PCM Installation at Three National Parks Initial Results Brian L. Cook National Park Service August 10, 2016

Size: px
Start display at page:

Download "PCM Installation at Three National Parks Initial Results Brian L. Cook National Park Service August 10, 2016"

Transcription

1 Session: Phase Change Material for Building Envelope PCM Installation at Three National Parks Initial Results Brian L. Cook National Park Service August 10, 2016 Rhode Island Convention Center Providence, Rhode Island

2 Introduction Tested phase change material, BioPCM TM, to vet as an energy conservation measure. Locations tested The Great Smoky Mountains National Park (GRSM, Gatlinburg, TN) Horseshoe Bend National Military Park (HOBE, Daviston, Alabama) Timucuan Ecological & Historic Preserve (TIMU, Jacksonville, FL) 2

3 Summary Results GRSM 11% increase in heating efficiency 13% increase in cooling efficiency TIMU 2.5% increase in cooling efficiency Heating efficiency not tested HOBE 1.3% decrease in cooling efficiency Heating efficiency not tested 3

4 GRSM: Photographs 4

5 GRSM: Methodology and Results Maintenance Breakroom Building, approximately 3,800 ft 2 facility with 2,400 ft 2 of BioPCM TM coverage March 2, BioPCM TM installed Above 5/8 acoustic tile Failed attempt at calculations, realized hobo loggers were needed to calculate the baseline. May 23, Hobo data loggers installed on HVAC units and baseline calculated. May 27 to July 13, Post-BioPCM TM data collected a total of 6 weeks and 5 days 5

6 GRSM: Methodology and Results Since hobo loggers were not installed pre- BioPCM TM installation, we used the following strategy to assess effectiveness. Baseline kwh calculated by [Metered kwh] - [Monthly HVAC kwh by hobo loggers]. Pre-install and post-install months with the closest CDD and HDD identified, and kwh/dd compared to assess efficiency. 6

7 GRSM: Methodology and Results Pre-installation and post-installation months with closest degree day (DD) totals were compared Results Heating 11.0% more efficient Cooling 13.1% more efficient 7

8 TIMU: Photographs 8

9 TIMU: Methodology and Results Ranger Station, an approximately 1,000 ft 2 building section with 500 ft 2 of BioPCM TM coverage May 26, Hobo data loggers installed on air conditioning unit June 16, BioPCM TM installed June 18 to July 10, Post BioPCM TM installation data collected, a total of 3 weeks and 1 day 9

10 TIMU: Methodology and Results Results: 2.5% more efficient 10

11 TIMU: Discussion of Results 11

12 TIMU: Discussion of Results 12

13 TIMU: Discussion of Results Need to control thermostat and behavior It was discovered on June 17 th that the thermostat setting had been changed from 74 to 70 the previous day due to a meeting. For this reason we did not use the data from June 16 th and June 17 th. Data suggested similar sudden increases in HVAC usage that would have confused product performance. Pre-install data (see regression analysis next slide) indicated a moderate relationship between CDD and kwh More data logging time needed to devalue some of the natural data fluctuation 13

14 TIMU: Discussion of Results Pre-Installation CDD, kwh, and kwh/cdd 14

15 HOBE: Photographs 15

16 HOBE: Methodology and Results Ranger Station, a 936 ft 2 building with 450 ft 2 of BioPCM TM coverage. May 25, Hobo data loggers affixed to air conditioning unit June 14, BioPCM TM installed June 15 to July 10, Post BioPCM TM installation data collected, a total of 3 weeks and 4 days. 16

17 HOBE: Methodology and Results Results: 1.3% less efficient 17

18 HOBE: Discussion of Results 18

19 HOBE: Discussion of Results Post Installation HVAC Regression Total kwh Linear (Total kwh) y = x R² = HVAC KWH CDD 65 19

20 HOBE: Discussion of Results Need to control thermostat and behavior Building wasn t controlled during the testing period and issues such as manipulation of the thermostat (i.e., occupants changing thermostat setpoints), changing usage patterns such as meetings in the space, increased occupancy after hours could have caused this. More data logging time needed to devalue some of the natural data fluctuation Post-installation weather was 25% hotter than preinstallation weather. Because regression analyses R 2 values so poor, reject conclusions. 20

21 Conclusions The GRSM and TIMU studies were both of value, and indicated BioPCM should be considered as an energy conservation measure. The pre-installation data at HOBE was poor and the study s results were not of value. Higher confidence in results by: Controlling building operations (thermostat, employee behavior, etc.) Longer duration of studies to collect more data 21

22 Questions Brian Cook National Park Service Southeast Region Environmental Management Branch Chief

Building Performance Energy Assessment

Building Performance Energy Assessment Building Performance Energy Assessment Site Owner: United States Post Office Audit Site: 420 N. Twin Oaks Valley Rd. San Marcos, CA 92069 Performed by: Phase Change Energy Solutions 120 East Pritchard

More information

Benchmarking EPA Portfolio Manager and Energy Star Certification

Benchmarking EPA Portfolio Manager and Energy Star Certification Benchmarking EPA Portfolio Manager and Energy Star Certification 1 What is Benchmarking? Energy Benchmarking is the practice of comparing any given building to similar buildings for the purpose of evaluating

More information

AN INTRODUCTION TO WEATHER NORMALIZATION OF UTILITY BILLS FOR ALTERNATIVE ENERGY CONTRACTORS. John Avina, Director Abraxas Energy Consulting

