Conservation of fuel and power

Size: px
Start display at page:

Download "Conservation of fuel and power"

Transcription

1 Appendix B Conservation of fuel and power B.1 The requirement Part L1 Conservation of fuel and power Reasonable provision shall be made for the conservation of fuel and power in buildings by: (a) limiting heat gains and losses: (i) through thermal elements and other parts of the building fabric; and (ii) from pipes, ducts and vessels used for space heating, space cooling and hot water services; (b) providing and commissioning energy-efficient fixed building services with effective controls; and (c) providing to the owner sufficient information about the building, the fixed building services and their maintenance requirements so that the building can be operated in such a manner as to use no more fuel and power than is reasonable in the circumstances. Note: In addition to Part L, some other Approved Documents also have requirements concerning the conservation of fuel and power. In particular these include: Part E (Resistance to the passage of sound); Part F (Ventilation);

2 Appendix B Conservation of fuel and power 31 Part C (Site preparation and resistance to moisture); and Part J (Combustion appliances and fuel storage systems). But, as specified in Regulation 9, Part L does not apply to: buildings which are used primarily as places of worship; temporary buildings that are going to be used for less than two years; industrial sites; workshops; non-residential agricultural buildings with a low energy demand (e.g. such as parts of a building that are used for seed germination and, therefore, only need to be heated for a few days in each year). B.2 Main changes in the 2006 edition Part L has now been increased (both in size and content) and is currently a four-part series of Approved Documents that cover the conservation of fuel and power in: new dwellings (L1A); existing dwellings (L1B); new buildings (other than dwellings) (L2A); existing buildings (other than dwellings (L2B). The 2006 editions represent an in-depth rewrite of Part L and the main changes (in addition to it now being in four separate volumes) are as follows: building control bodies authorized to accept self-certification by Competent Persons; general improvement in the performance standards for work on thermal elements, windows, doors heating, hot water, ventilation and lighting systems in existing dwellings; increased use of technical reference publications to form part of the approved guidance; more guidance on building extensions and conservatories; more guidance on complying with the new requirements to make costeffective consequential improvements whenever work is carried out on larger buildings; new minimum energy performance requirements; new requirement for the improvement of the energy performance of the buildings if the floor area exceeds 1000 m 2, whenever these buildings are subject to major works; new requirements for pressure testing, commissioning and energy calculations; significant changes to the definitions of works and exempt works; the list of works that need not be notified to building control bodies increased to include minor works on heating, ventilation and lighting systems; the scope of the Competent Persons schemes widened and more scheme operators have been approved.

3 32 Building Regulations in Brief It is estimated that adoption of Part L (and other associated Approved Documents) will result in buildings that are naturally ventilated and heated, achieving an overall improvement of about 23% and for air-conditioned buildings this improvement will be around 28%. The details of these changes are as follows. B.2.1 L1A New dwellings the omission of the Elemental Method and the Target U-value Method in favour of a new approach to show compliance with the energy efficiency requirements; the introduction of this new approach for compliance which addresses five criteria, namely that: the annual CO 2, emission rate of the completed dwelling must not exceed targets that have been set; building fabric and services performance specifications are within reasonable limits; solar shading and other measures to limit risks of summer overheating are reasonably acceptable; fabric insulation and airtightness are as intended; satisfactory information has been provided to the occupier(s); the inclusion of an appendix containing a new checklist for builders and building control bodies to help in assessing compliance; the inclusion of an appendix listing the threshold performance values; details of new competent persons schemes that have been approved for pressure testing and energy performance calculations. B.2.2 L1B Existing dwellings a new definition of thermal element to address more types of alteration and renovation work; a new appendix giving examples of what can be achieved cost-effectively; new requirements for providing and/or renovating thermal elements; new requirements for commissioning heating, ventilation and lighting systems; new section containing guidance on ways of complying with these new requirements concerning the provision and renovation of thermal elements. B.2.3 L2A New buildings other than dwellings The omission of the Elemental Method and the Target U-value Method in favour of a new approach to show compliance with the energy efficiency requirements; the introduction of this new approach for compliance which addresses five criteria, namely that: the annual CO 2 emission rate of the completed building must not exceed targets that have been set;

4 Appendix B Conservation of fuel and power 33 building fabric and services performance specifications are within reasonable limits; non-air-conditioned buildings do not cause high internal temperatures as a result of excessive solar gains; fabric insulation and airtightness are as intended; satisfactory information has been provided to the occupier(s); the inclusion of an appendix containing a compliance checklist for builders and building control bodies. B.2.4 L2B Existing buildings other than dwellings a new definition of thermal element to address more types of alteration and renovation work; new requirements for providing and/or renovating thermal elements; new requirements for commissioning heating, ventilation and lighting systems; new section containing guidance on complying with the new requirements to make cost-effective improvements whenever work is carried out on new buildings. B.3 General guidance on the use of the four Approved Documents B.3.1 Types of work covered by L1A Approved Document L1A is intended to provide guidance on what, in ordinary circumstances, would be accepted as reasonable conditions for satisfying the requirements for creating new dwellings by means of new construction works. If part of a unit that contains living accommodation also contains space that is going to be used for commercial purposes (such as a workshop or office), it should be treated as a dwelling if the commercial part could revert to domestic use on a change of ownership. For example if: there was direct access between the commercial space and the living accommodation; and both were contained within the same thermal envelope; and the living accommodation occupied a substantial proportion of the total area of the building. When constructing a dwelling as part of a larger building that contains other types of accommodation, L1A should be used for guidance in relation to the individual dwellings whilst L2A should be used for the non-dwelling parts of such buildings such as heated common areas, and (in the case of mixed-use developments) commercial or retail space. In mixed use developments (i.e. where part of a building is used as a dwelling while another part has a non-domestic use) the requirements for non-domestic use should apply in all shared parts of the building.

5 34 Building Regulations in Brief If a conservatory is built as part of a new dwelling, then the performance of the dwelling should be assessed as if the conservatory were not there. If a dwelling is being created as the result of a material change of use, Approved Document L1B applies. Buildings containing rooms for residential purposes such as nursing homes, student accommodation and similar are not considered as dwellings and in such cases, Approved Document L2A would apply. B.3.2 Types of work covered by L1B L1B contains guidance on building work on existing dwellings, in particular: historic buildings; the extension of a dwelling; conservatories; when creating a new dwelling or part of a dwelling through a material change of use; material alterations to existing dwellings; work on controlled service and/or fittings; the provision and/or renovation of a thermal element. When completing building work in a dwelling that is part of a mixed use building, L1B should be used for guidance in relation to the dwelling and L2B for those parts of the building that are not dwellings, including any common areas. In most instances (but best to check with the local authority first) the Building Control Body will need to be notified of the intended work before the work actually commences, either in the form of a deposit of full plans or by a building notice. If, however, the work is being carried out by a person approved under the Competent Persons self-certification (CP) scheme, no advance notification is required but that person must provide the building owner with a certificate confirming that the installation has been carried out in accordance with the relevant requirements and notify the local authority to that effect. If the work involves an emergency repair (e.g. a failed boiler or a leaking hot water cylinder), although advance notification is not required, the repair must still comply with the requirements of Part L1B and a completion certificate issued in the normal way. If the work is of a minor nature (e.g. such as replacing a damaged cable, adding light fittings and switches to an existing circuit, upgrading supplementary equipotential bonding, work on telephone wiring etc.) the work must still comply with the relevant requirements, but need not be notified to the building control body. B.3.3 Types of work covered by L2A L2A contains guidance concerning: the construction of new buildings other than dwellings; fit-out works (i.e. specific requirements made by the incoming occupiers) which are included as part of the construction of the building;

6 Appendix B Conservation of fuel and power 35 the construction of extensions to existing buildings (where the total floor area of the extension is greater than 100 m 2 and greater than 25% of the total useful floor area of the existing building); the construction of parts of a building (such as heated common areas in the case of mixed use); the construction of boarding houses, hostels and student accommodation blocks. Note: Buildings used for industrial or commercial purposes (e.g. workshops and/or offices) that also contain living accommodation should be treated as a dwelling if the commercial part could revert to domestic use on a change of ownership. B.3.4 Types of work covered by L2B L2B contains guidance on building work on existing buildings, in particular: historic buildings; consequential improvements; extensions; material change of use; material alterations; the provision of a controlled service; thermal elements. B.4 Historic buildings Many books have been written about the problems related to restoring historic buildings and before considering any work of this nature, you should probably seek the advice of the local planning authority s conservation officer, particularly if you are contemplating: the restoration of a historic building that had been subject to previous inappropriate alteration (such as replacement windows, doors and rooflights); rebuilding a former building (e.g. following a fire or filling a gap site in a terrace); enabling the fabric of historic buildings to breathe so as to control moisture and potential long-term decay problems. In all cases, the overall aim should always be to improve energy efficiency without damaging the character of the building or increasing the risk of longterm deterioration to the building fabric or fittings. Note: See English Heritage publication Building Regulations and Historic Buildings for further advice).

