AR5 & AR5-L series. (CHECK-METER Program)

Size: px
Start display at page:

Download "AR5 & AR5-L series. (CHECK-METER Program)"

Transcription

1 SUPPLY NETWORK ANALYZER AR5 & AR5-L series ( Code M ) (CHECK-METER Program) ( Cod. M ) INSTRUCTION MANUAL ( M B ) (c) CIRCUTOR S.A.

2 SUPPLY NETWORK ANALYZER AR5-L Page nº 2 CONTENTS page 1.- BASIC INSTRUCTIONS Checking the contents of your package Safety conditions Connection instructions ANALYZER STARTUP Loading a new program Choice of the operation mode program Operation instructions CONNECTION MODES DATA VISUALIZATION ON DISPLAY Screen of instantaneous values Screen for energy meter check Warning messages PROGRAMMING THE AR5/AR5-L CHECK-METER Set-up of Instantaneous Values SETUP menu MEASURE WIRING: Circuit type PT/CT : Transformation ratios COMM: Communication parameters CLOCK: Internal clock PASSWORD: Safety setting RECALL: Read configuration DISPLAY menu CONTRAST: Screen contrast POWER FACTOR FILES Menu DIR: Directory DELETE: Deleting a file FORMAT: Formatting the AR5/AR5-L internal memory Menu OFF: Enable / Disable Password Menu LANGUAGE Setup for energy meter check... 20

3 SUPPLY NETWORK ANALYZER AR5-L Page nº Operation mode Checking energy meters Checking mechanic energy meters Checking electronic energy meters Checking electronic energy meters using the optical reader AR5/AR5-L COMMUNICATIONS TECHNICAL SPECIFICATIONS SAFETY WARNINGS MAINTENANCE TECHNICAL SERVICE A. CABLE ARRANGEMENT B. QUICK GUIDE C. QUICK GUIDE FOR AR5 - CHECK-METER D. EXAMPLE OF TRANSFORMATION RELATIONS... 34

4 SUPPLY NETWORK ANALYZER AR5-L Page nº BASIC INSTRUCTIONS This manual is aimed to familiarize the user with the operation of the CHECK- METER program for the portable analyser model AR5/AR5-L. To get all necessary information about operation instructions and safety warnings of the portable analyzer AR5/AR5-L consult it s instruction manual (code M ). The AR5/AR5-L analyzer loaded with the check-meter program permits to check both electronic or mechanic energy meters, either for active and reactive energy totalization. The Check-Meter instrument delivers an appropriate checking mode for each energy meter type. Besides of checking energy meter utility, the analyzer provides the visualization on screen of several electrical parameters to verify the correct connection of the analyzer. Recorded data can be downloaded from the AR5 to a PC and further analyzed by means of the PC software. Recording data process is done by means of an liner memory. That means that once memory is full, no new data is recorded anymore Checking the contents of your package After receiving the analyzer, please check the following points: a) The delivered material corresponds with your order specifications. b) After unpacking, check that the instrument has not been damaged in transit. c) The standard set includes the following items: 1 cartridge for programming the AR5/AR5-L containing the ordered operation mode program. 1 Instruction Manual. CD containing the PC software update Safety conditions The manual you hold in your hands contains information and warnings about the AR5/AR5-L that the user should respect in order to guarantee a proper operation of all the instrument functions and keep its safety conditions Connection instructions Before powering and connecting the analyzer check the following points: a) Supply voltage: Through and external power supplier set. Input mains 80 V a.c. 265 V a.c. / output to AR5/AR5-L 12V d.c. b) Frequency : Hz. c) Maximum voltage at the voltage measuring circuit: 500 V a.c. phase-to-neutral 866 V a.c. phase-to-phase

5 SUPPLY NETWORK ANALYZER AR5-L Page nº ANALYZER STARTUP Loading a new program The AR5/AR5-L has an internal memory to save diverse operation mode programs to be used by the user. Before starting this action, check that AR5/AR5-L is supplied through the power supplier set. To load any program, follow these instructions precisely: Turn the AR5/AR5-L off. It is necessary to load a coprocessor that comes in a cartridge to part, and that must settle only in the position of the coprocessor (the last position of the list) Connect the cartridge to the AUX input of the meter. Turn the meter on. Select with the keys [5] & [6] that you want to perform a program loading action (LOAD PROGRAM). Press [ENTER] or wait for a while to confirm this operation. Select the position to save the program into. The AR5/AR5-L will perform a test to check that the cartridge has been properly connected. If an inserted cartridge is detected, then the program will be loaded. Once the loading is completed, reset the meter. If no cartridge was found or a loading mistake occurred, reset the meter and redo the above steps. A cartridge will be only valid for the analyser, which the program was for the first time loaded into. Note on the cartridge the serial number of its related AR5/AR5-L.

6 SUPPLY NETWORK ANALYZER AR5-L Page nº Choice of the operation mode program The AR5/AR5-L can hold in memory different operation mode programs. The choice of the program to be used is done when starting the AR5/AR5-L up. Turn the AR5/AR5-L on. A list of available programs will be shown on display. Use keys [5] & [6] to choose the desired program. Press [ENTER] or wait for a while to confirm this operation. CHECK THE SETUP UP!!!! All programs have an independent setup; therefore, must be always checked to ensure a proper operation. For instance, whether the setup is modified at the CHECK-METER program, these modification will not be valid for the ANALYSER program, and so for any program Operation instructions The AR5/AR5-L is a programmable instrument so offering diverse operation modes which can be selected from the available programming menus (0 PROGRAMMING THE AR5/AR5-L). Please read carefully the paragraphs involving STARTING UP (2.-) AND PROGRAMMING THE AR5/AR5-L (5) in order to select the most suitable operation mode for your requirements. If the instrument is not used according to manufacturer s specifications, the protection of the instrument can be damaged.

7 SUPPLY NETWORK ANALYZER AR5-L Page nº CONNECTION MODES A.- THREE-PHASE MODE CONNECTION DIAGRAM B.- SINGLE-PHASE MODE CONNECTION DIAGRAM

8 SUPPLY NETWORK ANALYZER AR5-L Page nº 8 C.- ARON MODE CONNECTION DIAGRAM

9 SUPPLY NETWORK ANALYZER AR5-L Page nº DATA VISUALIZATION ON DISPLAY All measured instantaneous values, as well as maximum and minimum, can be read on a 160 x 160 pixel, liquid, crystal display (back-light ability). An indication of the type of data being displayed is shown at the upper right corner Screen of instantaneous values This screen is only for the verification of a correct connection of the analyzer. So, you can verify the correct positioning, the transforming ration setting, concord of voltage and current phases... Energy values are partial values. The value is always reset to zero when accessing this screen. These values are not accumulated. Pressing the key [SET] from this screen m the set-up menu is accessed. When powering the AR5/AR5-L on, the display will show: CHECK-METER INST L1 L2 L3 IIII Vp-n A kw kvarl KvarC P.F. Hz KVA kwh kvarhl kvarhc / 01 / : 31 : 29 Verification screen Voltage: Readout of the instantaneous RMS value measured at each phase (L1, L2 & L3) and the average value of the instantaneous values of the three phases (III). Current: Readout of the instantaneous RMS value measured at each phase (L1, L2 & L3) and the average value of the instantaneous values of the three phases (III). Active power: The active power is calculated from instantaneous voltage and current data. The readout gives the instantaneous values of the active power of each phase and also the three phase total instantaneous active power, which is the addition of each phase value. Inductive reactive power: The inductive reactive power is calculated from instantaneous voltage and current data. The readout gives the instantaneous

10 SUPPLY NETWORK ANALYZER AR5-L Page nº 10 values of the inductive reactive power of each phase and also the three phase total instantaneous inductive reactive power, which is the addition of each phase value. Capacitive reactive power: The capacitive reactive power is calculated from instantaneous voltage and current data. The readout gives the instantaneous values of the capacitive reactive power of each phase and also the three phase total instantaneous capacitive reactive power, which is the addition of each phase value. Power factor: Readout of the power factor of each phase and the three phase average value. Frequency: Readout of the instantaneous value of the frequency (Hz). Apparent power: Readout of the three phase total instantaneous apparent, which is the addition of each phase value. Energies: Readout of the instantaneous value of the active, inductive reactive and capacitive inductive energy accumulated. These are always reset to zero when this screen is exited. Time and Date. (time/date): Readout of present time and date. For any modification, see section Screen for energy meter check. This screen delivers the tools to perform the energy meter check. By means of keys [5] & [6] the position of the screen to be modified is selected. This position can be modified when pressing the key [SET]. CHECK-METER CHECK-METER User Name User s data 1/1 V 5/5 A Voltage ratio setting and Current ratio setting? kwh 3Φ? TURNS/IMP Energy meter type (Active/Reactive) n.circuit s phase kw/turn ratio of the energy meter? nturns/imp? N turns/impulses RECORDED? KWh START? kwh END RECORD Wh METER Wh AR5L % Initial energy of the energy meter Final energy of the energy meter Save check Measurement of the energy meter Measurement of the AR5 Energy meter error

