After refurbishment, heat recovery and demand control of the air flow were installed and the use of the systems were optimized.

Size: px
Start display at page:

Download "After refurbishment, heat recovery and demand control of the air flow were installed and the use of the systems were optimized."

Transcription

1 Property name: Nordstan Nordstan Objekt 6 Property owner: Vasakronan AB Consultants: GICON Total Concept method Step 1. Creating the action package Building and its use Year built: 1968 Area: m² Heated area Type of building: Office and shops The property Nordstaden 8:27 is commonly named Nordstan Objekt 6 and is situated in the central part of Gothenburg. The building is owned by Vasakronan AB and the total heated area of the building is m 2. It was originally built as a bank office. Since then, the building has been renovated several times and now hosts offices and warehouses. About 50 % of the area is office space and 46 % is shops. The building was latest refurbished in Indoor climate I After refurbishment, heat recovery and demand control of the air flow were installed and the use of the systems were optimized. The status of the building and its technical systems before measures I Building envelope In the pilot project in Nordstan Objekt 6 none of the energy saving measures were related to the building envelop. Heating The main part of heating is done with district heating. A heat pump with a yearly average COP of 4 was installed in the refurbishment. 1 (5)

2 Ventilation 2016 The ventilation system consists of twelve air handling units and it is a large building with complex systems. The systems had been rebuilt and extended in many different steps since 1968 and the documentation had not been updated. Recirculation fans were installed and the excess heat from cooling processes were recovered for heating. Some of the systems were separated in order to optimize the operation. It is still the original air handling unit from 1968 that operates. Cooling The cooling is done with both district cooling and cooling with outdoor air. Control and monitoring system(s) The original monitoring system made in 1996 is still used. Energy and resource use before measures (2009) Specific energy use before measures Whereas Heat energy Electricity for building operation District cooling 167 kwh/m²,year 57 kwh/m²,year 52 kwh/m²,year 62 kwh/m²,year The building initially used about 167 kwh/m 2, yr not included tenant s electricity. No baseline were set. Identified energy saving measures I 2 (5)

3 1.1 New air handling unit with new cooling treatment One (L66) of the twelve units serve location in the whole building. This is replaced with a new one with heat/cooling treatment to use excess energy in the building and connected with free cooling and with demand control. 1.2 Optimization air treatment unit with recirculation The operation of two air treatment units (L64 and L65) will be optimized and get new recirculation fans. 1.3 Installation of new heat pump During winter the building have both cooling and heat demand. New heat pump of 210 kw will transfer excess heat to the radiators. 1.4 Installation of heat recovery The heat from a cooling unit in a restaurant will be recovered in the heating system. 2.1 Adjustment/renovation of three air handling units serving shops The shops have different needs, the food shop have a heating demand while other shops have a large cooling demand. Install control for variable airflow in the supply and exhaust channels and time control. Prepare for free cooling with cold outdoor air in winter time and reduce airflow. CO2 control of ventilation. 2.2 Optimization of cooling circuit The house has large cooling demand due to large internal heat loads including from data centers and dense furnishing. The system have a constant flow through the two main pumps. The measure is to optimize the pumps in the system with pressure control to run variable flow in the circuit. Pumps will be shut down when free cooling is used wintertime. 2.3 Remove reheat coils Three air handling systems have reheat coils in the air handling system with high pressure drops and are not in operation and have no function. These will be removed and adjustments on airflow will be made. 2.4 Demand control of ventilation in offices Ventilation units for offices are provided with demand control through temperature compensation and time control. 2.5 Night cooling Function for night cooling exist but is not used. The function is modified and implemented and now include recirculation. 3 (5)

4 Summary of the measures in the action package Measure Optimization air treatment unit with recirculation Optimization of pump operation in the cooling circuit Invesment cost ksek Cost saving ksek/year Demand control of the air flow in offices Installation of heat recovery Night cooling in the circulation air and an air treatment unit Adjustments/renovation of three air handling units Remove reheat coils in three air treatment units Installation of heat pump New air handling unit with new cooling treatment Design and project management Sum: The costs do not include taxes. Energy saving MWh/year 4 (5)

5 Energy use [kwh/m2] heat cooling building electricty before package 1 (measure ) package 2 (measure ) Results The implementation of the energy saving measures was done in three phases, with three packages of measures, where the first two packages have been implemented. The total energy use of the building after the refurbishment (package 1 and 2) is 93 kwh/m2 and year and include 17 kwh/m2, yr for district heating, 40 kwh/m2, yr for cooling and 36 kwh/m2, yr for building electricity (December 2015). The aim for the two first phases was to achieve a total energy use of 84 kwh/m2, yr and the electricity use was not reduced as calculated. However, with a third package the consultant and the property owner believe that they can come down to a total energy use of about kwh/m2 in year (5)

Energy-Efficient Passive House using thermal mass to achieve high thermal comfort

Energy-Efficient Passive House using thermal mass to achieve high thermal comfort Energy-Efficient Passive House using thermal mass to achieve high thermal comfort Loa Andersson Managing Director RLI Byggdata AB rli@termodeck.com Alexander Engström Technical Director RLI Byggdata AB