7 36 Building Regulations in Brief B.5 Material change of use For the purposes of these Regulations, a material change of use is where there is a change in the purposes for which (or the circumstances in which) a building is used, so that after that change the building: is used as a dwelling; contains a flat; is used as an hotel or a boarding house; is used as an institution; is used as a public building; is not an exempt building (i.e. such as a building not frequented by people, a greenhouse temporary or ancillary buildings or a small detached building); contains a room for residential purposes; which contains at least one room for residential purposes, or contains a greater or lesser number of such rooms; is used as a shop where previously it was not; or the building, which contains at least one dwelling, contains a greater or lesser number of dwellings than it did previously. When a building is subject to a material change of use, then: any thermal element that is being retained should be upgraded; any existing window (including roof window or rooflight) or door which separates a conditioned space from an unconditioned space (or the external environment) and which has a U-value that is worse than 3.3 W/m 2 K, should be replaced. An accredited whole building calculation model such as SAP 2005 can be used to demonstrate that the CO 2 emissions from the building will be no greater than if the building had been improved. B.6 Material alterations Material alterations (i.e. where work, or any part of it, would result in a building or controlled service or fitting not complying with a relevant requirement where previously it did, or making previous compliance more unsatisfactory) should comply with the requirements for conservation of heat and energy as follows. B.6.1 Material alterations (domestic buildings) If a building is subject to a material alteration by: substantially replacing a thermal element; renovating a thermal element; making an existing element part of the thermal envelope of the building (where previously it was not);

8 Appendix B Conservation of fuel and power 37 providing a controlled fitting; providing (or extending) a controlled service; then in addition to the requirements of Part L, all applicable requirements from the following Approved Documents must be taken into account: Part A (structure); Paragraph B1 (means of warning and escape); Paragraph B3 (internal fire spread structure); Paragraph B4 (external fire spread); Paragraph B5 (access and facilities for the fire service); Part M (access to and use of buildings). B.6.2 Material alterations (buildings other than dwellings) When an existing element becomes part of the thermal element of a building (where previously it did not) and it has a U-value worse than 3.3 W/m 2 K it should be replaced (unless they are display windows or high usage doors). B.7 Consequential improvements (non-domestic buildings) If a building has a total useful floor area greater than 1000 m 2 and the proposed building work includes: an extension; or the initial provision of any fixed building services; or an increase to the installed capacity of any fixed building services; then consequential improvements should be made to improve the energy efficiency of the whole building. These will include: upgrading all thermal units which have a high U-value; replacing all existing windows (less display windows), roof windows, rooflights or doors (excluding high usage entrance doors) within the area served by the fixed building service with an increased capacity; replacing any heating system that is more than fifteen years old; replacing any cooling system that is more than fifteen years old; replacing any air handling system that is more than fifteen years old; upgrading any general lighting system that serves an area greater than 100 m 2 which has an average lamp efficacy of less than 40 lamp-lumens per circuit-watt; installing energy metering; upgrading existing LZC energy systems if they provide less than 10% of the building s energy demand.

9 38 Building Regulations in Brief B.8 Controlled fittings Where windows, roof windows, rooflights or doors are to be provided, then draught-proofed units with an area-weighted average performance no worse than that shown in Table B1 (for fittings provided during the constriction of an extension) or Table B2 (for replacement or new fittings installed in the existing dwelling). Note: See BR 443 and SAP 2005 Table 6e for further guidance and values etc. Table B1 Reasonable provision when working on controlled fittings Fitting Window, roof window and rooflight Doors with more than 50% of their internal face area glazed Other doors Standard for new fittings U-value 1.8 W/m 2 K or Window energy rating Band D, or Centre-pane U-value 1.2 W/m 2 K 2.2 W/m 2 K or centre-pane U-value 1.2 W/m 2 K 3.0 W/m 2 K Table B2 Standards for thermal elements Element Wall Pitched roof insulation at ceiling level Pitched roof insulation at rafter level Flat roof or roof with integral insulation Floors Standard for replacement thermal elements in an existing dwelling 0.35 W/m 2 K 0.16 W/m 2 K 0.20 W/m 2 K 0.25 W/m 2 K 0.25 W/m 2 K B.9 Controlled services (non-domestic buildings) Where the work involves the provision of a controlled service: all new services should be energy efficient; all windows, roof windows, rooflights and/or doors should be provided with draught-proofed units; new HVAC systems should be provided with controls that are capable of achieving a reasonable standard of energy efficiency; fixed building services systems should be sub-divided into separate control zones for each area of the building with a significantly different solar exposure, occupancy period or type of use; separate control zones should be capable of independent switching and control set-point.

10 Appendix B Conservation of fuel and power 39 If both heating and cooling are provided, then they should not be capable of operating simultaneously. The central plant serving zone-based systems should: only operate as and when required; have a default condition that is off. B.10 Extensions When building an extension to an existing dwelling or building, the following applies. B.10.1 Dwellings The area of windows, roof windows and doors in extensions should not be greater than 25% of the floor area of the extension plus the area of any windows or doors, which, as a result of the extension works, no longer exist or are no longer exposed. B.10.2 Buildings other than dwellings The area of windows and rooflights in the extension: of residential buildings should be less than 30% of the exposed wall; of offices, shops and places where people assemble should be less than 40% of the exposed wall; of industrial and storage buildings should be less than 15% of the exposed wall. The area of windows, roof windows and doors in extensions shall not exceed the sum of 25% of the floor area of the extension; plus the area of any windows or doors which, as a result of the extension works, no longer exist or are no longer exposed. Note: See BS :1992 for further guidance. The area weighted U-value of all the elements in the extension should be no greater than that of an extension of the same size and shape. The area weighted U-value for each element type should be no worse than the value for similar work being carried out on domestic buildings. B.11 Conservatories Conservatories that are built at ground level and which have a floor area less than 30 m 2 are exempt from the Building Regulations (other than having to satisfy the requirements of Part N).

11 40 Building Regulations in Brief To meet the requirements for energy conservation, conservatories (and other substantially glazed extensions) will need to be thermally separated from the heated area of an existing dwelling and to achieve this, the walls, doors and windows between the dwelling and the extension should be insulated and draughtstripped to at least the same extent as in the existing dwelling. Conservatories will also need to have: heating systems equipped with independent temperature and on/off controls; thermal elements that have U-values that are no worse than that shown in Table B3. Table B3 Standards for thermal elements (W/m 2 K) Element Standard for replacement thermal elements in an existing dwelling Wall 0.35 W/m 2 K Pitched roof insulation at ceiling level 0.16 W/m 2 K Pitched roof insulation at rafter level 0.20 W/m 2 K Flat roof or roof with integral insulation 0.25 W/m 2 K Floors 0.25 and glazed elements that comply with the following standards. B.11.1 Dwellings Table B4 Standards for glazed elements (W/m 2 K) for dwellings Element Windows, roof windows, rooflights & doors Doors with 50% of their internal face glazed Other doors Standard for replacement glazed element in an existing dwelling 2.2 W/m 2 K (1.2 centre pane) 2.2 W/m 2 K (1.2 centre pane) 3.0 W/m 2 K B.11.2 Buildings other than dwellings Table B5 Standards for glazed elements (W/m 2 K) for buildings other than dwellings Element Windows, roof windows, rooflights & doors Pedestrian doors with 50% of their internal face glazed High usage entrance doors Vehicle access and large doors Roof ventilators Standard for replacement glazed element in an existing dwelling 2.2 W/m 2 K (1.2 centre pane) 2.2 W/m 2 K 6.0 W/m 2 K 1.5 W/m 2 K 6.0 W/m 2 K

12 Appendix B Conservation of fuel and power 41 B.12 Thermal elements New thermal elements must be reasonably energy efficient. Renovated thermal elements shall have improved energy efficiency. Retained thermal elements whose U-value is worse than the threshold value shall be upgraded. Thermal bridges in the insulation layers around window and door openings shall be avoided. Unwanted air leakage through the new envelope parts shall be minimized. When a thermal element is being renovated or replaced it should meet the requirements for limiting heat gains and losses. B.12.1 U-values Newly constructed thermal elements that are part of an extension should meet the standards set out in column (a) Table B6 and have a U-value better than that shown in column (b), Table B7. Table B6 Standards for thermal elements Element (a) Standard for new (b) Standard for replacement thermal elements in thermal elements in an an extension existing dwelling Wall 0.30 W/m 2 K 0.35 W/m 2 K Pitched roof insulation at 0.16 W/m 2 K 0.16 W/m 2 K ceiling level Pitched roof insulation at 0.20 W/m 2 K 0.20 W/m 2 K rafter level Flat roof or roof with integral 0.20 W/m 2 K 0.25 W/m 2 K insulation Floors 0.22 W/m 2 K 0.25 W/m 2 K Table B7 Limiting U-value standards Element (a) Area-weighted (b) Limiting U-value average U-value Wall 0.35 W/m 2 K 0.70 W/m 2 K Floor 0.25 W/m 2 K 0.70 W/m 2 K Roof 0.25 W/m 2 K 0.35 W/m 2 K Windows, roof windows, 2.2 W/m 2 K 3.3 W/m 2 K rooflights and doors B.12.2 Continuity of insulation and airtightness Where reasonably possible, thermal bridges in the insulation layers (caused by gaps within the various elements, at the joints between elements and at the edges of elements such as those around window and door openings) should be reduced.

13 42 Building Regulations in Brief Note: See TSO Robust Details catalogue and/or BRE IP 1/06. B.13 Renovation of thermal elements When a thermal element is renovated it should, in most cases, meet the standard set out in column (b) of Table B8. If such an upgrade is not technically or functionally feasible (or would not achieve a simple payback of 15 years or less) the element should be in as per the guidance contained in Appendix A of Approved Document L1B. Thermal elements whose U-value is worse than the threshold value shown in column (a) of Table B8 should be upgraded to the best standard that is technically and functionally feasible and which delivers a simple payback period of 15 years or less. Table B8 Upgrading retained thermal elements Element (a) Threshold value (b) Improved value Cavity wall 0.70 W/m 2 K 0.55 W/m 2 K Other wall type 0.70 W/m 2 K 0.35 W/m 2 K Floor 0.70 W/m 2 K 0.25 W/m 2 K Pitched roof insulation at ceiling level 0.35 W/m 2 K 0.16 W/m 2 K Pitched roof insulation between rafters 0.35 W/m 2 K 0.20 W/m 2 K Flat roof or roof with integral insulation 0.35 W/m 2 K 0.25 W/m 2 K B.13.1 Conservatories and substantially glazed spaces If a conservatory is built as part of the new dwelling, then the performance of the dwelling should be assessed (i.e. as if the conservatory were not there) and L1B should be followed in respect of the construction of the conservatory itself. This means that the thermal separation between dwelling and conservatory must be constructed to a standard comparable to the rest of the external envelope of the dwelling. Substantially glazed spaces that are actually part with the dwelling (i.e. there is no thermal separation and therefore, by definition, the space is not a conservatory) should be included as part of the new dwelling when checking against the five compliance criteria. B.14 Demonstrating compliance Compliance with L1A and L2A s requirements and recommendations can be achieved by meeting the five criteria shown in Table B9.

