1 CLASSIFICATION OF REACTION TO FIRE Polymethylmethacrylate PMMA, Akrylon XT This is an electronic version of a classification report which was made as a copy of classification report officially issued in a form. The electronic version of a classification report shall be used only for informative purpose. Any information listed in this classification report is the property of the sponsor and shall not be used or published without written permission. Contents of this file may only be modified by the editor i.e. FIRES, s.r.o. Batizovce. Sponsor is allowed to publish this classification report in parts only with written permission of the editor. FIRES 9/S4-10/02/2010-E-el

2 CLASSIFICATION OF REACTION TO FIRE IN ACCORDANCE WITH EN : A1: 2009 with direct field of application Name of the product: Polymethylmethacrylate PMMA, Akrylon XT Sponsor: Prepared by: Polycasa Slovakia, s.r.o. M.R.Štefánika Žilina Slovak Republic FIRES, s.r.o. Osloboditeľov Batizovce Slovak Republic Tested property: Reaction to fire Test method: : 2002 Type of test: Accredited Task No.: PR Date of issue: Reports: 3 Copy No.: 2 Distribution list: Copy No. 1 Copy No. 2 Copy No. 3 FIRES, s. r. o., Osloboditeľov 282, Batizovce, Slovak Republic (electronic version) Polycasa Slovakia, s.r.o., M.R.Štefánika 71, Žilina, Slovak Republic (electronic version) Polycasa Slovakia, s.r.o., M.R.Štefánika 71, Žilina, Slovak Republic This classification report may only be used or reproduced in its entirety. This report includes accreditation mark SNAS with additional mark ILAC-MRA. SNAS is signatory of ILAC-MRA, Mutual recognition agreement (of accreditation), which is focused on promoting of international acceptance of accredited laboratory data and reducing technical barriers to trade, such as the retesting of products on markets of signatories. More information about ILAC-MRA is on Signatories of ILAC-MRA are e.g. SNAS (Slovakia), CAI (Czech Republic), PCA (Poland), DakkS (Germany) or BMWA (Austria). Up to date list of ILAC-MRA signatories is on FIRES, s.r.o. Batizovce is full member of EGOLF also, more information FIRES 049/S2-28/03/2014-E FIRES, s.r.o., Osloboditeľov 282, Batizovce, Slovak Republic tel , fax , Notified Body No. 1396, Approved Body No. SK01, Member of EGOLF

3 1. INTRODUCTION This classification report defines the reaction to fire classification assigned to element polymethylmethacrylate PMMA, Akrylon XT in accordance with the procedures given in EN : A1: DETAILS OF CLASSIFIED PRODUCT 2.1 GENERAL The element, polymethylmethacrylate PMMA, Akrylon XT is used in board form as a door glazing, separating walls, roofs ceilings and from thickness 10 mm as a sound barrier to the highways, after treatment by formation or bending as skylights, covers on lamps, luminous boards in accordance with EN ISO : PRODUCT DESCRIPTION Polymethylmethacrylate PMMA, type Akrylon XT is made from PMMA granulate, which contains from 4,5 % up to 6 % MA. The additional additives, which modify the polymer properties or its appearance, are possible to add (antioxidants, inner oils, UV absorbers etc.) Boards are made with thickness from 1,8 mm up to 25 mm and with bulk density from 1190 kg.m -3 up to 44 kg.m TEST REPORTS IN SUPPORT OF CLASSIFICATION 3.1 TEST REPORTS No. Name of laboratory Name of sponsor Test report No. Date of the test Test method [1] FIRES, s.r.o., Batizovce, SK MPA NRW, Erwitte, Germany Barlo Plastics Slovakia s.r.o., SK Barlo Plastics GmbH, Germany FIRES RF 040/04 CS STN EN ISO DIN EN ISO [1] - Test specimens were conditioned according to EN before the fire resistance test [1] Tested product Tested product Polymethylmethacrylate PMMA, AKRYLON XT, clear sheet, thickness 1,8 mm, bulk density 1190 kg.m -3 Tested product Polymethylmethacrylate PMMA, BARLO XT, clear sheet, thickness 1,8 mm, bulk density 1171 kg.m -3 ; Tested product Polymethylmethacrylate PMMA, BARLO XT opal, white translucent sheet, thickness 2 mm, bulk density 27 kg.m -3 ; Tested product Polymethylmethacrylate PMMA, BARLO XT opal, white translucent sheet, thickness 2 mm, bulk density 00 kg.m -3 ; Tested product Polymethylmethacrylate PMMA, BARLO XT opal, white opaque sheet, thickness 2 mm, bulk density 44 kg.m -3 ; Tested product Polymethylmethacrylate PMMA, BARLO XT opal, white opaque sheet, thickness 6 mm, bulk density 20 kg.m -3 ; FIRES 049/S2-28/03/2014-E Page: 2/5

4 3.2 TEST RESULTS AKRYLON XT clear sheet, thickness 1,8 mm, bulk density 1190 kg.m -3 [1] BARLO XT clear sheet, thickness 25 mm, bulk density 1171 kg.m -3 BARLO XT opal, white translucent sheet, thickness 2 mm, bulk density 27 kg.m -3 FIRES 049/S2-28/03/2014-E Page: 3/5

