Spec-Tech-Sales September 15, 2014

Size: px
Start display at page:

Download "Spec-Tech-Sales September 15, 2014"

Transcription

1 Page 1 of 6 Spec-Tech-Sales September 15, 2014 Integrated Boiler Room Solutions Commercial Technical Sales and Service For the Rocky Mountain Region West Vassar Drive Lakewood, CO Colorado Phone Fax Wyoming Phone Fax Website: Operations & Maintenance Manuals B-1 thru B-4 Vent Stacks for Condensing Boilers Specification Section # Project Name and Owner: Kelly Walsh High School 3500 East 12 th Street Natrona County School District # 1 Casper, Wyoming Architect: RB+B Architects Fort Collins, Colorado Mechanical Engineer: Engineering Design Associates Casper, Wyoming Mechanical Contractor: KK Mechanical Roy, Utah Sheet Metal Contractor: North Star HVAC West Haven, Utah Controls Contractor: Johnson Controls Casper, Wyoming Wholesale Distributor: Ferguson Enterprises Mills, Wyoming

2 Page 2 of 6 Schebler Company Engineered Venting System for Condensing Boilers Specified Basis of Design BASED UPON 100% FINAL CONSTRUCTION DRAWINGS & SPECIFICATIONS Re-Submittal Offered For Review and Approval 100% Construction Drawings & Documents Issue Date May 12, 2014 Schedule Tag: B-1 thru B-4 Vent Stacks for Condensing Boilers Specification Section # Vent Stacks Also Reference: Specification Section # Gas Fired Packaged Condensing Boilers Separate Submittal Package Specification Section # Plumbing Equipment Separate Submittal Package -And- Specification Section # Product Requirements Specification Section # Testing Adjusting & Balancing Specification Section # Commissioning of HVAC System Specification Section # Building Automation System Specification Section # HVAC Water Treatment Specification Section # Hydronic Piping Specification Section # Hydronic Specialties Specification Section # Hydronic Pumps Scope Primarily Provided By Others - Listed For Coordination Purposes Schebler Company Engineered Boiler Venting System Scope of Supply Tag: B-1 thru B-4 Engineered Boiler Venting System Re-Submittal For Approval Boiler Room Specific Complete Engineered Venting System & Individually Vented Vertical Boiler Stack for (4) each Patterson-Kelley MACH C-4000 Boilers Reference attached Schebler revised drawing # updated September 3, 2015 Lot package of Schebler E-vent series factory engineered and sized for full and part load performance at varying firing rates, varying stack temperatures and varying outside air temperatures type AL29-4C stainless steel double wall air insulated venting system third party type UL-1738 tested compliant and certified vent pipe and fittings and Schebler project specific engineered system. Lot package consisting of (4) each complete 10 diameter vent risers for the B-1 thru B-4 boilers with the applicable B-4 boiler changed to 10 vent diameter with 2-each 45-degree elbows for the offset as per submittal review comment. The boilers are to be individually vented as shown on boiler room floor plan and elevation details to include 10 diameter as required for the applicable specified basis of design Patterson-Kelley MACH model # C-4000 condensing boilers) each with applicable type AL29-4C s/s manually adjustable locking quadrant / blast gate type vent dampers each as detailed on the

3 Page 3 of 6 vertical vent risers for venting the applicable proposed (4) each Patterson-Kelley MACH series model # C-4000 condensing premium efficiency boiler assemblies. Lot package consisting of applicable vent pipe and fittings all as required for boiler placement location as detailed on specific floor plan. Complete system from the applicable boiler exhaust connection and including the applicable individual vertical vent stack riser for each boiler (routing as detailed) with necessary vent and roof termination. Package includes all necessary connectors, supports, transitions pieces, insulated thimble with flashing and rain collar, applicable condensate drains along with any and all necessary vent tapping s I.E. combustion analyzer and manometer tapping s for the included (4) each applicable adjustable locking quadrant vent dampers (1) per each boiler riser, and if applicable the tapping can be used at a later date with a removable optional stack thermometer provided by others. Lot package to also include if applicable any special termination flashing / cover for a typical chimney chase - vent penetration application as needed. NOTE: The applicable updated Schebler drawing -02 dated September 3, 2015 to reflect site visit validation sketch routing and layout dimension changes as issued by KK Mechanical on August 27, 2015 and signed approved submittal that was released to production, fabrication and shipping. Schebler s E-vent system consists of type AL29-4C high grade of stainless steel inner wall liner (higher grade and more corrosion resistant than the inferior type 316 s/s and as such Schebler for this engineered system offers a lifetime warranty against manufacturing and material defects warranty terms and conditions to apply). Schebler s E-vent system compliant with written specification section # B which requires 40 W.C. positive pressure capabilities. Schebler s E-vent system compliant with written specification section # Engineered CAD drawing details with stack sizing and performance validation calculations to follow with submittal package The applicable Patterson-Kelley MACH C-4000 boiler stack sizing calculation criteria coupled with project specific vent design layout CAD drawing details required from the applicable vent manufacturer which is required prior to boiler startup / commissioning is listed as follows: Project site elevation of 5150-feet above sea level Natural gas vent category IV positive pressure firebox of.22 W.C MBH input high fire 800-MBH input low fire Stack temperature illustrated at 210-degrees F. to 120-degrees F. CO2% level of 9.1% to 9.2% - key variable for condensing dew point Outside air temperature range of minus -13-degrees F. to 92-degrees F. The revised layout / offset coupled Schebler revised drawing # updated September 15, 2014 with the updated engineered vent sizing calculations and submittal review comments have changed the applicable B-4 boiler to the requested 10 diameter (like B-1 thru B-3 boilers) utilizing (2) each 45-degree elbows for the offset in lieu of the initial (2) each 90-degree elbows as initially submitted because the performance variables for the applicable high fire conditions at 120-degrees F. stack temperature at 92-degrees F. outside air temperature (required for summer domestic water operation considerations) with the design layout change we are within the operational parameters range at the vent outlet to the.22 W.C. positive pressure maximum allowable.

4 Page 4 of 6 Schebler E-vent system utilizes a superior gauge and superior flange to flange joining system (in lieu of gasket seal approach) for any and all connections. This superior flange to flange system offers optimum joint support, alignment and rigidity and enables the use of only a single vertical stack support plate and as such there will not be any additional chimney chase access or supports needed for this chimney chase application design a benefit for installation considerations and for minimizing the building and chimney construction impact if applicable. Where applicable (also factoring in the superior flange to flange joint alignment and load carrying capabilities and integrity) we could include if needed include optional lifting lugs (complete with engineering support to validate the weight / load and lifting rigging points needed) to be provided and fabricated on the top vent termination section to allow for rigging / lifting and craning options for dropping the new venting system into place for any of the chimney chase applications. Engineered system confirming proper operation and performance in accordance with Patterson- Kelley specific vent sizing criteria at site elevation of 5150-feet elevation in Casper, Wyoming and at varying firing rates between low fire up to high fire, varying stack temperatures impacted by outside air reset schedule range (if applicable) and system water temperature range being -degrees F. to -degrees F. as said operating water temperature impacts the stack temperature, varying outside air temperatures (the outside air reset schedule if applicable for ranges from minus -13-degrees F. or colder up to 92-degrees F. or warmer) as that impacts positive pressure or the draft at the boiler exhaust outlet we need to confirm that said operating and performance ranges does not go too far positive and / or too far negative at the vent / exhaust outlet and indirectly the boiler firebox all of which if outside the factory imposed parameters can impact applicable boiler air pressure switches, boiler / system wide performance, boiler / system wide combustion efficiency, condensing dew point I.E. if too much excess air if too much draft present in addition to impacting standby losses it also can impact the critical combustion CO2% (very important for condensing boiler applications) which impacts the condensing dew point (moving through the outside air reset schedule curve) which impacts the desired efficiency capabilities that condensing boiler designs offer thus the Locking Quadrant Vent Dampers as included offers a solution. Our scope does NOT include any new combustion air pipe, and fittings although we do have the boiler sealed combustion adapter and the motorized combustion air dampers with end switch to be wired into the ENVI control limit circuit. The Schebler project / building and boiler room specific venting system can be modified to include optional lifting lugs on the top section for any applicable chimney / chase application to help facilitate rigging / crane pick or use of a pulley system with cables to build up the vertical stack in the boiler room (from a roof pulley system with cables by others) allowing for lifting one section at a time from the roof.

5 Page 5 of 6 Schebler Company Chimney Systems an industry leading premier manufacturer of UL third party certified engineered pre-fabricated chimney stack and exhaust systems for boilers, water heaters, grease exhaust / grease duct, emergency generators, free-standing stack for process applications, fixed speed or variable speed draft induction fan and sequence draft control solutions. They offer solutions based engineering support with in depth project and application specific system sizing and design layout assistance offering peace of mind guarantees for the venting and equipment performance validation to the owner / end user and specifying mechanical engineer. event, event SD and event-plus 2 type AL29-4C s/s UL-1738 third party certified with 40 W.C. rated complete venting systems for condensing high efficiency boilers, water heaters and furnaces Boilers, water heaters, and furnaces venting and exhaust systems factory pre-fabricated air insulated or fiber insulated vent pipe, fittings and chimney systems for vent category I, II, III and IV rated appliances Comprehensive engineered vent and exhaust system design layout assistance with itemized CAD drawings and 3D modeling available Comprehensive engineered and validated boiler or grease duct exhaust / vent stack system sizing analysis for full and part load performance and outside air and boiler stack temperature ranges FyreGuard and SlimVent UL-2221 third party certified zero clearance to combustibles factory fiber insulated grease duct system Free-standing engineered stack division with structural engineering and load bearing calculation validation Emergency generator exhaust factory fabricated and insulated flange to flange connection with pressure relief valves, bellows assemblies and assorted Grease duct exhaust system factory fabricated flange to flange connection no field welding required with access doors, hood transitions and assorted Wing Fan - inline draft induction fans fixed speed or variable speed with control panel and controls system integration Sequence Draft Control modulating or fixed position draft control dampers for positive pressure or negative draft control with control panel and controls integration.

