Download "Capacity Shortages RE Module. Interconnection Training Program PJM State & Member Training Dept."

Transcription

1 Disclaimer This training presentation is provided as a reference for preparing for the PJM Certification Exam. Note that the following information may not reflect current PJM rules and operating procedures. For current training material, please visit: PJM 2014

2 Capacity Shortages RE Module Interconnection Training Program PJM State & Member Training Dept. 1

3 Agenda Basics Alerts Warnings/Actions Statistics Emergency Procedure Website 2

4 Emergency Procedures An emergency in PJM is defined as: An abnormal system condition requiring manual or automatic action to maintain system frequency, prevent loss of firm load, equipment damage or tripping of system elements that could adversely affect reliability of an electric system or the safety of persons or property Capacity deficiency or capacity excess conditions A fuel shortage requiring departure from normal operating procedures Abnormal natural events or man-made threats to reliability Including events external to PJM that may require PJM action Many emergencies involve a shortage of reserve generation OR inability to deliver generation to load PJM 3

5 Emergency Procedures Manual Reference 4

6 Emergency Procedures Manual Reference 5

7 Emergency Procedures Manual Reference 6

8 Emergency Procedures Manual Reference 7

9 Emergency Procedures PJM Control Area Carried out together across PJM RTO up to Load Dump assuming no transmission or other operating limitations. Will be directed by PJM Procedures may be issued by control zone if transmission limitations exist When procedures get to load dump, the control zone(s) that is capacity deficient will shed load. Determination of who is capacity deficient will be each control zone comparison of their generation with load Adjusted based on zone s net capacity position Adjusted based on any external purchases allocated to a control zone 8

10 Emergency Procedures PJM Manual M-13 - Page 14 The PJM dispatcher has the flexibility of implementing the emergency procedures in whatever order is required to ensure overall system reliability. The PJM OI dispatcher has the flexibility to exit the emergency procedures in a different order than they are implemented when conditions necessitate. Each procedure related to one side of the scale or the other: Maximizing supply OR Minimizing demand Categories Alerts Warnings Actions 9

11 NERC Energy Emergency Alerts (EEA s) Documentation found in Attachment 1 of NERC Standard EOP- 002 (Capacity and Energy Emergencies) Issued by Reliability Coordinator (via the Reliability Coordinators Information System - RCIS) for capacity and energy shortages Three Levels Provides common terminology for Reliability Coordinators to use when explaining energy emergencies to each other Levels may be declared in whatever order necessary, no need to proceed sequentially 10

12 NERC Energy Emergency Alerts EEA Level 1 Issued when a Control Area foresees or is experiencing conditions where all available resources are committed Concern about being able to sustain required Operating Reserves When does PJM issue? Max Emergency Generation Alert 11

13 NERC Energy Emergency Alerts EEA Level 2 Issued when a Control Area foresees or has implemented procedures up to but excluding interruption of firm load commitments Public Appeals, Voltage Reduction, Load Management, Interruption of Non-firm contracts When does PJM issue? Emergency Mandatory Load Management Reductions Action, or a Voltage Reduction Action (whichever issued first) 12

14 NERC Energy Emergency Alerts EEA Level 3 Issued when a Control Area foresees or has implemented firm load obligation interruption Prior to declaring: All generation on-line, regardless of cost All purchases made, regardless of cost All non-firm sales recalled All contractually interruptible load curtailed When does PJM issue? Manual Load Dump Action 13

15 Agenda Basics Alerts Warnings/Actions Statistics Emergency Procedure Website 14

16 Maximum Emergency Generation Alert Emergency Levels Alerts Primary Reserve Alert Voltage Reduction Alert Primary Reserve Warning Warnings Actions Voltage Reduction Warning Reduction of Non-critical Plant Load Manual Load Dump Warning Maximum Emergency Generation Emergency Mandatory Load Management Reductions Emergency Voluntary Energy Only Demand Response Reductions Voltage Reduction Curtailment of Non-essential Building Load All capacity related Alerts/Warnings/Actions are to be communicated vial the All-Call to local Transmission and Generation Owners and posted to the Emergency Procedure website Manual Load Dump 15

17 Capacity Shortage Alerts Alerts are issued in advance (Day-ahead) of a scheduled load period to allow sufficient time for members to prepare for anticipated initial capacity shortages The intent of the alert is to keep all affected system personal aware of the forecast and/or actual status of the PJM RTO Maximum Emergency Generation Alert Primary Reserve Alert Voltage Reduction Alert 16

18 Capacity Shortages - Alerts Maximum Emergency Generation Alert Primary Reserve Alert Voltage Reduction Alert EEA(Energy Emergency Alert) NERC EEA 1 ISSUED Maximum Emergency Generation Alert Purpose To provide an early alert that PJM Emergency Procedures may be required Trigger When Maximum Emergency Generation is called into the operating capacity Operating Reserve Requirement is greater than scheduled Operating Reserve. 17

19 Estimated Operating Reserve Less than Operating Reserve Objective ME Gen Econ Gen & Imports Pri Reserve Objective Op Reserve Objective Load Load and Capacity Profile 9:00 10:00 11:00 12:00 13:00 14: :00 16:00 17:00 18:00 19:00 Hour ending

20 Capacity Shortages - Alerts Maximum Emergency Generation Alert PJM Actions Notifications Internal PJM Management External Members; Issue NERC EEA Level 1 Performs a situation analysis and prepares capacity/load/interchange/ reserve projections for that day and future periods -- Issues the alert to members, stating the amount of estimated operating reserve and the requirement -- Reports any significant changes in the estimated operating reserve capacity -- Sets up Supplementary Status Report if required May not request until operating day for which alert is in effect 19

21 Capacity Shortages - Alerts Maximum Emergency Generation Alert PJM Actions Review the level of dependency on External Transactions to serve PJM load and to determine if the need to implement Capacity Benefit Margin is required 20

22 Capacity Shortages - Alerts Maximum Emergency Generation Alert Member Actions Notifications Management, generating stations, key personnel Review plans to determine if any maintenance or testing, scheduled or being performed, on any monitoring, control, transmission, or generating equipment can be deferred or halted Report any, or all fuel/environmental limited facilities as they occur and update PJM Dispatch as needed Suspend any high risk testing of generating or transmission equipment 21

23 Capacity Shortages Alerts Maximum Emergency Generation Alert Primary Reserve Alert Voltage Reduction Alert Primary Reserve Alert Purpose To alert members of the anticipated shortage of operating reserve capacity for a future critical period Trigger When the estimated operating reserve is less than the forecasted primary reserve requirement 22

24 Estimated Operating Reserve Less than Primary Reserve Requirement ME Gen Econ Gen & Imports Pri Reserve Objective Op Reserve Objective Load Load and Capacity Profile 9:00 10:00 11:00 12:00 13:00 14: :00 16:00 17:00 18:00 19:00 Hour ending

25 Capacity Shortages - Alerts Primary Reserve Alert PJM Actions Notifications to PJM management and member companies States the amount of estimated operating reserve capacity and the requirement Report significant changes in estimated operating reserve capacity Consider the need to obtain a temporary variance from environmental regulators for specific generators to assist in preventing load shed 24

26 Capacity Shortages - Alerts Primary Reserve Alert Member Actions Notifications Management, generating stations, key personnel Review plans to determine if any maintenance or testing, scheduled or being performed, on any monitoring, control, transmission, or generating equipment can be deferred or halted 25

27 Capacity Shortages - Alerts Maximum Emergency Generation Alert Primary Reserve Alert Voltage Reduction Alert Purpose To alert Members that a Voltage Reduction may be required in a future critical period Trigger When the estimated operating reserve capacity is less than the forecasted synchronized reserve requirement Voltage Reduction Alert 26

28 Capacity Shortages Alerts Voltage Reduction Alert PJM Actions Notifications Internal PJM Management External Members Give LCC s estimated hour of implementation Member Actions Notifications Management, generating stations, key personnel Take any necessary steps to expedite implementation of voltage reduction, should one become necessary (Transmission Dispatch/LSE s) SOS members consider issuance of Public Appeals PJM marketers proceed on heightened awareness regarding potential need for Emergency Energy purchases 27

