STANDARD CONSTRUCTION DETAILS SANITARY SEWER REVISED MARCH 2018 DEPARTMENT OF ENGINEERING
|
|
- Dinah Ward
- 5 years ago
- Views:
Transcription
1 STANDARD CONSTRUCTION DETAILS REVISED MARCH 2018
2 GENERAL NOTES EMBEDMENT DETAILS EMBEDMENT DETAILS TWO-WAY CLEANOUT - EXISTING LATERAL TWO-WAY CLEANOUT - NEW CONSTRUCTION TYPICAL SEWER HOUSE SERVICE CONNECTION STANDARD CLEANOUT CAST-IN-PLACE MANHOLE TYPE "S" MANHOLE, CAST IN PLACE KEYWAY WITH WATER STOP PRECAST CONCRETE PIPE MANHOLE, ALTERNATE "A" PRECAST CONCRETE PIPE MANHOLE, ALTERNATE "B" PRECAST CONCRETE FLAT TOP MANHOLE CAST IRON GRATE AND FRAME MANHOLE DROP CONNECTION INTERIOR DROP MANHOLE DETAIL PRESSURE TYPE MANHOLE FRAME AND COVER ARIAL CROSSING PIER CAP & CONCRETE COLLAR SD-SS01 SD-SS02 SD-SS03 SD-SS04 SD-SS05 SD-SS06 SD-SS07 SD-SS08 SD-SS09 SD-SS10 SD-SS11 SD-SS12 SD-SS13 SD-SS14 SD-SS15 SD-SS16 SD-SS17 SD-SS18 SD-SS19
3 GENERAL NOTES 1. ALL PIPE SHALL BE P.V.C. SDR-35 PIPE. OTHER PIPES SHALL BE SUBJECT TO APPROVAL BY THE CITY ENGINEER. 2. LATERALS SHALL INCLUDE 4" TEE WYE BEND, PIPE INSTALLED 10 FEET DOWNSTREAM FROM THE WATER MAIN SERVICE ON EACH LOT, UNLESS OTHERWISE INDICATED ON THE PLANS. 6" LATERALS REQUIRE MANHOLE AT MAIN SEWER PIPE. 3. PIPE JOINTS SHALL CONFORM TO ASTM DESIGNATIONS FOR P.V.C. PIPE. 4. UNLESS OTHERWISE NOTED, ALL MATERIAL AND CONSTRUCTION SHALL CONFORM TO THE STANDARD SPECIFICATION AND/OR SPECIAL PROVISIONS. 5. IN THE EVENT AN ITEM IS NOT COVERED IN THE CITY OF ALLEN SPECIFICATIONS, THE CITY ENGINEERS'S DECISION SHALL APPLY. 6. DROP MANHOLE REQUIRED FOR GRADE DIFFERENCES OF 18" OR GREATER. 7. TV CAMERA, MANDREL, AIR TEST AND VACUUM TEST LINE/MANHOLE AFTER ALL UTILITIES HAVE BEEN INSTALLED. 8. LINE WILL BE RE-AIR TESTED AFTER PAVING AND ALL UTILITIES HAVE BEEN INSTALLED. 9. TWENTY ONE (21) MONTHS INTO MAINTENANCE PERIOD, ALL LINES WILL BE CAMERA INSPECTED FOR SAGS, SETTLEMENTS, SEPARATION, ETC,. 10. SHALLOWER PARALLEL LINE REQUIRED WHEN FLOW LINE OF EXCEEDS 12 FT. DEPTH. VERTICAL DROP CONNECTIONS NOT PERMITTED. GENERAL NOTES AUG SD-SS01
4 1/4 O.D 4" MIN. 1/4 O.D 3" MIN. (6" MIN. IN ROCK) EMBEDMENT DETAILS 3" MIN. MAY 2017 SD-SS02 CLASS B-1 EMBEDMENT P.V.C. PRESSURE SEWER PIPE ONLY CRUSHED STONE SHALL BE 3/4", PASSING #4 SIEVE CLASS A-1 EMBEDMENT CONCRETE CAP
5 CLASS "B" CONCRETE BRICK OR CONCRETE BLOCK SUPPORT CRUSHED STONE EMBEDMENT DETAILS MAY 2017 SD-SS03
6 OVERFLOW SCREW ON FITTING 4" PVC PIPE ENLARGE DETAIL SEE ENLARGE DETAIL SIDEWALK 1' ROW/PROPERTY LINE EXTEND ABOVE GROUND AND PLUG with EZ-FLO " SEWER RELIEF VALVE OR APPROVE EQUAL. SEE ENLARGE DETAIL FINISH GRADE CONCRETE BLOCK MIN. WIDTH = O.D. +12" EXISTING SERVICE MAIN BEND AS REQUIRED CONCRETE NOTE: TWO-WAY CLEANOUT AT PROPERTY LINE 1. NO RISER OR CAPS WILL BE ACCEPTED IN THE SIDEWALK. (NEW CONSTRUCTION ONLY) 2. ALL CLEAN-OUT CAPS MUST BE FLUSH WITH FINISHED GRADE AND USE EZ-FLO OR APPROVED EQUAL CAPS. FINISHED PRODUCT SHALL BE MOWABLE. TWO-WAY CLEANOUT FOR EXISTING LATERAL FEB SD-SS04
7 SERVICE NEW CONSTRUCTION MARCH SD-SS05 ROW/PROPERTY LINE OVERFLOW SCREW ON FITTING EXTEND ABOVE GROUND AND PLUG with EZ-FLO " SEWER RELIEF VALVE OR APPROVE EQUAL. 4" PVC PIPE ENLARGE DETAIL RESIDENCE SIDEWALK DEVELOPER 1' MIN ABOVE FINISH GRADE FINISH GRADE REMOVE EXISTING SEWER LATERAL TO GRADE OF PLUMBED SERVICE. HOME BUILDER TO POUR CONCRETE 24" LONG 6" AROUND PIPE. 4" P.V.C. PIPE MAIN SLOPE AS REQ'D. BY PLUMBING CODE NOTES : DEVELOPER INSTALLED PLUG TAKEN OFF. HOME BUILDER TO INSTALL "CT" ADAPTER TO CONNECT EXISTING 4" SERVICE LINE. HOME BUILDER CONCRETE BLOCK MIN. WIDTH = O.D.+12" 1. SEWER LATERAL SHALL BE LOCATED 10-FT. DOWNSTREAM OF LOT CENTERLINE AND INSTALLED AT MINIMUM 2% SLOPE. (UNLESS OTHERWISE APPROVED BY COA ENGINEERING DEPT). 2. DEVELOPER SHALL INSTALL SEWER LATERAL TO PROJECT 1' MINIMUM ABOVE GRADE, AFTER PASSING VIDEO INSPECTION, DEVELOPER SHALL CAP, & PLUG SERVICE 1' MINIMUM ABOVE FINISHED GRADE. (NEW CONSTRUCTION ONLY) 3. BUILDER SHALL UNCOVER AND REMOVE SEWER LATERAL PIPE AS REQUIRED TO CONNECT HOME PLUMBING. LATERAL SHALL BE 3' BELOW FINISHED GRADE & TV INSPECTED BY BUILDER ONCE MORE PRIOR TO PLUMBING ROUGH IN. (NEW CONSTRUCTION ONLY) 4. ALL TV INSPECTIONS (BY DEVELOPER/BUILDER OR CONTRACTOR) SHALL REQUIRE THE INTRODUCTION OF WATER INTO LINE, AS REQUIRED TO CONFIRM NO SAGS/BELLIES ARE PRESENT. 3' 1' MIN