More information

AM-55, AM-56) B U I L D I N G P A R T N E R S H I P S F O R E N E R G Y S E C U R I T Y

AM-55, AM-56) B U I L D I N G P A R T N E R S H I P S F O R E N E R G Y S E C U R I T Y Nearly zero-energy building and components of the DIRECTIVE on energy performance of buildings 2010/31/EU Albin Zsebik, PhD, CEM Improving university curricula in the areas of a) energy efficiency in the

More information

LIGHTING POWERS IN SHOPS AND THEIR EFFECT ON THE ENERGY PERFORMANCE OF A SHOPPING MALL

LIGHTING POWERS IN SHOPS AND THEIR EFFECT ON THE ENERGY PERFORMANCE OF A SHOPPING MALL Eleventh International IBPSA Conference Glasgow, Scotland July 27-30, 2009 LIGHTING POWERS IN SHOPS AND THEIR EFFECT ON THE ENERGY PERFORMANCE OF A SHOPPING MALL Sofia Stensson 1, Monica Axell 1, Per Fahlén

More information

Integrating Geothermal Heat Pump Systems in Smart District Energy Networks Case studies for E.ON Malmö

Integrating Geothermal Heat Pump Systems in Smart District Energy Networks Case studies for E.ON Malmö ISRN LUTMDN/TMHP--13/ 5270--SE ISSN 0282-1990 Integrating Geothermal Heat Pump Systems in Smart District Energy Networks Case studies for E.ON Malmö Gustav Sandgren Examensarbete Energihushållning Institutionen

More information

Case Study: Marks & Spencer Oxford Street

Case Study: Marks & Spencer Oxford Street Case Study: Marks & Spencer Oxford Street Environmental Design Solutions Ltd M&S Oxford Street State of the art building simulation software... The Brief: Calibrate a base model using metered consumption

More information

ENERGETIC MONITORING AND OPTIMIZATION OF A SOLAR HOUSE

ENERGETIC MONITORING AND OPTIMIZATION OF A SOLAR HOUSE Bulletin of the Transilvania University of Braşov Vol. 3 (52) - 2010 Series I: Engineering Sciences ENERGETIC MONITORING AND OPTIMIZATION OF A SOLAR HOUSE M. MOLDOVAN 1 I. VIŞA 1 A. DUŢĂ 1 Abstract: Into

More information

Sub-metering to Electricity Use in Large-scale Commercial Buildings

Sub-metering to Electricity Use in Large-scale Commercial Buildings Sub-metering to Electricity Use in Large-scale Commercial Buildings Wang Yuan Tsinghua University 26.11 Index Situation of Energy consumption in commercial buildings Significance of sub-metering and statistics

More information

ECONOMIC HEATING SYSTEMS FOR LOW ENERGY BUILDINGS IN SWEDEN

ECONOMIC HEATING SYSTEMS FOR LOW ENERGY BUILDINGS IN SWEDEN Numbers of Abstract/Session (given by NOC) - 1 - ECONOMIC HEATING SYSTEMS FOR LOW ENERGY BUILDINGS IN SWEDEN Svein, Ruud, Senior expert, Department of Energy Technology, SP Technical Research Institute

More information

Integrated Design. Architectural Design v/s HVAC Design. HVAC Design after Architectural design

Integrated Design. Architectural Design v/s HVAC Design. HVAC Design after Architectural design Integrated Design A necessity for sustainable buildings Architectural Design v/s HVAC Design or HVAC Design after Architectural design or Integration of Concept, Location, Esthetic and Technical Design

More information

Comparing Economics of Various Methods of Improving Energy Efficiency of Commercial Buildings

Comparing Economics of Various Methods of Improving Energy Efficiency of Commercial Buildings Comparing Economics of Various Methods of Improving Energy Efficiency of Commercial Buildings Marek Czachorski¹, Tim Kingston¹ and Jaroslav Wurm, PhD² ¹Gas Technology Institute, Des Plaines, Illinois,

More information

The Elithis Tower is an experimental and demonstration. Elithis Tower in Dijon, France. nzeb case studies

The Elithis Tower is an experimental and demonstration. Elithis Tower in Dijon, France. nzeb case studies COM Elithis Tower in Dijon, France Elithis Tower, located in Dijon, France, provides strong evidence that net zero energy office buildings are achievable in near future. The building, which was designed

More information

Energy Assessment Report Clayville Elementary School DRAFT October George Washington Highway, Clayville, RI DRAFT

Energy Assessment Report Clayville Elementary School DRAFT October George Washington Highway, Clayville, RI DRAFT Report Clayville Elementary School October 2016 3 George Washington Highway, Clayville, RI 02815 Clayville Elementary School Summary of Findings On behalf of the School Building Authority at Rhode Island

More information

Project name Gentoo Retrofit Bid 1 Project summary Refurbishment of 2no. Semi Detached houses using Passivhaus principles

Project name Gentoo Retrofit Bid 1 Project summary Refurbishment of 2no. Semi Detached houses using Passivhaus principles http://lowenergybuildings.org.uk Project name Gentoo Retrofit Bid 1 Project summary Refurbishment of 2no. Semi Detached houses using Passivhaus principles Project Description Projected build start date

