Comparison of indoor air quality on a passenger ship and a chemical ship

Size: px
Start display at page:

Download "Comparison of indoor air quality on a passenger ship and a chemical ship"

Transcription

1 Indoor Air 28, August 28, Copenhagen, Denmark - Paper ID: 49 Comparison of indoor air quality on a passenger ship and a chemical ship Sun-Sook Kim 1,*, Yoon-Kyung Kang 1, Geun-Young Doe 2 and Yun-Gyu Lee 1 1 Korea Institute of Construction Technology, Korea 2 Korea Maritime University, Korea * Corresponding kictkss@kict.re.kr SUMMARY Indoor air quality on ships is important to the passengers comfort and crews habitability. Although the constructors and operators need to be aware of the importance and present status of indoor air quality, sufficient data and information is not available. In this study, we measured the pollutant concentrations on two different kinds of ships, a passenger ship and a chemical ship. Indoor air quality of the chemical ship was worse than that of the passenger ship, and concentrations of some pollutants on the chemical ship surpassed the domestic and international criteria. For a passenger ship, the variation of indoor air quality was also investigated after about one and half year. In order to achieve shipboard air quality, it is necessary to collect more data and to suggest minimum requirements. KEYWORDS Indoor air quality, Ship, Transportation, Volatile organic compound, Formaldehyde INTRODUCTION Recently, there has been a growing public concern over indoor air quality not only in buildings but also in transportations such as vehicles and airplanes. In some countries, indoor air quality measurement and management guidelines for the vehicles have been developed by automobile manufacturers voluntary efforts. The draft international standard that specifies the test method of volatile organic compounds (VOCs) in car interiors is currently under progressing in the ISO technical committee. Recently, the Ministry of Construction & Transportation in Korea also proposed the Standards of indoor air quality in new assembly cars in June, 27. Indoor air quality in airplane cabins has been treated as an important issue and a wide range of research has been conducted for decades. Although ships are not so much common and popular as vehicles and airplanes, indoor air quality on ships is also important to the heath and comfort of passengers and crews. Since the periods on board are relatively longer, poor indoor air quality may have a long-term harmful effect on them by increasing physical and mental fatigue. Furthermore, indoor air quality is likely to be worse on shipboard due to the airtight body and middle corridor-type accommodation layout. Therefore, constructors and operators need to be aware of the importance and present status of indoor air quality. Lloyd s Register assessed indoor air quality onboard a wide range types of vessels and compared it with that of office and residential buildings (Webster and Reynolds, 25). Jang et al. (27) investigated the crews activities and clothing in the cabins of maritime patrol vessels in order to estimate the optimum temperature for PMV/PPD based air conditioning. American Bureau of Shipping (ABS, 21) has developed the guides to meet the needs for passengers comfort and crews habitability on ships. These guides suggest indoor climate requirements and test procedures for air temperature, humidity, vertical and horizontal

2 gradient, and air velocity. In addition, the international standard on air conditioning and ventilation design in the passenger accommodation of ships makes recommendations with respect to temperature, relative humidity, supply, and exhaust air (ISO, 22 ; Webster and Reynolds, 25). However, these guides and standard do not cover the indoor air quality criteria including pollutant concentrations. Although the constructors and operators need to monitor and manage shipboard air quality, sufficient data and information is not available. Therefore, the purpose of this study is to analyze the characteristics of indoor air quality on ships by measuring the pollutant concentrations in a new passenger ship and a new chemical ship and to investigate the variations after a certain period. METHODS Pollutant concentrations and indoor climate were investigated by field measurements on two different types of ships as shown in Figure 1. The one is a passenger ship for use as a student training ship of the Korea Maritime University, and the other is an oil or chemical tanker. Both of the ships consist of six decks and a series of measurements were accomplished at various locations, including wheelhouse, passenger or crew s cabins, engine rooms, kitchens, and etc. For a passenger ship, the second measurements were conducted after 17 months. Outline of the measurements is shown in Table 1. Concentrations of VOCs, formaldehyde, carbon oxide(co), carbon dioxide(co 2 ), sulfur dioxide(so 2 ), and particulate matter were measured as well as indoor temperatures and relative humidity. Measurement and analysis methods for parameters are shown in Table 2. Figure 1. Features of the investigated ships. a), b). Table 1. Outline of the measurement. Types Size Measuring period Measuring points 6,7 ton 1st : 26 / 2 / 22 ~ 24 2nd : 27 / 7 / 25 ~ point 13, ton 27 / 6 / 4 ~ 5 8 point

3 Table 2. Measurement and analysis methods. Types VOCs Formaldehyde CO, CO 2, SO 2 Particulate matter Temperature and R.H. Instrument / Method 3. liters of air samples with Tenax-TA tubes Thermal desorber / Gas chromatography / Mass Spectrometry 15 liters of air samples with 2,4-DNPH sampler High Performance Liquid Chromatography Multi-gas monitor (3 minutes) Scanning mobility particle sizer (18 minutes) Measuring instrument with multi-probes (3 minutes) The main guidelines concerning indoor air quality were introduced by WHO (2) and ASHARE (26). In Korea, IAQ Management Act was enforced by the Ministry of Environment and came into effect of May, 24. These criteria shown in Table 3 have used for the evaluation of air quality on the ships. ANSI/ASHRAE standard (ASHRAE, 1992) was also referred for evaluating the indoor climate condition. Table 3. Indoor air quality criteria. Parameter WHO/Europe ASHRAE IAQ Act in Korea TVOC Toluene Benzene Ethylbenzene Styrene Xylene Formaldehyde CO CO 2 SO 2 Particulate matter 26 µg/m 3 (1 week) 26 µg/m 3 (1 week) 1 µg/m 3 (3min) 1 ppm(8h) 5 µg/m 3 12 µg/m 3 (3min) 1 µg/m 3 9 ppm(8h) 1 ppm 8 µg/m 3 (1year) 5 µg/m 3 5 µg/m 3 1 µg/m 3 3 µg/m 3 36 µg/m 3 3 µg/m 3 7 µg/m 3 21 µg/m 3 9 ppm 1 ppm.5 ppm 15 µg/m 3 RESULTS Temperature and relative humidity Figure 2 shows the temperature and relative humidity on the ships. The temperatures mainly ranged from 2 C to 26 C in the accommodation, which were acceptable for human comfort. However, temperature reached over 3 C at the engine rooms due to the heat transfer from the operating engines. The average relative humidity on the passenger ship was 24.6% at the 1 st measurement and 34.4% at the 2 nd measurement, which was relatively lower than the relative humidity criteria. The average relative humidity on the chemical ship was 59.9%, and it can be included to the comfort zone for summer. There was not so much variation in the temperature and relative humidity distribution on the passenger ship, but it seemed that the indoor climate on the chemical ship was not controlled fairly well.

