HVAC MANAGEMENT SYSTEMS WITH DYNAMIC ENERGY

Size: px
Start display at page:

Download "HVAC MANAGEMENT SYSTEMS WITH DYNAMIC ENERGY"

Transcription

1 HVAC MANAGEMENT SYSTEMS WITH DYNAMIC ENERGY AND DEMAND OPTIMIZATION San Diego Gas & Electric Emerging Technologies Program Technology Assessment Report Project ID ET14SDG7011 Prepared for: Kate Zeng and Matt Smith San Diego Gas and Electric Company Prepared by: Antonio Corradini, PE and Akane Karasawa, PE Alternative Energy Systems Consulting, Inc. March 2016

2 Acknowledgements San Diego Gas and Electric s Emerging Technologies (SDG&E ET) group is responsible for this project, developed under internal project numbers ET14SDG7011. AESC Inc. conducted the technology evaluation and reporting with overall guidance and management from Kate Zeng of SDG&E. SDG&E and AESC would like to thank all the host customers for their assistance and cooperation. Without their gracious volunteering this study would not have been possible. Additionally, thanks and acknowledgements are due to the technology vendor for their support, dedication to energy conservation, and ongoing efforts to provide energy efficiency products to the marketplace. For more information, contact ETinfo@sdge.com. Disclaimer This report was prepared by San Diego Gas and Electric and funded by California utility customers under the auspices of the California Public Utilities Commission. Reproduction or distribution of the whole or any part of the contents of this document without the express, written permission of SDG&E is prohibited. This work was performed with reasonable care and in accordance with professional standards. However, neither SDG&E nor any entity performing the work pursuant to SDG&E s authority make any warranty or representation, expressed or implied, with regard to this report, the merchantability or fitness for a particular purpose of the results of the work, or any analyses, or conclusions contained in this report. The results reflected in the work are generally representative of operating conditions; however, the results in any other situation may vary depending upon particular operating conditions. Readers are responsible for all decisions and actions based upon this report and for all resultant consequences.

3 EXECUTIVE SUMMARY The emerging technology (ET) presented in this report is an HVAC management system with dynamic energy and demand optimization designed for commercial rooftop units (RTUs) and split system applications. The ET replaces a traditional thermostat with multiple sensors that measure dry-bulb temperature and relative humidity in a zone. The information from the sensors is sent to an on-site controller, which relays the information to a cloud server for storage, analysis, and reporting. The on-site system then dynamically evaluates zone conditions using the sensor data, weather data (as a proxy for radiant heat), schedule information, as well as specific zone-by-zone properties such as air flow rates that are stored in the system s database. The controller then activates fans, compressors, and furnaces as applicable to maintain a comfort setpoint. The control mechanism differs from traditional thermostats, where fans and compressors are activated based solely on a specific dry-bulb temperature versus the whole comfort temperature relative humidity range. The collected data were also used to compare the thermal zone conditions before and after the installation of ET using the ASHRAE 55 thermal comfort zone as a guideline. The results revealed that the ET was able to improve the zone condition within the thermal comfort zone limits, therefore improving the occupants comfort. In this report, the energy savings associated with the proposed ET were evaluated by using the field test results obtained from two test sites. The technology yielded savings due to several factors: Reducing the run time of RTUs with scheduling and soft start strategies. Reducing the run time of the compressor by applying a comfort setpoint and therefore increasing the fan-only operating range. Analytical fault detection and diagnostics (FDD) to alert building operators of noncatastrophic conditions that might waste energy. The data analysis of the first field test showed a 29% reduction in energy used across five heat pumps and the second field test showed an overall 38% reduction in energy used across nine AC units due mainly from advanced scheduling. The calculations also found that the ET achieved 8% savings during occupied times at the second site, which could potential qualify for utility incentive. Finally, the ET was tested for its demand response and permanent demand reduction capabilities. The results showed that the ET was able to reduce the combined peak power of a facility by 30% by coordinating the operations of multiple units during a DR event. SDG&E Emerging Technologies Page 3

4 ABBREVIATIONS AND ACRONYMS AESC ASHRAE CPUC DEER DX EE EER EISG ET FDD M&V OAT RTU SDG&E Alternative Energy Systems Consulting American Society of Heating, Refrigerating, and Air Conditioning Engineers California Public Utilities Commission Database for Energy Efficient Resources Direct Expansion Energy efficiency Energy efficiency ratio Energy Innovation Small Grant Emerging technologies Fault detection and diagnostics Measurement and verification Outside air temperature Rooftop unit San Diego Gas and Electric SDG&E Emerging Technologies Page 4

5 CONTENTS HVAC MANAGEMENT SYSTEMS WITH DYNAMIC ENERGY AND DEMAND OPTIMIZATION 1 EXECUTIVE SUMMARY 3 ABBREVIATIONS AND ACRONYMS 4 BACKGROUND AND TECHNOLOGY 8 Market Overview Opportunity... 8 Applicable codes and standards... 8 Emerging Technology Description... 8 PROJECT OBJECTIVE 11 MEASUREMENT AND VERIFICATION PLAN 12 Host Sites Overview Data Collection DATA ANALYSIS 16 Site Site RESULTS 21 Thermal Comfort Compressor cycling Energy Savings Demand Reduction and Demand Response Site Site DISCUSSION 30 Customer Feedback Utility Energy Incentives Market Barriers Possible Risks Possible Future Study Conclusion REFERENCES 33 FIGURES Figure 1: Representation of proposed ET... 9 Figure 2: ASHRAE Standard 55 Thermal Comfort Zones SDG&E Emerging Technologies Page 5

6 Figure 4: Aerial view of the County of San Diego Building Figure 5: T/RH Hobo logger placed at the thermostat during baseline measurements Figure 6: Typical baseline unit operation Figure 7: Typical post-retrofit unit operation Figure 8: Regression analysis made for total power consumption of six heat pumps during occupied periods Figure 9: Typical baseline unit operation Figure 10: Typical post-retrofit unit operation Figure 11: Regression analysis made for total power consumption of nine AC units during occupied periods Figure 12: Site 1 pre and post conditions Figure 13: Site 2 zone 6 pre and post indoor conditions Figure 15: Site 2 Pre and Post Installation AC Figure 16: Pre- and post-retrofit comparison Figure 17: Daily average energy consumptions of six heat pumps Figure 18: Normalized pre and post models obtained from regression analysis in Figure Figure 19: average daily consumptions of nine AC units Figure 20: Average daily consumptions of nine AC units during occupied period Figure 21: Pre and post OAT conditions on Psychrometric chart.. 27 Figure 22: The enthalpy difference between indoor and outside air as function of outside air temperature Figure 23: Demand reduction testing at site Figure 24: Demand reduction testing at site TABLES Table 1: Building Features Table 2: Building one existing Thermostats schedule Table 3: Building Features Table 4: County of San Diego existing Thermostat schedules Table 5: Site 1 data collection summary Table 6: Site 2 data collection summary Table 7: Estimated energy savings per site SDG&E Emerging Technologies Page 6

7 INTRODUCTION Packaged air conditioning units, often referred to rooftop units (RTUs), account for 46% of cooling equipment installed in commercial buildings, according to the Department of Energy Buildings Energy Data Book (Department of Energy, 2012a). Approximately 27% of all electric energy consumed in commercial buildings is attributed to RTU operations. However, RTUs generally receive minimal maintenance and run until a major failure, at which point they must be serviced or replaced. The average efficiency of RTUs in service in 2010 was 11.2 EER when the efficiency of best-available RTU on the market was 13.9 EER (Department of Energy, 2012b). There are many retrofit options to improve the RTU operation efficiency available on the market. However, the ET presented in this report introduces a unique control algorithm for RTUs. The new control system allows for maximizing zone thermal comfort while reducing peak power and energy consumption. Understanding thermal comfort as a mean to reduce HVAC energy consumption has recently attracted much attention. For example, NREL is conducting a research in their newly constructed Comfort Suite to understand the effect of temperature, humidity, and air flow on human comfort (Hicks, 2015). Besides energy savings, the technology is capable of demand response and will also help increase the life expectancy of RTUs by reducing compressor cycling. The primary goal of this study is to confirm the energy savings, peak demand reduction, and demand response capabilities of the advanced controller for RTUs. SDG&E sponsored AESC to conduct field measurements and verification to evaluate the energy and demand saving potentials of the proposed technology. The functionality and the plausibility of the technology was also reviewed and confirmed. Finally, the advanced controller s energy saving features were evaluated for possible incorporation into existing incentive programs. The research and development of the evaluated technology was partially funded by the California Energy Commission s Energy Innovation Small Grant Program (EISG). SDG&E Emerging Technologies Page 7

8 BACKGROUND AND TECHNOLOGY The emerging technology (ET) targets the historically underserved market of small commercial spaces with single zone packaged units. A packaged air conditioning unit typically consists of compressor(s), fan(s), furnace(s), and a thermostat. RTUs are controlled by thermostats located in the interior zones and can operate in various configurations, such as always on, scheduled by time, or on as needed based on the temperature set-point (auto). Programmable thermostats can setback temperature setpoints and can be scheduled to turn the units off when the space is unoccupied. On the other hand, many old pneumatic thermostats operate the units without any setback for evening or weekends and can easily be left on all the time. Improperly set or programmed thermostats can cause occupant discomfort and energy waste. However, thermostats are often left unchecked for their calibration and settings unless the unit fails and creates a maintenance action item. Therefore, HVAC inefficiency stemming from the thermostat settings or defects can go unnoticed for a long time. The proposed technology remedies the issue by replacing thermostats with high-accuracy sensors and controls that can be monitored real time at a remote location through a cloud based interface. MARKET OVERVIEW OPPORTUNITY The ET targets packaged RTUs that are predominantly used in stand-alone retail, small office buildings, and medium office buildings (W. Wang, 2012). The California Commercial End-Use Survey shows that offices and retail buildings in the SDG&E region consumes 3,570 GWh or 42% of total electricity consumed by all commercial buildings and that 28% of the energy consumed is used for cooling and ventilation (Itron, Inc., 2006). APPLICABLE CODES AND STANDARDS The current 2013 non-residential Title 24 requires shut-off and reset controls for all spaceconditioning systems. Additionally, all thermostats are required to have setback programming capabilities with a minimum of four separate setpoints per 24-hour period. For unitary single zone air conditioners, heat pumps, and furnaces, Occupant Controlled Smart Thermostats (OCSTs) are also required. These thermostats are capable of responding to demand response signals in the event of grid congestion and shortages during high electrical demand periods. The emerging technology presented in this report meets all of the above code requirements. EMERGING TECHNOLOGY DESCRIPTION The ET is designed to retrofit packaged RTUs and consists of sensors, an on-site controller, and an optional cloud-based server. The ET sensors are mounted to replace the existing system thermostats. Once installed, the system controls RTU fan(s), compressor(s), and furnace(s) and provides analytical FDD to alert building operators of non-catastrophic conditions requiring attention. The sensors communicate with a building-wide controller, which is continuously connected to the cloud. The control strategy was developed to improve occupant comfort, increases compressor life through reduced cycling, and reduces energy consumption and peak demand. SDG&E Emerging Technologies Page 8

