1 ctbuh.org/papers Title: Authors: Subject: Keywords: The Evaluation of Performance for the Application of a Heat Recovery Ventilator to High-rise Apartments Sang-Min Kim, Principal Research Engineer, Hyundai Engineering & onstruction Heung-Don Ham, Professor, Daewon Plus onstruction Jang-Yeul Sohn, Professor, Hanyang University MEP Energy Efficiency MEP Publication Date: 24 Original Publication: Paper Type: TBUH 24 Seoul onference 1. Book chapter/part chapter 2. Journal paper 3. onference proceeding 4. Unpublished conference paper 5. Magazine article 6. Unpublished ouncil on Tall Buildings and Urban Habitat / Sang-Min Kim; Heung-Don Ham; Jang-Yeul Sohn

2 The Evaluation of Performance for the Application of a Heat Recovery Ventilator to High-rise Apartments Sang-Min Kim 1, Heung-Don Ham 2, Jang-Yeul Sohn 3 1 Principal Research Engineer, Hyundai Institute of onstruction Technology 2 Professor, Dept. of Indoor Environment Design, Daewon Science ollege 3 Professor, Architectural Environmental Engineering Lab., Hanyang University Abstract The individual HVA system and HRV has been installed in Korean apartment, but not the central cooling, heating and ventilation system which is operating in the most of office buildings. According to the heat exchange effectiveness of HRV and the operating method of HRV, it is possible to not reducing the energy reasonable way in Korea, which has four distinctive seasons. In this study, the optimum schedule for operating an HRV system that would save the most energy and sustain a reasonable rate of air exchange during the summer and winter was investigated Laboratory and field efficiency tests and some simulations were conducted for determining the optimum operating conditions for the HRV. A reduction of 15% in heating energy during the winter test period and a 1% reduction in cooling energy in summer test period were achieved. The results of the L show that operating the HRV 24 hours a day is the most economical method. Keywords: HRV, Energy-saving, Heat-recovery, L, ross-contamination 1. Introduction In Korea, high-rise apartment buildings up to 7-stories high are being constructed. Over the years, the air tightness of the windows and building surfaces has improved, and now these buildings appear to be energy efficient. However, other factors, such as the rate of infiltration and leakage, affect energy efficiency. Though the air-tightness of the windows and the building surfaces has improved over the years, the rate of infiltration and leakage has been falling accordingly. The combination of improved air tightness and increased infiltration and leakage, will cause contamination of indoor air unless an air ventilation strategy is applied. One air ventilation strategy that is being currently installed in apartment buildings is the HRV (Heat Recovery Ventilator). The HRV can save energy and improve the indoor air quality. The HRV is installed at each household for the first time. The individual cooling, heating system and HRV has been installed in Korean apartment, but not the central HVA system which is operating in the most of office buildings. Korea has four distinct seasons. Summers are hot and humid and winters are cold and dry. ontact Author: Sang-Min Kim Principal Research Engineer Hyundai Institute of onstruction Technology 12-4 Mabukri, Goosungeup, Yonginsi, Kyunggido, , Korea Tel: Fax: smkim@hdec.co.kr Therefore, a system is needed that can operate efficiently in both extremes. Factors that can affect the efficiency of the system are the heat exchange of the material, the specific alternation rate of heat exchange due to external temperature, humidity and the method of operation. Operating HRV according to the Ventilation Air Requirements (ANSI/ASHRAE Standard ) could be reasonable condition to saving energy and improving indoor air quality. This investigation attempts to determine the optimum operating conditions for a HRV that save energy and supply reasonable out door air requirements with respect to the external air temperature and the humidity of Korea, but not full time of the year. 2. Methods 2.1 The efficiency test due to the regulation The fixed-plate type of HRV is the most commonly used system among the variety of HRV systems installed in high-rise apartment buildings in Korea. The following 2 methods have been used to laboratory test the HRV samples in this study: - BS EN 38 : Heat exchanger-test procedures for establishing the performance of air to air and flue gases heat recovery devices - AN/ : Standard Methods of Test for Rating the Performance of Heat-Recovery Ventilators The contents of the 2 regulatory methods governing TBUH 24 October 1~13, Seoul, Korea 63

3 performance tests are shown below. - Airflow Measurements - External / Internal Leakage Tests - Internal Exhaust Air Leakage Tests - Pressure Drop Tests - Temperature and Humidity Ratio Tests - ross Air Leakage Tests(Tracer Gas Tests) A simplification of real airflow in an HRV is shown in Fig.1. The net air volume has been calculated by the equation (1) ~ (6). The results of net air volume are adjusted in the efficiency calculation. OA q c c q h c : Net Supply Air h : Net Exhaust Air q c : Leakage mass flow rate from supply air to exhaust air q h : Leakage mass flow rate from exhaust air to supply air : Air mass flow rate at supply air EA : Air mass flow rate at exhaust air : SF 6 oncentration at supply air OA : SF 6 oncentration at outdoor air RA : SF 6 oncentration at return air Two models, a sensible heat exchanger and a total heat exchanger, were selected to test the application efficiency in the field. According to the laboratory test result, these HRVs have almost equal amount of airflow, pressure drop and below the 5% of cross air leakage rate. EA Fig. 1. Air Leakage in HRV h RA 2.2 The application efficiency test on the field 1) Field measurement summary The air volume measured in supply air is equal to the sum of RA-EA air-side leakage air( q h ) and the net supply air volume( c ). The equation of the result is shown Equation (1). Also, because the concertration of the SF6 in net supply air volume( OA ) and the SF6 concertration in the RA-EA air-side leakage air( RA ) is equal to the SF6 concertration in ( ), the equation can be shown as Equation (2). The Equation (3) and (4) could be made from simultaneous calculation of the Equation (1) and (2). Also the Equation (5) and (6) could be gained due to the simultaneous equation of air volume of EA and the SF6 concertration of EA. (a) A-Apartment + q = h (1) + q = OA RA h (2) = (3) RA OA RA q OA h = (4) RA OA EA OA h = EA (5) RA OA q EA RA c = EA (6) OA RA (b) B -Apartment Fig. 2. Floor plan of apartment and schematic of HRV 64 TBUH 24 October 1~13, Seoul, Korea