29 Public Appeals Issued via media outlets (radio,tv) to inform and request customer conservation SOS Transmission determines when to release and scope PJM and member Communications depts can tailor messages for specific situations Messages give instructions for conservation to public Lower thermostats, close blinds Reduce appliance usage during peak hours 28

30 Public Appeals Draft messages are in Manual 13 Attachment A Level 1 Cold/Hot Weather Advisory (C1) (H1) Level 2 Statement/News Release for Cold/Hot Weather Emergency (C2) (H2) Released following Load Management programs Level 3 Statement/News Release for Cold/Hot Weather Emergency (C3) (H3) Released following Voltage Reduction Level 4 Statement/News Release for Cold/Hot Weather Emergency (C4) (H4) Released following Manual Load Dump Messages for exiting emergencies 29

31 Agenda Basics Alerts Warnings/Actions Statistics Emergency Procedure Website 30

32 Capacity Emergency Warnings/Actions Warnings and Actions are issued in real-time Warnings are issued to inform members of actual capacity shortages or contingencies that may jeopardize reliability A Warning typically precedes an associated Action Warnings keep all affected system personnel aware of the forecast and/or actual status of the PJM RTO M-13 combines the Warnings and Actions in their most probable sequence based on notification requirements during extreme peak conditions 31

33 Capacity Shortages - WARNINGS Warnings are issued during present operations To inform Members of actual capacity shortages and contingencies that may affect the reliability of the PJM Control Area Three Warnings: Primary Reserve Warning Voltage Reduction Warning and Reduction of Non-Critical Plant Load Manual Load Dump Warning 32

34 Capacity Shortage Actions Five Actions Maximum Emergency Generation Emergency Mandatory Load Management Reductions Emergency Voluntary Energy Only Demand Response Reductions Voltage Reduction/Curtailment of Non-Essential Load Manual Load Dump 33

35 Actions Actions Maximum Emergency Generation Emergency Mandatory Load Management Reductions Emergency Voluntary Energy Only Demand Response Reductions Voltage Reduction Curtailment of Non- Essential Building load Short Lead Time Long Lead Time Load Management Manual Load Dump PJM 34

36 Emergency Mandatory Load Management Reductions Restrictions Applies to any site registered in the PJM Demand Response Program as a: - Capacity resource of interruptible load for reliability - Demand resource of interruptible load for reliability Issued to provide additional load relief using controllable load management programs (Load relief is expected to be issued after initiating Maximum Emergency Generation Participating customers receive capacity credits and/or reduced retail rates for reducing load during emergencies PJM and/or Transmission Operator controlled and directed 35

37 Emergency Mandatory Load Management Reductions - Types PJM recognizes three types of Load Management: Direct Load Control (DLC) Load management which is initiated directly by the LSE s market operations center, employing a communication signal to cycle equipment Firm Service Level (FSL) Load management achieved by a customer reducing its load to a pre-determined level (the Firm Service Level), upon notification from the LSE s market operations center Guaranteed Load Drop (GLD) - Load management achieved by a customer reducing its load by a pre-determined amount (the guaranteed load drop), upon notification from the LSE s market operations center 36

38 Emergency Mandatory Load Management Reductions Restrictions PJM Actions: - Notifications to PJM management, public information personnel, and member companies - Use of public appeals to conserve electricity usage - Via the PJM All-Call, PJM requests Curtailment Service Providers to implement curtailment procedures - Via the RCIS, PJM issues a NERC Energy Emergency Alert Level 2 37

39 Emergency Mandatory Load Management Reductions Restrictions PJM Member Actions: - Member Curtailment Service Providers implement load reductions as requested by PJM - Notify member company management and consider the use of public appeals - Notify government agencies - Long Lead Time: curtailment achieved in 1-2 hours - Short Lead Time: curtailment achieved in 1 hour or less 38

40 Emergency Mandatory Load Management Reductions Restrictions Program Restrictions: Interruptible by PJM for 10 times during planning period (June May) From June through September, interruptible for up to six hours in duration from 12:00 to 20:00 on non-holiday weekdays From October through May, interruptible for up to six hours in duration from 14:00 to 22:00 on non-holiday weekdays Able to be implemented within 2 hrs Not used to assist adjacent Control areas 39

41 Primary Reserve Warning Primary Reserve Warning Voltage Reduction and Reduction of Non-critical Plant Load Manual Load Dump Warning Primary Reserve Warning Purpose To warn the Local Control Centers that the Primary Reserve is less than required and operations are getting critical Trigger Issued when the Primary Reserve is less than the Primary Reserve requirement but greater than the Synchronized Reserve requirement 40

42 Primary Reserve Warning PJM Actions: - Issues a warning to members and PJM management stating the amount of adjusted primary reserve capacity and the requirement - Notifies PJM public information personnel - Assure that all available equipment is scheduled and requested supplemental reserve has been brought into the primary reserve - Ensures all deferrable maintenance or testing on the communications and control systems has halted 41

43 Primary Reserve Warning PJM Actions: - Obtain a temporary variance from environmental regulators for specific generators to assist in preventing load shedding - Cancel warning when appropriate 42

44 Primary Reserve Warning PJM Member Actions: - Notify management - Advise all stations and key personnel - Prepare to load primary reserve, if required - Ensure all deferrable maintenance or testing affecting capacity or critical transmission is halted - PJM Marketers remain on a heightened awareness regarding regarding PJM conditions and the potential need for Emergency Energy Purchases 43

45 Actions Maximum Emergency Generation Emergency Mandatory Load Management Reductions Short Lead Time Actions Emergency Voluntary Energy Only Demand Response Reductions Voltage Reduction Curtailment of Non- Essential Building load Long Lead Time Load Management Manual Load Dump PJM 44

46 Maximum Emergency Generation Purpose To increase generation above the maximum economic level Trigger Real-time Generation is needed to meet the load demand that is greater than the highest incremental cost level 45

47 Load Exceeds Maximum Economic Generation Levels ME Gen Econ Gen & Imports Load Load and Capacity Profile 9:00 10:00 11:00 12:00 13:00 14: :00 16:00 17:00 18:00 19:00 Hour ending

48 Maximum Emergency Generation Action PJM Actions: - Issue the Maximum Emergency Generation Action - Notify PJM management, PJM public information personnel, and member dispatchers - Implements the Emergency Bid Process, requesting bids by posting messages to selected PJM web-sites, RCIS, and contacting neighboring Control Areas - Suspend regulation on all resources except for hydroelectric - Recalls off-system capacity sales from network resources 47

49 Maximum Emergency Generation Action PJM Actions: - Declares Maximum Emergency Generation and begins to load Maximum Emergency or start purchases of Emergency Energy bids based on economics and availability - Loads Maximum Emergency Generation incrementally as required (Max Emergency CT s are loaded prior to Max Emergency Steam in order to preserve synchronized reserve - Initiate scarcity pricing based on the loading of Maximum Emergency Generation or acceptance of Emergency Energy Purchases in the appropriate Scarcity Pricing Region 48

50 Maximum Emergency Generation Action PJM Member Actions: - Notify management - Recall off-system capacity sales that are recallable - Suspend regulation, as requested, and load all units to the Maximum Emergency Generation level, as required - Notify PJM of any Maximum Emergency Generation loaded prior to PJM requesting Maximum Emergency Generation be loaded 49

51 Maximum Emergency Generation Emergency Bid Process Member is responsible for delivery and transmission service PJM attempts to provide 60 minutes notice before energy is required Fax bid form and call to verify receipt Manual 13 Attachment D 50

52 Emergency Bid Process Bids may also be called into a pre-assigned, recorded voice line that should be structured as follows: - Time of energy available - Amount of energy available - Price of energy - Duration (hours) energy is available and limits on minimum time required to take - Notification time to cancel/accept - PJM Member identification - Interface and contract path 51

