HomeTeam Inspection Service 6550 Concord Beaumont, Texas (fax) Defective Drywall Inspection Report
|
|
- Kelley Chambers
- 6 years ago
- Views:
Transcription
1 HomeTeam Inspection Service 6550 Concord Beaumont, Texas (fax) Defective Drywall Inspection Report Client: XXXXXXXXXX Property Address: XXXXXXXXXXXXXXX Inspection Date: XXXXXXXXXXX 1
2 October 00, 2010 Mr. Re: XXXXXXX XXXXXX Drywall Inspection XXXXXXX Dear Mr. XXXXX: In complying with your request, the HomeTeam Inspection Service has completed an Inspection at the above referenced property. Our report is enclosed. The HomeTeam Inspection Service appreciates the opportunity to provide professional services to you. If you have any questions, please contact The HomeTeam Inspection Service at Respectfully submitted, Curtis Carr (Inspector) 2
3 Table of Contents 1.0 Introduction Purpose Investigative Work Report Basis Investigative Work Property Description Interview Observations Drywall Sampling Conclusions Limitations 8 Site Photographs Laboratory results Appendix A Appendix B 3
4 1.0 Introduction The HomeTeam Inspection Service was hired by XXXXX to conduct a defective drywall inspection of the structure located at XXXXXXX. 1.1 Purpose The purpose of HomeTeam s inspection was to determine the presence of defective drywall and any visible related corrosion in the home. 1.2 Investigative Work HomeTeam visited the site on October 00, Our assessment consisted of a visual inspection. We were attempting to locate any visible corrosion to metallic surfaces such as copper wires, copper plumbing lines, water heater lines, A/C coil, door hinges, ceiling fixtures, mirrors, etc. We were also attempting to identify the manufacture labels on the back of the drywall in the attic. We were directed by the client to do a visual inspection only (no samples taken). 1.3 Report Basis The conclusions contained in this report are based on information obtained during Home Team s assessment of the property. The following sources of information were used: We conducted an interview of the client for a history of the house regarding its building date and any additions and repaired that were made after construction. We searched for labels on the sheetrock backing in the attic by doing a random sampling in order to identify the manufacturer. We conducted a visual inspection of the interior of the structure. We checked the interior for any unusual odors that might be related to drywall off-gassing. 4
5 We searched for visible corrosion to metallic surfaces in the house. 2.0 Investigative Work 2.1 Property Description Through this report the terms right and left are used to describe the structure as viewed facing it from the street. The wood frame structure was on a slab on grade foundation. There was a brick veneer covering on the exterior and sheetrock on the interior. There was an asphalt-fiberglass roof. 2.2 Interview We were informed by the client that the home had been built in approximately The home was involved in a Real Estate sale. We were also informed that the home previously had four service responses within one and one half months dealing with problems on the air conditioning unit. The client stated that he was aware that damage to air conditioner coils is a possible result of Chinese drywall. The client was concerned that the drywall used in the construction of the home may have been the type that is defective. We were requested to do a defective drywall inspection of the home. 2.3 Observations All conditions are reported as they existed at the time of the inspection. A visual inspection and assessment of the structure was conducted to locate the presence of defective drywall and unusual corroded surfaces. (History of home) The home appeared to have been built in or around 2006, a date within the period of when the defective drywall in question first began to be used. (Manufacturer s label) The insulation was pulled back in the attic to reveal the manufacturer of the drywall as being Knauf. The label also contained a stamp, Dongguan, China, ASTM, C36. It is important to note that this was only a random sampling. We are unable to identify all of the 5
6 manufacturer s labels in the attic or any of the labels on the walls. In many homes more than one brand of drywall was used. Just because a particular manufacturer s label is identified in the attic does not mean that it was the only brand of drywall used in the home. (Unusual odor) No unusual sulfur-like odor was detected in the structure at the time of our inspection. (Visible metallic corrosion) No visible metallic surfaces showed signs of corrosion at the time of our inspection. 2.4 Drywall Sampling The purpose of the sampling is to identify the presence and levels of Orthorhombic Cyclooctasulfur. No drywall sampling was done per request of the client. 6
7 3.0 Conclusions Though no visible evidence was found of corrosion to any metallic surfaces, Chinese drywall has been identified in this home. It is impossible to determine how much of this product was used in the construction of this home with a visual inspection. Chinese drywall has been reported to have unusually high level of hydrogen sulphide and sulfur dioxide that over time causes corrosive damage to any metal in the home including electrical wiring, plumbing and HVAC units and possible health issues. The HomeTeam Inspection Service recommends that the client inform him/herself about the issues related to Chinese drywall prior to the closing of the home. It is recommended that laboratory testing be done to further evaluate the composition of the drywall found in the home. Additional information can be found at: 7
