1 TECHNICAL SESSION 3 Strengthening, Repair & Rehabilitation

2 2004 PTI Technical Session 3 T. Theryo, P. Garcia - Repair of Sunshine Skyway Bridge The Post-Tensioning Column Repair of High Level Approaches of Sunshine Skyway Bridge in Florida Teddy Theryo, P.E. Pepe Garcia, P.E. Technical Manager District Structures & Facilities Eng. Parsons Brinckerhoff Florida Dep. Of Transportation 5405 West Cypress St.,Ste Leslie Road MS Tampa, Florida Tampa, Florida ABSTRACT The Sunshine Skyway Bridge located over Tampa Bay on the west coast of Florida, U.S.A., has a total bridge length of 4.1miles, including approaches structure. The bridge is on Interstate 275 Highway, and links the major metropolitan areas of Tampa/St.Petersburg on the north and Bradenton/Sarasota on the south of Tampa Bay. The bridge consists of three major portions namely 4000 foot main cable stayed bridge span, 4860 foot high-level approach spans, and 13,000 foot low-level approach spans. The bridge was constructed with precast segmental construction method, including high level approach columns. This paper focuses on the repair of the high-level approach piers. The north and south high-level approaches consist of twin trapezoidal pre-cast post-tensioned (PT) box girder superstructures on pier columns supported on piles at 135 foot from center to center. The pier columns are post-tensioned and consist of pre-cast caps and elliptical shaped pre-cast segments with match-cast epoxy joints. The lower sections of the columns have a 2 foot thick wall and the upper sections have a 10 inches thick wall. The vertical tendons that hold the column segments together were internally bonded in the lower sections and are external in the upper sections of the columns. The tendons comprised of U loop tendons with 12, 17, and 18 strands of 0.5 inches diameter encased in 3 inches diameter smooth polyethylene (PE) primary duct. In the thick wall section of the columns, the primary duct was placed within a 5 inches diameter corrugated secondary PE duct, which was cast in the pre-cast segment. The U-loop tendons were looped in the footing (pile cap) and anchored in the pier cap. During a special inspection of the high-level approach columns in August 2000, severe tendon corrosion was discovered in one of 72 pier columns, namely 133 NB (northbound structure). Eleven of seventeen 0.5 inches strands in one of the four tendon legs, specifically the SE (southeast) tendon leg, had corroded fully in the external tendon region immediately below the column cap. The NE (northeast) tendon leg exhibited significant pitting corrosion, but no strand failure was identified. Both tendon legs had cracked PE ducts in the corroded areas. The rehabilitation of column 133 NB was completed on June 1, The detection of this severe corrosion failure prompted the Florida Department of Transportation (FDOT) to contract the services of Parsons Brinckerhoff Quade and Douglas, Inc. (PBQ&D) to perform comprehensive tendon corrosion investigation and repair of deficient structural members. As a result of the above investigation, a major rehabilitation of the 71 post-tensioned columns was recommended. The columns were repaired by filling the column shaft with reinforced concrete (Type 1 repair) or in combination with vertical PT bars in the upper part of the columns (Type 2 repair). For type 2 repair, the concrete was filled up to about 20 feet above the mean high water level. For both repair option, the existing vertical tendons were not utilized, however the tendons were left in place. Structurally, the repair method was designed based on composite action between the infill concrete and the existing column in resisting live loads, wind loads, temperature loads and ship impact loads. Vertical reinforcing bars were anchored in the footing by means of coring the footing and anchoring the bars with cementitious grout. The existing foundation capacity was also checked and it was determined that its support capacity is sufficient in supporting additional loads of infill concrete. The new PT bars were embedded in the infill concrete and anchored in the column cap by coring hole. A full scale vertical tendon mock-up grouting test was required in the repair contract. A new approved prepackaged grout material was utilized for the new vertical tendons. The pier caps were coated with elastomeric coating membrane to protect the PT system from future intrusion of contaminants. The columns rehabilitation was completed in February Copyright - Post-Tensioning Institute 19 All rights reserved

3 Engineering for Post-Tensioning Strengthening of Preheater Tower Dr. Ralph G. Oesterle, P.E., S.E. Senior Principal Structural Engineer Construction Technology Laboratories, Inc Old Orchard Road Skokie, IL (P) (F) Inspection by plant personnel revealed cracking in the concrete frame of a 326-ft-tall, 7-level preheater tower. On-site plant engineers deemed the cracking significant, especially since the structure supports critical manufacturing process equipment. A structural engineering consulting firm was retained to evaluate the extent of the problem and formulate a repair plan on a fast-track basis. The firm mobilized at the site in less than 24 hours and performed an initial structural safety assessment. A comprehensive condition survey and structural evaluation indicated that all levels of the structure required strengthening. Restoration consultants were engaged to assist locally with engineering and construction administration. A specialty repair contractor also was engaged to review the constructibility of several alternate repair schemes and maintain the fast-track schedule. After considering structural capacity and serviceability requirements, durability issues, the high-temperature operating environment, constructibility, and an aggressive construction schedule, the team recommended a retrofit consisting of bonded post-tensioning within internal holes drilled in the beams. This solution was quite extraordinary, as it required precision-drilling horizontal holes up to 87 ft long in the beams of the elevated frame structure, without cutting existing embedded reinforcement. Nondestructive impulse radar testing was used to locate existing embedded reinforcing steel, as well as to monitor the drilled holes trajectory. This process helped ensure proper tendon alignment and prevent damage to embedded steel. The cored holes served as post-tensioning ducts. The repairs were executed on a fast track and under challenging circumstances, which included working high on the exposed structure through a cold winter with severe wind conditions. The unique retrofit resulted in a structure that is stronger, more serviceable, and more durable than the original tower. The project represented an exceptional team effort, and its success is attributable to the leadership of the owner and client, the ingenuity of the engineering team, and the resourcefulness of the contractor. This presentation describes the engineering effort required for the strengthening work including the condition survey, structural evaluation, retrofit concept evaluations, retrofit design, and engineering support for the retrofit work. This presentation is intended to be given in conjunction with a presentation by Structural Preservations Systems, Inc. regarding the retrofit construction. Copyright - Post-Tensioning Institute 20 All rights reserved

4 Engineering for Post-Tensioning Strengthening of Preheater Tower Level 7 Level 6 Level 7 Level 6 N 1 2 Level 5 Level 5 B 8.2 FT. 9.5 FT. B X01 Level 4 Level 4 Level 3 320FT. Level 3 B X03 B X04 47 FT. Level 2 Level 2 Level 1 Level 1 A B X02 87 FT. Top/Grade Top/Grade 87 FT. 47 FT. Copyright - Post-Tensioning Institute 21 All rights reserved

