OPTIMISATION OF GRANULAR MEDIA FILTRATION: IMPACT OF CHEMICAL CONDITIONING

Size: px
Start display at page:

Download "OPTIMISATION OF GRANULAR MEDIA FILTRATION: IMPACT OF CHEMICAL CONDITIONING"

Transcription

1 OPTIMISATION OF GRANULAR MEDIA FILTRATION: IMPACT OF CHEMICAL CONDITIONING Con Pelekani 1, Neil Crossing 2, Loreline Kerlidou 3, Sam Hancock 1, Jean-Francois Robin 4 1. SA Water Corporation, Adelaide, South Australia 2. Allwater, Adelaide, South Australia 3. Inside Infrastructure, Adelaide, South Australia 4. Department of Process Integration and Optimisation, CIRSEE, Suez Environnement, France ABSTRACT Addition of chlorine to the influent of pilot granular media filters at Happy Valley water treatment plant (WTP) was found to result in significant reductions in filtered water particle counts compared with standard turbidity measurement. When the WTP is operated in enhanced coagulation mode, the limiting factor influencing chlorine dose is the presence of soluble manganese in the clarified water. Increasing filter influent ph improved kinetics of manganese oxidation by chlorine, with filtered water aluminium residuals below 0.2 mg/l. Polymer dosing was also found to be beneficial, with no adverse interaction with free chlorine. The use of a control filter was necessary to assess the impact of different treatments. Operating a filter with no chemicals to enable biofilm development was achieved reasonably quickly. However, filtered water turbidity and particle counts were generally higher than those from chemically conditioned filters. The ability of the biofilter to degrade algal metabolites (MIB and geosmin) was poor, confirming that alternative chemical conditioning practices are necessary. INTRODUCTION In 2011, in response to identified underdrain structural failures, a capital works project was initiated under the Cryptosporidium risk mitigation strategy to initially refurbish 8 of 16 filters at SA Water s largest water treatment plant at Happy Valley, to restore functionality to this critical treatment barrier. The project was completed in In 2012, a pilot plant was constructed to establish the optimum new sand media configuration (size, depth) to achieve the required filtered water quality requirements to maximise filtration barrier performance against protozoan pathogens, in particular, Cryptosporidium. Combined filtered water turbidity requirement for metropolitan Adelaide WTPs is <0.15 NTU (95% of the time per month), with individual filter turbidity target of < 0.15 NTU within 15 min and less than 0.3 NTU (100% of time per month). The pilot plant was also used to establish optimum filtration rate and backwash sequence conditions (Pilot Plant investigation Phase 1). Phase 2 of the investigation, the subject of this paper, involved characterisation of the impact of different chemical conditions applied to the clarified water upon filtration performance, as well as operational requirements and treatment performance of a non-chlorinated biofilter. MATERIALS AND METHODS Figures 1 and 2 illustrate a process schematic and photograph of the filtration pilot plant, respectively. Clarified water could be accessed from the settled water duct (which directly feeds the full-scale sand filters) or directly from the on-line sedimentation tanks (during periods when the full-scale plant is off-line). The rig is equipped with four filter columns (clear PVC construction; 250 mm diameter; 1.3 m of mm effective size sand with graded gravel support). The common supply line to the filters had provision for ph adjustment with sodium hydroxide. Filter 1 was designated as the control filter and was filtered/chlorinated water. Filter 2 was designated as the biological column. No chemicals were dosed into this filter and the backwash water did not contain chlorine. Filters 3 and 4 were designated as the chemically dosed filters and operated under the same treatment conditions (duplicate columns). Chemical dosing systems were initially provided for columns 1, 3 and 4. During the latter stages of the testing program, a dosing point was installed for column 2 (biological filter) to enable the MIB/Geosmin spiking trial. A filter loading rate of 13 m/h was employed for columns 1, 3 and 4. This value was found to provide optimum filtration conditions based on the work undertaken during Phase 1. For column 2 (biological), the loading rate was 5 m/h for the first month, after which it was increased to 10 m/h and maintained at this rate. Outlet flow control capability was provided for each column.

2 Test conditions are summarised in Tables 2 and 3.It is important to note that the stated polymer doses were five times higher than originally intended, due to a miscalculation of the actual batch polymer stock concentration produced for full-scale plant dosing (0.5%w/v versus 0.1%w/v). Unfortunately, this error was only identified near the end of the experimental period. In practice, filter aid polymer doses above 0.1 mg/l are impractical as they significantly increase the risk of filter clogging via mudballing. However, short-term testing of high doses provides an upper limit on the particle reduction capability afforded by use of high molecular weight polymers. Figure 1. Pilot filter process schematic Figure 2. Photo of filter pilot plant Each test was normally operated for a period of 24 hours, after which the test was repeated. Turbidity and particle count results were the average of the four tests corresponding to duplication of columns 3 and 4. Data analysis excludes the ripening period, typically designated as the first 30 minutes after filter start-up. Due to the start-stop nature of fullscale plant operation there was variation in feed water quality between different trials, the impact of which is described later. Table 2. Test conditions for chlorine and Mn dosing Trial Manganese dose (mg/l) Chlorine dose (mg/l) Low dose Mn Low dose Mn High dose Mn High dose Mn High dose Mn High dose Mn High ph High ph Biological Column Biological Column ph On-line turbidity (Hach 1720E) and particle counters (Chemtrac PC3400; 2-15 m range) were installed for each filter column for real time water quality analysis. Data from on-line sensors (flow, differential pressure) was stored on a dedicated PC located on-site. Remote access capability was enabled to view system status. An Excel macro was created to extract operational data into CSV type files for analysis. Table 1 summarises the backwash conditions for columns 1, 3 and 4, established from Phase 1. Table 1. Filter backwash conditions The following chemicals were employed: MnCl 2 solution (for manganese spiking trials); NaOH solution (for ph adjustment); LT22S solution (cationic polyacrylamide for filter aid polymer trials); and NaOCl solution (12.5%w/w; for chlorine addition). For Mn spiking trials, chemical was dosed for the first 6 hours of run time. Table 3. Test conditions for polymer dosing Trial Number Polymer Concentration (mg/l) Chlorine Concentration (mg/l) RESULTS AND DISCUSSION Turbidity and particle count profiles for duplicate columns 3 and 4 were found to be consistent for all test conditions. For this reason results presented herein are predominantly associated with column 3. Clarified water turbidity was normally very low (<0.5 NTU), with short-term spikes of up to 4 NTU observed after start-up of the full-scale WTP. The low turbidity supports the effectiveness of the sedimentation basins to achieve effective floc removal. ph

3 Impact of chlorination Figure 3 illustrates the filtered water turbidity and particle count results for the reference column (#1; no chemical dosing) and column 3, for 3 different chlorine dose conditions (0.5, 1, 1.5 mg/l). The colour coding allows visual comparison of columns 1 (control) and 3 for the same test period. Analysis of the steady state profiles is summarised in Table 4. The chlorine demand of columns 3 and 4 was in the range of 1 mg/l ( mg/l). The comparative reduction in particle counts was much greater than for turbidity. The findings are consistent with those of Roder et al. (2000), who evaluated the impact of filter pre-chlorination using pilot filters operated on settled water from Hope Valley WTP. In that study, filtered water particle counts decreased significantly during prechlorination (dosed to achieve a filter effluent residual of 0.3 mg/l). The effect was immediate and reversible once dosing ceased. Figure 3. Impact of filter pre-chlorination Table 4. Measured pre-chlorination improvement Chlorine Dose Turbidity removal C3&C4 compared to C1 Particle counts removal C3&C4 compared to C1 mg/l % Removal % Removal % +37% 1 +16% +50% % +52% Becker et al. (2004) conducted a comprehensive investigation of the impact of a range of oxidants for enhancement of filtration performance, including chlorine. A range of mechanisms were proposed, including reduction in the adsorbed hydrodynamic layer of NOM on influent particles associated with chemical structural changes. Batch tests were conducted using model surrogate Hematite particles (64 nm diameter) for a range of oxidant doses and water quality conditions (ph, ionic strength, calcium concentration). Dynamic laser light scattering equipment was used to measure the thickness of the adsorbed layer, while static light scattering was used to calculate particle attachment efficiency. The results did show a reduction in layer thickness with increasing oxidant dose, with a concomitant increase in attachment efficiency. Pilot testing with a range of surface waters showed significant and rapid decrease in filtered water particle counts once pre-oxidation was initiated. Performance deteriorated once oxidant dosing was ceased. The beneficial impact was dependent upon the oxidant used, with chlorine, ozone and chlorine dioxide all performing very well, while permanganate displayed only modest improvement. As with this study, the beneficial impact of filter preoxidation was far greater with particle counts than turbidity. Furthermore, comparison between filters exposed to oxidant and those operated in biological mode, consistently demonstrated higher particle counts from the biological filter. Manganese removal Chlorine is dosed into the clarified water of most WTPs serving metropolitan Adelaide. The primary reason is to oxidise dissolved manganese present in source waters to insoluble form (typically MnO 2 /Mn 3 O 4 ) for removal by filtration. Figure 4

