GulfRib Roof Panel over 15/32 Plywood Florida Product Approval #11651.22 R3 Florida Building Code 2017 Per Rule 61G20-3 Method:

More information

calculated with factor of safety of 2.5 for bending stress, 3.0 for shear stresses and deflection limitation of L/180.

calculated with factor of safety of 2.5 for bending stress, 3.0 for shear stresses and deflection limitation of L/180. Metl-Span CF-42 Light Mesa Wall Panels 26 Ga. Exterior / 26 ga. Interior Facings Allowable Connection Load 1,7,8,9,10 (psf) Two or More Equal Spans Panel Type 2 Design Criteria 3,4,5,6 Support Span 5 ft

More information

Specifications for FL-100 Soffit Panel

Specifications for FL-100 Soffit Panel Union Corrugating Company Specifications for FL-100 Soffit Panel SECTION 07410 METAL SOFFIT PANELS PART 1 GENERAL 1.1 DESCRIPTON A. Section Includes: 1. Preformed metal soffit panel system 2. Associated

More information

The FAQs of Standing Seam Panel Clips

The FAQs of Standing Seam Panel Clips Page 1 of 6 The FAQs of Standing Seam Panel Clips By Mark Robins, Posted 07/05/2017 These questions and answers provide information about standing seam panel clips Structural standing seam panels mate

More information

Residential, 26 Ga. Roof Panel over 15/32 Plywood. Florida Product Approval # R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D

Residential, 26 Ga. Roof Panel over 15/32 Plywood. Florida Product Approval # R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D Product Evaluation Report REED S METAL, INC. Residential, 26 Ga. Roof Panel over 15/32 Plywood Florida Product Approval # 12725.2 R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D Category: Roofing

More information

Metafor Panel System Installation Guide

Metafor Panel System Installation Guide Installation Guide innovative cladding design solutions Product Description Universal Flashing Kit Supplemental Guide for VM Pro-Zinc Training To enroll in a VM PRO-ZINC Training Course contact: UMICORE

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL WALL PANELS REPORT HOLDER: METL SPAN, A DIVISION OF NCI GROUP, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL WALL PANELS REPORT HOLDER: METL SPAN, A DIVISION OF NCI GROUP, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2218 Reissued 09/2017 This report is subject to renewal 09/2018. DIVISION: 07 00

More information

Metal Roof Panels

Metal Roof Panels University of New Hampshire University of New Hampshire Scholars' Repository Division 07 Thermal and Moisture Protection Chapter 5 Technical Construction and Renovation Standards 1-25-2013 074113 - Metal

More information

DIVISION: METALS SECTION: METAL FASTENINGS SECTION: STEEL DECKING REPORT HOLDER: HILTI, INC.

DIVISION: METALS SECTION: METAL FASTENINGS SECTION: STEEL DECKING REPORT HOLDER: HILTI, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 43 6587 (56) 699 0543 www.icc es.org ESR 97 Reissued /7 This report is subject to renewal /8. DIVISION: 05 00 00 METALS SECTION:

More information

FLORIDA PRODUCT APPROVAL GULFRIBTM FLORIDA PRODUCT APPROVAL NO R3. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC.

FLORIDA PRODUCT APPROVAL GULFRIBTM FLORIDA PRODUCT APPROVAL NO R3. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC. 26 Ga. GulfRib Roof Panel over 15/32 Plywood Florida Product Approval #11651.23 R3 Florida Building Code 2017 Per Rule 61G20-3 Method:

More information

CS-100 Guide Specifications

CS-100 Guide Specifications MANUFACTURER CUSTOM-BILT METALS 1333 Corporate Drive, Suite 103 Irving, Texas 75038-2520 (800) 826-7813 or info@custombiltmetals.com www.custombiltmetals.com CS-100 Guide Specifications This Guide Specification

More information

Structural vs Nonstructural Members. Roger LaBoube, Ph.D., P.E. Wei-Wen Yu Center for Cold-Formed Steel Structures

