SECTION IRRIGATION PIPELINE LINING (CURED-IN-PLACE PIPE)
|
|
- Darcy Chapman
- 5 years ago
- Views:
Transcription
1 SECTION IRRIGATION PIPELINE LINING (CURED-IN-PLACE PIPE) PART 1 GENERAL 1.01 SECTION INCLUDES A. Irrigation pipeline lining, as herein specified, consists of installing pipe liner by trenchless methods at the locations indicated in the Drawings. The Contractor shall provide all labor, material and equipment necessary to install the pipe liner, specials and appurtenant apparatus required to complete the pipeline installation in an operating, watertight condition. The Contractor shall also furnish all supports, bracing and other materials and all work required for hauling, unloading, protecting, dewatering, placing, and cleanup of the irrigation pipeline liner installation. B. The Contractor is hereby notified that the District s agricultural irrigation distribution pipelines are pressure pipelines, unlike gravity storm drain pipelines, and are therefore constructed to tighter standards than such storm drain pipelines. C. The size and configuration of the various components shall be as indicated herein, in the Standard Details, and in the approved Improvement Plans, if any. D. All materials and installation shall be in accordance with the standards and specifications of the Solano Irrigation District, latest revisions REFERENCED DOCUMENTS A. This specification references American Society for Testing and Materials (ASTM) standard specifications, which are made a part hereof by such reference and shall be the latest edition and revision thereof. B. F Standard Practice for Rehabilitation of Existing Pipelines and Conduits by the Inversion and Curing of a Resin Impregnated Tube. C. F-1743 Standard Practice for Rehabilitation of Existing Pipelines and Conduits by Pulled-in-Place Installation of Cured-in-Place Thermosetting Resin Pipe (CIPP). D. D Test Method for Tensile Properties of Plastics. E. D Test Method for Tensile Properties of Unreinforced and Reinforced Plastics and Electrical Insulating Materials. F. D Standard Specifications for Cured-In-Place Thermosetting Resin Sewer Piping Systems Approved: July 18, 2012 Page 1 of 8
2 1.03 DESCRIPTION OF WORK A. It is the intent of this specification to provide for the reconstruction of existing monolithic concrete irrigation pipelines by forming a new pipe within an existing structurally sound but cracked and leaking pipe that has generally maintained its original shape. The process is defined as the reconstruction of existing pipelines by installation of a thermosetting resin impregnated flexible felt fiber tube with an impermeable inner surface. The resin-impregnated tube is formed to the host pipe utilizing a water column. Curing is accomplished by circulating hot water (or other approved method) throughout the length of the tube to cure the thermosetting resin into a hard, impermeable pipe, in accordance with the specified curing schedule supplied by the resin manufacturer. B. The cured-in-place pipe (CIPP) shall provide flow capacity equal to or greater than 100 percent of the original pipe's flow capacity, when the original pipe was new. C. The CIPP shall extend the full length of the original pipe and shall provide a structurally sound, impermeable, jointless liner close fitting to the host pipe. D. The work shall be done after irrigation water deliveries are completed for the season. Flow bypassing will not be required SAFETY A. The Contractor shall particularly conform to applicable safety regulation pertaining to confined space procedures. Refer to General Conditions section DESIGN CONDITIONS A. Service conditions are as shown in the Drawings. Per ASTM F-1216, the pipe is partially deteriorated. The groundwater level should be below the pipe and the ground may be saturated during the rainy season while the pipe is empty REQUIRED SUBMITTALS A. The Contractor shall be responsible for submitting to the Engineer for approval the following: 1. CIPP design 2. Liner product information 3. CIPP samples 4. CIPP test results from pre-installation testing 5. Felt impregnation site 6. Contractor s installation procedure Page 2 of 8 Approved: July 18, 2012
3 PART 2 MATERIALS 2.01 FLEXIBLE FELT TUBE A. The tube shall consist of one or more layers of flexible needled felt material or an equivalent nonwoven or woven material capable of carrying resin and withstanding installation pressures, have sufficient strength to bridge missing pipe, and withstanding curing temperatures. The outside layer of the tube shall be coated with an impermeable, flexible membrane that will contain the resin and allow the resin impregnation (wet out) procedure to be monitored. The tubing shall be properly sized to the diameter and length of the irrigation pipe to be rehabilitated and be able to stretch to fit irregular pipe sections. B. The tube shall be marked for distance at regular intervals along its entire length, not to exceed 5 ft. Such markings shall include the manufacturers name or identifying symbol RESIN/CATALYST: A. The liquid thermosetting resin used to impregnate the tube shall produce a properly cured tube which will be resistant to abrasion due to solids, grit and sand. The cured tube shall also be resistant to corrosion due to acids and gases such as sulfuric acid, carbonic acid, hydrogen sulfide, methane and carbon monoxide. The resin selected shall have proven resistance to raw, untreated water used for irrigation. B. The resin system shall be a corrosion resistant polyester or vinyl ester system including all required catalysts and initiators that when cured within the tube create a composite that