53 Emergency Bid Process PJM accepts offers and schedules the energy using the following guidelines: - Energy is accepted based on economics; based on energy price and minimum hours - Energy schedules will be adjusted to correct economics if time permits - Similarly priced offers are selected based on timestamps; first in, first selected Bids do not set the Locational Marginal Price 52

54 Scarcity Pricing Implementation Pricing in the entire Scarcity Pricing Region will be set equal to the highest market-based offer price of all generating units operating under PJM direction to supply either energy or reserves on a real-time dispatch basis No offer capping for transmission constraints may be initiated or continued in the Scarcity Pricing Region while Scarcity Pricing is in effect Generation in the Scarcity Pricing Region shall remain subject to the overall offer cap of $1,000/MWh A generator outside of the SPR that is used to control for the transmission constraint that caused Scarcity Pricing shall be paid the higher of the Scarcity Region Price or its offer price 53

55 Scarcity Pricing Implementation - Issued for the following trigger points: - Online generators, partially designated as Max Emergency, dispatched into emergency output levels - Online generation, entirely designated as Max Emergency, dispatched above designated minimum load points, if they are currently on-line and operating at their minimum load points because of restrictive operating parameters associated with the generators - Offline generation, entirely designated as Max Emergency, dispatched having start-up and notification times less than or equal to 30 minutes 54

56 Scarcity Pricing Implementation Issued for the following trigger points: - Voltage Reduction action - Emergency Energy purchases - Manual Load Dump action Whenever any of the above actions trigger Scarcity Pricing, PJM will post the message on the Emergency Procedure Website describing the action and include in the posting the Scarcity Pricing Region for which the action is taken 55

57 Scarcity Pricing Implementation In defining scarcity conditions, PJM will consider generators that have been classified as Maximum Emergency only if they in one of the following categories: - Environmental limits: hard cap on its run hours that will temporarily limit temporarily limit its availability - Fuel limitations: physical event beyond the control of the unit s owner resulting in a temporary interruption of fuel supply and there is limited on-site fuel storage - Temporary emergency physical conditions (Continued) 56

58 Scarcity Pricing Implementation Temporary megawatt additions: provide additional MW s on a temporary basis by: 1. Oil topping 2. Boiler overpressure 3. Other techniques and such MW s are not otherwise available 57

59 Scarcity Pricing Implementation Scarcity Pricing Criteria: - Consist of at least two entire transmission zones - Consist of transmission zone and sub-zones with common boundaries - Transmission import or transfer must be limited by EHV (500 kv or greater) constraints - Consist of pricing nodes that have a 5% or greater positive power distribution factor (dfax) relative to the constraints 58

60 Scarcity Pricing Implementation If a Maximum Emergency Generation Alert is issued prior to 1800 hrs on the day prior to the operating day, the only units for which all or part of their capability may be designated as Maximum Emergency are those meeting the criteria in the previous slide If a Maximum Emergency Generation Alert is issued during the operating day for which the alert is effective, generation owners are responsible for removing any unit availability from the Maximum Emergency Generation category that does not meet the criteria within 4 hours of the issuance of the alert 59

61 Scarcity Pricing Implementation Scarcity Pricing will be terminated in a Scarcity Region when demand and reserves can be fully satisfied with generation that is not designated as Max Emergency Scarcity conditions will not be terminated if the following conditions exist in the Scarcity Region: - Voltage reduction action - Emergency energy purchases from offers that do not have minimum purchase requirements of greater than 30 minutes attached to the offer - Manual load dump action 60

62 Actions Actions Maximum Emergency Generation Emergency Mandatory Load Management Reductions Emergency Voluntary Energy Only Demand Response Reductions Voltage Reduction Curtailment of Non- Essential Building load Short Lead Time Long Lead Time Load Management Manual Load Dump 61

63 Emergency Voluntary Energy Only Demand Response Reductions Purpose - To request end-use customers who participate in the Emergency Voluntary Energy Only Demand Response Reductions to reduce load during emergency conditions Trigger - Additional load relief is still needed Program criteria: - Any site registered in the PJM Demand Response Program as an emergency energy only resource - Reductions are strictly voluntary 62

64 Emergency Voluntary Energy Only Demand Response Reductions PJM Actions: - Issues action via the All-Call and posts message on website - Notifies PJM management, PJM public information personnel, and PJM Markets personnel - Have Curtailment Service Providers with Demand Resources reduce load PJM Member Actions: - Notify management of the emergency procedure 63

65 Voltage Reduction & Reduction of Non-Critical Plant Load Primary Reserve Warning Voltage Reduction Warning and Reduction of Non-Critical Plant Load Manual Load Dump Warning Voltage Reduction Warning (& Reduction of Non-critical Plant Load) Purpose To inform the Member Companies that Synchronized Reserve is less than required and present operation has deteriorated such that voltage reduction may be required Trigger When actual Synchronized Reserve is less than the Synchronized Requirement All secondary and primary reserve (except MW s in Max Emergency) are first moved to Synchronized Reserve status 64

66 Voltage Reduction & Reduction of Non-Critical Plant Load PJM Actions: - Issues the warning to members and PJM management stating the amount of adjusted synchronized reserve capacity and the requirement - Notification of PJM public information personnel - Notification of the Department of Energy - Cancels the warning, when appropriate 65

67 Voltage Reduction & Reduction of Non-Critical Plant Load PJM Member Actions: - Notification to member company management - Notification to government agencies - Advise all stations and key personnel - Order all generating stations to curtail non-essential station light and power - Prepare for implementation of a Voltage Reduction Action - Implement load management programs, in addition to interrupting curtailable customers - Awareness of need for Emergency Energy Purchases 66

68 Manual Load Dump Warning Primary Reserve Warning Voltage Reduction Warning and Reduction of Non-Critical Plant Load Manual Load Dump Warning Manual Load Dump Warning Purpose To warn Member Companies of increasingly critical system conditions that may require manually dumping load Trigger When the Primary Reserve is less than the largest generating unit or the loss of a transmission facility jeopardizes reliability after all possible measures have been taken to increase reserves - Amount of load and the areas of location are specified 67

69 Manual Load Dump Warning PJM Actions: - Issue the warning to members and PJM Management, stating the estimated amount of load relief needed - Notification to PJM public information personnel - Notification to include the FERC Division of Reliability - Establish an awareness with Transmission Operators of the need for action with minimum delay - Examine EHV bus voltages 68

70 Manual Load Dump Warning PJM Member Actions: - Notification to member management - Notification to government agencies - Advise all station and key personnel - Review local procedures and prepare to dump load in the amount requested - Reinforce internal communications so that load dumping can occur with a minimum delay - Marketers remain on a heightened awareness of the potential need for Emergency Energy Purchases 69

71 Actions Actions Maximum Emergency Generation Emergency Mandatory Load Management Reductions Emergency Voluntary Energy Only Demand Response Reductions Voltage Reduction Curtailment of Non- Essential Building load NERC EEA 2 ISSUED Short Lead Time Long Lead Time Manual Load Dump 70

72 Voltage Reduction Action Purpose To reduce load to provide a sufficient amount of reserve to maintain tie flow schedules and preserve limited energy resources OR to increase transmission system voltages Trigger Load relief still needed to maintain ties Curtailment of non-essential building load may be implemented prior to, but no later than the voltage reduction. 71

73 Voltage Reduction Action Voltage is reduced at distribution levels by 2.5% to 5% of nominal values depending on the area Increases transmission voltages Produces a 2-3% decrease in system load Generally not noticed by customers Lights dimmer, slower heating City of Chicago limited to 2.5% voltage reduction 72

74 Effects of Voltage Reduction in BC/PEPCO in 2005 Reduction in MW Load Reduction in VAR Load 73

75 Effects of Voltage Reduction in BC/PEPCO in

76 Voltage Reduction Action PJM Actions: - Notification to PJM Management, PJM public information personnel, and member companies - Advise members to use public appeals for conservation of energy - Notification to the Department of Energy - Issue a system-wide or Control Zone-specific Public Media Message H-3 - Investigates loading of shared reserves with neighboring systems prior to a voltage reduction 75

