The definition of an extraneous-conductive-part, as given in Part 2 of BS 7671 is:

Size: px
Start display at page:

Download "The definition of an extraneous-conductive-part, as given in Part 2 of BS 7671 is:"

Transcription

1 Contents 1. Introduction Summary 1. Introduction Extraneous-conductive-parts are referred to extensively in BS 7671, mostly in relation to equipotential bonding, but also with regard to electric shock protection measures such as SELV, placing out of reach and non-conducting location. The definition of an extraneous-conductive-part, as given in Part 2 of BS 7671 is: Extraneous-conductive-part. A conductive part liable to introduce a potential, generally earth potential, and not forming part of the electrical installation. The aim of this topic is to give a clearer understanding of the definition, and thereby to provide assistance where it is necessary to decide whether or not a specific item of metalwork or other conducting material is an extraneous-conductive-part. Before moving on, however, it is stressed that the term extraneous-conductive-part is a single, hyphenated noun, and it is quite wrong to omit the hyphens when writing the term. 2. For the purposes of this topic, the definition is considered in the following three portions: First portion: A conductive part Second portion: liable to introduce a potential, generally earth potential Third portion: and not forming part of the electrical installation First portion: A conductive part In most situations, only parts which are made of metal need to be considered as conductive parts. Metals have a conductivity which is very much higher than that of most other materials. (Conductivity is a measure of the conductance of a standard cube of a material, just as resistivity, the reciprocal of conductivity, is a measure of the resistance of a standard cube of a material.) Non-metallic materials, however, cannot be entirely ruled out. For example, whilst distilled water may be regarded as an insulator, water which is laden with salts or some other types of impurity is generally a conductor albeit a poor one compared with metals. NICEIC NICEIC TECHNICAL MANUAL 27 SEP 01 1 of 7

2 E169-9 E EXTRANEOUS-CONDUCTIVE-PARTS In some circumstances, water containing impurities may be considered to be an extraneous-conductive-part. This may be true, for example, of dirty water in a handbasin or bath, draining away through a non-metallic waste pipe, at the far end of which the column of water is in contact with Earth potential, perhaps due to a metallic underground pipe or tank. Similarly, a metallic fitting or section of metallic pipe connected to the non-metallic pipe in the above example, somewhere within the building, could be considered to be an extraneous-conductive-part due to contact with the Earthy water. The implications of this are dealt with in Topic B Second portion: liable to introduce a potential, generally earth potential In considering this portion of the definition, it is convenient to deal firstly with the source of a potential, and secondly with the question of whether the potential is liable to be introduced Source of potential As indicated by this portion of the definition, the potential which is generally of interest is earth potential, the electric potential of the conductive mass of Earth, which is conventionally taken as zero. This is normally the potential of an item such as a metal pipe which is buried in the ground, or a structural steel column which is fixed in a foundation in the ground. Other potentials, however, may also be of interest. For example, the metalwork of a non-electrical service or other facility entering the premises from another building, in which it may be bonded to the main earthing terminal, could, under earth fault conditions in the installation in that building, be at a potential related to the fault The question of whether the potential is liable to be introduced Electric shock to a person or livestock is caused by a potential difference (a voltage) applied between two or more parts of the body. Therefore, in order to be involved in causing electric shock, a conductive part must not only be at a potential, it must be liable to introduce that potential to a person (or livestock). That is to say, the conductive part must be liable to introduce its potential to a person (or livestock) who may simultaneously be in contact with another potential. 2 of 7 27 SEP 01 NICEIC TECHNICAL MANUAL NICEIC

3 Such other potentials may include the potential of: (i) An exposed-conductive-part (ii) an extraneous-conductive-part (where liable to be at a potential other than that of the conductive part under consideration); or (iii) a bare live part * Accessibility Generally, in order for a conductive part to be liable to introduce a potential to a person or livestock in contact with the potential of any of the parts listed in (i), (ii) and (iii) above, the conductive part must be accessible to be touched by such a person (or livestock). A conductive-part (exposed structural metalwork) accessible to a person who may be in contact with an exposed-conductive-part ON O Exposed-conductive-part (motor casing) Exposed structural metalwork The extraneous-conductive-part (structural metalwork) may introduce earth potential by being accessible to a person in contact with the exposed-conductive-parts of the pillar drill. Fig 1 * Applicable only where protection against direct contact by placing out of reach is used, where Regulation requires a distance of at least 2.5 m between a bare live part and an extraneous-conductivepart). NICEIC NICEIC TECHNICAL MANUAL 27 SEP 01 3 of 7

4 E169-9 E EXTRANEOUS-CONDUCTIVE-PARTS Exceptionally, an electrical installation designer may decide that in his or her opinion a particular conductive part is not accessible to be touched by anyone in contact with the potential of any of the parts listed in (i), (ii) and (iii) above, and that it is therefore not an extraneous-conductive-part. For example, the conductive part may be situated a long distance away from all such parts and/or may be of small dimensions, so that it cannot be gripped or contacted by a major surface of the body. However, in most types of building, conductive parts such as non-electrical services or exposed structural metalwork are generally accessible to be touched by persons who may be in contact with exposed-conductive-parts (including those of portable equipment) or extraneous-conductive-parts. Even where this is not initially the case, consideration should be given to the possibility that it may become true later during the life of the building, due to changes in the mechanical and/or electrical services installations or in the use of the premises. In addition, at a location such as a swimming pool location or agricultural premises, an item should not be ruled out as being an exposed-conductive-part simply because its distance from any exposed-conductive-part or extraneousconductive-part is too great to be spanned by the body of a single person or livestock. In such a location, a group of persons or livestock may form, whose bodies are in electrical contact with each other. Finally, the possibility should not be overlooked of a conductive part introducing a potential to a person through metalwork with which it is in electrical contact. This could occur by means of the metalwork being touched by a person who is also in contact with an exposed-conductive-part or an extraneous-conductive-part (or metalwork in contact with one of these). High resistance connection A conductive part may be precluded from falling within the definition of an extraneous-conductive-part because it is connected to the source of its potential through a high resistance. For example, a conductive part may be connected to Earth potential through the high resistance of a non-metallic part of a building structure. Where the resistance of the connection is sufficiently high, the conductive part is incapable of introducing its source potential (e.g. Earth potential) to a person or livestock who is simultaneously in contact with the conductive part and an exposed-conductive-part or extraneous-conductive-part. This is because the voltage drop across the high resistance connection, produced by the current flowing through it, is such that the touch voltage to which someone is exposed is within safe limits. 4 of 7 27 SEP 01 NICEIC TECHNICAL MANUAL NICEIC

