B Improvements on High Voltage Electrical Substations to face the new Brazilian Legislation. G. M. Bastos (*) R. C. Valente E.

Size: px
Start display at page:

Download "B Improvements on High Voltage Electrical Substations to face the new Brazilian Legislation. G. M. Bastos (*) R. C. Valente E."

Transcription

1 21, rue d'artois, F Paris B3-214 Session 2004 CIGRÉ Improvements on High Voltage Electrical Substations to face the new Brazilian Legislation G. M. Bastos (*) R. C. Valente E. Leser J. L. F de Almeida O. J. M. da Motta Furnas Centrais Elétricas S.A. Rio de Janeiro - Brazil Abstract: The objective of this work is to present the improvements implemented in high voltage substations to attenuate the effects of the new structuring of the Brazilian Electric Section. The modifications and improvements were done in the substations with the purpose of quickly replacing defective transformers by its spare units, minimizing unavailability of the facilities. It will also be presented the on line monitoring system that is being installed in some substations with the purpose of on line monitor equipment. Keywords: Improvements, On line monitoring, Switching system, Transformers, Substations, Plug Cubicle, Transfer bars, Equipment 1- Introduction The deregulation of the Brazilian Electric System led the Brazilian utilities, private or public, to adapt themselves to this new reality. All the new electrical installations, such as substations or overhead transmission lines, are bid by ANEEL, the National Regulating Agency of the Brazilian System. In this way the electrical market became very competitive. Legislation created by the Agency foresees heavy penalties for unavailability of electrical equipment. In the last biddings for concession of transmission facilities made by ANEEL, penalties corresponding to 10 times the revenue are foreseen for scheduled outages. For non-scheduled outages the penalties are 150 times the revenue for the first 5 hours and 10 times the revenue for the subsequent hours. A quick analysis of these figures shows that a not scheduled outage of 5 hours, means a revenue loss of up to 750 hours (150 x 5 hours), which corresponds to one month revenue. According to the legislation scheduled outages are all those requested, in advance, to the ONS - The Company in charge of the operation of Brazilian System. All other outages are classified as nonscheduled ones. For example, the preventive and corrective maintenances are considered as scheduled outages while the failures or defects that remove from operation the transformers are examples of non scheduled ones. * Gilson Machado Bastos Furnas Centrais Elétricas S.A. gbastos@furnas.gov.br

2 As transformers are the kind of equipment associated with the largest revenues, some measures has been taken in order to adapt itself to the new demands, minimize penalties and remain competitive. The taken measures have the purpose to reduce the number of scheduled and non-scheduled outages and, since outages are unavoidable, replacing the transformer by the spare unit as fast as possible. To reduce the unavailability of an unit, it was projected a group of improvements that all together reduced the time of a transformer replacement from some hours to 20 minutes. To decrease the number of outages intelligent systems capable to monitor on-line the main equipment are being installed. On-line monitoring systems can be used continuously during the operation of the main substation equipment and offer in that way a possibility to record different relevant stresses which can affect their lifetime. The automatic evaluation of these data allows the early detection of incoming failures and performing conditioned based maintenance. 2- Transformer Replacement System As a generation and transmission power utility responsible for the transmission of large blocks of energy in voltages that vary from 138 to 765 kv, the power transformers installed in our system are rather great and heavy which require a large structure for movement them. The replacement of such great transformers as single-phase units of 765/345kV, 550 MVA may last more than one day. This time has an enormous cost, if one considers the loss of revenue due to the unavailability of the bank, besides the foreseen penalties. With the purpose of replacing a transformer installed in the smaller time possible a set of measures that combined can reduce the time of unavailability was developed. The system developed for quickly replacing a transformer is based on the philosophy adopted in our facilities of using bank of transformers formed by three single phases units instead of three phase units and the use of one spare unit for each Substation. The designed measures comprise the use of transfer bars, the installation of switches for the transfer of the units and the use of plug cubicles, which will be described below Transfer bars In order to allow the replacement of a transformer by a spare unit without the need of moving it, transfer bars are installed in all voltage sides of the transformer bank. These bars consist of rigid bus bar, installed in front of the terminals of the transformers, to which the spare transformer is permanently connected. 2.2 Switching system In the past the replacement of a single-phase transformer by its spare was made manually, through removable links previously designed for this purpose. The substitution of a transformer could last some hours, mainly in case of extra high voltage transformers, and didn't attend the demands imposed by the new model. Thus, it was necessary to develop a system that would reduce the time of replacement of the transformers. An automatic system that consists of the installation of single phase switches, motorized, connecting the terminal bushings of the transformers to the transfer bars was then designed. These switches are commanded locally or remotely, manually or automatically, through the digital control of the Substation. 2

3 An example of a scheme used in the Substations is shown in the Figure 1 below. Figure 1 - Single-phase electrical scheme showing the switching system used for transformers bank The switches used for the switching system are single-phase conventional ones. It should be pointed out that the switches that connect the phase unit to the transfer bar are subject to phase-phase voltage across their terminals when carrying out thir function of placing the spare unit in operation. For this purpose, the manufacturers supplied switches with larger gap distances. Special additional tests are foreseen for this case, such as the application of switching surges at both ends of the switches. Considering that transformers tertiary windings are usually delta connected, they deserve a special treatment. Initially, a total replacement of the transformer was foreseen, in order to maintain in operation the load connected to the tertiary. However, this option was shown onerous and complex due to the need to settle a great amount of switches in an area where the space is usually reduced. Thus, it was decided that the tertiary windings would not be substituted automatically and only grounded through switches at one end and connected to surge arresters at the other. In case of necessity, the load connected to the tertiary can be restored manually through links in more appropriate time. As for the neutral terminals, they are permanently connected to the neutral bar, grounded in one only point. Switching systems like these have been installed in some facilities, the first one was put into operation on the middle of The use of this same philosophy for single-phase shunt reactor banks is only justified in the cases where this equipment is essential for the operation of the electric system. This may happen in reactors installed at the end of some transmission lines. As the switches of the system have a very important function they needs high reliability. Then, they are equipped with a monitoring system Plug Cubicles The use of automatic switching system reduced the time of replacement of the transformers drastically. However the total replacement time is yet limited by the time spent for the connection of the whole control, supervision and protection systems, formed by hundreds of cables. 3

