Change-over natural and mechanical ventilation system energy consumption in single-family buildings

Size: px
Start display at page:

Download "Change-over natural and mechanical ventilation system energy consumption in single-family buildings"

Transcription

1 Change-over natural and mechanical ventilation system energy consumption in single-family buildings Maria Kostka 1,*, and Małgorzata Szulgowska-Zgrzywa 1 1 Wrocław University of Science and Technology, Faculty of Environmental Engineering, Wybrzeze Wyspiańskiego 27, Wrocław, Poland Abstract. The parameters of the outside air in Poland cause that in winter it is reasonable to use a mechanical ventilation equipped with a heat recovery exchanger. The time of spring, autumn, summer evenings and nights are often characterized by the parameters of the air, which allow for a natural ventilation and reduce the electricity consumption. The article presents the possibilities of energy consumption reduction for three energy standards of buildings located in Poland, ventilated by a change-over hybrid system. The analysis was prepared on the assumption that the air-to-water heat pump is the heat source for the buildings. 1 Introduction 1.1 Residential ventilation solutions in Poland A typical ventilation in single-family buildings in Poland is implemented in one of two ways natural/gravity or mechanical. In the natural system the driving force of the air exchange is the pressure difference on the building partition, caused by the difference of internal and external temperature and by the wind. This is the basic system used over many years in the Polish construction industry. Along with the change of regulations related to the quality of buildings, their thermal insulation improvement and energy demand reduction, the currently used mechanical systems are becoming popular. This type of ventilation in detached buildings reduces the energy consumption needed in the natural system for heating the outdoor infiltration air rate. The air exchange is provided by two fans placed in the air handling unit (AHU), equipped also with an exhaust air heat recovery exchanger, air filters and a heater. Usage of the heat recovery is crucial and justifies the choice of the mechanical systems. In case of the gravity ventilation used in low-energy buildings, cost of outdoor air heating become a significant operating cost [1]. Mechanical ventilation allows reducing the cost of ventilation and ensures the constant air exchange efficiency, which is not possible in the case of natural ventilation in the Polish climate. Fluctuations of the outside air temperature in Poland cause that the efficiency of natural ventilation is variable during the year. In winter the volume of the exchanged air is higher * Corresponding author: maria.kostka@pwr.edu.pl The Authors, published by EDP Sciences. This is an open access article distributed under the terms of the Creative Commons Attribution License 4.0 (

2 than during the rest of the year and the reason is the large difference between the internal and external temperatures. It has a significant impact on the energy demand and the building heating costs. In the warmer periods of the year, when the temperature differences decrease, the efficiency of the natural system is also getting lower. It may also happen that the air exchange ceases completely. The parameters of outside air in Poland indicate that a combination of the mechanical and the natural ventilation in detached buildings can be cost-effective and allow keeping the thermal comfort and good indoor air quality. Low temperatures in winter cause that it is reasonable to use mechanical ventilation equipped with a heat recovery from the exhaust air. Also during summer, in case of a high outside temperature and days of windless weather, the use of fans and a heat recovery system is justified because it maintains a proper air exchange in the building and reduces overheating of the interiors. The time of spring, autumn, summer evenings and nights are often characterized by the parameters of air, which allow for the natural building ventilation. The combination of the natural and the mechanical systems is realized by the hybrid ventilation. 1.2 Hybrid ventilation The hybrid ventilation is only a general name of system which combines the natural and the mechanical processes, but does not define the forms of control strategy. Their common operation can be implemented in a variety of ways: seasonal switching, switching as a result of a measured parameter (e.g. outside air temperature, indoor temperature, indoor CO 2 concentration) or simultaneous work of systems. In the professional literature, there is lack of information about the design of such systems. There are also very few examples of existing solutions and their energy efficiency. The hybrid ventilation in residential constructions was conducted by M. Kim and J. Hwang [2]. According to their definition, the system with a mechanical air exhaust and a natural air supply is classified as a hybrid system. For an apartment located in Seoul they attempted to determine the airflow which provides comfortable thermal conditions and good air quality, also taking into account the energy savings. A similar system with a mechanical exhaust was studied by D. Jreijiry, A. Husaunndee and C. Inrad [3]. They developed hybrid system control strategies for the housing sector. For buildings located in Greece and France their research conducted that a hybrid ventilation system enables decrease of more than 50% of the exposure of the occupants to high concentrations of CO 2 while reducing at the same time the electrical energy consumed by the fan by 90%. K. Miachou and all [4] conducted a comparative study of natural and hybrid systems for dwellings located in Athens. They showed a slight advantage of the natural system in the air exchange. Their research has been performed in the framework of the research project RESHYVENT [5]. This program defined the design objectives for hybrid ventilation systems and outlined the solutions proposed by the four industrial and scientific consortia for four different European climates zones. 1.3 The justification of the topic According to the report of Central Statistical Office of Poland, the percentage share of households in the energy consumption structure occupied the first place in 2014 and exceeded 30% [6]. On a national scale, with the construction of approximately 70,000 new single-family buildings each year, solutions that combine natural and mechanical ventilation can provide significant reductions in the energy needs. Due to the differences between the countries that have taken up the research topic earlier, including climatic conditions, typical building structures or even residents' expectations, the results of the research should not be directly applied to Poland. For this reason, there is a need to assess 2

3 the energy potential of the hybrid systems operating in the temperate climate of our country. 2 Climate in the selected cities Poland is located in the temperate climate zone, in the transitional area between the temperate oceanic climate on the west and the temperate continental climate on the east. Due to the influence of the continental and oceanic air masses, as well as the direct influence of the Baltic Sea and the presence of mountain areas, the parameters of the outside air in Poland are various in the different regions of the country. The assessment of the energy potential of hybrid ventilation systems should therefore be conducted on a case-by-case basis rather than being generalized to the national results. Figure 1 show the hourly average outside air parameters for 3 selected Polish cities located in the different regions of the country: Suwałki (influence of the continental air masses), Gdańsk (influence of the Baltic Sea) and Wrocław (temperate region). Figure 2 shows the duration of the outside air temperature for this locations. Fig. 1. The parameters of outside air Suwałki (left), Gdańsk (center), Wrocław (right). Fig. 2. The duration of the outside air temperature. 3