4 st measurement 2nd measurement R. H.(%) for winter for summer R. H.(%) for winter for summer Temperature( C) Figure 2. Comparison of temperature and relative humidity. a) The chemical ship and the passenger ship, b) 1 st measurement and 2 nd measurement on the passenger ship Pollutant concentrations on the new ships Figure 3, 4, and 5 shows the comparative data sets of the pollutant concentrations on two different types of ships. TVOC concentrations were higher than the domestic criteria, 5μg/m 3, all over the chemical ship. Especially, the concentration levels in a crew s cabin, the engine control room, and the engine room were so high as to exceed 3, μg/m 3. For the passenger ship, apart from the seminar room and the kitchen, TVOC concentrations were low when compared to the criteria and the chemical ship. As Figure 4 demonstrates, concentrations of most selected VOCs were also higher in the chemical ship than in the passenger ship. Concentrations of VOCs including toluene, ethyl benzene, xylene, and styrene were lower than the recommended standards in most locations, but a relatively larger quantity of toluene was detected in the engine control room of the chemical ship. Besides these four selected VOCs, variety of compounds were also detected including nonane, dodecane, tetradecane, 1,3,5-trimethyl-Benzene, and etc. The average formaldehyde concentration was 18μg/m 3 on the passenger ship and 29μg/m 3 on the chemical ship, which was much lower than the criteria. There was not so much difference in formaldehyde concentration between the ships Temperature( C) Em'cy Gen. R. IAQ act in Korea Em'cy Gen. R. ASHRAE standard TVOC concentration( μg / m3 ) Formaldehyde concentration( μg / m3 ) Figure 3. TVOC and Formaldehyde concentrations on the ships. a) TVOC, b) Formaldehyde.

5 6 5 P C Concentration( μg / m3 ) P C P C P C P C Toluene Ethylbenzene Xylene Styrene Figure 4. VOCs concentrations on two ships. CO and CO 2 concentrations on the passenger ship were below the criteria, but all the measurements on the chemical ship exceeded the criteria largely. CO and CO 2 levels were relatively high in the kitchen, engine control room, and engine room on both ships. Especially, in the engine control room of the chemical ship, the largest quantity of CO and CO 2 was observed. Em'cy Gen. R. ASHRAE standard IAQ act in Korea Em'cy Gen. Room ASHRAE standard IAQ act in Korea CO concentration(ppm) Figure 5. CO and CO 2 concentrations on two ships. a) CO, b) CO CO 2 concentration(ppm) Time variation in pollutant concentrations Figure 6 and 7 present variations of pollutant concentrations on the passenger ship at two different measurement periods. The results showed some differences between the selected VOCs levels and other pollutants. VOCs concentrations were decreased after about one and half year, except a few locations. On the other hand, CO, CO 2, SO 2, and PM levels were increased at 2 nd measurement in 27, and CO and CO 2 levels exceeded the criteria at some locations. Average SO 2 concentration is 13.3 ppm at the 1 st measurement and 29 ppm at the 2 nd measurement, and none of the measurements were below the Korean criteria,.5 ppm.

6 8 4 Toluene Ethylbenzene 2nd concentration( μg / m3 ) nd PM concentration( μg / m3 ) st concentration( μg / m3 ) st PM concentration( μg / m3 ) Figure 6. Time variations in VOCs and PM concentrations. a) VOCs, b) PM nd concentration(ppm) 2 1 CO 2nd CO2 concentration(ppm) SO st concentration(ppm) Figure 7. Time variations in CO, CO 2 and SO 2 concentrations. a) CO and SO 2, b) CO 2. DISCUSSION Generally, the pollutants concentrations on the chemical ship were higher than those on the passenger ship of which overall air quality was acceptable with a few exceptions. TVOC concentrations on the chemical ship exceeded the domestic and international criteria, while the concentrations in the passenger ship were lower than the criteria. The difference in the IAQ of two ships might be influenced various factors, including the air-conditioning systems, finishing materials, furnish, equipments, and etc. The difference in temperature and relative humidity might be resulted from the different seasonal condition and HVAC operations. Relative humidity seemed to be not so adequately controlled as temperature. High TVOC concentrations were shown in the kitchen, the seminar room, and the salon in the passenger ship. The reason for the high concentrations was considered to be related to the emission from the furniture, electronic equipments, and cooking utensils. In the chemical ship, st CO 2 concentration(ppm)

7 TVOC concentrations were high at the engine room and engine control room, and this might be attributed to the the new engines, control panels and other equipments and machinery. Since the chemical ship is not intended to carry passengers, it seems that finishing materials and HVAC systems were not so considered very much as the passenger ship. CO, CO 2, and SO 2 concentrations showed similar patterns throughout the measurements. From the high CO, CO 2, and SO 2 concentrations in the kitchen, engine room, and engine control room, high concentrations might be generally attributed to combustion sources. Contrary to other types of transportations, most ships are usually equipped with kitchen, and careful attention should be paid to prevent the spread of pollutants from the kitchens. Although an engine room is not an occupied space, it is also needed to be managed carefully for keeping good indoor air quality of the adjacent engine control room occupied by crews. Even though combustion sources are not so common on the accommodation spaces, it is necessary to investigate measures against pollutants from kitchens and engine rooms. VOCs were initially observed as a major problem on board ships due to the relatively high amount of cleaning, decorating, and furbishing, but these concentrations appeared to decay over a period. While VOCs concentrations in the ships were decreased with the passage of the time, CO, CO 2, SO 2, and PM concentrations were irrelevant to the time variation or increased with the passage of the time, which is similar to most inland buildings. CONCLUSIONS In this study, indoor climate and air quality was measured and compared on two different types of ships to investigate current status of shipboard air quality. Indoor air quality on ships was not considered to be severe when compared with the problems of inland buildings. However, the crews may stay longer, and poor indoor air quality may have a harmful effect on them. Constructors and operators should be aware of the importance and present status of indoor air quality. Since ventilation design is also one of the most important factors to keep good indoor air quality on ships, it is necessary to go on further research. REFERENCES ABS. 22. Guide for habitability on ships. American Bureau of Shipping. ABS. 22. Guide for passenger comfort on ships. American Bureau of Shipping. ASHRAE ASHRAE Standard , Thermal Environmental Conditions for Human Occupancy. American Society of Heating, Refrigerating, and Air-conditioning Engineers, Inc. ASHRAE. 24. ANSI/ASHRAE Standard , Ventilation for Acceptable Indoor Air Quality. American Society of Heating, Refrigerating, and Air-conditioning Engineers, Inc. ISO. 22. ISO 7547:22, Ships and marine technology - Air-conditioning and ventilation of accommodation spaces - Design conditions and basis of calculations. International Organization for Standards. Jang M.S., Koh C.D., and Moon I.S. 27. Review of thermal comfort design based on PMV/PPD in cabins of Korean maritime patrol vessels. Building and Environment, 42, Webster A.D. and Reynolds G.L. 25. Indoor air quality on passenger ships. In: The Handbook of Environmental Chemistry, Vol. 4, pp WHO. 2. Air Quality Guidelines for Europe, 2 nd edn. World Health Organization Regional Publications, European series No. 91.