Structural vs Nonstructural Members. Roger LaBoube, Ph.D., P.E. Wei-Wen Yu Center for Cold-Formed Steel Structures Structural vs Nonstructural Members Roger LaBoube, Ph.D., P.E. Wei-Wen Yu Center for Cold-Formed Steel Structures Behavior of Cold-Formed Steel Members STEEL DESIGN SPECIFICATIONS Type of steel Specification

More information

CBUCK Engineering. Product: Zee-Lock Roof Panel Material: Steel Panel Thickness: 24 gauge Panel Width: 16 Support: Wood Deck

CBUCK Engineering. Product: Zee-Lock Roof Panel Material: Steel Panel Thickness: 24 gauge Panel Width: 16 Support: Wood Deck Evaluation Report Zee-Lock With Continous Zee-Rib Clip Metal Roof Assembly Manufacturer: 1720 Maury Road Houston, TX 77026 (800) 231-8127 2333 for Florida Product Approval HVHZ # FL 15471.1 Florida Building

More information

RPR Insul-Mate Sheet and Roll Jacketing

RPR Insul-Mate Sheet and Roll Jacketing RPR Insul-Mate Sheet and Roll Jacketing ALUMINUM PRODUCTS Rolled Jacketing Sheeting (Flat and Corrugated) Cut to Length Cut & Rolled Width/Length: 36 and 48 wide 100, 50 and cut to length (thicker gauges

More information

NUCOR VR 16 II STANDING SEAM ROOF SYSTEM TABLE OF CONTENTS

NUCOR VR 16 II STANDING SEAM ROOF SYSTEM TABLE OF CONTENTS NUCOR VR 16 II STANDING SEAM ROOF SYSTEM TABLE OF CONTENTS Nucor VR16 II Vertical Rib Standing Seam Roof System...2 Nucor VR16 II Property and Span Tables...3 Standard Details...5 ED3010PE - Gutter...5

More information

MultiLok-24 Guide Specifications conforming to C.S.I. standards. A Division of ASC Profiles

MultiLok-24 Guide Specifications conforming to C.S.I. standards. A Division of ASC Profiles MultiLok-24 Guide Specifications conforming to C.S.I. standards A Division of ASC Profiles AEP SPAN MultiLok-24 Guide Spec i fi ca tions MANUFACTURER - AEP SPAN 5100 East Grand Avenue, Dallas, TX 75223,

More information

Item 442 Metal for Structures

Item 442 Metal for Structures Item 442 Metal for Structures 1. DESCRIPTION 2. MATERIALS Provide structural steel, high-strength bolts, forgings, steel castings, iron castings, wrought iron, steel pipe and tubing, aluminum castings

More information

Guide Specification SDP 200

Guide Specification SDP 200 PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Sheet metal roofing panels, metal trim, accessories, fasteners, closures, and sealants. [Specifier Note: Edit paragraph below to suit project requirements.]

More information

SECTION HVAC GRAVITY VENTILATORS

SECTION HVAC GRAVITY VENTILATORS SECTION 23 37 23 HVAC GRAVITY VENTILATORS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

CBUCK Engineering. Evaluation Report Cee Lock Panel Metal Roof Assembly

CBUCK Engineering. Evaluation Report Cee Lock Panel Metal Roof Assembly Specialty Structural Engineering CBUCK, Inc. Certificate of Authorization #8064 Prepared by: James L. Buckner, P.E., S.E.C.B. Florida Professional Engineer # 31242 Florida Evaluation ANE ID: 1916 Project

More information

1470 Dale Court Austell, GA Phone: Fax:

1470 Dale Court Austell, GA Phone: Fax: 1470 Dale Court Austell, GA 30168 Phone: 404-351-2202 Fax: 404-351-2203 LC METALS, INC. PRODUCT INDEX Page # STUD GUARDS...3 FHA STRAPS...3 BOCA PLATES (Nail Plates)...4 PLUMBERS TAPE (Banding Iron)...4

