Failure Investigations on Electrical Motors and Transformers Dr Morris Lockwood Technical Manager, Power systems, ERA Technology Ltd

Size: px
Start display at page:

Download "Failure Investigations on Electrical Motors and Transformers Dr Morris Lockwood Technical Manager, Power systems, ERA Technology Ltd"

Transcription

1 Failure Investigations on Electrical Motors and Transformers Dr Morris Lockwood Technical Manager, Power systems, ERA Technology Ltd 1

2 Summary Intended audience What is a failure and the consequences of failure The time element : Early life failures Mid life failures End of life failures The evolution of arcing failures Investigating failures 2

3 Intended audience The talk is aimed at : Brokers Underwriters Claims personnel from Insurers I have been told that the audience will be particularly interested in the Energy sector and offshore equipment Most of the examples are land based but similar equipment is used offshore I have assumed that at least some of the audience are not familiar with the engineering aspects of electrical equipment The talk will contain a minimum of technical details. I will be happy to expand on any particular points you wish to raise 3

4 What is a failure and the consequences of failure In the context of this talk a failure is an equipment malfunction which may give rise to an insurance claim. The malfunction might be due to an inherent defect due to poor materials, design or workmanship, or due to wear and tear etc The consequences of the failure often far outweigh the value of the failed element. The talk will look at electrical failures with an emphasis on transformers and rotating machinery (motors and generators) An example of chiller motor problem. 4

5 Chiller motor problem- Part 1 Case history multiple Motor Soft Start failures. Used for starting 415V, 250 kw chiller motors in a prestige building complex in S.E. London. LOTS of failures about to become a legal dispute. Epidemiology indicated a problem with a newly redesigned electronics board opto-isolators were failing on over-voltage indicating voltages in excess of 1 kv 5

6 Chiller motor problem- Part 2 The chiller motors were refrigerant immersed. There had not been any change in design of the motor nor the refrigerant. Build-up of static charge was suspected. This was confirmed using a vane type electrostatic voltmeter. Detailed examination of the circuit diagrams for the old and new circuit boards revealed that 3 resistors which gave an earth reference had been omitted! 6

7 Chiller motor problem- Part 3 Conclusions All first failures should be investigated Two similar failures is almost a guarantee of further failures. Multiple failures can destroy business confidence. 7

8 The time element Early life failures: Manufacturing failures non-eu manufactured transformers examples. Materials defects East European steel example. Design failures hospital generator example. Commissioning failures Dutch CT example System issues Emirates transformer example Mid life failures fewer but still important : Manufacturing failures Voltage transformer examples. End of life failures: Long term degradation transformer insulation aging etc. Motors and generators end winding failure due to multiple starts / load transients 8

9 Early life failure transformer example Manufacture of transformers relocated to Turkey and other countries ABB, Alstom, Siemens have all done this The result is a very high rate of failure. 9

10 Mid life failure 27.5 kv voltage transformer example Manufacturing defect allowed moisture to enter bushing led to very explosive failure 10

11 Mid life failure 27.5 kv voltage transformer example - continued 11

12 End of life failure overheated reactor 12

13 End of life failure overheated reactor site of arcing 13

14 Offshore example Angola sunrise FPSO 14

15 Emergency Power battery room fire Large array of NiCad cells. Each a metal can in a plastic pouch. One leak detectable and not a major problem. Two leaks creates a short circuit and fire. The monitor alarms were ignored TWICE two fires! 15

16 Arcing failures Most power electrical failures result in arcing Arcs are lightweight tubes of incandescent atoms. Very high currents can flow. Currents produce magnetic fields A current in a magnetic filed produces a force Arc forces are proportional to the square of current Therefore the direction of force is independent from the polarity of the current flow. The forces are always away from the energy source. 16

17 Arcing along switch panel busbars 17

18 Arcing along switch panel busbars - continued 18

19 Arcing along switch panel busbars - continued 19

20 Investigating failures preservation of evidence Most companies do not have procedures in place to handle failures. Critical evidence can be lost. Suppliers or manufacturers have a vested interest and should not be allowed near the failed equipment unaccompanied. 20

21 Investigating failures preservation of evidence 21

22 Investigating failures preservation of evidence 22

23 Investigating failures preservation of evidence Witness statements, both written and verbal can be critical. Cultural differences can make things difficult in overseas investigations. Loss adjusters should prevent disturbance of the failure site as much as practical. An example : 23

24 Case History Failed super-grid transformer 24

25 Case History Failed super-grid transformer 25

26 Bailing out! 26

27 Bailing out! 27

28 Bailing out! 28

29 Investigating failures The process Before looking at any physical evidence get a clear briefing on the circumstances leading up to the failure. In particular, had there been any changes or odd things happening? Look for evidence from protective devices in the system. Look at the failure without preconceptions. Get a feel for the equipment structure and power flows. Identify hypothetical failure mechanisms. Look for confirmatory evidence. REPORTING! 29

30 Partial discharge tracking trees and worm holes - Part 1 Electrical stress in mixed dielectric systems is in the inverse ratio of the relative permittivities The relative permittivity of air is 1 The relative permittivity of insulation is of the order of 5 Therefore voids in insulation material concentrate stress If the dielectric strength of the void is exceeded, there is a tiny spark a partial discharge 30

31 Partial discharge tracking trees and worm holes - Part 2 The partial discharge relieves the excess stress but carbonises the material near the void. This tends to add to the stress concentration and the process repeats. The carbonisation grows in trees and wormholes until a catastrophic failure occurs. 31

32 Partial discharge tracking trees and worm holes - Example 32

33 Contacts Hot stuff Electrical contacts depend on plastic deformation of the contact materials. Actual conduction area is tiny. Pressure is required to penetrate the surface contamination oxides, sulphates etc. Lack of pressure or excessive contamination lead to small area of contact followed by over-heating, oxidation, relaxation, arcing and failure. See example. 33