COMPARISON OF STRATEGIES TO IMPROVE INDOOR AIR QUALITY AT PRE-OCCUPANCY STAGE IN NEW APARTMENT BUILDINGS

COMPARISON OF STRATEGIES TO IMPROVE INDOOR AIR QUALITY AT PRE-OCCUPANCY STAGE IN NEW APARTMENT BUILDINGS Proceedings: Indoor Air 25 COMPARISON OF STRATEGIES TO IMPROVE INDOOR AIR QUALITY AT PRE-OCCUPANCY STAGE IN NEW APARTMENT BUILDINGS SS Kim 1, DH Kang 1, DH Choi 1, MS Yeo 2, KW Kim 2* 1 Department of Architecture,

More information

ANALYSIS OF INDOOR AIR QUALITY IN HIGH-SPEED TRAIN PASSENGER CABIN IN KOREA

ANALYSIS OF INDOOR AIR QUALITY IN HIGH-SPEED TRAIN PASSENGER CABIN IN KOREA ANALYSIS OF INDOOR AIR QUALITY IN HIGH-SPEED TRAIN PASSENGER CABIN IN KOREA Youngmin Cho 1, Soon-Bark Kwon 1, and Duck-Shin Park 1 1 Environment & Fire Control Research Team, Korea Railroad Research Institute,

More information

A measurement on chemicals emitted from computers and printers using test chamber method

A measurement on chemicals emitted from computers and printers using test chamber method A measurement on chemicals emitted from computers and printers using test chamber method Dong Won Yoon 1, Sung Min Hong 2, Hyo Seok Kang 2, Hyo Jun Kim 2, Ji Hun Kim 2 1 Kyungwon University, South Korea

More information

INDOOR CHEMICAL POLLUTION AND EMISSION RATES INVESTIGATED IN A REAL SIZED MODEL ROOM

INDOOR CHEMICAL POLLUTION AND EMISSION RATES INVESTIGATED IN A REAL SIZED MODEL ROOM Proceedings: Indoor Air 22 INDOOR CHEMICAL POLLUTION AND EMISSION RATES INVESTIGATED IN A REAL SIZED MODEL ROOM S Tanabe 1, R Shirai 1, M Banno 1 and Y Asai 2 1 Department of Architecture, Waseda University,

More information

http://www.diva-portal.org This is the published version of a paper presented at The 14th International Conference of Indoor Air Quality and Climate, Ghent, Belgium July 4-8 216. Citation for the original

More information

AIR QUALITY IN PASSENGER CARS OF THE GROUND RAILWAY TRANSIT SYSTEM IN BEIJING, CHINA

AIR QUALITY IN PASSENGER CARS OF THE GROUND RAILWAY TRANSIT SYSTEM IN BEIJING, CHINA AIR QUALITY IN PASSENGER CARS OF THE GROUND RAILWAY TRANSIT SYSTEM IN BEIJING, CHINA TT Li, JF Liu, GS Zhang, ZR Liu and YH Bai College of Environmental Science, Peking University, Beijing, 100871, China

More information

Improvement of Indoor Living Environment by Occupants Preferences for Heat Recovery Ventilators in High-Rise Residential Buildings

Improvement of Indoor Living Environment by Occupants Preferences for Heat Recovery Ventilators in High-Rise Residential Buildings Original Paper Indoor and Built Indoor Built Environ 212;21;4:486 52 Accepted: October 17, 211 Environment Improvement of Indoor Living Environment by Occupants Preferences for Heat Recovery Ventilators

More information

VIAQ Test Methods and Regulatory Compliance. Mark Polster Ford Motor Company

VIAQ Test Methods and Regulatory Compliance. Mark Polster Ford Motor Company VIAQ Test Methods and Regulatory Compliance Mark Polster Ford Motor Company Vehicle Interior Air Quality Intro Part 1 Vehicle owners in the Asia Pacific (AP) region have higher rates of interior odor complaints

More information

Good (4 points each) > mg/m Bq m Bq m Bq m -3 < ,000 1,000-10,000 10, ,000

Good (4 points each) > mg/m Bq m Bq m Bq m -3 < ,000 1,000-10,000 10, ,000 Rating (5 points each) (4 points each) (3 points each) (2 points each) (1 point each) Temperature ( C) 18-21 C Plus or minus 1 C (including Plus or minus 2 C (including Plus or minus 3 C (including Plus

More information

THE A DETAILED STUDY OF VOLATILE ORGANIC COMPOUNDS OF 5 AIR-CONDITIONED BUILDINGS IN SINGAPORE

THE A DETAILED STUDY OF VOLATILE ORGANIC COMPOUNDS OF 5 AIR-CONDITIONED BUILDINGS IN SINGAPORE THE A DETAILED STUDY OF VOLATILE ORGANIC COMPOUNDS OF 5 AIR-CONDITIONED BUILDINGS IN SINGAPORE KWTham 1, SCSekhar 1, M Amanullah 2, HKLee 3, D Cheong 1 and NHWong 4 1 Department of Building, National University

More information

Visible emissions were not observed in the school in the vicinity of the construction containment.

Visible emissions were not observed in the school in the vicinity of the construction containment. June 22, 2018 To: Waverly Elementary School From: Christopher Madden, CIH Indoor Environmental Quality Manager Re: Indoor Air Quality Testing During Renovations - May As Waverly Elementary School is currently

More information

INDOOR AIR QUALITY AND ENERGY EFFICIENCY IN THE DESIGN OF BUILDING SERVICES SYSTEMS FOR SCHOOL CLASSROOMS

INDOOR AIR QUALITY AND ENERGY EFFICIENCY IN THE DESIGN OF BUILDING SERVICES SYSTEMS FOR SCHOOL CLASSROOMS INDOOR AIR QUALITY AND ENERGY EFFICIENCY IN THE DESIGN OF BUILDING SERVICES SYSTEMS FOR SCHOOL CLASSROOMS KL Tam * Architectural Services Department, the Government of Hong Kong Special Administrative

More information

Test Report. L ISOLANTE K-FLEX S.r.l. Product Emissions in accordance with ISO K-Flex Solar. November Head of product emission test centre

Test Report. L ISOLANTE K-FLEX S.r.l. Product Emissions in accordance with ISO K-Flex Solar. November Head of product emission test centre Test Report L ISOLANTE K-FLEX S.r.l. Product Emissions in accordance with ISO 16000 November 2011 Client: L ISOLANTE K-FLEX S.r.l. Via Leonardo da Vinci 36 20877 Roncello (mi) Italy Date: 1 November 2011

More information

Visible emissions were not observed in the school in the vicinity of the construction containment.