5 Condition Survey Scope: Extensive Crack Survey Concrete Cores Ground Penetrating Radar (GPR) Ultrasonic Pulse Velocity (UPV) and Impulse Response (IR) Condition Survey Results: 4 Beams With Extensive Cracking at End Anchorage Regions Equivalent f ' c = 6,000 psi Cold Joint at Level 4 Adequate Reinforcement Was Consistent With Design Drawings #8 EF NDT Indicated Either Poor Concrete Consolidation Or Possible Splitting Cracks Copyright - Post-Tensioning Institute 22 All rights reserved

6 Structural Evaluation Scope: Reviewed Design Criteria Wind Load/Seismic Load Thermal Load Load Combinations Reviewed Original Computer Model Checked Reinforcement Details Structural Evaluation Scope: Analyses for Gravity, Thermal and Lateral Loads Beams Columns Diaphragms Foundations Structural Evaluation End Anchorage Requirements for Flexural Reinforcement Local or Global Problem? Structural Evaluation Results: All End Regions of All Beams at All Levels Required Strengthening Structural Evaluation Wind Load Results Beams Flexure and Shear Columns Flexure and Axial Shear Beam/Column Joint Shear Diaphragms Connection to Frame Foundation Pile Capacity 47 FT. Copyright - Post-Tensioning Institute 23 All rights reserved

7 Retrofit Concept Evaluation Beam/Joint Flexural Strengthening Requirements: Control of Cracking Sense of Safety Long Term Confidence High Temperature Environment Constructibility Aggressive Construction Schedule Retrofit Concrete Evaluation Early Concepts: Unbonded External Post-Tensioning Local Post-Tensioning Across Column Above and Below Beams King Post Truss System Bonded External Post-Tensioning External Plates Retrofit Concept Evaluation Unbonded External Post-tensioning tensioning Constructibility and Time to Install Required Post-Tensioning Crack Control Temperature Protection Retrofit Concepts Evaluation Bonded External Post-Tensioning Copyright - Post-Tensioning Institute 24 All rights reserved

8 Retrofit Design Requirements for Internal Post-Tensioning Design for Full Strength Utilize Existing Rebar for Crack Control Thermal Analyses Strength Reductions for Long Term Temperature Effects Increased Creep and Shrinkage Other Retrofit Issues Beam/Column Joint Shear Column Shear Column Axial Load Beam B302 Epoxy Injection Diaphragms Foundations Copyright - Post-Tensioning Institute 25 All rights reserved

9 Other Retrofit Issues Beam/Column Joint Shear Column Shear Column Axial Load Beam B302 Epoxy Injection Diaphragms Foundations Other Retrofit Issues Beam/Column Joint Shear Column Shear Column Axial Load Beam B302 Epoxy Injection Diaphragms Foundations Other Retrofit Issues Beam/Column Joint Shear Column Shear Column Axial Load Beam B302 Epoxy Injection Diaphragms Foundations Copyright - Post-Tensioning Institute 26 All rights reserved

10 Engineering Support of Retrofit Work Scope Continuous Site Engineering Presence Review/Respond to Submittals RFI s Field Clarification Engineering Support of Retrofit Work Structural Safety Crack Monitoring Elevation Survey Wind Monitoring Wind Monitoring Initial 35 mph Evacuation Criteria (15% of Design Wind) Seasonal Winds Increased Evacuation Decreased Productivity Wind Monitoring Reviewed Site Records Wind Consultant to Refine Loading Meteorological Consultant to Forecast Winds Refine Post-Tensioning Sequence to Strengthen Critical Members Earlier in Schedule Coring Support Pre-coring Surveys Individual Layouts With Anticipated Steel Use of GPR to Monitor Core Barrel Reviewed Each Core for Embedded Steel Analyses/Resolution of the Effects of Cut Steel Copyright - Post-Tensioning Institute 27 All rights reserved

11 Engineering for Post-Tensioning Strengthening of Preheater Tower Copyright - Post-Tensioning Institute 28 All rights reserved

12 2004 PTI Technical Session 3 S. Greenhaus - Strengthening the Holcim Preheater Tower Construction Strengthening the Holcim Preheater Tower Repair Work Items Epoxy injection Internal Post tensioning Multistrand tendons Grouted anchor bars Column enlargement Column strengthening Local zone reinforcement Mechanical relocations Beam enlargements Steel frame modifications Access and Logistics Tower completely scaffolded Interior and exterior access Hanging work platforms Service elevator and material hoists Access and Logistics Safety Issues Vertical work area Falling object protection Access and Logistics 24/7 operation 200 people Engineering communication Access and Logistics Winter Construction Core drilling operations -20 deg wind chill Heating Copyright - Post-Tensioning Institute 29 All Rights Reserved

13 2004 PTI Technical Session 3 S. Greenhaus - Strengthening the Holcim Preheater Tower Mock Ups Drilling, grouting and bearing plate installation were performed on decommissioned pier Internal Post-Tensioning Internal Post-tensioning scheme required accurate core drilling Pre-heat tower was constructed by slipform methods Reinforcement placement? Jackrod locations? Environmental concerns Winter construction Waste water Core Drilling Drilling mock up Decommissioned kiln pier Holes drilled to ensure accuracy 4.75 cores- 39 ft in length Trial drilling successful Deviation 3/8 horizontal, 5/8 vertical Production Core Drilling Predrilling process GPR survey to locates rebar Set up string line to establish entry/exit points Erect drill frame to proper orientation Establish horizontal and vertical ref. Points Review GPR survey for rebar interferences Production Core Drilling Water Feed Insulated water tank Waste water handling Water collection system Production Core Drilling (8 crews) Drill 3-5 to first rebar location, remove core Continue drilling to the next rebar, break core, remove for logging Follow sighting procedures at each core removal Continue drilling every 4,6,10 intervals inside the column, break cores and remove for logging Copyright - Post-Tensioning Institute 30 All Rights Reserved

