1 NBS model specification H92 rainscreen cladding: insulation with rendered finish Dryvit Infinty Incorporating: SG H92-Dryvit/120A Wall System Dryvit UK Ltd. Ref: DUK 636

2 DRYVIT INFINITY WALL SYSTEM PRODUCT DESCRIPTION Dryvit UK Ltd. Unit 4 Wren Park Hitchin Road Shefford Bedfordshire SG17 5JD Tel: Fax: ukenquiries@dryvit.com web: Dryvit pressure equalised rainscreen system engineered to prevent water infiltration caused by wind pressure differentials. An exterior insulation and finish system (EIFS) consisting of a moisture barrier, cavity formed by a patented EPS insulation and an outer lamina layer of base coat, mesh and finish. This system also benefits from the design versatility associated with all Dryvit EIFS. SCOPE This specification is based on NBS standard version H92 dated March 2000 and is intended to be used with the standard or intermediate version of this section to produce project specifications. For guidance on the specification of other Dryvit products see specification guides: H20 Rigid Sheet Cladding SG H20-Dryvit/150, Dens -Glass Gold M20 - External Insulation and Finish Systems SG M20-Dryvit/160A, Dryvit ACR 300 TM SG M20-Dryvit/160B, Dryvit ACR 200 TM SG M20-Dryvit/160C, Dryvit ACR 150 TM SG M20-Dryvit/160D, Dryvit ACR 100 TM SG M20-Dryvit/160E, Dryvit ACR 50 TM M21 Acrylic Based Anti-Crack Render Systems SG M21-Dryvit/210A, Outsulation Plus System SG M21-Dryvit/210B, Outsulation System SG M21-Dryvit/210C, Roxsulation System SG M21-Dryvit/210D Residential MD System SG M21-Dryvit/220A, Dryvit Rail System TM M60 - Acrylic-based finish coatings SG M60-Dryvit/110A, Dryvit Finish Coats Dryvit specification clauses are also available in NBS Plus to registered subscribers. H92/1 of 13

3 GUIDANCE ON USE INTRODUCTION Specification Guides These are produced by manufactures to facilitate the specification of their products in NBS. A license must be obtained from NBS Services prior to publication, which requires model specifications to be compatible with the correspondence NBS work section. Specification Guides contain a set of proprietary clauses -edited versions of generic NBS clauses, and new clauses written by the product manufacturer. To specify the product, some or all of these clauses are incorporated in the corresponding NBS work section. It is not possible to produce a project specification by using the clauses from the Specification Guide in isolation-generic clauses must also be used. An unlimited number of Specification Guides can be used to specify products in an NBS work section, e.g. Specification Guides by several manufactures could be used to specify rainscreen cladding in section H92. Specification Guides are based on the corresponding NBS Standard Version, but can generally be used in conjunction with the Standard or Intermediate Version. Reference numbers Each NBS specification guide is identified by a unique reference number, e.g. SG H92-Dryvit/120A (Specification Guide H92 Rainscreen System/ Dryvit/120A Infinity Wall System reference). Clause numbers Edited versions of NBS clauses are given a new clause number with a single character suffix, e.g. clause H92/120 might become H92/120A or H92/121A. Clauses written by the product manufacturer are allocated a new clause number - these also include a single character suffix, e.g. H92/120A. Model specifications index This is located in the first ring binder, and in the NBS for Windows and Specification Manager manuals. It comprises a Model Specifications Index which lists the model specifications available in each work section, and a List of Manufactures which lists the model specifications produced by each company. Specification Guides need to be revised when the manufacturer makes changes to the product of product range. They may also need to be revised following an update of the NBS work section on which they are based. Appropriate details will be provided in the Model Specifications Index, which should be checked to ensure a current Specification Guide is being used. The index is revised twice a year to coincide with NBS updates, but if in doubt about the status of a Specification Guide, check with the manufacturer using the telephone or fax numbers shown on the first page of this document. SPECIFICATION PRODUCTION Using a computer These instructions will be appropriate if you are producing a product specification on screen using Specification Manager or a word processing package - for the latter it is necessary to have access to NBS text files through membership of the NBS disc service or NBS for Windows. If you also have access to a text file containing the Specification Guide, copy and paste the clauses you require into the appropriate NBS text file(s). Otherwise, edit the text file(s) in accordance with the alterations shown in the Specifications Guide - the following conventions are used: Proprietary text is shown in bold italics. Irrelevant or inappropriate NBS text is shown struck out. The proprietary text added to the NBS computer file should be formatted in a plain font style, not in bold italics. The latter is only reproduced on paper copy f or the identification purposes explained above. Complete the specification in the normal manner, with the help of clause guidance from the NBS section and the Specification Guide. Ensure that clause numbers are not duplicated - especially where they have been incorporated from more than one Specification Guide. Using mark-up copy You need an NBS mark-up copy of the relevant work section (or a print out from your computer), and a photocopy of the Specification Guide to use as supplementary mark-up copy. Use these side by side and complete the specification in the usual manner, selecting NBS and Specification Guide clauses as appropriate. As work proceeds, record the selection of Specification Guide clauses in the margin of the NBS mark-up copy, e.g. Ins ert 150A [ refer to separate page] between NBS clauses 150 and 160. Ensure that clause numbers are not duplicated - especially where they have been incorporated from more than one Specification Guide. Inform the person who is going to word process the specification about the text formatting conventions described above (see Specification production using a computer ). They should also understand that mark-up copy which includes a company name or logo in the header originates from a Specification Guide - the clauses on these pages will not be found in the NBS text file and will need to be copied across or keyed in as described above. The specification is completed in the normal manner by editing the NBS text file in accordance with the hand-written notes on the mark-up copy. H92/2 of 13

4 GUIDANCE NOTES MODEL SPECIFICATION CLAUSES H92 DRYVIT RAINSCREEN SYSTEM To be read with Preliminaries/General conditions. TYPE(S) OF RAINSCREEN CLADDING Dryvit UK Ltd, Unit 4 Wren Park, Hitchin Road, Shefford, Beds. SG17 5JD Telephone: ; Facsimile: ukenquiries@dryvit.com Dryvit has been part of the External Insulation and Finish Systems (EIFS) industry for over 30 years with a world-wide portfolio of projects of various sizes. An RPM Company with ISO All Dryvit EIFS offer unlimited design freedom with high performance properties. The Dryvit range of systems are specified to meet all the functional and aesthetic needs of a building s external envelope, allowing the designer to select from a large variety of textured finishes and colours. We suggest the designer contact Dryvit in the first instance to discuss specific needs, so that the appropriate EIFS can be recommended. You can contact us directly by telephone, fax, and also visit our web site as detailed above. Dryvit External Wall Insulation and Finish Systems (EIFS) are available for a variety of applications suitable for commercial and residential projects. The Dryvit EIFS holds BBA Agrément Certificate No. 98/3548. A. Commercial Systems are suitable for projects including institutional, offices, healthcare, retail, hotel, industrial, public buildings and multi-storeyed residential buildings etc. for options of on-site or prefabricated panelled applications, of any size. 1. Dryvit Infinity System: A pressure -equalised and moisture drained engineered rainscreen EIFS with thermal properties. It incorporates grade SD type FRA expanded polystyrene (EPS) insulation for thermal performance. (See Clause H92/120A). Other non-rainscreen (EIFS) systems are as below: See Work Section M21 1. Dryvit Outsulation Plus System: A highperformance EIFS with moisture drainage incorporating an Air & Moisture Protective Barrier and grade SD type FRA expanded polystyrene (EPS) insulation for thermal performance. (See Section M21.210A). 2. Dryvit Outsulation System: A polymer-based barrier EIFS incorporating grade SD type FRA expanded polystyrene (EPS) insulation for thermal rating. Agrément Certificate No. H92/3 of 13

5 thermal rating. Agrément Certificate No. 98/3548 Detail Sheet 2. (See Section M21.210B). 3. Dryvit Roxsulation System: A polymer-based barrier EIFS incorporating mineral wool (slab or lamella) insulation for thermal rating. Agrément Certificate No. 98/3548 Detail Sheet 3. (See Section M21.210C). 4. Dryvit Rail System TM : A mechanically fastened rail EIFS to be used over walls with damaged or brittle substrates or irregular surfaces on retrofit or new build construction. It incorporates grade SD type FRA expanded polystyrene (EPS) insulation for thermal performance. (See Section M21.210D). B. Residential Systems are suitable for residential projects for on-site or pre-fabricated applications. They are: 1. Dryvit Residential MD System : A residential EIFS with moisture drainage, incorporating grade SD type FRA expanded polystyrene (EPS) insulation for thermal performance. The system has a specially designed fibrous mat - that is installed between the secondary weather barrier and the insulation board - to create a drainage plane. The system is mechanically fastened over a weather barrier to plywood. This system can also be applied in commercial use, contact Dryvit for advice. (See Section M21.210E). 2. Dryvit Outsulation System: A polymer-based barrier EIFS incorporating grade SD type FRA expanded polystyrene (EPS) insulation for thermal rating. Agrément Certificate No. 98/3548 Detail Sheet 2. (See Section M21.210B). 3. Dryvit Roxsulation System: A polymer-based barrier EIFS incorporating mineral wool (slab or lamella) insulation for thermal rating. Agrément Certificate No. 98/3548 Detail Sheet 3. (See Section M21.210C). 120A RAINSCREEN CLADDING: (SG/H92-Dryvit/120A) - Location: [ Insert, e.g. External walls, from First to Tenth Floor Levels, facing south and east/all elevations (as applicable) ]. - Drawing reference(s): [ insert, e.g. Drawing numbers or See Drawing Schedule ]. - Primary support structure: [ Insert details of fabric/structure to which the EIFS system will be fixed, e.g. reinforced concrete structure, masonry structural/lightweight steel frame. If a lightweight steel frame is used then we would expect a sheathing board to be applied as the substrate to which the rainscreen system would be fixed. For Dryvit sheathing board see Work Section H20/150A. The primary support structure may be by others or by this Works Contractor, and should comply with the requirements of BS 6399:Part 1 and BS A RAINSCREEN CLADDING: - Location: [ ]. - Drawing reference(s): [ ]. - Primary support structure: [ e.g. Lightweight metal stud framework by others, to receive sheathing board (see also Work Section H20/150A) to Dryvit approval ]. - Rainscreen Cladding System: Pressure equalised. - Manufacturer: Dryvit UK Ltd., Unit 4 Wren park, Hitchin Road, Shefford, Beds. SG17 5JD Telephone: ; Facsimile: ; ukenquiries@dryvit.com ]. - System reference: Dryvit Infinity Wall System. [ General Dryvit EIFS Agrément Certificate No.:98/3548 Detail Sheet 1 ] - Material: General build up consists of : H92/4 of 13