4 According to the presented meteorological data [7], Gdańsk is characterized by the mildest parameters of the outdoor air. Temperatures in the range of 1 20 C occurs there for about 85% of the year, while in Wroclaw about 75%, and in Suwałki only about 66% of the year. Wroclaw has the highest number of hours with temperatures above 20 C over 7% of the year, while in Suwałki it is about 5% and in Gdańsk less than 4%. The longest duration of the temperature 0 C and less occurs in Suwałki about 29% of the year. In Wrocław it is about 18%, and in Gdańsk only about 11%. Demonstrated differences indicate a higher climate potential for the hybrid system in the areas characterized by a mild climate. In these locations, the longer the time of the natural ventilation system usage the lower the energy savings associated with the mechanical ventilation work is expected. 3 The research problem The article presents the energy benefits of using a hybrid ventilation system instead of a full-year mechanical ventilation with the heat recovery. The analysis was performed for a single-family building with a usable area of 160m 2. The ventilation air flow rate is 250 m 3 /h, which corresponds to a building air change rate ACH = 0.5h -1. The first step of the calculations was to analyse the work of the building in the variant with the mechanical ventilation with the heat recovery (MW). The reason for this is that the heat recovery is an essential element that increases the energy efficiency of a building. Then, for the hybrid ventilation (HW), the energy savings potential of the final energy demand for the building s heating was determined. In this case the hybrid ventilation was implemented as temporary switching from the mechanical ventilation (MW) to the natural system (NW). The decision to switch between the ventilation systems in the applied algorithm is based on the total final energy consumption of the building. It is defined further below, in Table 3. The analysis was performed for the climatic data presented in point 2 of this article. The heat source in the analysed case was an air-to-water heat pump. 3.1 Building energy class As a result of the increase of the energy efficiency requirements, the demand for usable energy for heating the newly designed single-family houses in Poland is decreasing. An analysis of the hybrid ventilation impact on the building s energy efficiency has been carried out on three variants of a detached house, described by the building s heat losses because of the transmission (Q tr). These variants are: a standard building B9 (Q tr = 9 kw), a low energy building B6 (Q tr = 6 kw) and an ultra-low energy building B3 (Q tr = 3 kw). The standard building is the one whose heat transfer coefficients meet the minimum requirements for single-family houses in Poland and the usable energy index for heating (EU) is c.a. 100 kwh/(m 2 year). The low-energy building is the one in which the heat transfer coefficients guarantee that the EU index is smaller than 40 kwh/(m 2 year). The ultra-low-energy building requires the EU index at about 15 kwh/(m 2 year). Table 1 summarizes the buildings heat losses by transmission (Q tr) and the usable energy indexes (EU) for the three variants of the building energy classes in different climate conditions. 4

5 Qtr EUNW Table 1. The static heat losses and the usable energy index. Gdańsk Wrocław Suwałki EUMW EUNW EUMW EUNW EUMW kw Mechanical ventilation system The air volume for the mechanical ventilation system is 250 m 3 /h. Figure 3 shows the configuration of the air handling unit (AHU). The AHU is assumed in the cross-counter flow heat exchanger with the 80% efficiency. The frost protection of the heat exchanger is an electric preheater, operated when the temperature of the exhaust air (measured by the sensor T e) drops below 5 C and at the same time outside air temperature is below 0 C. The supply air temperature is controlled by an electric heater to a temperature T s = 16 C. The heaters work with the fluent regulation of power. The electrical power of the fans is 160W. Fig. 3. AHU configuration (D damper, FR filter, FN fan, HRE heat recovery exchanger, PH preheater, H heater, To outside air temperature sensor, Ts supply air temperature sensor, Te exhaust air temperature sensor, Rts supply air temperature regulator). 3.3 Heating system The calculations were made on the assumption that the building is heated by an air-to-water heat pump. Selection of the heat pump in each of the analyzed variations was based on the thermal characteristics of the building equipped with the mechanical ventilation system with a heat recovery exchanger. In each of the climatic zones and for each building energy class, the power of the pump was chosen so that the bivalent point was -10 C. Table 2 shows the heat pomp COP data for the heating water supply temperature 35 C and 45 C. The analysis assumes that the building is equipped with an underfloor heating with the parameters of heating agent 40/30 C. The minimum outdoor air temperature required to the heat pump is T a = -15 C. Table 2. The COP of the heat pump for the heating water supply temperature 35 C and 45 C. Ta, o C COP for 35 o C COP for 45 o C

6 3.4 Methods of calculations The simulations in this article were made in hourly steps based on the climate data described in point 2. The total final energy demand for the buildings with the natural ventilation as well as with the mechanical ventilation with the heat recovery were calculated. The total final energy demand for the building with the natural ventilation comes from the electricity required to run the heat pump for the building s heating (Q HP,NW). The total final energy demand for the building with the mechanical ventilation comes from the electricity required to run the heat pump for the building s heating (Q HP,MW) and the electricity required for the central air supply (the power for the fans and the electric preheater - Q EL,MW). The electricity demand for the operation of the air-to-water heat pump for heating the building was determined based on the seasonal coefficient of the performance (SCOP). The SCOP of the air-to-water heat pump was calculated taking into account the partial load correction of the equipment and the operation in the stand-by mode. The steps of the calculations were described in the Table 3. For the building with the hybrid ventilation, the decision in which ventilation system (NW or MW) it should be operating was based on the comparison of the total final energy consumption for both solutions (Q K,NW) and (Q K,HW) in every hour. Next, the share of the working time of the ventilation system with the heat recovery (τ MW) and the savings results from the use of the hybrid ventilation, both the quantitative (ΔQ HW) and the percentage (β HW), were calculated. The ventilation system The total final energy consumption of the building calculated for each hour in year ( h) The savings resulting from the use of the hybrid ventilation Table 3. The steps of the analysis. Building with the Building with the mechanical ventilation hybrid ventilation MW NW MW QK,MW = = QHP,MW + QEL,M.W. - QHP,NW QHP,MW + QEL,MW QK,HW = min(qhp,nw, QEL,MW+QHP,MW) ΔQHW=Σi(QHP,MW+QEL,MW-QHP,NW) where: i the hours in year when QHP,NW<(QEL,MW+QHP,MW) βh.w.=δqh.w/(qhp,m.w.+qel,m.w) 4 Results The results of the analysis for all the variants are summarized in Table 4. The following values were shown: the total final energy demand during the year for the building with the mechanical ventilation with the heat recovery (Q HP,MW and Q EL,MW), the savings results from the work of the hybrid ventilation system (ΔQ H.W. and β H.W.) and the time of the work of the mechanical ventilation per year in percentage (τ M.W.). For the standard energy class (B9) building, the annual savings results due to the hybrid ventilation (β H.W.) are between 9% and 10%. Quantitatively (ΔQ H.W.), the highest savings were observed for Suwałki, 950 kwh per year. Because in this location the total final energy demand for the heat pump and the ventilation unit is the highest, the share of the energy saving is the smallest. For the low energy class (B6) building, the annual energy savings (β HW) range from 13% to 15%. These savings are quantitatively slightly higher than in the standard building (B9). For the ultra-low energy class (B3) building, the annual energy savings (β HW) are between 18% and 28%. Although the amount of the energy savings is lower than in other energy standards, the savings potential is the highest in these buildings. 6