5 BARLO XT opal, white translucent sheet, thickness 4 mm, bulk density 00 kg.m -3 BARLO XT opal, white opaque sheet, thickness 2 mm, bulk density 44 kg.m -3 BARLO XT opal, white opaque sheet, thickness 6 mm, bulk density 20 kg.m -3 * Specimens main surface and edge (bottom part of boards) were exposed. 4. CLASSIFICATION AND FIELD OF APPLICATION 4.1 REFERENCE OF CLASSIFICATION This classification has been carried out in accordance with clause 11.3 of EN : A1: FIRES 049/S2-28/03/2014-E Page: 4/5

6 4.2 CLASSIFICATION The product, Polymethylmethacrylate PMMA, Akrylon XT, in relation to its reaction to fire behaviour is classified: E The additional classification in relation to smoke production is: - The additional classification in relation to is: - The format of the reaction to fire classification for construction products excluding floorings is: Fire behaviour Smoke production Flaming droplets E - - -, - - Reaction to fire classification: E 4.3 FIELD OF APPLICATION This classification is valid for the following final use applications: Thickness change in the thickness from 1,8 mm up to 25 mm for clear sheets and from 2 mm up to 25 mm for translucent colour sheets is allowed; Bulk density change in the bulk density from 1190 kg.m -3 up to 44 kg.m -3 is allowed; Chemical composition no change in chemical composition of product is allowed; 5. LIMITATIONS This classification document does not represent type approval or certification of the product. The classification is valid provided that the product, field of application and standards and regulations are not changed. Approved: Signed: Ing. Štefan Rástocký leader of the testing laboratory Ing. Samuel Skokan technician of the testing laboratory FIRES 049/S2-28/03/2014-E Page: 5/5

CLASSIFICATION OF REACTION TO FIRE FIRES-CR AUPE

CLASSIFICATION OF REACTION TO FIRE FIRES-CR AUPE CLASSIFICATION OF REACTION TO FIRE FIRES-CR-138-13-AUPE Self-supporting double skin metal faced insulating panels with PIR core, type THERMOWALL KOMBI This is an electronic version of a classification

More information

CLASSIFICATION OF FIRE RESISTANCE FIRES-CR AUPE

CLASSIFICATION OF FIRE RESISTANCE FIRES-CR AUPE CLASSIFICATION OF FIRE RESISTANCE FIRES-CR-175-13-AUPE Reactive fire protection coating AITHON A90H applied to concrete This is an electronic version of a classification report which was made as a copy

More information

TEST REPORT FIRES-FR AUNE. Single side-hung lift landing semiautomatic door, thermally insulated with polyurethane

TEST REPORT FIRES-FR AUNE. Single side-hung lift landing semiautomatic door, thermally insulated with polyurethane TEST REPORT Single side-hung lift landing semiautomatic door, thermally insulated with polyurethane This is an electronic version of a test report which was made as a copy of test report officially issued

More information

FIRE RESISTANCE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION FIRES-JR NURE. Fire resistance shutter with retractable stairs, type LMF

FIRE RESISTANCE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION FIRES-JR NURE. Fire resistance shutter with retractable stairs, type LMF FIRE RESISTANCE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION FIRES-JR-004-11-NURE Fire resistance shutter with retractable stairs, type LMF This is an electronic version of a classification report which

More information

CLASSIFICATION OF FIRE RESISTANCE FIRES-CR AUPE

CLASSIFICATION OF FIRE RESISTANCE FIRES-CR AUPE CLASSIFICATION OF FIRE RESISTANCE FIRES-CR-179-17-AUPE A single leaf aluminium framed doorset, type ALIPLAST FR90 EI60 This is an electronic version of a classification report which was made as a copy

More information

Title: CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN : 2002 Notified Body No: 0833 Product Name: Mix Report No:

Title: CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN : 2002 Notified Body No: 0833 Product Name: Mix Report No: Title: CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1: 2002 Notified Body No: 0833 Product Name: Mix Report No: 155547 Issue No: 1 Prepared for: Tessera Carpet Tiles, Unit

More information

Title: CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1: Notified Body No: 0833 Product Name:

Title: CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1: Notified Body No: 0833 Product Name: Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: CLASSIFICATION OF REACTION TO

More information

Classification of Reaction to Fire in accordance with DIN EN :

Classification of Reaction to Fire in accordance with DIN EN : Classification of Reaction to Fire in accordance with DIN EN 13501-1 : 2010-01 No. of classification report: K-3680/881/13-MPA BS Client: Prepared by: Notified Body No.: Dr. Lietz Marketing Services GmbH

More information

1 st August Title: CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1: 2009.