5 Formula (1) may be used to assess whether Earth potential is liable to be introduced by a conductive part which is connected to the general mass of Earth through a resistance, as described above. The formula is intended to be used when a measurement has been made of the resistance (R CP ) between the conductive part concerned and the main earthing terminal of the installation. Allowance should be made, where appropriate, for the measurement not having been carried out under conditions of maximum moisture (ie worst case). If the resistance R CP (Ω) is such that: U 0 R CP > Z TL I B the conductive part can be considered not to be liable to introduce Earth potential. Where: (1) R CP U 0 I B Z TL is the resistance between the conductive part concerned and the main earthing terminal of the installation (Ω). is the nominal voltage to Earth of the installation (V). is the value of current through the human body (or livestock) which should not be exceeded (A). is the impedance of the human body (or livestock) (Ω). Values of Z TL and I B should be selected from PD 6519 depending on the conditions expected to arise in the installation concerned. For example, for a risk of electric shock to a person from hand-to-hand contact, where U 0 is 230 V (50 Hz), PD 6519 indicates that a suitable value to take for Z TL is 1,000 Ω in dry conditions. PD 6519 indicates that a suitable value to take for I B in an installation where the conditions of BS 7671 for automatic disconnection are fulfilled is between 0.5 ma (the threshold of perception) and 10 ma (the threshold of let-go) Third portion: and not forming part of the electrical installation This portion of the definition limits extraneous-conductive-parts to being items which do not form part of the electrical installation in question. Therefore, items which may be extraneous-conductive-parts include the following, which are referred to in Regulation of BS 7671 with regard to main equipotential bonding (provided such items are also covered by the other portions of the definition referred to in this topic): The content of PD 6519 is discussed in Topic E65-5. NICEIC NICEIC TECHNICAL MANUAL 27 SEP 01 5 of 7

6 E169-9 E EXTRANEOUS-CONDUCTIVE-PARTS water service pipes gas installation pipes other service pipes and ducting central heating and air conditioning systems exposed metallic structural parts of a building a lightning protection system In addition, any other non-electrical items which fall within the definition may be extraneous-conductive-parts. Although the definition precludes items forming part of the electrical installation from being extraneous-conductive-parts, items serving a purely non-electrical purpose within an installation should not be ruled out. Such items may include, for example, a metal support system or carrier for cables having non-metallic sheaths which is not required to be earthed. Moreover, items forming part of another electrical installation (that is, an installation supplied from a different origin or having a separate earthing arrangement) are not precluded from being extraneous-conductive-parts. Such items may include, for example, a metal conduit or the metal sheath or armouring of a cable entering the premises from another building. 3. Summary In order to decide whether or not a specific item is an extraneous-conductive-part, the following should be considered: Is the item conductive? In order to be conductive, an item must be formed of metal or some other conducting material (which may include a conducting liquid). Is the item liable to introduce a potential, generally earth potential? That is to say, is the item liable to introduce a potential to a person (or livestock) who may be in contact with another potential? To introduce a potential to such a person, the item must not only be at a potential, but must also be able to introduce the potential. Introduction of the potential requires two things. The first is that the item (or a conducting item in electrical contact with it) must be accessible to be touched by a part of such a person s body. The second is that any electrical resistance through which the item is connected to the source of its potential (such as the resistance connecting an item with Earth potential) must not be so great as to prevent the potential being introduced to a person (due to voltage drop in the resistance). 6 of 7 27 SEP 01 NICEIC TECHNICAL MANUAL NICEIC

7 Is the item part of the electrical installation? Only an item which does not form part of the electrical installation concerned may be an extraneous-conductive-part. However, items serving a purely non-electrical purpose within the installation should not be ruled out. Moreover, items forming part of another installation are not precluded. Topics referred to in this text: B37-45 BONDING: Metallic parts connected to non-metallic pipework E65-5 ELECTRIC SHOCK: The hazard, physiological effect of electric current through the body Topics not referred to in this text, which are related and may be of interest: D41-11 DIRECT CONTACT, PROTECTION AGAINST: Placing out of reach E161-9 EXTRA-LOW VOLTAGE (ELV): PELV (Protective extra-low voltage) E EXTRA-LOW VOLTAGE (ELV): SELV (Separated extra-low I17-9 INDIRECT CONTACT, PROTECTION AGAINST: Non-conducting location Requirements for electrical installations (BS 7671): Some of the most important requirements are found in: Definitions Part 2 NICEIC NICEIC TECHNICAL MANUAL 27 SEP 01 7 of 7

IET Wiring Regulations (BS 7671:2008+A3:2015) - SECTION 705 AGRICULTURAL AND HORTICULTURAL PREMISES

IET Wiring Regulations (BS 7671:2008+A3:2015) - SECTION 705 AGRICULTURAL AND HORTICULTURAL PREMISES IET Wiring Regulations (BS 7671:2008+A3:2015) - SECTION 705 AGRICULTURAL AND HORTICULTURAL PREMISES 705.1 Scope The particular requirements of this section apply to fixed electrical installations indoors

More information

C C CEILING(S) Suspended. Contents. 1. Introduction. 2. Earthing and bonding. 3. Supporting of electrical cables