AN INTRODUCTION TO WEATHER NORMALIZATION OF UTILITY BILLS FOR ALTERNATIVE ENERGY CONTRACTORS. John Avina, Director Abraxas Energy Consulting AN INTRODUCTION TO WEATHER NORMALIZATION OF UTILITY BILLS FOR ALTERNATIVE ENERGY CONTRACTORS John Avina, Director Abraxas Energy Consulting UTILITY BILL TRACKING: THE REPORT CARD FOR ALTERNATIVE ENERGY

More information

Building Performance Energy Assessment

Building Performance Energy Assessment Building Performance Energy Assessment Site Owner: United States Post Office Audit Site: 420 N. Twin Oaks Valley Rd. San Marcos, CA 92069 Performed by: Phase Change Energy Solutions 120 East Pritchard

More information

Supplemental Data for California Smart Thermostat Work Paper

Supplemental Data for California Smart Thermostat Work Paper Supplemental Data for California Smart Thermostat Work Paper Large scale analysis of the efficiency of Nest customer thermostat set point schedules with projected heating and cooling savings compared to

More information

Paying Your Fair Share A Billing Analysis and Literature Review of Condominium Submetering

Paying Your Fair Share A Billing Analysis and Literature Review of Condominium Submetering Paying Your Fair Share A Billing Analysis and Literature Review of Condominium Submetering Jenny Fraser, Evergreen Economics Chris Ann Dickerson, CAD Consulting Merissa Sakuda, Hawaii Public Utilities

More information

Phase Change Materials

Phase Change Materials [STRATEGY] BRIEF DESCRIPTION Phase change materials (PCMs) are materials that are capable of absorbing and releasing thermal energy when they undergo a phase change from solid to liquid and from liquid

More information

Energy Management Strategies for MURB & Commercial Buildings. Konrad Seemann PL Consulting Corp CEM,CBCP,CEP,CMVP

Energy Management Strategies for MURB & Commercial Buildings. Konrad Seemann PL Consulting Corp CEM,CBCP,CEP,CMVP Energy Management Strategies for MURB & Commercial Buildings Konrad Seemann PL Consulting Corp CEM,CBCP,CEP,CMVP Utilizing an ASHRAE LEVEL 2 Energy Audit An Energy Audits executive summary will give you

More information

FROM: Dan Rubado, Evaluation Project Manager, Energy Trust of Oregon; Phil Degens, Evaluation Manager, Energy Trust of Oregon

FROM: Dan Rubado, Evaluation Project Manager, Energy Trust of Oregon; Phil Degens, Evaluation Manager, Energy Trust of Oregon September 2, 2015 MEMO FROM: Dan Rubado, Evaluation Project Manager, Energy Trust of Oregon; Phil Degens, Evaluation Manager, Energy Trust of Oregon TO: Marshall Johnson, Sr. Program Manager, Energy Trust

More information

EnergyCAP Cost Avoidance Formula Validation

EnergyCAP Cost Avoidance Formula Validation EnergyCAP Cost Avoidance Formula Validation This document describes and illustrates the formulas used by the EnergyCAP software to perform cost avoidance calculations Table of Contents Formula # F1...

More information

FINAL REPORT EXECUTIVE SUMMARY

FINAL REPORT EXECUTIVE SUMMARY Search for CM comment: to find my comments. FINAL REPORT EXECUTIVE SUMMARY Field Monitoring and Hourly Simulation of Energy and Demand Savings from Use of the Telkonet SS5000 System Hotel HAC Occupancy

More information

M&V Fundamentals & the International Performance Measurement and Verification Protocol

M&V Fundamentals & the International Performance Measurement and Verification Protocol M&V Fundamentals & the International Performance Measurement and Verification Protocol What is M&V? Measurement & Verification (M&V) is the process of using measurements to reliably determine actual saving

More information

Healthcare Facilities: Planning for Increasing Extreme Heat Events

Healthcare Facilities: Planning for Increasing Extreme Heat Events Proceedings of the 014 Industrial and Systems Engineering Research Conference Y. Guan and H. Liao, eds. Healthcare Facilities: Planning for Increasing Extreme Heat Events Ahmad Rabanimotlagh, Michael Overcash,

More information

A Look Inside the Eye on the Wall: Sub-metering Data Analysis and Savings Assessment of the Nest Learning Thermostat

A Look Inside the Eye on the Wall: Sub-metering Data Analysis and Savings Assessment of the Nest Learning Thermostat A Look Inside the Eye on the Wall: Sub-metering Data Analysis and Savings Assessment of the Nest Learning Thermostat ABSTRACT Phillip Kelsven, Bonneville Power Administration Robert Weber, Bonneville Power

More information

Truing-Up to Billing Data

Truing-Up to Billing Data Truing-Up to Billing Data The Imperative for Accurate Software Estimations Dave Beaulieu- CSG Ethan MacCormick- PSD Presenters Ethan MacCormick Dave Beaulieu Description: This session will provide concrete

More information

Retro-commissioning and on-going commissioning 23 November 2016

Retro-commissioning and on-going commissioning 23 November 2016 Retro-commissioning and on-going commissioning 23 November 2016 1 CONTENTS 1. Needs for Retro-Commissioning (RCx) 2. Retro-Commissioning (RCx) Definition and Scope 3. Briefing of RCx Process 4. Alternative

More information

7 Measurement and Verification for Generic Variable Loads

7 Measurement and Verification for Generic Variable Loads 7 Measurement and Verification for Generic Variable Loads 7 Measurement and Verification for Generic Variable Loads 7.1 Overview Projects that improve the efficiency of end-uses that exhibit variable energy

More information

Multifamily Impact Evaluation. National Grid Rhode Island

Multifamily Impact Evaluation. National Grid Rhode Island Multifamily Impact Evaluation National Grid Rhode Island KEMA, Inc. January 12, 2016 Table of Contents 1 INTRODUCTION AND STUDY OBJECTIVES... 1 1.1 PROGRAM DESCRIPTION AND PARTICIPATION...1 1.2 2013 PROGRAM