1 st August Title: CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1: 2009. Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: CLASSIFICATION OF REACTION TO

More information

Title: CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1: Notified Body No: 0833 Product Name:

Title: CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1: Notified Body No: 0833 Product Name: Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: CLASSIFICATION OF REACTION TO FIRE PERFORMANCE

More information

Technical Product Information

Technical Product Information Technical Product Information AKRYLON XT 1. PRODUCT IDENTIFICATION... 2 1.1 Characteristics... 2 1.2 Applications... 2 1.3 Fabrication and finishing techniques... 2 2. TECHNICAL INFORMATION... 3 2.1 Colours

More information

Title: CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1: Notified Body No: Product Name:

Title: CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1: Notified Body No: Product Name: Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: CLASSIFICATION OF REACTION TO

More information

Title: CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1: Notified Body No: 0833 Product Name:

Title: CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1: Notified Body No: 0833 Product Name: Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: CLASSIFICATION OF REACTION TO

More information

Title: CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009 Notified Body No: 0833 Product Name: Type II

Title: CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009 Notified Body No: 0833 Product Name: Type II Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: CLASSIFICATION OF REACTION TO

More information

^pr oeti. Report VNLF Classification Report

^pr oeti. Report VNLF Classification Report ^pr oeti ^arx. Report VNLF 080866.4 Classification Report Applicant KLEEN-TEX Industries in Europa GmbH Münchner Straße 21 6330-Kufstein Austria Reference Mrs. Antje Schlegel Application Classification

More information

MATERIAL SPECIFICATION RIGID FOAM; CLOSED CELL POLYMETHACRYLIMIDE (PMI)

MATERIAL SPECIFICATION RIGID FOAM; CLOSED CELL POLYMETHACRYLIMIDE (PMI) Proposal of a specification MATERIAL SPECIFICATION RIGID FOAM; CLOSED CELL POLYMETHACRYLIMIDE (PMI) Contents 1 SCOPE Page 2 1.1 Scope Page 2 1.2 Classification Page 2 2 APPLICABLE DOCUMENTS Page 3 3 REQUIREMENTS

More information

Sika Tricomer Compression Seals

Sika Tricomer Compression Seals PRODUCT DATA SHEET Sika Tricomer Compression Seals Preformed Tricomer based profiles for covering and closing low movement joints PRODUCT DESCRIPTION are weather-resistant joint covering or closing profiles

More information

This classification report consists of five pages and may only be used or reproduced in its entirety.

This classification report consists of five pages and may only be used or reproduced in its entirety. Title: Classification of Fire Resistance Performance In Accordance With EN 0-2: 200 Notified Body No: 08 Product Name: Pyrobelite 2 Report No: WF 9 Issue No: Prepared for: Glaverbel S. A. BU Industrial

More information

CERTIFICATE. No

CERTIFICATE. No ZUS TECHNICKÝ A ZKUŠEBNÍ ÚSTAV STAVEBNÍ PRAHA, s.p. Technical and Test Institute for Construction Prague Accredited Test Laboratory, Authorized Body, Certification Body, Inspection Body Authorized Body

More information

Earthwool Glasswool Insulation

Earthwool Glasswool Insulation Global-Mark Pty Ltd, Suite 4.07, 32 Delhi Road, North Ryde NSW 2113, Australia Tel: +61 (0)2 9886 0222 - www.global-mark.com.au Certificate Holder: Knauf Insulation Pty Ltd Unit 2 44 Borthwick Avenue Murarrie,

More information

Product data. HERADESIGN micro

Product data. HERADESIGN micro Product data Product data Single layer layer magnesite-bonded wood wool acoustic panel with fi ne pore surface structure, building biology recommended. Colour variants The natural characteristic structure

More information

TFI Report acoustics

TFI Report acoustics TFI Report 441076-02 acoustics Customer Tapibel NV Industrielaan 4 B-3900 Overpelt BELGIUM Product textile floor covering Responsible at TFI Dr.-Ing. Alexander Siebel Tel: +49 241 9679 170 a.siebel@tfi-online.de

More information

Title: CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN : 2007 Notified Body No: 0833 Product Name:

Title: CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN : 2007 Notified Body No: 0833 Product Name: Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: CLASSIFICATION OF REACTION TO

More information

BRE Global Classification Report

BRE Global Classification Report BRE Global Classification Report Classification of reaction to fire performance in accordance with EN 13501-1: 2007 + A1: 2009 on Vitracore G2 Prepared for: Valcan Limited Date: 12 December 2016 Report

More information

PLEXIGLAS SOUNDSTOP XT BIRD GUARD

PLEXIGLAS SOUNDSTOP XT BIRD GUARD PLEXIGLAS SOUNDSTOP XT BIRD GUARD PLEXIGLAS SOUNDSTOP XT BIRD GUARD Large-size, highly transparent extruded noise barrier sheets with integrated bird protection. Transparent acoustic screens as well as

More information

Calibration service - Central and Eastern Europe

Calibration service - Central and Eastern Europe Calibration service - Central and Eastern Europe Consultation Calibration Test Device Management DAkkS calibration in the Limburg laboratory or on site UKAS calibration eurotherm.de DAkkS calibration (Limburg

More information

C L A S S I F I C A T I O N R E P O R T

C L A S S I F I C A T I O N R E P O R T C L A S S I F I C A T I O N R E P O R T IN ACCORDANCE TO EN 13501-2:2007+A1:2009 Load-bearing slab with a cantilevered balcony slab connected to an Isokorb K50S-CV30-V8-H160 Classification report No.:

More information

BRE Global Test Report

BRE Global Test Report BRE Global Test Report Classification of reaction to fire performance in accordance with EN 13501-1: 2007 + A1: 2009 on Multi-Pro, Multi-Pro XS and Render Pro Prepared for: Resistant Building Products