6 Page 6 of 6 BASE PACKAGE SCOPE FIELD PIPING & INTERFACE CONNECTIONS Lot package scope summary overview complete as detailed above for the B-1 thru B-4 engineered boiler venting system individual risers for use with (4) total Patterson-Kelley MACH C-4000 condensing water boilers complete with factory authorized initial startup / programming and combustion test to be done by Spec-Tech-Sales for the 1 st trip during the initial temporary heating requirements and the 2 nd trip for the final system startup upon construction completion and a 3 rd trip for follow up assessment and fine tuning after 6-months of operation, along with extended (for temporary heating requirements) and enhanced limited warranty offerings including site visit assessment and any and all applicable limited boiler scope warranty related labor assessment and work to be done by Spec- Tech-Sales warranty terms and conditions to apply complete with freight included to project destination. 1. Our proposal includes the items and bill of material as listed, and is offered subject to final mechanical engineer owner approval in its entirety complete with exceptions and clarifications as noted. Pricing and / or scope adjustments to follow for any additional material required over and above our base package scope as offered and / or for change orders or directives as given and / or for reduction in scope if / as required. 2. Our proposal includes conservative freight allowance (standard shipping freight is included in this proposal) included from factory destination to jobsite destination with some initial projections factored in for realistic shipping and scheduling guidelines IE multiple shipments are accounted for in this proposal and scope. 3. NOTE: Upon receipt, please forward stamped approved submittal package and when applicable any coordination requirements for the formal release to production, fabrication and subsequent shipping as needed. Project specific installation / operation and maintenance manuals and any point to point wiring interface clarification assistance to follow upon receipt of approved submittal package. Approximate material shipping material lead time frames upon release to production and fabrication as follows: 4. Approximate shipping lead time frame after receipt of formal submittal approval and formal release to production and fabrication: Schebler Venting = approximately 2-weeks (NOTE: If new factory provided CAD drawing is required IE field verified changes that would add an additional 1-week give or take to finalize a new drawing) Option B: Patterson-Kelley Skid Package Concept = approximately 12 to 14-weeks

7

8 C US INSTALLATION INSTRUCTIONS OPERATION AND MAINTENANCE MANUAL Models event SD, event, Event Plus, and event Plus2 (Condensing Boiler Systems) A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE TO MAINTAIN REQUIRED CLEARANCES (AIR SPACES) TO COMBUSTIBLE MATERIALS. IT IS OF UTMOST IMPORTANCE THAT THIS VENT BE INSTALLED ONLY IN ACCORDANCE WITH THESE INSTRUCTIONS. IMPORTANT: DO NOT INSTALL VENTING SYSTEM WITHOUT FIRST READING THESE INSTRUCTIONS.

9 TABLE OF CONTENTS General UL Listing USA and Canada Venting Applications Termination Height Requirements Horizontal Termination Requirements Vent Environment Part Identification Clearances and Enclosures Support Limits Limitations Individual Part Installation Basic Pipe and Fitting Assembly for Models event, eventplus and eventplus Basic Pipe and Fitting Assembly for Models eventsd Variable Straight (VS) Horizontal Termination (HT) Boiler Adapter Kits (BKF and BKR) Degree Tee (90T) Elbows (30L, 45L and 90L) Degree Lateral Tee (45LT) Degree Wye (90Y) Support Plate (SP) Wall Support (WS) Wall Guide (WG) Floor Roof Guide (FRG) Full Angle Ring (FR) Half Angle Ring (HR) Flashing (FL) Rain Collar (RC) Insulated Thimble (IT) Rain Cap (CC) Top Section (TS) Exit Cone (EXC) Guy Section (GS) End Cap (EC) Drain Tee Cap (DTC) Drain Section (Ds) Horizontal Drain (HD) Operating Precautions Maintenance GENERAL & These instructions cover installation requirements for the Schebler listed double wall special stainless steel venting systems: event SD, event, eventplus and eventplus2. Schebler models event SD, event, eventplus and eventplus2 must be installed in accordance with local building code and as well as national codes. Examine all components for possible damage prior to installation. Contact your local Schebler distributor with any questions. Proper joint construction is essential for a safe installation. Follow these instructions exactly as written. The venting system must be free to expand and contract. This venting system must be supported in accordance with these instructions. Check for proper joint construction when joining pipe to fittings. Different manufacturers have different joint systems and adhesives. Do not mix pipe, fittings or joining methods from different manufacturers. UL LISTING All Schebler event series Models are listed to UL 1738 and ULC for installations manufactured in even and odd diameters. The Schebler Models eventsd, event, eventplus, and eventplus2 maybe utilized in the same system. Proper installation methods must be followed as called for in these instructions. The venting system shall terminate in accordance with the requirements of CAN/CGA-b149.1, Natural Gas Installation code, or CAN/CGA-B149.2 Propane Installation code. Refer to The Schebler Company Venting System catalog for the description of all necessary parts. Check for unrestricted vent movement through, walls, ceiling, and roof penetrations. 2

10 VENTING APPLICATIONS Models event SD, event, eventplus and eventplus2 are a double wall special stainless steel venting system for gas fired appliances listed as Category II, III, & IV with a maximum flue gas temperature of 550 F, and 40" w.c. positive pressure. Gas vent - BH, Class I/Class II C. Models event SD, event, eventplus and eventplus2 is also suitable for other applications that call for an AL 29-4C vent. Models event SD, event, eventplus and eventplus2 are to be installed as a complete system connecting the appliance(s) to the outdoors, while operating under positive forced draft, negative induced draft, or neutral gravity flow internal pressure conditions using only Schebler models event SD, event, eventplus and eventplus2 vent parts. No vent part from another manufacturer should ever be mixed with models event SD, event, eventplus and eventplus2. If a drain fitting is required by the appliance manufacturer, it must be located as close to the flue outlet as possible. Multiple category II, III & IV appliances may not be common vented unless approved by the manufacturers. Do not mix natural draft and forced draft appliances together. Venting systems are to be sized in accordance the ASHRAE Handbook, Equipment Volume, the appliance manufacturer s instructions, or by contacting The Schebler Company. Models event SD, event, eventplus and eventplus2 shall not be routed into, through, to within any other vent such as an existing masonry or factory-built vent that is connected to another appliance. Recommendations that exterior mounted venting systems be enclosed below the roof line to limit condensation and protect against mechanical damage. Methods of providing additional insulation may be specified. A requirement to check the joints and seams for gas tightness when using the venting system with a Category III or IV appliance. The maximum rated pressure for which the venting system is intended to be used. Note: Horizontally terminated systems must be pitched ¼" per foot back toward the appliance being vented. Ensure any condensate is collected by strategically placing drains, or the appliance itself if permitted by the appliance manufacturer. Note: For vertically terminated systems it is recommended that longer horizontal runs be pitched ¼" per foot back toward the appliance being vented. Ensure any condensate is collected by strategically placing drains, or the appliance itself if permitted by the appliance manufacturer. VENT ENVIRONMENT It is suggested that a vent being installed in a corrosive atmosphere be constructed of Type 304, 430 or 316 stainless steel for the outer shell material. PART IDENTIFICATION These instructions and the catalog identify parts by name followed by a part code. Part numbers are made up of the model, part code, flue inside diameter and material code. The part number is shown on the UL label. EXAMPLE: The part number for a Model event (EV), 35 long Straight Section (35S), 8 ID (08), with a AL 29-4C stainless steel liner and an aluminized steel shell (K) would be EV35S08K. event Series material codes are shown in the following chart: CODE K L M R LINER/SHELL MATERIAL AL 29-4C Stainless Steel / Aluminized Steel AL 29-4C Stainless Steel / 304 Stainless Steel AL 29-4C Stainless Steel / 316 Stainless Steel AL 29-4C Stainless Steel / 430 Stainless Steel CLEARANCES AND ENCLOSURES CAUTION DO NOT PLACE ANY TYPE OF INSULATION OR COMBUSTIBLE MATERIALS IN THE REQUIRED CLEARANCE SPACES SURROUNDING THE VENT. This vent is to be installed unenclosed or with enclosures. If the vent passes through any zone or story of a building above that on which the connected appliance is located, it is to be enclosed in construction having a fire rating equal to or greater than that of the floor or roof assemblies through which it passes. NOTE: Always check with the Authority Having Jurisdiction for material with an appropriate fire rating. If a portion of the vent passes between a dropped ceiling and roof, that portion is to be enclosed in a fire rated enclosure or proper clearance to combustibles are maintained. Vents are not intended to pass through combustible walls. Any wall through which the vent passes must be of noncombustible construction unless proper clearance to combustibles are maintained. Vents installed in open rooms or fully ventilated areas on the same story as the equipment connected to it shall have a minimum clearance to combustibles as shown in the following tables: SYSTEMS TERMINATING VERTICALLY event Series Vent Clearances - Vertically Terminating Systems Inside Diameter 550 F (288 C) inches mm " (25mm) " (38mm) " ( 51mm) " (76mm) " (102mm) " (127mm) SYSTEMS TERMINATING HORIZONTALLY event Series Vent Clearances - Horizontally Terminating Systems Inside Diameter 550 F (288 C) inches mm " (25mm) " (38mm) " ( 51mm) " (76mm) " (102mm) " (127mm) " (152mm) Clearances to non-combustibles shall be necessary for installation, inspection and maintenance. TERMINATION HEIGHT REQUIREMENTS Vents are to terminate a minimum of 3-ft. (0.92 m) above the highest point of the roof penetration and 2-ft. (0.61m) minimum above any portion of a building within 10-ft (3.1 m) horizontally. Consult the Authority Having Jurisdiction about restrictions in your area. See NFPA

11 Models event, eventplus and eventplus2 INDIVIDUAL PART INSTALLATION This section identifies Models event, eventplus and eventplus2 by name and part number or part code. See the section titled Part Identification on page 3 of these instructions for part number details. When referring to parts always include the model and flue size to avoid confusion. These instructions comprise both general and specific requirements for all parts in the event, eventplus and eventplus2 series product lines only. (For Model event SD please refer to the specific instructions for Model eventsd. BASIC PIPE AND FITTING ASSEMBLY Before beginning an installation, thoroughly review these instructions. Inner Band Figure 1 - Straight Section SEALANT APPLICATION Figure 3 Step 1: Clean Flanges Step 2: Apply a continuous bead of Schebler part number S600 sealant covering the 1/2" flange of one of the two parts being joined. Fill the "V" groove of the inner band with the S600 sealant provided. See figure 2. Flange "V" of Inner Band Step 4A: (For eventplus2) Wrap inner band tightly with 4" wide insulation strip provided with the system. Step 4: Place outer band around both sections covering the space between the shells. The flanges on the outer band fit into the grooves on the shells. Install nuts/screws and tighten using screwdriver. Step 5: Figure 4 - Horizontal Installation Orientation S600 cure time is 3 days at ambient temperature. Step 3: Figure 2 Join flanged ends of two sections. Install inner band around the two flanges, and use a screw driver to tighten inner band around sections. -See figure 4 for correct orientation. Tap on inner band with rubber or rawhide mallet to ensure a proper tight joint. Note: Once properly installed, sealant will ooze out from between the band and event liner at the inner band connection. This is a indication that the proper amount of sealant has been applied and should not be removed. The sealant may be smoothed for a finished appearance. Note: For outdoor installations, or installations in areas of moisture, apply a bead of S600 sealant in the groove at upper end of the outer band and at the band overlap. Outer Band Figure 5 4