8 4" P.V.C. SANITARY SEWER LATERAL AT 2% MIN. SLOPE 4" P.V.C. SANITARY SEWER LATERAL AT 2% MIN. SLOPE 4" 6" 2000 P.S.I CONCRETE BLOCKING TEE WYE 4" 4" SECTION B-B A P L A N COLLECTION SEWER CRUSHED STONE B 4" 6" 2000 P.S.I CONCRETE BLOCKING 4" P.V.C. SANITARY SEWER LATERAL AT 2% MIN. SLOPE SECTION A-A TEE WYE TYPICAL SEWER HOUSE SERVICE CONNECTION TYPICAL SEWER HOUSE SERVICE CONNECTION JAN SD-SS06
9 A BASS & HAYS CASING 339 6" SPIGOT PLUG J.M. MNFG. CAT # OR APPROVED EQUAL UNDISTURBED GROUND 2" SLAB. 2'-10" LONG 2000 LB. CONCRETE OR CLASS "A" 3000 P.S.I. IF LOCATED IN ROADWAY. BASS & HAYS CASING 339 2" SLAB. 2'-10" LONG 2000 LB. CONCRETE OR CLASS "A" 3000 P.S.I. IF LOCATED IN ROADWAY. STANDARD CLEANOUT CRUSHED STONE EMBEDMENT REQUIRED 6" CLEAN OUT STACK (P.V.C. PIPE) UNDISTURBED GROUND 2000 LB. CONCRETE 6" CLEAN OUT STACK WYE SOIL 4" 4" PLUG 2000 LB. CONCRETE CRUSHED STONE EMBEDMENT REQUIRED NOT LESS THAN 3" MAY 2006 SD-SS07 SECTION A-A STANDARD CLEANOUT A SIDE ELEVATION
10 FRAME AND COVER SEE COA DETAIL SD-SS14 PRECAST CONCRETE ADJUSTMENT RINGS (SET IN MORTAR BED AND BRING TO GRADE) MAXIMUM RING ADJUSTMENT=18" CLASS "F" CONCRETE MONOLITHIC 4000 P.S.I. CONCRETE FOR CAST-IN-PLACE MANHOLES STUBOUTS TO BE A MINIMUM OF 5' LONG WITH CONCRETE CRADLE UNDER ENTIRE LENGTH. COUPLING W/O-RING RUBBER GASKETS, KOR-N-SEAL, A-LOK OR APPROVED EQUAL. STANDARD CAST-IN-PLACE MANHOLE NOTE: IF FALSE MANHOLE BOTTOMS ARE REQUIRED, THEY SHALL BE CONSTRUCTED, INSTALLED AND REMOVED. CAST-IN-PLACE NOTES: 1. KEYWAYS REQUIRED FOR ALL CONSTRUCTION JOINTS. 2. P.V.C. WATER STOP REQUIRED FOR ALL JOINTS IN LOWER 4'-0" OF MANHOLES 3. CONCRETE SHALL BE 4000 P.S.I. 4. ALL MANHOLES SHALL PASS VACUUM TEST AS PER NCTCOG SPECIFICATIONS CAST-IN-PLACE MANHOLE DEC 1992 MAY 2010 SD-SS08
11 TYPE "S" MANHOLE CAST IN PLACE DEC 1992 AUG SD-SS09 MANHOLE FRAME CAST IN ROOF W/CONTINUOUS POUR FROM BASE. ROOF OPTIONS A A FIRM, WELL DRAINED MATERIAL OR ROCK FOUNDATION PER NCTCOG SPECIFICATION, SECTION NOTES 1. IF FALSE MANHOLE BOTTOMS REQUIRED, THEY SHALL BE CONSTRUCTED, INSTALLED AND REMOVED. TYPE "S" MANHOLE (CAST IN PLACE) 2. ALL MANHOLES SHALL PASS VACUUM TEST AS PER NCTCOG SPECIFICATIONS 30" (6') CONSTRUCTION JOINT WITH KEYWAY WATERSTOP AND #3'S 12" O.C. EXTENDING 9" INTO WALL (NOT REQUIRED FOR CONTINUOUS POUR). SECTION A #3'S AT 6" O.C.E.W. MANHOLE LID SHOULD BE IN LINE WITH UPSTREAM PIPE WHERE POSSIBLE 36" PRESSURE TYPE MANHOLE FRAME AND COVER SEE COA DETAIL SD-SS17 #3'S AT 6" O.C.E.W. PRESSURE TYPE MANHOLE FRAME AND COVER SEE COA DETAIL SD-SS17 CONCRETE CONE PRESSURE TYPE MANHOLE FRAME AND COVER SEE COA DETAIL SD-SS17 ASBESTOS CEMENT COUPLING WITH O-RING RUBBER GASKET FOR PIPE OTHER THAN CLAY OR CONCRETE, ALTERNATE COUPLINGS MUST BE APPROVED BY CITY ENGINEER. STUBOUT TO BE FITTED WITH STOPPER OR CAP. STUBOUTS TO BE A MIN. OF 5' LONG W/ CONCRETE CRADLE (FROM SAME POUR AS BASE) UNDER ENTIRE LENGTH. PER NCTCOG SPECIFICATION, TRANSITION DETAIL FOR 5' AND 6'
12 STANDARD 2 X 4 KEYWAY ROUGHEN EDGES PRIOR TO MAKING SECOND POUR. PROVIDE 4" HEAVY DUTY P.V.C. WATERSTOP AT ALL CONSTRUCTION JOINTS. KEYWAY WITH WATERSTOP KEYWAY WITH WATERSTOP AUG SD-SS10
13 8" X 30" DIA. PRECAST REINFORCED CONCRETE GRADE RINGS (SET IN MORTAR BED AND BRING TO GRADE) RINGS 18" MAX. CAST IRON MANHOLE FRAME AND COVER SUITABLE FOR HEAVY TRAFFIC (SEE COA DETAIL SD-SS14 MORTAR CONCENTRIC MANHOLE CONE. SEE NOTE FOR LARGER THAN 48" DIA. JOINT WITH NEOPRENE "O" RING GASKET AND MASTIC 30" 3' FOR 48" DIA. MANHOLE NOTE A: MANHOLE DIAMETER LARGER THAN 48" I.D. PRE-CAST FLAT TOP MANHOLE COVER AS PER ASTM C478 SHALL BE INSTALLED. FOR HEAVY TRAFFIC SPECIAL DESIGN REQUIRED. SEE DETAIL. REFER TO NCTCOG SPECIFICATIONS (LATEST EDITION) FOR : REINFORCED CONCRETE PIPE C-76. CLASS III WITH RUBBER GASKET JOINT. 1. CONCRETE CLASS. 2. CONCRETE PIPE MATERIAL. 3. MANHOLE MATERIAL. 4. RUBBER GASKET JOINT. VARIABLE 1" GROUT SPACEFILL WITH CEMENT MORTAR OR MASTIC MATERIAL. 6" MIN BOTTOM SECTION OF MANHOLE IN LENGTHS OF ONE (1), TWO (2) OR THREE (3) FEET, TO BE SET ON 1" OF LEVEL GROUT. COUPLING WITH O-RING RUBBER GASKET WITH P.V.C. PIPE. STUBOUTS TO PL OR ESMT. (MIN. 5' LONG) WITH CONCRETE CRADLE UNDER ENTIRE LENGTH. 12" MIN. 6" MIN. PIPE I.D VARIABLE GROUT CLASS "F" CONCRETE BASE FOR PRECAST MANHOLE. PRECAST CONCRETE PIPE MANHOLE ALTERNATE "A" NOTE: FALSE BOTTOMS ARE REQUIRED IN MANHOLES, AND SHALL BE CONSTRUCTED ONCE MANHOLE IS IN SERVICE. FALSE BOTTOM SHALL BE REMOVED ONCE CONSTRUCTION ACTIVITY IS COMPLETE. ALL MANHOLES SHALL PASS VACUUM TEST AS PER NCTCOG SPECIFICATIONS PRECAST CONCRETE PIPE MANHOLE ALTERNATE "A" DEC 1992 MAY SD-SS11