6 requirements of BS 6399:Part 1 and BS Please note that a secondary support structure is not required for the Infinity system ]. - Rainscreen Cladding System: [ Pressure equalised ]. Unlike traditional rainscreen systems the infinity system does not require a continuous air gap between the primary structure and the system. Pressure equalisation is achieved be venting and compartmentalisation of the insulation boards to meet the Engineer/Architect requirements. - Manufacturer: Dryvit UK Ltd, Unit 4 Wren Park, Hitchin Road, Shefford, Beds. SG17 5JD Telephone: ; Facsimile: ; ukenquiries@dryvit.com] - System reference: [ Dryvit Infinity Wall System ]. - Material: Typical system build up: 1. Substrate (structural framing). 2. Sheathing (See Work Section H20/150A). 3. Dryshield ABA air barrier and adhesive. 4. Dryvit Grid Tape 5. I.S Insulation Board (EPS) 6. I.S Insulation Closure Board (EPS) 7. Dryvit Vent Assembly 8. Dryvit Track & Vent Track 9. I.S Base Coat, with embedded I.S Reinforcing Mesh 10. Infinitex or speciality finish coat (with sealants if required). - Thickness: [ ]mm. Refer to thermal insulation requirements below. - Finish/Colour:[ A. Colour: See Dryvit standard colour range or as instructed by the CA. Consult Dryvit Uk for colour samples. B. Texture: See relevant finish textures outlined below or customised finish agreed with the CA in relation to sample panel ]. Dryvit Infinitex or speciality finishes are available in a standard colour range and can alternatively be providing protective and decorative properties to suit. The finishes offer low maintenance advantages with DPR TM (Dirt Pickup Resistance) and PMR TM (Proven Mildew Resistance) technology. The various texture and finish types are: 1. Infinitex elastomeric 100% acrylic finish with quartz aggregate, mildew and dirt resistant technology. Colorprime primer. a. Infinitex QP coarse texture. b. Infinitex SP rough pebble texture. c. Infinitex SPF fine pebble-like texture. d. Infinitex ADB : smooth texture. 2. Standard Coatings: a. Demandit (Weathercoat TM Smooth) b. Revyvit (Weathercoat Textured) 3. Speciality Finishes: a. Ameristone b. Stone Mist c. Metallics d. Custom Brick /Stone e. Interior Finishes 1. Dryshield ABA air barrier on substrate. 2. I.S Insulation adhesively fixed with Dryshield ABA to substrate. 3. I.S Base Coat & Mesh 4. Infinitex or speciality finish as detailed below - Thickness: [ ]mm - Finish/colour: [ Infinitex or Speciality finish A. Colour: From standard range or customised. B. Texture: Selected finish type ]. - Other System requirements: All the necessary ancillary products required to achieve pressure equalisation must be allowed for as per Engineer/Architect requi rements and applied in accordance with Dryvit UK Ltd. current recommendations. Detail mesh should be used to back wrap the system at all termination details of the system. Dryvit starter track is recommended at ground floor. Please also refer to clauses H92: 320A, 330A, 350A, 381A, 910A. - Fixing system: [ Dryshield ABA adhesive ]. - Joint type: See Clause H92:380A & 770A. - Joint width: [ Terminations 19mm wide between Infinity system and adjoining materials. mm at expansion joints ]. - Backing wall: [ ]. - Breather membrane: Dryvit Dryshield ABA. - Thermal insulation: [ W/m 2 K. Relative to the thickness of the Infinity System detailed above and including the make up of the primary support structure ]. - Accessories: [ 1. All metal work by others including coping at parapet, flashing at base etc. 2. As indicated on the Design Drawings ]. - Attachments: [ e.g. 1. Feature bands around window openings including arc and pier moulding. 2. Projecting plinth at base of EIFS system. 3. External corner quoins ]. - Incorporated components: [ ]. - Other requirements: [ ]. - Co-ordination: [ the work with interfacing building elements 1. Metal coping by others. 2. Windows by others. 3. Doors by others. 4. Roof flashings by others. 5. Signage by others ]. H92/5 of 13

7 4. Customisation of finishes to the CA s requirement can be obtained. Contact Dryvit to discuss various possibilities prior to specifying non-standard options] - Other system requirements: All the necessary ancillary products required to achieve pressure equalisation must be allowed for as per engineer/architect requirements and applied in accordance with Dryvit UK Ltd. current recommendations. Detail mesh should be used to back wrap the system at all termination details of the system. Dryvit starter track is recommended at ground floor. Please also refer to clauses H92: 320A, 330A, 350A, 381A, 910A. - Fixing system: [ Dryshield ABA adhesive ]. The I.S Insulation boards are normally adhesively fixed. The only exception to this would be if mechanical fixings were required to secure the system to an existing substrate. - Joint type: See Clause H92:380A & 770A. - Joint width: [ 1.Terminations: system shall be held back from adjoining materials by minimum 19mm wide or as instructed by the Architect/CA with the approval of Dryvit UK Ltd. 2. Expansion joints in system width dependent on expected movement to Architect/CA requirements ]. - Air gap: Not applicable to the Infinity System as there is not a continuous air gap between the system and the primary support structure. Pressure equalisation is achieved by the vented compartmentalisation of the system as designed by the Engineer/Architect with assistance from Dryvit UK Ltd. Not included in clause. See H92:330A. - Secondary support/framing system: Not applicable with the Infinity system therefore not included in clause H92:120A. - Backing wall: [ Insert substrate type: refer to primary structure details above. i.e. sheathing board by Dryvit See also H20:150 ]. - Breather membrane: Dryvit Dryshield ABA - Thermal insulation: [ Insert overall wall performance i.e W/m 2 K. Relative to the thickness of the Infinity System detailed above and including the make up of the primary support structure ]. Determined by the thermal insulation value required. The I.S EPS insulation incorporated within the system will contribute to the performance of the wall and Dryvit UK Ltd. can be consulted to assist in this calculation. - Accessories: [ 1. All metal work by others including coping at parapet, flashing at base etc. 2. As indicated on the Design Drawings ]. - Attachments: Describe here any Dryvit architectural prefabricated standard and/or bespoke mouldings, feature/surround bands around windows/door/louvre openings e.g. arc, ledges, moulding, billet, pier, architrave, fillet or chamfer, plinth, quoins. - Incorporated components: Describe here any major standard items you wish to include in the Infinity system. e.g. if you are pre-fabricating panels this may describe window units that should be incorporated. H92/6 of 13

8 should be incorporated. - Other requirements: Use this item to draw attention to any unusual requirements. - Co-ordination: [ Co-ordinate the Work with interfacing building elements 1. Electrical fittings by others. 2. Mechanical Services by others. 3. Hydraulic Services by others. 4. Access equipment bracket penetrations by others. 5. Metal coping by others. 6. Windows by others. 7. Doors by others. 8. Roof flashings by others. 9. Roof eaves boards by others. 10. Signage by others ]. GENERAL REQUIREMENTS/ PREPARATORY WORK 225A INFORMATION TO BE PROVIDED WITH TENDER: With the tender, the contractor provides descriptive literature for each product, which he proposes to use. The CA uses this information to verify compliance with the specification. 225A INFORMATION TO BE PROVIDED WITH TENDER: [ Manufacturer s current product data describing products that will be used on this project ]. 230A INFORMATION TO BE PROVIDED AFTER ACCEPTANCE OF TENDER: For prefabricated panel construction, the panel fabricator will need to produce shop drawings indicating panel and framing member sizes, spacing, sheathing and attachment, panel to framing attachment, panel layout, and any other information requested by the CA. The CA will review and approve these drawings prior to panel fabrication commences. 230A INFORMATION TO BE PROVIDED AFTER ACCEPTANCE OF TENDER: [ For panellised construction, the panel fabricator to supply complete drawings showing wall layout, connections, details, expansion joints, and installation sequence for approval by the Architect/CA ]. 240A PRODUCT SAMPLES: Before commencing detailed design provide the CA with identified samples of: [ insert list of product samples and sizes following agreement with Dryvit. e.g. - The contractor to submit 2 samples of each finish, texture and colour to be used on the project. Samples to be of sufficient size to accurately represent each colour and texture being utilised on the project ]. Obtain approval of [ the product, finish, colour and] appearance before proceeding. - These samples are provided for approval of the product, finish and colour prior to proceeding. 270 MOCK-UP: At an agreed stage during detailed design work construct in an approved location a mock-up of: Purpose(s) of mock-up:. Arrange f or inspection to be carried out jointly with the CA. Obtain approval of appearance before proceeding. Retain mock-up in undisturbed condition until completion of rainscreen cladding installation. - The mock up is larger sized than samples and may be part of the actual work on the building. It is intended to provide a standard of quality for 240A PRODUCT SAMPLES: Before commencing detailed design provide the CA with identified samples of: - [ The contractor to submit 2 samples of each finish, texture and colour to be used on the project. Samples to be of sufficient size to accurately represent each colour and texture being utilised on the project ]. - Obtain approval of [ the product, finish, colour and ] appearance before proceeding. 270 MOCK-UP: At an agreed stage during detailed design work construct in an approved location a mock-up of: Purpose(s) of mock-up:. Arrange for inspection to be carried out jointly with the CA. Obtain approval of appearance before proceeding. Retain mock-up in undisturbed condition until completion of rainscreen cladding installation. - [ The Contractor to provide the CA a mock up for approval. The mock up to be of sufficient size to accurately represent each colour and texture to H92/7 of 13