satisfies the requirements of ASTM F1216, ASTM D5813 and ASTM F1743, the physical properties herein, and those which are to be utilized in the submitted and approved design of the CIPP for this project. The resin shall produce a CIPP that will comply with the structural and chemical resistance requirements of this specification TUBE IMPREGNATION A. The Contractor will designate a location where the felt tube will be impregnated. The quantity of resin used for tube impregnation shall be sufficient to fill the volume of air voids in the tube with additional allowances for polymerization shrinkage and the loss of resin through cracks and irregularities in the original pipe wall. A vacuum impregnation process shall be used, and a roller system shall be used to uniformly distribute the resin throughout the tube. B. The tube should be vacuum impregnated with resin (wet-out) under controlled conditions. The volume of resin used should be sufficient to fill all voids in the tube material at nominal thickness and diameter. The volume should be adjusted by adding 5 to 10 % excess resin for the change in resin volume due to polymerization and to allow for any migration of resin into the cracks and joints in the original pipe Approved: July 18, 2012 Page 3 of 8
4 PART 3 EXECUTION 3.01 STRUCTURAL REQUIREMENTS A. The CIPP thickness shall be calculated and designed based upon the following physical condition of the existing pipe to be rehabilitated. 1. All pipes shall be designed in accordance with ASTM F-1216 specifications. 2. All pipes shall be subjected to soil load of 120 lbs./cu.ft., when applicable. 3. All pipes may have a minimum of 2% ovality in the circumference. Note: Conditions 1 and/or 3 may change after the video inspection and later caseby-case design calculations CONDITIONS OF PREPARATION A. Entry into the existing monolithic concrete pipeline will be made from an existing above ground concrete box structure. The concrete structure typically has an interior dimensions of four feet square (4 x4 ) or four feet by six feet (4 x6 ) with an exterior height of eight to ten feet above grade. The concrete structures are free standing without ladders, stairs or pedestrian access points INSTALLATION PREPARATION A. The Contractor shall execute his operations in strict accordance with all Cal/OSHA and manufacturer's safety requirements. Particular attention is required for those safety requirements involving working with scaffolding, entering confined spaces and operations with hot media. B. The interior of the pipeline shall be carefully inspected by remote video methods to determine the location of any conditions which may prevent proper installation of the lining into the pipelines. The locations shall be noted so that these conditions can be corrected before the installation of the CIPP. Inspection of the pipeline shall be performed by experienced personnel trained in locating breaks, obstacles, and service connections by closed-circuit television. The District shall be given and keep a videotape and suitable log for later reference. C. It shall be the Contractor's responsibility to remove all debris located within the irrigation pipe to the degree required by the liner manufacturer and dispose of debris in accordance with all applicable laws and regulations, at the Contractor s expense. D. It shall be the responsibility of the Contractor to conduct a videotape inspection of the irrigation pipe immediately before insertion of the resin impregnated tube to assure that the pipe is clean and existing pipe conditions are acceptable for lining Page 4 of 8 Approved: July 18, 2012
5 E. The Contractor shall be responsible to correct internal pipe conditions that prevent proper installation of the liner INSTALLATION PROCEDURE A. The resin-impregnated felt tube shall be inserted through an existing concrete box structure by means of an inversion ring, standpipe, or pulled-in-place, capable of applying the hydrostatic head required to fully extend the tube to the next designated structure. The tube shall be inserted into the inversion standpipe, and then the tube shall be turned inside out and attached to the inversion standpipe so that a leak-proof seal is created. The inversion head shall be adjusted to a sufficient height to invert the tube from structure to structure and to hold it tightly against the existing pipe wall, producing dimples at side connections and flared ends at the structure boxes. Care shall be taken not to over-stress the felt tube at the elevated curing temperatures, which may cause damage or failure prior to cure. The Contractor is responsible for providing any special equipment or stands to direct the liner over the top of and into the concrete box structure. 1. The Contractor may remove any existing slide gates to access the monolithic concrete pipeline entrance and exit. If the gates are removed, the Contractor must replace the gates when the work has been completed. The removal and replacement of the slide gates shall be at the Contractor s expense. B. After the inversion is completed, the Contractor shall supply a suitable heat source, water source, and water recirculation equipment capable of delivering heated water throughout the section to uniformly raise the water temperature above the temperature required to affect a cure of the resin. The appropriate temperature shall be recommended by the resin/catalyst system manufacturer. 