4 The test was conducted in each room in 2 high-rise apartment units, which have the typical HVA system. In each unit a package air-conditioner, hot water floor heating panel(ondol) and the HRV for ventilation have been installed. The floor plane of apartment is shown on Fig.2 and the area of each room and ventilation are shown in Table.1. The same identical HRVs as tested in the laboratory were installed to the each apartment. The total heat recovery ventilators were installed in the two units, the upper and lower floors (39th floor, 4th floor) in the apartment A, sharing the same architectural factors such as area and direction, etc. Heat exchanger performance was measured during the summer from June 6 to August 3, 23. A package air conditioner was used to control the indoor temperature which was maintained at 26. However, the humidity was not controlled. The sensible heat exchanger was installed in the 2 units, the upper and lower floors in the apartment B, sharing the same architectural factors such as area and direction, etc. The performance of the heat exchanger was measured during the winter from January 9 to February 28, 24). The hot water floor heating panel (Ondol) was used to control the indoor temperature, which was maintained at 2. Table 1. Area and air change rate(ah) in apartments Apartment Room Area(m 2 ) AH Room Room A Apartment B Bpartment Room Room Living Room Dining Room Etc Total Room Room Room Room Living Room Dining Room Etc Total However, the humidity wasn't controlled. In order to measure the energy saving efficiency of HRV, the tests were conducted under two different conditions. Under the first condition, the HRV was turned on for 24 hours in upper floor (ase 1). Under the second condition, the same amount of wind of OA was forced inside without passing through the HRV in lower floor (ase 2). The air exchange rate was maintained at.5 AH in both of ase 1 and ase 2. The temperature, the humidity, heating and cooling energy consumption, electric energy consumption of HRV fan, air volume and air exchange rate were measured to evaluate performance. 2.3 S/W Simulation The simulation was used to estimate the yearly energy consumption according to the operating schedule of HRV(Fig.3) under the condition of Korean climate. The simulation schedule cases are shown below. 1) Schedule A, B : The operating condition to maximize total heat exchange efficiency of HRV 2) Schedule, D : The operating condition to intake maximum outdoor air is necessary to eliminate pollutants generated from occupants and cooking activity. 3) Schedule E : The operating condition to intake the reasonable outdoor air for 24 hours without considering outdoor air temperature and humidity. 4) Schedule F, G : The operating condition of HRV turned on/off for 24 hours to compare the field measurement result heating and cooling energy consumption during the summer term(3 months) and winter term(2 months). Figure 3 shows the 7 HRV operating schedules. In the laboratory, the total heat exchanger efficiency performance was measured at about 5%, which was the same as determined by the simulation. 3. Results 3.1 Results of efficiency test in the test chamber 1) Airflow Measurements and Pressure Drop Tests The air volume of HRV and pressure drop were Fig. 3. HRV on/off schedule TBUH 24 October 1~13, Seoul, Korea 65

5 measured according to ASHRAE Standard (RA92). Table 2 shows the air volume of HRV and pressure drop in apartments A and B. Table 2. Airflow and Pressure Drop Tests Results OA RA EA A-HRV Airflow(l /s) (A-Apartment) Pressure Drop 15.3(15pa) 15.7(154pa) B-HRV Airflow(l /s) (B-Apartment) Pressure Drop 16(157pa) 16.6(162.8pa) 2) External / Internal Leakage Tests External/internal leakage was measured in 5pa increments from to 25pa using a pressure chamber. External leakage was measured as 4.6%, 3% in ± 25pa of the mass flow rate. The results from apartment A are shown in figure 4. Leakage Airflow[l/s] Pressure [Pa] Fig. 4. Result of external leakage tests(a-apartment) 3) ross Air Leakage Tests and net air volume ross air leakage was measured between the OA- and the RA-EA. A tracer gas test was conducted in OA,, RA, EA air-side, using SF6 gas. The net air volume was calculated using equations (1) (6) and the results of measurement are shown in table 3. Table 3. Air leakage and net air volume Airflow(l /s) % of Air leakage Heat tranfer type H q q h OA-(q h ) RA-EA(q c ) A-HRV (Total HRV) B-HRV (Sensible HRV) 4) Temperature and Humidity Ratio Test In order to measure the heat exchange efficiency, the temperatures at the exhaust air inlet and the supply air inlet were set at 25 of and 5, respectively. The electric pre-heater was turned off during the measurement despite the low temperature. The efficiency of total heat exchange of the 2 HRVs were about 5%, and cross air leakage was calibrated. The detailed information is shown in table 4. Table 4. Results of HRV Performance A-HRV A apartment B-HRV B apartment Static pressure(mmaq) 8.8(86pa) 9.6(94pa) Heat tranfer type Total heat Sensible heat exchanger exchanger Airflow(l /s) Operating mode High/Middle/Low High/Middle/Low Electric energy(w) 198(High mode) 21(High mode) Points of supply diffuser 5points 6points Points of return air diffuser 3points 3points ondition High temperature room 25 / Low temperature room 5 Sensible heat effectiveness Total heat effectiveness Results of field measurement and simulation A comparison of the results of case 1 (HRV turned on for 24 hours) and case 2 (HRV turned off for 24 hours) were analyzed for both apartments A and B. Figure 5 shows the temperature, humidity and heating energy consumption patterns of case 1 and case 2 on a certain day of winter in apartment B. Figure 6 shows the temperature, humidity and cooling energy consumption patterns of case 1 and case 2 on a certain day of summer in apartment A. The total heat exchange efficiency was reasonable during the hours of 12 and 15, heating energy consumption was 15% lower than case 2. The temperature, humidity and heating energy consumption patterns were measured and analyzed for summer of apartment A. The total heat exchange efficiency was less than the winter term. The cooling energy consumption was 1% lower in case 1 than case 2. Figure 7 and table 5 show the measurement result of monthly energy consumption in both cases 1 and 2. According to the field measurements, about 15% of heating energy is saved in the winter and about 1% of the cooling energy is saved in winter term. Figure 8 and table 6 show the comparison of results of the field measurements and the simulation. The monthly energy consumption pattern is similar in both case 1 and case 2, despite the 12% error resulting from the comparison of the field measurements and simulation. The error between the results of field measurements and the simulation may appear from difference of weather condition during term of measurement and weather data of simulation program. 66 TBUH 24 October 1~13, Seoul, Korea

6 Table 5. The monthly energy consumption of ase1, 2 Operating B-Apartment A-Apartment ondition Jan Feb Jun Jul Aug 24h HRV on (ase1) h HRV off (ase2) ase1/asex1(%) RA Temp.( ) Total Eff.(%) HRV off(kwh) OA Temp.( ) HRV on(kwh) OA R.H.(%) Energy onsum. [kwh] Meas. 24H HRV on Simul. 24h HRV on Meas. 24H HRV off Simul. 24h HRV off Hour Fig. 5. The real measured results in certain day of winter term (B-Apartment) OA Temp.( ) HRV off( 1kwh) OA R.H.(%) HRV on( 1kwh) Total Eff.(%) RA Temp.( ) Hour Fig. 6. The real measured results in certain day of summer term(a-apartment) Fig. 8. The monthly energy consumption of measurement and simulation Table 6. omparison of monthly energy consumption between field measurement and S/W Simulation Analysis Method Operating B-Apartment A-Apartment ondition Jan Feb Jun Jul Aug 24h HRV on Field Measurement 24h HRV off S/W 24h HRV on Simulation 24h HRV off According to the HRV operating schedule under Korean weather conditions, 7 operating schedules were simulated to estimate yearly energy consumption. (Fig. 2) The amount of energy savings can be shown as F-D-B-E--A-G from the top to bottom. Similar result appears in apartment A, B, total heat exchanger and sensible heat exchanger. onsidering yearly energy consumption of apartments A, B in schedule G (HRV turned off 24 hours) and F, the schedule F could reduce energy consumption by 17% in apartment A and 14% in apartment B. 16 Jan Feb Jun Jul Aug Heating ooling Total 14 Energy onsum. [kwh] h HRV on 24h HRV off Energy consum. [kwh] Jan Feb Jun Jul Aug Schedule A Schedule B Schedule Schedule D Schedule E Schedule F Schedule G Schedule A Schedule B Schedule Schedule D Schedule E Schedule F Schedule G B-Apartment A-Apartment A-Apartment B-Apartment Fig. 7. The monthly energy consumption of ase1, ase2 Fig. 9. The yearly heating and cooling energy consumption TBUH 24 October 1~13, Seoul, Korea 67