14 Appendix B Conservation of fuel and power 43 Table B9 The five criteria for demonstrating compliance with AD L1A Criteria Requirement In a nutshell 1 Achieving the TER The predicted rate of CO 2 emissions from the dwelling (i.e. the dwelling emission rate or DER) and/or a building (i.e. the Building Emission Rate or BER) shall not be greater than the target emission rate (TER). 2 Limits on design flexibility The performance of the building fabric, the fixed building services and parts of the building provided with comfort cooling should be no worse than the design limits. 3 Limiting the effects of solar The dwelling shall have appropriate gains in summer passive control measures to limit the effect of solar gains on indoor temperatures in summer. 4 Building fabric The performance of the dwelling, as built, shall be the BER or DER (as appropriate). 5 Commissioning of heating The necessary provisions for energy and hot water systems efficient operation of the dwelling are put in place. Appendix A to Parts L1A and L2A contain checklists that can be used to confirm that all the provisions in a new dwelling or building have been met satisfactorily. These checklists have been included at Appendix 1 to this appendix. B.14.1 Criterion 1 Achieving the TER The Target CO 2 Emission Rate (TER) is the minimum energy performance requirement for all new dwellings and buildings, expressed in terms of the amount of carbon dioxide (CO 2 ) in units of kg per m 2 of floor area, that is annually emitted by a standardized household through the provision of heating, hot water, ventilation and internal fixed lighting and (in addition) buildings as a result of cooling and lighting. The requirement from Regulation 17C clearly states that New buildings shall meet the target CO 2 emission rate for the building. In other words, the Dwellings (CO 2 ) Emission Rate (DER) or the Building (CO 2 ) Emission Rate (BER) must not be worse than the Target (CO 2 ) Emission Rate (TER) and so the final calculation must be based on the building as constructed, incorporating: any changes to the performance specifications that have been made during construction; the measured air permeability, ductwork leakage and fan performances as commissioned.

15 44 Building Regulations in Brief The person carrying out the work shall: ensure that pressure testing has been carried out in accordance with approved procedures and the results have been forwarded for approval to the local authority (if the person carrying out the work is registered by the British Institute of Non-destructive Testing, then the local authority will accept a certificate signed by that person as proof of compliance); ensure that the local authority are (when necessary) supplied with a notice confirming that the fixed building services have been commissioned in accordance with approved procedures; provide the local authority with a notice which specifies: the target CO 2 emission rate for the building; and the calculated CO 2 emission rate for the building as constructed. (if the person carrying out the work is registered by FAERO Limited; or BRE Certification Limited in respect of the calculation of CO 2 emission rates of buildings, then the local authority will accept a certificate signed by that person as proof of compliance). Air leakage testing of ductwork should be carried out on: all systems served by fans with a design flow rate greater than 1 m 3 /s and all sections of ductwork where HVCA DW/143 recommends testing. CO 2 emission rate calculations Individual dwellings For individual dwellings the TER is calculated by using: the Government s Standard Assessment Procedure (SAP) for individual dwellings with less than 450 m 2 total floor area; the Simplified Building Energy Model (SBEM) for individual dwellings with more than 450 m 2 total floor area; as follows: first, estimate the amount of CO 2 emissions from a notional dwelling that is the same size and shape as the new dwelling and whose emissions arise from: the provision of heating and hot water, CH (which includes the energy used by pumps and fans); and the use of internal fixed lighting CL. secondly, determine the TER using the following formula: TER (CH fuel factor CJ (1 improvement factor) where the fuel factor is taken from Table B10 and the improvement factor (for the 2006 revision of Part L) is 20%.

16 Appendix B Conservation of fuel and power 45 Table B10 Fuel factor Heating fuel Fuel factor Mains gas 1.00 LPG 1.10 Oil 1.17 Grid electricity (for direct acting, storage and electric heat pump systems) 1.47 Solid mineral fuel 1.28 Renewable energy (including bio-fuels such as wood pellets) 1.00 Solid multi-fuel 1.00 Note: The specific fuel factor should be used for those appliances that can only burn the particular fuel. Where an appliance is classed as multi-fuel, the multifuel factor should be used, except where the dwelling is in a smoke control area. In such cases the solid mineral fuel figure should be used, unless the specific appliance type has been approved for use within smoke control areas. The fuel factor used to calculate the TER should be based on the following fuel: Where all the heating appliances the fuel used in those appliances are served by the same fuel Where a dwelling has more than the fuel used for the TER one heating appliance and these are served by different fuels calculation should be: mains gas if any of the heating appliances are fired by mains gas; otherwise the fuel used in the main heating system Where a dwelling is served by a the principal fuel used by the community heating scheme community heating system Buildings with multiple dwellings For buildings consisting of multiple dwellings (e.g. terrace houses or blocks of apartments), the floor area-weighted average of all the individual TERs (using the following formula) should be used: (TER Floor area) (TER 2 Floor area 2 ) (TER N Floor area N ) Floor area Floor area 2 Floor area N Compliance (i.e. with Regulation 17C) will be achieved if: either every individual dwelling has a DER that is no greater than its corresponding TER; or the average DER is no greater than the average TER. Note: The average DER is the floor area-weighted average of all the individual DERS, and is calculated in the same way as the average TER (see above).

17 46 Building Regulations in Brief New buildings The TER is calculated using either the simplified building energy model (SBEM) or another approved software such as dynamic simulation models (see Annex 1 to ODPM Circular 03/2006). The TER is calculated in two steps: Step 1 Use an approved calculation tool to calculate the CO 2 emission rate (C notional ) from a notional building with the same size, shape, energy performance value and which is subject to the same occupancy levels and environmental conditions as the proposed building; Step 2 Adjust the CO 2 emissions rate (calculated in Step 1) by an improvement factor using the following formula: TER C notional (1 improvement factor) (1 LZC benchmark) where the: improvement factor is the improvement in energy efficiency shown in column A of Table B11 that is appropriate to the classes of building services being provided in the proposed building; LZC benchmark is the benchmark provision for low and zero carbon energy sources shown in column B of Table B11. Table B11 Improvement in whole building carbon dioxide emissions Building services strategy A B Improvement factor LZC benchmark Heated and naturally ventilated Heated and mechanically ventilated Air conditioned The BER is calculated in a similar manner to the TER (see above) but in this case, two calculations are required as follows: 1. A preliminary calculation as part of the design submission (based on plans and specifications and the CO 2 emissions factors shown in Table B12). Note: This would normally be provided as part of the full plans submission. 2. A final calculation (based on the dwelling as constructed and incorporating any changes to the performance specifications that have been made during construction) together with the measured air permeability, ductwork leakage and fan performance as commissioned. In some cases, management features can improve the energy efficiency of a building. When this occurs, the BER can be reduced by the adjustment factor shown in Table B13.

18 Appendix B Conservation of fuel and power 47 Table B12 CO 2 emission factors Fuel CO 2 emission factor (kg CO 2 /kwh) Natural gas LPG Biogas Oil Coal Anthracite Smokeless fuel (including coke) Duel fuel appliances (e.g. mineral wood) Biomass Grid supplied electricity Grid displaced electricity (i.e. building integrated power generation systems) Waste heat (e.g. from industrial processes) Note: The power factor adjustment can only be taken if the whole building power factor is corrected to the level stated. Table B13 Enhanced management and control features Feature Adjustment factor Automatic monitoring and targeting with alarms for out of range values Power factor correction to achieve a whole-building power factor of at least 0.90 Power factor correction to achieve a whole-building power factor of at least 0.95 Technical risk Whilst all building work must satisfy the technical requirements set out in the Regulations, the inclusion of any particular energy efficiency measure should not involve excessive technical risk. Limits on design flexibility (domestic buildings) The performance of the building fabric and the fixed building services should be no worse than the design limits. Reasonable provision should be made to limit heat gains and losses through the fabric of the building. Energy-efficient building services and effective controls should be provided. Secondary heating Where a secondary heating appliance is fitted, the efficiency of the actual appliance with its appropriate fuel shall be used in the calculation of the DER. Where a chimney or flue is provided (but no appliance is actually installed) then the presence of the following appliances shall be assumed when

19 48 Building Regulations in Brief calculating the DER: if a gas point is located then a decorative fuel effect fire open to the chimney or adjacent to the hearth flue with an efficiency of 20% shall be assumed if there is no gas point then an open fire in grate with an efficiency of 37% burning multi-fuel (unless the dwelling is in a smoke control area when the fuel should be taken as smokeless solid mineral fuel) shall be assumed In all other cases an electric room heater shall be taken as the secondary heating appliance. Lighting In all cases the DER should be calculated using a fixed assumption of 30% low energy lighting. Fixed internal lighting Lighting fittings (including lamp, control gear and an appropriate housing, reflector, shade or diffuser or other device for controlling the output light) should only take lamps with a luminous efficiency greater than 40 lumens per circuit-watt (please note that light fittings in less frequented areas such as cupboards and other storage areas do not count). Fluorescent and compact fluorescent lighting fittings will meet this requirement but light fittings for GLS tungsten lamps with bayonet cap or Edison screw bases, or tungsten halogen lamps will not. Fixed internal lighting domestic buildings Light fittings should only take lamps with a luminous efficiency greater than 40 lumens per circuit-watt The occupiers of a dwelling should be provided with efficient electric lighting whenever a dwelling is extended; or a new dwelling is created from a material change of use; or an existing lighting system is being replaced as part of re-wiring works. All re-wiring works must comply with Part P. A light fitting may contain one or more lamps. In some cases, of course, it might be better to install an energy-efficient light fitting in a location that is not part of the building work (i.e. such as replacing the fitting on the landing when a new bedroom is created via a loft conversion). Fixed external lighting Fixed external lighting, when supplied, should be provided with effective control and/or the use of efficient lamps.