C C CEILING(S) Suspended. Contents. 1. Introduction. 2. Earthing and bonding. 3. Supporting of electrical cables Contents 1. Introduction 2. Earthing and bonding 3. Supporting of electrical cables 4. Final connection to luminaires 5. Thermoplastic luminaire diffusers 6. Fire-protecting suspended ceilings 1. Introduction

More information

GN7 Amendment 3-5 Agricultural and horticultural premises

GN7 Amendment 3-5 Agricultural and horticultural premises GN7 Amendment 3-5 Agricultural and horticultural premises 5.1Introduction Amendment No. 3 to the 17th Edition Sect 705 There are no significant changes introduced in Section 705by Amendment No. 3 to the

More information

DOMESTIC ELECTRICAL INSTALLATION PERIODIC INSPECTION REPORT (FOR A SINGLE DWELLING) B ADDRESS AND DETAILS OF THE INSTALLATION Address: SPECIMEN

DOMESTIC ELECTRICAL INSTALLATION PERIODIC INSPECTION REPORT (FOR A SINGLE DWELLING) B ADDRESS AND DETAILS OF THE INSTALLATION Address: SPECIMEN A DETAILS OF THE CLIENT Client / Address: C PURPOSE OF THE REPORT Purpose for which this report is required: E PARTICULARS OF THE CONTRACTOR Trading Title: Address: DOMESTIC ELECTRICAL INSTALLATION PERIODIC

More information

To bond or not to bond: domestic swimming pools

To bond or not to bond: domestic swimming pools To bond or not to bond: domestic swimming pools With the summer sun warming our skin and tempting us into plans for weekends spent poolside, Paul Harris BEng (Hons) CEng FIHEEM MIEE MCIBSE, of Harris Associates

More information

C&G 2382 BS7671: th Edition IEE Wiring Regulations. 25 Questions

C&G 2382 BS7671: th Edition IEE Wiring Regulations. 25 Questions C&G 2382 BS7671:2008 17 th Edition IEE Wiring Regulations 25 Questions 1. BS7671 states that installation design must take into account a. current copper prices b. the effects of climate change c. a comparison

More information

Code of practice for protective earthing of electrical installations

Code of practice for protective earthing of electrical installations BS 7430:2011 Incorporating corrigendum No. 1 BSI Standards Publication Code of practice for protective earthing of electrical installations NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT

More information

Same as Client Address. 40, Havelock Close. India Way. London. Postcode: W12 7NQ

Same as Client Address. 40, Havelock Close. India Way. London. Postcode: W12 7NQ DOMESTIC ELECTRICAL INSTALLATION CONDITION REPORT Issued in accordance with British Standard BS 7671 - Requirements for Electrical Installations Certificate Reference: 1 DETAILS OF THE CLIENT 2 ADDRESS

More information

SECTION EARTHING AND EARTH FAULT PROTECTION

SECTION EARTHING AND EARTH FAULT PROTECTION SECTION 16660 PART 1 - GENERAL 1.01 DESCRIPTION A. The work to be performed includes, but is not necessarily limited to, all work involved with the construction and assembly of a complete electrical earthing

More information

Same As Client Address SPECIMEN. operational limitations. of the inspection and. agreed with):

Same As Client Address SPECIMEN. operational limitations. of the inspection and. agreed with): DOMESTIC ELECTRICAL INSTALLATION CONDITION REPORT Issued in accordance with British Standard BS 7671 - Requirements for Electrical Installations Certificate Reference: DEICR000021652 1 DETAILS OF THE CLIENT

More information

Grounding & Bounding. 1. Bonded Connected to establish electrical continuity and conductivity.

Grounding & Bounding. 1. Bonded Connected to establish electrical continuity and conductivity. & Bounding Article 100 Definitions 1. Bonded Connected to establish electrical continuity and conductivity. 2. Raceway fittings bonds sections of raceway Bonding jumper bonds receptacles to boxes Threaded

More information

Earthing in electrical network purpose, methods and measurement

Earthing in electrical network purpose, methods and measurement Earthing in electrical network purpose, methods and measurement Earth / Ground Conductive ground whose electrical potential at each point is set equal to zero, It is a conductor which provides a low impedance

More information

An Overview of Earthing

An Overview of Earthing 2018 Earthing An Overview of Earthing Gary Blackshaw, Global Business Development Manager Founded by William Joseph Furse Originally as a Steeplejack company Relocated to Traffic Street More emphasis on

More information

On successful completion of the Unit candidates will be able to carry out a simple earthing exercise on a simulated electrical installation.

On successful completion of the Unit candidates will be able to carry out a simple earthing exercise on a simulated electrical installation. National Unit Specification: general information CODE F5HE 11 SUMMARY This Unit is designed for candidates with little or no prior knowledge of earthing systems for electrical installations but who wish

More information

ELECTRICAL SAFETY Information Bulletin

ELECTRICAL SAFETY Information Bulletin ELECTRICAL SAFETY Information Bulletin February 2019 Page 1 of 8 2018 CANADIAN ELECTRICAL CODE SUBJECT: Section 10 Grounding and bonding Rule 10-102 Grounding electrodes Replacing metal water service lines

More information

Level 4 Design, Construction Management and Initial Verification of Electrical Installations Chief Examiner's report March 2018

Level 4 Design, Construction Management and Initial Verification of Electrical Installations Chief Examiner's report March 2018 2396-402 Level 4 Design, Construction Management and Initial Verification of Electrical Installations Chief Examiner's report March 2018 www.cityandguilds.com March 2018 Version 1.0 About City & Guilds

More information

Installation Address. Postcode. Purpose of the report This form to be used only for reporting on the condition of an existing installation.

