Energy labelling and ecodesign requirements for heat pumps

Size: px
Start display at page:

Download "Energy labelling and ecodesign requirements for heat pumps"

Transcription

1 Prepared for the Danish Energy Agency by Pia Rasmussen, Danish Technological Institute 31 December 2011 Energy labelling and ecodesign requirements for heat pumps The following document describes adopted and expected EU legislation for air- to- air, air- to- water and brine- to- water heat pumps. In addition, calculations have been made for selected heat pumps. is the annual (seasonal COP) that is used as a benchmark in the regulations pursuant to the Ecodesign Directive. The results are used to assess requirements (ecodesign requirements) and labelling scales for the different types of heat pump and are compared with the national requirements in the Danish building code (BR10) and figures for heat pumps on the Danish marked 2011 This document was written in parallel with the document "Calculation of for heat pumps according to EN 14825", which provides a general introduction to measurement points and calculation methodology for. Ecodesign and heat pumps Ecodesign work is the basis for the development of labelling and ecodesign requirements for a number of - using appliances, including heat pumps. Ecodesign work is divided into several lots, each covering different areas that are progressing in different stages towards formulation and adoption of legislation for the area. Different types of heat pumps are covered by different lots, which are illustrated in the following figure. Air-to-water Water based central heating Sanitary hot water Lot 1 : Boilers Lot 2 : water heaters Brine-to-water Water based central heating Sanitary hot water Lot 1 : Boilers Lot 2 : water heaters Air-to-air Heating + Cooling < 12 kw Cooling > 12 kw Heating > 12 kw Lot 10: Residential room conditioning appliances Lot 6: Airconditioning and ventilation systems Lot 21: Central air heating products Air-to-water Heating > 12 kw Lot 21: Central air heating products Figure 1: Overview of which lots cover the various types of heat pumps Exhaust air heat pumps are not covered by the lots. 1

2 The figure shows that a total of five lots cover heat pumps. The status of these lots are: Area Status Implementation of the step 1 requirements Lot 1: Boilers Expected adoption 2012 expected in 2014 Lot 2: Water heaters Expected adoption 2012 expected in 2014 Lot 6: Airconditioning & ventilation Preliminary study in preparation? Lot 10: Residential room conditioning Adopted and published 1 Jan Lot 21: Central hot air heating Preliminary study in preparation? Table 1: Overview of status of European legislation on heat pumps Lot 1 on space heaters for water- based central room heating systems and combined room- and water heating, Lot 2 on heating sanitary hot water have been synchronised in the work flow. A data basis for future assessment of legislative options is still under preparation for Lot 6 and Lot 21. The following description focuses on Lot 1 for brine- to- water and air- to- water heat pumps and Lot 10 for air- to- air heat pumps with a rated capacity below 12 kw. Air- to- air heat pumps with a rated capacity below 12 kw Legislation for air- to- air heat pumps with a rated capacity below 12 kw was adopted in spring 2011 and will enter into force on 1 January The legislation includes both requirements and labelling, and covers requirements for heating as well as cooling. As illustrated in the following figure, regulations will be introduced in stages over several years. 1.jan jan jan jan jan 2019 Energy requirements 1 Energy requirements 2 Energy label 1 Energy label 2 Energy label 3 Energy label 4 Figure 2: Timetable for introduction of requirements and labels for air- to- air heat pumps Energy requirements for the first and second round are shown in the following figure. As the figure shows, the reduced requirement can be met, if heat pumps use particularly environmentally friendly refrigerants. 1.jan SEER GWP>150 3,40 3,60 GWP 150 3,06 3,24 1.jan 2014 SEER SEER < 6 kw GWP>150 GWP 150 3,80 4,60 3,42 4, kw GWP>150 3,80 4,30 GWP 150 3,42 3,87 Figure 3: 1. and 2. Minimum requirements for of air- to- air heat pumps 2

3 For most heat pumps, this means that they must observe a of 3.40 in 2013 and 3.80 in Similarly, a number of classes based on values will be introduced. These will be: A+++ 5,10 A++ 4,60 < 5,10 A+ 4,00 < 4,60 A 3,40 < 4,00 B 3,10 < 3,40 C 2,80 < 3,10 D 2,50 < 2,80 E 2,20 < 2,50 F 1,90 < 2,20 G < 1,90 SEER 8,50 6,10 SEER < 8,50 5,60 SEER < 6,10 5,10 SEER < 5,60 4,60 SEER < 5,10 4,10 SEER < 4,60 3,60 SEER < 4,10 3,10 SEER < 3,60 2,60 SEER < 3,10 SEER < 2,60 Figure 4: Scale for labelling of air- to- air heat pumps Until the above labelling enters into force, the current European labelling will apply which is based on at a single operating point. To achieve an A label under the "old" scale, COP must be more than 3.6 at operating point 7 C/20 C. In Denmark, new air- to- air heat pumps for installation must have an A label. Calculated values for air- to- air heat pumps In order to assess the magnitude of the classes, as well as the requirements, values have been calculated for a number of heat pumps that comply with requirements included in the list of air- to- air heat pumps prepared by Danish Energy Saving Trust 1. At present, no calculated annual performance is used for air- to- air heat pumps. Instead, requirements included in the requirements for the Danish Energy Saving Trust list have been determined at specific operating points, as illustrated below. Where the temperature refer to the air temperature at the cold side (outdoor temperature), while the temperature at the warm side (indoor temperature) is constant and 20 C Temperature COP minimum requirements -7 C 2 C 2,5 2,8 7 C 3,6 Table 2: Energy requirements at various temperatures for inclusion on the Danish Energy Saving Trust list of - efficient air- to- air heat pumps has been calculated for five heat pumps, for which data has been available for four full load test points (- 15 C, - 7 C, 2 C and 7 C) and two part load test points (2 C and 7 C) measured at approx. 50% capacity. Values from these test points have been interpolated and extrapolated to the values required by 1 The Danish Energy Saving Trust is an independent, public- sector organisation, promoting in households, the public sector and the business community. 3

4 the calculation. The heat pumps are all with variable speed compressors and is calculated on the basis of interpolated part load based on the stated part load points. For calculation purposes, it is assumed that all of the air- to- air heat pumps are reversible, which makes consumption for various standby consumptions in the calculation minimal, as the number of hours in the different operating conditions is significantly less. The following has been assumed: a crankcase heater consumption of 10W, a thermostat off consumption of 2W and an off consumption of 1W for all sizes of heat pump, which means a maximum of 0.2% for the value. The results of the calculations are shown in the following table, in which both the value and the corresponding label are indicated. As mentioned previously, the requirement for will be 3.4 in 2013 and 3.8 from 2014 under the new European scheme. Navn Energy label VP1 4,12 VP2 4,13 VP3 4,05 VP4 3,92 VP5 3,99 A+ A+ A+ A A Table 3: Calculated values for five heat pumps from the Danish Energy Saving Trust list of - efficient air- to- air heat pumps Trends in requirements and labelling of air- to- air heat pumps The five selected heat pumps all have values of around 4.0, and the future European requirements will be 3.4 in 2013 and 3.8 from This means that all of these heat pumps will comply with both the first as well as the second set of ecodesign requirements. The requirements in the Danish Energy Saving Trust list are therefore more stringent than future Ecodesign requirements. Furthermore, the results show that these heat pumps will be at the top of the A class or at the bottom of the A+ class. The five selected heat pumps in this analysis represent the best heat pumps currently available on the Danish market. More of these heat pumps are within the A+ class and there is therefore room to reward further development in the of air- to- air heat pumps with even better labels. However, the A+ label will not become available before 2015 and A++ label before This means that there is no incentive to improve of the currently best heat pumps before 2017, at which time such an improvement can be reflected in the label. Design of label for air- to- air heat pumps As illustrated in figure 2, the label will be introduced in four versions. The design of the four labels will be similar, with the exception that the labelling scale will be adjusted every other two year. 4