4 The task of substituting and testing these hundreds of control, supervision and protection cables could last some hours. In order to reduce this time, a cubicle was designed with multi pole plugs, armored, for the connection of all cables from control protection and supervision circuits. The plug cubicles can be installed inside or adjacent to the transformer common cubicles and they have sockets for the three phases of transformers and for the spare unit. Inside the panel and to make the connections easier, the circuits are combined by its purpose and clearly identified as current circuits, alarm circuits, trip circuits temperature circuits, etc. The philosophy of the plug cubicle is presented in the figure 2 where a connection diagram for a bank of transformers formed by three single-phase units and an spare unit is shown. Figure 2- Plug cubicle used to facilitate transformer replacement A drawing of a plug cubicle is shown in the Figure 3 bellow. Figure 3 - Outline drawing of a plug cubicle 4

5 The following photos show a plug cubicle installed in the common cubicle of three single phase transformers bank, 525/138 kv, 133 MVA. Figure 4 - Photographs showing the internal view of a transformer plug cubicle When it is necessary to replace a transformer unit by its spare, the operator of the substation can easily and very quickly disconnect the plugs of the phase to be substituted and connect them to the proper sockets of the spare unit. The installation of the plug cubicles has reduced the total transformer replacement time, no matter how large its dimensions are, to 20 minutes, the time necessary for the connection of all plugs, task still done manually. However, we are evaluating the use of PLC - Programmable Logic Controller - to execute this task which could reduce the time of substitution to just a few minutes. One additional advantage of this system is to assure that all transformers have the same operation time if the replacement is done from time to time Economical Evaluation The automatic switching is not very expensive and can be easily installed in new substations. To install a new 765/525 kv transformers bank, which annual revenue is US$ ,00 the cost of the switching system is US$ ,00. If one applies the penalties imposed by ANEEL for this installation, one non-scheduled outage of 5 hours would lead to a penalty of US ,00. Only one quick replacement of the transformer by its spare unit will save, in terms of penalty reduction, an amount equivalent to all costs related to the switching system. 3 - On Line Monitoring System The monitoring system has the purpose of "on line" monitor the state of the equipment, supplying means and conditions so that the maintenance people can modify its routine of preventive maintenance for a corrective one and, consequently, to decrease the time and the number of outages for maintenance. Besides, the system helps to detect incipient defects, decreasing the risk of failures and, in consequence, reducing the non-schedule outages. It was decided to monitor transformers, reactors, breakers, switches and series capacitors banks implementing a monitoring network where monitoring servers from different substations are connected to. The necessary information to the monitoring system is acquired through sensors, installed in the equipments and all monitoring data are directly accessed through web servers. The 5

6 utility internal network (Intranet) is connected to the monitoring network, facilitating the remote access to a group of users previously authorized. Through the monitoring system it can be verified, graphically, the evolution of the variables monitored, analyzing its tendencies and correlating them in such a way to establish diagnostics of the situation of the equipment and to establish prognostics of the future behavior of the equipment on the grounds of the present values. The installation of monitoring systems was a strategic decision to adapt to the new market, when, more than never, readiness and reliability became imperatives. The typical architecture of a monitoring system is shown in the following illustration. Figure 5 - Monitoring system architecture Through the study of the data obtained by the on line monitoring system, the periodic maintenance should be well established and the outages can be scheduled. In the future, the monitoring system shall be integrated and shall operate altogether with the supervision system, in order to allow a more consistent analysis of equipment's defects. The monitoring system can be divided in the following sub-systems: - Data Acquisition: Sensors - Data Treatment: Prognostics and Diagnostics; - Data Transmission: Architecture of the System; - Data Presentation Data Acquisition: Sensors The data acquisition is done through sensors installed in the body of the equipment to be monitored. The sensors are responsible for the collection of several informations about the monitored equipment. The choice of the variables to be monitored was based on the operative experience, in the historical of maintenance and in the sensors available on the market. 6

7 3.2- Data Treatment: Prognostics and Diagnostics. Diagnostics is the identification of the probable cause of a failure or defect, while prognostic is the indication of its tendency that may lead to deterioration of components or cause failures or defects. For the identification of a diagnostic and/or calculation of a prognostic it is necessary the manipulation of a specific group of values and the use of some mathematical equations or models, elaborated according to the operative needs and together with the expertise of the manufacturers Data Transmission: Architecture of the System. One of the largest challenges of this system was to create one system that can work together with the products developed by the different manufacturers, with varied communication protocols and data storage. The monitoring system specification establishes an open system, using worldly known communication protocols and data storage. The main technical characteristics of the architecture of the system, unique in the world are listed bellow. - Monitoring network: Systems of different manufacturers are to be directly connected to the network to allow easy accesses, avoiding that the substation control room be overcrowded with monitors and computers dedicated to each supplied equipment; - Connection of the monitoring network with the internal INTRANET is controlled by an access device to the network (fire-wall); - WEB pages: Monitoring data will be stored according to a standard format of database and accessible through WEB pages similar to the INTERNET standard; - Standard database format, commercially available on the market, is used so that applications can be developed for different maintenance purposes helping decisions Data Presentation The collected data, as well as the result of the diagnostics and prognostics of the system, are shown through tables and graphs in any personal computer connected to the internal net. Besides, tendency curves can be traced combining more than one variable to provide technical information of the behavior of the equipment 3.5- Economical analysis The first facilities with a monitoring system was put into operation in 2003 and a more detailed analysis of the economic advantages in function of both reduction of the maintenance costs and reduction of the number of defects will only be possible after some years of utilization. However, the reduction of the number of outages for preventive maintenance already justifies the investment in extra high voltage transformers due to revenue associated to them and also by the duration of their replacement. Regarding at the cost of installation of this system, using the example of the transformer 765/525 kv mentioned previously, the cost of the system was approximately of 5 % in relation to the cost of the equipment. 4- Conclusion The improvements introduced to face the new model have shown to be effective to minimize the time of transformers replacement for up to 20 minutes, reducing thus the penalties imposed by the National Agency of Energy. They also bring benefits to the system, since they allow the fast restoration of the system if a substitution of a transformer for its spare is needed. The use of Programmable Logic 7