Installation Address. Postcode. Purpose of the report This form to be used only for reporting on the condition of an existing installation. A B C Details of the installation Owner*/Occupier*/Customer*/ (*Delete as necessary) Only for the reporting on the condition of an existing installation Purpose for which this report is required Installation

More information

DPN6C/ CRN/ Original (To the person ordering the work) A. DETAILS OF THE CLIENT

DPN6C/ CRN/ Original (To the person ordering the work) A. DETAILS OF THE CLIENT Contractor s Reference Number CRN/ A. DETAILS OF THE CLIENT Client: Address: B. PURPOSE OF THE REPORT Purpose for which this report is required: MR M REYNARD The Old Rectory Rectory Lane Barham Canterbury

More information

FREQUENTLY ASKED QUESTIONS

FREQUENTLY ASKED QUESTIONS March 2010 FREQUENTLY ASKED QUESTIONS Wiring Rules The new edition of the Australian/New Zealand Standard for Wiring Rules (AS/NZS 3000:2007) was released in November 2007 and revised by Amendment 1 in

More information

The Equipotential Plane in New Livestock Facilities

The Equipotential Plane in New Livestock Facilities The Equipotential Plane in New Livestock Facilities Keith G. Tinsey, P.E., Truman C. Surbrook P.E. and Jonathan R. Althouse Agricultural Engineering Department Michigan State University Introduction An

More information

New Whole-Current-Metered Connections up to 60kVA

New Whole-Current-Metered Connections up to 60kVA Electricity Specification 212 Issue 4 March 2015 New Whole-Current-Metered Connections up to 60kVA Contents 1 Introduction 2 Scope 3 General 4 Connection Arrangements 5 Equipment Records 6 Documentation

More information

FREQUENTLY ASKED QUESTIONS

FREQUENTLY ASKED QUESTIONS March 2015 FREQUENTLY ASKED QUESTIONS Wiring Rules 2007 edition The sixth edition of the Australian/New Zealand Standard for Wiring Rules (AS/NZS 3000:2018) was released in June 2018 and the relevant technical

More information

GUIDELINES FOR SUB-SYSTEM COMPLETION CERTIFICATES AND TEST RECORDS FOR ELECTRICAL INSTALLATIONS IN POTENTIALLY EXPLOSIVE ATMOSPHERES

GUIDELINES FOR SUB-SYSTEM COMPLETION CERTIFICATES AND TEST RECORDS FOR ELECTRICAL INSTALLATIONS IN POTENTIALLY EXPLOSIVE ATMOSPHERES Sub-System Completion Certificate: Scope: In the case of new installations or modifications to existing installations, where part of the installation traverses hazardous areas, this Sub-system Completion

More information

AS/NZS 3000: 2018 Changes to Wiring Rules Standard

AS/NZS 3000: 2018 Changes to Wiring Rules Standard BUILDING SERVICES Ref: BCA 19-01 Current at January 2019 AS/NZS 3000: 2018 Changes to Wiring Rules Standard The new edition of AS/NZS 3000 Wiring Rules Standard (Electrical Installations) was published

More information

ElECTrICAl INSTAllATION CONDITION

ElECTrICAl INSTAllATION CONDITION ElECTrICAl INSTAllATION CONDITION report Certificate number: Registration number: (optional) Sheet SECTION A: DETAIlS Of ThE ClIENT / person OrDErINg ThE report Name... Address... SECTION b: reason for

More information

APPLICATION NOTE 6. Use of Decouplers for AC Voltage Mitigation. PART 2: DESIGN CONSIDERATIONS

APPLICATION NOTE 6. Use of Decouplers for AC Voltage Mitigation.   PART 2: DESIGN CONSIDERATIONS APPLICATION NOTE 6 Use of Decouplers for AC Voltage Mitigation Introduction AC voltage mitigation is primarily of concern when cathodically protected pipelines are adjacent to electric power distribution

More information

Lightning Protection and Trees

Lightning Protection and Trees Lightning Protection and Trees By Ben Fuest INTRODUCTION This research was established for the purpose of developing a better understanding of lightning protection systems specifically designed to be fitted

More information

BS 7671:2018 MODEL FORMS

BS 7671:2018 MODEL FORMS BS 7671:2018 MODEL FORMS Usage and Reproduction of IET Forms Subject to your agreement to the following conditions, you are permitted to, free of charge, photocopy and/or electronically manipulate the

More information

7. For items classified in Section K as C1 ( Danger

7. For items classified in Section K as C1 ( Danger NAPIT Electrical Installation Condition Report Guidance for recipients This report is an important and valuable document which should be retained for future reference. 1. The purpose this condition report

More information

7. For items classified in Section K as C1 ( Danger

7. For items classified in Section K as C1 ( Danger PIT Electrical Installation Condition Report Guidance for recipients This report is an important and valuable document which should be retained for future reference.. The purpose this condition report

More information

ELECTRICAL SAFETY Information Bulletin

ELECTRICAL SAFETY Information Bulletin ELECTRICAL SAFETY Information Bulletin March 2014 CEC-10 [rev-8] Page 1 of 8 CANADIAN ELECTRICAL CODE SUBJECT: Section 10 Grounding and Bonding Rule 10-204 Grounding Connections for Alternating-Current

More information

Guidance note Electrical Wiring Installations in Churches

Guidance note Electrical Wiring Installations in Churches Guidance note Electrical Wiring Installations in Churches Those responsible for the care of a church building need to understand the procedures for the maintenance and testing of electrical systems and

More information

The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999

The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999 CANADIAN ELECTRICAL CODE 1 The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999 Repealed by Chapter E-6.3 Reg 8 (effective June 24, 2003). Formerly Chapter E-6.3 Reg 6 (effective March

More information

ELECTRICAL SAFETY Information Bulletin

ELECTRICAL SAFETY Information Bulletin ELECTRICAL SAFETY Information Bulletin February 2019 Page 1 of 5 2018 CANADIAN ELECTRICAL CODE SUBJECT: Section 6 Services and service equipment Rule 6-102 Number of supply services permitted Row housing

More information

0.6/1 kv LOW VOLTAGE CONTROL CABLES. Conductors. Insulation. Assembly. Standard Colour Code. Armour (Optional) Screening (Optional) Outer Sheath