9 It is intended to provide a standard of quality for the work and may includes other wall components such as windows, doors, features, etc. to indicated method of treatment. accurately represent each colour and texture to be utilised on the project. The mock up to be prepared with the same products, tools, equipment and techniques required for the actual applications. The approved mock up to be available and maintained at the jobsite or at an agreed location as instructed by the CA ]. DESIGN/PERFORMANCE REQUIREMENTS 310A GENERALLY: - The tests to be carried out in order to verify the system s performance in accordance with recognised and equivalent national or international test standards. - The purpose of the tests will be to verify air leakage, pressure equalisation and durability performance of the products. 311 DURABILITY TEST: - The following tests to be carried out in order to verify the system s performance in accordance with recognised test standards. Tests will verify air leakage, pressure equalisation and durability performance of the products. - The Dryvit Infinity rainscreen system to have been tested for durability as follows: a. Air Leakage: ASTM E283; less than 0.3 l/min/m 2. b. Dynamic Pressure Equalisation: National Research Council of 750 Pa, K=.99, φ=3.7. c. Water Penetration: ASTM E331; no water penetration. d. Water Resistance: ASTM D2247; passed. e. Moisture Drainage Efficiency: ASTM E331 (Modified); Minimum 95% Efficiency. f. Absorption/Freeze/Thaw: ASTM C67; 60 cycles. g. Absorption/Freeze/Thaw: ICBO Procedure; 10 cycles. h. Accelerated Weathering: ASTM G23; 2000 hrs ]. 312 STRUCTURAL PERFORMANCE TEST: Structural performance testing in accordance with recognised test standards to verify performance regarding wind load resistance, impact resistance and tensile bond tests to the specified substrate. - The Dryvit Infinity rainscreen system have been tested, passed to comply for structural performance as follows: a. Transverse Load Test: ASTM E330; negative 4.8 kpa minimum. b. Impact Resistance: EIMA ; I. S. Reinforcing Mesh, 3-6 J; Panzer 20 Mesh and I. S. Reinforcing Mesh, >39 J. c. Tensile Bond: ASTM C297; passed. d. Tensile Bond: ICBO Procedure; passed. 313 FIRE PERFORMANCE TEST: - Test to be performed to verify the system s fire performance in accordance with standard test methods. - The Infinity System to have been tested for fire performance as follows: 310A GENERALLY: - [ The tests to be carried out in order to verify the system s performance in accordance with recognised and equivalent national or international test standards. - The purpose of the tests will be to verify air leakage, pressure equalisation and durability performance of the products ]. 311 [ DURABILITY TEST: The rainscreen system to have been tested for durability as follows: a. Air Leakage: ASTM E283; less than 0.3 l/min/m 2. b. Dynamic Pressure Equalisation: National Research Council of 750 Pa, K=.99, f=3.7. c. Water Penetration: ASTM E331; no water penetration. d. Water Resistance: ASTM D2247. e. Moisture Drainage Efficiency: ASTM E331 (Modified); Minimum 95% Efficiency. f. Absorption/Freeze/Thaw: ASTM C67; 60 cycles. g. Absorption/Freeze/Thaw: ICBO Procedure; 10 cycles. h. Accelerated Weathering: ASTM G23; 2000 hrs ]. 312 [ STRUCTURAL PERFORMANCE TEST: The Infinity rainscreen system to have been tested for structural performance as follows: a. Transverse Load Test: ASTM E330; negative 4.8 kpa minimum. b. Impact Resistance: EIMA ; I. S. Reinforcing Mesh, 3-6 J ; Panzer 20 Mesh and I. S. Reinforcing Mesh, >39 J c. Tensile Bond: ASTM C297. d. Tensile Bond: ICBO Procedure ]. 313 [ FIRE PERFORMANCE TEST: - Test to be performed to verify the system s fire performance in accordance with standard test methods. - The Infinity System to have been tested for fire performance as follows: H92/8 of 13

10 a. Multi Story Test: UBC 26-9 ISMA Multi Story Fire Test. b. Full Scale Test: ASTM E108 (Modified). c. Rated Wall Test: ASTM E119 (one-hour). d. BOCA Radiant Heat Ignitability Test. e. Flame Spread - Insulation Board: ASTM E84; Flame Spread <25, Smoke Developed <450. f. Flame Spread - Infinitex Finish: ASTM E84; Flame Spread 10, Smoke Devel oped 5. g. Flame Spread - Dryshield ABA: ASTM E84; Flame Spread 5, Smoke Developed 0. h. Flame Spread - I. S. Base: STM E84; Flame Spread 3, Smoke Developed 0. i. Flame Spread - Stone Mist: ASTM E84; Flame Spread 10, Smoke Developed A HORIZONTAL ZONING OF WIND PRESSURE: Reference heights are as follows: [ Insert e.g. See the Design Drawings or at maximum 9.1m measured vertically ]. - Each wall façade to be separated into zones of approximate equal wind pressure - Each area will be separated form adjacent areas using closure blocks to prevent differential pressure from travelling to adjacent compartments. ASCE 7-95 provides guidelines for locating wind zones on a building façade and can be used as a basis for design. Wind tunnel test results also are acceptable. The maximum compartment heights are based on rational method to minimise delay in pressure equalisation of the cavity. a. Multi Story Test: UBC 26-9 ISMA Multi Story Fire Test. b. Full Scale Test: ASTM E108 (Modified). c. Rated Wall Test: ASTM E119 (onehour). d. BOCA Radiant Heat Ignitability Test. e. Flame Spread - Insulation Board: ASTM E84; Flame Spread <25, Smoke Developed <450. f. Flame Spread - Infinitex Finish: ASTM E84; Flame Spread 10, Smoke Developed 5. g. Flame Spread - Dryshield ABA: ASTM E84; Flame Spread 5, Smoke Developed 0. h. Flame Spread - I. S. Base: STM E84; Flame Spread 3, Smoke Developed 0. i. Flame Spread - Stone Mist: ASTM E84; Flame Spread 10, Smoke Developed 30 ]. 320A HORIZONTAL ZONING OF WIND PRESSURE: Reference heights are as follows: - [ See the Design Drawings or at maxi mum 9.1m measured vertically. - The CA to divide each building face into compartments, which approximate areas of equal wind pressures. - Compartment boundaries to coincide with the location zones as define by ASCE 7-95, wind tunnel studies or other rational method. - Elevations to be divided with a horizontal separation at intervals not to exceed 9.1m measured vertically ]. 330A INTEGRITY OF VENTILATED RAINSCREEN: 330A INTEGRITY OF VENTILATED RAINSCREEN: - VENTING REQUIREMENTS RAINSCREEN CLAD WALLS The minimum vent area is required to ensure fast pressure equalisation of the interlocking cavity behind the EPS insulation. The horizontal spacing between vents will also affect the rate of pressure equalisation. A minimum vent area of cm 2 is required for every 28 m 2 of wall area. Spacing between vents not to exceed 6m. - IMPACT LOADING: The finished wall(s) must have the impact resistance(s) as recommended by BS 8200 or BRE information paper No. IP 19/81 or as specified by the Structural engineer or as recommended by the manufacturer from standard/combination options: Dryvit mesh options: Standard TM 4 Nm Standard Plus TM 6 Nm Intermediate 12 Nm Panzer 15/Standard TM 18 Nm Panzer 20/Standard TM 40 Nm Panzer 15/Standard Plus TM 20 Nm Panzer 20/Standard Plus TM 42 Nm - [ VENTING REQUIREMENTS RAINSCREEN CLAD WALLS, A minimum vent area of cm 2 is required for every 28 m 2 of wall area. Spacing between vents not to exceed 6m ]. - [ IMPACT LOADING: The finished wall(s) must be designed to withstand the following impact resistance(s): [ Ground floor: 42 Nm, using Dryvit Panzer 20 + Standard Plus Mesh or as advised by the manufacture. First to fifth floors: 6Nm, using Standard Plus Mesh or advised by the manufacture] Note: Dryvit systems can be designed to achieve desired impact loading by combining the H92/9 of 13