7 Table 4. The results of the analysis. The climate data QHP,MW QEL,MW ΔQHW τmw βhw kwh/year kwh/year kwh/year % % Building B9 Suwałki % 9% Building B9 Wrocław % 8% Building B9 Gdańsk % 10% Building B6 Suwałki % 13% Building B6 Wrocław % 12% Building B6 Gdańsk % 15% Building B3 Suwałki % 18% Building B3 - Wrocław % 23% Building B3 - Gdańsk % 28% In addition to the annual total final energy demand, it is interesting to discuss the monthly statistics of the potential savings in the total final energy demand due to using the hybrid ventilation instead of the full-year mechanical ventilation. These results are summarized in Figure 4. Fig. 4. The reduction in the finally energy demand in the building as a result of the hybrid ventilation. In the winter months, the savings resulting (β HW) from the periodical shutdown of the mechanical ventilation are low. The percentages of these savings are the highest in Suwałki 7

8 (up to 4%), which results from the energy consumption in the protection system for the heat recovery exchanger before the frost. It is also clear that these savings are even higher when the building has a better energy class. During the transition periods III-V and IX-X the savings resulting (β HW) from the switching between the mechanical and the natural ventilation are already significant. For the ultra-low-energy building (B3) in the months V and IX, the savings (β HW) up to 60% comparing to the system with the continuous mechanical ventilation were found. In summer, the natural ventilation is a better system. In Gdansk, it would be advisable to completely shut off the mechanical ventilation system. In Wroclaw and in Suwałki the natural ventilation allows for a significant reduction in energy demand (from 65% to 95%), although the ventilation unit work is periodically profitable. 5 Conclusions Single-family buildings represent a large share of the residential market in Poland and they are impacting significantly the energy consumption in Poland. The climate in Poland varies in the different regions and the systems which are sensitive to the change of the ambient air temperature require the individual analysis. An example of such a system is the mechanical ventilation which periodically can be more costly than the natural ventilation. A detailed analysis of the energy effectiveness of using the hybrid ventilation (i.e. the periodic replacement of the mechanical ventilation by the natural ventilation) can only be carried out together with an analysis of the heating system and for the specific location of the building. In this study, the analysis of the ventilation system operation was carried out in cooperation with an air-to-water heat pump. Both systems are very sensitive to the ambient air temperature data and in this case the impact of climate data on the system efficiency is particularly important. The significant potential of the energy savings in the total final energy demand (for the building s heating system) has been demonstrated for all the analyzed climates. It should be noted that the tendencies in the construction industry, enforced by the legal regulations, are that the buildings will have better and better energy classes, and the air-to-water heat pumps will become more and more popular in Poland. The presented analysis showed that the lower the demand for the usable energy for heating, the greater the effect of introducing the hybrid ventilation. From a practical point of view, the analytical and research work are needed to develop both the technical solutions and the control algorithms for the hybrid ventilation systems in the single-family buildings. Acknowledgments This work is supported by funds from the Ministry of Higher Education for research and development works of young scientists and doctoral students. Project number: 0402/0098/16. References 1. M. Kostka, M. Szulgowska-Zgrzywa, Rynek Instalacyjny, 3 (2016) 2. M. Kim, J. Hwang, Energ. Buildings 41, (2009) 3. D. Jreijiry, A. Husaunndee, C. Inard, Sol. Energy 81, (2007) 4. K. Niachou, S. Hassid, M. Santamouris, I. Livanda, Energ. Buildings 37, (2005) 8

9 5. RESHYVENT, Cluster Project on Demand Controlled Hybrid Ventilation in Residential Buildings with Specific Emphasis of the Integration of Renewables, European Joule Project, Contract No. ENK6-CT (2002) 6. [access: ] 7. [access: ] 9

Computational and the real energy performance of a single-family residential building in Poland an attempt to compare: a case study

Computational and the real energy performance of a single-family residential building in Poland an attempt to compare: a case study Computational and the real energy performance of a single-family residential building in Poland an attempt to compare: a case study Piotr Kowalski 1,*, and Paweł Szałański 1 1 Department of Air Conditioning,

More information

Methods for Improving Energy Performance of Single-family Buildings in Poland s Climatic Conditions

Methods for Improving Energy Performance of Single-family Buildings in Poland s Climatic Conditions Environmental Engineering 10th International Conference eissn 2029-7092 / eisbn 978-609-476-044-0 Vilnius Gediminas Technical University Lithuania, 27 28 April 2017 Article ID: enviro.2017.261 http://enviro.vgtu.lt

More information

Energy consumption and thermal comfort in a passive house built in Romania

Energy consumption and thermal comfort in a passive house built in Romania Chapter 3 - High Performance Sustainable Building Solutions Energy consumption and thermal comfort in a passive house built in Romania Cristina Tanasa, Cristian Sabau, Daniel Dan & Valeriu Stoian Polytechnic

More information

The influence of the ground parameters assumptions on the low enthalpy heat pump s energy source simulation s results

The influence of the ground parameters assumptions on the low enthalpy heat pump s energy source simulation s results The influence of the ground parameters assumptions on the low enthalpy heat pump s energy source simulation s results Ewelina Stefanowicz 1, and Natalia Fidorów-Kaprawy 1,* 1 Wrocław University of Science

More information

Cool Roof Case Studies

Cool Roof Case Studies Michele Zinzi ENEA Cool Roof Case Studies 09/03/2014 European Cool Roofs Council 1 Solar reflecting materials for the building envelope were a widely used construction technology The Mediterranean region

More information

Assessment of the energy demand in energy-saving office buildings from the viewpoint of variations of internal heat gains

Assessment of the energy demand in energy-saving office buildings from the viewpoint of variations of internal heat gains Assessment of the energy demand in energy-saving office buildings from the viewpoint of variations of internal heat gains Andrzej Baranowski 1,2 and Joanna Ferdyn-Grygierek 1,2 1 Silesian University of

More information

The optimization of the mechanical night cooling system in the office building

The optimization of the mechanical night cooling system in the office building The optimization of the mechanical night cooling system in the office building Milos Lain 1, Jan Hensen 2 1 Department of Environmental Engineering, Faculty of Mechanical Engineering, Czech Technical University

More information

Higher efficiency of the cooling unit

Higher efficiency of the cooling unit Higher efficiency of the cooling unit Wojciech Cepiński 1,* 1 Wrocław University of Science and Technology, Faculty of Environmental Engineering, Department of Air Conditioning, Heating, Gas Engineering

More information

Energy-Efficient Passive House using thermal mass to achieve high thermal comfort

Energy-Efficient Passive House using thermal mass to achieve high thermal comfort Energy-Efficient Passive House using thermal mass to achieve high thermal comfort Loa Andersson Managing Director RLI Byggdata AB rli@termodeck.com Alexander Engström Technical Director RLI Byggdata AB

More information

Principles of Ventilation and Air Conditioning Design & Installation

Principles of Ventilation and Air Conditioning Design & Installation Unit 10: Unit code Principles of Ventilation and Air Conditioning Design & Installation D/615/1926 Unit level 4 Credit value 15 Introduction The demands of modern living as well as the potential impact

More information

SUMMER THERMAL COMFORT IN TYPICAL FRENCH RESIDENTIAL BUILDINGS: IMPACT ASSESSMENT OF BUILDING ENVELOPE INSULATION ENHANCEMENT

