1 An Experimental Study for the Evaluation of the Environmental Performance by the Application of the Automated Venetian Blind Ji-Hyun Kim 1, Kyoung-Wn Yang 1, Young-Joon Park 1, Kyung-Hee Lee 2, Myoung-Souk Yeo 3 and Kwang-Woo Kim 3 1 Department of Architecture, Graduate School of Seoul National University, Korea 2 Department of Architecture Engineering, College of Natural Resource and Life Sciences, Pusan National University 3 Department of Architecture, Seoul National University, Korea Corresponding snukkw@snu.ac.kr SUMMARY Venetian blind can have a major impact on building energy use and occupant's comfort. But manual or motorized Venetian blind has limitations in meeting occupant s needs and in reducing energy consumption. These limitations can be overcome by the automatic control of the Venetian blind. This study aims to analyze the control method of commercially used automated Venetian blind and to evaluate the environmental performance of this type of blind. The environmental performance of an automated Venetian blind was evaluated by a real-scale experiment and occupant s response in summer. The enhancement of environmental performance by the application of an automated Venetian blind was confirmed. 1. INTRODUCTION Recently, cooling loads through the building envelope has greatly increased with the increase of glass area in office buildings in Korea. Windows provide occupants with daylight, direct sunlight, visual contact with the outside and a feeling of openness. While it is desirable to introduce sunlight for natural lighting over a given constant level, the radiation heat of the sun has to be determined to allow its entrance or not according to the weather conditions. The radiation heat from the sun reduces the heating load in the winter season but increases the cooling load during the summer season. Due to the characteristics of solar energy, which is comprised of light and heat, solar energy is not easy to control; that is, daylight introduction and excessive heat isolation have to be considered at the same time. In addition, excessive sunlight will cause glare problems in an office space, which are a major complaint by occupants. These glare problems must also be taken into consideration. In office buildings, since the reduction of the opening ratio and the design of the windows orientation are restricted from the design perspective, Venetian blinds are generally used to control the incoming solar radiation. Venetian blinds are better than roll blinds because they can be controlled to slat angle as well as to occlusion index. Venetian blinds can greatly affect building energy use and occupant comfort, so it is important to control Venetian blinds properly according to the change of the external weather condition for enhancement of indoor environment. But previous studies have shown that in reality, occupants rarely change the position of the manual or motorized Venetian blind [1] [2] [3] [4] [5] [6] [7]. The manual or motorized Venetian blind has limitations in meeting occupant s needs and in reducing energy consumption. To overcome these limitations, the Venetian blind must be controlled automatically. The use of the automated Venetian blind,

2 controlled automatically by sensors according to the external weather condition, would be more effective than the manual or motorized Venetian blind. During times of peak solar gain, such a blind can reduce cooling loads and overheating. Under cloudy conditions, or in winter, it can be withdrawn to allow daylight and useful solar gains to enter the building, so that the building can reduce its dependence on electric lighting and heating requirement. To achieve this condition, the blind should be properly controlled. Otherwise, unwanted solar gain may enter the building and increase the cooling load. Occupants may experience glare from the sun and be unable to operate the shading to alleviate it. This study aims to analyze the control method of the commercially used automated Venetian blind and to evaluate its environmental performance in comparison to the manual or motorized Venetian blind. The environmental performance of the automated Venetian blind was evaluated by a real-scale experiment and occupant s response in summer. Finally, the potential of energy savings and comfort enhancement by use of the automatic control was confirmed. 2. BLIND TYPE AND OPERATION SURVEY A blind can be categorized into manual, motorized and automated according to its control method. The manual blind is the simplest type of blind without a motorized device. It is controlled directly by the occupant and used generally in modern buildings. But the occupants control the manual blind only when they feel discomfort [8]. In fact, manual blind control has problems because occupants do not control the blind until they feel discomfort such as glare and solar radiation. The motorized blind that can be controlled by a remote controller, and in some buildings, computer are used to control motorized blinds. Though the motorized blind can be controlled easier than the manual blind, it is operated inefficiently in real situations. According to the operation survey of actual motorized blinds, though it is able to control the motorized blind in central control room, central control is not used by the occupants need and 82.6% of all motorized blinds do not move, as shown in Tables 1 and 2. Also, the occlusion index of the stopped blind is usually, almost opened (0 ~ 20%) or closed (80 ~ 100%), as shown in Table 3. An automated blind is automatically controlled by sensors according to the external weather condition to enhance environmental performance. A motorized blind requires higher initial cost than a manual blind but does not produce better environmental performance. Therefore, the application of automated blind is necessary. Table 1. Outline of survey building City, County Number of floors Sky condition Seoul, Korea 22 Cleary sky(2 days) Overcast sky(2 days) Table 2. Frequency of blind operation. (South orientation) Frequency Number Percentage(%) Total Table 3. Occlusion index of blind. (Frequency 0) Occlusion index(%) Number Percentage(%) 0 ~ ~ ~ Total

3 3. EVALUATION EXPERIMENT ON ENVIRONMEMTAL PERFORMANCE BY AUTOMATED BLIND 3.1 Outline The effects of commercially used automated blind on thermal and visual environment performance and comfort are compared with those of conventional manually operated blinds. The product specification of an automated blind used in this experiment is presented in Tables 4 ~ 6. In the test room, located on the top floor of a building in Seoul National University, Korea, evaluation experiments were conducted to measure the energy saving effect and occupant comfort enhancement for the month of August Two test rooms of dimensions 5.8m x 4.8m x 2.7m with the same architectural planning were used to reproduce the same conditions. Each room was equipped with an internal Venetian blind of same material and color, and the blind in one room was manually controlled and that in the other room automatically controlled, as shown in Figure 1 and 2. Various instruments were installed inside and outside the rooms to measure and analyze the various environments, as presented in Table 7. Table 4. Product specification of the automated blind Blind Sensor Operation mode Aluminum(gray) Slat width : 50mm Sun sensor (Outdoor vertical illuminance sensing) Energy saving mode(see Table 5) Comfort mode(see Table 6) Table 5. Operation sequence of energy saving mode. Control conditions Operation at ON ON OFF Control time Operation at OFF Exterior Exterior Occlusion delay delay Slat angle Illuminance Illuminance index 09:00 ~ 18:00 16 klux 3 min. 15 klux 15 min 100% 90 Completely open Table 6. Operation sequence of comfort mode. Control conditions ON OFF Control time Exterior Exterior delay Illuminance Illuminance Operation at ON delay Occlusion index 09:00 ~ 10:30 25 klux 3 min. 15 klux 15 min 100% 45 10:30 ~ 12:00 25 klux 3 min. 15 klux 15 min 100% 30 12:00 ~ 13:00 16 klux 3 min. 15 klux 15 min 100% 90 13:00 ~ 13:45 25 klux 3 min. 15 klux 15 min 100% 30 13:45 ~ 18:00 25 klux 3 min. 15 klux 15 min 100% 45 Slat angle Operation at OFF Completely open Figure 1. Plan view of test rooms.