More information

Measurement & Verification for Performance Contracts Through Rebuild Colorado. January Rebuild Colorado

Measurement & Verification for Performance Contracts Through Rebuild Colorado. January Rebuild Colorado Measurement & Verification for Performance Contracts Through Rebuild Colorado January 2005 Rebuild Colorado A Program of the Governor's Office of Energy Management and Conservation 225 East 16th Avenue

More information

PROVING THE SAVINGS: MEASUREMENT & VERIFICATION

PROVING THE SAVINGS: MEASUREMENT & VERIFICATION METERING BILLING CRM/CIS CONFERENCE 2005 Le Meridien at Rialto, Melbourne Australia 16 March 2005 PROVING THE SAVINGS: MEASUREMENT & VERIFICATION Presented by Fred Nicolosi Copyright 2004 Energy Decisions

More information

June 4, 2009 Dave Moser, PE, Senior Engineer Portland Energy Conservation, Inc.

June 4, 2009 Dave Moser, PE, Senior Engineer Portland Energy Conservation, Inc. Time Savers for Energy Savers: Available EBCx Tools and Resources Based on Natural Resources Canada s Assessment (March 2009) Existing Building Cx for Energy Savings June 4, 2009 Dave Moser, PE, Senior

More information

ENRG Blanket goes to work immediately to save energy costs and reduce carbon emissions.

ENRG Blanket goes to work immediately to save energy costs and reduce carbon emissions. ENRG Blanket goes to work immediately to save energy costs and reduce carbon emissions ENRG Blanket is a proven and cost-effective means to reduce energy consumption. It works together with traditional

More information

ComEd Energy Efficiency Incentives

ComEd Energy Efficiency Incentives ComEd Energy Efficiency Incentives 2016June16 C O N F I D E N T I A L Agenda ü ComEd Overview ü Background of Energy Efficiency ü Commercial and Industrial Program Elements 2 ComEd ü ComEd is an electric

More information

NYSERDA High Performance Development Challenge Energy Monitoring Report Hudson Passive Project

NYSERDA High Performance Development Challenge Energy Monitoring Report Hudson Passive Project NYSERDA High Performance Development Challenge Energy Monitoring Report Hudson Passive Project The participating home is a single family detached home in Hudson, NY. The house was completed and occupied

More information

Is More Always Better? A Comparison of Billing Regression Results Using Monthly, Daily and Hourly AMI Data

Is More Always Better? A Comparison of Billing Regression Results Using Monthly, Daily and Hourly AMI Data Is More Always Better? A Comparison of Billing Regression Results Using Monthly, Daily and Hourly AMI Data John Cornwell, Evergreen Economics, Portland, OR Stephen Grover, Evergreen Economics, Portland,

More information

Incentives. After work is complete:

Incentives. After work is complete: SAVE your WAY Create your own Energy Demand Savings with OUC s Commercial & Industrial Custom Incentive Program Overview OUC is committed to helping your business become more energy efficient. We understand

More information

National Grid of New York Niagara Mohawk, Brooklyn Union Gas (KEDNY), Keyspan Long Island (KEDLI)

National Grid of New York Niagara Mohawk, Brooklyn Union Gas (KEDNY), Keyspan Long Island (KEDLI) National Grid of New York Niagara Mohawk, Brooklyn Union Gas (KEDNY), Keyspan Long Island (KEDLI) EnergyWise and Residential Products Programs: Impact Evaluation Summary Prepared by: DNV KEMA, February

More information

Field Test of Cold Climate Air Source Heat Pumps

Field Test of Cold Climate Air Source Heat Pumps CASE STUDY 1 June 2018 Field Test of Cold Climate Air Source Heat Pumps BACKGROUND This field study is an extension of the recently completed CARD field study of flex fuel and ductless cold climate air

More information

Characteristics of Energy Consumption by building type of a U.S. Navy Installation in Hot and Humid Climate

Characteristics of Energy Consumption by building type of a U.S. Navy Installation in Hot and Humid Climate Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 216 Characteristics of Energy Consumption by building type of a U.S. Navy Installation

More information

ENERGY STAR Performance Ratings Technical Methodology for Medical Office Building

ENERGY STAR Performance Ratings Technical Methodology for Medical Office Building ENERGY STAR Performance Ratings Technical Methodology for Medical Office Building This document presents specific details on the EPA s analytical result and rating methodology for Medical Office Building.

More information

MEASUREMENT AND VERIFICATION GUIDELINES FOR RETROFIT AND NEW CONSTRUCTION PROJECTS

MEASUREMENT AND VERIFICATION GUIDELINES FOR RETROFIT AND NEW CONSTRUCTION PROJECTS EL PASO ELECTRIC COMPANY S LARGE COMMERCIAL AND INDUSTRIAL STANDARD OFFER PROGRAM MEASUREMENT AND VERIFICATION GUIDELINES FOR RETROFIT AND NEW CONSTRUCTION PROJECTS This document includes detailed information

More information

The following is attached for paperless electronic filing: Official Exhibits of the National Housing Trust. Sincerely,

The following is attached for paperless electronic filing: Official Exhibits of the National Housing Trust. Sincerely, October 5, 2017 Ms. Kavita Kale Michigan Public Service Commission 7109 W. Saginaw Hwy. P. O. Box 30221 Lansing, MI 48909 Via E-filing RE: MPSC Case No. U-18261 Dear Ms. Kale: The following is attached

More information

Energy Assessment Report Clayville Elementary School DRAFT October George Washington Highway, Clayville, RI DRAFT