14 MANHOLE RING AND COVER TO BE SET TO GRADE OF PROPOSED PAVEMENT, OR FLUSH WITH PROPOSED GROUND GRADE. STANDARD CAST IRON MANHOLE FRAME AND COVER SEE COA DETAIL SD-SS14 MORTAR COATING USE PRECAST CONCRETE GRADE RINGS TO RAISE TO GRADE 1" MIN. 18" MAX, AS PER NCTCOG SPECIFICATION SECTION NOTE A: MANHOLE DIAMETER LARGER THAN 48" I.D. PRE-CAST FLAT TOP MANHOLE COVER AS PER ASTM C478 SHALL BE INSTALLED. FOR HEAVY TRAFFIC SPECIAL DESIGN REQUIRED. SEE DETAIL. NEOPRENE "O-RING" GASKET AND MASTIC. REFER TO NCTCOG SPECIFICATION (LATEST EDITION) FOR : 1. CONCRETE CLASS. 2. CONCRETE PIPE MATERIAL. 3. MANHOLE MATERIAL. 4. RUBBER GASKET JOINT. 30" VARIES INTERMEDIATE RISER AVAILABLE IN : 1',2' & 3' 3' TO 5' 3' FOR 4' MANHOLE AND 4' LENGTHS (USE MINIMUM NO. OF RISERS) KOR-N-SEAL, OR APPROVED EQAUL. VOIDS TO BE GROUTED 6" TO 18" PRESS-SEAL OR APPROVED EQUAL. CONN. OVER 18". TOP OF PIPE 8" BASE RISER (VARIES) EMBEDMENT AS SPECIFIED BY STANDARD DETAILS. KOR-N-SEAL, OR APPROVED EQUAL. VOIDS TO BE GROUTED 1' MIN. 5' STONE CUSHION FOUNDATION AS PER NCTCOG SPECIFICATIONS SECTION NOTE: FALSE BOTTOMS ARE REQUIRED IN MANHOLES, AND SHALL BE CONSTRUCTED ONCE MANHOLE IS IN SERVICE. FALSE BOTTOM SHALL BE REMOVED ONCE CONSTRUCTION ACTIVITY IS COMPLETE. ALL MANHOLES SHALL PASS VACUUM TEST AS PER NCTCOG SPECIFICATIONS GEOTEXTILE MATERIAL, AS PER NCTCOG SPECIFICATION SECTION PRECAST CONCRETE MANHOLE ALTERNATE "B" PRECAST CONCRETE PIPE MANHOLE ALTERNATE "B" DEC 1992 MAY 2017 SD-SS12
15 CAST IRON FRAME AND COVER FOR MANHOLE SHALL BE SUITABLE FOR HEAVY TRAFFIC. SEE COA DETAIL SD-SS14 30" DIA. BOTTOM SECTION OF RISER PIPE BUTT AND BELL REINFORCED CONCRETE PIPE C-76, CLASS III WITH RUBBER GASKET JOINT. GROUT SPACE TO BE FILLED WITH CEMENT MORTAR OR MASTIC MATERIAL. 60" AND 72" DIA. CLASS "F" CONCRETE BASE FOR PRECAST MANHOLE. NOTE: FALSE BOTTOMS ARE REQUIRED IN MANHOLES, AND SHALL BE CONSTRUCTED ONCE MANHOLE IS IN SERVICE. FALSE BOTTOM SHALL BE REMOVED ONCE CONSTRUCTION ACTIVITY IS COMPLETE. PRECAST CONCRETE FLAT TOP MANHOLE ALL MANHOLES SHALL PASS VACUUM TEST AS PER NCTCOG SPECIFICATIONS PRECAST CONCRETE FLAT TOP MANHOLE DEC 1992 MAY 2017 SD-SS13
16 (4) Ø7/8" BOLT HOLES ON A 35 1/2" DIA B.C. CUSTOM LOGO A A (2) CAST PICKBARS CITY OF ALLEN SLIP RESISTANT SURFACE 1" FLAT FACE LETTERING 1/2" FLAT FACE LETTERING 32" DIA 1 1 2" 33 11/16" DIA 32 1/4" DIA 1 1 2" 4" 30" DIA 32 1/4" DIA 38" DIA SECTION A-A 1 1 2" NOTE! FRAME IS REVERSIBLE CAN BE INSTALLED AS A TOP FLANGE UNIT. PRODUCT NUMBER DESIGN FEATURES SPECIAL FEATURES DESIGNATES MACHINE SURFACE CAST IRON GRATE AND FRAME SEPT 2016 SD-SS14
17 FINISH GRADE CONCRETE GRADE RINGS FOR ADJUSTMENT 18" MAXIMUM. STANDARD MANHOLE COVER SEE COA DETAIL SD-SS14 30" MINIMUM 3" THICK CONCRETE 3000 P.S.I. ENCASE IN CONCRETE MIN. 6" AROUND DROP PIPE. FLUSH WITH INSIDE FACE OF MANHOLE. SAME AS MAIN- 12" MAX. TOP OF PIPE ON MAIN LINE FOR PIPE SMALLER THAN 24" DIA. 12" MAX. MANHOLE DROP CONNECTION NOTES : 1. BACKFILL AND INVERT TO CITY SPECIFICATIONS. 2. ALL CAST IRON FITTINGS SHALL BE DOMESTIC. MANHOLE DROP CONNECTION MAY 2010 SD-SS15
18 FINISH GRADE CONCRETE GRADE RINGS FOR ADJUSTMENT 18" MAX STANDARD MANHOLE COVER SEE COA DETAIL SD-SS14 3' MIN. 15" (5') 1' MIN. 2' OR 3' CUT HOLE IN TOP OF TEE BELL & SPIGOT TEE 30" PIPE VOID UNDER PIPE TO BE COMPACTED STAINLESS STEEL EXPANSION BOLTS ON 12" CENTERS 1' MIN. 30" (6') 5' (MIN.) 8' (MIN.) INTERIOR DROP MANHOLE DETAIL INTERIOR DROP MANHOLE DETAIL JAN 1993 MAY 2010 SD-SS16