SUMMER THERMAL COMFORT IN TYPICAL FRENCH RESIDENTIAL BUILDINGS: IMPACT ASSESSMENT OF BUILDING ENVELOPE INSULATION ENHANCEMENT 13th Conference of International Building Simulation Association, Chambéry, France, August 26-28 SUMMER THERMAL COMFORT IN TYPICAL FRENCH RESIDENTIAL BUILDINGS: IMPACT ASSESSMENT OF BUILDING ENVELOPE INSULATION

More information

The Renewable Heat Incentive

The Renewable Heat Incentive The Renewable Heat Incentive Heating RHI Expected Outcome Non-Domestic Ground Source Heat Pumps Air Source and Ground Source Heat Pumps Increased tariffs for Air and Ground Source RHI First Announcement

More information

Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France

Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France Sylvain Boulet 1, Stéphanie Armand-Decker 2, FCBA Technological Institute I2M-TREFLE laboratory -

More information

Improvement of Indoor Living Environment by Occupants Preferences for Heat Recovery Ventilators in High-Rise Residential Buildings

Improvement of Indoor Living Environment by Occupants Preferences for Heat Recovery Ventilators in High-Rise Residential Buildings Original Paper Indoor and Built Indoor Built Environ 212;21;4:486 52 Accepted: October 17, 211 Environment Improvement of Indoor Living Environment by Occupants Preferences for Heat Recovery Ventilators

More information

Theory versus practice of energy and comfort in 4 low energy houses in Belgium

Theory versus practice of energy and comfort in 4 low energy houses in Belgium Theory versus practice of energy and comfort in 4 low energy houses in Belgium Griet Verbeeck 1,*, Werner Carmans 1, Veerle Martens 1 1 PHL University College, Diepenbeek, Belgium * Tel: +32 11249207,

More information

DTS & ENERGY MODELLING PROTOCOL GUIDE Version 1.0

DTS & ENERGY MODELLING PROTOCOL GUIDE Version 1.0 DTS & ENERGY MODELLING PROTOCOL GUIDE Version 1.0 Green Star SA Multi Unit Residential v1 DTS & Energy Modelling Protocol Guide First Released: 27 th October 2011 Last Update: 27 th October 2011 Change

More information

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE S447 THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE by Bojan V. ANDJELKOVIĆ *,a, Branislav V. STOJANOVIĆ b, Mladen M. STOJILJKOVIĆ b, Jelena N. JANEVSKI

More information

Ventilation Solutions in Renovated Apartment Buildings in Cold Climate Conditions

Ventilation Solutions in Renovated Apartment Buildings in Cold Climate Conditions Engineering, 2015, 7, 129-139 Published Online March 2015 in SciRes. http://www.scirp.org/journal/eng http://dx.doi.org/10.4236/eng.2015.73011 Ventilation Solutions in Renovated Apartment Buildings in

More information

The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort

The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort Ongun Berk Kazanci, Bjarne W. Olesen 1 1 International Center for Indoor Environment and

More information

MODELLING THE ENERGY PERFORMANCE OF NIGHT-TIME VENTILATION USING THE QUASI-STEADY STATE CALCULATION METHOD

MODELLING THE ENERGY PERFORMANCE OF NIGHT-TIME VENTILATION USING THE QUASI-STEADY STATE CALCULATION METHOD MODELLING THE ENERGY PERFORMANCE OF NIGHT-TIME VENTILATION USING THE QUASI-STEADY STATE CALCULATION METHOD Jérôme Le Dréau, Per Heiselberg, Rasmus L. Jensen and Ayser D. Selman Department of Civil Engineering,

More information

SIMULATION MODEL IN TRNSYS OF A SOLAR HOUSE FROM BRAŞOV, ROMANIA

SIMULATION MODEL IN TRNSYS OF A SOLAR HOUSE FROM BRAŞOV, ROMANIA SIMULATION MODEL IN TRNSYS OF A SOLAR HOUSE FROM BRAŞOV, ROMANIA C. Şerban 1, E. Eftimie 1 and L. Coste 1 1 Department of Renewable Energy Systems and Recycling Transilvania University of Braşov B-dul

More information

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Available online at  ScienceDirect. Energy Procedia 78 (2015 ) Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 1093 1098 6th International Building Physics Conference, IBPC 2015 Verifying a need of artificial cooling - a simplified

More information

Less energy, more savings and comfort year-round

Less energy, more savings and comfort year-round COMPANION GUIDE: Air-Source Heat Pump Less energy, more savings and comfort year-round Designed for Electrically-Heated Homes 02 How do air-source heat pumps work? 03 What are the rebates? 04 Why it pays

More information

Varennes Net-Zero Library City of Varennes

Varennes Net-Zero Library City of Varennes Varennes Net-Zero Library City of Varennes 2016 Canadian Consulting Engineering Awards 2016 Canadian Consulting Engineering Awards Varennes Net-Zero Library 1 ii 2016 Canadian Consulting Engineering Awards

More information

PERFORMANCE EVALUATION OF PV VENTILATED GLAZING

PERFORMANCE EVALUATION OF PV VENTILATED GLAZING Eleventh International IBPSA Conference Glasgow, Scotland July 27-30, 2009 PERFORMANCE EVALUATION OF PV VENTILATED GLAZING Tin-tai Chow 1,*, Zhongzhu Qiu 2, and Chunying Li 1 1 Building Energy and Environmental

More information

Sustainable Chilled Beam Design

Sustainable Chilled Beam Design MAIJA VIRTA HARRI ITKONEN PANU MUSTAKALLIO MIKA RUPONEN RISTO KOSONEN 1 - Halton Oy ABSTRACT Chilled beam technology is seen as a very sustainable technology providing both excellent indoor conditions

More information

Green Star Shopping Centre Design PILOT Energy Calculator Guide

Green Star Shopping Centre Design PILOT Energy Calculator Guide Green Star Shopping Centre Design PILOT Energy Calculator Guide Prepared by: Advanced Environmental Green Building Council of Australia Page 1 of 29 EXECUTIVE SUMMARY The Green Star Shopping Centre Design

More information

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE Andjelković, V., B.et. al.: Thermal Mass Impact on Energy Performance of A Low, Medium and Heavy S507 THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE by Bojan

More information

EnergyPro Building Energy Analysis. Single-story School Building

EnergyPro Building Energy Analysis. Single-story School Building EnergyPro Building Energy Analysis Single-story School Building EnergyPro Building Energy Analysis for a single-story school bulding Project Scope The purpose of the EnergyPro energy model was to evaluate

More information

An Investigation of Energy Efficient and Sustainable Heating Systems for Buildings: Combining Photovoltaics with Heat Pump

An Investigation of Energy Efficient and Sustainable Heating Systems for Buildings: Combining Photovoltaics with Heat Pump Chapter 18 An Investigation of Energy Efficient and Sustainable Heating Systems for Buildings: Combining Photovoltaics with Heat Pump Arefeh Hesaraki and Sture Holmberg Division of Fluid and Climate Technology,