11 SUPPLY NETWORK ANALYZER AR5-L Page nº Warning messages Some warning messages can appear on the visualization screens. These messages inform about the AR5/AR5-L performance: - STOP: The analyser is not recording data. - RECORD: The analyser is recording data. - M. Full: Memory is full. - M.Error: There is an error in the memory. The memory must be formatted. - Analyser battery charge status. When only the symbol 3is shown, it means that the battery is very low and the analyser might turn off at any moment. - The battery is charging. The user can also see the accumulated battery charge level. - Full battery charge. - WARNING MAX 500 V: The maximum allowable phase to neutral voltage of 500 V has been exceeded during the measuring process. When measuring phase to phase voltages the limit is set at 866 V. 5.- PROGRAMMING THE AR5/AR5-L CHECK-METER The CHECK-METER program has 2 different set-up menus: AR5 Set-up. This is accessible from the screen of instantaneous values (Section 5.1.-) Check Set-up. This is accessible from the screen of energy meter check (Section 5.6.-) Set-up of Instantaneous Values To accessing AR5/AR5-L setup options press the key [SET], on the instantaneous values screen The analyzer will then inquiry for a password that consists of a key sequence to be pressed (the user has 15 seconds to press this sequence). If the default password has not been modified, then the following key sequence must be followed: PASSWORD [3] [SET] [5] [SET] Standard Password Once this password is entered, the analyzer will permit the user to modify any Setup parameters. All programs have an independent setup, therefore, the setup must be always check to ensure a proper operation, since any modification will only affect the active operation program.

12 SUPPLY NETWORK ANALYZER AR5-L Page nº 12 Diverse setting MENUS are available: SETUP DISPLAY FILES CLEAR OFF LANGUAGE INITIAL MENU Select one option with keys [6] & [5]. To access any menu option use [8] or [ENTER]. To close the menu press [3] or [ESC]. If this key is used when only the main menu is open, this is closed. If any modification over any setup parameter was done, before closing a confirmation of setup change is requested on display.

13 SUPPLY NETWORK ANALYZER AR5-L Page nº SETUP menu The AR5/AR5-L meter can be user-configured to different performances involving its data analysis and recording modes, as it is followed shown: SETUP MEASURE COMM CLOCK PASSWORD RECALL SETUP menu. MEASURE WIRING PT/CT 4 wires / 3 wires / Aron / Single-phase. V and A transformation ratios. COMM Baud / Parity / Bits / Stop bits. CLOCK DD/MM/YY hh:mm:ss. PASSWORD Setting the analyzer password RECALL Standard. Recall Setup sure <yes > <no> MEASURE Use this option to set measuring conditions: CONNECTION MODE SETTING ( 3 or 4 wires or single-phase) and VOLTAGE and CURRENT TRANSFORMATION RATIOS SETTING. MEASURE : WIRING PT / CT 3Φ 3 Wires, 3Φ 4 Wires, Aron and1φ Prim. V, Secon. V, Prim. I

14 SUPPLY NETWORK ANALYZER AR5-L Page nº WIRING: Circuit type Choose the circuit type to be analysed (rotary input). 3Φ 4 Wires: To measure Three-phase systems with Neutral wire. 3Φ 3 Wires: To measure Three-phase systems with Neutral wire. For this arrangement 3 current clamps must be used. 1Φ: To measure Single-phase systems PT/CT : Transformation ratios Voltage and current transformation ratios setting. The program will sequentially inquire for following data: PRIM. V: Voltage transformer primary value. SEC. V: Voltage transformer secondary value. PRIM. I: Current transformer primary / Current clamp primary, used for measuring the line currents. NOTE 1 : If voltage is directly measured (no voltage transformer is used), you must set PRIM.V = 1/SECV.V = 1. NOTE 2 : PRIM. I --> This option permits to program: a) The ratio of the Current clamp to be used. b) In case of a high voltage system, the measurement will be carried out through the secondary of current transformers. A shunt ATS-III 5 A a.c./ 2 V a.c. or CP5 clamp will be then required to enter the measurement signal into the AR5/AR5-L analyzer (Never directly connect the 5 A signal to the AR5/AR5-L.). For this case, the C.T. primary must be set at the primary value of the C.T. used for measuring purposes. Ratio set must be modified for each Current or transformer type change to avoid measurement mistakes. Standard clamps give a voltage output (generally 2 a.c. at full-scale). NOTE : Secondary is always set at 2 V a.c. (it is not user-programmable) COMM: Communication parameters Program here the parameters of the built-in RS-232 serial output. When selecting this option the present parameters are shown on display: COM 9600 NO 8 1 Baud Parity Bits Stop bits - Pressing [ENTER]: values on display are directly validated. - To modify: (rotary input). - Select with keys [4] or [3] the position to modify.

15 SUPPLY NETWORK ANALYZER AR5-L Page nº 15 - Though keys [6], [5] the value of the selected position is increased or decreased. - [ENTER] to validate the total value or [ESC] to exit with no modification CLOCK: Internal clock Use this section to set the analyzer internal clock in time: date / time and displaying format. When this option is selected, presently programmed values are shown by display: CLOCK TYPE DD /MM/YY HH :MM:SS CLOCK TYPE MM/DD/YY HH :MM:SS After validating the date format, the present date and time will be displayed according to the selected arrangement: CLOCK 00 /00 /00 00 :00 : 00 Proceed similarly than for the former section PASSWORD: Safety setting. Set here the analyser password configuration. This password will be required to access the SETUP menu. Thus, the manipulation of the analyser by notauthorized people can be avoided. The password can be also required for turning the analyser off. The default password is: Change of SETUP access password: Firstly enter the old password: Then enter the new password: Finally, confirm the new password: PASSWORD [3] [SET] [5] [SET] OLD PASSWORD * * * * NEW PASSWORD * * * * CHECK PASSWORD * * * *

16 SUPPLY NETWORK ANALYZER AR5-L Page nº 16 During this password modification process, the following error messages can be shown in screen during 5 s: Incorrect Old password Incorrect Check password Wrong password The confirmation of the new password has failed RECALL: Read configuration You can here recall a standard configuration. Set Standard.. sure? <yes > <no> - A confirmation is requested: Recall Setup sure <yes> or <no>. With keys [4] & [3] select yes or no, and then press [ENTER]. A Standard operation program for the AR5/AR5-L is available to be user-recalled. Its features are: - C.T. Ratio (SET + A) : 5 - V.T. Ratio (SET + V) : 1 / 1 - Circuit type : Three phase (III - Phase) - File name (FILE Name) : CK_METER - FILE type :.ACM - Communication parameters : 9600,No,8,1

17 SUPPLY NETWORK ANALYZER AR5-L Page nº DISPLAY menu DISPLAY CONTRAST ANGLE Contrast Show cosϕ or power factor (PF) You can at this point, define the options about the parameters to be visualized on display, the graphic mode performance, CONTRAST: Screen contrast The user can here vary the contrast of the AR5/AR5-L display: - With the [4] you can intensify the display contrast and with the key [3] this can be lowered: CONTRAST DEC INC % POWER FACTOR The user can chose cosϕ or power factor (PF) to be shown, φ Angle PF - With the [3] and [4] keys, it s possible change the value.

18 SUPPLY NETWORK ANALYZER AR5-L Page nº FILES Menu Non-volatile AR5/AR5-L internal memory is storing data up to its maximum capacity. Once full, no new data will not be saved in, nor stored data will be lost (provided no incorrect operation is done). When memory is full, the display will show: "MEMORY FULL". FILES DIR DELETE FORMAT FILES MENU DIR: Directory This option shows on display a directory of all files saved in memory. AR5-L - DIR STD-PROG. STD xxxxx bytes File name / File size dd / mm / yy hh : mm : ss Day / Time TEST1. STD xxxxx bytes dd / mm / yy hh : mm : ss STD-PROG. STD xxxxx bytes dd / mm / yy hh : mm : ss... /... Free bytes: xxxxxxxxxx Number of free bytes in memory - Keys [6] or [5] allows reading more files in case that all files stored by the AR5/AR5-L cannot be shown in only one screen. - Keys [ENTER] or [ESC] to exit DELETE: Deleting a file You can here delete any file from the internal memory. STD-PROG. STD TEST1. STD STD-PROG. STD DELETE xxxxx bytes File name / File size xxxxx bytes xxxxx bytes - With keys [6] & [5] select the file to be deleted. - [ENTER] to confirm selected file erasing. Once press, a confirmation is required.