11 achieve desired impact loading by combining the above options, e.g. to achieve 42Nm impact loading insert,..42 Nm, using Panzer 20 and Standard Plus Dryvit mesh or as advised by the manufacturer. 350A DEFLECTION UNDER WIND LOAD: - The underlying wall assembly is limited in deflection to minimise transfer of stresses to the exterior coatings. A structure that is to flexible under wind load conditions, will stres s the exterior coatings and may result in cracks. - At positive and negative applications of the design wind pressure the maximum normal deflection for the listed components must not exceed [ insert e.g. 1/240 of the span between supports ]. 350A DEFLECTION UNDER WIND LOAD: At positive and negative applications of the design wind pressure the maximum normal deflection for the listed components must not exceed: [ 1/240 of the span between supports ]. 380A CONSTRUCTION/MOVEMENT JOINTS: 380A CONSTRUCTION/MOVEMENT JOINTS: The construction or expansion joints must align with the movement joints (note: Expansion/Movement joints are the responsibility of the Designer/CA and to be indicated on the Design Drawings, to be installed by others). Movement joints should be incorporated where: 1. Expansion joints occur in the substrate system. 2. Building expansion joints occur. 3. Continuous elevations at intervals not exceeding 23m. measured horizontally. 4. [ Prefabricated panels abut one another. 5. System meets floor lines in timber frame construction. 6. The rainscreen cladding butts dissimilar materials. 7. The substrate material changes. 8. Significant structural movement occurs such as changes in roofline, building shapes or structural system. 9. Other special locations ]. Form joints accurately to detail and in locations shown on the [ Design] Drawings. If modifications to any joint location or design are necessary on site, agree revisions with CA before proceeding. Movement joints should be incorporated where 1. Expansion joints occur in the substrate system, location as indicated on the Design Drawings. 2. Building expansion joints occur. 3. Continuous elevations exceed 23m. [ 4. Other special locations, insert as applicable ]. 381A SLOPE LIMITATIONS: - The system is not intended to be used in areas that may be classified as roofs and will need to support structural loads. Also long or shallow slopes will weather faster and require more frequent maintenance and should be avoided. - The slopes on ledges or inclined surfaces must not be less than 1:2 or 28 degrees, and the length must not exceed 305 mm. 381A [ SLOPE LIMITATIONS: The slopes on ledges or inclined surfaces must not be less than 1:2 or nominally 28 degrees, and the length must not exceed 305mm ]. 450A VAPOUR CONTROL LAYER: - Determine the interstitial condensation risk of the rainscreen wall using the method described in BS 5250 Appendix D. Designer to provide all necessary information to produce calculations - [ The designer to determine the interstitial condensation risk of the wall assembly and provide a suitable vapour control layer as required ]. 450A VAPOUR CONTROL LAYER: - Determine the interstitial condensation risk of the rainscreen wall using the method described in BS 5250 Appendix D. Designer to provide all necessary information to produce calculations - [ The designer to determine the interstitial condensation risk of the wall assembly and provide a suitable vapour control layer as required ]. H92/10 of 13

12 490A FIRE BARRIERS: 490A FIRE BARRIERS: - - [ Lamella or Slab] mineral wool non-combustible material to BS 476:Part 4. - Size: Minimum 100 mm x total thickness of external wall insulation. 1. [ Install barriers at every floor level from third storey or as indicated on Design Drawings ] 2. [ Barriers to be [ adhesively or mechanically] fixed with Dryvit Detail Mesh applied over barrier to lap adjacent EPS on either side a minimum of 50mm to manufacturer recommendations. Consult Dryvit UK Ltd with guidance on how to prepare face of slab fixed to substrate ]. - [ Lamella ] mineral wool non-combustible material to BS 476:Part 4. - Size: Minimum 100 mm x total thickness of external wall insulation. 1. [ Install barriers at every floor level from third storey or as indicated on Design Drawings ] 2. [ Barriers to be [ e.g. adhesively ] fixed with Dryvit Detail Mesh applied over barrier to lap adjacent EPS on either side a minimum of 50mm to manufacturer recommendations. Consult Dryvit UK Ltd with guidance on how to prepare face of slab fixed to substrate ]. PRODUCTS 770A SEALANT JOINTS: Sealants are used to weatherproof transitions to other materials within the wall assembly and should be tested for compatibility in accordance with standard methods. - Location(s): [ Insert e.g. Seal around windows, doors where applicable and insert at building movement joints ]. 1. Sealant: [ Insert e.g. Dryvit 1 TM Low modulus sealant with baking filler ]. 2. Colour: [ Insert, e.g. White or to be selected from the standard range. Also see Work Section Z22 ]. 3. [ Form in accordance with Work Section Z22 and system manufacturer's recommendations using any necessary joint filler, backing strips, etc ]. 4. The sealant to be tested as follows: a. Adhesion In Peel: ASTM C794; 89 kg/m. minimum. b. Tensile 50% Elongation: ASTM C1135 (Modified); dry 138 kpa, 1 and 7 day immersion 104 kpa, frozen 138 kpa. c. Modulus of 50% Elongation: ASTM C1135 (Modified); 241 kpa at -40 C, 138 kpa at 82 C. 770A SEALANT JOINTS: - Location(s): [ Seal around windows, doors where applicable and insert at building movement joints ]. 1. Sealant: [ Dryvit 1 TM low modulus silicone sealant or equal ]. 2. Colour: [ White ] 3. [ Form in accordance with Work Section Z22 and system manufacturer 's recommendations using any necessary joint filler, backing strips, etc ]. FABRICATION AND INSTALLATION 910A INSTALLATION 910A [ INSTALLATION GENERALLY: - GENERAL REQUIREMENTS 1. The Dens Glass Gold sheathing to be installed in accordance with Georgia- Pacific Bulletin #94-02 [ the manufacturer s instructions as supplied by Dryvit UK Ltd]; Dens Glass Gold Application and Installation Procedures for Dryvit Infinity System. 2. The Infinity System to be installed in accordance with the current Dryvit Infinity Installation Ins tructions DS145, and Infinity Installation Details DS Infinity base coat surfaces in contact with sealant to be coated with Demandit or Colorprime. 1. The sheathing to be installed in accordance with the manufacturer s instructions, for application and installation procedures for the System. 2. The System to be installed in accordance with the current Installation Instructions and Details. 3. Base coat surfaces in contact with sealant to be coated with [ Dryvit Demandit or Colorprime ]. 4. Sealant must not be applied directly to textured finishes or uncoated base coat. 5. The base coat to be applied in accordance with the current H92/11 of 13

13 Colorprime. 4. Sealant must not to be applied directly to textured finishes or uncoated base coat. 5. The base coat to be applied in accordance with the current Dryvit Infinity Installation Instructions (DS145).Sealants to be installed in accordance with Dow Corning Procedure for the Installation of Dow Corning Silicone Building Sealants With Dryvit Infinity Systems. - APPLICATION: Dryvit Applicator Training Programme. Dryvit operates a training programme for Specialist Installers of their manufactured EIFS systems. The levels of applicators to be employed to undertake the work depend upon the type of contract. Contact Dryvit for advice. There are three levels of training: Level 1: Applicator must attend a combined practical and theory training course to demonstrate they are conversant in the use of the Dryvit materials, associated tools and basic details skills. Level 2: Advanced Applicator level card holder is continuation of level 1 applicator but with advanced detail skills and a measure of the continued practical experience. Level 3: Supervisor level cardholder is a senior applicator and must provide references of Dryvit system applications to demonstrate their practical experience. Must complete a multiple choice paper on Dryvit materials and their applications and must be capable of training the applicators under their supervision. accordance with the current Installation Instructions. 6. Sealants to be installed in accordance with sealant manufacturer s procedure recommended for the System.- APPLICATION: Installation to be carried out only by a Specialist Installer using operatives participating in the Dryvit Applicator Traini ng Programme. [ One operative on site to be trained to level 3 - Supervisor level, as agreed with the CA ]. 950A ACCEPTANCE OF BACKGROUNDS: Dryvit/Specialist Installer must be consulted on obtaining the acceptance of the background, especially when a guarantee on materials supplied by Dryvit and the Installers guarantee on workmanship and installation are required. [ Insert e.g. Dryvit/Specialist Installer must be consulted on obtaining the acceptance of the background ]. 950A ACCEPTANCE OF BACKGROUNDS: Before preparation or application of coatings ensure that: - Backgrounds are secure, adequately true and level to achieve specified tolerances, free from contamination and loose areas, reasonably dry and in a suitable condition to receive specified coatings. - All cutting, chasing, fixing of concealed conduits, service outlets and the like, and making good of the background, is completed. - [ Dryvit/Specialist Installer must be consulted on obtaining the acceptance of the background ]. H92/12 of 13

14 The Specification clauses and guidance notes in this document (the Information) are based on those in the NBS Subscription Service and shall be subject to the provisions of the Copyright Notice, Conditions of Sale and Disclaimer upon which that service is supplied, whether made available as part of that Service or otherwise, and references in those provisions to NBS shall be deemed also to include a reference to Dryvit (UK) Ltd in accordance with its disclaimer applicable to such Information. The Information, to the extent that it relates exclusively to products manufactured, marketed or supplied by Dryvit (UK) Ltd, is published under the sole authority of Dryvit (UK) Ltd. The Information is not intended to be exhaustive and is given in good faith to assist in defining specifications for the installation of Dryvit systems. All users and others must verify the Information and ensure its suitability for the particular applications for which it is required. Dryvit (UK) Ltd and NBS Ltd have no control over site conditions or installation procedures and accordingly neither of them can accept any liability for loss or damage which may arise from the application or the Information and they expressly exclude liability for such loss or damage to the extent permitted by the law. Dryvit UK Ltd, Unit 4 Wren Park Hitchin Road Shefford Bedfordshire SG17 5JD Tel: Fax: ukenquiries@dryvit.com web: H92/13 of 13

Incorporating: SG M21-Dryvit/210B. Dryvit UK Ltd. Ref: DUK 618 ISO 9001 Certified

Incorporating: SG M21-Dryvit/210B.   Dryvit UK Ltd. Ref: DUK 618 ISO 9001 Certified NBS model specification M21 insulation with rendered finish Dryvit Outsulation System Incorporating: SG M21-Dryvit/210B www.dryvit.co.uk DRYVIT OUTSULATION PRODUCT DESCRIPTION Dryvit UK Ltd. Unit 4 Wren

More information

Incorporating: SG M21-Dryvit/210A. Dryvit UK Ltd. Ref: DUK 637 ISO 9001 Certified

Incorporating: SG M21-Dryvit/210A.   Dryvit UK Ltd. Ref: DUK 637 ISO 9001 Certified NBS model specification M21 insulation with rendered finish Dryvit Outsulation Plus System Incorporating: SG M21-Dryvit/210A www.dryvit.co.uk DRYVIT OUTSULATION PLUS PRODUCT DESCRIPTION Dryvit UK Ltd.