5 The first label is shown in figure 5. The scale on the first label will be A to G. The label shows the of heating in the three different climate zones (different climate conditions) as well as cooling. Energy label information is optional for cooling, and for Warmer and Colder climate conditions. The label also indicates noise levels form the inside part as well as outside part. Moreover, the label shows the design capacity in kw, calculated and annual consumption for the three climate zones, and for cooling. Design capacity is the heating demand at the design temperature and it is the same as is used in the calculation (Average = - 10 C, Colder = - 22 C and Warmer = 2 C). This means that an label is not only a tool to assess the of heat pumps; consumers can use labels to choose the size of heat pump to suit their needs, which could prove to be crucial for the actually experienced by the consumer in practice. Figure 5: European label for air- to- air heat pumps from 1 Jan Shown in figure 6 is the design for the next three labels to be introduced on 1 January 2015, 2017 and 2019, respectively. The best heat pumps on the Danish marked today, which are currently eligible for the A+ label, will therefore only be able to obtain an A label until Similarly, from 2015 to 2017 these pumps will only be able to obtain an A+ label, and from 2017 to 2019 only an A++. 5

6 Figure 6: Energy labels for air- to- air heat pumps from 1 Jan. 2015, 2017 and 2019 Air- to- water heat pumps and brine- to- water heat pumps So far, no common European regulation has been adopted for the area covered by Lot 1 "Space heaters and combination heaters", which includes air- to- water and brine- to- water heat pumps. However, specific proposals have been drafted and updated documents were released on 2 February, on which the following is based. The regulation is expected to be adopted in Furthermore, the requirements will most likely become applicable two years after the adoption. Expected implementation is shown in the following figure Energy requirements 1 Energy requirements 2 Energy label 1 Energy label 2 Figure 7: Expected timetable for implementation of requirements and labels for air- to- water and brine- to- water heat pumps Air- to- water and brine- to- water heat pumps will be compared across heating technologies and will therefore be assessed according to the same labelling scale as, for example, oil- fired boilers and gas- fired boilers. However, a special labelling scale has been made for heat pumps for low- temperature systems, such as underfloor heating. This is due to the fact that the output temperature plays a significant role for the of the heat pumps. The requirements have been determined for underfloor heating with a design flow 6

7 temperature of 35 C, corresponding to "low temperature" in the EN14825 standard. The comprehensive label is designed for radiator systems with design temperatures of 55 C. Conversely, different ecodesign requirements are set for gas and oil boilers, electrical boilers and heat pumps for different output temperatures. The following analysis focuses solely on space heating and not heating of sanitary hot water. The proposal for the EU regulations provides for labelling of combined sanitary hot water and space heating. In order to compare input across different technologies, an factor for space heating is applied known as "Seasonal space heating " as a benchmark (referred to as η s in the figures). The factor describes the heat output compared to the input. For electricity, a conversion factor of 2.5 is used as input, known as the primary factor (PEF), where the calculated value is divided by the PEF value on the assumption that it takes 2.5 units of primary fuel to produce 1 unit of electricity. The Ecodesign requirements are shown in figure C 35 C 2014 ηs ηs 2,25 90 % 2, % 2016 ηs ηs 2, % 3, % Figure 8: 1. and 2. Minimum requirements for of air- to- water and brine- to- water heat pumps Similarly, a number of classes based on values will be introduced. Energy classes for radiator heating are shown to the left and underfloor heating (low temperature) to the right. A+++ A++ A+ A > 3,75 3,13 < 3,75 2,45 < 3,13 2,25 < 2,45 ηs > 150 % 125 % ηs < 150 % 98 % ηs < 125 % 90 % ηs < 98 % A+++ A++ A+ A > 4,38 3,75 < 3,88 3,08 < 3,75 2,88 < 3,08 ηs > 175 % 139 % ηs < 175 % 123 % ηs < 150 % 115 % ηs < 123 % B 2,05 < 2,25 82 % ηs < 90 % B 2,68 < 2, % ηs < 115 % C 1,88 < 2,05 75 % ηs < 82 % C 2,50 < 2, % ηs < 107 % D 0,93 < 1,88 37 % ηs < 75 % D 1,55 < 2,50 62 % ηs < 100 % E 0,85 < 0,93 34 % ηs < 37 % E 1,48 < 1,55 59 % ηs < 62 % F 0,75 < 0,85 30 % ηs < 34 % F 1,38 < 1,48 55 % ηs < 59 % G < 0,75 ηs < 30% G < 1,38 ηs < 55 % Figure 9: Scales for labelling of air- to- water and brine- to- water heat pumps for 55 C (left) and 35 C (right) In addition, there are two correction factors that influence the calculation of η s in relation to. Due to temperature regulation, 3% is deducted for heat pumps. Due to consumption for geothermal 7

8 heating, a further 5% is deducted for brine- to- water heat pumps alone. Therefore, the calculation of η s is as follows: Air- to- water heat pumps: η! =!"#$!"# 3% Brine- to- water heat pumps: η! =!"#$!"# 3% 5% Correction factors have not been included in in figure 9. To find the exact corresponding, the shown should be added 0,075 for air- to water heat pumps and the value for brine- to water heat pumps should be added 0, ,125. The magnitude of these requirements and classes is assessed by calculating values for selected heat pumps that comply with the requirements of the Danish building regulation The requirements of Building regulation 2010 are based on a nominal which is calculated on the basis of four or five full load test points. In the following, calculations and results are reviewed for air- to- water and brine- to- water heat pumps, respectively, as well as for, radiators and underfloor heating. Since the nominal is based on other test points than, the values for the calculations have been interpolated and extrapolated. The following has been assumed: a crankcase heater consumption of 15W, a thermostat off consumption of 2W and an off consumption of 1W for all sizes of heat pumps. This means that these consumptions are more significant for smaller heat pumps than large heat pumps. For instance, this means a reduction in of approx. 1.3% for a heat pump with a nominal capacity of 6kW, compared with a reduction in of approx. 0.5% for a heat pump with a capacity of 13kW. Furthermore, calculations are based on full load data in accordance with the calculation method. values will be slightly higher if part load tests are conducted for frequency controlled heat pumps. For further information about the calculation method, please see "Calculation of for heat pumps according to EN 14825". Air- to- water heat pumps calculation results The test points for calculating the nominal and the values for radiator heating and underfloor heating are shown in the following table. See annex 1 of "Calculation of for heat pumps according to EN 14825" for a general overview of test points, which also includes the climate profiles Warmer and Colder. Test points nominal Test points 55 C reference (radiator) Test points 35 C reference (underfloor heating) 7/45 C - 7/52 C - 7/34 C 2/45 C 2/42 C 2/30 C 7/35 C 7/36 C 7/27 C 2/55 C 12/30 C 12/24 C - 7/55 C 8

9 Table 4: Test points for the calculation of nominal and values for air- to- water heat pumps Results air- to- water 55 C Radiator heating Nine heat pumps have been selected from the Danish Energy Agency's list of heat pumps (dated December 2011, at that time almost 170 A/W were at the list). All nine pumps are immediately above or below the requirements for stipulated in the building regulations. Building regulation 2010 stipulates a nominal of more than 2.7 from 1 January The table below shows the nominal and calculated values for the heat pumps. Seasonal space heating (η s ) is also shown in the table because EU regulation for this type of heat pump is based on. Name Capacity 7/45 Optimum Pdesign h Nominal (NEF) Calculated Energy (η s ) /NEF Expected class VP % 98% A+ VP % 97% A+ VP % 103% A+ VP % 98% A+ VP % 101% A+ VP % 96% A+ VP % 101% A+ VP % 100% A+ VP % 103% A+ Table 5: calculation results for air- to- water heat pumps with a 55 C design flow temperature; radiator heating The value is calculated from η s and the correction factor on 3% is included. The results above have relatively little uncertainty, as test values of the nominal fall within the same temperature range as the values that are used in the calculation. Only the point 12/30 C falls outside the available test points from the nominal test. However, as heating demand decreases with increasing temperatures, it is assumed that this point only has a peripheral impact on the value. The results show a strong correlation between the calculated value for nominal and the calculated value. This is also illustrated in the last column in which the calculated value has been divided by the nominal (NEF). The /NEF ratio indicates that the European calculation method represents heat pump operation under Danish conditions just as well as the existing Danish nominal. If the current requirements of the Danish Building regulation 2010 for are converted, they correspond to a requirement of 108%. This requirement will be tightened no later than 2015, with the 9