1. It is recommended that the curing procedure utilize an environmentally safe steam cure. 2. If the use of hot water is necessary, the water must be collected and properly disposed of by the Contractor, at the Contractor s expense. The Contractor may be required to provide the District with a copy of the National Pollutant Discharge Elimination System (NPDES) permit. C. The heat source shall be fitted with suitable monitors to gauge the temperature of the incoming and outgoing water supply. Another such gauge shall be placed between the impregnated felt tube and the host pipe in the upstream and the downstream concrete structures to determine the temperatures during cure. Water, or steam, temperature in the line during the cure period shall not be less than 150 F or more than 200 F as measured at the heat source return line. Initial cure may be considered completed when the exposed portions of the felt tube pipe appear to be hard, and the remote sensing device indicates the temperatures to be adequate, as recommended by the resin/catalyst system manufacturer Approved: July 18, 2012 Page 5 of 8
6 D. The Contractor shall cool the hardened CIPP to a temperature below 100 degrees Fahrenheit before relieving the water column or steam pressure. Cool water may be added to the water column while draining hot water from a small hole at the opposite end of the CIPP, so that a constant water column height is maintained until cool-down is completed. Care shall be taken in the release of the water column to avoid vacuum development, which could damage the newly installed CIPP. E. The finished pipe shall be continuous over the entire length of the inversion run between the two access points and be as free, as commercially possible, from significant defects. Any defects which will affect, in the foreseeable future or warranty period, the integrity or strength of the pipe shall be repaired in a manner mutually agreed upon by the Engineer and the Contractor. Said repairs shall be funded and implemented by the Contractor INSPECTION A. After the work is completed, the Contractor shall provide the Engineer with a videotape showing both the before and after condition. Visual inspection of the CIPP shall be in accordance with ASTM F1743, Section 8.6. B. After installation, CIPP samples shall be prepared for each installation or approximately 20% of the project s installations. Pipe physical properties will be tested in accordance with ASTM F1216 or ASTM F1743, Section 8, using either method proposed. C. Wall thickness of samples shall be determined as described in paragraph of ASTM F1743. The minimum wall thickness at any point shall not be less than 87½% of the submitted minimum design wall thickness calculated TESTING REQUIREMENTS A. Hydraulic Capacity - Overall, the hydraulic cross-section shall be maintained as large as possible. The CIPP shall have a minimum of the full flow capacity of the original pipe before rehabilitation. Calculated capacities will be derived using a commonly accepted roughness coefficient for the original pipe material in its new condition. B. Leakage Test per ASTM standards F-1216 section 8.2 and F-1743 section 8.2. C. Short-term flexural (bending) properties test per ASTM F-1216 section D. De-lamination test per ASTM F-1216 section 8A CLEAN UP A. After the installation work has been completed and all testing acceptable to the Engineer, the Contractor shall clean up the entire project area to its original preconstruction condition. All excess material and debris not incorporated into the Page 6 of 8 Approved: July 18, 2012
7 /// END OF SECTION permanent installation shall be disposed of by the Contractor, at the Contractor s expense Approved: July 18, 2012 Page 7 of 8
8 THIS PAGE INTENTIONALLY BLANK Page 8 of 8 Approved: July 18, 2012
SPECIAL SPECIFICATION 4411 Cured-In-Place Pipe (CIPP) (Drainage Structures)
2004 Specifications CSJ 6165-86-001 SPECIAL SPECIFICATION 4411 Cured-In-Place Pipe (CIPP) (Drainage Structures) 1. Description. Reconstruct existing cross drainage structures by forming a new pipe within
More informationSPECIFICATIONS FOR PREMIER-PIPE USA CURED-IN-PLACE TECH LINER
SPECIFICATIONS FOR PREMIER-PIPE USA CURED-IN-PLACE TECH LINER 1. General Statement: This specification is for the Cured in Place Pipe process (CIPP) of pipe rehabilitation using a glass fiber reinforced
More informationSPECIAL SPECIFICATION 4631 Cured-In-Place Pipe (CIPP)
2004 Specifications CSJ 0912-34-171 SPECIAL SPECIFICATION 4631 Cured-In-Place Pipe (CIPP) 1. Description. Reconstruct existing drainage structures by forming a new pipe within an existing deteriorated
More informationSpecial Specification SS1- INTERNAL CIPP POINT REPAIR OF PIPELINES. A. General. 1. Scope
Special Specification SS1- INTERNAL CIPP POINT REPAIR OF PIPELINES A. General 1. Scope The work covered in this item includes the labor, equipment, materials for performing all work necessary to rehabilitate
More informationSample Bid Specification Revision 2 PVC Expanded-in-Place Pipeline Reconstruction
Sample Bid Specification Revision 2 PVC Expanded-in-Place Pipeline Reconstruction 1.00 DESCRIPTION 1.01 WORK INCLUDED: This work shall include the furnishing of all labor, equipment and materials necessary
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-22 05 83.63 (November 2016) -------------------------------- Preparing Activity: NASA UFGS-22 05 83.63 (November 2013) UNIFIED FACILITIES GUIDE SPECIFICATIONS References
More informationInstallation Practice InnerSeal
Installation Practice InnerSeal Rehabilitation of a Full-Length Sewer Service Lateral using One-Piece Main and Lateral Cured-In-Place Liner Assembly Installed By Means Of Air Inversion 1. Intent This instruction
More informationTable 1 Description of Work Pipe Size (mm) 1 Sunshine Way A/C No. A/C Yes