More information

Energy Performance of Buildings Directive: Achieving both high indoor air quality and low energy consumption in European buildings

Energy Performance of Buildings Directive: Achieving both high indoor air quality and low energy consumption in European buildings Energy Performance of Buildings Directive: Achieving both high indoor air quality and low energy consumption in European buildings EVIA calls upon decision-makers to strengthen provisions ensuring proper

More information

Bruck an der Mur. Project summary. Energy concept: Background for the renovation reasons

Bruck an der Mur. Project summary. Energy concept: Background for the renovation reasons Bruck an der Mur Project summary Energy concept: Background for the renovation reasons The aim of this project was to gather information and experiences of the pilot project and the research, so that those

More information

Strategies for energy efficiency improvement in residential and office buildings: their role at building and country scale

Strategies for energy efficiency improvement in residential and office buildings: their role at building and country scale The Future Role of Energy Storage in South Eastern Europe Enlargement and Integration Action Workshop Strategies for energy efficiency improvement in residential and office buildings: their role at building

More information

Is it possible to build near zero energy single family buildings in very cold arctic climate?

Is it possible to build near zero energy single family buildings in very cold arctic climate? Is it possible to build near zero energy single family buildings in very cold arctic climate? Svein Ruud 1[0000-0002-7949-1978] 1 RISE Research Institutes of Sweden, Built environment, Energy and circular

More information

The carbon gap; analysis of the effects of grid decarbonisation on building CO 2 emissions and design

The carbon gap; analysis of the effects of grid decarbonisation on building CO 2 emissions and design The carbon gap; analysis of the effects of grid decarbonisation on building CO 2 emissions and design April 2017 The way the UK produces electricity is changing 2012: 42% coal 531gCO 2 /kwh 2016: 10% coal

More information

Design and development of a residential gas-fired heat pump

Design and development of a residential gas-fired heat pump Design and development of a residential gas-fired heat pump Edward A Vineyard a*, Ahmad Abu-Heiba a, Isaac Mahderekal b a Oak Ridge National Laboratory, P.O. Box 2008, MS 6070, Oak Ridge, TN, 37831, USA

More information

Retrocommissioning Investigation Report

Retrocommissioning Investigation Report Continuous Optimization for Commercial Buildings Program Retrocommissioning Investigation Report March 22, 2013 Prepared for: Thompson Rivers University International Building BC Hydro #:COP10-353 Prism

More information

6 District heating Substation District Heating Training Course

6 District heating Substation District Heating Training Course k v = q v p 6 District heating Substation District Heating Training Course B09HVen 16.04.2002 Mikkeli Polytechnic Siemens Building Technologies Building Automation Siemens Building Technologies Ltd. Building

More information

Energy modeling in IDA ICE according to ASHRAE , app. G

Energy modeling in IDA ICE according to ASHRAE , app. G Energy modeling in IDA ICE according to ASHRAE 90.1-2007, app. G About this document This document is a user s guide for a relatively experienced IDA ICE operator for using the 90.1 add-in and for performing

More information

Air distribution and temperature control in classrooms

Air distribution and temperature control in classrooms Air distribution and temperature control in classrooms Jarek Kurnitski D.Sc., Docent HELSINKI UNIVERSITY OF TECHNOLOGY Laboratory of Heating, Ventilation and Air Conditioning Swegon Air Academy 11.6.2008

More information

Singapore s Green Building Efficiency Standards

Singapore s Green Building Efficiency Standards Singapore s Green Building Efficiency Standards Energy Evolution of BCA Green Mark Standard 2005 2007 2008 2010 2012 2015 Version 1.0 Other Green IEQ Features [PERCENTAGE] 4% Environmental Protection 22%

More information

DEMAND CONTROLLED VENTILATION (DCV) SYSTEMS

DEMAND CONTROLLED VENTILATION (DCV) SYSTEMS DEMAND CONTROLLED VENTILATION (DCV) SYSTEMS Mari-Liis Maripuu, PhD CIT Energy mari-liis.maripuu@cit.chalmers.se Swegon Air Academy, Portugal, 27 May 211 Outline Introduction Concept of a DCV system Adapting

More information

Evaluating the Building Performance of the Center for Promotion of Science in Block 39 in Belgrade, Serbia

Evaluating the Building Performance of the Center for Promotion of Science in Block 39 in Belgrade, Serbia Evaluating the Building Performance of the Center for Promotion of Science in Block 39 in Belgrade, Serbia Berrak Balci Abstract This paper presents the evaluation of the building performance of the previously

More information

Objectives of NatVent

Objectives of NatVent of! This seven nation pan European project aims to reduce primary energy consumption (and consequently CO2 emissions) in office type buildings by: (a) providing solutions to barriers which prevent the

More information

The SOLCER Energy Positive House: Whole System Simulation. Phillip Jones, Xiaojun Li, Ester Coma and Jo Patterson

The SOLCER Energy Positive House: Whole System Simulation. Phillip Jones, Xiaojun Li, Ester Coma and Jo Patterson The SOLCER Energy Positive House: Whole System Simulation Phillip Jones, Xiaojun Li, Ester Coma and Jo Patterson Welsh School of Architecture, Cardiff University, Cardiff, United Kingdom Abstract There