34 Contacts Example Hydrogen Sulphide contamination 34

35 Contacts Example Hydrogen Sulphide contamination 35

36 Blowing in the wind a case of poor house keeping. A prestigious bank had dual redundant UPS back-to-back. The UPS company were carrying out a routine maintenance check. The technician opened the door to one of the two UPS. The other UPS suffered a serious arcing failure. The two UPS shared a common under-cabinet void. Inspection of the void revealed : Cleanliness is next to godliness 36

37 Foreign bodies Washers Metal foil Tape Swarf Plastic fitments and steel nuts and washers 37

38 The smoking gun 38

39 Blowing in the wind a case of poor house keeping - continued. Around a quarter of failures in electrical equipment are due to foreign bodies or other visually obvious causes like water ingress, chemical contamination, biological contamination. Cleanliness is next to godliness 39

40 Evolution of a transformer failure photograph taken some time after the explosion (or whoosh) 40

41 Evolution of a transformer failure This was a 140 kva, 33 kv to 400 V three phase oil-filled transformer. The manufacturers had had a series of failures mainly associated with poor quality high voltage windings. The fault was so severe the tank was split along two edge seams. The reaction force of the expelled oil moved the unit about 0.5 metre. 41

42 Evolution of a transformer failure Current traces I A I B

43 The time element Early life failures: Manufacturing failures non-eu manufactured transformers examples. Materials defects East European steel example. Design failures hospital generator example. Commissioning failures Dutch CT example System issues Emirates transformer example Mid life failures fewer but still important : Manufacturing failures Voltage transformer examples. End of life failures: Long term degradation transformer insulation aging etc. Motors and generators end winding failure due to multiple starts / load transients 43

Friday, May 29, Update on Testing Medium Voltage Cable and Switchgear Systems

Friday, May 29, Update on Testing Medium Voltage Cable and Switchgear Systems Update on Testing Medium Voltage Cable and Switchgear Systems Friday, May 29, 2015 Presented by: Ashley Harkness Ashley.Harkness@Emerson.com Electrical Reliability Services Value--- When we find the one

More information

TOGA Electrical Insulating Fluid Analysis. Improving performance and protecting assets.

TOGA Electrical Insulating Fluid Analysis. Improving performance and protecting assets. TOGA Electrical Insulating Fluid Analysis Improving performance and protecting assets. It happens all the time - transformers fail unexpectedly, and there are often no external visual clues on what caused

More information

Enhance Power Equipment Reliability with Predictive Maintenance Technologies

Enhance Power Equipment Reliability with Predictive Maintenance Technologies Enhance Power Equipment Reliability with Predictive Maintenance Technologies November 2012/1910DB1208 by S. Frank Waterer, Electrical Engineerinig, Fellow Schneider Electric USA, Inc. Make the most of

More information

Power Transformers. Dissolved Gas Analysis Siemens Energy, Inc. All Rights Reserved

Power Transformers. Dissolved Gas Analysis Siemens Energy, Inc. All Rights Reserved Power Transformers Dissolved Gas Analysis 2008 Siemens Energy, Inc. All Rights Reserved Application ü DGA allows to detect the presence and severity of faults: Air leaks Hot metal faults Arcing and partial

More information

TOGA PRESENTATION REVIEW OF CASE STUDIES. Paul Boman,

TOGA PRESENTATION REVIEW OF CASE STUDIES. Paul Boman, TOGA PRESENTATION REVIEW OF CASE STUDIES Paul Boman, paul_boman@hsb.com October 8, 2014 HSB s TOGA History TOGA Transformer Oil Gas Analyst Registered trademark of Hartford Steam Boiler Inspection and

More information

Featured Product. Transformer Monitoring and Diagnostic Systems

Featured Product. Transformer Monitoring and Diagnostic Systems Featured Product Transformer Monitoring and Diagnostic Systems Transformer Predictive Analysis Owners of critical transformer equipment can realize the benefits of predictive analysis on transformer health

More information

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH SPECIFICATIONS FOR LOAD BREAK SWITCH This specification is property of SEC and subject to change or modification without any notice TABLE OF CONTENTS 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE CODES

More information

Main Steam & T/G Systems, Safety

Main Steam & T/G Systems, Safety Main Steam & T/G Systems, Safety Page 1 This steam generator, built for the Wolsong station in Korea, was manufactured in Canada by the Babcock and Wilcox company. In Wolsong 2,3, and 4 a joint venture

More information

Carry out routine inspection and service on high voltage indoor metal clad circuit breakers and bus

Carry out routine inspection and service on high voltage indoor metal clad circuit breakers and bus Page 1 of 7 Carry out routine inspection and service on high voltage indoor metal clad circuit breakers and bus Level 4 Credits 4 Purpose People credited with this unit standard are able to: prepare for

More information

Electrostatic Discharge in Hydraulic and Lubrication Systems

Electrostatic Discharge in Hydraulic and Lubrication Systems HYDRAULIC AND LUBE FILTRATION Electrostatic Discharge in Hydraulic and Lubrication Systems May 23, 2018 Ralf Haller Industrial Training / Northeast 1 Remember, ESD is only one potential source of varnish

More information

Nuclear Service One Standard For Safety, Quality and Repair

Nuclear Service One Standard For Safety, Quality and Repair Nuclear Service One Standard For Safety, Quality and Repair INTEGRATED POWER SERVICES IPS NUCLEAR SERVICE RELIABILITY. DELIVERED. Nuclear Service Coast to Coast One Service Standard for Safety, Quality

More information

Instruction Manual Pocket scale

Instruction Manual Pocket scale KERN & Sohn GmbH Ziegelei 1 D-72336 Balingen email: info@kern-sohn.com Tel: +49-[0]7433-9933-0 Fax: +49-[0]7433-9933-149 Internet: www.kern-sohn.com Instruction Manual Pocket scale KERN TAB Version 1.1

More information

Alvin.Xu, ABB Xiamen Switchgear Co,Ltd, Green & Energy saving concept of ABB MV apparatus For a better tomorrow.