9 FIGURE 1: REPRESENTATION OF PROPOSED ET 1. Thermal Comfort The ET measures dry-bulb temperature, relative humidity, OAT as proxy for radiant heat, and has user settings for occupant activity intensity level to determine fan, compressor, and furnace operations. The space conditions are controlled to be kept within thermal comfort zone limits rather than a set dry-bulb temperature. Thermal comfort zone is defined as the zone environment where 80% of sedentary or slightly active persons find thermally acceptable. Shaded regions in Figure 2 below represent the summer and winter thermal comfort zones as defined by ASHRAE Standard 55. To prevent warm discomfort in the summer, relative humidity below 60% is also recommended (ASHRAE, 2013). The ET takes advantage of the fact that the thermal comfort zone extends to regions with dry-bulb temperature up to 80 F at low humidity conditions. With its innovative control strategy, the system allows zone dry-bulb temperatures to float up while still maintaining comfort, which results in reduced compressor operating hours and energy savings. SDG&E Emerging Technologies Page 9

10 FIGURE 2: ASHRAE STANDARD 55 THERMAL COMFORT ZONES 2. Compressor Cycling The median lifetime of commercial RTUs is 15 years (Department of Energy, 2012c), which is short compared to other mechanical equipment. One of the reasons for this low life expectancy is the short cycling that many single zone RTUs are subjected to. The proposed technology will reduce short cycling which may extend the life of the most critical piece of the unit, the compressor. 3. Energy Consumption As described above, the ET evaluates zone comfort in terms of dry-bulb temperature, relative humidity, and OAT as proxy for radiant heat. It activates the fan and compressor accordingly to maintain a comfort setpoint rather than a specific temperature. As the result, the compressor run time and energy consumption are often reduced compared to traditional systems. The energy savings are also achieved from scheduling, where units are programmed to operate only during occupied hours, therefore reducing compressor and fan run hours. 4. Peak Demand The proposed technology s controlling algorithm allows the user to specify a kw-cap across all controlled RTUs, which can reduce peak demand. The demand limiting algorithm can maintain the total demand below the kw-cap by cycling compressors within the facility. The cycling strategy is dynamic to zone conditions, such that when the building load cannot be met with the kw-cap, all zones deviate from their setpoints at approximately the same rate. The demand limiting feature can be exploited continuously or during DR events. SDG&E Emerging Technologies Page 10

11 PROJECT OBJECTIVE The primary goal of this study is to confirm the energy savings and demand reduction of the advanced controller for RTUs. The energy savings will be assessed based on field measurements. The functionality and the plausibility of the technology will also be reviewed and confirmed. The following list summarizes the objectives of this project: 1. Describe system setup, operations, and functionality, 2. Quantify energy and peak demand savings, 3. Analyze factors that may cause variations in energy savings under different circumstances such as different base RTUs or climate zones, 4. Review utility programs with respect to their present applicability to this technology and provide recommendations on how utilities could further support this technology, 5. Research the potential market size and possible barriers to adoption, 6. Gather and present customer feedback, 7. Suggest possible improvements to the technology, 8. Assess risks introduced by this technology. SDG&E Emerging Technologies Page 11

12 MEASUREMENT AND VERIFICATION PLAN The M&V plan for the emerging technology assessment was performed through field measurements of installed technology. Plans were developed for two sites to collect data that captures the energy consumptions of RTUs during typical building operations before and after the technology implementation. The instrumentation and M&V approach was agreed upon by all involved parties: AESC, SDG&E, and the vendor supplying the emerging technology product. HOST SITES OVERVIEW M&V was performed at two sites. The first test site is operated by an electronics manufacturer and is a single story commercial building located in Poway, California in Climate Zone 10. The building consists of office spaces along the perimeter and manufacturing and warehouse spaces in the core. General building features are listed in Table 1. TABLE 1: BUILDING ONE FEATURES Building Feature Building Attribute Year built 1998 Size Approx. 12,000 ft² Location Poway, CA California Climate Zone 10 Occupancy type Office/Laboratory Occupancy schedule Monday Friday, 08:00-17:00 Building Management System None Mechanical System Summary Constant Volume, Packaged, Single Zone Heat Pumps The building has nine single zone heat pumps, but only six were included in this study: Heat pump units serving zone 1 and 7 were excluded because the vendor had used the zones as test labs and therefore the retrofit had already been implemented prior to this study. Zone 4 was also excluded because it is a storage room, where the air conditioning system is not used. All of the heat pumps are packaged RTUs with cooling capacities between three and five tons. All RTUs have constant-volume fans and single-stage constant-speed compressors with rated cooling efficiency of 9.5 EER. The RTUs do not have economizers and therefore they constantly supply minimum outside air. All units are over 15 years old as they were installed when the building was built. Each heat pump is connected to its own thermostat, which is configured to heat only mode, cool only mode, or both, depending on the zone served. Two heat pumps (HP-2 and HP-3) commonly serve a manufacturing space and the rest each serves an office space. Prior to retrofit, the RTUs operated on weekly time schedules. Refer to Table 2 for the baseline thermostat schedules and settings. SDG&E Emerging Technologies Page 12

13 TABLE 2: BUILDING ONE EXISTING THERMOSTATS SCHEDULE Zone 2 Zone 3 Zone 5 Zone 6 Zone 7 Zone 8 Zone 9 M F Prgrm SS Prgrm M F Prgrm SS Prgrm M F Prgrm SS Prgrm M F Prgrm SS Prgrm M F Prgrm SS Prgrm M F Prgrm SS Prgrm M F Prgrm SS Prgrm Time ON 7:30 AM 5:00 AM 8:00 AM 5:00 AM 8:00 AM 7:00 AM 8:00 AM 7:00 AM 8:00 AM 7:00 AM 7:30 AM 7:00 AM 7:30 AM 7:00 AM Heat Temp Cool Temp Time ON 5:00 PM 6:00 PM 5:00 PM 6:00 PM 5:00 PM 6:00 PM 5:00 PM 6:00 PM 1:00 PM 6:00 PM 5:00 PM 6:00 PM 5:00 PM 5:00 PM Heat Temp Cool Temp Time ON 5:00 PM Heat Temp 45 Cool Temp 88 system setting Heat Auto Cool Auto Auto Auto Cool fan setting Auto Auto Auto Auto Fan On Auto Auto The second test site is a single-story office building owned by the County of San Diego. The building is located in San Diego, California in Climate Zone 10. The building consists of a lobby, a conference room, office spaces, and common areas. General building features are listed in Table 3 below. TABLE 3: BUILDING TWO FEATURES Building Feature Building Attribute Year built 1960s Size 26,000 ft² Location San Diego, CA California Climate Zone 10 Occupancy type Office Occupancy schedule Monday Friday, 08:00-17:00 Building Management System None Mechanical System Summary Constant Volume, Packaged, Single Zone Direct Expansion (DX)/furnace units The building has four split systems and ten packaged DX units on the rooftop. M&V was performed on ten DX units that served offices and common areas. The split systems were excluded from this study because they serve closed areas with atypical loads such as server rooms and a storage room. All RTUs have constant-volume fans and constant-speed compressors and ran 24/7 prior to retrofit. The RTUs do not have economizers and therefore they supply minimum constant volume of outside air. All units are between 10 and 15 years old. Each unit is connected to its own thermostat, which is not programmed. Refer to Table 4 for zone characteristics and thermostat schedule and cooling setpoints. TABLE 4: COUNTY OF SAN DIEGO EXISTING THERMOSTAT SCHEDULES Unit ID AC1 AC2 AC3 AC4 AC5 AC6 AC7 AC8 AC9 AC10 Rooms T stat SP F TBS/Lun ch room 116, 120, 121 Commun ication Room Receptio n/lobby 222,223, Confere nce room Occupied Hours M F: 6AM 7PM M F: 6AM 7PM M F: 6AM 7PM M F: 6AM 7PM M F: 6AM 7PM M F: 6AM 7PM M F: 6AM 7PM M F: 6AM 7PM M F: 6AM 7PM M F: 6AM 7PM SDG&E Emerging Technologies Page 13

14 FIGURE 3: AERIAL VIEW OF THE COUNTY OF SAN DIEGO BUILDING DATA COLLECTION At the first test site, six T/RH Hobo loggers were placed at the thermostats throughout the building and one T/RH Hobo logger was placed on the roof to sample ambient temperature and relative humidity data every one minute. The baseline measurements were performed from December 12, 2013 to March 2, 2014 and post-retrofit measurements from March 6, 2014 to June 1, Current transducers and voltage probes were also placed on units HP- 1 through HP-9 on the roof to collect power data at one-minute interval. The following table summarizes the location and type of data collected at the first site: TABLE 5: SITE 1 DATA COLLECTION SUMMARY Location Quantity Equipment Data collected Frequency Outdoor 1 Hobo T/RH logger Ambient temperature (dry-bulb) Ambient relative humidity Thermostats 9 Hobo T/RH logger Zone temperature (dry-bulb) Zone relative humidity Every one minute Every one minute Heat pumps (rooftop) 9 egauge logger Power (kw) Every one minute SDG&E Emerging Technologies Page 14