8 Controllers - PLC - instead of the plug cubicles is a natural evolution and it should be implemented in the future, increasing even more the reliability of the system and reducing the time for replacement of transformers. The Monitoring System facilitates the maintenance of the main equipment of the substations, optimizes the periods between maintenances, formerly accomplished periodically. Also, it will allow knowledge of the state of the equipment in order to foresee the occurrence of failures or defects, to minimize the unavailability and to improve the operation of the Brazilian electric system. The justification for on-line monitoring of power transformers is driven by the needs of electrical utilities to reduce operating costs and enhance the availability and reliability of their equipment. The evaluation of data acquired by an on-line monitoring system shows the capability to detect incoming failures within active part, bushings, on-load tap changer and cooling unit. Using the benefits of modern Internet technology the distribution of information about the condition of the equipment can easily be done by means of standardized web browser technology. When considering the installation of on-line monitoring systems, the size, importance and condition of a power transformer should be analyzed. Especially for old transformers and in general at strategic locations in the electrical network on-line monitoring is necessary and recommended, because it saves the costs related to outages, repair and associated collateral damages due to major failures. 5- Bibliography [1] S. Tenbohlen, G. Bastos and others: " Experienced-based Evaluation of Economical Benefits of On-line Monitoring Systems for Power Transformers" CIGRE Session 2002, Paris, [2] Cláudio Semprine, G Bastos and others: Como Furnas enfrenta os desafios impostos pelo novo modelo do setor elétrico - Melhorias e Modernizações" Cigrè - SNPTEE- Brazil 2003 [3] Orlando M. da Mota, and others: Sistemas de monitoramento para equipamentos de subestações de energia elétrica, Cigrè - SNPTEE- Brazil 2003 [4] G. Bastos:" Major Electrical Equipments Monitoring Systems - The Brazilian experience" T & D July

International ejournals

International ejournals ISSN 2249 5460 Available online at www.internationalejournals.com International ejournals International Journal of Mathematical Sciences, Technology and Humanities 21 (2011) 205 212 ENERGY CONTROL CENTER

More information

Experienced-based Evaluation of Economic Benefits of On-line Monitoring Systems for Power Transformers

Experienced-based Evaluation of Economic Benefits of On-line Monitoring Systems for Power Transformers 21, rue d'artois, F-75008 Paris http://www.cigre.org 12-110 Session 2002 CIGRÉ Experienced-based Evaluation of Economic Benefits of On-line Monitoring Systems for Power Transformers by S. Tenbohlen *,

More information

Designated Entity Design Standards Task Force (DEDSTF) Minimum Design Requirements for FERC Order 1000 Projects. System Protection Subgroup

Designated Entity Design Standards Task Force (DEDSTF) Minimum Design Requirements for FERC Order 1000 Projects. System Protection Subgroup Designated Entity Design Standards Task Force (DEDSTF) Minimum Design Requirements for FERC Order 1000 Projects System Protection Subgroup For any substation facility included in the scope of a transmission

More information

EQUIPMENT CONDITION MONITORING

EQUIPMENT CONDITION MONITORING EQUIPMENT CONDITION MONITORING FOR MORE THAN 25 YEARS, TREETECH HAS PIONEERED IN THE DEVELOPMENT OF INTELLIGENT SENSORS AND ONLINE HIGH-VOLTAGE DEVICE PROGNOSIS, DIAGNOSIS, AND MONITORING SOFTWARE IN ORDER

More information

OPERATIONAL PROCEDURES FOR CONNECTION OF AUTOPRODUCERS AND INDEPENDENT POWER PRODUCERS IN THE DISTRIBUTION NET

OPERATIONAL PROCEDURES FOR CONNECTION OF AUTOPRODUCERS AND INDEPENDENT POWER PRODUCERS IN THE DISTRIBUTION NET - OPERATIONAL PROCEDURES FOR CONNECTION OF AUTOPRODUCERS AND INDEPENDENT POWER PRODUCERS IN THE DISTRIBUTION NET Camargo Dirceu B. dirceu.camargo@elektro.com.br 1. INTRODUCTION With the energy crisis lived

More information

2012 Grid of the Future Symposium. Proposed Business Case Model for Implementing a Self-Healing Distribution Smart Grid

2012 Grid of the Future Symposium. Proposed Business Case Model for Implementing a Self-Healing Distribution Smart Grid 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2012 Grid of the Future Symposium Proposed Business Case Model for Implementing a Self-Healing Distribution Smart Grid

More information

Study Committee A3. High Voltage Equipment. Action Plan

Study Committee A3. High Voltage Equipment. Action Plan Study Committee A3 High Voltage Equipment Action Plan October 2011 CIGRE Study Committee A3 - High Voltage Equipment Action Plan 1 Content 1 Content...2 2 Purpose of the Action Plan...3 3 Activities of

More information

National Grid s Approach to Commissioning of Smart Grid Pilot Devices. J. VALENZUELA M.L. COOPER National Grid USA

National Grid s Approach to Commissioning of Smart Grid Pilot Devices. J. VALENZUELA M.L. COOPER National Grid USA 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium National Grid s Approach to Commissioning of Smart Grid Pilot Devices J. VALENZUELA

More information

B3-101 STRATEGIES FOR OPTIMIZING THE USE OF SUBSTATION ASSETS. W. DEGEN K. LASKOWSKI Siemens AG (Germany)

B3-101 STRATEGIES FOR OPTIMIZING THE USE OF SUBSTATION ASSETS. W. DEGEN K. LASKOWSKI Siemens AG (Germany) 21, rue d'artois, F-75008 Paris http://www.cigre.org B3-101 Session 2004 CIGRÉ STRATEGIES FOR OPTIMIZING THE USE OF SUBSTATION ASSETS G. BALZER * Darmstadt University of Technology W. DEGEN K. LASKOWSKI

More information

A Unified, Intelligent & Evolvable Solution to Enable NERC CIP Compliance and Substation Knowledge

A Unified, Intelligent & Evolvable Solution to Enable NERC CIP Compliance and Substation Knowledge A Unified, Intelligent & Evolvable Solution to Enable NERC CIP Compliance and Substation Knowledge Travis Jaffray SUBNET Solutions, Inc Modern Challenges, Modern Opportunities Existing Infrastructure Internal

More information

AMERICAN RENEWABLES GAINESVILLE REGIONAL UTILITIES GAINESVILLE RENEWABLE ENERGY CENTER

AMERICAN RENEWABLES GAINESVILLE REGIONAL UTILITIES GAINESVILLE RENEWABLE ENERGY CENTER AMERICAN RENEWABLES GAINESVILLE REGIONAL UTILITIES --------------------------------------------- GAINESVILLE RENEWABLE ENERGY CENTER OPERATING PROCEDURES Revision 0; September 1, 2012 Revision 1; November

More information

Standard MH-TPL Transmission System Planning Performance Requirements

Standard MH-TPL Transmission System Planning Performance Requirements A. Introduction 1. Title: Transmission System Planning Performance Requirements 2. Number: MH-TPL-001-4 3. Purpose: Establish Transmission system planning performance requirements within the planning horizon

More information

Featured Product. Transformer Monitoring and Diagnostic Systems

Featured Product. Transformer Monitoring and Diagnostic Systems Featured Product Transformer Monitoring and Diagnostic Systems Transformer Predictive Analysis Owners of critical transformer equipment can realize the benefits of predictive analysis on transformer health