19 SUPPLY NETWORK ANALYZER AR5-L Page nº FORMAT: Formatting the AR5/AR5-L internal memory This option lets the user to format the internal memory. FORMAT Once the format action over the internal memory is confirmed, a confirmation is required. Take into account that this action will mean all stored data to be deleted. Note: Do not turn the AR5/AR5-L off during the memory format process, otherwise the display will show an error message and the process should be redone Menu OFF: Enable / Disable Password. In order to avoid an accidental manipulation of the analyser, the AR5/AR5-L can be set to request for a password when the user wants to turn it off. Password? <Yes> <No> - With the key [4],[3] you can select: - YES: A password is requested to turn the AR5/AR5-L off. - NO: No password is required to turn the AR5/AR5-L off. - [ENTER] to validate the choice or [ESC] to exit with no modification. The procedure to follow when this password is enabled is: 1) Press the key [OFF] during 5 seconds. 2) You will see in display: PASSWORD 3) Enter the correct Password. 4) Press [OFF] again The analyser will turn off if the entered password is the correct one Menu LANGUAGE It allows selecting the language in which the menus will be presented. Language English - With keys [6] & [5] select the language. - [ENTER] to confirm selected language Press key [ESC] to exit with no modification. NOTE: This configuration is commune for all the programs.

20 SUPPLY NETWORK ANALYZER AR5-L Page nº Setup for energy meter check AR5 CHECK-METER User Name 1/1V 5/5A? kwh 3? TURNS/IMP? nturns?? kwh START? kwh END RECORD? Wh METER? Wh AR5L % (1) User's data (2) P.T. and C.T. ratios (3) Check of energy meters (4) Check of number turns or pulses (5) Check start and end energy test (6) Saving check results (7) Check result (8) % Error Use the keys [6] & [5] to select the option to be modified. Press the key [SET], to modify the selected option. Press the key [ENTER] to start the energy meter checking process. Press the key [ESC] to switch to the screen of instantaneous values. According the position within the verification screen, by pressing [SET] you can define: 1. Type the name of the user, no. of contract and a brief commentary about the performed checking action. 2. Measurement conditions setting: Primary and secondary of the P.T. used. Primary of the C.T or Clamps. 3. Features of the meter to be checked and type of connection: Energy meter type: - kwh -> Checking of active energy meters. - kvarh -> Checking of reactive energy meters. kwh / no. of turns or pulses ratio of the energy meter Circuit type: select the connection type used for the energy meter check:, three-phase (III-Phase) or single-phase (II-Phase). 4. Set the number of turns for the mechanic energy meter checking. When checking an electronic energy meter, will appear the number of impulses well-read by the optical reader. 5. Electronic energy meter check: set the value of the energy meter when starting the check and also when this is finished. 6. RECORD: To save in memory the record of the performed check. 7. This section will show the real value measured by the AR5/AR5-L and also the value that the CHECK-METER should have measured according to the user-programmed values (points: 3, 4 & 5). 8. Error: You can here read the % of error for the energy meter check in relation with the measurement performed by the AR5/AR5-L. 9. To save the check results (6) by pressing [SET].

21 SUPPLY NETWORK ANALYZER AR5-L Page nº Operation mode When checking energy meters it is advisable to: For any type of energy meter: To perform the energy meter check when the installation is at full operation conditions. The higher the consumption is, the higher the check reliability will be. For active energy meters: Whether power factor correction units are installed in the power system, check that those are in operation. The higher the power factor is, the higher the check reliability will be.. It is advisable to perform the checking process with a power factor >0,71. For reactive energy meters: Whether power factor correction units are installed in the power system, check that those are disconnected. in operation. The lower the power factor is, the lower the check reliability will be.. It is advisable to perform the checking process with a power factor <0,71. When the check process is finished, following messages could be shown on screen: - Overflow Energy: The checking process has been too long. The AR5 s inner energy counter cannot count up to such a high energy level. The check process duration can last a maximum of 20 hour at full-load conditions %: The error of the checked energy meter in comparison with the value measured by the CHECK-METER is very big. Check of active energy meters: Connect all power factor correction systems Check of reactive energy meters: Disconnect all power factor correction systems The check process is advisable to be performed at full-load conditions

22 SUPPLY NETWORK ANALYZER AR5-L Page nº Checking energy meters Checking mechanic energy meters AR5 CHECK-METER User Name 1/1V 5/5A? kwh 3? TURNS/IMP? nturns? (1) User's data (2) P.T. and C.T. ratios (3) Check of energy meters (4) Check of number turns or pulses? kwh START? kwh END RECORD? Wh METER? Wh AR5L % (6) Saving check results (7) Check result (8) % Error Use the keys [6] & [5] to select the option to be modified. Press the key [SET], to modify the selected option. 1.- Enter user s attribute (Name, no. of contract). (1) 2.- Set transforming ratio of P.T. and C.T. (clamps/shunts) used for the checking action. (2) 3.- Type of energy meter: active or reactive energy meter. (3) (ENERGY: kwh (Active) or kvarh (reactive). 4.- Set the ratio of the mechanic energy meter: Energy x no. of turns. (3) 5.- Type of energy meter to be checked: single-phase/three-phase. (3) 6.- Press [ENTER] to start the energy meter checking process. After a confirmation inquiry, you will see at the bottom of the screen: START When pressing then [ENTER] the energy meter checking process will start.

23 SUPPLY NETWORK ANALYZER AR5-L Page nº During some moments of data recording: 8.- You will see again at the bottom of the screen: STOP 9.- The energy meter checking process will be stopped when pressing again [ENTER] Enter the number of turns occurred during the checking process. (4) 11.- The % of error for the energy meter check in relation with the measurement performed by the AR5 will be shown at the bottom of the screen.(8) 12.- Save check results. (6) by pressing [SET]

24 SUPPLY NETWORK ANALYZER AR5-L Page nº Checking electronic energy meters AR5 CHECK-METER User Name 1/1V 5/5A? kwh 3? TURNS/IMP (1) User's data (2) P.T. and C.T. ratios (3) Check of energy meters? nturns?? kwh START? kwh END RECORD? Wh METER? Wh AR5L % (5) Check start and end energy test (6) Saving check results (7) Check result (8) % Error Use the keys [6] & [5] to select the option to be modified. Press the key [SET], to modify the selected option. 1.- Enter user s attribute (Name, no. of contract). (1) 2.- Set transforming ratio of P.T. and C.T. (clamps/shunts) used for the checking action. (2) 3.- Type of energy meter: active or reactive energy meter. (3) (ENERGY: kwh (Active) or kvarh (reactive). 4.- Press [ESC] and disregard inquiries about the mechanic meter ratio. (3) 5.- Type of energy meter to be checked: single-phase/three-phase. (3) 6.- Press [ENTER] to start the energy meter checking process. After a confirmation inquiry, you will see at the bottom of the screen: When pressing then [ENTER] checking process will start. START the energy meter

25 SUPPLY NETWORK ANALYZER AR5-L Page nº During some moments of data recording 8.- You will see again at the bottom of the screen: STOP 9.- The energy meter checking process will be stopped when pressing again [ENTER] Enter the initial and ending energy readouts of the energy meter to be checked. (5) 11.- The % of error for the energy meter check in relation with the measurement performed by the AR5 will be shown at the bottom of the screen.(8) 12.- Save check results. (6)

26 SUPPLY NETWORK ANALYZER AR5-L Page nº Checking electronic energy meters using the optical reader. It is possible to connect an optical reader (ref XXXXXXX) for those meters that have a LED. Connect the optical reader into AUX plugin The communications must be set to: 9600 / NO / 8 / 1 AR5 CHECK-METER User Name 1/1V 5/5A? kwh 3? TURNS/IMP? nturns? (1) User's data (2) P.T. and C.T. ratios (3) Check of energy meters (4) Check of number turns or pulses? kwh START? kwh END RECORD? Wh METER? Wh AR5L % (6) Saving check results (7) Check result (8) % Error Use the keys [6] & [5] to select the option to be modified. Press the key [SET], to modify the selected option. 1.- Enter user s attribute (Name, no. of contract). (1) 2.- Set transforming ratio of P.T. and C.T. (clamps/shunts) used for the checking action. (2) 3.- Type of energy meter: active or reactive energy meter. (3) (ENERGY: kwh (Active) or kvarh (reactive). 4.- Set the ratio of the electronic energy meter: Energy x no. of pulses. (3) 5.- Type of energy meter to be checked: single-phase/three-phase. (3)

27 SUPPLY NETWORK ANALYZER AR5-L Page nº Connect the optical reader, if it is not connected yet, to the AR5/AR5-L and align optical head with the LED of the meter. AUX 7.- Press [ENTER] to start the energy meter checking process. After requesting a confirmation the relation of transformation of INTENSITY of the TRANSFORMER is due to introduce where it goes connected the meter 100 PRIM. METER ENTER 5 SEC. METER ENTER 8.- When pressing the optical reader button the energy meter checking process will start. When pressing then [ENTER] checking process will start. START the energy meter

28 SUPPLY NETWORK ANALYZER AR5-L Page nº During some moments of data recording 10.- You will see again at the bottom of the screen: STOP 11.- The energy meter checking process will be stopped when pressing again the optical reader button The % of error for the energy meter check in relation with the measurement performed by the AR5/AR5-L will be shown at the bottom of the screen.(8), 13.- The number of impulses that has been read, will shown at no turns/imp (4) 14.- Save check results. (6) If you want check more energy meters with optical reader, keep it connected. If you need to do another check, disconnect the optical reader. 8.- AR5/AR5-L COMMUNICATIONS To connection to PC of the AR5/AR5-L must be done through the power supplier set, which will be necessary connected to the main. Perform the connection using the two wires factory-delivered with the AR5/AR5-L. One cable will link the AR5/AR5-L to the power supplier set, and another cable is a standard RS232 connector. When starting communication tasks take into account: Communication parameters of the AR5/AR5-L and the PC must fully coincide. The power supplier set must be plugged into. The AR5/AR5-L cannot be into the setup menu. CIRCUTOR has a software package that permits the user to retrieve stored data in the AR5/AR5-L to PC for a further complete analysis. The download archive is in text format, that allow to be opened and edited.