More information

SECTION NON-STRUCTURAL METAL FRAMING

SECTION NON-STRUCTURAL METAL FRAMING PART 1 - GENERAL 1.1 DESCRIPTION SECTION 09 22 16 1. Use this section only for NCA projects. 2. Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable

More information

Alply CLASSIC WALL Architectural Insulated Panel Wall System

Alply CLASSIC WALL Architectural Insulated Panel Wall System SECTION 07 42 13 INSULATED METAL WALL PANELS ALPLY Insulated Panels Alply CLASSIC WALL Architectural Insulated Panel Wall System PART 1 / GENERAL 1.1 SYSTEM DESCRIPTION A. Smooth, non-embossed steel, insulated

More information

Flotation Docking Systems, Inc.

Flotation Docking Systems, Inc. GENERAL SPECIFICATIONS The following data outlines the design calculations and specifications around which Flotation Docking Systems, Inc. products are constructed. The use of such information for contract

More information

TESTING APPLICATION STANDARD (TAS) No TEST PROCEDURE FOR STATIC UPLIFT RESISTANCE OF MORTAR OR ADHESIVE SET TILE SYSTEMS

TESTING APPLICATION STANDARD (TAS) No TEST PROCEDURE FOR STATIC UPLIFT RESISTANCE OF MORTAR OR ADHESIVE SET TILE SYSTEMS TESTING APPLICATION STANDARD (TAS) No. 101-95 TEST PROCEDURE FOR STATIC UPLIFT RESISTANCE OF MORTAR OR ADHESIVE SET TILE SYSTEMS 1. Scope 2. Referenced Documents 1.1 This Protocol covers the determination

More information

Steelway Building Systems. Product Specifications Guide

Steelway Building Systems. Product Specifications Guide Steelway Building Systems Product Specifications Table of Contents 1.0 Scope... 2 2.0 Design Standards... 3 3.0 Product Standards... 3 3.1 Plate, Coil and Hot-Rolled... 3 3.2 Bolts and Fasteners... 3 4.0

More information

INSULATED PANEL OVERVIEW

INSULATED PANEL OVERVIEW INSULATED PANEL OVERVIEW Our various series of wall and roof panels are filled with non CFC polyisocyanurate foam. The panels are manufactured in a uniform pressure laminating process that bonds metal

More information

SECTION ROOF SPECIALTIES

SECTION ROOF SPECIALTIES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 71 00 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable

More information

DIVISION: METALS SECTION: STEEL DECKING REPORT HOLDER: EPIC METALS CORPORATION 11 TALBOT AVENUE RANKIN, PENNSYLVANIA 15104

DIVISION: METALS SECTION: STEEL DECKING REPORT HOLDER: EPIC METALS CORPORATION 11 TALBOT AVENUE RANKIN, PENNSYLVANIA 15104 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2047 Reissued 07/207 This report is subject to renewal 07/209. DIVISION: 05 00 00

More information

Design Manual and Catalog of Steel Deck Products STEEL DECK INSTITUTE MEMBER

Design Manual and Catalog of Steel Deck Products STEEL DECK INSTITUTE MEMBER Design Manual and Catalog of Steel Deck Products s STEEL DECK INSTITUTE MEMBER Manufacturers of products History CMC Joist & Deck is a leading producer of steel deck, open-web steel joists, long span steel

More information

Section 906. STRUCTURAL STEEL

Section 906. STRUCTURAL STEEL 906.01 Section 906. STRUCTURAL STEEL 906.01. General Requirements. Finished rolled shapes must be free from imperfections that affect strength and durability in accordance with ASTM A 6. Rolled shapes

More information

AMERICAN NATIONAL STANDARD ANSI/NAAMM STANDARD. Maximum Bearing Bar Depth / 2 (63.5 mm)