More information

Bill of Quantities Guidance Document

Bill of Quantities Guidance Document Bill of Quantities Guidance Document Dryvit UK Ltd. Unit 4 Wren Park Hitchin Road Shefford Bedfordshire SG17 5JD Tel: 01462 819555 Fax: 01462 819556 email: ukenquiries@dryvit.com www.dryvit.co.uk ISO 9001

More information

STRATUM GUARD I AND II An Exterior Insulation and Finish System with Drainage DSC106C. Stratum Guard I and II System Installation Details

STRATUM GUARD I AND II An Exterior Insulation and Finish System with Drainage DSC106C. Stratum Guard I and II System Installation Details STRATUM GUARD I AND II An Exterior Insulation and Finish System with Drainage DSC106C Stratum Guard I and II System Installation Details Stratum Guard I and II DETAIL Table of Contents NOTE SG.0.0.01 SG.0.0.02

More information

Third Party Inspection Guidelines For Inspectors As Part of the dryvitcare EIFS Repair/Restoration

Third Party Inspection Guidelines For Inspectors As Part of the dryvitcare EIFS Repair/Restoration Third Party Inspection Guidelines For Inspectors As Part of the dryvitcare EIFS Repair/Restoration DS497 SECTION ONE A. Objective The objective of this guide is to provide owners and general contractors/construction

More information

CI/SfB (41) x M2 June 2005 EPS

CI/SfB (41) x M2 June 2005 EPS CI/SfB (41) x M2 June 2005 EPS INNOVATION PermaRock is the leading name in external wall insulation (EWI) and architectural façade systems in the United Kingdom, having pioneered the development of external

More information

19 East Ave. Mullica Hill, N.J Phone: Fax: ARCHITECTURAL FOAM FABRICATORS, LLC.

19 East Ave. Mullica Hill, N.J Phone: Fax: ARCHITECTURAL FOAM FABRICATORS, LLC. Table of Contents Trims...1-17 Sills...18-21 Frieze Boards...22-23 Cornices...24-28 Bands...29-32 Keystones...33-35 Pilasters...36 Columns...37-39 Quoins...40 Arches & Circles...41-42 4 1/2 Trims 7 6 14

More information

Dryvit Exterior Architectural Coatings

Dryvit Exterior Architectural Coatings Dryvit Exterior Architectural Coatings 100% Acrylic Architectural Coatings For Exterior Use Dryvit Exterior Architectural Coatings Specifications MANUFACTURER SPECIFICATION SECTION 09960 DRYVIT EXTERIOR

More information

NBS model specification

NBS model specification NBS model specification M60 painting/clear finishing Dryvit Acrylic Based Finish Coatings Incorporating: SG M60-Dryvit/110A www.dryvit.co.uk DRYVIT ACRYLIC-BASED FINISH COATINGS Dryvit UK Ltd. Unit 4 Wren

More information

SECTION EXTERIOR SOLID PHENOLIC RAINSCREEN PANELS

SECTION EXTERIOR SOLID PHENOLIC RAINSCREEN PANELS SECTION 074233 EXTERIOR SOLID PHENOLIC RAINSCREEN PANELS PART 1 - GENERAL 1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION COMPOSITE WALL PANELS PART 1 GENERAL 1.01 SECTION INCLUDES

SECTION COMPOSITE WALL PANELS PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 07 4243 - PART 1 GENERAL 1.01 SECTION INCLUDES A. Composite wall panel system consisting of aluminum-faced composite panels in a rainscreen application as part of the assembly described below.

More information

m^obu EXTERIOR INSULATION AND FINISH SYSTEMS STUCCO

m^obu EXTERIOR INSULATION AND FINISH SYSTEMS STUCCO EXTERIOR INSULATION AND FINISH SYSTEMS STUCCO Practical Technology Leadership Solutions Solutions for commercial, institutional, or residential construction. 1 Coat Stucco, 3 Coat Stucco, EIFS, and Acrylic

More information

[Project Name] Section [ ]

[Project Name] Section [ ] Page 1 PART 1 - GENERAL 1.1 SECTION INCLUDES 1.1.1 Design, labor, products, equipment and services necessary for interior/exterior Aluminum Facade System (AFS) work, in accordance with the Contract Documents.

More information

CUSTOM BRICK. Custom Brick Finish Polymer System Specifications For Use On Vertical Walls DS151. Architectural Finish for Use on Vertical Walls

CUSTOM BRICK. Custom Brick Finish Polymer System Specifications For Use On Vertical Walls DS151. Architectural Finish for Use on Vertical Walls CUSTOM BRICK Architectural Finish for Use on Vertical Walls Custom Brick Finish Polymer System Specifications For Use On Vertical Walls PART I- GENERAL DRYVIT SYSTEMS, INC. MANUFACTURER S SPECIFICATION

More information

CUSTOM BRICK. Custom Brick Finish Polymer System Specifications For Use On Vertical Walls DS151. Architectural Finish for Use on Vertical Walls

CUSTOM BRICK. Custom Brick Finish Polymer System Specifications For Use On Vertical Walls DS151. Architectural Finish for Use on Vertical Walls CUSTOM BRICK Architectural Finish for Use on Vertical Walls Custom Brick Finish Polymer System Specifications For Use On Vertical Walls PART I- GENERAL DRYVIT SYSTEMS, INC. MANUFACTURER S SPECIFICATION

More information

Light steel frame walls

Light steel frame walls Light Steel Frame Walls Light steel frame walls Solution optimiser and pathfinder Overview Light steel framing is extensively used due to its good thermal and structural behaviour. Heat loss reduction

More information

Evaluation Report CCMC R Icynene ProSeal Air Barrier System

Evaluation Report CCMC R Icynene ProSeal Air Barrier System Evaluation Report CCMC 14052-R Icynene ProSeal Air Barrier System MasterFormat: 07 27 09.01 Evaluation issued: 2016-12-23 Re-evaluation due: 2019-12-23 1. Opinion It is the opinion of the Canadian Construction

More information

LOWER MACUNGIE TOWNSHIP COMMUNITY CENTER ADDITIONS AND RENOVATIONS

LOWER MACUNGIE TOWNSHIP COMMUNITY CENTER ADDITIONS AND RENOVATIONS SECTION 07.2419 - WATER-DRAINAGE EXTERIOR INSULATION AND FINISH SYSTEM (EIFS) PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. EIFS-clad drainage-wall assemblies that are field applied over substrate.

More information

SECTION WATER-DRAINAGE EXTERIOR INSULATION AND FINISH SYSTEM (EIFS)

SECTION WATER-DRAINAGE EXTERIOR INSULATION AND FINISH SYSTEM (EIFS) SECTION 072419 WATER-DRAINAGE EXTERIOR INSULATION AND FINISH SYSTEM (EIFS) PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and General Provisions of the Contract, including General and Supplementary

More information

External Wall Insulation Systems GUARANTEED TO PERFORM!

External Wall Insulation Systems GUARANTEED TO PERFORM! External Wall Insulation Systems GUARANTEED TO PERFORM! External Wall Insulation Systems The wrap-around solution for warmer homes, lower bills Soaring energy costs have brought the need for more effective

More information

SECTION STAINLESS STEEL WALL PANELS

SECTION STAINLESS STEEL WALL PANELS SECTION 07400 PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Dry joint, Rainscreen stainless steel wall panel system. 2. Accessories including attachments, clips, sub girts, shims, and fasteners 3.

More information

R E S I D E N T I A L B U I L D E R S R E F E R E N C E G U I D E

R E S I D E N T I A L B U I L D E R S R E F E R E N C E G U I D E DRYVIT SYSTEMS CANADA DSC504 R E S I D E N T I A L B U I L D E R S R E F E R E N C E G U I D E BUILDING SUCCESSFULLY WITH DRYVIT OUTSULATION RESIDENTIAL SYSTEMS INTRODUCTION Building Successfully with

More information

MLC MASONRY AND BRICK PLASTER SYSTEM. Product. Scope. Appraisal No. 839 [2013] Appraisal No. 839 (2013) BRANZ Appraisals

MLC MASONRY AND BRICK PLASTER SYSTEM. Product. Scope. Appraisal No. 839 [2013] Appraisal No. 839 (2013) BRANZ Appraisals MLC MASONRY AND BRICK PLASTER SYSTEM BRANZ Appraisals Technical Assessments of products for building and construction. Specialized Construction Products Ltd PO Box 101 127 North Shore Mail Centre Auckland

More information

Guide Specification for the OSI QUAD Window and Door Flashing System

Guide Specification for the OSI QUAD Window and Door Flashing System Henkel Corporation 26235 First Avenue Westlake, OH 1-866-591-2178 www.ositough.com Guide Specification for the OSI QUAD Window and Door Flashing System Specifier Note: The purpose of this guide specification

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: TRESPA NORTH AMERICA, LTD.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: TRESPA NORTH AMERICA, LTD. 0 ICC ES Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 Most Widely Accepted and Trusted ESR 1687 Reissued 02/2016 This report is subject to renewal 02/2017. DIVISION: 07 00 00 THERMAL

More information

FOCAL POINT RENDAPANEL TM CLADDING SYSTEM

FOCAL POINT RENDAPANEL TM CLADDING SYSTEM FOCAL POINT RENDAPANEL TM CLADDING SYSTEM strength and durability SYSTEM INFORMATION & TECHNICAL SPECIFICATION V4 2002 Page 1 of 7 INTRODUCTION Monolithic Light Weight Cement Render Cladding RendaPanel