77 Voltage Reduction Action PJM Actions: - Issues the order for a 2.5% to 5% voltage reduction - Issues a NERC Energy Emergency Alert Level 2 via the RCIS - Initiates Scarcity Pricing based on the issuance of a voltage reduction in the appropriate Scarcity Pricing Region - Cancels the reduction, when appropriate 76

78 Voltage Reduction Action PJM Member Actions: - Notification of member company management - Notification of government agencies - Consider the use of public appeals to conserve energy - Take steps to implement a voltage reduction 77

79 Curtailment of Non-Essential Building Load Purpose: - The purpose is to provide additional relief, to be expedited prior to, but no later than the same time as the voltage reduction 78

80 Curtailment of Non-Essential Building Load PJM Actions: - Notification to PJM Management, PJM public information personnel, and member companies - Advise members to utilize public appeals to conserve energy - Issue the request to curtail non-essential building load - Cancel the request, when appropriate 79

81 Curtailment of Non-Essential Building Load PJM Member Actions: - Notification of member company management - Notification of government agencies - Consider the use of public appeals to conserve energy - Switch off all non-essential light and power in companyowned commercial, operations, and administration offices 80

82 Actions Maximum Emergency Generation Emergency Mandatory Load Management Reductions Short Lead Time Actions Emergency Voluntary Energy Only Demand Response Reductions Voltage Reduction Curtailment of Non- Essential Building load Long Lead Time Load Management Manual Load Dump NERC EEA 3 ISSUED 81

83 Manual Load Dump Action Issued to provide relief when all other possible means of supplying internal load have been exhausted to prevent a catastrophe within PJM or to maintain tie schedules so as not to jeopardize the reliability of other interconnected regions Implemented when PJM cannot provide adequate capacity to meet load or critically overloaded transmission lines or equipment cannot be relieved in any other way and/or low frequency operation occurs within a part(s) of the RTO 82

84 Manual Load Dump Action PJM Actions: - Verifies that separations have not occurred and that load dumping is desirable on the system being controlled - Instructs members to suspend all remaining regulation - Determines which Control Zone(s) are capacity deficient and the relative proportion of deficiency - Estimates the total amount of load to be dumped - Orders appropriate members to dump load - Notification to PJM Management, PJM public information personnel, and member companies 83

85 Manual Load Dump Action PJM Actions: - Advise members to consider the use of public appeals to conserve energy - Notification to other Control Areas through the RCIS - Notifications to DOE, FEMA, and NERC offices - Notification to FERC via the FERC Division of Reliability s electronic pager system - Issue a NERC Energy Emergency Alert Level 3 - PJM Management issues a system-wide or Control Zone specific Public/Media Notification Message H-4 (Should be issued prior to Manual Load Dump Action) 84

86 Manual Load Dump Action PJM Actions: - Initiates Scarcity Pricing based on the issuance of a Manual Load Dump Action in the appropriate Scarcity Pricing Region - Cancels the action and restores required regulation, when appropriate - If a partial restoration of the load dumped is requested by PJM, confirmation of restored load by each member must be made prior to any further load restoration - If UFLS is insufficient to return frequency to acceptable ranges, PJM will dump sufficient load to restore system frequency 85

87 Manual Load Dump Action Member Actions: - Suspend regulation, as required, prior to load dump - Notification member company management of the procedure - Notification of government agencies - Consider the use of public appeals to conserve energy - Promptly dump load equal to or in excess of the company s allotment of load dump - Maintain the requested amount of load relief until the load dump order is cancelled by PJM - Load dump plan should consider/recognize priority/critical load - Report amount of load curtailed/restored upon implementation 86

88 Manual Load Dump Action Process described here pertains only to capacity deficient situations For transmission constraints or voltage problems, load dump will be ordered in areas where it is most effective If Mid-Atlantic region is deemed deficient, total load shed must be further broken down by Manual Load Dump Allocation Tables Manual M-13 Attachment E Manual Load Dump last utilized in PJM on January 19, PJM 87

89 Manual Load Dump Action 88

90 Agenda Basics Alerts Warnings/Actions Emergency Procedure Website 89

91 Access to PJM Emergency Procedure Messages Emergency Procedures Messages can be accessed by using any of the following: PJM Website Homepage edata OASIS esuite 90

92 2008 PJM 91

93 Emergency Procedure Application PJM 92

94 Emergency Procedure Application PJM 93

95 Summary Know where your emergency procedures are. Know your part as a System Operator. KEEP THE LIGHTS ON! 94

96 Questions 95

97 Disclaimer: PJM has made all efforts possible to accurately document all information in this presentation. The information seen here does not supersede the PJM Operating Agreement or the PJM Tariff both of which can be found by accessing: For additional detailed information on any of the topics discussed, please refer to the appropriate PJM manual which can be found by accessing: 96

98 Resources and References PJM Manual 13 Emergency Procedures 97

A. Introduction Balancing Authority Reliability Coordinator Transmission Operator. 5. Effective Date:

A. Introduction Balancing Authority Reliability Coordinator Transmission Operator. 5. Effective Date: A. Introduction 1. Title: Emergency Operations 2. Number: EOP-011-1 3. Purpose: To address the effects of operating Emergencies by ensuring each Transmission Operator and Balancing Authority has developed

More information

Capacity Performance Training. March 16, 2015

Capacity Performance Training. March 16, 2015 Capacity Performance Training March 16, 2015 Training Objectives Provide Capacity Market Sellers with information necessary to participate in the Reliability Pricing Model (RPM) under a Capacity Performance

More information

Operating Procedure PURPOSE... 1

Operating Procedure PURPOSE... 1 Table of Contents PURPOSE... 1 1. RESPONSIBILITIES... 2 2. SCOPE/APPLICABILITY... 2 2.1. Background... 2 2.2. Scope/ Applicability... 2 3. PROCEDURE DETAIL... 3 3.1. Order of Steps... 3 3.2. Restricted

More information

LOAD SERVING ENTITIES PJM REGION

LOAD SERVING ENTITIES PJM REGION Intra-PJM Tariffs --> RELIABILITY ASSURANCE AGREEMENT PJM Interconnection, L.L.C. Rate Schedule FERC No. 44 RELIABILITY ASSURANCE AGREEMENT Among LOAD SERVING ENTITIES in the PJM REGION Effective Date:

More information

3. RELATIONSHIP BETWEEN ISO AND PARTICIPATING TOs. Each Participating TO shall enter into a Transmission Control Agreement with the

3. RELATIONSHIP BETWEEN ISO AND PARTICIPATING TOs. Each Participating TO shall enter into a Transmission Control Agreement with the FERC ELECTRIC TARIFF First Revised Sheet No. 121 ORIGINAL VOLUME NO. I Replacing Original Sheet No. 121 3. RELATIONSHIP BETWEEN ISO AND PARTICIPATING TOs. 3.1 Nature of Relationship. Each Participating

More information

Dispatch Signal & Locational Marginal Pricing (LMP)

Dispatch Signal & Locational Marginal Pricing (LMP) Dispatch Signal & Locational Marginal Pricing (LMP) PJM State & Member Training Dept. Objectives Students will be able to: Identify how PJM dispatches & utilizes LMP Dispatch Rate Economic control signal

More information

Load Management Performance Report 2015/2016

Load Management Performance Report 2015/2016 Load Management Performance Report 2015/2016 August 2016 PJM has made all efforts possible to accurately document all information in this report. However, PJM cannot warrant or guarantee that the information

More information

Educating System Operators in the New Millennium! Background. Course Level. Target Audience. NERC Continuing Education Hours

Educating System Operators in the New Millennium! Background. Course Level. Target Audience. NERC Continuing Education Hours Background The class will be delivered over a 3-day period. The class is comprised of three training modules covering the areas of: Communications, Critical Thinking, and Restoration. The course consists

More information

POTOMAC ELECTRIC POWER COMPANY

POTOMAC ELECTRIC POWER COMPANY POTOMAC ELECTRIC POWER COMPANY FERC Form 715 (Part 4) - Transmission Planning Study Guidelines Transmission Reliability Guidelines 1. General Overview The reliability guidelines used to plan the transmission

More information

Capacity Performance Training. June 24, 2015

Capacity Performance Training. June 24, 2015 Capacity Performance Training June 24, 2015 Training Objectives Provide Capacity Market Sellers with information necessary to participate in the Reliability Pricing Model (RPM) under a Capacity Performance

More information

California Independent System Operator Corporation Fifth Replacement Electronic Tariff

California Independent System Operator Corporation Fifth Replacement Electronic Tariff Table of Contents California Independent System Operator Corporation 8. Ancillary Services... 3 8.1 Scope... 3 8.2 Ancillary Services Standards... 4 8.2.1 Determination Of Ancillary Service Standards...