7 3.3 Life ycle ost Analysis The L 2 results of comparison operating schedule G with other schedule in apartment A is shown in table 8. Here, the L 2 was calculated on the basis of initial cost, heating and cooling energy cost, management cost, inflation index 5%, energy cost ascent rate 2.5%. The L 2 can be shown as -A-E-B-D-F from top to bottom. The L analysis result was directly proportioned to operating time. However, HRV could be economical by assuming that HRV effectiveness improves and the energy price shoots up. Table. 8 L result of apartment A Operating schedule L 2 ($) Simple Payback Year(yr) Schedule A 23,781 7 Schedule B 23,46 4 Schedule 23,95 8 Schedule D 23,52 3 Schedule E 23,66 5 Schedule F 22,493 3 Schedule G 24,19-4. onclusions In order to identify the optimal operation schedule, we performed efficiency tests and field measurements of HRV. The results are shown below. 1) The factors we measured were airflow, external/internal leakage, internal exhaust air leakage, pressure drop, temperature and humidity ratio, cross air leakage. 2) The effectiveness of a total heat exchanger and sensible heat exchanger applied to 2 households was measured. Total heat exchange effectiveness has a maximum value when the outdoor temperature is high during the winter season, and at 4 p.m. during the summer. 3) The energy analysis results suggested the optimum operating schedule, which effectively saves energy consumption under Korean weather conditions, considering the effectiveness of HRV and occupants living pattern. Schedule F(HRV turned on for 24 hours) could reduce cooling energy consumption. 4) The result of L analysis including electricity consumption of fan in HRV appears that 24 hour operation of HRV such as schedule F is the most economic in Korea weather condition. References 1) ASHRAE Ventilation for Acceptable Indoor Air uality, ANSI/ASHRAE Standard , pp ).G. Barringer, P.E Effect of Residential Air-to-Air Heat and Moisture Exchangers on Indoor Humidity, ASHRAE Transactions 1989 PART 1, pp ) Hoagland, L Moisture transfer characteristics of heat recovery ventilation systems employing rotary materials-winter and summer conditions, Draft of paper presented at BTE onference on Air infiltration. 4) R.. Alexander, P.E omparison of Performance Indices for Heat-Recovery Ventilators. ASHRAE Transactions 1992 PART 2, pp ) W.J. Fisk, P.E Formaldehyde and Tracer Gas Transfer between Airstreams in Enthalpy-Type Air-to-Air Heat Exchangers, ASHRAE Transactions 1985 PART 1, pp ) Y.J. Huang DOE-2.1D Data Base of Building Loads for Prototypical Multifamily Buildings in the U.S,. ASHRAE Transactions 1989 PART 2, pp TBUH 24 October 1~13, Seoul, Korea

E/V Shaft Cooling Method as a Stack Effect Countermeasure in Tall Buildings

E/V Shaft Cooling Method as a Stack Effect Countermeasure in Tall Buildings ctbuh.org/papers Title: Authors: Subject: Keywords: E/V Shaft Cooling Method as a Stack Effect Countermeasure in Tall Buildings Joonghoon Lee, Samsung C&T Corporation Doosam Song, Sungkyunkwan University

More information

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1 Air System Design Load Summary for Zona 3 Project Name: Av. Cabildo 3067, 4 piso 02/13/2011 DESIGN COOLING DESIGN HEATING COOLING DATA AT Feb 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 34.9 C / 23.8

More information

A Study on the Operational Status of the Chamber for Testing the Thermal Performance of Curtain Walls

A Study on the Operational Status of the Chamber for Testing the Thermal Performance of Curtain Walls ctbuh.org/papers Title: Author: Subject: Keywords: A Study on the Operational Status of the Chamber for Testing the Thermal Performance of Curtain Walls Sang Tae No, Korea National University of Transportation

More information

Whole Building Energy Performance Evaluation through. Similar Control Strategies

Whole Building Energy Performance Evaluation through. Similar Control Strategies Whole Building Energy Performance Evaluation through Similar Control Strategies S.H. Cheon 1, Y.H. Kwak 1, C.Y. Jang 2, and J.H. Huh 1* 1 Department of Architectural Engineering, University of Seoul, Seoul

More information

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1 Air System Design Load Summary for Zona 8 DESIGN COOLING DESIGN HEATING COOLING DATA AT Dec 1700 HEATING DATA AT DES HTG COOLING OA DB / WB 33.1 C / 23.5 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible Latent

More information

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1 Air System Design Load Summary for Zona 11 DESIGN COOLING DESIGN HEATING COOLING DATA AT Dec 1700 HEATING DATA AT DES HTG COOLING OA DB / WB 33.1 C / 23.5 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible

More information

AIRFLOW PATTERNS AND STACK PRESSURE SIMULATION IN A HIGH RISE RESIDENTIAL BUILDING LOCATED IN SEOUL

AIRFLOW PATTERNS AND STACK PRESSURE SIMULATION IN A HIGH RISE RESIDENTIAL BUILDING LOCATED IN SEOUL 92 AIRFLOW PATTERNS AND STACK PRESSURE SIMULATION IN A HIGH RISE RESIDENTIAL BUILDING LOCATED IN SEOUL Khoukhi Maatouk Abstract Buoyancy forces due to air density difference between outdoor air and indoor

More information

ENERGY EFFICIENT RETROFIT OF A HIGH-RISE MULTIFAMILY BUILDING

ENERGY EFFICIENT RETROFIT OF A HIGH-RISE MULTIFAMILY BUILDING ENERGY EFFICIENT RETROFIT OF A HIGH-RISE MULTIFAMILY BUILDING Brittany Hanam 1, Lorne Ricketts 2, Andrew Pape-Salmon 3 ABSTRACT The National Institute of Building Sciences estimates that over 70% of the

More information

THE OPTIMAL INSULATION DETAIL OF THE THERMAL BRIDGE ADJACENT TO HOT WATER PIPES IN APARTMENT BUILDING SLABS. Seung Yeong Song & Kwang Woo Kim

THE OPTIMAL INSULATION DETAIL OF THE THERMAL BRIDGE ADJACENT TO HOT WATER PIPES IN APARTMENT BUILDING SLABS. Seung Yeong Song & Kwang Woo Kim THE OPTIMAL INSULATION DETAIL OF THE THERMAL BRIDGE ADJACENT TO HOT WATER PIPES IN APARTMENT BUILDING SLABS Seung Yeong Song & Kwang Woo Kim Department of Architecture, Seoul National University, San 56-1,

More information

I S O. Eco-Smart Energy Recovery Ventilator

I S O. Eco-Smart Energy Recovery Ventilator I S O I S O 9 0 0 1 1 4 0 0 1 Eco-Smart Energy Recovery Ventilator What s Eco-Smart? Holtop has manufactured heat and energy recovery ventilation products for over 12 years. We pay high attentions on the