12 Model eventsd INDIVIDUAL PART INSTALLATION This section identifies Model eventsd by name and part number or part code. See the section titled Part Identification on page 3 of these instructions for part number details. When referring to parts always include the model and flue size to avoid confusion. These instructions comprise both general and specific requirements for all parts in the event, eventplus and eventplus2 series product lines only. (For Models event, eventplus and eventplus2 please refer to the specific instructions for Model eventsd. Before beginning an installation, thoroughly review these instructions. BASIC PIPE AND FITTING ASSEMBLY Figure 6 - Typical Straight Section Step 1: Step 2: Clean inside of female end, outside of male and, and vee groove of SD inner band. Apply a 3/4" continuous bead of Schebler S600 sealant provided to the outside of the male end approximately 3/8" from the edge. Apply a second 3/8" continuous bead of sealant on the inside of the female end, approximately 3/8" from the edge. Fill the vee groove of the SD inner band with S600. Figure 7 - Sealant Application Note: Once properly installed, sealant will ooze out from between the band and event liner at the inner band connection. This is a indication that the proper amount of sealant has been applied and should not be removed. Step 3: Insert male end of the event SD into the female end until it stops at the end of the stopping bead. Install SD inner band around the joint spacer clips, using a screwdriver to tighten the SD inner band around the clips with provided hardware. Lightly tap on SD inner band with rubber or rawhide mallet to ensure proper tight joint. Step 4: Step 5: Center outer band over gap between the outer shells of the two sections and tighten with supplied hardware. S600 cure time is 5 days at ambient temperature. Figure 9 Figure 8 - Final Inner Joint Connection Figure 10 - Final Outer band Connection 5

13 These sections identifies Models eventsd, event, eventplus and eventplus2 by name and part number or part code. See the section titled Part Identification on page 3 of these instructions for part number details. Refer to the correct models installation instructions for specific joint connection instructions. When referring to parts always include the model and flue size to avoid confusion. Variable Straights (VS) Model eventsd only. Refer to specific instructions for Models event, eventplus and event PLUS2 Variable Straight instructions. The inner liner is completed by using the inner liner section and slip collar. The inner liner section is cut to length. Take great care in measuring the length required so both joints can be properly secured before the section is cut. The slip collar will slide on to the inner liner section once cut to complete the ducts inner liner. The crimped end of the liner will connect the same as standard straight sections and is not to be cut. The Variable Straight is not designed to support any load. Variable Straights (VS) Models event, eventplus and event PLUS2 only. Refer to specific instructions for Model eventsd Variable Straight instructions. The inner liner is completed by using the inner liner section and slip collar. The inner liner section can be cut to length or slipped inside of the next fixed section of pipe. The slip collar will slide on to the inner liner section and will be drawn tight around the raw end of the inner liner. The flanged ends of the liner and slip collar will connect the same as standard straight sections. The outer comes in two halves. The outer can be cut to length or slipped over the adjacent section. The two halves are drawn together on the sides with the supplied hardware. The Variable Straight is not designed to support any load. GAS FLOW CONDENSATE FLOW Figure 11 Measuring length Variable Straight Length Do not cut the crimped end of the Variable Length Section. First cut back the outer shell of the section. Once completed cut back the inner liner of the same section the same distance as the outer shell. Slide on the slip collar over the inner liner and install section as per the instructions found on page 5. SLIP COLLAR INNER LINER FIXED JOINT SECTIONS TO BE JOINED Figure 13 GAS FLOW CONDENSATE FLOW Figure 12 Cutting to Length Required GAS FLOW INNER "V" BAND ON FLANGED END Figure 14 CONDENSATE FLOW Note: Once properly installed, sealant will ooze out from between the band and event liner at the inner band connection. This is a indication that the proper amount of sealant has been applied and should not be removed. SLIP COLLAR BUTTED AGAINST FLANGE INNER "V" BAND Figure 15 Note: Apply a bead of sealant between the slip collar and inner liner near the flanged end. 6

14 Exhaust systems terminating out a buildings sidewall have additional considerations as compared with traditional through roof terminations. Please refer to specific instructions contained in this section. Figure 16 Horizontal Termination Assembly HORIZONTAL TERMINATION (HT) The Horizontal Termination is utilized when an appliance is exhausted out the sidewall of a building. The system includes a duct Horizontal Termination, Wall Thimble, Thimble Clips, and Wall Flashing. BASIC eventsd WALL TERMINATION ASSEMBLY Step 1: Cut a opening in the wall just large enough to allow the Wall Thimble to penetrate the wall. Keep the Wall Thimble flush with the outside face of the wall. Figure 19 Final Horizontal Termination Installation Note: Horizontally terminated systems must be pitched ¼" per foot back toward the appliance being vented. Ensure any condensate is collected by strategically placing drains, or the appliance itself if permitted by the appliance manufacturer. HORIZONTAL TERMINATION REQUIREMENTS event Series Horizontal Support Spacing eventsd When Terminating Horizontally Up To 6' event, eventplus & eventplus2 Up To 12' Note: Minimum horizontal clearance from appliance outlet to wall of final termination is 3'. VERTICAL TERMINATION REQUIREMENTS Figure 17 Installation of the Wall Thimble event Series Horizontal Support Spacing eventsd When Terminating Vertically Up To 8' event, eventplus & eventplus2 Up To 12' Step 2: Utilizing the Wall Thimble Clips, secure the Wall thimble to the inside of the wall by fastening the clips to the Wall Thimble and the wall being penetrated. Space the clips equally around the perimeter of the Wall Thimble to ensure tight installation. Step 3: Center the Horizontal Termination in the Wall Thimble. A minimum of 3" of inner liner of the Horizontal Termination must penetrate past the outside of the wall and Wall Thimble. See figure 18. Figure 20 Termination Requirements Above a Pitched Roof Figure 18 Installation of the Horizontal Termination Step 4: Mount the Wall Flashing over the Wall Termination sealing the gap between the Wall Thimble and the wall opening. Level the Flashing and seal around perimeter of the Inner Liner with a bead of S600 sealant. Figure 21 Termination Requirements Above a Flat Roof Note: For vertically terminated systems it is recommended that long horizontal runs be pitched ¼" per foot back toward the appliance being vented. Ensure any condensate is collected by strategically placing drains, or the appliance itself if permitted by the appliance manufacturer. 7

15 BOILER ADAPTER KITS (BKF and BKR) "C" Clamp Starter Section 90 DEGREE TEE (90T) When properly supported, the 90-Degree Tee will support 50 feet of vertical vent. This fitting is used to connect horizontal pipe runs into the vertical vent as well as a drain and/or inspection opening. Where access for a drain or an inspection opening is required, the following method for support can be used: Split Starter Ring Boiler outlet Figure 22 - Flanged Boiler Adapter For flanged appliance outlets, the Boiler Kit Flanged (BKF) should be used. The Boiler Kit Flanged consists of a split starter ring, starter section and the required number of "C" clamps for the installation. The Boiler Kit Flanged is installed in the following procedure: Apply a continuous bead of the proper sealant to the inner flange on one end of the Starter Section. Center the starter section on the boiler flange and place the two piece Split Starter Ring over the bottom flange on the Starter Section. Be sure that the tabs on the Split Starter Ring overlap and all parts fit snug. Place the required number of "C" clamps over the boiler flange and starter ring and tighten clamps. The flange can be field drilled to match the appliance outlet if desired. All other vent parts can now be installed (see joint assembly for the proper procedure). Figure Tees A. Suspended Tee - Support Plate or Wall Support at upper tee joint as shown in Figure 17. Raw end to connect to raw boiler outlet Rolled Flange to be connected to next section of pipe Figure 23 - Raw Boiler Adapter For a raw appliance outlets the Boiler Kit Raw (BKR) should be used. The Boiler Kit Raw consists of a collar type starter section. The Boiler Kit Raw is installed in the following procedure: Figure 25 - Suspended Tee B. Two axis support - This method is recommended if the total thermal expansion is expected to be above ¼ as shown in Figure Apply a continuous bead of the proper sealant to the inner flange of the appliance outlet. Place the starter section on the appliance outlet and tighten in place with the hardware provided. All other vent parts can now be installed (see joint assembly for the proper procedure). The boiler kits include a seal ring that will cover the gap between the inner and the outer shell. The seal ring clamps around the outer shell pipe and is held in place with (4) ¼ x 1 ½ bolts. Figure 25 - Two Axis Supported Tee 8