8 4.0 Limitations This defective drywall inspection was conducted following standard practices and guidelines as formulated by the HomeTeam Inspection Service. The HomeTeam Inspection Service was hired to provide a defective drywall inspection only. A Protocol detailing any remediation or mitigation that might be needed was excluded and therefore was not included on this project and report. The submittal of this report constitutes the conclusion of services provided by The HomeTeam Inspection Service to the client. The HomeTeam Inspection Service reserves the right to provide additional services for an additional fee at a future date if requested. Regardless of how thorough an inspection may be conducted, it is always possible that additional areas containing defective drywall, corrosion to metallic surfaces or other adverse conditions may be present, though not readily visible or accessible at the time of the inspection. The findings represent conditions that were visible and in areas that were accessible at the time of the inspection. It is important to understand that building conditions such as indoor air quality can and do change on a daily basis and some symptoms of defective drywall may not be visible or fully developed at the time of the inspection. The home could have defective drywall that is offgassing, but may not have had the time needed to develop visible signs. If additional information or evidence becomes available which may affect The HomeTeam Inspection Service s findings, we request the opportunity to evaluate the information and modify our findings as appropriate. It is the opinion of The HomeTeam Inspection Service that we have met what is recognized as the accepted standards normally exercised by others in conducting a defective drywall inspection of a structure. No warranty, expressed or implied, is made regarding the information contained in this report. All conditions are reported as they existed at the time of the inspection. Although some maintenance and/or safety items may be disclosed, this report does not include all maintenance or safety items, and should not be relied upon for such items. This is not a code inspection report. This report does not address the insurability of the property. Identifying items included in manufacturer recalls are 8
9 not within the scope of the inspection. Acceptance and/or use of this report implies acceptance of the Defective Drywall Inspection Agreement and the terms stated therein. Defective items listed in this report should be repaired prior to closing if the building is involved in a Real Estate sale. The client named at the beginning of this report has acknowledged that the inspection report is intended for the CLIENT s sole, confidential, and exclusive use and is not transferable in any form. The HomeTeam Inspection Service assumes no responsibility for the use or misinterpretation by third parties. 9
10 Appendix A Site Photographs Front exterior Water heater (no corrosion to lines) No corrosion to wire ends No corrosion to evaporator coil 10
11 Label states, made in Dongguan, China Label states the manufacturer was Knauf 11
Property Condition Assessment
Property Condition Assessment Pewaukee, WI 53072 Inspection Date: 1/6/15 Prepared For: Report Number: Prepared By: Shamrock Building Inspection Consultants LLC N29 W29951 Shel-Mar Dr. Pewaukee, WI 53072
More informationBuilding Inspection Report
Building Inspection Report Sample Commercial Inspection Report Inspection Date: Prepared For: Prepared By: Professional Property Inspection Consultants 4857 Winterset Drive Columbus, OH 43220 (614) 459-5941
More informationA Sample Report On The Conditions At:
HomeInfo, LLC Information You Deserve 3620 McCurdy Street Montgomery, AL 36111-2148 334-303-4284 Office 334-264-7755 Fax A Sample Report On The Conditions At: 123 Main Street Anytown, Alabama 36101-1101
More informationInspection Report. Prepared for: Gil Turiel. Property Address: 545 Briar Run Court Loganville, GA Date: July 17, 2011
Inspection Report Prepared for: Gil Turiel Property Address: Loganville, GA 30052 Date: July 17, 2011 Inspector: Charles Mann (770) 594-2222 www.edificeinspections.com Page 1 INSPECTION CONDITIONS CLIENT
More informationLighthouse Engineering, L.L.C.
Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website: www.lighthouseeng.com Email: Office@LighthouseEng.com Thursday, September 04, 2014 TO: Our Client RE: Initial Engineering
More informationInspection Report. Prepared for: Yossi Berg. Property Address: 4925 Diggers Way Sugar Hill, GA. Date: July 20, 2011
Inspection Report Prepared for: Yossi Berg Property Address: Sugar Hill, GA. Date: July 20, 2011 Inspector: Charles Mann (770) 594-2222 www.edificeinspections.com Page 1 INSPECTION CONDITIONS CLIENT &
More informationMadison's Home Inspections
Cover Page Madison's Home Inspections Property Inspection Report my street, Clarksville TN, 37043 Inspection prepared for: Gary Mann Agent: gary mann - Madison's Inspection Date: 0/4/2009 Time: 12 pm Age:
More informationNational Property Inspections
National Property Inspections Anywhere, USA (325) 382-8754 Property Location 9375 Burt Street Anywhere USA Prepared for John Investor Consultant Al Standard (325) 382-8754 Page 1 of 27 TABLE OF CONTENTS
More informationBulletin No Rev. March 15, 2009 SCOPE OF CHINESE DRYWALL CONCERNS EXPANDS
TECHNICAL BULLETIN Bulletin No. 09-563 - Rev. March 15, 2009 SCOPE OF CHINESE DRYWALL CONCERNS EXPANDS Florida has been the focal point for problems associated with the outgassing of sulfur from drywall
More informationCONDITION OF PROPERTY SURVEY Structural Integrity of Framing.