Alvin.Xu, ABB Xiamen Switchgear Co,Ltd, Green & Energy saving concept of ABB MV apparatus For a better tomorrow. Alvin.Xu, ABB Xiamen Switchgear Co,Ltd, 2014-11 Green & Energy saving concept of ABB MV apparatus For a better tomorrow Slide 1 VD4 vacuum circuit-breaker in China Inheritance and innovation Y1992 Y2003

More information

ELECTRICITY SUPPLY - POWER SYSTEM MAINTENANCE Carry out routine inspection and servicing on high voltage minimum oil circuit breakers

ELECTRICITY SUPPLY - POWER SYSTEM MAINTENANCE Carry out routine inspection and servicing on high voltage minimum oil circuit breakers 1 of 9 level: 4 credit: 6 planned review date: December 2006 sub-field: purpose: entry information: Electricity Supply People credited with this unit standard are able to: prepare for inspection, testing

More information

Components, Systems and Service for Transformers.

Components, Systems and Service for Transformers. Components, Systems and Service for Transformers. HYDAC Headquarters in Germany HYDAC China Your Professional Partner for the Optimization of Transformers. With over 5,500 employees worldwide HYDAC is

More information

2010 Culver Media, LLC 1

2010 Culver Media, LLC 1 Alternating current Also known as AC power, alternating current is electricity that reverses direction within a circuit. The electricity we use in our homes does this 120 times per second. Appliances Devices

More information

APDRP SCHEME, WESCO. Technical Specification for 33KV Air Break Switch PART 1: SCOPE AND CONDITIONS

APDRP SCHEME, WESCO. Technical Specification for 33KV Air Break Switch PART 1: SCOPE AND CONDITIONS PART 1: SCOPE AND CONDITIONS 1. SCOPE This specification covers the design, engineering, manufacture, testing, supply, delivery, off-loading and performance requirements of 33kV, 200 amp, triple pole Gang

More information

AUTOMATIC CAPACITOR BANK FOR LOW VOLTAGE NETWORKS INSTRUCTION MANUAL. MIBATBT_05i

AUTOMATIC CAPACITOR BANK FOR LOW VOLTAGE NETWORKS INSTRUCTION MANUAL. MIBATBT_05i AUTOMATIC CAPACITOR BANK FOR LOW VOLTAGE NETWORKS INSTRUCTION MANUAL MIBATBT_05i COMMISSIONING AND OPERATION MANUAL FOR LOW VOLTAGE AUTOMATIC CAPACITOR BANKS 1. DESCRIPTION The automatic capacitor banks

More information

WESTERN CONNECTICUT STATE UNIVERSITY ELECTRICAL SAFETY PROCEDURE S-109

WESTERN CONNECTICUT STATE UNIVERSITY ELECTRICAL SAFETY PROCEDURE S-109 WESTERN CONNECTICUT STATE UNIVERSITY ELECTRICAL SAFETY PROCEDURE S-109 Draft Issued 12/10/97 Revised 2/98, 7/09, 10/14 Please direct any questions or comments about the applicability of this document to

More information

POWER PINNER BENCH HAND WELDER 7250 OPERATOR S MANUAL

POWER PINNER BENCH HAND WELDER 7250 OPERATOR S MANUAL POWER PINNER BENCH HAND WELDER 7250 OPERATOR S MANUAL Copyright: November 20, 2018 Revised: Serial No. Gripnail Corporation An Employee Owned Company 97 Dexter Road East Providence, Rhode Island 02914-2045

More information

Diagnostic Techniques of Composite Insulators

Diagnostic Techniques of Composite Insulators Diagnostic Techniques of Composite Insulators to learn more - join CITI Those which are considered low cost turn into pricy. This statement applies to various aspects but in particular to power lines NCI

More information

ELA-6, ELA -30V, ELA -60V, ELA -120 ELECTRON-BEAM WELDING EQUIPMENT

ELA-6, ELA -30V, ELA -60V, ELA -120 ELECTRON-BEAM WELDING EQUIPMENT ELECTRON- BEAM WELDING IN VACUUM ELA-6, ELA -30V, ELA -60V, ELA -120 ELECTRON-BEAM WELDING EQUIPMENT Single pass welding of metals and of different thickness from 0,1 up to 400 mm in vacuum. ELECTRON-BEAM

More information

Carry out routine inspection and servicing on high voltage bulk oil circuit breakers

Carry out routine inspection and servicing on high voltage bulk oil circuit breakers Page 1 of 6 Carry out routine inspection and servicing on high voltage bulk oil circuit breakers Level 4 Credits 6 Purpose People credited with this unit standard are able to: prepare for inspection, testing

More information

WE01A GMA (MIG) Plug Weld

WE01A GMA (MIG) Plug Weld Uniform Procedures For Collision Repair WE01A GMA (MIG) Plug Weld 1. Description This procedure describes methods for making and evaluating gas metal arc (GMA) plug welds (MIG plug welds) on all types

More information

OPERATION MANUAL. A220 Arc Welding Machine. Serial Number: Where Purchase: Date of purchased:

OPERATION MANUAL. A220 Arc Welding Machine. Serial Number: Where Purchase: Date of purchased: OPERATION MANUAL A220 Arc Welding Machine Serial Number: Where Purchase: Date of purchased: CONTENT 1.Safety... 2 2. Summary... 4 3. Electrical principle drawing... 5 4. Specifications... 6 5. Operation

More information

Preventing transformer explosions

Preventing transformer explosions Published on ScienceNordic (http://sciencenordic.com) Home > Printer-friendly PDF > Printer-friendly PDF Preventing transformer explosions Technology[1] Technology[1]electricity [2]Material technology

More information

ELECTRICAL SYSTEMS. TEST YOURSELF QUESTIONS: Answer Key. CHAPTER 1: Sustainability in Electrical Systems

ELECTRICAL SYSTEMS. TEST YOURSELF QUESTIONS: Answer Key. CHAPTER 1: Sustainability in Electrical Systems ELECTRICAL SYSTEMS TEST YOURSELF QUESTIONS: Answer Key CHAPTER 1: Sustainability in Electrical Systems 1. What are the benefits of sustainability in green building design? The benefits of sustainability

More information

PROGRESS IN PAPER DEGRADATION ASSESSMENT IN SERVICE-AGED TRANSFORMERS

PROGRESS IN PAPER DEGRADATION ASSESSMENT IN SERVICE-AGED TRANSFORMERS PROGRESS IN PAPER DEGRADATION ASSESSMENT IN SERVICE-AGED TRANSFORMERS H. Ding, R. Heywood, J. Lapworth, S. Ryder and A. Wilson Presenter: Dr Hongzhi Ding Doble PowerTest Ltd UK INSUCON - 17 th May 2017

More information

Magnets. Physical Processes Gr7

Magnets. Physical Processes Gr7 Name: Class: Date: Grade 7 Science Related Reading/Physical Processes Magnets Physical Processes Gr7 Magnets are made from magnetic materials. These are metals that can be magnetised or will be attracted

More information

Medium Voltage UPS Solutions - When and Why? Frank Herbener, Piller Group GmbH, Germany

Medium Voltage UPS Solutions - When and Why? Frank Herbener, Piller Group GmbH, Germany Medium Voltage UPS Solutions - When and Why? Frank Herbener, Piller Group GmbH, Frank.Herbener@Piller.com, Germany 1 Contents 1 Scope 3 2 Power Demand and Distribution in today s Mission Critical Applications

More information

ELECTRICAL EQUIPMENT IN HAZARDOUS AREAS (EEHA) MAINTENANCE STANDARD

ELECTRICAL EQUIPMENT IN HAZARDOUS AREAS (EEHA) MAINTENANCE STANDARD Planning and Capability Group Mechanical and Electrical Services ELECTRICAL EQUIPMENT IN HAZARDOUS AREAS (EEHA) Document No.: VERSION 1 REVISION 3 AUGUST 2014 FOREWORD Electrical Equipment in Hazardous

More information

PI Electrical Equipment - tourse PI 30.2 INSULATION. On completion of this module the student will be able to:

PI Electrical Equipment - tourse PI 30.2 INSULATION. On completion of this module the student will be able to: Electrical Equipment - tourse PI 30.2 INSULATION OB~ECTIYES On completion of this module the student will be able to: 1. Explain. in writing, the term "leakage current" and indicate the normal range of

More information

Accreditation Scope by Certification Test Order

Accreditation Scope by Certification Test Order Organization NEMA MW 1000 NEMA RE-2 Section 4.11 ASTM D149 ASTM D150 ASTM D256 ASTM D257 ASTM D495 ASTM D570 ASTM D635 ASTM D638 ASTM D790 ASTM D882 ASTM D1653 ASTM D1676 ASTM D1822 ASTM D1830 ASTM D1876

More information

Interpreting long-term insulation resistance trends. Megger is a registered trademark

Interpreting long-term insulation resistance trends. Megger is a registered trademark WWW.MEGGER.COM Interpreting long-term insulation trends Megger is a registered trademark Title Author Interpreting long-term insulation trends Paul Swinerd Date July 2011 Keywords Abstract Guard terminal,

More information

SECTION SUBSTATION BUS ASSEMBLIES ERGLE SUBSTATION

SECTION SUBSTATION BUS ASSEMBLIES ERGLE SUBSTATION SECTION 16-372 SUBSTATION BUS ASSEMBLIES ERGLE SUBSTATION 1. GENERAL SPECIFICATIONS The work of this Section includes furnishing all labor, equipment, materials (unless specifically identified as Owner-furnished)

More information

COMPARISON OF WELDING/BONDING METHODS

COMPARISON OF WELDING/BONDING METHODS TYPE OF WELDING/BONDING Adhesive Bonding Diffusion Welding Electron Beam Welding Explosive Welding SUMMARY ADVANTAGES DISADVANTAGES Bond is established through use of an intermediate adhesive layer applied

More information

Installation and Operation Manual

Installation and Operation Manual Installation and Operation Manual Solarion M210T General Information This document contains important information for the installation of Solarion M210T solar modules from OC3 AG. Please read this document

More information

KRIWAN Wind Sensors. Operating Instructions Accessories and Application Information

KRIWAN Wind Sensors. Operating Instructions Accessories and Application Information KRIWAN Wind Sensors Operating Instructions Accessories and Application Information Contents Contents General information... 4 Manufacturer...4 Storage information...4 Supplementary documents...4 List of

More information

15 O&M Issues in Solar Farms

15 O&M Issues in Solar Farms 15 O&M Issues in Solar Farms Perimeter Fence Damage Damage caused to the perimeter fence can immediately have a negative effect on facility operations. Whether the damage was due to vandals, a storm or