10 adoption of new building regulations. EU ecodesign requirements for both 2013 (90%) and 2015 (100%) are less than the Danish requirements. Moreover, the results show that all the nine heat pumps will all obtain the A+ label. Results of air- to- water 35 C underfloor heating Building regulation 2010 stipulates a nominal of 3.2 for underfloor heating. values for the same nine air- to- water heat pumps have been calculated. All the selected heat pumps have a nominal above the requirement of Building regulation The results are shown in the following table. Name Capacity 7/45 Optimum Pdesign Nominal NEF Calculated Energy ((η s )) /NEF Expected class VP % 108% A++ VP % 96% A+ VP % 102% A+ VP % 109% A+ VP % 104% A+ VP % 110% A+ VP % 105% A+ VP % 104% A+ VP % 107% A++ Table 6: calculation results for air- to- water heat pumps with 35 C design flow temperature; underfloor heating The value is calculated from η s and the correction factor on 3% is included. The results for air- to- water underfloor heating are associated with a greater degree of uncertainty as the test values for nominal have been monitored at higher temperatures than most of the values used in the calculation. This means that a certain amount of extrapolation has been applied, which results in greater uncertainty. The test points at the cold and warm side vary, which necessitate inter and extrapolation on both values. For 35 C, values are approx. 5% higher than nominal (also at 35 C), however, the two calculations are still well aligned. The difference between the two calculations could be due to differences in calculation methods for underfloor heating and radiator heating, respectively, as well as uncertainty from extrapolation. If the current requirements of the Danish Building regulation 2010 for are converted, they correspond to a requirement of 128%. This requirement will also be tightened no later than The EU ecodesign requirements for 2014 (115%) are less than the Danish requirements, while the requirements for 2016 (125%) match the requirements of Building regulation

11 Eight of the nine heat pumps will obtain the label A+ for low temperature, while one will obtain A++. Brine- to- water heat pumps calculation results The test points for calculating the nominal as well as values for brine- to- water heat pumps for radiator heating and underfloor heating are shown below. A more comprehensive overview is available in Annex 1 of "Calculation of for heat pumps according to EN 14825". Test points nominal Test points 55 C reference (radiator) Test points 35 C reference (underfloor heating) 0/45 C 0/52 C 0/34 C 0/35 C 0/42 C 0/30 C 0/55 C 0/36 C 0/27 C - 5/55 C 0/30 C 0/24 C Table 7: Test points for use in calculating nominal and values for brine- to- water heat pumps Results brine- to- water 55 C radiator heating Similarly, nine brine- to- water heat pumps have been selected from the Danish Energy Agency's heat pump list (December 2011 at that time almost 360 B/W were at the list). All are close to compliance with the requirements of the building regulations which will enter into force 1 January Building regulation 2010 requires nominal NEF of above 2.8 for brine- to- water heat pumps with a capacity of between 3kW and 6kW, and above 3.0 for heat pumps with a capacity above 6kW. The results are shown in the following table. Name Capacity 0/45 Optimum Pdesign Nominal Calculated Energy (η s ) /Nominal Expected class VP % 101 % A+ VP % 102 % A+ VP % 100 % A+ VP % 101 % A++ VP % 101 % A++ VP % 102 % A+ VP % 102 % A+ VP % 102 % A++ VP % 105 % A++ Table 8: calculation results for brine- to- water heat pumps with 55 C design flow temperature; radiator heating The value is calculated from η s and the correction factor on 8% is included. 11

12 The results above have relatively little uncertainty, as test values of the nominal fall within the same temperature range as the values that are used in the calculation. Furthermore three of the four of the nominal NEF test points have 0 C on the cold side. This means that mainly an amount of interpolation has been applied, which results in lower uncertainty. Only the point 0/30 C falls outside the nominal test points. However, this point only impacts a very small share of the annual consumption and therefore it only plays a peripheral role. Again there is a strong correlation between and the nominal, with approx. 2% better than nominal. The larger of brine- to- water heat pumps compared to air- to- water heat pumps, as indicated by the nominal (NEF) requirements in the national building regulation, is also seen for the calculated values. Existing Danish building regulation 2010 requirements came into force 1 January 2012 correspond to requirements for (η s ) of respectively 112% and 120%. The EU ecodesign requirements for 2014 (90%) and for 2016 (100%) are less than the Danish requirements which. The national requirements will also be tightened no later than As brine- to- water heat pumps are slightly more efficient than air- to- water heat pumps, the calculated efficiencies for the nine chosen heat pumps (between 119% and 137%) are significantly higher than the EU ecodesign requirements, which are 90% in the first phase and 100% in the second phase. When used for radiator heat four out of nine brine- to- water heat pumps will qualify for A++, while five heat pumps will qualify for A+. Results of brine- to- water 35 C underfloor heating Building regulation 2010 stipulates nominal NEF of more than 3.6 for brine- to- water heat pumps of between 3kW and 6kW, and 3.7 for heat pumps over 6 kw from 1 January values have been calculated for the same nine brine- to- water heat pumps. The results are shown in the following table. Name Capacity 0/45 Optimum Pdesign Nominal NEF Calculated Energy (η s ) /NEF Expected class VP % 102 % A++ VP % 103 % A++ VP % 101 % A+ VP % 101 % A++ VP % 102 % A++ VP % 102 % A++ VP % 103 % A++ VP % 103 % A++ VP % 105 % A++ Table 9: calculation results for brine- to- water heat pumps with 55 C design flow temperature; underfloor heating 12

13 The value is calculated from η s and the correction factor on 8% is included. The results for brine- to- water underfloor heating are also associated with a greater degree of uncertainty, than for radiator heating as the test values from the nominal NEF are conducted at higher temperatures than most of the values used in the calculation. Once again there is good agreement between nominal NEF and the calculation, where the value is approx. 2% higher than nominal NEF. The Danish requirements in Building regulation 2010 convert to Energy (η s ) 144% (3-6kW) and 148%(>6kW). These requirements will also be tightened by no later than The high level of efficiencies (η s )of the heat pumps is well above the EU requirements for both 2014 (115%) and 2016 (125%). The calculated Energy (η s ) for the nine pumps from the Danish list are as seen in table 9 from 147% to 170%. Eight of the nineheat pumps will be given label A++, while one heat pump will be at the top of the A+ class. Expected design of labels In the proposal for energilabeling of spaceheaters and combinations send in interservice consultation by the EU commission it is proposed to introduced the label for the product in two phases, with the A+++ class being introduced after four years the regulation enter into force. The first labels to be introduced two years after the entry into force will range from A++ to G, while the other label ranges from A+++ to D. Moreover, there will be two different labels for radiator heating and underfloor heating, respectively. These two labels are shown in figure 10 and 11. The label shows the class for radiator heating and underfloor heating, respectively. Additionally, heating capacity, including electrical backup at design temperature in the different climate zones, is indicated in the box below. This figure reflects the heating demand used in the calculations at design outdoor temperatures. These values may be a dimensioning parameter, since consumers can look for heat pumps that match their needs at a given temperature. In previous proposal for the design of the labelling, should also be indicated; 13