Visible emissions were not observed in the school in the vicinity of the construction containment. April 23, 2018 To: Waverly Elementary School From: Christopher Madden, CIH Indoor Environmental Quality Manager Re: Indoor Air Quality Testing During Renovations - March As Waverly Elementary School is

More information

Determination of volatile compounds in automotive interior materials by thermal desorption GC-MS

Determination of volatile compounds in automotive interior materials by thermal desorption GC-MS APPLICATION NOTE 10363 Determination of volatile compounds in automotive interior materials by thermal desorption GC-MS Authors Jinshui Che 1, Guifeng Deng 1, Lina Liang 1, Hans-Joachim Huebschmann 2 ;

More information

Evaluation of Volatile Organic Compounds and aldehydes emitted by a Anodized aluminium profile supply by ALUMINIOS CORTIZO according to ISO 16000

Evaluation of Volatile Organic Compounds and aldehydes emitted by a Anodized aluminium profile supply by ALUMINIOS CORTIZO according to ISO 16000 Saint Ouen l'aumone, the 22 th of June 2016 Evaluation of Volatile Organic Compounds and aldehydes emitted by a Anodized aluminium profile supply by ALUMINIOS CORTIZO according to ISO 16000 Report N D-310516-04389-002

More information

Dynamic Small-Scale Chamber Emissions Testing

Dynamic Small-Scale Chamber Emissions Testing Dynamic Small-Scale Chamber Emissions Testing Compliance Report per California Dept. of Public Health Standard Method Version 1.1 and FloorScore Selit Bloc Underlayment Prepared for: 550 Old Peachtree

More information

Variables affecting indoor air quality in newly finished buildings- a multivariate evaluation

Variables affecting indoor air quality in newly finished buildings- a multivariate evaluation Variables affecting indoor air quality in newly finished buildings- a multivariate evaluation Helena Järnström 1,2, Kristina Saarela 1, Pentti Kalliokoski 2, Anna-Liisa Pasanen 3 1 VTT, P.O.Box 1000, FIN-02044

More information

Indoor Air Quality Assessments during Renovations at Waverly Elementary School Project #J (January 4, 12, 15, 25 and 29, 2018)

Indoor Air Quality Assessments during Renovations at Waverly Elementary School Project #J (January 4, 12, 15, 25 and 29, 2018) March 29, 2018 Mr. Jeff Klenk Howard County Public School System (HCPSS) 10910 Route 108 Ellicott City, MD 21043 RE: Indoor Air Quality Assessments during Renovations at Waverly Elementary School Project

More information

VOC TEST REPORT French VOC Regulation

VOC TEST REPORT French VOC Regulation Mulcol International Arnesteinweg 18 4338 PD Middelburg The Netherlands Eurofins Product Testing A/S Smedeskovvej 38 8464 Galten Denmark VOC@eurofins.com www.eurofins.com/voc-testing 1 Sample Information

More information

ASHRAE s. Indoor Air Quality Procedure. in Ventilation Design

ASHRAE s. Indoor Air Quality Procedure. in Ventilation Design Elliott Horner, PhD UL Environment elliott.horner@ul.com M: 678-249-8856 ASHRAE s Indoor Air Quality Procedure Jim Dennison, CIH, PhD Century Environmental Hygiene jim@centuryenvironmental.com O: 970-266-8000

More information

Scope of application. Definitions. Translation from Finnish Legally binding only in Finnish and Swedish Ministry of Social Affairs and Health

Scope of application. Definitions. Translation from Finnish Legally binding only in Finnish and Swedish Ministry of Social Affairs and Health Translation from Finnish Legally binding only in Finnish and Swedish Ministry of Social Affairs and Health Decree of the Ministry of Social Affairs and Health on Health-related Conditions of Housing and

More information

Indoor air quality in a multifamily apartment building before and after energy renovation

Indoor air quality in a multifamily apartment building before and after energy renovation Downloaded from orbit.dtu.dk on: Dec 18, 2017 Indoor air quality in a multifamily apartment building before and after energy renovation Bekö, Gabriel; Földváry, Veronika ; Langer, Sarka; Arrhenius, Karine

More information

Mechanical vs. Natural Ventilation in Schools: Less Can Be More

Mechanical vs. Natural Ventilation in Schools: Less Can Be More Mechanical vs. Natural Ventilation in Schools: Less Can Be More Brad Stanley Purafil, Inc. Seminar 5 -Natural Ventilation in Schools: Boon or Bust? ASHRAE Annual Meeting Long Beach, California June 24-27,

More information

VOC EMISSION TEST REPORT French VOC Regulation

VOC EMISSION TEST REPORT French VOC Regulation PPG Dyrup, S.A. Rua Cidade de Goa, 26 2685-038 Sacavém PORTUGAL Eurofins Product Testing A/S Smedeskovvej 38 8464 Galten Denmark VOC@eurofins.com www.eurofins.com/voc-testing 1 Sample Information VOC EMISSION

More information

VOC TEST REPORT French VOC Regulation

VOC TEST REPORT French VOC Regulation CROMOLOGY, S.L. CL FRANCIA, 7 P.I. PLA DE LLERONA 08520 LES FRANQUESES DEL VALLES (BARCELONA) SPAIN Eurofins Product Testing A/S Smedeskovvej 38 8464 Galten Denmark VOC@eurofins.com www.eurofins.com/voc-testing

More information

VENTILATION REQUIREMENTS IN A RETAIL STORE

VENTILATION REQUIREMENTS IN A RETAIL STORE - VENTILATION REQUIREMENTS IN A RETAIL STORE D.T. Grimsrud, B.B. Bridges, N.G. Carlson, D.E. Hadlich University of Minnesot~ USA ABSTRACT This field study was organized to determine the ventilation required

More information

VOC TEST REPORT French VOC Regulation

VOC TEST REPORT French VOC Regulation PINTURAS DE LA PEÑA, S.L. CTRA. ORGAZ S/N Mora (Toledo) 45400 SPAIN Eurofins Product Testing A/S Smedeskovvej 38 8464 Galten Denmark VOC@eurofins.com www.eurofins.com/voc-testing 1 Sample Information VOC

More information

The Impact of Plants on the Reduction of Volatile Organic Compounds in a Small Space

The Impact of Plants on the Reduction of Volatile Organic Compounds in a Small Space The Impact of Plants on the Reduction of Volatile Organic Compounds in a Small Space Jeong-Eun Song 1), Yong-Shik Kim 2) and Jang-Yeul Sohn 3) 1) Dept. of Sustainable Architectural Engineering, Graduate

More information

Indoor Environmental Quality Policy

Indoor Environmental Quality Policy University of Florida Indoor Environmental Quality Policy For New Construction and Renovation Environmental Health and Safety Division June 2009 Introduction Effective management of the indoor environmental

More information

A STUDY ON PM 10 AND VOCS CONCENTRATIONS OF INDOOR ENVIRONMENT IN SCHOOL AND RECOGNITION OF INDOOR AIR QUALITY

A STUDY ON PM 10 AND VOCS CONCENTRATIONS OF INDOOR ENVIRONMENT IN SCHOOL AND RECOGNITION OF INDOOR AIR QUALITY A STUDY ON PM 10 AND VOCS CONCENTRATIONS OF INDOOR ENVIRONMENT IN SCHOOL AND RECOGNITION OF INDOOR AIR QUALITY BS Son 1,*, MR Song 2, WH Yang 3 1 Department of Environmental Health Science, Soonchunhyang