20 Appendix B Conservation of fuel and power 49 Re-wiring works must comply with Part P. Fixed energy-efficient light fittings (one per 25 m 2 dwelling floor area (excluding garages) and one per four fixed light fittings) should be installed in the most frequented locations in the dwelling. Fixed external lighting (i.e. lighting that is fixed to an external surface of the dwelling and which is powered from the dwelling s electrical system) should either: have a lamp capacity not exceeding 150 W per light fitting that automatically switches off when there is enough daylight and when it is not required at night; or include sockets that can only be used with lamps which have an efficiency greater than 40 lumens per circuit watt. Note: Compact fluorescent lamps would meet this last requirement but, lamps with bayonet cap or Edison screw bases or tungsten halogen lamps would not. Lighting controls (non-domestic buildings) Local switches should be: located in easily accessible positions within each working area (or at boundaries between working areas and general circulation routes); operated by the deliberate action of the occupants, either manually or remotely; located within six metres (or twice the height of the light fitting above the floor if this is greater) any luminaire it controls. Lighting controls should be provided that switch off the lighting during daylight hours and when the area is unoccupied. Automatically switched lighting systems should be subject to a risk assessment. Manually operated local switches should be in easily accessible positions within each working area, at boundaries between working areas, and at general circulation routes. If the space is daylit space served by side windows, the perimeter row of luminaires should be separately switched. Local (manual) switching can be supplemented by automatic controls which: switch the lighting off when they sense the absence of occupants or dim (or switch off) the lighting when there is sufficient daylight. Office, industrial and storage areas (non-domestic buildings) Classrooms, seminar and conference rooms etc. shall have an average efficiency of not less than 45 luminaire-lumens/circuit-watt. Display lighting in all types of space (non-domestic buildings) Display lighting should have an average initial (100 hour) efficiency of not less than 15 lamp-lumens per circuit-watt.

21 50 Building Regulations in Brief Where possible, display lighting should be connected in dedicated circuits that can be switched off at times when people will not be inspecting exhibits or merchandise or attending entertainment events. Emergency escape lighting (non-domestic buildings) Emergency escape lighting, specialist process lighting and vertical transportation systems are not subject to the requirements of Part L. General lighting efficiency in all other types of space (non-domestic buildings) Lighting (over the whole of these areas) should have an average initial efficacy of not less than 45 luminaire-lumens/circuit-watt. Lighting systems serving other types of space, may use lower powered and less efficient lamps. B.14.2 Criterion 2 Limits on design flexibility Criterion 2 sets out the design limits for the building fabric to meet the requirements for conservation of fuel through thermal elements and other parts of the building fabric and for the provision and commission of energy efficient fixed building services and controls. Note: In all cases the performance of the building fabric and the heating, hot water and fixed lighting systems should be no worse than the design limits. Design limits for envelope standards U-values U-values (i.e. the overall coefficient of heat transmission) indicate the heat flow through materials and need to be calculated using the methods and conventions set out in BR 443 ( Conventions for U-value calculations ) and recognized limits for plane element U-values for building fabric elements are shown in Table B14 below: Table B14 Limiting U-value standards (W/m 2 K) Element Area-weighted Worst individual dwelling average sub-element Wall Floor Roof Windows, roof windows, rooflights & doors Pedestrian doors Vehicle access & similar large doors High usage entrance doors Roof ventilators (including smoke vents)

22 Appendix B Conservation of fuel and power 51 Note: Display windows and similar glazing are not required to meet the standard given for Windows and rooflight. Air permeability Air permeability is the physical property used to measure the airtightness of the building fabric and is defined as air leakage rate per envelope area at the test reference pressure differential across the building envelope of 50 Pa (50 N/ml). The envelope area of the building is the total area of all floors, walls and ceilings bordering the internal volume subject to the test and including walls and floors below external ground level. Overall internal dimensions are used to calculate this area and no subtractions are made for the area of the junctions of internal walls, floors and ceilings with exterior walls, floors and ceilings. A reasonable limit for the design air permeability is 10 m 3 /(h.m 2 ) at 50 Pa and guidance on some ways of achieving this is given in Limiting thermal bridging and air leakage: Robust construction details for dwellings and similar buildings (available from Building services Controls Systems should be sub-divided into separate control zones. Separate control zones should be capable of independent timing, temperature control and (where appropriate) ventilation and air recirculation rate. Heating and cooling systems should not operate simultaneously. Central plant should only operate when zone systems require it. The default condition should be off. Energy meters Energy performance monitoring meters should be included in the installation of all new building services equipment. Separate meters should be provided to monitor low or zero carbon (LZC) systems. Buildings with floor areas greater than 1000 m 2 should include an automatic meter reading and data collection facility. Heating and hot water system(s) If a heating or hot water system is being provided or extended then the installed appliance should: not be less than that recommended for its type in the Domestic Heating Compliance Guide; have an efficiency which is not worse than 2% lower than that of the appliance being replaced if the appliance is the primary heating service;

23 52 Building Regulations in Brief be provided with controls that meet the minimum control requirements of the Domestic Heating Compliance Guide for the particular type of appliance and heat distribution system; be commissioned so that at completion, the system(s) and their controls are left in working order and can operate efficiently for the purposes of the conservation of fuel and power: Note: The person carrying out the work shall provide the local authority with a notice (signed by a suitably qualified person) confirming that all fixed building services have been properly commissioned in accordance with the Domestic Heating Compliance Guide. Insulation of pipes, ducts and vessels Hot and chilled water pipework, storage vessels, refrigerant pipework and ventilation ductwork should be insulated so as to conserve energy and to maintain the temperature of the heating or cooling service. Air handling plant Should be an efficient and effective control system. Should be capable of achieving a specific fan power at 25% of design flow rate. Fans rated at more than 1100 W should be equipped with variable speed drives. Ventilation ductwork should be reasonably airtight. Mechanical ventilation The performance of systems should be better than those described in GPG 2689 (Energy-efficient ventilation in housing) and their fan powers and heat recovery efficiency should be no worse than those listed in Table B15. Table B15 Limits on design flexibility for mechanical ventilation System type Performance Specific fan power (SFP) for continuous supply only and continuous 0.8 litre/s.w extract only SFP for balanced systems 2.0 litre/s.w Heat recovery efficiency 66% In dwellings, mechanical ventilation systems must satisfy the requirements in Part F.

24 Appendix B Conservation of fuel and power 53 Cooling plant Cooling systems should have a: suitably efficient cooling plant, and an effective control system. Mechanical cooling Fixed air conditioners in new dwellings should have an energy efficiency classification equal to or better than Class C in Schedule 3 of the labelling scheme adopted under The Energy Information (Household Air Conditioners) No 2 Regulations (SI 2005/1726). Building services (non-domestic buildings) For energy saving purposes, Approved Document L2A requires that: all heating, ventilation and air-conditioning systems should be provided with controls to enable them to achieve reasonable standards of energy efficiency; display lighting should be connected in dedicated circuits that can be switched off at times when people will not be inspecting exhibits or merchandise or attending entertainment events; heating and hot water service systems (cooling plant and/or air-handling plants) should have an efficiency not less than that recommended for its type in the non-domestic heating, cooling and ventilation compliance guide; lighting systems should be capable of being automatically (or in certain circumstances, mechanically) being switched off during daylight hours and in unoccupied working spaces etc.; pipes, ducts and vessels should be insulated in accordance with the recommendations contained in the ODPM s Domestic Heating Compliance Guide; systems should be provided with energy meters to efficiently manage the amount energy used. Emergency escape lighting, specialist process lighting and vertical transportation systems are not subject to the requirements of Part L. Inspection and commissioning of the building services systems For non-domestic buildings, when building services systems are commissioned: the systems and their controls shall be left in their intended working order and are capable of operating efficiently regarding the conservation of fuel and power; the person carrying out the work shall provide the local authority with a notice confirming that all fixed building services have been properly commissioned; leakage testing should be carried out in accordance with the procedures set out in DW/143, HVCA, 2000.

25 54 Building Regulations in Brief B.14.3 Criterion 3 Limiting the effects of solar gains in summer High internal temperatures caused by solar gains should be minimized by a combination of: window size and orientation; shading; ventilation; and high thermal capacity. Note: For further guidance on how to control overheating, see: BR 364 Solar shading of buildings; AM 10 Natural ventilation in non-domestic buildings; BS 8206 Part 2 Code of practice for daylighting; CE129 Reducing overheating a designer s guide; TM37 Design for improved solar shading control; Building Bulletins 87 and 101 (concerning school buildings); SAP 2005 Appendix P (which contains a procedure enabling designers to check whether solar gains are excessive). When trying to limit solar gains, consideration should also be given to the provision of adequate levels of daylight. BS 8206 Part 2 (Code of practice for daylighting) provides some guidance on maintaining adequate levels of daylighting. Note: Those parts of the building that are provided with comfort cooling should have passive control measures to limit the effect of solar gains. Dwellings Dwellings shall have passive control measures to limit the effect of solar gains on indoor temperatures in summer. High internal temperatures caused by solar gains should be minimized by a combination of window size and orientation; shading; ventilation and high thermal capacity. Buildings other than dwellings High internal temperatures caused by solar gains should be minimized by a combination of: window size and orientation; shading; ventilation and high thermal capacity. In occupied spaces that are not served by a comfort cooling system: the combined solar and internal casual gains (people, lighting and equipment) per unit floor area averaged over the period of daily occupancy should not be greater than 35 W/m 2 calculated over a perimeter area not more than 6 m from the window wall and averaged during the period hrs GMT; the operative dry resultant temperature does not exceed 28ºC for more than a reasonable number of occupied hours per annum.