19 (4) 1" DIA BOLT HOLES ON A " DIA B.C. CUSTOM LOGO A A (2) CAST PICKBARS CITY OF ALLEN (4) SS BOLTS WITH 1 2" STEEL AND RUBBER WASHERS SLIP RESISTANT SURFACE 3/4" FLAT FACE LETTERING 1/2" FLAT FACE LETTERING 32" DIA 1 1 2" 1 4 " NEOPRENE GASKET 33 11/16" DIA 32 1/4" DIA 1 1 2" 4" 30" DIA 32 1/4" DIA 38" DIA SECTION A-A 1 1 2" NOTE! FRAME IS REVERSIBLE CAN BE INSTALLED A TOP FLANGE UNIT. PRODUCT NUMBER DESIGN FEATURES SPECIAL FEATURES DESIGNATES MACHINE SURFACE PRESSURE TYPE MANHOLE FRAME AND COVER MAY 2010 SD-SS17
20 ENGINEERING DESIGN SHALL BE SUBMITTED FOR EACH CROSSING. PIERS SHALL BE PLACED AT MAXIMUM SPAN DISTANCE AS DICTATED BY DESIGN. CONSTRUCT CONCRETE COLLAR JOINT LENGTH VARIES AERIAL CROSSING JOINT LENGTH VARIES JOINT LENGTH VARIES CONSTRUCT CONCRETE COLLAR MANHOLE MANHOLE CONCRETE COLLAR 3' MIN. AERIAL CROSSING PIPE MH TO MH STEEL PIPE SHALL BE OF THE TYPE SHOWN IN THE SPECIFICATIONS. STEEL PIPE SHALL HAVE THICKNESS REQUIRED FOR SIZE AND SPAN WITH MINIMUM WALL THICKNESS OF 3/8 INCHES. PIPE COUPLING SHALL BE PLACED A MAXIMUM OF 5 FEET FROM CENTERLINE OF PIERS. CONCRETE ENCASEMENT NOTE : STEEL PIPE SHALL BE JOINT WITH STEEL COUPLING 18" DIAMETER PIERS MINIMUM (SEE DETAIL) CONCRETE ENCASEMENT PIER PLACEMENT AND SPACING SHALL BE SUBMITTED TO CITY FOR APPROVAL. PIER SHALL EXTEND 6 FEET MINMUM INTO SHALE OR ROCK. MATERIALS SHALL CONFORM TO THE SPECIAL PROVISIONS AND/OR THE STANDARD SPECIFICATIONS. MANHOLE TO MANHOLE AERIAL CROSSING DETAIL AERIAL CROSSING AUG 2006 SD-SS18
21 PIER CAP & CONCRETE COLLAR AUG 2006 SD-SS " X 1 4" L STRAPS HOT DIPPED GALVANIZED AFTER FABRICATION. 30" MIN O.D. + 6" 2 O.D. + 6" 1" NON-SHRINK GROUT. 3 4 " CHAMPER 3" 18" DIA. MIN. AERIAL CROSSING PIER CAP DETAIL 8" 4" NOTE: CONSTRUCT MINIMUM WIDTH OF COLLAR ALONG PIPE= 2'-0" (1'-0" EACH SIDE OF JOINT). 3 4 "Ø X 1' BOLT WITH HEX NUT AND WASHER. HOT DIPPED GALVANIZED. * O.D. OF LARGEST PIPE AT EACH COLLAR. AERIAL CROSSING CONCRETE COLLAR DETAIL MATERIALS SHALL CONFORM TO THE SPECIAL PROVISIONS AND/OR THE STANDARD SPECIFICATIONS. R=1/2 O.D. + 3" 8" see Detail PIPE O.D.* 8" O.D. + 16" 3 4 " CHAMPER 10" 1/2 O.D.* + 8" O.D. + 16" 1/2 O.D.* + 8" 120 DETAIL
PERMANENT PAVEMENT REPAIR NO SCALE
SAWCUT EXISTING PAVEMENT 2" BITUMINOUS CONCRETE SURFACE COURSE, CLASS 2 (MIN) CLEAN EDGE PRIOR TO PAVING AND PAINT WITH LIQUID BITUMEN. INSTALL SEALANT OVER JOINT UPON COMPLETION 2" BITUMINOUS CONCRETE
More informationONE PIPE LENGTH MAX (REFER TO 1/4"/FT SLOPE (MIN) 5'-0" (MIN) OR 4" LATERAL NOTE #1) INCREASER RIGHT-OF-WAY/ 4"x6" REFER TO TYPICAL EXCAVATION,
VENT CAP (MUSHROOM TYPE) SOLID CAP EXIST GRADE MIN BUILDING REFER TO NOTE #4 MIN CONCRETE SIDEWALK CURB OR EDGE OF SIDEWALK STREET CLEANOUT (REFER TO NOTE #3) VENT PIPE 4" PVC 6" PVC CLEANOUT CONCRETE
More informationTOWN OF HOLLY SPRINGS ENGINEERING DEPARTMENT
COMPACTED BACK FILL COMPACTED BACK FILL UNDISTURBED TRENCH WALL INITIAL BACKFILL SPRING LINE OF PIPE HAUNCHING EMBEDMENT MATERIAL SPRING LINE OF PIPE HAUNCHING EMBEDMENT MATERIAL MIN. BEDDING BEDDING MINIMUM
More informationCITY OF FARGO SPECIFICATION SANITARY SEWER
SECTION 1200 SECTION 1200 CITY OF FARGO SPECIFICATION SANITARY SEWER PART 1 DESCRIPTION OF WORK (revised March, 2007) The work to be done under these Specifications and the accompanying drawings consist
More informationMANHOLES, VAULTS AND CATCH BASINS SECTION A. Section Soil and Aggregate Materials. C. Section Storm Drainage Systems
SECTION 02607-1 1.0 GENERAL 1.1 SCOPE: A. This section covers the work necessary for the construction of sanitary and storm system manholes, catch basins, and miscellaneous concrete structures complete.
More informationSECTION 39 - MANHOLES TABLE OF CONTENTS 39-1 GENERAL PRECAST CONCRETE MANHOLES
Section SECTION 39 - MANHOLES TABLE OF CONTENTS 39-1 GENERAL... 39-1 39-2 PRECAST CONCRETE MANHOLES... 39-1 39-2.01 Precast Concrete Storm Drain Manholes... 39-1 39-3 SADDLE MANHOLES... 39-2 39-3.01 Saddle
More informationCity of Middletown WATER & SEWER DEPARTMENT 82 Berlin Street Middletown, CT TEL: (860) FAX: (860)
City of Middletown WATER & SEWER DEPARTMENT 82 Berlin Street Middletown, CT 06457 TEL: (860) 638-3500 FAX: (860) 343-8091 GENERAL REQUIREMENTS SANITARY SEWER MAIN AND LATERAL INSTALLATION JANUARY 2017
More informationSANITARY MANHOLE S-1 ENGINEERING DEPARTMENT PLATE NUMBER NEENAH R-1733 CASTING ASSEMBLY OR AS NOTED ON PLAN OR APPROVED EQUAL.