September 29, 2017 TO: REF: CONDITION OF PROPERTY SURVEY Structural Integrity of Framing. Dear Ms. : HEDDERMAN ENGINEERING, INC. performed an inspection today on the property located at, Houston, Texas.
More informationREPORT CHECKLIST SUPPLEMENT
REPORT CHECKLIST SUPPLEMENT This checklist will assist in assuring that a home inspection report complies with The Arizona Standards of Professional Practice for Home Inspectors For use by: Applicants,
More informationThe Inspector. Property Inspection Report
Cover Page The Inspector Property Inspection Report Inspection prepared for: ******** ******* Date of Inspection: 11/18/2013 Time: 12PM Age of Home: unknown Size: 2000sf Weather: overcast / 40 Inspector:
More informationSUMMARY OF AREAS REQUIRING FURTHER EVALUATION
January 24, 2011 RE: ABC Lane Surprise, AZ 85374 Dear Mr. Sample: At your request, a visual inspection of the above referenced property was conducted January 24, 2011. An earnest effort was made on your
More informationChris Nowling Inspection Services 6608 Wolfcreek Pass Austin, TX (512)
Chris Nowling Inspection Services 6608 Wolfcreek Pass Austin, T 78749 (512) 288-0288 PROPERTY INSPECTION REPORT Prepared For: Craig Hawes (Name of Client) Concerning: 1005 FM 2571 Smithville, T 78957 (Address
More informationInspection Report. Prepared for: Tonia Mann. Property Address: 2557 Briar Valley Way Dacula, GA Date: March 01, 2012
Inspection Report Prepared for: Tonia Mann Property Address: Dacula, GA 30019 Date: March 01, 2012 Inspector: Charles Mann (770) 594-2222 www.edificeinspections.com Page 1 INSPECTION CONDITIONS CLIENT
More informationStorm Damage Assessment Report For: 1234 Example Street., Houston, TX 77002
Storm Damage Assessment Report For: 1234 Example Street., Houston, TX 77002 Prepared For: Miriam Saliba nspection Date: 9/6/2017 Prepared By: Adam Wells TREC License # 21140 105 E Spreading Oaks Ave, Friendswood,
More informationSUMMARY OF IDENTIFICATION GUIDANCE FOR HOMES WITH CORROSION FROM PROBLEM DRYWALL AS OF MARCH 18, 2011
SUMMARY OF IDENTIFICATION GUIDANCE FOR HOMES WITH CORROSION FROM PROBLEM DRYWALL AS OF MARCH 18, 2011 In its continuing effort to provide accurate and helpful information, the Federal Interagency Task
More informationStructural Condition Assessment
108 6 th Street, Garland, Texas Engineering Report Date: September 29, 2016 RLG No. : 16729 Prepared for: Mr. Jeff D. Bulls III AIA 3030 LBJ Freeway, Suite 1220 Dallas, TX 75234 PM: Harold F. Phillips
More informationAlabama Home Inspections
Cover Page Property Inspection Report 1000 Sample Dr., Sampletown USA Inspection prepared for: Report Sample Inspection Date: 1/21/2010 Time: 400pm Size: Approx. 2,200sf Weather: Cloudy 62 Inspector: Bobby
More informationInsurance Risk Services 104 South Park Ave. Sanford, FL Phone Fax:
Access Home Insurance Company Inspector: Monica Angelette Agent: TRINTON INSURANCE GROUP LLC Completed: 4/20/2017 Insurance Risk Services 104 South Park Ave. Sanford, FL 32771 Phone 800-644-5112 Fax: 800-644-0567
More informationExcellence in Experts, Efficiency and Service
Excellence in Experts, Efficiency and Service February 12, 2009 Insurance Company P.O. Box 1209 Horse Canyon, California 92808 RE: Insured: Mr. and Mrs. Insured 1669 Wild Horse Ranch Tobiano Paint, California
More informationMr. Homeowner Mrs. Homeowner
NATIONAL PROPERTY INSPECTIONS America's Premier Inspection Service Inspection Report Prepared on Behalf of: Mr. Homeowner Mrs. Homeowner Concerning Property Located at: 123 Any Street Keller, TX National
More informationHome Energy Score. Learn more at homeenergyscore.gov. Uses more energy. Uses less energy Milvia Street Berkeley, CA 94704
ADDRESS 2120 Milvia Street Berkeley, CA 94704 HOME SIZE YEAR BUILT AIR CONDITIONING 1,450 square feet 1970 Your home's current score 3 Uses more energy 1 2 3 4 5 6 7 8 9 10 Uses less energy Learn more
More informationInspection Report. Prepared for: Tonia Mann. Property Address: 56 Riverview Place Douglasville, GA Date: September 19, 2012
Inspection Report Prepared for: Tonia Mann Property Address: Douglasville, GA 30134 Date: September 19, 2012 Inspector: Charles Mann Edifice Inspections, Inc. (770) 594-2222 www.edificeinspections.com
More informationInspection Report. Jay Coleman. Property Address: Cooper Rd Brookshire TX Bill Harvey Inspection Services
Inspection Report Jay Property Address: 35505 Cooper Rd Brookshire TX 77423 Bill Harvey Inspection Services Bill Harvey 5648 13119 Jasper Lane Cypress TX 77429 281-477-7875 Table of Contents Cover Page...1
More informationACCESSORY BUILDING. Building Permit Requirements: (must be completed before submitting application)
ACCESSORY BUILDING Before your application can be deemed complete and ready for processing you will need the following: (Please hand in entire application package including this cover sheet) Zoning- check
More informationa) For the purposes of this Section, the terms listed below shall mean:
Page 1 of 5 TITLE 68: PROFESSIONS AND OCCUPATIONS CHAPTER VIII: OFFICE OF BANKS AND REAL ESTATE PART 1410 HOME INSPECTOR LICENSE ACT SECTION 1410.200 STANDARDS OF PRACTICE Section 1410.200 Standards of
More informationQuality Inspection 8618 London Heights San Antonio, TX Phone: (210)
Quality Inspection 8618 London Heights San Antonio, TX 78254 Phone: (210) 240-0476 PRE DRYWALL INSPECTION REPORT Prepared For: DELETED (Name of Client) Concerning: DELETED, San Antonio, TX 78258 (Address
More informationHomeOwner Services, Inc.