16 DRAIN TEE CAP (DTC) 90 DEGREE WYE (90Y) The Wye fitting is used when the vertical vent is located between two boilers and a low-pressure loss system is required. The Wye should be installed with the usual precautions observed for thermal expansions. Figure 26 - Drain Tee Cap The event, event Plus and event Plus2 has a 1" drain pipe that must be connected to a suitable drain. The eventsd has a 1/2" drain connection. The Drain Tee Cap must be connected at all times to a suitable drain. Upon entering the vent, rain will wash down and remove any corrosive combustible residue. The Drain Tee Cap must be installed with sealant at its mating surfaces with the flanged joint. This will ensure that moisture is drained through the drain as intended and will provide a tight seal. The Tee Cap can be installed for inspection access as required. 30, 45 AND 90 DEGREE ELBOWS (30L, 45L AND 90L) These elbows must be protected from the effects of thermal expansion. SUPPORT PLATE (SP) Figure 29-90Y The Support Plate offers the greatest strength for support of the event Series Venting System. It will provide vertical support and will provide for joint alignment and support for horizontal applications. Between any two fixed points in a system or whenever an adjustable length must be used to prevent the bending of tees and other fittings, locate and secure the Support Plate as necessary by means of structural ties to the building. The Support Plate must be secured to structural members of the building, which can adequately support the weight of the vent as shown on page 12 of these instructions. Figure 27-45, 30 and 90 Elbows 45 DEGREE LATERAL TEE (45LT) For venting systems that require a 45 degree entry to the vertical vent, the 45 Degree Lateral Tee (45LT) may be used. The 45 Degree Lateral Tee should be supported in the same way as the 90 Degree Tee. When properly supported, the 45 Degree Lateral Tee will support 50 feet of vertical vent and may be installed with a Drain Tee Cap or End Cap. Figure 30 - Support Plate Attachment The Support Plate consists of a split clamp flange, split plate and necessary hardware. The split clamp flange and the split plate are used to clamp the inner flanges together and are turned 90 degrees apart. The notches in the split plate and in the clamp flange are to accommodate the inner band end clips, allowing the "V" to rest solidly on the split plate. The installation procedure is as follows: Figure Lateral Tee Connect the joint to be supported by use of the inner band as previously discussed. Connect the split clamp flange to the split plate with the provided hardware. The split plate should be below the finished joint and the clamp flange should be above the finished joint. 3/8 x 1 ½ bolts should be used in all of the inner clamp flange holes. Tighten all bolts. Install the special outer bands provided and seal with sealant. 9

17 Proper performance and long service life of the Model event Series Venting System requires that the vent be rigidly braced and supported. Every installation offers unique support and bracing requirements and the following guidelines will provide minimum acceptable sizes for the mechanical hardware supplied by others. When the support plate is bolted to framework 3/8 bolts should be used in all of the holes on the perimeter of the support plate. event Series Size Framework Bracing 4" - 20" 2 x 1 x 3/16 to 5 x 2 x 2 x 2 x 3/16 3/16 or equivalent 22" - 36" 5 x 2 x 3/16 to 6 x 2 x 3 x 3 x 1/4 3/16 or equivalent 38" - 48" 6 x 2 x 3/8 or equivalent 4 x 4 x 3/8 The Wall Support is intended for attachment to non-combustible structures. When attached, the Wall Support provides a fixed point in the vent system. Install a Variable Length below a Wall Support to provide the necessary expansion compensation. The Wall Support, when properly installed, will allow for the required clearances to combustibles along the wall and will support the length of pipe outlined on page 12 of these instructions. WALL GUIDE (WG) The wall guide is used to protect the vertical vent from lateral wind loads and to allow for thermal expansions. When assembled, the proper installation location is at a joint but below the outer band. The outer wall of the vent must be able to move away from the outer ring of the wall guide. When properly attached to a combustible wall, the Wall Guide will maintain the proper clearances to combustibles. Wall Guides should be equally spaced along the wall at spacings no greater than 16 for 4 through 10 diameters and 24 for 12 through 48 diameters. WALL SUPPORT (WS) Figure 31 - Support Plate Bracing The Wall Support consists of two split plates, brackets and all necessary hardware. The notches in the split plates on the Wall Support are to accommodate the inner band end clips, allowing the "V" to be clamped between the split plates. Installation for the Wall Support is accomplished with the following procedure: Figure 33 - Wall Guide Connect the joint to be supported by use of the inner band as previously discussed. Connect the split clamp flange to the split plate with the provided hardware. The split plate should be below the finished joint and the clamp flange should be above the finished joint. 3/8 x 1 1/2 bolts should be used in all of the inner clamp flange holes. Tighten all bolts. Bolt the wall brackets to the split plate assembly with the (6) 3/8 x 1 ½ bolts as provided. Locate and bolt the entire assembly to the wall with (8) ½ dia. bolts. Apply sealant around outer Half Bands and support plate for exterior installations. CAUTION: Always maintain proper clearances to combustibles when installing all guides and supports. Keep all insulation away from required clearance (air) spaces surrounding the vent. Guides and supports are only suitable for attachment to noncombustible construction due to possible heat conduction. FLOOR ROOF GUIDE (FRG) Floor Roof Guides are used to provide lateral support for the vent in the roof and floor opening. The Floor Roof Guide is to be bolted to non-combustible construction in (4) four places. Figure 34 - Floor Roof Guide Figure 32 - Wall Support 10

18 FULL AND HALF ANGLE RINGS (FR AND HR) The full and half rings are used to guide the vent either vertically or horizontally. The rings should be placed at intervals shown in the chart below and securely connected to the building structure. The diameter of the Full Ring is slightly larger than the pipe. This will allow the pipe to slide within the ring. This movement must be allowed to compensate for thermal expansion. INSULATED THIMBLE (IT) The insulated thimble is used in conjunction with the flashing and rain collar when clearances to combustibles cannot be maintained at a roof penetration. The Insulated Thimble should be dropped through the roof opening. The (4) four tabs will set upon the roof deck and nailed or bolted down. The flashing is then set over the Insulated Thimble. event Series Horizontal Support Spacing eventsd When Terminating Horizontally Up To 6' eventsd When Terminating Vertically Up To 8' Event, eventplus & eventplus2 Up To 12' event Series Vertical Guide Spacing All event Series Diameters 5" to 10" Up To 16' All event Series Diameters 11" to 48" Up To 24' RAIN CAP (CC) Figure 37 - Insulated Thimble Figure 35 - Full Ring and Half Ring FLASHING AND RAIN COLLAR (FL AND RC) The Rain Cap provides partial protection from rain and debris. The Rain Cap is mounted on the end of a standard pipe section with the use of a inner band. A closure ring is provided to close off the space between the inner and outer liners. A minimum clearance of 8 feet (2.44 m) is recommended to ensure that all exhausted products are dispersed away from the building and intakes. To install the Rain Cap, the following procedure should be used: Both the Flashing and the Rain Collar are designed to fit the outside of the Model event Series Venting System. They are constructed of galvanized steel and should be protected from corrosion by cleaning and painting. The Flashing is nonventilated and for non-combustible and combustible flat roofs. Flashings of a special pitch are available upon request. The Flashing should be protected from lateral movement of the stack by use of the Full Ring or the floor/roof Guide Apply a bead of the proper sealant to the flange of the inner pipe to receive the Rain Cap. Place the Rain Cap on the existing inner flange and attach the "V" band as previously mentioned. Install the provided collar as shown. Apply a silicon sealant to fill any gaps and joints on the collar and tighten all bolts. The Rain Collar is secured around the pipe immediately above the flashing and should be sealed with a silicone sealant. Figure 36 - Roof Penetration Figure 38 - Rain Cap Assembly 11

19 To clean the flue or replace the Rain Cap, reverse the above procedure. To reinstall, follow the installation procedure. TOP SECTION (TS) The Top Section is installed using the same procedures as a Rain Cap (CC). Figure 39 - Top Section EXIT CONE (EXC) The Exit Cone is installed using the same procedure as the Rain Cap (CC). Figure 42 Rigid Guying Angle GUY SECTION (GS) Figure 40 - Exit Cone When the height above the roof line exceeds 12 feet, a Guy Section is recommended. The inner flanges of the Guy Section are connected in the same procedure as the typical pipe sections. The outer shell is then sealed by using special half bands and sealant. Guy wires or braces are to be attached to the horizontal flanges of the Guy Section (See Figure 35). The cables and pipe guys must be slightly loose to allow for thermal expansions. To reduce the thermal expansion effects on rigid bracing or guy wires, a Support Plate (SP) or Wall Support (WS) may be installed at or below the roof line. Guy tensioners may be required if the thermal expansion exceeds the allowable slack in cables. Figure 43 Bracing Requirements Figure 41 - Guy Section Figure 44 Maximum Freestanding Height 12

20 LIMITATIONS MAXIMUM HEIGHT ABOVE TOP LATERAL BRACE OR GUY Vent Inside Diameter Maximum Height 4-10 ( mm) 8 feet (2.44m) ( mm) 12 feet (3.66m) If the height above the roof line is less than that specified above, no guying or bracing is required. However, a Insulated Thimble (IT), Floor/Roof Guide (FRG) or Full Ring (FR) at the roof line is necessary to protect the Flashing (FL) from side loads caused by wind. For heights above the roof line greater than that shown above, the vent must be guyed or braced. Guying or bracing is accomplished by use of the Guy Section (GS) Full Ring (FR) or Wall Guide (WG). Guy wires or braces are to be attached to the horizontal flanges of the Guy Section. While 3 guys are usually sufficient, it is recommended that 4 equally spaced wires at an angle of 45 from the vertical be utilized. The cables and guys must be slightly loose to allow for the thermal expansion. Rigid bracing requires two braces with not less than 60 angle between them. The braces must be attached to a Guy Section (GS) or Full Ring (FR). DRAIN TEE CAP (DTC) DRAIN SECTION (DS) Figure 45 - End Cap The drain tee cap is installed exactly the same as the end cap. The drain section is used to drain rain water and condensation from within the stack. The NPT nipple should be connected to a suitable drain. event SERIES SUPPORT LIMITS SECTION INSIDE DIA. SUPPORT PLATE (SP) WALL SUPPORT (WS) inches mm feet meters feet meters Figure 46 - Drain Section HORIZONTAL DRAIN (HD) The horizontal drain is used to drain rain water and condensation from within the breeching. The NPT nipple should be connected to a suitable drain. END CAP (EC) The end cap is used to cap off a tee and to allow a means to enter the system for inspection and cleaning. The end cap is installed by connecting the inner cone to the adjacent pipe section with a inner band and sealant. The outer cover piece is then fitted over the outer shell and bolted into place with (2) ¼ x 1 ½ stainless steel bolts. Whenever the end cap is removed for inspection purposes the flanges must be cleaned and resealed when reinstalling the part. Figure 47 - Horizontal Drain 13