0.6/1 kv LOW VOLTAGE CONTROL CABLES. Conductors. Insulation. Assembly. Standard Colour Code. Armour (Optional) Screening (Optional) Outer Sheath 0.6/1 kv LOW VOLTAGE CONTROL CABLES PVC OR XLPE INSULATED, PVC SHEATHED AS PER IEC 60502-1 Conductors Conductors shall be Circular Stranded, Class 2 as per IEC 60228, BS EN 60228. Upon request, Solid Circular

More information

PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES

PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

Landlord Report Operational limitations including the reasons (see page No. ) N/A. years

Landlord Report Operational limitations including the reasons (see page No. ) N/A. years Installer s Reference Number IRN/ A. DETAILS OF THE CLIENT Client: Rosen Rentals ltd UNKNOWN Address: Issued in accordance with British Standard 61 Requirements for Electrical Installations by an ELECSA

More information

SECTION GROUNDING

SECTION GROUNDING SECTION 16450 GROUNDING PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies general grounding and bonding requirements of electrical and telecommunication installations for personnel safety, equipment

More information

Level 4 Principles, Design, Erection and Verification of Electrical Installations. Chief Examiner's report June 2018

Level 4 Principles, Design, Erection and Verification of Electrical Installations. Chief Examiner's report June 2018 2394-302 Level 4 Principles, Design, Erection and Verification of Electrical Installations. Chief Examiner's report June 2018 www.cityandguilds.com June 2018 Version 1.0 About City & Guilds City & Guilds

More information

TESTING PTE EARTHING

TESTING PTE EARTHING 1 SCOPE This section of the Power Systems Live Working Manual details the procedures to be followed to achieve Safety from the System when carrying out examination, testing and remedial work on PTE (Pole

More information

Purchase Now ANSI/ICEA S STANDARD FOR 600 VOLT SINGLE LAYER THERMOSET INSULATED UTILITY UNDERGROUND DISTRIBUTION CABLES

Purchase Now ANSI/ICEA S STANDARD FOR 600 VOLT SINGLE LAYER THERMOSET INSULATED UTILITY UNDERGROUND DISTRIBUTION CABLES ANSI/ICEA S-05-692 STANDARD FOR 600 VOLT SINGLE LAYER THERMOSET INSULATED UTILITY UNDERGROUND DISTRIBUTION CABLES Approved as an American National Standard ANSI Approval Date: 9/29/ ANSI/ICEA Publication

More information

Grounding Principles. The need to ground! Definitions. Introduction. Grounding Codes and Standards. 2 Ph:

Grounding Principles. The need to ground! Definitions. Introduction. Grounding Codes and Standards. 2 Ph: Introduction Grounding and bonding are an integral part of any modern electrical protection system design. An effective, low-impedance ground system is a key element of this system. It is crucial in ensuring

More information

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS SECTION 26 05 26 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.1 DESCRIPTION A. Scope: 1. CONTRACTOR shall provide labor, materials, equipment, and incidentals as shown, specified, and

More information

Engineering Data for Copper and Aluminum Conductor Electrical Cables

Engineering Data for Copper and Aluminum Conductor Electrical Cables 2018 Edition Engineering Data for Copper and Aluminum Conductor Electrical Cables THE OKONITE COMPANY Okonite Cables...A higher Standard! The Okonite Company, 2018 Okonite Cables Table of Contents SECTION

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 5/12/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 5/12/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 5/12/10 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. Is it illegal to install a wet-niche luminaire face-up

More information

These Electricity Safety Rules and associated National Safety Instructions are written to safeguard personnel working for or on behalf of National

These Electricity Safety Rules and associated National Safety Instructions are written to safeguard personnel working for or on behalf of National These Electricity Safety Rules and associated National Safety Instructions are written to safeguard personnel working for or on behalf of National Grid, on or near to its electricity apparatus. National

More information

PARTICULAR SPECIFICATION E11: GENERAL ELECTRICAL EARTHING AND LIGHTNING PROTECTION

PARTICULAR SPECIFICATION E11: GENERAL ELECTRICAL EARTHING AND LIGHTNING PROTECTION E11 : General Electrical Earthing and LIGHTNING Protection PARTICULAR SPECIFICATION E11: GENERAL ELECTRICAL EARTHING AND LIGHTNING PROTECTION 1 2009-05-12 Review of Mechanical / Electrical and Control

More information

Rise of Earth Potential at Electricity Stations

Rise of Earth Potential at Electricity Stations ISIS practice For BT People TEPT/PPS/B012T Issue 7, 7-Dec-2007 Published by Openreach, NCAD Rise of Earth Potential at Electricity Stations About this document... About this document... Author The author

More information

Substation Grounding. Presented by: Bruce Kayser, PE Assisted by Danny Seele

Substation Grounding. Presented by: Bruce Kayser, PE Assisted by Danny Seele Substation Grounding Presented by: Bruce Kayser, PE 785-633-5756 Assisted by Danny Seele Introduction Bruce Kayser, PE BSEE from KSU in 1989 Licensed Professional Engineer in KS Employed by ElectriComm,

More information

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 DESCRIPTION SECTION 28 05 26 GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY SPEC WRITER NOTE: Delete // // if not applicable to project. Also delete any other item or paragraph

More information

Estimation of Corrosion Protection Condition on Buried Steel Pipeline under Cathodic Protection with IR-free Probe

Estimation of Corrosion Protection Condition on Buried Steel Pipeline under Cathodic Protection with IR-free Probe WP3-6 Estimation of Corrosion Protection Condition on Buried Steel Pipeline under Cathodic Protection with IR-free Probe Akinobu Nishikawa, Masahiro Sawai and Hidemasa Nonaka Osaka Gas Co., Ltd. JAPAN

More information

ELECTRICAL WORKS IN CHURCHES Guidance note from the Diocesan Advisory Committee for the Care of Churches 2016

ELECTRICAL WORKS IN CHURCHES Guidance note from the Diocesan Advisory Committee for the Care of Churches 2016 ELECTRICAL WORKS IN CHURCHES Guidance note from the Diocesan Advisory Committee for the Care of Churches 2016 These are basic guidelines intended for PCCs to make available to specifiers and electrical

More information

Code of Practice for Electrical Safety in Beer Dispense in Licensed Premises 2011

Code of Practice for Electrical Safety in Beer Dispense in Licensed Premises 2011 Fourth Edition April 2011 Code of Practice for Electrical Safety in Beer Dispense in Licensed Premises 2011 Issued by the British Beer and Pub Association 1 Contents Preface 5 1. Introduction 7 1.1 General

More information

A guide to our training courses and premises.