29 SUPPLY NETWORK ANALYZER AR5-L Page nº TECHNICAL SPECIFICATIONS Supply voltage: Through an external power supplier set 230 V a.c. (+10% / -15%) Frequency : Hz Burden : 8 VA Operation temperature : 0 / 50 ºC Measuring circuit : SINGLE-PHASE, THREE-PHASE, ARON Voltage measurement: Measuring range : 20 to 866 V a.c. (between phases) 20 to 500 V a.c. (phase-neutral) Automatic scale adjustment Other voltages : through suitable voltage transformers Frequency : 45 to 65 Hz Current measurement: Measuring range: according to current clamps Current transducer ratio : user-programmable Measurement units : automatic scale adjustment Constructive characteristics of the cartridge Case : Anti-chock plastic Dimensions : 64 x 19 x 40 mm Connection terminals : 1 input/output terminal Accuracy class: Current % of readout ± 2 digits Voltage % of readout ± 2 digits Active power % of readout ± 2 digits Reactive power % of readout ± 2 digits Measuring conditions to assure accuracy class: Errors due to external voltage and current transformer not included Temperature range : 5 ºC to 45 ºC Power factor : 0.5 to 1. Measuring range : between 5 % and 100 %. ACCESSORIES AR5/AR5-L Programs - HARMONIC...CODE. M FLICKER...CODE. M DISTORTIONS...CODE. M CHECK-METER...CODE. M FAST CHECK...CODE. M Software CirEnergy...Visit our web site Current measurement: a) Through Current clamps (3 Clamps KIT): CP CODE M CPR CODE M CPR CODE M CP-100 (M1-U)... CODE M CPR-100 (For Neutral current measurement)...code M CP CODE M 81041

30 SUPPLY NETWORK ANALYZER AR5-L Page nº 30 b) Through flexible Current clamps (3 Clamps KIT): C-FLEX 200/2000/ Length 45 cm... CODE M C-FLEX 200/2000/ Length 80 cm... CODE M C-FLEX 200/2000/ Length 120 cm... CODE M c) ATS-5 shunt (5 A / 2 V a.c.) + current transformers (../5 A)...CODE M Carrying case - Carrying case for AR5/AR5-L current clamps... CODE M Carrying case for AR5/AR5-L... CODE M case (with protection rubber CPR-1000)... CODE M case (with protection rubber CPR-2000)... CODE M 89921

31 SUPPLY NETWORK ANALYZER AR5-L Page nº SAFETY WARNINGS The user should take into account all installation instructions referred in sections INSTALLATION AND STARTUP, CONNECTION INSTRUCTIONS and TECHNICAL SPECIFICATIONS of the analyser. Note that with the instrument powered on, the terminals could be dangerous to touching, and cover opening or elements removal actions may allow accessing dangerous parts. The analyser has been designed and tested to meet IEC 348 standard and is factory-shipped in proper conditions MAINTENANCE The AR5/AR5-L does not require any special maintenance. No adjustment, maintenance or repairing actions should be done over the instrument open and, should those are essential, high-qualified operators must perform them. Before any adjustment, replacement, maintenance or repairing operation is carried out, the instrument must be disconnected from any power supply source. When any protection failure is suspected to exist, the instrument must be immediately put out of service. The own instrument design permits a quick replacement in case of damage TECHNICAL SERVICE For any inquiry about the instrument operation mode or in case of malfunction, you can contact CIRCUTOR s technical service. CIRCUTOR S.A. - Aftersales Service Vial Sant Jordi, s/n Viladecavalls (SPAIN) Tel: (+34) Fax: (+34) ar5@circutor.es

32 SUPPLY NETWORK ANALYZER AR5-L Page nº 32 A. CABLE ARRANGEMENT Different cables used with the AR5/AR5-L have following arrangements: Communication cable RS232: PC - Power supplier set PC POWER SUPPLIER SET Power supply/communication: Power supplier set - AR5/AR5-L POWER SUPPLIE R SET AR5/AR 5- L

33 SUPPLY NETWORK ANALYZER AR5-L Page nº 33 B. QUICK GUIDE Menu Description Options Standard Setup Measure Circuit Choice type of measuring circuit. Three-phase Single-phase Three-phase Tr. Rel Rel. V Voltage transformers ratio. Primary=1 Secondary=1 Rel. A Current transformers ratio. Primary=5 Comm Communication parameters setting 9600,n,8,1 Clock Analyzer s date and time setting Password Set here the analyzer password configuration Recall Recalling standard configuration Standard Display Files OFF Contrast. SET de contrast Angle Choose between cosϕ or P.F visualization. Dir Directory of stored files. Delete Deleting a file. Format Clearing all memory content. set to request for a password when the user wants to turn it off. Language Set the user language. English C. QUICK GUIDE FOR AR5 - CHECK-METER. Span ish AR5 CHECK-METER User Name 1/1V 5/5A? kwh 3? TURNS/IMP? nturns? (1) User's data (2) P.T. and C.T. ratios (3) Check of energy meters (4) Check of number turns or pulses? kwh START? kwh END RECORD? Wh METER? Wh AR5L % (6) Saving check results (7) Check result (8) % Error Check of active energy meters: Connect all power factor correction systems Check of reactive energy meters: Disconnect all power factor correction systems The check process is advisable to be performed at full-load conditions

34 SUPPLY NETWORK ANALYZER AR5-L Page nº 34 D. EXAMPLE OF TRANSFORMATION RELATIONS Clamps connected in the secondary one V 500 A L1 L2 L3 5A clamps 110 V 5 A METER L3 L2 L1 CHECK-METER USER 27000/110V 500/5 Clamps connected in the primary one V 500 A L1 L2 L A clamps 110 V 5 A METER L3 L2 L1 CHECK-METER USER 27000/110V 1000/5

FAST POWER FACTOR REGULATOR. Computer-14df - xx - 144a INSTRUCTION MANUAL ( M / 00A ) (c) CIRCUTOR S.A.

FAST POWER FACTOR REGULATOR. Computer-14df - xx - 144a INSTRUCTION MANUAL ( M / 00A ) (c) CIRCUTOR S.A. FAST POWER FACTOR REGULATOR Computer-14df - xx - 144a INSTRUCTION MANUAL ( M 981 611 / 00A ) (c) CIRCUTOR S.A. -------- POWER FACTOR REGULATOR COMPUTER- 14f --------- Page 2 POWER FACTOR REGULATOR COMPUTER-

More information

3 PHASE ENERGY ELECTRONIC METERS MKB-363-M INSTRUCTION MANUAL ( M / 00 B

3 PHASE ENERGY ELECTRONIC METERS MKB-363-M INSTRUCTION MANUAL ( M / 00 B 3 PHASE ENERGY ELECTRONIC METERS MKB-363-M INSTRUCTION MANUAL ( M 981 198 / 00 B ) (c) CIRCUTOR S.A. -- MKB-363-M ELECTRONIC METERS -- M-981198 -- Page Nº 2 THREE-PHASE THREE-WIRE ACTIVE ENERGY ELECTRONIC

More information

EGT-AF08 USER GUIDE WHEEL WEIGHING SYSTEMS WITH VARIOUS PLATFORMS

EGT-AF08 USER GUIDE WHEEL WEIGHING SYSTEMS WITH VARIOUS PLATFORMS EGT-AF08 USER GUIDE WHEEL WEIGHING SYSTEMS WITH VARIOUS PLATFORMS Revision 1.00 Last update 01/02/2013 Page intentionally left blank. EGT-AF01 USER GUIDE Table of contents 1 INTRODUCTION... 5 2 TECHNICAL

More information

Daker DK kva. Parallel installation quick start. Part. LE08927AA-09/15-01 GF

Daker DK kva. Parallel installation quick start. Part. LE08927AA-09/15-01 GF Daker DK 4.5-10 kva Parallel installation quick start Part. LE08927AA-09/15-01 GF Daker DK 4.5-10 kva UK ENGLISH 3 2 Daker DK 4.5-10 kva Index Introduction 2 1 Important Safety Instructions 2 2 Parallel

More information

DeskDECT Feature Phone

DeskDECT Feature Phone DeskDECT Feature Phone Please read this manual carefully before using your DeskDECT. 1. 2. 2.1 2.2 INTRODUCTION -------------------------------------------------- GETTING STARTED ---------------------------------------------

More information

WS 10 Weighing indicator USER MANUAL

WS 10 Weighing indicator USER MANUAL WS 10 Weighing indicator USER MANUAL Edition:10052001A Safety Instruction For safety operation follow the safety instructions. WARNING Setting, Calibration Inspection and Maintain of the indicator is prohibited

More information

Fixed Demand (Block Demand) The utility company sends a signal to synchronize the start of the Maximum Demand period.