HomeOwner Services, Inc. 1431 E. Jonquil Circle, Arlington Heights, IL 60004 Tel: 847-749-3444 Fax: 747-749-3555 Mobile: 847-308-1495 www.homeownerservicesinc.com tommyers55@aol.com Sample Inspection Report
More informationHome Inspection Services
Home Inspection Services Catering to the Client Global Engineering & Contracting, Inc. is highly qualified in the area of home and building inspection due to the wealth of experience that we developed
More informationHome Inspection Report
Home Inspection Report 1 of 16 Table of Contents Definitions 2 General Information 2 Electrical 3 Roof 7 HVAC System 10 Plumbing 12 2 of 16 Definitions NOTE: All definitions listed below refer to the property
More informationBVSC BVSC. Midwest Technical Inspections Survey Worksheet. Account / Account Code: Insured: Policy #: Building Data - Section 1
Midwest Technical Inspections Survey Worksheet BVSC BVSC Account / Account Code: Agency: Insured: Policy #: Telephone: Alt. Phone: Building Data - Section 1 Building Name (Entire Valuation) Section Name
More informationInspection Report. Property Address:
Inspection Report provided by: Safe Side Home Inspection Inspector: Corey Stuart TN License # 778 434 Margaret Circle McMinnville, TN 37110 safesideinspection@blomand.net Property Address: 1234 Anywhere
More informationAMERICAN SOCIETY OF HOME INSPECTORS AUXILIARY STANDARD OF PROFESSIONAL PRACTICE FOR RESIDENTIAL DECK INSPECTIONS DRAFT
AMERICAN SOCIETY OF HOME INSPECTORS AUXILIARY STANDARD OF PROFESSIONAL PRACTICE FOR RESIDENTIAL DECK INSPECTIONS 1. PURPOSE OF THIS STANDARD 1.1 The purpose of this Auxiliary Standard of Professional Practice
More informationInspection Report. Prepared for: Tonia Mann. Property Address: 1295 Greyland Hills Drive Lawrenceville, GA Date: April 24, 2012
Inspection Report Prepared for: Tonia Mann Property Address: Lawrenceville, GA 30046 Date: April 24, 2012 Inspector: Charles Mann (770) 594-2222 www.edificeinspections.com Page 1 INSPECTION CONDITIONS
More informationPROFESSIONAL ENGINEERING INSPECTIONS, INC. P. O. BOX HOUSTON, TEXAS (713)
PROFESSIONAL ENGINEERING INSPECTIONS, INC. P. O. BOX 271492 HOUSTON, TEXAS 77277 http://www.profengineering.com (713) 664-1264 June 19, 2000 Mr. Samuel Underdog 329 Castle Dr. Houston TX 77018 Dear Mr.
More informationPost Remediation Warranty
Post Remediation Warranty This warranty is provided by: Manufacturer: Anabec, Inc. 9393 Main Street PO Box 433 Clarence, NY 14031 716-759-1674 info@anabec.com & Qualified Contractor (Contractor): Presented
More informationRESIDENTIAL GUIDELINES
PO Box 368 212 Main Street Lake Dallas, Texas 75065 940 497-2226 ext 110 www.lakedallas.com RESIDENTIAL GUIDELINES NEW RESIDENTIAL PERMIT SUBMITTAL REQUIREMENTS: Before a building application may be submitted
More informationSECTION 6. Residential Warranty Corporation 10 Year, Limited Structural Warranty. Year One
SECTION 6 Residential Warranty Corporation 10 Year, Limited Structural Warranty Year One Foundations basement, crawl space, slab on grade. Framing ceiling, floor, roof, wall. Exterior structurally attached
More informationOttawa Inspections Inspection Report
Ottawa Inspections Inspection Report 76 Lilico Street, Ottawa, ON Inspection prepared for: Client s Name Agent: Agent s Name Inspection Date: xxxxxx-xxxxx Weather: Sunny 16 degree Celcius Inspector: Choun
More informationFINEGAN INSPECTION SERVICES, INC.