More information

CALL TO TALK TO THE SAS TEAM

CALL TO TALK TO THE SAS TEAM CALL 01647 24620 TO TALK TO THE SAS TEAM new EIFS.indd 1 1 8/29/2013 11:21:00 AM Contents Insulation overview Page 4 ProRend EIFS Adhesive System Installation Page 6 ProRend EIFS Rail System Installation

More information

External Steel Stud and Top Hat Walls. Details SYSTEMS 176 NON-FIRE RATED SYSTEMS 176 FIRE RATED SYSTEMS 178 BRICK VENEER SYSTEMS 183 INSTALLATION 185

External Steel Stud and Top Hat Walls. Details SYSTEMS 176 NON-FIRE RATED SYSTEMS 176 FIRE RATED SYSTEMS 178 BRICK VENEER SYSTEMS 183 INSTALLATION 185 Details SYSTEMS 176 NON-FIRE RATED SYSTEMS 176 FIRE RATED SYSTEMS 178 BRICK VENEER SYSTEMS 183 INSTALLATION 185 GENERAL REQUIREMENTS 185 FRAMING 185 PLASTERBOARD LAYOUT 189 PLASTERBOARD FIXING 190 EXTERIOR

More information

BUILDING SUCCESSFULLY WITH DRYVIT RESIDENTIAL SYSTEMS.

BUILDING SUCCESSFULLY WITH DRYVIT RESIDENTIAL SYSTEMS. BUILDING SUCCESSFULLY WITH DRYVIT RESIDENTIAL SYSTEMS. DS504 THE FOLLOWING IS A LIST OF MAJOR CONSIDERATIONS THAT WILL HELP ENSURE A QUALITY DRYVIT INSTALLATION. SUBSTRATES (INSPECTION/WALK-AROUND) Prior

More information

BACKSTOP TM NT - Texture A high performance, water-resistive membrane and air barrier

BACKSTOP TM NT - Texture A high performance, water-resistive membrane and air barrier BACKSTOP TM NT - Texture A high performance, water-resistive membrane and air barrier Backstop NT - Texture Specifications DRYVIT SYSTEMS CANADA MANUFACTURER S SPECIFICATION SECTION 07240 BACKSTOP NT -

More information

Product and System Specifications DuPont Flashing Systems

Product and System Specifications DuPont Flashing Systems DuPont Building Innovations March 2007 4417 Lancaster Pike Chestnut Run Plaza 721 Wilmington, DE 19805 1-800-448-9835 www.construction.tyvek.com Product and System Specifications DuPont Flashing Systems

More information

CHAPTER 3: Modern Methods of Construction (MMC)

CHAPTER 3: Modern Methods of Construction (MMC) CONTENTS 3.1.1 INTRODUCTION 3.1.2 SUITABILITY OF SYSTEMS AND COMPONENTS 3.1.3 TYPES OF MODERN METHODS OF CONSTRUCTION (MMC) 3.1.4 SUITABILITY OF SYSTEMS TO MEET WARRANTY REQUIREMENTS 3.1.5 INSULATED CONCRETE

More information

.1 Provide textured finish system for gypsum or cement board soffit and ceiling surfaces.

.1 Provide textured finish system for gypsum or cement board soffit and ceiling surfaces. Page 1 of 5 SPEC NOTE: IMPORTANT: This guide specification covers installation of a textured finish system over building code compliant soffit or ceiling construction. It does not address air sealing,

More information

A. Omega-Lite aluminum-faced composite panels, air and vapor barrier, attachments and sealants.

A. Omega-Lite aluminum-faced composite panels, air and vapor barrier, attachments and sealants. Section 07 42 13 Page 1 PART 1 GENERAL 1.1 SECTION INCLUDES A. Omega-Lite aluminum-faced composite panels, air and vapor barrier, attachments and sealants. 1.2 RELATED SECTIONS A. Section 06112 - Framing

More information

Sto Guide Specification No. F601S StoQuik Gold Finish System for Soffits and Ceilings

Sto Guide Specification No. F601S StoQuik Gold Finish System for Soffits and Ceilings Sto Corp. 3800 Camp Creek Parkway Building 1400, Suite 120 Atlanta, GA 30331 Tel: 404-346-3666 Toll Free: 1-800-221-2397 Fax: 404-346-3119 www.stocorp.com Sto Guide Specification No. F601S StoQuik Gold

More information

Detail Booklet StoTherm ci XPS

Detail Booklet StoTherm ci XPS Detail Booklet Series 53sxx Steel Frame Construction February 2017 professional, general contractor or builder They should be installed in accordance with those specifications and Sto s instructions Sto

More information

PAGE 297. Part 6 Superstructure (excluding roofs) Chapter 6.9. Curtain walling and cladding

PAGE 297. Part 6 Superstructure (excluding roofs) Chapter 6.9. Curtain walling and cladding PAGE 297 Part 6 Superstructure (excluding roofs) Chapter PAGE 298 CONTENTS Clause Page INTRODUCTION 1 DESIGN Design standards D1 2 Statutory requirements D2 2 Design life D3 2 Accessibility for maintenance

More information

This is what you see. DS 265

This is what you see. DS 265 This is what you see. 2 DS 265 This is what you get. Faster, less costly construction Lower energy bills Less environmental impact Lifetime warranty potential The High Performance Cladding Choice for New

More information

April Section Cladded Walls

April Section Cladded Walls April 2012 Section Cladded Walls Cladded Walls Cladded walls Rainscreen cladding and curtain wall systems Rainscreen cladding systems There are a wide variety of proprietary rainscreen cladding systems

More information

2002 Advanced Building Products, Inc., P.O. Box 98, Springvale, Maine TEL: ; FAX: ; WEBSITE:

2002 Advanced Building Products, Inc., P.O. Box 98, Springvale, Maine TEL: ; FAX: ; WEBSITE: SECTION 07651 FLEXIBLE COPPER SHEET FLASHINGS Advanced Building Products, Inc. manufacturer many types of flexible copper sheet flashings. Due to their ductility, high tensile strength, and resistance

More information

SOPREMA JARDIN Double Layer Torch-on membrane For water proofing roof gardens and planters

SOPREMA JARDIN Double Layer Torch-on membrane For water proofing roof gardens and planters TECHNICAL DATA Technical data may be updated at any time. It is the users responsibility to check data validity by reference to the website or Nuplex Construction Products MANUAL SECTION ISSUE DATE AUTHORISED

More information

Insulation. First Revison October DC14 Drainage Mat INSTALLATION GUIDE FOR RESIDENTIAL & COMMERCIAL APPLICATIONS

Insulation. First Revison October DC14 Drainage Mat INSTALLATION GUIDE FOR RESIDENTIAL & COMMERCIAL APPLICATIONS Insulation First Revison October 2016 DC14 Drainage Mat INSTALLATION GUIDE FOR RESIDENTIAL & COMMERCIAL APPLICATIONS 1. General Information This Guide describes the use of Kingspan GreenGuard DC14 Drainage

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: FUNDERMAX GMBH

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: FUNDERMAX GMBH 0 Most Widely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3340 Reissued 05/2017 This report is subject to renewal 05/2018. DIVISION: 07 00 00 THERMAL

More information

A. Section includes fluid applied, vapor permeable membrane air barriers.

A. Section includes fluid applied, vapor permeable membrane air barriers. Master Construction Specifications Insert Project Name SECTION 072726 FLUID APPLIED MEMBRANE AIR BARRIERS PART 1 GENERAL 1.1 SUMMARY A. Section includes fluid applied, vapor permeable membrane air barriers.

More information

BUILDING SUCCESSFULLY WITH DRYVIT RESIDENTIAL SYSTEMS.

BUILDING SUCCESSFULLY WITH DRYVIT RESIDENTIAL SYSTEMS. BUILDING SUCCESSFULLY WITH RESIDENTIAL S. DS504 THE FOLLOWING IS A LIST OF MAJOR CONSIDERATIONS THAT WILL HELP ENSURE A QUALITY INSTALLATION. SUBSTRATES (INSPECTION/WALK-AROUND) Prior to starting a job,

More information

SPECIFICATION GUIDELINE

SPECIFICATION GUIDELINE Environmental StoneWorks specification guideline should be used to assist design professionals in the preparation of projects. Edit and delete items that may not be applicable. Verify all referenced section

More information

CEMENT BOARD MD FINISH SYSTEM

CEMENT BOARD MD FINISH SYSTEM CEMENT BOARD MD FINISH SYSTEM An Exterior Finish System Applied Over Exterior Cement Board With A Water-Resistive Barrier And Moisture Drainage Cement Board MD Finish System Specifications DRYVIT SYSTEMS,

More information

ICC ES SYSTEM SYSTEM. Trusted DIVISION: 07 SECTION: AND FINISH REPORT HOLDER: ICC-ES Evaluation. Reissued 08/2016.