A guide to our training courses and premises. A guide to our training courses and premises 01444 872 145 www.electriciancourses4u.co.uk Contents 3. About Us 4. Why Us? 5. Our Premises 6-13. Training Courses 6. Domestic Electrician Course 7. Domestic

More information

Insulated sheath power cable systems

Insulated sheath power cable systems PRODUCED BY THE OPERATIONS DIRECTORATE OF ENERGY NETWORKS ASSOCIATION Engineering Recommendation C55 Insulated sheath power cable systems www.energynetworks.org PUBLISHING AND COPYRIGHT INFORMATION 2014

More information

2015 Code Rollout Meeting Q & A

2015 Code Rollout Meeting Q & A 1 SECTION QUESTION SaskPower Inspections Dept. ANSWER 2 3 4 5 6 7 8 9 10 11 12 15-02-024 15-02-200 15-02-200 15-02-200 15-02-314 Are existing single or double 'weather proof when not in use' covers allowed

More information

GB Translated English of Chinese Standard: GB NATIONAL STANDARD OF THE PEOPLE S REPUBLIC OF CHINA

GB Translated English of Chinese Standard: GB NATIONAL STANDARD OF THE PEOPLE S REPUBLIC OF CHINA Translated English of Chinese Standard: GB50169-2016 www.chinesestandard.net Buy True-PDF Auto-delivery. Sales@ChineseStandard.net GB NATIONAL STANDARD OF THE PEOPLE S REPUBLIC OF CHINA UDC P GB 50169-2016

More information

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL). 16450 GROUNDING ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 05 26 An optional keynote to the

More information

THATCH STRUCTURES LIGHTNING PROTECTION INNOVATION ISOLATED LIGHTNING PROTECTION USING HVI CONDUCT

THATCH STRUCTURES LIGHTNING PROTECTION INNOVATION ISOLATED LIGHTNING PROTECTION USING HVI CONDUCT THATCH STRUCTURES LIGHTNING PROTECTION INNOVATION ISOLATED LIGHTNING PROTECTION USING HVI CONDUCTORS PREPARED BY : LIGHTNING PROTECTION CONCEPTS PONTINS REFERENCE : D001-THATCH-051 ISSUE : A DATE : 4 March

More information

Level 3 Principles, Practices and Legislation for the Periodic Inspection, Testing and Condition Reporting of Electrical Installations.

Level 3 Principles, Practices and Legislation for the Periodic Inspection, Testing and Condition Reporting of Electrical Installations. 2395-302 Level 3 Principles, Practices and Legislation for the Periodic Inspection, Testing and Condition Reporting of Electrical Installations. www.cityandguilds.com December 2017 Version 1.0 Chief Examiner

More information

NPS/002/020 Technical Specification for 11 & 20kV Power Cables

NPS/002/020 Technical Specification for 11 & 20kV Power Cables Version:- 3.1 of Issue:- Nov - 09 Page 1 of 11 NPS/002/020 Technical Specification for 11 & 20kV Power Cables 1. Purpose The purpose of this document is to detail Northern Powergrid (the Company) requirements

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Date Description of Change Pages / Sections Modified ID 6/15/16 Updated format, division title, and removed references to other sections. - mgl44 A. Summary This section contains design criteria for the

More information

Level 3 Principles, Practices and Legislation for the Periodic Inspection, Testing and Condition Reporting of Electrical Installations.

Level 3 Principles, Practices and Legislation for the Periodic Inspection, Testing and Condition Reporting of Electrical Installations. 2395-302 Level 3 Principles, Practices and Legislation for the Periodic Inspection, Testing and Condition Reporting of Electrical Installations. www.cityandguilds.com April 2015 Version 1.0 Chief Examiner

More information

Toolkit 2 - Apprentice Training and Profiling

Toolkit 2 - Apprentice Training and Profiling Attachment 3 Toolkit 2 - Apprentice Training and Profiling Page 1 The Apprentice Training and Profiling Tool has been developed to support Apprentice Training that best suit business needs and the needs

More information

Fixings, bonds and clamps

Fixings, bonds and clamps Square tape clamp Material 25 x 3mm Copper 0.12kg CT105-H 25 x 6mm Copper 0.30kg CT110-H 50 x 6mm Copper 0.60kg CT115-H Manufactured from high quality copper and aluminium alloys. Simple to install, providing

More information

Interpretation. Section 23. Clearances

Interpretation. Section 23. Clearances Interpretation Section 23. Clearances Rule 232.A. Table 1 Vertical clearance of wires above ground or rails Basic clearances Minimum vertical clearance of wires above ground or rails (1961, 6th Edition;

More information

EFFECTIVE DATE: November 1, 2011, unless a later date is cited at the end of a section. [ NMAC - Rp,

EFFECTIVE DATE: November 1, 2011, unless a later date is cited at the end of a section. [ NMAC - Rp, TITLE 14 CHAPTER 10 PART 4 HOUSING AND CONSTRUCTION ELECTRICAL CODES 2011 NEW MEXICO ELECTRICAL CODE 14.10.4.1 ISSUING AGENCY: The Construction Industries Division of the Regulation and Licensing Department.