"INFI-SHIELD" SEAL OR EQUAL. NEENAH R-1733 CASTING ASSEMBLY OR AS NOTED ON PLAN OR APPROVED EQUAL. 27" HDPE ADJUSTING RINGS (2 MIN., 1' MAX. OF RINGS). ECCENTRIC CONE 4.0' HIGH 48" 5" P2 PROFILE GASKET
More informationB. Fiberglass for construction in back lot easements placed on cast-in-place base.
Section 02083 PART 1 G E N E R A L 1.01 SECTION INCLUDES A. Fiberglass manholes for unpaved areas placed on top of a precast base to form a manhole. B. Fiberglass for construction in back lot easements
More informationSANITARY SEWER GENERAL NOTES. Sanitary Sewer Construction Notes
Sanitary Sewer Construction Notes 1. All public sanitary sewer systems shall be constructed in accordance with the latest edition of the Washington State Department of Transportation Standard Specifications
More informationSECTION MANHOLES AND STRUCTURES. A. Section Includes: 1. Manholes for water, storm drain and sanitary sewer systems.
SECTION 33 05 13 MANHOLES AND STRUCTURES PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Manholes for water, storm drain and sanitary sewer systems. B. Related Sections: 1. Section 03 20 00 - Concrete
More informationSECTION D2 MANHOLES AND CATCH BASINS GENERAL MATERIALS
SECTION D2 MANHOLES AND CATCH BASINS GENERAL This section covers the installation of new manholes, catch basins, drop inlets, drywall structures and the installation of hoods in existing catch basins.
More informationSANITARY SEWERS. B. Construct or relocate building sanitary sewer services, stubs, and connections.
SANITARY SEWERS PART 1 - GENERAL 1.01 SECTION INCLUDES A. Sanitary Sewer Gravity Mains B. Sanitary Sewer Force Mains C. Sanitary Sewer Services 1.02 DESCRIPTION OF WORK A. Construct sanitary sewer gravity
More informationPART 1 COMMON FOR WATER & WASTEWATER CONSTRUCTION TITLE By Other Than Open Cut (Non-T.x.D.O.T. - Non Railroad) --- 101 Highway Crossing - All Wastewater Mains & Water Mains 12" and Smaller in Diameter.
More informationSECTION 39 - MANHOLES TABLE OF CONTENTS
Section SECTION 39 - MANHOLES TABLE OF CONTENTS Page 39-1 GENERAL... 39.1 39-2 CONCRETE MANHOLES... 39.1 39-2.01 NOT USED... 39.1 39-2.02 Concrete Storm Drain Manholes... 39.1 39-3 SADDLE SEWER MANHOLES...
More informationCHAPTER 6 - SANITARY SEWER
CHAPTER 6 - SANITARY SEWER 6.1 GENERAL This section covers the requirements for PVC plastic sewer pipe materials and installation in sanitary sewer construction. 6.2 PIPE PVC gravity sewer pipe and fittings
More informationSECTION STORM DRAINAGE
SECTION 02720 STORM DRAINAGE PART 1 - GENERAL 1.01 WORK INCLUDED A. Trenching and other excavation. B. Ground water control. C. Pipe bedding. D. Installation of storm drains and appurtenances. E. Installation
More information2.1.2 Minimum wall thickness shall be 90 mm Frames and covers shall be bitumen coated by dipping.
1.0 GENERAL 1.1 Scope 2.0 PRODUCTS 1.1.1 The work shall consist of the construction, renovation or the adjustment of manholes and/or catchbasins as detailed on the plans or where designated by the Engineer
More informationCATCH BASIN ST-1 ENGINEERING DEPARTMENT PLATE NUMBER 3.33' 3.0' 2.0' 4.33' 3.0' 4.0' 1.00' TO BACK OF CURB LINE
3.33' 3.0' 2.0' 4.33' 4.0' 3.0' 1.00' TO BACK OF CURB LINE TOP OF GRATE ELEV. - SEE PLAN NEENAH CASTING R-3067-V OR AS NOTED ON PLANS. "INFA-SHIELD" SEAL OR EQUAL. RINGS (2 MIN., 1' MAX. OF RINGS AND MORTAR).
More informationTable of Contents. Section Structures for Sanitary and Storm Sewers Section Includes Description of Work 1. 1.
SUDAS Standard Specifications Division 6 - Structures for Sanitary and Storm Sewers Table of Contents Section 6010 - Structures for Sanitary and Storm Sewers Page No. Part 1 - General 1.01 Section Includes
More informationNOTE: 1) PRIOR TO BEGINNING WORK TRANSFER RIM ELEV. FROM MH K1 TO A TEMPORARY BENCH MARK FOR USE AS CONTROL DURING CONSTRUCTION. 2) CONTRACTOR TO INST
NOTE: 1) PRIOR TO BEGINNING WORK TRANSFER RIM ELEV. FROM MH K1 TO A TEMPORARY BENCH MARK FOR USE AS CONTROL DURING CONSTRUCTION. 2) CONTRACTOR TO INSTALL MANHOLE LIDS FLUSH WITH EXISTING GROUND SURFACE.
More informationFOX METRO WATER RECLAMATION DISTRICT MANHOLE / SEWER PIPE MATERIALS AND INSTALLATION SPECIFICATIONS MATERIALS 1. PIPE & FITTINGS
FOX METRO WATER RECLAMATION DISTRICT MANHOLE / SEWER PIPE MATERIALS AND INSTALLATION SPECIFICATIONS MATERIALS 1. PIPE & FITTINGS Rev: 3/26/18 Pipe and fittings used in sanitary sewer construction shall
More informationSection 403. DRAINAGE STRUCTURES
403.01 Section 403. DRAINAGE STRUCTURES 403.01. Description. This work consists of adjusting, constructing, or temporarily lowering drainage structures and cleaning existing drainage structures and leads
More information2. A preconstruction meeting with the TWA s staff is required prior to initiating construction.
General: 1. Construct utilities in accordance to TWA approved plans and shop drawings. Any deviation from the approved plans shall be approved by the DEVELOPER S ENGINEER and TWA 2. A preconstruction meeting
More informationSECTION PRECAST CONCRETE MANHOLES
SECTION 02601 PRECAST CONCRETE MANHOLES PART 1 GENERAL 1.1 The work specified in this section shall include the furnishing, hauling, and placing of all precast manholes shown on the drawings and as specified
More information1. Division 01 Section General Requirements - Temporary Facilities and Controls. 2. Division 31 Section Earthwork.
PAGE 334000-1 SECTION 334000 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification sections,
More informationNORTH HARRIS COUNTY REGIONAL WATER AUTHORITY CAST-IN-PLACE. Section CAST-IN-PLACE CONCRETE MANHOLES
PART 1 GENERAL 1.01 SUMMARY This Section includes: Section 02081 CAST-IN-PLACE A. Cast-in-place concrete manholes for sanitary sewers and storm sewers, including box sewers. B. Pile-supported concrete
More informationSECTION SANITARY SEWER SYSTEM
SECTION 02530 SANITARY SEWER SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. Section includes sanitary sewer system piping for collection of wastewater. B. Related Sections include but are not limited to: 1. Division
More informationTABLE OF CONTENTS
DIVISION 33: SEWER AND SEPTIC SYSTEMS 33 3633 UTILITY SEPTIC TANK DRAINAGE FIELD TABLE OF CONTENTS 33 0000-1 SECTION 33 3633-- UTILITY SEPTIC TANK DRAINAGE FIELD PART 1 - GENERAL 1.1 SUMMARY A. Includes
More informationSANITARY SEWERS. B. Construct or relocate building sanitary sewer services, stubs, and connections.