More information

ANNUAL ENERGY PERFORMANCE OF SOLAR THERMAL SYSTEMS IN BRAŞOV, ROMANIA

ANNUAL ENERGY PERFORMANCE OF SOLAR THERMAL SYSTEMS IN BRAŞOV, ROMANIA Bulletin of the Transilvania University of Braşov Series I: Engineering Sciences Vol. 5 (54) No. 2-212 ANNUAL ENERGY PERFORMANCE OF SOLAR THERMAL SYSTEMS IN BRAŞOV, ROMANIA C. ŞERBAN 1 E. EFTIMIE 1 Abstract:

More information

Chapter Six{ TC "Chapter Six" \l 1 } System Simulation

Chapter Six{ TC Chapter Six \l 1 } System Simulation Chapter Six{ TC "Chapter Six" \l 1 } System Simulation In the previous chapters models of the components of the cooling cycle and of the power plant were introduced. The TRNSYS model of the power plant

More information

Performance evaluation of an actual building airconditioning

Performance evaluation of an actual building airconditioning IOP Conference Series: Materials Science and Engineering OPEN ACCESS Performance evaluation of an actual building airconditioning system To cite this article: M F Othman et al 2013 IOP Conf. Ser.: Mater.

More information

Realization of Sustainable Energy by Smart Campus

Realization of Sustainable Energy by Smart Campus Energy Management Action Network (EMAK) Workshop 8 Energy Management Best Practice Realization of Sustainable Energy by Smart Campus 3rd February 2017 Masaaki Bannai Mie University Contents 1 Toward Smart

More information

ENERGY EFFICIENCY OF RESIDENTIAL BUILDINGS IN SERBIA

ENERGY EFFICIENCY OF RESIDENTIAL BUILDINGS IN SERBIA Šumarac, D. M., et.al.: Energy Efficiency of Residential Buildings in Serbia S97 ENERGY EFFICIENCY OF RESIDENTIAL BUILDINGS IN SERBIA by Dragoslav M. ŠUMARAC a, Maja N. TODOROVIĆ b, Maja D. DJUROVIĆ-PETROVIĆ

More information

Comparative Heating Performances of Ground Source and Air Source Heat. Pump Systems for Residential Buildings in Shanghai

Comparative Heating Performances of Ground Source and Air Source Heat. Pump Systems for Residential Buildings in Shanghai Comparative Heating Performances of Ground Source and Air Source Heat Pump Systems for Residential Buildings in Shanghai Zhaohui Liu 1,2, Hongwei Tan 1,2,3* 1 School of Mechanical Engineering, Tongji University,

More information

Student Modeling Competition

Student Modeling Competition Student Modeling Competition Design and Simulation of a Near-zero Energy Building Building Simulation 2013 Apoorv Goyal agoyal@gsd.harvard.edu Arta Yazdanseta ayazdans@gsd.harvard.edu Keojin Jin kjin@gsd.harvard.edu

More information

EVALUATION OF THE INDOOR AIR QUALITY IN A SINGLE FAMILY ACTIVE HOUSE

EVALUATION OF THE INDOOR AIR QUALITY IN A SINGLE FAMILY ACTIVE HOUSE Topic A8: IAQ and perceived indoor air quality EVALUATION OF THE INDOOR AIR QUALITY IN A SINGLE FAMILY ACTIVE HOUSE Christoffer PLESNER * and Karsten DUER VELUX A/S, Daylight Energy and Indoor climate,

More information

NUMERICAL STUDY ON THERMAL DEPLETION OF THE GROUND AROUND A GEOTHERMAL HEAT PUMP S PROBE

NUMERICAL STUDY ON THERMAL DEPLETION OF THE GROUND AROUND A GEOTHERMAL HEAT PUMP S PROBE U.P.B. Sci. Bull., Series C, Vol. 75, Iss. 3, 2013 ISSN 2286-3540 NUMERICAL STUDY ON THERMAL DEPLETION OF THE GROUND AROUND A GEOTHERMAL HEAT PUMP S PROBE Constantin IONESCU 1, Clément MONTANGE 2 Long

More information

ScienceDirect. Influence of the balcony glazing construction on thermal comfort of apartments in retrofitted large panel buildings

ScienceDirect. Influence of the balcony glazing construction on thermal comfort of apartments in retrofitted large panel buildings Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 108 (2015 ) 481 487 7th Scientific-Technical Conference Material Problems in Civil Engineering (MATBUD 2015) Influence of the

More information

ZEM ds : Case studies

ZEM ds : Case studies ZEMedS: Case studies Case study: Salamanque Group school, Montpellier, France The sole responsibility for the content of this publication lies with the authors. It does not necessarily reflect the opinion

More information

7S9X0 - Week 5 Uncertainties in building performance simulation

7S9X0 - Week 5 Uncertainties in building performance simulation 7S9X0 - Week 5 Uncertainties in building performance simulation Uncertainties Does any of you observe large variations in output due to unknown inputs in BESTEST case assignment? 7000 BESTEST CASE CASE-A

More information

EFFECTIVENESS OF ENERGY CONSERVATION MEASURES IN RESIDENTIAL SECTOR OF JAPANESE CITIES

EFFECTIVENESS OF ENERGY CONSERVATION MEASURES IN RESIDENTIAL SECTOR OF JAPANESE CITIES EFFECTIVENESS OF ENERGY CONSERVATION MEASURES IN RESIDENTIAL SECTOR OF JAPANESE CITIES Ayako TANIGUCHI 1, Yoshiyuki SHIMODA 1, Takahiro ASAHI 1, Yukio YAMAGUCHI 1, and Minoru MIZUNO 1 1 Division of Sustainable

More information

MODELLING THE IMPACTS OF NEW UK FUTURE WEATHER DATA ON A SCHOOL BUILDING

MODELLING THE IMPACTS OF NEW UK FUTURE WEATHER DATA ON A SCHOOL BUILDING MODELLING THE IMPACTS OF NEW UK FUTURE WEATHER DATA ON A SCHOOL BUILDING Hu Du, Jerry Edge, Chris Underwood School of Built and Natural Environment, Northumbria University, Newcastle upon Tyne, United

More information

CONSTRUCTION REQUIREMENTS

CONSTRUCTION REQUIREMENTS CONSTRUCTION REQUIREMENTS Note: The buildings on the UCCS campus are divided into two categories: General Fund and Auxiliaries. General Fund Buildings include academic and administrative functions. Auxiliary

More information

Performance Testing of Cold Climate Air Source Heat Pumps

Performance Testing of Cold Climate Air Source Heat Pumps Performance Testing of Cold Climate Air Source Heat Pumps Martin Kegel a*, Jeremy Sager b, Martin Thomas b, Daniel Giguere a, Roberto Sunye a a Natural Resources Canada, CanmetENERGY, 1615 Blvd Lionel

More information

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS Bjarne W. Olesen Ph. D, International Centre for Indoor Environment and Energy, Department of Mechanical Engineering, Technical