14 2004 PTI Technical Session 3 S. Greenhaus - Strengthening the Holcim Preheater Tower Production Core Drilling Continue drilling every 4,6,&10 max. intervals inside the column Stop drilling if steel is encountered or deviation exceeds 1 in either horizontal or vertical direction. Perform radar survey to locate the core bit inside the beam at quarter points for long span beams Corrective actions Trajectory wedge/shoe Back drilling Production Core Drilling Core logging Cores reviewed for rebar Accurate logs retained Hole Preparation Bonded P-T Spec-ICRI CSP-6 required rough hole surface roughness Hole prepared with QC- Flexible high pressure water boroscope monitoring Flushing and air drying Internal Post-Tensioning 114 Internal tendons 19, 31 and 37 strand,.5 dia. 270 ksi tendons 265,000 lf strand 4 tendons per location Tendon Installation Strands precut to length Strands push through entry and exit anchor heads Wedges installed Tendon stressing Staged stressing Steel diaphragm modified to allow for frame shortening Monostrand stressing Copyright - Post-Tensioning Institute 31 All Rights Reserved

15 2004 PTI Technical Session 3 S. Greenhaus - Strengthening the Holcim Preheater Tower Tendon Stressing 2 monostrand rams/corner top & bottom 4 strands stressed per tendon Stressed to 20%, then 50% to 100% Permanent anchor cap installed Tendon Grouting Raw mill operations to start prior to grouting Thermal protection installed Jack rods grouted Low points established Low bleed prepackaged grout 2 pumps- ground level and 7th floor Tendon Grouting PTI grouting manual Mud balance Colloidal mixer Flow cone Anchor bar installation Shear reinforcement in column buildouts Full length embedment (6-8 ) Spacing Stressed and grouted Anchor Bar Installation Procedure 2 dia. core drill Roughen the surface of the hole using a high-pressure water jet to obtain CSP 6 Flush out the hole with water and then with air to obtain a clean dry hole. Anchor Bar Installation Procedure Install anchor bar & apply torque of 200 ft-lb. Install the washer and nut and apply torque of ft-lb. After installation of the anchor bars, grout holes through anchor bar. Copyright - Post-Tensioning Institute 32 All Rights Reserved

16 2004 PTI Technical Session 3 S. Greenhaus - Strengthening the Holcim Preheater Tower Concrete Enlargement Column enlargement-levels 2-5 Column build outs at anchorage zones Beam enlargement-level 3 Concrete Enlargement Completed Repairs Thank You Copyright - Post-Tensioning Institute 33 All Rights Reserved

SUNSHINE SKYWAY BRIDGE

SUNSHINE SKYWAY BRIDGE SUNSHINE SKYWAY BRIDGE Retrofit of the Post-Tensioned Precast Transition Pier Columns on the Sunshine Skyway Bridge Presented by: Antonio Ledesma, P.E. May 7, 2012 SUNSHINE SKYWAY BRIDGE, FLORIDA Presentation

More information

US-131 Over the Muskegon River. Corey Rogers, P.E. Bridge Construction Engineer

US-131 Over the Muskegon River. Corey Rogers, P.E. Bridge Construction Engineer US-131 Over the Muskegon River Corey Rogers, P.E. Bridge Construction Engineer NB and SB US-131 Each bridge is a three-span, 580 foot long, cast-in-place, post-tensioned concrete box girder structure resting

More information

NDT in Grouted PT Inspection for Bridges

NDT in Grouted PT Inspection for Bridges NDT in Grouted PT Inspection for Bridges PTI Technical Conference & Exhibition Miami, FL May 8, 2007 Hong-gang gang Cao CTLGroup (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 1 of 37

More information

Florida DOT efforts toward improving Post Tension Durability

Florida DOT efforts toward improving Post Tension Durability Florida DOT efforts toward improving Post Tension Durability By William Nickas 1 (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHTS RESERVED Page 1 of 73 Post-Tensioning Strategies Enhanced PT Systems

More information

The Hashemite University Department of Civil Engineering. Dr. Hazim Dwairi. Dr. Hazim Dwairi 1

The Hashemite University Department of Civil Engineering. Dr. Hazim Dwairi. Dr. Hazim Dwairi 1 Department of Civil Engineering Lecture 2.1 Methods of Prestressing Advantages of Prestressing Section remains uncracked under service loads Reduction of steel corrosion (increase durability) Full section

More information

Special Considerations for Maintenance of the Sunshine Skyway Bridge

Special Considerations for Maintenance of the Sunshine Skyway Bridge Florida Department of TRANSPORTATION Special Considerations for Maintenance of the Sunshine Skyway Bridge 2014 NATIONAL BRIDGE PRESERVATION PARTNERSHIP CONFERENCE James J. Jacobsen, P.E. District Structures

More information

1. Cast-in-place concrete is specified in Section

1. Cast-in-place concrete is specified in Section SECTION 03 38 00 PART 1 - GENERAL 1.01 DESCRIPTION A. This Section describes the requirements for furnishing and installing post-tensioned slabs, jacks, jacking and anchors at Parking Structure, and record

More information

Bonner Bridge Replacement Update:

Bonner Bridge Replacement Update: Bonner Bridge Replacement Update: Jerry D. Jennings, PE - NCDOT Division 1 Engineer Pablo A. Hernandez, - NCDOT Resident Engineer September 18, 2017 Bonner Bridge Replacement Timeline Refresher Bonner

More information

Modjeski and Masters, Inc. Consulting Engineers 04/18/06 St. Croix River Bridge 3D Analysis Report Introduction

Modjeski and Masters, Inc. Consulting Engineers 04/18/06 St. Croix River Bridge 3D Analysis Report Introduction Introduction This memo presents a summary of a three dimensional (3D) analysis of the Organic concept for the proposed St. Croix River bridge project. The Organic concept has several attributes that are

More information

Post-tensioned Structures Solutions for Repair and Protection

Post-tensioned Structures Solutions for Repair and Protection Post-tensioned Structures Solutions for Repair and Protection Concrete Preservation Alliance Vector Construction, Vector Corrosion Technologies, and Vector Corrosion Services are working to advance the

More information

Statement of Special Inspections

Statement of Special Inspections Statement of Special Inspections SUCF Project No: Project Title: Registered Design Professionals in Responsible Charge: (Name) (Address) Architect: Structural Engineer: Mechanical Engineer: Identification

More information

TAB.3 13 Post Tensioning Terminology (PTT)

TAB.3 13 Post Tensioning Terminology (PTT) TAB.3 13 Post Tensioning Terminology (PTT) PTI Technicical Advisory Board Page 0 of 34 The following Post-Tensioning Terminology (PTT) document contains the consensus definitions for terms relating to

More information

Critical Structures Construction Issues

Critical Structures Construction Issues Critical Structures Construction Issues FLORIDA DEPARTMENT OF TRANSPORTATION STATE CONSTRUCTION OFFICE Specification 1-3: Definitions Contractor s Engineer of Record Specialty Engineer CLASS OF CONTRACTOR

More information

Ironton Russell Bridge Project

Ironton Russell Bridge Project Construction Update March 1, 2014 Rendering by URS Responsible for Construction Inspection & Engineering Prepared by: Brian Davidson, P.E. Ironton Russell Bridge Project Project Summary: March 1, 2014

More information

SPECIAL SPECIFICATION 4584 Segmental Concrete Bridge Unit

SPECIAL SPECIFICATION 4584 Segmental Concrete Bridge Unit 2004 Specifications CSJ: 0028-09-111 SPECIAL SPECIFICATION 4584 Segmental Concrete Bridge Unit 1. Description. Construct cast-in-place segmental concrete box girder superstructure according to the plans,

More information

STRUCTURAL STEEL FRAMING

STRUCTURAL STEEL FRAMING SECTION 05 12 00 - STRUCTURAL STEEL FRAMING PART 1 - GENERAL 1.1 SUMMARY A. Section includes 1. Structural steel framing 2. Structural steel framing required for support and framing of rooftop mechanical

More information

The designer shall also submit additional information required by the University as described and underlined below.