4 compares the performance of different levels of chlorine upon removal of designated high Mn (0.1 mg/l) dosed filter influent for columns 3 and 4. Mn removal was poor for chlorine doses less than 2 mg/l. At 2 mg/l, Mn removal was consistently poor at short time scales (30 min), reflecting the kinetic limitation associated with oxidation by chlorine. deteriorate rapidly at longer run times (4-6 hours of dosing) (Figure 5). Biological removal is possible for Mn 2+, as it can be used in co-metabolism for microbial energy production. However, it appears that the active biofilm s capacity (if present) is limited. Figure 5. Mn removal: control versus chlorinated filters Figure 6 shows the impact of increasing filter influent ph from ambient (7.2) to ~7.6. As expected Mn removal was improved at short time scales. However, the greatest overall improvement was observed when increasing the chlorine dose to 3 mg/l. In the full-scale WTP, chlorine is typically dosed to achieve a residual in the filtered water ( mg/l). The accumulation of MnO 2 on the sand filter grains with time (volume of water processed) is most likely responsible for the very good removal of Mn under ambient ph conditions. MnO 2 acts catalytically to accelerate the rate of dissolved Mn oxidation (Knocke et al. 1991). The Mn spiking trials were short and specific events, with no long term dosing to generate a coating of MnO 2 on sand grains. Irrespective, the results do confirm the relative importance of ph and chlorine dose. The latter strongly influences the redox potential (ORP), which needs to be high (>700 mv) to drive effective oxidation of dissolved Mn to MnO 2 precipitate. Increasing ph does shift Mn speciation towards insoluble species, but ORP is the controlling parameter. Figure 4. Impact of filter pre-chlorination on Mn removal. Comparison against the control filter (#1) yielded surprising results. Mn removal was found to be significantly better for Filter 1, although did

5 doses, however poor particle count removal was observed at 0.1 mg/l. Figure 6. Impact of ph on Mn removal. Impact of filter aid polymer LT22S (BASF, Australia), a polyacrylamide polymer is dosed as a filter aid at the Happy Valley WTP. Figure 7 illustrates the filtered water turbidity and particle counts for the reference column (#1; no chemical dosing) and filter column 3, for 2 different polymer doses (0.1 and 0.4 mg/l). An analysis of the steady state filtrate profiles is summarised in Table 5. A comparative reduction in filtered water turbidity was observed for both applied polymer Figure 7. Impact of filter aid Table 5. Measured water quality improvement from polymer dosing

6 Figure 8 illustrates the filtered water turbidity and particle count profiles for the reference column (#1; with 2 mg/l of chlorine dosing) and column 3, for 3 different LT22S doses (0.02, 0.1 and 0.4 mg/l) and 2 mg/l of chlorine. Analysis of the steady state profiles is summarised in Table 6. Increased turbidity and particle count removals were observed with pre-chlorination, consistent with previous findings. No apparent negative interaction between chlorine and LT22S was observed. Turbidity (NTU) Turbidity (NTU) Total Particle Counts (cts/ml) Total Particle Counts (cts/ml) Column 1 - Reference Summary Turbidity - Polymer & Chlorine Rep 1 & Figure 8. Impact of filter aid (with pre-chlorination) Column 3 Summary Turbidity - Polymer & Chlorine Rep 1 & Column 1 - Reference Summary Particle Counts - Polymer & Chlorine Rep 1 & Poly = 0.02 mg/l Poly = 0.10 mg/l Poly = 0.40 mg/l Column 3 Summary Particle Counts - Polymer & Chlorine Rep 1 & Poly = 0.02 mg/l Poly = 0.10 mg/l Poly = 0.40 mg/l Table 6. Measured filter aid improvement with prechlorination The Happy Valley WTP was offline due to maintenance for some of the filter aid dosing trials. This led to significant variations in residence time in the sedimentation basins and ultimately changes in the quality of settled water used to feed the pilot plant. This variation in settled water quality can be seen to have an impact on filtered water quality in the reference filter (Figure 7) making a direct comparison of filtered water turbidity and particle counts for these trials inconclusive. Comparative reductions in particle counts and turbidity allowed for trial results to still be utilised despite the varying settled water quality conditions. A comparison of the turbidity and particle count reductions at ambient ph (7.2) and elevated ph (7.6) yielded inconsistent results (Table 7). Decreased turbidity and particle count removals were observed for a low polymer dose with prechlorination but increased removals were observed at a high polymer dose without pre-chlorination. It is hypothesised that the turbidity and particle count removal may decrease with elevated ph, due to an increased anionic particle charge. Variable settled water quality during these tests possibly contributed to these results. Settled water and filtrate samples were collected during the high polymer dose trial to assess aluminium breakthrough when operating the filters at an elevated ph of 7.6. All samples were found to comply with the Australian Drinking Water Guideline value of 0.2 mg/l (acid-soluble Al). Table 7. Measured filter aid improvement at elevated ph Biological filtration To encourage biological activity, column 2 was backwashed with non-chlorinated filtrate produced from the filter. Figure 9 illustrates the particle count and turbidity profiles for column 2 (blue line) and the control column (pink line) over a 4 month period (May-August 2014). The control column was subject to chlorinated backwash conditions. Raw water flow for the full-scale WTP is also included (green line). In general, trends were similar, with most data in the NTU range. Particle count trends were also similar, converging towards the end of the period.

7 Figure 10. Headloss profiles for biological and reference columns. Measurements of dissolved oxygen, oxidation reduction potential, UV 254 absorbance and true colour 456 nm) were taken for the inlet and outlet of the control and biological filters (Figure 11). Surprisingly, no significant changes were observed between the inlet and outlet of the biological filter for any of these parameters. It is hypothesised that the empty bed contact time of 7.8 min was not long enough to encourage appropriate microbiological growth on the sand media surface. Figure 9. Turbidity profiles for biological and reference filter columns. A contributing factor to the transient variability in filtered water quality is the backwash sequence and interval. Figure 10 illustrates the headloss profiles for the biological and reference filters. Numerical designations 1-3 refer to the type of backwash sequence. Type 1 involved only a low rate water wash (20 m/h for 5 min). This was employed to prevent potential loss of active biofilms associated with turbulent backwash. Type 2 involved addition of separate air scour (50 Nm/h for 1 min) before the water wash. Type 3 involved air scour, combined air and water sequence, equivalent to that employed for chemically treated filter columns (refer to Table 1). Backwash of the biological filter was normally triggered when the headloss exceeded 2 m, with a maximum of 3 m. An important indicator of success was the ability of the backwash to restore headloss to less than 0.5 m. Water only (Type 1) was not able to achieve this requirement on a consistent basis. Intermediate Type 2 backwash did assist. However, the addition of a combined air/water scour (Type 3) was necessary to achieve operational stability. Under these conditions the rate of headloss development was not significantly different between the biological and reference filters. Figure 11. Impact of biological filtration on DO, ORP, UV 254 and colour After more than 6 months of operation, a taste and odour spiking test was undertaken to assess whether the non-chlorinated biological filter could remove selected algal metabolites of interest: geosmin and 2-methyl-isoborneol (MIB). The reference and biological columns were spiked with a laboratory prepared solution of MIB and geosmin to achieve approximately 250 ng/l at the inlet to the filters. The stock solution was kept chilled to minimise losses by volatilisation. Solution was dosed for a period of 4.5 hours, with samples collected at regular intervals for GCMS analysis inhouse. No significant decrease in MIB or geosmin was observed for either the control or biological filter (Figure 12). Sampling of the filter effluent one week after the spiking test did not reveal any measurable quantities of either compound, confirming that the biological filter was not producing MIB or geosmin. The findings confirm that simply passing non-chlorinated water that has been subjected to coagulation, flocculation and clarification does not guarantee effective