14 similarly to the label for air to air heat pumps, however, these are not indicated by the label in its current design. The information on the of the heat pump gives the consumer a chance to compare different heat pumps in the same class. This is especially important when the classes are as big as 25-40% which is the case for heat pumps. The label also shows the noise level of the indoor part and outdoor part, respectively. Figure 10: First label for air- to- water and brine- to- water heat pumps for radiator heating and underfloor heating If the heat pump can only produce low- temperature heating (underfloor heating), the label below should be used.figure 11: First label for air- to- water and brine- to- water heat pumps for only low temperature heating (underfloor heating) The labels shown below will be introduced two years later. Figure 12: Second label for air- to- water and brine- to- water heat pumps and underfloor heating alone 14

Heat Pumps. and energy labelling regulations

Heat Pumps. and energy labelling regulations Heat Pumps European ecodesign and energy labelling regulations CIAT: responsible thinking the Ecodesign regulation The objective of the Ecodesign directive is to bring manufacturers to design their products

More information

SIMPLICITY OR INTELLIGENCE? Heat pumps and water-cooled chillers Cooling capacity kw Heating capacity kw 30WG / 61WG / 30WGA

SIMPLICITY OR INTELLIGENCE? Heat pumps and water-cooled chillers Cooling capacity kw Heating capacity kw 30WG / 61WG / 30WGA EW ATION D E S I G N I N G I N N O V A T I V E S O L U T I O N S AIR CONDITIONING AND HEATING SOLUTIONS SIMPLICITY OR INTELLIGENCE? AQUASNAP, BECAUSE YOU SHOULD NOT HAVE TO CHOOSE. Heat pumps and water-cooled

More information

Labelling and certification of HVAC products

Labelling and certification of HVAC products Labelling and certification of HVAC products Sylvain COURTEY Eurovent - Certification s.courtey@eurovent-certification.com Introduction For some years now, the European commission has pushed for energy

More information

EHPA suggestion We thus suggest to integrate waste heat recovery into the aligned test standards.

EHPA suggestion We thus suggest to integrate waste heat recovery into the aligned test standards. EHPA review of the documents on possible requirements for air heating, cooling products and high temperature process chillers (Ecodesign ENTR Lot 6 / ENER Lot 21) EHPA, as the representative of the European

More information

L 301/14 Official Journal of the European Union DECISIONS COMMISSION

L 301/14 Official Journal of the European Union DECISIONS COMMISSION L 301/14 Official Journal of the European Union 20.11.2007 II (Acts adopted under the EC Treaty/Euratom Treaty whose publication is not obligatory) DECISIONS COMMISSION COMMISSION DECISION of 9 November

More information

The Renewable Heat Incentive

The Renewable Heat Incentive The Renewable Heat Incentive Heating RHI Expected Outcome Non-Domestic Ground Source Heat Pumps Air Source and Ground Source Heat Pumps Increased tariffs for Air and Ground Source RHI First Announcement

More information

An Integrated Solution for Commercial AC Chillers Using Variable Speed Scroll Compressors

An Integrated Solution for Commercial AC Chillers Using Variable Speed Scroll Compressors Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 An Integrated Solution for Commercial AC Chillers Using Variable Speed

More information

Borehole storage coupled with heat pump for domestic heating system and space free cooling

Borehole storage coupled with heat pump for domestic heating system and space free cooling Borehole storage coupled with heat pump for domestic heating system and space free cooling ----- The analysis of temperature traces of the boreholes and system SPF Bo He, PhD; David Kroon, Msc. Nibe AB,

More information

Product datasheet on energy consumption Greenstore 11 Combi LECP

Product datasheet on energy consumption Greenstore 11 Combi LECP The following product data complies with the requirements of EU Regulations 811/2013, 812/2013, 813/2013 and 814/2013 as supplement to the Directive 2010/30/EU. Productdata Symbol Unit Brine-to-water heat

More information

AIR-TO-AIR HEAT PUMPS EVALUATED FOR NORDIC CLIMATES- TRENDS AND STANDARDS

AIR-TO-AIR HEAT PUMPS EVALUATED FOR NORDIC CLIMATES- TRENDS AND STANDARDS Poster P.2.14-1 - AIR-TO-AIR HEAT PUMPS EVALUATED FOR NORDIC CLIMATES- TRENDS AND STANDARDS Helena Nakos, MSc, SP Technical Research Institute of Sweden, Energy Technology, Box 857, 501 15 Borås, Sweden;

More information

European KEYMARK Scheme

European KEYMARK Scheme European KEYMARK Scheme Heat Pumps Revision Number: 1.1 (2016-05-01) Page: 2 of 11 Foreword This KEYMARK Scheme for heat pumps is prepared by the European Scheme Group for Heat Pumps (SG-HP) under coordination

More information

ECODESIGN PREPARATORY STUDY FOR AIR-CONDITIONING AND VENTILATION SYSTEMS ENTR LOT 6

ECODESIGN PREPARATORY STUDY FOR AIR-CONDITIONING AND VENTILATION SYSTEMS ENTR LOT 6 ECODESIGN PREPARATORY STUDY FOR AIR-CONDITIONING AND VENTILATION SYSTEMS ENTR LOT 6 EPEE comments on the draft final preparatory study April 2012 Dear Mr Rivière, [Cc = Mr Biermann, Mr Kemna, Mrs Lichtenvort]

More information

Preparatory Studies for Ecodesign Requirements of EuPs (III)

Preparatory Studies for Ecodesign Requirements of EuPs (III) Preparatory Studies for Ecodesign Requirements of EuPs (III) ENER Lot 21 Central heating products that use hot air to distribute heat Task 8: Scenario, policy, impact and sensitivity analysis Report to

More information

> HGW WATER - WATER AND BRINE - WATER HEAT PUMPS FOR INDOOR INSTALLATION. Available range. Unit description. Options. Accessories

> HGW WATER - WATER AND BRINE - WATER HEAT PUMPS FOR INDOOR INSTALLATION. Available range. Unit description. Options. Accessories > HGW WATER - WATER AND BRINE - WATER HEAT PUMPS FOR INDOOR INSTALLATION Available range Unit type IH Heat pump IP Reversible heat pump (reversible on the refrigerant side) ECO-FRIENDLY REFRIGERANT GAS

More information

OH 1-5es - S/W Art.Nr.: B C 35 C A ++ A + A B C D E F G A + A /2013

OH 1-5es - S/W Art.Nr.: B C 35 C A ++ A + A B C D E F G A + A /2013 I II OH 1-5es - S/W Art.Nr.: B10886 55 C 35 C A ++ A + A B C D E F G A + A ++ 39 db --- db 2015 811/2013 Package (heat pumps and combination heater with heat pump) Seasonal space heating energy efficiency

More information

OH 1-6es - W/W Art.Nr.: B C 35 C A ++ A ++ A ++ A + A B C D E F G /2013

OH 1-6es - W/W Art.Nr.: B C 35 C A ++ A ++ A ++ A + A B C D E F G /2013 I II OH 1-6es - W/W Art.Nr.: B10893 55 C 35 C A ++ A + A B C D E F G A ++ A ++ 39 db --- db 2015 811/2013 Package (heat pumps and combination heater with heat pump) Seasonal space heating energy efficiency

More information

1/51 7 Heat pumps sizing

1/51 7 Heat pumps sizing 1/51 7 Heat pumps sizing heat pump characteristics testing & operation conditions balance point storage size hydraulics Heat pump 2/51 Q k rejected heat Q k P el Q v sink side P el COP Q P k el Q v Q k