The designer shall also submit additional information required by the University as described and underlined below. I. Structural Engineering Submissions The designer shall submit all information required by the State Construction Office (SCO) as described in the State Construction Manual Chapter 300 - Project Design

More information

John James Audubon Bridge

John James Audubon Bridge John James Audubon Bridge Cable-Stayed Main Span Over the Mississippi River Johns Hopkins University Whiting School of Engineering September 10, 2008 The Project Scheduled Time to Complete Estimated Number

More information

DESIGN AND ANALYSIS OF PRECAST CONCRETE BRIDGES IN AREAS OF HIGH OR MODERATE SEISMICITY

DESIGN AND ANALYSIS OF PRECAST CONCRETE BRIDGES IN AREAS OF HIGH OR MODERATE SEISMICITY DESIGN AND ANALYSIS OF PRECAST CONCRETE BRIDGES IN AREAS OF HIGH OR MODERATE SEISMICITY ABSTRACT Jugesh Kapur, PE, SE 1 The seismic design and detailing of bridges made of precast prefabricated members

More information

2016 ACEC/PA ANNUAL MEETING

2016 ACEC/PA ANNUAL MEETING 2016 ACEC/PA ANNUAL MEETING z I-49 North, Segment K (I-220 to Martin Luther King Drive) Interchange Project Durk Krone, P.E., TRC Engineers Inc., Baton Rouge, La 1 I-49 North Segment K Project 2 AGENDA

More information

UNDERWATER BRIDGE INSPECTION REPORT DISTRICT 6 - RICE COUNTY

UNDERWATER BRIDGE INSPECTION REPORT DISTRICT 6 - RICE COUNTY UNDERWATER BRIDGE INSPECTION REPORT STRUCTURE NO. 66532 227 th STREET (TWP 45) OVER THE STRAIGHT RIVER DISTRICT 6 - RICE COUNTY SEPTEMBER 12, 2012 PREPARED FOR THE MINNESOTA DEPARTMENT OF TRANSPORTATION

More information

SPECIAL INSPECTION AND TESTING AGREEMENT

SPECIAL INSPECTION AND TESTING AGREEMENT COUNTY OF MENDOCINO DEPARTMENT OF PLANNING AND BUILDING SERVICES 860 NORTH BUSH STREET UKIAH CALIFORNIA 95482 120 WEST FIR STREET FT. BRAGG CALIFORNIA 95437 STEVE DUNNICLIFF, DIRECTOR PHONE: 707-234-6650

More information

ACI MANUAL OF CONCRETE PRACTICE-2009

ACI MANUAL OF CONCRETE PRACTICE-2009 ACI MANUAL OF CONCRETE PRACTICE-2009 The ACI Manual of Concrete Practice is a six-part compilation of current ACI standards and committee reports. -ACI117-06 to ACI224.3R-95(08) Part 2-ACI 225-99(05) to

More information

Structural Tests and Special Inspections Form. Inspection of Fabricators (1704.2)

Structural Tests and Special Inspections Form. Inspection of Fabricators (1704.2) Inspection of Fabricators (1704.2) Furnish inspection reports (1704.2.1) - Fabricators that have not been approved Provide a Certificate of Compliance (1704.2.2) - Approved Fabricators Steel Construction

More information

Construction Measurement III SBQ3314. Precast Pre stressed Concrete Works. Dr. Sarajul Fikri Mohamed

Construction Measurement III SBQ3314. Precast Pre stressed Concrete Works. Dr. Sarajul Fikri Mohamed Construction Measurement III SBQ3314 Precast Pre stressed Concrete Works Dr. Sarajul Fikri Mohamed Table of Contents 1. Pre stressed concrete in bridgeworks: technological aspects 2. SMM2 measurement rules

More information

Project Address: Name of Person Completing Form:

Project Address: Name of Person Completing Form: Statement of Inspections This form is provided as a way to list aspects of the project that require special inspection and testing in accordance with IBC Sections 107.1, 1704, and 1705 and define duties

More information

Design and Construction of the SH58 Ramp A Flyover Bridge over IH70. Gregg A. Reese, PE, CE, Summit Engineering Group, Inc.

Design and Construction of the SH58 Ramp A Flyover Bridge over IH70. Gregg A. Reese, PE, CE, Summit Engineering Group, Inc. Design and Construction of the SH58 Ramp A Flyover Bridge over IH70 Gregg A. Reese, PE, CE, Summit Engineering Group, Inc., Littleton, CO ABSTRACT: The SH58 Ramp A bridge in Golden, CO is the latest on

More information

Intermountain Section AWWA Conference - 2.0MG Layton Water Tank. Jake O Brien

Intermountain Section AWWA Conference - 2.0MG Layton Water Tank. Jake O Brien Intermountain Section AWWA Conference - 2.0MG Layton Water Tank Jake O Brien Presentation Outline Layton City s decision process Tank Design/Construction Tendon Tanks - don t shed the good stuff Layton

More information

PRECAST CONCRETE GIRDER ERECTION

PRECAST CONCRETE GIRDER ERECTION 7.1 Precast Concrete Girder Erection - General Erection of precast concrete girders includes transporting the girders to the site, handling and temporary storage, installing anchor bolts, shear blocks

More information

EXECUTIVE SUMMARY POST-TENSIONING TENDON PROTECTION STRATEGIES FOR PRECAST ELEMENTS

EXECUTIVE SUMMARY POST-TENSIONING TENDON PROTECTION STRATEGIES FOR PRECAST ELEMENTS EXECUTIVE SUMMARY POST-TENSIONING TENDON PROTECTION STRATEGIES FOR PRECAST ELEMENTS Larry B. Krauser, General Technologies, Inc., Stafford, TX Post-tensioning tendon protection strategies for precast elements