EPBD and Part L. Anthony Slater. BRE Environment

EPBD and Part L. Anthony Slater. BRE Environment EPBD and Part L Anthony Slater BRE Environment Energy Performance of Buildings Directive Directive 2002/91/EC of the European Parliament and Council published 4 January 2003 Directive lays down requirements

More information

The Building Regulations, Part L (2013)

The Building Regulations, Part L (2013) Latest Release November 2013 Technical Briefing Note The Building Regulations, Part L (2013) www.xtratherm.com Technical Briefing Note The Building Regulations, Part L (2013) The latest revisions to energy

More information

I Prophets energy services

I Prophets energy services CIBSE LOW CARBON CONSULTANTS REGISTER SESSION 7 BUILDING REGULATIONS APPROVED DOCUMENT L2B I Prophets energy services 03012013 Key Features Slide 4 ADL2B Details Slide 13 Controlled Fittings Slide 20 Controlled

More information

Building Control. A Guide to Compliance When Designing Domestic Extensions

Building Control. A Guide to Compliance When Designing Domestic Extensions Building Control Technical Guidance Leaflet No. 18 Approved Document L1B 2010 Conservation of Fuel and Power This leaflet is one of a series produced by the Hertfordshire Building Control Technical Forum

More information

Department of Finance and Personnel Building Regulations (Northern Ireland) October 2012

Department of Finance and Personnel  Building Regulations (Northern Ireland) October 2012 Department of Finance and Personnel www.dfpni.gov.uk Building Regulations (Northern Ireland) 2012 G u i d a n c e Technical Booklet F1 Conservation of fuel and power in dwellings October 2012 Contents

More information

conservation of fuel and power

conservation of fuel and power The conservation of fuel and power Approved document Conservation of fuel and power in new dwellings 2013 edition for use in England* main changes in the 2013 edition This approved document, Approved Document

More information

City of York Council Offices West Offices, York for

City of York Council Offices West Offices, York for City of York Council Offices for Part L2A Compliance Report 'As Built' Udox Solutions Ltd Low Carbon & Sustainability Consultants 7 Spur Drive Leeds West Yorkshire LS15 8UD T 0113 260 2855 1010178 / L2A

More information

CIBSE LOW CARBON CONSULTANTS REGISTER SESSION 5 BUILDING REGULATIONS APPROVED DOCUMENT L2A. I Prophets energy services

CIBSE LOW CARBON CONSULTANTS REGISTER SESSION 5 BUILDING REGULATIONS APPROVED DOCUMENT L2A. I Prophets energy services CIBSE LOW CARBON CONSULTANTS REGISTER SESSION 5 BUILDING REGULATIONS APPROVED DOCUMENT L2A I Prophets energy services 03012013 CONTENTS Demonstrating Compliance - Overview Criterion One Criterion Two Criterion

More information

Approved Document L1A and L2A

Approved Document L1A and L2A Guide to: Approved Document L1A and L2A For England and Wales NEWBUILD Conservation of fuel and power APPROVED DOCUMENTL1A Conservation of fuel and power APPROVED DOCUMENTL2A Talk to the SIG360 team at

More information

O N L I N E V E R S I O N

O N L I N E V E R S I O N The Building Regulations 2010 APPROVED DOCUMENT in existing dwellings In effect from 1 October 2010 For use in England* 2010 edition incorporating 2010, 2011 and 2013 amendments MAIN CHANGES IN THE 2010

More information

L1A ONLINE VERSION ONLINE VERSION ONLINE VERSION edition. Conservation of fuel and power APPROVED DOCUMENT. The Building Regulations 2000

L1A ONLINE VERSION ONLINE VERSION ONLINE VERSION edition. Conservation of fuel and power APPROVED DOCUMENT. The Building Regulations 2000 The Building Regulations 2000 APPROVED DOCUMENT L1A L1A in new dwellings Coming into effect 1 October 2010 2010 edition MAIN CHANGES IN THE 2010 EDITION 1. This comes into force on 1 October 2010 in support

More information

ONLINE VERSION ONLINE VERSION ONLINE VERSION edition. Conservation of fuel and power APPROVED DOCUMENT. The Building Regulations 2000

ONLINE VERSION ONLINE VERSION ONLINE VERSION edition. Conservation of fuel and power APPROVED DOCUMENT. The Building Regulations 2000 The Building Regulations 2000 APPROVED DOCUMENT L1A L1A in new dwellings Coming into effect 1 October 2010 2010 edition MAIN CHANGES IN THE 2010 EDITION 1. This comes into force on 1 October 2010 in support

More information

Guide to Building Regulations changes 2010

Guide to Building Regulations changes 2010 T E C H N I C A L PA P E R - N O. 1 0 / 0 2 The authors HUW EVANS has a post-graduate degree in Technical Authorship from Sheffield Hallam University. He has a particular interest in building physics and

More information

L1B ONLINE VERSION ONLINE VERSION ONLINE VERSION edition. Conservation of fuel and power APPROVED DOCUMENT. The Building Regulations 2000

L1B ONLINE VERSION ONLINE VERSION ONLINE VERSION edition. Conservation of fuel and power APPROVED DOCUMENT. The Building Regulations 2000 The Building Regulations 2000 APPROVED DOCUMENT in existing dwellings Coming into effect 1 October 2010 2010 edition MAIN CHANGES IN THE 2010 EDITION 1. This comes into force on 1 October 2010 in support

More information

O N L I N E V E R S I O N

O N L I N E V E R S I O N The Building Regulations 2010 APPROVED DOCUMENT in existing dwellings In effect from 1 October 2010 For use in England* 2010 edition incorporating 2010, 2011, 2013, 2016 and 2018 amendments MAIN CHANGES

More information

The Building Regulations Conservation of fuel and power L2B APPROVED DOCUMENT. in existing buildings other than dwellings

The Building Regulations Conservation of fuel and power L2B APPROVED DOCUMENT. in existing buildings other than dwellings The Building Regulations 2000 APPROVED DOCUMENT in existing buildings other than dwellings Coming into effect 6 April 2006 2006 edition MAIN CHANGES IN THE 2006 EDITIONS 1. This comes into force on 06

More information

The Building Regulations Part L Conservation of Fuel & Power 2013 Edition

The Building Regulations Part L Conservation of Fuel & Power 2013 Edition The Building Regulations 2010 Part L Conservation of Fuel & Power 2013 Edition Without looking into the technical input for SAP etc (subject to a further presentation), what does it mean in practical terms

More information

O N L I N E V E R S I O N

O N L I N E V E R S I O N The Building Regulations 2010 APPROVED DOCUMENT in existing dwellings In effect from 1 October 2010 For use in England* 2010 edition incorporating 2010, 2011, 2013 and 2016 amendments MAIN CHANGES IN THE

More information

CHAPTER 13: Sustainability

CHAPTER 13: Sustainability CONTENTS 13.1 THE CODE FOR SUSTAINABLE HOMES 13.2 LOW CARBON / LOW ENERGY HOMES 13.3 AIR TIGHTNESS AND ROBUSTNESS 13.4 RENEWABLE ENERGY SOURCES Chapter 13 FUNCTIONAL REQUIREMENTS FUNCTIONAL REQUIREMENTS

More information

L2A 2010 In 30 Minutes!!

L2A 2010 In 30 Minutes!! 00:14:58 L2A 2010 In 30 Minutes!! The Stroma Group Building Sustainability & Compliance Presented by: Richard de Fleury BEng (hons) MSc 14:59:56 Part L 2010 - Agenda Summary of changes Criterion 1 Criterion

More information

Engineers Ireland Cork Region CPD lecture series

Engineers Ireland Cork Region CPD lecture series Engineers Ireland Cork Region CPD lecture series NZEB and Emerging Legislation & SEAI s Deep Retrofit Pilot Programme Orla Coyle NZEB Programme Manager Conor Hanniffy Deep Retrofit Pilot Programme Manager

More information

Energy efficiency and the Code for Sustainable Homes

Energy efficiency and the Code for Sustainable Homes CE290 Energy efficiency and the Code for Sustainable Homes Level 3 Also available: Energy efficiency guidance for level 4 Energy efficiency guidance for levels 5 and 6 Contents 1. Introduction 3 1.1 The

More information

Part L 2010 Energy Performance Certificates

Part L 2010 Energy Performance Certificates Introduction Timescales for Implementation Changes to Changes for New Buildings Changes for Existing Buildings Part L 2010 Energy Performance Certificates Summary Version A: Sept 2010 Introduction Government

More information

Approved Document. New buildings other than dwellings. The Building Regulations Conservation of fuel and power L2A. Coming into effect July 2014

Approved Document. New buildings other than dwellings. The Building Regulations Conservation of fuel and power L2A. Coming into effect July 2014 The Building Regulations 2010 Conservation of fuel and power Approved Document New buildings other than dwellings Coming into effect July 2014 For use in Wales* Main changes in the 2014 edition This approved

More information

Building Regulations Part L 2013 For England. Ant Wilson Director/AECOM Fellow Building Engineering AECOM

Building Regulations Part L 2013 For England. Ant Wilson Director/AECOM Fellow Building Engineering AECOM Building Regulations Part L 2013 For England Ant Wilson Director/AECOM Fellow Building Engineering AECOM 1 st May 2014 2 Building Byelaws Thermal Insulation 3 Bringing in Part L 2002 Working With DETR

More information

IES <Virtual Environment> Live e-training Trainee notes <VE Compliance> England and Wales VE-DSM 2010 Version 6.4

IES <Virtual Environment> Live e-training Trainee notes <VE Compliance> England and Wales VE-DSM 2010 Version 6.4 IES Live e-training Trainee notes England and Wales VE-DSM 2010 Version 6.4 Introduction These training notes are to be used in conjunction with your scheduled IES

More information

This draft design submission has been prepared from plans and specifications and may not reflect the property as constructed.