Fixed Demand (Block Demand) The utility company sends a signal to synchronize the start of the Maximum Demand period. Maximum demand control systems M 6 M.6.02 GB Maximum Demand Control There are three terms that appear on the majority of electric company bills: Active energy consumption (kw h) Reactive energy consumption

More information

Winzer Corporation 1 Revision: 4.0

Winzer Corporation 1 Revision: 4.0 Table of Content Section 1: Getting Started... 2 1.1 Overview... 2 Section 2: Installation Overview... 3 2.1 Install CD / Start.exe... 3 2.2 Welcome Screen... 4 2.3 Device Selection... 4 2.4 Auto or Industrial...

More information

SIWAREX FTC-B Weighing Module for Belt Scales Set-up of SIWAREX FTC with SIWATOOL FTC_B

SIWAREX FTC-B Weighing Module for Belt Scales Set-up of SIWAREX FTC with SIWATOOL FTC_B SIWAREX FTC-B Weighing Module for Belt Scales Set-up of SIWAREX FTC with SIWATOOL FTC_B Quick Guide For modules with order number 7MH4900-3AA01 1 Hardware Requirements... 3 2 Connections... 5 3 SIWATOOL

More information

Imperial Series. Model IMP-425/525/625/825/1000AP IMD-425/525/625/825/1000AP IMP-1025/1200/1500/2000AP IMD-1025/1200/1500/2000AP

Imperial Series. Model IMP-425/525/625/825/1000AP IMD-425/525/625/825/1000AP IMP-1025/1200/1500/2000AP IMD-1025/1200/1500/2000AP Service Manual Imperial Series Model IMP-425/525/625/825/1000AP IMD-425/525/625/825/1000AP IMP-1025/1200/1500/2000AP IMD-1025/1200/1500/2000AP Contents of Service Manual 1. Safety Precautions ------------------------------------------------------------------

More information

INDEX. 1 Introduction. 2 Software installation. 3 Open the program. 4 General parameters. 5 Tuning

INDEX. 1 Introduction. 2 Software installation. 3 Open the program. 4 General parameters. 5 Tuning SET UP MANUAL INDEX 1 Introduction 2 Software installation 3 Open the program 4 General parameters 5 Tuning 2 1 Introduction Here below the instruction to use the FLYJET software. 1.1 Software features

More information

CONTENTS. 3-1 Unpacking and Checking Installing Components Leveling the Scale... 1

CONTENTS. 3-1 Unpacking and Checking Installing Components Leveling the Scale... 1 CONTENTS 1. Introduction... 1 2. Precautions... 1 3. Before Using the Product 3-1 Unpacking and Checking. 1 3-2 Installing Components.... 1 3-3 Leveling the Scale.... 1 4. Product Introduction 4-1 Specifications

More information

Please read these instructions before use and retain for future reference

Please read these instructions before use and retain for future reference User Manual DPF-830 Please read these instructions before use and retain for future reference 1 CONTENTS 1. Safety Precautions ------------------------------------------------------------------------------3

More information

Operating Instructions

Operating Instructions Operating Instructions Excellence Balances XS Models Part 2 Terminal System settings Firmware Applications Weighing Statistics Formulation Piece Counting Percent Weighing Density Dynamic Weighing LabX

More information

TotalTime Plus+ Startup and User Guide. USB Memory Stick Version

TotalTime Plus+ Startup and User Guide. USB Memory Stick Version TotalTime Plus+ Startup and User Guide USB Memory Stick Version 2 Part one Startup Guide Unpack the TotalTimePlus+ terminal, you should find the following: One TotalTimePlus+ terminal, One wall mounting

More information

Quick Guide. CSN950 MultiHead Dimensioner _v2d_MAN_QG_CSN950MH_EN

Quick Guide. CSN950 MultiHead Dimensioner _v2d_MAN_QG_CSN950MH_EN Quick Guide CSN950 MultiHead Dimensioner File: 20160406_v2d_MAN_QG_CSN950MH_EN CSN950 MultiHead Quick Guide Table of Contents 1. Safety Instructions... 2 Safety and General Precautions... 2 2. Specifications

More information

Remote AMD Operator Manual

Remote AMD Operator Manual Remote AMD Operator Manual SOFTWARE Remote AMD V1.0.3 User manual (English) Project name: Project: Order / Project NO.: 1-2 Index 1. Introduction ---------------------------------------------------- 1-4

More information

DWP-5500FP (4 x4 ) DWP-11KRFP (5 X5 ) Weighing Indicator. User Manual. Content

DWP-5500FP (4 x4 ) DWP-11KRFP (5 X5 ) Weighing Indicator. User Manual. Content DWP-5500FP (4 x4 ) DWP-11KRFP (5 X5 ) Weighing Indicator User Manual Please read the user manual carefully before using Please keep the user manual properly for future reference Content CHAPTER 1 MAIN

More information

Instruction number PTI-16-03/09/06/A

Instruction number PTI-16-03/09/06/A Instruction number PTI-16-03/09/06/A MANUFACTURER OF ELECTRONIC WEIGHING INSTRUMENTS RADWAG 26 600 Radom Bracka 28 Street Phone +48 48 38 48 800, phone/fax. +48 48 385 00 10 Selling department +48 48 366

More information

Technical Manual. Section 521 Built-In ACD Supervisor Guide

Technical Manual. Section 521 Built-In ACD Supervisor Guide Technical Manual Section 521 Built-In ACD Supervisor Guide USA Version 2.5 (ACD Version 3.0) Issued March 1999 FCC Warning Warning: This service information is designed for experienced repair technicians

More information

INSTRUCTION MANUAL FOR USE AND MAINTENANCE

INSTRUCTION MANUAL FOR USE AND MAINTENANCE R.ESPINAR, S.L. INSTRUCTION MANUAL FOR USE AND MAINTENANCE AUTOCLAVES FOR STERILIZATION MICROPROCESSOR CONTROLLED WITH DRY AND PREVACUUM Models: AE-28 DRY AE-75 DRY AE-110 DRY AE-150 DRY 1/22 This manual

More information

USER MANUAL BR LED Headlight Rev /05/2016

USER MANUAL BR LED Headlight Rev /05/2016 www.optomic.com OP-HL15 LED HEAD LAMP 0. Index 0. INDEX... 2 1. WARNINGS... 3 1.1. QUALIFIED TECHNICAL PERSONNEL... 4 2. NOMENCLATURE... 5 3. APPLICATIONS... 6 4. MAIN CHARACTERISTICS... 7 5. OPERATION...

More information

HotSwap MBP Maintenance Bypass

HotSwap MBP Maintenance Bypass ENGLISH HotSwap MBP Maintenance Bypass MBP6K208 MBPK208 Installation and user manual Copyright 202 EATON All rights reserved. Service and suort: Call your local service representative SAFETY INSTRUCTIONS

More information

Year-End Close Checklists

Year-End Close Checklists Sage Master Builder Year-End Close Checklists Calendar-year, Fiscal-year, Combined NOTICE This document and the Sage Master Builder software may be used only in accordance with the accompanying Sage Master

More information

64C Amplification Block. Instruction Manual

64C Amplification Block. Instruction Manual 64C Amplification Block Instruction Manual Caution: All rights reserved. Quidel Corporation reserves the right to modify this manual at any time without notice. Any part of the manual shall not be duplicated,

More information

Technical System Catalogue Modular PDU (PSM)

Technical System Catalogue Modular PDU (PSM) Technical System Catalogue Modular PDU (PSM) Benefits of PSM busbars at a glance Modular configuration, flexibly extendible Redundant designs in busbars are supported Vertical mounting in the rack without

More information

Instruction Manual Dräger MSI EM200-s

Instruction Manual Dräger MSI EM200-s Dräger MSI GmbH Rohrstraße 32 58093 Hagen Tel.: +49-2331 / 9584-0 Fax: +49-2331 / 9584-29 e-mail: info@draeger-msi.de D 950; Edition 2011-01-01 Content 1. Reference notes Page 3 1.1 Approvals 1.2 Information

More information

QUICK Guide. System start-up and shutdown 3. Operating panels. State colors. General process description. Device operating modes

QUICK Guide. System start-up and shutdown 3. Operating panels. State colors. General process description. Device operating modes QUICK Guide System start-up and shutdown 3 Operating panels 4 State colors 5 General process description 6 Device operating modes Recovering from an error situation 15 19 Tips 21 MMS5 rev. 2.0 / FMS Options

More information

WP200e Wallbox to CD Changer Adapter

WP200e Wallbox to CD Changer Adapter WP200e Wallbox to CD Changer Adapter Supported Wallbox Models AMI W-40 & W-80 & W-120, 40/80/120 Select AMI WQ-200, 200 Select Rock-Ola 1558 & 500, 160 Select Rock-ola 1555, 200 Select Rowe WRA, WRB &

More information

Sby SR Instruments, Inc.