More information

SPECIAL INSPECTION AND OBSERVATION PROGRAM CITY OF CONCORD BUILDING DIVISION. Project Address:

SPECIAL INSPECTION AND OBSERVATION PROGRAM CITY OF CONCORD BUILDING DIVISION. Project Address: SPECIAL INSPECTION AND OBSERVATION PROGRAM CITY OF CONCORD BUILDING DIVISION Permit Application #: Project Address: Purpose: To meet the requirements of CBC Section 1704.3 this form may be used as a statement

More information

ADDENDA #9- RFP Sylvania CC building Re-Roof Progressive Design Build for Sylvania Campus CC Building Re-Roof Services

ADDENDA #9- RFP Sylvania CC building Re-Roof Progressive Design Build for Sylvania Campus CC Building Re-Roof Services ADDENDA #9- RFP Sylvania CC building Re-Roof Progressive Design Build for Sylvania Campus CC Building Re-Roof Services Addenda Dated: 01/25/2019 PURPOSE: The purpose of this Addenda #9 is to provide a

More information

Mechanical Engineer of Record: (Smoke Control Systems Only) Name & License Company. Others: Responsible Party Name & License Company

Mechanical Engineer of Record: (Smoke Control Systems Only) Name & License Company. Others: Responsible Party Name & License Company PRINCE WILLIAM COUNTY Department Development Services Building Development Division STATEMENT OF SPECIAL INSPECTIONS (Building/Other Structures other than Retaining Walls) Version 2015-12-31 Building Permit

More information

EVALUATION & REPAIR OF CORROSION DAMAGED ROOF LIFT SLAB WITH WIRE POST-TENSIONING SYSTEM (BUTTON HEADS)

EVALUATION & REPAIR OF CORROSION DAMAGED ROOF LIFT SLAB WITH WIRE POST-TENSIONING SYSTEM (BUTTON HEADS) EVALUATION & REPAIR OF CORROSION DAMAGED ROOF LIFT SLAB WITH WIRE POST-TENSIONING SYSTEM (BUTTON HEADS) (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHT RESERVED 1 of 23 The following presentation discusses

More information

Barrier Cable Systems, Inc.

Barrier Cable Systems, Inc. 055220 BARRIER CABLE SYSTEMS PART 1- GENERAL 1.1 DESIGN The 2012 IBC compliant barrier systems must meet both following requirements: A. For automobile restraint: the systems shall be able to withstand

More information

SUMMARY SHEETS OF HYBRID CONNECTIONS

SUMMARY SHEETS OF HYBRID CONNECTIONS APPENDIX E SUMMARY SHEETS OF HYBRID CONNECTIONS NCHRP 12-88 Connection Evaluations Appendix E E-1 APPENDIX E SUMMARY SHEETS OF HYBRID CONNECTIONS NCHRP 12-88 Connection Evaluations Appendix E E-2 Location:

More information

SPECIAL INSPECTION AND OBSERVATION PROGRAM City of Walnut Creek Building Division. Project Address:

SPECIAL INSPECTION AND OBSERVATION PROGRAM City of Walnut Creek Building Division. Project Address: SPECIAL INSPECTION AND OBSERVATION PROGRAM City of Walnut Creek Building Division Permit Application #: Project Address: Purpose: To meet the requirements of City of Walnut Creek Municipal Code Section

More information

CONCRETE TECHNOLOGY CORPORATION

CONCRETE TECHNOLOGY CORPORATION PRECAST, PRESTRESSED HOLLOW CORE SLABS DESIGN CRITERIA & SPAN-LOAD CHARTS Introduction 2 Design Criteria for Development of the Span-Load Charts 2 Related Publications 3 Manufacturing Tolerances 4 8" Bare

More information

SPECIAL INSPECTION AGREEMENT

SPECIAL INSPECTION AGREEMENT PART 1 STATEMENT OF SPECIAL INSPECTIONS When special inspection is required to be performed in accordance with International Building Code Chapter 17, a building permit cannot be issued until a statement

More information

Ironton Russell Bridge Project

Ironton Russell Bridge Project Construction Update October 1, 2014 Rendering by URS Responsible for Construction Inspection & Engineering Prepared by: Brian Davidson, P.E. Ironton Russell Bridge Project Project Summary: October 1, 2014

More information

POST-TENSIONING VS. PRESTRESSING

POST-TENSIONING VS. PRESTRESSING POST-TENSIONING VS. PRESTRESSING Miroslav F. VEJVODA, MBA, P.E. Managing Director Engineering & Professional Development PURPOSE STATEMENT This seminar is intended to develop an understanding for the differences

More information

SUMMARY SHEETS OF GROUTED DUCT CONNECTIONS

SUMMARY SHEETS OF GROUTED DUCT CONNECTIONS APPENDIX B SUMMARY SHEETS OF GROUTED DUCT CONNECTIONS NCHRP 12-88 Connection Evaluations Appendix B B-1 APPENDIX B SUMMARY SHEETS OF GROUTED DUCT CONNECTIONS NCHRP 12-88 Connection Evaluations Appendix

More information

SEISMIC DESIGN AND RETROFIT OF BRIDGES ON MISSOURI S EARTHQUAKE PRIORITY ROUTES

SEISMIC DESIGN AND RETROFIT OF BRIDGES ON MISSOURI S EARTHQUAKE PRIORITY ROUTES SEISMIC DESIGN AND RETROFIT OF BRIDGES ON MISSOURI S EARTHQUAKE PRIORITY ROUTES Shyam Gupta, 1 P.E., Bryan A. Hartnagel, 2 Ph.D., P.E. Abstract The heart of the New Madrid Seismic Zone lies in the southeast

More information

Building Department Informational Handout

Building Department Informational Handout City of Sonoma Building Department Informational Handout Statement of Special Inspections Handout No: 7 Revised 1/12/2017 Project Name: Project Address: For building permit applications of projects requiring

More information

STATEMENT OF SPECIAL INSPECTION FORM

STATEMENT OF SPECIAL INSPECTION FORM Project Title: Permit #: Project Address: STATEMENT OF SPECIAL INSPECTION FORM This Statement of Special Inspections is submitted in fulfillment of the requirements of CBC Sections 1704 and 1705. Special

More information

STANDARDIZED STRUCTURES

STANDARDIZED STRUCTURES Q, QH & QL TOWERS 16.1 Q, QH, and QL Towers General Description The series includes three and four leg angle towers, which are suited for a variety of antenna mounting positions and load conditions. The