This draft design submission has been prepared from plans and specifications and may not reflect the property as constructed. This Design Draft submission has been prepared by a Competent, registered with Faero Ltd. Faero Ltd. Scheme membership covers Criterion 1 of this checklist, that is, the requirement for the predicted carbon

More information

The effect of Building Regulations (Part L1 2002) on existing dwellings

The effect of Building Regulations (Part L1 2002) on existing dwellings GENERAL INFORMATION LEAFLET 70 The effect of Building Regulations (Part L1 2002) on existing dwellings Information for installers and builders for extensions and alterations in England and Wales " Insulation

More information

ONLINE VERSION ONLINE VERSION ONLINE VERSION edition. Conservation of fuel and power APPROVED DOCUMENT. The Building Regulations 2000

ONLINE VERSION ONLINE VERSION ONLINE VERSION edition. Conservation of fuel and power APPROVED DOCUMENT. The Building Regulations 2000 The Building Regulations 2000 APPROVED DOCUMENT L1A L1A in new dwellings Coming into effect 1 October 2010 2010 edition Amendments to Approved Documents and Compliance Guides 2010 All references to the

More information

Module 15. Country Specific Legislation

Module 15. Country Specific Legislation Module 15 Country Specific Legislation Module 15 Country Specific Legislation On completion of this module learners will be able to: List the main pieces of legislation and standards which affect the energy

More information

Building Performance Evaluation

Building Performance Evaluation BUILDING PERFORMANCE EVALUATION CASE STUDY ONE BRIGHTON One Planet Living Zero carbon (renewable heat, on and off-site renewable electricity) Mechanical ventilation with heat recovery, communal heating,

More information

Part L Review New Domestic Buildings Tom Lelyveld, AECOM

Part L Review New Domestic Buildings Tom Lelyveld, AECOM Part L Review New Domestic Buildings 2014 Tom Lelyveld, AECOM 11 th -13 th February 2014 What I will be talking about Introduction Background Key changes to Part L1A 2014 meeting the five new-build compliance

More information

England and Wales. Lighting requirements for Part L of the Building Regulations. England and Wales. Installer s lighting guide number 4

England and Wales. Lighting requirements for Part L of the Building Regulations. England and Wales. Installer s lighting guide number 4 Installer s lighting guide number 4 Lighting requirements for Part L of the Building Regulations England and Wales The aim of this guide is to provide simple and practical guidance in understanding the

More information

Complying with the Minimum Energy Efficiency Standards (MEES)

Complying with the Minimum Energy Efficiency Standards (MEES) Complying with the Minimum Energy Efficiency Standards (MEES) Advantages of using DSM software to calculate the EPC Rating Introduction The Minimum Energy Efficiency Standards (MEES) for commercially rented

More information

DESIGNING WITH ROOFLIGHTS : SUPPORTING THE GUIDANCE IN AD L2A & AD L2B (2006)

DESIGNING WITH ROOFLIGHTS : SUPPORTING THE GUIDANCE IN AD L2A & AD L2B (2006) NATIONAL ASSOCIATION OF ROOFLIGHT MANUFACTURERS DESIGNING WITH ROOFLIGHTS : SUPPORTING THE GUIDANCE IN AD L2A & AD L2B (2006) Issue 1 - November 2006 Note: it is expected that there will be on going updates

More information

Amendments to the Approved Documents

Amendments to the Approved Documents The Building Regulations 2010 Amendments to the Approved Documents This document contains amendments to the following Approved Documents: A, B vol 1, B vol 2, C, D, E, F, G, H, J, L1A, L1B, L2A, L2B and

More information

The calculation procedure will continue to be known as SAP 2005 but the SAP version number is incremented from 9.80 to 9.81.

The calculation procedure will continue to be known as SAP 2005 but the SAP version number is incremented from 9.80 to 9.81. Amendments to SAP 2005 (version 9.81) April 2008 The calculation procedure will continue to be known as SAP 2005 but the SAP version number is incremented from 9.80 to 9.81. 1 Very little overshading The

More information

6.4 Insulation of pipes, ducts and vessels. 6.6 Mechanical ventilation and air conditioning. 6.7 Commissioning building services

6.4 Insulation of pipes, ducts and vessels. 6.6 Mechanical ventilation and air conditioning. 6.7 Commissioning building services domestic energy contents 2007 Contents 6.0 Introduction 6.1 Carbon dioxide emissions 6.2 Building insulation envelope 6.3 Heating system 6.4 Insulation of pipes, ducts and vessels 6.5 Artificial and display

More information

Amendments to the Approved Documents

Amendments to the Approved Documents The Building Regulations 2010 Amendments to the Approved Documents This document contains amendments to the following Approved Documents: A, B vol 1, B vol 2, C, D, E, F, G, H, J, L1A, L1B, L2A, L2B and

More information

Interim NZEB Performance Specification Calculation Methodology

Interim NZEB Performance Specification Calculation Methodology Interim NZEB Performance Specification Calculation Methodology Q1 2018 Contents: 1 Introduction... 2 2 Reference Building... 4 2.1 Project Database... 4 2.2 Geometry... 4 2.3 HVAC Systems... 6 2.4 HWS

More information

Glass and Building Regulations: Thermal Insulation and Energy Efficiency.

Glass and Building Regulations: Thermal Insulation and Energy Efficiency. Pilkington Activ TM CI/SfB (31) Ro5 (A3j) March 2003 ENERGY SPECIAL MANAGEMENT APPLICATIONS Glass and Building Regulations: Thermal Insulation and Energy Efficiency. England and Wales Approved Documents

More information

6.4 Insulation of pipes, ducts and vessels. 6.6 Mechanical ventilation and air conditioning. 6.7 Commissioning building services

6.4 Insulation of pipes, ducts and vessels. 6.6 Mechanical ventilation and air conditioning. 6.7 Commissioning building services domestic energy contents 2007 Contents 6.0 Introduction 6.1 Carbon dioxide emissions 6.2 Building insulation envelope 6.3 Heating system 6.4 Insulation of pipes, ducts and vessels 6.5 Artificial and display

More information

Project name SOLAR HOUSE 80/50 Project summary

Project name SOLAR HOUSE 80/50 Project summary http://lowenergybuildings.org.uk Project name SOLAR HOUSE 80/50 Project summary Project Description Projected build start date 01 Mar 2010 Projected date of occupation 19 Jul 2010 Project stage Under construction

More information

Part L, SBEM & What you need to know to get your building to pass. Mike Andrews DipNDEA, DipDEC, DipOCDEA, DipHI

Part L, SBEM & What you need to know to get your building to pass. Mike Andrews DipNDEA, DipDEC, DipOCDEA, DipHI Part L, SBEM & What you need to know to get your building to pass. Mike Andrews DipNDEA, DipDEC, DipOCDEA, DipHI The Building Regulations Part L2A, SBEM & the National Calculation Methodology what they

More information

ONLINE VERSION ONLINE VERSION ONLINE VERSION edition. Conservation of fuel and power APPROVED DOCUMENT. The Building Regulations 2000

ONLINE VERSION ONLINE VERSION ONLINE VERSION edition. Conservation of fuel and power APPROVED DOCUMENT. The Building Regulations 2000 The Building Regulations 2000 APPROVED DOCUMENT L1B L1B in existing dwellings Coming into effect 1 October 2010 2010 edition Amendments to Approved Documents and Compliance Guides 2010 All references to

More information

The Driver for Building Regulations on Energy Efficiency. Ant Wilson FREng, FCIBSE, FEI Director/AECOM Fellow Building Engineering AECOM

The Driver for Building Regulations on Energy Efficiency. Ant Wilson FREng, FCIBSE, FEI Director/AECOM Fellow Building Engineering AECOM The Driver for Building Regulations on Energy Efficiency Ant Wilson FREng, FCIBSE, FEI Director/AECOM Fellow Building Engineering AECOM 23 rd September 2015 2 CIBSE HNNW - Disclaimer The following material

More information

England Building Regulations Part L 2013

England Building Regulations Part L 2013 England Building Regulations Part L 2013 Domestic buildings Tom Lelyveld, David Ross 08 October 2013 Content Introduction Background Changes to meeting the five new-build compliance steps Existing dwellings

More information

Section 6 (Scotland) (2005) Methods (non-dwellings) <Virtual Environment> 5.9

Section 6 (Scotland) (2005) Methods (non-dwellings) <Virtual Environment> 5.9 Section 6 (Scotland) (2005) Methods (non-dwellings) 5.9 Page 1 of 21 Contents 1. Acknowledgements...3 2. Introduction...4 3. Basis for calculations...6 4. Section 6 Elemental and

More information

The BIG Energy Upgrade Energy Innovation for Retrofitting Deprived Community Housing in the UK

The BIG Energy Upgrade Energy Innovation for Retrofitting Deprived Community Housing in the UK The BIG Energy Upgrade Energy Innovation for Retrofitting Deprived Community Housing in the UK Dr. Hasim Altan Lecturer in Sustainable Environmental Design Director of BEAU Research Centre, School of Architecture

More information

The effect of Building Regulations (Part L1 2002) on existing dwellings

The effect of Building Regulations (Part L1 2002) on existing dwellings Energy Efficiency Best Practice in Housing The effect of Building Regulations (Part L1 2002) on existing dwellings Information for installers and builders for extensions and alterations in England and

More information

CI/SfB / / (31.4) / Xh2 / / June 2006 Catalogue No. 260X. Revised PART L Explained

CI/SfB / / (31.4) / Xh2 / / June 2006 Catalogue No. 260X. Revised PART L Explained CI/SfB / / (31.4) / Xh2 / / June 2006 Catalogue No. 260X S T E E L W I N D O W S Revised Explained revised explained... Introduction With effect from April 2006 a revised Building Regulations Approved

More information

L2A ONLINE VERSION ONLINE VERSION ONLINE VERSION edition. Conservation of fuel and power APPROVED DOCUMENT. The Building Regulations 2000