Sby SR Instruments, Inc. Part No.: MAN947IFS_170629 Page 1 of 12 Sby SR Instruments, Inc. SRV947IFS REMOTE DISPLAY PLATFORM SCALE Operating and Service Manual Part No.: MAN947IFS_170629 Page 2 of 12 TABLE OF CONTENTS TABLE OF

More information

RESTORE 1030TM Testing Protocol

RESTORE 1030TM Testing Protocol RESTORE 1030TM Testing Protocol Test protocols will vary depending on the type of equipment being evaluated. The length of time required to do the testing, however, remains consistent no matter what the

More information

Content. 5. Appendix Technical Specifications... 13

Content. 5. Appendix Technical Specifications... 13 User Manual v1.0 Content Content... 1 1. Disclaimer and Warning... 2 2. XLink at a glance... 2 System requirements... 2 Parts list... 2 What s included... 3 Terminology... 3 3. 2.4G Bluetooth digital transmitter...

More information

MERIGAUGE MODEL 3900 OPERATING INSTRUCTIONS

MERIGAUGE MODEL 3900 OPERATING INSTRUCTIONS 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com MERIGAUGE MODEL 3900 OPERATING INSTRUCTIONS Meriam Instrument s MERIGAUGE Model

More information

electroplating DC power supply type SIFCO PROCESS POWER PACK 1028

electroplating DC power supply type SIFCO PROCESS POWER PACK 1028 Documentation type: Author: Quick start manual J. Schumann Last modification: Last modification by: D. Mayer-Eckardt Print date: 9/9/2010 10:46 AM Last saving: 9/9/2010 10:46 AM Doc-Nr.: ZK-xxxxxx-01-V01

More information

User s Guide. Localization system StarGazer TM for Intelligent Robots.

User s Guide. Localization system StarGazer TM for Intelligent Robots. User s Guide Localization system StarGazer TM for Intelligent Robots www.hagisonic.com User s Guide Table of Contents 1. Product Overview -------------------------------------------------------------------------------------------------

More information

Best Selection for Your Business. Electronic Pricing Scale. User s Manual. (Model: TP-31)

Best Selection for Your Business. Electronic Pricing Scale. User s Manual. (Model: TP-31) Best Selection for Your Business Electronic Pricing Scale User s Manual (Model: TP-31) CATALOG 1. Foreword... 2 1.1. Introductions... 2 1.2. Main functions and features... 2 1.3. Specification... 2 1.4.

More information

4Ch Real time / Duplex LCD Combo DVR

4Ch Real time / Duplex LCD Combo DVR 4Ch Real time / Duplex LCD Combo DVR The most stable and reliable real stand alone Digital Video Multiplex Recorder Installation & Safeguards INSTALLATION & SAFEGUARDS All the safety and operating instructions

More information

Contents. 1 Welcome. 2 Getting Started. 3 Getting To Know the Cash Register

Contents. 1 Welcome. 2 Getting Started. 3 Getting To Know the Cash Register Contents 1 Welcome Before Starting...1 Using the Programming Menu... 1 Using Buttons... 2 What s in the Box?... 2 Important Phone Numbers... 2 2 Getting Started Getting Started...3 Setting the Language...

More information

Safety Precautions. 3. Cabinet Assembly 4. Operating buttons / functions.5-6. Machine Operation

Safety Precautions. 3. Cabinet Assembly 4. Operating buttons / functions.5-6. Machine Operation USER MANUAL Contents Safety Precautions. 3 Cabinet Assembly 4 Operating buttons / functions.5-6 Machine Operation...7-11 Convert from Inches to Millimeters / Millimeters to Inches.. 7 Programming in Manual

More information

XSTi Standby UPS. 400VA, 600VA, 800VA Models. User & Installation Manual

XSTi Standby UPS. 400VA, 600VA, 800VA Models. User & Installation Manual XSTi Standby UPS 400VA, 600VA, 800VA Models User & Installation Manual www.xpcc.com 2015. All rights reserved. (Rev 12/14/15) Table of Contents Package Contents... 3 Product Introduction... 3 Product Overview...

More information

Stopwatch Display Timer Owner s Manual

Stopwatch Display Timer Owner s Manual The Leader in Event Critical Timing Electronics Stopwatch Display Timer Owner s Manual Rev H RaceAmerica Corporation P.O. Box 3469 Santa Clara, CA 95055-3469 (408) 988-6188 http://www.raceamerica.com info@raceamerica.com

More information

MEDIZINTECHNIK FÜR TIERÄRZTE

MEDIZINTECHNIK FÜR TIERÄRZTE GB Tabel of contents: Operation Instructions Electronic Platfoorm Balances MEDIZINTECHNIK FÜR TIERÄRZTE 1 Technical data 17 2 Fundamental information (general) 18 2.1 Intended use 18 2.2 Inappropriate

More information

Manual Rotary Heat Sealers. Type: F108TX. List of content : Introduction 2. General description 3. Application 4. Safety precautions 5

Manual Rotary Heat Sealers. Type: F108TX. List of content : Introduction 2. General description 3. Application 4. Safety precautions 5 Manual Rotary Heat Sealers Type: F108TX List of content : Page: Introduction 2 General description 3 Application 4 Safety precautions 5 Transport and storage 6 Installation 7 First Set-up 8 Connection

More information

Using the Commonwealth Bank EFTPOS terminal with QuickPOS

Using the Commonwealth Bank EFTPOS terminal with QuickPOS Q U I C K P O S S U P P L E M E N T Using the Commonwealth Bank EFTPOS terminal with QuickPOS This special supplement shows you how to set up and use QuickPOS with the Commonwealth Bank s EFTPOS terminal.

More information

Paper Store. Version

Paper Store. Version Paper Store Version 1.1 2000-06-30 3Tec automation GmbH - Wilhelmstr. 8 - D-32602 Vlotho Tel. +49 5733-960009 - Fax +49 5733 960007 E-Mail info@3tec.de - Sparkasse Bielefeld - BLZ 480 501 61 - Konto-Nr.

More information

OM-90 SERIES Portable Temperature and Humidity Data Loggers. Shop online at omega.com

OM-90 SERIES Portable Temperature and Humidity Data Loggers. Shop online at omega.com TM For complete product manual: www.omega.com/manuals/manualpdf/m5440.pdf Shop online at omega.com e-mail: info@omega.com For latest product manuals: www.omegamanual.info OM-90 SERIES Portable Temperature

More information

star PROGRAMMER INSTRUCTIONS MANUAL

star PROGRAMMER INSTRUCTIONS MANUAL star PROGRAMMER INSTRUCTIONS MANUAL MA-5028-ENG vers. 1.11-240414 star Programmer manual General contents General contents User manual 1. INTRODUCTION --------------------------------------------------------------------------------------------------------------

More information

Belgacom IDS 310. Reception Terminal Manual. Forum IS16/48/80/160

Belgacom IDS 310. Reception Terminal Manual. Forum IS16/48/80/160 Belgacom IDS 310 Reception Terminal Manual Forum IS16/48/80/160 1 2 Symbols used in the documentation Actions, events Keypads Press. Digital pad. Lift receiver. Alphabetical pad. Hang up. Specific digital

More information

NOTES TABLE OF CONTENTS

NOTES TABLE OF CONTENTS NOTES TABLE OF CONTENTS 1.0 Measuring procedure.. 2 2.0 Design of the device 4 3.0 Calibration curves 5 4.0 Activation of the super user function.. 6 5.0 Changing batteries.. 7 6.0 Determination of the

More information

HCP-7000 Opreator s Manual 1. Operator s Manual.