More information

Energy Conservation and Transformation

Energy Conservation and Transformation Next Generation Science Standards NGSS Science and Engineering Practices: Asking questions and defining problems Developing and using models Planning and carrying out investigations Analyzing and interpreting

More information

Electrical installations Marinas and boats

Electrical installations Marinas and boats AS/NZS 3004.2:2014 Incorporating Amendment No. 1 Australian/New Zealand Standard Electrical installations Marinas and boats Part 2: Boat installations Superseding AS/NZS 3004.2:2008 AS/NZS 3004.2:2014

More information

Ensure no person makes contact with the steel pole streetlight or temporary earth electrode while the testing procedures are being undertaken.

Ensure no person makes contact with the steel pole streetlight or temporary earth electrode while the testing procedures are being undertaken. NOTE: SAFETY: Tests must be carried out after the installation, alteration or repair and before putting back to service. At all times maintain suitable clearance to all other electrical equipment and verify

More information

Part I. Design of Electrical Installation Systems

Part I. Design of Electrical Installation Systems Part I Design of Electrical Installation Systems Chapter 1 Regulations Governing Electrical Installations Whatever type of electrical equipment is installed, it has to be connected by means of cables and

More information

TracPipe CounterStrike White Paper. The Best Gets Better: TracPipe CounterStrike. Page 1 of 7. FGP-611G 09/11 Omega Flex Inc.

TracPipe CounterStrike White Paper. The Best Gets Better: TracPipe CounterStrike. Page 1 of 7. FGP-611G 09/11 Omega Flex Inc. TracPipe CounterStrike White Paper The Best Gets Better: TracPipe CounterStrike FGP-611G 09/11 Omega Flex Inc. Page 1 of 7 Patented Protection Against Arcing From Lightning Strikes Lightning is unpredictable;

More information

Cable Jointing Manual. Jointing Procedures. Module 18. Concentric Cables

Cable Jointing Manual. Jointing Procedures. Module 18. Concentric Cables Cable Jointing Manual Jointing Procedures Module 18 Concentric Cables Version: 1.0 Date of Issue: June 2008 Author: Richard Summers Job Title: Cables Specialist Approver: Keith Nutter Job Title: Network

More information

Technical Seminar for Cathodic Protection to GOGC Design Unit Specialists. Dr. Nick Kioupis, Cathodic & Lightning Protection Section Head, DESFA

Technical Seminar for Cathodic Protection to GOGC Design Unit Specialists. Dr. Nick Kioupis, Cathodic & Lightning Protection Section Head, DESFA Technical Seminar for Cathodic Protection to GOGC Design Unit Specialists Dr. Nick Kioupis, Cathodic & Lightning Protection Section Head, DESFA Cathodic protection of complex structures is protection applicable

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION TECHNICAL SPECIFICATION IEC/TS 62344 Edition 1.0 2013-01 colour inside Design of earth electrode stations for high-voltage direct current (HVDC) links General guidelines INTERNATIONAL ELECTROTECHNICAL

More information

Factors Affecting Current Ratings for Underground and Air Cables

Factors Affecting Current Ratings for Underground and Air Cables Factors Affecting Current Ratings for Underground and Air Cables S. H. Alwan, J. Jasni, M. Z. A. Ab Kadir, N. Aziz Abstract The aim of this paper is to present a parametric study to determine the major

More information

CERTIFICATE OF ACCREDITATION

CERTIFICATE OF ACCREDITATION CERTIFICATE OF ACCREDITATION In terms of section 22(2)(b) of the Accreditation for Conformity Assessment, Calibration and Good Laboratory Practice Act, 2006 (Act 19 of 2006), read with sections 23(1),

More information

SECTION PART 1 GENERAL

SECTION PART 1 GENERAL SECTION 16060 GROUNDING AND BONDING PART 1 GENERAL 1.1 SUMMARY A. Section Includes: Grounding of electrical systems and equipment and basic requirements for ground for equipment, circuits, and systems.

More information

ROAD LIGHTING ELECTRICIAL INSTALLATION CERTIFICATE. (Requirements for Electrical Installations BS7671 (IET Wiring Regulations) (1) (See notes page 6)

ROAD LIGHTING ELECTRICIAL INSTALLATION CERTIFICATE. (Requirements for Electrical Installations BS7671 (IET Wiring Regulations) (1) (See notes page 6) CC10 ROAD LIGHTING ELECTRICIAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS7671 (IET Wiring Regulations) (1) (See notes page 6) Reference Number Details of the Installation New

More information

Induced currents in gas pipelines due to nearby power lines

Induced currents in gas pipelines due to nearby power lines University of Wollongong Research Online University of Wollongong Thesis Collection 1954-2016 University of Wollongong Thesis Collections 2005 Induced currents in gas pipelines due to nearby power lines

More information

SECTION LIGHTNING PROTECTION SYSTEM

SECTION LIGHTNING PROTECTION SYSTEM SECTION 16670 - LIGHTNING PROTECTION SYSTEM PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Stack Parking Surface Mounted Stackers

Stack Parking Surface Mounted Stackers 1 / 6 Stack Parking Surface Mounted Stackers swiss-park V-2 Comfort The V-2 is designed to park cars of any size thanks to its vertical adjustability. It will accommodate cars as tall as the garage ceiling

More information

DESIGN OF MV OVERHEAD LINES TO MAXIMISE BIRD SAFETY

DESIGN OF MV OVERHEAD LINES TO MAXIMISE BIRD SAFETY DESIGN OF MV OVERHEAD LINES TO MAXIMISE BIRD SAFETY Andreas BEUTEL BeutelAA@eskom.co.za Bruce MCLAREN mlarenb@eskom.co.za Hendri GELDENHUYS GeldenHJ@eskom.co.za John VAN COLLER University of the Witwatersrand