L2A ONLINE VERSION ONLINE VERSION ONLINE VERSION edition. Conservation of fuel and power APPROVED DOCUMENT. The Building Regulations 2000 The Building Regulations 2000 APPROVED DOCUMENT L2A L2A in new buildings other than dwellings Coming into effect 1 October 2010 2010 edition MAIN CHANGES IN THE 2010 EDITION 1. This comes into force on

More information

L2B edition. Conservation of fuel and power ONLINE VERSION APPROVED DOCUMENT ONLINE VERSION. The Building Regulations 2010

L2B edition. Conservation of fuel and power ONLINE VERSION APPROVED DOCUMENT ONLINE VERSION. The Building Regulations 2010 The Building Regulations 2010 APPROVED DOCUMENT L2B L2B in existing buildings other than dwellings In effect from 1 October 2010 For use in England* 2010 edition incorporating 2010, 2011, 2013 and 2016

More information

National Calculation Methodology (NCM) modelling guide (for buildings other than dwellings in England and Wales) 2010 Edition

National Calculation Methodology (NCM) modelling guide (for buildings other than dwellings in England and Wales) 2010 Edition National Calculation Methodology (NCM) modelling guide (for buildings other than dwellings in England and Wales) 2010 Edition May 2010 NCM modelling guide for buildings other than dwellings in England

More information

ONLINE VERSION ONLINE VERSION ONLINE VERSION edition. Conservation of fuel and power APPROVED DOCUMENT. The Building Regulations 2000

ONLINE VERSION ONLINE VERSION ONLINE VERSION edition. Conservation of fuel and power APPROVED DOCUMENT. The Building Regulations 2000 The Building Regulations 2000 APPROVED DOCUMENT L2A L2A in new buildings other than dwellings Coming into effect 1 October 2010 2010 edition MAIN CHANGES IN THE 2010 EDITION 1. This comes into force on

More information

For calculating and rating the energy performance of new and existing non-domestic buildings in the Republic of Ireland

For calculating and rating the energy performance of new and existing non-domestic buildings in the Republic of Ireland Non-domestic Energy Assessment Procedure (NEAP) Modelling Guide & SBEM Technical Manual version 3.5.a For calculating and rating the energy performance of new and existing non-domestic buildings in the

More information

IECC Residential Significant Changes Summary. Tier I

IECC Residential Significant Changes Summary. Tier I 2009-2015 IECC Residential Significant Changes Summary Tier I R401.2 Compliance options for compliance are now prescriptive path, Total UA (which is part of prescriptive), Performance and the new Energy

More information

8 TH ANNUAL INTERNATIONAL CONSTRUCTION MANAGEMENT Building Regulations What Next. By Eamonn Smyth Advisor Building Standards Section

8 TH ANNUAL INTERNATIONAL CONSTRUCTION MANAGEMENT Building Regulations What Next. By Eamonn Smyth Advisor Building Standards Section 8 TH ANNUAL INTERNATIONAL CONSTRUCTION MANAGEMENT Building Regulations What Next By Eamonn Smyth Advisor Building Standards Section Building Control Acts Building Regulations Technical Guidance Documents

More information

L2B ONLINE VERSION ONLINE VERSION ONLINE VERSION edition. Conservation of fuel and power APPROVED DOCUMENT. The Building Regulations 2000

L2B ONLINE VERSION ONLINE VERSION ONLINE VERSION edition. Conservation of fuel and power APPROVED DOCUMENT. The Building Regulations 2000 The Building Regulations 2000 APPROVED DOCUMENT L2B L2B in existing buildings other than dwellings Coming into effect 1 October 2010 2010 edition MAIN CHANGES IN THE 2010 EDITION 1. This comes into force

More information

ONLINE VERSION ONLINE VERSION ONLINE VERSION edition. Conservation of fuel and power APPROVED DOCUMENT. The Building Regulations 2000

ONLINE VERSION ONLINE VERSION ONLINE VERSION edition. Conservation of fuel and power APPROVED DOCUMENT. The Building Regulations 2000 The Building Regulations 2000 APPROVED DOCUMENT L2B L2B in existing buildings other than dwellings Coming into effect 1 October 2010 2010 edition MAIN CHANGES IN THE 2010 EDITION 1. This comes into force

More information

P78. Implementation of the EPBD in Ireland: Status and planning August [Country review] > Legal context. Deirdre Flood.

P78. Implementation of the EPBD in Ireland: Status and planning August [Country review] > Legal context. Deirdre Flood. [Country review] P78 25-08-2008 Deirdre Flood Sustainable Energy Ireland Ireland More Information Papers on other European activities can be found at: www.buildingsplatform.eu Implementation of the EPBD

More information

REScheck Software Version Compliance Certificate

REScheck Software Version Compliance Certificate REScheck Software Version 4.3.1 Compliance Certificate Project Title: Chow Residence Renovation Energy Code: 2009 IECC Location: Boston, Massachusetts Construction Type: Single Family Project Type: Addition/Alteration

More information

IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST

IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST ENVELOPE REQUIREMENTS Project: Date: Instructions RECOMMENDED: List performance values, note exceptions that were applied, or provide other

More information

ABBE LEVEL 3 DIPLOMA IN ON CONSTRUCTION ENERGY ASSESSMENT ABBE LEVEL 3 CERTIFICATE IN DOMESTIC ON CONSTRUCTION ENERGY ASSESSMENT (QCF)

ABBE LEVEL 3 DIPLOMA IN ON CONSTRUCTION ENERGY ASSESSMENT ABBE LEVEL 3 CERTIFICATE IN DOMESTIC ON CONSTRUCTION ENERGY ASSESSMENT (QCF) E LEVEL 3 IPLOM IN ON ONSTRUTION ENERGY SSESSMENT E LEVEL 3 ERTIFITE IN OMESTI ON ONSTRUTION ENERGY SSESSMENT (QF) SMPLE EXMINTION QUESTIONS The purpose of this document is to provide examples of typical

More information

Building Regulations Part L1A (2006)

Building Regulations Part L1A (2006) PART L1A GUIDE ENGLAND & WALES MAY 2006 High performance insulation for new mixed development housing Building Regulations Part L1A (2006) COST EFFECTIVE THERMAL SOLUTIONS House Type A House Type B House

More information

Designing with rooflights. Supporting Part L Building Regulation guidance in England; Approved Documents L1A, L1B, L2A and L2B (2013 editions)

Designing with rooflights. Supporting Part L Building Regulation guidance in England; Approved Documents L1A, L1B, L2A and L2B (2013 editions) Designing with rooflights Supporting Part L Building Regulation guidance in England; Approved Documents L1A, L1B, L2A and L2B (2013 editions) CONTENTS PAGE Scope 1 Introduction 2 Designing with Rooflights

More information

Energy Performance Certificate

Energy Performance Certificate Tuckeys Surveying Ltd Energy Performance Certificate Non-Domestic (Commercial) Building for Beck Steps Gift Shop, College Road, Grasmere, Cumbria LA22 9SZ 01 July 2014 Energy Performance Certificate

More information

Building Regulations - Part L (2002 Edition) User Guide

Building Regulations - Part L (2002 Edition) User Guide Building Regulations - Part L (2002 Edition) User Guide IES Virtual Environment Last update: Version 5.9 Copyright 2014 Integrated Environmental Solutions Limited. All rights reserved. No part of the manual

More information

Part L, SBEM & What you need to know to get your building to pass. Mike Andrews DipNDEA, DipDEC, DipOCDEA, DipHI

Part L, SBEM & What you need to know to get your building to pass. Mike Andrews DipNDEA, DipDEC, DipOCDEA, DipHI Part L, SBEM & What you need to know to get your building to pass. Mike Andrews DipNDEA, DipDEC, DipOCDEA, DipHI The Building Regulations Part L2A, SBEM & the National Calculation Methodology what they

More information

non-domestic energy introduction Introduction

non-domestic energy introduction Introduction non-domestic energy introduction 2007 6.0 Introduction 6.0.1 Background 6.0.2 Aims 6.0.3 General guidance 6.0.4 U-values 6.0.5 Thermal conductivity 6.0.6 Insulation envelope where the u-values should be

More information

SAP: The Essential Guide For Dwelling Designers And Architects By Mike Andrews

SAP: The Essential Guide For Dwelling Designers And Architects By Mike Andrews SAP: The Essential Guide For Dwelling Designers And Architects By Mike Andrews The overall aim is to give the dwelling designer a better understanding of what SAP is, how it is used to demonstrate compliance

More information

2012 Consultation on changes to the Building Regulations in England. (with focus on Part L Non Domestic) BSRIA Workshop 14 March 2012

2012 Consultation on changes to the Building Regulations in England. (with focus on Part L Non Domestic) BSRIA Workshop 14 March 2012 2012 Consultation on changes to the Building Regulations in England (with focus on Part L Non Domestic) BSRIA Workshop 14 March 2012 1 2012 Consultation Context The 2012 Building Regulations consultation

More information

FLORIDA BUILDING CODE Energy Code (Residential) 6 TH Edition (2017) Chapter 1 [RE]: Scope and Administration

FLORIDA BUILDING CODE Energy Code (Residential) 6 TH Edition (2017) Chapter 1 [RE]: Scope and Administration FLORIDA BUILDING CODE Energy Code (Residential) 6 TH Edition (2017) Code Changes based on the document provided by DBPR - 2014 and 6th Edition (2017) Florida Building Code Comparison R101.4.1 Chapter 1

More information

Project Description. Projected build start date 02 Aug 2010 Projected date of occupation 03 Dec

Project Description. Projected build start date 02 Aug 2010 Projected date of occupation 03 Dec http://lowenergybuildings.org.uk Project name Hounslow Council Passivhaus Retrofit - and the development of a decision making matrix Project summary The house is a 3-bedroom semi-detached single-family

More information

Building Regulations Part L and F Consultation

Building Regulations Part L and F Consultation Building Regulations Part L and F Consultation CIBSE South West Region 3 September 2009 Ken Bromley, Sustainable Buildings Division Communities and Local Government Building Regulations Parts L and F Consultation

More information

L1A. Conservation of fuel and power ONLINE VERSION APPROVED DOCUMENT. The Building Regulations in new dwellings. In effect from 1 October 2010

L1A. Conservation of fuel and power ONLINE VERSION APPROVED DOCUMENT. The Building Regulations in new dwellings. In effect from 1 October 2010 Building Regulations 2010 Published by NBS, part of RIBA Enterprises Ltd, and available from: RIBA Bookshops Customer Services The Old Post Office St. Nicholas Street, Newcastle Upon Tyne NE1 1RH Telephone

More information

One Size Fits All. Insulation A GUIDE TO BUILDING REGULATIONS / STANDARDS COMPLIANCE FOR NEW DWELLINGS USING STRUCTURAL INSULATED PANELS (SIPS)

One Size Fits All. Insulation A GUIDE TO BUILDING REGULATIONS / STANDARDS COMPLIANCE FOR NEW DWELLINGS USING STRUCTURAL INSULATED PANELS (SIPS) Insulation Second Issue April 2018 One Size Fits All A GUIDE TO BUILDING REGULATIONS / STANDARDS COMPLIANCE FOR NEW DWELLINGS USING STRUCTURAL INSULATED PANELS (SIPS) Low Energy Low Carbon Buildings 2

More information

FOR ADDITIONS and REMODELS Before filling out this application, read Green Building & Green Points Guideline Booklet for more in-depth information.