HCP-7000 Opreator s Manual 1. Operator s Manual. -------------------------------------------------------------------- HCP-7000 Opreator s Manual 1 Operator s Manual Chart Projector 2 HCP-7000 Operator s Manual -----------------------------------------------------------------------

More information

PISO-CAN200-D/T PISO-CAN400-D/T DASYLab CAN Driver User s Manual

PISO-CAN200-D/T PISO-CAN400-D/T DASYLab CAN Driver User s Manual PISO-CAN200-D/T PISO-CAN400-D/T DASYLab CAN Driver User s Manual Warranty All products manufactured by ICP DAS are warranted against defective materials for a period of one year from the date of delivery

More information

X30 System Components

X30 System Components X30 System Components X30 Monitor - Monitor is 12.1 inches - LINUX operating system not windows - Can-based communication. No serial ports - New part number 3132-10 LED Light Bar Battery Status LED Light

More information

Precision Automatic Vacuum Control (PAVC+)

Precision Automatic Vacuum Control (PAVC+) USER GUIDE UGE105-1216 www.conairgroup.com Precision Automatic Vacuum Control (PAVC+) Corporate Office: 724.584.5500 l Instant Access 24/7 (Parts and Service): 800.458.1960 l Parts and Service: 814.437.6861

More information

DJ Switch 10F V2 ORDERCODE 50365

DJ Switch 10F V2 ORDERCODE 50365 DJ Switch 10F V2 ORDERCODE 5035 Congratulations! You have bought a great, innovative product from Showtec. The Showtec DJ Switch brings excitement to any venue. Whether you want simple plug-&-play action

More information

ATOMSCOPE HF200A. Operating Instruction Manual. Ver. 3.1

ATOMSCOPE HF200A. Operating Instruction Manual. Ver. 3.1 ATOMSCOPE HF00A Operating Instruction Manual Ver.. This special purpose portable equipment is for diagnostic radiography only. It is not designed, nor does it meet, the standards for any other use. CONTENTS

More information

topshelf2.0 QUICK REFERENCE DEVICE MANUAL

topshelf2.0 QUICK REFERENCE DEVICE MANUAL topshelf2.0 QUICK REFERENCE DEVICE MANUAL Scout topshelf2.0 Quick Reference Device Manual January 2007 2007 Scout Inc. Table of Contents 1) Introduction...6 System Requirements Initial Setup Common to

More information

2% & (+ 2% PSI.

2% & (+ 2% PSI. Warning: If your vehicle has an engine that has spark plugs, be sure they are resistor type spark plugs or you may damage the memory chip of this unit. If the scale unit fails when the engine is running,

More information

Magner /35-3 Series Currency Counter. Operator's Manual

Magner /35-3 Series Currency Counter. Operator's Manual Magner 35-2003/35-3 Series Currency Counter Operator's Manual Magner 35-2003 / 35-3 Series Introduction. The MAGNER 35-2003 / 35-3 is the most advanced Currency Counter available today. MAGNER's Design

More information

imark Mobile Ordering System

imark Mobile Ordering System imark Mobile Ordering System Locate the switch, generally located in the back office Plug the green Ethernet cable into PORT 6, if 6 is in use then use PORT 2 Plug the other end of the cable into the imark

More information

Inscale Measurement Technology Ltd Tel: Fax:

Inscale Measurement Technology Ltd Tel: Fax: TCC SERIES Inscale Measurement Technology Ltd 7 Heron Close, St. Leonards-on-Sea. East Sussex TN38 8DX United Kingdom Tel: +44(0)1424 200722 Fax: +44(0)1424 443976 Email: sales@inscale-scales.co.uk Http:www.inscale-scales.co.uk

More information

ITEM AND VENDOR RANKING REPORTS

ITEM AND VENDOR RANKING REPORTS ITEM AND VENDOR RANKING REPORTS i The documentation in this publication is provided pursuant to a Sales and Licensing Contract for the Prophet 21 System entered into by and between Prophet 21 and the Purchaser

More information

Contents OVERVIEW... 3

Contents OVERVIEW... 3 Contents OVERVIEW... 3 Feature Summary... 3 CONFIGURATION... 4 System Requirements... 4 ConnectWise Manage Configuration... 4 Configuration of a ConnectWise Manage Login... 4 Configuration of GL Accounts...

More information

Foreword. Sales Associates Managers

Foreword. Sales Associates Managers Foreword This book is a pocket guide for using the Register module for the InfoTouch Store Manager. It outlines the basic steps and procedures for processing sales, from the beginning to the end of a day.

More information

Troubleshooting Guide 9702 Series

Troubleshooting Guide 9702 Series Troubleshooting Guide 9702 Series Satellite Solutions for Mobile Markets 11200 Hampshire Avenue South, Bloomington, MN 55438-2453 Phone: (800) 982-9920 Fax: (952) 922-8424 www.kingcontrols.com 1305-AUTO

More information

Operating Instructions METTLER TOLEDO Excellence XS Precision Balances

Operating Instructions METTLER TOLEDO Excellence XS Precision Balances Operating Instructions METTLER TOLEDO Excellence XS Precision Balances www.mt.com/support Overview of your XS precision balance 6 5 7 10 11 8 6 6 4 3 2 1 10 3 3 11 11 6 1 Terminal (for details s. Section

More information

C60 Standby UPS. 800VA Models. User & Installation Manual Xtreme Power Conversion Corporation. All rights reserved.

C60 Standby UPS. 800VA Models. User & Installation Manual Xtreme Power Conversion Corporation. All rights reserved. For more information, visit www.247technology.com/on-line-ups/c60-standby-ups C60 Standby UPS 800VA Models User & Installation Manual 2015. All rights reserved. (Rev 6/23/15) Table of Contents Package

More information

New Zealand Technical Standard Order NZTSO 2001

New Zealand Technical Standard Order NZTSO 2001 New Zealand Technical Standard Order NZTSO 2001 Revision 1 Time in Service Recorders 17/11/15 Published by Civil Aviation Authority PO Box 3555 WELLINGTON 6140 NEW ZEALAND Approved by Manager Aircraft

More information

Wallbox Translator. Connect any vintage wallbox to your jukebox...

Wallbox Translator. Connect any vintage wallbox to your jukebox... Wallbox Translator Connect any vintage wallbox to your jukebox... TRANSLATED WALLBOX MODEL TYPES AMI W-40 AMI W-80 AMI W-120 AMI WQ-200 Rock-Ola 500 Rock-Ola 503 Rock-Ola 1555 Rock-Ola 1558 Rowe WRA Rowe

More information

PeopleSoft Financials epro Process Guide

PeopleSoft Financials epro Process Guide epro Process Guide General Stores Requisitions Information Management Client Support Services DCATS 210 567 7777 / Option 5 epro Process Guide Version 2 May 2011 Introduction to the PeopleSoft Financials

More information

Call-Back Configuration for the CR800/CR1000 MultiLogger Application Note #19

Call-Back Configuration for the CR800/CR1000 MultiLogger Application Note #19 5 Gould Road, PO Box 2155 New London, NH 03257 Voice: (603) 526-9088 info@canarysystems.com www.canarysystems.com Call-Back Configuration for the CR800/CR1000 MultiLogger Application Note #19 Overview

More information

7700 TEST KIT OPERATIONS MANUAL

7700 TEST KIT OPERATIONS MANUAL 7700 TEST KIT OPERATIONS MANUAL 1 The following specifications apply to the CosaTron Model 7700 Digital Test Kit. SPECIFICATIONS: HV DISPLAY ------------------------------------------- 3 Digit (XX.X KV),

More information

GK INDICATOR. (P.N. 9264, Revision K1, July 2011)

GK INDICATOR. (P.N. 9264, Revision K1, July 2011) Adam Equipment GK INDICATOR (P.N. 9264, Revision K1, July 2011) V1.17 GK-H scales for Europe V2.25 EC Approved scale V3.32 GK scale for Europe V4.07 GK-H scale for USA V5.32 GK scales for USA Adam Equipment

More information

NAB EFTPOS User Guide. for Countertop & Mobile Terminals

NAB EFTPOS User Guide. for Countertop & Mobile Terminals NAB EFTPOS User Guide for Countertop & Mobile Terminals YOUR NAB EFTPOS TERMINAL 2 NAB EFTPOS User Guide TABLE OF CONTENTS Getting to know your NAB EFTPOS Ingenico terminal 5 Contactless Tap & Go 8 Sale

More information

Stopwatch Display Timer Owner s Manual

Stopwatch Display Timer Owner s Manual Stopwatch Display Timer Owner s Manual Models 4432SC & 6432SC Rev A RaceAmerica Corp. 280 Martin Ave. Unit#1 Santa Clara, CA 95050 (408) 988-6188 www.raceamerica.com info@raceamerica.com Copyright 2006

More information

IDS 1632 Installer Manual K Issued September 2009

IDS 1632 Installer Manual K Issued September 2009 1 IDS 1632 Installer Manual 700-256-02K Issued September 2009 IDS 1632 Installer Manual 700-256-02K Issued September 2009 2 Contents 1. Introduction to the IDS 1632 ---------------------------------------------------------------------

More information

First Data EFTPOS. User Guide. 8006L2-3CR Integrated PIN Pad

First Data EFTPOS. User Guide. 8006L2-3CR Integrated PIN Pad First Data EFTPOS User Guide 8006L2-3CR Integrated PIN Pad 2 Contents What are you looking for? Get to know your PIN pad Introduction 05 PIN Pad location and PIN privacy 05 PIN Pad ownership 06 Your PIN

More information

Using UPSMON-PRO Monitoring Software. Opening UPSMON-PRO Monitoring Software

Using UPSMON-PRO Monitoring Software. Opening UPSMON-PRO Monitoring Software Using UPSMON-PRO Monitoring Software With this UPS monitoring software, you can : Get UPS connection from serial port, usb port, or snmp agent Monitor UPS status, battery capacity, output voltage, load

More information

FAST SPOTTER WT-FS-5.0

FAST SPOTTER WT-FS-5.0 . FAST SPOTTER WT-FS-5.0 Installation, Operating and Maintenance Manual WELDING TECHNOLOGIES www.weldingnet.com 1365 Horseshoe Dr., Blue Bell, PA 19422 Phone: 610-278-9325 Fax: 610-278-9325 Toll Free Number:

More information

Instruction Manual. for. gskin U-Value Kit

Instruction Manual. for. gskin U-Value Kit Instruction Manual for gskin U-Value Kit Status: July 12, 2016 gskin U-Value KIT: Instruction Manual 1 / 10 Content 1. The gskin U-Value KIT delivery overview... 1 2. General overview of the gskin U-value

More information

LC-1000/ LC Loadout. Manual

LC-1000/ LC Loadout. Manual LC-1000/ LC-2000 Loadout Manual ********************************************************************************************* All equipment is tested for proper operation before shipping from the factory.