More information

Measurement of Sound Absorption Coefficient for Perfopan slotted Wall Panels Code No. SLT 7x7-PR 12%, DS 270, on 45 mm mineral wool

Measurement of Sound Absorption Coefficient for Perfopan slotted Wall Panels Code No. SLT 7x7-PR 12%, DS 270, on 45 mm mineral wool DELTA Test Report TEST Reg. no. 100 Measurement of Sound Absorption Coefficient for Perfopan slotted Wall Panels Code No. SLT 7x7-PR 12%, DS 270, on 45 mm mineral wool Client: Aktan Mobilya Fabrikasi,

More information

BS 6853:1999 Annex B.2. Area based toxic fume test used in the design and construction of Passenger Carrying Trains. J. P. Polymer Sheetings Limited

BS 6853:1999 Annex B.2. Area based toxic fume test used in the design and construction of Passenger Carrying Trains. J. P. Polymer Sheetings Limited Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com BS 6853:1999 Annex B.2 Area based toxic

More information

BS 476: Part 7: Method For Classification Of The Surface Spread Of Flame Of Products. WF Report Number: Test Sponsor:

BS 476: Part 7: Method For Classification Of The Surface Spread Of Flame Of Products. WF Report Number: Test Sponsor: BS 476: Part 7: 1997 Method For Classification Of The Surface Spread Of Flame Of Products WF Report Number: 146240 Test Sponsor: Wilhelm Kaimann GmbH & Co. KG Date: 13 th April 2005 Page 2 of 11 Warringtonfire

More information

Additional reaction to fire classification report No K

Additional reaction to fire classification report No K Additional reaction to fire classification report. 16736K Owner of the additional classification report Rokerijweg 5 1271 AH Huizen The Netherlands Introduction This additional classification report defines

More information

NFP Epiradiateur Test. WF Report Number: (Issue 2) Test Sponsor: Fiba Tech Industries Limited. Date of original report:

NFP Epiradiateur Test. WF Report Number: (Issue 2) Test Sponsor: Fiba Tech Industries Limited. Date of original report: NFP 92-501 Epiradiateur Test WF Report Number: 145349 Test Sponsor: Fiba Tech Industries Limited Date of original report: 15 th March 2005 Date of issue 2: 18 th March 2005 Page 2 of 9 Warringtonfire Test

More information

Quality Blanks direct from the Manufacturer

Quality Blanks direct from the Manufacturer Mechanical Applications Division Quality Blanks direct from the Manufacturer Expanded range of colors for translucent zirconium oxide On a long term basis, high quality is the basic requirement to become

More information

This TRANSLATION of the German original is not verified by the MPA NRW.

This TRANSLATION of the German original is not verified by the MPA NRW. This TRANSLATION of the German original is not verified by the MPA NRW. MPA NRW Branch office Erwitte Auf den Thränen 2 59597 Erwitte Tel (02943) 897 33 E-Mail: erwitte@mpanrw.de General building regulation

More information

Sika Elastomer Compression Seals

Sika Elastomer Compression Seals PRODUCT DATA SHEET Sika Elastomer Compression Seals Preformed EPDM elastomer based joint closing and concealing profile strips PRODUCT DESCRIPTION are weather-resistant, EPDM elastomer based, joint covering

More information

GRP Panels. PANOLIT - CPR Plywood core coated on both sides with glassfibre reinforced polyester resin. Thicknesses and Weights

GRP Panels. PANOLIT - CPR Plywood core coated on both sides with glassfibre reinforced polyester resin. Thicknesses and Weights PANOLIT - CPR Plywood core coated on both sides with glassfibre reinforced polyester resin. Thickness in mm 6 11 14 17 20 24 27 30 Weight kg/m 2 CPR 5.5 9.0 9.4 11.2 12.7 16.2 18.5 20.5 Weight kg/m 2 CPRFR

More information

BS 476: Part 7: Method For Classification Of The Surface Spread Of Flame Of Products. A Report To: Ronald Mark Associates Inc

BS 476: Part 7: Method For Classification Of The Surface Spread Of Flame Of Products. A Report To: Ronald Mark Associates Inc Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS 476: Part 7: 1997 Method For Classification

More information

Title: EXTENDED APPLICATION REPORT IN ACCORDANCE WITH EN/TS Notified Body No: 0833 Product Name:

Title: EXTENDED APPLICATION REPORT IN ACCORDANCE WITH EN/TS Notified Body No: 0833 Product Name: Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: EXTENDED APPLICATION REPORT IN

More information

BS 476 Part 3: External Fire Exposure Roof Test. A Report To: Light Weight Tiles Limited. Document Reference: Date: 16 th March 2015

BS 476 Part 3: External Fire Exposure Roof Test. A Report To: Light Weight Tiles Limited. Document Reference: Date: 16 th March 2015 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS 476 Part 3: 2004 External Fire Exposure

More information

Product data. HERADESIGN superfi ne

Product data. HERADESIGN superfi ne Product data Product data Single layer layer magnesite-bonded wood wool acoustic panel (Fibre width 1 mm). With high quality surface structure, building biology recommended. Colour variants The natural

More information

Tensile Testing Services Ltd.