4 Figure 2. External view of test rooms. Table 7. Measuring equipments. Equipment Interior illuminance Daylight factor meter, Lux meter Room temperature T-type thermocouple Outdoor temperature T-type thermocouple Solar radiation Irradiance meter Exterior illuminance Exterior lux meter Position Room 1, Room 2 Room 1, Room 2 Outside Roof(Outside) Roof(Outside) 3.2 Method In order to investigate the effect of the automated blind on the environmental performances of the rooms in the summer season, experiments were conducted for four cases, as presented in Table 8. In test room 1, the energy saving mode and comfort mode, which were controlled by an outdoor illuminance sensor, were selected. When in the energy saving mode, it was set up to shut out the solar radiation at the maximum level within the control range (see Table 5), and in the comfort mode, the slat angle was controlled to cut off direct daylight (although allowing some daylight to enter), in consideration of the working hours of the occupants and the comfort factor (see Table 6). Table 8. Experiment cases. Case Test room 1 Test room 2 Air-conditioned Remarks 1 Completely open Energy saving mode 2 Completely close ⅹ Evaluate energy consumption 3 Completely open Comfort mode 4 Motorized* Evaluate comfort * Occlusion index 75%, Slat angle: 90 For the set up of the compared blind, three model cases were selected, in which the blind was completely open (occlusion index: 0%), the blind was completely close (occlusion index: 100%, Slat angle: 90 ), and the blind was motorized (occlusion index: 75%, Slat angle: 90 ), respectively. The latter case represented the results of the blind operation survey. In cases 1 and 2, the characteristics of automatic control in terms of energy consumption in comparison with those of the extreme case of manual control were verified by comparing temperature and workplace illuminance. In cases 3 and 4, the conditions (with and without automatic control) were compared by PMV measurement and workplace illuminance, and a questionnaire was conducted four times per day(10:00, 12:00, 14:00, 16:00) to investigate their characteristics with regard to comfort. For each case, the experiments were conducted from 09:00 AM to 18:00 PM, without artificial lighting.

5 4. EXPERIMENT RESULT AND DISCUSSION 4.1 Case 1 : energy saving mode vs. completely open Case 1 was conducted on August 12th. On this day, the sky was fairly clear but became rather cloudy from 13:00 ~ 14:00. The temperature of the interior zone of the test room is shown in Figure 3 a). The temperature in test room 2 was higher than that of test room 1. Because solar radiation was effectively shut out in the energy saving mode, the temperature in test room 1 was lower than test room 2 by a maximum of 1.0. For the perimeter zone, which is directly subject to solar radiation, the temperature difference was greater. In Figure 3 b), the perimeter zone temperature of test room 1 was lower than that of test room 2 by a maximum of 2.7. Temperature [ ] Difference [ ] a) Interior zone b) Perimeter zone Figure 3. Temperature profile of case 1. In conclusion, the rise in room temperature was effectively reduced by the automated blind. In particular, in the perimeter zone, the automated blind effectively shut out solar radiation to reduce temperature rise. Especially, on clear summer day, the cooling load by the excessive solar radiation can be minimized through the appropriate automatic control of blind. 4.2 Case 2 : energy saving mode vs. completely close Case 2 was conducted on August 16th. The sky was cloudy all day. There was little temperature difference between the two test rooms. Therefore, though the blind was fully opened a few times during the experimental period in response to the external weather condition, the cooling load of test room 1 was slightly higher than that of test room 2, but the lighting energy of test room 1 could be saved by introducing daylight. The room depth meeting the required illuminance profile at the workplace in the two test rooms are shown in Figure 4. Compared to test room 2(completely close), which needed artificial lighting on whole day, test room 1 could satisfy the illuminance criteria( 500lux) during most of the experiment period without artificial lighting because daylight was introduced. So the lighting energy of test room 2 was saved. Consequently, the overall energy consumption, including cooling and lighting energy consumption, could be reduced by using the automated blind. In addition, the automated blind provided an open field of vision and a view of the outside scenery.

6 4.0 Test Room 1 Test Room 2 Room Depth Meeting Required Illuminance [m] :00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 OFF ON OFF ON OFF (0%) (100%) (0%) (100%) (0%) Room 1 Control Room 2 Control Completely Close (100%) a) Room depth within satisfied range b) Workplace illuminance profile Figure 4. Analysis of the satisfied range and measured workplace illuminance of case Case 3 : comfort mode vs. completely open Case 3 was conducted in August. The sky was clear. A representative comfort indicator PMV was measured in two test rooms to determine the degrees of comfort of the two test rooms, as shown in Figure 5. In the interior zone, since both rooms were air-conditioned continuously and the PMV meter was installed away from the influence of solar radiation, the difference in the measured values was insignificant, and largely satisfied with the comfort criteria (-0.5 < PMV < +0.5) of the ISO. However, in the perimeter zone, which is directly subject to the influence of solar radiation, the PMV measured in test room 2 remained constant between 1.2 and 1.6, which indicated a discomfort environment. However, the PMV in test room 1 fell by about 0.5 at 10:30 when the blind began to be controlled, and as a result, enhanced the degree of comfort. a) Interior zone b) Perimeter zone Figure 5. PMV profile of case 3. With respect to the overall operation of the blind, 87.5% of the subjects in test room 1 were satisfied, while 62.5% of those in test room 2 were dissatisfied due to the rise in temperature resulting from solar radiation as shown in Figure 6 a). With respect to workplace illuminance, both test rooms showed illuminance of higher than 500lux during entire experiment period, but in test room 2, the illuminance exceeded the recommended upper limit (3,340lux [9]) during most of the experiment period as shown in Figure 6 b). Test room 1, which was operated in the comfort mode, was maintained within the recommended value because slat angle was controlled to cut off direct sunlight but allow daylight to flow in. Since the experiment had been conducted during a period of hot weather and clear sky, solar radiation must have had great impact on the result. Consequently, the degree of direct radiation and direct light should be appropriately controlled with a blind to protect the occupants from glare and to improve comfort.