More information

Camera Eyepiece. User s Manual. KS035200G4-Ver1.0

Camera Eyepiece. User s Manual. KS035200G4-Ver1.0 Camera Eyepiece User s Manual Content CHAPTER 1 NOTES AND SAFETY REQUIREMENTS ------------------------- - 1-1.1 Cautions and Notes ------------------------------------------------------------------- -

More information

HR3290 CS Marlin. Wireless 2D Barcode Scanner User Guide

HR3290 CS Marlin. Wireless 2D Barcode Scanner User Guide HR3290 CS Marlin Wireless 2D Barcode Scanner User Guide Disclaimer 2016-2017 Fujian Newland Auto-ID Tech. Co., Ltd. All rights reserved. Please read through the manual carefully before using the product

More information

ACTIVANT ACCLAIM LOGISTICS MANAGEMENT. Version 16.0

ACTIVANT ACCLAIM LOGISTICS MANAGEMENT. Version 16.0 ACTIVANT ACCLAIM Version 16.0 This manual contains reference information about software products from Activant Solutions Inc. The software described in this manual and the manual itself are furnished under

More information

AP5K-C Precision AC Double-Pulse Spot Welding Machine User s Manual Shenzhen Will-Best Electronics Co., Ltd

AP5K-C Precision AC Double-Pulse Spot Welding Machine User s Manual Shenzhen Will-Best Electronics Co., Ltd AP5K-C Precision AC Double-Pulse Spot Welding Machine User s Manual Shenzhen Will-Best Electronics Co., Ltd 1 Content 1. Introduction...3 1.1 Functions...3 1.2 Units of AP5K-C...4 2. The Initial Installation

More information

Operating instructions. METTLER TOLEDO MultiRange Application software IND690-Batch.

Operating instructions. METTLER TOLEDO MultiRange Application software IND690-Batch. Operating instructions METTLER TOLEDO MultiRange Application software IND690-Batch www.mt.com/support Congratulations on choosing the quality and precision of METTLER TOLEDO. Proper use according to these

More information

Energia Online. User Guide

Energia Online. User Guide Energia Online User Guide Contents Registration and Login: Page 1 Energia Plus: Page 4 Energia Premium: Page 14 Glossary: Page 31 Contents Registration It is possible to register for access to Energia

More information

User s Manual. Chart Projector GCP-7000

User s Manual. Chart Projector GCP-7000 User s Manual Chart Projector GCP-7000 ------------------------------------------------------------------------ Chart Projector GCP-7000 1 IMPORTANT NOTICE This product may malfunction due to electromagnetic

More information

Thank you for purchasing the SC-CONVERSION System 500/600 Conversion Kit. This Kit is available in two different versions:

Thank you for purchasing the SC-CONVERSION System 500/600 Conversion Kit. This Kit is available in two different versions: Rev. 1 (Jun 30, 2016) Thank you for purchasing the SC-CONVERSION System 500/600 Conversion Kit. This Kit is available in two different versions: Part # 4K01328-FI SC-CONVERSION Conversion Kit with MEI

More information

abc SOFTWARE & OPERATION MANUAL FOR INSPEC SAMPLER VERSION 1.08 (VOLUME 2 OF 2)

abc SOFTWARE & OPERATION MANUAL FOR INSPEC SAMPLER VERSION 1.08 (VOLUME 2 OF 2) abc SOFTWARE & OPERATION MANUAL FOR INSPEC SAMPLER VERSION 1.08 (VOLUME 2 OF 2) This Jiskoot Product is designed to provide outstanding service if correctly installed, used and maintained recognising the

More information

USER MANUAL. ExStik CL200A. Waterproof Total Residual Chlorine Tester. Patent Pending. Additional User Manual Translations available at

USER MANUAL. ExStik CL200A. Waterproof Total Residual Chlorine Tester. Patent Pending. Additional User Manual Translations available at USER MANUAL ExStik CL200A Waterproof Total Residual Chlorine Tester Patent Pending Additional User Manual Translations available at www.extech.com Introduction Congratulations on your purchase of the ExStik

More information

2012 G25; MIL ON WITH DTC P0101 AND/OR P010B

2012 G25; MIL ON WITH DTC P0101 AND/OR P010B Classification: Reference: Date: EC13-019 ITB13-054 December 13, 2013 2012 G25; MIL ON WITH DTC P0101 AND/OR P010B APPLIED VEHICLES: 2012 G25 Sedan (V36) APPLIED ENGINE: VQ25HR IF YOU CONFIRM: MIL ON with

More information

DIGITAL PORTION SCALE PS-5 OWNER S Manual

DIGITAL PORTION SCALE PS-5 OWNER S Manual DIGITAL PORTION SCALE PS-5 OWNER S Manual CARDINAL SCALE MFG. CO. 8528-M013-O1 Rev G PO BOX 151 WEBB CITY, MO 64870 Printed in USA 09/00 PH (417) 673-4631 FAX (417) 673-5001 Web Site - http://www.detectoscale.com

More information

Zebra s Repair Order Portal for Partners COURSE CODE: RPE01

Zebra s Repair Order Portal for Partners COURSE CODE: RPE01 Zebra s Repair Order Portal for Partners COURSE CODE: RPE01 April 2017 Introduction Welcome to the Zebra s Repair Order Portal for Partners course. This course explains how to navigate the Repair Order

More information

Fluke Oscilloscope Calibration Solutions. Helping you measure up to the highest standards

Fluke Oscilloscope Calibration Solutions. Helping you measure up to the highest standards Fluke Oscilloscope Calibration Solutions Helping you measure up to the highest standards Fluke offers more ways to meet your oscilloscope calibration needs If your organization is like most, you are competing

More information

Contents OVERVIEW... 3

Contents OVERVIEW... 3 Contents OVERVIEW... 3 Feature Summary... 3 CONFIGURATION... 4 System Requirements... 4 ConnectWise Manage Configuration... 4 Configuration of Manage Login... 4 Configuration of GL Accounts... 5 Configuration

More information

Amadeus Hotel Store. User guide 16 March Taking hotel consolidator content to a new level with Transhotel

Amadeus Hotel Store. User guide 16 March Taking hotel consolidator content to a new level with Transhotel Amadeus Hotel Store User guide 16 March 2009 Taking hotel consolidator content to a new level with Transhotel Index Amadeus Hotel Store is now open for business!...3 Technical requirements...3 Log-in...4

More information

USER MANUAL. Model TIF 2000 Digital Hybrid Telephone Line Interface

USER MANUAL. Model TIF 2000 Digital Hybrid Telephone Line Interface USER MANUAL Model TIF 2000 Digital Hybrid Telephone Line Interface 9350-7674-000 Rev B, 4/2003 1 PROPRIETARY NOTICE The RTS product information and design disclosed herein were originated by and are the

More information

Year End Close Procedures - 1 -

Year End Close Procedures - 1 - Microsoft Dynamics GP 2011 Year-End Closing Procedures This manual should be used as a guide along with the screen specific help, printed Microsoft manuals and on-line help available through CustomerSource,

More information

Temperature Controllers: JC Series Digital Indicating Controllers. JC Series. High Performance Controllers...at the lowest prices anywhere!

Temperature Controllers: JC Series Digital Indicating Controllers. JC Series. High Performance Controllers...at the lowest prices anywhere! JC Series High Performance Controllers...at the lowest prices anywhere! Structure Units available in standard DIN sizes (1/16, 1/8, and 1/4 DIN) NEMA 4X protective construction Black enclosure Programmable

More information

NorthStar Club Management System. Retail Point of Sale (RPOS) Version General Users Guide RPOS

NorthStar Club Management System. Retail Point of Sale (RPOS) Version General Users Guide RPOS Retail Point of Sale (RPOS) Version 2.3.0 RPOS-12052006 December 05, 2006 Copyright Statement Except as otherwise specifically noted, NorthStar Technologies, Inc. reserves the right to change all or part

More information