Tensile Testing Services Ltd. Tensile Testing Services Ltd. Unit B1, Smithstown Industrial Estate, Shannon, Co. Clare Testing Laboratory Registration number: 276T is accredited by the Irish National Board (INAB) to undertake testing

More information

Application Note: this form shall only be used by applicants outside the European Economic Area (EEA)

Application Note: this form shall only be used by applicants outside the European Economic Area (EEA) (Will be filled-in by Deutsche Akkreditierungsstelle GmbH (DAkkS)) Case No.: Customer Manager: Incoming date/stamp: Deutsche Akkreditierungsstelle GmbH Central Application Processing (ZAB) Spittelmarkt

More information

Review of Fire Test Report

Review of Fire Test Report Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Review of Fire Test Report A Report To:

More information

BS 476: Part 6: Method Of Test For Fire Propagation For Products. WF Additional Report Number: Date: 18 th February 2008.

BS 476: Part 6: Method Of Test For Fire Propagation For Products. WF Additional Report Number: Date: 18 th February 2008. BS 476: Part 6: 1989 Method Of Test For Fire Propagation For Products WF Additional Report Number: 170998 Date: 18 th February 2008 Test Sponsor: Lindab Limited 0249 Page 2 of 15 Bodycote warringtonfire

More information

ILAC Mutual Recognition Arrangement: Policy and Management ILAC-P4:06/2017

ILAC Mutual Recognition Arrangement: Policy and Management ILAC-P4:06/2017 ILAC Mutual Recognition Arrangement: Policy and Manag ement ILAC-P4:06/ /2017 ILAC International Laboratory Accreditation Cooperation ILAC is the international authority on laboratory, inspection body,

More information

Review of Fire Test Report

Review of Fire Test Report Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Review of Fire Test Report A Report To:

More information

DRAFT - MOCA STANDARD for Fiber-Reinforced Magnesium Cement Board

DRAFT - MOCA STANDARD for Fiber-Reinforced Magnesium Cement Board 1. Scope 1.1 This standard defines the minimum prescriptive quality and performance requirements for Fiberreinforced Magnesium Cement Board products intended for use in buildings in North America. For

More information

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C Date of issue , Updated July 1, 2011

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C Date of issue , Updated July 1, 2011 CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS

More information

Issue AIR-board Panels. Inspired Solutions.

Issue AIR-board Panels. Inspired Solutions. Issue 28 Panels Inspired Solutions. Panels The panels Our unique bonding technology enables us to combine a rigid honeycomb core with transparent thermoplastic top sheets resulting in a panel with exceptional

More information

Issue AIR-board Panels. Inspired Solutions.

Issue AIR-board Panels. Inspired Solutions. Issue 26 Panels Inspired Solutions. Panels The panels Our unique bonding technology enables us to combine a rigid honeycomb core with transparent thermoplastic top sheets resulting in a panel with exceptional

More information

P.O. Box ZN Bleiswijk Brandpuntlaan Zuid NZ Bleiswijk The Netherlands

P.O. Box ZN Bleiswijk Brandpuntlaan Zuid NZ Bleiswijk The Netherlands P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com Determination of the fire resistance according to EN 1364-1:1999 and FprEN 1364-1:2014

More information

P.O. Box ZN Bleiswijk Brandpuntlaan Zuid NZ Bleiswijk The Netherlands

P.O. Box ZN Bleiswijk Brandpuntlaan Zuid NZ Bleiswijk The Netherlands P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com Classification of the fire resistance according to EN 13501-2:2007+ A1:2009

More information

Test Report No. 100/12

Test Report No. 100/12 CENTUM STAVEBNÍHO INŽENÝSTVÍ, a. s. CENTE OF BUILDING CONSTUCTION ENGINEEING, Joint Stock Company workplace Zlín, K Cihelně 304, 764 32 Zlín - Louky Door and window testing laboratory, heat and acoustical

More information

SOUND ABSORBER FOR CHALLENGING ENVIRONMENTS REAPOR. SOUNDPROOFING SOLUTIONS FOR ALL INDUSTRIES pyroteknc.com

SOUND ABSORBER FOR CHALLENGING ENVIRONMENTS REAPOR. SOUNDPROOFING SOLUTIONS FOR ALL INDUSTRIES pyroteknc.com SOUND ABSORBER FOR CHALLENGING ENVIRONMENTS REAPOR SOUNDPROOFING SOLUTIONS FOR ALL INDUSTRIES pyroteknc.com Exceptionally high Noise Reduction Coefficient (NRC) Unique, non-combustible glass-based material

More information

Polymer ST and TEGOPAC. Your solution for innovative silane-modified adhesives and sealants

Polymer ST and TEGOPAC. Your solution for innovative silane-modified adhesives and sealants Polymer ST and TEGOPAC Your solution for innovative silane-modified adhesives and sealants Contents Our Place in the Market 3 4 Silane-Modified Polymers Fascinating Technologies Our Product Portfolio 5