15 FIGURE 4: T/RH HOBO LOGGER PLACED AT THE THERMOSTAT DURING BASELINE MEASUREMENTS At the second test site, baseline measurement was performed for two months from September The data were collected from 14 T/RH Hobo loggers placed at the thermostats throughout the building as well as one T/RH logger placed on the roof. These loggers were set to sample T/RH every 1 minute. Current transducers and voltage probes were also placed on units AC1 through AC10 on the roof and set to sample current at one-minute interval. Post-installation measurement started briefly after the installation in November of The data was continuously collected until September of For this site, the postimplementation power data was collected with egauges. The following table summarizes the location and type of data collected at the second site: TABLE 6: SITE 2 DATA COLLECTION SUMMARY Location Quantity Equipment Data collected Frequency Outdoor 1 Hobo T/RH logger Ambient temperature (dry-bulb) Every one minute Ambient humidity relative Thermostats 14 Hobo T/RH logger Zone temperature (dry-bulb) Every one minute Zone humidity relative AC units (rooftop) 10 egauge logger Power (kw) Every one minute Although outside air temperature and relative humidity were collected at the site, NOAA weather data was used in the analysis to minimize inaccuracies in the measurements. SDG&E Emerging Technologies Page 15

16 DATA ANALYSIS The energy savings, peak demand, and demand response evaluations in this report were done by comparing the energy consumptions of RTUs before and after the ET implementation. All data were collected in one-minute intervals. However, the analysis was performed by also combining data into hourly averages to reduce variability and noise. The data was also filtered by the day of week and the time of day in some cases to account for building occupancy and RTU scheduling. The same methodology was used in both baseline and post-installation cases to be consistent. Since both pre and post-implementation data were collected for limited measurement periods, a weather-normalized savings method was used to estimate the annual energy consumption of the RTUs. In the normalized savings method, the annual energy savings are determined by subtracting adjusted post-installation energy usage from the adjusted baseline usage. Therefore, the method requires mathematical models to adjust measured data. In this study, models were developed using empirical relationship between RTU energy use and outside air temperature, an independent variable, in accordance with M&V guideline (ASHRAE, 2014). The models were then adjusted using typical NOAA ambient temperature data to determine normalized annual savings under TMY3 conditions. Model uncertainty was measured by coefficient of determination (R²) and coefficient of variation of the root mean squared error (CV-RMSE). For each site, avoided energy use and normalized savings estimates and their uncertainties were calculated to evaluate the goodness of fit. SITE 1 As previously mentioned, each heat pump was independently controlled to provide heating or cooling to the building. Only HP-2 and HP-3 served the same zone and therefore the customer tried to keep the two independent thermostats with the same setpoint during baseline period. As expected, the baseline data showed that heat pumps mostly operated in heating mode in the morning to warm up the building and in cooling mode in the afternoon. As shown in Figure 5, heat pumps turned on at around 7 AM to heat the space until the 68 F setpoint was reached. During the afternoon, the heat pumps frequently cycled on and off to keep the 74 F setpoint. Note that HP-5 and HP-6 had the thermostats set in fan auto mode. In this mode, the fan is turned on only when there is a demand for cooling or heating, but otherwise turned off. This operating mode is commonly used in residential HVAC, but not a preferable method in commercial spaces because it does not provide adequate ventilation to the space. However, because this was the customer s preferred setting, the mode was not changed in the post installation to have a fair comparison. SDG&E Emerging Technologies Page 16

17 Temperature, dry bulb (F) Relative Humidity (%) OAT HP 9 Indoor Temp HP 9 Indoor RH HP 9 Power Hour HP Power (kw) FIGURE 5: TYPICAL BASELINE UNIT OPERATION Figure 6 shows that the heat pumps turned on briefly in the morning to heat the building after the ET was implemented. The operational difference is clearly visible in the afternoon, where the amount of cycling is reduced drastically. Additionally, the scheduling was improved by slightly delaying the morning warm up and shutting off the units at 5PM to match the building occupancy. Temperature, dry bulb (F) Relative Humidity (%) OAT HP 9 Indoor Temp HP 9 Indoor RH HP 9 Power Hour HP Power (kw) FIGURE 6: TYPICAL POST-RETROFIT UNIT OPERATION Several attempts were made to create a model using regression analysis, but acceptable accuracy was not achieved for both baseline and retrofit periods due to general lack of data points, lack of post-retrofit data points in the high temperature range above 75 F, and irregular baseline operation during holidays. The efforts included analysis using different independent variables, multiple variables, inferred the building heating/cooling balance point SDG&E Emerging Technologies Page 17

18 from our scatter plots. Figure 7 below shows one of regression analysis performed for the total hourly energy consumption of six heat pumps Pre Post Linear (Pre) Linear (Post) y = x R² = kw y = x R² = OAT FIGURE 7: REGRESSION ANALYSIS MADE FOR TOTAL POWER CONSUMPTION OF SIX HEAT PUMPS DURING OCCUPIED PERIODS SITE 2 At the second site, the power consumption of ten AC units and zone conditions were monitored for two months during baseline and seven months during post-retrofit. Since the satisfactory models could not be developed for site 1, the data were collected for prolonged durations. Of ten AC units, one of the AC units (AC-10) was removed from the analysis because the logged data showed erratic behavior and it was later determined that the sensors had been defective. At this site, the thermostats were not programmed for scheduling or night setback. The fans were also set to be always on for some units. Thus, all RTUs operated 24/7. Figure 8 below represents the typical operation of a baseline unit, which shows the unit fan operated continuously drawing about three amps and the compressor cycled on and off throughout the day to keep the indoor temperature at 72 F. SDG&E Emerging Technologies Page 18

19 FIGURE 8: TYPICAL BASELINE UNIT OPERATION Figure 9 below shows the typical operation of the same retrofitted unit during a weekday. After the retrofit, RTUs were scheduled to turn on only during occupied period from 6AM to 7PM. The zero-power draw at night indicates that scheduling was successfully implemented to reduce both fan and compressor run hours. Additionally, the number of compressor cycling during the occupied period was clearly reduced. FIGURE 9: TYPICAL POST-RETROFIT UNIT OPERATION To assess energy savings, the energy consumptions of nine AC units were compared before and after the retrofit. Per the appropriate normalized savings method, regression analysis was performed against outside air temperature. For this analysis, the energy consumption of the RTUs during unoccupied period was disregarded because the RTUs were scheduled to be SDG&E Emerging Technologies Page 19

20 turned off. No other data filtering was performed as they did not improve the uncertainty. The resultant models showed a slight increase of post-retrofit energy consumption during operational hours. This was shown to be caused by both unusually humid conditions as well as comfort improvements that applied only to the retrofit period. Further details will be discussed in the following sections. FIGURE 10: REGRESSION ANALYSIS MADE FOR TOTAL POWER CONSUMPTION OF NINE AC UNITS DURING OCCUPIED PERIODS SDG&E Emerging Technologies Page 20

21 RESULTS M&V results obtained from the two test sites are detailed in the following four categories: Thermal Comfort, Compressor Cycling, Energy Savings, and Demand Reduction. THERMAL COMFORT The algorithm proposed by the vendor utilized not only dry-bulb temperature but also relative humidity, radiant heat, and other factors relevant to human comfort to determine heating or cooling demand in an effort to improve thermal comfort in a zone. The green shaded area in the psychrometric chart below represents the summer comfort zone set by ASHRAE Standard 55. Thermal comfort is determined by the combination of dry-bulb temperature and humidity. For example, thermal comfort can be met even when space temperature is raised up to 80 F, if the relative humidity is kept between 20% and 60%. Dry-bulb temperature and humidity data were collected in each zone and their hourly averages were plotted in a psychrometric chart. The figures below are for only one of the building zones, but the data are typical of the other zones as well. Figure 11 displays data points outside of the green shaded area, or thermal comfort zone, even though the temperature was maintained at or below 72 F setpoint indicating that thermal comfort was not met during baseline periods at Site 1. On the other hand, the post-retrofit data shows that the space conditions were maintained within thermal comfort limits. These include times when the dry-bulb temperature exceeded the 72 F setpoint because the low humidity condition in the zone allowed the space temperature to drift up. Since the compressor only responds to the dry-bulb temperature, the retrofit resulted in reduced compressor run hours and energy savings. FIGURE 11: SITE 1 PRE AND POST CONDITIONS At site 2, the ET was also able to achieve improved thermal comfort. However, the effort to increase thermal comfort resulted in an increase in energy consumptions for several reasons. First, the San Diego region experienced unusually humid weather conditions during postretrofit measurement periods. Therefore, meeting thermal comfort required an increase in SDG&E Emerging Technologies Page 21

22 total enthalpy removed from outside air as compared to baseline conditions. Secondly, the customer survey revealed that the setpoint was frequently changed after the retrofit. The usability of the ET allowed the maintenance personnel to readily modify setpoint whenever requested by the occupants. As a result, the space temperature was not able to drift to a higher temperature as much as was originally expected. Figure 12 shows how the humidity was lowered during the post installation period even if the outside air humidity was actually higher. The post-retrofit hourly average data around 77-79F represents the system s default control target that was subsequently overridden by the users in favor of setpoints between 72-75F. FIGURE 12: SITE 2 ZONE 6 PRE AND POST INDOOR CONDITIONS COMPRESSOR CYCLING An additional benefit of the installed controls, although not its primary objective, is the reduction of compressor cycling. Figure 5 and Figure 6 illustrated that the cycling frequency was reduced after the ET retrofit at Site 1. During the baseline, the heat pump compressor cycled on and off approximately 10 times in less than four hours. The operational improvement is evident in the post-installation data, where the compressors cycling frequency was reduced greatly. At the second site, the AC units were not scheduled before the ET retrofit and therefore ran continuously. Figure 13 below shows the AC units were on 24/7 to keep the zone temperature setpoint and the compressors cycled on and off frequently. The number of compressor cycling was greatly reduced post-retrofit. Note how the indoor temperature was let float during the unoccupied hours. SDG&E Emerging Technologies Page 22