More information

Draft. COMMISSION DELEGATED REGULATION (EU) No /

Draft. COMMISSION DELEGATED REGULATION (EU) No / EN EN EN EUROPEAN COMMISSION Brussels, xxx C(2011) yyy final Draft COMMISSION DELEGATED REGULATION (EU) No / of [ ] supplementing Directive 2010/30/EU of the European Parliament and of the Council with

More information

(Notices) EUROPEAN COMMISSION

(Notices) EUROPEAN COMMISSION 16.6.2012 Official Journal of the European Union C 172/1 IV (Notices) NOTICES FROM EUROPEAN UNION INSTITUTIONS, BODIES, OFFICES AND AGCIES EUROPEAN COMMISSION Commission Communication in the framework

More information

European KEYMARK Scheme

European KEYMARK Scheme European KEYMARK Scheme Heat Pumps Revision Number: 4 (07/03/2018) Page: 2 of 12 Date Description of modification Revision number 01/05/2016 Initial version 1.1 10/03/2017 Addition of air/air product Editorial

More information

European KEYMARK Scheme

European KEYMARK Scheme European KEYMARK Scheme Heat Pumps Revision Number: 2 (2017-03-10) Page: 2 of 12 Date Description of modification Revision number 01/05/2016 Initial version 1.1 10/03/2017 Addition of air/air product Editorial

More information

FTXM-K + RXM-L. Product catalogue 2015

FTXM-K + RXM-L. Product catalogue 2015 FTXM-K + RXM-L Product catalogue 2015 Why choose Daikin Our promise is to ensure that your customers can depend on Daikin for the ultimate in comfort. We dedicate ourselves to technological excellence,

More information

Variable Speed Solutions. Outstanding performance for residential applications

Variable Speed Solutions. Outstanding performance for residential applications Variable Speed Solutions Outstanding performance for residential applications Heat pumps - an efficient technology using renewable energy Environmental impact, reduction of carbon footprint and energy

More information

EHPA regulations for granting the international quality label for electrically driven heat pumps

EHPA regulations for granting the international quality label for electrically driven heat pumps EHPA regulations for granting the international quality label for electrically driven heat pumps Version 1.6 Release 16.02.17 European Heat Pump Association Rue d Arlon 63-67 B-1040 Brussels www.ehpa.org

More information

Requirements of the ErP Directive on HVAC systems. What you need to know.

Requirements of the ErP Directive on HVAC systems. What you need to know. Requirements of the ErP Directive on HVAC systems. What you need to know. The background to the Ecodesign Directive Under the Kyoto Protocol, the European Union has committed itself to reducing its CO

More information

Variable Speed Solutions Outstanding Performance For Heat Pump Applications

Variable Speed Solutions Outstanding Performance For Heat Pump Applications Variable Speed Solutions Outstanding Performance For Heat Pump Applications Your Choice For An Efficient Heating Solution Emerson Climate Technologies offers a wide selection of products from single components

More information

European KEYMARK Scheme

European KEYMARK Scheme European KEYMARK Scheme Heat Pumps Revision Number: 3 (2017-09-12) Page: 2 of 12 Date Description of modification Revision number 01/05/2016 Initial version 1.1 10/03/2017 Addition of air/air product Editorial

More information

City Multi VRF. Seasonal Efficiency Explained

City Multi VRF. Seasonal Efficiency Explained City Multi VRF Seasonal Efficiency Explained The Need for Energy Efficient Buildings and Products This Mitsubishi Electric guide gives an overview of the Ecodesign Directive for Energy Related Products

More information

Air Conditioner ErP Test Report

Air Conditioner ErP Test Report Air Conditioner ErP Test Report Report Number Test Laboratory Name / Address Applicant Name / Address Manufacturing Name / Address Product Brand Name Description Model(s) (if applicable) Indoor Unit (split

More information

A new generation, energy-efficient, sanitary hot water solution for commercial applications

A new generation, energy-efficient, sanitary hot water solution for commercial applications A new generation, energy-efficient, sanitary hot water solution for commercial applications Using CO2 gas as a natural refrigerant 1 The Q-ton story The high efficiency Q-ton is an air-to-water heat pump

More information

Instant discount of 33% off improvement cost, up to $1,250 Plus, potential savings bonus of up to $250 (**)

Instant discount of 33% off improvement cost, up to $1,250 Plus, potential savings bonus of up to $250 (**) RESIDENTIAL PROGRAM HOME PERFORMANCE with ENERGY STAR IMPROVE YOUR HOME'S COMFORT. SAVE MONEY. REDUCE ENERGY. EARN S. Home Performance with ENERGY STAR offers homeowners instant discounts for making recommended

More information

1/74. Heat pumps. types parameters effectivity

1/74. Heat pumps. types parameters effectivity 1/74 Heat pumps types parameters effectivity Heat pumps 2/74 generally devices for: pumping the thermal energy from environment A at low (= nonutilisable) temperature (anergy) and transferring it to environment

More information

COOLING BENCHMARKING STUDY Part 3: Testing Component Report

COOLING BENCHMARKING STUDY Part 3: Testing Component Report COOLING BENCHMARKING STUDY Part 3: Testing Component Report June 2011 BY André Pierrot and Julio Conde CEIS in Partnership with The Collaborative Labeling and Appliance Standards Program (CLASP) ACKNOWLEDGEMENTS

More information

The calculation of HP contribution to renewable energy use in EU energy statistics Thomas Nowak, EHPA

The calculation of HP contribution to renewable energy use in EU energy statistics Thomas Nowak, EHPA The calculation of HP contribution to renewable energy use in EU energy statistics Thomas Nowak, EHPA IEE/08/776/SI2.529222 Target: to determine the share of renewable sources from ambient energy used

More information

Reduce energy costs and create environmentally friendly hot water all year round

Reduce energy costs and create environmentally friendly hot water all year round RENEWABLES HOT WATER HEAT PUMPS Reduce energy costs and create environmentally friendly hot water all year round Intelligent German engineering that uses air as an energy source for generating hot water

More information

Comfortable Energy-Saving & Environment-Friendly

Comfortable Energy-Saving & Environment-Friendly Heating & Warm Water CRUCE Series Water Heating Systems Comfortable Energy-Saving & Environment-Friendly Tien System Group. CRUCE series energy-saving water heating system offers tailor made heating concepts

More information

Water Heating Technologies To Meet Energy & Environmental Challenges

Water Heating Technologies To Meet Energy & Environmental Challenges Water Heating Technologies To Meet Energy & Environmental Challenges Giovanni Zullo Vice President - Marketing & Planning Emerson Climate Technologies, Asia Pacific Our Vision: Emerson Climate Technologies,

More information

COMMISSION STAFF WORKING DOCUMENT EXECUTIVE SUMMARY OF THE IMPACT ASSESSMENT. Accompanying the document

COMMISSION STAFF WORKING DOCUMENT EXECUTIVE SUMMARY OF THE IMPACT ASSESSMENT. Accompanying the document EUROPEAN COMMISSION Brussels, 30.11.2016 SWD(2016) 421 final COMMISSION STAFF WORKING DOCUMENT EXECUTIVE SUMMARY OF THE IMPACT ASSESSMENT Accompanying the document Commission Regulation implementing Directive

More information

LG Renewable Heating Solutions

LG Renewable Heating Solutions RENEWABLE > SHIFT AWAY FROM FOSSIL FUELS LG Renewable Heating Solutions Products in this brochure contain fluorinated greenhouse gases (R410A) and (R134a) LG Air Conditioning and Energy Solutions UK Energy

More information

Heat pumps. WP5 Education and Economic Promotion

Heat pumps. WP5 Education and Economic Promotion WP5 Education and Economic Promotion Heat pumps Educational product: New lecture material for training modules dealing with knowledge and skills how to apply suitable methods of energy efficient refurbishment