More information

Report VNLF Classification Report

Report VNLF Classification Report Report VNLF 081254.2 Classification Report Applicant KLEEN-TEX Industries in Europa GmbH Münchner Straße 21 6330-Kufstein Austria Reference Ms. Antje Schlegel Application Classification ofthe burning behaviour

More information

Evidence of Performance Thermal transmittance

Evidence of Performance Thermal transmittance Evidence of Performance Test Report No. 15-004068-PR04 (PB 02-K20-06-en-01) Client Product Results OKNOPLUS Sp. z o.o. ul. Zgodna 55 30-444 Kraków - Libertów Poland Plastic profile, profile combination:

More information

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 Q-LAB DEUTSCHLAND GMBH In den Hallen 30 66115 Saarbrücken, Germany Markus Weyland Phone: +49 681 857470 Email: mweyland@q-lab.com Website: www.q-lab.com MECHANICAL

More information

CERTIFICATE No VTT-C Date of issue

CERTIFICATE No VTT-C Date of issue NAME OF PRODUCT CERTIFICATE No VTT-C-9190-12 Date of issue 3.12.2012 CERTIFICATE HOLDER ACTIS SA Avenue de Catalogne 11300 Limoux France MANUFACTURER ACTIS SA PRODUCT DESCRIPTION is a vapour control multifoil

More information

PAROC FIRE PROTECTION SOLUTIONS FOR PIPE PENETRATIONS

PAROC FIRE PROTECTION SOLUTIONS FOR PIPE PENETRATIONS PAROC FIRE PROTECTION SOLUTIONS FOR PIPE PENETRATIONS APPROVED FIRE SAFETY WITH PAROC STONE WOOL EN 1366-3 is a harmonized European standard for fire resistance tests for penetration seals. The test method

More information

EXOVA REPORT TEST REPORT ISSUED BY AN ACCREDITED TESTING LABORATORY

EXOVA REPORT TEST REPORT ISSUED BY AN ACCREDITED TESTING LABORATORY /P-12/110 EXOVA REPORT TEST REPORT ISSUED BY AN ACCREDITED TESTING LABORATORY RESTRICTED DISTRIBUTION DETERMINATION OF THE LONG-TERM HYDROSTATIC STRENGTH ISO 9080:2003-evaluation of the PE-RT pipe grade

More information

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR MINERAL COMPOSITE FIBER REINFORCED (MCFR) BUILDING SYSTEM EC 030-2018 (Proposed November

More information

Title: The Fire Resistance Performance of Modified Timber Based Doorsets. WF Assessment Report No: Issue 2. Prepared for:

Title: The Fire Resistance Performance of Modified Timber Based Doorsets. WF Assessment Report No: Issue 2. Prepared for: assessment report Title: The Fire Resistance Performance of Modified Timber Based Doorsets WF Assessment Report No: 163997 Issue 2 Prepared for: Sauerlander Spanplatten GmbH Postfach 5553 59805 Arnsberg

More information

BRE Global Test Report

BRE Global Test Report BRE Global Test Report BS 476-7: 1997 Surface spread of flame test on K-Flex ST, 50mm Prepared for: L Isolante K-Flex S.p.A. Date: 26 May 2015 Report Number: P100094-1003- BRE Global Ltd Watford, Herts

More information

BS 476: Part 7: Method For Classification Of The Surface Spread Of Flame Of Products. A Report To: Contra Vision. Document Reference:

BS 476: Part 7: Method For Classification Of The Surface Spread Of Flame Of Products. A Report To: Contra Vision. Document Reference: Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Method For Classification Of The Surface

More information

voestalpineaustriadrahtgmbh

voestalpineaustriadrahtgmbh voestalpineaustriadrahtgmbh www.voestalpine.com/austriadraht PRESTRESSING STEEL PRESTRESSING STEEL STRAND BRIGHT Prestressing steel 7 wire strand pren 10138-3 Tensile strength Crosssectional area Mass

More information

the most beautiful...

the most beautiful... Arguably... the most beautiful... Whether replacing your windows, doors or building a conservatory, there can be no better choice than SynerJy. Every section of the SynerJy system incorporates an elegant

More information

BRE Global Test Report

BRE Global Test Report BRE Global Test Report BS 476-7: 1997 Surface spread of flame test on K-Flex ECO + ALU Prepared for: L'Isolante K-Flex S.p.A. Date: 24 April 2015 Report Number: 261123 BRE Global Ltd Watford, Herts WD25

More information

Report VNLF Classification Report

Report VNLF Classification Report Report VNLF 082011.1 Classification Report Applicant EGETAEPPER A/S Industrivej Nord 25 7400-Herning Denmark Reference Lenette Ormstrup Application Classification of burning behaviour according to EN 13501-1.