21 OPERATING PRECAUTIONS A licensed or qualified vent sweep should be contacted to clean the vent. Contact local building or fire officials about restrictions and installation inspection in your area. MAINTENANCE Venting and Exhaust Systems 1. After the installation of the vent or exhaust system, ensure that the required clearances are maintained and For tee caps, adequate clearance is required around clean-outs to assure accessibility for removal of caps and products accumulated within the vent. 2. that the system continues to be supported properly. The venting system should be inspected if there is any evidence of damage to the vent system, and at least annually, for internal deposits, soundness and correct clearances. Cleaning and repairs shall be as needed. It is recommended that exterior mounted venting systems located in geographical areas which experience sustained low ambient temperatures be enclosed to reduce or limit condensation, creosote buildup and poor draft Caulking on exterior portions of the vent, flashing, rain collar, etc. should be inspected and repaired or replaced as needed to prevent leakage. Painted portions of the vent shall be cleaned and touched-up or repainted as required to prevent corrosion. Supports, guys, braces, etc. should be inspected at least annually to make sure bolts are tight. For further information see NFPA 211, latest edition, chapter titled Maintenance. 14

22 5665 Fenno Rd. Bettendorf, IA Jan 2012 Phone: Fax:

23 venting systems for high efficiency appliances series

INSTALLATION INSTRUCTIONS OPERATION AND MAINTENANCE MANUAL Models event SD, event, Event Plus, and event Plus2 (Condensing Boiler Systems)

INSTALLATION INSTRUCTIONS OPERATION AND MAINTENANCE MANUAL Models event SD, event, Event Plus, and event Plus2 (Condensing Boiler Systems) C US INSTALLATION INSTRUCTIONS OPERATION AND MAINTENANCE MANUAL Models event SD, event, Event Plus, and event Plus2 (Condensing Boiler Systems) A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE TO MAINTAIN

More information

O B R O U N D G R E A S E D U C T

O B R O U N D G R E A S E D U C T TM O B R O U N D G R E A S E D U C T SlimVent OBROUND GREASE DUCT SlimVent is a UL Classified zero-clearance grease duct system with the space saving profile of a field fabricated rectangular product.

More information

female pipe. A Wall Support must be installed just above the tee and at least every 8 feet thereafter. If the pipe is to be run through a roof overhang then a Flashing, Storm Collar and Vertical Rain Cap

More information

ICC - Model VIP+ Positive Pressure Chimney System and Grease Duct

ICC - Model VIP+ Positive Pressure Chimney System and Grease Duct Scope and Recommendations ICC - Model VIP+ Positive Pressure Chimney System and Grease Duct INSTALLATION AND MAINTENANCE INSTRUCTIONS The ICC Model VIP+ is a double wall construction listed venting system

More information

BuildingName The Description of the Project P DOCUMENTS

BuildingName The Description of the Project P DOCUMENTS ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION

More information

Technical and Dimensional Data. Saf-T Vent SC

Technical and Dimensional Data. Saf-T Vent SC Technical and Dimensional Data Saf-T Vent SC 3"/5" & 4"/7" Concentric Reduced Clearance Double Wall for Special Gas Vent and/or Sealed Combustion Systems Copyright 2003 Saf-T Vent is a registered trademark

More information

A MAJOR CAUSE OF CHIMNEY RELATED FIRES IS FAILURE TO MAINTAIN REQUIRED CLEARANCES (AIR SPACES) TO COMBUSTIBLE MATERIALS.

A MAJOR CAUSE OF CHIMNEY RELATED FIRES IS FAILURE TO MAINTAIN REQUIRED CLEARANCES (AIR SPACES) TO COMBUSTIBLE MATERIALS. 1 Model DW Series General Installation Guidelines UL Listed under Standard 103 for Flue Gas Temperatures up to 1400 F (759 C) Venting System for Factory-Built Chimneys For Building Heating Appliances A

More information

P36-10 / P36E-10 Gas Fireplace. 11 W.C. (2.74 kpa) 10 W.C. (2.49 kpa) 6.4 W.C. (1.59 kpa) 22,000 BTU/h (6.44 kw) 28,500 BTU/h (8.

P36-10 / P36E-10 Gas Fireplace. 11 W.C. (2.74 kpa) 10 W.C. (2.49 kpa) 6.4 W.C. (1.59 kpa) 22,000 BTU/h (6.44 kw) 28,500 BTU/h (8. Model P36-NG10 P36-LP10 P36E-NG10 P36E-LP10 Fuel Type Natural Gas Propane Natural Gas Propane Gas Fireplaces P36-10 / P36E-10 Gas Fireplace Minimum Supply Pressure 5 W.C. (1.25 kpa) 12 W.C. (3.00 kpa)

More information

Chimney Lining Systems

Chimney Lining Systems R Chimney Lining Systems Gas or Propane Fired Appliances Table of Contents 1. General Instructions and Warnings U.L. and Manufacturers Specifi cations...2 2. Types of Liner Systems...3 3. FLEXJET Installation

More information

PROJECT: PREPARED BY: PREPARED FOR: Boiler Breeching and Stack Generator Engine Exhaust Fume Venting Fireplace Venting

PROJECT: PREPARED BY: PREPARED FOR: Boiler Breeching and Stack Generator Engine Exhaust Fume Venting Fireplace Venting M&G DURAVENT DURASTACK PRO POSITIVE PRESSURE SYSTEMS MODELS DAS1 1 INCH AIR INSULATED DIS1 1 INCH CERAMIC FIBER INSULATED DIS2 2 INCH CERAMIC FIBER INSULATED DIS4 4 INCH CERAMIC FIBER INSULATED DCL SINGLE

More information

Gas Fireplaces. P33-10/P33E-10 Gas Fireplace P33 DIMENSIONS WITH VIGNETTE FACEPLATE CLEARANCES WITH VIGNETTE FACEPLATE

Gas Fireplaces. P33-10/P33E-10 Gas Fireplace P33 DIMENSIONS WITH VIGNETTE FACEPLATE CLEARANCES WITH VIGNETTE FACEPLATE Model P33-NG10 P33-LP10 P33E-NG10 P33E-LP10 Fuel Type Natural Gas Propane Natural Gas Propane Minimum Supply Pressure 5 W.C. (1.25 kpa) 11 W.C. (2.74 kpa) 5 W.C. (1.25 kpa) 11 W.C. (2.74 kpa) Manifold

More information

MODEL IPIC SERIES 4G GREASE DUCT

MODEL IPIC SERIES 4G GREASE DUCT INSTALLATION AND MAINTENANCE INSTRUCTIONS WALMART APPLICATION 637N MODEL IPIC SERIES 4G GREASE DUCT 7N71 IT IS OF THE UTMOST IMPORTANCE THAT THIS DUCT BE INSTALLED ONLY IN ACCORDANCE WITH THESE INSTRUCTIONS.

More information

Taking value to the highest level.

Taking value to the highest level. Venting Solutions Taking value to the highest level. Example: 2D Drawings Schebler Chimney Systems is a premier source of custom, modular prefabricated stainless steel chimneys, heavy wall engineered stacks,

More information

SECURE STACK PRO POSITIVE PRESSURE SYSTEMS MODELS

SECURE STACK PRO POSITIVE PRESSURE SYSTEMS MODELS SECURITY CHIMNEYS INTERNATIONAL SECURE STACK PRO POSITIVE PRESSURE SYSTEMS MODELS Boiler Breeching and Stack Generator Engine Exhaust Fume Venting Fireplace Venting CAX1 1 INCH AIR INSULATED CIX1 1 INCH

More information

Z-Vent Model SVE Series III

Z-Vent Model SVE Series III Special Stainless Steel Venting System for Gas Burning Appliances Category I, II, III, & IV Tested and Listed By Underwriters Laboratories Inc. UL 1738 & BH636 Note the following before installation of

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Boiler and Engine Exhaust Chimney Systems Grease Duct Systems (CIX only) Double Wall Construction Positive Pressure Chimney Systems P/N 506065-03 REV. N 02/2015 MODELS CIX / CAX

More information

RECEIVING AND INSPECTION

RECEIVING AND INSPECTION Non-Welded Double Wall Grease Duct/Type HT Chimney Systems Installation, Operation, and Maintenance Manual FOR YOUR SAFETY TWO MAJOR CAUSES OF GREASE DUCT RELATED FIRES: (1) FAILURE TO MAINTAIN REQUIRED

More information

Pre-Fabricated Roof Curbs

Pre-Fabricated Roof Curbs TC-1, TC-2, TC-3, TC-5 Table of Contents General Information 4-5 Specifications 6-9 Assembly Instructions 10-16 Pitch Information 17 Submittal 18-21 54 years of excellence... www.thybar.com 3 Insulated

More information

Installation Instructions

Installation Instructions Installation Instructions SAVE THESE INSTRUCTIONS Please read this entire manual before you install and use your room heater. Failure to follow instructions may result in property damage, bodily injury,

More information

County of Yolo Development Services Building Inspection Division

County of Yolo Development Services Building Inspection Division County of Yolo Development Services Building Inspection Division 292 W. Beamer Street Woodland, CA. 95695 www.yolocounty.org (530) 666-8775 Mechanical Plan Review Comments Plan Review No. Owners Name Job

More information

Installation Instructions

Installation Instructions Installation Instructions Flue Gas System Basic Kit GA-K - Chimney Flue Gas System for GB125 Oil Condensing Boiler For trained and certified installers Please read carefully prior to installation. 6 720

More information

APPLICATION AND LISTING

APPLICATION AND LISTING DURALINER (SDL) 6"-8" DIAMETER (ROUND & OVAL) INSTALLATION INSTRUCTIONS MH14420 CMH1329 THESE INSTALLATION AND OPERATION INSTRUCTIONS COVER DURALINER MASONRY RELINING SYSTEM A MAJOR CAUSE OF CHIMNEY RELATED

More information

Gas Fireplaces. P36D-10 Gas Fireplace. Unit Dimensions With Vignette Faceplate. *** Important: Framing height requires consideration of the hearth

Gas Fireplaces. P36D-10 Gas Fireplace. Unit Dimensions With Vignette Faceplate. *** Important: Framing height requires consideration of the hearth 28-15/16 (735mm) Model P36D-NG10 P36D-LP10 Fuel Type Natural Gas Propane Gas Fireplaces Minimum Supply Pressure Manifold Pressure - High Manifold Pressure - Low 5 W.C. (1.25 kpa) 3.8 W.C. (0.95 kpa) 1.1

More information

Regency Horizon HZ30E Gas Fireplace

Regency Horizon HZ30E Gas Fireplace Specifications: Framing Dimensions: Model HZ3E-NG HZ3E-LP Fuel Type Natural Gas Propane Gas Minimum Supply Pressure Manifold Pressure - High Approved Venting Systems Flex Vent Systems: Rigid Pipe Vent

More information

SECTION DUCTS PART 1 GENERAL 1.01 SUMMARY

SECTION DUCTS PART 1 GENERAL 1.01 SUMMARY 1 1 1 1 1 1 1 1 0 1 0 1 SECTION 1 DUCTS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Duct Materials.. Insulated flexible ducts.. Single wall spiral round ducts.. Ductwork fabrication.. Duct cleaning.