23 FIGURE 13: SITE 2 PRE AND POST INSTALLATION AC-6 ENERGY SAVINGS Limited data were collected at the first site due to the specific operations. Therefore, regression models were not attainable with acceptable accuracy for both baseline and retrofit periods. However, pre- and post-retrofit heat pump operations of two similar days were compared as shown in Figure 14 and a few energy saving features were noted, under comparable outside conditions: The compressor and fan run times during unoccupied hours were reduced by improving scheduling. The amount of heating consumption in the morning warm up was reduced. The overall energy consumption in cooling mode was reduced. SDG&E Emerging Technologies Page 23

24 OAT & indoor Temp DB pre OAT pre HP 9 Temp post OAT post HP 9 Temp pre HP 9 kw post HP 9 kw Hrs of day kw FIGURE 14: PRE- AND POST-RETROFIT COMPARISON To quantify the energy savings, the daily energy consumptions of six heat pumps were compared by selecting two pre- and post-retrofit days with similar ambient conditions. As Figure 15 below shows, five of six heat pumps evaluated in this study exhibited savings. The combined savings for the six units represents 29% of baseline energy consumption. The result did not show significant demand reduction during the 12PM to 6PM peak period. FIGURE 15: DAILY AVERAGE ENERGY CONSUMPTIONS OF SIX HEAT PUMPS At site 2, the energy savings were calculated using the regression analysis results with NOAA meteorological data for San Diego. Figure 16 illustrates the modeled hourly energy use for baseline and post-retrofit cases for the entire year. The resulting savings for the nine units represented 38% of the baseline energy consumption. Table 7 below summarizes the energy savings achieved at each site. SDG&E Emerging Technologies Page 24

25 TABLE 7: ESTIMATED ANNUAL ENERGY SAVINGS PER SITE Baseline Retrofit Savings % Savings kwh kwh kwh Site 1 NA NA NA 29% Site 2 57,900 35,900 22,100 38% Figure 16 illustrates the modeled hourly energy use for baseline and post-retrofit cases for the entire year for Site 2. The hourly energy consumption of nine AC units during the occupied periods increased slightly in post-retrofit, especially at low outside air temperature range. This increase in energy consumption can be explained by change in RTU operations. In baseline, RTUs were on all the time and therefore the compressors ran under steady state condition even during the night when the building was not occupied. After the retrofit, however, RTUs were scheduled to shut off at the end of business hours. Since the RTUs didn t operate at night, the thermal load accumulated in the building until the units turned on in the morning. This caused the AC compressors to run more in the morning until the load accumulated during the night was satisfied, and the building reached the steady state condition. FIGURE 16: NORMALIZED PRE AND POST MODELS OBTAINED FROM REGRESSION ANALYSIS IN FIGURE 8 The average daily energy consumptions of nine RTUs during weekday were also compared and shown in Figure 17 below. All units showed energy savings from the ET implementation. However, the majority of savings come from scheduling the units or shutting the units off during unoccupied periods. SDG&E Emerging Technologies Page 25

26 FIGURE 17: AVERAGE DAILY CONSUMPTIONS OF NINE AC UNITS As Title 24 requires seven-day programmable thermostats on unitary systems, the savings achieved from scheduling will not be eligible for utility program incentive. Therefore, energy savings that occurred during occupied periods were evaluated by comparing the pre- and post-retrofit energy consumptions of the nine AC units between 6AM and 6PM. Of nine units, daily average consumptions of six AC units increased when the energy consumptions were compared only during occupied periods. Overall, the total daily average energy consumption of the facility increased from 166 kwh per day to 173 kwh per day. FIGURE 18: AVERAGE DAILY CONSUMPTIONS OF NINE AC UNITS DURING OCCUPIED PERIOD One of the major reasons for the increase in unit energy consumption is due to difference in outside weather conditions between baseline and post-retrofit periods. In the summer of 2015, San Diego region experienced above average humidity levels due to El Niño (a weather phenomenon caused by unusually warm water of the western Pacific Ocean flowing eastward), which coincided with the post-retrofit measurement period. Figure 19 is the plot of outside air SDG&E Emerging Technologies Page 26

27 conditions during baseline and post-retrofit measurements periods on a psychrometric chart. It is evident from the chart that outside air contained more moisture during the post-retrofit measurement period, especially at high dry-bulb temperatures. FIGURE 19: PRE AND POST OAT CONDITIONS ON PSYCHROMETRIC CHART To examine the effect of outside air humidity, the differences in enthalpies between outside air and the conditioned indoor air ( h) were calculated and compared. As previously mentioned, NOAA weather data was used to calculate the hourly average enthalpy of outside air. The hourly average enthalpy of indoor air was calculated for each zone, using measured data including zone air temperature and relative humidity. The h was then plotted with respect to outside air temperature (dry-bulb) and regression models were created. The resulting Figure 20 below shows that h is greater during post-retrofit measurement period, especially at high outside air temperatures. FIGURE 20: THE ENTHALPY DIFFERENCE BETWEEN INDOOR AND OUTSIDE AIR AS FUNCTION OF OUTSIDE AIR TEMPERATURE SDG&E Emerging Technologies Page 27

28 The increase in h translates into compressor load increase. To account for this increase in the load, the baseline was adjusted up to match the post-retrofit load. Per the Statewide Customized Retrofit Offering Procedures Manual, the energy savings are calculated using post-retrofit equipment load: Where = efficiency of baseline equipment (kw/ h) = efficiency of equipment after the retrofit = equipment load after the retrofit ( hpost) = post-retrofit energy consumption Annual hourly post-retrofit loads ( hpost) were modeled using the regression coefficients obtained from Figure 20 and NOAA meteorological data for San Diego. The efficiency of baseline equipment was deduced from the combination of previously modeled baseline energy consumption (unadjusted) and the modeled pre-retrofit loads. Using the above equation, the hourly baseline consumption was adjusted by multiplying the calculated baseline efficiency and the post-retrofit loads. No change was made to the modeled hourly post-retrofit consumptions. The above adjustments resulted in overall increase in the baseline consumption during occupied periods and yielded 8% savings. The results of the so adjusted savings calculation are summarized in Table 8 below. TABLE 8: ESTIMATED ANNUAL ENERGY SAVINGS WITH ENTHALPY ADJUSTMENT AT SITE 2 Baseline kwh Retrofit kwh Savings kwh % Savings All hours 83,800 35,900 47,900 57% Occupied hours only 38,200 35,200 3,000 8% DEMAND REDUCTION AND DEMAND RESPONSE Demand reduction was not observed during the initial testing because the demand limiting feature of the ET was turned off by the vendor. This was done so that the energy savings from the other control features can be isolated from the demand reduction. A separate testing was conducted on May 30 th, 2014 at test site 1 and on September 25 th, 2015 at test site 2 to demonstrate the permanent demand reduction and demand response capabilities of this technology. SITE 1 At test site 1, all units except for HP1 were tested for permanent demand reduction. The heat pumps were programmed to operate below a maximum power setpoint, which was set at the total demand of 16 kw per hour or approximately 65% of facility HVAC peak load. In this testing, three units were allowed to run concurrently at full capacity. The units were rotated so that each zone would receive cooling, but the overall consumption of all units at any one point in time would stay below 16 kw. Figure 21 below shows the ET successfully implemented demand reduction after 12:30 PM, which was when the test was initiated. SDG&E Emerging Technologies Page 28

29 FIGURE 21: DEMAND REDUCTION TESTING AT SITE 1 SITE 2 At test site 2, all units except for AC10 were controlled to operate under a demand limit, which was set at 70% of full capacity beginning at 10:30am for permanent demand reduction purposes and at 50% beginning at 3:30pm for demand response purposes. At 4:30pm, the system was set back to 70%. The testing was concluded at 6pm when the building s occupancy schedule ended. Figure 22 below shows that total power demands were kept within the pre-programmed limits for the duration of the test. The 50% demand reduction was kept only for an hour period. During the hour, the average indoor air temperature started to increase slightly (~1 F), indicating that the zone loads were not completely satisfied. This reaction is typical for demand response events. FIGURE 22: DEMAND REDUCTION TESTING AT SITE 2 SDG&E Emerging Technologies Page 29

30 DISCUSSION The M&V results showed that the installed ET at two sites both succeeded its objectives to increase occupant comfort, to reduce compressor cycling, and to reduce energy and demand. The following sections discuss the functionality and the plausibility of the ET based on the results. CUSTOMER FEEDBACK The vendor and the consultant conducted a survey at each test site and received feedback from the customers. Overall, the customers liked the new thermostats and the app like feel of the web interface, which allowed them to adjust schedules, setpoints, and other parameters as needed. The fact that the customers desired to keep the new system in place at both sites is a testimony to their satisfaction. The customers were especially pleased at the first site, where each occupant was given his/her own control and was able to access the settings online. The improvement in the zone comfort was also noted by the occupants. At the second site, both compliments and complaints were filed during the survey. Overall, the occupants confirmed the increase in comfort due to less humidity. Some customers saw the technology survey as an opportunity to complain about the HVAC system in general, which is a common behavior found in this type of survey. A few complaints were made about experiencing discomfort at the second site. However, they are believed to be related to the problem with existing HVAC system configuration rather than with the studied technology. For example, the air conditioning of five separate offices is controlled by one thermostat located in one of the offices. The discomfort experienced by the occupant in one of these offices is not because of the installed technology, but is likely due to the lack of thermostat and the HVAC system configuration. It should also be noted that there were several mechanical failures not related to ET, which were not addressed immediately by the facility management. Since the technology vendor was often present at the site due to the ongoing test, they were usually the first to be suspected for causing any mechanical issues even when the root cause was later identified to be an unrelated to the test. This may also have biased survey responses somewhat negatively. UTILITY ENERGY INCENTIVES There are several types of smart thermostats, which are already incentivized by the California utilities. In SDG&E territory, a smart thermostat is incentivized in midstream program. The current Title 24 code requires seven-day programmable thermostats. As such, the energy savings from shutting off the units at night and during the weekend are not eligible for utility incentive programs. However, the energy savings resulting from the ET s other features such as controlling the unit based on a comfort factor, the cycling of the compressor, and the demand limiting would be all eligible for incentives. The ET is OpenADR 2.0a compliant and capable of managing multiple RTUs to reduce the facility peak demand. Thus, the author believes that the ET would best fit in the utility s Automated Demand Response Program and/or Custom Incentive Program for demand reduction for its capability to do demand response while also providing the customer with energy efficiency and permanent peak demand reduction. Further analysis by the utility should be conducted to decide where the product best fits within the incentive programs. SDG&E Emerging Technologies Page 30