More information

Changes to the Minnesota Commercial Energy Code. Presented by: Andy Thielen, PE

Changes to the Minnesota Commercial Energy Code. Presented by: Andy Thielen, PE Changes to the Minnesota Commercial Energy Code Presented by: Andy Thielen, PE Warning! The following is an outline of proposed code changes. There is no guarantee that the final code adopted by the State

More information

Workshop 1 Design and planning Step one: Mapping of present and future heat and cooling demand

Workshop 1 Design and planning Step one: Mapping of present and future heat and cooling demand Step one: Mapping of present and future heat and cooling demand Step one: Mapping of present and future heat and cooling demand Methods for identifying the heat and cooling demand: 1. Information from

More information

Steam Load Shed Events

Steam Load Shed Events Steam Load Shed Events Fall 2014 DSR Roundtable Nathan Hunter & Ellen Sweet Cornell University EHS Sent: Wednesday, January 29, 2014 7:35 AM To: SPECIALCONDITIONS-L Subject: Steam Load Shed Initiated for

More information

Passive houses for the Northern climate

Passive houses for the Northern climate Passive houses for the Northern climate Jyri Nieminen Customer Manager VTT Technical Research Centre of Finland Finland Jyri.Nieminen@vtt.fi Jouko Knuutinen Regional Director TA Yhtymä Finland Jouko.Knuutinen@TA.fi

More information

Workshop 1 Design and planning Step one: Mapping of present and future heat and cooling demand

Workshop 1 Design and planning Step one: Mapping of present and future heat and cooling demand Step one: Mapping of present and future heat and cooling demand Step one: Mapping of present and future heat and cooling demand Methods for identifying the heat and cooling demand: 1. Information from

More information

Ventilation Solutions in Renovated Apartment Buildings in Cold Climate Conditions

Ventilation Solutions in Renovated Apartment Buildings in Cold Climate Conditions Engineering, 2015, 7, 129-139 Published Online March 2015 in SciRes. http://www.scirp.org/journal/eng http://dx.doi.org/10.4236/eng.2015.73011 Ventilation Solutions in Renovated Apartment Buildings in

More information

EnergyPro Building Energy Analysis. Nine-story Office Building

EnergyPro Building Energy Analysis. Nine-story Office Building EnergyPro Building Energy Analysis Nine-story Office Building EnergyPro Building Energy Analysis for an office building Project Scope The purpose of the EnergyPro energy model was to evaluate the energy

More information

Energy Recovery Process Cooling Example. Presentation - Overview. Air Change Australia Pty Ltd. Air Change Energy Recovery Range

Energy Recovery Process Cooling Example. Presentation - Overview. Air Change Australia Pty Ltd. Air Change Energy Recovery Range 2 Presentation - Overview Energy Recovery Range + Designing Plant Rooms for Energy Efficiency The Company and the Technology Energy Recovery Product Range Product Range Pre-conditioners vs ERV-AHU s Energy

More information

Higher productivity and lower energy cost through better indoor climate and life cycle cost analysis

Higher productivity and lower energy cost through better indoor climate and life cycle cost analysis Higher productivity and lower energy cost through better indoor climate and life cycle cost analysis Dennis Johansson Forskning och utveckling Swegon AB Byggnadsfysik/Installationsteknik LTH dennis.johansson@swegon.se

More information

SURNA Grow Facility: Systems Comparison - IEA

SURNA Grow Facility: Systems Comparison - IEA SURNA Grow Facility: Systems Comparison - IEA May 2016 SURNA Grow Facility This analysis provides the projected energy and associated cost comparison between the Surna proposed facility in comparison to

More information

Reducing running costs, whilst benefiting the environment and the future

Reducing running costs, whilst benefiting the environment and the future Reducing running costs, whilst benefiting the environment and the future The Danfoss DHP-R produces heating and hot water using stored solar energy from the bedrock, surface ground, groundwater or exhaust

More information

PERFORMANCE OF LOW PRESSURE MECHANICAL VENTILATION CONCEPT WITH DIFFUSE CEILING INLET FOR RENOVATION OF SCHOOL CLASSROOMS

PERFORMANCE OF LOW PRESSURE MECHANICAL VENTILATION CONCEPT WITH DIFFUSE CEILING INLET FOR RENOVATION OF SCHOOL CLASSROOMS PERFORMANCE OF LOW PRESSURE MECHANICAL VENTILATION CONCEPT WITH DIFFUSE CEILING INLET FOR RENOVATION OF SCHOOL CLASSROOMS Søren Terkildsen *1, Svend Svendsen 1, 1 Technical University of Denmark Department

More information

Depth: Mechanical Redesign

Depth: Mechanical Redesign Depth: Mechanical Redesign Redesign Objectives The most important objective of the mechanical redesign is to provide Greenbriar East with ventilation that meets the requirements of ASHRAE Standard 62-2001.