More information

Renewable Energy. to heat your home. thermia.com

Renewable Energy. to heat your home. thermia.com Renewable Energy Use air to heat your home all year round thermia.com Low-carbon heating is the key to sustainable development With the twin goals of reducing costs and maximizing sustainability, pressures

More information

ECONOMIC HEATING SYSTEMS FOR LOW ENERGY BUILDINGS IN SWEDEN

ECONOMIC HEATING SYSTEMS FOR LOW ENERGY BUILDINGS IN SWEDEN Numbers of Abstract/Session (given by NOC) - 1 - ECONOMIC HEATING SYSTEMS FOR LOW ENERGY BUILDINGS IN SWEDEN Svein, Ruud, Senior expert, Department of Energy Technology, SP Technical Research Institute

More information

Common Benchmark Ecolabel & GPP Criteria for Hydronic Central Heating Systems. Elena Rodriguez Vieitez & Oliver Wolf

Common Benchmark Ecolabel & GPP Criteria for Hydronic Central Heating Systems. Elena Rodriguez Vieitez & Oliver Wolf Common Benchmark Ecolabel & GPP Criteria for Hydronic Central Heating Systems Elena Rodriguez Vieitez & Oliver Wolf October 2010 COMMON BENCHMARK ECOLABEL & GPP CRITERIA FOR HYDRONIC CENTRAL HEATING SYSTEMS

More information

KAROLINA KOWAL. Warsaw University of Technology Student. Warsaw University of Technology Student

KAROLINA KOWAL. Warsaw University of Technology Student. Warsaw University of Technology Student Project of HVAC systems for the meteorological station DAGMARA ĆWIEK Technology Student, dagmaracwiek@gmail.com TOMASZ KOLSICKI Technology Student KAROLINA KOWAL Technology Student BARTŁOMIEJ TOKARZEWSKI

More information

Benchmarking method of seasonal performance D4.4. Benchmarking method of seasonal performance under consideration of boundary conditions.

Benchmarking method of seasonal performance D4.4. Benchmarking method of seasonal performance under consideration of boundary conditions. SEasonal PErformance factor and MOnitoring for heat pump systems in the building sector SEPEMO-Build Benchmarking method of seasonal performance D4.4. Benchmarking method of seasonal performance under

More information

IEA HPP Annex 28 Uniform testing and seasonal performance calculation of combined operating heat pump systems

IEA HPP Annex 28 Uniform testing and seasonal performance calculation of combined operating heat pump systems IEA HPP Annex 28 Uniform testing and seasonal performance calculation of combined operating heat pump systems Carsten Wemhoener, Thomas Afjei and Ralf Dott Institute of Energy in Building, University of

More information

Guide. Heat Pump Boilers. Information. Issue Ten >

Guide. Heat Pump Boilers. Information. Issue Ten > Information Guide Heat Pump Boilers Issue Ten > Heat Pump Boilers Information Guide This is an independent guide produced by Mitsubishi Electric to enhance the knowledge of its customers and provide a

More information

The impact of the work under partial load on the energy efficiency of an air-to-water heat pump

The impact of the work under partial load on the energy efficiency of an air-to-water heat pump The impact of the work under partial load on the energy efficiency of an airtowater heat pump Krzysztof Piechurski 1,*, Małgorzata SzulgowskaZgrzywa 1, and Jan Danielewicz 1 1 Wrocław University of Science

More information

Farm Energy IQ. Farms Today Securing Our Energy Future. Farm Energy Efficiency Principles Tom Manning, New Jersey Agricultural Experiment Station

Farm Energy IQ. Farms Today Securing Our Energy Future. Farm Energy Efficiency Principles Tom Manning, New Jersey Agricultural Experiment Station Farm Energy IQ Farms Today Securing Our Energy Future Farm Energy Efficiency Principles Tom Manning, New Jersey Agricultural Experiment Station Farm Energy IQ Farm Energy Efficiency Principles Tom Manning,

More information

A VISION FOR HEATING AND COOLING PRIORITIES FOR TODAY AND TOMORROW

A VISION FOR HEATING AND COOLING PRIORITIES FOR TODAY AND TOMORROW A VISION FOR HEATING AND COOLING PRIORITIES FOR TODAY AND TOMORROW EXECUTIVE SUMMARY EPEE, representing the heating, cooling and refrigeration industry in Europe, strongly supports the energy efficiency

More information

Let Geo LEED the Way. 1

Let Geo LEED the Way.   1 By: Ryan Carda Let Geo LEED the Way By now, nearly everyone has at least heard of LEED but not many understand what it means to be LEED-certified or how best to earn certification. Developed by the US

More information

EU heat pump system quality: well on its way, but roadworks ahead

EU heat pump system quality: well on its way, but roadworks ahead SEasonal PErformance factor and MOnitoring for heat pump systems in the building sector SEPEMO-Build EU heat pump system quality: well on its way, but roadworks ahead D5.5. Position paper on heat pump

More information

heat pumps environmentally friendly heating solutions heating that doesn t cost the Earth

heat pumps environmentally friendly heating solutions heating that doesn t cost the Earth heat pumps environmentally friendly heating solutions heating that doesn t cost the Earth Issue 1 March 2006 SOLAR ENERGY AVAILABLE ALL YEAR ROUND Air Earth Expansion valve Evaporator Condenser 3 /4 environmental

More information

Nilan VPL Active heat recovery and cooling (air/air)

Nilan VPL Active heat recovery and cooling (air/air) M a r k e t l e a d i n g c o m m e r c i a l a n d d o m e s t i c v e n t i l at i o n w i t h h e at r e c o v e r y Nilan 31-125 Active heat recovery and cooling (air/air) Nilan 31-125 Commercial ventilation

More information

PUBLIC UTILITIES COMMISSION 505 VAN NESS AVENUE SAN FRANCISCO, CA

PUBLIC UTILITIES COMMISSION 505 VAN NESS AVENUE SAN FRANCISCO, CA STATE OF CALIFORNIA PUBLIC UTILITIES COMMISSION 505 VAN NESS AVENUE SAN FRANCISCO, CA 94102-3298 Edmund G. Brown Jr., Governor TO: All Parties in R.13-11-005 FROM: Robert Hansen, Utilities Engineer DATE:

More information

for refurbishing future?

for refurbishing future? High temperature residential heat pump for refurbishing What preferred refrigerant for the next future? Denis CLODIC IEA Workshop Paris, November 8, 2004 CENTRE D ENERGETIQUE 1 Contents Heat pump specifications

More information

6. SPECIFIC ACTIVITIES Screenings INQUIRIES AND REPORTS 15

6. SPECIFIC ACTIVITIES Screenings INQUIRIES AND REPORTS 15 Annual report 2016 2 Contents 1. INTRODUCTION 3 2. ECODESIGN AND ENERGY LABELLING 4 3. THE ACTIVITIES OF THE SECRETARIAT FOR ECODESIGN AND ENERGY LABELLING OF PRODUCTS 5 3.1. Inspections 5 3.2. Guidance

More information

Heat Pump Hot Water Supply Systems

Heat Pump Hot Water Supply Systems 2007年度版 Heat Pump Hot Water Supply Systems (1) Aims A great amount of energy is consumed for supplying hot water in the residential, commercial and industrial sectors. emission from residential hot water

More information

Bifluid Geothermal System New Generation

Bifluid Geothermal System New Generation Bifluid Geothermal System New Generation The Geothermal Energy - from the Greek roots geo, meaning earth, and thermos, meaning heat - ie the thermal energy stored in the underground of our planet, and

More information

Condensing boilers: still the most cost-effective technology for domestic space heating and hot water

Condensing boilers: still the most cost-effective technology for domestic space heating and hot water Condensing boilers: still the most cost-effective technology for domestic space heating and hot water By Jean Schweitzer Sixty million gas boilers are installed in the EU and represent one of the major