8 biofiltration for rapid gravity filters. Sawade et. al. (2011) found that at least 10 months of filtration at an empty bed contact time of 15 min was necessary before biological removal of MIB and geosmin would become significant on filter sand media. To achieve reliable and consistent removal of target compounds using biofiltration is likely to require optimisation of influent nutrient conditions to encourage appropriate biological activity and to minimise production of extracellular polymeric substances (EPS) that foul the media. Also referred to as engineered biofiltration, this has the potential to significantly enhance the treatment capability of traditional media filters (Lauderdale et al., 2012). This is the subject of current research activity at SA Water. confirming the importance of conditioning the filter influent to select for appropriate biological conditions. ACKNOWLEDGMENTS Loreline Kerlidou was the Allwater project engineer for Phase 1 and 2 pilot investigations from May 2013 to August Emma Sawade, Rolando Fabris and Mary Drikas (Water Treatment, Research & Innovation Services group, SA Water) for managing the MIB/Geosmin spiking trial. Uwe Kaeding (Water Treatment Manager, Allwater) and Dr. Jeremy Lucas (Senior Manager Water Quality & Treatment Strategy, SA Water) for sponsoring this applied research initiative. REFERENCES Figure 12. MIB and geosmin spiking trial results CONCLUSIONS In this study, the benefits of chlorine and/or polymer addition to filter influent were demonstrated. Filter pre-chlorination resulted in a significant reduction in filtered water turbidity and particle counts (2-15 m), when a dose above 0.5 mg/l was applied. Chlorine doses in excess of 2 mg/l were necessary to achieve acceptable reductions in soluble manganese at ambient ph (~7.2). Filtration at an elevated ph of 7.6 was found to improve the oxidation kinetics of manganese using chlorine without exceeding the regulatory limit for soluble aluminium (0.2 mg/l). Filter aid polymer addition afforded improvements in filtered water turbidity and particle counts with no apparent negative interaction when dosed simultaneously with chlorine. The water quality benefits, as measured via turbidity and particle count analysis, confirm that the filter pre-chlorination and polymer dosing can be employed to reduce the risk of pathogen (e.g. Cryptosporidium) breakthrough, thus improving barrier effectiveness. Becker W.C., O Melia C.R., Au K. and Young Jr. J.S. (2004), Using Oxidants to Enhance Filter Performance. American Water Works Association Research Foundation. Report # Knocke W.R., Occiano S.C. and Hungate R. (1991), Removal of Soluble Manganese by Oxide-Coated Filter Media: Sorption Rate and Removal Mechanism Issues. Journal American Water Works Association, 83:8: Lauderdale C., Chadik P., Kirisits M.J. and Brown J. (2012), Engineered biofiltration: Enhanced biofilter performance through nutrient and peroxide addition. Journal American Water Works Association, 104(5): Roder E., Holmes M. and Chipps M. (2000), The Application of Particle Counters in the Optimisation of Water Filtration. Proceedings of the Water Quality Technology Conference, American Water Works Association, USA. Sawade E., Slyman N., Dixon M., Ho, L. Hoefel D., McDowall B. and Newcombe G. (2011), Biological filtration for the treatment of cyanobacterial metabolites. Proceedings of the Australian Water Association Ozwater Conference, Adelaide, South Australia. Operating a filter without chlorine to encourage biological activity for the purposes of enhancing taste and odour removal capability was undertaken. Optimisation of the physical backwash sequence was necessary to achieve stable filter runs. Filtered water quality (turbidity and particle counts) were generally higher than for chemically dosed filters. Even after 6 months of operation no effective removal of MIB and geosmin was observed,

Optimisation of granular media filtration: impact of chemical conditioning Con Pelekani & Loreline Kerlidou SA Water & Allwater

Optimisation of granular media filtration: impact of chemical conditioning Con Pelekani & Loreline Kerlidou SA Water & Allwater Optimisation of granular media filtration: impact of chemical conditioning Con Pelekani & Loreline Kerlidou SA Water & Allwater Wednesday, 27 May 2015 PRESENTATION OUTLINE CONTEXT & OBJECTIVES TEST METHODOLOGY

More information

Optimizing Conventional Treatment for the Removal of Cyanobacteria and Toxins [Project #4315]

Optimizing Conventional Treatment for the Removal of Cyanobacteria and Toxins [Project #4315] Optimizing Conventional Treatment for the Removal of Cyanobacteria and Toxins [Project #4315] ORDER NUMBER: 4315 DATE AVAILABLE: February 2015 PRINCIPAL INVESTIGATORS: Gayle Newcombe, Jennifer Dreyfus,

More information

Optimizing Filter Conditions for Improved Manganese Control During Conversion To Biofiltration [Project #4448]

Optimizing Filter Conditions for Improved Manganese Control During Conversion To Biofiltration [Project #4448] Optimizing Filter Conditions for Improved Manganese Control During Conversion To Biofiltration [Project #4448] ORDER NUMBER: 4448 DATE AVAILABLE: May 2016 PRINCIPAL INVESTIGATORS: Chance V. Lauderdale,

More information

OPTIMISING PAC DOSING TO REMOVE MIB AND GEOSMIN IN FOUR ADELAIDE METROPOLITAN WATER TREATMENT PLANTS. David Cook

OPTIMISING PAC DOSING TO REMOVE MIB AND GEOSMIN IN FOUR ADELAIDE METROPOLITAN WATER TREATMENT PLANTS. David Cook OPTIMISING PAC DOSING TO REMOVE MIB AND GEOSMIN IN FOUR ADELAIDE METROPOLITAN WATER TREATMENT PLANTS Paper Presented by: David Cook Authors: David Cook, Australian Water Quality Centre - SA Gayle Newcombe,

More information

SIMPLE FILTER CAPPING APPROACHES FOR ENAHANCED BIOLOGICAL FILTRATION PERFORMANCE. Andrew WT Wong, EIT, University of Waterloo*

SIMPLE FILTER CAPPING APPROACHES FOR ENAHANCED BIOLOGICAL FILTRATION PERFORMANCE. Andrew WT Wong, EIT, University of Waterloo* SIMPLE FILTER CAPPING APPROACHES FOR ENAHANCED BIOLOGICAL FILTRATION PERFORMANCE Andrew WT Wong, EIT, University of Waterloo* Monica B Emelko, Ph.D., University of Waterloo Timothy Walton, A.Sc.T., Region

More information

Overview Increased Increased federal emphasis emphasis on on filter filter performance Virginia s emphasis emphasis on

Overview Increased Increased federal emphasis emphasis on on filter filter performance Virginia s emphasis emphasis on Overview Increased federal emphasis on filter performance Virginia s emphasis on filter performance Media filter optimization Challenges to good filtration Finding solutions Federal Emphasis on Filter

More information

OPTIMISING FILTRATION AT DUNGOG WTP. David Turner. Hunter Water Australia

OPTIMISING FILTRATION AT DUNGOG WTP. David Turner. Hunter Water Australia OPTIMISING FILTRATION AT DUNGOG WTP Paper Presented by: David Turner Author: David Turner, Operations Support Manager, Darren Bailey, Treatment Operations Manager, Hunter Water Australia 7 th Annual WIOA

More information

Comparing the Leopold Clari-DAF System to Upflow Contact Clarification

Comparing the Leopold Clari-DAF System to Upflow Contact Clarification JUST ADD WATER Comparing the Leopold Clari-DAF System to Upflow Contact Clarification James E. Farmerie Product Manager The F. B. Leopold Co., Inc. 227 South Division Street Zelienople, Pennsylvania 16063

More information

Process Instruments (UK) Ltd.