March 2, 2018 To: Cured-In-Place Pipe (CIPP) Relining Contractors RE: CITY OF GRAND FORKS REQUEST FOR QUOTE FOR CIPP RELINING CONTRACTORS 1.0 INTRODUCTION The City of Grand Forks is requesting quotes to
More informationTECHNICAL SPECIFICATION FOR CURED-IN-PLACE MANHOLE REHABILITATION LINER SYSTEM
TECHNICAL SPECIFICATION FOR CURED-IN-PLACE SYSTEM PART 1 GENERAL 1.01 SCOPE OF WORK Furnish all materials, labor, equipment, tools and required incidentals for providing and installing a resin impregnated
More informationTECHNICAL SPECIFICATIONS FIBERGLASS/ULTRAVIOLET LIGHT CURED-IN-PLACE PIPE (CIPP) FOR MAINLINE RENEWAL
TECHNICAL SPECIFICATIONS FIBERGLASS/ULTRAVIOLET LIGHT CURED-IN-PLACE PIPE (CIPP) FOR MAINLINE RENEWAL PART 1 - PRODUCTS 1.1 GENERAL It is the intent of this specification to provide for the reconstruction
More informationProject Specifications
Project Specifications 2016 Work Description - Root remove, clean via hydro-jetting, perform pre-televising and install Cured In Place Pipe liner (CIPP) utilizing either an inverted or pulled in place
More informationSPECIAL SPECIFICATION 5256 Cured-In-Place Pipe (Sanitary Sewer)
2004 Specifications CSJ 0912-71-657 SPECIAL SPECIFICATION 5256 Cured-In-Place Pipe (Sanitary Sewer) 1. Description. Furnish and install cured-in-place pipe. A. Resin-impregnated flexible tubes inserted
More informationThe Rehabilitation of Existing Building Drains and Building Sewers by the
Inversion or Pulled-in-Place Method and Curing of Resin-impregnated Tube Page 1 of 7 www.icc-es.org/pmg (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council PROPOSED PMG LISTING
More informationGENERAL SPECIFICATION FOR THE REHABILITATION OF SEWERS USING THE THERMOFORM (PVC) PIPE LINING SYSTEM
1. GENERAL 1.01 DESCRIPTION GENERAL SPECIFICATION FOR THE REHABILITATION OF SEWERS USING THE THERMOFORM (PVC) PIPE LINING SYSTEM A. The Contractor shall furnish all labor, equipment and materials necessary
More informationCIPP REFERENCE SPECIFICATION
CIPP REFERENCE SPECIFICATION This CIPP Reference Specification serves as only a guideline and is not intended to encompass the requirements of every municipality or industrial application. However, the
More informationEVALUATION SUBJECT: HAMMERHEAD CURED-IN- PLACE PIPE (CIPP) LINING SYSTEM DIVISION: PLUMBING SECTION: SANITARY WASTE AND VENT PIPING
ICC-ES Report PMG-1273 Reissued 01/2018 This report is subject to renewal 01/2019 EVALUATION SUBJECT: HAMMERHEAD CURED-IN- PLACE PIPE (CIPP) LINING SYSTEM DIVISION: 22 00 00 PLUMBING SECTION: 22 13 16
More informationCured-in-Place Pipe (CIPP) for Pressure Pipe. Presented by: Mike Moore
Cured-in-Place Pipe (CIPP) for Pressure Pipe Presented by: Mike Moore CIPP Proven Technology Introduced over 45 years ago Most used trenchless technology for the rehabilitation of gravity flow pipeline
More informationSECTION 808 CURED-IN-PLACE-PIPE (CIPP)
SECTION 808 CURED-IN-PLACE-PIPE (CIPP) 808-1 DESCRIPTION: This Work consists of providing labor, materials, equipment, and supervision necessary to accomplish the CIPP lining of all sewer mains designated
More informationSTANDARD SPECIFICATIONS FOR CONSTRUCTING SANITARY SEWER FACILITIES DIVISION III - CONSTRUCTION SPECIFICATIONS
STANDARD SPECIFICATIONS FOR CONSTRUCTING SANITARY SEWER FACILITIES DIVISION III - CONSTRUCTION SPECIFICATIONS SECTION 5 REHABILITATION OF SANITARY SEWER MAINS BY THE CURED-IN-PLACE PIPE (CIPP) METHOD 5.01
More informationGENERAL SPECIFICATION FOR THE REHABILITATION OF SEWERS
AM-LINER II PATENTED GENERAL SPECIFICATION FOR THE REHABILITATION OF SEWERS USING THE AM-LINER II PATENTED (PVC)PIPELINING SYSTEM TRENCHLESS TECHNOLOGY August 16, 2005 1 AMERICAN PIPE & PLASTICS, INC.
More informationProduct Information. Polyester Felt Cured-In-Place Pipe (CIPP) Lining Tube
1468 West Hospital Road Paoli, Indiana 47454 Phone: (812) 723-0244 Fax: (812) 723-0405 Polyester Felt Cured-In-Place Pipe (CIPP) Lining Tube Revised November 16, 2016 Company Profile Product Types Resins
More informationCured-In-Place-Pipe (CIPP) LATERAL SEALS
Cured-In-Place-Pipe (CIPP) LATERAL SEALS PERFORMANCE SPECIFICATION GUIDELINE October, 2016 Thanks to the following participants for the development of this document: Brendan Doyle BLD Services LLC (Chair)
More informationSECTION 809 CURED-IN-PLACE PIPE (CIPP) LATERALS
SECTION 809 CURED-IN-PLACE PIPE (CIPP) LATERALS 809-1 DESCRIPTION: This Work consists of installing a cured-in-place pipe (CIPP) liner to stabilize structural defects and construction inadequacies in sanitary
More informationCEDAR RAPIDS METROPOLITAN AREA STANDARD SPECIFICATIONS FOR PUBLIC IMPROVEMENTS May 2014 SECTION SEWER LINERS
SECTION 02310 SEWER LINERS PART 1 GENERAL 1.01 - References A. American Society for Testing and Materials (ASTM): 1. ASTM D638 Test method for tensile properties of plastics. 2. ASTM D790 Test method for
More informationCITY OF TAMPA ADDENDUM NO. 1. DATE: September 15, Contract 11-C-00001; Wastewater Sewer Rehabilitation by Cured-in-Place Pipe (C.I.P.P.
CITY OF TAMPA Pam Iorio, Mayor CONTRACT ADMINISTRATION DEPARTMENT David L. Vaughn, AIA, Director ADDENDUM NO. 1 DATE: September 15, 2010 Contract 11-C-00001; Wastewater Sewer Rehabilitation by Cured-in-Place
More informationInfrastructure Point Repair System Technical Specifications
4301 A 34 t h Street North St. Petersburg, FL 33714 PH: 877-327-4216 Fax: 727-327- 4118 Web: www.irsi.net Infrastructure Point Repair System 1. Scope: This specification defines the approved methodology
More informationCIPMH (Cured-in-Place Manhole) Lining System
Product Submittal Document Information CIPMH (Cured-in-Place Manhole) Lining System CIPMH FULL DEPTH-PA For Structural Rehabilitation Updated 9/25/14 Product Submittal Review ITEM 1. Manufacturer Company