More information

Conservation First Framework LDC Tool Kit Final v2.1 July 1, 2017

Conservation First Framework LDC Tool Kit Final v2.1 July 1, 2017 Program Name: Save on Energy Heating and Cooling Program 1. Program Description The Heating and Cooling Program encourages individuals and businesses to replace or retrofit existing heating and cooling

More information

ground source heat pumps

ground source heat pumps Heating & hot water fact sheet 5 A guide to ground source heat pumps SevernWye energy advice The benefits of ground source heat pumps Ground source heat pumps can be used to produce heating and hot water

More information

Preparatory Studies for Ecodesign Requirements of EuPs (III)

Preparatory Studies for Ecodesign Requirements of EuPs (III) Preparatory Studies for Ecodesign Requirements of EuPs (III) ENER Lot 2 Local Room Heating Products Task 8: Scenario, policy, impact and sensitivity analysis European Commission, DG ENER 25 June 212 Developed

More information

Energy Performance Certificate

Energy Performance Certificate Energy Performance Certificate Address of dwelling and other details 2F1 29 Falcon Gardens Newbattle Edinburgh EH10 4AR This dwelling's performance ratings Dwelling type: Mid-floor flat Name of approved

More information

Farm Energy IQ. Farm Energy Efficiency Principles 2/16/2015. Farm Energy Efficiency. Basic Energy Principles

Farm Energy IQ. Farm Energy Efficiency Principles 2/16/2015. Farm Energy Efficiency. Basic Energy Principles Farm Energy IQ Farm Energy IQ Farms Today Securing Our Energy Future Farm Energy Efficiency Principles Tom Manning, New Jersey Agricultural Experiment Station Farm Energy Efficiency Principles Tom Manning,

More information

Eligibility of a Heat Pump Based on the Primary Energy Factor

Eligibility of a Heat Pump Based on the Primary Energy Factor Eligibility of a Heat Pump Based on the Primary Energy Factor Primož Poredoš* a, Boris Vidrih a, Tjaša Duh a, Andrej Kitanovski a, Alojz Poredoš a a Laboratory for Refrigeration and District Energy, University

More information

The Potential and Challenges of Solar Boosted Heat Pumps for Domestic Hot Water Heating

The Potential and Challenges of Solar Boosted Heat Pumps for Domestic Hot Water Heating The Potential and Challenges of Solar Boosted Heat Pumps for Domestic Hot Water Heating Stephen Harrison Ph.D., P. Eng., Solar Calorimetry, Dept. of Mechanical and Materials Engineering, Queen s University,

More information

Heat Pumps Community Workshop Manchester Library, Manchester

Heat Pumps Community Workshop Manchester Library, Manchester Heat Pumps Community Workshop Manchester Library, Manchester Jake Marin Program Manager HVAC/R Efficiency Vermont April 14, 2015 1 Our Roadmap Brief Technology Overview Heat Pump Economics Successful Applications

More information

ENERGETIC MONITORING AND OPTIMIZATION OF A SOLAR HOUSE

ENERGETIC MONITORING AND OPTIMIZATION OF A SOLAR HOUSE Bulletin of the Transilvania University of Braşov Vol. 3 (52) - 2010 Series I: Engineering Sciences ENERGETIC MONITORING AND OPTIMIZATION OF A SOLAR HOUSE M. MOLDOVAN 1 I. VIŞA 1 A. DUŢĂ 1 Abstract: Into

More information

APPLICATION PACK FOR THE ECOLABEL. PART 2: Application form for heat pumps. Final draft. November 2007

APPLICATION PACK FOR THE ECOLABEL. PART 2: Application form for heat pumps. Final draft. November 2007 Final draft APPLICATION PACK FOR THE ECOLABEL PART 2: Application form for heat pumps November 2007 Please fill out: [Insert name of Competent Body and contact details, including address, telephone and

More information

Hydronic Central Heating Generators Green Public Procurement Product Sheet

Hydronic Central Heating Generators Green Public Procurement Product Sheet Hydronic Central Heating Generators Green Public Procurement Product Sheet Green Public Procurement (GPP) is a voluntary instrument. This Product Sheet provides a summary of the European Commission GPP

More information

Rocky Mountain Power s Planned Changes to the Home Energy Savings Program in Idaho February 2017

Rocky Mountain Power s Planned Changes to the Home Energy Savings Program in Idaho February 2017 Rocky Mountain Power s Planned Changes to the Home Energy Savings Program in Idaho February 2017 PacifiCorp (Company) is planning to make modifications to the Home Energy Savings program (HES Program)

More information

NEW HOME ENERGY SAVINGS PROGRAM

NEW HOME ENERGY SAVINGS PROGRAM NEW HOME ENERGY SAVINGS PROGRAM Program Guidelines The Process Please see eligibility criteria on the website and the following page. 1. To register, visit our website or call us at 1 800 663 6272. During

More information

SUPERB CLIMATE SOLUTION WITH A PROVEN RECORD

SUPERB CLIMATE SOLUTION WITH A PROVEN RECORD GEOTHERMAL ENERGY SUPERB CLIMATE SOLUTION WITH A PROVEN RECORD thermia.com Low-carbon heating is the key to sustainable development With the twin goals of reducing costs and maximizing sustainability,

More information

FLOWRATE DEPENDENT HEAT-PUMP MODEL

FLOWRATE DEPENDENT HEAT-PUMP MODEL Poster P.4.10-1 - FLOWRATE DEPENDENT HEAT-PUMP MODEL Andreas, Genkinger, dipl. Phys., Research Associate, University of Applied Sciences and Arts Northwestern Switzerland, School of Architecture, Civil

More information

NEW HOME ENERGY SAVINGS PROGRAM

NEW HOME ENERGY SAVINGS PROGRAM NEW HOME ENERGY SAVINGS PROGRAM Program Guidelines The Process Please see eligibility criteria on the website and the following page. 1. To register, visit our website or call us at 1 800 663 6272. During

More information

Gas: the right choice for heating in Europe

Gas: the right choice for heating in Europe Gas: the right choice for heating in Europe The report has been prepared by a taskforce comprising members of Eurogas, Marcogaz and GERG. Avenue de Cortenbergh 172 1000 Brussels Belgium +32 2 894 48 48

More information

Contents. Introduction (3) Tasks of the Secretariat (4) Market surveillance activities completed in 2014 (6)

Contents. Introduction (3) Tasks of the Secretariat (4) Market surveillance activities completed in 2014 (6) Annual Report 2014 SEE / Annual Report 2014 / Contents 2 Contents Introduction (3) Tasks of the Secretariat (4) Market surveillance activities completed in 2014 (6) Inspection of shops (7) Notifications

More information

Recent U. S. R&D results from IEA HPP Annex 41

Recent U. S. R&D results from IEA HPP Annex 41 Air source heat pumps for cold climate applications Recent U. S. R&D results from IEA HPP Annex 41 Air source heat pumps are easily applied to buildings almost anywhere. They are widespread in milder climate

More information

Chapter 9: Applications of the Laws of Thermodynamics

Chapter 9: Applications of the Laws of Thermodynamics Chapter 9: Applications of the Laws of hermodynamics Goals of Period 9 Section 9.1: Section 9.2: Section 9.3: o review the first law of thermodynamics o discuss heat engines and their efficiency o discuss

More information

Energy Efficient Cities. Oddgeir Gudmundsson, Director, Projects. One Company. Focused on Climate & Energy. 1 Danfoss Heating Segment A&T Projects

Energy Efficient Cities. Oddgeir Gudmundsson, Director, Projects. One Company. Focused on Climate & Energy. 1 Danfoss Heating Segment A&T Projects Energy Efficient Cities Oddgeir Gudmundsson, Director, Projects One Company Focused on Climate & Energy 1 Danfoss Heating Segment A&T Projects Oddgeir Gudmundsson - 2016 Political targets Political Targets