More information

ExISTING SubSTATION INfORmATIONON

ExISTING SubSTATION INfORmATIONON ExISTING SubSTATION INfORmATIONON drives equipment LIFe extension, modernization, and retrofitting david dolezilek and GeraLdo rocha, Schweitzer Engineering Laboratories, Inc. i. introduction Much of the

More information

A SUBSTATION CONCEPT FOR CHANGEABLE LOAD CONDITIONS

A SUBSTATION CONCEPT FOR CHANGEABLE LOAD CONDITIONS A SUBSTATION CONCEPT FOR CHANGEABLE LOAD CONDITIONS Willy LORD SwedPower AB Sweden willy.lord@swedpower.com Lennart AHNLUND Vattenfall Eldistribution AB Sweden B. WALLBING-LÖVGREN Vattenfall Eldistribution

More information

CONTENTS. 1.Scope 1. 2.General Conditions 1. 3.Material Information 1. Table 1 - TRHP Three-Phase Recloser 24.2 kv 1

CONTENTS. 1.Scope 1. 2.General Conditions 1. 3.Material Information 1. Table 1 - TRHP Three-Phase Recloser 24.2 kv 1 CONTENTS Page 1.Scope 1 2.General Conditions 1 3.Material Information 1 Table 1 - TRHP Three-Phase Recloser 24.2 kv 1 Table 2 - TRHP Single-Phase Recloser 15 kv 2 DISTRIBUTION ND 2.6 Table 3 - TRHP Three-Phase

More information

Research and Application Study on Accident-Based 3D Power Station Simulation Technology

Research and Application Study on Accident-Based 3D Power Station Simulation Technology International Conference on Electromechanical Control Technology and Transportation (ICECTT 2015) Research and Application Study on Accident-Based 3D Power Station Simulation Technology Tie Li, Xiaoming

More information

AMERICAN RENEWABLES GAINESVILLE REGIONAL UTILITIES GAINESVILLE RENEWABLE ENERGY CENTER

AMERICAN RENEWABLES GAINESVILLE REGIONAL UTILITIES GAINESVILLE RENEWABLE ENERGY CENTER AMERICAN RENEWABLES GAINESVILLE REGIONAL UTILITIES --------------------------------------------- GAINESVILLE RENEWABLE ENERGY CENTER OPERATING PROCEDURES Revision 0; September 1, 2012 Revision 1; November

More information

Information Document Protection System Information ID# R

Information Document Protection System Information ID# R Information Documents are for information purposes only and are intended to provide guidance. In the event of any discrepancy between the Information Document and the related authoritative document(s)

More information

Improved transformer temperature monitoring. Increasing the availability, reliability, and reducing maintenance costs COLUMN ABSTRACT KEYWORDS

Improved transformer temperature monitoring. Increasing the availability, reliability, and reducing maintenance costs COLUMN ABSTRACT KEYWORDS ABSTRACT This article discusses transformer temperature monitoring where a strategy of reduction in maintenance costs and outages, by replacing older ancillary technology with modern IEDs, can offer a

More information

Analysis of distribution system reliability and outage rates

Analysis of distribution system reliability and outage rates Reclosers Technical Data TD280026EN Supersedes pril 2003 (R280-90-7) COOPER POWER SERIES nalysis of distribution system reliability and outage rates Recloser Technical Data TD280026EN nalysis of distribution

More information

Standard Development Timeline

Standard Development Timeline Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard is adopted by the NERC Board of Trustees (Board).

More information

Standard TPL Transmission System Planning Performance Requirements

Standard TPL Transmission System Planning Performance Requirements A. Introduction 1. Title: Transmission System Planning Performance Requirements 2. Number: TPL-001-4 3. Purpose: Establish Transmission system planning performance requirements within the planning horizon

More information

PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES

PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

IMPLEMENTATION OF DISTRIBUTION AUTOMATION SYSTEMS (DAS) IN THE ELECTRICA COMPANY ROMANIA

IMPLEMENTATION OF DISTRIBUTION AUTOMATION SYSTEMS (DAS) IN THE ELECTRICA COMPANY ROMANIA IMPLEMENTATION OF DISTRIBUTION AUTOMATION SYSTEMS (DAS) IN THE ELECTRICA COMPANY ROMANIA Gheorghe Ion MAZILU - ELECTRICA SA Mihaela CONU - ELECTRICA SA Romania Romania Serban COCULESCU - ANRE Adrian Ion

More information

Standard Development Timeline

Standard Development Timeline Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard is adopted by the NERC Board of Trustees (Board).

More information

Modicon Advance Program Your migration to the future

Modicon Advance Program Your migration to the future Modicon Advance Program Your migration to the future Improve process integrity. Maximize system expandability. Increase automation platform return on investment. Advance your legacy products to state-of-the-art

More information

WILEY A JOHN WILEY & SONS, INC., PUBLICATION

WILEY A JOHN WILEY & SONS, INC., PUBLICATION POWER DISTRIBUTION SYSTEM RELIABILITY Practical Methods and Applications Ali A. Chowdhury Don O. Koval IEEE PRESS SERIES ON POWER ENGINEERING IEEE Press WILEY A JOHN WILEY & SONS, INC., PUBLICATION Preface

More information

The Analysis of Renovation Criteria for Protective Relay in Power Substation

The Analysis of Renovation Criteria for Protective Relay in Power Substation The Analysis of Renovation for Protective Relay in Power Substation Thanapong Suwanasri, Cattareeya Suwanasri, Tospon Hearunyakij, and Sarawut Wattanawongpitak Abstract This paper proposes the renovation

More information

CIRED Workshop - Lyon, 7>8 June 2010 Paper 0004 ABSTRACT WHAT IS ISCM? INTRODUCTION WHY ISCM?

CIRED Workshop - Lyon, 7>8 June 2010 Paper 0004 ABSTRACT WHAT IS ISCM? INTRODUCTION WHY ISCM? ISCM, INTEGRATED SUBSTATION CONDITION MONITORING Norbert KAISER Markus SCHULER Chris CHARLSON Germany Germany UK nkkaiser@siemens.com markus.schuler@siemens.com chris.charlson@siemens.com ABSTRACT This

More information

Evaluating Your Electrical Distribution System

Evaluating Your Electrical Distribution System Evaluating Your Electrical Distribution System September 22, 2016 Doug Marshall, P.Eng, Reliability Engineer Magna IV Engineering 2 Introduction Virtually all industrial and commercial installations are

More information

Enhance Power Equipment Reliability with Predictive Maintenance Technologies

Enhance Power Equipment Reliability with Predictive Maintenance Technologies Enhance Power Equipment Reliability with Predictive Maintenance Technologies November 2012/1910DB1208 by S. Frank Waterer, Electrical Engineerinig, Fellow Schneider Electric USA, Inc. Make the most of

More information

FIELD TEST AND OPERATIONAL CHECK SECTION A. Refer to Section 16010, Electrical General Requirements.