More information

Introduction to the PJM Markets

Introduction to the PJM Markets Introduction to the PJM Markets PJM 2015 1 Objectives Students will be able to: Describe some of the basic functions of PJM PJM 2015 The History of PJM EKPC joins PJM 2013 PJM 2015 3 Our Responsibility

More information

California Independent System Operator Corporation Fifth Replacement Electronic Tariff

California Independent System Operator Corporation Fifth Replacement Electronic Tariff Table of Contents 40. Resource Adequacy Demonstration for all SCs in the CAISO BAA... 3 40.1 Applicability... 3 40.1.1 [Not Used]... 3 40.2 Information Requirements for Resource Adequacy Programs... 3

More information

Committed Offer: Offer on which a resource was scheduled by the Office of the Interconnection for a particular clock hour for the Operating Day.

Committed Offer: Offer on which a resource was scheduled by the Office of the Interconnection for a particular clock hour for the Operating Day. Proposed Tariff Revisions Attachment K-Appendix and Schedule 1 of the Operating Agreement Generator Offer Flexibility Senior Task Force Revisions Related To Make-Whole and Lost Opportunity Cost Payments

More information

NERC Reliability Functional Model Technical Document Version 5

NERC Reliability Functional Model Technical Document Version 5 Reliability Functional Model Technical Document Version 5 Prepared by the Functional Model Working Group This document is a companion to Version 5 of the Functional Model. It provides context, explanations,

More information

Load Management Performance Report 2017/2018. (mid Delivery Year update)

Load Management Performance Report 2017/2018. (mid Delivery Year update) Load Management Performance Report 2017/2018 (mid Delivery Year update) January 2018 PJM has made all efforts possible to accurately document all information in this report. However, PJM cannot warrant

More information

California Independent System Operator Corporation Fifth Replacement Electronic Tariff

California Independent System Operator Corporation Fifth Replacement Electronic Tariff Table of Contents 8. Ancillary Services... 3 8.1 Scope... 3 8.2 Ancillary Services Standards... 4 8.2.1 Determination of Ancillary Service Standards... 4 8.2.2 Time-Frame for Revising Ancillary Service

More information

Reserve Market. PJM State & Member Training Dept. PJM /06/2016

Reserve Market. PJM State & Member Training Dept. PJM /06/2016 Reserve Market PJM State & Member Training Dept. PJM 2016 Objectives Define Reserve products Explain the Reserve requirements Calculate Reserve offers PJM 2016 2 Reserves Reserves are additional generation

More information

PJM Manual 27: Open Access Transmission Tariff Accounting Revision: 88 Effective Date: November 16, 2017

PJM Manual 27: Open Access Transmission Tariff Accounting Revision: 88 Effective Date: November 16, 2017 PJM Manual 27: Open Access Transmission Tariff Accounting Revision: 88 Effective Date: November 16, 2017 Prepared by Market Settlements Development Department PJM 2017 Table of Contents Table of Contents

More information

PJM Manual 10: Pre-Scheduling Operations Revision: 36 Effective Date: December 22, Prepared by Operations Planning Division

PJM Manual 10: Pre-Scheduling Operations Revision: 36 Effective Date: December 22, Prepared by Operations Planning Division PJM Manual 10: Pre-Scheduling Operations Revision: 36 Effective Date: December 22, 2017 Prepared by Operations Planning Division PJM 2017 Table of Contents Table of Contents Table of Exhibits...4 Approval...5

More information

Demand Response. Overview. Recommendations

Demand Response. Overview. Recommendations Section 6 Demand Response Demand Response Markets require both a supply side and a demand side to function effectively. The demand side of wholesale electricity markets is underdeveloped. Wholesale power

More information

FERC Directives in Order 693 Addressed in IROL Implementation Plan

FERC Directives in Order 693 Addressed in IROL Implementation Plan The following Interconnection Reliability Operating Limit (IROL) standards were under development when the Version 0 project was initiated: IRO-008 Reliability Coordinator Operational Analyses and Real-time

More information

MISO MODULE B FERC Electric Tariff TRANSMISSION SERVICE MODULES Effective On: November 19, 2013

MISO MODULE B FERC Electric Tariff TRANSMISSION SERVICE MODULES Effective On: November 19, 2013 MISO MODULE B TRANSMISSION SERVICE MISO I INTRODUCTION The Transmission Provider shall provide Point-To-Point and Network Integration Transmission Service pursuant to the applicable terms and conditions

More information

Federal Energy Regulatory Commission/RTO Training Session

Federal Energy Regulatory Commission/RTO Training Session Federal Energy Regulatory Commission/RTO Training Session Scott H. Strauss Jeffrey A. Schwarz Institute for Policy Integrity NYU Law School June 2011 Agenda FERC -- Who and what is it? History of FERC

More information

Operating Procedure PURPOSE... 1

Operating Procedure PURPOSE... 1 No. 4120 Table of Contents PURPOSE... 1 1. RESPONSIBILITIES... 2 2. SCOPE/APPLICABILITY... 3 2.1 Background... 3 2.2 Scope/ Applicability... 4 3. PROCEDURE DETAIL... 4 3.1 General Information... 4 3.2

More information

PJM TO/TOP Matrix of Shared or Assigned Tasks

PJM TO/TOP Matrix of Shared or Assigned Tasks PJM TO/TOP Matrix of hared or ssigned Tasks Draft Version 11 s of eptember 8, 2017 Finalized pproved by the TO/TOP Matrix ubcommittee: June 16, 2017 pproved by the Transmission Owners greement-dministrative

More information

Demand Response. Mathangi Srinivasan. New York Market Orientation Course (NYMOC) Senior Market Trainer, NYISO. March 20-23, 2018 Rensselaer, NY 12144

Demand Response. Mathangi Srinivasan. New York Market Orientation Course (NYMOC) Senior Market Trainer, NYISO. March 20-23, 2018 Rensselaer, NY 12144 Demand Response Mathangi Srinivasan Senior Market Trainer, NYISO New York Market Orientation Course (NYMOC) March 20-23, 2018 Rensselaer, NY 12144 1 Demand Response Module Objectives Upon completion of

More information

Appendix 1 PRELIMINARY DELIVERABILITY BASELINE ANALYSIS STUDY REPORT

Appendix 1 PRELIMINARY DELIVERABILITY BASELINE ANALYSIS STUDY REPORT Generation and Import Deliverability to the Aggregate of Load (Baseline) Study Methodology Executive Summary Deliverability is an essential element of any resource adequacy requirement. Specifically, Load

More information

Functional Entity Roles and Responsibilities

Functional Entity Roles and Responsibilities Functional Entity Roles and Responsibilities NWPP MC Phase 3 Operations Integration Work Group 9/28/2014 Page 1 of 13 Table of Contents 1. Purpose... 3 2. Roles and Responsibilities of Functional Entities...