More information

ELECTRICAL SAFETY Information Bulletin

ELECTRICAL SAFETY Information Bulletin ELECTRICAL SAFETY Information Bulletin March 2014 CEC-12 [rev-6] Page 1 of 6 CANADIAN ELECTRICAL CODE SUBJECT: Section 12 Wiring Methods Conductors General Insulation Thickness on Conductors Used in Ungrounded

More information

CHAPTER 13 GROUNDING AND BONDING

CHAPTER 13 GROUNDING AND BONDING GROUNDING AND BONDING CHAPTER 13 GROUNDING AND BONDING Grounding and bonding must be in accordance with Article 250 of the National Electrical Code (NEC). Bonding is defined in the NEC as the permanent

More information

Earthing of Utility and Industrial Distribution Systems

Earthing of Utility and Industrial Distribution Systems Earthing of Utility and Industrial Distribution Systems YOU WILL LEARN: 4 hour live, practical online course The basic principles of grounding of electrical systems The function of power system grounding

More information

Specifications for Residential Overhead Electric Service Installation

Specifications for Residential Overhead Electric Service Installation Specifications for Residential Overhead Electric Service Installation This brochure addresses most typical residential overhead service installations. Variances for the following specifications must be

More information

ABSTRACT EXECUTIVE SUMMARY

ABSTRACT EXECUTIVE SUMMARY MIE TALK August 2016 Compiled by: Schalk J. P. Kruger ABSTRACT Corrosion is a major issue in industrial plant processes especially where any part of the structure is submerged in ground or water. The management

More information

SABO EARTHING SOLUTION

SABO EARTHING SOLUTION SABO SABO EARTHING SOLUTION The installation and maintenance of an effective low resistance earthing system is essential due to the following- - Efficiently dissipate heavy fault currents and electrical

More information

7. For items classified in Section K as C1 ( Danger

7. For items classified in Section K as C1 ( Danger NAPIT Electrical Installation Condition Report Guidance for recipients This report is an important and valuable document which should be retained for future reference.. The purpose this condition report

More information

ELECTRICAL INSTALLATION DESIGN Three Day Course with option to achieve BTEC Advanced Award

ELECTRICAL INSTALLATION DESIGN Three Day Course with option to achieve BTEC Advanced Award ELECTRICAL INSTALLATION DESIGN Three Day Course with option to achieve BTEC Advanced Award INTRODUCTION This course is aimed at the needs of designers, specifiers and others involved in the design and

More information

Training Certification Categories

Training Certification Categories Training Certification Categories Residential Residential Building Inspector structures are free from hazardous structural conditions and comply with the UCC. Duties include inspection of footings and

More information

OPTIONS FOR SHOWING ELECTRICAL INSTALLATION COMPETENCE

OPTIONS FOR SHOWING ELECTRICAL INSTALLATION COMPETENCE OPTIONS FOR SHOWING ELECTRICAL INSTALLATION COMPETENCE The following is provided as a guide to the different ways in which any electrical work undertaken can be certified. If an Approved Certifier of Construction

More information

Pro-Heat Plumbing & Heating Ltd How to get the most out of working with us

Pro-Heat Plumbing & Heating Ltd How to get the most out of working with us Pro-Heat Plumbing & Heating Ltd How to get the most out of working with us Thank you for asking us to quote for your plumbing work. Before you ask us to go ahead, however, there are a few important things

More information

Field Instruction. Any part of a person (body). Any conducting object, tool or equipment being held or carried.

Field Instruction. Any part of a person (body). Any conducting object, tool or equipment being held or carried. 2.17 Safe Approach Distances Purpose This instruction outlines the safe approach distances (SAD) for authorised Horizon Power Workers, Mobile Plant and Vehicles working near live electrical apparatus.

More information

IOM3 Underground Seminar. Health and Safety Laboratory Buxton. 27 May 2010

IOM3 Underground Seminar. Health and Safety Laboratory Buxton. 27 May 2010 IOM3 Underground Seminar Health and Safety Laboratory Buxton 27 May 2010 Applications and Limitations of Cathodic Protection within Plants Dave Harvey CEng, FICorr Engineering Manager Pipeline Maintenance

More information

Electrical Protection Methods and Devices SAMPLE. Learner Workbook Version 1. Training and Education Support Industry Skills Unit Meadowbank

Electrical Protection Methods and Devices SAMPLE. Learner Workbook Version 1. Training and Education Support Industry Skills Unit Meadowbank Electrical Protection Methods and Devices Learner Workbook Version 1 Training and Education Support Industry Skills Unit Meadowbank Product Code: 5635 Table of Contents Introduction... 5 1. Protection

More information

General instructions on lightning protection for shelters

General instructions on lightning protection for shelters 928 General instructions on lightning protection for shelters About 1.5 million lightning incidents are registered in Germany each year. Lightning is fascinating to watch, but also extremely dangerous.

More information

MEDIUM VOLTAGE XLPE INSULATED POWER CABLES [6.35/11kV Copper XLPE Three-Core HDPE Sheathed]

MEDIUM VOLTAGE XLPE INSULATED POWER CABLES [6.35/11kV Copper XLPE Three-Core HDPE Sheathed] [6.35/11kV Copper XLPE Three-Core HDPE Sheathed] APPLICATION Mostly used as feeder electric cable for power distribution network such as power supply station, substation, switching system etc. They are

More information

Ontario ENGINEERING STANDARD SPECIFICATION 1/10 REV. ELECTRICAL DISTRIBUTION HIGH VOLTAGE SUBSTATION GROUNDING AND BONDING. Approved by.

Ontario ENGINEERING STANDARD SPECIFICATION 1/10 REV. ELECTRICAL DISTRIBUTION HIGH VOLTAGE SUBSTATION GROUNDING AND BONDING. Approved by. /0 Rev Description Revision by Approved by Issue Date YYYY/MM/DD New Format Replaces 5322-0.0. T.C. 206/02/09 T.C. 206/03/02 206/03/02 2/0.0 PURPOSE This specification describes the minimum requirements

More information