FIELD TEST AND OPERATIONAL CHECK SECTION A. Refer to Section 16010, Electrical General Requirements. FIELD TEST AND OPERATIONAL CHECK SECTION 16080 PART 1 GENERAL 1.1 GENERAL REQUIREMENTS A. Refer to Section 16010, Electrical General Requirements. 1.2 WORK INCLUDED A. General Scope: 1. The Contractor

More information

Lifetime Decisions. Investments can be planned, lifetime costs of equipment made transparent and decisions based on informed fact.

Lifetime Decisions. Investments can be planned, lifetime costs of equipment made transparent and decisions based on informed fact. Lifetime Decisions Ageing assets, rising energy demand, and the need to deliver without outage are issues facing utilities and industries around the world. At the same time, financial constraints demand

More information

Standard Development Timeline

Standard Development Timeline Standard TPL-001-4 Transmission System Planning Performance Requirements Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be

More information

16300 HIGH VOLTAGE DISTRIBUTION

16300 HIGH VOLTAGE DISTRIBUTION 16300 HIGH VOLTAGE DISTRIBUTION PART 1: GENERAL 1.01 WORK INCLUDED A. Most new loads will be served from the underground electric distribution system. This system is a primary open loop configuration served

More information

B Improved Performance of OPGW Under Lightning Discharges in Brazilian Regions with a High Keraunic Level

B Improved Performance of OPGW Under Lightning Discharges in Brazilian Regions with a High Keraunic Level 21, rue d'artois, F-75008 Paris http://www.cigre.org B2-316 Session 2004 CIGRÉ Improved Performance of OPGW Under Lightning Discharges in Brazilian Regions with a High Keraunic Level by M.G.Alvim (*) A.O.Silva

More information

Multi-Agent Model for Power System Simulation

Multi-Agent Model for Power System Simulation Multi-Agent Model for Power System Simulation A.A.A. ESMIN A.R. AOKI C.R. LOPES JR. G. LAMBERT-TORRES Institute of Electrical Engineering Federal School of Engineering at Itajubá Av. BPS, 1303 Itajubá/MG

More information

ORC TURBOGENERATOR TYPE CHP - Organic Rankine Cycle Turbogenerator fed by thermal oil, for the combined production of electric energy and heat -

ORC TURBOGENERATOR TYPE CHP - Organic Rankine Cycle Turbogenerator fed by thermal oil, for the combined production of electric energy and heat - Doc. : 08C00031_e Date : 02.02.2009 Page : 1 / 9 ORC TURBOGENERATOR TYPE CHP - Organic Rankine Cycle Turbogenerator fed by thermal oil, for the combined production of electric - (Preliminary) Doc. : 08C00031_e

More information

Standard PRC-002-NPCC-01 Disturbance Monitoring

Standard PRC-002-NPCC-01 Disturbance Monitoring A. Introduction 1. Title: Disturbance Monitoring 2. Number: PRC-002-NPCC-01 3. Purpose: Ensure that adequate disturbance data is available to facilitate Bulk Electric System event analyses. All references

More information

Fault Current Contributions from Wind Plants Dean Miller PacifiCorp July 25, 2012

Fault Current Contributions from Wind Plants Dean Miller PacifiCorp July 25, 2012 Fault Current Contributions from Wind Plants Dean Miller PacifiCorp July 25, 2012 1 Presentation Overview Joint Working Group The Issue Structure of the Report Wind Plant Configuration Wind Turbine Generators

More information

Electricity Supply to Africa and Developing Economies Challenges and Opportunities. Technology solutions and innovations for developing economies

Electricity Supply to Africa and Developing Economies Challenges and Opportunities. Technology solutions and innovations for developing economies Electricity Supply to Africa and Developing Economies Challenges and Opportunities Technology solutions and innovations for developing economies Employment of various strategies in Eskom to optimize the

More information

Standard Development Timeline

Standard Development Timeline Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard is adopted by the NERC Board of Trustees (Board).

More information

Grid Solutions. ASSET PERFORMANCE MANAGEMENT for Electrical Substations

Grid Solutions. ASSET PERFORMANCE MANAGEMENT for Electrical Substations Grid Solutions ASSET PERFORMANCE MANAGEMENT for Electrical Substations Electrical equipment is a critical component of an asset portfolio. Beyond its financial value, it plays an even greater role in overall

More information

ASSOCIATED NERC STANDARD(S): TPL (referred to as TPL-001 in this document) IMPLEMENTATION: In effect when approved.

ASSOCIATED NERC STANDARD(S): TPL (referred to as TPL-001 in this document) IMPLEMENTATION: In effect when approved. ASSOCIATED NERC STANDARD(S): TPL-001-4 (referred to as TPL-001 in this document) IMPLEMENTATION: In effect when approved. Phase in of individual TPL-001 requirements will be based on the effective dates

More information

SECTION SECONDARY UNIT SUBSTATIONS

SECTION SECONDARY UNIT SUBSTATIONS SECTION 26 12 16 SECONDARY UNIT SUBSTATIONS PART 1 GENERAL 1.1 SUMMARY This section describes metal-clad, indoor or outdoor, secondary unit substations with integral primary fused disconnect switches,

More information

Technical Requirements for Distributed Generation Connection

Technical Requirements for Distributed Generation Connection Technical Requirements for Distributed Generation Connection Distributed Generation Connection Requirements SECTION 1: INTRODUCTION 1.1 General Purpose This document defines the requirements for connecting

More information

Distribution Automation. What? D A. How? Why?