More information

CONDENSING TEMPERATURE CONTROL THROUGH ENERGY MANAGEMENT SYSTEM SIMULATON FOR A LARGE OFFICE BUILDING

CONDENSING TEMPERATURE CONTROL THROUGH ENERGY MANAGEMENT SYSTEM SIMULATON FOR A LARGE OFFICE BUILDING CONDENSING TEMPERATURE CONTROL THROUGH ENERGY MANAGEMENT SYSTEM SIMULATON FOR A LARGE OFFICE BUILDING Young-Hoon Kwak 1, Dong-Seok Kong 1, Se-Hwan Cheon 1, Ro-Yeul Kwak 2, and Jung-Ho Huh 3 1 Department

More information

Great Ocean Rd Ice Creamery

Great Ocean Rd Ice Creamery Great Ocean Rd Ice Creamery BCA Section J - JV3 Compliance Report Revision: 01 Job No: 2171 Date: 7 July 2015 ADP Consulting Pty Ltd Level 10, 10 Queens Rd, Melbourne Vic 3004 www.adpconsulting.com.au

More information

Where,h(t)the indicial response of thermal flow rate, B 0 the

Where,h(t)the indicial response of thermal flow rate, B 0 the This paper presents the results of investigations that were made on a simulation program, which calculates the temperature, the heat loads, the ventilation rates and the indoor air quality considering

More information

Performance-Risk Methodology for the Design of High-Performance Affordable Homes

Performance-Risk Methodology for the Design of High-Performance Affordable Homes April 3 rd, 2012 1 Performance-Risk Methodology for the Design of High-Performance Affordable Homes Building Enclosure Science & Technology Conference BEST3, Atlanta Rodrigo Mora, British Columbia Institute

More information

Coppin State University Physical Education Complex - Technical Report 2

Coppin State University Physical Education Complex - Technical Report 2 Coppin State University Physical Education Complex - Technical Report 2 Building and Plant Energy Analysis Report Kaylee M Damico Advisor: Dr. Jelena Srebric Location: Baltimore, MD Table of Contents Contents

More information

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION 3.1 Purpose of Thermal Load Estimation 3.2 Heating Load versus Cooling Load 3.3 Critical Conditions for Design 3.4 Manual versus Computer Calculations 3.5 Heating

More information

Optimization of air tightness and night ventilation for Passive houses in Italian climates under Fanger and Adaptive comfort models

Optimization of air tightness and night ventilation for Passive houses in Italian climates under Fanger and Adaptive comfort models L. Pagliano et al, I: Optimization of air tightness and night ventilation for Passive houses in Italian climates... 1 Optimization of air tightness and night ventilation for Passive houses in Italian climates

More information

Application of a cooling tower model for optimizing energy use

Application of a cooling tower model for optimizing energy use Advances in Fluid Mechanics X 305 Application of a cooling tower model for optimizing energy use G. C. O Mary & D. F. Dyer Department of Mechanical Engineering, Auburn University, USA Abstract The overall

More information

YORK UNITIZED ENERGY RECOVERY VENTILATOR (ERV) Superior air-flow 300 6,200 CFM

YORK UNITIZED ENERGY RECOVERY VENTILATOR (ERV) Superior air-flow 300 6,200 CFM YORK UNITIZED ENERGY RECOVERY VENTILATOR (ERV) Superior air-flow 300 6,200 CFM YORK UNITIZED ENERGY RECOVERY VENTILATORS Regardless of building type or rating system, today s building must be as energy

More information

ANNUAL ENERGY PERFORMANCE OF SOLAR THERMAL SYSTEMS IN BRAŞOV, ROMANIA

ANNUAL ENERGY PERFORMANCE OF SOLAR THERMAL SYSTEMS IN BRAŞOV, ROMANIA Bulletin of the Transilvania University of Braşov Series I: Engineering Sciences Vol. 5 (54) No. 2-212 ANNUAL ENERGY PERFORMANCE OF SOLAR THERMAL SYSTEMS IN BRAŞOV, ROMANIA C. ŞERBAN 1 E. EFTIMIE 1 Abstract:

More information

Energy Recovery Ventilation Equipment

Energy Recovery Ventilation Equipment ANSI/AHRI Standard 1060 (I-P) 2014 Standard for Performance Rating of Airto-Air Exchangers for Energy Recovery Ventilation Equipment Approved by ANSI on May 15, 2015 IMPORTANT SAFETY DISCLAIMER AHRI does

More information

UC Berkeley Indoor Environmental Quality (IEQ)

UC Berkeley Indoor Environmental Quality (IEQ) UC Berkeley Indoor Environmental Quality (IEQ) Title Energy savings from extended air temperature setpoints and reductions in room air mixing Permalink https://escholarship.org/uc/item/28x9d7xj Authors

More information

Implementing Demand Controlled Ventilation to Meet ASHRAE Standard By KlasC. Haglid, P.E., R.A., CEM

Implementing Demand Controlled Ventilation to Meet ASHRAE Standard By KlasC. Haglid, P.E., R.A., CEM Implementing Demand Controlled Ventilation to Meet ASHRAE Standard 62.1-2010 By KlasC. Haglid, P.E., R.A., CEM 1 Klas C. Haglid, P.E., R.A., CEM - Bio ASHRAE Distinguished Service Award 2011 ASHRAE Handbook,

More information

Urban Greening and the UHI: Seasonal Trade-offs in Heating and Cooling Energy Consumption in Manchester, UK

Urban Greening and the UHI: Seasonal Trade-offs in Heating and Cooling Energy Consumption in Manchester, UK Urban Greening and the UHI: Seasonal Trade-offs in Heating and Cooling Energy Consumption in Manchester, UK T H E R E S E A R C H E R S C y n t h i a S k e l h o r n PhD Physical Geography Post-Doctoral

More information

CEN/TC 89 - Thermal performance of buildings and building components

CEN/TC 89 - Thermal performance of buildings and building components CEN/TC 89 - Thermal performance of buildings and building components Standard reference EN 1934:1998 EN 1946-1:1999 EN 1946-2:1999 EN 1946-3:1999 EN 1946-4:2000 EN 1946-5:2000 6946:2007 7345:1995 8497:1996

More information

HEATING LOAD PREDICTIONS USING THE STATIC NEURAL NETWORKS METHOD. S.Sholahudin 1, Hwataik Han 2*

HEATING LOAD PREDICTIONS USING THE STATIC NEURAL NETWORKS METHOD. S.Sholahudin 1, Hwataik Han 2* International Journal of Technology (2015) 6: 946-953 ISSN 2086-9614 IJTech 2015 HEATING LOAD PREDICTIONS USING THE STATIC NEURAL NETWORKS METHOD S.Sholahudin 1, Hwataik Han 2* 1 Graduate School of Mechanical

More information

ctbuh.org/papers Optimal Combination between Concrete Strength and Sets of Forms in High-rise Building Title:

ctbuh.org/papers Optimal Combination between Concrete Strength and Sets of Forms in High-rise Building Title: ctbuh.org/papers Title: Authors: Subjects: Keywords: Optimal Combination between Concrete Strength and Sets of Forms in High-rise Building Sung-Hoon An, Ph. D Candidate, Korea University Kyung-In Kang,