More information

Where,h(t)the indicial response of thermal flow rate, B 0 the

Where,h(t)the indicial response of thermal flow rate, B 0 the This paper presents the results of investigations that were made on a simulation program, which calculates the temperature, the heat loads, the ventilation rates and the indoor air quality considering

More information

7. Passivhus Norden Sustainable Cities and Buildings. Evaluation of energy performance and indoor climate in the passive house area Vallda Heberg

7. Passivhus Norden Sustainable Cities and Buildings. Evaluation of energy performance and indoor climate in the passive house area Vallda Heberg Copenhagen, 20-21 August 2015 7. Passivhus Norden Sustainable Cities and Buildings Brings practitioners and researchers together Evaluation of energy performance and indoor climate in the passive house

More information

ENERY COST AND CONSUMPTION IN A LARGE ACUTE HOSPITAL

ENERY COST AND CONSUMPTION IN A LARGE ACUTE HOSPITAL , Volume 5, Number 1, p.11-19, 24 ENERY COST AND CONSUMPTION IN A LARGE ACUTE HOSPITAL S.C. Hu, J.D. Chen and Y.K. Chuah Department of Air-Conditioning and Refrigeration Engineering, National Taipei University

More information

Building & Ductwork Airtightness Standards

Building & Ductwork Airtightness Standards Building & Ductwork Airtightness Standards Version 1.02, August 2013 Standard Reference Technical Body Title ICS (International Classification for Standards) Scope Door and Windows EN 12207:1999 Windows

More information

Passiv Haus Institut. Certification as "Quality Approved Passive House" Criteria for Non-Residential Passive House Buildings

Passiv Haus Institut. Certification as Quality Approved Passive House Criteria for Non-Residential Passive House Buildings Passiv Haus Institut Dr. Wolfgang Feist Rheinstr. 44/46 D-64283 Darmstadt www.passiv.de Certification as "Quality Approved Passive House" Criteria for Non-Residential Passive House Buildings Passive Houses

More information

EFFICIENCY OF HEAT PUMP SYSTEMS UNDER REAL OPERATING CONDITIONS

EFFICIENCY OF HEAT PUMP SYSTEMS UNDER REAL OPERATING CONDITIONS - 1 - EFFICIENCY OF HEAT PUMP SYSTEMS UNDER REAL OPERATING CONDITIONS M. Miara, Dipl.-Ing., Head of Team Heat Pumps, Fraunhofer-Institute for Solar Energy Systems ISE, Heidenhofstrasse 2, 79110 Freiburg,

More information

The Centre for Sustainable Building (ZUB) * A Case Study

The Centre for Sustainable Building (ZUB) * A Case Study The Centre for Sustainable Building (ZUB) * A Case Study Dietrich Schmidt Tekn. Lic. 1,2 1 KTH-The Royal Institute of Technology. Division of Building Technology. Brinellvägen 34. SE-100 44 Stockholm.

More information

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates Kittitach Pichatwatana, and Fan Wang Abstract This paper examines the TAS computer

More information

UC DAVIS WEST VILLAGE ENERGY INITIATIVE ANNUAL REPORT

UC DAVIS WEST VILLAGE ENERGY INITIATIVE ANNUAL REPORT UC DAVIS WEST VILLAGE ENERGY INITIATIVE ANNUAL REPORT 2013 2014 UC DAVIS WEST VILLAGE ENERGY INITIATIVE ANNUAL REPORT 2013 2014 EXECUTIVE SUMMARY UC Davis West Village (West Village) is a neighborhood

More information

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Research on indoor thermal environment of stilted buildings in Chongqing, China

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Research on indoor thermal environment of stilted buildings in Chongqing, China Healthy uildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0270 ISN: 978-83-7947-232-1 Research on indoor thermal environment of stilted buildings in Chongqing, China Ya nan Xu 1, Zhenjing Yang

More information

Changes to the Minnesota Commercial Energy Code. Presented by: Andy Thielen, PE

Changes to the Minnesota Commercial Energy Code. Presented by: Andy Thielen, PE Changes to the Minnesota Commercial Energy Code Presented by: Andy Thielen, PE Warning! The following is an outline of proposed code changes. There is no guarantee that the final code adopted by the State

More information

After refurbishment, heat recovery and demand control of the air flow were installed and the use of the systems were optimized.

After refurbishment, heat recovery and demand control of the air flow were installed and the use of the systems were optimized. Property name: Nordstan Nordstan Objekt 6 Property owner: Vasakronan AB Consultants: GICON Total Concept method Step 1. Creating the action package Building and its use Year built: 1968 Area: 48 600 m²

More information

FEDERATION TOWER MOSCOW DIFFERENT ROOM CLIMATES UNDER ONE ROOF

FEDERATION TOWER MOSCOW DIFFERENT ROOM CLIMATES UNDER ONE ROOF FEDERATION TOWER MOSCOW DIFFERENT ROOM CLIMATES UNDER ONE ROOF Oliver Baumann 1, and Claudius Reiser 1/2 1 Ebert & Baumann Consulting Engineers, Washington, D.C. 2 Ebert-Ingenieure GmbH &Co. KG, Munich,

More information

Module 15. Country Specific Legislation

Module 15. Country Specific Legislation Module 15 Country Specific Legislation Module 15 Country Specific Legislation On completion of this module learners will be able to: List the main pieces of legislation and standards which affect the energy

More information

ANALYSIS OF FACTORS CREATING VARIETY IN RESIDENTIAL ENERGY DEMAND BASED ON MEASURED ELECTRICITY CONSUMPTION

ANALYSIS OF FACTORS CREATING VARIETY IN RESIDENTIAL ENERGY DEMAND BASED ON MEASURED ELECTRICITY CONSUMPTION ~15 15~2 2~25 25~3 3~35 35~4 4~45 45~5 5~55 55~6 6~ Household ratio[%] Proceedings of BS215: 14th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 215.

More information

Experimental investigation of zero energy office under natural and forced ventilation

Experimental investigation of zero energy office under natural and forced ventilation Experimental investigation of zero energy office under natural and forced ventilation Hussain H. Al-Kayiem 1, Syed I. U. Gilani 1, * and Mahmoud S. Abdalfatah 2 1 Mech. Eng. Dept., Universiti Teknologi

More information

Proceedings of BS2013: 13th Conference of International Building Performance Simulation Association, Chambéry, France, August 26-28

Proceedings of BS2013: 13th Conference of International Building Performance Simulation Association, Chambéry, France, August 26-28 HVAC CONTROL SIMULATION STUDY FOR AUSTRALIAN OFFICE BUILDINGS Hongsen Zhang and Paul Bannister Exergy Australia Pty Ltd, Canberra, Australia hongsen@xgl.com.au; paul@xgl.com.au ABSTRACT This paper presents

More information

Complying with the Minimum Energy Efficiency Standards (MEES)

Complying with the Minimum Energy Efficiency Standards (MEES) Complying with the Minimum Energy Efficiency Standards (MEES) Advantages of using DSM software to calculate the EPC Rating Introduction The Minimum Energy Efficiency Standards (MEES) for commercially rented