Distribution Automation. What? D A. How? Why? Distribution Automation What? How? D A Why? Typical Power System Generating Plant Step-up transformers Generation System Circuit breakers Transmission System Transmission System Distribution System substations

More information

POWER SYSTEM DYNAMICS AND CONTROL

POWER SYSTEM DYNAMICS AND CONTROL POWER SYSTEM DYNAMICS AND CONTROL 1 POWER SYSTEM DYNAMICS AND CONTROL INTRODUCTION Electric power system comprises components and systems like Generators, transformers, transmission lines and distribution

More information

DISTRIBUTION OPERATIONS AND MAINTENANCE

DISTRIBUTION OPERATIONS AND MAINTENANCE EB-00-00 Exhibit F Tab Schedule Filed: 00 Aug Page of DISTRIBUTION OPERATIONS AND MAINTENANCE 0 PREDICTIVE MAINTENANCE Predictive maintenance expenditures fund work that is required to test and audit distribution

More information

ELECTRICITY SUPPLY - POWER SYSTEM MAINTENANCE Carry out routine inspection and service on oil filled distribution power transformers 11kV to 400V

ELECTRICITY SUPPLY - POWER SYSTEM MAINTENANCE Carry out routine inspection and service on oil filled distribution power transformers 11kV to 400V 1 of 8 level: 4 credit: 8 planned review date: December 2006 sub-field: purpose: entry information: Electricity Supply People credited with this unit standard are able to: prepare for routine service transformers

More information

Improvement in Reliability Analysis using Distributed Generators

Improvement in Reliability Analysis using Distributed Generators International Journal of Scientific & Engineering Research Volume 3, Issue 5, May-2012 1 Improvement in Reliability Analysis using Distributed Generators Japinder Pal Singh Virk, Dr. Smarajit Ghosh Abstract

More information

SUMMARY SUPERINTENDENT OF PLANNING, HIGH VOLTAGE PROJECTS, ENGINEERING AND AUTOMATION DISTRIBUTION DISTRIBUTION ASSETS ENGINEERING MANAGEMENT

SUMMARY SUPERINTENDENT OF PLANNING, HIGH VOLTAGE PROJECTS, ENGINEERING AND AUTOMATION DISTRIBUTION DISTRIBUTION ASSETS ENGINEERING MANAGEMENT SUMMARY Pág. DISTRIBUCTION REF. CONEM 1. OBJECTIVE OF THE DOCUMENT... 2 2. GENERAL CONDITIONS... 2 3. MATERIAL INFORMATIONS... 3 4. DEFINITIONS... 3 4.1 Supplier with homologated Material... 3 4.2 Supplier

More information

Executive summary. by Vanya Ignatova and Chuck Hoeppner

Executive summary. by Vanya Ignatova and Chuck Hoeppner 998-2095-05-01-15-AR0 by Vanya Ignatova and Chuck Hoeppner Executive summary Power quality problems are one of the major causes of unscheduled downtime and equipment malfunction and damage. This paper

More information

Transmission System Security and Planning Standards

Transmission System Security and Planning Standards ver. 1.4 page 1 from 13 Transmission System Security and Planning Standards April 2014 ver. 1.4 page 2 from 13 TABLE OF CONTENTS 1 Introduction... 4 2 Definitions... 4 2.1 Transmission System... 4 2.2

More information

BluePlant SCADA/HMI Software

BluePlant SCADA/HMI Software BluePlant SCADA/HMI Software www.altus.com.br evolution in automation A new vision of your reality Impressive: high-quality graphics and intuitive configuration Superior: security, redundancy and high

More information

edart Tickets PJM State & Member Training Dept. PJM /27/2016

edart Tickets PJM State & Member Training Dept. PJM /27/2016 edart Tickets PJM State & Member Training Dept. PJM 2016 1 edart edart stands for electric Dispatcher Applications and Reporting Tool edart is an internet tool for submitting Generation and Transmission

More information

Slide 1. ABB August 23, 2016

Slide 1. ABB August 23, 2016 Claudio Facchin, President Power Grids division, ABB Cigré Keynote Address, Paris, August 21, 2016 Big shift in power Shaping power systems of the future Slide 1 Big shift in power Global challenges Population

More information

Integrated Volt/VAR Control

Integrated Volt/VAR Control Yukon energy automation software platform Integrated Volt/VAR Control For more efficient, higher quality, and less costly power. Integrated Volt/VAR Control enables Smart Grid power quality strategies

More information

POTOMAC ELECTRIC POWER COMPANY

POTOMAC ELECTRIC POWER COMPANY POTOMAC ELECTRIC POWER COMPANY FERC Form 715 (Part 4) - Transmission Planning Study Guidelines Transmission Reliability Guidelines 1. General Overview The reliability guidelines used to plan the transmission

More information

Transmission Owner Asset Management

Transmission Owner Asset Management Transmission Owner Asset Management Pieces of Asset Management New customers, load growth, repairs, maintenance, operational issues, etc. All the pieces make up the asset management plan for repair or

More information

Distribution Information Exchange Code

Distribution Information Exchange Code Distribution Information Exchange Code Version 5.1 Approved September 2007 Comments to this document can be forwarded to: The RSA Grid Code Secretariat Attention: Mr. Bernard Magoro Eskom, Transmission

More information

Integrated Volt/VAR Control

Integrated Volt/VAR Control Yukon energy automation software platform Integrated Volt/VAR Control For more efficient, higher quality and less costly power Integrated Volt/VAR Control enables smart grid power quality strategies 2

More information

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY DISTRIBUTION ENGINEERING NETWORK SYSTEMS SECTION

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY DISTRIBUTION ENGINEERING NETWORK SYSTEMS SECTION CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING NETWORK SYSTEMS SECTION SPECIFICATION EO- 4035 REVISION 12 OCTOBER, 2006 OPERATION AND MAINTENANCE

More information

SUMMARY OF PRICES FOR 30MVA 161/24/36 kv MOBILE SUBSTATION ACCORDING to SR-152

SUMMARY OF PRICES FOR 30MVA 161/24/36 kv MOBILE SUBSTATION ACCORDING to SR-152 Israel Electric Corporation Ltd. Tender no. Name of Contractor: SUMMARY OF PRICES FOR 30MVA 161/24/36 kv MOBILE SUBSTATION ACCORDING to SR-152 1. GENERAL INSTRUCTIONS 2.1. Prices for the above captioned

More information

TRANSMISSION PLANNING ASSESSMENT METHODOLOGY AND CRITERIA

TRANSMISSION PLANNING ASSESSMENT METHODOLOGY AND CRITERIA TRANSMISSION PLANNING ASSESSMENT METHODOLOGY AND CRITERIA For Compliance with NERC Reliability Standard: TPL-001-4 1/10/2017 Version: 4.2 Table of Contents 1 Revision and Approval History... 2 1.1 Revision

More information

Facility Interconnection Requirements

Facility Interconnection Requirements Facility Interconnection Effective 1/1/2016 1. Purpose Facility Interconnection Facility Interconnection (FAC-001-2) To avoid adverse impacts on the reliability of the Bulk Electric System (BES), RPU documents