More information

Today s over-all economic situation and air-conditioning market in Japan

Today s over-all economic situation and air-conditioning market in Japan Technology and Market Trend of GHP in Japan K.Yamaguchi Gas air-conditioning sales promotion center Japan Gas Association Tokyo, Japan Phone; +81 3 352 115, Fax: +81 3 3593 1312 Abstract The energy consumption,

More information

OVERALL EXTERNAL SERVICES COSTS

OVERALL EXTERNAL SERVICES COSTS EB-00-0 Exhibit C Page of OVERALL EXTERNAL SERVICES COSTS 0 INTRODUCTION THESL uses external services to complement its internal capacity to execute work programs. External services comprise those services

More information

MANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS

MANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS DAIMLERCHRYSLER MANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS ISSUE DATE: 5/1/90 EFFECTIVE DATE: 2/4/92 REVIEW DATE:

More information

Project Name: - Caithness House Copenhagen Street, Islington, N1 0JB Project Reference: - B ROOF SURVEY REPORT

Project Name: - Caithness House Copenhagen Street, Islington, N1 0JB Project Reference: - B ROOF SURVEY REPORT Client: - James Tindall Partner james@guardiansurveyors.co.uk mobile: 07584 495880 Guardian Surveyors 619 Holloway Road, London N19 5SS Tel: 020 7561 0189 Date of Survey: The following report is based

More information

CAT INTEGRATED SYSTEMS. Electric Power continuous power solutions

CAT INTEGRATED SYSTEMS. Electric Power continuous power solutions CAT INTEGRATED SYSTEMS Electric Power continuous power solutions CATERPILLAR: YOUR SINGLE SOURCE FOR CLEAN, CONTINUOUS POWER With a Cat continuous power solution, you can protect your critical operations

More information

VALLIAMMAI ENGINEERING COLLEGE DEPARTMENT OF MECHANICAL ENGINEERING ME 6302 MANUFACTURING TECHNOLOGY 1 (QUESTION BANK) I-METAL CASTING PROCESSES PART-A (2 MARKS) 1.Name any four types of commonly used

More information

OVERALL EXTERNAL SERVICES COSTS

OVERALL EXTERNAL SERVICES COSTS EB-00-0 Exhibit C Page of OVERALL EXTERNAL SERVICES COSTS 0 INTRODUCTION THESL uses external services to complement its internal capacity to execute work programs. External services comprise those services

More information

Detailed Requirements Document (DRD) Rail Engineering Advanced Technician Level 4 Electrification Knowledge & Skills Content

Detailed Requirements Document (DRD) Rail Engineering Advanced Technician Level 4 Electrification Knowledge & Skills Content Detailed Requirements Document (DRD) Rail Engineering Advanced Technician Level 4 Electrification Knowledge & Skills Content Purpose The purpose of this Detailed Requirements Document (DRD) is to provide

More information

REED SWITCH PROBE (RSP) FOR USE WITH GEOSENSE GEO-XM MAGNETIC EXTENSOMETER SYSTEMS

REED SWITCH PROBE (RSP) FOR USE WITH GEOSENSE GEO-XM MAGNETIC EXTENSOMETER SYSTEMS REED SWITCH PROBE (RSP) FOR USE WITH GEOSENSE GEO-XM MAGNETIC EXTENSOMETER SYSTEMS I N S T R U C T I O N M A N U A L 2 CONTENTS PAGE 1.0 INTRODUCTION 1.1 General description 4 1.2 Theory of operation 5

More information

Model # PR /21/2018 Page 1 of 10

Model # PR /21/2018 Page 1 of 10 Model # PR-32 11/21/2018 Page 1 of 10 1/21/2018 Page 2 of 10 1675 Locust Street Red Bud, IL 62278 Phone: 618-282-8200 Fax: 618-282-8202 WARRANTY & TERMS WARRANTY: 5 Year Limited Warranty on Thermoplastic

More information

Electrical Principles and Technologies Unit D

Electrical Principles and Technologies Unit D Electrical Principles and Technologies Topic 1 Topic 2 Topic 3 Topic 4 Topic 5 Topic 6 Topic 7 Topic 8 Electric Charges Producing Charges Making Sense of Electrical Charges Conductors, Insulators, and

More information

SECTION SECONDARY UNIT SUBSTATIONS

SECTION SECONDARY UNIT SUBSTATIONS SECTION 26 12 16 SECONDARY UNIT SUBSTATIONS PART 1 GENERAL 1.1 SUMMARY This section describes metal-clad, indoor or outdoor, secondary unit substations with integral primary fused disconnect switches,

More information

USN. Hosur : 6A/6B/6C 10ME665. Discuss briefly. 1 a.

USN. Hosur : 6A/6B/6C 10ME665. Discuss briefly. 1 a. USN 1 P E PESIT Bangalore South Campus Hosur road, 1km before Electronic City, Bengaluru -100 Department of Mechanical Engineering INTERNAL ASSESSMENT TEST 3 Solutions Subject & Code : NTM 10ME665 Name

More information

Standard Grade Physics

Standard Grade Physics Standard Grade Physics Name: Vale of Leven Academy Physics Department UNIT 6 ENERGY MATTERS PUPIL PACK Study Guides Summary Notes Homework Sheets Number : Working at Home TO THE PUPIL Each day you have

More information

SUMMARY OF PRICES FOR 30MVA 161/24/36 kv MOBILE SUBSTATION ACCORDING to SR-152

SUMMARY OF PRICES FOR 30MVA 161/24/36 kv MOBILE SUBSTATION ACCORDING to SR-152 Israel Electric Corporation Ltd. Tender no. Name of Contractor: SUMMARY OF PRICES FOR 30MVA 161/24/36 kv MOBILE SUBSTATION ACCORDING to SR-152 1. GENERAL INSTRUCTIONS 2.1. Prices for the above captioned