31 MARKET BARRIERS While it is premature to make any assumptions regarding the market penetration of the studied technology, it is appropriate to state that it could serve an important share of the HVAC market. One of market barriers of promoting proposed technology is lack of consumer knowledge. Customers have difficulties choosing the right product for their building s HVAC needs because there are many varieties of products in the market. The lack of information and knowledge about the products and technologies often lead consumers to select the one that requires the least initial cost, which might not necessary be the least expensive option in the long run. The proposed technology costs approximately $350 per zone including thermostats, controllers, and installation. The payback of the system varies widely depending on the facility and whether or not the units are currently running all the time or have a schedule. Additionally, the payback depends from the contribution of utility incentives that often pay by the energy saved (kwh), the permanent demand reduction (kw), and the demand response peak reduction (kw). AESC calculated that the payback could go from 8 years for customers that have already tight equipment scheduling and whose building is located in a utility territory that does not provide incentives to 3 years for customers that would have higher savings due to lack of scheduling and whose building is located in a utility territory with high incentives. POSSIBLE RISKS It will be important to distinguish the permanent load reduction and the demand response capabilities of this technology. The demand reduction results showed demand limiting feature of the system works as designed with relatively moderate settings. At both sites, the total HVAC demand was reduced by 30%-35% with no effect to the zone conditions. With more aggressive settings, demand control can bring additional energy savings. However, the extent of reduction should be carefully selected to avoid causing occupant discomfort. At site 2, for instance, the indoor air temperature started to deviate from the setpoint when the total HVAC demand was reduced by 50%. The feasible amount of reduction without jeopardizing occupant comfort may differ from facility to facility depending on their load characteristics and trial and error approach may be required to find the appropriate limit. The evaluator did not see any specific technology risks associated with the installation. POSSIBLE FUTURE STUDY Both studied installations, while successful, had some characteristics that deviated from a typical office building. The first building included a manufacturing space with a storage room. Additionally, some heat pumps were programmed with fans in the auto mode, which is atypical for a commercial building due to ventilation risks. The second site also had issues with existing HVAC configurations including unscheduled thermostats, poor air distribution, and unmatched zoning due to facility changes over time. Additionally, the baseline data required adjustment because M&V was performed over the span of two summer seasons and the weather conditions changed dramatically during that period. To obtain more reliable results, a future study is recommended in an office with more consistent zoning and programmable thermostats. Such future study should be performed preferably within a single season, in a week-on, weekoff manner, to minimize the risk of successful data normalization and need for correction. SDG&E Emerging Technologies Page 31

Low Cost Building Automation System for Small- and Medium- Sized Commercial Buildings

Low Cost Building Automation System for Small- and Medium- Sized Commercial Buildings Low Cost Building Automation System for Small- and Medium- Sized Commercial Buildings Srinivas Katipamula, Ph.D. Staff Scientist, Pacific Northwest National Laboratory Other TAG Members: Irfan Rehmanji

More information

CASE STUDIES IN USING WHOLE BUILDING INTERVAL DATA TO DETERMINE ANNUALIZED ELECTRICAL SAVINGS

CASE STUDIES IN USING WHOLE BUILDING INTERVAL DATA TO DETERMINE ANNUALIZED ELECTRICAL SAVINGS CAS STUDIS IN USING WHOL BUILDING INTRVAL DATA TO DTRMIN ANNUALIZD LCTRICAL SAVINGS Mark ffinger James Anthony Lia Webster ngineer ngineer Senior ngineer Portland nergy Conservation, Inc Portland, OR USA

More information

ENERGY INITIATIVE ENERGY EFFICIENCY PROGRAM Impact Evaluation of Prescriptive and Custom Lighting Installations. National Grid. Prepared by DNV GL

ENERGY INITIATIVE ENERGY EFFICIENCY PROGRAM Impact Evaluation of Prescriptive and Custom Lighting Installations. National Grid. Prepared by DNV GL ENERGY INITIATIVE ENERGY EFFICIENCY PROGRAM Impact Evaluation of Prescriptive and Custom Lighting Installations National Grid Prepared by DNV GL Date: September 25, 2015 DNV GL www.dnvgl.com September,

More information

Packaged Refrigerant Based Energy Storage (RBES) Air Conditioning System

Packaged Refrigerant Based Energy Storage (RBES) Air Conditioning System Packaged Refrigerant Based Energy Storage (RBES) Air Conditioning System Ram Narayanamurthy Ice Energy, Inc. this technology provides some of the largest opportunities we have right now to address the

More information

Case Study for Fortune 500 Telecom: Retrofitting Pneumatic Controls for Energy Efficiency

Case Study for Fortune 500 Telecom: Retrofitting Pneumatic Controls for Energy Efficiency Case Study for Fortune 500 Telecom: Retrofitting Pneumatic Controls for Energy Efficiency Summary Major Fortune 500 Telecom Company Estimated 40% the corporate building portfolio still use pneumatic thermostats

More information

Building Controls Strategies Conference. Retro-Commissioning with BAS Overview. 10 March Steve Brown, CAP ESD Controls Team Leader

Building Controls Strategies Conference. Retro-Commissioning with BAS Overview. 10 March Steve Brown, CAP ESD Controls Team Leader Building Controls Strategies Conference Retro-Commissioning with BAS Overview 10 March 2015 Steve Brown, CAP ESD Controls Team Leader Kevin Caho PE, LEED AP ESD Energy Engineer Agenda BAS Overview RCx

More information

Persistence Tracking in a Retro-commissioning Program

Persistence Tracking in a Retro-commissioning Program Persistence Tracking in a Retro-commissioning Program Mike Eardley Architectural Energy Corporation Synopsis The persistence of energy savings and electrical demand reductions created by retrocommissioning

More information

Energy Efficiency Impact Study

Energy Efficiency Impact Study Energy Efficiency Impact Study for the Preferred Resources Pilot February, 2016 For further information, contact PreferredResources@sce.com 2 1. Executive Summary Southern California Edison (SCE) is interested

More information

Program Year Final Consultant Report Submitted: February 10, 2010 Volume 1. Prepared for the

Program Year Final Consultant Report Submitted: February 10, 2010 Volume 1. Prepared for the Evaluation Measurement and Verification of the California Public Utilities Commission HVAC High Impact Measures and Specialized Commercial Contract Group Programs 2006-2008 Program Year Final Consultant

More information

Energy Savings Made Simple

Energy Savings Made Simple Energy Savings Made Simple SWARM LOGIC FOR DEMAND MANAGEMENT EXCESSIVE COINCIDENCE LEADS TO HIGHER THAN NECESSARY PEAK DEMAND The issue at hand is a lack of system-wide coordination of HVAC loads, which

More information

Smart Residential Thermostats Results from the FlashTAG on December 20, 2012

Smart Residential Thermostats Results from the FlashTAG on December 20, 2012 Smart Residential Thermostats Results from the FlashTAG on December 20, 2012 Introduction The E3T program conducted its first FlashTAG by conference call and webinar on December 20, 2012 to discuss smart

More information

Leveraging Smart Meter Data & Expanding Services BY ELLEN FRANCONI, PH.D., BEMP, MEMBER ASHRAE; DAVID JUMP, PH.D., P.E.

Leveraging Smart Meter Data & Expanding Services BY ELLEN FRANCONI, PH.D., BEMP, MEMBER ASHRAE; DAVID JUMP, PH.D., P.E. ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For more information about ASHRAE,

More information

Save with Business Programs and Services

Save with Business Programs and Services Business Programs and Services Change the current way you use energy and make your bill even lower. Save with Business Programs and Services Learn about energy-saving programs, services and rebates available

More information

Project Measurement and Verification Procedures

Project Measurement and Verification Procedures Project and Verification Procedures 1) Introduction The objective of measurement and verification (M&V) activities at the Project level is to confirm that the Measures that are supported by the Retrofit

More information

HVAC Efficiency and Baseline Nonresidential HVAC Stakeholder Meeting #2

HVAC Efficiency and Baseline Nonresidential HVAC Stakeholder Meeting #2 1 HVAC Efficiency and Baseline Nonresidential HVAC Stakeholder Meeting #2 California Statewide Utility Codes and Standards Program Abhijeet Pande Heschong Mahone Group, Inc. December 9, 2010 12/09/2010

More information

Small Oil-Less Centrifugal Compressors: Bringing Energy Efficiency and Reduced Costs to Chiller Plants

Small Oil-Less Centrifugal Compressors: Bringing Energy Efficiency and Reduced Costs to Chiller Plants Small Oil-Less Centrifugal Compressors: Bringing Energy Efficiency and Reduced Costs to Chiller Plants Ben Erpelding and Annika Moman, San Diego Regional Energy Office ABSTRACT According the U.S. Department

More information

Ductless Mini Pilot Study

Ductless Mini Pilot Study Ductless Mini Pilot Study Final Report Prepared For: NSTAR Electric and Gas Corporation National Grid Connecticut Light and Power United Illuminating Western Massachusetts Electric Company Connecticut

More information

Energy Conservation Pilot Program

Energy Conservation Pilot Program Energy Conservation Pilot Program Pineapple Hill Residence 126 124 122 Average Voltage 12 118 116 114 112 Incoming Voltage After MicroPlanet Regulation Voltage Before and After MicroPlanet Regulation Prepared

More information

Smart Thermostats: Paving the Way for Smart EM&V

Smart Thermostats: Paving the Way for Smart EM&V Smart Thermostats: Paving the Way for Smart EM&V Claire Miziolek, NEEP Joe Loper, Itron Abigail Daiken, US Environmental Protection Agency Richard Counihan, Nest Labs Nkechi Ogbue, ecobee Setting the Scene

More information

Impact Evaluation of Upstream HVAC Programs (HVAC1)

Impact Evaluation of Upstream HVAC Programs (HVAC1) Impact Evaluation of 2013-14 Upstream HVAC Programs (HVAC1) California Public Utilities Commission Date: CALMAC Study ID [Fill In here] LEGAL NOTICE This report was prepared under the auspices of the California

More information

Chilled Water Plant Redesign

Chilled Water Plant Redesign 17 Chilled Water Plant Redesign OVERVIEW The chilled water plant redesign includes the addition of a thermal energy storage system. This allows for economic and operational benefits for the facility by

More information

Air Source Heat Pumps in the Commercial Market. Thursday, February 5, :00-10:30 a.m.