SANITARY SEWERS PART 1 - GENERAL 1.01 SECTION INCLUDES A. Sanitary Sewer Gravity Mains B. Sanitary Sewer Force Mains C. Sanitary Sewer Services 1.02 DESCRIPTION OF WORK A. Construct sanitary sewer gravity
More informationTable of Contents. Section Structures for Sanitary and Storm Sewers Section Includes Description of Work 1. 1.
SUDAS Standard Specifications Division 6 - Structures for Sanitary and Storm Sewers Table of Contents Section 600 - Structures for Sanitary and Storm Sewers Page No. Part - General.0 Section Includes.0
More informationITEM NO. 853 SANITARY SEWER GLASS-FIBER REINFORCED POLYESTER (FRP) MANHOLES
ITEM NO. 853 SANITARY SEWER GLASS-FIBER REINFORCED POLYESTER (FRP) MANHOLES 853.1 DESCRIPTION: This item shall govern the construction of FRP sanitary sewer complete in place and the material therein,
More informationSECTION SANITARY UTILITY SEWERAGE PIPING
SECTION 33 31 00 SANITARY UTILITY SEWERAGE PIPING PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Sanitary sewer pipe and fittings. 2. Underground pipe markers. 3. Connection to existing manholes. 4.
More informationSECTION PRECAST CONCRETE MANHOLES
SECTION 03 48 10 PRECAST CONCRETE MANHOLES PART 1: GENERAL 1.01 SECTION INCLUDES A. Precast concrete manholes for sanitary sewers and water lines or as indicated on the Drawings. B. Precast concrete sanitary
More informationChanges for the. TOHOPEKALIGA WATER AUTHORITY Standards, Specifications and Details
Changes for the 2017 TOHOPEKALIGA WATER AUTHORITY Standards, Specifications and Details The following changes are made to the existing standards and details to clarify or improve existing information.
More informationA. Codes and Standards that are standard at the University. C. Coordinate cleanout locations with Architect.
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationSECTION UTILITY POLYETHYLENE CONTAINMENT PIPE SYSTEMS
SECTION 02670 UTILITY POLYETHYLENE CONTAINMENT PIPE SYSTEMS PART 1 - GENERAL 1.01 WORK INCLUDED A. Trenching and other excavation. B. Ground water control. C. Pipe bedding. D. Installation of containment
More informationSECTION FACILITY SANITARY SEWERS
SECTION 22 13 13 FACILITY SANITARY SEWERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationCHAPTER 6. Sanitary Sewer
CHAPTER 6 Sanitary Sewer A. Introduction All proposed developments, subdivisions, and buildings must have a properly designed and constructed sanitary sewer collection system. The system shall provide
More informationCounty of Sacramento Standard Construction Specifications January 1, 2008 TECHNICAL PROVISIONS
County of Sacramento Standard Construction Specifications January 1, 2008 TECHNICAL PROVISIONS SECTION 39 MANHOLES 39-1 GENERAL Sewer and storm drain manholes, consisting of precast concrete manholes or
More informationSECTION SANITARY SEWERAGE PART 1 GENERAL 1.01 RELATED DOCUMENTS
SECTION 02530 - SANITARY SEWERAGE PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,
More informationDIVISION 3: SEWER. Improvement Design Standards City of Dundee Oregon. Division 3 : Sewer Page 1
DIVISION 3: SEWER 3.1 DESIGN CRITERIA A. APPLICABILITY 1. These Design Standards shall govern all construction and upgrading of public sanitary sewer facilities in the City of Dundee and applicable work
More informationVALLECITOS WATER DISTRICT SECTION PRECAST REINFORCED CONCRETE MANHOLES
PART 1 GENERAL 1.1 DESCRIPTION A. This section includes materials, testing, and installation of precast concrete manholes, manhole bases, manhole frames, and covers. 1.2 RELATED WORK SPECIFIED ELSEWHERE
More informationSPECIAL SPECIFICATION 5925 Polyvinyl Cloride (PVC) Sewer Pipe and Fittings
1993 Specifications CSJ 0144-01-060 SPECIAL SPECIFICATION 5925 Polyvinyl Cloride (PVC) Sewer Pipe and Fittings 1. General. (1) Scope. This Section includes the furnishing, installation, and subsequent
More informationSECTION UTILITY MANHOLES AND STRUCTURES
SECTION 33 05 14 UTILITY MANHOLES AND STRUCTURES PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Precast reinforced concrete manholes and structures with tongue-and-groove joints with masonry transition
More information4 ft. and 6 ft. Downstream Defender Handling and Installation Instructions
4 ft. and 6 ft. Downstream Defender Handling and Installation Instructions Page 2 Materials Supplied By Hydro International Ledger Angle (x4) Top Slab Top Riser Benching Skirt 4ft./6ft. Downstream Defender
More informationTYPE "A" CATCH BASIN
27" 1.67' TO BACK OF CURB LINE TOP OF GRATE ELEV. - SEE PLAN NEENAH CASTING R-3250-BV OR APPROVED EQUAL. "INFI SHIELD" SEAL OR APPROVED EQUAL RINGS (2 MIN., 1' MAX. OF RINGS AND MORTAR). PLASTER OUTSIDE,
More informationSECTION SANITARY SEWERS
SECTION 02730 SANITARY SEWERS PART 1 GENERAL 1.01 WORK INCLUDED A. Trenching and other excavation. B. Ground water control. C. Pipe bedding. D. Installation of sanitary sewers and appurtenances. E. Backfill
More informationWater and Wastewater Engineering Department
Water and Wastewater Engineering Department Page: WW-.0 WW WASTEWATER GRAVITY MAIN, PROPOSED WW WASTEWATER GRAVITY MAIN, EXISTING FM WASTEWATER (PRESSURE) FORCE MAIN, PROPOSED FM WASTEWATER (PRESSURE)
More informationWASTEWATER REVIEW CHECKLIST. Project Number: Reviewed By: Telephone:
The City of East Point DEPARTMENT OF WATER AND SEWER 1526 East Forrest Ave. Suite 400 East Point, Georgia 30344 FAX (404) 270-7215 www.eastpointcity.org WASTEWATER REVIEW CHECKLIST Project Name: Tax ID
More informationCITY OF NEW BERLIN DEVELOPMENT HANDBOOK SECTION 4 STORM SYSTEM. 1 of 15 Adopted by BPW:
TABLE OF CONTENTS 4... 2 4.1 SPECIFICATIONS... 2 4.1.1 STORM SEWER PIPE... 2 4.1.2 STORM LATERALS (From main to lot line)... 3 4.1.3 CULVERTS... 4 4.1.4 MASONRY ENDWALLS... 5 4.1.5 FLARED END SECTIONS...