More informationPIPE REHABILITATION. Comply with Division 1 - General Provisions and Covenants, as well as the following:
PIPE REHABILITATION PART 1 - GENERAL 1.01 SECTION INCLUDES A. Sliplining Pipe B. Cured-in-place Pipe Lining C. Deformed/Reformed Pipe Lining D. Folded/Formed Pipe Lining E. Spot Repairs by Pipe Replacement
More informationSPECIFICATIONS. Cured-in-Place Pipe Liner (CIPP Liner). Shall comply with Subsection
PIPELINE SYSTEM REHABILITATION SPECIFICATIONS The intent of the work under this section involves the trenchless rehabilitation of existing sewer pipelines. This lining shall rebuild strength and substantially
More informationADDENDUM No. 2. City of Joliet, 2017 Spring Creek Interceptor Sewer Lining at CN Railyard
ADDENDUM No. 2 October 19, 2017 TO: PROJECT: All Potential Bidders, 2017 Spring Creek Interceptor Sewer Lining at CN Railyard BID OPENING: Tuesday, October 24, 2017 at 11:00 A.M. The following is a list
More informationLS 2760 CURED-IN-PLACE SEWER LINING
LS 2760 CURED-IN-PLACE SEWER LINING A. Related Documents B. Summary C. Submittals D. Quality Assurance E. Project Conditions F. Sequencing and Scheduling G. Quantities H. Liner and Resins I. Initial Sewer
More informationInland Pipe Rehabilitation. August 17 OAWWA Canton, OH
Inland Pipe Rehabilitation August 17 OAWWA Canton, OH Presentation Agenda Introduction to IPR IPR Products & Services RS Technik by HammerHead Advanced CIPP Process Spartanburg, SC project review IPR Overview
More informationCITY OF FARGO SPECIFICATIONS PIPE AND MANHOLE REHABILITATION
PIPE AND MANHOLE REHABILITATION PART 1 DESCRIPTION OF WORK The work to be done under this section of the Specifications and the accompanying plans shall include all labor, materials, and equipment necessary
More informationCIPP Cured-in-Place Pipeline CIPP. cured-in-place pipe. trenchless pipe rehabilitation
CIPP Cured-in-Place Pipeline CIPP cured-in-place pipe trenchless pipe rehabilitation MPC ToughTube cured-in-place pipe lives up to its name. The lining process is accomplished by either inverting or pulling
More informationSECTION F1 SEWER AND DRAIN PIPE LINING (NON-MAN ENTRY) GENERAL
SECTION F1 SEWER AND DRAIN PIPE LINING (NON-MAN ENTRY) GENERAL This section describes requirements for furnishing all labor, materials, transportation, and equipment necessary for the rehabilitation of
More informationGENERAL REQUIREMENTS AND TECHNICAL SPECIFICATIONS
11701 Community Center Dr Northglenn CO 80233 GENERAL REQUIREMENTS AND TECHNICAL SPECIFICATIONS TABLE OF CONTENTS 013300 SUBMITTAL PROCEDURES 013500 SPECIAL CONDITIONS 330140 CURED IN PLACE PIPE (CIPP)
More informationMokapu CIPP Case Study & Innovations in Trenchless Technologies for Wastewater System Rehabilitation
Mokapu CIPP Case Study & Innovations in Trenchless Technologies for Wastewater System Rehabilitation Presented by Mike York, Insituform Technologies, Inc. Trenchless v. Dig and Replace What is CIPP? Developed
More informationAMENDMENT OF SOLICITATION
Metropolitan Washington Airports Authority PROCUREMENT AND CONTRACTS DEPT. AMENDMENT OF SOLICITATION PAGE 1 Metropolitan Washington Airports Authority 1A. AMENDMENT OF SOLICITATION NO. 1B. DATED Procurement
More informationMethod One: Liner/Bladder Assembly-Inversion Method.
CIPP Sectional/Point Repairs Critical Factors Finally Explained By: Shaun M. Flanery Abstract A 1999 report from the American Society of Civil Engineers indicated at that time that the nation s 500,000
More informationCIPP Lateral Renewal Connection System
Product Submittal Document Information CIPP Lateral Renewal Connection System ManEntry Lapel Liner Updated 6/12/14 Product Submittal Review ITEM 1. Manufacturer Company Name: LMK Technologies, LLC Contact
More informationCLARIFICATIONS TO TECHNICAL SPECIFICATIONS SECTIONS
C-44 Reservoir/STA System Discharge Project RFB: 6000000620 Addendum No. 1 March 2014 CLARIFICATIONS TO TECHNICAL SPECIFICATIONS SECTIONS HDR Engineering, Inc. SECTION 02401 DEWATERING, COFFERDAM AND BYPASS
More informationCURED-IN-PLACE PIPE LINING
CURED-IN-PLACE PIPE LINING PROJECT DESCRIPTION (I) Scope of Work Sewer Repairs Contract for Inspection and In-Place Sewer System Rehabilitation consisting of Cured-in-Place Pipe Lining. General Requirements
More informationProcess Specification. Structural Rehabilitation & Corrosion Protection for Circular Structures in Wastewater Collection and Potable Water Systems
Process Specification Structural Rehabilitation & Corrosion Protection for Circular Structures in Wastewater Collection and Potable Water Systems SECTION 1: GENERAL 1.01 DESCRIPTION This specification
More informationPERFORMANCE SPECIFICATION GUIDELINE
PERFORMANCE SPECIFICATION GUIDELINE FOR THE INSTALLATION OF CURED-IN-PLACE PIPE (CIPP) June, 2011 Thanks to the following participants for the development of this document: Ted DeBoda - NASSCO Steve Gearhart
More informationEVALUATION SUBJECT: PERMA-LATERAL PULLED- IN-PLACE CURED-IN-PLACE PIPE LINING SYSTEM
ICC-ES Report PMG-1074 Reissued 11/2017 This report is subject to renewal 11/2018 EVALUATION SUBJECT: PERMA-LATERAL PULLED- IN-PLACE CURED-IN-PLACE PIPE LINING SYSTEM DIVISION: 22 00 00 PLUMBING SECTION:
More informationSECTION HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS (PRESSURE PIPE)
SECTION 02623 HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS (PRESSURE PIPE) PART 1 - GENERAL 1.1 SCOPE OF WORK A. Furnish all labor, materials, equipment and incidentals required and install high density
More informationLessons Learned from a 60 CIPP Storm Sewer Liner Installation. Robert Stolt, PE Christopher Beranek, PE