Process Instruments (UK) Ltd. Process Instruments (UK) Ltd. Coagulation Control; Past, Present and Future Mike Riding Process Instruments (UK) Ltd. What We Sell Biofilm ph Conductivity Dissolved Oxygen Free & Total Chlorine CRONOS

More information

OPERATORS PERSPECTIVE : OPTIMISATION OF A NEW PACKAGE WATER TREATMENT PLANT. Melina Entwistle. North East Water Authority

OPERATORS PERSPECTIVE : OPTIMISATION OF A NEW PACKAGE WATER TREATMENT PLANT. Melina Entwistle. North East Water Authority OPERATORS PERSPECTIVE : OPTIMISATION OF A NEW PACKAGE WATER TREATMENT PLANT Paper Presented by : Melina Entwistle Author: Melina Entwistle, Water and Wastewater Treatment Operator, North East Water Authority

More information

USING PARTICLE COUNTERS TO OPTIMISE WATER TREATMENT PLANTS. Michelle Colwell. Michelle Colwell, Water Treatment Technologist.

USING PARTICLE COUNTERS TO OPTIMISE WATER TREATMENT PLANTS. Michelle Colwell. Michelle Colwell, Water Treatment Technologist. USING PARTICLE COUNTERS TO OPTIMISE WATER TREATMENT PLANTS Paper Presented by : Michelle Colwell Author: Michelle Colwell, Water Treatment Technologist Gippsland Water 63 rd Annual Water Industry Engineers

More information

Trident. Package Water Treatment System

Trident. Package Water Treatment System Trident Package Treatment System The Trident Package Treatment System When Microfloc products first introduced the Trident technology, it represented a significant advancement in water and wastewater treatment

More information

Removal of Manganese from Drinking Water. Key Words: greensand, oxidation, adsorption, filtration, biological

Removal of Manganese from Drinking Water. Key Words: greensand, oxidation, adsorption, filtration, biological Fact Sheet Volume: 2 Issue: 4 Year: 2018 Removal of Manganese from Drinking Water Key Words: greensand, oxidation, adsorption, filtration, biological Manganese in Drinking Water Manganese is commonly found

More information

Improvement of Drinking Water Plant Treatment

Improvement of Drinking Water Plant Treatment Improvement of Drinking Water Plant Treatment A. ZOUBOULIS 1, *, G. TRASKAS 1 AND P. SAMARAS 2 1 Department of Chemistry, Division of Chemical Technology Aristotle University, Thessaloniki GR-541 24, Greece

More information

Drinking Water Production Using Moving Bed Filtration

Drinking Water Production Using Moving Bed Filtration Drinking Water Production Using Moving Bed Filtration Small to medium sized package units for surface water treatment Author: J.W. Wouters KEY WORDS Surface water; moving bed filtration; drinking water

More information

TARCUTTA TREATMENT PLANT IRON AND MANGANESE REMOVAL. Peter Outtrim. Riverina Water County Council

TARCUTTA TREATMENT PLANT IRON AND MANGANESE REMOVAL. Peter Outtrim. Riverina Water County Council . TARCUTTA TREATMENT PLANT IRON AND MANGANESE REMOVAL Paper Presented by: Peter Outtrim Author: Peter Outtrim,Water Quality Officer, Riverina Water County Council 3 rd Annual WIOA NSW Water Industry Engineers

More information

Drinking Water Treatment Overview Filtration and Disinfection

Drinking Water Treatment Overview Filtration and Disinfection Drinking Water Treatment Overview Filtration and Disinfection April 16 th, 2009 Yousry Hamdy, M.Sc., P.Eng Nicolás s Peleato, EIT 1 Table of Contents Introduction Filtration Cartridge filters Chemical

More information

WEFTEC.06. Lake Okeechobee, Actiflo, peroxone, surface water, Cyanobacteria

WEFTEC.06. Lake Okeechobee, Actiflo, peroxone, surface water, Cyanobacteria FRESH IDEAS FOR FRESH WATER: OKEECHOBEE UTILITY AUTHORITY S SURFACE WATER TREATMENT PLANT USES INNOVATIVE TECHNOLOGY TO ACHIEVE HIGH QUALITY DRINKING WATER FROM LAKE OKEECHOBEE By: Curtis Robinson, E.I.

More information

J.K. ENGINEERING LTD. CONSULTING * RESEARCH * DEVELOPMENT

J.K. ENGINEERING LTD. CONSULTING * RESEARCH * DEVELOPMENT J.K. ENGINEERING LTD. CONSULTING * RESEARCH * DEVELOPMENT #320, 7930 - Bowness Rd. N.W. Calgary, AB, T3B 0H3, Tel. (403) 247-1777 Fax. (403) 286-9895, e-mail: jkeng@telus.net WATER TECH 2009 BANFF, ALBERTA,

More information

Breaking a Paradigm: Benefits of Chlorine and other Oxidants on Biofiltration Pete D Adamo, PE, PhD Chance Lauderdale, PE, PhD

Breaking a Paradigm: Benefits of Chlorine and other Oxidants on Biofiltration Pete D Adamo, PE, PhD Chance Lauderdale, PE, PhD Breaking a Paradigm: Benefits of Chlorine and other Oxidants on Biofiltration Pete D Adamo, PE, PhD Chance Lauderdale, PE, PhD 2014 HDR, Inc., all rights reserved. Where we are heading 1. Background and

More information

BIOLOGICAL MANGANESE REMOVAL A VERY SUSTAINABLE WATER TREATMENT TECHNOLOGY. Peter Baudish. Sinclair Knight Merz

BIOLOGICAL MANGANESE REMOVAL A VERY SUSTAINABLE WATER TREATMENT TECHNOLOGY. Peter Baudish. Sinclair Knight Merz BIOLOGICAL MANGANESE REMOVAL A VERY SUSTAINABLE WATER TREATMENT TECHNOLOGY Paper Presented by: Peter Baudish Author: Peter Baudish, Water Treatment Practice Leader, Sinclair Knight Merz 4 th Annual WIOA

More information

Unit Treatment Processes in Water and Wastewater Engineering

Unit Treatment Processes in Water and Wastewater Engineering Unit Treatment Processes in Water and Wastewater Engineering T J Casey AQUAVARRA RESEARCH LIMITED 22A Brookfield Avenue Blackrock Co. Dublin. October 2006 Author s Note Water and wastewater treatment technology

More information

IMPACT OF WATER QUALITY AND TREATMENT ON DISINFECTION BY-PRODUCT FORMATION. David Cook. Australian Water Quality Centre

IMPACT OF WATER QUALITY AND TREATMENT ON DISINFECTION BY-PRODUCT FORMATION. David Cook. Australian Water Quality Centre IMPACT OF WATER QUALITY AND TREATMENT ON DISINFECTION BY-PRODUCT FORMATION Paper Presented by: David Cook Authors: David Cook, Senior Research Officer-Water Treatment, Mary Drikas, Research Leader - Water

More information

Iron/Manganese Package Plant Pre-Engineered Ground Water Treatment. Village of Bolivar, NY