AMERICAN NATIONAL STANDARD ANSI/NAAMM STANDARD. Maximum Bearing Bar Depth / 2 (63.5 mm) METAL BAR GRATING AMERICAN NATIONAL STANDARD ANSI/NAAMM STANDARD MBG 531-17 GRATINGS 5 ANSI/NAAMM MBG 531-17 SEPTEMBER 7, 2017 METAL BAR GRATING MANUAL EIGHTH EDITION Maximum Bearing Bar Depth... 2 1 /

More information

REPORT HOLDER: RARE MANUFACTURING INC A AVENUE SURREY, BRITISH COLUMBIA V4N 4P2 CANADA EVALUATION SUBJECT: IRONWOOD SHAKE

REPORT HOLDER: RARE MANUFACTURING INC A AVENUE SURREY, BRITISH COLUMBIA V4N 4P2 CANADA EVALUATION SUBJECT: IRONWOOD SHAKE 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2134 Reissued 12/2017 This report is subject to renewal 12/2018. DIVISION: 07 00

More information

A. Product Data: For each type of deck, accessory, and product indicated.

A. Product Data: For each type of deck, accessory, and product indicated. SECTION 053100 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Roof deck. 2. Composite floor deck. 3. Noncomposite form deck. 1.2 SUBMITTALS A. Product Data: For each type of deck, accessory, and

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: POLYVINYL CHLORIDE ROOFING REPORT HOLDER: IB ROOF SYSTEMS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: POLYVINYL CHLORIDE ROOFING REPORT HOLDER: IB ROOF SYSTEMS 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 28 Reissued 02/2018 This report is subject to renewal 02/2019. DIVISION: 07 00 00

More information

CBUCK Engineering. Evaluation Report Englert Series 500 Metal Roof Assembly Manufacturer: Englert, Inc Amboy Avenue Perth Amboy, NJ

CBUCK Engineering. Evaluation Report Englert Series 500 Metal Roof Assembly Manufacturer: Englert, Inc Amboy Avenue Perth Amboy, NJ Evaluation Report Englert Series 500 Metal Roof Assembly Manufacturer: 1200 Amboy Avenue Perth Amboy, NJ 08862 for Florida Product Approval # FL 11698.2 R3 Florida Building Code 5th Edition (2014) Method:

More information

The Contractor is responsible for quality control, including workmanship and materials furnished by his subcontractors and suppliers.

The Contractor is responsible for quality control, including workmanship and materials furnished by his subcontractors and suppliers. SECTION 05 31 13 STEEL FLOOR DECKING PART 1 - GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the contract, including General and Supplementary Conditions and Division 01 - Specification

More information

ANSI/FM Approvals March FM Approvals LLC. All rights reserved.

ANSI/FM Approvals March FM Approvals LLC. All rights reserved. American National Standard for Evaluating the Simulated Wind Uplift Resistance of Roof Assemblies Using Static Positive and/or Negative Differential Pressures ANSI/FM Approvals 4474 March 2004 2004 FM

More information

Guide to Attaching Exterior Wall Coverings through Foam Sheathing to Wood or Steel Wall Framing

Guide to Attaching Exterior Wall Coverings through Foam Sheathing to Wood or Steel Wall Framing Guide to Attaching Exterior Wall Coverings through Foam Sheathing to Wood or Wall Framing Released September 20, 2010 Updated December 4, 2012 Note: Tables for cladding attachments to wood framing have

More information

CBUCK Engineering. Florida Product Approval # FL R2

CBUCK Engineering. Florida Product Approval # FL R2 Specialty Structural Engineering CBUCK, Inc. Certificate of Authorization #8064 Prepared by: James L. Buckner, P.E., SECB Florida Professional Engineer # 31242 Florida Evaluation ANE ID: 1916 Project Manager:

More information

Student Services & Classroom Addition

Student Services & Classroom Addition SECTION 095133 - ACOUSTICAL METAL PAN CEILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

ACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) PREFACE

ACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) PREFACE ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect ACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) AC191 Approved May 2008 Effective June 1, 2008 Previously approved February 2008, October 2007,

More information

SECTION PRE-ENGINEERED WOOD POST FRAME BUILDING SYSTEM. B. Products Supplied But Not Installed Under This Section:

SECTION PRE-ENGINEERED WOOD POST FRAME BUILDING SYSTEM. B. Products Supplied But Not Installed Under This Section: SECTION 13125 FRAME BUILDING SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Primary and secondary wood structural framing systems, roofing and wall covering systems, roof and wall insulation,

More information

SNAP-CLAD. Technical Information and Flashing Details. /

SNAP-CLAD. Technical Information and Flashing Details.  / SNAP-CLAD Technical Information and Flashing Details Product Information: PAGE 3 SNAP-CLAD Spec. Sheet PAGES 4-13 UL List Cards - UL Construction Numbers 261, 254, 255, 263, 343, 303, 508, 508A, 614, 790

More information

Exterior Research & Design, L.L.C. Building Science and Envelope Consultants

Exterior Research & Design, L.L.C. Building Science and Envelope Consultants Exterior Research & Design, L.L.C. Building Science and Envelope Consultants Certificate of Evaluation Report 3520.03.04-R2 Evaluation of Roof s for Florida Product Approval #FL2533-R2 Prepared for: CertainTeed

More information

FORMDECK. constructions. constructions

FORMDECK. constructions. constructions FORMDECK constructions constructions Introduction Formdeck300 (FD300) is a very efficient and durable permanent metal tray formwork, reinforcement and ceiling system used for suspended concrete slab construction.

More information

Understanding Wind Uplift Ratings

Understanding Wind Uplift Ratings Page 1 of 5 Home Understanding Wind Uplift Ratings By Stan Choiniere September 1, 2006 What is an FM Approvals wind test, and what do the various wind uplift ratings mean? This question is frequently asked,

More information

ESR-2015P* Reissued April 2014 This report is subject to renewal April 1, 2015.

ESR-2015P* Reissued April 2014 This report is subject to renewal April 1, 2015. ICC-ES Evaluation Report ESR-2015P* Reissued April 2014 This report is subject to renewal April 1, 2015. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council DIVISION:

More information

DIVISION: SPECIALTIES SECTION: DEMOUNTABLE PARTITIONS REPORT HOLDER: KRUEGER INTERNATIONAL, INC.

DIVISION: SPECIALTIES SECTION: DEMOUNTABLE PARTITIONS REPORT HOLDER: KRUEGER INTERNATIONAL, INC. 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3505 Issued 04/2017 This report is subject to renewal 04/2018. DIVISION: 10 00 00 SPECIALTIES

More information

TEST REPORT. Report No.: B Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

TEST REPORT. Report No.: B Rendered to: TREMCO, INCORPORATED Beachwood, Ohio Architectural Testing TEST REPORT Report No.: B2739.02-501-47 Rendered to: TREMCO, INCORPORATED Beachwood, Ohio PRODUCT TYPE: Air Barrier System SERIES/MODEL: ExoAir 230, ProGlaze ETA System 1, Spectrem

More information

CITY OF FARGO SPECIFICATIONS SIGNING

CITY OF FARGO SPECIFICATIONS SIGNING SIGNING PART 1 DESCRIPTION OF WORK The work to be done under this section of the Specifications and the accompanying plans consists of furnishing all labor, material and accessories necessary to complete

More information

Evaluation Report. Die Formed Skirt Ridge Ventilator. "12 Inch Throat" Manufacturer. Metallic Products Corporation Hollister Road

Evaluation Report. Die Formed Skirt Ridge Ventilator. 12 Inch Throat Manufacturer. Metallic Products Corporation Hollister Road Specialtu Structural Engineering CBUCK, Inc. Certificate of Authorization #864 Evaluation Report Die Formed Skirt Ridge Ventilator "12 Inch Throat" Manufacturer Metallic Products Corporation 7777 Hollister