More information

Chapter 2 Notation and Terminology

Chapter 2 Notation and Terminology Reorganized 318 Chapter Titles Chapter 1 General 1.1 Scope 1.2 Purpose 1.3 Interpretation 1.4 Drawings and Specifications 1.5 Testing and Inspection 1.6 Administatration and Enforcement 1.6.1 Retention

More information

Statement of Special Inspections Michigan Building Code 2012 (MBC 2012)

Statement of Special Inspections Michigan Building Code 2012 (MBC 2012) Gaines Charter Township 8555 Kalamazoo Ave SE Caledonia MI 49316 PH: 616 698-6640 Fax: 616 698-2490 www.gainestownship.org Building Department Statement of Special Inspections Michigan Building Code 2012

More information

B BASF MasterFlow MasterFlow MasterFlow MasterFlow C CGM Grout...8

B BASF MasterFlow MasterFlow MasterFlow MasterFlow C CGM Grout...8 B BASF MasterFlow 100...2 MasterFlow 648...5 MasterFlow 885...4 MasterFlow 928...3 C CGM...8 F FIVE STAR GROUT...7 G GROUT Five Star Non Shrink...7 General Purpose...6 Masterflow 100...2 Masterflow 648...5

More information

PLANNING DEPARTMENT 701 OCEAN STREET, 4 TH FLOOR, SANTA CRUZ, CA (831) FAX: (831)

PLANNING DEPARTMENT 701 OCEAN STREET, 4 TH FLOOR, SANTA CRUZ, CA (831) FAX: (831) County of Santa Cruz PLANNING DEPARTMENT 701 OCEAN STREET, 4 TH FLOOR, SANTA CRUZ, CA 95060 (831) 4542580 FA: (831) 4542131 STATEMENT OF SPECIAL INSPECTIONS California Building Code 1704.3 Prior to issuance,

More information

1. Base plates, setting plates and anchor rods for columns. 8. Lintels if connected to structural steel columns.

1. Base plates, setting plates and anchor rods for columns. 8. Lintels if connected to structural steel columns. PAGE 051200-1 SECTION 051200 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification sections,

More information

TECHNICAL SPECIAL PROVISION FOR CONCRETE REPAIRS. Financial Project ID , &

TECHNICAL SPECIAL PROVISION FOR CONCRETE REPAIRS. Financial Project ID , & TECHNICAL SPECIAL PROVISION FOR CONCRETE REPAIRS Financial Project ID 429140-1-52-01, 429140-2-52-01 & 428267-1-52-01 The official record of this Technical Special Provision is the electronic file signed

More information

John James Audubon Bridge. Introduction

John James Audubon Bridge. Introduction John James Audubon Bridge Introduction The Project Why build the bridge? The bridge--proposed to be the longest cable-stayed bridge in America--will replace an existing ferry between the communities of

More information

Ironton Russell Bridge Project

Ironton Russell Bridge Project Construction Update October 1, 2015 Rendering by URS Responsible for Construction Inspection & Engineering Prepared by: Brian Davidson, P.E. Ironton Russell Bridge Project Project Summary: October 1, 2015

More information

Ironton Russell Bridge Project

Ironton Russell Bridge Project Construction Update January 1, 2016 Rendering by URS Responsible for Construction Inspection & Engineering Prepared by: Brian Davidson, P.E. Project Overview The Ironton Russell Bridge Project entails

More information

Pushing the Envelope For 100 Years

Pushing the Envelope For 100 Years Pushing the Envelope For 100 Years Tunneling under the Chesapeake Bay The Parallel Thimble Shoal Highway Tunnel Presented by: Kevin Abt, PE Chesepeake Bay Bridge and Tunnel District Mike Kling, PE, PTOE

More information

Deep Water Drilled Shafts for the Herrington Lake Bridge Replacement Project

Deep Water Drilled Shafts for the Herrington Lake Bridge Replacement Project Deep Water Drilled Shafts for the Herrington Lake Bridge Replacement Project Darrin Beckett, P.E. Kentucky Transportation Cabinet 49 th Southeastern Transportation Geotechnical Engineering Conference October

More information

SPECIAL SPECIFICATION 4401 Prestressed Ground Anchors

SPECIAL SPECIFICATION 4401 Prestressed Ground Anchors 2004 Specifications CSJ 0581-02-121 & 0200-11-100 SPECI SPECIFICATION 4401 Prestressed Ground Anchors 1. Description. Install post-tensioned permanent ground anchors in place, with grouting as required

More information

Foundation Strengthening Of Bascule Piers At The Bridge Of Lions

Foundation Strengthening Of Bascule Piers At The Bridge Of Lions Paper No. 22 Foundation Strengthening Of Bascule Piers At The Bridge Of Lions Structural Elements Jian Huang, Ph.D., P.E. G. Alan Klevens, P.E. Lichtenstein Consulting Engineers TENTH BIENNIAL SYMPOSIUM

More information

GUIDELINES FOR EXECUTION OF ADAPT-PT 1

GUIDELINES FOR EXECUTION OF ADAPT-PT 1 Structural Concrete Software System GUIDELINES FOR EXECUTION OF ADAPT-PT 1 Update: December 09, 2004 TN172 guide_to_run_pt_12 120904 The guidelines presented will assist you in the selection of design

More information

INSPECTION AND LOAD RATING OF P-T SEGMENTAL BRIDGES. Elias Ajami, PE Illinois Tollway Brett Sauter, PE, SE Ciorba Group

INSPECTION AND LOAD RATING OF P-T SEGMENTAL BRIDGES. Elias Ajami, PE Illinois Tollway Brett Sauter, PE, SE Ciorba Group INSPECTION AND LOAD RATING OF P-T SEGMENTAL BRIDGES Elias Ajami, PE Illinois Tollway Brett Sauter, PE, SE Ciorba Group PRESENTATION SUMMARY 1. About the Illinois Tollway 2. Project Location and Information

More information

KEYWORDS: Barge Stability, Steel Truss Erection, Horizontal Sliding of Steel Trusses

KEYWORDS: Barge Stability, Steel Truss Erection, Horizontal Sliding of Steel Trusses Replacement of the BNSF Approach Spans over the Mississippi River DAVID ROGOWSKI, P.E. AND JOSH CRAIN, Genesis Structures Inc., Kansas City, Missouri and DAN SIEVE AND KEVIN BECKER, Walsh Construction

More information

MIDAS Training Series

MIDAS Training Series MIDAS midas Civil Title: All-In-One Super and Sub Structure Design NAME Edgar De Los Santos / MIDAS IT United States 2016 Substructure Session 1: 3D substructure analysis and design midas Civil Session