More information

Less energy, more savings and comfort year-round

Less energy, more savings and comfort year-round COMPANION GUIDE: Air-Source Heat Pump Less energy, more savings and comfort year-round Designed for Electrically-Heated Homes 02 How do air-source heat pumps work? 03 What are the rebates? 04 Why it pays

More information

The Potential and Challenges of Solar Boosted Heat Pumps for Domestic Hot Water Heating

The Potential and Challenges of Solar Boosted Heat Pumps for Domestic Hot Water Heating The Potential and Challenges of Solar Boosted Heat Pumps for Domestic Hot Water Heating Stephen Harrison Ph.D., P. Eng., Solar Calorimetry, Dept. of Mechanical and Materials Engineering, Queen s University,

More information

FINAL DRAFT 21 DECEMBER 2015 FREQUENTLY ASKED QUESTIONS. COMMISSION REGULATION (EU) No 1253/2014. of 7 July 2014

FINAL DRAFT 21 DECEMBER 2015 FREQUENTLY ASKED QUESTIONS. COMMISSION REGULATION (EU) No 1253/2014. of 7 July 2014 1 FINAL DRAFT 21 DECEMBER 2015 FREQUENTLY ASKED QUESTIONS TO COMMISSION REGULATION (EU) No 1253/2014 of 7 July 2014 implementing Directive 2009/125/EC of the European Parliament and of the Council with

More information

Annex 4: Energy Labelling Air Conditioner Equations and Calculations

Annex 4: Energy Labelling Air Conditioner Equations and Calculations Annex 4: Energy Labelling Air Conditioner Equations and Calculations Page 1 of 13 1 Guidance on the Calculations and Production of Equations from within EU Regulation 626/2011 Energy Labelling of Air Conditioners

More information

COPs, EERs, and SEERs

COPs, EERs, and SEERs Power Knot LLC 501 Valley Way Milpitas CA 95035 COPs, EERs, and SEERs How Efficient is Your Air Conditioning System? USA +1-408-889-8433 www.powerknot.com 1 Introduction This note discusses performances

More information

ENERGY STAR Qualified Homes National Program Requirements, Version 3.0

ENERGY STAR Qualified Homes National Program Requirements, Version 3.0 Qualifying Homes The following homes are eligible to earn the ENERGY STAR: Single-family homes; Units in multi-family buildings that are three stories or less; Units in multi-family buildings that are

More information

BEST PRACTICE DATABASE FOR GROUND SOURCE HEAT PUMPS

BEST PRACTICE DATABASE FOR GROUND SOURCE HEAT PUMPS - 1 - BEST PRACTICE DATABASE FOR GROUND SOURCE HEAT PUMPS A. Lehmann, FIZ Karlsruhe, Eggenstein-Leopoldshafen, Germany Abstract:The Best Practice Database represents a crucial part of the IEE project GROUND-

More information

Workshop for the Development of Criteria under the European Commission Green Public Procurement Scheme for Hydronic Central Heating Generators

Workshop for the Development of Criteria under the European Commission Green Public Procurement Scheme for Hydronic Central Heating Generators a EUROPEAN COMMISSION DIRECTORATE-GENERAL JRC JOINT RESEARCH CENTRE Institute for Prospective Technological Studies (Seville) Sustainable Production and Consumption Workshop for the Development of Criteria

More information

EU F-Gas Regulation Guidance Information Sheet 16: Manufacturers and Importers of Refrigeration, Air-Conditioning and Heat Pump Equipment

EU F-Gas Regulation Guidance Information Sheet 16: Manufacturers and Importers of Refrigeration, Air-Conditioning and Heat Pump Equipment Information Sheet 16: Manufacturers and Importers of Refrigeration, Air-Conditioning and Heat Pump Equipment Target audience for this Information Sheet This Information Sheet is aimed at manufacturers

More information

Standardizing Smart/Connected Products in a Highly Innovative and Dynamic Market

Standardizing Smart/Connected Products in a Highly Innovative and Dynamic Market Standardizing Smart/Connected Products in a Highly Innovative and Dynamic Market Robert Wilkins Thursday, September 15, 2016 10:00 a.m. 10:30 a.m. AHRI One of the nation s larger trade associations including

More information

TWO LARGE FIELD-TESTS OF NEW HEAT PUMPS IN GERMANY

TWO LARGE FIELD-TESTS OF NEW HEAT PUMPS IN GERMANY - 1 - TWO LARGE FIELD-TESTS OF NEW HEAT PUMPS IN GERMANY M. Miara, Fraunhofer-Institute for Solar Energy Systems ISE Freiburg, Germany Abstract: In 2006, two large field test campaigns of newly installed

More information

Tomorrow s heating is based on solar power and electricity!

Tomorrow s heating is based on solar power and electricity! The Energy+ house Tomorrow s heating is based on solar power and electricity! An energy-neutral house with solar energy and electric heating is a complete solution for the future built with innovative,

More information

Henrik N. Knudsen 1, Ole M. Jensen 1, Lars Kristensen 2 Danish Building Research Institute, Aalborg University The green House/Energy Service Denmark

Henrik N. Knudsen 1, Ole M. Jensen 1, Lars Kristensen 2 Danish Building Research Institute, Aalborg University The green House/Energy Service Denmark Occupant satisfaction with new low-energy houses Henrik N. Knudsen 1, Ole M. Jensen 1, Lars Kristensen 2 Danish Building Research Institute, Aalborg University The green House/Energy Service Denmark SUMMARY

More information

HEAT PUMP MISCELLANY

HEAT PUMP MISCELLANY HEAT PUMP MISCELLANY Over the last few months, we ve looked in detail at the different types of heat pump available taking their heat from the ground, outside air, exhaust air, or water. To conclude this

More information

CHAPTER 13: Sustainability

CHAPTER 13: Sustainability CONTENTS 13.1 THE CODE FOR SUSTAINABLE HOMES 13.2 LOW CARBON / LOW ENERGY HOMES 13.3 AIR TIGHTNESS AND ROBUSTNESS 13.4 RENEWABLE ENERGY SOURCES Chapter 13 FUNCTIONAL REQUIREMENTS FUNCTIONAL REQUIREMENTS

More information

HEAT PUMP WITH HIGH OUTLET TEMPERATURES

HEAT PUMP WITH HIGH OUTLET TEMPERATURES HEAT PUMP WITH HIGH OUTLET TEMPERATURES Dr. rer. nat. Bernd Hafner, Dr.-Ing. Klaus Heikrodt, Viessmann Werke GmbH & Co KG, 35107 Allendorf (Eder), Germany ABSTRACT For house heating applications heat-pumps

More information

Energy Performance of Buildings Directive: Achieving both high indoor air quality and low energy consumption in European buildings

Energy Performance of Buildings Directive: Achieving both high indoor air quality and low energy consumption in European buildings Energy Performance of Buildings Directive: Achieving both high indoor air quality and low energy consumption in European buildings EVIA calls upon decision-makers to strengthen provisions ensuring proper

More information

2. Ground Source Heat Pumps Invitations to complete questionnaire Responses received... 7

2. Ground Source Heat Pumps Invitations to complete questionnaire Responses received... 7 Case Study July 2012 2. Ground Source Heat Pumps Table of Contents 2.1 INTRODUCTION TO THE TECHNOLOGY...2 2.2 AVAILABLE TYPES OF THIS TECHNOLOGY...3 2.3 STRENGTHS, WEAKNESSES, OPPORTUNITIES AND THREATS...5

More information

The renewable heating experts

The renewable heating experts The renewable heating experts For industrial, agricultural, commercial and public sector estates and buildings of all sizes Finn Geotherm specialises in heat pumps. We supply and install the market leading

More information