More information

HEAT RECUPERATION IN VENTILATION SYSTEM OF BASEMENT LABORATORY

HEAT RECUPERATION IN VENTILATION SYSTEM OF BASEMENT LABORATORY HEAT RECUPERATION IN VENTILATION SYSTEM OF BASEMENT LABORATORY Alena Krofova, Pavel Kic Czech University of Life Sciences Prague krofovaa@tf.czu.cz, kic@tf.czu.cz Abstract. Basement spaces in many university

More information

Theory versus practice of energy and comfort in 4 low energy houses in Belgium

Theory versus practice of energy and comfort in 4 low energy houses in Belgium Theory versus practice of energy and comfort in 4 low energy houses in Belgium Griet Verbeeck 1,*, Werner Carmans 1, Veerle Martens 1 1 PHL University College, Diepenbeek, Belgium * Tel: +32 11249207,

More information

STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS

STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS 1. ABSTRACT In modern architecture the buildings are often designed with large glass facades or windows. Due to these

More information

Update to ASHRAE Ventilation Standards. William P. Bahnfleth, PhD, PE, FASHRAE, FASME The Pennsylvania State University University Park, PA, USA

Update to ASHRAE Ventilation Standards. William P. Bahnfleth, PhD, PE, FASHRAE, FASME The Pennsylvania State University University Park, PA, USA Update to ASHRAE Ventilation Standards William P. Bahnfleth, PhD, PE, FASHRAE, FASME The Pennsylvania State University University Park, PA, USA REHVA Annual Conference Riga, Latvia May 8 9, 2015 Acknowledgements

More information

Ground-Coupled Heat Pump And Energy Storage

Ground-Coupled Heat Pump And Energy Storage Ground-Coupled Heat Pump And Energy Storage By Ed Lohrenz, Member ASHRAE; and Sergio Almeida, P.Eng., Member ASHRAE Ground-coupled heat pump (GCHP) systems consume less purchased energy than an HVAC system

More information

IDENTIFICATION OF VENTILATION PROBLEMS IN AN UNDERGROUND BUS TERMINAL IN KOREA

IDENTIFICATION OF VENTILATION PROBLEMS IN AN UNDERGROUND BUS TERMINAL IN KOREA IDENTIFICATION OF VENTILATION PROBLEMS IN AN UNDERGROUND BUS TERMINAL IN KOREA H Han 1* and Y-I Kwon 2 1 Dept. Of Mechanical Engineering, Kookmin University, Korea 2 Dept. Of Building Mechanical Engineering,

More information

THERMAL STORAGE FEASIBILITY STUDY

THERMAL STORAGE FEASIBILITY STUDY THERMAL STORAGE FEASIBILITY STUDY SPRING 2005 NEW HOUSE RESIDENCE HALL PRESENTATION OUTLINE GENERAL PROJECT DATA PROJECT TEAM MECHANICAL REDESIGN ELECTRICAL ANALYSIS ACOUSTICAL ANALYSIS CONCLUSIONS GENERAL

More information

External Environment and Indoor Microclimate

External Environment and Indoor Microclimate External Environment and Indoor Microclimate Michal Kabrhel 1, Hana Dolezilkova 1 1 Department of Microenvironmental and Building Services Engineering, Faculty of Civil Engineering, Czech Technical University

More information

Energy-Efficient Passive House using thermal mass to achieve high thermal comfort

Energy-Efficient Passive House using thermal mass to achieve high thermal comfort Energy-Efficient Passive House using thermal mass to achieve high thermal comfort Loa Andersson Managing Director RLI Byggdata AB rli@termodeck.com Alexander Engström Technical Director RLI Byggdata AB

More information

Ceiling Radiant Cooling Panels

Ceiling Radiant Cooling Panels 2006, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc (wwwashraeorg) Published in ASHE Journal Vol 48, Oct 2006 For personal use only Additional reproduction, distribution,

More information

AVOIDING 2015 MINNESOTA ENERGY CODE VIOLATIONS

AVOIDING 2015 MINNESOTA ENERGY CODE VIOLATIONS AVOIDING 2015 MINNESOTA ENERGY CODE VIOLATIONS Commercial Energy Codes Support Program Pilot Russ Landry, PE, LEED AP Megan Hoye, LEED AP Pilot Program Support This project is supported by a grant from

More information

Energy Modeling of Dedicated Outdoor Air Systems for a Small Commercial Pilot Project

Energy Modeling of Dedicated Outdoor Air Systems for a Small Commercial Pilot Project Energy Modeling of Dedicated Outdoor Air Systems for a Small Commercial Pilot Project BUILDING ENERGY SIMULATION FORUM, AUGUST 17, 2016 AMY MONTGOMERY, MASc, P.Eng. Overview Pilot project: energy efficient

More information

Analysis 2: Alternative Thermal Window Design

Analysis 2: Alternative Thermal Window Design Analysis 2: Alternative Thermal Window Design (8.1) Problem Statement: In the first analysis, the cost and environmental impacts of the addition of solar PV panels to the roof of GrandView was determined.

More information

Corridor Pressurization System Performance in Multi-Unit Residential Buildings

Corridor Pressurization System Performance in Multi-Unit Residential Buildings Corridor Pressurization System Performance in Multi-Unit Residential Buildings Lorne Ricketts Student Member ASHRAE John Straube, PhD, P.Eng. Associate Member ASHRAE ABSTRACT Corridor pressurization based

More information

ASHRAE 62.2: What s New in 2016

ASHRAE 62.2: What s New in 2016 ASHRAE 62.2: What s New in 2016 Rick Karg 2016 Residential Energy Dynamics, LLC What We Will Talk About Overview of mechanics of 62.2-2016. Logic behind the Standard. Sizing local ventilation (exhaust-only).

More information

Passive House in Canada: Case Studies on a Near EnerPHit Retrofit and Post-Occupancy Research

Passive House in Canada: Case Studies on a Near EnerPHit Retrofit and Post-Occupancy Research Passive House in Canada: Case Studies on a Near EnerPHit Retrofit and Post-Occupancy Research Brittany Coughlin, RDH Building Science Inc. 224 W 8 th Ave, Vancouver, BC Canada Phone: +011 604 873 1181;

More information

Integrated Hygrothermal Analysis of Ecological Buildings

Integrated Hygrothermal Analysis of Ecological Buildings Integrated Hygrothermal Analysis of Ecological Buildings C. Rode M. Salonvaara & T. Ojanen C. Simonson K. Grau ABSTRACT: Ecological buildings typically are made with a lot of organic materials, e.g. for

More information

Moisture and temperature conditions in cold lofts and risk of mould growth

Moisture and temperature conditions in cold lofts and risk of mould growth Moisture and temperature conditions in cold lofts and risk of mould growth Sivert Uvsløkk, M. Sc. Norges byggforskningsinstitutt; sivert.uvslokk@byggforsk.no http://www.byggforsk.no/ KEYWORDS: roof, loft,

More information

EVALUATION OF THE SOLAR INCOME FOR BRAŞOV URBAN AREA

EVALUATION OF THE SOLAR INCOME FOR BRAŞOV URBAN AREA Bulletin of the Transilvania University of Braşov Vol. (5) - Series I: Engineering Sciences EVALUATION OF THE SOLAR INCOME FOR BRAŞOV URBAN AREA C. ŞERBAN E. EFTIMIE Abstract: Energy is an essential factor