More information

Indoor Air Quality Assessment Report

Indoor Air Quality Assessment Report Indoor Air Quality Assessment Report For M&W Business Centre At Unit B, 19/F, Kyoto Plaza, 491-499 Lockhart Road, Causeway Bay, Hong Kong Tel: 3896 0399 Attn: Melody Ko Tested and prepared by: Carman Lam

More information

Development of a design guide to improve building IAQ

Development of a design guide to improve building IAQ Indoor Air 2008, 17-22 August 2008, Copenhagen, Denmark - Paper ID: 857 Development of a design guide to improve building IAQ Andrew Persily 1,*, Martha Hewett 2, Jude Anders 3, Lynn Bellenger 4, Ronald

More information

VOC TEST REPORT French VOC Regulation

VOC TEST REPORT French VOC Regulation CROMOLOGY, S.L C/ Francia 7, Pol. Llerona 08520 Barcelona ESB08519076 Spain Eurofins Product Testing A/S Smedeskovvej 38 8464 Galten Denmark VOC@eurofins.com www.eurofins.com/voc-testing 1 Sample Information

More information

VOC TEST REPORT French VOC Regulation

VOC TEST REPORT French VOC Regulation FINANCIERA MADERERA S.A. - FINSA Carretera N-550 km 57 15707 Santiago de Compostela (A Coruña) SPAIN Eurofins Product Testing A/S Smedeskovvej 38 8464 Galten Denmark VOC@eurofins.com www.eurofins.com/voc-testing

More information

ERGONOMIC & SAFETY DISCUSSION PAPER

ERGONOMIC & SAFETY DISCUSSION PAPER ERGONOMIC & SAFETY DISCUSSION PAPER Habitability and Comfort Issue # 8 January 2016 INTRODUCTION Appropriate habitability criteria and design practices may have significant impact on the safety, fatigue

More information

SURVEY ON INDOOR AIR QUALITY IN CONTEMPORARY RESIDENTIAL BUILDINGS IN JAPAN

SURVEY ON INDOOR AIR QUALITY IN CONTEMPORARY RESIDENTIAL BUILDINGS IN JAPAN SURVEY ON INDOOR AIR QUALITY IN CONTEMPORARY RESIDENTIAL BUILDINGS IN JAPAN Teruaki Mitamura 1, Haruki Osawa 2, Yasuo Kuwasawa 2, and Hisashi Miura 2 1 Department of Architecture, Ashikaga Institute of

More information

Influence of Environmental Factors on Volatile Organic Compound (VOC) Emission from Plywood

Influence of Environmental Factors on Volatile Organic Compound (VOC) Emission from Plywood Influence of Environmental Factors on Volatile Organic Compound (VOC) Emission from Plywood Shuang Li 1 Jun Shen 2* Jingxian Wang 3 1 College of Material Science and Engineering, Northeast Forestry University,

More information

University of Rochester Environmental Health & Safety Indoor Air Quality Program March 23, 2005

University of Rochester Environmental Health & Safety Indoor Air Quality Program March 23, 2005 University of Rochester Environmental Health & Safety Indoor Air Quality Program March 23, 2005 1. Purpose: The purpose of this program is to inform the University community about indoor air quality (IAQ).

More information

WOOD PLASTIC COMPOSITE MATERIALS MADE FROM RECYCLED WASTE WOOD AND PLASTIC: ASSESSMENT OF FORMALDEHYDE AND VOC EMISSIONS

WOOD PLASTIC COMPOSITE MATERIALS MADE FROM RECYCLED WASTE WOOD AND PLASTIC: ASSESSMENT OF FORMALDEHYDE AND VOC EMISSIONS Topic B6: Prediction and measurement WOOD PLASTIC COMPOSITE MATERIALS MADE FROM RECYCLED WASTE WOOD AND PLASTIC: ASSESSMENT OF FORMALDEHYDE AND VOC EMISSIONS Sabrine TLILI *, Sabine CRUNAIRE, Marie VERRIELE,

More information

INDOOR AIR QUALITY AND MATERIAL EMISSIONS IN NEW BUILDINGS

INDOOR AIR QUALITY AND MATERIAL EMISSIONS IN NEW BUILDINGS INDOOR AIR QUALITY AND MATERIAL EMISSIONS IN NEW BUILDINGS H Järnström * and K Saarela VTT Building and Transport, Service Centre, P.O. Box. 141, FIN-244 VTT, Finland ABSTRACT A research project was established

More information

Analysis of VOCs & Formaldehyde

Analysis of VOCs & Formaldehyde Analysis of VOCs & Formaldehyde Indoor air quality testing in homes, schools & offices Tim Robinson Waverton Analytics Ltd Tim_Robinson@wavertonanalytics.com Preview Factors that define or influence indoor

More information

CASE STUDY. Improved Radon Needs More Air

CASE STUDY. Improved Radon Needs More Air FOR MORE INFORMATION, VISIT: HTTP://BUILDEQUINOX.COM/BLACKBOX/ CASE STUDY Improved Radon Needs More The subject of this test is a well maintained home occupied by a family of four (two adults and two children).

More information

Standards for evaluating indoor air

Standards for evaluating indoor air Indoor and Built Environment, 2011, Volume 20, Issue 4, pp389 392 Standards for evaluating indoor air Chuck Yu 1 *and Derrick Crump 2 1 International Society of the Built Environment (ISBE), UK Email:

More information

Indoor Air Quality Solutions

Indoor Air Quality Solutions Indoor Air Quality Solutions Ultimate Solutions for Indoor Air Quality Investigation Demand for quality indoor air continues to increase as we are spending more time indoors than ever before. Indoor air

More information

Investigation of indoor climate in a naturally ventilated office building

Investigation of indoor climate in a naturally ventilated office building Indoor Air 2008, 17-22 August 2008, Copenhagen, Denmark - Paper ID: 784 Investigation of indoor climate in a naturally ventilated office building Tine S. Larsen,*, Olena Kalyanova, Rasmus Lund Jensen and

More information

Designing Air-Distribution Systems To Maximize Comfort

Designing Air-Distribution Systems To Maximize Comfort Designing Air-Distribution Systems To Maximize Comfort By David A. John, P.E., Member ASHRAE An air-distribution system that provides occupant thermal comfort can be a complicated system to predict and

More information

Rapid Microchamber Tests for Screening Chemical Emissions from Car Trim in Accordance with ISO

Rapid Microchamber Tests for Screening Chemical Emissions from Car Trim in Accordance with ISO Application Note Rapid Microchamber Tests for Screening Chemical Emissions from Car Trim in Accordance with ISO 119- Abstract This Application Note demonstrates the efficiency and reliability of Markes

More information

INDOOR AIR QUALITY IN SCHOOLS: THE IMPACT OF VENTILATION CONDITIONS AND INDOOR ACTIVITIES

INDOOR AIR QUALITY IN SCHOOLS: THE IMPACT OF VENTILATION CONDITIONS AND INDOOR ACTIVITIES INDOOR AIR QUALITY IN SCHOOLS: THE IMPACT OF VENTILATION CONDITIONS AND INDOOR ACTIVITIES J Ribéron *, P O'Kelly, F Maupetit and E Robine Sustainable Development Dept., Centre Scientifique et Technique