Air Source Heat Pumps in the Commercial Market. Thursday, February 5, :00-10:30 a.m. Air Source Heat Pumps in the Commercial Market Thursday, February 5, 2015 9:00-10:30 a.m. 1. Commercial Equipment Applications, Benefits, Limitations 2. Case Studies 3. Efficiency Vermont Technical & Financial

More information

Advanced Rooftop Controllers Field Validated HVAC Energy Savings & More

Advanced Rooftop Controllers Field Validated HVAC Energy Savings & More Advanced Rooftop Controllers Field Validated HVAC Energy Savings & More Track 2 HVAC and Analytics May 25, 2017 Transformative Wave 2017 RTU FACTS ROOFTOP PACKAGED UNITS WHY CARE ABOUT AN RTU? THEY ARE

More information

Whole Building Energy Performance Evaluation through. Similar Control Strategies

Whole Building Energy Performance Evaluation through. Similar Control Strategies Whole Building Energy Performance Evaluation through Similar Control Strategies S.H. Cheon 1, Y.H. Kwak 1, C.Y. Jang 2, and J.H. Huh 1* 1 Department of Architectural Engineering, University of Seoul, Seoul

More information

Custom Application 2018 Retrofit Program

Custom Application 2018 Retrofit Program The Retrofit Program is designed for Commercial and Industrial (C&I) customers to help replace aging and inefficient equipment and systems with more energy efficient technologies. Tailored to a customer's

More information

Energy Modeling Applications for Existing Buildings

Energy Modeling Applications for Existing Buildings Energy Modeling Applications for Existing Buildings Presented by: Clark Denson PE, CEM, BEMP, LEED AP BD+C 4/27/12 Learning Objectives 1. List available methods and tools for energy modeling 2. Explain

More information

COMMERCIAL LOAD ESTIMATING. Load Estimating Level 3: Block and Zone Loads. Technical Development Program

COMMERCIAL LOAD ESTIMATING. Load Estimating Level 3: Block and Zone Loads. Technical Development Program COMMERCIAL LOAD ESTIMATING Load Estimating Level 3: Block and Zone Loads Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design,

More information

HVAC Real-time Remote Monitoring 4 year Case Study Delivering Value

HVAC Real-time Remote Monitoring 4 year Case Study Delivering Value Denis Collet, President - Engineer CLD industries, LLC dcollet@cld-industries.com Cell Number 845-399-8540 HVAC Real-time Remote Monitoring 4 year Case Study Delivering Value Denis Collet, CLD Industries

More information

Upstream HVAC Evaluation DRAFT Research Plan

Upstream HVAC Evaluation DRAFT Research Plan Upstream HVAC Evaluation DRAFT Research Plan WO# ED_D_HVAC_1 California Public Utilities Commission, Energy Division Contract # 12PS5095 Prepared by KEMA, Inc. 6/24/2015 LEGAL NOTICE This report was prepared

More information

United Illuminating Company and Connecticut Light & Power. Final Report, 2005 Coincidence Factor Study

United Illuminating Company and Connecticut Light & Power. Final Report, 2005 Coincidence Factor Study United Illuminating Company and Connecticut Light & Power, 2005 Coincidence Factor Study Prepared for: The Connecticut Energy Conservation Management Board and United Illuminating 157 Church Street New

More information

Matt Gudorf UCI Energy Manager

Matt Gudorf UCI Energy Manager Matt Gudorf UCI Energy Manager UNIVERSITY OF CALIFORNIA, IRVINE Comprehensive research university 22,216 Undergraduate Students $330 million sponsored research 27 lab buildings operating 24/7 ~7.5 Million

More information

Focus on Energy Evaluated Deemed Savings Changes

Focus on Energy Evaluated Deemed Savings Changes Focus on Energy Evaluated Deemed Savings Changes September 14, 2015 Public Service Commission of Wisconsin This page left blank. Prepared by: Cadmus Table of Contents Deemed Savings Analysis... 1 2014

More information

Standardizing Smart/Connected Products in a Highly Innovative and Dynamic Market

Standardizing Smart/Connected Products in a Highly Innovative and Dynamic Market Standardizing Smart/Connected Products in a Highly Innovative and Dynamic Market Robert Wilkins Thursday, September 15, 2016 10:00 a.m. 10:30 a.m. AHRI One of the nation s larger trade associations including

More information

Unitary Air Conditioner Field Performance

Unitary Air Conditioner Field Performance Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2004 Unitary Air Conditioner Field Performance Todd M. Rossi Field Diagnostic

More information

A Case Study in Energy Modeling of an Energy Efficient Building with Gas Driven Absorption Heat Pump System in equest

A Case Study in Energy Modeling of an Energy Efficient Building with Gas Driven Absorption Heat Pump System in equest A Case Study in Energy Modeling of an Energy Efficient Building with Gas Driven Absorption Heat Pump System in equest Altamash A. Baig Alan S. Fung Mechanical and Industrial Engineering, Ryerson University

More information

Does It Keep The Drinks Cold and Reduce Peak Demand? An Evaluation of a Vending Machine Control Program

Does It Keep The Drinks Cold and Reduce Peak Demand? An Evaluation of a Vending Machine Control Program Does It Keep The Drinks Cold and Reduce Peak Demand? An Evaluation of a Vending Machine Control Program Cathy Chappell, Heschong Mahone Group Ed Hamzawi and Wim Bos, Sacramento Municipal Utility District

More information

Bi-Level Office Lighting with Occupancy Sensors

Bi-Level Office Lighting with Occupancy Sensors FINAL REPORT E3T Emerging Technology Assessment Bi-Level Office Lighting with Occupancy Sensors January 2011 Prepared for: This publication contains material written and produced for public distribution.

More information

2012 Statewide Load Impact Evaluation of California Aggregator Demand Response Programs Volume 1: Ex post and Ex ante Load Impacts

2012 Statewide Load Impact Evaluation of California Aggregator Demand Response Programs Volume 1: Ex post and Ex ante Load Impacts 2012 Statewide Evaluation of California Aggregator Demand Response Programs Volume 1: Ex post and Ex ante s CALMAC Study ID PGE0318.01 Steven D. Braithwait Daniel G. Hansen David A. Armstrong April 1,

More information

RESTORE 1030TM Testing Protocol

RESTORE 1030TM Testing Protocol RESTORE 1030TM Testing Protocol Test protocols will vary depending on the type of equipment being evaluated. The length of time required to do the testing, however, remains consistent no matter what the

More information

Building Energy Modeling Using Artificial Neural Networks

Building Energy Modeling Using Artificial Neural Networks Energy Research Journal Original Research Paper Building Energy Modeling Using Artificial Neural Networks Maya Arida, Nabil Nassif, Rand Talib and Taher Abu-Lebdeh Department of Civil, Architectural and

More information

South Carolina Society for Hospital Engineers

South Carolina Society for Hospital Engineers South Carolina Society for Hospital Engineers Selecting Energy Partners: Criteria & Pitfalls and the Top 10 Ways to Reduce Energy in a Hospital Presented by Jon Dierking, PE, CEM, LEED AP Director of Energy

More information

Building Energy Analysis for a Multi-Family Residential Building (Multi V III VRF Heat-Pump System)

Building Energy Analysis for a Multi-Family Residential Building (Multi V III VRF Heat-Pump System) Building Energy Analysis for a Multi-Family Residential Building (Multi V III VRF Heat-Pump System) Residential-Building Energy-Modeling Engineering Study VRF-ES-BH-001-US 012E03 Executive Summary Contents

More information

Residential Smart Thermostat

Residential Smart Thermostat Work Paper SW13XX### Revision # Program Administrator: Southern California Edison Prepared by Southern California Edison and Nest Labs Residential Smart Thermostat For Work Paper Reviewer Use Only List

More information

PARTICIPANT HANDBOOK

PARTICIPANT HANDBOOK 2013-2014 PARTICIPANT HANDBOOK POLICIES AND PROCEDURES FOR PARTICIPATION IN THE STATEWIDE SAVINGS BY DESIGN PROGRAM Last Revised: January 15, 2014 www.savingsbydesign.com This program is funded by California

More information

Energy Savings from Connected Thermostats: Issues, Challenges, and Results

Energy Savings from Connected Thermostats: Issues, Challenges, and Results Energy Savings from Connected Thermostats: Issues, Challenges, and Results Michael Blasnik. Nest Labs, Palo Alto, CA ABSTRACT Internet-connected thermostats are gaining wider adoption in the marketplace

More information

SUMMARY OF SERVICES & INCENTIVES

SUMMARY OF SERVICES & INCENTIVES SMALL BUSINESS PROGRAM 2017 SUMMARY OF SERVICES & INCENTIVES Effective through December 31, 2017 Last updated February 1, 2017 EFFICIENCY INCENTIVES SUMMARY The Focus on Energy Small Business Program offers

More information

Instant discount of 33% off improvement cost, up to $1,250 Plus, potential savings bonus of up to $250 (**)

Instant discount of 33% off improvement cost, up to $1,250 Plus, potential savings bonus of up to $250 (**) RESIDENTIAL PROGRAM HOME PERFORMANCE with ENERGY STAR IMPROVE YOUR HOME'S COMFORT. SAVE MONEY. REDUCE ENERGY. EARN S. Home Performance with ENERGY STAR offers homeowners instant discounts for making recommended