FINEGAN INSPECTION SERVICES, INC. TERRY FINEGAN 76 WEST FOSTER MAINEVILLE ROAD MAINEVILLE, OHIO 45039 683-0733-PHONE 697-0163-FAX Email- finegan @ fuse.net CLIENT: 1/14/08 Mr. BUILDING LOCATION As in all
More informationPROPERTY OVERVIEW PROPERTY HIGHLIGHTS. 2,340 SF Convenience Store. 3,508 SF Three Unit Strip Center. U-Haul Business. Sunoco Branded Gas Station
RETAIL FOR SALE 5990 Asheville Highway, Hendersonville, NC 28791 OFFERING SUMMARY SALE PRICE: $1,350,000 LOT SIZE: 0.75 Acres YEAR BUILT: 1980 BUILDING SIZE: 5,848 SF RENOVATED: 2018 C-2 Commercial ZONING:
More informationHome Inspection Report
Pfeifer Home Inpsection, LLC 8332 Crystal Pointe Lane Indianapolis, Indiana 46236 317-340-1734 Lic #HI01700103 Home Inspection Report Indianapolis, IN 46236 Page 1 of 24 Table of Contents Definitions 2
More informationLimited Visual Assessment Report
Terramar School Peoria, Arizona July 27, 2015 Terracon Project No. 65157316 Prepared for: Deer Valley Unified School District Glendale, Arizona Prepared by: Terracon Consultants, Inc. Tempe, Arizona July
More informationASBESTOS AND LEAD-BASED PAINT SURVEY 732 Jessamine Avenue East St. Paul, Minnesota. Prepared for:
ASBESTOS AND LEAD-BASED PAINT SURVEY 732 Jessamine Avenue East St. Paul, Minnesota Prepared for: City of St. Paul Department of Planning and Economic Development 1100 City Hall Annex 25 West 4 th Street
More informationNational Property Inspections
Monday, August 22, 2011 Inspector Joe Smith 548-254-3658 Page 1 of 33 GENERAL INFORMATION GENERAL CONDITIONS AT TIME OF INSPECTION : No Property Occupied : Property Faces : North South East þ West Year(s)
More informationResidential Building Permits
JWS INSPECTION SERVICE 3407-43B Avenue Lloydminster, Saskatchewan S9V-2G1Ph:780-808-5704 Email: jsydoruk@sasktel.net Residential Building Permits A residential building is a one or two unit dwelling, along
More information3D Home Improvement and Inspection Services, Inc
Property Inspection Report Cover Page ABC Disney Lane, Winter Garden FL, 34787 Inspection prepared for: John Doe Inspection Date: 7/15/2010 Time: 11:00 am Age: 6 Years Size: 3,378 LSF / 4,427 TSF Weather:
More informationTOWN OF ROTTERDAM BUILDING DEPARTMENT RESIDENTIAL ACCESSORY BUILDINGS AND STRUCTURE PERMIT APPLICATION Ext 395
TOWN OF ROTTERDAM BUILDING DEPARTMENT RESIDENTIAL ACCESSORY BUILDINGS AND STRUCTURE PERMIT APPLICATION 518-355-7575 Ext 395 Needed to Obtain a Residential Accessory Structure Building Permit: 1. Building
More informationThe Inspection Process. Waxhaw N.C.
The Inspection Process In Waxhaw N.C. This information is provided by the Waxhaw Enforcement Division to assist you in the progression of your project. Nothing in this document should be considered "Code"
More informationPHASE (pre-drywall) INSPECTION REPORT
PHASE (pre-drywall) INSPECTION REPORT Prepared For: (Name of Client) Concerning: Phase Sample 2014 (Address or Other Identification of Inspected Property) By: Dean Limbaugh #4599 2014 (Name and License
More informationEnergy Efficiency in New Constructions built by Blake Taylor
Energy Efficiency in New Constructions built by Blake Taylor Yes, he builds a beautiful home. It is so full of detail. He really loves what he does, you can tell. It is so rich in architectural detail.