More informationELEVATION (A - A) PLAN GATE W ELL JOB NO. SHEET NO. DATE MARCH 2015 OF. Gate Wel Dimensions - Inches
CL Gate Wel Opening East Jordan Iron Works, Inc. Manhole Cover No. 1040 (or approved equal) w/ bolted frame 01-APR-2015 15:29 = I:\MSV8i\Plotting\piblack.ptb V:\201001\\C\8x11_Howell_Det\wm_det01_8x11_wm01.dgn
More informationCONSTRUCTION SPECIFICATION FOR THE INSTALLATION OF ELECTRICAL CHAMBER
ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 602 MARCH 1993 CONSTRUCTION SPECIFICATION FOR THE INSTALLATION OF ELECTRICAL CHAMBER 602.01 SCOPE 602.02 REFERENCES 602.05 MATERIALS TABLE OF CONTENTS
More informationTable of Contents. Section Structures for Sanitary and Storm Sewers Section Includes Description of Work 1. 1.
SUDAS Standard Specifications Division 6 - Structures for Sanitary and Storm Sewers Table of Contents Section 6010 - Structures for Sanitary and Storm Sewers Page No. Part 1 - General 1.01 Section Includes
More informationHAMILTON TOWNSHIP MUNICIPAL UTILITIES AUTHORITY
HEIGHT TO REMOVE STRAINER ELEMENT D C G I E B H F J A Operating Characteristics Meter Normal Operating Range* AWWA Low Flow Maximum Size @100% Accuracy (±1.5%) Standard @95% Accuracy Intermittent Flow
More informationSan Antonio Water System Standard Specifications for Construction ITEM NO. 853 SANITARY SEWER GLASS-FIBER REINFORCED POLYESTER (FRP) MANHOLES
ITEM NO. 853 SANITARY SEWER GLASS-FIBER REINFORCED POLYESTER (FRP) MANHOLES 853.1 DESCRIPTION: This item shall govern the construction of FRP sanitary sewer complete in place and the material therein,
More informationDrainage structure refers to manholes, catch basins, leaching basins, inlets and drop inlets. Drainage structures are designated as follows.
403.01 Section 403. DRAINAGE STRUCTURES 403.01 Description. Adjust, construct, or temporarily lower drainage structures. Clean existing drainage structures and leads as directed by the Engineer. Drainage
More informationA. Gravity-Flow, Nonpressure, Drainage-Piping Pressure Rating: 10-foot head of water (30 kpa).
SECTION 221313 - FACILITY SANITARY SEWERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationSECTION 920 SANITARY AND STORM SEWER MANHOLES
SECTION 920 SANITARY AND STORM SEWER MANHOLES 920.1 GENERAL This section contains items which are relative to the installation of sanitary and storm sewer manholes. 920.2 REFERENCES 920.2.1 ASTM C 43 C
More informationPublic Water Supply District #2 of St. Charles County, Missouri
Public Water Supply District #2 of St. Charles County, Missouri POLICIES, PROCEDURES, AND REQUIREMENTS FOR CONNECTION AND INSPECTIONS OF: RESIDENTIAL WATER AND/OR SEWER SERVICE CONNECTIONS COMMERCIAL WATER
More informationSECTION STORM SEWER COLLECTION SYSTEM
SECTION 02722 STORM SEWER COLLECTION SYSTEM PART 1 GENERAL 1.01 SUMMARY A. This section addresses the installation of storm sewer collection mains and includes the acceptable products, materials, and construction
More informationD. Encase exterior cleanouts in concrete with access cover installed flush with grade.
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationPRECAST CONCRETE MANHOLES. A. Precast concrete manholes for sanitary sewers, storm sewers, and water lines.
Section 02082 PART 1 G E N E R A L 1.01 SECTION INCLUDES A. Precast concrete manholes for sanitary sewers, storm sewers, and water lines. B. Precast concrete sanitary sewer manholes with PVC liner where
More information1.1 SECTION INCLUDES.1 Materials and installation for water mains, hydrants, valves, valve boxes, and valve chambers, including service connections.
Issued 2005/06/01 Section 02511 Water Mains Page 1 of 10 PART 1 GENERAL 1.1 SECTION INCLUDES.1 Materials and installation for water mains, hydrants, valves, valve boxes, and valve chambers, including service
More informationWater and Wastewater Engineering Department
Water and Wastewater Engineering Department Page: WW-.0 WW WASTEWATER GRAVITY MAIN, PROPOSED WW WASTEWATER GRAVITY MAIN, EXISTING FM WASTEWATER (PRESSURE) FORCE MAIN, PROPOSED FM WASTEWATER (PRESSURE)
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 33 3400 STORM UTILITY DRAINAGE PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationSECTION STORM DRAINAGE UTILITIES. B. Section : Site Restoration and Rehabilitation
SECTION 33 40 00 STORM DRAINAGE UTILITIES 1. PART 1 GENERAL 1.1 RELATED WORK A. Section 31 23 00: Excavation and Fill B. Section 32 00 01: Site Restoration and Rehabilitation C. Special Conditions for
More informationPulaski County, Virginia
Pulaski County, Virginia Typical Retaining Wall Details Based on the 2009 International Residential Code CONTENTS Timber Retaining Wall... 2 General Requirements... 2 Wall Construction... 2 Deadmen...
More informationSECTION SANITARY SEWER SYSTEM
SECTION 02731 SANITARY SEWER SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Sanitary sewer system including necessary accessories indicated on drawings and specified in this section. Contractor
More informationCHAPTER 200 STORM SEWER CONSTRUCTION STANDARDS
CHAPTER 200 STORM SEWER CONSTRUCTION STANDARDS Storm Sewer System: 1. Detention/retention of stormwater runoff shall be provided in accordance with the requirements of the DuPage County Countywide Stormwater
More informationSECTION VI SANITARY SEWERS
SECTION VI SANITARY SEWERS VI-1. DESIGN GUIDELINES Sewer collection lines and appurtenant structures within the jurisdiction of City of Paso Robles shall be constructed in accordance with plans prepared
More informationSection 4 Service Lines
Section 4 Service Lines A. General 1. A service line is that portion of a sanitary sewer line that extends from the outer building wall or foundation wall to its connection with the sewer lateral at the
More informationITEM D-701 PIPE FOR STORM DRAINS AND CULVERTS
ITEM D-701 PIPE FOR STORM DRAINS AND CULVERTS 701-1 DESCRIPTION 701-1.1 This item shall consist of the construction of pipe culverts, and storm drains, removal of existing storm pipes, connections to existing
More information100' MAXIMUM DETAIL NOTES: INSTALL 6" MINIMUM PIPE SIZE IN R.O.W. INSTALL 6" CLEANOUT PER STD DETAIL 606.
MAX. 5 C.O. CLEAN OUT REQUIRED AT ALL ANGLE POINTS OVER 5 5' MAXIMUM.MATERIAL LIST: IF GREATER THAN 5', INSTALL ADDITIONAL CLEAN OUT BUILDING CONNECTION. MAX. 5 6" MIN. 5 NOTES: BUILDING.. SEE SECTION
More informationA. Provide floor drains in all restrooms placed a minimum of 7 from back of wet wall, janitor closets, and mechanical rooms.
SECTION 22 13 00 FACILITY SANITARY SEWERAGE PART 1 - GENERAL 1.1 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design.