More information

Cornell University Chilled Water Best Management Practices Program Annual Report -

Cornell University Chilled Water Best Management Practices Program Annual Report - Cornell University Chilled Water Best Management Practices Program - 2014 Annual Report - Prepared by: Cornell University Facilities Services Energy and Sustainability Utilities Report Date: 30 January

More information

SMART HVAC & LIGHTING SYSTEMS. Savings From Two Major C&I End Uses

SMART HVAC & LIGHTING SYSTEMS. Savings From Two Major C&I End Uses SMART HVAC & LIGHTING SYSTEMS Savings From Two Major C&I End Uses September 21, 2016 PRESENTATION OVERVIEW Why this focus? Significant savings potential Smart controls coupled with more efficient technologies

More information

Next Generation District Heating

Next Generation District Heating Next Generation District Heating FVB: Ulrika Ottosson, Heimo Zinko Lund University: Janusz Wollerstrand, Patrick Lauenburg, Marek Brand (DTU) a project The Swedish District Heating Association s R&D programme

More information

Green Star Shopping Centre Design PILOT Energy Calculator Guide

Green Star Shopping Centre Design PILOT Energy Calculator Guide Green Star Shopping Centre Design PILOT Energy Calculator Guide Prepared by: Advanced Environmental Green Building Council of Australia Page 1 of 29 EXECUTIVE SUMMARY The Green Star Shopping Centre Design

More information

Evaluation of Energy Savings of the New Chinese Commercial Building Energy Standard

Evaluation of Energy Savings of the New Chinese Commercial Building Energy Standard Evaluation of Energy Savings of the New Chinese Commercial Building Energy Standard Wei Feng, Ke Huang, Mark Levine and Nan Zhou, Lawrence Berkeley National Laboratory Shicong Zhang, Lawrence Berkeley

More information

Level 1 Modules tdp-101 hvac industry overview tdp-103 concepts of air conditioning tdp-102 abcs of comfort

Level 1 Modules tdp-101 hvac industry overview tdp-103 concepts of air conditioning tdp-102 abcs of comfort TDP-101 HVAC Industry Overview This TDP provides a general overview of the commercial HVAC industry and provides an awareness of the design process and construction. The documents involved in construction,

More information

Ecodesign FROM REGULATION 1253 & 1254/2014. For Residential And Non-Residential Ventilation Units

Ecodesign FROM REGULATION 1253 & 1254/2014. For Residential And Non-Residential Ventilation Units Ecodesign FROM REGULATION 1253 & 1254/2014 For Residential And Non-Residential Ventilation Units FULL FRESH AIR SYSTEMS Creating a better internal environment The Ecodesign Directive The Ecodesign Directive

More information

Energy Efficiency in Building Active Design Part II

Energy Efficiency in Building Active Design Part II Energy Efficiency in Building Active Design Part II Presented by: CK Tang BSEEP Component 4 Manager Veritas Enviornment Sdn Bhd ck.tang@veritas.com.my Air Conditioning System System Sizing 1 Current Industry

More information

How to maximise energy efficiency and cost effectiveness of different type heat pump projects three case studies

How to maximise energy efficiency and cost effectiveness of different type heat pump projects three case studies How to maximise energy efficiency and cost effectiveness of different type heat pump projects three case studies Presenter: Alex Koncar GreenKon Pty Ltd, Sydney, Australia E-mail: alexkoncar@greenkon.com.au

More information

EnergyPro Building Energy Analysis. Single-story School Building

EnergyPro Building Energy Analysis. Single-story School Building EnergyPro Building Energy Analysis Single-story School Building EnergyPro Building Energy Analysis for a single-story school bulding Project Scope The purpose of the EnergyPro energy model was to evaluate

More information

APPLICATIONS Air-to-Air Energy Recovery

APPLICATIONS Air-to-Air Energy Recovery APPLICATIONS Air-to-Air Energy Recovery Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application

More information

Lincoln University Energy Conservation Program

Lincoln University Energy Conservation Program Lincoln University Energy Conservation Program 7/21/2011 Table of Contents Table of Contents Table of Contents... 2 Purpose... 3 Scope... 3 A. Summary of Implementation Plan Initiatives... 3-5 B. Five

More information

Development of a compact single room ventilation unit with heat recovery dedicated to tertiary building

Development of a compact single room ventilation unit with heat recovery dedicated to tertiary building Development of a compact single room ventilation unit with heat recovery dedicated to tertiary building Samuel Gendebien *1, Jonathan Martens 2, Luc Prieels 2 and Vincent Lemort 1 1 University of Liege

More information

HVAC SYSTEM CONFIGURATIONS, AN ENERGY ASPECT

HVAC SYSTEM CONFIGURATIONS, AN ENERGY ASPECT HVAC SYSTEM CONFIGURATIONS, AN ENERGY ASPECT Y Zhang 1,*, JA Wright 2 and VI Hanby 1 1 Institute of Energy and Sustainable Development, De Montfort University, Leicester, LE1 9BH, UK 2 Department of Civil

More information

SECTION H ENERGY EFFICIENCY TABLE OF CONTENTS UNSW DESIGN & CONSTRUCTION REQUIREMENTS WEB ENTRY PAGE

SECTION H ENERGY EFFICIENCY TABLE OF CONTENTS UNSW DESIGN & CONSTRUCTION REQUIREMENTS WEB ENTRY PAGE SECTION H ENERGY EFFICIENCY TABLE OF CONTENTS UNSW DESIGN & CONSTRUCTION REQUIREMENTS WEB ENTRY PAGE SECTION A INTRODUCTION SECTION B DEVELOPMENT & PLANNING SECTION C ARCHITECTURAL REQUIREMENTS SECTION