More information

Marina Bay Sands Hotel Arch 631 Kayla Brittany Maria Michelle

Marina Bay Sands Hotel Arch 631 Kayla Brittany Maria Michelle Marina Bay Sands Hotel Arch 631 Kayla Brittany Maria Michelle Overall Information Location: Singapore Date of Completion: 2010 Cost: $5.7 billion Architect: Moshe Safdie Executive Architect: Aedas, Pte

More information

Evaluation and Repair of Existing Post- Tensioned Buildings with Paper Wrapped Tendons Experiencing Corrosion Damage

Evaluation and Repair of Existing Post- Tensioned Buildings with Paper Wrapped Tendons Experiencing Corrosion Damage Evaluation and Repair of Existing Post- Tensioned Buildings with Paper Wrapped Tendons Experiencing Corrosion Damage K. Dirk Bondy, S.E. President Seneca Structural Engineering, Inc. The Great American

More information

Accelerated Bridge Construction in USA

Accelerated Bridge Construction in USA Accelerated Bridge Construction in USA Abstract Rush hour traffic is a common daily occurrence in the USA. Highway and bridge construction further aggravates the situation. The Federal Highway Administration

More information

Stay-Cable Replacement Design

Stay-Cable Replacement Design Stay-Cable Replacement Design Mississippi River Bridge Luling, Louisiana Christopher Ligozio CTLGroup Copyright Post-Tensioning Institute all rights reserved. Page 1 of 35 Luling Bridge Copyright Post-Tensioning

More information

Retrofit Measures for Superstructures, Bearings, and Seats

Retrofit Measures for Superstructures, Bearings, and Seats Retrofit Measures for Superstructures, Bearings, and Seats Presented by Richard V Nutt Elements to be Retrofitted Bridge Decks and Girders Bearings, Anchorages and Pedestals Expansion Joints 1 Elements

More information

SUMMARY SHEETS OF INTEGRAL CONNECTIONS

SUMMARY SHEETS OF INTEGRAL CONNECTIONS APPENDIX F SUMMARY SHEETS OF INTEGRAL CONNECTIONS NCHRP 12-88 Connection Evaluations Appendix F F-1 APPENDIX F SUMMARY SHEETS OF INTEGRAL CONNECTIONS NCHRP 12-88 Connection Evaluations Appendix F F-2

More information

STANDARD SPECIFICATION FOR MICROPILE CONSTRUCTION

STANDARD SPECIFICATION FOR MICROPILE CONSTRUCTION Section 67.0 Knoxville, Tennessee March 2013 1. Description STANDARD SPECIFICATION FOR MICROPILE CONSTRUCTION a) This work shall consist of constructing micropiles as shown on the Contract plans in accordance

More information

Statement of Special Inspection Requirements

Statement of Special Inspection Requirements Statement of Special Inspection Requirements California Building Code Chapter 17 Construction plans shall include a statement of special inspection in accordance with CBC chapter 17. The statement of special

More information

Major Building and Special Structures

Major Building and Special Structures TECHNICAL SESSION 1 Major Building and Special Structures Moderator Russell B. Price, P.E. Suncoast Post-Tension L.P. Houston, Texas 2004 PTI Technical Conference Session 1 Dennis Wittry -- Denver's Invesco

More information

Ironton Russell Bridge Project

Ironton Russell Bridge Project Construction Update September 1, 2014 Rendering by URS Responsible for Construction Inspection & Engineering Prepared by: Brian Davidson, P.E. Ironton Russell Bridge Project Project Summary: September

More information

SECTION STRUCTURAL STEEL

SECTION STRUCTURAL STEEL SECTION 05120 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

Erie on the Park. Timothy Moore Penn State University Architectural Engineering Structural Emphasis Advisor: Prof. Ali Memari

Erie on the Park. Timothy Moore Penn State University Architectural Engineering Structural Emphasis Advisor: Prof. Ali Memari Timothy Moore Penn State University Architectural Engineering Structural Emphasis Advisor: Prof. Ali Memari Thesis Presentation - Spring 2006 Contents Introduction Building Professionals Existing Structure

More information

Final Estimates Level 2

Final Estimates Level 2 Florida Department of TRANSPORTATION Final Estimates Level 2 Module 6: Structures 11/1/2017 FDOT Final Estimates Level 2 Release 11, Module 6 1 6-1 Module Content Concrete Structures Bridges Substructure

More information

SECTION 1 INTRODUCTION TO POST-TENSIONED CONCRETE DEVELOPED BY THE PTI EDC-130 EDUCATION COMMITTEE

SECTION 1 INTRODUCTION TO POST-TENSIONED CONCRETE DEVELOPED BY THE PTI EDC-130 EDUCATION COMMITTEE SECTION 1 INTRODUCTION TO POST-TENSIONED CONCRETE DEVELOPED BY THE PTI EDC-130 EDUCATION COMMITTEE NOTE: MOMENT DIAGRAM CONVENTION In PT design, it is preferable to draw moment diagrams to the tensile

More information

CTP STITCH-TIE AGAIN! Quick and easy way to re-anchor existing veneers to back-up structures.

CTP STITCH-TIE AGAIN! Quick and easy way to re-anchor existing veneers to back-up structures. Helical Wall Tie System for Stabilizing Veneers and Structural Repair AGAIN! ANOTHER CTP SOLUTION! CTP STITCH-TIE Quick and easy way to re-anchor existing veneers to back-up structures. Brick to Concrete

More information

CSU GUIDELINES. April 27, 2018 FOR POST-TENSIONED CONCRETE STRUCTURES.