More information

Originally Issued: 05/20/2013 Revised: 07/07/2017 Valid Through: 05/31/ Design

Originally Issued: 05/20/2013 Revised: 07/07/2017 Valid Through: 05/31/ Design BRADY INNOVATIONS, LLC. PROX HEADER SYSTEM CSI Section: 05 05 23 Metal Fastenings 05 40 00 Cold-formed Metal Framing 1.0 RECOGNITION Brady Innovations, LLC s ProX Header System recognized in this report

More information

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

REPORT HOLDER: ispan SYSTEMS LP 70 BRENTWOOD DRIVE PRINCETON, ONTARIO N0J 1V0 CANADA EVALUATION SUBJECT:

REPORT HOLDER: ispan SYSTEMS LP 70 BRENTWOOD DRIVE PRINCETON, ONTARIO N0J 1V0 CANADA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 2-6587 (562) 699-05 www.icc-es.org ESR-787 Issued 07/2017 This report is subject to renewal 07/2018. DIVISION: 05 00 00 METALS

More information

COMBINED ADHESIVE-STEEL PIN APPLICATIONS FOR CFS FRAME SHEAR WALLS

COMBINED ADHESIVE-STEEL PIN APPLICATIONS FOR CFS FRAME SHEAR WALLS Department of Civil Engineering Santa Clara University COMBINED ADHESIVE-STEEL PIN APPLICATIONS FOR CFS FRAME SHEAR WALLS Final Report: CLFSR-5-4 May 31, 24 By Ioi Lam, Henry Qi and Christopher Pitt (Undergraduate

More information

1 1 4" FRAMING SYSTEM

1 1 4 FRAMING SYSTEM 4" FRAMING SYSTEM A000 (4 Gauge)...6-70 A00 (4 Gauge)...7-7 A4000 ( Gauge)...7-74 A000 (4 Gauge)... 7 Channel Nuts and Closure Strips...76-77 Flat Plate Fittings... 77 Ninety Degree Fittings...77-78 Z

More information

Product Guide Specification

Product Guide Specification ALGRIP Manufactured by April 2017 104 North Maple Avenue P.O. Box 646 Leola, Pennsylvania 17540 Toll Free 800-345-8170 Fax 717-656-2041 Website www.algrip.com / www.rosstechnology.com E-mail sales@rosstechnology.com

More information

Originally Issued: 09/19/2014 Revised: 10/17/2017 Valid Through: 11/15/2017

Originally Issued: 09/19/2014 Revised: 10/17/2017 Valid Through: 11/15/2017 EVALUATION SUBJECT: QUALITY EDGE MATTERHORN METAL ING REPORT HOLDER: Quality Edge, Inc. 2712 Walkent Drive Walker, MI 49544 (888) 784-0878 www.quality-edge.com CSI Division: 07 THERMAL AND MOISTURE PROTECTION

More information

ESR ICC Evaluation Service, Inc. Issued November 1, 2003 This report is subject to re-examination in one year.

ESR ICC Evaluation Service, Inc. Issued November 1, 2003 This report is subject to re-examination in one year. ESR-1015 Issued November 1, 2003 This report is subject to re-examination in one year. ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office # 5360 Workman Mill Road, Whittier, California

More information

PRE-ENGINEERED METAL BUILDING SYSTEM

PRE-ENGINEERED METAL BUILDING SYSTEM PRE-ENGINEERED METAL BUILDING SYSTEM PART 1 GENERAL 1.1 SUMMARY A. The building shall include all primary and secondary structural framing members, connection bolts, roof and wall covering, flashing, gutter,

More information

METAL BUILDING SYSTEM SPECIFICATIONS

METAL BUILDING SYSTEM SPECIFICATIONS METAL BUILDING SYSTEM SPECIFICATIONS 1. GENERAL 1.1. SCOPE 1.1.1. These specifications apply to metal buildings systems as engineered, designed, and fabricated by Tyler Building Systems, L.P. ( Tyler ).