Energy Assessment Report Clayville Elementary School DRAFT October George Washington Highway, Clayville, RI DRAFT Report Clayville Elementary School October 2016 3 George Washington Highway, Clayville, RI 02815 Clayville Elementary School Summary of Findings On behalf of the School Building Authority at Rhode Island

More information

Project Measurement and Verification Procedures

Project Measurement and Verification Procedures Project and Verification Procedures 1) Introduction The objective of measurement and verification (M&V) activities at the Project level is to confirm that the Measures that are supported by the Retrofit

More information

Technical Reference. Portfolio Manager ENERGY STAR. Parking and the ENERGY STAR Score in the United States and Canada OVERVIEW

Technical Reference. Portfolio Manager ENERGY STAR. Parking and the ENERGY STAR Score in the United States and Canada OVERVIEW OVERVIEW and the ENERGY STAR Score in the United States and Canada The ENERGY STAR score provides a fair assessment of the energy performance of a property relative to its peers, taking into account the

More information

Parking and the ENERGY STAR Score in the United States and Canada

Parking and the ENERGY STAR Score in the United States and Canada and the ENERGY STAR Score in the United States and Canada OVERVIEW The ENERGY STAR score provides a fair assessment of the energy performance of a property relative to its peers, taking into account the

More information

Climate Change in Canada: Impacts on Building Energy Use Intensity

Climate Change in Canada: Impacts on Building Energy Use Intensity Climate Change in Canada: Impacts on Building Energy Use Intensity Nathan Kegel IES, Ltd. Minneapolis, MN ABSTRACT Whole building energy simulation is a useful tool in assessing building energy performance

More information

LOADS, CUSTOMERS AND REVENUE

LOADS, CUSTOMERS AND REVENUE Page of LOADS, CUSTOMERS AND REVENUE The purpose of this evidence is to present the Company s load, customer and distribution revenue forecast for the test years. The detailed test year forecasts are shown

More information

Applied Research Study Results Aircosaver Technology DURHAM COLLEGE OFFICE OF RESEARCH SERVICES AND INNOVATION

Applied Research Study Results Aircosaver Technology DURHAM COLLEGE OFFICE OF RESEARCH SERVICES AND INNOVATION Applied Research Study Results Aircosaver Technology DURHAM COLLEGE OFFICE OF RESEARCH SERVICES AND INNOVATION June MacDonald-Jenkins 12/23/2010 Outcomes/Methods Primary Outcomes/Methods - To determine

More information

When You Can t Go for the Gold: What is the best way to evaluate a non-rct demand response program?

When You Can t Go for the Gold: What is the best way to evaluate a non-rct demand response program? When You Can t Go for the Gold: What is the best way to evaluate a non-rct demand response program? Olivia Patterson, Seth Wayland and Katherine Randazzo, Opinion Dynamics, Oakland, CA ABSTRACT As smart

More information

Intelligent Energy Management for Multi-Unit Operations:

Intelligent Energy Management for Multi-Unit Operations: Intelligent Energy Management for Multi-Unit Operations: CASE STUDY: How One Nationwide Retail Chain Achieved Significant Energy and HVAC Repair Savings with BAYweb Cloud EMS Effective energy management

More information

Learned from Residential HVAC Programs in the Desert Southwest. Page 1

Learned from Residential HVAC Programs in the Desert Southwest. Page 1 The Sun Devil In The Details: Lessons Learned from Residential HVAC Programs in the Desert Southwest Page 1 Introduction» Navigant Consulting conducted three studies of new Residential HVAC equipment in

More information

Statistical Path Analysis Performance Evaluation Of ElectroFlow For Skippy

Statistical Path Analysis Performance Evaluation Of ElectroFlow For Skippy Statistical Path Analysis Performance Evaluation Of ElectroFlow For Skippy Little Rock, Arkansas U.S.A September 9, 2014 1 Table of Contents Table of Contents Page Executive Summary 2 Standard Features

More information

Small-scale Methodology AMS-III.AE.: Energy efficiency and renewable energy measures in new residential buildings

Small-scale Methodology AMS-III.AE.: Energy efficiency and renewable energy measures in new residential buildings CLEAN DEVELOPMENT MECHANISM CDM-EB101-A14 Small-scale Methodology AMS-III.AE.: Energy efficiency and renewable energy measures in new TABLE OF CONTENTS Page 1. INTRODUCTION... 3 2. SCOPE, APPLICABILITY,

More information

ENERGY STAR Portfolio Manager. Technical Reference. ENERGY STAR Score for Supermarkets and Food Stores in Canada OVERVIEW

ENERGY STAR Portfolio Manager. Technical Reference. ENERGY STAR Score for Supermarkets and Food Stores in Canada OVERVIEW OVERVIEW ENERGY STAR Score for Supermarkets and Food Stores in Canada The ENERGY STAR Score for Supermarket and Food Stores in Canada applies to supermarkets, grocery stores, food sales and convenience

More information

M&V 2.0: A User s Guide

M&V 2.0: A User s Guide M&V 2.0: A User s Guide West Coast Energy Management Congress June 8, 2017 David Jump, Ph.D., P.E. kw Engineering djump@kw-engineering.com 1 Agenda What is M&V 2.0? Process Steps & Tools Non-Routine Events

More information

Solar Thermal Radiant Heating at Pohakuloa Training Area

Solar Thermal Radiant Heating at Pohakuloa Training Area Solar Thermal Radiant Heating at Pohakuloa Training Area DoD Executive Agent Office Office of the of the Assistant Assistant Secretary of the of Army the Army (Installations and and Environment) Heather