More information

Renovation of a Detached Single-Family House into an Energy Efficient Low Energy House Larsen, Tine Steen; Maagaard, Steffen; Jensen, Rasmus Lund

Renovation of a Detached Single-Family House into an Energy Efficient Low Energy House Larsen, Tine Steen; Maagaard, Steffen; Jensen, Rasmus Lund Aalborg Universitet Renovation of a Detached Single-Family House into an Energy Efficient Low Energy House Larsen, Tine Steen; Maagaard, Steffen; Jensen, Rasmus Lund Published in: Proceedings of the 9th

More information

BUILDING DESIGN AND THERMAL INERTIA: WHEN, WHY, WHERE

BUILDING DESIGN AND THERMAL INERTIA: WHEN, WHY, WHERE Int. Journal for Housing Science, Vol.34, No.4 pp. 221-231, 2010 Published in the United States BUILDING DESIGN AND THERMAL INERTIA: WHEN, WHY, WHERE R. Albatici, S. Penasa Department of Civil and Environmental

More information

Thermal Performance of Retrofitted Envelopes with Internal Insulation: A Comparative Analysis

Thermal Performance of Retrofitted Envelopes with Internal Insulation: A Comparative Analysis PLEA2013-29th Conference, Sustainable Architecture for a Renewable Future, Munich, Germany 10-12 September 2013 Thermal Performance of Retrofitted Envelopes with Internal Insulation: A Comparative Analysis

More information

Passive Houses Worlswide: International Developments

Passive Houses Worlswide: International Developments Passive Houses Worlswide: International Developments Henk Kaan, ECN Energy Research Centre of the Netherlands, P.O. Box 1, 1755 ZG Petten, The Netherlands, Isolda Strom, DHV Building and Industry, P.O.

More information

AAON. Energy and Economics

AAON. Energy and Economics Energy and Economics AAON Analysis Program AAON Energy and Economics Analysis Program The AAON Energy and Economics Analysis Program (AAON EEAP) is a tool for AAON sales representatives, consulting engineers,

More information

How to Design Zero Emission Buildings

How to Design Zero Emission Buildings Federico Butera, Politecnico di Milano Energy end uses Europe 2004 (Source: Eurostat Yearbook 2006-2007) EU Targets: Reduction of greenhouse gas emissions by 20% and ensure 20% of renewable energy sources

More information

COMFORT DRIVEN ADAPTIVE WINDOW OPENING BEHAVIOR AND THE INFLUENCE OF BUILDING DESIGN

COMFORT DRIVEN ADAPTIVE WINDOW OPENING BEHAVIOR AND THE INFLUENCE OF BUILDING DESIGN COMFORT DRIVEN ADAPTIVE WINDOW OPENING BEHAVIOR AND THE INFLUENCE OF BUILDING DESIGN P. Tuohy 1, H.B. Rijal 2, M.A. Humphreys 2, J.F. Nicol 2, A. Samuel 1, J. Clarke 1 1 Energy Systems Research Unit, University

More information

Getting Started with Your First Project: Considering Rules

Getting Started with Your First Project: Considering Rules Getting Started with Your First Project: Considering Rules to Deploy So you re ready to start a pilot project with a new customer. You have identified what data is available and where it is and how you

More information

ARPAN JOHARI. Architect. 13/08/10 AW Design. Ahmedabad

ARPAN JOHARI. Architect. 13/08/10 AW Design. Ahmedabad ARPAN JOHARI. Architect THERMAL MASS Thermal mass (or thermal capacitance) is defined as the ability of a body to store heat THERMAL MASS Thermal mass is also known as Fabric Energy Storage, FES (The Concrete

More information

Passive house optimization for Southern Italy based on the New Passivhaus Standard

Passive house optimization for Southern Italy based on the New Passivhaus Standard Passive house optimization for Southern Italy based on the New Passivhaus Standard Paolo Zangheri end-use Effi ciency Research Group, Dipartimento di Energia Politecnico di Milano, Italy paolo.zangheri@polimi.it

More information

Dienstleistung. Certification as "Quality Approved Passive House" Criteria for Residential-Use Passive Houses

Dienstleistung. Certification as Quality Approved Passive House Criteria for Residential-Use Passive Houses Passiv Haus Institut Passivhaus Dienstleistung GmbH Dr. Wolfgang Feist Rheinstr. 44/46 Rheinstr. 44/46 D-64283 Darmstadt D-64283 Darmstadt www.passiv.de www.passivhaus-info.de Certification as "Quality

More information

THE ENERGY BEHAVIOUR OF THE RESIDENTIAL BUILDING STOCK IN CYPRUS IN VIEW OF THE ENERGY PERFORMANCE OF BUILDINGS DIRECTIVE IMPLEMENTATION

THE ENERGY BEHAVIOUR OF THE RESIDENTIAL BUILDING STOCK IN CYPRUS IN VIEW OF THE ENERGY PERFORMANCE OF BUILDINGS DIRECTIVE IMPLEMENTATION THE ENERGY BEHAVIOUR OF THE RESIDENTIAL BUILDING STOCK IN CYPRUS IN VIEW OF THE ENERGY PERFORMANCE OF BUILDINGS DIRECTIVE IMPLEMENTATION S.A Kalogirou, Cyprus University of Technology, Department of Mechanical

More information

Tomorrow s heating is based on solar power and electricity!

Tomorrow s heating is based on solar power and electricity! The Energy+ house Tomorrow s heating is based on solar power and electricity! An energy-neutral house with solar energy and electric heating is a complete solution for the future built with innovative,

More information

Retrofit of an historical building toward NZEB

Retrofit of an historical building toward NZEB Available online at www.sciencedirect.com ScienceDirect Energy Procedia 00 (2015) 000 000 www.elsevier.com/locate/procedia 6th International Building Physics Conference, IBPC 2015 Retrofit of an historical

More information

MODELLING AND SIMULATION OF BUILDING ENERGY SYSTEMS USING INTELLIGENT TECHNIQUES

MODELLING AND SIMULATION OF BUILDING ENERGY SYSTEMS USING INTELLIGENT TECHNIQUES MODELLING AND SIMULATION OF BUILDING ENERGY SYSTEMS USING INTELLIGENT TECHNIQUES Ph.D. THESIS by V. S. K. V. HARISH ALTERNATE HYDRO ENERGY CENTRE INDIAN INSTITUTE OF TECHNOLOGY ROORKEE ROORKEE-247667 (INDIA)

More information

Solar Energy Technologies

Solar Energy Technologies 1 Solar Energy Technologies ME 430 Queen s University The Solar Energy Resource Varies over day and year, (i.e., intermittent) Generally non-dispatchable Ottawa average for year ~4 kwh/m 2 per day e.g.,