More information

ASHRAE Standard INTRODUCTION AND OVERVIEW Plus a few other issues: Outdoor Air Quality and the IAQ Procedure

ASHRAE Standard INTRODUCTION AND OVERVIEW Plus a few other issues: Outdoor Air Quality and the IAQ Procedure ASHRAE Standard 62.1-2004 INTRODUCTION AND OVERVIEW Plus a few other issues: Outdoor Air Quality and the IAQ Procedure Andy Persily ASHRAE Fellow National Institute of Standards and Technology ASHRAE Winter

More information

Chapter 14 Indoor Air Quality

Chapter 14 Indoor Air Quality Chapter 14 Indoor Air Quality 1 Indoor Environment and Built Environment Buildings Transportations vehicles 2 1 Indoor Air Quality (IAQ) Indoor air quality (IAQ) is the quality of air in an indoor environment.

More information

Comparison of emission specifications in the US and in Europe

Comparison of emission specifications in the US and in Europe Indoor Air 2008, 17-22 August 2008, Copenhagen, Denmark - Paper ID: 954 Comparison of emission specifications in the US and in Europe Thomas Neuhaus * and Reinhard Oppl Eurofins Product Testing A/S, Denmark

More information

MEASUREMENT OF VOC AND SVOC EMITTED FROM AUTOMOTIVE INTERIOR MATERIALS BY THERMAL DESORPTION TEST CHAMBER METHOD

MEASUREMENT OF VOC AND SVOC EMITTED FROM AUTOMOTIVE INTERIOR MATERIALS BY THERMAL DESORPTION TEST CHAMBER METHOD MEASUREMENT OF VOC AND SVOC EMITTED FROM AUTOMOTIVE INTERIOR MATERIALS BY THERMAL DESORPTION TEST CHAMBER METHOD K Hoshino 1*, S Kato 2, S Tanabe 3, Y Ataka 4, S Ogawa 1, T Shimofuji 1 1 GL Sciences Inc.,

More information

BIU Büro für integrierten Umweltschutz

BIU Büro für integrierten Umweltschutz Eurofins VOC Seminar 2015 for Manufacturers at Frankfurt Airport 28 th October 2015 Eco-friendly and low emitting building products for sustainable and green buildings certified by LEED, BREEAM & DGNB

More information

Indoor Air Quality (IAQ) Requirements

Indoor Air Quality (IAQ) Requirements University of New Hampshire University of New Hampshire Scholars' Repository Division 01 General Requirements Chapter 5 Technical Construction and Renovation Standards 1-25-2013 013560 - Indoor Air Quality

More information

PRINCIPLES AND NEW DEVELOPMENTS OF THE EMISSION CLASSIFICATION OF BUILDING MATERIALS IN FINLAND

PRINCIPLES AND NEW DEVELOPMENTS OF THE EMISSION CLASSIFICATION OF BUILDING MATERIALS IN FINLAND PRINCIPLES AND NEW DEVELOPMENTS OF THE EMISSION CLASSIFICATION OF BUILDING MATERIALS IN FINLAND L Sariola 1* and E Kukkonen 2 1 Building Information Foundation RTS, Finland 2 Finnish Society of Indoor

More information

Economic and Social Council

Economic and Social Council United Nations Economic and Social Council ECE/TRANS/WP.29/GRPE/2017/10 Distr.: General 27 March 2017 Original: English Economic Commission for Europe Inland Transport Committee World Forum for Harmonization

More information

Measurement of emissions to air of volatile aldehydes, VOCs and SVOCs from automotive interiors

Measurement of emissions to air of volatile aldehydes, VOCs and SVOCs from automotive interiors Indoor Air 2008, 17-22 August 2008, Copenhagen, Denmark - Paper ID: 593 Measurement of emissions to air of volatile aldehydes, VOCs and SVOCs from automotive interiors Chuck Yu 1,*, Veronica Brown 1, Derrick

More information

Air STANDARD. FOR COMMERCIAL INTERIORS v2.0. RESET Air STANDARD for Commercial Interiors v2.0. Copyright 2018 RESET

Air STANDARD. FOR COMMERCIAL INTERIORS v2.0. RESET Air STANDARD for Commercial Interiors v2.0. Copyright 2018 RESET Air STANDARD FOR COMMERCIAL INTERIORS v2.0 Table of Contents 2.2.0 Preface 2.2. Certification Approach 2.2.2 Indoor Air Quality Performance Targets 2.2.3 Data Analysis Algorithm 2.2.4 Data Provider Requirements

More information

Overview on Indoor Thermal Environment and Air Quality Issues for Residential Buildings in Japan

Overview on Indoor Thermal Environment and Air Quality Issues for Residential Buildings in Japan ctbuh.org/papers Title: Author: Subject: Keywords: Overview on Indoor Thermal Environment and Air Quality Issues for Residential Buildings in Japan Hiroshi Yoshino, Professor, Tohoku University MEP Energy

More information

What is molecular filtration?

What is molecular filtration? What is molecular filtration? Molecular Filtration Fundamentals Molecules are 1,000-10,000 times smaller than the particles removed by HEPA filters There are many, many more molecules in the air than particles

More information

White paper: Indoor air quality and carbon dioxide sensors

White paper: Indoor air quality and carbon dioxide sensors White paper: Indoor air quality and carbon dioxide sensors January 30, 2017 Author: Markku Rouvala, Hardware Design manager, New Nordic Engineering. Email: mr@n.build Indoor air quality depends mostly

More information

CASE STUDY. Two Dogs and Two Cats Insufficient Air Exchange with High CO2

CASE STUDY. Two Dogs and Two Cats Insufficient Air Exchange with High CO2 FOR MORE INFORMATION, VISIT: HTTP://BUILDEQUINOX.COM/BLACKBOX/ CASE STUDY Two Dogs and Two Cats Insufficient Exchange with High CO2 A Black Box IAQ was placed in the main living area of a pre-1900 home.