More information

MODEL N, VSI, IVSI & ZC SINGLE WALL, DOUBLE WALL AIR & CERAMIC FIBER INSULATED POSITIVE PRESSURE PIPING SYSTEMS

MODEL N, VSI, IVSI & ZC SINGLE WALL, DOUBLE WALL AIR & CERAMIC FIBER INSULATED POSITIVE PRESSURE PIPING SYSTEMS INSTALLATION INSTRUCTIONS & MAINTENANCE GUIDE MODEL N, VSI, IVSI & ZC SINGLE WALL, DOUBLE WALL AIR & CERAMIC FIBER INSULATED POSITIVE PRESSURE PIPING SYSTEMS BOILER STACK ENGINE EXHAUST GREASE DUCT VENTILATION

More information

MODEL G, PS, IPS & ZC SINGLE WALL, DOUBLE WALL AIR & CERAMIC FIBER INSULATED POSITIVE PRESSURE PIPING SYSTEMS

MODEL G, PS, IPS & ZC SINGLE WALL, DOUBLE WALL AIR & CERAMIC FIBER INSULATED POSITIVE PRESSURE PIPING SYSTEMS INSTALLATION INSTRUCTIONS & MAINTENANCE GUIDE MODEL G, PS, IPS & ZC SINGLE WALL, DOUBLE WALL AIR & CERAMIC FIBER INSULATED POSITIVE PRESSURE PIPING SYSTEMS BOILER STACK ENGINE EXHAUST GREASE DUCT A MAJOR

More information

DuraFlex. Flexible stainless steel relining for masonry chimney. UL 1777 and ULC S635.

DuraFlex. Flexible stainless steel relining for masonry chimney. UL 1777 and ULC S635. DuraFlex Flexible stainless steel relining for masonry chimney. UL 1777 and ULC S635. Specifications DuraFlex Pro Applications DuraFlex Pro ultra flexible relining for masonry chimney. Use with gas, wood

More information

Concentric Vent/Air System Supplement

Concentric Vent/Air System Supplement Concentric Vent/Air System Supplement This document is intended to be used by a qualified heating contractor or service technician. Read all instructions within this document and within the CHAL- LENGER

More information

B. American Society for Testing and Materials: 1. ASTM F708 - Standard Practice for Design and Installation of Rigid Pipe Hangers.

B. American Society for Testing and Materials: 1. ASTM F708 - Standard Practice for Design and Installation of Rigid Pipe Hangers. SECTION 230529 - HANGERS AND SUPPORTS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe hangers and supports. 2. Hanger rods. 3. Inserts. 4. Flashing. 5. Sleeves. 6. Mechanical sleeve seals. 7. Firestopping

More information

DuraFlex. Flexible stainless steel relining for masonry chimney. UL 1777 and ULC S635.

DuraFlex. Flexible stainless steel relining for masonry chimney. UL 1777 and ULC S635. DuraFlex Flexible stainless steel relining for masonry chimney. UL 1777 and ULC S635. Specifications DuraFlex SW Applications DuraFlex SW smooth wall flexible relining for masonry chimney. Use with gas,

More information

SUBMITTAL RECORD. Material Selection FLUE (INNER WALL) CASING (OUTER WALL) GALVALUME

SUBMITTAL RECORD. Material Selection FLUE (INNER WALL) CASING (OUTER WALL) GALVALUME SUBMITTAL RECORD UL 1978 - Grease Duct Professional Series Kitchen Ventilation DCL Single Wall DAS1 1-inch Air Insulated DIS1 1-inch Insulated (AES WOOL) DIS2 2-inch Insulated (AES WOOL) DIS4 4-inch Insulated

More information

InoxSabiana 25 Flues. Stainless Steel Double Wall

InoxSabiana 25 Flues. Stainless Steel Double Wall Cert. n 0545/5 Flues Stainless Steel Double Wall Introduction and main constructional characteristics Double Wall, Stainless Steel Flues The is the result of innovative development based on over 0 years

More information

P36 - P36D Zero Clearance Direct Vent Gas Fireplace. 12 W.C. (3.00 kpa) 11 W.C. (2.74 kpa) 2.9 W.C. (0.72 kpa) 15,000 BTU/h (3.

P36 - P36D Zero Clearance Direct Vent Gas Fireplace. 12 W.C. (3.00 kpa) 11 W.C. (2.74 kpa) 2.9 W.C. (0.72 kpa) 15,000 BTU/h (3. P36 - P36D Zero Clearance Direct Vent Gas Fireplace Model P36-NG4 P36-LP4 P36D-NG1 P36D-LP1 Fuel Type Natural Gas Propane Natural Gas Propane Minimum Supply Pressure 5 W.C. (1.25 kpa) 12 W.C. (3. kpa)

More information

Installation Instructions. PolyPro Double-Wall Flex Gas Vent System for Category II & IV Gas-Burning Appliances. PolyPro Flex

Installation Instructions. PolyPro Double-Wall Flex Gas Vent System for Category II & IV Gas-Burning Appliances. PolyPro Flex Installation Instructions PolyPro Double-Wall Flex Gas Vent System for Category II & IV Gas-Burning Appliances PolyPro Flex A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE TO MAINTAIN REQUIRED CLEARANCES

More information

HIGH EFFICIENCY POSITIVE PRESSURE VENTING SYSTEMS FOR CONDENSING APPLIANCES, CATEGORIES II, III AND IV Single & Double Wall Construction

HIGH EFFICIENCY POSITIVE PRESSURE VENTING SYSTEMS FOR CONDENSING APPLIANCES, CATEGORIES II, III AND IV Single & Double Wall Construction HIGH EFFICIENCY POSITIVE PRESSURE VENTING SYSTEMS FOR CONDENSING APPLIANCES, CATEGORIES II, III AND IV Single & Double Wall Construction Models HEP HEPL HEPL2 28 KJ This symbol shows that CHEMINÉE LINING.E

More information

SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT SECTION 23 05 29 HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section includes pipe and equipment supports, hangers, anchors, bases sleeves and the sealing of work

More information

DuraLiner. Insulated, double-wall masonry relining. UL 1777, ULC S635, and ULC S640.

DuraLiner. Insulated, double-wall masonry relining. UL 1777, ULC S635, and ULC S640. DuraLiner Insulated, double-wall masonry relining. UL 1777, ULC S635, and ULC S640. Specifications pplications DuraLiner is a high-temperature, insulated double-wall masonry relining system for use with

More information

Exterior System installation instructions

Exterior System installation instructions Exterior System installation instructions 11/20/14 WPS ES-400 & 500 INSTALLATION INSTRUCTION. The WPS ES-400 & 500 systems Façade panels are designed for use as an external wall cladding in conjunction

More information

Building Permit Application

Building Permit Application Building Permit Application Administrative Use Only PARENT PERMIT NUMBER (Required if part of another project) PERMITTEE: PERMITTEE ADDRESS: E-MAIL ADDRESS: ARCHITECT/ENGINEER: ARCHITECT/ENGINEER ADDRESS:

More information

Light Stainless Flexible Liner

Light Stainless Flexible Liner Light Stainless Flexible Liner Dalsin Line light flexible liner is listed for chimney relining and is suitable for wood, pellet, gas, oil, and coal applications. This liner is manufactured using.006 thick

More information

SUBMITTAL RECORD. Material Selection FLUE (INNER WALL) CASING (OUTER WALL) GALVALUME

SUBMITTAL RECORD. Material Selection FLUE (INNER WALL) CASING (OUTER WALL) GALVALUME SUBMITTAL RECORD UL 1978 - Grease Duct Professional Series Kitchen Ventilation SCL Single Wall CAX1 1-inch Air Insulated CIX1 1-inch Insulated (AES WOOL) CIX2 2-inch Insulated (AES WOOL) CIX4 4-inch Insulated

More information

MODEL N, VSI, IVSI & ZC SINGLE WALL, DOUBLE WALL AIR & FIBER INSULATED POSITIVE PRESSURE PIPING SYSTEMS BOILER STACK ENGINE EXHAUST GREASE DUCT

MODEL N, VSI, IVSI & ZC SINGLE WALL, DOUBLE WALL AIR & FIBER INSULATED POSITIVE PRESSURE PIPING SYSTEMS BOILER STACK ENGINE EXHAUST GREASE DUCT INSTALLATION INSTRUCTIONS & MAINTENANCE GUIDE MODEL N, VSI, IVSI & ZC SINGLE WALL, DOUBLE WALL AIR & FIBER INSULATED POSITIVE PRESSURE PIPING SYSTEMS BOILER STACK ENGINE EXHAUST GREASE DUCT A MAJOR CAUSE

More information

Gas Fireplaces. P33 Zero Clearance Direct Vent Gas Fireplace. *** Important: Framing height requires consideration of the hearth

Gas Fireplaces. P33 Zero Clearance Direct Vent Gas Fireplace. *** Important: Framing height requires consideration of the hearth P33 Zero Clearance Direct Vent Gas Fireplace P33 WITH THE FLUSH OR BAY FRONT Model P33-NG4 P33-LP4 Fuel Type Natural Gas Propane Minimum Supply Pressure 5 W.C. (1.25 kpa) 12 W.C. (3.00 kpa) Manifold Pressure

More information

DETAIL INSTRUCTION No. 1

DETAIL INSTRUCTION No. 1 BEFORE BEGINNING INSTALLATION, PLEASE READ THROUGH ALL INSTRUCTIONS. Uncrate shipment and check against packing list to insure all materials are included before beginning installation. If any discrepencies

More information

Duct Wrap Flexible Wraps

Duct Wrap Flexible Wraps Design No. 3MU/ 60-01 December 23, 2010 VENTILATION DUCT PROTECTION 3M Company 3M Fire Barrier Duct Wraps: 615 and 615+ 3M Fire Barrier Sealants: Water-Tight 1000-NS Silicone, Water-Tight 1003-SL Silicone

More information

Pre-Fabricated Roof Curbs

Pre-Fabricated Roof Curbs Knock Down Curb Assembly Instructions These roof curb assembly instructions are to be used as general guidelines only. Included with shipment are as-built drawings for proper location of sections and channels.