More information

AIR QUALITY IN COW HOUSES WITH CURTAIN WALL VENTILATION IN FINNISH CLIMATE

AIR QUALITY IN COW HOUSES WITH CURTAIN WALL VENTILATION IN FINNISH CLIMATE ISAH-27 Tartu, Estonia 947 AIR QUALITY IN COW HOUSES WITH CURTAIN WALL VENTILATION IN FINNISH CLIMATE Kivinen, T. 1, Mattila, K.M. 2, Teye, F. 2, Heikkinen, J. 3 and Heimonen, I. 3 1 MTT Agrifood Research

More information

Great Ocean Rd Ice Creamery

Great Ocean Rd Ice Creamery Great Ocean Rd Ice Creamery BCA Section J - JV3 Compliance Report Revision: 01 Job No: 2171 Date: 7 July 2015 ADP Consulting Pty Ltd Level 10, 10 Queens Rd, Melbourne Vic 3004 www.adpconsulting.com.au

More information

Ventilating of old apartment buildings

Ventilating of old apartment buildings Ventilating of old apartment buildings Teet-Andrus Koiv 1, Alo Mikola 1 Department of Environmental Engineering 1 Tallinn University of Technology Ehitajate tee 5 Estonia teet.koiv@ttu.ee http://www.ttu.ee

More information

Available online at ScienceDirect. Energy Procedia 78 (2015 ) th International Building Physics Conference, IBPC 2015

Available online at  ScienceDirect. Energy Procedia 78 (2015 ) th International Building Physics Conference, IBPC 2015 Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 907 912 6th International Building Physics Conference, IBPC 2015 Potential for finance and energy savings of detached

More information

Paul Tuohy*, Sue Roaf, Fergus Nicol, Mike Humphreys and Atze Boerstra

Paul Tuohy*, Sue Roaf, Fergus Nicol, Mike Humphreys and Atze Boerstra 1 21 st Century Standards for Thermal Comfort: Fostering Low Carbon Building Design. Paul Tuohy*, Sue Roaf, Fergus Nicol, Mike Humphreys and Atze Boerstra *Energy Systems Research Unit, University of Strathclyde,

More information

Coppin State University Physical Education Complex - Technical Report 2

Coppin State University Physical Education Complex - Technical Report 2 Coppin State University Physical Education Complex - Technical Report 2 Building and Plant Energy Analysis Report Kaylee M Damico Advisor: Dr. Jelena Srebric Location: Baltimore, MD Table of Contents Contents

More information

MEP's Letter of Assurance

MEP's Letter of Assurance MEP's Letter of Assurance Instructions Multifamily Residential WELL Certification is determined by onsite Performance Verification and documentation, including Letters of Assurance from the appropriate

More information

Evaluation of Energy Savings of the New Chinese Commercial Building Energy Standard

Evaluation of Energy Savings of the New Chinese Commercial Building Energy Standard Evaluation of Energy Savings of the New Chinese Commercial Building Energy Standard Wei Feng, Ke Huang, Mark Levine and Nan Zhou, Lawrence Berkeley National Laboratory Shicong Zhang, Lawrence Berkeley

More information

ctbuh.org/papers The Evaluation of Performance for the Application of a Heat Recovery Ventilator to High-rise Apartments Title:

ctbuh.org/papers The Evaluation of Performance for the Application of a Heat Recovery Ventilator to High-rise Apartments Title: ctbuh.org/papers Title: Authors: Subject: Keywords: The Evaluation of Performance for the Application of a Heat Recovery Ventilator to High-rise Apartments Sang-Min Kim, Principal Research Engineer, Hyundai

More information

EER & SEER AS PREDICTORS OF SEASONAL COOLING PERFORMANCE

EER & SEER AS PREDICTORS OF SEASONAL COOLING PERFORMANCE EER & SEER AS PREDICTORS OF SEASONAL COOLING PERFORMANCE Developed by: Southern California Edison Design & Engineering Services 6042 N. Irwindale Avenue, Suite B Irwindale, California 91702 December 15,

More information

Available online at ScienceDirect. Energy Procedia 81 (2015 )

Available online at  ScienceDirect. Energy Procedia 81 (2015 ) Available online at www.sciencedirect.com ScienceDirect Energy Procedia 81 (215 ) 17 69th Conference of the Italian Thermal Engineering Association, ATI 214 Climate influence on seasonal performances of

More information

Propane Saving in Poultry Farm through Waste Heat Recovery System

Propane Saving in Poultry Farm through Waste Heat Recovery System Heat Equivilent (Gallon/day) Ambient Temperature, F Introduction Propane Saving in Poultry Farm through Waste Heat Recovery System Dr. Shawn Yunsheng Xu, Tingsheng Xu, and Dr. Robert Reed College of Engineering,

More information

DISTRIBUTION TRANSFORMER COOLING USING THE GEOTHERMAL ENERGY FROM THE UNDERGROUND ELECTRIC PIPELINES

DISTRIBUTION TRANSFORMER COOLING USING THE GEOTHERMAL ENERGY FROM THE UNDERGROUND ELECTRIC PIPELINES DISTRIBUTION TRANSFORMER COOLING USING THE GEOTHERMAL ENERGY FROM THE UNDERGROUND ELECTRIC PIPELINES Pedro Manuel del Rosal Cimadevilla Hidrocantábrico Distribución Eléctrica (EDP) Spain prosal@edpenergia.es

More information

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1 Air System Design Load Summary for Zona 3 Project Name: Av. Cabildo 3067, 4 piso 02/13/2011 DESIGN COOLING DESIGN HEATING COOLING DATA AT Feb 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 34.9 C / 23.8

More information

ACTIVA Rooftop. YKN2open. ARC-ARG-ARH-ARD A complete range from 48 kw up to 84 kw. Nomenclature A R C 045 B B. Features

ACTIVA Rooftop. YKN2open. ARC-ARG-ARH-ARD A complete range from 48 kw up to 84 kw. Nomenclature A R C 045 B B. Features ACTIVA Rooftop ARC-ARG-ARH-ARD A complete range from 48 kw up to 84 kw YKN2open Features High efficiency EER and COP Low noise level All configurations: Cooling only, Cooling + gas, Heating, Heating +

More information

Energy-saving Potential Study on Telecommunication Base Station Free Cooling With a Thermosyphon Heat Exchanger in China

Energy-saving Potential Study on Telecommunication Base Station Free Cooling With a Thermosyphon Heat Exchanger in China Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2012 Energy-saving Potential Study on Telecommunication Base Station Free Cooling With

More information

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1 Air System Design Load Summary for Zona 8 DESIGN COOLING DESIGN HEATING COOLING DATA AT Dec 1700 HEATING DATA AT DES HTG COOLING OA DB / WB 33.1 C / 23.5 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible Latent

More information

Building Concepts for a mid-century energy-neutral society

Building Concepts for a mid-century energy-neutral society ECN-M--6-15 SET26-5 th International Conference on Sustainable Energy Technologies. Vicenza, Italy Page 1 of 8 Building Concepts for a mid-century energy-neutral society I.J. Opstelten, E.J. Bakker, B.J.

More information