More information

AN EXPERIENCE IN DETERMINING A COST VERSUS QUALITY OF SERVICE CHARACTERISTIC IN ORDER TO DEFINE OPTIMAL INVESTMENT LEVEL

AN EXPERIENCE IN DETERMINING A COST VERSUS QUALITY OF SERVICE CHARACTERISTIC IN ORDER TO DEFINE OPTIMAL INVESTMENT LEVEL AN EXPERIENCE IN DETERMINING A COST VERSUS QUALITY OF SERVICE CHARACTERISTIC IN ORDER TO DEFINE OPTIMAL INVESTMENT LEVEL Ivo Ordonha Cyrillo Marcelo Aparecido Pelegrini Gabriel Quiroga Sinapsis Inovação

More information

Exhibit to Agenda Item #1

Exhibit to Agenda Item #1 Exhibit to Agenda Item #1 Board Directors Meeting Wednesday,, scheduled to begin at 5:30 p.m. Customer Service Center, Rubicon Room Powering forward. Together. Agenda 2016 SD-4 annual monitoring report

More information

End-to-end electrical solutions for the biggest challenges involved with connecting wind energy to the grid. Solutions for Wind Energy Integration

End-to-end electrical solutions for the biggest challenges involved with connecting wind energy to the grid. Solutions for Wind Energy Integration End-to-end electrical solutions for the biggest challenges involved with connecting wind energy to the grid Solutions for Wind Energy Integration There are lots of challenges involved in harnessing the

More information

Session 2002 CIGRÉ. A Proposal for using Value Engineering Technique in a Power Plant to Minimize Maintenance cost

Session 2002 CIGRÉ. A Proposal for using Value Engineering Technique in a Power Plant to Minimize Maintenance cost 21, rue d'artois, F-75008 Paris http://www.cigre.org 39-301 Session 2002 CIGRÉ A Proposal for using Value Engineering Technique in a Power Plant to Minimize Maintenance cost A.Moazedi* Moshanir Power Engineering

More information

DECISION SUPPORT FOR LIFE TIME MANAGEMENT OF HV INFRASTRUCTURES

DECISION SUPPORT FOR LIFE TIME MANAGEMENT OF HV INFRASTRUCTURES DECISION SUPPORT FOR LIFE TIME MANAGEMENT OF HV INFRASTRUCTURES E.Gulski (1), J.J.Smit (1), B. Quak (1), E.R.S.Groot (2) (1) Delft University of Technology, (2) KSANDR The Netherlands e.gulski@ewi.tudelft.nl

More information

FACILITY CONNECTION REQUIREMENTS NERC TO-FAC 001-0

FACILITY CONNECTION REQUIREMENTS NERC TO-FAC 001-0 FACILITY CONNECTION REQUIREMENTS NERC TO-FAC 001-0 TABLE OF CONTENTS (NERC TO-FAC-001-0) Facility Connection Requirements Introduction Procedures for Coordinated Joint Studies...1 Procedures for Notification...1

More information

ANALYSIS OF AUTOMATED DISTRIBUTION SYSTEMS SCHEMES

ANALYSIS OF AUTOMATED DISTRIBUTION SYSTEMS SCHEMES ANALYSIS OF AUTOMATED DISTRIBUTION SYSTEMS SCHEMES Mauricio Sperandio 1 Edison A.C. Aranha Neto 1 Jorge Coelho 1 Rodrigo Ramos 2 1 LabPlan \ UFSC, Brazil 2 CELESC ABSTRACT The objective of this paper is

More information

MANAGING SITUATION AWARENESS IN POWER DISTRIBUTION GRID DISTURBANCES

MANAGING SITUATION AWARENESS IN POWER DISTRIBUTION GRID DISTURBANCES MANAGING SITUATION AWARENESS IN POWER DISTRIBUTION GRID DISTURBANCES Kaisa PYLKKÄNEN Finland kaisa.pylkkanen@student.tut.fi Turo IHONEN Elenia Oy Finland turo.ihonen@elenia.fi ABSTRACT Power grid is one

More information

Company Introduction and Information EPTCON LTD. 560 SHELDON DRIVE, CAMBRIDGE ONTARIO. PHONE:

Company Introduction and Information EPTCON LTD. 560 SHELDON DRIVE, CAMBRIDGE ONTARIO. PHONE: Company Introduction and Information EPTCON LTD. 560 SHELDON DRIVE, CAMBRIDGE ONTARIO. PHONE: 519 620 4414 WWW.EPTCON.COM Company Background ABOUT US EPTCON Ltd. (Electrical Power & Transmission Construction),

More information

Relevant aspects of Maintenance Management strategies of Itaipu GIS on monitoring and control gas emissions of greenhouse effects

Relevant aspects of Maintenance Management strategies of Itaipu GIS on monitoring and control gas emissions of greenhouse effects Relevant aspects of Maintenance Management strategies of Itaipu GIS on monitoring and control gas emissions of greenhouse effects ADRIÁN ¹, DOUGLAS ¹, GREGORIO ², DIEGO ² ¹ Itaipu Binacional, ² Fundación

More information

Circuit Breaker Asset Management Using Intelligent Electronic Device (IED)- Based Health Monitoring

Circuit Breaker Asset Management Using Intelligent Electronic Device (IED)- Based Health Monitoring 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2014 Grid of the Future Symposium Circuit Breaker Asset Management Using Intelligent Electronic Device (IED)- Based Health

More information

Information and Risk-based Strategies for Lifetime Asset Management

Information and Risk-based Strategies for Lifetime Asset Management 21, rue d Artois, F-75008 PARIS PS1: Life cycle asset management http : //www.cigre.org NAGOYA 2015 Information and Risk-based Strategies for Lifetime Asset Management Ravish P.Y. MEHAIRJAN 1, 2, Nicolaie

More information

HyCon MD Monitoring, Analysis and Diagnosis

HyCon MD Monitoring, Analysis and Diagnosis HyCon MD Monitoring, Analysis and Diagnosis The Voith HyCon MD Monitoring, Analysis and Diagnosis system combines our engineering and manufacturing expertise with your operational experience and knowledge

More information

Fundamentals of Transmission Operations

Fundamentals of Transmission Operations Fundamentals of Transmission Operations Equipment Outages PJM State & Member Training Dept. Objectives At the end of this presentation the Learner will be able to: Identify how weather may influence outage

More information

C2-304 INTEGRATED INFORMATION SYSTEM FOR THE SIEPAC REGIONAL ELECTRICITY MARKET

C2-304 INTEGRATED INFORMATION SYSTEM FOR THE SIEPAC REGIONAL ELECTRICITY MARKET 21, rue d'artois, F-75008 Paris http://www.cigre.org C2-304 Session 2004 CIGRÉ INTEGRATED INFORMATION SYSTEM FOR THE SIEPAC REGIONAL ELECTRICITY MARKET RENATO CÉSPEDES *, KEMA (Colombia) LEON MADRID, KEMA

More information

DA concept for higherquality. supplies. 24 ABB Review 4/1996

DA concept for higherquality. supplies. 24 ABB Review 4/1996 DA concept for higherquality power supplies Low power network losses and an uninterrupted supply of electricity are no longer enough to satisfy today s consumers, who take a highquality power supply for

More information

Carry out routine inspection and service on high voltage indoor metal clad circuit breakers and bus

Carry out routine inspection and service on high voltage indoor metal clad circuit breakers and bus Page 1 of 7 Carry out routine inspection and service on high voltage indoor metal clad circuit breakers and bus Level 4 Credits 4 Purpose People credited with this unit standard are able to: prepare for

More information

Connection Study Requirements

Connection Study Requirements Document Release Released: September 20, 2010 The Customer shall comply with all the applicable requirements in this document when performing connection studies to produce the engineering study report.