FOR ADDITIONS and REMODELS Before filling out this application, read Green Building & Green Points Guideline Booklet for more in-depth information. City of Boulder Residential Building Guide Green Building & Green Application Resource Conservation Ordinance 7565 www.bouldergeenpoints.com FOR ADDITIONS and REMODELS Before filling out this application,

More information

Report Date: 26/02/2018. Assessor: Thomas O'Flynn Address: KNOCKAUNFARGARVE BALLYDUFF UPPER CO. WATERFORD P51 A2K0 BER: MPRN:

Report Date: 26/02/2018. Assessor: Thomas O'Flynn Address: KNOCKAUNFARGARVE BALLYDUFF UPPER CO. WATERFORD P51 A2K0 BER: MPRN: Report Date: 26/02/2018 Assessor: Thomas O'Flynn Address: KNOCKAUNFARGARVE BALLYDUFF UPPER CO. WATERFORD P51 A2K0 BER: 110803822 MPRN: 10304953578 About this Advisory Report Energy use in our homes is

More information

Project name Gentoo Retrofit Bid 1 Project summary Refurbishment of 2no. Semi Detached houses using Passivhaus principles

Project name Gentoo Retrofit Bid 1 Project summary Refurbishment of 2no. Semi Detached houses using Passivhaus principles http://lowenergybuildings.org.uk Project name Gentoo Retrofit Bid 1 Project summary Refurbishment of 2no. Semi Detached houses using Passivhaus principles Project Description Projected build start date

More information

> Performance requirements: Part L UK vs Energiesprong vs Passivhaus.

> Performance requirements: Part L UK vs Energiesprong vs Passivhaus. > Performance requirements: Part L UK vs Energiesprong vs Passivhaus. Introduction The purpose of this paper is to highlight and compare the difference in performance requirements between UK Building Regulations

More information

Multi-Occupancy Building Solutions

Multi-Occupancy Building Solutions Multi-Occupancy Building Solutions b Multi-Occupancy building solutions Multi-Occupancy building solutions 2 Saint-Gobain helps improve daily life by creating great places to live. We offer multi-occupancy

More information

Energy Efficiency Criteria

Energy Efficiency Criteria MCS Company Scheme Criteria for: Energy Efficiency Criteria Current Criteria This document shows the Competence Criteria required to be met by a company undertaking the type of work detailed above. MCS

More information

Review of the interpretation and enforcement of Part L1B (2006)

Review of the interpretation and enforcement of Part L1B (2006) Review of the interpretation and enforcement of Part L1B (2006) Executive summary Following the 2006 revision to Part L of the Building Regulations, we were asked to review Local Authority Building Control

More information

Hardin County Planning and Development Commission

Hardin County Planning and Development Commission Location by Climate Zone: Hardin County (per Table N1101.2), and the entire state of Kentucky is located in Climate Zone 4, the HDD is 4000 to 4999. Building Requirements; Building Thermal Envelope The

More information

Domestic Green Deal Advice Training

Domestic Green Deal Advice Training Domestic Green Deal Advice Training Appendix T, PAS 2030, Building Physics, Regulations and Energy Efficient Lighting Appendix T, PAS 2030, and Funding Energy Efficiency Measures Appendix T What Appendix

More information

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK 17065:2012 to provide product conformity certification Unit 4 Pioneer Way Pioneer Business Park Castleford WF10 5QU Contact: Mr Mark Rollins-Mann Tel: +44 (0)845 621111 Fax: +44 (0)845 621112 E-Mail: info@stroma.com

More information

Report Date: 30/05/2018. Assessor: Kevin O'Shaughnessy Address: 584 SOUTH CIRCULAR ROAD DUBLIN 8 BER: MPRN:

Report Date: 30/05/2018. Assessor: Kevin O'Shaughnessy Address: 584 SOUTH CIRCULAR ROAD DUBLIN 8 BER: MPRN: Report Date: 30/05/2018 Assessor: Kevin O'Shaughnessy Address: 584 SOUTH CIRCULAR ROAD DUBLIN 8 BER: 105805345 MPRN: 10000715004 About this Advisory Report Energy use in our homes is responsible for almost

More information

Leaving Certificate Revision Notes. Airtightness. Potential air leakage paths (the numbered points in section 2.1 give a description for

Leaving Certificate Revision Notes. Airtightness. Potential air leakage paths (the numbered points in section 2.1 give a description for Leaving Certificate Revision Notes Airtightness 6 7 8 8 9 10 5 11 5 12 4 3 1 2 13 12 14 Potential air leakage paths (the numbered points in section 2.1 give a description for Airtightness Introduction

More information

National Calculation Methodology (NCM) modelling guide (for buildings other than dwellings in England*)

National Calculation Methodology (NCM) modelling guide (for buildings other than dwellings in England*) National Calculation Methodology (NCM) modelling guide (for buildings other than dwellings in England*) 2013 Edition April 2014 NCM modelling guide for buildings other than dwellings in England Page 2

More information

Part L of Building Regulations 2017-Buildings other than Dwellings. Seán Armstrong, Housing/Building Standards Section, DHPCLG

Part L of Building Regulations 2017-Buildings other than Dwellings. Seán Armstrong, Housing/Building Standards Section, DHPCLG Part L of Building Regulations 2017-Buildings other than Dwellings Seán Armstrong, Housing/Building Standards Section, DHPCLG Outline Implementing the Energy Performance of Buildings Directive and NZEB

More information

Technical Handbook - Non-Domestic

Technical Handbook - Non-Domestic Technical Handbook - Non-Domestic Technical Handbook - Non-Domestic Table of Contents Technical Handbook: Non-Domestic... 1 6. Energy... 2 6.0 Introduction... 2 6.1 Carbon dioxide emissions... 8 6.2 Building

More information

Residential Codes FAQs: 2015 International Energy Conservation Code (IECC) with MA Amendments & MA Stretch Energy Code

Residential Codes FAQs: 2015 International Energy Conservation Code (IECC) with MA Amendments & MA Stretch Energy Code Residential Codes FAQs: 2015 International Energy Conservation Code (IECC) with MA Amendments & MA Stretch Energy Code GENERAL 9 th EDITION Q: Which version of the energy code is in effect? A: On July

More information

National Calculation Methodology (NCM) modelling guide (for buildings other than dwellings in Wales)

National Calculation Methodology (NCM) modelling guide (for buildings other than dwellings in Wales) National Calculation Methodology (NCM) modelling guide (for buildings other than dwellings in Wales) 2014 Edition July 2014 NCM modelling guide for buildings other than dwellings in Wales P a g e 2 Main

More information

Asset Energy Calculator Guidance

Asset Energy Calculator Guidance Asset Energy Calculator Guidance Introduction This section has been produced to give BREEAM In-Use assessors further guidance on the workings of the asset energy calculator so it is clear how any improvements

More information

Energy Assessment Report Clayville Elementary School DRAFT October George Washington Highway, Clayville, RI DRAFT

Energy Assessment Report Clayville Elementary School DRAFT October George Washington Highway, Clayville, RI DRAFT Report Clayville Elementary School October 2016 3 George Washington Highway, Clayville, RI 02815 Clayville Elementary School Summary of Findings On behalf of the School Building Authority at Rhode Island

More information

Project Description. Projected build start date 12 Apr 2010 Projected date of occupation 28 Feb

Project Description. Projected build start date 12 Apr 2010 Projected date of occupation 28 Feb http://lowenergybuildings.org.uk Project name PassivHaus Retrofit - Octavia Housing Project summary PassivHaus retrofit of a three storey solid brick Victorian terraced house in a conservation area. Produce

More information

SCHEME OF BUILDING REGULATION CHARGES AND ASSOCIATED MATTERS FOR South Cambridgeshire District Council

SCHEME OF BUILDING REGULATION CHARGES AND ASSOCIATED MATTERS FOR South Cambridgeshire District Council APPENDIX B4 (B) SCHEME OF BUILDING REGULATION CHARGES AND ASSOCIATED MATTERS FOR South Cambridgeshire District Council Date this Scheme will come into effect: 1st April 2013 Page 1 of 16 Index Page Purpose

More information

A Mixed Use Scheme Large Office Building

A Mixed Use Scheme Large Office Building BUILDING SIMULATION REPORT FOR GUILDFORD BOROUGH COUNCIL A Mixed Use Scheme Large Office Building 5 TH APRIL 2017 Contents 1. Introduction... 2 1.1. The Simulations... 3 1.2. Building Information Model

More information