More information

WEST VIRGINIA UNIVERSITY ALUMNI CENTER Morgantown, West Virginia

WEST VIRGINIA UNIVERSITY ALUMNI CENTER Morgantown, West Virginia TECHNICAL REPORT I ASHRAE STANDARDS 62.1 AND 90.1 COMPLIANCE EVALUATION 8/29/08 WEST VIRGINIA UNIVERSITY ALUMNI CENTER Morgantown, West Virginia GREGORY SMITHMYER PENN STATE UNIVERSITY ARCHITECTURAL ENGINEERING

More information

THERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING. Gang Wang, Yafeng Hu, and Songtao Hu

THERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING. Gang Wang, Yafeng Hu, and Songtao Hu THERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING Gang Wang, Yafeng Hu, and Songtao Hu School of Environmental & Municipal Engineering, Qingdao Technological University, Qingdao

More information

Low Cost Building Automation System for Small- and Medium- Sized Commercial Buildings

Low Cost Building Automation System for Small- and Medium- Sized Commercial Buildings Low Cost Building Automation System for Small- and Medium- Sized Commercial Buildings Srinivas Katipamula, Ph.D. Staff Scientist, Pacific Northwest National Laboratory Other TAG Members: Irfan Rehmanji

More information

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS Bjarne W. Olesen Ph. D, International Centre for Indoor Environment and Energy, Department of Mechanical Engineering, Technical

More information

The Mirenda Center for Sports, Spirituality, and Character Development

The Mirenda Center for Sports, Spirituality, and Character Development prepared by: Zachary Heilman MECHANICAL OPTION prepared for: James Freihaut, PhD Technical Report 3: (Mechanical Systems Existing Conditions Evaluation) Due Date: November 29, 2010 The Mirenda Center for

More information

THERMAL CHARACTERISTICS AND ENERGY CONSERVATION MEASURES IN AN INDOOR SPEED-SKATING ARENA

THERMAL CHARACTERISTICS AND ENERGY CONSERVATION MEASURES IN AN INDOOR SPEED-SKATING ARENA Proceedings of Building Simulation 2: THERMAL CHARACTERISTICS AND ENERGY CONSERVATION MEASURES IN AN INDOOR SPEED-SKATING ARENA Junta Matsuo, Tatsuo Nagai, Akio Sagae 2, Michihiko Nakamura, Shotaro Shimizu,

More information

Core Building Advances: Introduction to Sustainable Building & Building Science

Core Building Advances: Introduction to Sustainable Building & Building Science Core Building Advances: Introduction to Sustainable Building & Building Science Rob Howard & Mike Mongeon Habitat for Humanity International rhoward@habitat.org mmongeon@habitat.org Introductions Name

More information

SURVEY ON INDOOR AIR QUALITY IN CONTEMPORARY RESIDENTIAL BUILDINGS IN JAPAN

SURVEY ON INDOOR AIR QUALITY IN CONTEMPORARY RESIDENTIAL BUILDINGS IN JAPAN SURVEY ON INDOOR AIR QUALITY IN CONTEMPORARY RESIDENTIAL BUILDINGS IN JAPAN Teruaki Mitamura 1, Haruki Osawa 2, Yasuo Kuwasawa 2, and Hisashi Miura 2 1 Department of Architecture, Ashikaga Institute of

More information

A STUDY OF CROSS CONTAMINATION OF IN-SUITE VENTILATION SYSTEMS USED IN MULTI-UNIT RESIDENTIAL BUILDINGS

A STUDY OF CROSS CONTAMINATION OF IN-SUITE VENTILATION SYSTEMS USED IN MULTI-UNIT RESIDENTIAL BUILDINGS A STUDY OF CROSS CONTAMINATION OF IN-SUITE VENTILATION SYSTEMS USED IN MULTI-UNIT RESIDENTIAL BUILDINGS C.A. Parker, K.D. Pressnail, M.F. Touchie, D. DeRose, and S. Dedesko ABSTRACT Complaints of cross

More information

INVESTIGATIONS OF GYPSUM BOARDS WITH REGARD TO THE MOISTURE-BUFFERING-EFFECTS

INVESTIGATIONS OF GYPSUM BOARDS WITH REGARD TO THE MOISTURE-BUFFERING-EFFECTS INVESTIGATIONS OF GYPSUM BOARDS WITH REGARD TO THE MOISTURE-BUFFERING-EFFECTS Kristin Lengsfeld, Andreas Holm, and Martin Krus Department of Indoor Environment and Climate Impacts, Fraunhofer-Institute

More information

Sub Wet-Bulb Evaporative Chiller

Sub Wet-Bulb Evaporative Chiller Emerging Technologies Sub Wet-Bulb Evaporative Chiller Prepared by: Emerging Products Customer Service Southern California Edison June 2015 Acknowledgments Southern California Edison s Emerging Products

More information

Senior Design Project for UNO. Design of the International Studies Building: An Environmental Analysis

Senior Design Project for UNO. Design of the International Studies Building: An Environmental Analysis Senior Design Project for UNO Design of the International Studies Building: An Environmental Analysis Design Intent Implement Passive & Active design strategies in order to make the building: More Energy

More information

Computational and the real energy performance of a single-family residential building in Poland an attempt to compare: a case study

Computational and the real energy performance of a single-family residential building in Poland an attempt to compare: a case study Computational and the real energy performance of a single-family residential building in Poland an attempt to compare: a case study Piotr Kowalski 1,*, and Paweł Szałański 1 1 Department of Air Conditioning,

More information

Energy equivalent R-value

Energy equivalent R-value Mechanical & Aerospace Engineering Energy equivalent R-value Part 1: Integrated evaluation methodology for BE Mark Bomberg and Thomas Thorsell,, Syracuse University, Outline Objective: measure simultaneously

More information

UNCERTAINTY AND SENSITIVITY ANALYSIS OF NATURAL VENTILATION IN HIGH-RISE APARTMENT BUILDINGS.

UNCERTAINTY AND SENSITIVITY ANALYSIS OF NATURAL VENTILATION IN HIGH-RISE APARTMENT BUILDINGS. UNCERTAINTY AND SENSITIVITY ANALYSIS OF NATURAL VENTILATION IN HIGH-RISE APARTMENT BUILDINGS Se-Hoon Hyun 1, and Cheol-Soo Park 1, Godfried Augenbroe 1 Department of architectural Engineering, SungKyunKwan

More information

Design Strategies and Guide lines for Tropical Coast of Pakistan, Using Climate Consultant

Design Strategies and Guide lines for Tropical Coast of Pakistan, Using Climate Consultant European Journal of Sustainable Development (2016), 5, 3, 505-512 ISSN: 2239-5938 Doi: 10.14207/ejsd.2016.v5n3p505 Design Strategies and Guide lines for Tropical Coast of Pakistan, Using Climate Consultant

More information

Sustainable Design in High-Rise Residential

Sustainable Design in High-Rise Residential ctbuh.org/papers Title: Author: Subjects: Keywords: Sustainable Design in High-Rise Residential Dan Kaplan, Senior Principal, FXFOWLE Architectural/Design Building Case Study Sustainability/Green/Energy