More information

Northwest Power Pool Processes

Northwest Power Pool Processes Northwest Power Pool Processes Background The Northwest Power Pool membership (NWPP) was founded in 1941 to promote efficient production of electrical energy. The NWPP is the geographic area encompassed

More information

CUSTOMER GUIDE TO PJM BILLING

CUSTOMER GUIDE TO PJM BILLING CUSTOMER GUIDE TO PJM BILLING Billing Line Items include PJM Open Access Tariff (OATT) references, PJM Operating Agreement (OpAgr) references, and PJM Manual references. Reports are available for viewing,

More information

Day-ahead ahead Scheduling Reserve (DASR) Market

Day-ahead ahead Scheduling Reserve (DASR) Market Day-ahead ahead Scheduling Reserve (DASR) Market Agenda Implementation Overview of the DASR Market Market Clearing Process Market Clearing Example Performance Compliance Market Settlements Appendix: emkt

More information

BALANCING CODE NO. 1 (BC1)

BALANCING CODE NO. 1 (BC1) Paragraph No/Title BALANCING CODE NO. 1 (BC1) PRE GATE CLOSURE PROCESS CONTENTS (This contents page does not form part of the Grid Code) Page Number BC1.1 INTRODUCTION... 1 BC1.2 OBJECTIVE... 1 BC1.3 SCOPE...

More information

Two Settlement PJM /06/2016

Two Settlement PJM /06/2016 Two Settlement PJM 2016 Objectives Describe Two-Settlement process Day-Ahead Market Balancing Market Explain Virtual Transactions and their settlement Inc Offers Dec Bids Up-to Congestion Transactions

More information

PJM Manual 14A: New Services Request Process Revision: 20 Effective Date: October 1, Prepared by Interconnection Planning Department

PJM Manual 14A: New Services Request Process Revision: 20 Effective Date: October 1, Prepared by Interconnection Planning Department PJM Manual 14A: New Services Request Process Revision: 20 Effective Date: October 1, 2017 Prepared by Interconnection Planning Department PJM 2017 Table of Contents Table of Contents Table of Exhibits...7

More information

RPM 301 Performance in Reliability Pricing Model

RPM 301 Performance in Reliability Pricing Model RPM 301 Performance in Reliability Pricing Model PJM State & Member Training Dept. PJM 2017 Disclaimer: PJM has made all efforts possible to accurately document all information in this presentation. The

More information

NORTHWEST POWER POOL. Energy Emergency Plan

NORTHWEST POWER POOL. Energy Emergency Plan NORTHWEST POWER POOL Energy Emergency Plan Revised August 2017 Table of Contents I. Background... 3 II. Purpose... 3 III. Potential Actions of the Emergency Plan... 4 IV. Key Plan Components and Definitions...

More information

Transmission System Outage Scheduling Process. Interconnection Training Program PJM State & Member Training Dept.

Transmission System Outage Scheduling Process. Interconnection Training Program PJM State & Member Training Dept. Disclaimer This training presentation is provided as a reference for preparing for the PJM Certification Exam. Note that the following information may not reflect current PJM rules and operating procedures.

More information

Load Shed Philosophy

Load Shed Philosophy APPLICABILITY: Reliability Coordinator I. Background While time limits exist for mitigation of the exceedance of certain types of system operating limits, events can occur quickly necessitating a responsive

More information

Standard TPL Transmission System Planning Performance Requirements

Standard TPL Transmission System Planning Performance Requirements A. Introduction 1. Title: Transmission System Planning Performance Requirements 2. Number: TPL-001-4 3. Purpose: Establish Transmission system planning performance requirements within the planning horizon

More information

SCHEDULE 6A Black Start Service

SCHEDULE 6A Black Start Service SCHEDULE 6A Black Start Service References to section numbers in this Schedule 6A refer to sections of this Schedule 6A, unless otherwise specified. To ensure the reliable restoration following a shut

More information

Energy Markets - The Basics

Energy Markets - The Basics Disclaimer This training presentation is provided as a reference for preparing for the PJM Certification Exam. Note that the following information may not reflect current PJM rules and operating procedures.

More information

Pre-Scheduling Operations

Pre-Scheduling Operations Style Definition: PJM_Normal Style Definition: PJM_Bulleted_Para_1 PJM Manual 10: Pre-Scheduling Operations Revision: 365 Effective Date: January 1, 2017 Prepared by Operations Support Division Generation

More information

Fundamentals of Transmission Operations

Fundamentals of Transmission Operations Fundamentals of Transmission Operations Telecommunications PJM State & Member Training Dept. PJM 2014 9/10/2013 Objectives The student will be able to: Explain the back-up satellite phone testing requirements

More information

Section 5: Network Integration Transmission Service Accounting. 5.1 Network Integration Transmission Service Accounting Overview

Section 5: Network Integration Transmission Service Accounting. 5.1 Network Integration Transmission Service Accounting Overview Section 5: Network Integration Transmission Service Accounting Welcome to the Network Integration Transmission Service Accounting section of the PJM Manual for Open Access Transmission Tariff Accounting.

More information

PJM Reserve Market. PJM State & Member Training Dept. PJM /27/2015

PJM Reserve Market. PJM State & Member Training Dept. PJM /27/2015 PJM Reserve Market PJM State & Member Training Dept. Objectives Students will be able to: Identify the process and procedures for participating in the Real Time Reserve Market Reserves Overview What are

More information

Certification and Training Requirements

Certification and Training Requirements PJM Manual 40 Certification and Training Requirements Revision: 03 Effective Date: 1/25/2008 Prepared by System Operations Division PJM 2008 PJM 2008 1 Table of Contents PJM Manual 40 Certification and

More information

Distribution System Operating Code

Distribution System Operating Code Distribution System Operating Code Draft Rev 5 Approved September 2007 Comments to this document can be forwarded to: RSA Grid Code Secretariat Attention: Mr. Bernard Magoro Eskom, Transmission System

More information

Assessment of Load Shed Service for Import (LSSi) Product

Assessment of Load Shed Service for Import (LSSi) Product Assessment of Load Shed Service for Import (LSSi) Product Date: March 27, 2014 Prepared by: Prepared for: Mike Law Jenny Chen Senior Market Design Specialist Vice President, Market Services Table of Contents

More information

804 OFF-NOMINAL FREQUENCY LOAD SHEDDING AND RESTORATION

804 OFF-NOMINAL FREQUENCY LOAD SHEDDING AND RESTORATION Operating Policies and Procedures Emergency System Operations OPP 804 Issued:2008-11-13 Supersedes Interim OPP Effective:2008-05-01 804 OFF-NOMINAL FREQUENCY LOAD SHEDDING AND RESTORATION 1. Purpose To

More information

System Impact Study and Facilities Study Process Manual For Cleco Power LLC

System Impact Study and Facilities Study Process Manual For Cleco Power LLC System Impact Study and Facilities Study Process Manual For Cleco Power LLC Version 3 March 2010 System Impact Study and Facilities Study Manual for Cleco Power LLC 1.0 Introduction.3 1.1 Purpose.3 1.2

More information

Transmission Constraint Relaxation Parameter Revision ISO Straw Proposal

Transmission Constraint Relaxation Parameter Revision ISO Straw Proposal Transmission Constraint Relaxation Parameter Revision ISO Straw Proposal October 18, 2012 Prepared by: Market and Infrastructure Development Version: 1.0 California Independent System Operator Contents

More information

Con Edison. Evolution of Con Edison efforts in Energy Efficiency and Demand Management:

Con Edison. Evolution of Con Edison efforts in Energy Efficiency and Demand Management: Evolution of Con Edison efforts in Energy Efficiency and Demand Management: Innovative programs and technologies, and their impacts on customers, contractors and the markets Con Edison Con Edison - Overview

More information

the Real-Time Market will be based on the system marginal costs produced by the Real-Time

the Real-Time Market will be based on the system marginal costs produced by the Real-Time 17.1 LBMP Calculation The Locational Based Marginal Prices ( LBMPs or prices ) for Suppliers and Loads in the Real-Time Market will be based on the system marginal costs produced by the Real-Time Dispatch

More information

Incremental Black Start RFP Response Template & General Information

Incremental Black Start RFP Response Template & General Information Revision 2: 7/28/2015 Incremental Black Start RFP Response Template & General Information Overview This document is divided into three sections: Section 1: An incremental RFP response template Section