Iron/Manganese Package Plant Pre-Engineered Ground Water Treatment. Village of Bolivar, NY Iron/Manganese Package Plant Pre-Engineered Ground Water Treatment Village of Bolivar, NY Fe/Mn Removal/Village of Bolivar, NY Presentation Outline Fe/Mn Overview Treatment Options Village of Bolivar Challenge

More information

IMPACT OF OPERATIONAL STRATEGY ON DBP FORMATION. Emma Sawade. Emma Sawade, Scientist, AWQC, SA Water Corporation

IMPACT OF OPERATIONAL STRATEGY ON DBP FORMATION. Emma Sawade. Emma Sawade, Scientist, AWQC, SA Water Corporation IMPACT OF OPERATIONAL STRATEGY ON DBP FORMATION Paper Presented by: Emma Sawade Authors: Emma Sawade, Scientist, AWQC, et al SA Water Corporation 77 th Annual WIOA Victorian Water Industry Operations Conference

More information

ENVIRONMENTAL ENGINEERING LECTURE 3: WATER TREATMENT MISS NOR AIDA YUSOFF

ENVIRONMENTAL ENGINEERING LECTURE 3: WATER TREATMENT MISS NOR AIDA YUSOFF ENVIRONMENTAL ENGINEERING LECTURE 3: WATER TREATMENT MISS NOR AIDA YUSOFF LEARNING OUTCOMES Define the concept and process of water treatment. Describe the concept of coagulation, flocculation, and sedimentation

More information

EVALUATION OF TECHNIQUES TO CONTROL FILTER RIPENING TURBIDITY SPIKES AT SOUTH AUSTRALIAN WATER FILTRATION PLANTS

EVALUATION OF TECHNIQUES TO CONTROL FILTER RIPENING TURBIDITY SPIKES AT SOUTH AUSTRALIAN WATER FILTRATION PLANTS EVALUATION OF TECHNIQUES TO CONTROL FILTER RIPENING TURBIDITY SPIKES AT SOUTH AUSTRALIAN WATER FILTRATION PLANTS Daniel Bonini 1 1. SA Water, Adelaide, SA, Australia ABSTRACT Filter ripening spikes are

More information

2017 HDR, Inc., all rights reserved.

2017 HDR, Inc., all rights reserved. Evaluating Operational Factors that Influence Biofiltration Performance in Various Source Waters Samantha Black, EIT, PhD HDR Pete D Adamo, PE, PhD HDR Mike Hughes City of Raleigh 2017 HDR, Inc., all rights

More information

Treatment Processes for Potable Water

Treatment Processes for Potable Water Treatment Processes for Potable Water Drinking Water Potable water is water that is free of harmful chemicals, microorganisms, and other contaminants and is safe to drink Drinking water also should be

More information

Removal of Manganese by Microfiltration in a Water Treatment Plant*

Removal of Manganese by Microfiltration in a Water Treatment Plant* Removal of Manganese by Microfiltration in a Water Treatment Plant* Carl Schneider, Ph.D., P.E., Senior Process Engineer Wiedeman & Singleton, Inc., Atlanta, GA Peter Johns, P.E., Vice-President Wiedeman

More information

CE 370. Filtration. Overview of the Process Location in the Treatment Plant

CE 370. Filtration. Overview of the Process Location in the Treatment Plant CE 370 Filtration 1 Overview of the Process Location in the Treatment Plant After the water has been settled, some fine solids/flocs may still be in suspension, therefore, removal of these fine solids

More information

DW Module 23: Organic Removal Answer Key

DW Module 23: Organic Removal Answer Key DW Module 23: Organic Removal Answer Key EXERCISE UNIT 1: Use the Word Box above to complete questions. Words used twice are indicated with a (2). Word Box Air Stripping (2) Adsorption (2) Boiling Carbon

More information

Construction of Rapid Sand Filters i) Media

Construction of Rapid Sand Filters i) Media Filtration Process The flow of clarified water through a bed of granular media Purpose is to remove any particulate matter left over after flocculation and sedimentation Process operates based on 2 principles

More information

Rehabilitation by Chemical Treatment for Sand Media of Rapid Sand Filtration units for Sangli City

Rehabilitation by Chemical Treatment for Sand Media of Rapid Sand Filtration units for Sangli City IOSR Journal Of Environmental Science, Toxicology And Food Technology (IOSR-JESTFT) e-issn: 2319-2402,p- ISSN: 2319-2399. Volume 6, Issue 5 (Sep. - Oct. 2013), PP 32-37 www.iosrjournals.org Rehabilitation

More information

History of Coagulation Control. John Clark Chemtrac Inc.

History of Coagulation Control. John Clark Chemtrac Inc. History of Coagulation Control John Clark Chemtrac Inc. About Us Biofilm ph Conductivity Dissolved Oxygen Free & Total Chlorine CRONOS CRIUS ORP TSS Chlorine Dioxide Ozone Streaming Current Particle Counter

More information

FILTER OPTIMISATION AT VICTORIA S LARGEST WATER TREATMENT PLANT. Mark Jarvis. Melbourne Water Corporation

FILTER OPTIMISATION AT VICTORIA S LARGEST WATER TREATMENT PLANT. Mark Jarvis. Melbourne Water Corporation FILTER OPTIMISATION AT VICTORIA S LARGEST WATER TREATMENT PLANT Paper Presented by : Mark Jarvis Author: Mark Jarvis, Senior Process Engineer, Melbourne Water Corporation 68 th Annual Water Industry Engineers

More information

FROM RAW WATER INTAKE TO DISTRIBUTION NETWORK: THE JOURNEY OF DBP CONTROL

FROM RAW WATER INTAKE TO DISTRIBUTION NETWORK: THE JOURNEY OF DBP CONTROL FROM RAW WATER INTAKE TO DISTRIBUTION NETWORK: THE JOURNEY OF DBP CONTROL Jane Xiaojie Gan, E.I.T., Porter Rivers, P.E. URS, 101 Research Drive, Columbia, SC 29203 ABSTRACT The Chester Metropolitan District

More information

Disinfectant dosing of blended drinking waters

Disinfectant dosing of blended drinking waters 18 th World IMACS / MODSIM Congress, Cairns, Australia 13-17 July 2009 http://mssanz.org.au/modsim09 Disinfectant dosing of blended drinking waters van Leeuwen, J. 1,3, D. Cook 2, C. Chow 1,2,3 and M.

More information

WRF Webcast Optimizing Engineered Biofiltration (#4346)

WRF Webcast Optimizing Engineered Biofiltration (#4346) No part of this presentation may be copied, reproduced, or otherwise utilized without permission. WRF Webcast Optimizing Engineered Biofiltration (#4346) Click to refresh. No audio? Type in the box. 2012

More information

Rinconada Water Treatment Plant Reliability Improvement Project (RIP) Filter Pilot Study

Rinconada Water Treatment Plant Reliability Improvement Project (RIP) Filter Pilot Study Rinconada Water Treatment Plant Reliability Improvement Project (RIP) Filter Pilot Study AWWA 2014 Fall Conference Lei Hong, Ph.D., P.E. Lale Guven, Environmental Engineer October 23, 2014 Presentation

More information

REAL WORLD APPLICATIONS OF USING DYNAMIC SIMULATION SOFTWARE TO OPTIMIZE WATER TREATMENT PLANT PROCESS OPERATIONS

REAL WORLD APPLICATIONS OF USING DYNAMIC SIMULATION SOFTWARE TO OPTIMIZE WATER TREATMENT PLANT PROCESS OPERATIONS REAL WORLD APPLICATIONS OF USING DYNAMIC SIMULATION SOFTWARE TO OPTIMIZE WATER TREATMENT PLANT PROCESS OPERATIONS (FRIT05) OCTOBER 30, 2015 Authors: Matt Ridens/CH2M, Jason Curl/CH2M Overview Drivers for