Lessons Learned from a 60 CIPP Storm Sewer Liner Installation Robert Stolt, PE Christopher Beranek, PE Presentation Outline 1. CIPP Project Scope 2. CIPP Liner Installation 3. Defects Identified 4. Warranty
More informationSPECIAL SPECIFICATIONS UV CURED IN-PLACE SPIRAL WOUND FIBERGLASSS PIPE LINING
5101.1 Description This item shall govern approved methods and materials for the rehabilitation of deteriorated gravity sewer and storm water pipes by an Ultra-Violet Light Cured-In-Place Pipe (CIPP) lining
More informationSPECIAL SPECIFICATION 5787 Manhole Rehabilitation
2004 Specifications CSJ 1062-04-047 SPECIAL SPECIFICATION 5787 Manhole Rehabilitation 1. Description. Repair, rehabilitate, or replace deteriorated, leaking, or structurally unsound existing sanitary sewer
More informationSan Antonio Water System Standard Specifications for Construction
Item No. 905.1 Rehabilitation of Sanitary Sewer By Cured-In-Place Pipe (UV Light Cured) 905.1 DESCRIPTION: This specification includes requirements to rehabilitate existing sanitary sewers by the Ultraviolet
More informationSECTION XXXXX CHEMICAL GROUTING
SECTION XXXXX CHEMICAL GROUTING PART 1 -- GENERAL 1.01 SCOPE OF WORK A. Provide all labor, materials, accessories, equipment, and tools required for the rehabilitation, infiltration reduction, and root
More informationMS-2A LINER SPECIFICATIONS: for STRUCTURAL REPAIR and SEALING of MANHOLES
MS-2A LINER SPECIFICATIONS: for STRUCTURAL REPAIR and SEALING of MANHOLES INTENT: To provide a system for reconstruction of concrete or masonry structures to stop inflow, infiltration, exfiltration, and
More informationWastewater Capital Projects Management Standard Construction Specification
CITY AND COUNTY OF DENVER ENGINEERING DIVISION Wastewater Capital Projects Management Standard Construction Specification 10.1 PRECAST CONCRETE PIPE 10.1.1 General This section covers material requirements,
More informationSpecifications. Chapter 13. Specifications (800) CULVERT 96
Chapter 13 WWW.CULVERT-REHAB.COM (800) CULVERT 96 Material Requirement These specifications cover the purchase of high density polyethylene (HDPE) pipe liners for lining existing culvert pipes. Pipe liners
More informationSECTION C10 CLEANING AND CEMENT LINING GENERAL
SECTION C10 CLEANING AND CEMENT LINING GENERAL The work under this section consists of the cleaning and cement mortar lining of existing cast iron water mains in place within the limits specified on the
More informationFiber Reinforced Cured-in-Place Rehabilitation Under an Interstate
Fiber Reinforced Cured-in-Place Rehabilitation Under an Interstate UCT Conference - February 2017 Presented By Chantal Evans Representing Owner Jonathan Stathis/Cedar City Owner and owner issues Cedar
More informationCITY OF TAMPA ADDENDUM NO. 3. DATE: February 15, 2017
CITY OF TAMPA Bob Buckhorn, Mayor CONTRACT ADMINISTRATION DEPARTMENT Michael W. Chucran, Director ADDENDUM NO. 3 DATE: February 15, 2017 Contract 16-C-00027; Ragan Park Restroom Improvements - Rebid Bidders
More informationSpecifying Trenchless Sewer Rehabilitation Projects. Presented by: Todd Stelmacher Visu-Sewer, Inc.
Specifying Trenchless Sewer Rehabilitation Projects Presented by: Todd Stelmacher Visu-Sewer, Inc. Todd Stelmacher Bio Visu-Sewer Sales Engineer MN, ND, SD, WI 30+ years public utilities experience Municipal
More informationBMEC AUTHORIZATION:
777 Bay Street, 2 nd Floor Toronto, Ontario, M5G 2E5 777, rue Bay, 2 e etage Toronto, Ontario, M5G 2E5 T: F: W: 416 585 4234 416 585 7531 www.ontario.ca/buildingcode/ T: TC: W: 416 585 4234 416 585 7531
More informationSection [ ] Stormwater Catch Basin Filtration Device
PART 1 GENERAL Section [ ] Stormwater Catch Basin Filtration Device 01.01.00 Purpose The purpose of this specification is to establish generally acceptable criteria for devices used for filtration of stormwater
More informationINTERFIT LATERAL SEALING SYSTEM INSTALLATION GUIDELINE SPECIFICATION
INTERFIT LATERAL SEALING SYSTEM INSTALLATION GUIDELINE SPECIFICATION INTERFIT LATERAL SEALING SYSTEM SECTION 1: GENERAL 1.1 INTENT 1.2 SCOPE 1.3 REFERENCE DOCUMENTS AND STANDARDS 1.4 SUBMITTALS SECTION
More informationSan Antonio Water System Specifications for Construction ITEM NO. 853 SANITARY SEWER GLASS-FIBER REINFORCED POLYESTER (FRP) MANHOLES
ITEM NO. 853 SANITARY SEWER GLASS-FIBER REINFORCED POLYESTER (FRP) MANHOLES 853.1 DESCRIPTION: This item shall govern the construction of FRP sanitary sewer manholes, complete in place and the materials
More informationI&I Mitigation: Rehabilitation of Sewer Laterals and Sealing the Collection System
I&I Mitigation: Rehabilitation of Sewer Laterals and Sealing the Collection System Rick Gage, Vice President of Sales Mike Czipar, Vice President of Business Development Discussion Points Mainline CIPP
More informationprofile-mix-plus, Page 1 of 8, Rev
Strong-Seal Profile Mix for reconstructing deteriorated structures to original dimensions, eliminating infiltration and providing structural restoration, corrosion protection and a smooth surface for application
More informationITEM NO SLIPLINING SANITARY SEWERS
ITEM NO. 1100 SLIPLINING SANITARY SEWERS 1100.1 DESCRIPTION: Sliplining is accomplished by pulling or pushing liner pipe into existing sewers by use of mechanical or hydraulic equipment. Once in place,
More informationChanges for the. TOHOPEKALIGA WATER AUTHORITY Standards, Specifications and Details
Changes for the 2017 TOHOPEKALIGA WATER AUTHORITY Standards, Specifications and Details The following changes are made to the existing standards and details to clarify or improve existing information.