More information

31-SDMS-03 REV. 01 SPECIFICATIONS FOR

31-SDMS-03 REV. 01 SPECIFICATIONS FOR 31-SDMS-03 REV. 01 SPECIFICATIONS FOR LOW VOLTAGE CABINET FOR POLE MOUNTED TRANSFORMER This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Description

More information

SUGGESTED SPECIFICATION for Low Voltage (600V) Generator Paralleling Switchboard

SUGGESTED SPECIFICATION for Low Voltage (600V) Generator Paralleling Switchboard SUGGESTED SPECIFICATION for Low Voltage (600V) Generator Paralleling Switchboard PART 1 GENERAL 1.1 Scope A. The intent of this specification is to provide power control for the parallel operation of generator

More information

Example of Information for EOL Projects. American Municipal Power October 19, 2017

Example of Information for EOL Projects. American Municipal Power October 19, 2017 Example of Information for EOL Projects American Municipal Power October 19, 2017 Baseline Project: Description of Project Add detailed map for all facilities mentioned for Problem Statement: PJM/NERC/TO

More information

OPERATION MANUAL HARVEST OPAL

OPERATION MANUAL HARVEST OPAL ALL PUMPS SUPPLIED BY HARVEST HEALTHCARE COMPLY TO THE FOLLOWING STANDARDS LISTED BELOW BS 5724 PART 1 IEC 601-1 HARVEST HEALTHCARE BRADMARSH BUSSINESS PARK BRADMARSH WAY ROTHERHAM SOUTH YORKSHIRE ENGLAND

More information

BAGFAS PORT MAINTENANCE WORKS PROCEDURE 1. OBJECTIVE

BAGFAS PORT MAINTENANCE WORKS PROCEDURE 1. OBJECTIVE 1. OBJECTIVE BAGFAS PORT MAINTENANCE WORKS PROCEDURE To keep the company operation in business, to ensure that the machinery and equipment can work properly to prevent damage to property, life and environment

More information

Coating Thickness Gauge Model: AX-CTG10 User s Manual

Coating Thickness Gauge Model: AX-CTG10 User s Manual Coating Thickness Gauge Model: AX-CTG10 User s Manual Coating Thickness Gauge Model:AX-CTG10 Introduction AX-CTG10 coating thickness gauge adapts principles of electromagnetic induction and magnetic induced

More information

i. Supplier may visit to the site and get familiarized with the exact requirements

i. Supplier may visit to the site and get familiarized with the exact requirements 2. Design, Fabrication, Supply, Installation, Commissioning, Warranty of Control Panel for 5 Te Outdoor Semi Gantry Crane in adherence to attached specifications, dismantling & removal of the existing

More information

How to choose the right UPS service approach

How to choose the right UPS service approach White Paper Markets Served Data center & IT By Arthur Mulligan Product Line Manager, Eaton U.S. Power Quality How to choose the right UPS service approach Introduction The old adage of, If it ain t broke,

More information

Strathaven Academy Physics Department

Strathaven Academy Physics Department Number : Standard Grade Physics Name: Strathaven Academy Physics Department UNIT 6 ENERGY MATTERS PUPIL PACK Study Guides Summary Notes Homework Sheets Working at Home TO THE PUPIL Each day you have physics

More information

Pre-Insulated Busbars

Pre-Insulated Busbars Pre-Insulated Busbars PIB 2013 Contents Introduction 2 Reasons for Insulation 2 Insulation Methods 2 Standards and Compliance 3 Thermal Effect of Insulation 3 Colours 3 Powder Coating Data 3 Fabrication

More information

What to Look for in a Good Quality Arrester

What to Look for in a Good Quality Arrester All good quality arresters have much in common. This first in a series of articles, sponsored by NEMA Surge Arrester Section members, covers what to look for in that quality arrester. Introduction We've

More information

SERIES 800 / 810 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTER ASSEMBLIES

SERIES 800 / 810 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTER ASSEMBLIES SERIES 800 / 810 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTER ASSEMBLIES MANUALLY OPERATED / REMOTELY OPERATED DEAD FRONT PADMOUNTED SWITCHGEAR WITH VACUUM LOAD INTERRUPTING

More information

ABSORPTION HYBRID FILTER FAR-Q TYPE

ABSORPTION HYBRID FILTER FAR-Q TYPE ABSORPTION HYBRID FILTER FAR-Q TYPE USER MANUAL Code M98206701-03-07A ------ Absorption filter ------ User Manual, M98206701-03-07A ------ Page 1 of 11------ CONTENTS 1.- BASIC INSTRUCTIONS... 2 1.1.-

More information

Pomona, CA May 24 25, 2016

Pomona, CA May 24 25, 2016 Pomona, CA May 24 25, 2016 Transformer Technology Seminar Modular approach on economic condition assessment for power transformer; data management, Fleet screening and risk ranking Siemens AG 2014 All

More information

Cutlass Fasteners, Inc. 83 Vermont Ave., Unit 6, Warwick, RI Tel: (401) Fax: (401) cutlass-studwelding.com

Cutlass Fasteners, Inc. 83 Vermont Ave., Unit 6, Warwick, RI Tel: (401) Fax: (401) cutlass-studwelding.com MODEL : A-58 ARC WELD GUN PART NO. : 602-378A SERIAL NO. : PLEASE READ THIS OPERATION AND MAINTENANCE MANUAL CAREFULLY BEFORE USING YOUR NEW CUTLASS STUD WELDER. COPYRIGHT CFI 2009 email: sales@ PAGE -

More information

S. C. Electric Cooperative s Specification for a Single-Phase, Two Bushing Overhead Distribution Transformer (Revised 10/2013)