7 a) Overall satisfaction b) Illuminance profile Figure 6. Subject response and illuminance profile at workplace of case Case 4 : comfort mode vs. motorized The experiment was conducted on August 29th, a cloudy day with rainfall starting from the late afternoon. Motorized blind condition was determined based on the operation survey results. Since the weather was cloudy and no significant influence from solar radiation was likely to be felt, no significant difference of PMV was observed due to the constant air conditioning, and the ISO comfort criteria were largely satisfied in both interior and perimeter zones. With respect to the overall operation of the blind, subjects in test room 1 were satisfied since optimal illuminance could be obtained by automatic control, while subjects in test room 2 were dissatisfied with the brightness, since the blind kept shutting out the daylight greatly during the cloudy weather as shown in Figure 7 a). With respect to workplace illuminance, test room 1 showed illuminance of higher than 500lux during most of the experimental period, but test room 2 under 500lux, as shown in Figure 7 b). Test room 1 was able to introduce more daylight by automatic control of the blind reflecting the outdoor weather condition. Room 1 Perimeter Room 1 Interior Room 2 Perimeter Room 2 Interior Outdoor 12,000 50,000 10,800 45,000 9,600 40,000 8,400 7,200 6,000 4,800 3,600 2,400 Upper Limit of Illuminance 35,000 30,000 25,000 20,000 15,000 10, :00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 a) Overall satisfaction b) Illuminance profile Figure 7. Subject response and illuminance profile at workplace of case 4. 1,200 Room 1 Control Off (0%) Off 5,000

8 Based on the questionnaire and measurements, visual comfort could be improved without additional lighting by introducing daylight selectively with the automated blind in accordance with the prevailing weather conditions. Additionally, it was judged that an open field of vision could be provided by automatic control. 5. CONCLUSION In this study, control methods of commercially used automated Venetian blind were analyzed and improvement effects of environmental performance were proven through the experiments on energy saving and comfort. In the energy saving mode, cooling load was reduced more than that with the fully opened window because blind blocked solar radiation according to established conditions under the clear sky condition. In overcast sky, the blind allows daylight to enter according to established conditions and so it can reduce the lighting energy and minimize the cooling load increase, simultaneously. In the energy saving mode, in which the blind is only fully opened or closed, the modification of the occlusion index and slat angle is not considered. Therefore, we need a control method that can consider the lighting and cooling energy saving simultaneously by proper control of the occlusion index and slat angle. In the comfort mode, the slat angle is controlled to cut off direct sunlight and this reduces the discomfort from excessive solar radiation and direct sunlight. Also, in this mode, daylight can be introduced to supply a feeling of openness to the occupant. Because modification of the occlusion index is not considered and modification of slat angle is limited to two times per day in the comfort mode, a more detailed and delicate control method which can consider the control of occlusion index is necessary. The control method discussed in this paper is operated only through external weather condition sensing. But the purpose of blind control is to improve indoor environment, so a more effective and enhanced control method which can reflect indoor environment needs to be developed by sensing internal factors such as workplace illuminance, indoor temperature etc. REFERENCES 1. Rubin, A I, Collins, B L, and Tibbott, R L Window blinds as a potential energy saver a case study. NSB Building Science Series Vol National Institute for Standards and Technology. 2. Rea, M Window blind occlusion: a pilot study. Building and Environment. Vol. 19 (2), pp Foster, M and Oreszczyn, T Occupant control of passive systems: the use of Venetian blinds. Building and Environment. Vol. 36 (2), pp Reinhart, C F and Voss, K Monitoring manual control of electric lighting and blinds. Lighting Research and Technology. Vol. 35 (3), pp Lindsay, C T R and Littlefair, P J Occupant use of Venetian blinds in offices. Building Research Establishment contract PD233/ Rea, M S, Rutledge, B and Maniccia, D Beyond daylight dogma, Proceedings of the Daylighting 98 Conference, ON: Natural Resources Canada, pp Escuyer, S and Fontoynont, M Lighting controls: a field study of office workers reactions. Lighting Research and Technology. Vol. 33 (2), pp Inoue, T, Kawase, T, Ibamoto, T, et al The development of an optimal control system for window shading devices based on investigations in office buildings. ASHRAE Transactions. Vol. 94, pp IESNA IESNA Lighting Handbook. Illuminating Engineering Society of North America.

additional cooling energy consumption. Because the thermal resistance of windows has always been a weak point, even with vacuum glass or low-e glass,

additional cooling energy consumption. Because the thermal resistance of windows has always been a weak point, even with vacuum glass or low-e glass, Simulation Study of Automated Blinds Control Strategy for Minimizing Cooling and Lighting Energy Consumptions L. Xiao 1, F. Wang 2,*, Y. Gao 2, T. Gong 2, Y. Di 2, Y. Qian 2, and X. Luo 2 1 School of Mechanical

More information

Analysis of Indoor Luminous Environment and Power Generation by Roll Screen and Venetian Blind with PV Modules

Analysis of Indoor Luminous Environment and Power Generation by Roll Screen and Venetian Blind with PV Modules European Journal of Sustainable Development (2017), 6, 4, 302-308 ISSN: 2239-5938 Doi: 10.14207/ejsd.2017.v6n4p302 Analysis of Indoor Luminous Environment and Power Generation by Roll Screen and Venetian

More information

SPLIT CONTROLLED BLINDS AS A THERMAL AND DAYLIGHTING ENVIRONMENTAL CONTROL SYSTEM

SPLIT CONTROLLED BLINDS AS A THERMAL AND DAYLIGHTING ENVIRONMENTAL CONTROL SYSTEM SPLIT CONTROLLED BLINDS AS A THERMAL AND DAYLIGHTING ENVIRONMENTAL CONTROL SYSTEM Svetlana OLBINA Ph.D. 1 Keywords: automated blinds, illuminance, energy savings, computer simulations Abstract Commercially

More information

OPENING DESIGN TO IMPROVE THE NATURAL VENTILATION PERFORMANCE OF HIGH-RISE RESIDENTIAL BUILDINGS

OPENING DESIGN TO IMPROVE THE NATURAL VENTILATION PERFORMANCE OF HIGH-RISE RESIDENTIAL BUILDINGS OPENING DESIGN TO IMPROVE THE NATURAL VENTILATION PERFORMANCE OF HIGH-RISE RESIDENTIAL BUILDINGS Cho Rong Kim 1, Ga Young Cho 1, Sun Woo Lee 1, Myoung Souk Yeo 2, and Kwang Woo Kim 2 1 Department of Architecture,

More information

An enhancement of the daylighting from side-window using two-section venetian blind

An enhancement of the daylighting from side-window using two-section venetian blind An enhancement of the daylighting from side-window using two-section venetian blind Vichuda Mettanant 1,2, Pipat Chaiwiwatworakul 1,2,*, Pattana Rakkwamsuk 3 1 The Joint Graduate School of Energy and Environment,

More information

Automating the Balance of Energy Performance with Occupant Comfort with Smart Fenestrations

Automating the Balance of Energy Performance with Occupant Comfort with Smart Fenestrations College of Engineering Dept. of Civil Construction and Environmental Engineering Automating the Balance of Energy Performance with Occupant Comfort with Smart Fenestrations Dr. Kristen Cetin, P.E., LEED

More information

Design and retrofitting of a hybrid building in Athens

Design and retrofitting of a hybrid building in Athens International Conference Passive and Low Energy Cooling 597 Design and retrofitting of a hybrid building in Athens A. Gavalas Gavalas Architects, Athens ABSTRACT This paper s aim is to present a building

More information

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Available online at   ScienceDirect. Energy Procedia 78 (2015 ) Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 2857 2862 6th International Building Physics Conference, IBPC 2015 Optimized Blind Control Method to minimize Heating,

More information

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016 Aalborg Universitet CLIMA 2016 - proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols Publication date: 2016 Document Version Publisher's PDF, also known as Version of record Link to publication

More information

The effect of shading design and control on building cooling demand

The effect of shading design and control on building cooling demand International Conference Passive and Low Energy Cooling 953 for the Built Environment, May 25, Santorini, Greece The effect of shading design and control on building cooling demand A. Tzempelikos and A.K.