ICC ES SYSTEM SYSTEM. Trusted DIVISION: 07 SECTION: AND FINISH REPORT HOLDER: ICC-ES Evaluation. Reissued 08/2016. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.orgg ESR 2562 Reissued 08/206 This report is subject to renewal 08/208. DIVISION: 07 00 00

More information

Tender No Section St. James - Assiniboia Centennial Pool Fitness Facility Addition Page 1

Tender No Section St. James - Assiniboia Centennial Pool Fitness Facility Addition Page 1 Fitness Facility Addition Page 1 PART 1 GENERAL 1.1 SECTION INCLUDES.1 Extruded aluminum windows with fixed sash..2 Factory glazed..3 Perimeter sealant. 1.2 RELATED SECTIONS.1 Section 05500 - Metal Fabrications.2

More information

PERM-FLEX ASSEMBLY DIRECT APPLICATION TO CEMENTITIOUS SUBSTRATES MANUFACTURERS SPECIFICATION / SECTION 09960

PERM-FLEX ASSEMBLY DIRECT APPLICATION TO CEMENTITIOUS SUBSTRATES MANUFACTURERS SPECIFICATION / SECTION 09960 STUC-O-FLEX PERM-FLEX ASSEMBLY DIRECT APPLICATION TO CEMENTITIOUS SUBSTRATES MANUFACTURERS SPECIFICATION / SECTION 09960 PART 1 - GENERAL 1.01 DESCRIPTION Provide all labor, materials and equipment necessary

More information

THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150

THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150 THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150 SECTION ONE A. Objective The objective of this guide is to provide Owners and General Contractors/Construction

More information

PERM-FLEX ASSEMBLY DIRECT APPLICATION TO CEMENT BOARD SUBSTRATES MANUFACTURERS SPECIFICATION / SECTION 09960

PERM-FLEX ASSEMBLY DIRECT APPLICATION TO CEMENT BOARD SUBSTRATES MANUFACTURERS SPECIFICATION / SECTION 09960 STUC-O-FLEX PERM-FLEX ASSEMBLY DIRECT APPLICATION TO CEMENT BOARD SUBSTRATES MANUFACTURERS SPECIFICATION / SECTION 09960 PART 1 - GENERAL 1.01 DESCRIPTION Provide all labor, materials and equipment necessary

More information

Building Science Control Layer Glossary. Façade Visible exterior face of a building, usually vertical or nearly so, but imprecisely used.

Building Science Control Layer Glossary. Façade Visible exterior face of a building, usually vertical or nearly so, but imprecisely used. It is far more important than often appreciated to use precise, unambiguous, clear definitions when describing aspects of buildings, building enclosures, and building science performance. The following

More information

SECTION EXTERIOR INSULATION AND FINISH SYSTEMS

SECTION EXTERIOR INSULATION AND FINISH SYSTEMS SECTION 07 24 00 EXTERIOR INSULATION AND FINISH SYSTEMS PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred

More information

SPECIFICATION GUIDELINE

SPECIFICATION GUIDELINE SPECIFICATION GUIDELINE Environmental Stoneworks Corporate Office 6300 East Stapleton Drive South Denver, CO 80216 Phone (303) 309-3040 Fax (303) 309-3059 www.estoneworks.com Environmental Stoneworks specification

More information

REPORT HOLDER: OMEGA PRODUCTS INTERNATIONAL, INC CALIFORNIA AVENUE CORONA, CALIFORNIA EVALUATION SUBJECT:

REPORT HOLDER: OMEGA PRODUCTS INTERNATIONAL, INC CALIFORNIA AVENUE CORONA, CALIFORNIA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (00) 423-657 (562) 699-0543 www.icc-es.org ESR-2064 Reissued 11/2017 This report is subject to renewal 11/201. DIVISION: 07 00 00

More information

wall underlay Product BRANZ APPRAISAL No. 695 (2010) Scope Thermakraft Industries (NZ) Ltd PO Box Botany Manukau 2163 Auckland

wall underlay Product BRANZ APPRAISAL No. 695 (2010) Scope Thermakraft Industries (NZ) Ltd PO Box Botany Manukau 2163 Auckland Product 1.1 Watergate-Plus is a fire retardant, flexible synthetic wall underlay for use under direct fixed and non-direct fixed wall cladding on timber and steel framed buildings. The product is manufactured

More information

Gensler 2014/06/16 Hertz Global Headquarters ISSUE FOR BUILDING PERMIT Estero, Florida SECTION

Gensler 2014/06/16 Hertz Global Headquarters ISSUE FOR BUILDING PERMIT Estero, Florida SECTION SECTION 072700 VAPOR PERMEABLE AIR BARRIER LIQUID MEMBRANE PART 1 GENERAL 1.1 GENERAL REQUIREMENTS A. The Work of this Section, as shown or specified, shall be in accordance with the requirements of the

More information

ROCKCOTE RESENE MONOTEK SYSTEMS

ROCKCOTE RESENE MONOTEK SYSTEMS Product Appraisal No.500 [2007] BRANZ Appraisals Technical Assessments of products for building and construction 1.1 The Rockcote Resene Monotek Systems consists of the Rockcote Resene Monotek Texture

More information

A. Source Limitations: Obtain each type of building insulation through one source.

A. Source Limitations: Obtain each type of building insulation through one source. SECTION 07210 - BUILDING INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

AquaFlash System Installation Guide

AquaFlash System Installation Guide AquaFlash System Installation Guide I. General: A. This document provides guidelines for the application and use of the Dryvit AquaFlash System at rough openings for windows, doors and other penetrations,

More information

RH & RV CAVITY BARRIERS

RH & RV CAVITY BARRIERS RH & RV CAVITY For use in external envelope or fabric of buildings SIDERISE RH OPEN STATE HORIZONTAL AND RV VERTICAL CAVITY BARRIER RANGE REPRESENT THE DEFAULT CHOICE FOR MARKET-LEADING, HIGH-PERFORMANCE

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIBER CEMENT SIDING REPORT HOLDER: RIEDER FASERBETON ELEMENTE GmbH

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIBER CEMENT SIDING REPORT HOLDER: RIEDER FASERBETON ELEMENTE GmbH 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2810 Reissued 02/2018 This report is subject to renewal 07/2018. DIVISION: 07 00

More information

Installation Guidelines

Installation Guidelines Installation Guidelines The Vertibreak Wall System: Installation Guidelines Rainscreen Insulation for New or Retrofit Construction Applications Vertibreak rainscreen insulation is an expanded polystyrene

More information

SECTION FLUID-APPLIED MEMBRANE AIR BARRIERS, VAPOR PERMEABLE

SECTION FLUID-APPLIED MEMBRANE AIR BARRIERS, VAPOR PERMEABLE PART 1 - GENERAL 1.1 SUMMARY SECTION 07 27 26 FLUID-APPLIED MEMBRANE AIR BARRIERS, VAPOR PERMEABLE SPEC WRITER NOTE: 1. Delete text between // // not applicable to project. Edit remaining text to suit

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: ARCONIC ARCHITECTURAL PRODUCTS, LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: ARCONIC ARCHITECTURAL PRODUCTS, LLC 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3435 Reissued 07/2017 This report is subject to renewal 07/2018. DIVISION: 07 00

More information

[Project Name] Section [ ] SINTERED CERAMIC FACADE SYSTEM (SCFS) Page 1

[Project Name] Section [ ] SINTERED CERAMIC FACADE SYSTEM (SCFS) Page 1 Page 1 PART 1 - GENERAL 1.1 SECTION INCLUDES 1.1.1 Design, labor, products, equipment and services necessary for large format interior/exterior Sintered Ceramic Facade System (SCFS) work, in accordance

More information

Roofing. Carrier Membrane SA. Self-adhesive Carrier Membrane. Product Description. Tests. Product Data. Form. Storage

Roofing. Carrier Membrane SA. Self-adhesive Carrier Membrane. Product Description. Tests. Product Data. Form. Storage Carrier Membrane SA Self-adhesive Carrier Membrane Product Description Carrier Membrane SA is a multi-layer self-adhesive membrane made of polymer modified bitumen with an aluminium foil/random fibre top

More information

MANUFACTURER S (SHORT FORM) SPECIFICATION / SECTION

MANUFACTURER S (SHORT FORM) SPECIFICATION / SECTION STUC-O-FLEX - ELASTOMERIC ACRYLIC FINISH APPLICATION TO PORTLAND CEMENT PLASTER / CONCRETE RENDER MANUFACTURER S (SHORT FORM) SPECIFICATION / SECTION 09220-09 24 00 PART 1-GENERAL SCOPE: Manufacturer's

More information

MANUFACTURERS (SHORT FORM) SPECIFICATION / SECTION

MANUFACTURERS (SHORT FORM) SPECIFICATION / SECTION STUC-O-FLEX - ELASTOMERIC ACRYLIC FINISH APPLICATION TO PORTLAND CEMENT PLASTER / CONCRETE RENDER MANUFACTURERS (SHORT FORM) SPECIFICATION / SECTION 09220-09 24 00 PART 1-GENERAL SCOPE: Manufacturer's

More information

August 2008: Issue 1. Non - Residential New Build 4.5 Basements

August 2008: Issue 1. Non - Residential New Build 4.5 Basements Non - Residential New Build 4.5 Basements August 2008: Issue 1 Non-residential new build 4.0 Non-residential New Build Basements Contents Introduction find online page Solution optimiser and pathfinder

More information

The Disclaimer located on the reverse side of the title page of the OAA Rain Penetration Practice Guide applies to each section of the Guide.