More information

Building Operator Certification Level I

Building Operator Certification Level I Building Operator Certification Level I A Partnership of the CUNY Institute for Urban Systems Building Performance Lab, the CUNY School of Professional Studies, and the New York State Energy Research &

More information

RESTORE 1030TM Testing Protocol

RESTORE 1030TM Testing Protocol RESTORE 1030TM Testing Protocol Test protocols will vary depending on the type of equipment being evaluated. The length of time required to do the testing, however, remains consistent no matter what the

More information

Markets Report. Paul M. Sotkiewicz, Ph.D Chief Economist, Markets MC Webinar January 20, 2015 PJM 2015

Markets Report. Paul M. Sotkiewicz, Ph.D Chief Economist, Markets MC Webinar January 20, 2015 PJM 2015 Markets Report Paul M. Sotkiewicz, Ph.D Chief Economist, Markets MC Webinar January 20, 2015 Executive Summary PJM Wholesale Cost for calendar year 2014 was $70.40/MWh, and increase of 47% and 33% over

More information

2017 Seasonal Savings Evaluation

2017 Seasonal Savings Evaluation Prepared for National Grid Submitted by: Navigant Consulting, Inc. 77 South Bedford Street Suite 400 Burlington, MA 01803 781.270.8300 navigant.com Reference No.: 194701 March 9, 2018 2018 Navigant Consulting,

More information

Pay for Performance Case Study 3 Years of Performance

Pay for Performance Case Study 3 Years of Performance Pay for Performance Case Study 3 Years of Performance Chris Smith, PE, CEM Energy 350 Kathleen Belkhayat & Oliver Kesting Energy Trust of Oregon Introduction A Pay for Performance (PfP) program structure

More information

MONITORING, TARGETING AND REPORTING (MT&R) FUNDAMENTALS AND APPLICATIONS IN THE COP PROGRAM. Robert Greenwald, P.Eng., MBA Prism Engineering g Ltd.

MONITORING, TARGETING AND REPORTING (MT&R) FUNDAMENTALS AND APPLICATIONS IN THE COP PROGRAM. Robert Greenwald, P.Eng., MBA Prism Engineering g Ltd. MONITORING, TARGETING AND REPORTING (MT&R) FUNDAMENTALS AND APPLICATIONS IN THE COP PROGRAM Robert Greenwald, P.Eng., MBA Prism Engineering g Ltd. WHAT DOES MT&R MEAN? MONITORING The regular collection

More information

USE OF SIMULATION TOOLS FOR MANAGING BUILDINGS ENERGY DEMAND. Alberto Hernandez Neto, Flávio Augusto Sanzovo Fiorelli

USE OF SIMULATION TOOLS FOR MANAGING BUILDINGS ENERGY DEMAND. Alberto Hernandez Neto, Flávio Augusto Sanzovo Fiorelli USE OF SIMULATION TOOLS FOR MANAGING BUILDINGS ENERGY DEMAND Alberto Hernandez Neto, Flávio Augusto Sanzovo Fiorelli University of São Paulo, Escola Politécnica, Department of Mechanical Engineering. Sao

More information

Success with MEASUREMENT & VERIFICATION

Success with MEASUREMENT & VERIFICATION 2016 Success with MEASUREMENT & VERIFICATION Prepared for the North Carolina Department of Environmental Quality. Project funded by the U.S. Department of Energy, Office of Energy Efficiency and Renewable

More information

Methodologies for Determining Persistence of Commissioning Benefits

Methodologies for Determining Persistence of Commissioning Benefits Methodologies for Determining Persistence of Commissioning Benefits David E. Claridge Energy Systems Laboratory Texas A&M University System College Station, TX Abstract: Studies on the persistence of commissioning

More information

More is Better? Analyzing the Relation between Metering Duration and Accuracy of Results for Residential Lighting Evaluations

More is Better? Analyzing the Relation between Metering Duration and Accuracy of Results for Residential Lighting Evaluations More is Better? Analyzing the Relation between Metering Duration and Accuracy of Results for Residential Lighting Evaluations Joel D. Pertzsch, Michaels Energy Inc., La Crosse, WI Ryan M. Kroll, Michaels

More information

Phase Change Materials for Building Cooling Applications

Phase Change Materials for Building Cooling Applications Emerging Products Phase Change Materials for Building Cooling Applications Analysis of Energy Performance in a Quick Service Restaurant Report Prepared by: Emerging Products Customer Service Southern California

More information

Comprehensive Multifamily Building Solution

Comprehensive Multifamily Building Solution Comprehensive Multifamily Building Solution 2016 HOPP Stakeholder Webinar 5/5/2016 1 5/5/2016 SoCalGas Multifamily Sector State Wide Number of Existing Buildings: 3,126,000 (23 percent of residential buildings)

More information

THREE POWERFUL UTILITY BILL ANALYSIS METHODS FOR THE ENERGY MANAGER. John Avina, Director Abraxas Energy Consulting

THREE POWERFUL UTILITY BILL ANALYSIS METHODS FOR THE ENERGY MANAGER. John Avina, Director Abraxas Energy Consulting THREE POWERFUL UTILITY BILL ANALYSIS METHODS FOR THE ENERGY MANAGER John Avina, Director Abraxas Energy Consulting ABSTRACT Utility Bill Tracking systems are at the center of an effective energy management

More information

Energy Analysis of Using Thermal Mass in a Hot Humid climate

Energy Analysis of Using Thermal Mass in a Hot Humid climate Energy Analysis of Using Thermal in a Hot Humid climate SARA MOTAMEDI Architecture Department University of Texas at Austin 1 University Station B7500 Austin, Texas, U.S.A, 787us2-0222 s.motamedi@mail.utexas.edu