S. C. Electric Cooperative s Specification for a Single-Phase, Two Bushing Overhead Distribution Transformer (Revised 10/2013) S. C. Electric Cooperative s Specification for a Single-Phase, Two Bushing Overhead Distribution Transformer (Revised 10/2013) 1.0 GENERAL 1.1 This specification covers the electrical and mechanical characteristics

More information

B. Provide liquid-filled secondary substation transformers as indicated on drawings.

B. Provide liquid-filled secondary substation transformers as indicated on drawings. SECTION 26 12 13 PART 1 - GENERAL 1.01 WORK INCLUDED A. Comply with the provisions of Sections 26 05 00. B. Provide liquid-filled secondary substation transformers as indicated on drawings. 1.02 RELATED

More information

TECH TIPS. Booms/Scissors. Service Call: Platform repair instructions of steel guard rails on Terex/Genie Aerial Work Platforms and Scissors

TECH TIPS. Booms/Scissors. Service Call: Platform repair instructions of steel guard rails on Terex/Genie Aerial Work Platforms and Scissors TECH TIPS Service Call: Platform repair instructions of steel guard rails on Terex/Genie Aerial Work Platforms and Scissors Tools Needed: See attached document for required tools Model: Booms/Scissors

More information

Smart Grid Monitoring of Transformers by DGA. Michel Duval. CIGRE Thailand, Bangkok 2013

Smart Grid Monitoring of Transformers by DGA. Michel Duval. CIGRE Thailand, Bangkok 2013 Smart Grid Monitoring of Transformers by DGA Michel Duval CIGRE Thailand, Bangkok 2013 1 Electric Power 2 Power Transformers 3 Catastrophic Failures 4 Failures in Service - The failure rate of power transformers

More information

Quick-Start Operating Guide Document No Process Gas Cooler Copyright 2010 Terra Universal Inc. All rights reserved. Revised October 2010

Quick-Start Operating Guide Document No Process Gas Cooler Copyright 2010 Terra Universal Inc. All rights reserved. Revised October 2010 Document No. 1800-56 Copyright 2010 Terra Universal Inc. All rights reserved. Revised October 2010 Terra Universal, Inc. TerraUniversal.com 800 S. Raymond Ave. Fullerton, CA 92831 TEL: (714) 578-6000 FAX:

More information

Small and Lightweight Reactor for Boost Converter

Small and Lightweight Reactor for Boost Converter FEATURED TOPIC Small and Lightweight Reactor for Boost Converter Shinichiro YAMAMOTO*, Kazushi KUSAWAKE, Junji IDO, Hajime KAWAGUCHI, Atsushi ITO and Masayuki KATO The number of motorized vehicles, such

More information

VHSR-SERIES RACKS FOR SHEET MATERIAL

VHSR-SERIES RACKS FOR SHEET MATERIAL VESTIL MANUFACTURING CORP. 2999 North Wayne Street, P.O. Box 507, Angola, IN 46703 Telephone: (260) 665-7586 -or- Toll Free (800) 348-0868 Fax: (260) 665-1339 www.vestilmfg.com e-mail: sales@vestil.com

More information

ELECTRICAL SAFETY Information Bulletin

ELECTRICAL SAFETY Information Bulletin ELECTRICAL SAFETY Information Bulletin February 2019 Page 1 of 8 2018 CANADIAN ELECTRICAL CODE SUBJECT: Section 10 Grounding and bonding Rule 10-102 Grounding electrodes Replacing metal water service lines

More information

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0 REVISION NO. 0 NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0 PAGE NO. 1 OF 24 DATE OF ISSUE (MONTH/YEAR) TOTAL NO. OF PAGES (Including cover

More information

Recent Technical Trends of Vacuum Circuit-Breakers (VCBs)

Recent Technical Trends of Vacuum Circuit-Breakers (VCBs) Switchgear Technical Trends and Basic Technologies Recent Technical Trends of Vacuum Circuit-Breakers (VCBs) Hitoshi Saito, Makoto Honma, Masayuki Sakaki Keywords Circuit-breaker, Switchgear, Vacuum interrupter,

More information

INTEGRATED SUBSTATION CONTROL SYSTEM WITH EQUIPMENT MONITORING AND DIAGNOSTICS

INTEGRATED SUBSTATION CONTROL SYSTEM WITH EQUIPMENT MONITORING AND DIAGNOSTICS INTEGRATED SUBSTATION CONTROL SYSTEM WITH EQUIPMENT MONITORING AND DIAGNOSTICS K. Caird W.J. Ros GE Harris Energy Control Systems GE Power Systems Energy Consulting Calgary, CANADA Schenectady, NY 12345

More information

A REVIEW ON FAULT ANALYSIS IN UNDERGROUND CABLES

A REVIEW ON FAULT ANALYSIS IN UNDERGROUND CABLES A REVIEW ON FAULT ANALYSIS IN UNDERGROUND CABLES Siddharth Lohia 1, Usman Khan 2, Swati Dixit 3 1, 2 Students, Electrical Engineering Department Greater Noida Institutes of Technology, Gr.Noida, (India)

More information

Name: New Document 1. Class: Date: 87 minutes. Time: 87 marks. Marks: Comments:

Name: New Document 1. Class: Date: 87 minutes. Time: 87 marks. Marks: Comments: New Document Name: Class: Date: Time: 87 minutes Marks: 87 marks Comments: Q. Figure shows a radio. The radio can be powered by connecting the two-core cable to the mains electricity supply. (a) (i) What

More information

IEC Installation Guide for SERAPHIM Photovoltaic Module

IEC Installation Guide for SERAPHIM Photovoltaic Module SUSA [InstallationGuide] 2016.11_V1.0 IEC Installation Guide for SERAPHIM Photovoltaic Module Table of Contents 2 Purpose of this guide General safety Handling safety Installation safety Fire safety 5