More information

INTRODUCTION TO WUFI PASSIVE & PHIUS+ 2015

INTRODUCTION TO WUFI PASSIVE & PHIUS+ 2015 INTRODUCTION TO WUFI PASSIVE & PHIUS+ 2015 Lisa White: lisa@passivehouse.us 2017 Passive House Institute US PHIUS 1 PASSIVE BUILDING PRINCIPLES 2016 PHIUS 2017 Passive House Institute US PHIUS 2 PHIUS+

More information

INTEGRATING WHOLE BUILDING AIR LEAKAGE TEST DATA INTO ENERGYPLUS INFILTRATION MODELS

INTEGRATING WHOLE BUILDING AIR LEAKAGE TEST DATA INTO ENERGYPLUS INFILTRATION MODELS ASHRAE and IBPSA-USA SimBuild 2016 Building Performance Modeling Conference Salt Lake City, UT August 8-12, 2016 INTEGRATING WHOLE BUILDING AIR LEAKAGE TEST DATA INTO ENERGYPLUS INFILTRATION MODELS Edward

More information

CO2 in Vending Machine

CO2 in Vending Machine CO2 in Vending Machine CO2 SANYO Electric Co., Ltd. Commercial Solutions Company Daiki Shiomi Outline Contents 1. Company Profile 2. CO2 Compressor / Refrigeration System 3. CO2 System Performance 4. VM

More information

DISPLACEMENT VENTILATION

DISPLACEMENT VENTILATION DISPLACEMENT VENTILATION D3 OVERVIEW The fundamental approach to displacement ventilation utilizes the natural buoyancy forces created by the convective flows from heat sources in the space. As supply

More information

Performance evaluation of a small-scale polygeneration plant including a desiccant cooling system and an innovative natural gas ICE

Performance evaluation of a small-scale polygeneration plant including a desiccant cooling system and an innovative natural gas ICE Performance evaluation of a small-scale polygeneration plant including a desiccant cooling system and an innovative natural gas ICE Armando Portoraro Energetics Department Politecnico di Torino (Italy)

More information

Green Star Shopping Centre Design PILOT Energy Calculator Guide

Green Star Shopping Centre Design PILOT Energy Calculator Guide Green Star Shopping Centre Design PILOT Energy Calculator Guide Prepared by: Advanced Environmental Green Building Council of Australia Page 1 of 29 EXECUTIVE SUMMARY The Green Star Shopping Centre Design

More information

The Core Urban Design Strategies of Tall Building - Low Carbon Community

The Core Urban Design Strategies of Tall Building - Low Carbon Community ctbuh.org/papers Title: Authors: Subject: Keywords: The Core Urban Design Strategies of Tall Building - Low Carbon Community Enfang Liu, Shanghai Institute of Architectural Design & Research Wenli Fan,

More information

A Solar Wall System Utilized in Rural Houses of Northeast China

A Solar Wall System Utilized in Rural Houses of Northeast China A Solar Wall System Utilized in Rural Houses of Northeast China Tiantian Zhang and Yufei Tan in rural buildings, for instance, only 16.4% of the investigated houses employ solar energy to produce hot water

More information

IAQ & Energy Impact of Exhaust Air Transfer Ratio

IAQ & Energy Impact of Exhaust Air Transfer Ratio This article was published in ASHRAE Journal, November 207. Copyright 207 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission

More information

ASHRAE and Indoor Air Quality

ASHRAE and Indoor Air Quality ASHRAE 62.2-2013 and Indoor Air Quality Weatherize Ohio Conference October 27 29, 2015 The State of Ohio is an Equal Opportunity Employer and Provider of ADA Services Introduction ASHRAE: Why is it needed?

More information

Performance Testing of Cold Climate Air Source Heat Pumps

Performance Testing of Cold Climate Air Source Heat Pumps Performance Testing of Cold Climate Air Source Heat Pumps Martin Kegel a*, Jeremy Sager b, Martin Thomas b, Daniel Giguere a, Roberto Sunye a a Natural Resources Canada, CanmetENERGY, 1615 Blvd Lionel

More information

COMFORT DRIVEN ADAPTIVE WINDOW OPENING BEHAVIOR AND THE INFLUENCE OF BUILDING DESIGN

COMFORT DRIVEN ADAPTIVE WINDOW OPENING BEHAVIOR AND THE INFLUENCE OF BUILDING DESIGN COMFORT DRIVEN ADAPTIVE WINDOW OPENING BEHAVIOR AND THE INFLUENCE OF BUILDING DESIGN P. Tuohy 1, H.B. Rijal 2, M.A. Humphreys 2, J.F. Nicol 2, A. Samuel 1, J. Clarke 1 1 Energy Systems Research Unit, University

More information

Ventilative Cooling potential tool

Ventilative Cooling potential tool Ventilative Cooling potential tool User guide Version 1.0 IEA EBC Programme Annex 62 Ventilative Cooling AUTHORS: ANNAMARIA BELLERI EURAC RESEARCH Institute for renewable energy Druso 1 39100 Bolzano Italy

More information

Residential Energy Consumption: Longer Term Response to Climate Change

Residential Energy Consumption: Longer Term Response to Climate Change 24 th USAEE/IAEE North American Conference July 8-10, 2004, Washington, DC Residential Energy Consumption: Longer Term Response to Climate Change Christian Crowley and Frederick L. Joutz GWU Department

More information

Bryant University s Energy Guidelines for Sustainability

Bryant University s Energy Guidelines for Sustainability Bryant University s Energy Guidelines for Sustainability Rising carbon emissions have a disruptive impact on global climate patterns and pose a risk to the security of communities around the world. The

More information

Comparison of indoor air quality on a passenger ship and a chemical ship

Comparison of indoor air quality on a passenger ship and a chemical ship Indoor Air 28, 17-22 August 28, Copenhagen, Denmark - Paper ID: 49 Comparison of indoor air quality on a passenger ship and a chemical ship Sun-Sook Kim 1,*, Yoon-Kyung Kang 1, Geun-Young Doe 2 and Yun-Gyu

More information

MODELLING AND SIMULATION OF BUILDING ENERGY SYSTEMS USING INTELLIGENT TECHNIQUES

MODELLING AND SIMULATION OF BUILDING ENERGY SYSTEMS USING INTELLIGENT TECHNIQUES MODELLING AND SIMULATION OF BUILDING ENERGY SYSTEMS USING INTELLIGENT TECHNIQUES Ph.D. THESIS by V. S. K. V. HARISH ALTERNATE HYDRO ENERGY CENTRE INDIAN INSTITUTE OF TECHNOLOGY ROORKEE ROORKEE-247667 (INDIA)

More information

Economical and Environmental Effects of Thermal Insulation Thickness in Four Different Climatic Regions of Turkey

Economical and Environmental Effects of Thermal Insulation Thickness in Four Different Climatic Regions of Turkey A.E.Gürel, A.Daşdemir,Vol.1, No.1, pp.1-10, 011 Economical and Environmental Effects of Thermal Insulation Thickness in Four Different limatic egions of Turkey Ali Etem Gürel*, Ali Daşdemir ** * Duzce