More information

Ozone for the Removal of Harmful Algal Bloom Toxins and Geosmin & MIB

Ozone for the Removal of Harmful Algal Bloom Toxins and Geosmin & MIB Ozone for the Removal of Harmful Algal Bloom Toxins and Geosmin & MIB Dr. Saad Y. Jasim, P.Eng. Manager, Utilities, Engineering and Municipal Operation White Rock, BC, Canada HARMFUL ALGAL BLOOMS, CYANOBACTERIA

More information

Meeting Manganese Removal Goals: A Pilot Study

Meeting Manganese Removal Goals: A Pilot Study Meeting Manganese Removal Goals: A Pilot Study Amy Gao, Russell Ford, David Best and Manthos Tsotsos PA AWWA Annual Conference Thursday, May 12, 2016 Background Oswestry WTW Owned and Operated by United

More information

OPTIMISATION OF IMAGE FLAT WATER TREATMENT PLANT. Tony Humphries. Tony Humphries, Operator, SEQ Water

OPTIMISATION OF IMAGE FLAT WATER TREATMENT PLANT. Tony Humphries. Tony Humphries, Operator, SEQ Water OPTIMISATION OF IMAGE FLAT WATER TREATMENT PLANT Paper Presented by: Tony Humphries Author: Tony Humphries, Operator, SEQ Water 34th Annual Qld Water Industry Operations Workshop Indoor Sports Stadium,

More information

Alternative Filter Media for Potable Water Treatment

Alternative Filter Media for Potable Water Treatment Alternative Filter Media for Potable Water Treatment M.E. Steele*, M.J. Chipps*, R. Bayley*, A. Mikol** & C.S.B. Fitzpatrick** * Thames Water Research & Development ** Department of Civil & Environmental

More information

Ready, Set, and Go: Deer Valley WTP East Basins Performance Testing, Start-Up, and Commissioning Toby Teegerstrom Brian Watson

Ready, Set, and Go: Deer Valley WTP East Basins Performance Testing, Start-Up, and Commissioning Toby Teegerstrom Brian Watson Ready, Set, and Go: Deer Valley WTP East Basins Performance Testing, Start-Up, and Commissioning Toby Teegerstrom Brian Watson January 25, 2011 Presentation Outline Background Process Overview Start-Up

More information

Oxelia OXIDATION-ENHANCED BIOLOGICALLY ACTIVE FILTRATION

Oxelia OXIDATION-ENHANCED BIOLOGICALLY ACTIVE FILTRATION Oxelia OXIDATION-ENHANCED BIOLOGICALLY ACTIVE FILTRATION In the battle with hard-to-treat contaminants, drinking water just got a powerful new ally. Leopold Oxelia oxidation-enhanced biologically active

More information

Texas Hazardous Waste Research Center

Texas Hazardous Waste Research Center TO: FROM: SUBJECT: Texas Hazardous Waste Research Center Dr. Mary Jo Kirisits and Ms. Sarah Keithley The University of Texas at Austin Department of Civil, Architectural, and Environmental Engineering

More information

Treatment Technologies

Treatment Technologies Treatment Technologies Precipitation Softening INTRODUCTION CHEMISTRY OF PRECIPITATION SOFTENING COLD LIME SOFTENING WARM LIME SOFTENING HOT PROCESS SOFTENING SILICA REDUCTION REDUCTION OF OTHER CONTAMINANTS

More information

WRF Webcast Biofilter Conversion Guidance Manual

WRF Webcast Biofilter Conversion Guidance Manual No part of this presentation may be copied, reproduced, or otherwise utilized without permission. WRF Webcast Biofilter Conversion Guidance Manual March 28, 2017 Biofiltration: Defining Benefits and Developing

More information

ADSORPTION AND BIOLOGICAL FILTRATION OF MICROCYSTINS

ADSORPTION AND BIOLOGICAL FILTRATION OF MICROCYSTINS ADSORPTION AND BIOLOGICAL FILTRATION OF MICROCYSTINS By Haixiang Wang School of Chemical Engineering The University of Adelaide Australia A thesis submitted to the University of Adelaide for the degree

More information

Drinking Water Audit Report

Drinking Water Audit Report Drinking Water Audit Report County: Co. Mayo Date of Audit: 06/09/2016 Plant(s) visited: Lough Mask Water Treatment Plant, Tourmakeady, Co. Mayo Date of issue of Audit Report: File Reference: 09/09/2016

More information

REMOVAL OF COLOUR AND SOLIDS FROM QAL SEA WATER NEUTRALISATION EFFLUENT USING VEOLIA ACTIFLO HIGH RATE CLARIFIER

REMOVAL OF COLOUR AND SOLIDS FROM QAL SEA WATER NEUTRALISATION EFFLUENT USING VEOLIA ACTIFLO HIGH RATE CLARIFIER REMOVAL OF COLOUR AND SOLIDS FROM QAL SEA WATER NEUTRALISATION EFFLUENT USING VEOLIA ACTIFLO HIGH RATE CLARIFIER *Kane A 1, Leong T 1, Jenner R 2. 1 Queensland Alumina Limited 2 Formerly Veolia Water Solutions

More information

SIMPLE SOLUTIONS TO MANGANESE PROBLEMS. Jeff Roscoe. North East Region Water Authority

SIMPLE SOLUTIONS TO MANGANESE PROBLEMS. Jeff Roscoe. North East Region Water Authority SIMPLE SOLUTIONS TO MANGANESE PROBLEMS Paper Presented by : Jeff Roscoe Author: Jeff Roscoe, Plant Operator, North East Region Water Authority 65 th Annual Water Industry Engineers and Operators Conference

More information

TREATMENT OF WATER. A.Sateesh Chemist State Level Laboratory

TREATMENT OF WATER. A.Sateesh Chemist State Level Laboratory TREATMENT OF WATER A.Sateesh Chemist State Level Laboratory Treatment The aim of water treatment is to convert raw water from it s contaminate laden state to as aesthetically acceptable and hygienically

More information

Hypolimnetic Aeration System is Breathing New Life Into Aurora Reservoir

Hypolimnetic Aeration System is Breathing New Life Into Aurora Reservoir Hypolimnetic Aeration System is Breathing New Life Into Aurora Reservoir November 8, 2017 North American Lake Management Society 2017 Annual Conference M o b le y E n g i n e e r i n g Presenters and Authors

More information

MWUA 92 nd Annual February Meeting & Trade Show

MWUA 92 nd Annual February Meeting & Trade Show MWUA 92 nd Annual February Meeting & Trade Show Biological Filtration for Iron & Manganese Treatment: Operating Experience in Cavendish, VT February 7, 2018 John N. McClellan, Ph.D., P.E. Vice President

More information

Case Study: Parkson DynaSand D2 Filtration and Compliance Jessy Matthew John, The Probst Group

Case Study: Parkson DynaSand D2 Filtration and Compliance Jessy Matthew John, The Probst Group Case Study: Parkson DynaSand D2 Filtration and Compliance Jessy Matthew John, The Probst Group Primarily we will be discussing DynaSand D2 Sand Filters and performance, a method of advanced tertiary filtration.