More information

according to Section 4.2 heroal-johann Henkenjohann GmbH & Co. KG Österwieher Str Verl Germany Window system heroal W65

according to Section 4.2 heroal-johann Henkenjohann GmbH & Co. KG Österwieher Str Verl Germany Window system heroal W65 Test Report Summary and Expert Statement No. 14-002745-PR02 (GAS-A01-04-en-01) for test report 14-002745-PR01 (PB Z06-A01-04-de-02) and 14-002745-PR01 (PB Z08-A01-04-de-02) dated 27 January 2015 Airborne

More information

RD 30 RD 50. Radiation Shielding Glass

RD 30 RD 50. Radiation Shielding Glass RD 30 RD 50 Radiation Shielding Glass 2 SCHOTT is an international technology group with 130 years of ex perience in the areas of specialty glasses and materials and advanced technologies. With our high-quality

More information

DD CEN/TS 1187: 2012 Test 4

DD CEN/TS 1187: 2012 Test 4 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com DD CEN/TS 1187: 2012 Test 4 Incorporating

More information

P.O. Box ZN Bleiswijk Brandpuntlaan Zuid NZ Bleiswijk The Netherlands

P.O. Box ZN Bleiswijk Brandpuntlaan Zuid NZ Bleiswijk The Netherlands P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com Determination of the fire resistance according to EN 1364-1:1999 and FprEN 1364-1:2014

More information

HIRSCH Porozell MODULAR BOARDS FOR UNDERFLOOR HEATING. Expanding with Ideas.

HIRSCH Porozell MODULAR BOARDS FOR UNDERFLOOR HEATING. Expanding with Ideas. MODULAR BOARDS FOR UNDERFLOOR HEATING Expanding with Ideas. Porozell Porozell THE Partner for System Users for Over 25 Years. As a system supplier, develops, produces and sells boards for top-quality radiant

More information

Acoustics Laboratory measurement of sound insulation of building elements. Part 1: Application rules for specific products

Acoustics Laboratory measurement of sound insulation of building elements. Part 1: Application rules for specific products Provläsningsexemplar / Preview INTERNATIONAL STANDARD ISO 10140-1 Second edition 2016-08-15 Acoustics Laboratory measurement of sound insulation of building elements Part 1: Application rules for specific

More information

BS 476: Part 7: Method For Classification Of The Surface Spread Of Flame Of Products. A Report To: Thermaflex International Holding B.V.

BS 476: Part 7: Method For Classification Of The Surface Spread Of Flame Of Products. A Report To: Thermaflex International Holding B.V. Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS 476: Part 7: 1997 Method For Classification

More information

NEW. HALFEN HVG VERSOGRID Installation grid THE VERSATILE FIXING SYSTEM. Benefits at a glance:

NEW. HALFEN HVG VERSOGRID Installation grid THE VERSATILE FIXING SYSTEM. Benefits at a glance: HALFEN HVG VERSOGRID Installation grid THE VERSATILE FIXING SYSTEM NEW Benefits at a glance: Simple and quick installation and removal of the cross elements no bolts required! The VERSOGRID main profiles

More information

ILAC-P10:2002. ILAC Policy on Traceability of Measurement Results

ILAC-P10:2002. ILAC Policy on Traceability of Measurement Results ILAC-P10:2002 ILAC Policy on Traceability of Measurement Results Copyright ILAC 2002 ILAC encourages the authorised reproduction of its publications, or parts thereof, by organisations wishing to use such

More information

É Plaques extrudées. Notre offre Extruded sheet - PMMA Catalogue. Altuglas International manufactures and markets PMMA acrylic sheet:

É Plaques extrudées. Notre offre Extruded sheet - PMMA Catalogue. Altuglas International manufactures and markets PMMA acrylic sheet: É Plaques extrudées Notre offre 2010 - PMMA 2012 Catalogue Altuglas International manufactures and markets PMMA acrylic sheet: Altuglas EX Altuglas EI with enhanced Impact Resistance. The Altuglas EX and

More information

EN Test Report

EN Test Report LGAI LGAI Technological Center, S.A. Campus UAB-Ronda de la Font del Carme, s/n E - 08193 Bellaterra (Barcelona) T +34 93 567 20 00 F +34 93 567 20 01 www.appluslaboratories.com R/F Page 1 Bellaterra:

More information

CERTIFICATE No VTT C Date of issue NAME OF PRODUCT CERTIFICATE HOLDER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE

CERTIFICATE No VTT C Date of issue NAME OF PRODUCT CERTIFICATE HOLDER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE CERTIFICATE No VTT C 594 06 Date of issue 23.5.2006 NAME OF PRODUCT METROBOND, METROSHAKE, METROSHINGLE and METROROMAN metal roofing tiles CERTIFICATE HOLDER Metrotile Europe NV Heersterveldweg 15 3700

More information

STRATOCELL WHISPER FR SOUND ABSORBING FOAM. Product. Scope. Building Regulations. Appraisal No. 949 [2017] Appraisal No. 949 (2017) BRANZ Appraisals

STRATOCELL WHISPER FR SOUND ABSORBING FOAM. Product. Scope. Building Regulations. Appraisal No. 949 [2017] Appraisal No. 949 (2017) BRANZ Appraisals STRATOCELL WHISPER FR SOUND ABSORBING FOAM BRANZ Appraisals Technical Assessments of products for building and construction. Product 1.1 Stratocell Whisper FR is a perforated closed cell laminated polyethylene

More information

DECLARATION OF PERFORMANCE

DECLARATION OF PERFORMANCE EN DECLARATION OF PERFORMANCE according to Annex III of the Regulation (EU) Nr. 305/2011 (Construction Products Regulation) Hilti Firestop Wrap CFS-W No. Hilti CFS 0843-CPD-0103 1. Unique identification