The Disclaimer located on the reverse side of the title page of the OAA Rain Penetration Practice Guide applies to each section of the Guide. Note: This document has been divided into several sections in order to suit the limitations of the website. The Disclaimer located on the reverse side of the title page of the OAA Rain Penetration Practice

More information

REPORT HOLDER: GREENMAKER INDUSTRIES, LLC 697 OAKWOOD AVENUE WEST HARTFORD, CONNECTICUT EVALUATION SUBJECT: DECOPLAST DDARS NOTCHED

REPORT HOLDER: GREENMAKER INDUSTRIES, LLC 697 OAKWOOD AVENUE WEST HARTFORD, CONNECTICUT EVALUATION SUBJECT: DECOPLAST DDARS NOTCHED 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3428 Reissued 07/2017 This report is subject to renewal 07/2019. DIVISION: 07 00

More information

DuPont Tyvek Air Barrier Installation Guidelines. Canadian Version. Version 2

DuPont Tyvek Air Barrier Installation Guidelines. Canadian Version. Version 2 DuPont Tyvek Air Barrier Installation Guidelines Helping you get the job done right Canadian Version Version 2 Table of Contents Applicable Products...2 Required Materials...2 Code Requirements...3 General

More information

SECTION THERMAL INSULATION

SECTION THERMAL INSULATION Pactiv Building Products 2100 RiverEdge Parkway Suite 175 Atlanta, GA 30328 Toll Free: (800) 241-4402 Web Site: www.green-guard.com SECTION 07210 THERMAL INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS

More information

MARQUIS Tualatin FIBER-CEMENT SIDING June 15, rev

MARQUIS Tualatin FIBER-CEMENT SIDING June 15, rev PART 1 - GENERAL 1.1 SUMMARY A. This Section includes: 1. Reinforced fiber-cement shingle panel siding, 2. Reinforced fiber-cement lap siding. B. Related Sections: 1. Division 1 Section "Quality Requirements"

More information

SRP-AirOutshield UV Issued:

SRP-AirOutshield UV Issued: SECTION 07276: SRP-AirOutshield UV Ultra Violet (UV) resistant, Vapour Permeable Air Barrier Underlayment and Sheathing Membrane Guide Specification This specification is a guide only and may need editing

More information

Design No. HI/BP PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table 1

Design No. HI/BP PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table 1 FIRESTOP JOINT SPRAY CFS-SP WB SILICONE JOINT SPRAY CFS-SP SIL F-RATING 2-HR. 2-HR. T-RATING -HR. -HR. APPLICATION THICKNESS PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table /8" WET FILM (/6"

More information

PASSIVE FIRE PROTECTION SYSTEMS Application & Technical Manual: Cavity & Smoke Barriers, Parapet & Spandrel Walls

PASSIVE FIRE PROTECTION SYSTEMS Application & Technical Manual: Cavity & Smoke Barriers, Parapet & Spandrel Walls PASSIVE FIRE PROTECTION SYSTEMS Application & Technical Manual: Cavity & Smoke Barriers, Parapet & Spandrel Walls For Promat Asia Pacific Organisation February 0 PASSIVE FIRE PROTECTION SYSTEMS Application

More information

Sept 30, 2004 Page 1

Sept 30, 2004 Page 1 Sept 30, 2004 Page 1 This section includes a manufacturer's guide specification for TERRAFOAM EPS building insulation. Refer also to Product Description for detailed product properties, options, and other

More information

U.S. EDITION RESIDENTIAL CONSTRUCTION DETAILS SAMPLE. A visual guide to construction detailing. Emma Walshaw

U.S. EDITION RESIDENTIAL CONSTRUCTION DETAILS SAMPLE. A visual guide to construction detailing. Emma Walshaw RESIDENTIAL CONSTRUCTION DETAILS U.S. EDITION A visual guide to construction detailing Emma Walshaw Contents INTRODUCTION 4 PRINCIPLES OF CONSTRUCTION DETAILING 6 FOUNDATIONS 9 PRINCIPLES OF FOUNDATION

More information

SPECIFICATIONS FOR. CEI Composite Materials, LLC Featuring R4000 Rear Back Ventilated Rainscreen System. Section Aluminum Composite Panels

SPECIFICATIONS FOR. CEI Composite Materials, LLC Featuring R4000 Rear Back Ventilated Rainscreen System. Section Aluminum Composite Panels SPECIFICATIONS FOR (1/13 Edition) CEI Composite Materials, LLC Featuring R4000 Rear Back Ventilated Rainscreen System Section 074243 Aluminum Composite Panels (Based upon CEI Composite Materials R4000

More information

80230 StoColor Coat Sand Acrylic-Based, Vertical Above-Grade Exterior Wall Coating for New Concrete, Stucco, and Masonry Construction

80230 StoColor Coat Sand Acrylic-Based, Vertical Above-Grade Exterior Wall Coating for New Concrete, Stucco, and Masonry Construction 80230 StoColor Coat Sand Acrylic-Based, Vertical Above-Grade Exterior Wall Coating for New Concrete, Stucco, and Masonry Construction Section 099723 CONCRETE AND MASONRY COATINGS Sto Corp. 3800 Camp Creek

More information

Evaluation Report CCMC R Demilec Air Barrier System

Evaluation Report CCMC R Demilec Air Barrier System Evaluation Report CCMC 14068-R Demilec Air Barrier System MasterFormat: 07 27 09.01 Evaluation issued: 2017-08-30 Re-evaluation due: 2020-08-30 1. Opinion It is the opinion of the Canadian Construction

More information

Dow Corning Silicone Air Barrier System. A more. energy-efficient. shade. green

Dow Corning Silicone Air Barrier System. A more. energy-efficient. shade. green Silicone Air Barrier System of shade energy-efficient A more green Air and Moisture Protection for More Energy-Efficient Buildings Meeting regulatory requirements for energy efficiency is a significant

More information

Note to Specifier: Use this product for coated glass-mat faced polyisocyanurate insulation boards such as Rboard.

Note to Specifier: Use this product for coated glass-mat faced polyisocyanurate insulation boards such as Rboard. Note to Specifier: Use this product for coated glass-mat faced polyisocyanurate insulation boards such as Rboard. Note to Specifier: Make selections, such as board thickness and sizes, etc. Where selection

More information

Building Design Data

Building Design Data Building Design Data.. 1. Building Design The KORE ICF System is designed to meet the requirements of the Building Regulations 1997-2006, in the case of two storeys, single occupancy dwellings. If the

More information

Dryvit Interior Architectural Coatings Specifications

Dryvit Interior Architectural Coatings Specifications Dryvit Interior Architectural Coatings 100% Acrylic Architectural Coatings For Interior Use Dryvit Interior Architectural Coatings Specifications DRYVIT SYSTEMS, INC. MANUFACTURER SPECIFICATION SECTION

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS SECTION: AIR BARRIERS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS SECTION: AIR BARRIERS 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3172 Reissued 02/2018 This report is subject to renewal 02/2019. DIVISION: 07 00

More information

Textured Acrylic Finishes (TAFS) Over ICFs Specifications

Textured Acrylic Finishes (TAFS) Over ICFs Specifications TAFS over ICFs Textured 100% Acrylic Finishes (TAFS) For Use Over Insulating Concrete Forms (ICF) Textured Acrylic Finishes (TAFS) Over ICFs Specifications MANUFACTURER SPECIFICATION SECTION 09960 TEXTURED

More information

Sept 30, 2004 Page 1 PRODUCT DESCRIPTION PRODUCT FEATURES

Sept 30, 2004 Page 1 PRODUCT DESCRIPTION PRODUCT FEATURES Sept 30, 2004 Page 1 PRODUCT FEATURES BASIC USES / RELATED USES LOGIX Insulated Concrete Forms are stackable, interlocking expanded polystyrene (EPS) blocks that serve as permanent formwork to create solid

More information

June Non - Residential Refurbishment 5.5 Basements

June Non - Residential Refurbishment 5.5 Basements June 2010 Non - Residential Refurbishment 5.5 Basements Non-residential refurbishment 5.0 Non-residential Refurbishment Basements Contents Introduction find online page Solution optimiser and pathfinder

More information

ENVELOPE The Ultimate In Performance In A Dry-Joint System RAINSCREEN (RS) SYSTEM TECHNICAL MANUAL

ENVELOPE The Ultimate In Performance In A Dry-Joint System RAINSCREEN (RS) SYSTEM TECHNICAL MANUAL ENVELOPE 2000 RAINSCREEN (RS) SYSTEM The Ultimate In Performance In A Dry-Joint System TECHNICAL MANUAL System Assembly Substrate Layouts CAD Sections/Details Physical Properties Performance Properties

More information

Master Wall Inc. continuously tests our products and systems to meet the most current building codes.

Master Wall Inc. continuously tests our products and systems to meet the most current building codes. Master Wall Inc. continuously tests our products and systems to meet the most current building codes. Fire Testing Fire Resistance ASTM E119 No effect on the fire resistance of a rated wall assembly See

More information

AcroWall-ES System. Class PB Exterior Insulation and Finish System providing a primary moisture barrier. Typical Details

AcroWall-ES System. Class PB Exterior Insulation and Finish System providing a primary moisture barrier. Typical Details Typical Details AcroWall-ES System Class PB Exterior Insulation and Finish System providing a primary moisture barrier 1. Typical AcroWall-ES System Application 2. Typical Aesthetic Reveal 3. Typical Window

More information

Technical Data Sheet

Technical Data Sheet Technical Data Sheet ProGUARD Concrete Insulated Sheathing Specifications & Installation Table Of Contents Product Description... pg. 1 Basic Use... pg. 1 Exterior Finishes... pg. 1 Standard Sizes... pg.

More information

by Rollfab Metal Products

by Rollfab Metal Products by Rollfab Metal Products SECTION 07460 ALUMINUM SIDING AND SOFFITS PART 1 GENERAL 1.2 RELATED SECTIONS 1.3 REFERENCES A. SECTION INCLUDES B. Aluminum Siding. C. Aluminum Soffits. D. Aluminum trim and

More information

Dryvit Textured Acrylic Finishes. (TAFS Option 2) For Exterior Soffits Specifications

Dryvit Textured Acrylic Finishes. (TAFS Option 2) For Exterior Soffits Specifications Dryvit Textured Acrylic Finishes (TAFS Option 2) For Exterior Soffits 100% Acrylic Architectural Coatings For Use on Exterior Soffits Dryvit Textured Acrylic Finishes (TAFS Option 2) For Exterior Soffits

More information