More information

Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France

Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France Sylvain Boulet 1, Stéphanie Armand-Decker 2, FCBA Technological Institute I2M-TREFLE laboratory -

More information

SAGEGLASS VARIABLE TINTED GLAZING INPUT SHEET FOR DIAL+ SOFTWARE

SAGEGLASS VARIABLE TINTED GLAZING INPUT SHEET FOR DIAL+ SOFTWARE SAGEGLASS VARIABLE TINTED GLAZING INPUT SHEET FOR DIAL+ SOFTWARE V1 dated 21/04/2017 The following procedure describes data input and handling for SageGlass in DIAL+ natural lighting and thermal dynamic

More information

A Study on the Variation of Heating & Cooling Load by the Various Shading and Performance of Window in Office Buildings Seok-Hyun Kim 1, Kyung-ju Shin

A Study on the Variation of Heating & Cooling Load by the Various Shading and Performance of Window in Office Buildings Seok-Hyun Kim 1, Kyung-ju Shin A Study on the Variation of Heating & Cooling Load by the Various Shading and Performance of Window in Office Buildings Seok-Hyun Kim 1, Kyung-ju Shin 1, Bo-eun Choi 1, Jae-Hun Jo 2, Young-Hum Cho 3, Soo

More information

COOLING LOADS AND OCCUPANT COMFORT IN HIGHLY GLAZED BUILDINGS AND THE EFFECTIVE EVALUATION OF WINDOW RETROFITS

COOLING LOADS AND OCCUPANT COMFORT IN HIGHLY GLAZED BUILDINGS AND THE EFFECTIVE EVALUATION OF WINDOW RETROFITS COOLING LOADS AND OCCUPANT COMFORT IN HIGHLY GLAZED BUILDINGS AND THE EFFECTIVE EVALUATION OF WINDOW RETROFITS S. Armstrong ABSTRACT Urban centres contain thousands of mid to late 20th century commercial,

More information

A Study on Thermal Environment and the Design Methods to Save Energy in Small Glass-Skin Commercial Buildings

A Study on Thermal Environment and the Design Methods to Save Energy in Small Glass-Skin Commercial Buildings A Study on Thermal Environment and the Design Methods to Save Energy in Small Glass-Skin Commercial Buildings 1 and Kwangho Kim* 2 1 Professor, Department of Architectural Engineering, Yonsei University,

More information

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates Kittitach Pichatwatana, and Fan Wang Abstract This paper examines the TAS computer

More information

Energy Saving Benefits of Daylighting Combined with Horizontal Exterior Overhangs in Hot-and-Humid Regions

Energy Saving Benefits of Daylighting Combined with Horizontal Exterior Overhangs in Hot-and-Humid Regions Energy Saving Benefits of Daylighting Combined with Horizontal Exterior Overhangs in Hot-and-Humid Regions Speakers: Huang, Kuo-Tsang 1 ; Fu, Chun 2 1 Department of Bioenvironmental Systems Engineering,

More information

STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS

STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS 1. ABSTRACT In modern architecture the buildings are often designed with large glass facades or windows. Due to these

More information

COMPARATIVE EVALUATION OF SIDE-DAYLIGHTING STRATEGIES

COMPARATIVE EVALUATION OF SIDE-DAYLIGHTING STRATEGIES COMPARATIVE EVALUATION OF SIDE-DAYLIGHTING STRATEGIES Michael J. Holtz, FAIA LightLouver LLC 685 S. Arthur Avenue Louisville, Colorado 80027 mholtz@lightlouver.com Zack Rogers, PE, IESNA LightLouver LLC

More information

THE ENERGY EFFECTS OF CONTROLLING SOLAR SHADING

THE ENERGY EFFECTS OF CONTROLLING SOLAR SHADING somfy.com THE ENERGY EFFECTS OF CONTROLLING SOLAR SHADING Dr Paul Littlefair - Environmental Consultancy Centre - BRE Jose Ortiz and Claire Das Bhaumik - Sustainable Energy Centre - BRE SOMFY SAS, capital

More information

306: Sustainable Daylighting Design in Southern Europe

306: Sustainable Daylighting Design in Southern Europe 306: Sustainable Daylighting Design in Southern Europe A. J. Santos 1 *, L. C. Carvalho 2, A. Moret Rodrigues 3, C.A. Pina dos Santos 4 Laboratório Nacional de Engenharia Civil - LNEC-DED/NAICI, Lisbon,

More information

IMPROVING THE HUMAN EXPERIENCE IN THE BUILT ENVIRONMENT

IMPROVING THE HUMAN EXPERIENCE IN THE BUILT ENVIRONMENT IMPROVING THE HUMAN EXPERIENCE IN THE BUILT ENVIRONMENT SageGlass tints automatically to control daylight and solar heat, making it easier for architects to design sustainable, visually compelling buildings

More information

Making the working environment in offices more comfortable

Making the working environment in offices more comfortable Making the working environment in offices more comfortable Offices are now places where most employees spend the majority of their working hours. So it is essential that they are designed and built to

More information

Daylight Factor Analysis with Slat Angle Control for Glare Reduction in a Three Storied Office Building

Daylight Factor Analysis with Slat Angle Control for Glare Reduction in a Three Storied Office Building Daylight Factor Analysis with Slat Angle Control for Glare Reduction in a Three Storied Office Building *Badri Narayan Mohapatra, **Dr. M. Ravi Kumar ***Dr. Susanta Kumar Mandal, ****Rashmita Kumari Mohapatra

More information

Problem statement Definition and concepts Research model and methods Climate-responsive categorization Summary. Contents.

Problem statement Definition and concepts Research model and methods Climate-responsive categorization Summary. Contents. Contents Problem statement Definition and concepts Research model and methods Climate-responsive categorization Summary Problem statement Highly conditioned buildings VS. Climateresponsive buildings Building

More information

Effect of a Window Shade on Home Energy Use

Effect of a Window Shade on Home Energy Use University of Nebraska - Lincoln DigitalCommons@University of Nebraska - Lincoln Environmental Studies Undergraduate Student Theses Environmental Studies Program Fall 2015 Effect of a Window Shade on Home

More information

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya (vahid.vakiloroaya@engineer.com) ABSTRACT: The overall attainable reduction in energy consumption and enhancement of

More information

Comparative Performance of Internal Venetian Blind and Roller Blind with Respects to Indoor Illumination Levels

Comparative Performance of Internal Venetian Blind and Roller Blind with Respects to Indoor Illumination Levels Available online at www.sciencedirect.com ScienceDirect Procedia - Social and Behavioral Scien ce s 101 ( 2013 ) 542 553 AicQoL 2013 Langkawi AMER International Conference on Quality of Life Holiday Villa

More information

An assessment tool for selection of appropriate daylight solutions for buildings in tropical and subtropical regions:

An assessment tool for selection of appropriate daylight solutions for buildings in tropical and subtropical regions: An assessment tool for selection of appropriate daylight solutions for buildings in tropical and subtropical regions: Validation using radiance simulation Veronica Garcia-Hansen Gillian Isoardi, Michael

More information

Daylight has been a primary source of lighting in buildings. Daylighting improve indoor environmental quality and visual comfort. Moreover, it reduces

Daylight has been a primary source of lighting in buildings. Daylighting improve indoor environmental quality and visual comfort. Moreover, it reduces Effect of Window on Building Energy Performance and Indoor Environmental Quality T. Aker 1, C. Deniz 2, A. Tabancacı 3 and M.S. Mert 4 1 Energy Institute, Istanbul Technical University, Istanbul, Turkey,

More information

The potential of simplified concepts for daylight harvesting

The potential of simplified concepts for daylight harvesting The potential of simplified concepts for daylight harvesting Short Title for Running Head: Simplified concepts for daylight harvesting R Leslie MArch a, R Raghavan MS a, O Howlett MA, MSc a*, C Eaton BA

More information

Solar Shading System Based on Daylight Directing Glass Lamellas

Solar Shading System Based on Daylight Directing Glass Lamellas Solar Shading System Based on Daylight Directing Glass Lamellas Jacob B. Laustsen, Assistant Research Professor, Department of Civil Engineering, Technical University of Denmark; jbl@byg.dtu.dk Inês D.

More information

Comparing Whole Building Energy Implications of Sidelighting Systems with Alternate Manual Blind Control Algorithms

Comparing Whole Building Energy Implications of Sidelighting Systems with Alternate Manual Blind Control Algorithms Buildings 2015, 5, 467-496; doi:10.3390/buildings5020467 OPEN ACCESS buildings ISSN 2075-5309 www.mdpi.com/journal/buildings/ Article Comparing Whole Building Energy Implications of Sidelighting Systems

More information

The energy benefits of View Dynamic Glass

The energy benefits of View Dynamic Glass Workplace demonstration Energy monitoring over a period of 12 months resulted in the commercial office room installed with View Dynamic Glass saving 39 percent of the total energy consumed compared to

More information

A STUDY OF DAYLIGHTING TECHNIQUES AND THEIR ENERGY IMPLICATIONS USING A DESIGNER FRIENDLY SIMULATION SOFTWARE

A STUDY OF DAYLIGHTING TECHNIQUES AND THEIR ENERGY IMPLICATIONS USING A DESIGNER FRIENDLY SIMULATION SOFTWARE A STUDY OF DAYLIGHTING TECHNIQUES AND THEIR ENERGY IMPLICATIONS USING A DESIGNER FRIENDLY SIMULATION SOFTWARE Amarpreet Sethi College of Architecture and Environmental Design Arizona State University,

More information

Work Package 2: Performance of naturally ventilated buildings

Work Package 2: Performance of naturally ventilated buildings Work Package 2: Performance of naturally ventilated buildings Detailed Monitoring Report BRF-kredit Headquarters (DK2) Niels C. Bergsøe Danish Building Research Institute, SBI Energy and Indoor Climate

More information

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 2 Heiselberg, Per Kvols. Publication date: 2016

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 2 Heiselberg, Per Kvols. Publication date: 2016 Downloaded from vbn.aau.dk on: januar 28, 2019 Aalborg Universitet CLIMA 2016 - proceedings of the 12th REHVA World Congress volume 2 Heiselberg, Per Kvols Publication date: 2016 Document Version Publisher's

More information

Article Control of Thermally Activated Building System Considering Zone Load Characteristics

Article Control of Thermally Activated Building System Considering Zone Load Characteristics Article Control of Thermally Activated Building System Considering Zone Load Characteristics Woong June Chung 1, Sang Hoon Park 2, Myoung Souk Yeo 3 and Kwang Woo Kim 4, * 1 Department of Architecture

More information

FIELD SUMMER PERFORMANCE OF INTERIOR REFLECTIVE SCREEN SHADES FOR RESIDENTIAL WINDOWS

FIELD SUMMER PERFORMANCE OF INTERIOR REFLECTIVE SCREEN SHADES FOR RESIDENTIAL WINDOWS Eleventh International IBPSA Conference Glasgow, Scotland July 27-3, 29 FIELD SUMMER PERFORMANCE OF INTERIOR REFLECTIVE SCREEN SHADES FOR RESIDENTIAL WINDOWS A.D. Galasiu, A. Laouadi *, M.M. Armstong,

More information

Satyen Mukherjee, Dagnachew Birru, Dave Cavalcanti, Eric Shen, Maulin Patel, Yao-Jung Wen, and Sushanta Das, Philips Research North America

Satyen Mukherjee, Dagnachew Birru, Dave Cavalcanti, Eric Shen, Maulin Patel, Yao-Jung Wen, and Sushanta Das, Philips Research North America Closed Loop Integrated Lighting and Daylighting Control for Low Energy Buildings Satyen Mukherjee, Dagnachew Birru, Dave Cavalcanti, Eric Shen, Maulin Patel, Yao-Jung Wen, and Sushanta Das, Philips Research

More information

SKYLIGHT DESIGN PERFORMANCE EVALUATION METHOD DEVELOPMENT WITH THERMAL AND DAYLIGHT SIMULATION

SKYLIGHT DESIGN PERFORMANCE EVALUATION METHOD DEVELOPMENT WITH THERMAL AND DAYLIGHT SIMULATION SKYLIGHT DESIGN PERFORMANCE EVALUATION METHOD DEVELOPMENT WITH THERMAL AND DAYLIGHT SIMULATION Xianou Li, Frederick Wong, and Yihan Li Arup International Consultants (Shanghai) Co Ltd ABSTRACT This paper

More information

DAYLIGHTING PERFORMANCE OF TOPLIGHTING SYSTEMS IN THE HOT AND HUMID CLIMATE OF THAILAND

DAYLIGHTING PERFORMANCE OF TOPLIGHTING SYSTEMS IN THE HOT AND HUMID CLIMATE OF THAILAND DAYLIGHTING PERFORMANCE OF TOPLIGHTING SYSTEMS IN THE HOT AND HUMID CLIMATE OF THAILAND Siritip Harntaweewongsa and Liliana O. Beltrán, Ph.D. Texas A&M University College of Architecture College Station,

More information

Chapter 7. Passive Solar Contents

Chapter 7. Passive Solar Contents Chapter 7. Passive Solar Contents 7.1 Introduction 7.2 Types of Passive Solar Systems 7.3 Advantages and Disadvantages 7.4 General Design Principles 7.5 Design Information for Direct System 7.6 Design

More information

A Case Study on the Daylighting and Thermal Effects of Fixed and Motorized Light Louvers

A Case Study on the Daylighting and Thermal Effects of Fixed and Motorized Light Louvers A Case Study on the Daylighting and Thermal Effects of Fixed and Motorized Light Louvers Yuxiang Chen 1, Samson Yip 1, Andreas Athienitis 1 1 Building, Civil and Environmental Engineering, Concordia University,