More information

SMUD s Residential Summer Solutions Study

SMUD s Residential Summer Solutions Study + SMUD s Residential Summer Solutions Study An Investigation of the Effects of Real- Time Information, Dynamic Pricing, and Thermostat Automation on Residential Energy Conservation, Peak Load Shifting,

More information

Developing an Accurate Baseline for Electricity Consumption, Focusing on University Residence Halls

Developing an Accurate Baseline for Electricity Consumption, Focusing on University Residence Halls Developing an Accurate Baseline for Electricity Consumption, Focusing on University Residence Halls Richard Turner Mechanical Engineer UNC Chapel Hill Energy Management turnerrwjr@gmail.com 5/1/2012 Abstract

More information

Accounting for Price in Your Forecast - Measures and Methodologies

Accounting for Price in Your Forecast - Measures and Methodologies Electric / Gas / Water Accounting for Price in Your Forecast - Measures and Methodologies Itron s Forecasting Brown Bag Seminar March 21, 2006 Frank A. Monforte, Ph.D. J. Stuart McMenamin, Ph.D. Please

More information

COMMERCIAL LOAD ESTIMATING. Load Estimating Level 3: Block and Zone Loads. Technical Development Program

COMMERCIAL LOAD ESTIMATING. Load Estimating Level 3: Block and Zone Loads. Technical Development Program COMMERCIAL LOAD ESTIMATING Load Estimating Level 3: Block and Zone Loads Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design,

More information

Final Savings Estimates and Key Learnings from a Behavioral Messaging Thermostat Trial

Final Savings Estimates and Key Learnings from a Behavioral Messaging Thermostat Trial Final Savings Estimates and Key Learnings from a Behavioral Messaging Thermostat Trial Lucy Morris Candice Churchwell 2014 BECC Conference Washington, D.C. December 10, 2014 How do we get a thermostat

More information

Energy Savings for Stucco Walls Coated with Cool Colors

Energy Savings for Stucco Walls Coated with Cool Colors Energy Savings for Stucco Walls Coated with Cool Colors Tom Petrie, Jerry Atchley, Phil Childs, and André Desjarlais Oak Ridge National Laboratory Building Envelopes Group 6 December 2007 Pop Quiz With

More information

Review of Equipment Trial

Review of Equipment Trial Review of Equipment Trial Blackhawk Power Conditioner City of Edmonton Grand Trunk Leisure and Fitness Centre July 2013 Executive Summary A trial of the Blackhawk power conditioner was conducted at the

More information

Normal Children's Discovery Museum, LEED Silver:

Normal Children's Discovery Museum, LEED Silver: Normal Children's Discovery Museum, LEED Silver: Post Occupancy Energy Performance October 28, 2010 Hosted by: USGBC Illinois Chapter, Central Illinois Branch Sponsored by: ASHRAE Central Illinois Chapter

More information

Markets Report. Paul M. Sotkiewicz, Ph.D Chief Economist, Markets MC Webinar March 23, 2015 PJM 2015

Markets Report. Paul M. Sotkiewicz, Ph.D Chief Economist, Markets MC Webinar March 23, 2015 PJM 2015 Markets Report Paul M. Sotkiewicz, Ph.D Chief Economist, Markets MC Webinar March 23, 2015 Executive Summary PJM Wholesale Cost for the first two months of 2015 was $71.04/MWh, up from $54.29 in January.

More information

Solara: A Case Study in Zero Net Energy Design for Affordable Housing

Solara: A Case Study in Zero Net Energy Design for Affordable Housing Solara: A Case Study in Zero Net Energy Design for Affordable Housing Design, Construction, and Operational Lessons Learned from a California Energy Commission Zero Energy New Homes Project Jim Meacham,

More information

Statistical Path Analysis Performance Evaluation Of ElectroFlow For Majan Electricity Distribution

Statistical Path Analysis Performance Evaluation Of ElectroFlow For Majan Electricity Distribution Statistical Path Analysis Performance Evaluation Of ElectroFlow For Majan Electricity Distribution Sohar, Oman September 15, 2013 Executive Summary 2 We are delighted to report that, following the receipt

More information

LIST OF TABLES LIST OF FIGURES ACKNOWLEDGEMENTS ABSTRACT INTRODUCTION LITERATURE REVIEW STEEPLE

LIST OF TABLES LIST OF FIGURES ACKNOWLEDGEMENTS ABSTRACT INTRODUCTION LITERATURE REVIEW STEEPLE 0 TABLE OF CONTENT LIST OF TABLES... 2 LIST OF FIGURES... 3 ACKNOWLEDGEMENTS... 4 ABSTRACT... 5 INTRODUCTION... 6 LITERATURE REVIEW... 7 STEEPLE Analysis... 7 Background... 9 METHODOLOGY... 12 ANALYSIS...

More information

Allstream Centre Energy Performance Report

Allstream Centre Energy Performance Report Allstream Centre Energy Performance Report 2012 2014 TABLE OF CONTENTS INTRODUCTION... 1 ELECTRICAL CONSUMPTION... 2 ELECTRICAL ENERGY DISTRIBUTION... 3 BUILDING POWER AND SYSTEMS... 4 FACTORS CONTRIBUTING

More information

EFFECTS OF VARIATIONS OF OCCUPANT BEHAVIOR ON RESIDENTIAL BUILDING NET ZERO ENERGY PERFORMANCE. Michael J. Brandemuehl 1 and Kristin M.