More informationSPECTRASHIELD. Total System for Manholes (Brick/Concrete)
SPECTRASHIELD Total System for Manholes (Brick/Concrete) PART I GENERAL 1.01 DESCRIPTION The work described within details a complete program for manholes. This section details the methods, procedures,
More informationSection [ ] Stormwater Catch Basin Filtration Device
PART 1 GENERAL Section [ ] Stormwater Catch Basin Filtration Device 01.01.00 Purpose The purpose of this specification is to establish generally acceptable criteria for devices used for filtration of stormwater
More informationSS 207 Junction Sealing for Circular Non Man Entry Sewer Pipe
Standard Specification SS 207 Junction Sealing for Circular Non Man Entry Sewer Pipe Version 1 1 General 1.1 Intent The intent of this specification is to define the requirements for rehabilitating and
More information2017 SANITARY SEWER REHABILITATION SPECIFICATIONS SECTION 1.00 SCOPE... 1
2017 SANITARY SEWER REHABILITATION SPECIFICATIONS UTABLE OF CONTENTS SECTION 1.00 SCOPE... 1 UPage 1.01 General... 1 1.02 Work Included... 1 1.03 Location of Work... 1 1.04 Coordination of Work... 1 1.05
More informationCITY OF ODESSA SPECIAL SPECIFICATIONS ITEM 1000 GLASS-FIBER REINFORCED POLYESTER (FRP) REHAB/REPLACEMENT MANHOLE
CITY OF ODESSA SPECIAL SPECIFICATIONS ITEM 1000 GLASS-FIBER REINFORCED POLYESTER (FRP) REHAB/REPLACEMENT MANHOLE 1000.1 DESCRIPTION These specifications shall govern the furnishing of glass-fiber reinforced
More informationREGIONAL CONSTRUCTION STANDARDS
REGIONAL CONSTRUCTION STANDARDS SIXTH EDITION Publication Update 6.5 (Full Committee Approved Proposed Revision 6.5 Storm Sewer Joint Wrap - Section 302 As Publication Update 6.5) March 27, 2018 Copyright
More informationHIGH PERFORMANCE MIX SPECIFICATIONS
Strong-Seal Systems HIGH PERFORMANCE MIX SPECIFICATIONS INTENT: To provide a system for manhole reconstruction that stops inflow, infiltration, exfiltration, restores structural integrity and provides
More informationSPECTRASHIELD. Total System for Large Wastewater Structures PART I - GENERAL
1.01 DESCRIPTION SPECTRASHIELD Total System for Large Wastewater Structures PART I - GENERAL The work described within details a complete program for wet wells, treatment plants or other large wastewater
More informationSTATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 834 CONDUIT RENEWAL USING RESIN BASED LINER.
STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 834 CONDUIT RENEWAL USING RESIN BASED LINER 834.01 Description 834.02 Materials 834.03 Shipment and Storage 834.04 Submittals 834.05
More informationSECTION STORM DRAINAGE
SECTION 02720 STORM DRAINAGE PART 1 - GENERAL 1.01 WORK INCLUDED A. Trenching and other excavation. B. Ground water control. C. Pipe bedding. D. Installation of storm drains and appurtenances. E. Installation
More informationSECTION GRAVITY WASTEWATER LINES
SECTION GRAVITY WASTEWATER LINES 1. DESCRIPTION This specification shall govern all work required for furnishing, handling and installing gravity wastewater lines required to complete the project. 2. MATERIALS
More informationOTEC 2017 Spray Applied Pipe Liner Supplemental Specifications 833 Calculations for the Resin Based Liner Presented by Peter Blais, PE
Innovative Solutions through Engineered Products OTEC 2017 Spray Applied Pipe Liner Supplemental Specifications 833 Calculations for the Resin Based Liner Presented by Peter Blais, PE HydraTech Engineered
More informationSECTION GRAVITY IRRIGATION PIPELINES RUBBER GASKETED REINFORCED CONCRETE PIPE (RGRCP)
SECTION 02513 GRAVITY IRRIGATION PIPELINES RUBBER GASKETED REINFORCED CONCRETE PIPE (RGRCP) PART 1 GENERAL 1.01 SECTION INCLUDES A. Irrigation pipeline, as herein specified, consists of installing pipe
More informationSection SANITARY SEWER SYSTEM REHABILITATION
CCU STANDARD SPECIFICATIONS Section 009910 SANITARY SEWER SYSTEM REHABILITATION Effective Date: Nov. 1st, 2011 Page 1 of 48 PART 1 - GENERAL It is the intent of this specification to provide the requirements
More informationULTRAVIOLET LIGHT CIPP LINING OF EXISTING SEWERS
PART 1 GENERAL 1.01 DESCRIPTION A. SCOPE ULTRAVIOLET LIGHT CIPP LINING OF EXISTING SEWERS This contract covers the rehabilitation of severely deteriorated existing sanitary and combined sewers by lining
More informationNorth Pecos Water & Sanitation District Request for Proposal CURED-IN-PLACE-PIPE PROJECT 2015 SANITARY SEWER REHABILITATION
North Pecos Water & Sanitation District Request for Proposal CURED-IN-PLACE-PIPE PROJECT 2015 SANITARY SEWER REHABILITATION TABLE OF CONTENTS Request for Sealed Proposal Page 4 Proposal Guidelines and
More informationSECTION BORING AND/OR JACKING PIPE
02910-1 of 6 SECTION 02910 BORING AND/OR JACKING PIPE 02910.01 GENERAL A. Description Boring and/or jacking pipe shall include, but not necessarily be limited to, furnishing and installing carrier pipe