More information

Summary of 2016 MISO State of the Market Report

Summary of 2016 MISO State of the Market Report Summary of 2016 MISO State of the Market Report Presented to: MISO Board Markets Committee David B. Patton, Ph.D. MISO Independent Market Monitor July 20, 2017 Introduction As the Independent Market Monitor

More information

LOLE is expressed as hours per year with the usual target criteria being (0.1 days/year) or 1- day in 10-years MISO Tariff: Module E-1 - The

LOLE is expressed as hours per year with the usual target criteria being (0.1 days/year) or 1- day in 10-years MISO Tariff: Module E-1 - The 1 2 3 4 LOLE is expressed as hours per year with the usual target criteria being (0.1 days/year) or 1- day in 10-years MISO Tariff: Module E-1 - The Transmission Provider will calculate and post the Planning

More information

Southern California Edison Company SOUTHERN CALIFORNIA EDISON COMPANY WHOLESALE DISTRIBUTION ACCESS TARIFF

Southern California Edison Company SOUTHERN CALIFORNIA EDISON COMPANY WHOLESALE DISTRIBUTION ACCESS TARIFF SOUTHERN CALIFORNIA EDISON COMPANY WHOLESALE DISTRIBUTION ACCESS TARIFF Original Sheet No. TABLE OF CONTENTS. Applicability.... Definitions.... Nature of Distribution Service.... Term.... Distribution

More information

Central Hudson Gas & Electric Corporation Supplier Handbook For Customer Choice Retail Access Program

Central Hudson Gas & Electric Corporation Supplier Handbook For Customer Choice Retail Access Program Central Hudson Gas & Electric Corporation Supplier Handbook For Customer Choice Retail Access Program Central Hudson Gas & Electric Corporation 284 South Avenue Poughkeepsie, New York 12601 CHG&E Retail

More information

PLATTE RIVER POWER AUTHORITY OPEN ACCESS TRANSMISSION TARIFF. May 1, 2009

PLATTE RIVER POWER AUTHORITY OPEN ACCESS TRANSMISSION TARIFF. May 1, 2009 PLATTE RIVER POWER AUTHORITY OPEN ACCESS TRANSMISSION TARIFF May 1, 2009 Original Sheet No.1 TABLE OF CONTENTS I. COMMON SERVICE PROVISIONS... 8 1 Definitions... 8 1.1 Ancillary Services... 8 1.2 Annual

More information

ELECTRICITY SUPPLIER COORDINATION TARIFF IN THE DISTRICT OF COLUMBIA

ELECTRICITY SUPPLIER COORDINATION TARIFF IN THE DISTRICT OF COLUMBIA DC Electric Supplier--P.S.C. of D.C. No. 1 ELECTRICITY SUPPLIER COORDINATION TARIFF IN THE DISTRICT OF COLUMBIA Date of Issue: April 7, 2017 Date Effective: April 7, 2017 DC Electric Supplier--P.S.C. of

More information

Standard Development Timeline

Standard Development Timeline Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard is adopted by the NERC Board of Trustees (Board).

More information

SPP at a Glance. Located in Little Rock. Approximately 600 employees

SPP at a Glance. Located in Little Rock. Approximately 600 employees SPP at a Glance Located in Little Rock Approximately 600 employees Primary jobs electrical engineering, operations, settlements, and IT 24 x 7 operation Full redundancy and backup site 2 Regulatory Environment

More information

Statement of Compliance Registry Criteria (Revision 3.1)

Statement of Compliance Registry Criteria (Revision 3.1) Statement of Compliance Registry Criteria (Revision 3.1) Summary Since becoming the Electric Reliability Organization (ERO), NERC has initiated a program to identify candidate organizations for its compliance

More information

California Independent System Operator Corporation Fifth Replacement Tariff

California Independent System Operator Corporation Fifth Replacement Tariff Table of Contents Method to Assess Available Transfer Capability... 2 L.1 Description of Terms... 2 L.1.1 Available Transfer Capability (ATC)... 2 L.1.2 Total Transfer Capability (TTC)... 2 L.1.3 Existing

More information

Outage Types and Entering Tickets PJM State & Member Training Dept.

Outage Types and Entering Tickets PJM State & Member Training Dept. Outage Types and Entering Tickets PJM State & Member Training Dept. Objectives Students will be able to: Describe the outage reporting process and requirements 2 edart edart stands for Dispatcher Applications

More information

Operating Procedure PURPOSE... 1

Operating Procedure PURPOSE... 1 No. 5310 Table of Contents PURPOSE... 1 1. RESPONSIBILITIES... 1 2. SCOPE/APPLICABILITY... 2 2.1. Background... 2 2.2. Scope/ Applicability... 2 3. PROCEDURE DETAIL... 2 3.1. Reporting Requirements/...

More information

Technical Analysis of Operational Events and Market Impacts During the September 2013 Heat Wave

Technical Analysis of Operational Events and Market Impacts During the September 2013 Heat Wave During the September 2013 Heat Wave PJM Interconnection December 23, 2013 Contents 1 Executive Summary... 4 2 Introduction... 7 3 Load Shed Event Assessments... 11 3.1 Pigeon River 1 Load Shed Event (September

More information

Open Access Transmission Tariff ATTACHMENT K

Open Access Transmission Tariff ATTACHMENT K ATTACHMENT K PART I Introduction The Transmission Provider s (herein referred to as Tacoma Power) local transmission planning process will include open planning meetings that Tacoma Power will conduct

More information

Transmission Interconnection Requirements. Table of Contents

Transmission Interconnection Requirements. Table of Contents Transmission Interconnection Requirements Table of Contents I. Introduction II. Interconnection Agreement III. Facility Requirements IV. Interconnection Initiation I. Introduction A. Purpose and Scope

More information

Federal Energy Regulatory Commission Working Paper on Standardized Transmission Service and Wholesale Electric Market Design

Federal Energy Regulatory Commission Working Paper on Standardized Transmission Service and Wholesale Electric Market Design Federal Energy Regulatory Commission Working Paper on Standardized Transmission Service and Wholesale Electric Market Design To enhance competition in wholesale electric markets and broaden the benefits

More information

Issues in the Determination of Tariffs for Ancillary Services

Issues in the Determination of Tariffs for Ancillary Services Issues in the Determination of Tariffs for Ancillary Services Abstract: This paper will begin with a description of ancillary services and then go on to describe the types of ancillary services that are

More information

Generator Assessment & Roles During A Restoration

Generator Assessment & Roles During A Restoration Generator Assessment & Roles During A Restoration PJM State & Member Training Dept. PJM 2015 Objectives Students will be able to: Identify the process and requirements for operating during system restoration

More information

PJM TO/TOP Matrix of Shared or Assigned Tasks

PJM TO/TOP Matrix of Shared or Assigned Tasks PJM TO/TOP Matrix of hared or ssigned Tasks Revision 07 pproved by the TO/TOP Matrix ubcommittee: October 18, 2013 pproved by the Transmission Owners greement-dministrative Committee: November 27, 2013

More information

Con Ed/PSEG Wheel Replacement Proposal A joint white paper from the New York Independent System Operator and PJM Interconnection

Con Ed/PSEG Wheel Replacement Proposal A joint white paper from the New York Independent System Operator and PJM Interconnection Con Ed/PSEG Wheel Replacement Proposal A joint white paper from the New York Independent System Operator and PJM Interconnection DRAFT For Discussion Purposes Only V 4.0 December 19, 2016 Table of Contents

More information

Transmission and Dispatching Operations Manual. October 2017

Transmission and Dispatching Operations Manual. October 2017 MANUAL 12 Transmission and Dispatching Operations Manual October 2017 Version: 3.4 Effective Date: 10/09/2017 Committee Acceptance: BIC: 09/12/2017 OC: 09/15/2017 This document was prepared by: NYISO Energy

More information

Summary details for SPC TSR # and MH TSR # are shown in Tables ES.1 and ES.2: IFHS MH MW, firm :00:00 CS

Summary details for SPC TSR # and MH TSR # are shown in Tables ES.1 and ES.2: IFHS MH MW, firm :00:00 CS Executive Summary Firm point to point transmission service has been requested by Transmission Service Request (TSR) #80487374, under the SaskPower Open Access Transmission Tariff (OATT). The purpose of

More information

Summary details for SPC TSR # and MH TSR # are shown in Tables ES.1 and ES.2: Service Requested

Summary details for SPC TSR # and MH TSR # are shown in Tables ES.1 and ES.2: Service Requested Executive Summary Firm point to point transmission service has been requested by Transmission Service Request (TSR) #80439788, under the SaskPower Open Access Transmission Tariff (OATT). The purpose of

More information

California Independent System Operator Corporation Fifth Replacement Electronic Tariff

California Independent System Operator Corporation Fifth Replacement Electronic Tariff Table of Contents 34. Real-Time Market... 3 34.1 Inputs To The Real-Time Market... 3 34.1.1 Day-Ahead Market Results as Inputs to the Real-Time Market... 3 34.1.2 Market Model and System Information...