EFFECTS OF VARIATIONS OF OCCUPANT BEHAVIOR ON RESIDENTIAL BUILDING NET ZERO ENERGY PERFORMANCE. Michael J. Brandemuehl 1 and Kristin M. Proceedings of Building Simulation 211: EFFECTS OF VARIATIONS OF OCCUPANT BEHAVIOR ON RESIDENTIAL BUILDING NET ZERO ENERGY PERFORMANCE Michael J. Brandemuehl 1 and Kristin M. Field 2 1 University of Colorado,

More information

Energy Trust of Oregon New Homes Billing Analysis: Comparison of Modeled vs. Actual Energy Usage

Energy Trust of Oregon New Homes Billing Analysis: Comparison of Modeled vs. Actual Energy Usage ABSTRACT Energy Trust of Oregon 2009-2011 New Homes Billing : Comparison of Modeled vs. Actual Energy Dan Rubado, Energy Trust of Oregon, Portland, OR This paper describes a utility billing analysis of

More information

Focus on Energy Evaluated Deemed Savings Changes

Focus on Energy Evaluated Deemed Savings Changes Focus on Energy Evaluated Deemed Savings Changes September 14, 2015 Public Service Commission of Wisconsin This page left blank. Prepared by: Cadmus Table of Contents Deemed Savings Analysis... 1 2014

More information

Future U.S. Energy Use for as Computed with Temperatures from a Global Climate Prediction Model and Energy Demand Model

Future U.S. Energy Use for as Computed with Temperatures from a Global Climate Prediction Model and Energy Demand Model Future U.S. Energy Use for 2000-2025 as Computed with Temperatures from a Global Climate Prediction Model and Energy Demand Model Presented at the 24th Annual North American Conference of the USAEE/IAEE

More information

Cornell University Energy and Sustainability: ECI Campus Energy Metrics Fiscal Year 2014 Annual Analysis Purpose and Methodology. ECI Campus Summary:

Cornell University Energy and Sustainability: ECI Campus Energy Metrics Fiscal Year 2014 Annual Analysis Purpose and Methodology. ECI Campus Summary: Purpose and Methodology ECI Campus Summary: Starting in the 2011/2012 fiscal year, a yearly energy metrics analysis is being performed. This analysis supports creating Facilities Metrics and evaluation

More information

Web-Based Energy Savings Calculator for Building Envelope Air Tightness

Web-Based Energy Savings Calculator for Building Envelope Air Tightness Web-Based Energy Savings Calculator for Building Envelope Air Tightness André Desjarlais Oak Ridge National Laboratory Air Barrier Association of America (ABAA) is a Registered Provider with The American

More information

Energy Report - February 2008

Energy Report - February 2008 Energy Report - February 28 Glossary Ampere - The unit of measurement of electrical current produced in a circuit by 1 volt acting through a resistance of 1 Ohm. British thermal unit (Btu) - The quantity

More information

PV Generation Potential 17.1 kbtu/ft2/yr 15.4

PV Generation Potential 17.1 kbtu/ft2/yr 15.4 TOWNHOME PROTOTYPE HIGH PERFORMANCE 60 kbtu/sf/yr 50 kbtu/sf/yr 40 kbtu/sf/yr 30 kbtu/sf/yr 20 kbtu/sf/yr 10 kbtu/sf/yr 0 kbtu/sf/yr 54.4 Baseline 21.8 kbtu/ 2/yr 15 MMBtu 12 MMBtu 9 MMBtu 6 MMBtu 3 MMBtu

More information

Cornell University Energy and Sustainability: ECI Campus Energy Metrics Fiscal Year 2015 Annual Analysis Purpose and Methodology. ECI Campus Summary:

Cornell University Energy and Sustainability: ECI Campus Energy Metrics Fiscal Year 2015 Annual Analysis Purpose and Methodology. ECI Campus Summary: Purpose and Methodology ECI Campus Summary: Starting in the 2011/2012 fiscal year, a yearly energy metrics analysis is being performed. This analysis supports creating Facilities Metrics and evaluation

More information

LOW-RISE APARTMENT BUILDING PROTOTYPE HIGH PERFORMANCE PV Genera on Poten al 17.9 kbtu/ 2/yr

LOW-RISE APARTMENT BUILDING PROTOTYPE HIGH PERFORMANCE PV Genera on Poten al 17.9 kbtu/ 2/yr LOW-RISE APARTMENT BUILDING PROTOTYPE HIGH PERFORMANCE 40 kbtu/sf/yr 35 kbtu/sf/yr 30 kbtu/sf/yr 25 kbtu/sf/yr 20 kbtu/sf/yr 15 kbtu/sf/yr 10 kbtu/sf/yr 5 kbtu/sf/yr 0 kbtu/sf/yr 11.9 kbtu/ft2/yr 36.0

More information

EA PREREQUISITE 2: MINIMUM ENERGY PERFORMANCE

EA PREREQUISITE 2: MINIMUM ENERGY PERFORMANCE EA PREREQUISITE 2: MINIMUM ENERGY PERFORMANCE Project # 12332 THRESHOLD ATTEMPTED Points Attempted: All fields and uploads are required unless otherwise noted. ALL OPTIONS TARGET FINDER The following fields

More information

EA PREREQUISITE 2: MINIMUM ENERGY PERFORMANCE Project # SFPUC Administration Office Building

EA PREREQUISITE 2: MINIMUM ENERGY PERFORMANCE Project # SFPUC Administration Office Building LEED 29 for New Construction and Major Renovations EA PREREQUISITE 2: MINIMUM ENERGY PERFORMANCE Project # 1588 SFPUC Administration Office Building All fields and uploads are required unless otherwise

More information

Building Control Strategies That Work to Improve Your Energy Bottom Line

Building Control Strategies That Work to Improve Your Energy Bottom Line Building Control Strategies That Work to Improve Your Energy Bottom Line William D. (Skip) Milton MBA, CEM, CEA Assistant Director of Facilities Operations Texas Children s Hospital Objective: Learn how