More information

Declaration of Performance (DOP)

Declaration of Performance (DOP) Declaration of (DOP) No. 9174 073 DOP 2015-07-27 1. Unique identification code of the product-type: Multi-wall chimney system type FURADO-F according to 2. Type, batch or serial number or any other element

More information

DAYLIGHT PANELS A WIND AND WATERPROOF SYNTHETIC GLAZING SYSTEM

DAYLIGHT PANELS A WIND AND WATERPROOF SYNTHETIC GLAZING SYSTEM NovaClick 1040 DAYLIGHT PANELS A WIND AND WATERPROOF SYNTHETIC GLAZING SYSTEM PR OJ EC TB OU W NovaClick 1040 daylight panels A wind and waterproof synthetic glazing system NovaClick 1040 is a polycarbonate

More information

FIRE DOORS min

FIRE DOORS min FIRE DOORS 30-120 min Date: 08/03/2013 Page 2 For orders: Tel: +30 22990 47800 Fax: +30 22990 47688 Web: www.safedoor.gr - E-mail: info@safedoor.gr FIRE DOORS 30-120 min - TECHNICAL DESCRIPTION Each door

More information

EMPIRE SHAKE, EMPIRE PLUS SHAKE, AND EMPIRE SLATE POLYOLEFIN COMPOSITE TILES

EMPIRE SHAKE, EMPIRE PLUS SHAKE, AND EMPIRE SLATE POLYOLEFIN COMPOSITE TILES UL Evaluation Report UL ER18920-01 Issued: August 15, 2014 Visit UL s On-Line Certifications Directory: www.ul.com/erdirectory for current status of Report. UL Category Code: ULEX CSI MasterFormat DIVISION:

More information

Revision 1 of EN Changes and News

Revision 1 of EN Changes and News Page A1 Revision 1 of EN 14509 Changes and News Klaus Berner/Ute Pfaff Date: Oct. 2013 Page A2 1 List of in Rev.1 compared to the previous edition. 2 Use of Data obtained from earlier tests 3 Evaluation

More information

FLOOR COVERINGS & ELASTIC LAYERS

FLOOR COVERINGS & ELASTIC LAYERS FLOOR COVERINGS & ELASTIC LAYERS for outdoor areas Protection and safety in sports. UNI outdoor VERSATILE SURFACE FOR OUTDOOR AREAS SPORTEC UNI outdoor is a durable flooring suitable for various types

More information

EN : A1:2015

EN : A1:2015 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com EN 45545-2: 2013 + A1:2015 Summary Test

More information

DD CEN/TS 1187: 2012 Test 4

DD CEN/TS 1187: 2012 Test 4 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com DD CEN/TS 1187: 2012 Test 4 Incorporating

More information

P.O. Box ZN Bleiswijk Brandpuntlaan Zuid NZ Bleiswijk The Netherlands

P.O. Box ZN Bleiswijk Brandpuntlaan Zuid NZ Bleiswijk The Netherlands P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com Determination of the fire resistance according to EN 1364-1:1999 and FprEN 1364-1:2014

More information

Balcony systems. Decorative surfaces and effective protection

Balcony systems. Decorative surfaces and effective protection Balcony systems Decorative surfaces and effective protection Enhancing the enjoyment and safety of exterior living areas Balconies and terraces are general terms used to describe an incredibly wide range

More information

BS EN ISO : 1999

BS EN ISO : 1999 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN ISO 4589-2: 1999 Determination of

More information

ISO INTERNATIONAL STANDARD. Thermal spraying Coatings for protection against corrosion and oxidation at elevated temperatures

ISO INTERNATIONAL STANDARD. Thermal spraying Coatings for protection against corrosion and oxidation at elevated temperatures INTERNATIONAL STANDARD ISO 17834 First edition 2003-12-01 Thermal spraying Coatings for protection against corrosion and oxidation at elevated temperatures Projection thermique Revêtements de protection

More information

Velux Sun Tunnels TWR & TWF

Velux Sun Tunnels TWR & TWF Certification Body: Global-Mark Pty Ltd, Suite 4.07, 32 Delhi Road, North Ryde NSW 2113, Australia Tel: +61 (0)2 9886 0222 - www.global- Mark.com.au Certificate Holder: Velux Australia Pty Ltd 78 Henderson

More information

Title: WF Report No: Prepared for: International Petroleum Products Ltd Bradwell Hall Bradwell-On-Sea Essex CMO 7HX. Date: 24 th August 2015

Title: WF Report No: Prepared for: International Petroleum Products Ltd Bradwell Hall Bradwell-On-Sea Essex CMO 7HX. Date: 24 th August 2015 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The fire resistance performance

More information

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES 1.0 INTRODUCTION INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR COMPOSITE STEEL SHEET AND NONCOMBUSTIBLE SHEATHING PANELS EC 012-2016

More information

CERTIFICATE OF APPROVAL No CF 370 SAMUEL HEATH & SONS PLC

CERTIFICATE OF APPROVAL No CF 370 SAMUEL HEATH & SONS PLC CERTIFICATE OF APPROVAL No CF 370 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Leopold Street, Birmingham,

More information