More information

OPTIMIZATION OF ICE THERMAL STORAGE SYSTEM DESIGN FOR HVAC SYSTEMS

OPTIMIZATION OF ICE THERMAL STORAGE SYSTEM DESIGN FOR HVAC SYSTEMS OPTIMIZATION OF ICE THERMAL STORAGE SYSTEM DESIGN FOR HVAC SYSTEMS Nabil Nassif, Ph.D. P.E. Christopher Hall Dante' Freeland Assistant professor Graduate Student Graduate Student Department of Civil, Architectural,

More information

Overview on Indoor Thermal Environment and Air Quality Issues for Residential Buildings in Japan

Overview on Indoor Thermal Environment and Air Quality Issues for Residential Buildings in Japan ctbuh.org/papers Title: Author: Subject: Keywords: Overview on Indoor Thermal Environment and Air Quality Issues for Residential Buildings in Japan Hiroshi Yoshino, Professor, Tohoku University MEP Energy

More information

ARCH-MEDES (I) CONSULTANTS PVT. LTD. Green Park Delhi

ARCH-MEDES (I) CONSULTANTS PVT. LTD. Green Park Delhi Passive & Energy Efficient Design Assistance Report for Proposed Hospital Complex Manipal Health System at Pitampura, New Delhi ARCH-MEDES (I) CONSULTANTS PVT. LTD. Green Park Delhi Prepared By (Low Carbon

More information

Experimental investigation of zero energy office under natural and forced ventilation

Experimental investigation of zero energy office under natural and forced ventilation Experimental investigation of zero energy office under natural and forced ventilation Hussain H. Al-Kayiem 1, Syed I. U. Gilani 1, * and Mahmoud S. Abdalfatah 2 1 Mech. Eng. Dept., Universiti Teknologi

More information

Indoor Climate and Ventilation in Finnish Schools Air Distribution and Temperature Control in Classrooms

Indoor Climate and Ventilation in Finnish Schools Air Distribution and Temperature Control in Classrooms Indoor Climate and Ventilation in Finnish Schools Air Distribution and Temperature Control in Classrooms Abstract Finland is a country without a debate on natural ventilation. In such a cold climate, it

More information

A Field Study of Airflow in Mid to High-Rise Multi-Unit Residential Buildings

A Field Study of Airflow in Mid to High-Rise Multi-Unit Residential Buildings A Field Study of Airflow in Mid to High-Rise Multi-Unit Residential Buildings Lorne Ricketts, MASc, EIT John Straube, PhD, P.Eng. ABSTRACT Airflow into, out of, and within buildings is a fundamental factor

More information

ZEM ds : Case studies

ZEM ds : Case studies ZEMedS: Case studies Case study: Salamanque Group school, Montpellier, France The sole responsibility for the content of this publication lies with the authors. It does not necessarily reflect the opinion

More information

VELUX A/S, Daylight Energy and Indoor Climate, Ådalsvej 99, 2970 Hørsholm, Denmark *Corresponding author:

VELUX A/S, Daylight Energy and Indoor Climate, Ådalsvej 99, 2970 Hørsholm, Denmark *Corresponding author: VENTILATIVE COOLING OF RESIDENTIAL BUILDINGS: STRATEGIES, MEASUREMENT RESULTS AND LESSONS-LEARNED FROM THREE ACTIVE HOUSES IN AUSTRIA, GERMANY AND DENMARK Peter Foldbjerg *, Thorbjørn Asmussen VELUX A/S,

More information

Resolving Stack Effect Problems in a High-Rise Office Building by Mechanical Pressurization

Resolving Stack Effect Problems in a High-Rise Office Building by Mechanical Pressurization sustainability Article Resolving Stack Effect Problems in a High-Rise Office Building by Mechanical Pressurization Jung-yeon Yu 1, Kyoo-dong Song 2, * Dong-woo Cho 3 1 Department of Architectural Engineering,

More information

Modeling and analyzing solar cooling systems in Polysun

Modeling and analyzing solar cooling systems in Polysun Modeling and analyzing solar cooling systems in Polysun Seyed H. Rezaei (seyed.rezaei@velasolaris.com) 1 Andreas Witzig (andreas.witzig@velasolaris.com) 1 Michael Pfeiffer (michael.pfeiffer@velasolaris.com)

More information

Potential of ventilative cooling in German residential buildings

Potential of ventilative cooling in German residential buildings Potential of ventilative cooling in German residential buildings QUALICHeCK-Webinar, 2016-12-01 Auf Wissen bauen Fraunhofer IBP Introduction Background Highly insulated buildings with almost completely

More information

Field investigation on indoor thermal environment of a high-rise condominium in hot-humid climate of Bangkok, Thailand

Field investigation on indoor thermal environment of a high-rise condominium in hot-humid climate of Bangkok, Thailand Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 00 (2017) 000 000 www.elsevier.com/locate/procedia International High- Performance Built Environment Conference A Sustainable

More information

Bioclimatic Design Approach Integration into Architectural Design: a Library Case Study

Bioclimatic Design Approach Integration into Architectural Design: a Library Case Study PLEA 2016 Los Angeles - 36 th International Conference on Passive and Low Energy Architecture. Cities, Buildings, People: Towards Regenerative Environments Bioclimatic Design Approach Integration into

More information

Comprehensive Energy Audit For Kongiganak Health Clinic

Comprehensive Energy Audit For Kongiganak Health Clinic Comprehensive Energy Audit For Kongiganak Health Clinic Prepared For Native Village of Kongiganak September 15, 2011 Prepared By: ANTHC DEHE Energy Projects Group Anchorage, Alaska 99508 1 Table of Contents

More information

BUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY. Dr Mirek Piechowski 1, Adrian Rowe 1

BUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY. Dr Mirek Piechowski 1, Adrian Rowe 1 BUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY Dr Mirek Piechowski 1, Adrian Rowe 1 Meinhardt Building Science Group, Meinhardt Australia 1 Level 12, 501

More information

SUPPORTING CARBON NEUTRALITY IN URBAN ENVIRONMENTS USING POSITIVE ENERGY BUILDINGS

SUPPORTING CARBON NEUTRALITY IN URBAN ENVIRONMENTS USING POSITIVE ENERGY BUILDINGS C. Rau, Int. J. Sus. Dev. Plann. Vol. 12, No. 3 (2017) 580 588 SUPPORTING CARBON NEUTRALITY IN URBAN ENVIRONMENTS USING POSITIVE ENERGY BUILDINGS CHARLES RAU Rochester Institute of Technology. ABSTRACT

More information

Assignment 3 Integrated Energy Design

Assignment 3 Integrated Energy Design Assignment 3 Integrated Energy Design AAR4926 Marco Rimensberger Shabnam Arbab Shangyi Sun May 2012 Page 0 Contents 1 Introduction... 2 2 Background... 2 3 Design Progress... 2 3.1 Available Energy Sources...

More information

Optimisation of an HVAC system for energy saving and thermal comfort in a university classroom

Optimisation of an HVAC system for energy saving and thermal comfort in a university classroom Optimisation of an HVAC system for energy saving and thermal comfort in a university classroom Giovanni Semprini DIN / CIRI, University of Bologna, Bologna, Italy Cosimo Marinosci DIN / CIRI, University

More information