More information

ADVANCED FAÇADES AND HVAC SYSTEMS: PRELIMINARY RESULTS OF FULL-SCALE MONITORING

ADVANCED FAÇADES AND HVAC SYSTEMS: PRELIMINARY RESULTS OF FULL-SCALE MONITORING ADVANCED FAÇADES AND HVAC SYSTEMS: PRELIMINARY RESULTS OF FULL-SCALE MONITORING M. Kragh, M. Colombari and M. Zobec Permasteelisa Group, Research & Engineering, 31020 San Vendemiano (TV), Italy www.permasteelisa.com,

More information

Assessment of Indoor Climate: Learning from Buildings

Assessment of Indoor Climate: Learning from Buildings Roomvent 27: 1 th International Conference on Helsinki, June 1-15, 27 Assessment of Indoor Climate: Learning from Buildings Outdoor climate Edward Arens Center for the Built Environment UC Berkeley Indoor

More information

Daylight, Solar Gains and Overheating Studies in a Glazed Office Building

Daylight, Solar Gains and Overheating Studies in a Glazed Office Building Issue 2, Volume 2, 2008 129 Daylight, Solar Gains and Overheating Studies in a Glazed Office Building Hasim Altan, Ian Ward, Jitka Mohelníková, František Vajkay Abstract The Glazed envelopes represent

More information

Ventilated Illuminating Wall (VIW): Natural ventilation and daylight experimental analysis on a 1:1 prototype scale model

Ventilated Illuminating Wall (VIW): Natural ventilation and daylight experimental analysis on a 1:1 prototype scale model Ventilated Illuminating Wall (VIW): Natural ventilation and daylight experimental analysis on a 1:1 prototype scale model O. Boccia *, F. Chella, P. Zazzini D.S.S.A.R.R., Faculty of Architecture University

More information

TREES Training for Renovated Energy Efficient Social housing. Section 1 Techniques 1.2 Replacement of glazing

TREES Training for Renovated Energy Efficient Social housing. Section 1 Techniques 1.2 Replacement of glazing TREES Training for Renovated Energy Efficient Social housing Intelligent Energy -Europe programme, contract n EIE/05/110/SI2.420021 Section 1 Techniques 1.2 Replacement of glazing Bruno PEUPORTIER ARMINES

More information

Tage Møller Architect office building

Tage Møller Architect office building Architect office building presentation! It was built 1996 in windy surroundings.! It has a floor area of about 300 m 2.! The room height varies from 2.4 to 5 meters. PLAN VIEW N presentation The building

More information

What is Sustainable Design?

What is Sustainable Design? What is Sustainable Design? Part Three: The Basic Principles of Passive Design Terri Meyer Boake BES, BArch, MArch, LEED AP Associate Director School of Architecture University of Waterloo Past President

More information

User Interactions with Environmental Control Systems in Buildings

User Interactions with Environmental Control Systems in Buildings User Interactions with Environmental Control Systems in Buildings Ardeshir Mahdavi, Elham Kabir, Abdolazim Mohammadi, Lyudmila Lambeva, Claus Pröglhöf Department of Building Physics and Building Ecology

More information

Poor distribution & glare

Poor distribution & glare Light transmission The benefits of the use of natural daylight in buildings in respect of health & well-being, safety, productivity and energy savings are well documented. LIGHT TRANSMISSION Light that

More information

Martin Ratcliffe Visiting Research Fellow, Centre for Energy Studies at LSBU Head of Roger Preston Environmental

Martin Ratcliffe Visiting Research Fellow, Centre for Energy Studies at LSBU Head of Roger Preston Environmental REAPING THE BENEFITS AVOIDING THE PITFALLS Martin Ratcliffe Visiting Research Fellow, Centre for Energy Studies at LSBU Head of Roger Preston CIBSE/ASHRAE Meeting LSBU May 12th 2004 1 Show that glazing

More information

The Elithis Tower is an experimental and demonstration. Elithis Tower in Dijon, France. nzeb case studies

The Elithis Tower is an experimental and demonstration. Elithis Tower in Dijon, France. nzeb case studies COM Elithis Tower in Dijon, France Elithis Tower, located in Dijon, France, provides strong evidence that net zero energy office buildings are achievable in near future. The building, which was designed

More information

CHAPTER 2 LITERATURE REVIEW 1. Daylighting controls are perceived as a lucrative option for daylighting to gain acceptance

CHAPTER 2 LITERATURE REVIEW 1. Daylighting controls are perceived as a lucrative option for daylighting to gain acceptance CHAPTER 2 LITERATURE REVIEW 1 2.1 Introduction Daylighting controls are perceived as a lucrative option for daylighting to gain acceptance and reverse the current practice of total reliance on artificial

More information

Guidelines for Design and Construction of Energy Efficient County Facilities

Guidelines for Design and Construction of Energy Efficient County Facilities APPENDIX C - DAYLIGHTING The role of daylighting in the total energy balance and performance of a building is a significant one. The admission of useful daylight means that electrical lighting fixtures

More information

DYNAMIC FACADE. BUILDING ENERGY EFFICIENCY REHABILITATION.

DYNAMIC FACADE. BUILDING ENERGY EFFICIENCY REHABILITATION. Albert López. Architect (SOMFY Spain) albert.lopez@somfy.com DYNAMIC FACADE. BUILDING ENERGY EFFICIENCY REHABILITATION. 1. Energy in the the running costs of buildings. 2. The energy consumption of a building.

More information

Thermal performance of concrete wall panel with advanced coating materials: a sustainable design

Thermal performance of concrete wall panel with advanced coating materials: a sustainable design Topic: T2.1 Design and Innovation Reference number: 2046 Thermal performance of concrete wall panel with advanced coating materials: a sustainable design Ao Zhou 1, Denvid Lau 1, * 1. Department of Architecture

More information

10 tips from your Architect

10 tips from your Architect 10 tips from your Architect Within the context of the national week of Energy Efficiency, in collaboration with the Energy Efficiency Management Office, the Mauritius Association of Architects offers you

More information

HOW CURRENT TRENDS IN THE DESIGN OF FACADES INFLUENCE THE FUNCTIONAL QUALITY OF INTERIOR SPACES

HOW CURRENT TRENDS IN THE DESIGN OF FACADES INFLUENCE THE FUNCTIONAL QUALITY OF INTERIOR SPACES HOW CURRENT TRENDS IN THE DESIGN OF FACADES INFLUENCE THE FUNCTIONAL QUALITY OF INTERIOR SPACES B. Paule 1, F. Flourentzos 1, M. Bauer 1, S. Pantet 1 1: Estia SA, EPFL Innovation Park, Lausanne, Switzerland

More information

Effects of Fixed and Motorized Window Louvers on the Daylighting and Thermal Performance of Open-Plan Office Buildings

Effects of Fixed and Motorized Window Louvers on the Daylighting and Thermal Performance of Open-Plan Office Buildings Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 214 Effects of Fixed and Motorized Window Louvers on the Daylighting and Thermal Performance