More informationSummary of the 2011 Changes
The following is a list of amendments to the Residential Site Improvement s, N.J.A.C. 5:21, adopted in 2011. The Notice of Adoption of these changes appeared in the New Jersey Register on May 16, 2011.
More informationPART II. - SPECIFICATIONS AND DESIGN STANDARDS TO CITY OF HEWITT, TEXAS SUBDIVISION ORDINANCE FOR PUBLIC WORKS CONSTRUCTION [TEXT]
PART II. - SPECIFICATIONS AND DESIGN STANDARDS TO CITY OF HEWITT, TEXAS SUBDIVISION ORDINANCE FOR PUBLIC WORKS CONSTRUCTION [TEXT] A. - General. B. - Streets. C. - Stormwater drainage system. D. - Water
More informationITEM NO SLIPLINING SANITARY SEWERS
ITEM NO. 1100 SLIPLINING SANITARY SEWERS 1100.1 DESCRIPTION: Sliplining is accomplished by pulling or pushing liner pipe into existing sewers by use of mechanical or hydraulic equipment. Once in place,
More informationSANITARY WASTE AND VENT PIPING
SECTION 15420 - SANITARY WASTE AND VENT PIPING PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationTCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II
SECTION 221313 - FACILITY SANITARY SEWERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationContact the Jurisdictional Engineer for materials allowed by each jurisdiction.
Design Manual Chapter 3 - Sanitary Sewers 3C - Facility Design 3C-1 Facility Design A. Capacity of Pipe Pipe sizes 15 inches and smaller should carry the peak flow at a depth of no more than 0.67 of the
More informationA. Codes and Standards that are Standards at the University. A. Provide floor drains in all toilet rooms, janitor closets, and mechanical rooms.
PART 1: GENERAL 1.01 Purpose A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationF. Provide at least 2 feet of vertical separation between a water line and any utility or stormdrain crossing it.
Section 3 F. Provide at least 2 feet of vertical separation between a water line and any utility or stormdrain crossing it. 3.8 Highway Crossings The design engineer shall, prior to the design of any highway
More informationITEM 432 TUNNEL CONSTRUCTION
AFTER MARCH 1, 2012 ITEM 432 TUNNEL CONSTRUCTION 432.1 Description. This Item shall govern for tunnel lines under railroads, state highways, and concrete paved streets or other obstructions indicated.
More informationSan Antonio Water System Standard Specifications for Construction ITEM NO. 848 SANITARY SEWERS
ITEM NO. 848 SANITARY SEWERS 848.1 DESCRIPTION: This item shall govern the furnishing, installation and jointing of sanitary sewer pipe of the size and type specified by the project's plans and specifications.
More informationPASSAIC COUNTY TECHNICAL INSTITUTE CCA 1422 NEW S.T.E.M. BUILDING 2017
SECTION 02630 - STORM DRAINAGE PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationCUYAHOGA COUNTY DEPARTMENT OF PUBLIC WORKS - SANITARY DEPARTMENT DETAIL
STANDARD SPECIFICATIONS - SEWER MAINS AND APPURTENANCES DEVELOPER/ENGINEER PROCEDURES All Developer/Engineering Procedures as established by Cuyahoga County Department of Public Works (CCDPW) shall be
More informationNORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section PRECAST CONCRETE MANHOLES
PART 1 GENERAL 1.01 SUMMARY This Section includes: Section 02082 A. Precast concrete manholes for sanitary sewers, storm sewers and water lines. B. Precast concrete sanitary sewer manholes with PVC liner
More informationD-1 THE CITY OF HARRISBURG 1 1/2" MIN. ID-2 WEARING COARSE EXISTING STREET SURFACE AC-20 SEALER (ALL AROUND) 1 1/2" MIN. ID-2 BINDER COARSE
EXISTING STREET SURFACE 1 1/2" MIN. ID-2 BINDER COARSE 1 1/2" MIN. ID-2 WEARING COARSE AC-20 SEALER (ALL AROUND) 8" CLASS A P.C. CONCRETE SAW CUT TOP OF CONCRETE SHALL MEET SURFACE OF EXISTING CONCRETE.
More informationFacility Sanitary Sewers
University of New Hampshire University of New Hampshire Scholars' Repository Division 22 Plumbing Chapter 5 Technical Construction and Renovation Standards 4-23-2015 221313 - Facility Sanitary Sewers Sandra
More informationT a b l e o f C o n t e n t s
C i t y o f G l a d s t o n e P u b l i c W o r k s D e s i g n S t a n d a r d s T a b l e o f C o n t e n t s SECTION THREE SANITARY SEWER REQUIREMENTS... 1 3.0000 SANITARY SEWERS... 1 3.0010 General
More informationDUKE UNIVERSITY CONSTRUCTION STANDARDS
1 33 40 00 Storm Drainage 1. Introduction A. Duke University is divided into the main areas of the Medical Center, West Campus, Central Campus, and East Campus. The University also includes the Washington
More informationCITY OF WARRENVILLE STANDARD SPECIFICATIONS WATER MAIN, SANITARY SEWER AND STORM SEWER
CITY OF WARRENVILLE STANDARD SPECIFICATIONS WATER MAIN, SANITARY SEWER AND STORM SEWER WATER MAIN 1. All open cut water main shall be polyvinyl chloride plastic (PVC) pressure pipe per AWWA specification
More informationSUNY Genesee Community College JMZ Project No Implementation of Master Plan Projects - Phase 1 Site Improvements
PART 1 - GENERAL 1.01 SUMMARY SECTION 334100 STORM UTILITY DRAINAGE PIPING A. Section Includes: 1. Pipe and fittings. 2. Nonpressure transition couplings. 3. Expansion joints and deflection fittings. 4.
More informationCITY OF SCHERTZ TEXAS ENGINEERING AND PUBLIC WORKS
TEXAS STANDARD CONSTRUCTION NOTES DRWN. BY: DSGN. BY: KJW 1 of 2 *Place geotextile fabric as a permeable seperator to prevent mixing of coarse aggregate and underlying soil. (as needed). 1. GEOTEXTILE
More informationUNIVERSITY OF MISSOURI Hydronic Energy Distribution 2016 Q1
GENERAL: The scope of this document is to provide instruction for the installation and testing of chilled water piping installed for the University of Missouri. DESIGN GUIDELINES: 1. Materials 1.1. Pipe
More informationThe Most Advanced Name in Water Management Solutions TM. The most cost-effective slotted and trench surface drain systems.
The Most Advanced Name in Water Management Solutions TM The most cost-effective slotted and trench surface drain systems. A sensible alternative to metal and concrete Since 1987, Duraslot surface drains
More informationGUIDELINES FOR RETAINING WALLS 4-0 IN HEIGHT OR LESS
GUIDELINES FOR RETAINING WALLS 4-0 IN HEIGHT OR LESS Version 2014-11-11 Prepared by: Building Development Division Department of Development Services 5 County Complex Ct. Suite 120 Prince William, VA 22192
More informationSECTION STORM DRAINAGE SYSTEM Excavating, Backfilling, and Compaction for Utilities Cast-in-place Concrete.
SECTION 02720 STORM DRAINAGE SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 02221 - Excavating, Backfilling, and Compaction for Utilities. 2. 03300 - Cast-in-place Concrete. 1.02 REFERENCES
More information