More information

REPORT. Xcel Energy Colorado Smart Thermostat Pilot Evaluation Report. May 12, Prepared for Xcel Energy

REPORT. Xcel Energy Colorado Smart Thermostat Pilot Evaluation Report. May 12, Prepared for Xcel Energy REPORT Xcel Energy Colorado Smart Thermostat Pilot Evaluation Report May 12, 2017 Prepared for Xcel Energy Prepared by Josh Schellenberg Vice President Alana Lemarchand Senior Consultant Alexandra Wein

More information

Thermal Energy Storage

Thermal Energy Storage This article was published in ASHRAE Journal, June 2013. Copyright 2013 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission

More information

Optimal Design for a Hybrid Ground-Source Heat Pump

Optimal Design for a Hybrid Ground-Source Heat Pump Optimal Design for a Hybrid Ground-Source Heat Pump Zhongyi Yu, Xudong Yuan, Bin Wang School of Environmental Science and Engineering, Huazhong University of Science and Technology, Wuhan 430074, China,

More information

MEP's Letter of Assurance

MEP's Letter of Assurance MEP's Letter of Assurance Instructions Multifamily Residential WELL Certification is determined by onsite Performance Verification and documentation, including Letters of Assurance from the appropriate

More information

ARCHITECTURE AND FIELD TEST OF A RESTFUL WEB SERVICE FOR THE OPTIMISATION OF SPACE HEATING IN A COMMERCIAL OFFICE

ARCHITECTURE AND FIELD TEST OF A RESTFUL WEB SERVICE FOR THE OPTIMISATION OF SPACE HEATING IN A COMMERCIAL OFFICE ARCHITECTURE AND FIELD TEST OF A RESTFUL WEB SERVICE FOR THE OPTIMISATION OF SPACE HEATING IN A COMMERCIAL OFFICE D. Lindelöf 1, H. Afshari 1, M. Alisafaee 1, J. Biswas 1, P. Borsò 1, X. Mocellin 1, J.

More information

Fraunhofer CSE: Applied R&D to Drive Clean Energy Technology Commercialization & Economic Development June 2014

Fraunhofer CSE: Applied R&D to Drive Clean Energy Technology Commercialization & Economic Development June 2014 Fraunhofer CSE: Applied R&D to Drive Clean Energy Technology Commercialization & Economic Development June 2014 Fraunhofer is the largest organization for applied research in Europe More than 81 research

More information

YORK UNITIZED ENERGY RECOVERY VENTILATOR (ERV) Superior air-flow 300 6,200 CFM

YORK UNITIZED ENERGY RECOVERY VENTILATOR (ERV) Superior air-flow 300 6,200 CFM YORK UNITIZED ENERGY RECOVERY VENTILATOR (ERV) Superior air-flow 300 6,200 CFM YORK UNITIZED ENERGY RECOVERY VENTILATORS Regardless of building type or rating system, today s building must be as energy

More information

Electric Standard Offer Program

Electric Standard Offer Program Electric Standard Offer Program Procedure No. 360-17 Limits Used To Verify Energy Savings 1. Purpose: To document the rational and intent for the use of limits in the energy savings calculations utilized

More information

Assessment of the energy demand in energy-saving office buildings from the viewpoint of variations of internal heat gains

Assessment of the energy demand in energy-saving office buildings from the viewpoint of variations of internal heat gains Assessment of the energy demand in energy-saving office buildings from the viewpoint of variations of internal heat gains Andrzej Baranowski 1,2 and Joanna Ferdyn-Grygierek 1,2 1 Silesian University of

More information

2017 PARTICIPANT HANDBOOK

2017 PARTICIPANT HANDBOOK 2017 PARTICIPANT HANDBOOK POLICIES AND PROCEDURES FOR PARTICIPATION IN THE STATEWIDE SAVINGS BY DESIGN PROGRAM Last Revised: January 20, 2017 www.savingsbydesign.com This program is funded by California

More information

A METHODOLOGY FOR REDUCING BUILDING ENERGY CONSUMPTION

A METHODOLOGY FOR REDUCING BUILDING ENERGY CONSUMPTION ME 164 Senior Capstone Design The Cooper Union Spring 2014 A METHODOLOGY FOR REDUCING BUILDING ENERGY CONSUMPTION Eric Leong Cooper Union New York, NY Advised by Prof. Melody Baglione Cooper Union New

More information

Design and development of a residential gas-fired heat pump

Design and development of a residential gas-fired heat pump Design and development of a residential gas-fired heat pump Edward A Vineyard a*, Ahmad Abu-Heiba a, Isaac Mahderekal b a Oak Ridge National Laboratory, P.O. Box 2008, MS 6070, Oak Ridge, TN, 37831, USA

More information

Residential HVAC Field Verification and Diagnostics

Residential HVAC Field Verification and Diagnostics 2016 Title 24 Codes & Standards Enhancement (CASE) Proposal Residential HVAC Field Verification and Diagnostics Stakeholder Webinar, May 21 st, 2014 Farhad Farahmand, Cathy Chappell TRC Ffarahmand@TRCSolutions.com,

More information

Vivint Smart Home. Energy Savings Study. Heating and Cooling Results. September 2017

Vivint Smart Home. Energy Savings Study. Heating and Cooling Results. September 2017 Vivint Smart Home Energy Savings Study Heating and Cooling Results September 2017 For Vivint Element Thermostat enabled with Sky Smart Home Assistant DISCLAIMER: This study was commissioned by Vivint Smart

More information

Impact Evaluation of National Grid Rhode Island s Custom Refrigeration, Motor and Other Installations

Impact Evaluation of National Grid Rhode Island s Custom Refrigeration, Motor and Other Installations Impact Evaluation of National Grid Rhode Island s Custom Refrigeration, Motor and Other Installations National Grid Final Report Date: August 15, 2014 Table of contents 1 INTRODUCTION... 1 1.1 Purpose

More information

Performance Analysis of Hotel Lighting Control System

Performance Analysis of Hotel Lighting Control System Performance Analysis of Hotel Lighting Control System Erik Page and Michael Siminovitch, University of California, Davis, California Lighting Technology Center 1 ABSTRACT The Lighting Control System (LCS),

More information

Coincidence Factor Study Residential and Commercial & Industrial Lighting Measures. Prepared for; New England State Program Working Group (SPWG)

Coincidence Factor Study Residential and Commercial & Industrial Lighting Measures. Prepared for; New England State Program Working Group (SPWG) Coincidence Factor Study Residential and Commercial & Industrial Lighting Measures Prepared for; New England State Program Working Group (SPWG) For use as an Energy Efficiency Measures/Programs Reference

More information

A NEW ALGORITHM FOR SENSORS VERIFICATION AND CORRECTION IN AIR HANDLING UNITS

A NEW ALGORITHM FOR SENSORS VERIFICATION AND CORRECTION IN AIR HANDLING UNITS A NEW ALGORITHM FOR SENSORS VERIFICATION AND CORRECTION IN AIR HANDLING UNITS Nunzio Cotrufo, Radu Zmeureanu Department of Building, Civil and Environmental Engineering Concordia University Montréal Quebec,

More information

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS Bjarne W. Olesen Ph. D, International Centre for Indoor Environment and Energy, Department of Mechanical Engineering, Technical

More information

Uncertainties in Energy Consumption Introduced by Building Operations and Weather for a Medium-Size Office Building

Uncertainties in Energy Consumption Introduced by Building Operations and Weather for a Medium-Size Office Building Uncertainties in Energy Consumption Introduced by Building Operations and Weather for a Medium-Size Office Building Liping Wang, Paul Mathew, Xiufeng Pang Environmental Energy Technologies Division Lawrence

More information

New Approaches in Automating and Optimizing Demand Response to Solve Peak Load Management Problems

New Approaches in Automating and Optimizing Demand Response to Solve Peak Load Management Problems New Approaches in Automating and Optimizing Demand Response to Solve Peak Load Management Problems WHITE PAPER Abstract Grid power demand peaks and increasing supply/ demand inbalances create management

More information

Advanced Rooftop Unit Controls

Advanced Rooftop Unit Controls Advanced Rooftop Unit Controls Showcase January 23, 2013 Welcome. Today s webinar is being recorded and will be posted at: www.e3tnw.org www.conduitnw.org You may submit questions at any time during the

More information

9/13/2011. Mark Hanicits, Director of Facilities and Safety, MetroSouth Medical Center. Terry Malloy P.E., Cxa, Project Manager, Teng & Associates

9/13/2011. Mark Hanicits, Director of Facilities and Safety, MetroSouth Medical Center. Terry Malloy P.E., Cxa, Project Manager, Teng & Associates Mark Hanicits, Director of Facilities and Safety, MetroSouth Medical Center September 21 st, 2011 4:15pm 5:15pm Terry Malloy P.E., Cxa, Project Manager, Teng & Associates Energy consumption (BTU/SF) in

More information

EER & SEER AS PREDICTORS OF SEASONAL COOLING PERFORMANCE

EER & SEER AS PREDICTORS OF SEASONAL COOLING PERFORMANCE EER & SEER AS PREDICTORS OF SEASONAL COOLING PERFORMANCE Southern California Edison Design & Engineering Services 642 N. Irwindale Avenue, Suite B Irwindale, California 9172 October 24 ACKNOWLEDGEMENTS

More information

Normal Children's Discovery Museum, LEED Silver:

Normal Children's Discovery Museum, LEED Silver: Normal Children's Discovery Museum, LEED Silver: Post Occupancy Energy Performance October 28, 2010 Hosted by: USGBC Illinois Chapter, Central Illinois Branch Sponsored by: ASHRAE Central Illinois Chapter

More information

2012 LOAD IMPACT EVALUATION OF SDG&E SMALL COMMERCIAL PTR PROGRAM SDG0267 FINAL REPORT

2012 LOAD IMPACT EVALUATION OF SDG&E SMALL COMMERCIAL PTR PROGRAM SDG0267 FINAL REPORT 2012 LOAD IMPACT EVALUATION OF SDG&E SMALL COMMERCIAL PTR PROGRAM SDG0267 FINAL REPORT EnerNOC Utility Solutions Consulting 500 Ygnacio Valley Road Suite 450 Walnut Creek, CA 94596 925.482.2000 www.enernoc.com