More information

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 1 Heiselberg, Per Kvols. Publication date: 2016

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 1 Heiselberg, Per Kvols. Publication date: 2016 Downloaded from vbn.aau.dk on: April 11, 2019 Aalborg Universitet CLIMA 2016 - proceedings of the 12th REHVA World Congress volume 1 Heiselberg, Per Kvols Publication date: 2016 Document Version Publisher's

More information

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1 Air System Design Load Summary for Zona 6 DESIGN COOLING DESIGN HEATING COOLING DATA AT Feb 1600 HEATING DATA AT DES HTG COOLING OA DB / WB 34.5 C / 23.7 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible Latent

More information

Georgetown University New Science Center

Georgetown University New Science Center Georgetown University New Science Center Final Thesis Proposal PENN STATE UNIVERSITY Prepared For: Dr. William P. Bahnfleth Department of Architectural Engineering Prepared By: Kevin M Edstrom Mechanical

More information

Commissioning for Energy Savings

Commissioning for Energy Savings Commissioning for Energy Savings Presented To: AEE / ASHRAE / USGBC 2013 Energy Expo St. Paul RiverCentre, St. Paul, Minnesota October 2, 2013 Presented By: Rebecca T. Ellis, PE LEED AP BD+C, CCP, CPMP

More information

Cooling coil optimisation in hot and humid climates for IAQ and energy considerations

Cooling coil optimisation in hot and humid climates for IAQ and energy considerations Cooling coil optimisation in hot and humid climates for IAQ and energy considerations Chandra Sekhar 1, Uma Maheswaran 2 1 Department of Building, National University of Singapore 2 Jurong Consultants

More information

What s My Baseline? ASHRAE

What s My Baseline? ASHRAE 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions (2010, vol 116,part 2). For personal use only. Additional reproduction,

More information

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1 Air System Design Load Summary for Zona 9 DESIGN COOLING DESIGN HEATING COOLING DATA AT Jan 1400 HEATING DATA AT DES HTG COOLING OA DB / WB 34.5 C / 23.7 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible Latent

More information

TDPs provide you with new technical training materials designed to help your contractors, engineers, and designers to effectively design, specify,

TDPs provide you with new technical training materials designed to help your contractors, engineers, and designers to effectively design, specify, TDP Catalog TDPs provide you with new technical training materials designed to help your contractors, engineers, and designers to effectively design, specify, sell, and apply HVAC equipment in commercial

More information

Xiaofen Xu, Liang Zhang, Huajing Sha, Ying Ji, Peng Xu. Tongji University, Shanghai, China

Xiaofen Xu, Liang Zhang, Huajing Sha, Ying Ji, Peng Xu. Tongji University, Shanghai, China Establishment of Typical Building Models in Each Climate Regions in China and Research of Adaptability of Energy Saving Research of Adaptability of Energy- Technologies in the Standard of 65% Energy Saving

More information

Benchmarking energy consumption, IEA HPP Annex 44 Performance indicators for energy efficient supermarket buildings

Benchmarking energy consumption, IEA HPP Annex 44 Performance indicators for energy efficient supermarket buildings Benchmarking energy consumption, IEA HPP Annex 44 Performance indicators for energy efficient supermarket buildings Christian Heerup, Danish Technological Institute OBJECTIVES Objectives - create performance

More information

Impact of ventilation heat recovery on primary energy use of apartment buildings built to conventional and passive house standard

Impact of ventilation heat recovery on primary energy use of apartment buildings built to conventional and passive house standard Impact of ventilation heat recovery on primary energy use of apartment buildings built to conventional and passive house standard Leif Gustavsson 1,2, Ambrose Dodoo 2, *, Roger Sathre 2 1 Linnaeus University,

More information

Re: College of Lake County: AB Wing HVAC Remodeling Programming Mtg #3 Architect s Project Number: Meeting Minutes

Re: College of Lake County: AB Wing HVAC Remodeling Programming Mtg #3 Architect s Project Number: Meeting Minutes March 6, 204 VIA Email College of Lake County 935 West Washington Street Grayslake, Illinois 60030 Re: College of Lake County: AB Wing HVAC Remodeling Programming Mtg #3 Architect s Project Number: 2406.00

More information

Engineers Ireland Cork Region CPD lecture series

Engineers Ireland Cork Region CPD lecture series Engineers Ireland Cork Region CPD lecture series NZEB and Emerging Legislation & SEAI s Deep Retrofit Pilot Programme Orla Coyle NZEB Programme Manager Conor Hanniffy Deep Retrofit Pilot Programme Manager

More information

Session: HVAC Technologies

Session: HVAC Technologies Session: HVAC Technologies What s VRF? Mira Vowles Bonneville Power Administration August 10, 2016 Rhode Island Convention Center Providence, Rhode Island Why should I care about VRF? VRF systems: can