More informationTOWNSHIP OF DRUMMOND/NORTH ELMSLEY. Deck/Porch Guide & Permit
TOWNSHIP OF DRUMMOND/NORTH ELMSLEY Deck/Porch Guide & Permit New Dwelling Living Space Additions to Dwelling Living Space Summary of Building Permit Rates (calculations are based on outside dimensions)
More informationAugust 2, 2016 Mr. Stu Young 386 South Golf Drive Naples, FL 34102 Telephone: 610.203.4138 Email: StuYoung1@yahoo.com Subject: Report of Forensic Engineering Consulting Services 386 SOUTH GOLF DRIVE SETBACK
More informationBUILDING PERMIT INFORMATION GUIDE FOR THE HOMEOWNER
THE CORPORATION OF THE MUNICIPALITY OF SOUTH HURON 322 Main Street South, P.O. Box 759, Exeter, Ontario N0M 1S6 PHONE: (519) 235-0310 FAX: (519) 235-3304 TOLL FREE: 1-877-204-0747 WEBSITE: www.southhuron.ca
More informationOWNER S REPONSIBILITIES AND PREPARATION INSTRUCTIONS. Schedule "C"
OWNER S REPONSIBILITIES AND PREPARATION INSTRUCTIONS Schedule "C" Building Code All Ready To Move (RTM) Homes are built according to the Alberta Building Code and National Building Code. Please note that
More informationRESIDENTIAL BUILDING PERMIT GUIDE FOR MULTI-FAMILY DWELLINGS
RESIDENTIAL BUILDING PERMIT GUIDE FOR MULTI-FAMILY DWELLINGS New Construction, Addition, or Alteration All plans submitted must be prepared, sealed, and signed by a Registered Nebraska Design Professional
More informationEXTERIOR SIDING CONDITION SURVEY
EXTERIOR SIDING CONDITION SURVEY FOR FARRWOOD 2 CONDOMINIUMS 49-176 FARRWOOD DRIVE HAVERHILL, MA APRIL 2016 c/o PROPERTY MANAGEMENT OF ANDOVER, INC. P.O. BOX 488 ANDOVER, MA 01810 213 WEST STREET, MILFORD,
More informationcomponent was performing its intended function; installation and condition were appropriate for age and use.
April 23, 2012 Dear Home Seller, On April 6, 2012, Cities Inspection Service, Inc. completed a home inspection of the property located at 123 Oak Drive, Somewhere, Minnesota for you. Doug Hastings did
More informationHikone. Sincerely, Enclosures
August 8, 2013 Mr. Richard Higgins Norstar Development USA, L.P. 733 Broadway Albany, New York 12207 Re: Asbestos Containing Material Survey Hikone 2702 2760 Hikone Road, Ann Arbor, Michigan ERG Project
More informationMy Home Was Built In What Can I Expect To See On My Report?
My Home Was Built In 1956. What Can I Expect To See On My Report? Common Issues in 40 70 Year Old Homes Evidence of foundation settlement Older roof, limited service life remaining Older electrical system
More informationCalidad Home Inspection Colleyville, TX (817) /
Calidad Home Inspection Colleyville, TX 76034 (817) 896-1203 / info@calidad-tx.com This Professional Inspection Report Has Been Prepared Exclusively For: Mr and Mrs Home Buyer Kings Ranch RoadRIver Oaks,
More informationBoulder City NV Prepared by (Print Name) Signature Date
City of Boulder City Community Development Department Building & Safety Division 401 California Avenue Boulder City, NV 89005-2600 702-293-9282 (Main Line) 702-293-9392 (Fax) 2009 International Energy
More informationAn Applicants Guide to Residential Building Permits City of Galt Building Department
An Applicants Guide to Residential Building Permits City of Galt Building Department Service Assistance Telephone Numbers City of Galt Administration... 209-366-7100 Building Department... 209-366-7200
More informationInspection Report. Prepared for: Yaron Sternberg. Property Address: 926 Hemingway Road Stone Mountain, GA. Date: April 15, 2011
Inspection Report Prepared for: Yaron Sternberg Property Address: Stone Mountain, GA. Date: April 15, 2011 Inspector: Charles Mann (770) 594-2222 www.edificeinspections.com Page 1 INSPECTION CONDITIONS
More informationFeature Zone IECC 2009 IECC
Feature Zone 3 2006 IECC 2009 IECC Window U factor 0.65 0.50 Skylight U factor 0.65 0.65 Window SHGC 0.40 0.30 Ceiling R value 30 30 Wood frame R value 13 13 Mass wall R value 1 5 5/8 Floor R value 19
More informationSummary. Inspect It Like A Girl. P.O. Box 2283 Madison, MS Customer Happy Home. Address 123 Happy Home Road Jackson MS 39157
Summary P.O. Box 2283 Madison, MS 39110 Customer Happy Address 123 Happy Road Jackson MS 39157 The following items or discoveries indicate that these systems or components do not function as intended or
More informationSureHome Inspection Company. Home Inspection. Grant st Street Omaha, NE 68048
Home Inspection Grant 7142 21st Street Omaha, NE 68048 Page 1 of 13 Table of Contents Definitions 2 General Information 2 Roof 3 Exterior 4 Grounds 5 Attic 5 Garage 6 Bathroom 6 Interior 7 Kitchen 7 Laundry
More informationTruth in Sale of Housing Disclosure Report NOTICE - Read Entire Report Carefully. This is not a Buyer's Inspection!