More information

Quality and Performance in Construction Delivered by Trusted expertise for the product manufacturing sector

Quality and Performance in Construction Delivered by Trusted expertise for the product manufacturing sector Quality and Performance in Construction Delivered by Building responsibly World-class high performing supply chains & products you can build on Trusted expertise for the product manufacturing sector www.bregroup.com

More information

Trends and drivers in the Finnish ventilation and AC market

Trends and drivers in the Finnish ventilation and AC market Trends and drivers in the Finnish ventilation and AC market Jarek Kurnitski, D.Sc. Docent Helsinki University of Technology Finnish Society of Indoor Air Quality and Climate, FiSIAQ 1 Contents Indoor climate

More information

Customer : SILVADEC SA Ms POUDRÉ Number of sample : 1. Y. MALVAUT (temporary replacement of C. NICOLET, Technical Manager)

Customer : SILVADEC SA Ms POUDRÉ Number of sample : 1. Y. MALVAUT (temporary replacement of C. NICOLET, Technical Manager) Saint Ouen l'aumone, the 4 th of December 2013 Evaluation of Volatile Organic Compounds and aldehydes emitted by a Lamina Elegance, iroise gray, with a smooth finish according to ISO 16000 Report N D-101013-08326

More information

Aalborg Universitet. Formaldehyde in newly built dwellings. Gunnarsen, Lars; Logadóttir, Ásta; Funch, Lis Winther. Published in: Indoor Air 2008

Aalborg Universitet. Formaldehyde in newly built dwellings. Gunnarsen, Lars; Logadóttir, Ásta; Funch, Lis Winther. Published in: Indoor Air 2008 Downloaded from vbn.aau.dk on: March 3, 219 Aalborg Universitet Formaldehyde in newly built dwellings Gunnarsen, Lars; Logadóttir, Ásta; Funch, Lis Winther Published in: Indoor Air 28 Publication date:

More information

A STUDY ON REDUCTION EFFECT OF INDOOR AIR POLLUTANTS IN SPRING BY PLANTS

A STUDY ON REDUCTION EFFECT OF INDOOR AIR POLLUTANTS IN SPRING BY PLANTS A STUDY ON REDUCTION EFFECT OF INDOOR AIR POLLUTANTS IN SPRING BY PLANTS Jeong-Eun Song 1, Yong-Shik Kim 2, and Jang-Yeul Sohn 3 1 Dept. of Sustainable Architectural Engineering, Graduate School, Hanyang

More information

Do European standards for indoor air quality take into account outdoor air quality? Professor Bjarne W. Olesen, PhD, Department of Civil Engineering

Do European standards for indoor air quality take into account outdoor air quality? Professor Bjarne W. Olesen, PhD, Department of Civil Engineering Do European standards for indoor air quality take into account outdoor air quality? Professor Bjarne W. Olesen, PhD, Department of Civil Engineering Technical University of Denmark Global impact on people

More information

Vehicle Interior Air Quality: Volatile Organic Compounds

Vehicle Interior Air Quality: Volatile Organic Compounds Vehicle Interior Air Quality: Volatile Organic Compounds Douglas Booker 1,3, Nick Molden 2, Charlotte Farr 3 NAQTS 1, Emissions Analytics 2, Lancaster University 3 8 th UCR PEMS Conference March 22 nd

More information

Vehicle Interior Air Quality: Volatile Organic Compounds

Vehicle Interior Air Quality: Volatile Organic Compounds Vehicle Interior Air Quality: Volatile Organic Compounds Douglas Booker 1,3, Nick Molden 2, Charlotte Farr 3 NAQTS 1, Emissions Analytics 2, Lancaster University 3 8 th UCR PEMS Conference March 22 nd

More information

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Available online at   ScienceDirect. Energy Procedia 78 (2015 ) Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 2857 2862 6th International Building Physics Conference, IBPC 2015 Optimized Blind Control Method to minimize Heating,

More information

VENTILATION RATES AND IAQ IN EUROPEAN STANDARDS AND NATIONAL REGULATIONS

VENTILATION RATES AND IAQ IN EUROPEAN STANDARDS AND NATIONAL REGULATIONS VENTILATION RATES AND IAQ IN EUPEAN STANDARDS AND NATIONAL REGULATIONS Nejc Brelih *1, Olli Seppänen 1 1 REHVA Federation of European heating, ventilation and air conditioning associations Rue Washington,

More information

Thermal Comfort and Indoor Air Quality Evaluation of Hospital Patient Ward in Malaysia

Thermal Comfort and Indoor Air Quality Evaluation of Hospital Patient Ward in Malaysia Thermal Comfort and Indoor Air Quality Evaluation of Hospital Patient Ward in Malaysia F. AZIZPOUR, S. MOGHIMI, E. SALLEH, S.MAT, C.H.LIM, K. SOPIAN Solar Energy Research Institute, Universiti Kebangsaan

More information

C-TRAC Meeting # 8 Topic: IgCC Chapter 8: Indoor Environmental Quality Wednesday August 18, 2010, 3 5:30 pm

C-TRAC Meeting # 8 Topic: IgCC Chapter 8: Indoor Environmental Quality Wednesday August 18, 2010, 3 5:30 pm Utilities electric stormwater wastewater water 700 Wood Street PO Box 580 Fort Collins, CO 80522 970.221.6700 970.221.6619 fax 970.224.6003 TDD utilities@fcgov.com fcgov.com/utilities C-TRAC Meeting #

More information

Understanding Requirements for VOC Content vs. Emissions for Adhesives

Understanding Requirements for VOC Content vs. Emissions for Adhesives Understanding Requirements for VOC Content vs. Emissions for Adhesives Michael Lehmann National Sales Manager UL Environment 2013 Underwriters Laboratories, Inc. Agenda Introduction to Air Quality VOC

More information

THE EFFECT OF DUCT CLEANING ON INDOOR AIR QUALITY IN OFFICE BUILDINGS

THE EFFECT OF DUCT CLEANING ON INDOOR AIR QUALITY IN OFFICE BUILDINGS THE EFFECT OF DUCT CLEANING ON INDOOR AIR QUALITY IN OFFICE BUILDINGS S Kolari 1*, M Luoma 1, M Ikäheimo 2 and P Pasanen 2 1 VTT Technical Research Centre of Finland, Espoo, Finland 2 University of Kuopio,

More information

Work Package 2: Performance of naturally ventilated buildings

Work Package 2: Performance of naturally ventilated buildings Work Package 2: Performance of naturally ventilated buildings Detailed Monitoring Report The architectural office of Malmö (SE1) Åke Blomsterberg, Charlotte Svensson J&W Consulting Engineers Building Physics,

More information

DISPLACEMENT VENTILATION

DISPLACEMENT VENTILATION DISPLACEMENT VENTILATION D3 OVERVIEW The fundamental approach to displacement ventilation utilizes the natural buoyancy forces created by the convective flows from heat sources in the space. As supply

More information

Corridor Pressurization System Performance in Multi-Unit Residential Buildings

Corridor Pressurization System Performance in Multi-Unit Residential Buildings Corridor Pressurization System Performance in Multi-Unit Residential Buildings Lorne Ricketts Student Member ASHRAE John Straube, PhD, P.Eng. Associate Member ASHRAE ABSTRACT Corridor pressurization based

More information

Indoor Air Quality Assessments

Indoor Air Quality Assessments HS13_IAQ_SOP 1. Purpose and Requirements Symptoms arising from poor indoor air quality often mimic those symptoms commonly associated with a cold, flu or allergies. These symptoms may include upper respiratory

More information

Indoor Air Quality Program

Indoor Air Quality Program Environmental Health and Safety Office Indoor Air Quality Program The purpose of this program is to inform the University community about indoor air quality (IAQ). Adopted: May 28, 2008 Revised: April

More information

Indoor Air Quality Report

Indoor Air Quality Report Indoor Air Quality Report Test Number: Normal Occupancy Name: Equinox Email address: test@buildequinox.com Test Location: Urbana, IL Report Date: 12/20/2012 Overview: This Black Box IAQ report provides

More information

Dynamic Small-Scale Chamber Emissions Test

Dynamic Small-Scale Chamber Emissions Test Dynamic Small-Scale Chamber Emissions Test Classroom Desk Compliance Report Per LEED for Schools & CHPS Low-Emitting Furniture Criteria flipit Desk (Exemplar for certification and product bracketing) Prepared

More information

A. The project is intended to achieve LEED Certification at the Silver Level per the U.S. Green Building Council LEED for Schools 2007 rating system.