More information

GOTHENBURG ENERGY. Workshop London

GOTHENBURG ENERGY. Workshop London GOTHENBURG ENERGY Workshop London 2016-06-08 Gothenburg Energy In Numbers 2014 2013 Number employees, average 1 060 1 174 Result, MSEK 290 703 Turnover, MSEK 6 036 6 922 District Heating - Key Notes DH

More information

Cornell University Chilled Water Best Management Practices Program 2015 Annual Report

Cornell University Chilled Water Best Management Practices Program 2015 Annual Report Cornell University Chilled Water Best Management Practices Program 2015 Annual Report Prepared by: Cornell University Facilities Services Energy and Sustainability Utilities Report Date: 26 January 2016

More information

EUROPEAN MYTHOLOGY AND HELLENIC REALITY ABOUT ZERO ENERGY BUILDINGS

EUROPEAN MYTHOLOGY AND HELLENIC REALITY ABOUT ZERO ENERGY BUILDINGS EUROPEAN MYTHOLOGY AND HELLENIC REALITY ABOUT ZERO ENERGY BUILDINGS Flourentzos Flourentzou Nov 2013 Flourentzos Flourentzou Estia SA Par Scientifique EPFL 1015 Lausanne, Switzerland flou@estia.ch 0 Energy

More information

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1 Air System Design Load Summary for Zona 8 DESIGN COOLING DESIGN HEATING COOLING DATA AT Dec 1700 HEATING DATA AT DES HTG COOLING OA DB / WB 33.1 C / 23.5 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible Latent

More information

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1 Air System Design Load Summary for Zona 3 Project Name: Av. Cabildo 3067, 4 piso 02/13/2011 DESIGN COOLING DESIGN HEATING COOLING DATA AT Feb 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 34.9 C / 23.8

More information

Energy and Comfort Performance Analysis of Monitored Thermally Activated Building Systems Combined with Geothermal Heat Pumps

Energy and Comfort Performance Analysis of Monitored Thermally Activated Building Systems Combined with Geothermal Heat Pumps Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2012 Energy and Comfort Performance Analysis of Monitored Thermally Activated Building

More information

Feasibility Study of a Heat Pump Integrated Heat Recovery Ventilator (HRV) in Cold Climates

Feasibility Study of a Heat Pump Integrated Heat Recovery Ventilator (HRV) in Cold Climates Feasibility Study of a Heat Pump Integrated Heat Recovery Ventilator (HRV) in Cold Climates Robbin Garber-Slaght, P.E. Conor Sosebee Bruno Grunau, P.E. March 31, 2017 Cold Climate Housing Research Center

More information

Improving Energy Efficiency of Residential Buildings

Improving Energy Efficiency of Residential Buildings 1 November 2017 Improving Energy Efficiency of Residential Buildings Minenkov A.V. Head Department for Scientific and Technical Policy and Foreign Economic Relations Department for Energy Efficiency State

More information

Energy Efficiency. best in class

Energy Efficiency. best in class Page 1 The impact of Building Automation on Energy Efficiency Siemens with DESIGO and Synco best in class Energy is a major issue for the European Union Primary energy use in Europe Dependency Without

More information

CCS Purpose Energy performance calculation

CCS Purpose Energy performance calculation Purpose Energy performance calculation Process description June 2016 Kolofon 2016-06-27

More information

> HGW WATER - WATER AND BRINE - WATER HEAT PUMPS FOR INDOOR INSTALLATION. Available range. Unit description. Options. Accessories

> HGW WATER - WATER AND BRINE - WATER HEAT PUMPS FOR INDOOR INSTALLATION. Available range. Unit description. Options. Accessories > HGW WATER - WATER AND BRINE - WATER HEAT PUMPS FOR INDOOR INSTALLATION Available range Unit type IH Heat pump IP Reversible heat pump (reversible on the refrigerant side) ECO-FRIENDLY REFRIGERANT GAS

More information

Does NZEB pose a conflict to Good Indoor Air Quality? REHVA summit November 2017

Does NZEB pose a conflict to Good Indoor Air Quality? REHVA summit November 2017 Does NZEB pose a conflict to Good Indoor Air Quality? REHVA summit November 2017 Version: 2016-07-04 Niels Christensen Strategic Product Manager, ICS Email: niels.christensen@lindab.com Version: 2016-07-04

More information

IN THIS ISSUE INTRODUCTION BACKGROUND. March 2018 High Humidity in Winter: Analysis for Multi-Family Passive House Projects

IN THIS ISSUE INTRODUCTION BACKGROUND. March 2018 High Humidity in Winter: Analysis for Multi-Family Passive House Projects Page 1 High Humidity in Winter: Analysis for Multi-Family Passive House Projects IN THIS ISSUE Passive House for multi-family residential applications Analysis of high humidity levels in winter Impact

More information

Green Star Multi Unit Residential Calculator Guide

Green Star Multi Unit Residential Calculator Guide Green Star Multi Unit Residential Energy Calculator Guide 1 EXECUTIVE SUMMARY The Green Star Multi Unit Residential Energy Calculator has been developed to predict the performance of multi-unit residential

More information

Launching of the Probis Project, Procurement of building innovative solutions.