NOTICE - Read Entire Report Carefully. This is not a Buyer's Inspection! Current Owner Name: FREDDIE MAC Contact: FREDDIE MAC Business/Relationship: Owner Address: C/O 8937 AZTEC DRIVE I declare to the
More informationTHE CITY OF FAYETTEVILLE ADOPTED THE 2009 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) ON JULY 17, 2012
THE CITY OF FAYETTEVILLE ADOPTED THE 2009 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) ON JULY 17, 2012 Compliance with the code for new residential construction, additions, and substantial remodels will
More informationSPRINKLER SYSTEM Wet / Ordinary hazard
LOCATION & ACCESS Akron Business Centre I and II 4.2 acre site at Opportunity Parkway (Wooster Avenue) & Pier Drive Located in Downtown Akron Adjacent to Innerbelt Expressway (Route 59) and just north
More informationREQUIREMENTS FOR SUBSTANTIALLY DAMAGED AND SUBSTANTIALLY IMPROVED STRUCTURES
REQUIREMENTS FOR SUBSTANTIALLY DAMAGED AND SUBSTANTIALLY IMPROVED STRUCTURES If your home or business incurred damage, the engineering department, in conjunction with the Flood Mitigation Officer, will
More informationTOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION Ext. 395 Needed to Obtain Permit:
TOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION 355-7575 Ext. 395 Needed to Obtain Permit: 1. Building Permit Application, and/or residential plumbing permit application, as applicable, to be
More informationSANDTOWN CROSSING PROFESSIONAL OFFICE PARK Atlanta, GA
Atlanta, GA LOCATED AT CAMP CREEK PARKWAY AND CAMPBELLTON ROAD For Sale or Lease Single units start at 1,176sf and can be combined to exact specification Custom Designed Medical and Professional finishes
More informationCOMMERCIAL ENERGY EFFICIENCY
COMMERCIAL ENERGY EFFICIENCY Commercial buildings are all buildings that are not detached one- or two-family dwellings, multiple single-family dwellings (townhouses), or Group R-2, R-3 or R-4 buildings
More informationWhitley Shower Locker Toilet Facilities
Whitley Manufacturing Co., Inc. 201 W. First Street S. Whitley, IN 46787 Phone (260) 723-5131 Sales Fax (260) 723-6396 whitley@whitleyman.com Building Type Building Code Whitley Shower Locker Toilet Facilities
More informationProperty Condition Assessment. Summary Report
www.real-estate-inspections.com Property Condition Assessment Summary Report Subject Property Prepared for: Client in Detroit File Number: 05-15-005 Inspector: Craig Milliken, PE CPM Real Estate Inspections,
More informationBUILDING INSPECTION REPORT
PACIFIC NORTHWEST INSPECTION ENGINEERS 10738 169 th Avenue S.E., Renton, Washington 98059 (425)228-5975 BUILDING INSPECTION REPORT March 24, 2016 Engineer's Inspection of 11811, 11815, 11909, 11913, &
More informationAll Pro Home Inspection. Home Report South Your Town
Home Report 9999 South Your Town Page 1 of 22 Not Inspected Summary This summary is not the entire report. The complete report may include additional information of concern to the client. It is recommended
More informationHome Inspection Report
Home Inspection Report Example Home Inspection Report. Page 1 of 17 Table of Contents Definitions 2 Company Information 2 General Information 2 Lots and Grounds 3 Exteriors 3 Garage/Carport 4 Roof 5 Attic
More informationSpacePak Manual J Load Analysis Project Sheet
SpacePak www.spacepak.com Telephone: (413) 564-5530 Fax: (413) 564-5815 e-mail: presalesupport@spacepak.com This PDF has pull-down menus and text boxes that can be completed on your computer and either:
More informationTown of Enfield. Parks & Recreation P.O. Box 699 Enfield NC (252) telephone (252) fax
Town of Enfield Parks & Recreation P.O. Box 699 Enfield NC 27823 (252) 445-3146-telephone (252) 445-1019-fax www.enfieldnc.org Request for Proposals for the Renovation and/or Construction of the Recreation
More informationRCT Webinar-Updated 03/18/12
RCT Webinar-Updated 03/18/12 This instructional write up/guide is for the RCT Form that is found on the Main Information screen. When do we do the RCT? The RCT is done when a full exterior or full interior
More informationInspection Report. Provided by: Cummins Services LLC. Inspector: Bill Cummins. Phone:
Inspection Report Provided by: Cummins Services LLC Inspector: Bill Cummins Phone:814-599-5797 Email:cumminsservices01@gmail.com Property Address: 662 Ridgley Street Orbisonia, PA 17243 Table Of Contents:
More informationMinimum Residential Plan Submittal Requirements
Minimum Residential Plan Submittal Requirements BI-24 CRC 2016 In order to make your permit application and the plan review process go as smooth as possible it is important to have a general understanding
More informationGeneral Summary. inspectorroy.com Lake Austin Blvd #10104 Austin, TX Customer Jason Woosley
General Summary 2600 Lake Austin Blvd #10104 Austin, TX 78703 Customer Jason Address 3431 Guadalajara Street Round Rock TX 78665 The following items or discoveries indicate that these systems or components
More informationResidential Plan Submittal
Denton County F.W.S.D. No. 1-A 2540 King Arthur Blvd., Suite 220 Lewisville, Texas 75056 Residential Plan Submittal Phone: 972-899-4000 Fax: 972-899-9336 www.dentoncountyfwsd.com Denton County Fresh Water
More informationProud of its Heritage, Preparing for its Future
TUSTIN Proud of its Heritage, Preparing for its Future Revised August 2013 USER GUIDE FOR THE INSTALLATION OF RESIDENTIAL ROOM ADDITIONS OR ALTERATIONS PURPOSE This guide describes the City of Tustin s
More informationREQUEST FOR PROPOSALS March 4, 2010 PROJECT OVERVIEW:
Police Headquarters Project REQUEST FOR PROPOSALS March 4, 2010 PROJECT OVERVIEW: General description The objective is to renovate an approximately 18 x 24 section of the two-bay attached garage at Town
More informationflexible spaces all the right places... fogg.com Resource Business Centre I, II, III & IV 5399 Lancaster Dr. & Resource Dr.