More information

Estimating energy consumption by purpose and analyse standby power in non-residential buildings in Japan

Estimating energy consumption by purpose and analyse standby power in non-residential buildings in Japan Estimating energy consumption by purpose and analyse standby power in non-residential buildings in Japan June 2017 Bizen Green Energy Co. Ltd. TEL:+81-869-63-3600 E-mail:takuo@bizen-greenenergy.co.jp Contents

More information

Integrated Impact and Market Evaluation of Multiple Residential Programs at Florida Power and Light

Integrated Impact and Market Evaluation of Multiple Residential Programs at Florida Power and Light Integrated Impact and Market Evaluation of Multiple Residential Programs at Florida Power and Light Robert Uhlaner and Michael Sedmak, Quantum Consulting Inc. Sharyn Barata, Florida Power& Light Co. Florida

More information

ABASTRACT INTRODUCTION. building

ABASTRACT INTRODUCTION. building CASE STUDY OF AN ENERGY EFFICIENT COMMERCIAL BUILDING: VALIDATING DESIGN INTENT & ENERGY SIMULATION RESULTS WITH MONITORED PERFORMANCE DATA Prashant Bhanware, Indo-Swiss Building Energy Efficiency Project

More information

Pay for Performance Primer 10/12/18

Pay for Performance Primer 10/12/18 Pay for Performance Primer 10/12/18 Welcome to our 1st Pay for Performance Webinar Elizabeth Titus Director of Research and Evaluation, NEEP 2 Agenda What is Pay for Performance (P4P)? (12 mins) Megan

More information

PV Generation Potential 17.1 kbtu/ft2/yr 15.4

PV Generation Potential 17.1 kbtu/ft2/yr 15.4 TOWNHOME PROTOTYPE BASELINE 60 kbtu/sf/yr 50 kbtu/sf/yr 40 kbtu/sf/yr 30 kbtu/sf/yr 20 kbtu/sf/yr 10 kbtu/sf/yr 0 kbtu/sf/yr 54.4 Baseline 54.4 kbtu/ 2/yr 21.8 High Performance 18.2 PHIUS - IES 60 MMBtu

More information

Markets Report. Jennifer Warner-Freeman Senior Economist, Market Analysis March 19, PJM 2018

Markets Report. Jennifer Warner-Freeman Senior Economist, Market Analysis March 19, PJM 2018 Markets Report Jennifer Warner-Freeman Senior Economist, Market Analysis March 19, 2018 www.pjm.com Executive Summary PJM Wholesale Cost through February 2018 was $77.41/MWh, up from full-year 2017 costs

More information

Smart Grid Demonstration Final Report. MLGW President s Briefing January 17, 2013

Smart Grid Demonstration Final Report. MLGW President s Briefing January 17, 2013 Smart Grid Demonstration Final Report MLGW President s Briefing January 17, 2013 Smart Grid Demo Objective Demonstrate the operational and customer benefits of smart grid technology Labor and transportation

More information

Southern York County Library

Southern York County Library Southern York County Library Measurement & Verification Report April 20, 2009 Provided by: York County Community Foundation Energy Program Prepared by: Energy Opportunities, Inc. 1200 East Camping Area

More information

MID-RISE APARTMENT BUILDING PROTOTYPE HIGH PERFORMANCE PV Genera on Poten al 10.8 kbtu/ 2/yr

MID-RISE APARTMENT BUILDING PROTOTYPE HIGH PERFORMANCE PV Genera on Poten al 10.8 kbtu/ 2/yr MID-RISE APARTMENT BUILDING PROTOTYPE HIGH PERFORMANCE 50 kbtu/sf/yr 45.1 PROJECT INFORMATION 40 kbtu/sf/yr 30 kbtu/sf/yr 20 kbtu/sf/yr 10 kbtu/sf/yr 0 kbtu/sf/yr 13.0 kbtu/ft2/yr Baseline 10.8 kbtu/ft2/yr

More information

Field Test of Cold Climate Air Source Heat Pumps

Field Test of Cold Climate Air Source Heat Pumps CASE STUDY 2 June 2018 Field Test of Cold Climate Air Source Heat Pumps BACKGROUND This field study is an extension of the recently completed CARD field study of flex fuel and ductless cold climate air

More information

Final Report for National Grid USA Service Company. Evaluation of 2003 Custom HVAC Installations Part II. September 27, 2005.

Final Report for National Grid USA Service Company. Evaluation of 2003 Custom HVAC Installations Part II. September 27, 2005. Final Report for National Grid USA Service Company Evaluation of 2003 Custom HVAC Installations Part II September 27, 2005 Submitted by Select Energy Services, Inc. is the energy services subsidiary of

More information

ENERGY EFFICIENT RETROFIT OF A HIGH-RISE MULTIFAMILY BUILDING

ENERGY EFFICIENT RETROFIT OF A HIGH-RISE MULTIFAMILY BUILDING ENERGY EFFICIENT RETROFIT OF A HIGH-RISE MULTIFAMILY BUILDING Brittany Hanam 1, Lorne Ricketts 2, Andrew Pape-Salmon 3 ABSTRACT The National Institute of Building Sciences estimates that over 70% of the

More information

Managing Energy Use and Cost with Integrated Metering

Managing Energy Use and Cost with Integrated Metering Managing Energy Use and Cost with Integrated Metering Regional Municipality of Durham October 29, 2015 Joe Green P.Eng, CEM Overview Duffin Creek WPCP Jointly owned by York and Durham Regions Capacity

More information