A. The project is intended to achieve LEED Certification at the Silver Level per the U.S. Green Building Council LEED for Schools 2007 rating system. SECTION 23 01 01 HVAC LEED REQUIREMENTS PART 1 -GENERAL 1.1 WORK INCLUDES A. Compliance with LEED project requirements. B. Coordination of LEED construction phase activities. C. Data gathering of construction

More information

Volatile organic pollution in highly populated areas in South Africa

Volatile organic pollution in highly populated areas in South Africa Volatile organic pollution in highly populated areas in South Africa H. J. van der Walt 1, J. J. Pienaar 2 & J. B. McQuaid 3 1 Water and Environmental Technology, Sasol Technology R&D, South Africa 2 Atmospheric

More information

Economic and Social Council

Economic and Social Council United Nations Economic and Social Council ECE/TRANS/WP.29/GRPE/75/Add.2 Distr.: General 2 August 2017 English only Economic Commission for Europe Inland Transport Committee World Forum for Harmonization

More information

IAQ benchmarks of air-conditioned offices in Hong Kong

IAQ benchmarks of air-conditioned offices in Hong Kong Indoor Air 2008, 7-22 August 2008, Copenhagen, Denmark - Paper ID: 20 IAQ benchmarks of air-conditioned offices in Hong Kong K.W. Mui *, L.T. Wong ** and P.S. Hui Department of Building Services Engineering,

More information

Recently issues on Indoor air quality in Korea

Recently issues on Indoor air quality in Korea Recently issues on Indoor air quality in Korea Jee Yeon Jeong, PhD, P.E Department of Occupational and Environment Health Yongin University I. Introduction Now days, the air quality in the indoor environment

More information

Environmental Assessment of Building Materials for Good Indoor Air Quality

Environmental Assessment of Building Materials for Good Indoor Air Quality Environmental Assessment of Building Materials for Good Indoor Air Quality Miriam García-González (1), Anna Widheden (2), Sarka Langer (2) (1) Tecnalia Research & Innovation (2) IVL Swedish Environmental

More information

Economic and Social Council

Economic and Social Council United Nations Economic and Social Council ECE/TRANS/WP.29/2017/136 Distr.: General 25 August 2017 Original: English Economic Commission for Europe Inland Transport Committee World Forum for Harmonization

More information

SIP Homes: Built for a Lifetime of Comfort and Value

SIP Homes: Built for a Lifetime of Comfort and Value Innovative Steel Structures (949) 607-9729 leosmarthomes@gmail.com SIP Homes: Built for a Lifetime of Comfort and Value In also offer high-performance, sustainable homes made with Structural Insulated

More information

Chapter Overview. Chapter 3: Sources of Air Pollution 3-1. Role of Sources of Air Pollution in an Air Quality Management Program.

Chapter Overview. Chapter 3: Sources of Air Pollution 3-1. Role of Sources of Air Pollution in an Air Quality Management Program. 3-1 Chapter 3: Sources of Air Pollution Chapter Overview Introduction Sources of Air Pollutants Biogenic Sources (naturally occurring sources) Anthropogenic Sources (man-made sources) Mobile Sources Stationary

More information

ASHRAE s Initiatives for Energy Conservation in Existing Buildings

ASHRAE s Initiatives for Energy Conservation in Existing Buildings ASHRAE s Initiatives for Energy Conservation in Existing Buildings Lynn G. Bellenger, PE ASHRAE President Pathfinder Engineers & Architects LLP ASHRAE - Energy Conservation in Existing Buildings Commercial

More information

Measuring Indoor Air Quality presented to AAFAME Members Nov. 14, 2017

Measuring Indoor Air Quality presented to AAFAME Members Nov. 14, 2017 Measuring Indoor Air Quality presented to AAFAME Members Nov. 14, 2017 What is Indoor Air Quality? Appropriate IAQ can be defined as a function of three different components: 1) appropriate thermal comfort,

More information

Notes on Indoor Air Quality

Notes on Indoor Air Quality Notes on Indoor Air Quality Indoor Air Quality (IAQ) a Health and Safety Concern? Indoor air quality has become an important occupational health and safety concern. Energy conservation measures instituted

More information

THE IMPACTS OF HUMAN ACTIVITIES ON INDOOR AIR QUALITY IN PASSIVE HOUSES. Ryan Militello-Hourigan, PE Shelly Miller, PhD

THE IMPACTS OF HUMAN ACTIVITIES ON INDOOR AIR QUALITY IN PASSIVE HOUSES. Ryan Militello-Hourigan, PE Shelly Miller, PhD THE IMPACTS OF HUMAN ACTIVITIES ON INDOOR AIR QUALITY IN PASSIVE HOUSES Ryan Militello-Hourigan, PE Shelly Miller, PhD PERSONAL BACKGROUND Ryan Militello-Hourigan, PE (CA) Graduate Researcher Previously,

More information

AIR POLLUTION CAUSED BY VOLATILE ORGANIC COMPOUND (BENZENE, TOLUENE AND XYLENE) IN HO CHI MINH CITY AND MITIGATION SOLUTIONS

AIR POLLUTION CAUSED BY VOLATILE ORGANIC COMPOUND (BENZENE, TOLUENE AND XYLENE) IN HO CHI MINH CITY AND MITIGATION SOLUTIONS AIR POLLUTION CAUSED BY VOLATILE ORGANIC COMPOUND (BENZENE, TOLUENE AND XYLENE) IN HO CHI MINH CITY AND MITIGATION SOLUTIONS Nguyen Dinh Tuan and Do Thi Hong Hoa Hoa Sen University, Vietnam L/O/G/O June,

More information

THE REVISION OF STANDARD 62: WHAT A DIFFERENCE A DECADE MAKES

THE REVISION OF STANDARD 62: WHAT A DIFFERENCE A DECADE MAKES THE REVISION OF STANDARD 62: WHAT A DIFFERENCE A DECADE MAKES A Persily * National Institute of Standards and Technology, Gaithersburg, MD, USA ABSTRACT The American Society of Heating, Refrigerating and

More information

Components of the Steering Committee Charter

Components of the Steering Committee Charter Components of the Steering Committee Charter Committee objectives Roles and responsibilities Standard Committee Meeting Procedures Deliberation and Consensus Meeting frequency Meeting dates, times, and

More information