More information

ATTACHMENT K TRANSMISSION PLANNING PROCESS

ATTACHMENT K TRANSMISSION PLANNING PROCESS ATTACHMENT K TRANSMISSION PLANNING PROCESS 1.0 Introduction This Attachment K addresses the rights and obligations of Transmission Customers, relevant stakeholders and the Transmission Provider related

More information

effective date 1/8/01

effective date 1/8/01 25.211. Interconnection of On-Site Distributed Generation (DG). (a) (b) (c) Application. Unless the context clearly indicates otherwise, in this section and 25.212 of this title (relating to Technical

More information

Project : Generator Requirements at the Transmission Interface Background Resource Document

Project : Generator Requirements at the Transmission Interface Background Resource Document Project 2010-07: Generator Requirements at the Transmission Interface Background Resource Document Introduction The integrated grid consists of many parts such as power plants, Transmission, and Facilities

More information

2750 Monroe Blvd Audubon, PA

2750 Monroe Blvd Audubon, PA 2750 Monroe Blvd Audubon, PA 19403-2497 October 21, 2014 Mr. Jonathan Feipel Executive Director Illinois Commerce Commission 527 East Capitol Avenue Springfield, Illinois 62701 Dear Mr. Feipel: This report

More information

NYISO/PJM Market-to-Market Coordination

NYISO/PJM Market-to-Market Coordination NYISO/PJM Market-to-Market Coordination Joint Stakeholders Meeting July 21, 2011 / Rensselaer, NY Agenda Joint Operating Agreement (JOA) Overview Project Timeline & Progress Report Key Concepts Real-Time

More information

PJM Manual 18: PJM Capacity Market Revision: 38 Effective Date: July 27, Prepared by Capacity Market Operations

PJM Manual 18: PJM Capacity Market Revision: 38 Effective Date: July 27, Prepared by Capacity Market Operations PJM Manual 18: PJM Capacity Market Revision: 38 Effective Date: July 27, 2017 Prepared by Capacity Market Operations PJM 2017 Table of Contents Table of Contents Table of Exhibits...9 Approval...10 Current

More information

California Independent System Operator Corporation Fifth Replacement Electronic Tariff

California Independent System Operator Corporation Fifth Replacement Electronic Tariff Table of Contents Appendix N... 2 Pseudo-Tie Protocol... 2 1. Pseudo-Ties of Generating Units to the CAISO Balancing Authority Area... 2 1.1 Consistency with NERC/WECC Requirements... 2 1.2 CAISO Operating,

More information

PJM Manual 21: Rules and Procedures for Determination of Generating Capability Revision: 12 Effective Date: January 1, 2017

PJM Manual 21: Rules and Procedures for Determination of Generating Capability Revision: 12 Effective Date: January 1, 2017 PJM Manual 21: Rules and Procedures for Determination of Generating Capability Revision: 12 Effective Date: January 1, 2017 Prepared by System Planning Department PJM 2017 Table of Contents Table of Contents

More information

Outage Coordination Training MISO Training

Outage Coordination Training MISO Training MISO Last material update: 05/19/2015 Course Content and Disclaimer 2 1 2 3 4 Course Description This course will review MISO's outage study processes and the coordination opportunities with TOs and MPs.

More information

Section 3 Characteristics of Credits Types of units. Economic Noneconomic Generation.

Section 3 Characteristics of Credits Types of units. Economic Noneconomic Generation. Section 3 Operating Reserve Operating Reserve Day-ahead and real-time operating reserve credits are paid to market participants under specified conditions in order to ensure that resources are not required

More information

Business Practices for. Schedule 21-ES. (Modifications Issued on August 11, 2016)

Business Practices for. Schedule 21-ES. (Modifications Issued on August 11, 2016) (Modifications Issued on August 11, 2016) 1 List of Contents Introduction Purpose of Document Overview of Transmission Services in New England Definitions Applicable Schedules Services Applicable to these

More information

Updated Operating Parameter Definitions

Updated Operating Parameter Definitions Updated Operating Parameter Definitions Tom Hauske Senior Lead Engineer, Performance Compliance Market Implementation Committee February 10, 2016 Why are we discussing? A number of operating parameters

More information

Independent Transmission Organization. Stakeholder s Meeting December 2006

Independent Transmission Organization. Stakeholder s Meeting December 2006 SPP Presentation Independent Transmission Organization Stakeholder s Meeting December 2006 2 Introduction Participants Agenda Facilities 3 ITO Overview EON US (LG&E/KU) Overview EON US Tariff vs MISO Tariff

More information

Renewable Integration at ERCOT

Renewable Integration at ERCOT Renewable Integration at ERCOT Dan Woodfin Director of System Operations ERCOT CIGRE Chile September 12, 2016 The ERCOT Region The interconnected electrical system serving most of Texas, with limited external

More information

Schedule 9 and 10 PJM /23/2017

Schedule 9 and 10 PJM /23/2017 Schedule 9 and 10 PJM 2017 Schedule 9 PJM Scheduling, System Control and Dispatch Service How PJM pays its bills Unbundled Those who use the service, pay for it 6 categories plus FERC, NERC, RFC, OPSI,

More information

Primary Frequency Response Stakeholder Education Part 1 of 2

Primary Frequency Response Stakeholder Education Part 1 of 2 Primary Frequency Response Stakeholder Education Part 1 of 2 Primary Frequency Response Sr. Task Force September 1, 2017 Problem Statement / Issue Charge Summary Evaluate need for generator Primary Frequency

More information

Cost Development Guidelines

Cost Development Guidelines DRAFT Manual 15 Language Clean Version Approved by CDS on October 25, 2012 PJM Manual 15: Cost Development Guidelines Revision: 20 Effective Date: November 1, 2012 Prepared by Cost Development Subcommittee

More information

LEER/TLR 5 Drill Procedure General Coordination Procedures and Drill Scenario

LEER/TLR 5 Drill Procedure General Coordination Procedures and Drill Scenario LEER/TLR 5 Drill Procedure General Coordination Procedures and Drill Scenario General The participants of the Lake Erie Emergency Redispatch (LEER) procedure will perform drills of various scenarios of

More information

FRCC - PROC - RC - EOP-004. FRCC Disturbance Reporting Procedure

FRCC - PROC - RC - EOP-004. FRCC Disturbance Reporting Procedure FRCC - PROC - RC - EOP-004 FRCC Disturbance Reporting Procedure Revisions Rev. No. Date Description Developed by: Approved by: 1 September 2, 2009 Conversion of RRO Legacy document FRCC Disturbance Reporting

More information

TEMPORARY GRID RECONFIGURATIONS NET BENEFIT TEST METHODOLOGY

TEMPORARY GRID RECONFIGURATIONS NET BENEFIT TEST METHODOLOGY TEMPORARY GRID RECONFIGURATIONS NET BENEFIT TEST METHODOLOGY 1 1. Summary When one part of the grid is facing security of supply risk where local generation in one region of the grid is not enough for

More information