More information

Optimized substation asset testing for maximum efficiency

Optimized substation asset testing for maximum efficiency Optimized substation asset testing for maximum efficiency SAFETY > > Minimum user interaction, for example, for rewiring > > Controlled usage of high voltages and currents > > Safe distance between test

More information

UPS installation safety requirements

UPS installation safety requirements Smart tricks to improve power supply reliability White paper series UPS UPS installation safety requirements Janne Paananen Technology Manager, Large Systems Group, Eaton Martijn Imming Business Development

More information

Turning data from monitoring and condition assessment into transformer reliability information

Turning data from monitoring and condition assessment into transformer reliability information 1 Turning data from monitoring and condition assessment into transformer reliability information or dealing with the Big Data tsunami! Craig L Stiegemeier Director of Technology and Business Development

More information

SECTION 31 ACCESS FLOORS

SECTION 31 ACCESS FLOORS SECTION 31 ACCESS FLOORS 1 GENERAL 1.1 OVERVIEW OF ACCESS FLOORS SECTION General description Work under this section includes, but is not necessarily limited to, the supply and installation of proprietary

More information

Sulfur tolerant chip resistors

Sulfur tolerant chip resistors Sulfur tolerant chip resistors TRR series Datasheet Features 1)Special construction prevents sulfur gas penetration, significantly increasing reliability. 2)ROHM resistors have obtained ISO91 / ISO / TS16949

More information

Model # 95-S8. Page 1 of 8

Model # 95-S8. Page 1 of 8 Model # 95-S8 Page 1 of 8 Page 2 of 8 WARRANTY & TERMS WARRANTY: 5 Year Limited Warranty on Thermoplastic coated elements. Ultra Play guarantees all items for one full year to be free of defects in workmanship

More information

Understanding Power Factor, Crest Factor, and Surge Factor

Understanding Power Factor, Crest Factor, and Surge Factor Understanding Power Factor, Crest Factor, and Surge Factor White Paper #17 Revision 0 Executive Summary This paper explains the technical terms of Power Factor, Crest Factor, and Surge Factor. The use

More information

XBDM-HW63. 63A Model. User & Installation Manual Xtreme Power Conversion Corporation. All rights reserved.

XBDM-HW63. 63A Model. User & Installation Manual Xtreme Power Conversion Corporation. All rights reserved. XBDM-HW63 63A Model User & Installation Manual www.xpcc.com 2016. All rights reserved. (Rev 3/02/16) Table of Contents Introduction...3 Product Overview... 3 Installation and Operation...4 Inspection...4

More information

2 3 4 Distance from centre of reactor (m)

2 3 4 Distance from centre of reactor (m) ONE OPTIMISED NETWORK EQUIPMENT 12 January 2016 c 0MPRMF-4 Magnetic fields and air core reactors 1 Introduction Air core reactors are commonly used as shunt reactors, fault current limiting reactors, tuning

More information

ENGINEERING SPECIFICATION

ENGINEERING SPECIFICATION ENGINEERING SPECIFICATION No. Page 1 CATEGORY: TRANSFORMERS DATE: 11/16/2006 Subject: TABLE OF CONTENTS PURPOSE...2 SCOPE...2 REFERENCES...2 DEFINITIONS...2 SPECIFICATION...2 General... 2 High Voltage

More information

GENERAL GUARANTEE CONDITIONS OF POLTRONIC S.A. (SUPPLIER) FOR A COMMERCIAL PARTNER (PARTNER) FOR NEXTEC BRAND PRODUCTS

GENERAL GUARANTEE CONDITIONS OF POLTRONIC S.A. (SUPPLIER) FOR A COMMERCIAL PARTNER (PARTNER) FOR NEXTEC BRAND PRODUCTS GENERAL GUARANTEE CONDITIONS OF POLTRONIC S.A. (SUPPLIER) FOR A COMMERCIAL PARTNER (PARTNER) FOR NEXTEC BRAND PRODUCTS 1. The SUPPLIER gives a 24-month guarantee for all of the SUPPLIER s products, counting

More information

OVERALL EXTERNAL SERVICES COSTS

OVERALL EXTERNAL SERVICES COSTS EB-00-00 Tab Schedule Filed: 00 Aug Page of OVERALL EXTERNAL SERVICES COSTS INTRODUCTION THESL uses external services to complement its internal capacity to execute work programs. External services represent

More information

INCREMENTAL CAPITAL ELIGIBLE PROJECTS DETAILS Capital Expenditure $3,931,290 ($3,530,841 in 2013) Background:

INCREMENTAL CAPITAL ELIGIBLE PROJECTS DETAILS Capital Expenditure $3,931,290 ($3,530,841 in 2013) Background: EB-0-0 0 IRM Application Filed: September, 0 Page of INCREMENTAL CAPITAL ELIGIBLE PROJECTS DETAILS Program Title: Switching Units and Transformers 0 0 0 Capital Expenditure $,,0 ($,0, in 0) Background:

More information

mechanical integrity best practice for sulfuric acid plants

mechanical integrity best practice for sulfuric acid plants mechanical integrity best practice for sulfuric acid plants Larry Moore, PE AVP & Principal Engineer, Mining and Metallurgy FM Global Corporate Offices Johnston RI USA objectives acid plant hazards and

More information

33-SDMS-02 SPECIFICATIONS FOR

33-SDMS-02 SPECIFICATIONS FOR SPECIFICATIONS FOR MV AUTOMATIC LINE SECTIONLIZER UP TO 36 KV This specification is property of SEC and subject to change or modification without any notice TABLE OF CONTENTS SECTION T I T L E PAGE NO.

More information