More informationSection [ ] Stormwater Catch Basin Filtration Device
PART 1 GENERAL Section [ ] Stormwater Catch Basin Filtration Device 01.01.00 Purpose The purpose of this specification is to establish generally acceptable criteria for devices used for filtration of stormwater
More informationTechnical Information: Standard Inverted and Pull-In CIPP
17988 Edison Avenue Saint Louis, Missouri 63005 Phone: 636-530-8000 www.aegion.com 1. The CIPP Technical Envelope Technical Information: Standard Inverted and Pull-In CIPP Water Inversion Steam Inversion
More informationr.tec GmbH The technology provider of the Rabmer Group
r.tec GmbH The technology provider of the Rabmer Group Know How Technology Quality - Innovation What do we offer? We have developed a technology portfolio from the perspective of a contractor we serve
More informationInternational Aramoon Corp. Pipe Inspection and Rehabilitation By: Faiz Al-Elweet. SAWEA Al-Khobar KSA February 24, 2010
International Aramoon Corp. 1 Pipe Inspection and Rehabilitation By: Faiz Al-Elweet SAWEA Al-Khobar KSA February 24, 2010 International Aramoon Corp. 2 Nobody would like to wait until the problem appears
More informationSECTION STORM DRAIN REHABILITATION. 1. Protection of environment; Section O Trench excavation, backfill, and compaction; Section
02540-1 of 10 SECTION 02540 STORM DRAIN REHABILITATION 02540.01 GENERAL A. Description Storm drain rehabilitation shall include, but not necessarily be limited to, pipe joint sealing, inlet and manhole
More informationSPECIFICATIONS - DETAILED PROVISIONS Section Welded Steel Tanks for Water Storage C O N T E N T S
SPECIFICATIONS - DETAILED PROVISIONS Section 13311 - Welded Steel Tanks for Water Storage C O N T E N T S PART 1 - GENERAL... 1 1.01 REQUIREMENT... 1 1.02 QUALITY ASSURANCE... 2 1.03 SUBMITTALS... 2 1.04
More information***************************************************************************************************************
02732 SANITARY FORCE MAIN *************************************************************************************************************** SPECIFIER: CSI MasterFormat 2004 number 33 34 00. ***************************************************************************************************************
More informationSECTION WATERTIGHTNESS TEST FOR PLANT TANKAGE STRUCTURES
SECTION 01 48 00 - WATERTIGHTNESS TEST FOR PLANT TANKAGE STRUCTURES PART 1 - GENERAL 1.1 SCOPE OF WORK A. Furnish all labor, materials and incidentals required and perform tightness testing of water-containing
More informationSection [ ] Stormwater Catch Basin Filtration Device
PART 1 GENERAL Section [ ] Stormwater Catch Basin Filtration Device 01.01.00 Purpose The purpose of this specification is to establish generally acceptable criteria for devices used for filtration of stormwater
More informationSECTION 813 SEWER FLOW CONTROL
SECTION 813 SEWER FLOW CONTROL 813-1 DESCRIPTION: Sewer flow control is a set of methods to adjust the flow in the sewer system to allow for inspection, maintenance, repair or replacement. This is accomplished
More informationSPECIAL SPECIFICATION 5925 Polyvinyl Cloride (PVC) Sewer Pipe and Fittings
1993 Specifications CSJ 0144-01-060 SPECIAL SPECIFICATION 5925 Polyvinyl Cloride (PVC) Sewer Pipe and Fittings 1. General. (1) Scope. This Section includes the furnishing, installation, and subsequent
More informationService Lateral Rehabilitation Using Cured-In-Place-Pipe (CIPP)
THE TOTAL SOURCE Service Lateral Rehabilitation Using Cured-In-Place-Pipe (CIPP) Brendan Doyle BLD Services, LLC Introduction Intent, to provide information on: Lateral preparation Lateral CCTV Inspection
More informationSTANDARD SPECIFICATIONS FOR CONSTRUCTING SANITARY SEWER FACILITIES DIVISION III - CONSTRUCTION SPECIFICATIONS SECTION 4
STANDARD SPECIFICATIONS FOR CONSTRUCTING SANITARY SEWER FACILITIES DIVISION III - CONSTRUCTION SPECIFICATIONS SECTION 4 URETHANE/EPOXY REHABILITATION OF MANHOLES 4.01 SCOPE It is the intent of this Specification
More informationSECTION SLUDGE HOLDING TANK DEWATERING
SECTION 13215 SLUDGE HOLDING TANK DEWATERING PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Dewatering and cleaning of sludge holding tank and sludge disposal. Contractor shall pay for all sludge removal,
More informationSEwEr rehabilitation Spr technologies
SEwer rehabilitation spr technologies SEKISUI SPR s rehabilitation technologies FOR SEWER REHABILITATION SEKISUI SPR is synonymous with the development and implementation of trenchless pipe rehabilitation
More informationADDENDUM NO. 1 AUGUST 7, The attention of all Bidders is directed to the following additions and/or deletions to the Contract Documents.
2017 SANITARY SEWER IMPROVEMENTS PROJECT ADDENDUM NO. 1 AUGUST 7, 2017 This Addendum forms a part of the Contract Documents and modifies the original Bidding Documents as noted within this Addendum. All
More information