More information

Drinking Water Audit Report

Drinking Water Audit Report Drinking Water Audit Report County: Galway Date of Audit: 21 st August 2015 Plant(s) visited: Inisboffin PWS, Scheme code 1200PUB1024 Date of issue of Audit Report: File Reference: 1 st September 2015

More information

Greater Kegalle Water Treatment Plant Kegalle, Sri Lanka

Greater Kegalle Water Treatment Plant Kegalle, Sri Lanka Greater Kegalle Water Treatment Plant Kegalle, Sri Lanka 1. Background information of the water treatment plant Kegalle is located about 80 Km East of Colombo and the Greater Kegalle water treatment plant

More information

Leopold Desalination Pretreatment Systems

Leopold Desalination Pretreatment Systems Leopold Desalination Pretreatment Systems Reliable Protection from Membrane-Fouling, Performance-Inhibiting Seawater Contaminants Why Leopold for Your Desalination Pretreatment Solution? Leopold desalination

More information

Removing Algal Toxins from the Toledo Tap

Removing Algal Toxins from the Toledo Tap Removing Algal Toxins from the Toledo Tap Warren Henry City of Toledo Nick Burns Black & Veatch Agenda Lake Erie, 2011 Background on algal toxins Concerns Treatment Effectiveness Toledo Experience Summary

More information

Removal of iron and manganese from groundwater: a study of using potassium permanganate and sedimentation

Removal of iron and manganese from groundwater: a study of using potassium permanganate and sedimentation Removal of iron and manganese from groundwater: a study of using potassium permanganate and sedimentation Mohamed Elsheikh 1, *, H. Guirguis 1, A. Fathy 1 1 Civil Engineering Department, Faculty of Engineering,

More information

Removing Heavy Metals from Wastewater

Removing Heavy Metals from Wastewater Removing Heavy Metals from Wastewater Engineering Research Center Report David M. Ayres Allen P. Davis Paul M. Gietka August 1994 1 Removing Heavy Metals From Wastewater Introduction This manual provides

More information

Environment Protection Engineering

Environment Protection Engineering Environment Protection Engineering Vol. 41 2015 No. 1 DOI: 10.5277/epe150101 JOLANTA GUMIŃSKA 1, MARCIN KŁOS 1 EFFECT OF POLYALUMINIUM CHLORIDES OVERDOSAGE ON EFFECTIVENESS OF COAGULATION AND FILTRATION

More information

ISR (IRON SPECIFIC RESIN)

ISR (IRON SPECIFIC RESIN) Technical Bulletin ISR (IRON SPECIFIC RESIN) TABLE OF CONTENTS Introduction Iron Removal Methods ISR Design Guidelines System Hydraulics Technical Superiority Applications of INDION ISR Packaging, Storage

More information

Treatment of all source water influent & effluent for user application, be it commercial, industrial, domestic, to defined & required standards.

Treatment of all source water influent & effluent for user application, be it commercial, industrial, domestic, to defined & required standards. Overview of services for Influent & Effluent Treatment Solutions offered by Nimbus technologies Generally and as a rule, source water from a local water supplier is treated and should meet with SANS 241

More information

Optimizing the Operation of Gravity Media Filters

Optimizing the Operation of Gravity Media Filters Optimizing the Operation of Gravity Media Filters Thomas M. Getting, P.E., BCEE Principal Engineer-Filtration Leopold, a xylem brand Tom.Getting@xyleminc.com 724-453-2058 Website: www.fbleopold.com Presentation

More information

Selenium Reduction. Caroline Dale

Selenium Reduction. Caroline Dale Selenium Reduction Caroline Dale > Contents Biological Selenium Reduction The MBBR technology Operating Experience SeleniumZero Conclusions 2 Selenium Cycle Se(VI) Se(IV) Se(IV) Se(0) Se(-II) Selenium

More information

BIOLOGICAL FILTRATION FOR SUSTAINABLE TREATMENT OF GROUNDWATER WITH HIGH IRON AND MANGANESE CONTENT A CASE STUDY FROM OVERSTRAND MUNICIPALITY

BIOLOGICAL FILTRATION FOR SUSTAINABLE TREATMENT OF GROUNDWATER WITH HIGH IRON AND MANGANESE CONTENT A CASE STUDY FROM OVERSTRAND MUNICIPALITY BIOLOGICAL FILTRATION FOR SUSTAINABLE TREATMENT OF GROUNDWATER WITH HIGH IRON AND MANGANESE CONTENT A CASE STUDY FROM OVERSTRAND MUNICIPALITY ABSTRACT Geoff du Toit 1, Hanre Blignaut 2, Brendon Theunissen

More information

Specific Gravity 2.69 Minimum Bed Depth 24 Inches (600mm) Effective Size Freeboard 40% minimum Uniformity Coefficient 1.4 Service Flow Rate

Specific Gravity 2.69 Minimum Bed Depth 24 Inches (600mm) Effective Size Freeboard 40% minimum Uniformity Coefficient 1.4 Service Flow Rate TECHNICAL DATA SHEET Physical Properties Colour Brown to Black ph Range Operating Conditions Bulk Density 91.0 lbs/ft 3 Maximum Water 1.46 gr/m 3 Temperature 1.46 tonne/m 3 113 o F (45 o C) Specific Gravity

More information

WAT-E Physical and Chemical Treatment of Water and Waste Filtration. Adjunct Prof. Riina Liikanen

WAT-E Physical and Chemical Treatment of Water and Waste Filtration. Adjunct Prof. Riina Liikanen WAT-E2120 - Physical and Chemical Treatment of Water and Waste Filtration Adjunct Prof. Riina Liikanen Content / Learning outcomes Overview of granular media filtration Removal and transport mechanisms

More information

Effect of physical and chemical parameters on water treatment plant effluent quality (particle count and particle size)

Effect of physical and chemical parameters on water treatment plant effluent quality (particle count and particle size) Water Pollution IX 483 Effect of physical and chemical parameters on water treatment plant effluent quality (particle count and particle size) A. Torabian 1, A. Hesam Hasani 1 & A. R. Mehrabadi 2 1 Faculty

More information

There is no sludge treatment process at NWTP. Sludge generated from sedimentation and backwashing is drained directly to the Khan River.

There is no sludge treatment process at NWTP. Sludge generated from sedimentation and backwashing is drained directly to the Khan River. Namkhan Water Treatment Plant Luang Prabang City, Lao PDR 1. Background information Luang Prabang is a touristic city situated in northern part of Lao PDR and was declared a World Heritage City by UNESCO

More information

Cary/Apex Water Treatment Facility- Ozone Biofiltration Pilot Study

Cary/Apex Water Treatment Facility- Ozone Biofiltration Pilot Study Cary/Apex Water Treatment Facility- Ozone Biofiltration Pilot Study March 26, 2018 Judith Labrada Bill Dowbiggin, PE Agenda Project Background Project Drivers Why CAWTF considered a change? What is Ozone

More information

Enhanced Filtration. CEE 453: Laboratory Research in Environmental Engineering Spring 2001

Enhanced Filtration. CEE 453: Laboratory Research in Environmental Engineering Spring 2001 142 Introduction Slow sand filters have been used to remove particles from drinking water since the early 1800's. Although slow sand filtration is an old technology, the mechanisms responsible for particle

More information

biologically active filtration

biologically active filtration biologically active filtration FOR TASTE AND ODOR CONTROL AT LAKE MANATEE WATER TREATMENT PLANT BY MIKE NIXON, EI, ENGINEER INTERN, MCKIM & CREED PHIL LOCKE, PE, SENIOR PROJECT MANAGER, MCKIM & CREED KATIE

More information

Dipti Shah, Town of Gilbert Tuesday, January 25, 2011

Dipti Shah, Town of Gilbert Tuesday, January 25, 2011 Dipti Shah, Town of Gilbert Tuesday, January 25, 2011 Background Treatment Plant Water Treatment Process Filter types Experiments Results Review Historical BAF /Non- BAF data Conclusion Recommendation

More information

The 2013 University of Oklahoma International WaTER Conference

The 2013 University of Oklahoma International WaTER Conference The 2013 University of Oklahoma International WaTER Conference Hand pump attachable iron removal plant for field implication in rural areas 12/2/2013 Poonam Gwala Senior Research Fellow CSIR- NEERI, Nagpur

More information

Renovation of the Filters at the Soldier Canyon Filter Plant in Fort Collins, Colorado

Renovation of the Filters at the Soldier Canyon Filter Plant in Fort Collins, Colorado JUST ADD WATER Renovation of the Filters at the Soldier Canyon Filter Plant in Fort Collins, Colorado Thomas M. Getting, P.E., DEE, Filtration Product Manager John Geibel, P.E., Chief Engineer Michael