More information

SECTION INDUSTRIAL ACCESS / INSPECTION HATCH. A. Industrial Access / Inspection Hatch: Model AH-710

SECTION INDUSTRIAL ACCESS / INSPECTION HATCH. A. Industrial Access / Inspection Hatch: Model AH-710 Page 1 of 6 PART 1 - GENERAL SECTION 08370 INDUSTRIAL ACCESS / INSPECTION HATCH 1.1 SECTION INCLUDES A. Industrial Access / Inspection Hatch: Model AH-710 1.2 RELATED SECTIONS A. Section 04810 - Unit Masonry

More information

SSL-175. Specifications

SSL-175. Specifications SSL-175 Specifications Everlast Metals 10 Enterprise Court Lebanon, PA 17042 Phone: (717) 270-6554 Fax: (717) 270-6569 www.everlastmetals.com 7410 Preformed Metal Roofing PART 1: GENERAL 1.01 SECTION INCLUDES

More information

METALLIC CHIMNEY LINER SYSTEM Single Wall Construction Rigid Chimney Liner

METALLIC CHIMNEY LINER SYSTEM Single Wall Construction Rigid Chimney Liner METALLIC CHIMNEY LINER SYSTEM Single Wall Construction Rigid Chimney Liner Models CBI Cat. I: Part 1 CBH Cat I, II, III, IV: Part 2 3STS This symbol shows that venting systems Models CBI and CBH are Listed

More information

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT. A. ASME B31.1 (American Society of Mechanical Engineers) - Power Piping

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT. A. ASME B31.1 (American Society of Mechanical Engineers) - Power Piping SECTION 22 05 29 HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section includes pipe and equipment supports, hangers, anchors, bases sleeves and the sealing of

More information

SECTION CONDUITS AND BACKBOXES FOR COMMUNICATIONS SYSTEMS

SECTION CONDUITS AND BACKBOXES FOR COMMUNICATIONS SYSTEMS SECTION 16711-27 05 28.33 PART 1 - GENERAL 1.01 SUMMARY A. This section includes Labor, materials and equipment necessary to complete the installation required for the items specified under this Section,

More information

SI T T FSS/FSTT Open Fire

SI T T FSS/FSTT Open Fire SI 440-600-700-700T-780-780T-900-1100 FSS/FSTT Open Fire Freestanding Solid Fuel Burner - Indoor Open Wood Fire Available in Square Top or Taper Top Options Installation Instructions Note: Flue System

More information

ARTICLE 12 INTERNATIONAL RESIDENTIAL CODE 2012 International Residential Code Modification Summary (Statutory Authority: 1976 Code Section )

ARTICLE 12 INTERNATIONAL RESIDENTIAL CODE 2012 International Residential Code Modification Summary (Statutory Authority: 1976 Code Section ) 8-1200. International Residential Code. ARTICLE 12 INTERNATIONAL RESIDENTIAL CODE 2012 International Residential Code Modification Summary (Statutory Authority: 1976 Code Section 6-9-40) NOTE-This article

More information

Division 07 Thermal and Moisture Protection Thermal Protection Blanket Insulation Page 1 of 11

Division 07 Thermal and Moisture Protection Thermal Protection Blanket Insulation Page 1 of 11 07 21 16 Blanket Insulation Page 1 of 11 Unifrax I LLC Design No. UNI/BI 120-14 FIRE RESISTANT GREASE DUCT FyreWrap Elite 1.5 Duct Insulation ASTM E 2336-16 and ICC-ES Acceptance Criteria for Grease Duct

More information

Installation Instructions

Installation Instructions Installation Instructions Flue Gas System Basic Kit HT-K - Horizontal Flue Gas System For GB125 Oil Condensing Boiler For trained and certified Installers Please read carefully prior to installation. 6

More information

SI T T FST

SI T T FST SI 440-600-700-700T-780-780T-900-1100 Freestanding TAPER TOP Open Fire - Wood Burner Installation Instructions Note: FLUE SYSTEMS Casing. Flue System may require to be Doubled Lined to Comply. Ref ASNZS:2918:2001

More information

Division 07 Thermal and Moisture Protection Thermal Protection Blanket Insulation Page 1 of 17

Division 07 Thermal and Moisture Protection Thermal Protection Blanket Insulation Page 1 of 17 07 21 16 Blanket Insulation Page 1 of 17 Design Number UNI/BI 120-03 FIRE RESISTANT GREASE DUCT Unifrax I LLC FyreWrap Elite 1.5 Duct Insulation CAN/ULC S144 Fire Resistance Rating 2 hours Fire Inside

More information

SUBMITTAL RECORD MODEL CIX3Z ZERO CLEARANCE GREASE DUCT KITCHEN VENTILATION. Material Selection FLUE (INNER WALL) CASING (OUTER WALL) 316 GALVALUME

SUBMITTAL RECORD MODEL CIX3Z ZERO CLEARANCE GREASE DUCT KITCHEN VENTILATION. Material Selection FLUE (INNER WALL) CASING (OUTER WALL) 316 GALVALUME SUBMITTAL RECORD ZERO CLEARANCE GREASE DUCT KITCHEN VENTILATION MODEL CIX3Z Listed to standards: UL 1978 UL 2221 SUBMITTAL RECORD PREPARED FOR: REFERENCE: LOCATION: CONTACT: TELEPHONE: FAX: EMAIL: PREPARED

More information

MODEL GZ Zero Clearance Grease Duct Installation Instructions Tested to UL 1978/ULC S662, UL 2221/ULC S144, ASTM E814 CO., INC.

MODEL GZ Zero Clearance Grease Duct Installation Instructions Tested to UL 1978/ULC S662, UL 2221/ULC S144, ASTM E814 CO., INC. MODEL GZ Zero Clearance Grease Duct Installation Instructions Tested to UL 1978/ULC S662, UL 2221/ULC S144, ASTM E814 CO., INC. NOTES TABLE OF CONTENTS LISTING & CODE COMPLIANCE..................................................................

More information

SECTION ALUMINUM WALKWAY COVERS. A. The requirements of Division 1 specifications shall apply to work specified in the section.

SECTION ALUMINUM WALKWAY COVERS. A. The requirements of Division 1 specifications shall apply to work specified in the section. SECTION 10 5300 ALUMINUM WALKWAY COVERS Part 1 General 1.01 Related Documents A. The requirements of Division 1 specifications shall apply to work specified in the section. 1.02 References A. International

More information

DL-200. Specifications

DL-200. Specifications DL-200 Specifications Everlast Metals 10 Enterprise Court Lebanon, PA 17042 Phone: (717) 270-6554 Fax: (717) 270-6569 www.everlastmetals.com 7410 Structural Preformed Metal Roofing PART 1: GENERAL 1.01

More information

METALWorkS. RH200 Custom Hook-on Panels. General Installation Instructions. Ceiling 1.0 GENERAL Site Conditions Product Description

METALWorkS. RH200 Custom Hook-on Panels. General Installation Instructions. Ceiling 1.0 GENERAL Site Conditions Product Description Ceiling Systems Between us, ideas become reality METALWorkS General Installation Instructions RH200 Custom Hook-on Panels 1.0 GENERAL 1.1. Product Description RH200 system is a downward accessible, metal

More information

DuraPlus. All-fuel, triple-wall chimney system. UL 103 HT.

DuraPlus. All-fuel, triple-wall chimney system. UL 103 HT. DuraPlus ll-fuel, triple-wall chimney system. UL 103 HT. Specifications pplications DuraPlus himney is a triple-wall, all-fuel chimney for use with wood stoves, fireplaces, furnaces, boilers, stoves, ranges,

More information

Stainless Steel Aeration Equipment Specification

Stainless Steel Aeration Equipment Specification Section 15 Stainless Steel Aeration Equipment Specification Part 1 - General 1.01 Description A. Scope of Work 1. Furnish, install and test aeration system including air mains, drop pipes, valves, expansion

More information

Standard Installation Fire Damper Models: 119, 119(F), 119(SS), D19

Standard Installation Fire Damper Models: 119, 119(F), 119(SS), D19 Standard Installation Fire Damper Models: 119, 119(F), 119(SS), D19 Page 1 or 8 APPLICATION This fi re damper is intended to restrict the passage of fl ame. The standard installation requires that the

More information

SECTION NON-STRUCTURAL METAL FRAMING

SECTION NON-STRUCTURAL METAL FRAMING SECTION 09 22 16 PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies steel studs wall systems, shaft wall systems, ceiling or soffit suspended or furred framing, wall furring, fasteners, and accessories

More information

1. ARI 410 Standard for chilled water, hot water and steam coils. 2. ARI 430 Central Station Air Handling Units

1. ARI 410 Standard for chilled water, hot water and steam coils. 2. ARI 430 Central Station Air Handling Units PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION SECTION 21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 - GENERAL 1.1 SUMMARY A. This section supplements all sections in this division, including pipe, fittings, valves, and connections for sprinkler

More information

FIREPLACE INSERT ENCLOSURE INSTALLATION INSTRUCTIONS

FIREPLACE INSERT ENCLOSURE INSTALLATION INSTRUCTIONS FIREPLACE INSERT ENCLOSURE INSTALLATION INSTRUCTIONS ENCLOSURE MODEL 90566400 FOR INSERT MODEL 5660NA And ENCLOSURE MODEL 90566000 FOR INSERT MODEL 5660 STANDARD KEEP THESE INSTRUCTIONS FOR FUTURE USE

More information

HOTEL SPECIFICATION SECTION 08100

HOTEL SPECIFICATION SECTION 08100 Part 1 General HOTEL SPECIFICATION SECTION 08100 1.01 Work Included A. The work under this section shall include the furnishing of all items shown on the drawings and as specified including, but not limited

More information

A. Flat corner wall-to-wall See page 8. C. Outside corner wall-to-wall See page 8. B. Inside corner kit wall-to-wall See page 7

A. Flat corner wall-to-wall See page 8. C. Outside corner wall-to-wall See page 8. B. Inside corner kit wall-to-wall See page 7 System Overview These instructions review how to install drywall versions of TruGroove recessed corners. Please refer to layout drawings supplied by Philips Ledalite with these installation instructions.