flexible spaces all the right places......resource Business Centre I, II, III & IV 5399 Lancaster Dr. & 800-900 Resource Dr. Flexible Spaces in All the Right Places is what Fogg had in mind when designing
More informationCHECKLIST Inspecting a Garage
CHECKLIST Inspecting a Garage By Ben Gromicko This section deals with the details of the garage or carport inspection that may be performed. At the end of this section, you shall be able to: describe the
More informationBUILDING PERMIT APPLICATION
Town of Dansville 1487 Day Road Arkport, NY 14807 607-295-7223 http://townofdansvilleny.com/ Page 1 of 5 Date Recd: Fee Pd: How Pd: Recd by: Permit #: BUILDING PERMIT APPLICATION Please review all pages.
More informationCOLUMN SPACING TRUCK ACCESS/DOORS EAVE HEIGHT UTILITIES PARKING & DRIVES
LOCATION & ACCESS Akron Business Centre I and II 4.2 acre site at Opportunity Parkway (Wooster Avenue) & Pier Drive Located in Downtown Akron Adjacent to Innerbelt Expressway (Route 59) and just north
More informationItem Photographs Comments Completed Date Prior to Entering Home Address Verification Ensure you are at the Front of home
Initial Secure/1 st Time Lock Change Checklist The items listed in this checklist are to be completed on every property at initial secure. Item Photographs Comments Completed Date Prior to Entering Home
More informationTown of Fredonia. 25 N Main St. * PO Box 217 Fredonia AZ Fax: * Office
Town of Fredonia 25 N Main St. * PO Box 217 Fredonia AZ 86022 Fax: 928-643-7627 * Office 928-643-7241 Email: townclerk@fredonia.net To Whom It May Concern: Enclosed in the building permit packet for the
More informationThe Home Doctor, Inc.
February 7, 2013 The Home Doctor, Inc. Property: 26147 HUNTER GATES RD. LESTER, AL 35647 Client: JOHN DOE HOME INSPECTIONS With over 10,000 since 1994 1-800-246-4362 SUMMARY PAGE CLIENT(S): JOHN DOE ADDRESS:
More informationHawks Eye Home Inspection LLC. Shoreline, Wa Williams Rd. Renton, Wa 98057
Shoreline, Wa 98155 Renton, Wa 98057 Page 1 of 23 Table of Contents Definitions 2 General Information 2 Lots and Grounds 3 Exterior 4 Roof 5 Garage/Carport 6 Electrical 7 Structure 8 Attic 10 Basement
More informationSOUTH CAROLINA HOME INSPECTOR STANDARDS OF PRACTICE
SOUTH CAROLINA HOME INSPECTOR STANDARDS OF PRACTICE The following Standards provide guidelines for the Residential Home Inspector. The guidelines outline what the Residential Home Inspector should observe,
More informationMetropolitan Atlanta Performance Home Inspection Report
Metropolitan Atlanta Performance Home Inspection Report Property Address: 2900 Delray Drive Prepared For: Hannah Ruppert Date: August 30, 2015 Fax or Email Address: For more information about inspections
More informationInspection Report. Riverpark Place Condominium Complex S. Riverside Dr. Tulsa, Oklahoma. For
Inspection Report Riverpark Place Condominium Complex 1501-1567 S. Riverside Dr. Tulsa, Oklahoma For Travelers Insurance Company Claim No.: ETM 3045 May 21, 2012 EI File No.: 25374TC Prepared by: Mr. Shawn
More information