Launching of the Probis Project, Procurement of building innovative solutions. #1 Procurement of building innovative solutions newsletter # 1 November 2014 Editorial Launching of the Probis Project, Procurement of building innovative solutions. More than 20 European experts have

More information

Waste Heat Recapture from Supermarket Refrigeration Systems

Waste Heat Recapture from Supermarket Refrigeration Systems Waste Heat Recapture from Supermarket Refrigeration Systems Final Report Submitted to: Refrigeration Project Team Retail Energy Alliance Prepared by: Brian A. Fricke, Ph.D. Oak Ridge National Laboratory

More information

IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST

IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST ENVELOPE REQUIREMENTS Project: Date: Instructions RECOMMENDED: List performance values, note exceptions that were applied, or provide other

More information

Energy Conservation for Office Buildings. Major points, measures, and successful cases of energy conservation for office buildings

Energy Conservation for Office Buildings. Major points, measures, and successful cases of energy conservation for office buildings Energy Conservation for Office Buildings Major points, measures, and successful cases of energy conservation for office buildings The Energy Conservation Center, Japan Introduction The first commitment

More information

City of Toronto Tower Renewal Program

City of Toronto Tower Renewal Program Photo by Jesse Colin Jackson City of Toronto Tower Renewal Program CAC Presentation October 6, 2016 1 Tower Renewal A program to drive broad environmental, social, economic, and cultural change by improving

More information

Fifteen Year Plan for Energy Efficiency and Conservation Projects

Fifteen Year Plan for Energy Efficiency and Conservation Projects Fifteen Year Plan for Energy Efficiency and Conservation Projects Presented to the Board of Trustees of the Northeastern Ohio Universities Colleges of Medicine and Pharmacy, December, 2008, in accordance

More information

2-Pipe fan coil terminal units were selected as the parallel system to handle the remaining sensible cooling load.

2-Pipe fan coil terminal units were selected as the parallel system to handle the remaining sensible cooling load. Redesign Introduction This report is an in depth analysis of the mechanical systems of the Outreach Innovation Building located in University Park, PA and the impact these changes had on other systems

More information

Developers perspective on classification as a driver towards net zero buildings

Developers perspective on classification as a driver towards net zero buildings Developers perspective on classification as a driver towards net zero buildings REHVA in Tallin 2011 05 20 Jonas Gräslund, Skanska Commercial Development Nordic 1 The Skanska Group Group staff units Skanska

More information

Asset Energy Calculator Guidance

Asset Energy Calculator Guidance Asset Energy Calculator Guidance Introduction This section has been produced to give BREEAM In-Use assessors further guidance on the workings of the asset energy calculator so it is clear how any improvements

More information

PASSIVHAUS Designed for you to enjoy maximum comfort with minimum energy.

PASSIVHAUS Designed for you to enjoy maximum comfort with minimum energy. PASSIVHAUS Designed for you to enjoy maximum comfort with minimum energy. + Energy efficiency + Savings +Comfort WHAT IS PASSIVHAUS? The Passivhaus (Passive House) standard is the most stringent international

More information

AVOIDING 2015 MINNESOTA ENERGY CODE VIOLATIONS

AVOIDING 2015 MINNESOTA ENERGY CODE VIOLATIONS AVOIDING 2015 MINNESOTA ENERGY CODE VIOLATIONS Commercial Energy Codes Support Program Pilot Russ Landry, PE, LEED AP Megan Hoye, LEED AP Pilot Program Support This project is supported by a grant from

More information

Calculation of the yearly energy performance of heating systems based on the European Building Directive and related CEN Standards

Calculation of the yearly energy performance of heating systems based on the European Building Directive and related CEN Standards Downloaded from orbit.dtu.dk on: Oct 06, 2018 Calculation of the yearly energy performance of heating systems based on the European Building Directive and related CEN Standards Olesen, Bjarne W.; Langkilde,

More information

Heat Pump Hot Water Supply Systems

Heat Pump Hot Water Supply Systems 2007年度版 Heat Pump Hot Water Supply Systems (1) Aims A great amount of energy is consumed for supplying hot water in the residential, commercial and industrial sectors. emission from residential hot water

More information

Set Free Modular FSXN. Engineering for tomorrow. And the tomorrow after that.

Set Free Modular FSXN. Engineering for tomorrow. And the tomorrow after that. Set Free Modular FSXN Engineering for tomorrow. And the tomorrow after that. 0 03 Introducing a new addition to Hitachi s Set Free range of VRF air conditioning units - enhancing efficiency and user experience

More information

Coupling night ventilative and active cooling to reduce energy use in supermarkets with high refrigeration loads

Coupling night ventilative and active cooling to reduce energy use in supermarkets with high refrigeration loads Coupling night ventilative and active cooling to reduce energy use in supermarkets with high refrigeration loads ABSTRACT Zoi Mylona *1, Maria Kolokotroni 1 and Savvas Tassou 1 1 RCUK National Centre for

More information

University of Minnesota Duluth Civil Engineering Building

University of Minnesota Duluth Civil Engineering Building Energy Data Attachment University of Minnesota Duluth Civil Engineering Building LEED Energy Modeling The energy modeling for LEED NC 2.2 was performed against ASHRAE 9.1-24 Appendix using equest version

More information