More information

The Lehigh Valley Heritage Center Allentown, Pennsylvania

The Lehigh Valley Heritage Center Allentown, Pennsylvania Research on Smart Window Technology Building lighting loads in buildings account for a large percentage of electricity consumption and heat generation. Being able to utilize natural daylight to illuminate

More information

Research Article DevelopmentandPerformanceEvaluationofLightShelvesUsing Width-Adjustable Reflectors

Research Article DevelopmentandPerformanceEvaluationofLightShelvesUsing Width-Adjustable Reflectors Advances in Civil Engineering Volume 2018, Article ID 2028065, 9 pages https://doi.org/10.1155/2018/2028065 Research Article DevelopmentandPerformanceEvaluationofLightShelvesUsing Width-Adjustable Reflectors

More information

International Journal of Scientific & Engineering Research Volume 9, Issue 1, January ISSN

International Journal of Scientific & Engineering Research Volume 9, Issue 1, January ISSN International Journal of Scientific & Engineering Research Volume 9, Issue 1, January-2018 131 Design for appropriate size of fixed skylight in Famagusta, Cyprus Aisha Mahmud Umar, Halil Zafer Alibaba

More information

INTEGRATION OF LIGHTING PERFORMANCE INDICATORS INTO A DASHBOARD FOR DAYLIGHTING ASSESSMENTS. Beatriz Piderit 1, Daniela Besser 2

INTEGRATION OF LIGHTING PERFORMANCE INDICATORS INTO A DASHBOARD FOR DAYLIGHTING ASSESSMENTS. Beatriz Piderit 1, Daniela Besser 2 INTEGRATION OF LIGHTING PERFORMANCE INDICATORS INTO A DASHBOARD FOR DAYLIGHTING ASSESSMENTS Beatriz Piderit 1, Daniela Besser 2 1 Departament of Design and Architectural Theory, University of Bio-Bio,

More information

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Available online at  ScienceDirect. Procedia Engineering 121 (2015 ) Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 121 (2015 ) 1869 1879 9th International Symposium on Heating, Ventilation and Air Conditioning (ISHVAC) and the 3rd International

More information

Investigation of indoor climate in a naturally ventilated office building

Investigation of indoor climate in a naturally ventilated office building Indoor Air 2008, 17-22 August 2008, Copenhagen, Denmark - Paper ID: 784 Investigation of indoor climate in a naturally ventilated office building Tine S. Larsen,*, Olena Kalyanova, Rasmus Lund Jensen and

More information

CHAPTER 6 CONCLUSION

CHAPTER 6 CONCLUSION 255 CHAPTER 6 CONCLUSION This study thoroughly assessed the design principles employed in simple, durable and eco-friendly vernacular dwellings in the coastal regions of Tamil Nadu and their effectiveness

More information

The Effects of Light Shelf on Climate-based Daylight performance in Tropics- A Case Study

The Effects of Light Shelf on Climate-based Daylight performance in Tropics- A Case Study The Effects of Light Shelf on Climate-based Daylight performance in Tropics- A Case Study Speakers: Chien, S.-C. 1 ; Tseng, K. J. 2 1 Berkeley Education Alliance for Research in Singapore (BEARS), Singapore

More information

MAKING DAYLIGHTING WORK IN SCHOOLS

MAKING DAYLIGHTING WORK IN SCHOOLS MAKING DAYLIGHTING WORK IN SCHOOLS PRESENTERS: MELANIE ROSS AND ALI SYED SEPTEMBER 25, 2015 OUTLINE WHAT IS DAYLIGHTING SCHOOL LIGHTING LEVELS AND TYPICAL ENERGY USE DAYLIGHTING DESIGN PARAMETERS IMPACTS

More information

ANALYSIS AND EXPERIMENTAL INVESTIGATION OF THE NTCH BUILDING ON ENERGY CONSERVATION DESIGNS

ANALYSIS AND EXPERIMENTAL INVESTIGATION OF THE NTCH BUILDING ON ENERGY CONSERVATION DESIGNS , Volume 2, Number 1, p.7-14, 2001 ANALYSIS AND EXPERIMENTAL INVESTIGATION OF THE NTCH BUILDING ON ENERGY CONSERVATION DESIGNS K.H. Yang and J.N. Lee Mechanical Engineering Department, National Sun Yat-Sen

More information

SOMFY - PHILIPS Light balancing Whitepaper

SOMFY - PHILIPS Light balancing Whitepaper SOMFY - PHILIPS Light balancing Whitepaper Prepared by Dr Ya Roderick Mr Eoin Nolan Dr Craig Wheatley Mr David McEwan INTEGRATED ENVIRONMENTAL SOLUTIONS LIMITED March 2013 SOMFY - PHILIPS Light Balancing

More information

CONTROLITE. Intelligent Daylighting System FACADE SKYLIGHT

CONTROLITE. Intelligent Daylighting System FACADE SKYLIGHT CONTROLITE Intelligent Daylighting System FACADE SKYLIGHT INTELLIGENT DAYLIGHTING SYSTEM CONTROLITE FEATURES A TRANSLUCENT GLAZING PANEL WITH INTEGRATED, ROTATING LOUVRES THAT ADJUST THEIR POSITION THROUGHOUT

More information

SIMULATION-ASSISTED DAYLIGHT PERFORMANCE ANALYSIS IN A HIGH-RISE OFFICE BUILDING IN SINGAPORE

SIMULATION-ASSISTED DAYLIGHT PERFORMANCE ANALYSIS IN A HIGH-RISE OFFICE BUILDING IN SINGAPORE SIMULATION-ASSISTED DAYLIGHT PERFORMANCE ANALYSIS IN A HIGH-RISE OFFICE BUILDING IN SINGAPORE Szu-cheng Chien, Research Fellow, scchien@ntu.edu.sg Berkeley Education Alliance for Research in Singapore

More information

The lotus flower: biomimicry solutions in the built environment

The lotus flower: biomimicry solutions in the built environment Sustainable Development and Planning VII 1085 The lotus flower: biomimicry solutions in the built environment Y. Nanaa & H. Taleb Sustainable Design of the Built Environment, British University in Dubai,

More information

The Assessment of Advanced Daylighting Systems in Multi-Story Office Buildings Using a Dynamic Method

The Assessment of Advanced Daylighting Systems in Multi-Story Office Buildings Using a Dynamic Method The Assessment of Advanced Daylighting Systems in Multi-Story Office Buildings Using a Dynamic Method Jianxin Hu 1,*, Jiangtao Du 2, Wayne Place 1 1 College of Design, School of Architecture, North Carolina

More information

Shading systems and sustainable design

Shading systems and sustainable design Content Shading systems and sustainable design Randall Kohn Shade Factor Pty Ltd Australian agents for Warema Brief introduction of WAREMA Type 80 retractable external louvres Physical basics Slat and

More information

Chapter 2 Literature Review

Chapter 2 Literature Review Chapter 2 Literature Review The double façade system was first introduced in France in the early 1930s. During this time, Le Corbusier (1887-1965) designed a multiple glass layer wall called Mur Neutralisant,