More information

Moving Beyond Low Hanging Fruit: Successful Energy Efficiency Program Outreach Strategies for Commercial Facilities

Moving Beyond Low Hanging Fruit: Successful Energy Efficiency Program Outreach Strategies for Commercial Facilities ABSTRACT Moving Beyond Low Hanging Fruit: Successful Energy Efficiency Program Outreach Strategies for Commercial Facilities Peter Serian, Bryn Samuel, Mark D Antonio, Lucy Neiman, and Gary Epstein, ERS

More information

MEP Engineer's Letter of Assurance

MEP Engineer's Letter of Assurance Instructions MEP Engineer's Letter of Assurance WELL Building Standard, Jan 2016 WELL Certification and WELL Core and Shell Compliance are determined by onsite Performance Verification and Documentation,

More information

Permanent Load Shifting Program

Permanent Load Shifting Program 1. Program Description Permanent Load Shifting (PLS) can help reduce system peak load by storing energy produced during off-peak period and shifting electricity use from on-peak to off-peak periods on

More information

Focused Impact Evaluation of the Home Upgrade Program

Focused Impact Evaluation of the Home Upgrade Program Focused Impact Evaluation of the 2013-2014 Home Upgrade Program California Public Utilities Commission Date: March 22, 2016 CALMAC Study ID [Fill in here] LEGAL NOTICE This report was prepared as an account

More information

Small Building Tune-up Pilot Program. Kevin Afflerbaugh, LEED AP Jim Zarske, PE, CEM, LEED AP Nexant, Inc.

Small Building Tune-up Pilot Program. Kevin Afflerbaugh, LEED AP Jim Zarske, PE, CEM, LEED AP Nexant, Inc. Small Building Tune-up Pilot Program Kevin Afflerbaugh, LEED AP Jim Zarske, PE, CEM, LEED AP Nexant, Inc. AIA Quality Assurance Learning Objectives 1. The significant, yet untapped commissioning opportunities

More information

Best Practice Recommendations for Wall Retrofit on the Two-Story Flexible Research Platform (FRP) at Oak Ridge National Laboratory (ORNL).

Best Practice Recommendations for Wall Retrofit on the Two-Story Flexible Research Platform (FRP) at Oak Ridge National Laboratory (ORNL). Best Practice Recommendations for Wall Retrofit on the Two-Story Flexible Research Platform (FRP) at Oak Ridge National Laboratory (ORNL). Wall retrofit strategies for retrofit on the interior side of

More information

ENERGY EFFICIENT THERMAL ENERGY STORAGE FOR DX AIR CONDITIONING

ENERGY EFFICIENT THERMAL ENERGY STORAGE FOR DX AIR CONDITIONING ENERGY EFFICIENT THERMAL ENERGY STORAGE FOR DX AIR CONDITIONING Paul Kuhlman (pkuhlman@ice-energy.com) Ramachadran Narayanamurthy (ram@ice-energy.com) Ice Energy Inc. 9351 Eastman Park Dr.; Suite B Windsor

More information

NYSERDA CHP Assessment Report A S S E S S I N G T H E C H P P L A N T A T T O R E N C O N D O M I N I U M S

NYSERDA CHP Assessment Report A S S E S S I N G T H E C H P P L A N T A T T O R E N C O N D O M I N I U M S NYSERDA CHP Assessment Report A S S E S S I N G T H E C H P P L A N T A T T O R E N C O N D O M I N I U M S October 9, 2013 Toren Condominiums Toren Condominiums DISCLAIMER OF WARRANTY Information contained

More information

WELCOME. Page 1. WELCOME to the Building Environmental Comfort Verification Survey.

WELCOME. Page 1. WELCOME to the Building Environmental Comfort Verification Survey. WELCOME WELCOME to the Building Environmental Comfort Verification Survey. By answering a few brief questions, you can provide valuable information to assist in maintaining or improving temperature and

More information

High Technology Energy Savings Guide

High Technology Energy Savings Guide High Technology Energy Savings Guide The high-tech industry is a crucial and dynamic part of Oregon s economy that is expected to grow faster than other industries over the next decade. Working in a highly

More information

Ground-Coupled Heat Pump And Energy Storage

Ground-Coupled Heat Pump And Energy Storage Ground-Coupled Heat Pump And Energy Storage By Ed Lohrenz, Member ASHRAE; and Sergio Almeida, P.Eng., Member ASHRAE Ground-coupled heat pump (GCHP) systems consume less purchased energy than an HVAC system

More information

Benchmarking EPA Portfolio Manager and Energy Star Certification

Benchmarking EPA Portfolio Manager and Energy Star Certification Benchmarking EPA Portfolio Manager and Energy Star Certification 1 What is Benchmarking? Energy Benchmarking is the practice of comparing any given building to similar buildings for the purpose of evaluating

More information

Field investigation on indoor thermal environment of a high-rise condominium in hot-humid climate of Bangkok, Thailand

Field investigation on indoor thermal environment of a high-rise condominium in hot-humid climate of Bangkok, Thailand Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 00 (2017) 000 000 www.elsevier.com/locate/procedia International High- Performance Built Environment Conference A Sustainable

More information

Solar Decathlon Market Study USC FluxHome

Solar Decathlon Market Study USC FluxHome Emerging Products Solar Decathlon Market Study USC FluxHome Report Prepared by Emerging Products Customer Programs & Services Southern California Edison October 2014 Acknowledgments Southern California

More information

MODELLING AND SIMULATION OF BUILDING ENERGY SYSTEMS USING INTELLIGENT TECHNIQUES

MODELLING AND SIMULATION OF BUILDING ENERGY SYSTEMS USING INTELLIGENT TECHNIQUES MODELLING AND SIMULATION OF BUILDING ENERGY SYSTEMS USING INTELLIGENT TECHNIQUES Ph.D. THESIS by V. S. K. V. HARISH ALTERNATE HYDRO ENERGY CENTRE INDIAN INSTITUTE OF TECHNOLOGY ROORKEE ROORKEE-247667 (INDIA)

More information

Climate Change in Canada: Impacts on Building Energy Use Intensity

Climate Change in Canada: Impacts on Building Energy Use Intensity Climate Change in Canada: Impacts on Building Energy Use Intensity Nathan Kegel IES, Ltd. Minneapolis, MN ABSTRACT Whole building energy simulation is a useful tool in assessing building energy performance

More information

LIBRARY ENERGY WALK- THROUGH. Andy Robinson, Training and Education, SEDAC

LIBRARY ENERGY WALK- THROUGH. Andy Robinson, Training and Education, SEDAC LIBRARY ENERGY WALK- THROUGH Andy Robinson, Training and Education, SEDAC ILLINOIS ENERGY NOW University of Illinois 360 Energy Group 2 WHAT WE DO SEDAC Free Services Outreach and Training Energy Assistance

More information

Smart Energy Utilization System

Smart Energy Utilization System 10/4/2016 Smart Energy Utilization System 1/49 Smart Energy Utilization System Tyler Johnson Zachary Rubenfeld Claude Mickel Brooks James Dirkes Rahul Sinha Philip Maloney Garret Clark 10/4/2016 Smart

More information

MEP's Letter of Assurance

MEP's Letter of Assurance MEP's Letter of Assurance Instructions WELL Certification is determined by onsite Performance Verification and documentation, including Letters of Assurance from the appropriate professionals overseeing

More information

Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France

Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France Sylvain Boulet 1, Stéphanie Armand-Decker 2, FCBA Technological Institute I2M-TREFLE laboratory -

More information

THERMAL PERFORMANCE USING RADIANT BARRIER AND PHASE CHANGE MATERIAL IN ROOFS

THERMAL PERFORMANCE USING RADIANT BARRIER AND PHASE CHANGE MATERIAL IN ROOFS THERMAL PERFORMANCE USING RADIANT BARRIER AND PHASE CHANGE MATERIAL IN ROOFS Haider I. Alyasari1, Jae D. Chang1 1University of Kansas, Lawrence, Kansas ABSTRACT: Buildings are large consumers of energy

More information

V entilation control using carbon dioxide

V entilation control using carbon dioxide REAL-TIME VENTILATION Operational control of ventilation systems using sensors that measure concentrations Editors Note: A longer version of this article is available at no cost on HPAC Engineering s Website

More information

5-Ton Indirect Evaporative HVAC

5-Ton Indirect Evaporative HVAC Design & Engineering Services 5-Ton Indirect Evaporative HVAC Report Prepared by: Design & Engineering Services Customer Service Business Unit Southern California Edison October 27, 2011 Acknowledgements

More information

Optimizing Buildings Using Analytics and Engineering Expertise

Optimizing Buildings Using Analytics and Engineering Expertise Optimizing Buildings Using Analytics and Engineering Expertise Course Code: CEU244 CEU Value:.1 CEU April 2014 Learning Objectives Upon completion of this seminar you will be able to: Define the concept

More information

Residential New Construction. Baseline Study of Building Characteristics. Homes Built After 2001 Codes

Residential New Construction. Baseline Study of Building Characteristics. Homes Built After 2001 Codes Residential New Construction Baseline Study of Building Characteristics Homes Built After 2001 Codes Project Manager Mary Kay Gobris Pacific Gas and Electric Co. Prepared for: Pacific Gas and Electric

More information

Energy Audit Tool Manual. Client Name

Energy Audit Tool Manual. Client Name Energy Audit Tool Manual 1 Client Name CONTENTS I. About the ISO 50002 standard II. Introduction to the tool functionality III. Basic Interface and Menus IV. EA Tool Screens Detail 2 ABOUT THE ISO 50002

More information

Performance evaluation of an actual building airconditioning

Performance evaluation of an actual building airconditioning IOP Conference Series: Materials Science and Engineering OPEN ACCESS Performance evaluation of an actual building airconditioning system To cite this article: M F Othman et al 2013 IOP Conf. Ser.: Mater.

More information