More information

Evaluation of Conventional Activated Sludge Compared to Membrane Bioreactors

Evaluation of Conventional Activated Sludge Compared to Membrane Bioreactors Evaluation of Conventional Activated Sludge Compared to Membrane Bioreactors Short Course on Membrane Bioreactors 3/22/06 R. Shane Trussell, Ph.D., P.E. shane@trusselltech.com Outline Introduction Process

More information

Nakhon Sawan Water Treatment Plant Nakhon Sawan, Thailand

Nakhon Sawan Water Treatment Plant Nakhon Sawan, Thailand Nakhon Sawan Water Treatment Plant Nakhon Sawan, Thailand 1. Background Information Nakhon Sawan is located about 250 km north of Bangkok and marks the point of confluence of two of major Thai rivers,

More information

6.5 Filtration General

6.5 Filtration General 6.5 Filtration 6.5.1 General Turbidity and algae are removed from raw waters by screens, gravel filters and slow sand or rapid gravity filters. The difference between slow and rapid sand filtration is

More information

Another Tool in Our Toolbox

Another Tool in Our Toolbox BIOLOGICAL FILTRATION Another Tool in Our Toolbox Presented by: Grant L. Meyer, PE Surface Water Treatment Workshop May 2, 2018 BIOLOGICAL FILTRATION What is Biological Filtration? Why Consider Biological

More information

Government Center Water Treatment Plant Kamphaeng Phet Province, Thailand

Government Center Water Treatment Plant Kamphaeng Phet Province, Thailand Government Center Water Treatment Plant Kamphaeng Phet Province, Thailand 1. Background information Kamphaeng Phet is a province in the lower north of Thailand. The Ping River (main tributary of the Chao

More information

Health Based Targets Application of Log Reduction Values. Phillip Fasham Manager Water Quality Regulations and Verification

Health Based Targets Application of Log Reduction Values. Phillip Fasham Manager Water Quality Regulations and Verification Health Based Targets Application of Log Reduction Values Phillip Fasham Manager Water Quality Regulations and Verification Contents Log Credits & Treatment Barriers Typical Treatment Components and Critical

More information

CERAMIC MEMBRANE PILOT TESTING ON LAKE MICHIGAN. Abstract. Introduction. Background. Objectives

CERAMIC MEMBRANE PILOT TESTING ON LAKE MICHIGAN. Abstract. Introduction. Background. Objectives CERAMIC MEMBRANE PILOT TESTING ON LAKE MICHIGAN Holly Shorney-Darby, PhD, PE PWN Technologies, Dijkweg 1, 1619ZH Andijk, Netherlands, hshorney@pwntechnologies.com, +31(0)622737075 Rob Michaelson, Manitowoc

More information

MIEX RESIN WATER TREATMENT PROCESS

MIEX RESIN WATER TREATMENT PROCESS MIEX RESIN WATER TREATMENT PROCESS Marin Slunjski*, Keith Cadee**, John Tattersall*** * Orica Watercare, Adelaide, Australia ** Water Corporation of Western Australia, Perth, Australia *** Black & Veatch,

More information

Module 23 : Tertiary Wastewater Treatment Lecture 39 : Tertiary Wastewater Treatment (Contd.)

Module 23 : Tertiary Wastewater Treatment Lecture 39 : Tertiary Wastewater Treatment (Contd.) 1 P age Module 23 : Tertiary Wastewater Treatment Lecture 39 : Tertiary Wastewater Treatment (Contd.) 2 P age 23.3.6 Membrane module A single operational unit into which membranes are engineered for used

More information

A Study of Water Treatment at the Bhandup Water Treatment Plant, Mumbai.

A Study of Water Treatment at the Bhandup Water Treatment Plant, Mumbai. A Study of Water Treatment at the Bhandup Water Treatment Plant, Mumbai. Arshia Mehta May 2017 CAID 17615623 The water treatment in Mumbai is carried out by the Municipal Corporation of Greater Mumbai.

More information

Drinking Water Supply and

Drinking Water Supply and Drinking Water Supply and Health Engineered Water Systems Water and Health 80% of sickness in the world is caused by inadequate water supply or sanitation 40% of the world population does not have access

More information

Evaluation of Powdered Activated Carbon Feed System For Taste and Odor Removal at City of Camden WTP. Jane Gan

Evaluation of Powdered Activated Carbon Feed System For Taste and Odor Removal at City of Camden WTP. Jane Gan Evaluation of Powdered Activated Carbon Feed System For Taste and Odor Removal at City of Camden WTP Jane Gan Outline of the Presentation 2 An Overview of Algae Related T&O Factors affecting algae growth

More information

Water Treatment. Water Treatment. Water Treatment. Water Treatment. CIVL 1101 Introduction to Filtration 1/15

Water Treatment. Water Treatment. Water Treatment. Water Treatment. CIVL 1101 Introduction to Filtration 1/15 CIVL 1101 Introduction to 1/15 Water treatment describes those industrial-scale processes used to make water more acceptable for a desired end-use. These can include use for drinking water, industry, medical

More information

Overcoming Challenges to Achieve Optimization at the Crown Water Treatment Plant. Barbara Martin AWWA Mark Petrie Cleveland Water

Overcoming Challenges to Achieve Optimization at the Crown Water Treatment Plant. Barbara Martin AWWA Mark Petrie Cleveland Water Overcoming Challenges to Achieve Optimization at the Crown Water Treatment Plant Barbara Martin AWWA Mark Petrie Cleveland Water Outline Partnership for Safe Water Background Program Phases Crown Water

More information

FILTRATION INDUSTRY -An Overview

FILTRATION INDUSTRY -An Overview FILTRATION INDUSTRY -An Overview Introduction The term filtration, as applied to water treatment, refers to the removal of suspended solids from water. In most cases it is the last stage in the pre treatment

More information

Morton Treatment Plant Process Performance Evaluations: The Removal of Microbial Nutrients

Morton Treatment Plant Process Performance Evaluations: The Removal of Microbial Nutrients Morton Treatment Plant Process Performance Evaluations: The Removal of Microbial Nutrients H 2 O C, Limited 2401 Tahoe Court Columbia, Missouri 65203-1444 877-22-WATER Chronology of Project Initiation

More information

Submerged Membranes to Replace Media Filters to Increase Capacity 4X for a Small Community. Richard Stratton, PE HDR Engineering, Inc.

Submerged Membranes to Replace Media Filters to Increase Capacity 4X for a Small Community. Richard Stratton, PE HDR Engineering, Inc. Submerged Membranes to Replace Media Filters to Increase Capacity 4X for a Small Community Richard Stratton, PE HDR Engineering, Inc. Main Points of this Presentation Membranes can provide 4 times the

More information

Environmental Chemistry - Water HL

Environmental Chemistry - Water HL Name: Environmental Chemistry: Water 19. Environmental Chemistry - Water Objectives -define hardness in water -define temporary hardness in water -define permanent hardness in water -identify the causes

More information

Index. AWWA see American Water Works Association AWWARF see American Water Works Association Research Foundation

Index. AWWA see American Water Works Association AWWARF see American Water Works Association Research Foundation Index algae blue-green 8 concentration/theoretical flowpath relationship 12 microstrainer performance 8 ozone effectiveness 58 removal under coagulation conditions 17 American Water Works Association (AWWA)

More information

FUNDAMENTALS OF GRANULAR MEDIA FILTRATION. Gordon Williams, PhD, PE East Bay Municipal Utility District

FUNDAMENTALS OF GRANULAR MEDIA FILTRATION. Gordon Williams, PhD, PE East Bay Municipal Utility District FUNDAMENTALS OF GRANULAR MEDIA FILTRATION Gordon Williams, PhD, PE East Bay Municipal Utility District 1 OVERVIEW Filtration basics Filtration theory Filter media selection and design Monitoring and Troubleshooting

More information