More information

Evaluation methods for indoor environmental quality assessment according to EN15251

Evaluation methods for indoor environmental quality assessment according to EN15251 Summary of this article was published in the REHVA European HVAC Journal Vol 49, Issue 4 (August), 2012, pages 14-19, available at http://www.rehva.eu/en/rehva-european-hvac-journal. Evaluation methods

More information

optimize daylighting Opportunities

optimize daylighting Opportunities optimize daylighting Opportunities DESIGN STRATEGIES DESIGN STRATEGIES NATURAL LIGHTING FOR ENERGY EFFICIENCY DAYLIGHTING Using indirect natural light to illuminate indoor spaces as an alternative to electric

More information

Daylight And Seating Preference In Open-Plan Library Spaces

Daylight And Seating Preference In Open-Plan Library Spaces Daylight And Seating Preference In Open-Plan Library Spaces Zeynep Keskin 1, Yunhao Chen 1, Steve Fotios 1,* 1 School of Architecture, the University of Sheffield, UK Received 6 June 2015, Revised 7 July

More information

Modeling Energy Consumption Effects of Glazing

Modeling Energy Consumption Effects of Glazing Modeling Energy Consumption Effects of Glazing Daniel Lu 12/7/2012 Table of Contents Introduction... 3 Design Options... 5 Option 1... 5 Option 2... 5 Preliminary Energy Simulation... 7 Objectives... 7

More information

Ball State Architecture ENVIRONMENTAL SYSTEMS 1 Grondzik 1

Ball State Architecture ENVIRONMENTAL SYSTEMS 1 Grondzik 1 DAYLIGHT image by NASA use this powerful resource with skill and caution Ball State Architecture ENVIRONMENTAL SYSTEMS 1 Grondzik 1 Daylight and Design From the dawn of time until the widespread introduction

More information

BRF Kredit headquarters

BRF Kredit headquarters headquarters BRF Kredit Architect: KHR A/S presentation (1) BRF Kredit presentation (2) BRF Kredit! BRF-kredit is a financing institute for property mortgages! The company Headquarters is located in Lyngby,

More information

Assessment of shading devices with integrated PV for efficient energy use

Assessment of shading devices with integrated PV for efficient energy use Assessment of shading devices with integrated PV for efficient energy use Maria Mandalaki, Konstantinos Zervas and Theocharis Tsoutsos Technical University of Crete, Department of Environmental Engineering,

More information

This is the accepted manuscript version of the article

This is the accepted manuscript version of the article This is the accepted manuscript version of the article Solar shading control strategies in cold climates Heating, cooling demand and daylight availability in office spaces Grynning, S., Time, B., & Matusiak,

More information

Facade Design for Super High- Rise Building in Subtropic Region in China

Facade Design for Super High- Rise Building in Subtropic Region in China Facade Design for Super High- Rise Building in Subtropic Region in China Super high-rise building will always be iconic elements at any location. Accompanied by the growth of building technology and urbanization,

More information

Attaining Thermal Comfort in. Buildings with Predominantly. Glazed Facades. presented to: ANSYS Boston Regional Conference

Attaining Thermal Comfort in. Buildings with Predominantly. Glazed Facades. presented to: ANSYS Boston Regional Conference Attaining Thermal Comfort in Buildings with Predominantly Glazed Facades presented to: ANSYS Boston Regional Conference September 14, 2011 Case Study Background High floor to ceiling windows Large skylight

More information

New solar shading system based on daylight directing solar glass lamellas

New solar shading system based on daylight directing solar glass lamellas Indoor Air 2008, 17-22 August 2008, Copenhagen, Denmark - Paper ID: 519 New solar shading system based on daylight directing solar glass lamellas Steen Traberg-Borup 1,*, Kjeld Johnsen 1,* and Jacob B.

More information

Comparison of Energy and Visual Comfort Performance of Independent and Integrated Lighting and Daylight Controls Strategies

Comparison of Energy and Visual Comfort Performance of Independent and Integrated Lighting and Daylight Controls Strategies Comparison of Energy and Visual Comfort Performance of Independent and Integrated Lighting and Daylight Controls Strategies Eric Shen and Maulin Patel, Philips Research North America Jia Hu, University

More information

Glassworks Pty Ltd in Melbourne, Australia. Self-Tinting Interlayer for Dynamic Windows. In Alliance with

Glassworks Pty Ltd in Melbourne, Australia. Self-Tinting Interlayer for Dynamic Windows. In Alliance with by Glassworks Pty Ltd in Melbourne, Australia Self-Tinting Interlayer for Dynamic Windows In Alliance with SUNTUITIVE INTERLAYER What s happening above: All of the windows above have the same exterior

More information

Designing carbon neutral schools: The Victor Miller Building, a critical review

Designing carbon neutral schools: The Victor Miller Building, a critical review Designing carbon neutral schools: The Victor Miller Building, a critical review Daniela BESSER 1 Lucelia RODRIGUES 1 Benson LAU 1 1 School of the Built Environment UK ABSTRACT: Nowadays, one of the UK

More information

Thermal environment and thermal comfort in a passive residential building in the severe cold area of China

Thermal environment and thermal comfort in a passive residential building in the severe cold area of China Thermal environment and thermal comfort in a passive residential Yuchen Ji Ph D. Candidate Harbin Institute of Technology China 15B927029@hit.edu.cn Professor, Zhaojun Wang, Harbin Institute of Technology,

More information

Cost-Benefit Analysis of Dwelling Retrofit Options

Cost-Benefit Analysis of Dwelling Retrofit Options Cost-Benefit Analysis of Dwelling Retrofit Options The objective was to study the thermal behaviour of the existing house and suggest cost effective improvements. Over recent years the energy efficiency

More information

COMPARISON OF ENERGY USE INDICATORS OF A NON-RESIDENTIAL PASSIVE HOUSE WITH ASHRAE 90.1 BUDGET BUILDING

COMPARISON OF ENERGY USE INDICATORS OF A NON-RESIDENTIAL PASSIVE HOUSE WITH ASHRAE 90.1 BUDGET BUILDING COMPARISON OF ENERGY USE INDICATORS OF A NON-RESIDENTIAL PASSIVE HOUSE WITH ASHRAE 90.1 BUDGET BUILDING ABSTRACT F. Bagheri 1, M. Fakoor 1, B. Young 1, C. Cranswick 1 1 BC Building Science Ltd. 611 Bent

More information

Introduction to basics of energy efficient building design

Introduction to basics of energy efficient building design Introduction to basics of energy efficient building design Pierre Jaboyedoff Seminar on Energy Efficient & Thermally Comfortable Buildings in Amravati For CRDA, Andhra Pradesh May 2 nd 2017 Indo-Swiss

More information

Second International Conference on Energy and Indoor Environment for Hot Climates

Second International Conference on Energy and Indoor Environment for Hot Climates Second International Conference on Energy and Indoor Environment for Hot Climates Outdoor Cooling Technologies, Challenges, and Opportunities for the Hot Climates February 26th - 27th, 2017 Organizers:

More information