More information

CIM Commissioning Inspection and Maintenance

CIM Commissioning Inspection and Maintenance The solution for Services > Service industries > Industry > Telecommunications > Medical > Etc. APPLI 143 A For the availability of your energy needs Given the impact a continuous supply has on the availability

More information

SECTION AUTOMATIC TRANSFER SWITCH

SECTION AUTOMATIC TRANSFER SWITCH SECTION 26 36 23 AUTOMATIC TRANSFER SWITCH PART 1: GENERAL 1.01 SCOPE A. Furnish all labor, materials, equipment and appurtenances, install and test electrically operated, automatic transfer switch (ATS)

More information

How Do We Build the Efficient, Secure, Cost Effective Power Grid of Tomorrow? The Answer: Smart Grid. Bernard Norton Manager Energy Automation

How Do We Build the Efficient, Secure, Cost Effective Power Grid of Tomorrow? The Answer: Smart Grid. Bernard Norton Manager Energy Automation How Do We Build the Efficient, Secure, Cost Effective Power Grid of Tomorrow? The Answer: Smart Grid Bernard Norton Manager Energy Automation Transpower 2040 Conference Christchurch, 18 th June 2009 Ideas

More information

Training. Commercial Engineering Services. High Voltage Engineering Specialists A unique combination of experience and expertise

Training. Commercial Engineering Services. High Voltage Engineering Specialists A unique combination of experience and expertise What will you learn today? Training Commercial Engineering Services High Voltage Engineering Specialists A unique combination of experience and expertise Training Contents 02 01 Our Academy 03 02 Why Choose

More information

Standard Development Roadmap

Standard Development Roadmap Standard Development Roadmap This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed:

More information

Seminar on African Electrical Interconnection. Module 8 - Interconnected Systems Operating Conditions

Seminar on African Electrical Interconnection. Module 8 - Interconnected Systems Operating Conditions Seminar on African Electrical Interconnection Module 8 - Interconnected Systems Operating Conditions Module 8 - Interconnected Systems Operating Conditions Contents 1) Technical Operating Agreements 2)

More information

GSMPM BLOW CHARGE MODEL IMPLEMENTATION AT ARCELORMITTAL TUBARÃO*

GSMPM BLOW CHARGE MODEL IMPLEMENTATION AT ARCELORMITTAL TUBARÃO* GSMPM BLOW CHARGE MODEL IMPLEMENTATION AT ARCELORMITTAL TUBARÃO* Henrique Silva Furtado 1 Lourival Silva Machado 2 Roberto Dalmaso 3 Abstract This paper presents the results obtained on the exchange of

More information

FAC Version 1.1. Report Date: March 21, Authored by. Terry Harbour, MidAmerican Energy

FAC Version 1.1. Report Date: March 21, Authored by. Terry Harbour, MidAmerican Energy STANDARD APPLICATION GUIDE FAC-008-3 Version 1.1 Report Date: March 21, 2017 Authored by Andy Dolan, American Transmission Company Kerry Livingston, Great River Energy Terry Harbour, MidAmerican Energy

More information

Asset Management of Power Transformers

Asset Management of Power Transformers Asset Management of Power Transformers Prof. Dr.-Ing. C. Neumann TRANSFORM Partner Claus Neumann Study of electrical engineering at Technical University of Aachen, Germany Dr.-thesis at Technical University

More information

REVENUE METERING REQUIREMENTS MANUAL (REDLINE VERSION)

REVENUE METERING REQUIREMENTS MANUAL (REDLINE VERSION) REVENUE METERING REQUIREMENTS MANUAL (REDLINE VERSION) 9-10-2004 Revenue Meter Requirements Manual Revision: 1.0 Revision Date:9-10-2004 Disclaimer The information contained within this manual, along with

More information

Reliability Centered Asset Management (RCAM)

Reliability Centered Asset Management (RCAM) Reliability Centered Asset Management () Aiming at Energy Efficient Transmission & Distribution System IRFAN AHMAD (FIEEEP). Energy Management & Energy Audit Electrical Utilities Energy Management: Optimization

More information

Design & Implementation of an Industrial Facility Islanding and Load Shed System

Design & Implementation of an Industrial Facility Islanding and Load Shed System Design & Implementation of an Industrial Facility Islanding and Load Shed System Mark Adamiak GE Digital Energy Bernard Cable GE Energy 1. Abstract The availability of electricity supply in all areas of

More information

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY DISTRIBUTION ENGINEERING NETWORK SYSTEMS SECTION

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY DISTRIBUTION ENGINEERING NETWORK SYSTEMS SECTION CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT NETWORK SYSTEMS SECTION SPECIFICATION EO-4133 REVISION 2 OCTOBER, 2006 GENERAL REQUIREMENTS

More information

ANAFAS is a short-circuit calculation

ANAFAS is a short-circuit calculation ANAFAS Simultaneous Fault Analysis ANAFAS is a short-circuit calculation software that covers a wide range of automated fault simulations. Its output reports are guided by fault points or monitoring points.

More information

ELIPSE SOFTWARE S PLATFORMS COMMUNICATING WITH DIFFERENT SUPERVISORY AND CONTROL SYSTEMS GENERATE SAVINGS FOR ECHOENERGIA

ELIPSE SOFTWARE S PLATFORMS COMMUNICATING WITH DIFFERENT SUPERVISORY AND CONTROL SYSTEMS GENERATE SAVINGS FOR ECHOENERGIA ELIPSE SOFTWARE S PLATFORMS COMMUNICATING WITH DIFFERENT SUPERVISORY AND CONTROL SYSTEMS GENERATE SAVINGS FOR ECHOENERGIA Developed by Energia Automação and based on Elipse Power s and Elipse Plant Manager

More information