More information

GUIDE SPECIFICATION EXETER SECURITY SHIELD SECURITY WINDOW BARRIER SYSTEM

GUIDE SPECIFICATION EXETER SECURITY SHIELD SECURITY WINDOW BARRIER SYSTEM 1 GUIDE SPECIFICATION EXETER SECURITY SHIELD SECURITY WINDOW BARRIER SYSTEM 1.01 WORK INCLUDED PART 1: GENERAL A. Provide for all labor, equipment, materials and services to furnish and install SECURITY

More information

LINEAR METAL CEILINGS Section

LINEAR METAL CEILINGS Section PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL WALL PANELS REPORT HOLDER: FCP, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL WALL PANELS REPORT HOLDER: FCP, INC. 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2937 Reissued 05/2016 This report is subject to renewal 05/2018. DIVISION: 07 00 00 THERMAL

More information

LISTING INFORMATION OF ClarkDietrich Steel 'H' Stud and 'U' Track Fire-resistance-rated Area Separation Wall Assemblies SPEC ID: 26662

LISTING INFORMATION OF ClarkDietrich Steel 'H' Stud and 'U' Track Fire-resistance-rated Area Separation Wall Assemblies SPEC ID: 26662 LISTING INFORMATION OF ClarkDietrich Steel 'H' Stud and 'U' Track Fire-resistance-rated Area Separation Wall Assemblies SPEC ID: 26662 ClarkDietrich Building Systems 9100 Centre Pointe Drive, Suite 210

More information

SECTION METAL FLOOR PLATE STAIRS

SECTION METAL FLOOR PLATE STAIRS SECTION 05513 - METAL FLOOR PLATE STAIRS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

General. 2. Design. 3. Anchor Bolts And Foundations. 4. Drawings. 5. Structural Framing. 6. Roof Covering Nucor Classic Roof Panel

General. 2. Design. 3. Anchor Bolts And Foundations. 4. Drawings. 5. Structural Framing. 6. Roof Covering Nucor Classic Roof Panel The following Nucor Building Systems Specification Guide provides the owner or design professional a detailed description of all standard Nucor Building Systems (NBS) products. This guide is designed to

More information

DIVISION: METALS SECTION: METAL RAILINGS REPORT HOLDER: ULTRALOX 2955 LONE OAK DRIVE, SUITE 180 EAGAN, MINNESOTA 55121

DIVISION: METALS SECTION: METAL RAILINGS REPORT HOLDER: ULTRALOX 2955 LONE OAK DRIVE, SUITE 180 EAGAN, MINNESOTA 55121 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3485 Issued 10/2017 This report is subject to renewal 10/2018. DIVISION: 05 00 00

More information

Cyclonic Area. Design Manual. Using TOPSPAN profiles and LYSAGHT roofing and walling claddings in cyclonic areas

Cyclonic Area. Design Manual. Using TOPSPAN profiles and LYSAGHT roofing and walling claddings in cyclonic areas Cyclonic Area Design Manual Using TOPSPAN profiles and LYSAGHT roofing and walling claddings in cyclonic areas This manual has been prepared to assist architects, engineers and builders in the correct

More information

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi STRUCTURAL NOTES MATERIAL STRENGTHS Structural Steel Reinforcing Steel Concrete Masonry Structural Lumber Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel

More information

REPORT HOLDER: FASTENING SPECIALISTS, INC. 726 CENTRAL FLORIDA PARKWAY ORLANDO, FLORIDA EVALUATION SUBJECT:

REPORT HOLDER: FASTENING SPECIALISTS, INC. 726 CENTRAL FLORIDA PARKWAY ORLANDO, FLORIDA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2328 Reissued 10/2017 This report is subject to renewal 10/2018. DIVISION: 03 00

More information