More information

K. All mechanical rooms shall be designed with a minimum 3-1/2 dropped floor.

K. All mechanical rooms shall be designed with a minimum 3-1/2 dropped floor. PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

INSTALLATION AND MAINTENANCE INSTRUCTIONS

INSTALLATION AND MAINTENANCE INSTRUCTIONS INSTALLATION AND MAINTENANCE INSTRUCTIONS DuraStack Pro Series Boiler Stack Engine Exhaust Grease Duct DuraZDuct Zero Clearance Grease Duct MODEL DCL MODEL DIS1 MODEL DIS4 MH 10971 MH 45179 MODEL DAS1

More information

TYPICAL ROOF CONDITION LAYOUT

TYPICAL ROOF CONDITION LAYOUT FIXED POINTS TYPICAL ROOF CONDITION LAYOUT 15 17 9 16 29 12 14 11 3 7 35 20 6 23 30 31 24 13 18 Typical Roof Condition Layout... 1 Low Eave Isometric View - Fixed/ Floating... 2 Low Eave Section - Fixed/

More information

Diffused Aeration Piping Equipment

Diffused Aeration Piping Equipment 1.0 General 1.1. The specifications in this section include all components of the Diffused Aeration System with the exception of the individual diffuser units. Refer to additional specification sections

More information

A. Pipe Supports: ANSI B 31.1, Power Piping. B. Automatic Sprinkler Pipe Supports: Refer to Section

A. Pipe Supports: ANSI B 31.1, Power Piping. B. Automatic Sprinkler Pipe Supports: Refer to Section SECTION 15140 SUPPORTS, ANCHORS, AND SEALS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract including General and Supplementary Conditions, Division 1 Specification

More information

Description/Application Maximum Temperature Continuous Firing Maximum Temperature Intermittent Firing Fuel Construction Diameters: Insulation

Description/Application Maximum Temperature Continuous Firing Maximum Temperature Intermittent Firing Fuel Construction Diameters: Insulation Description/Application Double wall air or optional fiber insulated positive pressure system for venting boilers, kilns, grease ducts, emergency generators, caustic air, coffee roasters, bagel ovens, bread

More information

Dur aflex stainless steel

Dur aflex stainless steel Dur aflex stainless steel Simpson Dura-Vent Engineered Excellence DuraFlex SW DuraFlex SW is a smooth inner-wall, flexible stainless steel chimney liner. The smooth inner wall provides for no output reduction

More information

COLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100

COLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100 COLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100 Part 1 General 1.01 Work Included A. The work under this section shall include the furnishing of all items shown on the drawings and as specified,

More information

Outer Skin Kit & Flue: IB600, IB850, IB1100 Installation Manual

Outer Skin Kit & Flue: IB600, IB850, IB1100 Installation Manual Outer Skin Kit & Flue: IB600, IB850, IB1100 Installation Manual Please see IB series product installation guide for details of installing the gas fire into this preformed metal cavity. Important: The appliance

More information

City of Omaha Plans and Permits Commercial Alterations and Conversions Building Permit Submittal Checklist

City of Omaha Plans and Permits Commercial Alterations and Conversions Building Permit Submittal Checklist City of Omaha Plans and Permits Commercial Alterations and Conversions Building Permit Submittal Checklist This checklist contains the standard information required on submittals for commercial construction

More information

Nortrax Section David Manchester Road, Ottawa NON-STRUCTURAL METAL FRAMING 16 May 2014 Page 1

Nortrax Section David Manchester Road, Ottawa NON-STRUCTURAL METAL FRAMING 16 May 2014 Page 1 16 May 2014 Page 1 PART 1 GENERAL 1.1 DESCRIPTION This section specifies steel studs wall systems, shaft wall systems, ceiling or soffit suspended or furred framing, wall furring, fasteners, and accessories

More information

Simpson Dura-Vent Engineered Excellence

Simpson Dura-Vent Engineered Excellence DuraPlus Simpson Dura-Vent Engineered Excellence pplications DuraPlus himney is a triple-wall, all-fuel chimney for use with wood stoves, fireplaces, furnaces, boilers, stoves, ranges, water heaters, or

More information

Flat Bank SERIES 05FB AND 07FB. Options CONSTRUCTION FEATURES EQUIPMENT OPTIONS PRODUCT DATA CLEAN-LINE TM SERIES 05FB/07FB PD-CLFB-03A JANUARY 2003

Flat Bank SERIES 05FB AND 07FB. Options CONSTRUCTION FEATURES EQUIPMENT OPTIONS PRODUCT DATA CLEAN-LINE TM SERIES 05FB/07FB PD-CLFB-03A JANUARY 2003 PRODUCT SERIES 05FB/07FB PD-CLFB-03A FILTRATION EQUIPMENT SERIES 05FB AND 07FB 2" AND 4" FLAT BANK FILTER HOUSINGS Flat Bank CONSTRUCTION FEATURES 16 GAUGE ALUMINIZED STEEL FACTORY ASSEMBLED (2) HINGED

More information

150MM FREE STANDING WOOD FIRE FLUE KIT MKIII INSTALLATION INSTRUCTIONS

150MM FREE STANDING WOOD FIRE FLUE KIT MKIII INSTALLATION INSTRUCTIONS 150MM FREE STANDING WOOD FIRE FLUE KIT MKIII INSTALLATION INSTRUCTIONS WARNING: THIS FLUE KIT HAS BEEN MANUFACTURED IN ACCORDANCE WITH AS/NZS 2918:2001 AND TESTED TO APPENDIX F. TO ENSURE SAFETY THIS FLUE

More information

150MM FREE STANDING WOOD FIRE FLUE KIT MKIII INSTALLATION INSTRUCTIONS

150MM FREE STANDING WOOD FIRE FLUE KIT MKIII INSTALLATION INSTRUCTIONS 150MM FREE STANDING WOOD FIRE FLUE KIT MKIII INSTALLATION INSTRUCTIONS WARNING: THIS FLUE KIT HAS BEEN MANUFACTURED IN ACCORDANCE WITH AS/NZS 2918:2001 AND TESTED TO APPENDIX F. TO ENSURE SAFETY THIS FLUE

More information

Details of technical leaflets/write-up on various pieces of equipment.

Details of technical leaflets/write-up on various pieces of equipment. Details of technical leaflets/write-up on various pieces of equipment. (1) Insulator Designs: The insulators are provided in one, two, three, or four insulator designs per location and spaced to provide

More information

This specification describes the minimum requirements for industrial thermal insulation.

This specification describes the minimum requirements for industrial thermal insulation. 016/09/7 1/7 1.0 PURPOSE This specification describes the minimum requirements for industrial thermal insulation. Read it in conjunction with the applicable insulation and insulation finish specifications

More information

150MM FREE STANDING WOOD FIRE FLUE KIT MKIII INSTALLATION INSTRUCTIONS

150MM FREE STANDING WOOD FIRE FLUE KIT MKIII INSTALLATION INSTRUCTIONS ULEB 150MM FREE STANDING WOOD FIRE FLUE KIT MKIII INSTALLATION INSTRUCTIONS WARNING: THIS FLUE KIT HAS BEEN MANUFACTURED IN ACCORDANCE WITH AS/NZS 2918:2001 AND TESTED TO APPENDIX F. TO ENSURE SAFETY THIS

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 102239 - FOLDING PANEL PARTITIONS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

CONSTRUCTION DOCUMENTS CHECKLIST for the 2012 Michigan Building Code Including Building Permit Application Checklist

CONSTRUCTION DOCUMENTS CHECKLIST for the 2012 Michigan Building Code Including Building Permit Application Checklist CONSTRUCTION DOCUMENTS CHECKLIST for the 2012 Michigan Building Code Including Building Permit Application Checklist This checklist is a convenient reference to the 2012 Michigan Building Code. The checklist

More information

5. AMCA 301 Method of Publishing Sound Ratings for Air Moving Devices. 6. AMCA 500 Test Methods for Louver, Dampers, and Shutters

5. AMCA 301 Method of Publishing Sound Ratings for Air Moving Devices. 6. AMCA 500 Test Methods for Louver, Dampers, and Shutters PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

SECTION A. Product Data: Manufacturer's data sheets on each product to be used, including:

SECTION A. Product Data: Manufacturer's data sheets on each product to be used, including: Page 1 of 8 SECTION 083919 WATERTIGHT DOORS **Note to Specifier** This specification contains component and configuration options. Where indicated, choose the appropriate choice for your specific project

More information

EPV Pellet Vent Pellet Stove Venting System Installation Instructions

EPV Pellet Vent Pellet Stove Venting System Installation Instructions EPV Pellet Vent Pellet Stove Venting System Installation Instructions A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE TO MAINTAIN REQUIRED CLEARANCES (AIR SPACES) TO COMBUSTIBLE MATERIALS. IT IS OF THE

More information

A. Section includes busway and fittings including plug-in units.

A. Section includes busway and fittings including plug-in units. SECTION 26 25 00 ENCLOSED BUS ASSEMBLIES PART 1 - GENERAL 1.1 SUMMARY A. Section includes busway and fittings including plug-in units. 1.2 REFERENCES A. Institute of Electrical and Electronics Engineers:

More information

RECOMMENDED STANDARDS for the INSTALLATION of WOODBURNING STOVES

RECOMMENDED STANDARDS for the INSTALLATION of WOODBURNING STOVES RECOMMENDED STANDARDS for the INSTALLATION of WOODBURNING STOVES Prepared By Office of State Fire Marshal Maine Office of Energy Resources 52 State House Station 55 Capital Street Augusta, ME 04333 Augusta,

More information

SECTION ALUMINUM HANDRAIL SYSTEMS

SECTION ALUMINUM HANDRAIL SYSTEMS SECTION 05520 ALUMINUM HANDRAIL SYSTEMS PART 1 - GENERAL 1.01 SUMMARY A. Section includes aluminum handrails and railings. B. Related Work: 1. Section 03300 - Cast-in-Place Concrete C. References: 1. American

More information

SECTION STAINLESS STEEL WALL PANELS

SECTION STAINLESS STEEL WALL PANELS SECTION 07400 PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Dry joint, Rainscreen stainless steel wall panel system. 2. Accessories including attachments, clips, sub girts, shims, and fasteners 3.

More information