CSU GUIDELINES. April 27, 2018 FOR POST-TENSIONED CONCRETE STRUCTURES. CSU GUIDELINES FOR POST-TENSIONED CONCRETE STRUCTURES April 27, 2018 http://www.calstate.edu/cpdc/ae California State University Seismic Review Board Technical Guidelines January 9, 2018 The CSU Seismic

More information

LRFD Bridge Design Manual Changes

LRFD Bridge Design Manual Changes LRFD Bridge Design Manual Changes Dave Dahlberg Bridge Design Manual & Policy Engineer May 17, 2017 Bridge Office mndot.gov/bridge Overview 1) Concrete mix designations 2) Reinforcing bar development and

More information

SECTION TILT-UP PRECAST CONCRETE SANDWICH PANELS. A. Work includes, but is not limited to, the following:

SECTION TILT-UP PRECAST CONCRETE SANDWICH PANELS. A. Work includes, but is not limited to, the following: PART 1 GENERAL 1.01 SUMMARY SECTION 03460 TILT-UP PRECAST CONCRETE SANDWICH PANELS A. Work includes, but is not limited to, the following: 1. Architectural precast concrete sandwich wall panels. 2. Integral

More information

TILT-UP PRECAST CONCRETE SANDWICH PANELS. A. Work includes, but is not limited to, the following:

TILT-UP PRECAST CONCRETE SANDWICH PANELS. A. Work includes, but is not limited to, the following: PART 1 GENERAL 1.01 SUMMARY SECTION 03460 TILT-UP PRECAST CONCRETE SANDWICH PANELS A. Work includes, but is not limited to, the following: 1. Architectural precast concrete sandwich wall panels. 2. Integral

More information

Topic Outline. Two Stage Analysis Procedure: Podium Design. Part 2: Rigid Lower Portion Philip Miller, S.E. 2/8/2018

Topic Outline. Two Stage Analysis Procedure: Podium Design. Part 2: Rigid Lower Portion Philip Miller, S.E. 2/8/2018 Two Stage Analysis Procedure: Podium Design Part 2: Rigid Lower Portion Philip Miller, S.E. Topic Outline Types of Podium Construction Example Buildings PT Basics PT Analysis Modeling Tips Load Balancing

More information

Tilikum Crossing Transit Bridge. Portland, OR

Tilikum Crossing Transit Bridge. Portland, OR Tilikum Crossing Transit Bridge Portland, OR Technical Information Size of Project: The Tilikum Crossing Transit Bridge is 1,720 ft. long and required 24,000 cy total concrete Strength Requirements: The

More information

Ironton Russell Bridge Project

Ironton Russell Bridge Project Construction Update January 1, 2015 Rendering by URS Responsible for Construction Inspection & Engineering Prepared by: Brian Davidson, P.E. Project Overview The Ironton Russell Bridge Project entails

More information

***************************************************************************************************************

*************************************************************************************************************** 03365 POST-TENSIONED CONCRETE *************************************************************************************************************** SPECIFIER: CSI MasterFormat 2004 number 03 38 00. ***************************************************************************************************************

More information

2. Outline of the bridge 3-span continuous deck extradosed bridge Bridge length

2. Outline of the bridge 3-span continuous deck extradosed bridge Bridge length Construction of Extradosed Bridge in the Government Financed Section EUI-NAM PARK, PM, Incheon Bridge Section 5, Doosan Construction & Engineering corporation KYUNG-KUK JUNG, GM, Incheon Bridge Section

More information

2012 VIRGINIA TECH SCHEDULE OF SPECIAL INSPECTIONS

2012 VIRGINIA TECH SCHEDULE OF SPECIAL INSPECTIONS 2012 VIRGINIA TECH SCHEDULE OF SPECIAL INSPECTIONS HECO-6 GENERAL Pre-construction conference Preconstruction meeting Scheduled by SI with the Contractor, UBO, A/E, and relevant subs prior to commencement

More information

SECTION VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT

SECTION VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT SECTION 230548 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Elastomeric Isolation pads. 2. Elastomeric Isolation mounts. 3. [Freestanding] [Restrained] [Freestanding and restrained]

More information

Structural System Design

Structural System Design Structural System Design STRUCTURAL SYSTEM DESIGN DESIGN CRITERIA The primary goals and criteria governing the alternate concrete superstructure design are as follows: -maintain an open office layout,

More information

CONSTRUCTION PROCEDURES. AWWA D110 Type I Prestressed Concrete Tanks

CONSTRUCTION PROCEDURES. AWWA D110 Type I Prestressed Concrete Tanks CONSTRUCTION PROCEDURES AWWA D110 Type I Prestressed Concrete Tanks 2-3 4-5 6-7 8-9 10-11 12-13 14-15 16-17 Site Preparation Floor & Footings Wall Construction Roof Options Vertical Prestressing Abrasive

More information

Mezzanines By Design Page 1

Mezzanines By Design Page 1 SECTION 05120 STRUCTURAL STEEL PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General Conditions and Division 1 apply to this Section. 1.2 SUMMARY

More information

Contents. 1.1 Introduction 1

Contents. 1.1 Introduction 1 Contents PREFACE 1 ANCIENT MASONRY 1 1.1 Introduction 1 1.2 History of Masonry Materials 1 1.2.1 Stone 2 1.2.2 Clay Units 2 1.2.3 Calcium Silicate Units 4 1.2.4 Concrete Masonry Units 4 1.2.5 Mortars 5

More information

Lesson 7 REINFORCING CAGE. Version 1-1/

Lesson 7 REINFORCING CAGE. Version 1-1/ Lesson 7 REINFORCING CAGE 7-1 Version 1-1/15 7-1 Learning Outcomes Describe cage construction Determine the circumference of a shaft and rebar cage and calculate the required number of side spacers. Explain

More information

Northeast Bridge Preservation Partnership Meeting

Northeast Bridge Preservation Partnership Meeting Northeast Bridge Preservation Partnership Meeting Superstructure Preservation Strategies Aetna Viaduct Superstructure Repairs Route I-84 City of Hartford, CT State Project No. 63-648 David A. Cutler, P.E.

More information

I-74 over the Mississippi River

I-74 over the Mississippi River I-74 over the Mississippi River Design and Construction of Arch Foundations 104 th Transportation and Highway Engineering Conference Presented by: Andrew J. Keaschall, PE, SE, Alfred Benesch & Company

More information

w w w. d u t c h l a n d i n c. c o m

w w w. d u t c h l a n d i n c. c o m RECTANGULAR TANKS TYPICAL INSTALLATION Precast concrete elements are manufactured at a Precast/ Prestressed Concrete Institute (PCI) certified facility. Precast concrete elements are set on a poured-in-place

More information

Florida s Flexible Filler Experience. Dr. Natassia Brenkus, The Ohio State University

Florida s Flexible Filler Experience. Dr. Natassia Brenkus, The Ohio State University Florida s Flexible Filler Experience Dr. Natassia Brenkus, The Ohio State University Motivation Cost-effective method of bridge construction Prestressed Concrete Durability Issues Poor grouting practice

More information

Don Theobald, V.P., Gulf Coast Pre-Stress. Standardizing Existing Spliced Girder Systems

Don Theobald, V.P., Gulf Coast Pre-Stress. Standardizing Existing Spliced Girder Systems Standardizing Existing Spliced Girder Systems Hugh D. Ronald, P.E. Abstract: Correlation of the span and girder spacing requirements for an existing spliced girder system can be completed using a parametric

More information